Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:50

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610

Simulation Timestamp: 2023-10-16 08:50:54


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 13275.18 1170.11 1170.11
Net Site Energy 13275.18 1170.11 1170.11
Total Source Energy 23227.47 2047.32 2047.32
Net Source Energy 23227.47 2047.32 2047.32


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 3615.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 321.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 545.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 192.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1648.46 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 640.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 560.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 57.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 140.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.74 3628.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 43.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 4242.52 9032.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 3615.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 321.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 545.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 192.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 872.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 8.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 4.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 21.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 560.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 57.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 140.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.74 3628.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 15.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 20.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 3615.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 321.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 545.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 192.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1648.46 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 640.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 560.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 57.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 140.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.74 3628.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 43.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 90.91 638.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 218.04 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 373.95 796.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 90.91 638.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 218.04 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 373.95 796.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 4242.520 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 4242.520 100.00
     
Total On-Site and Utility Electric Sources 4242.520 100.00
Total Electricity End Uses 4242.520 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 0.91 0.03
Air to Air Heat Recovery for Heating 3377.71 99.97
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 3378.62 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 213.50
Time Setpoint Not Met During Occupied Cooling 37.17
Time Not Comfortable Based on Simple ASHRAE 55-2004 7936.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:50
RunPeriod RUNPERIOD 1
Weather File Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Latitude [deg] 64.82
Longitude [deg] -147.8
Elevation [m] 133.00
Time Zone -9.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 6.7179 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 9.6995 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 9.6995 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 4.6285 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 4.2862 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.7049 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 9.2569 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 9.0417 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 4.4132 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 4.4132 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 4.4132 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 4.4132 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 9.2569 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 9.2569 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 11.7327 4.65 2931.5031
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 4.4132 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.8577 7.07 41.0437
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.8577 7.07 41.0437
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 6.7179 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 9.6995 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 9.6995 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 4.6285 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 4.2862 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.7049 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 9.2569 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 9.0417 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 4.4132 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 4.4132 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 4.4132 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 4.4132 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 4.4132 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 4.4132 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 4.4132 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 4.4132 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 4.4132 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 4.4132 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 9.2569 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 9.2569 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 11.7327 4.65 2931.5031  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 4.4132 18.58 0.0000  
Total 11345.29             5.8577 3.54 41.0437  
Conditioned Total 11345.29             5.8577 3.54 41.0437  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 3.7137 8.82 37.1717
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 29-JUN-19:10 12-JAN-21:49 - - - - - - - - - - 09-MAY-20:10
Heating 0.00 753329.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 97264.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 41208.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 86131.51 75123.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 31523.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 27000.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 4539.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 8265.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 3827.07 308165.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1682.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 301443.71 1136619.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 753329.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 97264.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 41208.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 56456.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 37488.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 37635.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1219.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 27000.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 4539.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 8265.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3827.07 308165.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 771.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 670.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 3919.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1019.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1726.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 609.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5220.66 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2028.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1775.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 183.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 446.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.38 3932.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 138.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 13436.06 9791.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 345.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 89.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 152.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 53.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 460.16 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 178.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 156.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 16.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 39.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 346.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1184.29 863.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 345.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 89.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 152.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 53.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 460.16 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 178.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 156.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 16.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 39.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 346.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1184.29 863.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.19 0.687865 0.585000 1.28 1.00 0.500000 0.000554 0.000080 1.28 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.502143 0.101781 0.237000 0.119008 0.300000 0.500000 0.003743 0.000046 0.186280 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.226656 0.261116 0.607000 0.137580 0.696310 0.500000 0.001459 0.000018 0.137580 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.177999 0.703111 0.010000 0.001780 1.00 0.500000 0.000542 0.000027 0.108496 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.097024 0.744211 0.893000 0.086643 1.00 0.500000 0.000512 0.000019 0.086643 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.32 0.017936 0.010000 0.033154 0.300000 0.500000 0.021242 0.000036 0.145178 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.95 0.073763 0.520000 1.01 0.520000 0.500000 0.005165 0.000141 1.01 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 5.28 0.188873 0.538000 2.84 0.538000 0.500000 0.002017 0.000344 2.84 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.43 0.832147 0.499000 0.711732 1.00 0.500000 0.000458 0.000154 0.711732 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.11 0.119877 0.845000 1.78 0.845000 0.500000 0.003178 0.000166 1.78 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.21 0.114242 0.805000 1.78 0.805000 0.500000 0.003335 0.000167 1.78 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.27 0.062288 0.242000 0.550083 0.300000 0.500000 0.011002 0.000068 0.550083 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.765123 0.410442 0.246000 0.188220 1.00 0.500000 0.000928 0.000109 0.444154 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 9126.48 0.000080 194.04
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 5245.74 0.000046 143.16
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 2069.27 0.000018 47.90
MECH_FLR_1 VAV BOX REHEAT COIL 3055.03 0.000027 83.37
STORAGE_FLR_1 VAV BOX REHEAT COIL 2215.30 0.000019 58.36
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 4087.90 0.000036 111.56
CAFE_FLR_1 VAV BOX REHEAT COIL 16095.40 0.000141 376.13
LOBBY_FLR_1 VAV BOX REHEAT COIL 39328.83 0.000344 898.36
ROOM_1_FLR_3 FAN COIL HEATING COIL 9434.70 0.000083 269.61
ROOM_2_FLR_3 FAN COIL HEATING COIL 9427.28 0.000082 269.40
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 53045.55 0.000464 1515.87
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 52941.23 0.000463 1512.89
ROOM_5_FLR_3 FAN COIL HEATING COIL 9421.16 0.000082 269.23
ROOM_6_FLR_3 FAN COIL HEATING COIL 9413.73 0.000082 269.02
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 17602.31 0.000154 458.58
ROOM_1_FLR_6 FAN COIL HEATING COIL 2902.68 0.000025 82.95
ROOM_2_FLR_6 FAN COIL HEATING COIL 2900.22 0.000025 82.87
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 13914.30 0.000122 397.60
BANQUET_FLR_6 VAV BOX REHEAT COIL 18919.19 0.000166 417.19
DINING_FLR_6 VAV BOX REHEAT COIL 19083.83 0.000167 421.25
KITCHEN_FLR_6 VAV BOX REHEAT COIL 7752.66 0.000068 177.57
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 12508.55 0.000109 341.38
VAV WITH REHEAT HEATING COIL 469047.49 0.004103 6161.67
FLR_3_DOAS HEATING COIL 42957.20 0.000376 564.31
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.17 0.000083 0.000364
ROOM_2_FLR_3 FAN COIL 1.05 0.000082 0.000328
ROOM_3_MULT19_FLR_3 FAN COIL 8.74 0.000464 0.002691
ROOM_4_MULT19_FLR_3 FAN COIL 5.46 0.000463 0.001787
ROOM_5_FLR_3 FAN COIL 1.10 0.000082 0.000344
ROOM_6_FLR_3 FAN COIL 0.999244 0.000082 0.000311
ROOM_1_FLR_6 FAN COIL 0.305501 0.000025 0.000095
ROOM_2_FLR_6 FAN COIL 0.271862 0.000025 0.000085
ROOM_3_MULT9_FLR_6 FAN COIL 1.84 0.000122 0.000576
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 1.17
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 1.05
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 8.74
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.46
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 1.10
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 0.999244
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.305501
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.271862
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.84
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008535 12.80 0.008500 0.000364 1.17  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008539 12.80 0.008500 0.000328 1.05  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008480 12.80 0.008480 0.002691 8.74  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008724 12.80 0.008500 0.001787 5.46  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008537 12.80 0.008500 0.000344 1.10  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008541 12.80 0.008500 0.000311 0.999244  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008534 12.80 0.008500 0.000095 0.305501  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008538 12.80 0.008500 0.000085 0.271862  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008571 12.80 0.008500 0.000576 1.84  
VAV WITH REHEAT COOLING COIL 25.41 6.70 0.008526 10.95 0.008500 0.011259 22.40 393686.75
FLR_3_DOAS COOLING COIL 27.40 6.70 0.007007 11.91 0.007007 0.001096 2.05 38332.30
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 13.15 10.53 22.53 10.53 22.40 22.40 0.300000 0.469983 22.40
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 22.40  
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 9.33
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 22.40
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.011259 0.000042
VAV WITH REHEAT_HEATC_CONTROLLER 0.004103  
FLR_3_DOAS_COOLC_CONTROLLER 0.001096 0.000434
FLR_3_DOAS_HEATC_CONTROLLER 0.000376  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.018935 3060.92  
HEATSYS1 PUMP 0.007283 2171.62 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.007283 0.873965
COOLSYS1 0.018935 2.27
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 832496.05 832496.05 0.007283
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.018935 2119.18
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.018935 662071.15 662692.73 75.55
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 -3.10 -17.70 -19.30 -17.60 -15.40 -10.30 0.70 10.60 16.00 16.90 14.20 6.70


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 64.82 -147.85 -9.00 133.00 99737 1.1854


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA -1.53 36.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 6.718 5.380 0.000 0.000 0.000 0.000 12.098 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 9.699 10.760 0.000 0.000 0.000 0.000 20.459 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 9.699 10.760 0.000 0.000 0.000 0.000 20.459 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 4.628 5.380 0.000 0.000 0.000 0.000 10.008 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 4.286 2.690 0.000 0.000 0.000 0.000 6.976 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.705 61.680 535.850 0.000 0.000 0.000 603.235 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 9.257 5.380 0.000 0.000 0.000 0.000 14.637 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 9.042 8.070 0.000 0.000 0.000 0.000 17.112 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 4.413 0.000 0.000 0.000 0.000 0.000 4.413 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 9.257 67.820 0.000 0.000 0.000 0.000 77.077 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 9.257 67.820 0.000 0.000 0.000 0.000 77.077 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 11.733 512.243 2419.260 0.000 0.000 0.000 2943.236 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 4.413 0.000 0.000 0.000 0.000 0.000 4.413 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 13293.583 6.718 124.824 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 13293.583
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 650.557 9.699 60.075 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 650.557
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 753.347 9.699 60.076 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 753.347
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 760.196 4.628 286.650 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 760.196
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 406.155 4.286 199.096 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 406.155
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 445.205 5.705 53.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 445.205
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1748.285 9.257 12.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1748.285
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 11828.200 9.042 28.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 11828.200
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 108.229 4.413 72.152 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.229
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 108.258 4.413 72.172 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.258
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 1718.521 4.413 82.002 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1718.521
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 108.258 4.413 72.172 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.258
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3070.136 9.257 12.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3070.136
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3070.136 9.257 12.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3070.136
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1212.035 11.733 54.503 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1212.035
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 1818.789 4.413 82.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1818.789


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 277.500 2.686 12.479 0.000 0.250 0.000 0.750 ReachInFreezer 277.500 277.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 156.700 1.517 7.046 0.000 0.250 0.000 0.750 ReachInRefrigerator 156.700 156.700


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.760 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.1625 0.900 0.900 0.770 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.1625 0.900 0.900 0.770 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 0.4398 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 0.6205 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 0.6325 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 0.6205 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 0.6325 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1901 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1901 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.5681
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 6.093
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 6.093
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 2.106
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.444
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 1.414
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.444
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 1.414
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 5.000
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 5.000
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 3.628
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 3.628
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 3.628
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 3.628
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.7602615 1.7602615 1.7602615  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.63083111E-06 0.74112372E-09 -0.38647046E-05 0.15329585E-16
21 2 0.78415922 0.99752939E-03 1.0633801 -0.74093433E-06
22 1 -22.010056 0.66447931E-01 -6.3131541 0.20386814
23 0 21.355302 0.61958938E-01 5.3791822  
24 3 -0.63083111E-06 0.74112372E-09 -0.38647046E-05 0.15329585E-16
25 2 0.78415922 0.99752939E-03 1.0633801 -0.74093433E-06
26 1 -22.010056 0.66447931E-01 -6.3131541 0.20386814
27 0 21.355302 0.61958938E-01 5.3791822  
28 9 0.17371606E-14 -0.23506564E-15 -0.17234884E-09 -0.32590245E-16
29 8 0.25047502E-07 0.60224990E-13 0.41035840E-03 -0.28479873E-09
30 7 -0.13210747E-01 0.30368709E-08 -0.24480499E-01 0.15021102E-03
31 6 0.43168160 0.10447339E-05 0.49445446 -0.50581458E-02
32 5 -5.4474818 0.38634567E-04 -4.6127458 0.66369558E-01
33 4 34.139005 0.31329049E-03 22.110007 -0.43720821
34 3 -113.64276 0.67747045E-03 -56.947664 1.5501088
35 2 199.52538 0.37841992E-03 79.089894 -2.9387388
36 1 -172.04857 0.40136815E-04 -55.610049 2.7610814
37 0 57.057407 0.22679332E-06 15.501623  
38 9 0.70813426E-15 -0.32338650E-15 -0.16410183E-09 -0.10141964E-16
39 8 0.23891456E-07 0.84468069E-13 0.39866366E-03 -0.27165407E-09
40 7 -0.12863276E-01 0.43065613E-08 -0.23980655E-01 0.14626015E-03
41 6 0.42224223 0.14881230E-05 0.48645144 -0.49468774E-02
42 5 -5.3553902 0.55242587E-04 -4.5514413 0.65227641E-01
43 4 33.731817 0.44953144E-03 21.870751 -0.43180164
44 3 -112.77687 0.97513266E-03 -56.474829 1.5375981
45 2 198.66772 0.54621935E-03 78.655599 -2.9251182
46 1 -171.73197 0.58085406E-04 -55.482564 2.7555327
47 0 57.057407 0.32916664E-06 15.521701  
48 9 0.43401517E-15 -0.32871761E-15 -0.16354826E-09 -0.10464702E-16
49 8 0.23813808E-07 0.86070585E-13 0.39787146E-03 -0.27077120E-09
50 7 -0.12839716E-01 0.43915450E-08 -0.23946756E-01 0.14599225E-03
51 6 0.42160216 0.15179544E-05 0.48590822 -0.49393324E-02
52 5 -5.3491452 0.56364894E-04 -4.5472777 0.65150204E-01
53 4 33.704202 0.45877426E-03 21.854496 -0.43143498
54 3 -112.71814 0.99539661E-03 -56.442701 1.5367495
55 2 198.60954 0.55767767E-03 78.626100 -2.9241943
56 1 -171.71049 0.59314468E-04 -55.473923 2.7551562
57 0 57.057407 0.33620339E-06 15.523077  
58 9 0.70813426E-15 -0.32338650E-15 -0.16410183E-09 -0.10141964E-16
59 8 0.23891456E-07 0.84468069E-13 0.39866366E-03 -0.27165407E-09
60 7 -0.12863276E-01 0.43065613E-08 -0.23980655E-01 0.14626015E-03
61 6 0.42224223 0.14881230E-05 0.48645144 -0.49468774E-02
62 5 -5.3553902 0.55242587E-04 -4.5514413 0.65227641E-01
63 4 33.731817 0.44953144E-03 21.870751 -0.43180164
64 3 -112.77687 0.97513266E-03 -56.474829 1.5375981
65 2 198.66772 0.54621935E-03 78.655599 -2.9251182
66 1 -171.73197 0.58085406E-04 -55.482564 2.7555327
67 0 57.057407 0.32916664E-06 15.521701  
68 9 0.43401517E-15 -0.32871761E-15 -0.16354826E-09 -0.10464702E-16
69 8 0.23813808E-07 0.86070585E-13 0.39787146E-03 -0.27077120E-09
70 7 -0.12839716E-01 0.43915450E-08 -0.23946756E-01 0.14599225E-03
71 6 0.42160216 0.15179544E-05 0.48590822 -0.49393324E-02
72 5 -5.3491452 0.56364894E-04 -4.5472777 0.65150204E-01
73 4 33.704202 0.45877426E-03 21.854496 -0.43143498
74 3 -112.71814 0.99539661E-03 -56.442701 1.5367495
75 2 198.60954 0.55767767E-03 78.626100 -2.9241943
76 1 -171.71049 0.59314468E-04 -55.473923 2.7551562
77 0 57.057407 0.33620339E-06 15.523077  
78 7 -0.16359629E-14 -0.14530353E-16 -0.22331004E-13 0.54056000E-15
79 6 0.18262352E-10 0.22801053E-11 0.52333849E-09 -0.18642118E-10
80 5 -0.59540244E-07 0.11129510E-07 -0.21928235E-05 0.17164558E-06
81 4 0.60861605E-04 0.41961443E-05 0.17683552E-02 -0.28248824E-03
82 3 -0.87523238E-02 0.14809838E-03 -0.21562890 0.43346081E-01
83 2 0.12409989 0.64146884E-03 2.9009744 -0.61915653
84 1 -0.31397648 0.40472017E-03 -7.1381115 1.5697592
85 0 0.19977219 0.56546383E-05 4.4522022  
86 7 -0.22331004E-13 -0.14530353E-16 -0.16359629E-14 0.54056000E-15
87 6 0.52333849E-09 0.22801053E-11 0.18262352E-10 -0.18642118E-10
88 5 -0.21928235E-05 0.11129510E-07 -0.59540244E-07 0.17164558E-06
89 4 0.17683552E-02 0.41961443E-05 0.60861605E-04 -0.28248824E-03
90 3 -0.21562890 0.14809838E-03 -0.87523238E-02 0.43346081E-01
91 2 2.9009744 0.64146884E-03 0.12409989 -0.61915653
92 1 -7.1381115 0.40472017E-03 -0.31397648 1.5697592
93 0 4.4522022 0.56546383E-05 0.19977219  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
103 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
104 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
105 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
106 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
107 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
108 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
109 0 0.27512533 0.13606908E-04 60.838472  
110 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
111 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
112 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
113 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
114 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
115 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
116 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
117 0 0.27512533 0.13606908E-04 60.838472  
118 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
119 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
120 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
121 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
122 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
123 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
124 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
125 0 0.27512533 0.13606908E-04 60.838472  
126 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
127 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
128 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
129 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
130 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
131 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
132 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
133 0 0.27512533 0.13606908E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.265_SHGC_0.397 37 1 VerySmooth 1.505 1.505 1.000 0.398    
2 RESWINDOW_U_0.265_SHGC_0.397 38 1 VerySmooth 1.505 1.505 1.000 0.398    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   4.45510E-002 0.31125 0.49414 0.49414 0.43670 0.13422 0.17096 0.00000 0.84000 0.84000 9.10299E-002 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   4.45510E-002 0.31125 0.49414 0.49414 0.43670 0.13422 0.17096 0.00000 0.84000 0.84000 9.10299E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 2.320
2 RACK2 1 0 Zone Air-Cooled 6.980


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.263 2.9576E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1618
2 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 9.9145E-002
3 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1912
4 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 0.1206
5 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 8.8707E-002
6 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 3.6335E-002
7 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 4.5774E-002
8 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 1.5208E-002
9 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1805
10 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 0.1184
11 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.2133
12 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 0.1435
13 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 9.8133E-002
14 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 4.5682E-002
15 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 5.1377E-002
16 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 2.0772E-002
17 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 5.3245E-002
18 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 3.0425E-002
19 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 4.2478E-002
20 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 2.3992E-002
21 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 3.6410E-002
22 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.4310E-002
23 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 4.5051E-002
24 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.5975E-002
25 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 5.3245E-002
26 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 3.0425E-002
27 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 4.2478E-002
28 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 2.3992E-002
29 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 3.6410E-002
30 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.4310E-002
31 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 4.5051E-002
32 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.5975E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 29701.04068 29701.04068 2.19210 2.19210 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 23.42200 7.00114E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 2460.87529 2460.87529 0.10715 0.85446 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 6803.19995 6803.19995 0.50214 0.50214 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 27.40000 7.00714E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 4278.84844 4278.84844 0.18628 0.18628 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3070.68963 3070.68963 0.22666 0.22666 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 27.09400 7.00668E-003 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 1355.06407 1355.06407 5.89971E-002 9.17347E-002 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 2412.01970 2412.01970 0.17800 0.17800 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 27.19600 7.00683E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 2491.98324 2491.98324 0.10850 0.10850 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1314.73765 1314.73765 9.70243E-002 9.70243E-002 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 27.29800 7.00699E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 1765.55742 1765.55742 7.68688E-002 7.68688E-002 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44922.78253 44922.78253 3.31544 3.31544 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 27.40000 7.00714E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 3334.75999 3334.75999 0.14518 0.14518 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 26412.30239 26412.30239 1.95103 1.95103 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 27.40000 7.00714E-003 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 10828.40276 10828.40276 0.47143 0.67639 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 71483.66120 71483.66120 5.27782 5.27782 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 27.40000 7.00714E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 24587.22809 24587.22809 1.07048 1.89399 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 11780.01525 11780.01525 1.17152 1.17152 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 25.46200 7.00420E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 9434.70327 9434.70327 0.41315 0.41315 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 10594.88687 10594.88687 1.05366 1.05366 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 24.95200 7.00344E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 9427.27697 9427.27697 0.41282 0.41282 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 87935.67797 87935.67797 8.74492 8.74492 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 27.40000 7.00714E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 53045.54502 53045.54502 2.32303 2.32303 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 54932.70618 54932.70618 5.46330 5.46330 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:20:00 21.07600 6.99765E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 52941.23198 52941.23198 2.31847 2.31847 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 11110.32139 11110.32139 1.10492 1.10492 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 24.54400 7.00282E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 9421.16021 9421.16021 0.41255 0.41255 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 10047.69937 10047.69937 0.99924 0.99924 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 22.65700 7.00000E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 9413.73476 9413.73476 0.41223 0.41223 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 19325.95338 19325.95338 1.42632 1.42632 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40000 7.00714E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 13906.07876 13906.07876 0.60546 0.60546 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 3071.90582 3071.90582 0.30550 0.30550 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 25.46200 7.00420E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 2902.67805 2902.67805 0.12711 0.12711 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2733.65042 2733.65042 0.27186 0.27186 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 24.95200 7.00344E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 2900.22342 2900.22342 0.12700 0.12700 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 18471.58814 18471.58814 1.83705 1.83705 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 27.40000 7.00714E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 13914.30126 13914.30126 0.60933 0.60933 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 28529.60356 28529.60356 2.10818 2.10818 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40000 7.00714E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 9666.90151 9666.90151 0.42088 1.18780 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 29937.44794 29937.44794 2.21218 2.21218 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40000 7.00714E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 9834.61259 9834.61259 0.42818 1.18780 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 30720.33760 30720.33760 2.27307 2.27307 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 26.48200 7.00575E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 4899.56140 4899.56140 0.21329 0.36735 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 -41.90000 6.45023E-005 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 10367.19036 10367.19036 0.76512 0.76512 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40000 7.00714E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 10201.33996 10201.33996 0.44415 0.44415 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 336440.91 22.39823 22.39823 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 546284.84 7.82595 7.82595 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00
3 FLR_3_DOAS Cooling Sensible 35674.24 19.11046 2.05125 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 143185.63 7.15569 2.05125 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.19210
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.68787
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.58500
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.28238
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.53887E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.98425E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.28238
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9126.48309
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.98425E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 194.03701
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.50214
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10178
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23700
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.11901
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.74335E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.58920E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.18628
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5245.73533
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.58920E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 143.16083
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.22666
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.26112
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.60700
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13758
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.69631
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.45912E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.81029E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13758
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2069.27138
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.81029E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 47.90402
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.17800
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.70311
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000E-002
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.77999E-003
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.41878E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.67267E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.10850
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3055.03124
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.67267E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 83.37174
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.70243E-002
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.74421
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.89300
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.66427E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.11951E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.93805E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.66427E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2215.30457
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.93805E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 58.35675
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.31544
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.79361E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000E-002
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.31544E-002
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.12421E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.57628E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.14518
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4087.90463
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.57628E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 111.55863
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.95103
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.37626E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52000
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.01453
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52000
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.16522E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.40810E-004
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.01453
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16095.39746
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.40810E-004
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 376.13494
99 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.27782
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18887
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.53800
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.83947
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.53800
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.01723E-003
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.44066E-004
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.83947
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
110 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 39328.83397
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.44066E-004
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 898.36214
113 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
114 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.17152
115 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.17152
116 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 8.25389E-005
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.64047E-004
118 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69232
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.53540E-003
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.64047E-004
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.17152
125 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 9434.70327
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.25389E-005
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 269.61444
128 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
129 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.05366
130 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.05366
131 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 8.24739E-005
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.27756E-004
133 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69232
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.53908E-003
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.27756E-004
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.05366
140 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 9427.27697
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.24739E-005
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 269.40228
143 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
144 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 8.74492
145 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 8.74492
146 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.64066E-004
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.69079E-003
148 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69265
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.48040E-003
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.48040E-003
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.69079E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.74492
155 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 53045.54502
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.64066E-004
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 1515.87384
158 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
159 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.46330
160 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.46330
161 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.63153E-004
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.78652E-003
163 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69176
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.72431E-003
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.78652E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.46330
170 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 52941.23198
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.63153E-004
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 1512.89382
173 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
174 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.10492
175 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.10492
176 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 8.24204E-005
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.43528E-004
178 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69232
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.53726E-003
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.43528E-004
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.10492
185 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 9421.16021
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.24204E-005
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 269.22753
188 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
189 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.99924
190 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.99924
191 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 8.23555E-005
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.10982E-004
193 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69232
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.54085E-003
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.10982E-004
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.99924
200 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 9413.73476
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.23555E-005
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 269.01539
203 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.42632
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.83215
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.49900
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.71173
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.57852E-004
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.53993E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.71173
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
214 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 17602.31255
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.53993E-004
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 458.57951
217 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
218 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.30550
219 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.30550
220 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.53939E-005
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 9.48958E-005
222 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69233
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.53396E-003
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.48958E-005
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.30550
229 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2902.67805
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.53939E-005
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 82.94508
232 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
233 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.27186
234 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.27186
235 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.53724E-005
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 8.45385E-005
237 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69232
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.53789E-003
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 8.45385E-005
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.27186
244 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2900.22342
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.53724E-005
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 82.87496
247 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
248 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.83705
249 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.83705
250 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.21728E-004
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 5.76405E-004
252 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69206
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57055E-003
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.76405E-004
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.83705
259 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 13914.30126
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.21728E-004
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 397.60459
262 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.10818
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11988
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.84500
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.78141
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.84500
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.17825E-003
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.65513E-004
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.78141
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
273 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18919.18870
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.65513E-004
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 417.18767
276 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.21218
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11424
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.80500
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.78080
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.80500
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.33504E-003
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.66954E-004
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.78080
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
287 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19083.82741
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.66954E-004
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 421.25031
290 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.27307
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.22877E-002
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.24200
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.55008
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.10018E-002
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.78236E-005
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.55008
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
301 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7752.65879
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.78236E-005
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 177.57011
304 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.76512
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.41044
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.24600
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.18822
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.28267E-004
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.09430E-004
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.44415
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
315 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12508.54800
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.09430E-004
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 341.37987
318 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 13.15287
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 10.52680
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 22.52508
321 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 10.52680
322 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 22.39823
323 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 22.39823
324 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
325 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.46998
326 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
333 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
334 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 22.39823
335 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
336 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 22.39823
337 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 9.32920
338 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.40988
339 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.94818
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.52627E-003
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 393686.74908
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.12594E-002
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 22.39823
346 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 469047.49414
347 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.10343E-003
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 6161.67446
349 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 22.39823
350 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.12594E-002
351 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.22927E-005
352 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.10343E-003
353 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
354 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
355 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
356 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 27.40000
357 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.91318
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00714E-003
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00714E-003
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 38332.29647
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.09630E-003
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
364 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 42957.20027
365 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.75808E-004
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 564.31020
367 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
368 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.09630E-003
369 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 4.34362E-004
370 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 3.75808E-004
371 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 1.89352E-002
372 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 3060.92234
373 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 7.28304E-003
374 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.87396
375 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 7.28304E-003
376 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 2171.61523
377 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
378 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 832496.04648
379 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 832496.05000
380 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 7.28304E-003
381 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 1.89352E-002
382 PlantLoop COOLSYS1 Plant Loop Volume [m3] 2.27222
383 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 1.89352E-002
384 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 2119.17977
385 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 1.89352E-002
386 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 662071.14732
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 662692.73000
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 75.54697
389 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
390 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
391 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
392 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
393 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 9172.84
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 5265.64
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 2078.82
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 3066.63
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 2224.02
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 4103.42
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 16169.02
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 39512.71
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 10162.01
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 10154.01
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 57135.45
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 57023.11
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 10147.43
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 10139.43
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 17672.39
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 3126.35
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 3123.70
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 14986.51
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 19010.84
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 19176.18
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 7788.81
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 12556.01
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 249140.71
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 22817.28


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 18984.45 16439.49 2544.96 0.87 3822.11 38.77
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 17086.46 14789.65 2296.81 0.87 3436.34 34.85
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 141001.87 122583.63 18418.24 0.87 29025.18 294.39
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 91686.99 77770.16 13916.84 0.85 17617.50 178.69
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 17911.50 15507.04 2404.45 0.87 3604.16 36.56
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 16209.44 14027.65 2181.79 0.87 3258.29 33.05
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 4949.27 4286.51 662.76 0.87 996.84 10.11
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 4407.58 3815.63 591.95 0.87 886.73 8.99
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 29971.11 25849.07 4122.04 0.86 5979.88 60.65
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 506235.27 371653.32 134581.95 0.73 87553.70 888.02
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 51661.93 36376.38 15285.55 0.70 12474.20 126.52


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.93 13.40


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.270 0.259   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.270 0.259   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.270 0.259   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.270 0.259   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.440 0.413   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.440 0.413   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.440 0.413   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.440 0.413   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.440 0.413   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.760 1.760   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.440 0.413   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.440 0.413   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.440 0.413   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.440 0.413   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.440 0.413   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.440 0.413   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.440 0.413   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.440 0.413   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.620 0.568   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.620 0.568   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.620 0.568   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.620 0.568   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.620 0.568   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.620 0.568   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.620 0.568   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.620 0.568   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.620 0.568   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.620 0.568   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.620 0.568   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.620 0.568   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.620 0.568   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.620 0.568   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.632 0.578   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.632 0.578   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.163 0.158   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.632 0.578   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.632 0.578   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.163 0.158   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.632 0.578   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.163 0.158   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.632 0.578   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.632 0.578   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.632 0.578   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.632 0.578   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.632 0.578   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.632 0.578   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.632 0.578   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.632 0.578   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.265_SHGC_0.397 N/A 1.505 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.5976410071E-002 2.2068658109E-002 Pass Pass 2.8385090679E-003 4.3747118270E-003 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 1.3397202587E-003 9.7341006521E-004 Pass Pass 1.4902626463E-002 2.9478826606E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 1.0545900547E-003 7.3175543349E-004 Pass Pass 0.1584874076 0.5630940109 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 1.4716639992E-004 1.3164959363E-004 Pass Pass 5.7365483739E-002 0.1787574262 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 7.8284205990E-004 5.9315158049E-004 Pass Pass 1.1554399896E-002 2.0032521407E-002 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 9.7152823520E-005 1.8390113676E-004 Pass Pass 2.2146044275E-002 6.4188317491E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 2.4523794265E-003 1.7343410283E-003 Pass Pass 0.1041080862 0.4133446710 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 9.9502520188E-003 2.3314888525E-002 Pass Pass 3.6860355151E-002 0.1247453876 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 9.2668924261E-002 0.3375437075 Pass Pass 8.8053682342E-002 0.2586923529 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 9.2615861714E-002 0.3352696843 Pass Pass 8.7178041793E-002 0.2584866893 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 4.1479375711E-005 7.8365681880E-005 Pass Pass 2.7368823866E-002 6.7011317454E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 6.6700713128E-002 0.1955729645 Pass Pass 6.1502858559E-002 0.1685786513 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 9.2646771239E-002 0.3362727000 Pass Pass 8.8428912455E-002 0.2590759066 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 9.2620840536E-002 0.3339086719 Pass Pass 8.7585452872E-002 0.2587892378 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 4.8378376593E-004 3.6268418901E-004 Pass Pass 3.3676771184E-002 8.7674124706E-002 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 9.2649842892E-002 0.3503953903 Pass Pass 7.2420936697E-002 0.2506751852 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 9.2621299199E-002 0.3468688887 Pass Pass 7.1235333738E-002 0.2499687522 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 9.2621882893E-002 0.3355796779 Pass Pass 8.4253731462E-002 0.2419094019 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 2.9962503875E-002 8.0710668325E-002 Pass Pass 1.4126887031E-002 4.5461597815E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 3.5050606701E-002 8.8367655108E-002 Pass Pass 1.2468308750E-002 3.6772731818E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 1.0984219081E-003 2.0161186087E-003 Pass Pass 2.5954222309E-002 5.0619353392E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 6.5868771653E-004 4.2397210559E-004 Pass Pass 1.1758676205E-002 2.0544750272E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 2431.92 267.19 3313.54 9200.84 2333.55 17547.03



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB -41.90 0.00 -41.90 Wetbulb [C] 0.30 20.00
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 27.40 10.20 16.10 Wetbulb [C] 3.10 180.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.261 0.270 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.261 0.270 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.261 0.270 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.261 0.270 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.413 0.440 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.413 0.440 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.23 0.159 0.163 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.413 0.440 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.413 0.440 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.413 0.440 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.413 0.440 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.413 0.440 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.413 0.440 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.413 0.440 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.23 0.159 0.163 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.413 0.440 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.413 0.440 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.413 0.440 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.413 0.440 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.23 0.159 0.163 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.568 0.620 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.568 0.620 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.568 0.620 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.568 0.620 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.568 0.620 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.568 0.620 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.568 0.620 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.568 0.620 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.568 0.620 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.568 0.620 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 0.568 0.620 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 0.568 0.620 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 0.568 0.620 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 0.568 0.620 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.578 0.632 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.578 0.632 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.23 0.159 0.163 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 0.578 0.632 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.578 0.632 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.23 0.159 0.163 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.578 0.632 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.23 0.159 0.163 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.578 0.632 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.23 0.159 0.163 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.578 0.632 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.23 0.159 0.163 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.578 0.632 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.578 0.632 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 0.578 0.632 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.23 0.159 0.163 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 0.578 0.632 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 0.578 0.632 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 0.578 0.632 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.23 0.159 0.163 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.23 0.159 0.163 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.181 0.190 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.181 0.190 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.181 0.190 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.181 0.190 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.181 0.190 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.181 0.190 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.181 0.190 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.181 0.190 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.181 0.190 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.181 0.190 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.181 0.190 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.181 0.190 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.181 0.190 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.181 0.190 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.181 0.190 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.181 0.190 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.183 0.190 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.179 0.190 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.179 0.190 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.179 0.190 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.179 0.190 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.179 0.190 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.179 0.190 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.179 0.190 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.179 0.190 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.179 0.190 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.183 0.190 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.183 0.190 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.183 0.190 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.179 0.190 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.179 0.190 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.179 0.190 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.179 0.190 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.179 0.190 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.179 0.190 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.179 0.190 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.265_SHGC_0.397   23.26 0.00 0.00 23.26 23.26 1.505 0.398 0.438             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.265_SHGC_0.397   65.50 0.00 0.00 65.50 65.50 1.505 0.398 0.438             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.265_SHGC_0.397   85.08 0.00 0.00 85.08 85.08 1.505 0.398 0.438             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.265_SHGC_0.397   4.60 0.00 0.00 4.60 18.40 1.505 0.398 0.438             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.265_SHGC_0.397   8.58 0.00 0.00 8.58 34.34 1.505 0.398 0.438             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.265_SHGC_0.397   4.60 0.00 0.00 4.60 18.40 1.505 0.398 0.438             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.265_SHGC_0.397   8.58 0.00 0.00 8.58 34.34 1.505 0.398 0.438             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.265_SHGC_0.397   3.68 0.00 0.00 3.68 279.56 1.505 0.398 0.438             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.265_SHGC_0.397   3.68 0.00 0.00 3.68 279.65 1.505 0.398 0.438             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.265_SHGC_0.397   8.58 0.00 0.00 8.58 34.34 1.505 0.398 0.438             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.265_SHGC_0.397   4.60 0.00 0.00 4.60 18.40 1.505 0.398 0.438             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.265_SHGC_0.397   4.60 0.00 0.00 4.60 18.40 1.505 0.398 0.438             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.265_SHGC_0.397   8.58 0.00 0.00 8.58 34.34 1.505 0.398 0.438             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.265_SHGC_0.397   5.82 0.00 0.00 5.82 23.30 1.505 0.398 0.438             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.265_SHGC_0.397   2.15 0.00 0.00 2.15 8.59 1.505 0.398 0.438             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.265_SHGC_0.397   2.15 0.00 0.00 2.15 8.58 1.505 0.398 0.438             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.265_SHGC_0.397   5.82 0.00 0.00 5.82 23.30 1.505 0.398 0.438             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.265_SHGC_0.397   4.60 0.00 0.00 4.60 4.60 1.505 0.398 0.438             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.265_SHGC_0.397   8.58 0.00 0.00 8.58 8.58 1.505 0.398 0.438             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.265_SHGC_0.397   4.60 0.00 0.00 4.60 4.60 1.505 0.398 0.438             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.265_SHGC_0.397   8.58 0.00 0.00 8.58 8.58 1.505 0.398 0.438             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.265_SHGC_0.397   6.74 0.00 0.00 6.74 60.70 1.505 0.398 0.438             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.265_SHGC_0.397   32.19 0.00 0.00 32.19 32.19 1.505 0.398 0.438             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.265_SHGC_0.397   32.19 0.00 0.00 32.19 32.19 1.505 0.398 0.438             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.265_SHGC_0.397   4.60 0.00 0.00 4.60 4.60 1.505 0.398 0.438             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.265_SHGC_0.397   17.17 0.00 0.00 17.17 17.17 1.505 0.398 0.438             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.265_SHGC_0.397   4.60 0.00 0.00 4.60 4.60 1.505 0.398 0.438             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.265_SHGC_0.397   5.82 0.00 0.00 5.82 5.82 1.505 0.398 0.438             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.265_SHGC_0.397   5.21 0.00 0.00 5.21 5.21 1.505 0.398 0.438             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.265_SHGC_0.397   17.17 0.00 0.00 17.17 17.17 1.505 0.398 0.438             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 1.505 0.398 0.438                      
North Total or Average             432.95 1.505 0.398 0.438                      
Non-North Total or Average             780.84 1.505 0.398 0.438                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.393 1.760 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 6.7179 1978.83 13293.58 LightsWired LTG_SCH_BASEMENT 49.32 168.00 49.26 0.0000 Y 122.93
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 9.6995 67.07 650.56 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 6.26
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 9.6995 77.67 753.35 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 7.25
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 4.6285 164.24 760.20 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 8.37
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 4.2862 94.76 406.16 LightsWired LTG_SCH_STORAGE 30.30 168.00 30.27 0.0000 Y 2.31
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.7049 78.04 445.21 LightsWired LTG_SCH_LAUNDRY 58.69 168.00 58.63 0.0000 Y 4.90
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 9.2569 188.86 1748.29 LightsWired LTG_SCH_DINING 58.69 168.00 39.04 0.0000 Y 12.81
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 9.0417 1308.19 11828.20 LightsWired LTG_SCH_LOBBY 44.02 168.00 41.50 0.0000 Y 92.14
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 4.4132 156.09 688.85 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 4.4132 156.07 688.77 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 4.4132 1863.81 8225.38 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 58.78
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 4.4132 1864.32 8227.62 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 58.79
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 4.4132 156.09 688.85 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 4.4132 156.07 688.77 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 4.4132 1557.62 6874.08 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 56.74
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 4.4132 39.02 172.21 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 1.23
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 4.4132 39.02 172.19 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 1.23
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 4.4132 220.77 974.32 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 6.96
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 9.2569 331.66 3070.14 LightsWired LTG_SCH_DINING 58.69 168.00 48.88 0.0000 Y 28.17
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 9.2569 331.66 3070.14 LightsWired LTG_SCH_DINING 58.69 168.00 48.88 0.0000 Y 28.17
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 11.7327 103.30 1212.04 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 13.34
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 4.4132 412.12 1818.79 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 15.01
Interior Lighting Total       5.8577 11345.29 66457.67               365.55


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 11828.20 827.97
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 11828.20 827.97
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1748.29 681.83
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1748.29 681.83
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 3070.14 614.03
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 3070.14 614.03
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 3070.14 614.03
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 3070.14 614.03


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 12338.45 AstronomicalClock -   83.06 83.06 192.37
Exterior Lighting Total 12338.45           192.37



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 832496.05 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 662692.73 2.96 662809.21 2.96 3.93 13.40


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12729.22 18984.45 16439.49 2544.96 0.87 - 3822.11 38.77
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11460.28 17086.46 14789.65 2296.81 0.87 - 3436.34 34.85
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 94085.77 141001.87 122583.63 18418.24 0.87 - 29025.18 294.39
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 62467.09 91686.99 77770.16 13916.84 0.85 - 17617.50 178.69
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12011.74 17911.50 15507.04 2404.45 0.87 - 3604.16 36.56
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10873.73 16209.44 14027.65 2181.79 0.87 - 3258.29 33.05
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3318.11 4949.27 4286.51 662.76 0.87 - 996.84 10.11
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2955.96 4407.58 3815.63 591.95 0.87 - 886.73 8.99
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 20154.49 29971.11 25849.07 4122.04 0.86 - 5979.88 60.65
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 393686.75 506235.27 371653.32 134581.95 0.73 - 87553.70 888.02
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 38332.30 51661.93 36376.38 15285.55 0.70 - 12474.20 126.52
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 9126.48 9172.84 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 5245.74 5265.64 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2069.27 2078.82 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 3055.03 3066.63 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2215.30 2224.02 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 4087.90 4103.42 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 16095.40 16169.02 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 39328.83 39512.71 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 9434.70 10162.01 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 9427.28 10154.01 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 53045.55 57135.45 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 52941.23 57023.11 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 9421.16 10147.43 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 9413.73 10139.43 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 17602.31 17672.39 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 2902.68 3126.35 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 2900.22 3123.70 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 13914.30 14986.51 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 18919.19 19010.84 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 19083.83 19176.18 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 7752.66 7788.81 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 12508.55 12556.01 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 469047.49 249140.71 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 42957.20 22817.28 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.24 0.00 0.00 1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.17 824.33 703.64 1.00 1.16 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.05 741.40 703.64 1.00 1.18 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 8.74 6153.24 703.64 1.00 0.94 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.46 3844.18 703.64 1.00 0.96 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:20:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.10 777.46 703.64 1.00 1.17 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.00 703.10 703.64 1.00 1.20 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.31 214.96 703.64 1.00 1.70 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.27 191.29 703.64 1.00 1.78 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.84 1292.62 703.64 1.00 1.08 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 22.40 50186.34 2240.64 1.00 1.11 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.018935 3060.92 161652.92 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.007283 2171.62 298174.34 0.91 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.018935 2119.18 111917.77 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 29701.04 29701.04 15.01 2.192 2.192 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 24.00 24.00 0.00931 23.42 0.00700 0.854 0.00
RETAIL_1_FLR_1 6803.20 6803.20 101.43 0.502 0.502 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 24.00 0.00883 27.40 0.00701 0.079 0.00
RETAIL_2_FLR_1 3070.69 3070.69 39.54 0.227 0.227 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 24.00 24.00 0.00939 27.09 0.00701 0.092 0.00
MECH_FLR_1 2412.02 2412.02 14.69 0.178 0.178 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 24.00 24.00 0.00867 27.20 0.00701 0.000 0.00
STORAGE_FLR_1 1314.74 1314.74 13.87 0.097 0.097 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 24.00 0.00876 27.30 0.00701 0.058 0.00
LAUNDRY_FLR_1 44922.78 44922.78 575.64 3.315 3.315 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 24.00 0.00854 27.40 0.00701 0.000 0.00
CAFE_FLR_1 26412.30 26412.30 139.85 1.951 1.951 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 23.99 0.00969 27.40 0.00701 0.676 0.00
LOBBY_FLR_1 71483.66 71483.66 54.64 5.278 5.278 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 23.99 0.00981 27.40 0.00701 1.894 0.00
ROOM_1_FLR_3 11780.02 11780.02 301.88 1.172 1.172 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 21.11 21.11 0.00854 25.46 0.00700 0.062 0.00
ROOM_2_FLR_3 10594.89 10594.89 271.54 1.054 1.054 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 21.11 21.11 0.00854 24.95 0.00700 0.062 0.00
ROOM_3_MULT19_FLR_3 87935.68 87935.68 3585.72 8.745 8.745 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 21.11 21.11 0.00848 27.40 0.00701 0.837 0.00
ROOM_4_MULT19_FLR_3 54932.71 54932.71 2239.36 5.463 5.463 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:20:00 21.11 21.11 0.00872 21.08 0.00700 0.837 0.00
ROOM_5_FLR_3 11110.32 11110.32 284.72 1.105 1.105 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 21.11 21.11 0.00854 24.54 0.00700 0.062 0.00
ROOM_6_FLR_3 10047.70 10047.70 257.52 0.999 0.999 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 21.11 21.11 0.00854 22.66 0.00700 0.062 0.00
CORRIDOR_FLR_3 19325.95 19325.95 49.63 1.426 1.426 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00945 27.40 0.00701 0.475 0.00
ROOM_1_FLR_6 3071.91 3071.91 78.72 0.306 0.306 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 21.11 21.11 0.00853 25.46 0.00700 0.015 0.00
ROOM_2_FLR_6 2733.65 2733.65 70.06 0.272 0.272 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 21.11 21.11 0.00854 24.95 0.00700 0.015 0.00
ROOM_3_MULT9_FLR_6 18471.59 18471.59 753.00 1.837 1.837 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 21.11 21.11 0.00857 27.40 0.00701 0.099 0.00
BANQUET_FLR_6 28529.60 28529.60 86.02 2.108 2.108 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 23.98 0.01046 27.40 0.00701 1.188 0.00
DINING_FLR_6 29937.45 29937.45 90.27 2.212 2.212 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 23.99 0.01037 27.40 0.00701 1.188 0.00
KITCHEN_FLR_6 30720.34 30720.34 297.38 2.273 2.273 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.01006 26.48 0.00701 0.367 0.00
CORRIDOR_FLR_6 10367.19 10367.19 25.16 0.765 0.765 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00896 27.40 0.00701 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 2460.88 2460.88 1.24 0.107 0.854 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00800 -41.90 0.00006 0.854 0.00
RETAIL_1_FLR_1 4278.85 4278.85 63.80 0.186 0.186 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00750 -41.90 0.00006 0.079 0.00
RETAIL_2_FLR_1 1355.06 1355.06 17.45 0.059 0.092 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00740 -41.90 0.00006 0.092 0.00
MECH_FLR_1 2491.98 2491.98 15.17 0.108 0.108 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00725 -41.90 0.00006 0.000 0.00
STORAGE_FLR_1 1765.56 1765.56 18.63 0.077 0.077 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00738 -41.90 0.00006 0.058 0.00
LAUNDRY_FLR_1 3334.76 3334.76 42.73 0.145 0.145 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00724 -41.90 0.00006 0.000 0.00
CAFE_FLR_1 10828.40 10828.40 57.34 0.471 0.676 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00756 -41.90 0.00006 0.676 0.00
LOBBY_FLR_1 24587.23 24587.23 18.79 1.070 1.894 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00746 -41.90 0.00006 1.894 0.00
ROOM_1_FLR_3 9434.70 9434.70 241.78 0.413 0.413 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00748 -41.90 0.00006 0.062 0.00
ROOM_2_FLR_3 9427.28 9427.28 241.62 0.413 0.413 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00748 -41.90 0.00006 0.062 0.00
ROOM_3_MULT19_FLR_3 53045.55 53045.55 2163.02 2.323 2.323 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00751 -41.90 0.00006 0.837 0.00
ROOM_4_MULT19_FLR_3 52941.23 52941.23 2158.18 2.318 2.318 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00751 -41.90 0.00006 0.837 0.00
ROOM_5_FLR_3 9421.16 9421.16 241.43 0.413 0.413 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00748 -41.90 0.00006 0.062 0.00
ROOM_6_FLR_3 9413.73 9413.73 241.27 0.412 0.412 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00748 -41.90 0.00006 0.062 0.00
CORRIDOR_FLR_3 13906.08 13906.08 35.71 0.605 0.605 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00757 -41.90 0.00006 0.475 0.00
ROOM_1_FLR_6 2902.68 2902.68 74.39 0.127 0.127 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00757 -41.90 0.00006 0.015 0.00
ROOM_2_FLR_6 2900.22 2900.22 74.33 0.127 0.127 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00757 -41.90 0.00006 0.015 0.00
ROOM_3_MULT9_FLR_6 13914.30 13914.30 567.22 0.609 0.609 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00759 -41.90 0.00006 0.099 0.00
BANQUET_FLR_6 9666.90 9666.90 29.15 0.421 1.188 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00768 -41.90 0.00006 1.188 0.00
DINING_FLR_6 9834.61 9834.61 29.65 0.428 1.188 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00769 -41.90 0.00006 1.188 0.00
KITCHEN_FLR_6 4899.56 4899.56 47.43 0.213 0.367 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 21.00 21.00 0.00724 -41.90 0.00006 0.367 0.00
CORRIDOR_FLR_6 10201.34 10201.34 24.75 0.444 0.444 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00773 -41.90 0.00006 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 22.40 22.40 7.83 7.83 22.3982 10.5268 22.3982 0.4700 0.3000
FLR_3_DOAS 19.11 2.05 7.16 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 9126.483 9126.483 1.282378 0.00007984 194.037 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 9126.48 9126.48 1.282378 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00799839 50.9029 2460.88 0.00 9177.43 9177.43
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 5245.735 5245.735 0.186280 0.00004589 143.161 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5245.74 5245.74 0.186280 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00750379 47.7992 4278.85 0.00 5271.75 5271.75
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 2069.271 2069.271 0.137580 0.00001810 47.904 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2069.27 2069.27 0.137580 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00740339 47.1633 1355.06 0.00 2080.35 2080.35
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 3055.031 3055.031 0.108496 0.00002673 83.372 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 3055.03 3055.03 0.108496 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00724936 46.1937 2491.98 0.00 3070.18 3070.18
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 2215.305 2215.305 0.086643 0.00001938 58.357 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2215.30 2215.30 0.086643 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00737781 47.0025 1765.56 0.00 2226.40 2226.40
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 4087.905 4087.905 0.145178 0.00003576 111.559 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4087.90 4087.90 0.145178 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00723550 46.1104 3334.76 0.00 4108.18 4108.18
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 16095.397 16095.397 1.014534 0.00014081 376.135 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 16095.40 16095.40 1.014534 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00756312 48.1714 10828.40 0.00 16181.29 16181.29
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 39328.834 39328.834 2.839466 0.00034407 898.362 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 39328.83 39328.83 2.839466 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00745798 47.5070 24587.23 0.00 39540.27 39540.27
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 12729.220 -999.000 1.171523 0.00036405 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 unknown 7/21 17:30:00 12729.22 12621.54 1.171523 21.69 15.43 0.00853540 12.80 11.96 0.00850000 25.46 0.00700420 15.45 0.0000 21.11 0.00853540 53.9060 11780.02 0.00 12933.81 12933.81
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 9434.703 9434.703 0.413147 0.00008254 269.614 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 9434.70 9434.70 0.413147 21.11 14.26 0.00748206 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00748206 47.3394 9434.70 0.00 10170.52 10170.52
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 11460.281 -999.000 1.053662 0.00032776 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown 7/21 18:00:00 11460.28 11353.34 1.053662 21.69 15.44 0.00853908 12.80 11.96 0.00850000 24.95 0.00700344 15.26 0.0000 21.11 0.00853908 53.9290 10594.89 0.00 11644.31 11644.31
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 9427.277 9427.277 0.412822 0.00008247 269.402 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 9427.28 9427.28 0.412822 21.11 14.26 0.00748172 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00748172 47.3373 9427.28 0.00 10162.52 10162.52
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 94085.773 -999.000 8.744916 0.00269079 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown 7/21 14:10:00 94085.77 94085.77 8.744916 21.69 15.38 0.00848040 12.80 11.94 0.00848040 27.40 0.00700714 16.15 0.0000 21.11 0.00848040 53.5625 87935.68 0.00 95619.94 95619.94
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 53045.545 53045.545 2.323034 0.00046407 1515.874 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 53045.55 53045.55 2.323034 21.11 14.29 0.00750985 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00750985 47.5093 53045.55 0.00 57183.87 57183.87
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 62467.092 -999.000 5.463305 0.00178652 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:20:00 unknown 7/21 21:20:00 62467.09 59263.01 5.463305 21.69 15.60 0.00872431 12.80 11.96 0.00850000 21.08 0.00699765 13.80 0.0000 21.11 0.00872431 55.0838 54932.71 0.00 63458.03 63458.03
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 52941.232 52941.232 2.318466 0.00046315 1512.894 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 52941.23 52941.23 2.318466 21.11 14.29 0.00750882 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00750882 47.5029 52941.23 0.00 57071.41 57071.41
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 12011.743 -999.000 1.104922 0.00034353 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 unknown 7/21 10:40:00 12011.74 11904.84 1.104922 21.69 15.43 0.00853726 12.80 11.96 0.00850000 24.54 0.00700282 15.11 0.0000 21.11 0.00853726 53.9176 11110.32 0.00 12204.72 12204.72
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 9421.160 9421.160 0.412554 0.00008242 269.228 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 9421.16 9421.16 0.412554 21.11 14.26 0.00748137 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00748137 47.3351 9421.16 0.00 10155.92 10155.92
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 10873.731 -999.000 0.999244 0.00031098 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 unknown 7/21 09:30:00 10873.73 10767.71 0.999244 21.69 15.44 0.00854085 12.80 11.96 0.00850000 22.66 0.00700000 14.41 0.0000 21.11 0.00854085 53.9400 10047.70 0.00 11048.27 11048.27
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 9413.735 9413.735 0.412229 0.00008236 269.015 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 9413.73 9413.73 0.412229 21.11 14.26 0.00748102 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00748102 47.3329 9413.73 0.00 10147.92 10147.92
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 17602.313 17602.313 0.711732 0.00015399 458.580 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 17602.31 17602.31 0.711732 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00756770 48.1961 13906.08 0.00 17690.82 17690.82
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3318.110 -999.000 0.305501 0.00009490 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 unknown 7/21 17:30:00 3318.11 3291.17 0.305501 21.69 15.43 0.00853396 12.80 11.96 0.00850000 25.46 0.00700420 15.45 0.0000 21.11 0.00853396 53.8971 3071.91 0.00 3371.46 3371.46
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 2902.678 2902.678 0.127109 0.00002539 82.945 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2902.68 2902.68 0.127109 21.11 14.35 0.00757382 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00757382 47.9128 2902.68 0.00 3129.06 3129.06
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2955.960 -999.000 0.271862 0.00008454 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown 7/21 18:00:00 2955.96 2929.21 0.271862 21.69 15.43 0.00853789 12.80 11.96 0.00850000 24.95 0.00700344 15.26 0.0000 21.11 0.00853789 53.9216 2733.65 0.00 3003.44 3003.44
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2900.223 2900.223 0.127002 0.00002537 82.875 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2900.22 2900.22 0.127002 21.11 14.35 0.00757351 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00757351 47.9108 2900.22 0.00 3126.42 3126.42
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 20154.488 -999.000 1.837050 0.00057641 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown 7/21 14:10:00 20154.49 19817.50 1.837050 21.69 15.46 0.00857055 12.80 11.96 0.00850000 27.40 0.00700714 16.15 0.0000 21.11 0.00857055 54.1258 18471.59 0.00 20478.89 20478.89
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 13914.301 13914.301 0.609327 0.00012173 397.605 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 13914.30 13914.30 0.609327 21.11 14.36 0.00758975 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00758975 48.0110 13914.30 0.00 14999.63 14999.63
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 18919.189 18919.189 1.781414 0.00016551 417.188 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 18919.19 18919.19 1.781414 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00768122 48.9117 9666.90 0.00 19022.28 19022.28
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 19083.827 19083.827 1.780805 0.00016695 421.250 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 19083.83 19083.83 1.780805 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00768645 48.9445 9834.61 0.00 19187.77 19187.77
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 7752.659 7752.659 0.550083 0.00006782 177.570 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 7752.66 7752.66 0.550083 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00723894 46.1346 4899.56 0.00 7794.30 7794.30
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 12508.548 12508.548 0.444154 0.00010943 341.380 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 12508.55 12508.55 0.444154 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00773351 49.2397 10201.34 0.00 12570.58 12570.58
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 393686.749 -999.000 22.398229 0.01125939 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 393686.75 391856.94 22.398229 25.41 16.74 0.00852627 10.95 10.95 0.00850000 27.40 0.00700714 16.15 41.6515 23.99 0.00958523 50.7307 303286.48 0.00 398973.93 380437.75
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 469047.494 469047.494 6.719469 0.00410343 6161.674 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 469047.49 469047.49 6.719469 -41.90 -41.90 0.00006450 16.70 13.04 0.00800000 -41.90 0.00006450 -41.90 138.8384 21.00 0.00754875 48.0781 98659.87 0.00 300789.46 300789.46
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 38332.296 -999.000 2.051317 0.00109630 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 38332.30 38332.30 2.051317 27.40 16.15 0.00700714 11.91 10.04 0.00700714 27.40 0.00700714 16.15 99.9965 21.11 0.00857689 54.1644 192161.44 0.00 38875.86 38875.86
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 42957.200 42957.200 0.615395 0.00037581 564.310 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 42957.20 42957.20 0.615395 -41.90 -41.90 0.00006450 16.70 13.04 0.00800000 -41.90 0.00006450 -41.90 333.3216 21.11 0.00751009 47.5109 163400.85 0.00 27547.47 27547.47



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 9126.483 9126.483 1.282378 0.00007984 194.037 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 1.0747 1.096279 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 9126.48 9126.48 1.0000 1.52018081 1.282378 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.07983431 60.00 32.22 27.78 0.000 9126.48 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00799839 21.00 0.00799839 50.9029 2460.88 0.00 9177.43 9177.43 1.52018081 16.60 13.15 0.00800000 36934.7 22.52 15.42 0.00800000 42971.8
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 5245.735 5245.735 0.186280 0.00004589 143.161 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 0.6177 0.630121 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5245.74 5245.74 1.0000 0.22082364 0.186280 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.04588730 60.00 32.22 27.78 0.000 5245.74 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00750379 21.00 0.00750379 47.7992 4278.85 0.00 5271.75 5271.75 0.22082364 16.60 13.15 0.00800000 36934.7 40.01 21.19 0.00800000 60807.9
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 2069.271 2069.271 0.137580 0.00001810 47.904 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 0.2437 0.248562 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2069.27 2069.27 1.0000 0.16309325 0.137580 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.01810104 60.00 32.22 27.78 0.000 2069.27 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00740339 21.00 0.00740339 47.1633 1355.06 0.00 2080.35 2080.35 0.16309325 16.60 13.15 0.00800000 36934.7 29.11 17.74 0.00800000 49690.3
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 3055.031 3055.031 0.108496 0.00002673 83.372 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 0.3597 0.366972 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 3055.03 3055.03 1.0000 0.12861512 0.108496 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.02672402 60.00 32.22 27.78 0.000 3055.03 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00724936 21.00 0.00724936 46.1937 2491.98 0.00 3070.18 3070.18 0.12861512 16.60 13.15 0.00800000 36934.7 40.01 21.19 0.00800000 60805.8
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 2215.305 2215.305 0.086643 0.00001938 58.357 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 0.2609 0.266104 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2215.30 2215.30 1.0000 0.10270966 0.086643 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.01937847 60.00 32.22 27.78 0.000 2215.30 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00737781 21.00 0.00737781 47.0025 1765.56 0.00 2226.40 2226.40 0.10270966 16.60 13.15 0.00800000 36934.7 37.86 20.54 0.00800000 58611.4
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 4087.905 4087.905 0.145178 0.00003576 111.559 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 0.4814 0.491042 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4087.90 4087.90 1.0000 0.17209931 0.145178 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.03575912 60.00 32.22 27.78 0.000 4087.90 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00723550 21.00 0.00723550 46.1104 3334.76 0.00 4108.18 4108.18 0.17209931 16.60 13.15 0.00800000 36934.7 40.01 21.19 0.00800000 60805.7
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 16095.397 16095.397 1.014534 0.00014081 376.135 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 1.8952 1.933390 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 16095.40 16095.40 1.0000 1.20266792 1.014534 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.14079519 60.00 32.22 27.78 0.000 16095.40 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00756312 21.00 0.00756312 48.1714 10828.40 0.00 16181.29 16181.29 1.20266792 16.60 13.15 0.00800000 36934.7 29.79 17.97 0.00800000 50389.2
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 39328.834 39328.834 2.839466 0.00034407 898.362 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 4.6310 4.724207 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 39328.83 39328.83 1.0000 3.36601476 2.839466 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.34403070 60.00 32.22 27.78 0.000 39328.83 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00745798 21.00 0.00745798 47.5070 24587.23 0.00 39540.27 39540.27 3.36601476 16.60 13.15 0.00800000 36934.7 28.12 17.40 0.00800000 48681.6
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 12729.220 -999.000 1.171523 0.00036405 -999.000 -999.0000 1.00000 1.00000 1020.7069 1004.8586 1.1854 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.171523 1.38876947   4197.9300 999.8980 18.93321942 15.03 6.70 8.33 662071.15 1.9226 1.922600 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 unknown unknown unknown 7/21 17:30:00 Sensible 12729.22 12621.54 1.0000 1.38876947 1.171523 21.69 15.43 0.00853540 43488.0 12.80 11.96 0.00850000 34322.2 0.36401016 6.70 15.03 8.33 0.000 12729.22 25.46 0.00700420 15.45 0.00000000 0.0000 21.11 0.00853540 21.11 0.00853540 53.9060 11780.02 0.00 12933.81 12933.81 1.38876947 21.69 15.59 0.00853540 43488.0 12.57 12.04 0.00853540 34174.9
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 9434.703 9434.703 0.413147 0.00008254 269.614 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.171523 1.38876947   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 1.1109 1.133303 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 9434.70 9434.70 1.0000 0.48976050 0.413147 21.11 14.26 0.00748206 40216.4 40.00 21.00 0.00800000 60796.0 0.08253048 60.00 32.22 27.78 0.000 9434.70 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00748206 21.11 0.00748206 47.3394 9434.70 0.00 10170.52 10170.52 0.48976050 16.60 12.64 0.00748206 35623.4 36.98 19.88 0.00748206 56389.7
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 11460.281 -999.000 1.053662 0.00032776 -999.000 -999.0000 1.00000 1.00000 1020.7137 1004.8586 1.1854 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.053662 1.24905293   4197.9300 999.8980 18.93321942 15.03 6.70 8.33 662071.15 1.7310 1.730942 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown unknown unknown 7/21 18:00:00 Sensible 11460.28 11353.34 1.0000 1.24905293 1.053662 21.69 15.44 0.00853908 43497.4 12.80 11.96 0.00850000 34322.2 0.32772304 6.70 15.03 8.33 0.000 11460.28 24.95 0.00700344 15.26 0.00000000 0.0000 21.11 0.00853908 21.11 0.00853908 53.9290 10594.89 0.00 11644.31 11644.31 1.24905293 21.69 15.59 0.00853908 43497.4 12.56 12.04 0.00853908 34174.9
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 9427.277 9427.277 0.412822 0.00008247 269.402 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.053662 1.24905293   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 1.1101 1.132411 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 9427.28 9427.28 1.0000 0.48937499 0.412822 21.11 14.26 0.00748172 40215.5 40.00 21.00 0.00800000 60796.0 0.08246552 60.00 32.22 27.78 0.000 9427.28 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00748172 21.11 0.00748172 47.3373 9427.28 0.00 10162.52 10162.52 0.48937499 16.60 12.64 0.00748172 35622.5 36.98 19.88 0.00748172 56388.9
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 94085.773 -999.000 8.744916 0.00269079 -999.000 -999.0000 1.00000 1.00000 1020.6046 1004.8586 1.1854 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 8.744916 10.36656735   4197.9300 999.8980 18.93321942 15.03 6.70 8.33 662071.15 14.2108 14.210560 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown unknown unknown 7/21 14:10:00 Sensible 94085.77 94085.77 1.0000 10.36656735 8.744916 21.69 15.38 0.00848040 43348.6 12.80 11.94 0.00848040 34272.7 2.69051645 6.70 15.03 8.33 0.000 94085.77 27.40 0.00700714 16.15 0.00000000 0.0000 21.11 0.00848040 21.11 0.00848040 53.5625 87935.68 0.00 95619.94 95619.94 10.36656735 21.69 15.54 0.00848040 43348.6 12.65 12.02 0.00848040 34124.7
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 53045.545 53045.545 2.323034 0.00046407 1515.874 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 8.744916 10.36656735   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 6.2462 6.371868 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 53045.55 53045.55 1.0000 2.75381579 2.323034 21.11 14.29 0.00750985 40288.4 40.00 21.00 0.00800000 60796.0 0.46401823 60.00 32.22 27.78 0.000 53045.55 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00750985 21.11 0.00750985 47.5093 53045.55 0.00 57183.87 57183.87 2.75381579 16.60 12.67 0.00750985 35693.8 36.98 19.90 0.00750985 56459.1
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 62467.092 -999.000 5.463305 0.00178652 -999.000 -999.0000 1.00000 1.00000 1021.0581 1004.8586 1.1854 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.463305 6.47641600   4197.9300 999.8980 18.93321942 15.03 6.70 8.33 662071.15 9.4351 9.434926 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:20:00 unknown unknown unknown 7/21 21:20:00 Sensible 62467.09 59263.01 1.0000 6.47641600 5.463305 21.69 15.60 0.00872431 43967.5 12.80 11.96 0.00850000 34322.2 1.78633531 6.70 15.03 8.33 0.000 62467.09 21.08 0.00699765 13.80 0.00000000 0.0000 21.11 0.00872431 21.11 0.00872431 55.0838 54932.71 0.00 63458.03 63458.03 6.47641600 21.69 15.76 0.00872431 43967.5 12.10 12.03 0.00872431 34169.2
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 52941.232 52941.232 2.318466 0.00046315 1512.894 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.463305 6.47641600   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 6.2339 6.359337 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 52941.23 52941.23 1.0000 2.74840043 2.318466 21.11 14.29 0.00750882 40285.7 40.00 21.00 0.00800000 60796.0 0.46310575 60.00 32.22 27.78 0.000 52941.23 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00750882 21.11 0.00750882 47.5029 52941.23 0.00 57071.41 57071.41 2.74840043 16.60 12.67 0.00750882 35691.2 36.98 19.90 0.00750882 56456.5
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 12011.743 -999.000 1.104922 0.00034353 -999.000 -999.0000 1.00000 1.00000 1020.7103 1004.8586 1.1854 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.104922 1.30981774   4197.9300 999.8980 18.93321942 15.03 6.70 8.33 662071.15 1.8143 1.814234 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 unknown unknown unknown 7/21 10:40:00 Sensible 12011.74 11904.84 1.0000 1.30981774 1.104922 21.69 15.43 0.00853726 43492.7 12.80 11.96 0.00850000 34322.2 0.34349288 6.70 15.03 8.33 0.000 12011.74 24.54 0.00700282 15.11 0.00000000 0.0000 21.11 0.00853726 21.11 0.00853726 53.9176 11110.32 0.00 12204.72 12204.72 1.30981774 21.69 15.59 0.00853726 43492.7 12.56 12.04 0.00853726 34174.9
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 9421.160 9421.160 0.412554 0.00008242 269.228 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.104922 1.30981774   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 1.1094 1.131676 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 9421.16 9421.16 1.0000 0.48905746 0.412554 21.11 14.26 0.00748137 40214.6 40.00 21.00 0.00800000 60796.0 0.08241201 60.00 32.22 27.78 0.000 9421.16 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00748137 21.11 0.00748137 47.3351 9421.16 0.00 10155.92 10155.92 0.48905746 16.60 12.64 0.00748137 35621.7 36.98 19.88 0.00748137 56388.0
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 10873.731 -999.000 0.999244 0.00031098 -999.000 -999.0000 1.00000 1.00000 1020.7170 1004.8586 1.1854 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.999244 1.18454324   4197.9300 999.8980 18.93321942 15.03 6.70 8.33 662071.15 1.6424 1.642350 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 unknown unknown unknown 7/21 09:30:00 Sensible 10873.73 10767.71 1.0000 1.18454324 0.999244 21.69 15.44 0.00854085 43501.9 12.80 11.96 0.00850000 34322.2 0.31094979 6.70 15.03 8.33 0.000 10873.73 22.66 0.00700000 14.41 0.00000000 0.0000 21.11 0.00854085 21.11 0.00854085 53.9400 10047.70 0.00 11048.27 11048.27 1.18454324 21.69 15.59 0.00854085 43501.9 12.55 12.04 0.00854085 34174.9
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 9413.735 9413.735 0.412229 0.00008236 269.015 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.999244 1.18454324   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 1.1085 1.130784 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 9413.73 9413.73 1.0000 0.48867200 0.412229 21.11 14.26 0.00748102 40213.8 40.00 21.00 0.00800000 60796.0 0.08234706 60.00 32.22 27.78 0.000 9413.73 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00748102 21.11 0.00748102 47.3329 9413.73 0.00 10147.92 10147.92 0.48867200 16.60 12.64 0.00748102 35620.8 36.98 19.88 0.00748102 56387.1
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 17602.313 17602.313 0.711732 0.00015399 458.580 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 2.0727 2.114402 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 17602.31 17602.31 1.0000 0.84371543 0.711732 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.15397700 60.00 32.22 27.78 0.000 17602.31 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00756770 21.00 0.00756770 48.1961 13906.08 0.00 17690.82 17690.82 0.84371543 16.60 13.15 0.00800000 36934.7 37.16 20.33 0.00800000 57902.5
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3318.110 -999.000 0.305501 0.00009490 -999.000 -999.0000 1.00000 1.00000 1020.7042 1004.8586 1.1854 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.305501 0.36215304   4197.9300 999.8980 18.93321942 15.03 6.70 8.33 662071.15 0.5012 0.501162 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 unknown unknown unknown 7/21 17:30:00 Sensible 3318.11 3291.17 1.0000 0.36215304 0.305501 21.69 15.43 0.00853396 43484.4 12.80 11.96 0.00850000 34322.2 0.09488607 6.70 15.03 8.33 0.000 3318.11 25.46 0.00700420 15.45 0.00000000 0.0000 21.11 0.00853396 21.11 0.00853396 53.8971 3071.91 0.00 3371.46 3371.46 0.36215304 21.69 15.59 0.00853396 43484.4 12.57 12.04 0.00853396 34174.9
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 2902.678 2902.678 0.127109 0.00002539 82.945 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.305501 0.36215304   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 0.3418 0.348672 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2902.68 2902.68 1.0000 0.15068018 0.127109 21.11 14.35 0.00757382 40449.6 40.00 21.00 0.00800000 60796.0 0.02539130 60.00 32.22 27.78 0.000 2902.68 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00757382 21.11 0.00757382 47.9128 2902.68 0.00 3129.06 3129.06 0.15068018 16.60 12.73 0.00757382 35855.7 36.98 19.95 0.00757382 56622.0
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2955.960 -999.000 0.271862 0.00008454 -999.000 -999.0000 1.00000 1.00000 1020.7115 1004.8586 1.1854 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.271862 0.32227561   4197.9300 999.8980 18.93321942 15.03 6.70 8.33 662071.15 0.4465 0.446463 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown unknown unknown 7/21 18:00:00 Sensible 2955.96 2929.21 1.0000 0.32227561 0.271862 21.69 15.43 0.00853789 43494.3 12.80 11.96 0.00850000 34322.2 0.08452987 6.70 15.03 8.33 0.000 2955.96 24.95 0.00700344 15.26 0.00000000 0.0000 21.11 0.00853789 21.11 0.00853789 53.9216 2733.65 0.00 3003.44 3003.44 0.32227561 21.69 15.59 0.00853789 43494.3 12.56 12.04 0.00853789 34174.9
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2900.223 2900.223 0.127002 0.00002537 82.875 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.271862 0.32227561   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 0.3415 0.348377 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2900.22 2900.22 1.0000 0.15055276 0.127002 21.11 14.35 0.00757351 40448.8 40.00 21.00 0.00800000 60796.0 0.02536983 60.00 32.22 27.78 0.000 2900.22 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00757351 21.11 0.00757351 47.9108 2900.22 0.00 3126.42 3126.42 0.15055276 16.60 12.73 0.00757351 35854.9 36.98 19.95 0.00757351 56621.2
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 20154.488 -999.000 1.837050 0.00057641 -999.000 -999.0000 1.00000 1.00000 1020.7722 1004.8586 1.1854 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.837050 2.17771181   4197.9300 999.8980 18.93321942 15.03 6.70 8.33 662071.15 3.0442 3.044101 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown unknown unknown 7/21 14:10:00 Sensible 20154.49 19817.50 1.0000 2.17771181 1.837050 21.69 15.46 0.00857055 43577.1 12.80 11.96 0.00850000 34322.2 0.57634624 6.70 15.03 8.33 0.000 20154.49 27.40 0.00700714 16.15 0.00000000 0.0000 21.11 0.00857055 21.11 0.00857055 54.1258 18471.59 0.00 20478.89 20478.89 2.17771181 21.69 15.62 0.00857055 43577.1 12.48 12.04 0.00857055 34173.2
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 13914.301 13914.301 0.609327 0.00012173 397.605 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.837050 2.17771181   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 1.6384 1.671395 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 13914.30 13914.30 1.0000 0.72231993 0.609327 21.11 14.36 0.00758975 40490.5 40.00 21.00 0.00800000 60796.0 0.12171596 60.00 32.22 27.78 0.000 13914.30 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00758975 21.11 0.00758975 48.0110 13914.30 0.00 14999.63 14999.63 0.72231993 16.60 12.75 0.00758975 35896.1 36.98 19.96 0.00758975 56662.0
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 18919.189 18919.189 1.781414 0.00016551 417.188 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 2.2278 2.272586 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 18919.19 18919.19 1.0000 2.11175804 1.781414 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.16549643 60.00 32.22 27.78 0.000 18919.19 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00768122 21.00 0.00768122 48.9117 9666.90 0.00 19022.28 19022.28 2.11175804 16.60 13.15 0.00800000 36934.7 25.43 16.47 0.00800000 45942.5
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 19083.827 19083.827 1.780805 0.00016695 421.250 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 2.2471 2.292363 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 19083.83 19083.83 1.0000 2.11103580 1.780805 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.16693662 60.00 32.22 27.78 0.000 19083.83 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00768645 21.00 0.00768645 48.9445 9834.61 0.00 19187.77 19187.77 2.11103580 16.60 13.15 0.00800000 36934.7 25.51 16.50 0.00800000 46024.0
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 7752.659 7752.659 0.550083 0.00006782 177.570 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 0.9129 0.931255 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 Sensible 7752.66 7752.66 1.0000 0.65209011 0.550083 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.06781672 60.00 32.22 27.78 0.000 7752.66 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.79 0.00723894 21.00 0.00723894 46.1346 4899.56 0.00 7794.30 7794.30 0.65209011 16.60 13.15 0.00800000 36934.7 28.32 17.47 0.00800000 48887.5
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 12508.548 12508.548 0.444154 0.00010943 341.380 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 1.4729 1.502535 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 12508.55 12508.55 1.0000 0.52651719 0.444154 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.10941907 60.00 32.22 27.78 0.000 12508.55 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00773351 21.00 0.00773351 49.2397 10201.34 0.00 12570.58 12570.58 0.52651719 16.60 13.15 0.00800000 36934.7 40.01 21.19 0.00800000 60809.7
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 393686.749 -999.000 22.398229 0.01125939 -999.000 -999.0000 1.00000 1.00000 1020.6899 1004.8586 1.1854 VAV WITH REHEAT FAN Fan:VariableVolume 22.398229 26.55174082   4197.9300 999.8980 18.93321942 15.03 6.70 8.33 662071.15 59.4629 59.462907 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 Sensible 393686.75 391856.94 1.0000 26.55174082 22.398229 25.41 16.74 0.00852627 47259.3 10.95 10.95 0.00850000 32432.2 11.25824261 6.70 15.03 8.33 50186.337 343500.41 27.40 0.00700714 16.15 9.32920000 41.6515 23.99 0.00961069 23.99 0.00958523 50.7307 303286.48 0.00 398973.93 380437.75 26.55174082 25.41 16.91 0.00852627 47259.3 11.37 11.25 0.00824947 32233.0
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 469047.494 469047.494 6.719469 0.00410343 6161.674 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 VAV WITH REHEAT FAN Fan:VariableVolume 22.398229 26.55174082   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 55.2308 56.342309 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 469047.49 469047.49 1.0000 7.96552225 6.719469 -41.90 -41.90 0.00006450 -41946.5 16.70 13.04 0.00800000 37036.7 4.10301350 60.00 32.22 27.78 0.000 469047.49 -41.90 0.00006450 -41.90 9.32920000 138.8384 20.98 0.00759042 21.00 0.00754875 48.0781 98659.87 0.00 300789.46 300789.46 7.96552225 2.80 -4.37 0.00006450 2975.2 40.38 14.79 0.00006450 40736.6
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 38332.296 -999.000 2.051317 0.00109630 -999.000 -999.0000 1.00000 1.00000 1017.8659 1004.8586 1.1854 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.43162656   4197.9300 999.8980 18.93321942 15.03 6.70 8.33 662071.15 5.7898 5.789755 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 Sensible 38332.30 38332.30 1.0000 2.43171206 2.051317 27.40 16.15 0.00700714 45414.0 11.91 10.04 0.00700714 29650.5 1.09618699 6.70 15.03 8.33 2195.006 36137.29 27.40 0.00700714 16.15 2.05124512 99.9965 21.11 0.00857181 21.11 0.00857689 54.1644 192161.44 0.00 38875.86 38875.86 2.43171206 27.40 16.31 0.00700714 45414.0 11.69 10.08 0.00700714 29426.9
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 42957.200 42957.200 0.615395 0.00037581 564.310 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.43162656   4197.9300 999.8980 7.28229564 54.44 82.22 27.78 849250.36 5.0582 5.160049 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 42957.20 42957.20 1.0000 0.72951362 0.615395 -41.90 -41.90 0.00006450 -41946.5 16.70 13.04 0.00800000 37036.7 0.37576999 60.00 32.22 27.78 0.000 42957.20 -41.90 0.00006450 -41.90 2.05124512 333.3216 21.11 0.00751206 21.11 0.00751009 47.5109 163400.85 0.00 27547.47 27547.47 0.72951362 2.80 -4.37 0.00006450 2975.2 40.38 14.79 0.00006450 40736.6



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 22.40 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 249.33 8718.67 249.33
RETAIL_1_FLR_1 4642.17 6824.67 3615.50
RETAIL_2_FLR_1 1744.50 8376.33 1664.33
MECH_FLR_1 3140.83 7490.83 3121.67
STORAGE_FLR_1 3774.33 8760.00 3774.33
LAUNDRY_FLR_1 8645.83 2622.17 2622.17
CAFE_FLR_1 3251.17 7408.33 2507.67
LOBBY_FLR_1 1516.83 7568.00 1121.83
ROOM_1_FLR_3 4442.00 8509.00 4432.33
ROOM_2_FLR_3 5069.00 8317.33 4804.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4205.33 8722.67 4204.00
ROOM_5_FLR_3 4214.17 8322.33 4184.17
ROOM_6_FLR_3 4699.50 8245.33 4556.17
CORRIDOR_FLR_3 3228.67 8654.17 3228.67
ROOM_1_FLR_6 4748.00 8455.83 4724.00
ROOM_2_FLR_6 5370.33 8304.33 5109.17
ROOM_3_MULT9_FLR_6 4023.67 8247.17 3925.67
BANQUET_FLR_6 1467.50 7491.33 857.17
DINING_FLR_6 1363.33 6852.67 355.17
KITCHEN_FLR_6 8496.33 5607.17 5571.17
CORRIDOR_FLR_6 3976.50 7016.67 3613.17
Facility 8760.00 8760.00 7936.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 86.17 0.00 86.17 0.00
RETAIL_2_FLR_1 37.67 0.00 37.67 0.00
MECH_FLR_1 32.50 0.00 32.50 0.00
STORAGE_FLR_1 81.67 0.00 81.67 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 52.67 0.00 52.67 0.00
LOBBY_FLR_1 25.50 0.00 25.50 0.00
ROOM_1_FLR_3 54.00 2.50 54.00 2.50
ROOM_2_FLR_3 74.17 6.83 74.17 6.83
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 176.00 19.17 176.00 19.17
ROOM_5_FLR_3 62.33 4.33 62.33 4.33
ROOM_6_FLR_3 77.83 14.83 77.83 14.83
CORRIDOR_FLR_3 47.83 0.00 47.83 0.00
ROOM_1_FLR_6 74.67 3.33 74.67 3.33
ROOM_2_FLR_6 102.83 11.00 102.83 11.00
ROOM_3_MULT9_FLR_6 29.50 2.33 29.50 2.33
BANQUET_FLR_6 17.67 0.00 17.67 0.00
DINING_FLR_6 7.50 0.00 7.50 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 74.50 0.00 74.50 0.00
Facility 213.50 37.17 213.50 37.17
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.79 106.50 4826.41 0.686 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 1.362 0.145 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 1.152 0.048 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.095 0.054 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.593 0.054 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 14.469 0.156 0.000 0.000
CAFE_FLR_1 82.56 142.30 748.35 3.510 0.114 0.000 0.000
LOBBY_FLR_1 245.09 422.44 5183.56 1.417 0.047 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.343 0.188 0.000 0.031
ROOM_2_FLR_3 0.95 1.50 118.93 0.343 0.188 0.000 0.027
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.390 0.083 0.000 0.055
ROOM_5_FLR_3 0.95 1.50 118.94 0.343 0.188 0.000 0.031
ROOM_6_FLR_3 0.95 1.50 118.93 0.343 0.188 0.000 0.035
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.386 0.023 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.343 0.188 0.000 0.037
ROOM_2_FLR_6 0.95 1.50 118.93 0.343 0.188 0.000 0.028
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.390 0.153 0.000 0.058
BANQUET_FLR_6 144.99 249.90 1010.89 4.551 0.054 0.000 0.000
DINING_FLR_6 144.99 249.90 1010.89 4.564 0.054 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 14.504 0.157 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.451 0.038 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.79 106.50 4826.41 0.552 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 0.941 0.002 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 0.939 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.006 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.479 0.001 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 2.978 0.002 0.000 0.000
CAFE_FLR_1 82.56 142.30 748.35 2.830 0.002 0.000 0.000
LOBBY_FLR_1 245.09 422.44 5183.56 1.152 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.000 0.003 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.000 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.000 0.003 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.313 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.000 0.003 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.000 0.002 0.000 0.000
BANQUET_FLR_6 144.99 249.90 1010.89 3.685 0.001 0.000 0.000
DINING_FLR_6 144.99 249.90 1010.89 3.708 0.001 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 4.148 0.002 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.315 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.79 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.56 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 245.09 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.99 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.99 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.25 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 28424984.44 0.00 28424984.44 0.00 28424984.44 26946214.98 6170.48 140.13 2449.39 0.00
RETAIL_1_FLR_1 3108025.73 0.00 3108025.73 331381.90 3439407.63 2498216.28 5621.61 103.04 3035.35 0.00
RETAIL_2_FLR_1 3048110.08 0.00 3048110.08 127913.83 3176023.92 2892943.94 6198.02 124.21 2437.78 0.00
MECH_FLR_1 529963.06 0.00 529963.06 302312.31 832275.37 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1918650.33 0.00 1918650.33 174417.55 2093067.88 1821682.01 6197.21 124.59 2438.19 0.00
LAUNDRY_FLR_1 38236832.75 0.00 38236832.75 412792.02 38649624.76 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 22572973.55 0.00 22572973.55 732538.45 23305512.00 21330615.53 6154.79 129.93 2475.28 0.00
LOBBY_FLR_1 63045529.46 0.00 63045529.46 2093029.67 65138559.13 59728886.00 6200.29 121.48 2438.23 0.00
ROOM_1_FLR_3 1406076.84 32123.72 1438200.56 192345.67 1630546.23 1946875.62 2433.33 5953.83 372.83 0.00
ROOM_2_FLR_3 1405912.09 26939.40 1432851.49 192330.99 1625182.49 1946647.51 2433.33 6063.58 263.08 0.00
ROOM_3_MULT19_FLR_3 1099911.97 0.00 1099911.97 53666.60 1153578.57 26397887.27 8395.00 365.00 0.00 365.00
ROOM_4_MULT19_FLR_3 19070354.14 35105.57 19105459.70 53681.27 19159140.98 26405105.73 2433.33 5962.04 364.63 0.00
ROOM_5_FLR_3 1406076.84 32130.98 1438207.82 192345.67 1630553.48 1946875.62 2433.33 5953.86 372.81 0.00
ROOM_6_FLR_3 1405912.09 35735.01 1441647.10 192330.99 1633978.10 1946647.51 2433.33 5959.00 367.67 0.00
CORRIDOR_FLR_3 15761920.08 0.00 15761920.08 232584.61 15994504.69 14972100.18 6200.71 122.48 2436.81 0.00
ROOM_1_FLR_6 351519.21 37610.25 389129.45 192388.03 581517.48 486718.90 2322.96 5956.00 481.04 0.00
ROOM_2_FLR_6 351478.02 28370.50 379848.52 192373.35 572221.87 486661.88 2353.17 6091.18 315.65 0.00
ROOM_3_MULT9_FLR_6 2258331.41 37587.69 2295919.11 98432.45 2394351.55 3126920.42 2433.33 5953.50 373.17 0.00
BANQUET_FLR_6 39504601.53 0.00 39504601.53 469763.21 39974364.75 37458366.31 6197.49 124.37 2438.14 0.00
DINING_FLR_6 39580367.41 0.00 39580367.41 469763.21 40050130.62 37458366.31 6194.21 121.73 2444.06 0.00
KITCHEN_FLR_6 38947420.13 0.00 38947420.13 420546.99 39367967.12 11584760.86 39.81 54.33 8665.86 0.00
CORRIDOR_FLR_6 4859397.73 0.00 4859397.73 411607.93 5271005.65 3961413.96 5544.85 95.69 3119.46 0.00
Total Facility 0.19E+10 3580009.69 0.19E+10 19382910.50 0.19E+10 0.43E+10 8760.00 6491.29 8760.00 365.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 0.9014 0.0000 0.9014 0.0000 0.9014 0.8545 6170.48 140.13 2449.39
RETAIL_1_FLR_1 0.0986 0.0000 0.0986 0.0105 0.1091 0.0792 5621.61 103.04 3035.35
RETAIL_2_FLR_1 0.0967 0.0000 0.0967 0.0041 0.1007 0.0917 6198.02 124.21 2437.78
MECH_FLR_1 0.0168 0.0000 0.0168 0.0096 0.0264 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0608 0.0000 0.0608 0.0055 0.0664 0.0578 6197.21 124.59 2438.19
LAUNDRY_FLR_1 1.2125 0.0000 1.2125 0.0131 1.2256 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.7158 0.0000 0.7158 0.0232 0.7390 0.6764 6154.79 129.93 2475.28
LOBBY_FLR_1 1.9992 0.0000 1.9992 0.0664 2.0655 1.8940 6200.29 121.48 2438.23
ROOM_1_FLR_3 0.0446 0.0010 0.0456 0.0061 0.0517 0.0617 2433.33 5953.83 372.83
ROOM_2_FLR_3 0.0446 0.0009 0.0454 0.0061 0.0515 0.0617 2433.33 6063.58 263.08
ROOM_4_MULT19_FLR_3 0.6047 0.0011 0.6058 0.0017 0.6075 0.8373 2433.33 5962.04 364.63
ROOM_5_FLR_3 0.0446 0.0010 0.0456 0.0061 0.0517 0.0617 2433.33 5953.86 372.81
ROOM_6_FLR_3 0.0446 0.0011 0.0457 0.0061 0.0518 0.0617 2433.33 5959.00 367.67
CORRIDOR_FLR_3 0.4998 0.0000 0.4998 0.0074 0.5072 0.4748 6200.71 122.48 2436.81
ROOM_1_FLR_6 0.0111 0.0012 0.0123 0.0061 0.0184 0.0154 2322.96 5956.00 481.04
ROOM_2_FLR_6 0.0111 0.0009 0.0120 0.0061 0.0181 0.0154 2353.17 6091.18 315.65
ROOM_3_MULT9_FLR_6 0.0716 0.0012 0.0728 0.0031 0.0759 0.0992 2433.33 5953.50 373.17
BANQUET_FLR_6 1.2527 0.0000 1.2527 0.0149 1.2676 1.1878 6197.49 124.37 2438.14
DINING_FLR_6 1.2551 0.0000 1.2551 0.0149 1.2700 1.1878 6194.21 121.73 2444.06
KITCHEN_FLR_6 1.2350 0.0000 1.2350 0.0133 1.2484 0.3674 39.81 54.33 8665.86
CORRIDOR_FLR_6 0.1541 0.0000 0.1541 0.0131 0.1671 0.1256 5544.85 95.69 3119.46
Total Facility 58.3364 0.1135 58.4499 0.4853 58.9352 73.9670 8760.00 6491.29 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.42E+09 0.00 0.42E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 40409237.68 265603.13 40674840.81 64690340.46 8756.31 3.52 0.17 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 13.3477 0.0000 13.3477 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 1.2814 0.0084 1.2898 2.0513 8756.31 3.52 0.17


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 8.00 4054.30 0.00 0.00 0.00 4697.70 0.00 0.00 0.00
FLR_3_DOAS 0.00 0.00 0.00 0.00 6691.67 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 15.0260 15.5699 0.0000 0.0000 0.0000 11.4328 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 0.0000 0.0000 0.0000 1.6776 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1340
Defaulted Fields 1181
Fields with Defaults 4002
Autosized Fields 349
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 4242.52 55300.31 27-MAY-03:20 301443.71 29-JUN-19:10
Electricity:Building 2200.64 28601.08 10-JUN-05:00 132137.22 02-JAN-20:10
Electricity:Zone:BASEMENT 266.04 3144.96 02-JAN-02:10 19685.67 02-JAN-20:10
Electricity:SpaceType:GENERAL 2193.54 28459.93 10-JUN-05:00 131895.89 02-JAN-20:10
InteriorLights:Electricity 545.09 4566.26 10-JUN-05:00 45764.37 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 122.93 1117.06 02-JAN-02:10 10053.14 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 545.09 4566.26 10-JUN-05:00 45764.37 02-JAN-20:10
LightsWired:InteriorLights:Electricity 545.09 4566.26 10-JUN-05:00 45764.37 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 122.93 1117.06 02-JAN-02:10 10053.14 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 545.09 4566.26 10-JUN-05:00 45764.37 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 16.45 201.26 02-JAN-02:10 1197.92 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 6.26 56.92 02-JAN-02:10 512.31 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 6.26 56.92 02-JAN-02:10 512.31 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 19.05 233.06 02-JAN-02:10 1387.19 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 7.25 65.92 02-JAN-02:10 593.26 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 7.25 65.92 02-JAN-02:10 593.26 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 20.84 252.75 02-JAN-02:10 1523.62 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 8.37 76.02 02-JAN-02:10 684.18 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 8.37 76.02 02-JAN-02:10 684.18 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 5.91 71.95 02-JAN-02:10 430.87 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.31 20.97 02-JAN-02:10 188.71 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.31 20.97 02-JAN-02:10 188.71 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.84 1007.22 02-JAN-02:10 4973.49 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.90 44.52 02-JAN-02:10 400.68 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.90 44.52 02-JAN-02:10 400.68 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 27.15 241.68 06-MAY-05:00 2538.73 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 12.81 38.46 06-MAY-05:00 1573.46 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 12.81 38.46 06-MAY-05:00 1573.46 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 241.14 2874.33 10-JUN-05:00 18013.24 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 92.14 762.92 10-JUN-05:00 7984.04 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 92.14 762.92 10-JUN-05:00 7984.04 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 15.40 220.79 01-JAN-02:10 1160.40 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 15.40 220.76 01-JAN-02:10 1160.26 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 253.77 3619.58 02-JAN-10:10 20179.99 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 58.78 497.64 01-JAN-02:10 4523.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 58.78 497.64 01-JAN-02:10 4523.96 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 253.84 3620.57 02-JAN-10:10 20185.51 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 58.79 497.77 01-JAN-02:10 4525.19 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 58.79 497.77 01-JAN-02:10 4525.19 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 15.40 220.79 01-JAN-02:10 1160.40 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 15.40 220.76 01-JAN-02:10 1160.26 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 56.74 515.56 02-JAN-02:10 4640.01 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 56.74 515.56 02-JAN-02:10 4640.01 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 56.74 515.56 02-JAN-02:10 4640.01 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 3.85 55.20 01-JAN-02:10 290.10 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.23 10.42 01-JAN-02:10 94.72 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.23 10.42 01-JAN-02:10 94.72 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 3.85 55.19 01-JAN-02:10 290.07 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.23 10.42 01-JAN-02:10 94.71 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.23 10.42 01-JAN-02:10 94.71 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 30.06 428.75 02-JAN-10:10 2390.39 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 6.96 58.95 01-JAN-02:10 535.88 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 6.96 58.95 01-JAN-02:10 535.88 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 204.03 2433.51 06-MAY-04:50 9511.03 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 28.17 184.21 06-MAY-04:50 2763.12 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 28.17 184.21 06-MAY-04:50 2763.12 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 204.03 2433.51 06-MAY-04:50 9511.03 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 28.17 184.21 06-MAY-04:50 2763.12 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 28.17 184.21 06-MAY-04:50 2763.12 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 444.45 5944.83 02-JAN-02:10 18636.09 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.34 121.20 02-JAN-02:10 1090.83 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.34 121.20 02-JAN-02:10 1090.83 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 15.01 136.41 02-JAN-02:10 1227.68 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 15.01 136.41 02-JAN-02:10 1227.68 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 15.01 136.41 02-JAN-02:10 1227.68 02-JAN-20:10
InteriorEquipment:Electricity 1648.46 23893.67 02-JAN-02:10 88863.15 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1648.46 23893.67 02-JAN-02:10 88863.15 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 424.02 5682.48 01-JAN-00:10 16179.04 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
Refrigeration:Electricity 43.74 732.79 12-JAN-23:30 2786.65 16-JUL-10:20
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 507.35 2112.54 15-APR-01:10 123275.95 29-JUL-15:30
LowTempRefrigeration:Refrigeration:Electricity 15.79 0.00 01-JAN-11:10 1309.03 22-JUL-10:50
MedTempRefrigeration:Refrigeration:Electricity 20.86 598.29 12-JAN-05:00 714.07 25-JUL-13:10
Fans:Electricity 560.67 11931.39 19-SEP-03:00 31412.10 22-JUN-22:00
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 723.14 13832.27 19-SEP-03:00 39377.03 13-JAN-19:20
ExteriorEquipment:Electricity 640.54 9443.81 17-JUN-03:00 39153.73 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 21.51 378.98 10-JUN-05:00 1274.03 02-JAN-08:00
ElectricityPurchased:Facility 4242.52 55300.31 27-MAY-03:20 301443.71 29-JUN-19:10
ElectricityPurchased:Plant 4242.52 55300.31 27-MAY-03:20 301443.71 29-JUN-19:10
Cogeneration:ElectricityPurchased 4242.52 55300.31 27-MAY-03:20 301443.71 29-JUN-19:10
General:Cogeneration:ElectricityPurchased 4242.52 55300.31 27-MAY-03:20 301443.71 29-JUN-19:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 4242.52 55300.31 27-MAY-03:20 301443.71 29-JUN-19:10
ElectricityNet:Plant 4242.52 55300.31 27-MAY-03:20 301443.71 29-JUN-19:10
Cogeneration:ElectricityNet 4242.52 55300.31 27-MAY-03:20 301443.71 29-JUN-19:10
General:Cogeneration:ElectricityNet 4242.52 55300.31 27-MAY-03:20 301443.71 29-JUN-19:10
General:Fans:Electricity 560.67 11931.39 19-SEP-03:00 31412.10 22-JUN-22:00
ExteriorLights:Electricity 192.37 0.00 01-JAN-11:20 12338.45 01-JAN-00:10
General:ExteriorLights:Electricity 192.37 0.00 01-JAN-11:20 12338.45 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
HeatRecovery:Electricity 140.95 0.00 07-FEB-11:00 8265.52 01-JAN-00:10
General:HeatRecovery:Electricity 140.95 0.00 07-FEB-11:00 8265.52 01-JAN-00:10
WaterSystems:Electricity 90.74 1086.56 06-APR-01:00 4738.77 26-JAN-19:10
Water Heater:WaterSystems:Electricity 90.74 1086.56 06-APR-01:00 4738.77 26-JAN-19:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 321.96 0.00 01-JAN-00:20 114978.03 29-JUL-15:30
General:Cooling:Electricity 321.96 0.00 01-JAN-00:20 114978.03 29-JUL-15:30
Pumps:Electricity 57.99 47.91 05-JUL-14:10 4641.78 21-JUL-15:20
General:Pumps:Electricity 57.99 47.91 05-JUL-14:10 4641.78 21-JUL-15:20
WIRED_LTG_ELECTRICITY 19.19 0.00 01-JAN-00:10 1610.91 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 9032.66 29270.80 08-MAY-01:10 1136619.19 12-JAN-21:50
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 7243.82 15908.90 18-JUL-10:00 1061495.44 12-JAN-21:50
WaterSystems:NaturalGas 3628.21 15908.90 21-MAR-15:20 312595.80 03-MAR-21:30
Water Heater:WaterSystems:NaturalGas 3628.21 15908.90 21-MAR-15:20 312595.80 03-MAR-21:30
Heating:NaturalGas 3615.61 0.00 17-APR-20:10 783717.68 12-JAN-10:20
Boiler:Heating:NaturalGas 3615.61 0.00 17-APR-20:10 783717.68 12-JAN-10:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 985.26 0.00 01-JAN-00:20 399956.06 29-JUL-18:10
PlantLoopCoolingDemand:HVAC 985.26 0.00 01-JAN-00:20 399956.06 29-JUL-18:10
CoolingCoils:PlantLoopCoolingDemand 985.26 0.00 01-JAN-00:20 399956.06 29-JUL-18:10


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 09-MAY-20:10
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 09-MAY-20:10
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 09-MAY-20:10
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 09-MAY-20:10
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 09-MAY-20:10
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 09-MAY-20:10
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-08:00
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-08:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 18321.89 133633.26 06-OCT-13:50 1695593.12 29-JUL-18:10
EnergyTransfer:Building 4932.38 76706.45 05-MAR-15:00 328183.58 12-JUL-18:20
EnergyTransfer:Zone:KITCHEN_FLR_6 662.16 7739.05 26-FEB-04:00 36204.52 22-JUL-10:50
Refrigeration:EnergyTransfer 180.12 3939.28 12-JAN-03:20 10327.07 25-JUL-07:20
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 90.06 1969.64 12-JAN-03:20 5163.54 25-JUL-07:20
General:Refrigeration:EnergyTransfer 90.06 1969.64 12-JAN-03:20 5163.54 25-JUL-07:20
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 90.06 1969.64 12-JAN-03:20 5163.54 25-JUL-07:20
EnergyTransfer:Plant 6233.72 22232.52 20-SEP-15:10 961136.78 29-JUL-18:10
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.52 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 68.54 1733.07 12-JAN-05:00 2541.24 25-JUL-13:10
EnergyTransfer:Zone:BASEMENT 348.23 6035.70 01-MAR-15:00 18811.57 12-JAN-21:00
Heating:EnergyTransfer 783.48 0.00 18-MAR-17:10 144975.79 13-JAN-16:30
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 783.48 0.00 18-MAR-17:10 144975.79 13-JAN-16:30
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 4058.85 42066.56 13-JAN-15:00 325486.44 11-JUL-18:20
Cooling:EnergyTransfer:Zone:BASEMENT 348.23 6035.70 01-MAR-15:00 18811.57 12-JAN-21:00
General:Cooling:EnergyTransfer 4058.85 42066.56 13-JAN-15:00 325486.44 11-JUL-18:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 348.23 6035.70 01-MAR-15:00 18811.57 12-JAN-21:00
EnergyTransfer:Zone:RETAIL_1_FLR_1 37.40 0.00 06-APR-06:30 4950.54 25-AUG-13:30
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 13.14 0.00 23-JAN-12:00 2589.64 13-JAN-16:10
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 13.14 0.00 23-JAN-12:00 2589.64 13-JAN-16:10
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 24.26 0.00 01-JAN-00:10 4950.54 25-AUG-13:30
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 24.26 0.00 01-JAN-00:10 4950.54 25-AUG-13:30
EnergyTransfer:Zone:RETAIL_2_FLR_1 28.86 0.00 04-DEC-15:50 1727.17 21-JUN-21:00
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.04 0.00 01-JAN-00:10 439.82 13-JAN-16:00
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.04 0.00 01-JAN-00:10 439.82 13-JAN-16:00
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 28.82 0.00 01-JAN-14:20 1727.17 21-JUN-21:00
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 28.82 0.00 01-JAN-14:20 1727.17 21-JUN-21:00
EnergyTransfer:Zone:MECH_FLR_1 9.62 0.03 08-FEB-05:50 1335.82 21-JUL-20:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 4.92 0.00 02-JAN-21:00 1277.24 13-JAN-16:10
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 4.92 0.00 02-JAN-21:00 1277.24 13-JAN-16:10
Cooling:EnergyTransfer:Zone:MECH_FLR_1 4.70 0.00 01-JAN-00:10 1335.82 21-JUL-20:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 4.70 0.00 01-JAN-00:10 1335.82 21-JUL-20:00
EnergyTransfer:Zone:STORAGE_FLR_1 16.18 0.30 05-APR-14:50 986.47 13-JAN-16:10
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 6.18 0.00 07-FEB-20:20 986.47 13-JAN-16:10
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 6.18 0.00 07-FEB-20:20 986.47 13-JAN-16:10
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 10.00 0.00 01-JAN-00:10 971.23 23-JUL-10:40
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 10.00 0.00 01-JAN-00:10 971.23 23-JUL-10:40
EnergyTransfer:Zone:LAUNDRY_FLR_1 569.14 6793.92 13-JAN-05:00 39145.83 21-JUL-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 569.14 6793.92 13-JAN-05:00 39145.83 21-JUL-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 569.14 6793.92 13-JAN-05:00 39145.83 21-JUL-20:00
EnergyTransfer:Zone:CAFE_FLR_1 200.76 0.68 17-NOV-07:10 15671.27 25-AUG-14:10
Heating:EnergyTransfer:Zone:CAFE_FLR_1 3.04 0.00 01-JAN-00:10 3954.95 13-JAN-15:00
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 3.04 0.00 01-JAN-00:10 3954.95 13-JAN-15:00
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 197.72 0.00 01-JAN-11:10 15671.27 25-AUG-14:10
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 197.72 0.00 01-JAN-11:10 15671.27 25-AUG-14:10
EnergyTransfer:Zone:LOBBY_FLR_1 684.09 2.35 03-DEC-15:10 37197.75 11-AUG-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.05 0.00 01-JAN-00:10 4274.50 13-JAN-14:40
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.05 0.00 01-JAN-00:10 4274.50 13-JAN-14:40
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 684.04 0.00 13-JAN-10:20 37197.75 11-AUG-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 684.04 0.00 13-JAN-10:20 37197.75 11-AUG-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 86.11 0.00 02-JAN-08:00 11755.18 16-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 56.33 0.00 02-JAN-08:00 8680.74 13-JAN-16:30
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 56.33 0.00 02-JAN-08:00 8680.74 13-JAN-16:30
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 29.78 0.00 01-JAN-00:10 11755.18 16-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 29.78 0.00 01-JAN-00:10 11755.18 16-JUN-18:10
EnergyTransfer:Zone:ROOM_2_FLR_3 80.92 0.00 02-JAN-08:00 12246.54 06-JUL-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 61.92 0.00 02-JAN-08:00 8470.83 13-JAN-16:30
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 61.92 0.00 02-JAN-08:00 8470.83 13-JAN-16:30
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 19.00 0.00 01-JAN-00:10 12246.54 06-JUL-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 19.00 0.00 01-JAN-00:10 12246.54 06-JUL-18:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 356.69 0.00 22-JAN-08:20 61051.15 25-AUG-13:30
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 142.47 0.00 22-JAN-08:20 35054.39 12-JAN-04:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 142.47 0.00 22-JAN-08:20 35054.39 12-JAN-04:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 214.22 0.00 01-JAN-00:10 61051.15 25-AUG-13:30
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 214.22 0.00 01-JAN-00:10 61051.15 25-AUG-13:30
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 406.82 0.00 01-JAN-08:00 66733.18 10-JUL-22:10
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 212.63 0.00 01-JAN-08:00 45213.46 13-JAN-16:30
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 212.63 0.00 01-JAN-08:00 45213.46 13-JAN-16:30
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 194.19 0.00 01-JAN-00:10 66733.18 10-JUL-22:10
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 194.19 0.00 01-JAN-00:10 66733.18 10-JUL-22:10
EnergyTransfer:Zone:ROOM_5_FLR_3 89.53 0.00 02-JAN-08:00 12006.16 22-JUL-08:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 54.03 0.00 02-JAN-08:00 8546.59 13-JAN-16:30
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 54.03 0.00 02-JAN-08:00 8546.59 13-JAN-16:30
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 35.50 0.00 01-JAN-00:10 12006.16 22-JUL-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 35.50 0.00 01-JAN-00:10 12006.16 22-JUL-08:10
EnergyTransfer:Zone:ROOM_6_FLR_3 84.08 0.00 02-JAN-08:00 12732.49 11-JUL-09:00
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 59.17 0.00 02-JAN-08:00 8342.86 13-JAN-16:30
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 59.17 0.00 02-JAN-08:00 8342.86 13-JAN-16:30
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 24.91 0.00 01-JAN-00:10 12732.49 11-JUL-09:00
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 24.91 0.00 01-JAN-00:10 12732.49 11-JUL-09:00
EnergyTransfer:Zone:CORRIDOR_FLR_3 137.04 0.30 12-FEB-11:40 9206.10 22-JUL-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 30.21 0.00 04-JAN-22:10 7583.94 13-JAN-16:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 30.21 0.00 04-JAN-22:10 7583.94 13-JAN-16:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 106.82 0.00 01-JAN-00:10 9206.10 22-JUL-10:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 106.82 0.00 01-JAN-00:10 9206.10 22-JUL-10:40
EnergyTransfer:Zone:ROOM_1_FLR_6 26.44 0.00 19-JAN-08:00 3137.05 10-AUG-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 19.33 0.00 19-JAN-08:00 2593.88 13-JAN-16:30
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 19.33 0.00 19-JAN-08:00 2593.88 13-JAN-16:30
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 7.10 0.00 01-JAN-00:10 3137.05 10-AUG-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 7.10 0.00 01-JAN-00:10 3137.05 10-AUG-18:10
EnergyTransfer:Zone:ROOM_2_FLR_6 25.56 0.00 19-JAN-08:00 3186.28 06-JUL-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 21.07 0.00 19-JAN-08:00 2516.69 13-JAN-16:30
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 21.07 0.00 19-JAN-08:00 2516.69 13-JAN-16:30
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 4.49 0.00 01-JAN-00:10 3186.28 06-JUL-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 4.49 0.00 01-JAN-00:10 3186.28 06-JUL-18:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 122.88 0.00 01-JAN-08:00 18988.46 20-APR-15:20
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 67.91 0.00 01-JAN-08:00 12993.09 13-JAN-16:30
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 67.91 0.00 01-JAN-08:00 12993.09 13-JAN-16:30
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 54.97 0.00 01-JAN-00:10 18988.46 20-APR-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 54.97 0.00 01-JAN-00:10 18988.46 20-APR-15:20
EnergyTransfer:Zone:BANQUET_FLR_6 431.76 2918.58 13-JAN-13:20 21165.66 11-JUL-21:20
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 431.76 2918.58 13-JAN-13:20 21165.66 11-JUL-21:20
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 431.76 2918.58 13-JAN-13:20 21165.66 11-JUL-21:20
EnergyTransfer:Zone:DINING_FLR_6 459.62 4477.30 13-JAN-12:20 22591.54 11-JUL-21:10
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 459.62 4477.30 13-JAN-12:20 22591.54 11-JUL-21:10
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 459.62 4477.30 13-JAN-12:20 22591.54 11-JUL-21:10
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 572.11 5504.98 30-JAN-04:00 31141.48 22-JUL-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 572.11 5504.98 30-JAN-04:00 31141.48 22-JUL-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 68.51 0.16 27-MAR-22:50 6315.14 23-JUL-13:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 31.03 0.00 02-FEB-22:50 5609.02 13-JAN-16:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 31.03 0.00 02-FEB-22:50 5609.02 13-JAN-16:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 37.48 0.00 01-JAN-00:10 6315.14 23-JUL-13:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 37.48 0.00 01-JAN-00:10 6315.14 23-JUL-13:40
PlantLoopHeatingDemand:Facility 3763.90 12256.92 28-AUG-00:30 701240.02 12-JAN-07:50
PlantLoopHeatingDemand:Plant 971.99 12245.70 07-SEP-00:30 67261.32 16-FEB-07:10
WaterSystems:PlantLoopHeatingDemand 971.99 12245.70 07-SEP-00:30 67261.32 16-FEB-07:10
General:WaterSystems:PlantLoopHeatingDemand 971.99 12245.70 07-SEP-00:30 67261.32 16-FEB-07:10
EnergyTransfer:HVAC 7155.79 0.00 18-AUG-15:10 645664.29 12-JAN-10:20
HeatingCoils:EnergyTransfer 2791.91 0.00 17-APR-20:10 645664.29 12-JAN-10:20
PlantLoopHeatingDemand:HVAC 2791.91 0.00 17-APR-20:10 645664.29 12-JAN-10:20
HeatingCoils:PlantLoopHeatingDemand 2791.91 0.00 17-APR-20:10 645664.29 12-JAN-10:20
CoolingCoils:EnergyTransfer 985.26 0.00 01-JAN-00:20 399956.06 29-JUL-18:10
HeatRecoveryForHeating:EnergyTransfer 3377.71 0.00 03-JAN-07:40 425314.40 07-NOV-06:20
HeatRecoveryForCooling:EnergyTransfer 0.91 0.00 01-JAN-00:10 30863.28 29-JUL-16:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 971.99 12245.70 07-SEP-00:30 67261.32 16-FEB-07:10
WaterUse:WaterSystems:EnergyTransfer 971.99 12245.70 07-SEP-00:30 67261.32 16-FEB-07:10
Boilers:EnergyTransfer 2784.95 0.00 17-APR-20:10 643026.81 12-JAN-10:20
Chillers:EnergyTransfer 1032.38 0.00 01-JAN-00:20 404049.38 29-JUL-18:10
HeatRejection:EnergyTransfer 1354.34 0.00 01-JAN-00:20 515260.49 29-JUL-18:10
General:HeatRejection:EnergyTransfer 1354.34 0.00 01-JAN-00:20 515260.49 29-JUL-18:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -348.229 0.000 0.000 146.307 122.932 143.105 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -64.115
RETAIL_1_FLR_1 0.000 0.000 13.139 -24.261 0.000 0.000 15.359 6.265 10.186 23.450 0.000 0.006 0.000 0.000 -16.465 0.000 -9.626 -18.055
RETAIL_2_FLR_1 0.000 0.000 0.043 -28.816 0.000 0.000 17.799 7.255 11.795 0.000 0.000 0.004 0.000 0.000 0.000 0.000 -3.692 -4.388
MECH_FLR_1 0.000 0.000 4.923 -4.698 0.000 0.000 3.642 8.366 12.471 0.000 0.000 0.006 0.000 0.000 0.000 0.000 -8.946 -15.764
STORAGE_FLR_1 0.000 0.000 6.182 -9.999 0.000 0.000 3.002 2.308 3.598 0.000 0.000 0.010 0.000 0.000 0.000 0.000 -4.920 -0.180
LAUNDRY_FLR_1 0.000 0.000 0.000 -569.140 0.000 0.000 10.551 4.900 658.131 0.000 0.000 0.008 0.000 0.000 0.000 0.000 -12.989 -91.461
CAFE_FLR_1 0.000 0.000 3.043 -197.719 0.000 0.000 203.386 12.811 14.341 66.364 0.000 0.019 0.000 0.000 -45.799 0.000 -21.068 -35.377
LOBBY_FLR_1 0.000 0.000 0.052 -684.040 0.000 0.000 586.681 92.142 148.998 87.058 0.000 0.061 0.000 0.000 -62.201 0.000 -61.195 -107.556
ROOM_1_FLR_3 63.944 -25.518 0.000 -11.875 0.000 0.000 9.795 4.922 10.478 36.279 0.000 0.077 0.000 0.000 -37.783 0.000 -22.014 -28.306
ROOM_2_FLR_3 69.802 -14.621 0.000 -12.265 0.000 0.000 9.687 4.922 10.477 22.699 0.000 0.035 0.000 0.000 -39.944 0.000 -22.335 -28.457
ROOM_3_MULT19_FLR_3 142.965 -204.833 0.043 -9.921 0.000 0.000 0.000 58.777 194.997 274.575 0.000 0.008 0.000 0.000 -199.187 0.000 -117.527 -139.898
ROOM_4_MULT19_FLR_3 306.626 -125.144 0.000 -163.046 0.000 0.000 185.081 58.793 195.050 68.853 0.000 0.269 0.000 0.000 -221.254 0.000 -127.388 -177.841
ROOM_5_FLR_3 61.473 -31.048 0.000 -11.898 0.000 0.000 9.779 4.922 10.478 44.809 0.000 0.078 0.000 0.000 -37.218 0.000 -22.083 -29.293
ROOM_6_FLR_3 66.885 -20.428 0.000 -12.198 0.000 0.000 9.708 4.922 10.477 30.942 0.000 0.035 0.000 0.000 -39.005 0.000 -22.498 -28.840
CORRIDOR_FLR_3 0.000 0.000 30.214 -106.822 0.000 0.000 120.210 56.739 0.000 37.939 0.000 0.024 0.000 0.000 -47.401 0.000 -26.774 -64.129
ROOM_1_FLR_6 21.326 -6.133 0.000 -2.964 0.000 0.000 2.452 1.231 2.620 9.055 0.000 0.020 0.000 0.000 -9.375 0.000 -5.526 -12.705
ROOM_2_FLR_6 23.104 -3.456 0.000 -3.071 0.000 0.000 2.421 1.230 2.619 5.657 0.000 0.009 0.000 0.000 -9.918 0.000 -5.604 -12.991
ROOM_3_MULT9_FLR_6 79.340 -47.212 0.000 -19.186 0.000 0.000 21.966 6.962 23.098 61.493 0.000 0.136 0.000 0.000 -43.102 0.000 -26.247 -57.246
BANQUET_FLR_6 0.000 0.000 0.000 -431.764 0.000 0.000 348.526 28.170 175.857 7.897 0.000 0.021 0.000 0.000 -25.692 0.000 -13.723 -89.292
DINING_FLR_6 0.000 0.000 0.000 -459.624 0.000 0.000 343.086 28.170 175.857 7.718 0.000 0.018 0.000 0.000 -26.184 0.000 -13.865 -55.177
KITCHEN_FLR_6 0.000 0.000 0.000 -572.093 0.000 0.000 27.968 13.339 540.650 22.849 0.000 0.008 0.001 0.000 -16.710 0.000 -13.275 -2.735
CORRIDOR_FLR_6 0.000 0.000 31.029 -37.483 0.000 0.000 31.151 15.012 0.000 18.846 0.000 0.007 0.000 0.000 -21.064 0.000 -12.053 -25.446
Total Facility 835.464 -478.393 88.667 -3721.109 0.000 0.000 2108.557 545.088 2355.282 826.484 0.000 0.860 0.001 0.000 -898.301 0.000 -573.346 -1089.254


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 12-JAN-21:00 0.00 0.00 0.00 -18811.97 0.00 0.00 6150.25 10053.14 9632.53 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -7023.95
RETAIL_1_FLR_1 25-AUG-13:30 0.00 0.00 0.00 -4951.14 0.00 0.00 150.60 142.31 252.59 7149.23 0.00 0.00 0.00 0.00 -0.00 0.00 -26.97 -2716.62
RETAIL_2_FLR_1 21-JUN-21:00 0.00 0.00 0.00 -1727.34 0.00 0.00 697.60 527.34 752.15 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -0.46 -249.30
MECH_FLR_1 21-JUL-20:00 0.00 0.00 0.00 -1336.15 0.00 0.00 129.08 684.18 839.45 0.00 0.00 10.31 0.00 0.00 -0.00 0.00 0.00 -326.86
STORAGE_FLR_1 23-JUL-10:35 0.00 0.00 0.00 -973.80 0.00 0.00 47.70 62.90 101.96 0.00 0.00 0.85 760.38 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 21-JUL-20:00 0.00 0.00 0.00 -39150.87 0.00 0.00 408.79 400.68 44299.38 0.00 0.00 14.05 0.00 0.00 -0.00 0.00 0.00 -5972.04
CAFE_FLR_1 25-AUG-14:10 0.00 0.00 0.00 -15674.10 0.00 0.00 2968.49 96.16 355.63 17690.51 0.00 0.00 0.00 0.00 -0.00 0.00 -28.84 -5407.84
LOBBY_FLR_1 11-AUG-21:10 0.00 0.00 0.00 -37181.54 0.00 0.00 26439.58 5309.23 7389.94 0.00 0.00 0.00 0.00 0.00 -406.68 0.00 -121.41 -1429.13
ROOM_1_FLR_3 16-JUN-18:01 0.00 -14948.85 0.00 -673.69 0.00 0.00 335.50 337.19 484.65 9122.13 0.00 0.00 5715.06 0.00 -0.00 0.00 -372.00 0.00
ROOM_2_FLR_3 09-MAY-20:01 0.00 -15329.91 0.00 -691.44 0.00 0.00 329.27 337.15 726.90 2834.09 0.00 0.00 12110.80 0.00 -0.00 0.00 -316.85 0.00
ROOM_3_MULT19_FLR_3 25-AUG-13:30 0.00 -61051.84 0.00 0.00 0.00 0.00 0.00 1266.71 2352.88 85637.85 0.00 0.00 0.00 0.00 -0.00 0.00 -722.33 -27483.27
ROOM_4_MULT19_FLR_3 10-JUN-21:51 0.00 -75829.49 0.00 -10062.11 0.00 0.00 6134.24 3846.41 6668.31 0.00 0.00 0.00 69855.41 0.00 -11.41 0.00 -601.36 0.00
ROOM_5_FLR_3 13-MAY-08:61 0.00 -14142.23 0.00 -533.46 0.00 0.00 130.71 212.17 653.23 11238.66 0.00 0.00 2664.07 0.00 -0.00 0.00 -223.15 0.00
ROOM_6_FLR_3 22-JUL-08:32 0.00 -13989.06 0.00 -1033.19 0.00 0.00 88.30 212.14 653.15 11153.57 0.00 0.00 3091.76 0.00 -0.00 0.00 -176.68 0.00
CORRIDOR_FLR_3 23-JUL-10:35 0.00 0.00 0.00 -9215.55 0.00 0.00 1807.14 1546.67 0.00 8097.80 0.00 0.00 0.00 0.00 -0.00 0.00 -42.19 -2193.87
ROOM_1_FLR_6 16-JUN-18:01 0.00 -3893.69 0.00 -168.20 0.00 0.00 83.87 84.30 121.16 2270.48 0.00 0.00 1606.21 0.00 -0.00 0.00 -104.13 0.00
ROOM_2_FLR_6 09-MAY-19:42 0.00 -4252.93 0.00 -202.69 0.00 0.00 56.95 94.71 163.29 1053.80 0.00 0.00 3171.00 0.00 -0.00 0.00 -84.12 0.00
ROOM_3_MULT9_FLR_6 20-APR-15:11 0.00 -23502.32 0.00 -852.38 0.00 0.00 529.39 150.05 441.28 13803.79 0.00 0.00 9718.01 0.00 -0.00 0.00 -287.81 0.00
BANQUET_FLR_6 21-JUN-21:03 0.00 0.00 0.00 -21786.22 0.00 0.00 15718.76 1105.25 6747.90 902.06 0.00 0.00 0.00 0.00 -0.00 0.00 -9.33 -2678.41
DINING_FLR_6 11-JUL-21:10 0.00 0.00 0.00 -22592.53 0.00 0.00 15642.30 1105.25 6747.90 1875.21 0.00 0.00 0.00 0.00 -0.00 0.00 -37.24 -2740.90
KITCHEN_FLR_6 22-JUL-10:40 0.00 0.00 0.00 -31151.69 0.00 0.00 464.18 303.01 23951.61 5124.87 0.00 0.00 1315.63 0.00 -0.00 0.00 -7.62 0.00
CORRIDOR_FLR_6 23-JUL-13:40 0.00 0.00 0.00 -6314.42 0.00 0.00 308.46 272.82 0.00 5168.70 0.00 12.74 551.70 0.00 -0.00 0.00 0.00 0.00
Total Facility 29-JUL-18:02 0.00 -162863.98 0.00 -193622.02 0.00 0.00 66211.97 34560.19 113070.18 35945.27 0.00 2180.02 104518.36 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 13-JAN-16:10 0.00 0.00 2589.94 0.00 0.00 0.00 467.29 142.31 252.59 0.00 0.00 0.00 0.00 0.00 -1241.38 0.00 -604.28 -1606.46
RETAIL_2_FLR_1 13-JAN-16:00 0.00 0.00 439.84 0.00 0.00 0.00 312.61 164.79 292.50 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -238.75 -971.00
MECH_FLR_1 13-JAN-16:10 0.00 0.00 1277.28 0.00 0.00 0.00 112.08 190.05 309.27 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -555.62 -1333.06
STORAGE_FLR_1 13-JAN-16:10 0.00 0.00 986.52 0.00 0.00 0.00 88.14 52.42 89.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -317.15 -899.14
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 13-JAN-15:00 0.00 0.00 3955.00 0.00 0.00 0.00 2441.25 433.14 355.63 0.00 0.00 0.00 0.00 0.00 -3694.95 0.00 -1406.58 -2083.49
LOBBY_FLR_1 13-JAN-14:40 0.00 0.00 4274.54 0.00 0.00 0.00 6996.14 2213.80 3694.97 0.00 0.00 0.00 0.00 0.00 -5028.40 0.00 -4122.15 -8028.90
ROOM_1_FLR_3 13-JAN-16:23 8893.64 338.19 0.00 -338.19 0.00 0.00 274.12 106.08 200.18 0.00 0.00 0.00 0.00 0.00 -2812.66 0.00 -1379.26 -5282.10
ROOM_2_FLR_3 12-JAN-17:54 9356.34 0.00 0.00 0.00 0.00 0.00 285.59 106.07 505.67 0.00 0.00 0.00 0.00 0.00 -3729.75 0.00 -1877.32 -4646.60
ROOM_3_MULT19_FLR_3 12-JAN-04:10 35054.31 0.00 0.00 0.00 0.00 0.00 0.00 497.64 3333.24 0.00 0.00 0.00 0.00 0.00 -19419.21 0.00 -9512.98 -9952.99
ROOM_4_MULT19_FLR_3 12-JAN-10:53 48182.68 0.00 0.00 0.00 0.00 0.00 2089.16 1267.05 2353.52 0.00 0.00 0.00 0.00 0.00 -19073.54 0.00 -10080.03 -24738.85
ROOM_5_FLR_3 13-JAN-16:23 8743.71 334.35 0.00 -334.35 0.00 0.00 274.99 106.08 200.18 0.00 0.00 0.00 0.00 0.00 -2810.05 0.00 -1377.60 -5137.31
ROOM_6_FLR_3 12-JAN-17:54 9147.66 0.00 0.00 0.00 0.00 0.00 286.95 106.07 505.67 0.00 0.00 0.00 0.00 0.00 -3724.16 0.00 -1878.15 -4444.04
CORRIDOR_FLR_3 13-JAN-16:10 0.00 0.00 7584.40 0.00 0.00 0.00 3597.97 1288.89 0.00 0.00 0.00 0.00 0.00 0.00 -3586.84 0.00 -1699.47 -7184.95
ROOM_1_FLR_6 15-DEC-17:54 2776.06 0.00 0.00 0.00 0.00 0.00 68.97 26.52 126.43 0.00 0.00 0.00 0.00 0.00 -839.49 0.00 -393.25 -1765.25
ROOM_2_FLR_6 12-JAN-07:53 2720.26 0.00 0.00 0.00 0.00 0.00 57.17 53.04 237.03 0.00 0.00 0.00 0.00 0.00 -944.80 0.00 -487.38 -1635.31
ROOM_3_MULT9_FLR_6 13-JAN-16:23 13321.26 554.49 0.00 -554.49 0.00 0.00 612.41 150.05 441.28 0.00 0.00 0.00 0.00 0.00 -3247.12 0.00 -1593.73 -9684.15
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 13-JAN-16:10 0.00 0.00 5609.42 0.00 0.00 0.00 968.22 341.02 0.00 0.00 0.00 0.00 0.00 0.00 -1555.39 0.00 -746.61 -4616.66
Total Facility 13-JAN-16:23 65041.73 67843.24 20105.92 -67843.24 0.00 0.00 62406.91 12737.46 73604.29 0.00 0.00 0.00 0.00 0.00 -63516.09 0.00 -34167.69 -136212.53



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 22.5251 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 22.3982 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 13.1529 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.5268 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1921 2.1921 1.2824 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5021 0.5021 0.1190 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2267 0.2267 0.1376 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1780 0.1780 0.0018 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0970 0.0970 0.0866 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.3154 3.3154 0.0332 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.9510 1.9510 1.0145 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.2778 5.2778 2.8395 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4263 1.4263 0.7117 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1082 2.1082 1.7814 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2122 2.2122 1.7808 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2731 2.2731 0.5501 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7651 0.7651 0.1882 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 22.5251 22.3982 22.5251 10.5268 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2824 1.2824 1.2824 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2511 0.2511 0.1190 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1376 0.1376 0.1376 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0890 0.0890 0.0018 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0866 0.0866 0.0866 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6577 1.6577 0.0332 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0145 1.0145 1.0145 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8395 2.8395 2.8395 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7132 0.7132 0.7117 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7814 1.7814 1.7814 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7808 1.7808 1.7808 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1365 1.1365 0.5501 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3826 0.3826 0.1882 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 13.1529 10.5268 10.5268 10.5268 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 213.50
Number of hours cooling loads not met 37.17
Number of hours not met 250.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 3615.61 783717.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 321.96 114978.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 545.09 45764.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 192.37 12338.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 872.72 59188.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 8.75 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 4.94 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 21.51 1274.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 560.67 31412.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 57.99 4641.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 140.95 8265.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.74 4738.77 3628.21 312595.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 15.79 1309.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 20.86 714.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1692.20 4242.52
Natural Gas 1788.84 9032.66
Additional 0.00 0.00
Total 3481.04 13275.18


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 48.05
Space Heating 0.00
Space Cooling 28.38
Fans (All) 49.42
Service Water Heating 8.00
Receptacle Equipment 145.30
Miscellaneous (All) 373.95
Subtotal 373.95


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 318.69
Service Water Heating 319.80
Miscellaneous (All) 796.16
Subtotal 796.16


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 4.11
Space Heating 27.24
Space Cooling 2.43
Fans (All) 4.22
Service Water Heating 28.01
Receptacle Equipment 25.89
Miscellaneous 8.10


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2572. 8760.
LTG_SCH_LOBBY 2295. 8760.
LTG_SCH_STORAGE 1580. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 3061. 8760.
LTG_SCH_GUESTROOM 1980. 8760.
LTG_SCH_CORRIDOR 2295. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3737. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 8760. 8760.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 15.56 365 15.56 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 26.67 365 26.67 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8715.33 44.67 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8697.33 62.67 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8748.83 11.17 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8673.83 86.17 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8673.83 0.00 0.00 0.00 0.00
Max 8760.00 86.17 0.00 0.00 0.00
Average 8750.70 9.30 0.00 0.00 0.00
Sum 192515.33 204.67 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4134.33 19.67 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4108.33 45.67 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 45.67 0.00 0.00 0.00
Average 288884.08 2.97 0.00 0.00 0.00
Sum 6355449.67 65.33 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8755.33 4.67 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8719.33 40.67 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8607.83 152.17 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8746.50 13.50 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8686.17 73.83 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8754.17 5.83 0.00 0.00 0.00
DINING_FLR_6 8757.17 2.83 0.00 0.00 0.00
KITCHEN_FLR_6 8759.33 0.67 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8607.83 0.00 0.00 0.00 0.00
Max 8760.00 152.17 0.00 0.00 0.00
Average 8746.63 13.37 0.00 0.00 0.00
Sum 192425.83 294.17 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2113655.67 1773.33 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4129.17 24.83 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4152.83 1.17 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4104.83 49.17 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1244408.33 1306.67 0.00 0.00 0.00
DINING_FLR_6 1245113.67 601.33 0.00 0.00 0.00
KITCHEN_FLR_6 108261.67 7.33 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2113655.67 1773.33 0.00 0.00 0.00
Average 288715.96 171.08 0.00 0.00 0.00
Sum 6351751.17 3763.83 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:50:54

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8

For: Environment

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS

For: Environment

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.281319E+11 18811.57 12-JAN-21:00 -37.2 -37.3 0.690401E+10 4387.03 27-JAN-22:10 -13.2 -13.7
February 0.227837E+11 13886.81 28-FEB-21:00 -30.0 -30.1 0.590134E+10 4286.07 01-FEB-22:10 -30.0 -30.1
March 0.245773E+11 11960.44 01-MAR-00:10 -28.9 -29.2 0.649723E+10 4045.95 31-MAR-21:10 -13.2 -14.9
April 0.250945E+11 12500.19 22-APR-10:35 11.87 5.55 0.640179E+10 4111.07 14-APR-22:10 11.87 5.55
May 0.270932E+11 12922.07 14-MAY-10:35 16.83 8.94 0.668479E+10 4156.36 26-MAY-22:10 2.12 0.59
June 0.276682E+11 13443.91 29-JUN-10:35 21.83 15.68 0.665788E+10 4270.87 23-JUN-22:10 21.83 15.68
July 0.310965E+11 14699.86 23-JUL-10:35 22.23 15.22 0.725733E+10 4540.12 28-JUL-22:10 17.02 13.67
August 0.333072E+11 15325.78 26-AUG-10:35 15.93 12.30 0.776005E+10 4816.67 31-AUG-22:10 8.20 4.96
September 0.329187E+11 15889.16 20-SEP-21:00 8.30 7.74 0.771448E+10 4837.04 19-SEP-21:19 8.30 7.74
October 0.335096E+11 16105.84 06-OCT-21:00 7.80 3.59 0.797739E+10 4837.04 19-OCT-21:19 -1.7 -1.8
November 0.316262E+11 15365.95 28-NOV-23:00 -28.9 -29.1 0.750404E+10 4836.95 02-NOV-21:19 -28.9 -29.1
December 0.304213E+11 17194.65 15-DEC-07:52 -33.9 -34.0 0.729415E+10 4590.06 01-DEC-22:10 -33.9 -34.0
                     
Annual Sum or Average 0.348228E+12         0.845545E+11        
Minimum of Months 0.227837E+11 11960.44   -37.2 -37.3 0.590134E+10 4045.95   -33.9 -34.0
Maximum of Months 0.335096E+11 18811.57   22.23 15.68 0.797739E+10 4837.04   21.83 15.68



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 9958775.32 677.82 30-JAN-12:30 -23.9 -24.3 0.609917E+09 364.20 26-JAN-01:39 -23.9 -24.3
February 0.203149E+09 1165.62 15-FEB-13:40 -8.7 -9.6 0.561043E+09 364.29 18-FEB-05:19 -23.5 -23.8
March 0.108159E+10 2749.85 27-MAR-13:30 -5.5 -8.7 0.640644E+09 404.96 22-MAR-21:19 -5.5 -8.7
April 0.293207E+10 4520.09 22-APR-13:30 15.30 6.96 0.681470E+09 491.83 21-APR-21:19 15.30 6.96
May 0.380003E+10 4452.42 12-MAY-13:30 20.60 9.86 0.755823E+09 491.84 11-MAY-21:40 20.60 9.86
June 0.421834E+10 4196.48 30-JUN-12:30 26.15 17.75 0.775987E+09 491.85 16-JUN-21:10 26.15 17.75
July 0.439111E+10 4773.49 23-JUL-13:30 25.00 15.26 0.796202E+09 491.86 21-JUL-22:00 25.00 15.26
August 0.411290E+10 4950.54 25-AUG-13:30 21.70 14.78 0.780823E+09 491.84 03-AUG-22:10 21.70 14.78
September 0.252726E+10 4083.46 09-SEP-13:30 13.35 8.71 0.665719E+09 473.58 08-SEP-21:19 13.35 8.71
October 0.948958E+09 2993.55 03-OCT-13:20 10.57 6.12 0.631207E+09 431.97 03-OCT-21:30 7.20 2.97
November 35097267.84 965.23 08-NOV-13:40 -13.5 -14.3 0.598988E+09 364.21 08-NOV-02:20 -13.5 -14.3
December 0.00 0.00 01-DEC-00:10 -25.8 -26.0 0.617147E+09 364.21 09-DEC-00:40 -24.2 -24.5
                     
Annual Sum or Average 0.242605E+11         0.811497E+10        
Minimum of Months 0.00 0.00   -25.8 -26.0 0.561043E+09 364.20   -24.2 -24.5
Maximum of Months 0.439111E+10 4950.54   26.15 17.75 0.796202E+09 491.86   26.15 17.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.120556E+10 1053.46 23-JAN-21:00 -16.1 -16.4 0.716517E+09 444.14 20-JAN-23:10 -16.1 -16.4
February 0.143197E+10 1145.53 09-FEB-21:00 -8.9 -9.2 0.654410E+09 464.09 09-FEB-22:49 -10.4 -10.7
March 0.214822E+10 1270.01 22-MAR-20:00 2.80 0.30 0.743686E+09 494.66 22-MAR-22:10 1.42 -0.3
April 0.281663E+10 1519.36 21-APR-20:00 12.20 5.22 0.787552E+09 557.93 21-APR-21:40 8.13 2.71
May 0.327638E+10 1565.04 31-MAY-18:10 21.13 10.92 0.861832E+09 566.44 31-MAY-22:10 15.05 9.19
June 0.340152E+10 1727.17 21-JUN-21:00 23.90 13.75 0.871116E+09 569.56 16-JUN-21:10 23.90 13.75
July 0.352840E+10 1685.27 11-JUL-20:05 23.62 14.00 0.895626E+09 569.56 10-JUL-22:10 23.62 14.00
August 0.341687E+10 1675.15 11-AUG-21:00 22.80 14.12 0.889016E+09 569.55 01-AUG-22:10 22.80 14.12
September 0.286939E+10 1472.57 10-SEP-10:35 13.87 7.59 0.793320E+09 543.83 01-SEP-22:10 13.87 7.59
October 0.235912E+10 1340.83 03-OCT-20:00 6.10 2.72 0.756465E+09 514.51 03-OCT-22:10 7.30 3.10
November 0.132657E+10 1084.55 01-NOV-20:00 -8.9 -9.5 0.696924E+09 451.97 01-NOV-22:10 -9.0 -9.5
December 0.103504E+10 1023.62 19-DEC-21:00 -6.1 -7.0 0.717758E+09 436.67 19-DEC-23:10 -8.7 -9.2
                     
Annual Sum or Average 0.288157E+11         0.938422E+10        
Minimum of Months 0.103504E+10 1023.62   -16.1 -16.4 0.654410E+09 436.67   -16.1 -16.4
Maximum of Months 0.352840E+10 1727.17   23.90 14.12 0.895626E+09 569.56   23.90 14.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 2814799.82 14.04 19-JAN-21:00 -10.0 -10.4 0.151463E+09 94.11 20-JAN-22:10 -11.2 -11.4
February 7183762.00 15.78 09-FEB-21:00 -8.9 -9.2 0.138715E+09 101.02 09-FEB-22:10 -9.6 -9.9
March 19438898.79 18.30 22-MAR-20:00 2.80 0.30 0.158716E+09 111.47 22-MAR-21:10 2.12 0.08
April 85080700.14 536.74 21-APR-20:00 12.20 5.22 0.178792E+09 120.45 27-APR-22:40 4.07 1.37
May 0.545107E+09 984.76 31-MAY-20:55 16.70 9.87 0.204136E+09 120.45 11-MAY-22:10 16.70 9.87
June 0.128460E+10 1300.63 21-JUN-20:00 25.00 13.79 0.199174E+09 120.46 02-JUN-22:10 25.00 13.79
July 0.142764E+10 1335.82 21-JUL-20:00 25.00 16.11 0.205000E+09 120.46 21-JUL-23:10 19.72 15.53
August 0.108213E+10 1248.92 11-AUG-20:00 24.40 14.81 0.205762E+09 120.45 03-AUG-21:00 24.40 14.81
September 0.201636E+09 672.06 01-SEP-20:00 12.20 9.06 0.192515E+09 120.45 01-SEP-00:10 12.20 9.06
October 36938552.40 204.53 06-OCT-21:00 7.80 3.59 0.173327E+09 120.45 03-OCT-21:19 7.80 3.59
November 3681757.61 14.54 03-NOV-20:00 -6.1 -7.8 0.147234E+09 96.36 03-NOV-21:10 -6.6 -8.2
December 1716904.07 13.48 19-DEC-21:00 -6.1 -7.0 0.151835E+09 91.74 19-DEC-22:10 -8.3 -8.9
                     
Annual Sum or Average 0.469797E+10         0.210667E+10        
Minimum of Months 1716904.07 13.48   -10.0 -10.4 0.138715E+09 91.74   -11.2 -11.4
Maximum of Months 0.142764E+10 1335.82   25.00 16.11 0.205762E+09 120.46   25.00 15.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9 -15.4 0.115446E+09 68.58 26-JAN-01:10 -23.9 -24.2
February 2199585.50 124.97 08-FEB-22:00 1.10 -1.7 0.105325E+09 68.59 18-FEB-05:19 -23.5 -23.8
March 51106523.24 442.10 22-MAR-21:00 2.20 0.09 0.117211E+09 68.59 13-MAR-04:10 2.20 0.09
April 0.858039E+09 792.31 23-APR-10:35 9.80 3.70 0.113613E+09 72.82 21-APR-21:40 9.80 3.70
May 0.170541E+10 890.59 14-MAY-10:35 16.83 8.94 0.122356E+09 77.30 31-MAY-22:10 15.05 9.19
June 0.185852E+10 934.17 22-JUN-10:35 21.33 12.72 0.126296E+09 81.68 21-JUN-21:00 21.33 12.72
July 0.194568E+10 973.77 23-JUL-10:35 22.23 15.22 0.130732E+09 82.03 11-JUL-21:49 22.23 15.22
August 0.184566E+10 906.95 26-AUG-10:35 15.93 12.30 0.128135E+09 80.53 11-AUG-21:40 15.93 12.30
September 0.131766E+10 816.00 10-SEP-10:35 13.87 7.59 0.114800E+09 73.70 01-SEP-22:10 13.87 7.59
October 0.414539E+09 668.94 03-OCT-19:50 6.47 2.89 0.116772E+09 69.94 03-OCT-22:10 7.30 3.10
November 0.00 0.00 01-NOV-00:10 -10.0 -10.9 0.112768E+09 68.58 16-NOV-23:19 -23.9 -24.1
December 0.00 0.00 01-DEC-00:10 -25.8 -26.0 0.116434E+09 68.58 19-DEC-01:19 -24.1 -24.3
                     
Annual Sum or Average 0.999881E+10         0.141989E+10        
Minimum of Months 0.00 0.00   -25.8 -26.0 0.105325E+09 68.58   -24.1 -24.3
Maximum of Months 0.194568E+10 973.77   22.23 15.22 0.130732E+09 82.03   22.23 15.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.448652E+11 36315.77 19-JAN-21:00 -10.0 -10.4 0.649339E+09 381.60 03-JAN-22:19 -10.0 -10.4
February 0.411466E+11 36795.81 08-FEB-21:00 -1.1 -2.8 0.587073E+09 381.59 18-FEB-05:40 -22.6 -23.0
March 0.470190E+11 37524.30 22-MAR-20:00 2.80 0.30 0.652392E+09 381.58 22-MAR-23:40 -0.4 -1.6
April 0.474538E+11 38299.96 21-APR-20:00 12.20 5.22 0.629503E+09 381.58 07-APR-01:10 12.20 5.22
May 0.509801E+11 38784.04 31-MAY-20:00 17.20 10.12 0.650710E+09 381.58 17-MAY-21:10 17.20 10.12
June 0.502711E+11 39064.60 29-JUN-20:00 25.00 16.66 0.630881E+09 381.73 16-JUN-21:10 25.00 16.66
July 0.518566E+11 39145.83 21-JUL-20:00 25.00 16.11 0.649340E+09 381.71 01-JUL-00:10 25.00 16.11
August 0.515433E+11 38993.39 11-AUG-20:00 24.40 14.81 0.652089E+09 381.65 23-AUG-21:10 18.43 14.55
September 0.481290E+11 38196.84 01-SEP-20:00 12.20 9.06 0.629195E+09 381.57 27-SEP-23:30 -0.9 -1.3
October 0.477494E+11 37764.55 03-OCT-20:00 6.10 2.72 0.649650E+09 381.57 15-OCT-23:30 -0.9 -1.3
November 0.437015E+11 36439.02 01-NOV-20:00 -8.9 -9.5 0.628127E+09 381.57 07-NOV-23:49 -23.0 -23.3
December 0.444227E+11 36102.41 19-DEC-21:00 -6.1 -7.0 0.649339E+09 381.63 15-DEC-22:10 -6.1 -7.0
                     
Annual Sum or Average 0.569138E+12         0.765764E+10        
Minimum of Months 0.411466E+11 36102.41   -10.0 -10.4 0.587073E+09 381.57   -23.0 -23.3
Maximum of Months 0.518566E+11 39145.83   25.00 16.66 0.652392E+09 381.73   25.00 16.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.641482E+10 6830.07 06-JAN-23:10 -3.0 -4.1 0.809580E+10 4872.66 06-JAN-23:10 -3.0 -4.1
February 0.906924E+10 8118.57 15-FEB-13:40 -8.7 -9.6 0.738971E+10 5108.11 08-FEB-22:40 -8.7 -9.6
March 0.158398E+11 11277.68 27-MAR-15:10 -4.9 -8.2 0.849383E+10 5635.62 22-MAR-21:40 -4.9 -8.2
April 0.211005E+11 15392.11 22-APR-13:30 15.30 6.96 0.895886E+10 6273.25 21-APR-21:40 15.30 6.96
May 0.238965E+11 14529.06 13-MAY-13:10 18.98 8.91 0.957402E+10 6384.91 31-MAY-21:40 15.77 9.56
June 0.242914E+11 13637.51 20-JUN-15:10 25.10 14.57 0.961814E+10 6462.77 29-JUN-22:10 22.23 16.21
July 0.252245E+11 14930.83 23-JUL-13:30 25.00 15.26 0.985994E+10 6462.78 31-JUL-22:10 19.35 13.65
August 0.246171E+11 15671.27 25-AUG-14:10 22.88 15.43 0.979699E+10 6462.77 10-AUG-22:10 22.88 15.43
September 0.198480E+11 14331.43 09-SEP-13:30 13.35 8.71 0.881657E+10 6090.33 08-SEP-21:40 13.35 8.71
October 0.151638E+11 10832.31 03-OCT-14:10 11.88 6.64 0.846928E+10 5865.82 03-OCT-21:40 7.20 3.00
November 0.695734E+10 7007.21 08-NOV-13:30 -13.6 -14.4 0.787764E+10 4941.68 01-NOV-21:40 -13.6 -14.4
December 0.529372E+10 6450.73 19-DEC-22:20 -8.3 -8.9 0.813178E+10 4788.22 09-DEC-02:49 -8.3 -8.9
                     
Annual Sum or Average 0.197717E+12         0.105083E+12        
Minimum of Months 0.529372E+10 6450.73   -13.6 -14.4 0.738971E+10 4788.22   -13.6 -14.4
Maximum of Months 0.252245E+11 15671.27   25.10 15.43 0.985994E+10 6462.78   22.88 16.21



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.377948E+11 23170.94 06-JAN-22:00 -3.9 -4.8 0.249048E+11 16210.03 06-JAN-23:10 -3.0 -4.1
February 0.408345E+11 25632.20 28-FEB-22:10 -29.6 -29.7 0.228866E+11 16809.98 09-FEB-22:49 -29.6 -29.7
March 0.543183E+11 27690.85 22-MAR-20:00 2.80 0.30 0.265529E+11 17867.23 22-MAR-22:10 1.42 -0.3
April 0.631408E+11 32430.90 21-APR-21:10 9.53 3.30 0.280224E+11 19183.57 21-APR-21:49 7.67 2.50
May 0.712673E+11 33441.26 14-MAY-10:35 16.83 8.94 0.302551E+11 19186.29 11-MAY-21:40 16.83 8.94
June 0.728980E+11 36499.76 21-JUN-21:03 23.53 13.66 0.301812E+11 19186.57 30-JUN-23:00 15.10 14.10
July 0.757055E+11 37118.51 21-JUL-21:10 22.70 14.59 0.310378E+11 19186.91 01-JUL-00:10 22.70 14.59
August 0.738103E+11 37197.75 11-AUG-21:10 22.33 14.00 0.309800E+11 19186.28 01-AUG-22:10 22.33 14.00
September 0.637322E+11 32349.03 10-SEP-10:35 13.87 7.59 0.282492E+11 19166.58 08-SEP-22:10 13.87 7.59
October 0.562002E+11 29166.58 03-OCT-20:00 6.10 2.72 0.271187E+11 18536.84 03-OCT-22:10 7.30 3.10
November 0.393453E+11 24696.59 28-NOV-22:10 -27.5 -27.7 0.242342E+11 16454.19 01-NOV-22:10 -27.5 -27.7
December 0.349880E+11 24579.25 27-DEC-22:00 -26.1 -26.3 0.246218E+11 15929.03 19-DEC-23:10 -26.1 -26.3
                     
Annual Sum or Average 0.684035E+12         0.329045E+12        
Minimum of Months 0.349880E+11 23170.94   -29.6 -29.7 0.228866E+11 15929.03   -29.6 -29.7
Maximum of Months 0.757055E+11 37197.75   23.53 14.59 0.310378E+11 19186.91   22.70 14.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9 -15.4 91489037.36 56.69 04-JAN-04:40 -15.7 -15.9
February 1351660.47 399.49 15-FEB-16:14 -7.4 -8.8 83100413.63 56.69 23-FEB-04:10 -22.7 -22.9
March 41574402.00 3641.70 22-MAR-15:11 5.60 2.35 93625230.06 56.69 06-MAR-04:00 5.60 2.35
April 0.645337E+09 3849.09 20-APR-18:01 12.02 5.14 94184485.19 56.69 20-APR-22:10 5.13 1.65
May 0.126368E+10 3866.01 10-MAY-18:01 18.30 8.81 98946875.13 56.69 30-MAY-21:40 17.23 9.55
June 0.191296E+10 3905.68 16-JUN-18:01 19.40 10.53 96188312.06 56.70 19-JUN-21:10 21.23 12.32
July 0.184579E+10 3384.01 26-JUL-18:01 18.85 14.91 99280711.37 56.70 24-JUL-21:49 18.85 14.91
August 0.138901E+10 3800.10 31-AUG-15:11 14.27 5.23 99051722.82 56.70 02-AUG-21:49 14.27 5.23
September 0.327738E+09 3786.95 07-SEP-15:11 16.47 8.91 93626765.35 56.69 01-SEP-01:30 16.47 8.91
October 18025482.60 3190.98 13-OCT-15:12 1.70 -2.0 93204827.97 56.69 23-OCT-23:19 -5.0 -5.2
November 5104.65 8.51 08-NOV-14:00 -13.3 -14.1 88940645.20 56.69 17-NOV-04:49 -21.4 -21.7
December 0.00 0.00 01-DEC-00:10 -25.8 -26.0 91745250.24 56.69 23-DEC-04:10 -6.4 -7.4
                     
Annual Sum or Average 0.744547E+10         0.112338E+10        
Minimum of Months 0.00 0.00   -25.8 -26.0 83100413.63 56.69   -22.7 -22.9
Maximum of Months 0.191296E+10 3905.68   19.40 14.91 99280711.37 56.70   21.23 14.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9 -15.4 91299737.14 56.69 19-JAN-00:20 -9.2 -9.3
February 37239.91 160.93 08-FEB-19:06 0.22 -1.6 82984710.28 56.69 06-FEB-05:19 0.22 -1.6
March 3416761.81 729.51 26-MAR-15:14 -8.5 -10.4 92504987.36 56.69 15-MAR-04:40 -8.5 -10.4
April 0.338516E+09 3476.84 21-APR-18:01 14.22 5.92 92609244.44 56.69 21-APR-21:40 8.13 2.71
May 0.785253E+09 4005.33 09-MAY-20:01 13.35 5.95 0.103126E+09 87.50 10-MAY-21:10 14.13 6.05
June 0.135125E+10 3654.07 01-JUN-18:41 14.60 7.96 0.107716E+09 102.02 28-JUN-21:10 19.72 14.76
July 0.130442E+10 3486.46 06-JUL-21:51 18.90 13.76 0.108481E+09 91.12 11-JUL-21:10 21.83 13.37
August 0.820277E+09 3419.69 30-AUG-18:01 8.80 3.00 0.105880E+09 90.65 10-AUG-21:10 8.80 3.00
September 0.142070E+09 3378.34 07-SEP-18:01 14.13 7.59 92773059.19 56.69 02-SEP-23:19 14.13 7.59
October 4716579.76 1554.82 03-OCT-15:11 12.43 6.74 92554780.90 56.69 31-OCT-23:19 -10.3 -11.2
November 0.00 0.00 01-NOV-00:10 -10.0 -10.9 88904232.44 56.69 18-NOV-00:20 -14.1 -14.7
December 0.00 0.00 01-DEC-00:10 -25.8 -26.0 91703378.92 56.69 23-DEC-05:10 -4.8 -6.0
                     
Annual Sum or Average 0.474996E+10         0.115054E+10        
Minimum of Months 0.00 0.00   -25.8 -26.0 82984710.28 56.69   -14.1 -14.7
Maximum of Months 0.135125E+10 4005.33   18.90 13.76 0.108481E+09 102.02   21.83 14.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 2841.25 2.68 23-JAN-15:20 -10.4 -10.8 0.00 0.00 01-JAN-00:10 -10.4 -10.8
February 1494973.18 99.61 26-FEB-16:00 -23.9 -24.3 0.00 0.00 01-FEB-00:10 -23.9 -24.3
March 11107318.83 189.07 31-MAR-15:10 -9.9 -12.2 0.00 0.00 01-MAR-00:10 -9.9 -12.2
April 0.329434E+09 742.97 22-APR-13:20 15.20 6.93 0.00 0.00 01-APR-00:10 15.20 6.93
May 0.488510E+09 720.03 12-MAY-13:20 20.60 9.86 0.00 0.00 01-MAY-00:10 20.60 9.86
June 0.577568E+09 637.89 30-JUN-12:30 26.15 17.75 0.00 0.00 01-JUN-00:10 26.15 17.75
July 0.604793E+09 758.42 23-JUL-13:30 25.00 15.26 0.00 0.00 01-JUL-00:10 25.00 15.26
August 0.549388E+09 803.30 25-AUG-13:30 21.70 14.78 0.00 0.00 01-AUG-00:10 21.70 14.78
September 0.226712E+09 688.64 09-SEP-13:10 12.98 8.62 0.00 0.00 01-SEP-00:10 12.98 8.62
October 29459955.09 460.95 03-OCT-13:00 10.00 5.88 0.00 0.00 01-OCT-00:10 10.00 5.88
November 173296.67 34.63 08-NOV-15:20 -14.6 -15.2 0.00 0.00 01-NOV-00:10 -14.6 -15.2
December 0.00 0.00 01-DEC-00:10 -25.8 -26.0 0.00 0.00 01-DEC-00:10 -25.8 -26.0
                     
Annual Sum or Average 0.281864E+10         0.00        
Minimum of Months 0.00 0.00   -25.8 -26.0 0.00 0.00   -25.8 -26.0
Maximum of Months 0.604793E+09 803.30   26.15 17.75 0.00 0.00   26.15 17.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 923372.62 192.28 20-JAN-19:07 -13.1 -13.2 91498747.59 56.69 03-JAN-23:10 -13.1 -13.2
February 2127801.16 258.12 07-FEB-19:04 -1.1 -2.8 83463105.98 56.69 23-FEB-00:20 -22.8 -23.0
March 11585850.95 670.44 22-MAR-18:02 2.98 0.38 93744988.86 56.69 05-MAR-00:20 2.98 0.38
April 0.131113E+09 1012.96 30-APR-18:01 9.72 3.97 92726524.36 56.69 21-APR-21:10 9.72 3.97
May 0.437826E+09 1082.43 31-MAY-21:51 15.30 9.39 99605959.73 73.05 31-MAY-21:00 15.30 9.39
June 0.629473E+09 1130.15 10-JUN-21:51 19.40 11.22 0.101035E+09 79.14 19-JUN-21:19 20.77 12.16
July 0.637853E+09 1042.09 19-JUL-21:51 19.40 14.19 0.104237E+09 77.99 10-JUL-21:40 19.40 14.19
August 0.463553E+09 1082.01 10-AUG-21:51 16.10 9.68 0.102090E+09 75.03 02-AUG-21:30 16.10 9.68
September 0.198290E+09 992.59 10-SEP-18:01 15.32 9.12 93377776.06 56.69 01-SEP-21:10 15.32 9.12
October 41136566.06 930.36 03-OCT-18:01 9.72 4.62 94379460.49 56.69 04-OCT-21:19 3.30 1.35
November 689931.38 221.72 01-NOV-18:06 -8.9 -9.7 89101710.39 56.69 08-NOV-00:20 -23.0 -23.2
December 600156.75 242.15 24-DEC-19:05 -4.0 -4.2 91705120.44 56.69 16-DEC-00:20 -4.0 -4.2
                     
Annual Sum or Average 0.255517E+10         0.113697E+10        
Minimum of Months 600156.75 192.28   -13.1 -13.2 83463105.98 56.69   -23.0 -23.2
Maximum of Months 0.637853E+09 1130.15   19.40 14.19 0.104237E+09 79.14   20.77 14.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9 -15.4 91411705.62 56.69 04-JAN-05:49 -14.5 -14.6
February 2008662.58 438.21 09-FEB-16:15 -0.3 -1.2 83222644.13 56.69 23-FEB-00:20 -22.8 -23.0
March 66077198.85 3512.45 22-MAR-15:11 5.60 2.35 94742376.09 56.69 06-MAR-05:19 5.60 2.35
April 0.602966E+09 3602.76 22-APR-15:11 14.60 6.32 94760348.72 56.69 21-APR-21:30 14.60 6.32
May 0.170807E+10 3669.04 13-MAY-08:61 14.60 6.29 99399335.99 56.69 31-MAY-21:30 16.00 9.64
June 0.214547E+10 3610.79 07-JUN-15:12 19.40 10.06 96331100.85 56.70 30-JUN-21:49 17.82 14.24
July 0.222979E+10 3220.36 08-JUL-08:61 15.78 13.66 99454241.27 56.70 14-JUL-21:40 16.47 14.16
August 0.163958E+10 3596.89 10-AUG-18:02 22.62 12.07 99417119.08 56.70 25-AUG-21:49 15.65 12.71
September 0.442299E+09 3564.18 07-SEP-15:11 16.47 8.91 94328750.07 56.69 01-SEP-01:30 16.47 8.91
October 38849386.62 3174.85 04-OCT-08:62 7.88 2.97 93721498.94 56.69 27-OCT-04:10 -17.7 -18.2
November 0.00 0.00 01-NOV-00:10 -10.0 -10.9 88935062.76 56.69 11-NOV-00:20 -20.0 -20.3
December 0.00 0.00 01-DEC-00:10 -25.8 -26.0 91729677.55 56.69 23-DEC-04:30 -5.8 -6.9
                     
Annual Sum or Average 0.887511E+10         0.112745E+10        
Minimum of Months 0.00 0.00   -25.8 -26.0 83222644.13 56.69   -22.8 -23.0
Maximum of Months 0.222979E+10 3669.04   22.62 13.66 99454241.27 56.70   17.82 14.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9 -15.4 91226102.46 56.69 16-JAN-00:30 -10.3 -10.8
February 61280.75 196.08 08-FEB-19:06 0.22 -1.6 82997933.60 56.69 02-FEB-04:19 0.22 -1.6
March 19350295.39 1049.32 11-MAR-09:01 -8.9 -9.9 93167931.52 56.69 05-MAR-00:20 -8.9 -9.9
April 0.272874E+09 3260.03 22-APR-08:62 5.55 1.86 93399611.29 56.69 27-APR-21:10 7.43 3.48
May 0.124810E+10 3475.58 14-MAY-20:41 13.68 7.57 0.101859E+09 76.64 12-MAY-21:10 13.68 7.57
June 0.166285E+10 3603.84 10-JUN-21:51 19.40 11.22 0.103700E+09 81.28 22-JUN-21:30 20.00 11.87
July 0.168524E+10 3755.51 22-JUL-08:32 20.37 15.09 0.107457E+09 83.28 07-JUL-21:19 20.37 15.09
August 0.110198E+10 3262.55 31-AUG-08:62 2.48 -0.9 0.104314E+09 78.64 02-AUG-21:19 2.48 -0.9
September 0.226259E+09 3212.72 10-SEP-15:11 15.40 8.69 93620231.43 56.69 01-SEP-01:10 15.40 8.69
October 11400225.28 2093.35 04-OCT-08:62 7.88 2.97 92971089.06 56.69 31-OCT-23:19 -10.3 -11.2
November 0.00 0.00 01-NOV-00:10 -10.0 -10.9 88889631.39 56.69 18-NOV-04:10 -4.1 -5.7
December 0.00 0.00 01-DEC-00:10 -25.8 -26.0 91668437.16 56.69 23-DEC-05:00 -3.9 -5.1
                     
Annual Sum or Average 0.622812E+10         0.114527E+10        
Minimum of Months 0.00 0.00   -25.8 -26.0 82997933.60 56.69   -10.3 -11.2
Maximum of Months 0.168524E+10 3755.51   20.37 15.09 0.107457E+09 83.28   20.37 15.09



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 18971946.30 303.40 06-JAN-23:00 -2.8 -3.9 0.119250E+10 704.47 26-JAN-00:49 -23.8 -24.1
February 0.164888E+09 728.20 08-FEB-22:05 0.73 -1.8 0.108379E+10 704.48 18-FEB-05:10 -23.9 -24.3
March 0.110287E+10 1391.81 22-MAR-20:00 2.80 0.30 0.120506E+10 721.70 22-MAR-21:49 1.78 0.04
April 0.306202E+10 1918.37 22-APR-10:35 11.87 5.55 0.123315E+10 826.24 21-APR-21:30 11.87 5.55
May 0.423172E+10 2144.00 14-MAY-10:35 16.83 8.94 0.141724E+10 897.63 12-MAY-21:40 16.83 8.94
June 0.455865E+10 2255.11 13-JUN-10:35 21.83 12.30 0.147787E+10 951.85 22-JUN-22:10 19.22 11.60
July 0.470584E+10 2303.78 23-JUL-10:35 22.23 15.22 0.151416E+10 951.85 12-JUL-22:10 22.23 15.22
August 0.439048E+10 2152.95 01-AUG-10:35 15.93 12.83 0.145908E+10 933.42 02-AUG-21:40 19.80 14.37
September 0.316658E+10 1871.14 10-SEP-10:35 13.87 7.59 0.123521E+10 832.02 01-SEP-21:49 13.87 7.59
October 0.127064E+10 1502.19 03-OCT-10:40 5.37 3.67 0.120145E+10 734.09 03-OCT-22:10 7.30 3.10
November 27219319.25 429.25 01-NOV-21:30 -8.9 -9.5 0.115952E+10 704.48 08-NOV-02:00 -24.4 -24.7
December 5515665.36 313.09 24-DEC-22:50 -3.6 -4.0 0.119768E+10 704.48 22-DEC-00:00 -3.6 -4.0
                     
Annual Sum or Average 0.267054E+11         0.153767E+11        
Minimum of Months 5515665.36 303.40   -8.9 -9.5 0.108379E+10 704.47   -24.4 -24.7
Maximum of Months 0.470584E+10 2303.78   22.23 15.22 0.151416E+10 951.85   22.23 15.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9 -15.4 91178396.97 56.69 17-JAN-04:10 -7.2 -7.4
February 282909.30 372.97 09-FEB-16:15 -0.3 -1.2 82993068.35 56.69 02-FEB-05:10 -0.3 -1.2
March 32598466.11 3747.69 22-MAR-15:11 5.60 2.35 93091569.29 56.69 05-MAR-04:00 5.60 2.35
April 0.635595E+09 4017.61 21-APR-18:01 14.22 5.92 93730934.36 56.69 28-APR-21:10 3.53 1.78
May 0.118277E+10 4026.53 10-MAY-18:01 18.30 8.81 98738828.36 56.69 30-MAY-21:40 17.23 9.55
June 0.186166E+10 4061.94 16-JUN-18:01 19.40 10.53 96076343.43 56.70 29-JUN-22:40 20.53 15.75
July 0.179445E+10 3466.63 10-JUL-08:61 15.97 12.32 99169286.28 56.70 10-JUL-21:40 18.33 14.30
August 0.130469E+10 4050.87 10-AUG-18:02 22.62 12.07 98850941.23 56.70 09-AUG-21:30 22.62 12.07
September 0.280310E+09 3938.40 07-SEP-15:11 16.47 8.91 93109305.31 56.69 08-SEP-22:00 6.70 5.41
October 11485333.65 2555.67 03-OCT-15:11 12.43 6.74 92748766.05 56.69 31-OCT-23:19 -10.3 -11.2
November 0.00 0.00 01-NOV-00:10 -10.0 -10.9 88890547.47 56.69 18-NOV-04:30 -4.5 -5.9
December 0.00 0.00 01-DEC-00:10 -25.8 -26.0 91650291.40 56.69 23-DEC-03:39 -8.4 -9.2
                     
Annual Sum or Average 0.710384E+10         0.112023E+10        
Minimum of Months 0.00 0.00   -25.8 -26.0 82993068.35 56.69   -10.3 -11.2
Maximum of Months 0.186166E+10 4061.94   22.62 12.32 99169286.28 56.70   22.62 15.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9 -15.4 90909864.66 56.69 19-JAN-00:20 -9.2 -9.3
February 0.00 0.00 01-FEB-00:05 -20.2 -20.7 82886554.04 56.69 06-FEB-05:40 -11.9 -12.3
March 1183789.20 872.60 22-MAR-15:13 5.60 2.35 92308802.05 56.69 11-MAR-05:10 5.60 2.35
April 0.317578E+09 3590.06 21-APR-18:01 14.22 5.92 92140004.35 56.69 20-APR-21:19 14.22 5.92
May 0.696887E+09 4455.62 09-MAY-19:42 14.27 6.45 0.103504E+09 95.37 10-MAY-21:10 14.13 6.05
June 0.133876E+10 4006.52 28-JUN-21:32 18.87 14.85 0.108998E+09 113.08 28-JUN-21:10 18.87 14.85
July 0.128203E+10 3731.21 06-JUL-21:51 18.90 13.76 0.109320E+09 94.09 11-JUL-21:10 21.83 13.37
August 0.746637E+09 3567.27 01-AUG-21:51 16.70 13.45 0.106495E+09 99.37 10-AUG-21:10 17.93 10.68
September 0.103624E+09 3481.93 07-SEP-18:01 14.13 7.59 92165495.78 56.69 12-SEP-21:10 11.02 7.51
October 2635556.62 1042.66 01-OCT-15:13 13.70 7.69 92236014.68 56.69 30-OCT-03:49 -14.2 -15.0
November 0.00 0.00 01-NOV-00:10 -10.0 -10.9 88782533.85 56.69 11-NOV-00:20 -20.0 -20.3
December 0.00 0.00 01-DEC-00:10 -25.8 -26.0 91495824.34 56.69 23-DEC-04:49 -5.3 -6.4
                     
Annual Sum or Average 0.448934E+10         0.115124E+10        
Minimum of Months 0.00 0.00   -25.8 -26.0 82886554.04 56.69   -20.0 -20.3
Maximum of Months 0.133876E+10 4455.62   18.90 14.85 0.109320E+09 113.08   21.83 14.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 1130290.19 216.92 30-JAN-13:55 -23.9 -24.3 91761548.52 56.69 04-JAN-00:20 -23.9 -24.3
February 20162811.98 2556.60 15-FEB-16:11 -7.4 -8.8 84452988.52 56.69 23-FEB-00:20 -22.8 -23.0
March 0.220535E+09 2648.70 31-MAR-15:11 -9.8 -12.1 96010761.20 56.69 22-MAR-21:19 -9.8 -12.1
April 0.704859E+09 2706.14 20-APR-15:11 13.70 6.18 95117722.94 56.69 27-APR-21:49 5.97 2.67
May 0.984298E+09 2667.74 09-MAY-15:12 17.40 7.98 99104056.28 56.69 31-MAY-23:30 13.10 8.38
June 0.119537E+10 2630.90 16-JUN-18:01 19.40 10.53 96140997.24 56.70 29-JUN-21:49 22.88 16.35
July 0.126502E+10 2617.41 13-JUL-18:02 23.90 13.18 99259940.65 56.70 20-JUL-21:40 18.53 13.35
August 0.111637E+10 2674.48 31-AUG-15:11 14.27 5.23 99183993.78 56.70 25-AUG-21:40 14.27 5.23
September 0.481911E+09 2650.57 30-SEP-15:11 2.97 -0.7 94693602.61 56.69 07-SEP-21:49 2.97 -0.7
October 0.115909E+09 2609.90 14-OCT-15:11 3.90 -0.9 94905963.24 56.69 04-OCT-21:19 3.90 -0.9
November 1980536.36 1000.97 08-NOV-16:12 -16.8 -17.1 89224968.88 56.69 11-NOV-00:20 -20.0 -20.3
December 20059.26 200.59 24-DEC-09:05 0.18 -1.3 91755967.49 56.69 16-DEC-00:20 0.18 -1.3
                     
Annual Sum or Average 0.610756E+10         0.113161E+10        
Minimum of Months 20059.26 200.59   -23.9 -24.3 84452988.52 56.69   -23.9 -24.3
Maximum of Months 0.126502E+10 2706.14   23.90 13.18 99259940.65 56.70   22.88 16.35



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.294390E+11 15803.07 06-JAN-23:10 -3.0 -4.1 0.151823E+11 10227.17 06-JAN-23:10 -3.0 -4.1
February 0.276973E+11 17046.71 28-FEB-23:00 -29.3 -29.5 0.138371E+11 10479.75 08-FEB-23:00 -29.3 -29.5
March 0.331924E+11 16917.46 22-MAR-21:00 2.20 0.09 0.157688E+11 10739.94 22-MAR-22:10 1.42 -0.3
April 0.366709E+11 18234.40 21-APR-20:30 11.10 4.35 0.159829E+11 11193.81 21-APR-22:10 6.83 2.10
May 0.424683E+11 19751.91 31-MAY-21:10 16.47 9.79 0.174305E+11 11349.23 11-MAY-21:40 16.47 9.79
June 0.436547E+11 21790.55 21-JUN-21:03 23.53 13.66 0.174136E+11 11349.24 28-JUN-22:10 18.12 14.78
July 0.450334E+11 21345.72 11-JUL-21:10 21.83 13.37 0.178403E+11 11349.25 10-JUL-22:10 21.83 13.37
August 0.432581E+11 20862.44 02-AUG-21:10 20.40 14.60 0.176628E+11 11349.22 01-AUG-22:10 20.40 14.60
September 0.379714E+11 18233.24 01-SEP-21:00 11.10 8.75 0.163009E+11 11230.72 01-SEP-22:10 9.90 8.27
October 0.348139E+11 17303.40 06-OCT-21:00 7.80 3.59 0.160714E+11 10897.88 06-OCT-22:10 7.12 3.42
November 0.286843E+11 16833.76 28-NOV-23:00 -28.9 -29.1 0.146789E+11 10246.55 03-NOV-22:10 -28.9 -29.1
December 0.288775E+11 16997.92 14-DEC-22:30 -28.6 -28.8 0.150128E+11 10088.04 19-DEC-23:10 -8.7 -9.2
                     
Annual Sum or Average 0.431761E+12         0.193182E+12        
Minimum of Months 0.276973E+11 15803.07   -29.3 -29.5 0.138371E+11 10088.04   -29.3 -29.5
Maximum of Months 0.450334E+11 21790.55   23.53 14.60 0.178403E+11 11349.25   21.83 14.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.323551E+11 17547.30 11-JAN-22:20 -34.8 -34.9 0.156117E+11 10612.60 06-JAN-23:10 -34.8 -34.9
February 0.303060E+11 18062.94 28-FEB-22:20 -29.5 -29.7 0.142301E+11 10880.89 08-FEB-23:00 -29.5 -29.7
March 0.359562E+11 17807.53 22-MAR-21:00 2.20 0.09 0.162946E+11 11151.35 22-MAR-22:10 1.42 -0.3
April 0.388227E+11 18993.45 21-APR-21:10 9.53 3.30 0.165187E+11 11344.42 21-APR-22:10 6.83 2.10
May 0.442450E+11 21096.18 10-MAY-21:07 14.13 6.05 0.178726E+11 11349.22 11-MAY-21:40 12.20 6.17
June 0.453390E+11 22463.08 21-JUN-21:03 23.53 13.66 0.177910E+11 11349.24 28-JUN-22:10 18.12 14.78
July 0.467377E+11 22593.61 11-JUL-21:10 21.83 13.37 0.182326E+11 11349.25 10-JUL-22:10 21.83 13.37
August 0.449517E+11 21453.76 02-AUG-21:52 19.40 14.21 0.180691E+11 11349.22 01-AUG-22:10 19.40 14.21
September 0.400629E+11 19324.19 01-SEP-21:10 10.92 8.67 0.168542E+11 11344.94 07-SEP-22:49 9.50 6.17
October 0.375676E+11 18245.71 06-OCT-21:00 7.80 3.59 0.166646E+11 11334.72 06-OCT-22:10 7.12 3.42
November 0.314944E+11 17517.53 28-NOV-23:00 -28.9 -29.1 0.150857E+11 10636.69 03-NOV-22:10 -28.9 -29.1
December 0.317834E+11 18201.94 14-DEC-23:00 -29.4 -29.6 0.153970E+11 10460.67 19-DEC-23:10 -8.7 -9.2
                     
Annual Sum or Average 0.459622E+12         0.198622E+12        
Minimum of Months 0.303060E+11 17517.53   -34.8 -34.9 0.142301E+11 10460.67   -34.8 -34.9
Maximum of Months 0.467377E+11 22593.61   23.53 14.21 0.182326E+11 11349.25   21.83 14.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.415668E+11 23874.83 22-JAN-11:50 -6.6 -6.9 0.188593E+11 11319.72 14-JAN-18:10 -6.6 -6.9
February 0.389675E+11 25252.06 09-FEB-11:50 -2.0 -2.3 0.170395E+11 11319.71 25-FEB-18:10 -23.0 -23.5
March 0.462139E+11 27437.33 22-MAR-10:40 2.43 0.50 0.188753E+11 11319.66 04-MAR-18:10 2.43 0.50
April 0.486483E+11 29522.37 22-APR-10:50 12.33 5.78 0.182622E+11 11319.68 22-APR-17:10 14.13 6.18
May 0.543257E+11 30010.71 12-MAY-10:40 17.43 8.33 0.188716E+11 11319.65 06-MAY-17:10 17.43 8.33
June 0.543051E+11 30530.16 29-JUN-10:50 22.02 15.69 0.182659E+11 11319.68 10-JUN-17:10 22.02 15.69
July 0.561862E+11 31170.94 22-JUL-10:40 23.67 16.46 0.188681E+11 11319.69 29-JUL-17:10 29.53 18.36
August 0.545745E+11 30259.49 10-AUG-10:50 19.13 11.78 0.188753E+11 11319.69 26-AUG-17:10 21.02 13.58
September 0.492294E+11 29105.14 10-SEP-10:50 14.13 7.69 0.182615E+11 11319.66 09-SEP-17:10 14.13 7.69
October 0.468001E+11 27324.65 03-OCT-10:40 5.37 3.67 0.188688E+11 11319.66 28-OCT-17:10 -8.9 -9.3
November 0.404333E+11 23589.03 01-NOV-18:03 -8.9 -9.7 0.182564E+11 11319.72 25-NOV-18:10 -21.0 -21.2
December 0.408543E+11 24019.42 24-DEC-11:50 1.60 -0.2 0.188639E+11 11319.71 16-DEC-18:10 1.60 -0.2
                     
Annual Sum or Average 0.572105E+12         0.222168E+12        
Minimum of Months 0.389675E+11 23589.03   -8.9 -9.7 0.170395E+11 11319.65   -23.0 -23.5
Maximum of Months 0.561862E+11 31170.94   23.67 16.46 0.188753E+11 11319.72   29.53 18.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9 -15.4 0.125506E+10 745.68 26-JAN-01:10 -23.9 -24.2
February 55987551.74 1246.35 09-FEB-13:40 -0.4 -1.6 0.114623E+10 745.76 18-FEB-05:10 -23.9 -24.3
March 0.901630E+09 1655.72 22-MAR-10:35 2.43 0.50 0.127967E+10 801.35 22-MAR-21:49 1.78 0.04
April 0.349424E+10 3183.74 22-APR-14:00 15.60 7.03 0.137628E+10 978.46 21-APR-21:30 15.60 7.03
May 0.567114E+10 5096.20 31-MAY-14:10 20.18 10.25 0.164058E+10 1007.40 11-MAY-21:40 20.18 10.25
June 0.767092E+10 5931.37 29-JUN-14:20 25.77 16.19 0.165700E+10 1007.43 02-JUN-22:10 25.77 16.19
July 0.790840E+10 6315.14 23-JUL-13:40 25.00 15.26 0.170383E+10 1007.44 01-JUL-00:10 25.00 15.26
August 0.637706E+10 5364.19 10-AUG-15:10 22.30 12.06 0.168106E+10 1007.42 01-AUG-01:10 22.30 12.06
September 0.395224E+10 2301.80 02-SEP-15:13 16.70 10.68 0.141031E+10 958.60 01-SEP-21:40 16.70 10.68
October 0.145080E+10 1685.84 03-OCT-10:40 5.37 3.67 0.128640E+10 829.45 03-OCT-22:10 7.30 3.10
November 0.00 0.00 01-NOV-00:10 -10.0 -10.9 0.122671E+10 745.71 08-NOV-02:30 -24.1 -24.4
December 0.00 0.00 01-DEC-00:10 -25.8 -26.0 0.126655E+10 745.68 19-DEC-03:30 -24.5 -24.7
                     
Annual Sum or Average 0.374824E+11         0.169297E+11        
Minimum of Months 0.00 0.00   -25.8 -26.0 0.114623E+10 745.68   -24.5 -24.7
Maximum of Months 0.790840E+10 6315.14   25.77 16.19 0.170383E+10 1007.44   25.77 16.19



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9
February 0.00 0.00 01-FEB-00:05 -20.2
March 0.00 0.00 01-MAR-00:10 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:10 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.333037E+10 2589.64 13-JAN-16:10 -23.6
February 0.174687E+10 1924.71 28-FEB-08:07 -25.6
March 0.619540E+09 1918.99 01-MAR-08:10 -28.1
April 44499695.96 790.38 03-APR-06:05 -21.5
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 2738455.82 244.79 30-SEP-06:55 -5.0
October 0.463743E+09 1407.96 30-OCT-08:30 -16.7
November 0.286098E+10 2097.70 30-NOV-16:00 -25.6
December 0.407073E+10 2311.02 06-DEC-14:30 -25.0
         
Annual Sum or Average 0.131395E+11      
Minimum of Months 0.00 0.00   -28.1
Maximum of Months 0.407073E+10 2589.64   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 12908882.70 439.82 13-JAN-16:00 -23.9
February 951349.31 93.14 27-FEB-12:30 -30.9
March 0.00 0.00 01-MAR-00:10 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 3557497.93 178.81 29-NOV-10:51 -28.3
December 25435423.02 185.79 14-DEC-14:40 -24.6
         
Annual Sum or Average 42853152.96      
Minimum of Months 0.00 0.00   -30.9
Maximum of Months 25435423.02 439.82   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.122038E+10 1277.24 13-JAN-16:10 -23.6
February 0.831381E+09 1085.11 27-FEB-13:30 -29.4
March 0.333420E+09 991.78 01-MAR-05:00 -28.3
April 9079511.80 235.30 03-APR-09:30 -13.1
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 73842027.46 393.43 31-OCT-09:53 -16.7
November 0.994050E+09 1037.62 30-NOV-10:53 -28.9
December 0.146059E+10 1070.44 15-DEC-17:51 -29.4
         
Annual Sum or Average 0.492274E+10      
Minimum of Months 0.00 0.00   -29.4
Maximum of Months 0.146059E+10 1277.24   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.138978E+10 986.47 13-JAN-16:10 -23.6
February 0.103922E+10 870.14 27-FEB-17:51 -25.6
March 0.605453E+09 849.20 01-MAR-09:35 -24.6
April 63752961.80 380.05 03-APR-08:03 -17.1
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.233946E+09 488.26 27-OCT-09:10 -19.5
November 0.125498E+10 878.76 29-NOV-14:00 -24.4
December 0.159443E+10 896.56 06-DEC-14:00 -24.4
         
Annual Sum or Average 0.618157E+10      
Minimum of Months 0.00 0.00   -25.6
Maximum of Months 0.159443E+10 986.47   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9
February 0.00 0.00 01-FEB-00:05 -20.2
March 0.00 0.00 01-MAR-00:10 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:10 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.857207E+09 3954.95 13-JAN-15:00 -25.6
February 81533719.75 1772.98 27-FEB-15:00 -28.3
March 3744601.69 912.71 01-MAR-08:10 -28.1
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 6007962.70 1160.89 30-OCT-08:40 -16.7
November 0.516771E+09 2702.08 27-NOV-10:20 -27.2
December 0.157794E+10 3656.05 14-DEC-15:00 -24.4
         
Annual Sum or Average 0.304321E+10      
Minimum of Months 0.00 0.00   -28.3
Maximum of Months 0.157794E+10 3954.95   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 34442525.68 4274.50 13-JAN-14:40 -26.0
February 0.00 0.00 01-FEB-00:05 -20.2
March 0.00 0.00 01-MAR-00:10 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 820086.16 398.81 30-NOV-10:20 -28.5
December 16776189.05 847.86 14-DEC-14:40 -24.6
         
Annual Sum or Average 52038800.89      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 34442525.68 4274.50   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.296761E+10 2223.41 13-JAN-16:23 -23.0
February 0.211034E+10 2167.82 25-FEB-16:23 -21.9
March 0.137986E+10 2138.48 06-MAR-09:01 -15.2
April 0.297655E+09 2108.88 03-APR-08:62 -17.1
May 13333393.82 1252.93 01-MAY-08:03 10.87
June 2479320.86 1156.69 08-JUN-08:04 13.68
July 2783032.57 1194.51 06-JUL-08:03 14.60
August 7377653.88 1333.39 19-AUG-08:03 8.98
September 0.197054E+09 2086.24 28-SEP-08:61 -2.0
October 0.116663E+10 2147.27 27-OCT-08:62 -18.2
November 0.269030E+10 2182.86 26-NOV-16:23 -22.8
December 0.324781E+10 2198.85 06-DEC-16:23 -23.1
         
Annual Sum or Average 0.140832E+11      
Minimum of Months 2479320.86 1156.69   -23.1
Maximum of Months 0.324781E+10 2223.41   14.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.305446E+10 2339.03 12-JAN-17:54 -36.7
February 0.239343E+10 2119.38 24-FEB-16:12 -21.9
March 0.177767E+10 2108.18 03-MAR-09:02 -21.0
April 0.443303E+09 2068.87 03-APR-08:62 -17.1
May 17439668.52 1132.51 01-MAY-08:03 10.87
June 1543271.04 1057.52 06-JUN-08:04 11.28
July 2042581.17 1177.97 05-JUL-18:04 11.10
August 10755612.94 1207.02 14-AUG-18:04 15.40
September 0.273024E+09 2055.06 30-SEP-08:61 -5.0
October 0.138646E+10 2096.13 27-OCT-08:62 -18.2
November 0.284319E+10 2126.85 26-NOV-16:23 -22.8
December 0.327559E+10 2135.80 06-DEC-16:23 -23.1
         
Annual Sum or Average 0.154789E+11      
Minimum of Months 1543271.04 1057.52   -36.7
Maximum of Months 0.327559E+10 2339.03   15.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.544109E+09 461.24 12-JAN-04:10 -37.3
February 0.195410E+09 339.16 27-FEB-05:10 -36.1
March 17478172.67 312.03 01-MAR-05:00 -28.3
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 14248893.44 179.19 30-OCT-04:00 -14.4
November 0.426378E+09 368.86 29-NOV-05:00 -28.9
December 0.676985E+09 431.28 15-DEC-05:00 -33.3
         
Annual Sum or Average 0.187461E+10      
Minimum of Months 0.00 0.00   -37.3
Maximum of Months 0.676985E+09 461.24   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.590621E+09 633.98 12-JAN-10:53 -37.2
February 0.452629E+09 600.70 28-FEB-16:12 -22.6
March 0.314882E+09 598.96 02-MAR-16:11 -12.2
April 56219212.37 579.76 02-APR-15:11 -6.9
May 534998.05 488.00 26-MAY-15:14 5.73
June 59950.34 238.75 01-JUN-18:46 14.60
July 56146.91 169.60 31-JUL-21:56 19.60
August 188723.77 240.02 31-AUG-08:03 2.48
September 7051874.42 558.00 30-SEP-15:11 2.97
October 0.170012E+09 596.74 22-OCT-15:11 -9.4
November 0.548273E+09 598.98 25-NOV-16:12 -20.4
December 0.657189E+09 595.26 08-DEC-16:12 -22.1
         
Annual Sum or Average 0.279772E+10      
Minimum of Months 56146.91 169.60   -37.2
Maximum of Months 0.657189E+09 633.98   19.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.293459E+10 2185.92 13-JAN-16:23 -23.0
February 0.199225E+10 2133.67 25-FEB-16:23 -21.9
March 0.114733E+10 2097.97 01-MAR-19:02 -19.7
April 0.291994E+09 2057.73 04-APR-08:62 -8.0
May 8652388.29 1200.08 27-MAY-18:03 7.52
June 1123697.34 1117.16 24-JUN-18:04 12.12
July 1816418.12 1180.46 04-JUL-18:04 12.12
August 5500449.36 1155.64 14-AUG-08:04 11.88
September 0.157511E+09 2026.75 27-SEP-15:11 3.50
October 0.104024E+10 2114.45 27-OCT-08:62 -18.2
November 0.268427E+10 2146.65 26-NOV-16:23 -22.8
December 0.324152E+10 2161.25 06-DEC-16:23 -23.1
         
Annual Sum or Average 0.135068E+11      
Minimum of Months 1123697.34 1117.16   -23.1
Maximum of Months 0.324152E+10 2185.92   12.12



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.301886E+10 2286.87 12-JAN-17:54 -36.7
February 0.226094E+10 2091.27 28-FEB-16:12 -22.6
March 0.148929E+10 2074.91 02-MAR-16:11 -12.2
April 0.444176E+09 2022.65 03-APR-15:11 -5.4
May 12143178.51 1286.09 28-MAY-20:43 13.68
June 934058.07 1127.58 24-JUN-18:04 12.12
July 1147723.14 1105.36 26-JUL-08:04 12.38
August 7614152.65 1187.76 14-AUG-08:04 11.88
September 0.219846E+09 1999.08 27-SEP-15:11 3.50
October 0.123281E+10 2064.52 27-OCT-08:62 -18.2
November 0.283689E+10 2095.19 25-NOV-16:12 -20.4
December 0.326801E+10 2186.73 15-DEC-10:55 -33.3
         
Annual Sum or Average 0.147927E+11      
Minimum of Months 934058.07 1105.36   -36.7
Maximum of Months 0.326801E+10 2286.87   13.68



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.202894E+10 1895.98 13-JAN-16:10 -23.6
February 0.953700E+09 1555.00 27-FEB-16:00 -27.2
March 0.173309E+09 1277.60 01-MAR-08:63 -28.1
April 7257784.76 417.85 03-APR-08:03 -17.1
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.194908E+09 1064.76 30-OCT-08:03 -16.7
November 0.167360E+10 1646.35 27-NOV-15:00 -23.9
December 0.252186E+10 1759.91 06-DEC-14:00 -24.4
         
Annual Sum or Average 0.755357E+10      
Minimum of Months 0.00 0.00   -28.1
Maximum of Months 0.252186E+10 1895.98   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.393384E+10 2744.39 12-JAN-17:54 -36.7
February 0.288585E+10 2572.58 25-FEB-16:23 -21.9
March 0.197155E+10 2525.60 15-MAR-08:62 -22.4
April 0.502266E+09 2484.92 03-APR-08:62 -17.1
May 46188933.31 1702.56 27-MAY-08:62 0.68
June 2257436.84 1197.15 25-JUN-18:03 13.98
July 3127910.67 1020.10 06-JUL-08:03 14.60
August 22922525.50 2333.73 30-AUG-08:62 2.07
September 0.375172E+09 2472.10 30-SEP-08:61 -5.0
October 0.170025E+10 2536.14 27-OCT-08:62 -18.2
November 0.361824E+10 2593.74 26-NOV-16:23 -22.8
December 0.427074E+10 2776.01 15-DEC-17:54 -29.4
         
Annual Sum or Average 0.193324E+11      
Minimum of Months 2257436.84 1020.10   -36.7
Maximum of Months 0.427074E+10 2776.01   14.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.402945E+10 2720.15 12-JAN-07:53 -38.3
February 0.320415E+10 2496.66 25-FEB-16:23 -21.9
March 0.246234E+10 2476.72 03-MAR-09:02 -21.0
April 0.713959E+09 2425.44 03-APR-08:62 -17.1
May 58149913.41 1901.72 27-MAY-08:62 0.68
June 2138945.89 1108.56 28-JUN-08:04 11.97
July 2240753.16 1099.73 04-JUL-18:04 12.12
August 29659854.82 2281.80 31-AUG-08:62 2.48
September 0.505275E+09 2406.98 30-SEP-08:61 -5.0
October 0.197062E+10 2460.91 27-OCT-08:62 -18.2
November 0.378858E+10 2510.57 26-NOV-16:23 -22.8
December 0.429932E+10 2523.05 06-DEC-16:23 -23.1
         
Annual Sum or Average 0.210659E+11      
Minimum of Months 2138945.89 1099.73   -38.3
Maximum of Months 0.429932E+10 2720.15   12.12



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.175070E+10 1480.13 13-JAN-16:23 -23.0
February 0.102894E+10 1432.45 01-FEB-16:23 -12.2
March 0.556892E+09 1389.15 13-MAR-08:62 -23.0
April 0.102204E+09 1375.43 03-APR-08:62 -17.1
May 5898444.86 915.41 01-MAY-08:03 10.87
June 1313406.90 679.19 25-JUN-15:14 12.77
July 1297586.01 631.95 06-JUL-08:03 14.60
August 2542250.64 719.20 20-AUG-08:03 6.78
September 55700719.46 1342.21 28-SEP-08:61 -2.0
October 0.503194E+09 1406.99 30-OCT-08:62 -16.7
November 0.152528E+10 1448.78 17-NOV-16:23 -18.6
December 0.201149E+10 1471.86 06-DEC-16:23 -23.1
         
Annual Sum or Average 0.754546E+10      
Minimum of Months 1297586.01 631.95   -23.1
Maximum of Months 0.201149E+10 1480.13   14.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9
February 0.00 0.00 01-FEB-00:05 -20.2
March 0.00 0.00 01-MAR-00:10 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:10 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9
February 0.00 0.00 01-FEB-00:05 -20.2
March 0.00 0.00 01-MAR-00:10 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:10 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9
February 0.00 0.00 01-FEB-00:05 -20.2
March 0.00 0.00 01-MAR-00:10 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:10 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.748353E+10 5609.02 13-JAN-16:10 -23.6
February 0.462283E+10 4497.06 28-FEB-07:10 -25.6
March 0.183869E+10 4512.47 01-MAR-08:25 -27.8
April 0.172076E+09 2370.44 03-APR-06:10 -21.5
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 1554212.19 261.05 30-SEP-06:55 -5.0
October 0.110514E+10 3050.48 27-OCT-08:15 -18.5
November 0.693957E+10 4896.51 30-NOV-16:00 -25.6
December 0.886588E+10 5119.37 06-DEC-15:30 -24.5
         
Annual Sum or Average 0.310293E+11      
Minimum of Months 0.00 0.00   -27.8
Maximum of Months 0.886588E+10 5609.02   16.35



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104372E+11 10053.14 02-JAN-20:10 0.121516E+11 9632.53 02-JAN-20:10
February 0.942384E+10 10053.14 01-FEB-20:10 0.109726E+11 9632.53 01-FEB-20:10
March 0.104694E+11 10053.14 01-MAR-20:10 0.121771E+11 9632.53 01-MAR-20:10
April 0.100833E+11 10053.14 03-APR-19:10 0.117446E+11 9632.53 03-APR-19:10
May 0.104553E+11 10053.14 01-MAY-19:10 0.121662E+11 9632.53 01-MAY-19:10
June 0.101296E+11 10053.14 01-JUN-19:10 0.117829E+11 9632.53 01-JUN-19:10
July 0.104091E+11 10053.14 03-JUL-19:10 0.121279E+11 9632.53 03-JUL-19:10
August 0.104734E+11 10053.14 01-AUG-19:10 0.121808E+11 9632.53 01-AUG-19:10
September 0.100874E+11 10053.14 01-SEP-19:10 0.117482E+11 9632.53 01-SEP-19:10
October 0.104332E+11 10053.14 02-OCT-19:10 0.121479E+11 9632.53 02-OCT-19:10
November 0.101215E+11 10053.14 01-NOV-19:10 0.117774E+11 9632.53 01-NOV-19:10
December 0.104091E+11 10053.14 01-DEC-20:10 0.121279E+11 9632.53 01-DEC-20:10
             
Annual Sum or Average 0.122932E+12     0.143105E+12    
Minimum of Months 0.942384E+10 10053.14   0.109726E+11 9632.53  
Maximum of Months 0.104734E+11 10053.14   0.121808E+11 9632.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.531884E+09 512.31 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.480243E+09 512.31 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.533523E+09 512.31 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.513850E+09 512.31 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.532806E+09 512.31 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.516207E+09 512.31 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.530449E+09 512.31 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.533728E+09 512.31 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.514055E+09 512.31 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.531679E+09 512.31 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.515797E+09 512.31 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.530449E+09 512.31 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.626467E+10     0.101856E+11    
Minimum of Months 0.480243E+09 512.31   0.780982E+09 685.60  
Maximum of Months 0.533728E+09 512.31   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.615923E+09 593.26 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.556123E+09 593.26 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.617822E+09 593.26 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.595041E+09 593.26 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.616991E+09 593.26 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.597770E+09 593.26 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.614262E+09 593.26 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.618059E+09 593.26 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.595278E+09 593.26 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.615686E+09 593.26 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.597295E+09 593.26 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.614262E+09 593.26 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.725451E+10     0.117950E+11    
Minimum of Months 0.556123E+09 593.26   0.904380E+09 793.93  
Maximum of Months 0.618059E+09 593.26   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.710312E+09 684.18 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.641347E+09 684.18 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.712502E+09 684.18 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.686229E+09 684.18 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.711544E+09 684.18 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.689376E+09 684.18 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.708397E+09 684.18 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.712775E+09 684.18 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.686503E+09 684.18 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.710039E+09 684.18 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.688829E+09 684.18 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.708397E+09 684.18 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.836625E+10     0.124712E+11    
Minimum of Months 0.641347E+09 684.18   0.956227E+09 839.45  
Maximum of Months 0.712775E+09 684.18   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.195918E+09 188.71 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.176896E+09 188.71 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.196522E+09 188.71 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.189275E+09 188.71 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.196257E+09 188.71 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.190143E+09 188.71 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.195389E+09 188.71 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.196597E+09 188.71 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.189351E+09 188.71 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.195842E+09 188.71 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.189992E+09 188.71 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.195389E+09 188.71 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.230757E+10     0.359760E+10    
Minimum of Months 0.176896E+09 188.71   0.275845E+09 242.16  
Maximum of Months 0.196597E+09 188.71   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.415991E+09 400.68 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.375602E+09 400.68 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.417273E+09 400.68 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.401887E+09 400.68 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.416712E+09 400.68 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.403730E+09 400.68 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.414869E+09 400.68 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.417433E+09 400.68 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.402047E+09 400.68 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.415830E+09 400.68 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.403409E+09 400.68 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.414869E+09 400.68 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.489965E+10     0.679355E+11    
Minimum of Months 0.375602E+09 400.68   0.520895E+10 4572.80  
Maximum of Months 0.417433E+09 400.68   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.150742E+10 1573.46 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.121599E+10 1573.46 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.116335E+10 1573.46 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.815738E+09 1573.46 03-APR-19:40 0.117692E+10 965.27 03-APR-19:10
May 0.719412E+09 1398.63 04-MAY-20:30 0.121917E+10 965.27 01-MAY-19:10
June 0.589381E+09 1214.60 02-JUN-20:00 0.118076E+10 965.27 01-JUN-19:10
July 0.655449E+09 1263.59 28-JUL-20:00 0.121533E+10 965.27 03-JUL-19:10
August 0.835107E+09 1573.46 29-AUG-19:30 0.122063E+10 965.27 01-AUG-19:10
September 0.104808E+10 1573.46 01-SEP-19:30 0.117729E+10 965.27 01-SEP-19:10
October 0.129369E+10 1573.46 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.139489E+10 1573.46 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.157259E+10 1573.46 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.128111E+11     0.143405E+11    
Minimum of Months 0.589381E+09 1214.60   0.109956E+10 965.27  
Maximum of Months 0.157259E+10 1573.46   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.818709E+10 7984.04 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.725700E+10 7984.04 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.789805E+10 7984.04 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.735588E+10 7984.04 03-APR-19:40 0.122282E+11 10029.21 03-APR-19:10
May 0.752271E+10 7809.31 02-MAY-19:00 0.126672E+11 10029.21 01-MAY-19:10
June 0.719448E+10 7667.15 02-JUN-19:00 0.122682E+11 10029.21 01-JUN-19:10
July 0.744075E+10 7625.65 28-JUL-19:00 0.126273E+11 10029.21 03-JUL-19:10
August 0.763635E+10 7984.04 29-AUG-19:30 0.126824E+11 10029.21 01-AUG-19:10
September 0.755492E+10 7984.04 01-SEP-19:30 0.122320E+11 10029.21 01-SEP-19:10
October 0.798827E+10 7984.04 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.787865E+10 7984.04 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.822770E+10 7984.04 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.921419E+11     0.148998E+12    
Minimum of Months 0.719448E+10 7625.65   0.114244E+11 10029.21  
Maximum of Months 0.822770E+10 7984.04   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104684E+09 94.72 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 94540036.54 94.72 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.103852E+09 94.72 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.101428E+09 94.72 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.104268E+09 94.72 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.100623E+09 94.72 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.105087E+09 94.72 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.103852E+09 94.72 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.101455E+09 94.72 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.104671E+09 94.72 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.101025E+09 94.72 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.105100E+09 94.72 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.123059E+10     0.261953E+10    
Minimum of Months 94540036.54 94.72   0.200969E+09 237.06  
Maximum of Months 0.105100E+09 94.72   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104672E+09 94.71 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 94528959.80 94.71 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.103840E+09 94.71 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.101416E+09 94.71 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.104256E+09 94.71 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.100611E+09 94.71 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.105074E+09 94.71 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.103840E+09 94.71 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.101443E+09 94.71 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.104658E+09 94.71 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.101014E+09 94.71 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.105088E+09 94.71 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.123044E+10     0.261922E+10    
Minimum of Months 94528959.80 94.71   0.200945E+09 237.03  
Maximum of Months 0.105088E+09 94.71   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 65789991.58 59.53 01-JAN-19:10 0.217935E+09 232.19 01-JAN-08:09
February 59414784.75 59.53 01-FEB-20:10 0.196843E+09 232.19 01-FEB-07:10
March 65267117.48 59.53 01-MAR-20:10 0.217824E+09 232.19 01-MAR-07:10
April 63743496.62 59.53 01-APR-18:10 0.210923E+09 232.19 01-APR-07:10
May 65528554.53 59.53 01-MAY-19:10 0.217879E+09 232.19 01-MAY-06:10
June 63237765.93 59.53 01-JUN-19:10 0.210812E+09 232.19 01-JUN-06:10
July 66042856.93 59.53 01-JUL-18:10 0.217991E+09 232.19 01-JUL-07:10
August 65267117.48 59.53 01-AUG-19:10 0.217824E+09 232.19 01-AUG-06:10
September 63760640.03 59.53 01-SEP-19:10 0.210923E+09 232.19 01-SEP-06:10
October 65781419.88 59.53 01-OCT-18:10 0.217935E+09 232.19 01-OCT-07:10
November 63490631.27 59.53 01-NOV-19:10 0.210867E+09 232.19 01-NOV-06:10
December 66051428.64 59.53 01-DEC-20:10 0.217991E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.773376E+09     0.256575E+10    
Minimum of Months 59414784.75 59.53   0.196843E+09 232.19  
Maximum of Months 66051428.64 59.53   0.217991E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 65807981.74 59.54 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 59431031.62 59.54 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 65284964.65 59.54 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 63760927.16 59.54 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 65546473.20 59.54 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 63255058.18 59.54 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 66060916.23 59.54 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 65284964.65 59.54 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 63778075.26 59.54 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 65799407.69 59.54 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 63507992.67 59.54 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 66069490.28 59.54 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.773587E+09     0.256645E+10    
Minimum of Months 59431031.62 59.54   0.196897E+09 232.26  
Maximum of Months 66069490.28 59.54   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104684E+09 94.72 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 94540036.54 94.72 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.103852E+09 94.72 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.101428E+09 94.72 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.104268E+09 94.72 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.100623E+09 94.72 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.105087E+09 94.72 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.103852E+09 94.72 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.101455E+09 94.72 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.104671E+09 94.72 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.101025E+09 94.72 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.105100E+09 94.72 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.123059E+10     0.261953E+10    
Minimum of Months 94540036.54 94.72   0.200969E+09 237.06  
Maximum of Months 0.105100E+09 94.72   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104672E+09 94.71 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 94528959.80 94.71 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.103840E+09 94.71 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.101416E+09 94.71 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.104256E+09 94.71 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.100611E+09 94.71 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.105074E+09 94.71 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.103840E+09 94.71 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.101443E+09 94.71 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.104658E+09 94.71 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.101014E+09 94.71 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.105088E+09 94.71 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.123044E+10     0.261922E+10    
Minimum of Months 94528959.80 94.71   0.200945E+09 237.03  
Maximum of Months 0.105088E+09 94.71   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.120431E+10 1160.00 02-JAN-20:10 0.00 0.00
February 0.108739E+10 1160.00 01-FEB-20:10 0.00 0.00
March 0.120803E+10 1160.00 01-MAR-20:10 0.00 0.00
April 0.116348E+10 1160.00 03-APR-19:10 0.00 0.00
May 0.120640E+10 1160.00 01-MAY-19:10 0.00 0.00
June 0.116882E+10 1160.00 01-JUN-19:10 0.00 0.00
July 0.120107E+10 1160.00 03-JUL-19:10 0.00 0.00
August 0.120849E+10 1160.00 01-AUG-19:10 0.00 0.00
September 0.116395E+10 1160.00 01-SEP-19:10 0.00 0.00
October 0.120385E+10 1160.00 02-OCT-19:10 0.00 0.00
November 0.116789E+10 1160.00 01-NOV-19:10 0.00 0.00
December 0.120107E+10 1160.00 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.141847E+11     0.00 0.00
Minimum of Months 0.108739E+10 1160.00   0.00 0.00
Maximum of Months 0.120849E+10 1160.00   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104684E+09 94.72 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 94540036.54 94.72 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.103852E+09 94.72 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.101428E+09 94.72 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.104268E+09 94.72 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.100623E+09 94.72 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.105087E+09 94.72 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.103852E+09 94.72 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.101455E+09 94.72 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.104671E+09 94.72 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.101025E+09 94.72 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.105100E+09 94.72 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.123059E+10     0.261953E+10    
Minimum of Months 94540036.54 94.72   0.200969E+09 237.06  
Maximum of Months 0.105100E+09 94.72   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104672E+09 94.71 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 94528959.80 94.71 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.103840E+09 94.71 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.101416E+09 94.71 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.104256E+09 94.71 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.100611E+09 94.71 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.105074E+09 94.71 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.103840E+09 94.71 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.101443E+09 94.71 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.104658E+09 94.71 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.101014E+09 94.71 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.105088E+09 94.71 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.123044E+10     0.261922E+10    
Minimum of Months 94528959.80 94.71   0.200945E+09 237.03  
Maximum of Months 0.105088E+09 94.71   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 65807981.74 59.54 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 59431031.62 59.54 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 65284964.65 59.54 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 63760927.16 59.54 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 65546473.20 59.54 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 63255058.18 59.54 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 66060916.23 59.54 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 65284964.65 59.54 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 63778075.26 59.54 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 65799407.69 59.54 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 63507992.67 59.54 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 66069490.28 59.54 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.773587E+09     0.256645E+10    
Minimum of Months 59431031.62 59.54   0.196897E+09 232.26  
Maximum of Months 66069490.28 59.54   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.281025E+10 2763.12 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.241048E+10 2763.12 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.248641E+10 2763.12 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.207938E+10 2763.12 03-APR-19:40 0.144540E+11 6747.90 01-APR-06:10
May 0.199717E+10 2456.11 04-MAY-20:30 0.149358E+11 6747.90 01-MAY-06:10
June 0.183788E+10 2332.05 02-JUN-19:00 0.144540E+11 6747.90 01-JUN-06:10
July 0.194254E+10 2341.32 26-JUL-20:00 0.149358E+11 6747.90 01-JUL-06:10
August 0.214270E+10 2763.12 29-AUG-19:30 0.149358E+11 6747.90 01-AUG-06:10
September 0.232873E+10 2763.12 01-SEP-19:30 0.144540E+11 6747.90 01-SEP-06:10
October 0.260940E+10 2763.12 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.268158E+10 2763.12 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.284327E+10 2763.12 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.281698E+11     0.175857E+12    
Minimum of Months 0.183788E+10 2332.05   0.134904E+11 6747.90  
Maximum of Months 0.284327E+10 2763.12   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.281025E+10 2763.12 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.241048E+10 2763.12 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.248641E+10 2763.12 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.207938E+10 2763.12 03-APR-19:40 0.144540E+11 6747.90 01-APR-06:10
May 0.199717E+10 2456.11 04-MAY-20:30 0.149358E+11 6747.90 01-MAY-06:10
June 0.183788E+10 2332.05 02-JUN-19:00 0.144540E+11 6747.90 01-JUN-06:10
July 0.194254E+10 2341.32 26-JUL-20:00 0.149358E+11 6747.90 01-JUL-06:10
August 0.214270E+10 2763.12 29-AUG-19:30 0.149358E+11 6747.90 01-AUG-06:10
September 0.232873E+10 2763.12 01-SEP-19:30 0.144540E+11 6747.90 01-SEP-06:10
October 0.260940E+10 2763.12 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.268158E+10 2763.12 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.284327E+10 2763.12 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.281698E+11     0.175857E+12    
Minimum of Months 0.183788E+10 2332.05   0.134904E+11 6747.90  
Maximum of Months 0.284327E+10 2763.12   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.113250E+10 1090.83 02-JAN-20:10 0.360126E+11 16179.04 01-JAN-07:10
February 0.102255E+10 1090.83 01-FEB-20:10 0.325275E+11 16179.04 01-FEB-07:10
March 0.113599E+10 1090.83 01-MAR-20:10 0.360126E+11 16179.04 01-MAR-07:10
April 0.109410E+10 1090.83 03-APR-19:10 0.348509E+11 16179.04 01-APR-06:10
May 0.113446E+10 1090.83 01-MAY-19:10 0.360126E+11 16179.04 01-MAY-06:10
June 0.109912E+10 1090.83 01-JUN-19:10 0.348509E+11 16179.04 01-JUN-06:10
July 0.112945E+10 1090.83 03-JUL-19:10 0.360126E+11 16179.04 01-JUL-06:10
August 0.113643E+10 1090.83 01-AUG-19:10 0.360126E+11 16179.04 01-AUG-06:10
September 0.109454E+10 1090.83 01-SEP-19:10 0.348509E+11 16179.04 01-SEP-06:10
October 0.113207E+10 1090.83 02-OCT-19:10 0.360126E+11 16179.04 01-OCT-06:10
November 0.109825E+10 1090.83 01-NOV-19:10 0.348509E+11 16179.04 01-NOV-06:10
December 0.112945E+10 1090.83 01-DEC-20:10 0.360126E+11 16179.04 01-DEC-07:10
             
Annual Sum or Average 0.133389E+11     0.424019E+12    
Minimum of Months 0.102255E+10 1090.83   0.325275E+11 16179.04  
Maximum of Months 0.113643E+10 1090.83   0.360126E+11 16179.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.127458E+10 1227.68 02-JAN-20:10 0.00 0.00
February 0.115083E+10 1227.68 01-FEB-20:10 0.00 0.00
March 0.127851E+10 1227.68 01-MAR-20:10 0.00 0.00
April 0.123137E+10 1227.68 03-APR-19:10 0.00 0.00
May 0.127679E+10 1227.68 01-MAY-19:10 0.00 0.00
June 0.123701E+10 1227.68 01-JUN-19:10 0.00 0.00
July 0.127114E+10 1227.68 03-JUL-19:10 0.00 0.00
August 0.127900E+10 1227.68 01-AUG-19:10 0.00 0.00
September 0.123186E+10 1227.68 01-SEP-19:10 0.00 0.00
October 0.127409E+10 1227.68 02-OCT-19:10 0.00 0.00
November 0.123603E+10 1227.68 01-NOV-19:10 0.00 0.00
December 0.127114E+10 1227.68 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.150123E+11     0.00 0.00
Minimum of Months 0.115083E+10 1227.68   0.00 0.00
Maximum of Months 0.127900E+10 1227.68   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.104372E+11 0.121516E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.942384E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.104694E+11 0.121771E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.100833E+11 0.117446E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.104553E+11 0.121662E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.101296E+11 0.117829E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.104091E+11 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.104734E+11 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.100874E+11 0.117482E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.104332E+11 0.121479E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.101215E+11 0.117774E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.104091E+11 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.122932E+12 0.143105E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.942384E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.104734E+11 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.531884E+09 0.864900E+09 0.00 0.00 0.00 0.00 0.00 0.137302E+10
February 0.179968E+10 0.480243E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.118001E+10
March 0.199990E+10 0.533523E+09 0.866718E+09 0.00 0.00 0.00 0.00 0.00 0.111435E+10
April 0.192973E+10 0.513850E+09 0.835931E+09 0.00 0.00 0.00 0.00 0.00 0.702452E+09
May 0.199475E+10 0.532806E+09 0.865939E+09 0.00 0.00 0.00 0.00 0.00 0.403260E+09
June 0.193394E+10 0.516207E+09 0.838659E+09 0.00 0.00 0.00 0.00 1755291.53 0.236969E+09
July 0.199054E+10 0.530449E+09 0.863211E+09 0.00 0.00 0.00 0.00 4086284.89 0.216818E+09
August 0.199896E+10 0.533728E+09 0.866978E+09 0.00 0.00 0.00 0.00 439955.11 0.293593E+09
September 0.192879E+10 0.514055E+09 0.836191E+09 0.00 0.00 0.00 0.00 0.00 0.487487E+09
October 0.199148E+10 0.531679E+09 0.864640E+09 0.00 0.00 0.00 0.00 0.00 0.830476E+09
November 0.192552E+10 0.515797E+09 0.838269E+09 0.00 0.00 0.00 0.00 0.00 0.133921E+10
December 0.199054E+10 0.530449E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.00 0.144790E+10
                   
Annual Sum or Average 0.234744E+11 0.626467E+10 0.101856E+11 0.00 0.00 0.00 0.00 6281531.53 0.962554E+10
Minimum of Months 0.179968E+10 0.480243E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.216818E+09
Maximum of Months 0.199990E+10 0.533728E+09 0.866978E+09 0.00 0.00 0.00 0.00 4086284.89 0.144790E+10



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.615923E+09 0.100156E+10 0.00 0.00 0.00 0.00 0.00 0.531835E+09
February 0.208403E+10 0.556123E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 0.455473E+09
March 0.231589E+10 0.617822E+09 0.100366E+10 0.00 0.00 0.00 0.00 0.00 0.426985E+09
April 0.223463E+10 0.595041E+09 0.968011E+09 0.00 0.00 0.00 0.00 0.00 0.266867E+09
May 0.230993E+10 0.616991E+09 0.100276E+10 0.00 0.00 0.00 0.00 0.00 0.150089E+09
June 0.223950E+10 0.597770E+09 0.971170E+09 0.00 0.00 0.00 0.00 1206917.68 85518103.07
July 0.230505E+10 0.614262E+09 0.999601E+09 0.00 0.00 0.00 0.00 2858419.49 78640572.41
August 0.231480E+10 0.618059E+09 0.100396E+10 0.00 0.00 0.00 0.00 433322.44 0.108656E+09
September 0.223354E+10 0.595278E+09 0.968312E+09 0.00 0.00 0.00 0.00 0.00 0.188571E+09
October 0.230614E+10 0.615686E+09 0.100126E+10 0.00 0.00 0.00 0.00 0.00 0.322343E+09
November 0.222975E+10 0.597295E+09 0.970719E+09 0.00 0.00 0.00 0.00 0.00 0.517365E+09
December 0.230505E+10 0.614262E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.00 0.559591E+09
                   
Annual Sum or Average 0.271834E+11 0.725451E+10 0.117950E+11 0.00 0.00 0.00 0.00 4498659.62 0.369193E+10
Minimum of Months 0.208403E+10 0.556123E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 78640572.41
Maximum of Months 0.231589E+10 0.618059E+09 0.100396E+10 0.00 0.00 0.00 0.00 2858419.49 0.559591E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.710312E+09 0.105898E+10 0.00 0.00 0.00 0.00 0.00 0.125721E+10
February 0.440737E+09 0.641347E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.107714E+10
March 0.489771E+09 0.712502E+09 0.106120E+10 0.00 0.00 0.00 0.00 0.00 0.101240E+10
April 0.472586E+09 0.686229E+09 0.102351E+10 0.00 0.00 0.00 0.00 0.00 0.653740E+09
May 0.488511E+09 0.711544E+09 0.106025E+10 0.00 0.00 0.00 0.00 0.00 0.394381E+09
June 0.473617E+09 0.689376E+09 0.102685E+10 0.00 0.00 0.00 0.00 1600967.05 0.229003E+09
July 0.487480E+09 0.708397E+09 0.105691E+10 0.00 0.00 0.00 0.00 3727217.93 0.211808E+09
August 0.489542E+09 0.712775E+09 0.106152E+10 0.00 0.00 0.00 0.00 401223.34 0.289266E+09
September 0.472357E+09 0.686503E+09 0.102382E+10 0.00 0.00 0.00 0.00 0.00 0.489836E+09
October 0.487709E+09 0.710039E+09 0.105866E+10 0.00 0.00 0.00 0.00 0.00 0.785919E+09
November 0.471555E+09 0.688829E+09 0.102637E+10 0.00 0.00 0.00 0.00 0.00 0.122255E+10
December 0.487480E+09 0.708397E+09 0.105691E+10 0.00 0.00 0.00 0.00 0.00 0.132275E+10
                   
Annual Sum or Average 0.574883E+10 0.836625E+10 0.124712E+11 0.00 0.00 0.00 0.00 5729408.32 0.894601E+10
Minimum of Months 0.440737E+09 0.641347E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.211808E+09
Maximum of Months 0.489771E+09 0.712775E+09 0.106152E+10 0.00 0.00 0.00 0.00 3727217.93 0.132275E+10



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.195918E+09 0.305485E+09 0.00 0.00 0.00 0.00 0.00 0.723699E+09
February 0.339028E+09 0.176896E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 0.619799E+09
March 0.376747E+09 0.196522E+09 0.306128E+09 0.00 0.00 0.00 0.00 0.00 0.578310E+09
April 0.363528E+09 0.189275E+09 0.295253E+09 0.00 0.00 0.00 0.00 0.00 0.347397E+09
May 0.375778E+09 0.196257E+09 0.305852E+09 0.00 0.00 0.00 0.00 8214.90 0.184450E+09
June 0.364321E+09 0.190143E+09 0.296217E+09 0.00 0.00 0.00 0.00 2686101.48 0.101094E+09
July 0.374985E+09 0.195389E+09 0.304889E+09 0.00 0.00 0.00 0.00 5912628.39 93253469.73
August 0.376571E+09 0.196597E+09 0.306219E+09 0.00 0.00 0.00 0.00 1389973.87 0.130784E+09
September 0.363352E+09 0.189351E+09 0.295345E+09 0.00 0.00 0.00 0.00 0.00 0.240986E+09
October 0.375161E+09 0.195842E+09 0.305393E+09 0.00 0.00 0.00 0.00 0.00 0.432844E+09
November 0.362735E+09 0.189992E+09 0.296079E+09 0.00 0.00 0.00 0.00 0.00 0.704723E+09
December 0.374985E+09 0.195389E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.00 0.762534E+09
                   
Annual Sum or Average 0.442217E+10 0.230757E+10 0.359760E+10 0.00 0.00 0.00 0.00 9996918.64 0.491987E+10
Minimum of Months 0.339028E+09 0.176896E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 93253469.73
Maximum of Months 0.376747E+09 0.196597E+09 0.306219E+09 0.00 0.00 0.00 0.00 5912628.39 0.762534E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.415991E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 0.00 0.185049E+10
February 0.139600E+10 0.375602E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.158760E+10
March 0.155131E+10 0.417273E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 0.00 0.149894E+10
April 0.149688E+10 0.401887E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 0.00 0.941208E+09
May 0.154732E+10 0.416712E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 0.00 0.541521E+09
June 0.150015E+10 0.403730E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 2185083.87 0.312710E+09
July 0.154405E+10 0.414869E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 5088899.19 0.289240E+09
August 0.155059E+10 0.417433E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 547482.99 0.395271E+09
September 0.149615E+10 0.402047E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 0.00 0.683902E+09
October 0.154478E+10 0.415830E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 0.00 0.115064E+10
November 0.149361E+10 0.403409E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 0.00 0.179738E+10
December 0.154405E+10 0.414869E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.00 0.193988E+10
                   
Annual Sum or Average 0.182090E+11 0.489965E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 7821466.05 0.129888E+11
Minimum of Months 0.139600E+10 0.375602E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.289240E+09
Maximum of Months 0.155131E+10 0.417433E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 5088899.19 0.193988E+10



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.150742E+10 0.121771E+10 0.00 0.00 0.00 0.00 0.00 0.304118E+10
February 0.236489E+11 0.121599E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.260706E+10
March 0.262800E+11 0.116335E+10 0.122027E+10 0.00 0.00 0.00 0.00 0.00 0.245929E+10
April 0.253579E+11 0.815738E+09 0.117692E+10 0.00 0.00 0.00 0.00 0.00 0.154048E+10
May 0.262123E+11 0.719412E+09 0.121917E+10 0.00 0.00 0.00 0.00 0.00 0.850178E+09
June 0.254132E+11 0.589381E+09 0.118076E+10 0.00 0.00 0.00 0.00 5439920.53 0.470701E+09
July 0.261570E+11 0.655449E+09 0.121533E+10 0.00 0.00 0.00 0.00 12421232.90 0.425801E+09
August 0.262677E+11 0.835107E+09 0.122063E+10 0.00 0.00 0.00 0.00 1438477.37 0.601122E+09
September 0.253456E+11 0.104808E+10 0.117729E+10 0.00 0.00 0.00 0.00 0.00 0.106834E+10
October 0.261693E+11 0.129369E+10 0.121734E+10 0.00 0.00 0.00 0.00 0.00 0.184024E+10
November 0.253025E+11 0.139489E+10 0.118021E+10 0.00 0.00 0.00 0.00 0.00 0.296069E+10
December 0.261570E+11 0.157259E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.00 0.320248E+10
                   
Annual Sum or Average 0.308468E+12 0.128111E+11 0.143405E+11 0.00 0.00 0.00 0.00 19299630.81 0.210676E+11
Minimum of Months 0.236489E+11 0.589381E+09 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.425801E+09
Maximum of Months 0.262800E+11 0.157259E+10 0.122063E+10 0.00 0.00 0.00 0.00 12421232.90 0.320248E+10



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.818709E+10 0.126520E+11 0.00 0.00 0.00 0.00 0.00 0.874719E+10
February 0.702046E+11 0.725700E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.750182E+10
March 0.780153E+11 0.789805E+10 0.126786E+11 0.00 0.00 0.00 0.00 0.00 0.708362E+10
April 0.752779E+11 0.735588E+10 0.122282E+11 0.00 0.00 0.00 0.00 0.00 0.447004E+10
May 0.778146E+11 0.752271E+10 0.126672E+11 0.00 0.00 0.00 0.00 0.00 0.253378E+10
June 0.754422E+11 0.719448E+10 0.122682E+11 0.00 0.00 0.00 0.00 17131326.56 0.144453E+10
July 0.776503E+11 0.744075E+10 0.126273E+11 0.00 0.00 0.00 0.00 39144578.78 0.132925E+10
August 0.779788E+11 0.763635E+10 0.126824E+11 0.00 0.00 0.00 0.00 4688172.14 0.183779E+10
September 0.752414E+11 0.755492E+10 0.122320E+11 0.00 0.00 0.00 0.00 0.00 0.318183E+10
October 0.776868E+11 0.798827E+10 0.126482E+11 0.00 0.00 0.00 0.00 0.00 0.537467E+10
November 0.751137E+11 0.787865E+10 0.122624E+11 0.00 0.00 0.00 0.00 0.00 0.850843E+10
December 0.776503E+11 0.822770E+10 0.126273E+11 0.00 0.00 0.00 0.00 0.00 0.918240E+10
                   
Annual Sum or Average 0.915726E+12 0.921419E+11 0.148998E+12 0.00 0.00 0.00 0.00 60964077.47 0.611954E+11
Minimum of Months 0.702046E+11 0.719448E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.132925E+10
Maximum of Months 0.780153E+11 0.822770E+10 0.126824E+11 0.00 0.00 0.00 0.00 39144578.78 0.918240E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104684E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.788375E+09
February 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.674275E+09
March 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.00 0.633059E+09
April 0.293479E+09 0.101428E+09 0.215344E+09 0.00 0.00 0.00 0.00 0.00 0.390699E+09
May 0.303504E+09 0.104268E+09 0.222446E+09 0.00 0.00 0.00 0.00 28767.82 0.209961E+09
June 0.293842E+09 0.100623E+09 0.215230E+09 0.00 0.00 0.00 0.00 3090449.08 0.108655E+09
July 0.303141E+09 0.105087E+09 0.222560E+09 0.00 0.00 0.00 0.00 6264298.59 98352082.08
August 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 1549567.31 0.143436E+09
September 0.293479E+09 0.101455E+09 0.215344E+09 0.00 0.00 0.00 0.00 0.00 0.270003E+09
October 0.303322E+09 0.104671E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.471608E+09
November 0.293661E+09 0.101025E+09 0.215287E+09 0.00 0.00 0.00 0.00 0.00 0.766345E+09
December 0.303141E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.829794E+09
                   
Annual Sum or Average 0.357224E+10 0.123059E+10 0.261953E+10 0.00 0.00 0.00 0.00 10933082.81 0.538456E+10
Minimum of Months 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 0.00 98352082.08
Maximum of Months 0.303685E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 6264298.59 0.829794E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104672E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.787916E+09
February 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.673618E+09
March 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.00 0.628260E+09
April 0.293479E+09 0.101416E+09 0.215319E+09 0.00 0.00 0.00 0.00 0.00 0.384151E+09
May 0.303504E+09 0.104256E+09 0.222420E+09 0.00 0.00 0.00 0.00 0.00 0.214990E+09
June 0.293842E+09 0.100611E+09 0.215205E+09 0.00 0.00 0.00 0.00 2376378.09 0.123821E+09
July 0.303141E+09 0.105074E+09 0.222534E+09 0.00 0.00 0.00 0.00 4649347.16 0.110051E+09
August 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 955550.47 0.151804E+09
September 0.293479E+09 0.101443E+09 0.215319E+09 0.00 0.00 0.00 0.00 0.00 0.266103E+09
October 0.303322E+09 0.104658E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.468879E+09
November 0.293661E+09 0.101014E+09 0.215262E+09 0.00 0.00 0.00 0.00 0.00 0.766132E+09
December 0.303141E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.829609E+09
                   
Annual Sum or Average 0.357224E+10 0.123044E+10 0.261922E+10 0.00 0.00 0.00 0.00 7981275.72 0.540533E+10
Minimum of Months 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.110051E+09
Maximum of Months 0.303685E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 4649347.16 0.829609E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 65789991.58 0.217935E+09 0.00 0.00 0.00 0.00 0.00 0.192391E+09
February 0.00 59414784.75 0.196843E+09 0.00 0.00 0.00 0.00 0.00 0.165042E+09
March 0.00 65267117.48 0.217824E+09 0.00 0.00 0.00 0.00 0.00 0.173017E+09
April 0.00 63743496.62 0.210923E+09 0.00 0.00 0.00 0.00 0.00 0.133550E+09
May 0.00 65528554.53 0.217879E+09 0.00 0.00 0.00 0.00 0.00 84203316.54
June 0.00 63237765.93 0.210812E+09 0.00 0.00 0.00 0.00 10042.37 53826389.58
July 0.00 66042856.93 0.217991E+09 0.00 0.00 0.00 0.00 100490.30 50869418.33
August 0.00 65267117.48 0.217824E+09 0.00 0.00 0.00 0.00 0.00 65297923.64
September 0.00 63760640.03 0.210923E+09 0.00 0.00 0.00 0.00 0.00 0.100091E+09
October 0.00 65781419.88 0.217935E+09 0.00 0.00 0.00 0.00 0.00 0.137710E+09
November 0.00 63490631.27 0.210867E+09 0.00 0.00 0.00 0.00 0.00 0.186954E+09
December 0.00 66051428.64 0.217991E+09 0.00 0.00 0.00 0.00 0.00 0.203455E+09
                   
Annual Sum or Average 0.00 0.773376E+09 0.256575E+10 0.00 0.00 0.00 0.00 110532.67 0.154641E+10
Minimum of Months 0.00 59414784.75 0.196843E+09 0.00 0.00 0.00 0.00 0.00 50869418.33
Maximum of Months 0.00 66051428.64 0.217991E+09 0.00 0.00 0.00 0.00 100490.30 0.203455E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 65807981.74 0.217995E+09 0.00 0.00 0.00 0.00 0.00 0.220236E+09
February 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 0.00 0.188592E+09
March 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 0.00 0.176658E+09
April 0.293479E+09 63760927.16 0.210981E+09 0.00 0.00 0.00 0.00 0.00 0.107589E+09
May 0.303504E+09 65546473.20 0.217939E+09 0.00 0.00 0.00 0.00 0.00 58395673.06
June 0.293842E+09 63255058.18 0.210869E+09 0.00 0.00 0.00 0.00 681239.70 31934696.88
July 0.303141E+09 66060916.23 0.218051E+09 0.00 0.00 0.00 0.00 1361955.02 29008190.78
August 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 294479.14 40725598.82
September 0.293479E+09 63778075.26 0.210981E+09 0.00 0.00 0.00 0.00 0.00 75048904.00
October 0.303322E+09 65799407.69 0.217995E+09 0.00 0.00 0.00 0.00 0.00 0.132604E+09
November 0.293661E+09 63507992.67 0.210925E+09 0.00 0.00 0.00 0.00 0.00 0.214171E+09
December 0.303141E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 0.00 0.231760E+09
                   
Annual Sum or Average 0.357224E+10 0.773587E+09 0.256645E+10 0.00 0.00 0.00 0.00 2337673.86 0.150672E+10
Minimum of Months 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 0.00 29008190.78
Maximum of Months 0.303685E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 1361955.02 0.231760E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104684E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.788246E+09
February 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.674970E+09
March 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.00 0.638554E+09
April 0.293479E+09 0.101428E+09 0.215344E+09 0.00 0.00 0.00 0.00 0.00 0.393381E+09
May 0.303504E+09 0.104268E+09 0.222446E+09 0.00 0.00 0.00 0.00 28804.87 0.211410E+09
June 0.293842E+09 0.100623E+09 0.215230E+09 0.00 0.00 0.00 0.00 3112325.72 0.109142E+09
July 0.303141E+09 0.105087E+09 0.222560E+09 0.00 0.00 0.00 0.00 6286096.78 98950205.64
August 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 1567928.81 0.144638E+09
September 0.293479E+09 0.101455E+09 0.215344E+09 0.00 0.00 0.00 0.00 0.00 0.272715E+09
October 0.303322E+09 0.104671E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.473893E+09
November 0.293661E+09 0.101025E+09 0.215287E+09 0.00 0.00 0.00 0.00 0.00 0.766344E+09
December 0.303141E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.829746E+09
                   
Annual Sum or Average 0.357224E+10 0.123059E+10 0.261953E+10 0.00 0.00 0.00 0.00 10995156.18 0.540199E+10
Minimum of Months 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 0.00 98950205.64
Maximum of Months 0.303685E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 6286096.78 0.829746E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104672E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.787783E+09
February 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.673801E+09
March 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.00 0.631756E+09
April 0.293479E+09 0.101416E+09 0.215319E+09 0.00 0.00 0.00 0.00 0.00 0.388659E+09
May 0.303504E+09 0.104256E+09 0.222420E+09 0.00 0.00 0.00 0.00 0.00 0.215024E+09
June 0.293842E+09 0.100611E+09 0.215205E+09 0.00 0.00 0.00 0.00 2398054.54 0.119435E+09
July 0.303141E+09 0.105074E+09 0.222534E+09 0.00 0.00 0.00 0.00 4661347.93 0.110155E+09
August 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 969229.19 0.151077E+09
September 0.293479E+09 0.101443E+09 0.215319E+09 0.00 0.00 0.00 0.00 0.00 0.270094E+09
October 0.303322E+09 0.104658E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.470773E+09
November 0.293661E+09 0.101014E+09 0.215262E+09 0.00 0.00 0.00 0.00 0.00 0.766100E+09
December 0.303141E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.829525E+09
                   
Annual Sum or Average 0.357224E+10 0.123044E+10 0.261922E+10 0.00 0.00 0.00 0.00 8028631.65 0.541418E+10
Minimum of Months 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.110155E+09
Maximum of Months 0.303685E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 4661347.93 0.829525E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.120431E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.967479E+09
February 0.348285E+10 0.108739E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.827868E+09
March 0.387034E+10 0.120803E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.772382E+09
April 0.373454E+10 0.116348E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.475215E+09
May 0.386038E+10 0.120640E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.273521E+09
June 0.374269E+10 0.116882E+10 0.00 0.00 0.00 0.00 0.00 1575069.12 0.162143E+09
July 0.385223E+10 0.120107E+10 0.00 0.00 0.00 0.00 0.00 3675556.35 0.148058E+09
August 0.386853E+10 0.120849E+10 0.00 0.00 0.00 0.00 0.00 698177.95 0.197373E+09
September 0.373273E+10 0.116395E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.331660E+09
October 0.385404E+10 0.120385E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.578464E+09
November 0.372639E+10 0.116789E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.941041E+09
December 0.385223E+10 0.120107E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.101821E+10
                   
Annual Sum or Average 0.454292E+11 0.141847E+11 0.00 0.00 0.00 0.00 0.00 5948803.43 0.669341E+10
Minimum of Months 0.348285E+10 0.108739E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.148058E+09
Maximum of Months 0.387034E+10 0.120849E+10 0.00 0.00 0.00 0.00 0.00 3675556.35 0.101821E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104684E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.789070E+09
February 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.674989E+09
March 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.00 0.632031E+09
April 0.293479E+09 0.101428E+09 0.215344E+09 0.00 0.00 0.00 0.00 0.00 0.390161E+09
May 0.303504E+09 0.104268E+09 0.222446E+09 0.00 0.00 0.00 0.00 26191.37 0.210494E+09
June 0.293842E+09 0.100623E+09 0.215230E+09 0.00 0.00 0.00 0.00 2991336.03 0.109336E+09
July 0.303141E+09 0.105087E+09 0.222560E+09 0.00 0.00 0.00 0.00 6092368.48 99001643.36
August 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 1489640.46 0.143894E+09
September 0.293479E+09 0.101455E+09 0.215344E+09 0.00 0.00 0.00 0.00 0.00 0.269263E+09
October 0.303322E+09 0.104671E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.471136E+09
November 0.293661E+09 0.101025E+09 0.215287E+09 0.00 0.00 0.00 0.00 0.00 0.767457E+09
December 0.303141E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.830891E+09
                   
Annual Sum or Average 0.357224E+10 0.123059E+10 0.261953E+10 0.00 0.00 0.00 0.00 10599536.35 0.538772E+10
Minimum of Months 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 0.00 99001643.36
Maximum of Months 0.303685E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 6092368.48 0.830891E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104672E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.788443E+09
February 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.674563E+09
March 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.00 0.628874E+09
April 0.293479E+09 0.101416E+09 0.215319E+09 0.00 0.00 0.00 0.00 0.00 0.383617E+09
May 0.303504E+09 0.104256E+09 0.222420E+09 0.00 0.00 0.00 0.00 0.00 0.216135E+09
June 0.293842E+09 0.100611E+09 0.215205E+09 0.00 0.00 0.00 0.00 2318815.86 0.126176E+09
July 0.303141E+09 0.105074E+09 0.222534E+09 0.00 0.00 0.00 0.00 4536465.41 0.111914E+09
August 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 928138.32 0.153198E+09
September 0.293479E+09 0.101443E+09 0.215319E+09 0.00 0.00 0.00 0.00 0.00 0.265065E+09
October 0.303322E+09 0.104658E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.469001E+09
November 0.293661E+09 0.101014E+09 0.215262E+09 0.00 0.00 0.00 0.00 0.00 0.767094E+09
December 0.303141E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.830471E+09
                   
Annual Sum or Average 0.357224E+10 0.123044E+10 0.261922E+10 0.00 0.00 0.00 0.00 7783419.59 0.541455E+10
Minimum of Months 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.111914E+09
Maximum of Months 0.303685E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 4536465.41 0.830471E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 65807981.74 0.217995E+09 0.00 0.00 0.00 0.00 0.00 0.404517E+09
February 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 0.00 0.348766E+09
March 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 0.00 0.329692E+09
April 0.293479E+09 63760927.16 0.210981E+09 0.00 0.00 0.00 0.00 0.00 0.202389E+09
May 0.303504E+09 65546473.20 0.217939E+09 0.00 0.00 0.00 0.00 12305.08 0.108294E+09
June 0.293842E+09 63255058.18 0.210869E+09 0.00 0.00 0.00 0.00 1544413.62 56044315.56
July 0.303141E+09 66060916.23 0.218051E+09 0.00 0.00 0.00 0.00 3126964.38 50798915.65
August 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 765146.05 74188563.17
September 0.293479E+09 63778075.26 0.210981E+09 0.00 0.00 0.00 0.00 0.00 0.140666E+09
October 0.303322E+09 65799407.69 0.217995E+09 0.00 0.00 0.00 0.00 0.00 0.245308E+09
November 0.293661E+09 63507992.67 0.210925E+09 0.00 0.00 0.00 0.00 0.00 0.393557E+09
December 0.303141E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 0.00 0.425322E+09
                   
Annual Sum or Average 0.357224E+10 0.773587E+09 0.256645E+10 0.00 0.00 0.00 0.00 5448829.13 0.277954E+10
Minimum of Months 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 0.00 50798915.65
Maximum of Months 0.303685E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 3126964.38 0.425322E+09



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.281025E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.197789E+10
February 0.415303E+11 0.241048E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.169480E+10
March 0.461508E+11 0.248641E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.159377E+10
April 0.445315E+11 0.207938E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.986740E+09
May 0.460320E+11 0.199717E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.556073E+09
June 0.446286E+11 0.183788E+10 0.144540E+11 0.00 0.00 0.00 0.00 5438587.81 0.315008E+09
July 0.459349E+11 0.194254E+10 0.149358E+11 0.00 0.00 0.00 0.00 13330239.94 0.290141E+09
August 0.461292E+11 0.214270E+10 0.149358E+11 0.00 0.00 0.00 0.00 2719115.51 0.396631E+09
September 0.445099E+11 0.232873E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.703727E+09
October 0.459565E+11 0.260940E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.120936E+10
November 0.444343E+11 0.268158E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.192230E+10
December 0.459349E+11 0.284327E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.207617E+10
                   
Annual Sum or Average 0.541708E+12 0.281698E+11 0.175857E+12 0.00 0.00 0.00 0.00 21487943.27 0.137226E+11
Minimum of Months 0.415303E+11 0.183788E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.290141E+09
Maximum of Months 0.461508E+11 0.284327E+10 0.149358E+11 0.00 0.00 0.00 0.00 13330239.94 0.207617E+10



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.281025E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.198868E+10
February 0.415303E+11 0.241048E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.170445E+10
March 0.461508E+11 0.248641E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.160718E+10
April 0.445315E+11 0.207938E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.100166E+10
May 0.460320E+11 0.199717E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.568777E+09
June 0.446286E+11 0.183788E+10 0.144540E+11 0.00 0.00 0.00 0.00 4679667.92 0.325049E+09
July 0.459349E+11 0.194254E+10 0.149358E+11 0.00 0.00 0.00 0.00 11551548.76 0.299508E+09
August 0.461292E+11 0.214270E+10 0.149358E+11 0.00 0.00 0.00 0.00 2197862.50 0.407807E+09
September 0.445099E+11 0.232873E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.719246E+09
October 0.459565E+11 0.260940E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.122474E+10
November 0.444343E+11 0.268158E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.193212E+10
December 0.459349E+11 0.284327E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.208552E+10
                   
Annual Sum or Average 0.541708E+12 0.281698E+11 0.175857E+12 0.00 0.00 0.00 0.00 18429079.18 0.138647E+11
Minimum of Months 0.415303E+11 0.183788E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.299508E+09
Maximum of Months 0.461508E+11 0.284327E+10 0.149358E+11 0.00 0.00 0.00 0.00 11551548.76 0.208552E+10



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.113250E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.188764E+10
February 0.369574E+10 0.102255E+10 0.293798E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.162041E+10
March 0.410691E+10 0.113599E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.153109E+10
April 0.396281E+10 0.109410E+10 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.962691E+09
May 0.409635E+10 0.113446E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.555491E+09
June 0.397146E+10 0.109912E+10 0.314783E+11 0.295556E+11 0.00 0.00 0.00 2084756.42 0.322079E+09
July 0.408770E+10 0.112945E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 4923429.70 0.298169E+09
August 0.410499E+10 0.113643E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 497177.36 0.406445E+09
September 0.396089E+10 0.109454E+10 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.700485E+09
October 0.408962E+10 0.113207E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.117625E+10
November 0.395417E+10 0.109825E+10 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.183483E+10
December 0.408770E+10 0.112945E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.197978E+10
                   
Annual Sum or Average 0.482060E+11 0.133389E+11 0.382987E+12 0.359593E+12 0.00 0.00 0.00 7505363.48 0.132754E+11
Minimum of Months 0.369574E+10 0.102255E+10 0.293798E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.298169E+09
Maximum of Months 0.410691E+10 0.113643E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 4923429.70 0.197978E+10



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.127458E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.171226E+10
February 0.368610E+10 0.115083E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.146722E+10
March 0.409620E+10 0.127851E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.137120E+10
April 0.395248E+10 0.123137E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.864783E+09
May 0.408566E+10 0.127679E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.525326E+09
June 0.396110E+10 0.123701E+10 0.00 0.00 0.00 0.00 0.00 2023960.79 0.313435E+09
July 0.407704E+10 0.127114E+10 0.00 0.00 0.00 0.00 0.00 4788101.88 0.289623E+09
August 0.409429E+10 0.127900E+10 0.00 0.00 0.00 0.00 0.00 479178.95 0.387671E+09
September 0.395056E+10 0.123186E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.618662E+09
October 0.407896E+10 0.127409E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.103050E+10
November 0.394385E+10 0.123603E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.166769E+10
December 0.407704E+10 0.127114E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.180423E+10
                   
Annual Sum or Average 0.480803E+11 0.150123E+11 0.00 0.00 0.00 0.00 0.00 7291241.62 0.120526E+11
Minimum of Months 0.368610E+10 0.115083E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.289623E+09
Maximum of Months 0.409620E+10 0.127900E+10 0.00 0.00 0.00 0.00 0.00 4788101.88 0.180423E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 10053.14 02-JAN-20:10 9632.53 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 10053.14 01-FEB-20:10 9632.53 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 10053.14 01-MAR-20:10 9632.53 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 10053.14 03-APR-19:10 9632.53 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 10053.14 01-MAY-19:10 9632.53 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 10053.14 01-JUN-19:10 9632.53 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 10053.14 03-JUL-19:10 9632.53 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 10053.14 01-AUG-19:10 9632.53 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 10053.14 01-SEP-19:10 9632.53 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 10053.14 02-OCT-19:10 9632.53 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 10053.14 01-NOV-19:10 9632.53 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 10053.14 01-DEC-20:10 9632.53 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   10053.14   9632.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   10053.14   9632.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 512.31 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 829.48 12-JAN-06:00
February 1169.53 01-FEB-00:10 512.31 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 799.85 27-FEB-05:00
March 1169.53 01-MAR-00:10 512.31 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 705.22 01-MAR-00:10
April 1169.53 01-APR-00:10 512.31 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 580.56 03-APR-06:00
May 1169.53 01-MAY-00:10 512.31 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 262.46 28-MAY-02:00
June 1169.53 01-JUN-00:10 512.31 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 48.62 30-JUN-15:00 236.06 02-JUN-04:00
July 1169.53 01-JUL-00:10 512.31 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 67.83 29-JUL-16:50 191.69 31-JUL-03:00
August 1169.53 01-AUG-00:10 512.31 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 18.24 11-AUG-16:00 293.47 31-AUG-06:00
September 1169.53 01-SEP-00:10 512.31 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 337.83 30-SEP-09:00
October 1169.53 01-OCT-23:10 512.31 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 567.75 22-OCT-06:20
November 1169.53 01-NOV-00:10 512.31 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 704.43 29-NOV-02:00
December 1169.53 01-DEC-00:10 512.31 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 766.38 15-DEC-07:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   512.31   685.60   0.00 0.00 0.00 0.00 0.00   191.69  
Maximum of Months 1169.53   512.31   685.60   0.00 0.00 0.00 0.00 67.83   829.48  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 593.26 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 331.57 12-JAN-06:00
February 1354.32 01-FEB-00:10 593.26 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 315.63 27-FEB-05:50
March 1354.32 01-MAR-00:10 593.26 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 272.30 01-MAR-07:00
April 1354.32 01-APR-00:10 593.26 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 224.59 03-APR-06:00
May 1354.32 01-MAY-00:10 593.26 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 105.85 27-MAY-04:00
June 1354.32 01-JUN-00:10 593.26 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 23.00 30-JUN-15:00 94.33 02-JUN-04:00
July 1354.32 01-JUL-00:10 593.26 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 31.17 29-JUL-16:00 76.14 31-JUL-04:40
August 1354.32 01-AUG-00:10 593.26 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 11.39 11-AUG-17:00 119.45 31-AUG-06:00
September 1354.32 01-SEP-00:10 593.26 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 131.88 29-SEP-06:53
October 1354.32 01-OCT-23:10 593.26 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 219.14 22-OCT-06:30
November 1354.32 01-NOV-00:10 593.26 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 276.75 29-NOV-10:00
December 1354.32 01-DEC-00:10 593.26 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 303.89 15-DEC-07:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   593.26   793.93   0.00 0.00 0.00 0.00 0.00   76.14  
Maximum of Months 1354.32   593.26   793.93   0.00 0.00 0.00 0.00 31.17   331.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 684.18 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 785.92 12-JAN-07:40
February 286.42 01-FEB-00:10 684.18 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 742.21 27-FEB-05:40
March 286.42 01-MAR-00:10 684.18 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 643.54 01-MAR-07:00
April 286.42 01-APR-00:10 684.18 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 529.63 03-APR-06:00
May 286.42 01-MAY-00:10 684.18 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 266.40 27-MAY-06:55
June 286.42 01-JUN-00:10 684.18 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 44.36 30-JUN-15:00 236.82 02-JUN-04:00
July 286.42 01-JUL-00:10 684.18 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 61.88 29-JUL-17:00 190.17 31-JUL-03:00
August 286.42 01-AUG-00:10 684.18 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 16.64 11-AUG-16:00 297.85 31-AUG-06:00
September 286.42 01-SEP-00:10 684.18 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 326.37 29-SEP-06:53
October 286.42 01-OCT-23:10 684.18 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 520.45 22-OCT-07:00
November 286.42 01-NOV-00:10 684.18 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 654.14 29-NOV-10:00
December 286.42 01-DEC-00:10 684.18 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 721.33 15-DEC-07:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   684.18   839.45   0.00 0.00 0.00 0.00 0.00   190.17  
Maximum of Months 286.42   684.18   839.45   0.00 0.00 0.00 0.00 61.88   785.92  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 188.71 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 445.86 12-JAN-06:00
February 220.32 01-FEB-00:10 188.71 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 423.82 27-FEB-05:00
March 220.32 01-MAR-00:10 188.71 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 370.71 01-MAR-00:10
April 220.32 01-APR-00:10 188.71 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 305.57 03-APR-06:00
May 220.32 01-MAY-00:10 188.71 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 2.96 31-MAY-16:00 138.14 28-MAY-02:00
June 220.32 01-JUN-00:10 188.71 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 35.60 30-JUN-15:00 120.92 02-JUN-04:00
July 220.32 01-JUL-00:10 188.71 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 46.68 29-JUL-17:00 96.61 31-JUL-05:00
August 220.32 01-AUG-00:10 188.71 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 21.37 11-AUG-17:00 153.65 31-AUG-06:00
September 220.32 01-SEP-00:10 188.71 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 176.14 30-SEP-09:00
October 220.32 01-OCT-23:10 188.71 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 298.80 22-OCT-06:50
November 220.32 01-NOV-00:10 188.71 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 374.41 29-NOV-10:00
December 220.32 01-DEC-00:10 188.71 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 410.11 15-DEC-07:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   188.71   242.16   0.00 0.00 0.00 0.00 0.00   96.61  
Maximum of Months 220.32   188.71   242.16   0.00 0.00 0.00 0.00 46.68   445.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 400.68 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 0.00 01-JAN-00:05 1138.69 12-JAN-08:00
February 907.20 01-FEB-00:10 400.68 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 0.00 01-FEB-00:05 1072.02 27-FEB-06:00
March 907.20 01-MAR-00:10 400.68 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 0.00 01-MAR-00:10 931.53 01-MAR-07:00
April 907.20 01-APR-00:10 400.68 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 0.00 01-APR-00:10 773.97 03-APR-06:00
May 907.20 01-MAY-00:10 400.68 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 0.00 01-MAY-00:10 373.64 28-MAY-02:00
June 907.20 01-JUN-00:10 400.68 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 60.57 30-JUN-15:00 323.35 02-JUN-04:00
July 907.20 01-JUL-00:10 400.68 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 84.50 29-JUL-16:20 259.66 31-JUL-04:00
August 907.20 01-AUG-00:10 400.68 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 22.72 11-AUG-16:00 409.10 31-AUG-06:00
September 907.20 01-SEP-00:10 400.68 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 0.00 01-SEP-00:10 464.94 30-SEP-09:00
October 907.20 01-OCT-23:10 400.68 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 0.00 01-OCT-00:10 758.14 22-OCT-07:00
November 907.20 01-NOV-00:10 400.68 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 0.00 01-NOV-00:10 945.72 29-NOV-10:00
December 907.20 01-DEC-00:10 400.68 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 0.00 01-DEC-00:10 1038.82 15-DEC-08:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   400.68   4572.80   39726.58   0.00 0.00 0.00 0.00   259.66  
Maximum of Months 907.20   400.68   4572.80   39726.58   0.00 0.00 0.00 84.50   1138.69  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1573.46 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1902.07 12-JAN-06:00
February 15368.40 01-FEB-00:10 1573.46 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 1807.80 27-FEB-05:00
March 15368.40 01-MAR-00:10 1573.46 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1559.49 01-MAR-07:00
April 15368.40 01-APR-00:10 1573.46 03-APR-19:40 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1283.38 03-APR-06:00
May 15368.40 01-MAY-00:10 1398.63 04-MAY-20:30 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 603.49 27-MAY-05:00
June 15368.40 01-JUN-00:10 1214.60 02-JUN-20:00 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 109.01 30-JUN-15:00 535.35 02-JUN-04:00
July 15368.40 01-JUL-00:10 1263.59 28-JUL-20:00 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 164.57 29-JUL-17:00 429.36 31-JUL-05:00
August 15368.40 01-AUG-00:10 1573.46 29-AUG-19:30 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 64.96 11-AUG-18:00 664.40 31-AUG-06:00
September 15368.40 01-SEP-00:10 1573.46 01-SEP-19:30 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 739.83 30-SEP-09:00
October 15368.40 01-OCT-23:10 1573.46 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1255.09 22-OCT-06:20
November 15368.40 01-NOV-00:10 1573.46 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1561.09 29-NOV-02:00
December 15368.40 01-DEC-00:10 1573.46 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1728.23 15-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1214.60   965.27   0.00 0.00 0.00 0.00 0.00   429.36  
Maximum of Months 15368.40   1573.46   965.27   0.00 0.00 0.00 0.00 164.57   1902.07  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 7984.04 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 5495.91 12-JAN-06:00
February 45622.98 01-FEB-00:10 7984.04 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 5164.62 27-FEB-05:40
March 45622.98 01-MAR-00:10 7984.04 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4455.56 01-MAR-07:00
April 45622.98 01-APR-00:10 7984.04 03-APR-19:40 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 3728.22 03-APR-06:00
May 45622.98 01-MAY-00:10 7809.31 02-MAY-19:00 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1798.69 27-MAY-04:00
June 45622.98 01-JUN-00:10 7667.15 02-JUN-19:00 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 357.21 30-JUN-15:00 1593.49 02-JUN-04:00
July 45622.98 01-JUL-00:10 7625.65 28-JUL-19:00 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 487.38 29-JUL-16:00 1290.45 31-JUL-05:00
August 45622.98 01-AUG-00:10 7984.04 29-AUG-19:30 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 163.12 11-AUG-17:00 1996.07 31-AUG-06:00
September 45622.98 01-SEP-00:10 7984.04 01-SEP-19:30 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 2208.33 30-SEP-06:00
October 45622.98 01-OCT-23:10 7984.04 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 3618.05 22-OCT-07:00
November 45622.98 01-NOV-00:10 7984.04 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4527.09 29-NOV-10:00
December 45622.98 01-DEC-00:10 7984.04 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4986.56 15-DEC-07:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   7625.65   10029.21   0.00 0.00 0.00 0.00 0.00   1290.45  
Maximum of Months 45622.98   7984.04   10029.21   0.00 0.00 0.00 0.00 487.38   5495.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.72 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 501.67 12-JAN-07:50
February 180.00 01-FEB-00:10 94.72 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 475.87 27-FEB-05:10
March 180.00 01-MAR-00:10 94.72 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 410.70 01-MAR-07:00
April 180.00 01-APR-00:10 94.72 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 338.18 03-APR-06:00
May 180.00 01-MAY-00:10 94.72 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 7.00 31-MAY-16:00 153.45 28-MAY-02:00
June 180.00 01-JUN-00:10 94.72 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 36.58 20-JUN-18:10 129.96 02-JUN-04:00
July 180.00 01-JUL-00:10 94.72 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 58.05 29-JUL-16:40 100.50 31-JUL-03:10
August 180.00 01-AUG-00:10 94.72 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 29.46 11-AUG-16:00 169.51 31-AUG-06:00
September 180.00 01-SEP-00:10 94.72 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 195.38 30-SEP-09:00
October 180.00 01-OCT-00:10 94.72 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 330.72 22-OCT-06:00
November 180.00 01-NOV-00:10 94.72 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 417.15 29-NOV-10:00
December 180.00 01-DEC-00:10 94.72 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 459.30 15-DEC-07:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 0.00   100.50  
Maximum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 58.05   501.67  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.71 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 498.76 12-JAN-07:50
February 180.00 01-FEB-00:10 94.71 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 474.46 27-FEB-05:00
March 180.00 01-MAR-00:10 94.71 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 410.66 01-MAR-07:00
April 180.00 01-APR-00:10 94.71 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 338.16 03-APR-06:00
May 180.00 01-MAY-00:10 94.71 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 153.44 28-MAY-02:00
June 180.00 01-JUN-00:10 94.71 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 36.58 20-JUN-18:50 129.95 02-JUN-04:00
July 180.00 01-JUL-00:10 94.71 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 58.05 29-JUL-16:10 100.49 31-JUL-03:00
August 180.00 01-AUG-00:10 94.71 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 29.46 11-AUG-16:00 169.50 31-AUG-06:00
September 180.00 01-SEP-00:10 94.71 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 195.37 30-SEP-09:00
October 180.00 01-OCT-00:10 94.71 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 330.70 22-OCT-06:00
November 180.00 01-NOV-00:10 94.71 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 415.25 29-NOV-10:00
December 180.00 01-DEC-00:10 94.71 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 459.26 15-DEC-07:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 0.00   100.49  
Maximum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 58.05   498.76  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 59.53 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 128.08 12-JAN-07:54
February 0.00 01-FEB-00:10 59.53 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 119.89 27-FEB-06:00
March 0.00 01-MAR-00:10 59.53 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 109.21 31-MAR-06:00
April 0.00 01-APR-00:10 59.53 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 99.85 03-APR-06:00
May 0.00 01-MAY-00:10 59.53 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 52.96 27-MAY-07:20
June 0.00 01-JUN-00:10 59.53 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 2.91 30-JUN-15:00 47.18 02-JUN-04:00
July 0.00 01-JUL-00:10 59.53 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 6.02 29-JUL-17:00 39.20 31-JUL-03:00
August 0.00 01-AUG-00:10 59.53 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 0.00 01-AUG-00:10 58.48 31-AUG-06:00
September 0.00 01-SEP-00:10 59.53 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 63.60 30-SEP-09:00
October 0.00 01-OCT-00:10 59.53 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 85.20 22-OCT-09:00
November 0.00 01-NOV-00:10 59.53 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 103.83 29-NOV-10:00
December 0.00 01-DEC-00:10 59.53 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 115.46 15-DEC-07:54
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   59.53   232.19   0.00 0.00 0.00 0.00 0.00   39.20  
Maximum of Months 0.00   59.53   232.19   0.00 0.00 0.00 0.00 6.02   128.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 59.54 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 137.71 12-JAN-07:50
February 180.00 01-FEB-00:10 59.54 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 130.26 27-FEB-05:00
March 180.00 01-MAR-00:10 59.54 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 114.23 01-MAR-07:00
April 180.00 01-APR-00:10 59.54 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 94.38 03-APR-06:00
May 180.00 01-MAY-00:10 59.54 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 44.64 27-MAY-07:20
June 180.00 01-JUN-00:10 59.54 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 10.21 20-JUN-18:50 36.27 02-JUN-04:00
July 180.00 01-JUL-00:10 59.54 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 16.20 29-JUL-16:00 28.05 31-JUL-04:10
August 180.00 01-AUG-00:10 59.54 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 8.22 11-AUG-16:00 47.31 31-AUG-06:00
September 180.00 01-SEP-00:10 59.54 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 55.18 30-SEP-08:00
October 180.00 01-OCT-00:10 59.54 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 92.30 22-OCT-06:00
November 180.00 01-NOV-00:10 59.54 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 114.32 29-NOV-10:00
December 180.00 01-DEC-00:10 59.54 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 126.84 15-DEC-07:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 0.00   28.05  
Maximum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 16.20   137.71  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.72 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 500.23 12-JAN-07:50
February 180.00 01-FEB-00:10 94.72 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 475.87 27-FEB-05:20
March 180.00 01-MAR-00:10 94.72 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 410.70 01-MAR-07:00
April 180.00 01-APR-00:10 94.72 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 338.18 03-APR-06:00
May 180.00 01-MAY-00:10 94.72 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 7.00 31-MAY-16:00 154.44 27-MAY-07:10
June 180.00 01-JUN-00:10 94.72 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 36.59 20-JUN-18:10 129.96 02-JUN-04:00
July 180.00 01-JUL-00:10 94.72 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 58.05 29-JUL-16:50 100.50 31-JUL-03:00
August 180.00 01-AUG-00:10 94.72 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 29.46 11-AUG-16:00 177.10 31-AUG-07:00
September 180.00 01-SEP-00:10 94.72 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 202.70 30-SEP-08:00
October 180.00 01-OCT-00:10 94.72 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 330.72 22-OCT-06:30
November 180.00 01-NOV-00:10 94.72 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 416.36 29-NOV-10:00
December 180.00 01-DEC-00:10 94.72 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 459.30 15-DEC-07:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 0.00   100.50  
Maximum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 58.05   500.23  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.71 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 497.42 12-JAN-07:50
February 180.00 01-FEB-00:10 94.71 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 473.21 27-FEB-05:00
March 180.00 01-MAR-00:10 94.71 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 410.66 01-MAR-07:00
April 180.00 01-APR-00:10 94.71 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 338.16 03-APR-06:00
May 180.00 01-MAY-00:10 94.71 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 154.14 27-MAY-07:10
June 180.00 01-JUN-00:10 94.71 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 36.58 20-JUN-18:10 129.95 02-JUN-04:00
July 180.00 01-JUL-00:10 94.71 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 58.05 29-JUL-16:10 100.49 31-JUL-03:00
August 180.00 01-AUG-00:10 94.71 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 29.46 11-AUG-16:00 176.84 31-AUG-07:00
September 180.00 01-SEP-00:10 94.71 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 199.43 30-SEP-08:00
October 180.00 01-OCT-00:10 94.71 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 330.70 22-OCT-06:00
November 180.00 01-NOV-00:10 94.71 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 414.50 29-NOV-10:00
December 180.00 01-DEC-00:10 94.71 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 459.19 15-DEC-07:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 0.00   100.49  
Maximum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 58.05   497.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1160.00 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 605.29 12-JAN-06:00
February 2263.36 01-FEB-00:10 1160.00 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 574.21 27-FEB-05:00
March 2263.36 01-MAR-00:10 1160.00 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 495.55 01-MAR-07:00
April 2263.36 01-APR-00:10 1160.00 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 407.89 03-APR-06:00
May 2263.36 01-MAY-00:10 1160.00 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 192.40 27-MAY-04:00
June 2263.36 01-JUN-00:10 1160.00 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 37.00 30-JUN-15:00 171.75 02-JUN-04:00
July 2263.36 01-JUL-00:10 1160.00 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 51.34 29-JUL-17:00 139.91 31-JUL-05:00
August 2263.36 01-AUG-00:10 1160.00 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 17.56 23-AUG-17:50 215.44 31-AUG-06:00
September 2263.36 01-SEP-00:10 1160.00 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 235.27 30-SEP-09:00
October 2263.36 01-OCT-23:10 1160.00 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 398.87 22-OCT-06:50
November 2263.36 01-NOV-00:10 1160.00 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 501.10 29-NOV-10:00
December 2263.36 01-DEC-00:10 1160.00 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 552.15 15-DEC-07:51
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1160.00   0.00 0.00 0.00 0.00 0.00 0.00   139.91  
Maximum of Months 2263.36   1160.00   0.00 0.00 0.00 0.00 0.00 51.34   605.29  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.72 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 497.07 12-JAN-07:50
February 180.00 01-FEB-00:10 94.72 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 476.06 27-FEB-05:00
March 180.00 01-MAR-00:10 94.72 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 411.28 01-MAR-07:00
April 180.00 01-APR-00:10 94.72 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 338.74 03-APR-06:00
May 180.00 01-MAY-00:10 94.72 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 6.60 31-MAY-16:00 153.91 28-MAY-02:00
June 180.00 01-JUN-00:10 94.72 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 36.20 20-JUN-18:10 130.42 02-JUN-04:00
July 180.00 01-JUL-00:10 94.72 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 57.67 29-JUL-16:50 100.95 31-JUL-03:50
August 180.00 01-AUG-00:10 94.72 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 29.07 11-AUG-16:10 169.99 31-AUG-06:00
September 180.00 01-SEP-00:10 94.72 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 195.87 30-SEP-09:00
October 180.00 01-OCT-00:10 94.72 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 331.27 22-OCT-06:00
November 180.00 01-NOV-00:10 94.72 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 415.13 29-NOV-10:00
December 180.00 01-DEC-00:10 94.72 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 459.91 15-DEC-07:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 0.00   100.95  
Maximum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 57.67   497.07  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.71 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 492.93 12-JAN-07:50
February 180.00 01-FEB-00:10 94.71 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 471.71 27-FEB-05:00
March 180.00 01-MAR-00:10 94.71 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 411.26 01-MAR-07:00
April 180.00 01-APR-00:10 94.71 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 338.71 03-APR-06:00
May 180.00 01-MAY-00:10 94.71 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 153.90 28-MAY-02:00
June 180.00 01-JUN-00:10 94.71 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 36.19 20-JUN-19:00 130.41 02-JUN-04:00
July 180.00 01-JUL-00:10 94.71 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 57.67 29-JUL-16:00 100.94 31-JUL-03:00
August 180.00 01-AUG-00:10 94.71 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 29.07 11-AUG-16:00 169.98 31-AUG-06:00
September 180.00 01-SEP-00:10 94.71 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 195.86 30-SEP-09:00
October 180.00 01-OCT-00:10 94.71 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 331.25 22-OCT-06:00
November 180.00 01-NOV-00:10 94.71 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 412.65 29-NOV-10:00
December 180.00 01-DEC-00:10 94.71 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 456.87 15-DEC-07:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 0.00   100.94  
Maximum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 57.67   492.93  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 59.54 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 259.20 12-JAN-07:50
February 180.00 01-FEB-00:10 59.54 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 243.78 27-FEB-06:00
March 180.00 01-MAR-00:10 59.54 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 210.42 01-MAR-07:00
April 180.00 01-APR-00:10 59.54 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 173.31 03-APR-06:00
May 180.00 01-MAY-00:10 59.54 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 3.37 31-MAY-16:00 78.75 28-MAY-02:00
June 180.00 01-JUN-00:10 59.54 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 18.52 20-JUN-18:40 66.72 02-JUN-04:00
July 180.00 01-JUL-00:10 59.54 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 29.51 29-JUL-16:50 51.65 31-JUL-03:20
August 180.00 01-AUG-00:10 59.54 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 14.87 11-AUG-16:00 86.97 31-AUG-06:00
September 180.00 01-SEP-00:10 59.54 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 100.21 30-SEP-09:00
October 180.00 01-OCT-00:10 59.54 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 169.49 22-OCT-06:00
November 180.00 01-NOV-00:10 59.54 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 213.80 29-NOV-10:00
December 180.00 01-DEC-00:10 59.54 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 235.30 15-DEC-07:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 0.00   51.65  
Maximum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 29.51   259.20  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2763.12 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1232.49 12-JAN-06:00
February 26988.77 01-FEB-00:10 2763.12 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 1161.38 27-FEB-05:20
March 26988.77 01-MAR-00:10 2763.12 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1002.19 01-MAR-07:00
April 26988.77 01-APR-00:10 2763.12 03-APR-19:40 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 839.11 03-APR-06:00
May 26988.77 01-MAY-00:10 2456.11 04-MAY-20:30 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 406.15 27-MAY-05:00
June 26988.77 01-JUN-00:10 2332.05 02-JUN-19:00 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 91.70 30-JUN-15:00 359.82 02-JUN-04:00
July 26988.77 01-JUL-00:10 2341.32 26-JUL-20:00 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 127.17 29-JUL-16:00 289.58 31-JUL-05:00
August 26988.77 01-AUG-00:10 2763.12 29-AUG-19:30 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 53.18 11-AUG-18:00 446.11 31-AUG-06:00
September 26988.77 01-SEP-00:10 2763.12 01-SEP-19:30 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 499.18 30-SEP-06:00
October 26988.77 01-OCT-23:10 2763.12 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 823.56 22-OCT-07:00
November 26988.77 01-NOV-00:10 2763.12 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1017.58 29-NOV-10:00
December 26988.77 01-DEC-00:10 2763.12 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1118.63 15-DEC-07:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2332.05   6747.90   0.00 0.00 0.00 0.00 0.00   289.58  
Maximum of Months 26988.77   2763.12   6747.90   0.00 0.00 0.00 0.00 127.17   1232.49  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2763.12 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1235.79 12-JAN-06:00
February 26988.77 01-FEB-00:10 2763.12 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 1161.38 27-FEB-05:20
March 26988.77 01-MAR-00:10 2763.12 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1003.16 01-MAR-00:10
April 26988.77 01-APR-00:10 2763.12 03-APR-19:40 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 845.68 03-APR-06:00
May 26988.77 01-MAY-00:10 2456.11 04-MAY-20:30 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 410.65 27-MAY-05:00
June 26988.77 01-JUN-00:10 2332.05 02-JUN-19:00 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 87.34 30-JUN-15:00 363.81 02-JUN-04:00
July 26988.77 01-JUL-00:10 2341.32 26-JUL-20:00 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 122.52 29-JUL-16:00 293.60 31-JUL-05:00
August 26988.77 01-AUG-00:10 2763.12 29-AUG-19:30 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 48.45 11-AUG-18:00 451.15 31-AUG-06:00
September 26988.77 01-SEP-00:10 2763.12 01-SEP-19:30 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 506.07 30-SEP-06:00
October 26988.77 01-OCT-23:10 2763.12 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 830.81 22-OCT-07:00
November 26988.77 01-NOV-00:10 2763.12 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1018.65 29-NOV-10:00
December 26988.77 01-DEC-00:10 2763.12 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1123.11 15-DEC-07:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2332.05   6747.90   0.00 0.00 0.00 0.00 0.00   293.60  
Maximum of Months 26988.77   2763.12   6747.90   0.00 0.00 0.00 0.00 122.52   1235.79  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1090.83 02-JAN-20:10 14604.56 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 0.00 01-JAN-00:05 1161.95 12-JAN-08:00
February 2401.70 01-FEB-00:10 1090.83 01-FEB-20:10 14604.56 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:05 1084.61 27-FEB-06:20
March 2401.70 01-MAR-00:10 1090.83 01-MAR-20:10 14604.56 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 0.00 01-MAR-00:10 950.69 01-MAR-07:00
April 2401.70 01-APR-00:10 1090.83 03-APR-19:10 14604.56 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 0.00 01-APR-00:10 790.15 03-APR-06:00
May 2401.70 01-MAY-00:10 1090.83 01-MAY-19:10 14604.56 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 0.00 01-MAY-00:10 382.21 28-MAY-02:00
June 2401.70 01-JUN-00:10 1090.83 01-JUN-19:10 14604.56 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 60.39 30-JUN-15:00 330.98 02-JUN-04:00
July 2401.70 01-JUL-00:10 1090.83 03-JUL-19:10 14604.56 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 84.83 29-JUL-16:00 266.08 31-JUL-03:50
August 2401.70 01-AUG-00:10 1090.83 01-AUG-19:10 14604.56 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 21.90 11-AUG-16:00 418.30 31-AUG-06:00
September 2401.70 01-SEP-00:10 1090.83 01-SEP-19:10 14604.56 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 0.00 01-SEP-00:10 475.18 30-SEP-09:00
October 2401.70 01-OCT-23:10 1090.83 02-OCT-19:10 14604.56 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 0.00 01-OCT-00:10 774.12 22-OCT-07:00
November 2401.70 01-NOV-00:10 1090.83 01-NOV-19:10 14604.56 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 0.00 01-NOV-00:10 965.09 29-NOV-10:00
December 2401.70 01-DEC-00:10 1090.83 01-DEC-20:10 14604.56 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 0.00 01-DEC-00:10 1060.18 15-DEC-08:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1090.83   14604.56   22492.83   0.00 0.00 0.00 0.00   266.08  
Maximum of Months 2401.70   1090.83   14604.56   22492.83   0.00 0.00 0.00 84.83   1161.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1227.68 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1055.39 12-JAN-06:00
February 2395.44 01-FEB-00:10 1227.68 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 1007.45 27-FEB-05:00
March 2395.44 01-MAR-00:10 1227.68 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 877.73 01-MAR-00:10
April 2395.44 01-APR-00:10 1227.68 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 722.86 03-APR-06:00
May 2395.44 01-MAY-00:10 1227.68 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 348.71 27-MAY-04:00
June 2395.44 01-JUN-00:10 1227.68 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 58.96 30-JUN-15:00 317.08 02-JUN-04:00
July 2395.44 01-JUL-00:10 1227.68 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 82.81 29-JUL-16:50 257.53 31-JUL-05:00
August 2395.44 01-AUG-00:10 1227.68 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 21.21 11-AUG-16:00 385.46 31-AUG-06:00
September 2395.44 01-SEP-00:10 1227.68 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 417.31 30-SEP-09:00
October 2395.44 01-OCT-23:10 1227.68 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 706.91 22-OCT-06:40
November 2395.44 01-NOV-00:10 1227.68 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 883.44 29-NOV-10:00
December 2395.44 01-DEC-00:10 1227.68 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 968.81 15-DEC-07:51
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1227.68   0.00 0.00 0.00 0.00 0.00 0.00   257.53  
Maximum of Months 2395.44   1227.68   0.00 0.00 0.00 0.00 0.00 82.81   1055.39  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 18811.57 12-JAN-21:00 8945.92 10053.14 9632.53 0.00 0.00 0.00 0.00 0.00 0.00
February 13886.81 28-FEB-21:00 8945.92 10053.14 9632.53 0.00 0.00 0.00 0.00 0.00 0.00
March 11960.44 01-MAR-00:10 11501.89 2233.99 3041.85 0.00 0.00 0.00 0.00 0.00 0.00
April 12500.19 22-APR-10:35 7667.93 5585.17 7097.65 0.00 0.00 0.00 0.00 0.00 0.00
May 12922.07 14-MAY-10:35 7667.93 6702.09 8111.60 0.00 0.00 0.00 0.00 0.00 0.00
June 13443.91 29-JUN-10:35 5111.95 5585.17 7097.65 0.00 0.00 0.00 0.00 0.00 0.00
July 14699.86 23-JUL-10:35 7667.93 6702.09 8111.60 0.00 0.00 0.00 0.00 0.00 0.00
August 15325.78 26-AUG-10:35 7667.93 5585.17 7097.65 0.00 0.00 0.00 0.00 0.00 0.00
September 15889.16 20-SEP-21:00 10223.90 8936.08 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
October 16105.84 06-OCT-21:00 10223.90 8936.08 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
November 15365.95 28-NOV-23:00 11501.89 6702.09 7097.65 0.00 0.00 0.00 0.00 0.00 0.00
December 17194.65 15-DEC-07:52 40895.62 44680.27 48669.62 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11960.44   5111.95 2233.99 3041.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18811.57   40895.62 44680.27 48669.62 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 677.82 30-JAN-12:30 259.90 142.31 252.59 0.00 0.00 0.00 0.00 0.00 606.40
February 1165.62 15-FEB-13:40 259.90 142.31 252.59 0.00 0.00 0.00 0.00 0.00 423.10
March 2749.85 27-MAR-13:30 259.90 142.31 252.59 0.00 0.00 0.00 0.00 0.00 376.05
April 4520.09 22-APR-13:30 389.84 142.31 252.59 0.00 0.00 0.00 0.00 0.00 102.01
May 4452.42 12-MAY-13:30 259.90 142.31 252.59 0.00 0.00 0.00 0.00 0.00 39.23
June 4196.48 30-JUN-12:30 259.90 142.31 252.59 0.00 0.00 0.00 0.00 24.49 0.00
July 4773.49 23-JUL-13:30 259.90 113.85 216.51 0.00 0.00 0.00 0.00 11.43 0.00
August 4950.54 25-AUG-13:30 259.90 142.31 252.59 0.00 0.00 0.00 0.00 0.00 26.97
September 4083.46 09-SEP-13:30 389.84 142.31 252.59 0.00 0.00 0.00 0.00 0.00 127.32
October 2993.55 03-OCT-13:20 259.90 142.31 252.59 0.00 0.00 0.00 0.00 0.00 161.50
November 965.23 08-NOV-13:40 259.90 142.31 252.59 0.00 0.00 0.00 0.00 0.00 468.75
December 0.00 01-DEC-00:10 1169.53 113.85 216.51 0.00 0.00 0.00 0.00 0.00 639.35
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   259.90 113.85 216.51 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4950.54   1169.53 142.31 252.59 0.00 0.00 0.00 0.00 24.49 639.35



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1053.46 23-JAN-21:00 1053.36 593.26 793.93 0.00 0.00 0.00 0.00 0.00 187.61
February 1145.53 09-FEB-21:00 1053.36 593.26 793.93 0.00 0.00 0.00 0.00 0.00 154.45
March 1270.01 22-MAR-20:00 1053.36 593.26 793.93 0.00 0.00 0.00 0.00 0.00 93.44
April 1519.36 21-APR-20:00 1053.36 593.26 793.93 0.00 0.00 0.00 0.00 0.00 52.26
May 1565.04 31-MAY-18:10 6320.16 3164.06 4512.87 0.00 0.00 0.00 0.00 0.00 9.04
June 1727.17 21-JUN-21:00 1203.84 527.34 752.15 0.00 0.00 0.00 0.00 0.00 0.46
July 1685.27 11-JUL-20:05 9630.72 4218.74 6017.16 0.00 0.00 0.00 0.00 0.00 1.72
August 1675.15 11-AUG-21:00 2407.68 1054.69 1504.29 0.00 0.00 0.00 0.00 0.00 5.34
September 1472.57 10-SEP-10:35 902.88 395.51 668.57 0.00 0.00 0.00 0.00 0.00 38.11
October 1340.83 03-OCT-20:00 1053.36 593.26 793.93 0.00 0.00 0.00 0.00 0.00 77.58
November 1084.55 01-NOV-20:00 1053.36 593.26 793.93 0.00 0.00 0.00 0.00 0.00 147.26
December 1023.62 19-DEC-21:00 1053.36 593.26 793.93 0.00 0.00 0.00 0.00 0.00 130.35
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1023.62   902.88 395.51 668.57 0.00 0.00 0.00 0.00 0.00 0.46
Maximum of Months 1727.17   9630.72 4218.74 6017.16 0.00 0.00 0.00 0.00 0.00 187.61



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 14.04 19-JAN-21:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 0.00 368.24
February 15.78 09-FEB-21:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 0.00 370.39
March 18.30 22-MAR-20:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 0.00 230.70
April 536.74 21-APR-20:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 0.00 128.29
May 984.76 31-MAY-20:55 509.18 1216.31 1590.53 0.00 0.00 0.00 0.00 0.00 78.35
June 1300.63 21-JUN-20:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 10.44 0.00
July 1335.82 21-JUL-20:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 10.31 0.00
August 1248.92 11-AUG-20:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 4.15 0.00
September 672.06 01-SEP-20:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 0.00 128.52
October 204.53 06-OCT-21:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 0.00 173.85
November 14.54 03-NOV-20:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 0.00 319.39
December 13.48 19-DEC-21:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 0.00 309.55
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 13.48   222.77 608.16 795.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1335.82   509.18 1216.31 1590.53 0.00 0.00 0.00 0.00 10.44 370.39



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 342.72 125.80 203.92 0.00 0.00 0.00 0.00 0.00 244.19
February 124.97 08-FEB-22:00 195.84 167.74 229.41 0.00 0.00 0.00 0.00 0.00 130.12
March 442.10 22-MAR-21:00 195.84 167.74 229.41 0.00 0.00 0.00 0.00 0.00 123.57
April 792.31 23-APR-10:35 146.88 125.80 203.92 0.00 0.00 0.00 0.00 0.00 70.24
May 890.59 14-MAY-10:35 146.88 125.80 203.92 0.00 0.00 0.00 0.00 0.00 29.33
June 934.17 22-JUN-10:35 97.92 104.84 178.43 0.00 0.00 0.00 0.00 0.00 4.93
July 973.77 23-JUL-10:35 146.88 125.80 203.92 0.00 0.00 0.00 0.00 0.85 0.00
August 906.95 26-AUG-10:35 146.88 104.84 178.43 0.00 0.00 0.00 0.00 0.00 36.01
September 816.00 10-SEP-10:35 146.88 125.80 203.92 0.00 0.00 0.00 0.00 0.00 45.36
October 668.94 03-OCT-19:50 171.36 188.71 242.16 0.00 0.00 0.00 0.00 0.00 92.96
November 0.00 01-NOV-00:10 220.32 31.45 63.73 0.00 0.00 0.00 0.00 0.00 210.90
December 0.00 01-DEC-00:10 220.32 41.94 76.47 0.00 0.00 0.00 0.00 0.00 336.48
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   97.92 31.45 63.73 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 973.77   342.72 188.71 242.16 0.00 0.00 0.00 0.00 0.85 336.48



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 36315.77 19-JAN-21:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 543.76
February 36795.81 08-FEB-21:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 391.14
March 37524.30 22-MAR-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 328.71
April 38299.96 21-APR-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 175.18
May 38784.04 31-MAY-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 99.49
June 39064.60 29-JUN-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 14.18 0.00
July 39145.83 21-JUL-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 14.05 0.00
August 38993.39 11-AUG-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 5.65 0.00
September 38196.84 01-SEP-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 175.50
October 37764.55 03-OCT-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 271.29
November 36439.02 01-NOV-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 516.00
December 36102.41 19-DEC-21:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 465.24
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 36102.41   705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 39145.83   705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 14.18 543.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6830.07 06-JAN-23:10 15368.40 524.49 406.43 0.00 0.00 0.00 0.00 0.00 653.16
February 8118.57 15-FEB-13:40 3415.20 96.16 355.63 0.00 0.00 0.00 0.00 0.00 892.05
March 11277.68 27-MAR-15:10 17076.00 192.31 711.25 0.00 0.00 0.00 0.00 0.00 810.17
April 15392.11 22-APR-13:30 5122.80 96.16 355.63 0.00 0.00 0.00 0.00 0.00 225.48
May 14529.06 13-MAY-13:10 5122.80 96.16 355.63 0.00 0.00 0.00 0.00 0.00 129.12
June 13637.51 20-JUN-15:10 8538.00 96.16 355.63 0.00 0.00 0.00 0.00 27.78 0.00
July 14930.83 23-JUL-13:30 3415.20 76.92 304.82 0.00 0.00 0.00 0.00 25.29 0.00
August 15671.27 25-AUG-14:10 5122.80 96.16 355.63 0.00 0.00 0.00 0.00 0.00 28.84
September 14331.43 09-SEP-13:30 5122.80 96.16 355.63 0.00 0.00 0.00 0.00 0.00 281.42
October 10832.31 03-OCT-14:10 5122.80 96.16 355.63 0.00 0.00 0.00 0.00 0.00 320.23
November 7007.21 08-NOV-13:30 3415.20 96.16 355.63 0.00 0.00 0.00 0.00 0.00 1010.33
December 6450.73 19-DEC-22:20 15368.40 1048.97 711.25 0.00 0.00 0.00 0.00 0.00 810.05
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6450.73   3415.20 76.92 304.82 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15671.27   17076.00 1048.97 711.25 0.00 0.00 0.00 0.00 27.78 1010.33



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 23170.94 06-JAN-22:00 40553.76 7096.92 9501.36 0.00 0.00 0.00 0.00 0.00 2013.41
February 25632.20 28-FEB-22:10 45622.98 5322.69 7389.94 0.00 0.00 0.00 0.00 0.00 4508.59
March 27690.85 22-MAR-20:00 35484.54 7984.04 10029.21 0.00 0.00 0.00 0.00 0.00 1562.34
April 32430.90 21-APR-21:10 91245.96 10645.38 14779.89 0.00 0.00 0.00 0.00 0.00 1098.93
May 33441.26 14-MAY-10:35 30415.32 4577.51 8445.65 0.00 0.00 0.00 0.00 0.00 443.48
June 36499.76 21-JUN-21:03 273737.88 30244.55 44339.66 0.00 0.00 0.00 0.00 0.00 34.23
July 37118.51 21-JUL-21:10 91245.96 10442.30 14779.89 0.00 0.00 0.00 0.00 0.00 93.98
August 37197.75 11-AUG-21:10 45622.98 5309.23 7389.94 0.00 0.00 0.00 0.00 0.00 121.41
September 32349.03 10-SEP-10:35 30415.32 4577.51 8445.65 0.00 0.00 0.00 0.00 0.00 665.81
October 29166.58 03-OCT-20:00 35484.54 7984.04 10029.21 0.00 0.00 0.00 0.00 0.00 1302.20
November 24696.59 28-NOV-22:10 45622.98 5322.69 7389.94 0.00 0.00 0.00 0.00 0.00 4261.34
December 24579.25 27-DEC-22:00 40553.76 7096.92 9501.36 0.00 0.00 0.00 0.00 0.00 4208.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 23170.94   30415.32 4577.51 7389.94 0.00 0.00 0.00 0.00 0.00 34.23
Maximum of Months 37197.75   273737.88 30244.55 44339.66 0.00 0.00 0.00 0.00 0.00 4508.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 360.00 49.25 89.56 0.00 0.00 0.00 0.00 0.00 270.44
February 399.49 15-FEB-16:14 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 214.68
March 3641.70 22-MAR-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 117.04
April 3849.09 20-APR-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 73.82
May 3866.01 10-MAY-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 29.15
June 3905.68 16-JUN-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 22.33
July 3384.01 26-JUL-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 23.73
August 3800.10 31-AUG-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 57.29
September 3786.95 07-SEP-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 40.96
October 3190.98 13-OCT-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.00 141.90
November 8.51 08-NOV-14:00 36.00 26.52 31.61 0.00 0.00 0.00 0.00 0.00 244.20
December 0.00 01-DEC-00:10 180.00 20.84 44.78 0.00 0.00 0.00 0.00 0.00 372.29
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   36.00 20.84 31.61 0.00 0.00 0.00 0.00 0.00 22.33
Maximum of Months 3905.68   970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 372.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 360.00 49.25 89.55 0.00 0.00 0.00 0.00 0.00 270.42
February 160.93 08-FEB-19:06 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 151.02
March 729.51 26-MAR-15:14 378.00 218.77 387.15 0.00 0.00 0.00 0.00 0.00 222.80
April 3476.84 21-APR-18:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 57.94
May 4005.33 09-MAY-20:01 1602.00 842.88 1817.24 0.00 0.00 0.00 0.00 0.00 79.21
June 3654.07 01-JUN-18:41 1247.40 758.59 1090.34 0.00 0.00 0.00 0.00 0.00 61.42
July 3486.46 06-JUL-21:51 1800.00 634.53 895.45 0.00 0.00 0.00 0.00 0.00 39.47
August 3419.69 30-AUG-18:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 97.83
September 3378.34 07-SEP-18:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 56.72
October 1554.82 03-OCT-15:11 680.40 185.62 350.28 0.00 0.00 0.00 0.00 0.00 60.50
November 0.00 01-NOV-00:10 180.00 16.10 44.77 0.00 0.00 0.00 0.00 0.00 233.71
December 0.00 01-DEC-00:10 180.00 20.84 44.77 0.00 0.00 0.00 0.00 0.00 372.26
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   180.00 16.10 44.77 0.00 0.00 0.00 0.00 0.00 39.47
Maximum of Months 4005.33   1800.00 842.88 1817.24 0.00 0.00 0.00 0.00 0.00 372.26



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2.68 23-JAN-15:20 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 53.84
February 99.61 26-FEB-16:00 0.00 19.64 33.54 0.00 0.00 0.00 0.00 0.00 88.11
March 189.07 31-MAR-15:10 0.00 33.33 98.04 0.00 0.00 0.00 0.00 0.00 77.23
April 742.97 22-APR-13:20 0.00 19.64 33.54 0.00 0.00 0.00 0.00 0.00 21.87
May 720.03 12-MAY-13:20 0.00 33.33 61.92 0.00 0.00 0.00 0.00 0.00 11.41
June 637.89 30-JUN-12:30 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 1.04
July 758.42 23-JUL-13:30 0.00 19.64 33.54 0.00 0.00 0.00 0.00 0.00 3.18
August 803.30 25-AUG-13:30 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 9.50
September 688.64 09-SEP-13:10 0.00 19.64 33.54 0.00 0.00 0.00 0.00 0.00 26.62
October 460.95 03-OCT-13:00 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 32.61
November 34.63 08-NOV-15:20 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 69.64
December 0.00 01-DEC-00:10 0.00 13.10 43.86 0.00 0.00 0.00 0.00 0.00 91.57
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 13.10 30.96 0.00 0.00 0.00 0.00 0.00 1.04
Maximum of Months 803.30   0.00 33.33 98.04 0.00 0.00 0.00 0.00 0.00 91.57



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 192.28 20-JAN-19:07 831.60 317.95 712.25 0.00 0.00 0.00 0.00 0.00 72.86
February 258.12 07-FEB-19:04 970.20 370.95 830.96 0.00 0.00 0.00 0.00 0.00 44.74
March 670.44 22-MAR-18:02 831.60 317.95 712.25 0.00 0.00 0.00 0.00 0.00 36.57
April 1012.96 30-APR-18:01 819.00 416.79 830.96 0.00 0.00 0.00 0.00 0.00 25.12
May 1082.43 31-MAY-21:51 1800.00 398.93 877.41 0.00 0.00 0.00 0.00 0.00 15.33
June 1130.15 10-JUN-21:51 1386.00 506.11 877.41 0.00 0.00 0.00 0.00 0.00 7.91
July 1042.09 19-JUL-21:51 1800.00 398.93 877.41 0.00 0.00 0.00 0.00 0.00 8.12
August 1082.01 10-AUG-21:51 1800.00 398.93 877.41 0.00 0.00 0.00 0.00 0.00 13.77
September 992.59 10-SEP-18:01 819.00 416.79 830.96 0.00 0.00 0.00 0.00 0.00 12.93
October 930.36 03-OCT-18:01 970.20 370.95 830.96 0.00 0.00 0.00 0.00 0.00 22.57
November 221.72 01-NOV-18:06 970.20 370.95 830.96 0.00 0.00 0.00 0.00 0.00 61.23
December 242.15 24-DEC-19:05 702.00 357.25 712.25 0.00 0.00 0.00 0.00 0.00 50.71
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 192.28   702.00 317.95 712.25 0.00 0.00 0.00 0.00 0.00 7.91
Maximum of Months 1130.15   1800.00 506.11 877.41 0.00 0.00 0.00 0.00 0.00 72.86



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 360.00 49.25 89.56 0.00 0.00 0.00 0.00 0.00 270.44
February 438.21 09-FEB-16:15 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.00 158.02
March 3512.45 22-MAR-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 118.95
April 3602.76 22-APR-15:11 378.00 218.80 387.20 0.00 0.00 0.00 0.00 0.00 54.05
May 3669.04 13-MAY-08:61 378.00 371.29 1143.15 0.00 0.00 0.00 0.00 0.00 55.79
June 3610.79 07-JUN-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.00 20.82
July 3220.36 08-JUL-08:61 378.00 371.29 1143.15 0.00 0.00 0.00 0.00 0.00 45.78
August 3596.89 10-AUG-18:02 831.60 505.79 726.98 0.00 0.00 0.00 0.00 1.63 0.00
September 3564.18 07-SEP-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 40.64
October 3174.85 04-OCT-08:62 180.00 208.38 566.31 0.00 0.00 0.00 0.00 0.00 94.10
November 0.00 01-NOV-00:10 180.00 16.10 44.78 0.00 0.00 0.00 0.00 0.00 233.72
December 0.00 01-DEC-00:10 180.00 20.84 44.78 0.00 0.00 0.00 0.00 0.00 372.28
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   180.00 16.10 44.78 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3669.04   831.60 505.79 1143.15 0.00 0.00 0.00 0.00 1.63 372.28



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 360.00 49.25 89.55 0.00 0.00 0.00 0.00 0.00 270.42
February 196.08 08-FEB-19:06 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 151.02
March 1049.32 11-MAR-09:01 378.00 371.25 1143.02 0.00 0.00 0.00 0.00 0.00 222.17
April 3260.03 22-APR-08:62 324.00 318.21 979.73 0.00 0.00 0.00 0.00 0.00 119.86
May 3475.58 14-MAY-20:41 1386.00 947.05 1817.24 0.00 0.00 0.00 0.00 0.00 66.57
June 3603.84 10-JUN-21:51 1386.00 805.00 895.45 0.00 0.00 0.00 0.00 0.00 29.55
July 3755.51 22-JUL-08:32 324.00 318.21 979.73 0.00 0.00 0.00 0.00 0.00 44.17
August 3262.55 31-AUG-08:62 216.00 250.02 679.49 0.00 0.00 0.00 0.00 0.00 146.07
September 3212.72 10-SEP-15:11 378.00 218.77 387.15 0.00 0.00 0.00 0.00 0.00 47.14
October 2093.35 04-OCT-08:62 180.00 208.35 566.24 0.00 0.00 0.00 0.00 0.00 93.18
November 0.00 01-NOV-00:10 180.00 16.10 44.77 0.00 0.00 0.00 0.00 0.00 233.71
December 0.00 01-DEC-00:10 180.00 20.84 44.77 0.00 0.00 0.00 0.00 0.00 372.26
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   180.00 16.10 44.77 0.00 0.00 0.00 0.00 0.00 29.55
Maximum of Months 3755.51   1386.00 947.05 1817.24 0.00 0.00 0.00 0.00 0.00 372.26



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 303.40 06-JAN-23:00 2263.36 773.33 0.00 0.00 0.00 0.00 0.00 0.00 205.15
February 728.20 08-FEB-22:05 4526.71 1546.67 0.00 0.00 0.00 0.00 0.00 0.00 177.35
March 1391.81 22-MAR-20:00 1760.39 1160.00 0.00 0.00 0.00 0.00 0.00 0.00 160.02
April 1918.37 22-APR-10:35 1508.90 644.45 0.00 0.00 0.00 0.00 0.00 0.00 86.31
May 2144.00 14-MAY-10:35 1508.90 773.33 0.00 0.00 0.00 0.00 0.00 0.00 51.49
June 2255.11 13-JUN-10:35 1005.94 644.45 0.00 0.00 0.00 0.00 0.00 0.00 13.17
July 2303.78 23-JUL-10:35 1508.90 773.33 0.00 0.00 0.00 0.00 0.00 0.00 10.55
August 2152.95 01-AUG-10:35 1005.94 644.45 0.00 0.00 0.00 0.00 0.00 0.00 61.37
September 1871.14 10-SEP-10:35 1508.90 773.33 0.00 0.00 0.00 0.00 0.00 0.00 68.30
October 1502.19 03-OCT-10:40 502.97 322.22 0.00 0.00 0.00 0.00 0.00 0.00 134.95
November 429.25 01-NOV-21:30 2263.36 773.33 0.00 0.00 0.00 0.00 0.00 0.00 264.75
December 313.09 24-DEC-22:50 2011.87 644.45 0.00 0.00 0.00 0.00 0.00 0.00 214.93
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 303.40   502.97 322.22 0.00 0.00 0.00 0.00 0.00 0.00 10.55
Maximum of Months 2303.78   4526.71 1546.67 0.00 0.00 0.00 0.00 0.00 0.00 264.75



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 360.00 49.25 89.56 0.00 0.00 0.00 0.00 0.00 270.95
February 372.97 09-FEB-16:15 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.00 158.48
March 3747.69 22-MAR-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 116.42
April 4017.61 21-APR-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 58.51
May 4026.53 10-MAY-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 29.58
June 4061.94 16-JUN-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 22.67
July 3466.63 10-JUL-08:61 252.00 291.73 792.83 0.00 0.00 0.00 0.00 0.00 44.04
August 4050.87 10-AUG-18:02 831.60 505.79 726.98 0.00 0.00 0.00 0.00 0.00 0.39
September 3938.40 07-SEP-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 41.28
October 2555.67 03-OCT-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 70.80
November 0.00 01-NOV-00:10 180.00 16.10 44.78 0.00 0.00 0.00 0.00 0.00 234.22
December 0.00 01-DEC-00:10 180.00 20.84 44.78 0.00 0.00 0.00 0.00 0.00 372.85
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   180.00 16.10 44.78 0.00 0.00 0.00 0.00 0.00 0.39
Maximum of Months 4061.94   970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 372.85



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 360.00 49.25 89.55 0.00 0.00 0.00 0.00 0.00 270.93
February 0.00 01-FEB-00:05 360.00 41.67 89.55 0.00 0.00 0.00 0.00 0.00 316.92
March 872.60 22-MAR-15:13 680.40 185.62 350.28 0.00 0.00 0.00 0.00 0.00 111.36
April 3590.06 21-APR-18:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 58.49
May 4455.62 09-MAY-19:42 831.60 568.23 979.73 0.00 0.00 0.00 0.00 0.00 84.12
June 4006.52 28-JUN-21:32 1080.00 380.72 537.27 0.00 0.00 0.00 0.00 0.00 53.24
July 3731.21 06-JUL-21:51 1800.00 634.53 895.45 0.00 0.00 0.00 0.00 0.00 42.95
August 3567.27 01-AUG-21:51 1800.00 634.53 895.45 0.00 0.00 0.00 0.00 0.00 55.52
September 3481.93 07-SEP-18:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 57.14
October 1042.66 01-OCT-15:13 378.00 218.77 387.15 0.00 0.00 0.00 0.00 0.00 51.46
November 0.00 01-NOV-00:10 180.00 16.10 44.77 0.00 0.00 0.00 0.00 0.00 234.20
December 0.00 01-DEC-00:10 180.00 20.84 44.77 0.00 0.00 0.00 0.00 0.00 372.82
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   180.00 16.10 44.77 0.00 0.00 0.00 0.00 0.00 42.95
Maximum of Months 4455.62   1800.00 634.53 979.73 0.00 0.00 0.00 0.00 0.00 372.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 216.92 30-JAN-13:55 72.00 33.34 61.93 0.00 0.00 0.00 0.00 0.00 173.47
February 2556.60 15-FEB-16:11 680.40 116.70 343.22 0.00 0.00 0.00 0.00 0.00 113.80
March 2648.70 31-MAR-15:11 680.40 116.70 343.22 0.00 0.00 0.00 0.00 0.00 125.08
April 2706.14 20-APR-15:11 680.40 116.70 343.22 0.00 0.00 0.00 0.00 0.00 31.98
May 2667.74 09-MAY-15:12 583.20 100.03 294.19 0.00 0.00 0.00 0.00 0.00 17.89
June 2630.90 16-JUN-18:01 970.20 370.95 830.96 0.00 0.00 0.00 0.00 0.00 10.27
July 2617.41 13-JUL-18:02 831.60 317.95 712.25 0.00 0.00 0.00 0.00 5.57 0.00
August 2674.48 31-AUG-15:11 680.40 116.70 343.22 0.00 0.00 0.00 0.00 0.00 29.72
September 2650.57 30-SEP-15:11 378.00 137.54 379.35 0.00 0.00 0.00 0.00 0.00 72.75
October 2609.90 14-OCT-15:11 378.00 137.54 379.35 0.00 0.00 0.00 0.00 0.00 67.95
November 1000.97 08-NOV-16:12 583.20 100.03 294.19 0.00 0.00 0.00 0.00 0.00 149.50
December 200.59 24-DEC-09:05 324.00 200.06 959.99 0.00 0.00 0.00 0.00 0.00 76.30
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 200.59   72.00 33.34 61.93 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2706.14   970.20 370.95 959.99 0.00 0.00 0.00 0.00 5.57 173.47



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 15803.07 06-JAN-23:10 26988.77 921.04 6747.90 0.00 0.00 0.00 0.00 0.00 451.44
February 17046.71 28-FEB-23:00 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 1008.82
March 16917.46 22-MAR-21:00 23990.02 2456.11 6747.90 0.00 0.00 0.00 0.00 0.00 366.58
April 18234.40 21-APR-20:30 23990.02 2298.49 6747.90 0.00 0.00 0.00 0.00 0.00 207.74
May 19751.91 31-MAY-21:10 53977.54 3322.39 13495.81 0.00 0.00 0.00 0.00 0.00 126.86
June 21790.55 21-JUN-21:03 161932.61 6631.49 40487.42 0.00 0.00 0.00 0.00 0.00 9.33
July 21345.72 11-JUL-21:10 53977.54 2210.50 13495.81 0.00 0.00 0.00 0.00 0.00 37.19
August 20862.44 02-AUG-21:10 53977.54 3586.89 13495.81 0.00 0.00 0.00 0.00 0.00 61.39
September 18233.24 01-SEP-21:00 23990.02 2456.11 6747.90 0.00 0.00 0.00 0.00 0.00 208.70
October 17303.40 06-OCT-21:00 23990.02 2456.11 6747.90 0.00 0.00 0.00 0.00 0.00 254.41
November 16833.76 28-NOV-23:00 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 992.57
December 16997.92 14-DEC-22:30 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 998.11
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 15803.07   23990.02 921.04 6747.90 0.00 0.00 0.00 0.00 0.00 9.33
Maximum of Months 21790.55   161932.61 6631.49 40487.42 0.00 0.00 0.00 0.00 0.00 1008.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 17547.30 11-JAN-22:20 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 1145.73
February 18062.94 28-FEB-22:20 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 1015.64
March 17807.53 22-MAR-21:00 23990.02 2456.11 6747.90 0.00 0.00 0.00 0.00 0.00 373.96
April 18993.45 21-APR-21:10 53977.54 3684.16 13495.81 0.00 0.00 0.00 0.00 0.00 247.70
May 21096.18 10-MAY-21:07 80966.30 5184.14 20243.71 0.00 0.00 0.00 0.00 0.00 166.47
June 22463.08 21-JUN-21:03 161932.61 6631.49 40487.42 0.00 0.00 0.00 0.00 0.00 9.33
July 22593.61 11-JUL-21:10 53977.54 2210.50 13495.81 0.00 0.00 0.00 0.00 0.00 37.24
August 21453.76 02-AUG-21:52 269887.68 18420.82 67479.03 0.00 0.00 0.00 0.00 0.00 78.54
September 19324.19 01-SEP-21:10 53977.54 3684.16 13495.81 0.00 0.00 0.00 0.00 0.00 224.04
October 18245.71 06-OCT-21:00 23990.02 2456.11 6747.90 0.00 0.00 0.00 0.00 0.00 261.77
November 17517.53 28-NOV-23:00 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 998.97
December 18201.94 14-DEC-23:00 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 1020.61
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 17517.53   23990.02 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 9.33
Maximum of Months 22593.61   269887.68 18420.82 67479.03 0.00 0.00 0.00 0.00 0.00 1145.73



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 23874.83 22-JAN-11:50 800.57 363.61 14604.56 18744.03 0.00 0.00 0.00 0.00 488.71
February 25252.06 09-FEB-11:50 1067.42 606.02 29209.11 37488.05 0.00 0.00 0.00 0.00 421.32
March 27437.33 22-MAR-10:40 1067.42 606.02 29209.11 37488.05 0.00 0.00 0.00 0.00 341.57
April 29522.37 22-APR-10:50 800.57 303.01 14604.56 18744.03 0.00 0.00 0.00 0.00 177.20
May 30010.71 12-MAY-10:40 1067.42 606.02 29209.11 37488.05 0.00 0.00 0.00 0.00 98.60
June 30530.16 29-JUN-10:50 533.71 303.01 14604.56 18744.03 0.00 0.00 0.00 0.00 30.44
July 31170.94 22-JUL-10:40 1601.14 606.02 29209.11 37488.05 0.00 0.00 0.00 0.00 7.62
August 30259.49 10-AUG-10:50 533.71 303.01 14604.56 18744.03 0.00 0.00 0.00 0.00 74.42
September 29105.14 10-SEP-10:50 800.57 363.61 14604.56 18744.03 0.00 0.00 0.00 0.00 148.57
October 27324.65 03-OCT-10:40 533.71 303.01 14604.56 18744.03 0.00 0.00 0.00 0.00 291.35
November 23589.03 01-NOV-18:03 13075.94 6787.40 102231.89 104966.55 0.00 0.00 0.00 0.00 526.70
December 24019.42 24-DEC-11:50 800.57 363.61 14604.56 18744.03 0.00 0.00 0.00 0.00 346.47
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 23589.03   533.71 303.01 14604.56 18744.03 0.00 0.00 0.00 0.00 7.62
Maximum of Months 31170.94   13075.94 6787.40 102231.89 104966.55 0.00 0.00 0.00 0.00 526.70



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 3726.24 818.45 0.00 0.00 0.00 0.00 0.00 0.00 577.90
February 1246.35 09-FEB-13:40 532.32 341.02 0.00 0.00 0.00 0.00 0.00 0.00 340.15
March 1655.72 22-MAR-10:35 1064.64 682.05 0.00 0.00 0.00 0.00 0.00 0.00 292.29
April 3183.74 22-APR-14:00 798.48 341.02 0.00 0.00 0.00 0.00 0.00 0.00 123.63
May 5096.20 31-MAY-14:10 798.48 341.02 0.00 0.00 0.00 0.00 0.00 0.00 56.75
June 5931.37 29-JUN-14:20 798.48 341.02 0.00 0.00 0.00 0.00 0.00 23.53 0.00
July 6315.14 23-JUL-13:40 532.32 272.82 0.00 0.00 0.00 0.00 0.00 12.74 0.00
August 5364.19 10-AUG-15:10 1330.80 341.02 0.00 0.00 0.00 0.00 0.00 0.00 26.17
September 2301.80 02-SEP-15:13 4790.88 2046.14 0.00 0.00 0.00 0.00 0.00 0.00 109.89
October 1685.84 03-OCT-10:40 532.32 341.02 0.00 0.00 0.00 0.00 0.00 0.00 246.25
November 0.00 01-NOV-00:10 2395.44 204.61 0.00 0.00 0.00 0.00 0.00 0.00 499.34
December 0.00 01-DEC-00:10 2395.44 272.82 0.00 0.00 0.00 0.00 0.00 0.00 795.86
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   532.32 204.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6315.14   4790.88 2046.14 0.00 0.00 0.00 0.00 0.00 23.53 795.86



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.353691E+12 219453.60 30-JAN-20:10 0.116586E+13 1136619.19 12-JAN-21:49
February 0.312477E+12 217953.92 27-FEB-20:10 0.969741E+12 1012829.02 28-FEB-21:30
March 0.338534E+12 214793.80 27-MAR-19:30 0.791647E+12 908419.52 01-MAR-21:00
April 0.330201E+12 221464.02 21-APR-18:10 0.587894E+12 542868.23 24-APR-20:49
May 0.358584E+12 241332.49 30-MAY-19:10 0.527557E+12 447290.86 27-MAY-21:00
June 0.390446E+12 301443.71 29-JUN-19:10 0.449176E+12 405661.34 01-JUN-17:49
July 0.415649E+12 298855.31 11-JUL-19:10 0.457369E+12 400484.44 03-JUL-17:19
August 0.386479E+12 291274.84 11-AUG-19:10 0.470804E+12 410844.44 30-AUG-21:00
September 0.323874E+12 222050.45 07-SEP-19:49 0.571620E+12 526297.35 29-SEP-18:10
October 0.335988E+12 214886.85 23-OCT-19:30 0.677125E+12 554242.99 16-OCT-18:10
November 0.339345E+12 218267.18 30-NOV-20:10 0.108518E+13 1028344.24 30-NOV-17:49
December 0.357251E+12 220062.21 15-DEC-20:40 0.127869E+13 1065951.65 15-DEC-17:19
             
Annual Sum or Average 0.424252E+13     0.903266E+13    
Minimum of Months 0.312477E+12 214793.80   0.449176E+12 400484.44  
Maximum of Months 0.415649E+12 301443.71   0.127869E+13 1136619.19  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.479245E+11 0.265474E+11 0.140003E+12 0.544027E+11 0.504863E+11 0.157935E+10 0.00 0.168998E+09 0.00 0.00 0.211760E+11 0.770438E+10 0.00
February 0.427397E+11 0.198624E+11 0.126445E+12 0.491378E+11 0.434162E+11 0.162293E+10 0.00 0.304866E+09 0.00 0.00 0.186452E+11 0.696187E+10 0.00
March 0.466066E+11 0.173306E+11 0.140056E+12 0.544046E+11 0.450319E+11 0.263895E+10 0.00 0.151012E+10 0.00 0.00 0.195497E+11 0.770289E+10 0.00
April 0.438692E+11 0.122003E+11 0.135446E+12 0.526461E+11 0.433098E+11 0.555094E+10 0.00 0.155664E+11 0.00 0.00 0.105698E+11 0.746489E+10 0.00
May 0.448313E+11 0.797311E+10 0.140035E+12 0.544021E+11 0.466355E+11 0.810709E+10 0.00 0.426516E+11 0.00 0.00 0.253306E+10 0.770426E+10 0.00
June 0.429917E+11 0.444184E+10 0.135537E+12 0.526479E+11 0.480510E+11 0.916833E+10 0.00 0.841202E+11 0.00 0.00 0.240789E+10 0.745688E+10 0.00
July 0.445844E+11 0.617416E+10 0.139944E+12 0.543996E+11 0.493349E+11 0.968611E+10 0.00 0.964043E+11 0.00 0.00 0.366446E+10 0.771241E+10 0.00
August 0.453370E+11 0.106530E+11 0.140067E+12 0.544038E+11 0.474834E+11 0.882805E+10 0.00 0.658300E+11 0.00 0.00 0.242194E+10 0.770435E+10 0.00
September 0.448103E+11 0.148135E+11 0.135457E+12 0.526468E+11 0.426364E+11 0.517618E+10 0.00 0.133062E+11 0.00 0.00 0.395411E+10 0.746623E+10 0.00
October 0.471009E+11 0.199809E+11 0.139992E+12 0.544023E+11 0.441117E+11 0.264974E+10 0.00 0.184319E+10 0.00 0.00 0.144926E+11 0.770291E+10 0.00
November 0.462012E+11 0.239637E+11 0.135531E+12 0.526484E+11 0.480353E+11 0.132037E+10 0.00 0.128703E+09 0.00 0.00 0.204929E+11 0.744881E+10 0.00
December 0.480916E+11 0.284278E+11 0.139944E+12 0.544017E+11 0.521399E+11 0.166487E+10 0.00 0.124281E+09 0.00 0.00 0.210465E+11 0.771240E+10 0.00
                           
Annual Sum or Average 0.545088E+12 0.192369E+12 0.164846E+13 0.640544E+12 0.560672E+12 0.579929E+11 0.00 0.321959E+12 0.00 0.00 0.140954E+12 0.907423E+11 0.00
Minimum of Months 0.427397E+11 0.444184E+10 0.126445E+12 0.491378E+11 0.426364E+11 0.132037E+10 0.00 0.124281E+09 0.00 0.00 0.240789E+10 0.696187E+10 0.00
Maximum of Months 0.480916E+11 0.284278E+11 0.140067E+12 0.544046E+11 0.521399E+11 0.968611E+10 0.00 0.964043E+11 0.00 0.00 0.211760E+11 0.771241E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.700893E+12 0.00 0.313050E+12 0.00 0.00
February 0.137204E+12 0.00 0.549684E+12 0.00 0.282853E+12 0.00 0.00
March 0.152024E+12 0.00 0.326345E+12 0.00 0.313278E+12 0.00 0.00
April 0.146956E+12 0.00 0.137854E+12 0.00 0.303085E+12 0.00 0.00
May 0.151978E+12 0.00 0.632802E+11 0.00 0.312299E+12 0.00 0.00
June 0.147114E+12 0.00 0.404414E+10 0.00 0.298018E+12 0.00 0.00
July 0.151820E+12 0.00 0.197136E+10 0.00 0.303577E+12 0.00 0.00
August 0.152039E+12 0.00 0.178130E+11 0.00 0.300952E+12 0.00 0.00
September 0.146971E+12 0.00 0.133828E+12 0.00 0.290821E+12 0.00 0.00
October 0.151903E+12 0.00 0.222658E+12 0.00 0.302564E+12 0.00 0.00
November 0.147091E+12 0.00 0.641541E+12 0.00 0.296546E+12 0.00 0.00
December 0.151820E+12 0.00 0.815702E+12 0.00 0.311166E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.361561E+13 0.00 0.362821E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.197136E+10 0.00 0.282853E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.815702E+12 0.00 0.313278E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 45764.37 02-JAN-20:10 12338.45 01-JAN-00:10 88863.15 02-JAN-07:10 39153.73 02-JAN-07:19 30078.80 13-JAN-19:19 2269.36 27-JAN-06:10 0.00 01-JAN-00:10
February 45764.37 01-FEB-20:10 12338.45 01-FEB-00:10 88863.15 01-FEB-07:10 39153.73 01-FEB-07:19 28724.20 25-FEB-19:19 2333.70 15-FEB-16:19 0.00 01-FEB-00:10
March 45764.37 01-MAR-20:10 12338.45 01-MAR-00:10 88863.15 01-MAR-07:10 39153.73 01-MAR-07:19 27092.94 01-MAR-19:19 2933.16 31-MAR-15:30 0.00 01-MAR-00:10
April 45764.37 03-APR-19:40 12338.45 01-APR-00:10 88863.15 03-APR-06:10 39153.73 03-APR-06:19 25482.39 21-APR-18:10 3975.30 22-APR-15:39 0.00 01-APR-00:10
May 44592.48 02-MAY-19:00 12338.45 01-MAY-00:10 88863.15 01-MAY-06:10 39151.70 16-MAY-06:19 27231.89 31-MAY-21:00 4141.36 31-MAY-15:09 0.00 01-MAY-00:10
June 44070.94 02-JUN-19:00 12338.45 01-JUN-00:10 88863.15 01-JUN-06:10 39151.68 27-JUN-06:19 31412.10 22-JUN-21:00 4603.18 21-JUN-18:10 0.00 01-JUN-00:10
July 43720.36 26-JUL-19:00 12338.45 01-JUL-00:10 88863.15 03-JUL-06:10 39151.86 25-JUL-06:19 31376.78 11-JUL-21:00 4641.78 21-JUL-15:20 0.00 01-JUL-00:10
August 45764.37 29-AUG-19:30 12338.45 01-AUG-00:10 88863.15 01-AUG-06:10 39151.85 29-AUG-06:19 29235.16 02-AUG-21:00 4618.33 11-AUG-15:30 0.00 01-AUG-00:10
September 45764.37 01-SEP-19:30 12338.45 01-SEP-00:10 88863.15 01-SEP-06:10 39153.73 13-SEP-06:19 25101.81 08-SEP-18:10 3941.06 01-SEP-16:10 0.00 01-SEP-00:10
October 45764.37 02-OCT-19:10 12338.45 01-OCT-00:10 88863.15 02-OCT-06:10 39153.73 02-OCT-06:19 25760.76 30-OCT-18:10 3141.10 03-OCT-15:20 0.00 01-OCT-00:10
November 45764.37 01-NOV-19:10 12338.45 01-NOV-00:10 88863.15 01-NOV-06:10 39153.73 01-NOV-06:19 28334.49 09-NOV-19:19 2262.14 18-NOV-06:10 0.00 01-NOV-00:10
December 45764.37 01-DEC-20:10 12338.45 01-DEC-00:10 88863.15 01-DEC-07:10 39153.73 01-DEC-07:19 29742.02 04-DEC-19:19 2275.31 24-DEC-19:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 43720.36   12338.45   88863.15   39151.68   25101.81   2262.14   0.00  
Maximum of Months 45764.37   12338.45   88863.15   39153.73   31412.10   4641.78   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 1729.45 23-JAN-06:10 0.00 0.00 8265.52 01-JAN-00:10 4738.77 26-JAN-19:10 0.00
February 2104.95 15-FEB-16:19 0.00 0.00 8265.52 01-FEB-00:10 4738.68 02-FEB-19:10 0.00
March 11686.39 31-MAR-15:20 0.00 0.00 8265.52 01-MAR-00:10 4738.62 30-MAR-18:10 0.00
April 44322.28 22-APR-15:20 0.00 0.00 8265.52 01-APR-00:10 4737.65 04-APR-06:30 0.00
May 65881.34 31-MAY-15:00 0.00 0.00 8265.52 28-MAY-01:39 4738.25 03-MAY-06:19 0.00
June 100655.74 20-JUN-18:19 0.00 0.00 8265.52 03-JUN-15:50 4738.58 08-JUN-18:10 0.00
July 114978.03 29-JUL-15:30 0.00 0.00 8265.52 06-JUL-15:00 4738.73 13-JUL-18:10 0.00
August 95788.47 11-AUG-18:10 0.00 0.00 8265.52 11-AUG-15:20 4738.47 10-AUG-18:10 0.00
September 41613.96 09-SEP-15:20 0.00 0.00 8265.52 09-SEP-05:49 4738.28 20-SEP-06:19 0.00
October 16412.27 03-OCT-15:20 0.00 0.00 8265.52 03-OCT-03:00 4738.75 12-OCT-18:10 0.00
November 1591.73 04-NOV-05:10 0.00 0.00 8265.52 01-NOV-00:10 4738.69 15-NOV-19:10 0.00
December 2225.97 24-DEC-19:10 0.00 0.00 8265.52 01-DEC-00:10 4738.24 18-DEC-19:10 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 1591.73   0.00 0.00 8265.52   4737.65   0.00
Maximum of Months 114978.03   0.00 0.00 8265.52   4738.77   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 219453.60 30-JAN-20:10 45764.37 86131.51 12338.45 31526.42 28492.05 1258.35 0.00 0.00 0.00
February 217953.92 27-FEB-20:10 45764.37 86131.51 12338.45 31526.42 27067.22 1365.71 0.00 0.00 0.00
March 214793.80 27-MAR-19:30 45764.37 86131.51 12338.45 31530.53 21852.30 2216.86 0.00 976.19 0.00
April 221464.02 21-APR-18:10 36642.55 77265.07 0.00 31327.27 25482.39 3833.48 0.00 39612.46 0.00
May 241332.49 30-MAY-19:10 41336.01 86131.51 0.00 31523.14 23131.12 3872.57 0.00 50349.26 0.00
June 301443.71 29-JUN-19:10 41208.81 86131.51 0.00 31523.14 27000.70 4539.97 0.00 97264.07 0.00
July 298855.31 11-JUL-19:10 41208.81 86131.51 0.00 31523.14 27976.01 4548.89 0.00 94204.09 0.00
August 291274.84 11-AUG-19:10 41728.69 86131.51 0.00 31523.32 26902.92 4536.68 0.00 87255.36 0.00
September 222050.45 07-SEP-19:49 45764.37 86131.51 12338.45 31530.53 22653.62 3206.71 0.00 13224.36 0.00
October 214886.85 23-OCT-19:30 45764.37 86131.51 12338.45 31530.53 22330.91 2182.27 0.00 626.22 0.00
November 218267.18 30-NOV-20:10 45764.37 86131.51 12338.45 31526.42 27414.31 1462.14 0.00 0.00 0.00
December 220062.21 15-DEC-20:40 45764.37 86131.51 12338.45 31530.53 29323.64 1446.78 0.00 0.00 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 214793.80   36642.55 77265.07 0.00 31327.27 21852.30 1258.35 0.00 0.00 0.00
Maximum of Months 301443.71   45764.37 86131.51 12338.45 31530.53 29323.64 4548.89 0.00 97264.07 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 783717.68 12-JAN-10:20 0.00 312560.72 02-JAN-21:40 0.00
February 104248.32 01-FEB-18:10 0.00 731428.99 27-FEB-07:10 0.00 312582.23 22-FEB-21:49 0.00
March 104248.32 01-MAR-18:10 0.00 671924.99 01-MAR-07:10 0.00 312595.80 03-MAR-21:30 0.00
April 104248.32 01-APR-17:10 0.00 227329.63 03-APR-08:09 0.00 312582.66 26-APR-20:49 0.00
May 104248.32 01-MAY-17:10 0.00 163922.45 28-MAY-01:30 0.00 312572.74 11-MAY-20:19 0.00
June 104248.32 01-JUN-17:10 0.00 101790.53 02-JUN-03:00 0.00 309321.80 01-JUN-20:30 0.00
July 104248.32 01-JUL-17:10 0.00 34137.35 31-JUL-03:00 0.00 303583.36 03-JUL-20:40 0.00
August 104248.32 01-AUG-17:10 0.00 175525.59 31-AUG-04:10 0.00 299470.38 01-AUG-20:40 0.00
September 104248.32 01-SEP-17:10 0.00 198423.78 27-SEP-08:09 0.00 298487.16 29-SEP-20:40 0.00
October 104248.32 02-OCT-17:10 0.00 250492.98 27-OCT-08:20 0.00 302464.30 31-OCT-20:19 0.00
November 104248.32 01-NOV-17:10 0.00 719883.22 29-NOV-10:09 0.00 307602.61 29-NOV-21:49 0.00
December 104248.32 01-DEC-18:10 0.00 750826.70 15-DEC-10:50 0.00 312495.03 29-DEC-21:19 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 34137.35   0.00 298487.16   0.00
Maximum of Months 104248.32   0.00 783717.68   0.00 312595.80   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 56.17 18.90 56.17 18.90 0.00 18.90 0.00 18.90
February 6.67 19.90 6.67 19.90 0.00 19.90 0.00 19.90
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 4.17 20.28 4.17 20.28 0.00 20.28 0.00 20.28
December 19.17 19.55 19.17 19.55 0.00 19.55 0.00 19.55
                 
Annual Sum or Average 86.17 19.18 86.17 19.18 0.00 19.18 0.00 19.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 56.17 20.28 56.17 20.28 0.00 20.28 0.00 20.28



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 31.00 19.97 31.00 19.97 0.00 19.97 0.00 19.97
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 6.67 20.15 6.67 20.15 0.00 20.15 0.00 20.15
                 
Annual Sum or Average 37.67 20.00 37.67 20.00 0.00 20.00 0.00 20.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31.00 20.15 31.00 20.15 0.00 20.15 0.00 20.15



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 32.50 20.21 32.50 20.21 0.00 20.21 0.00 20.21
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 32.50 20.21 32.50 20.21 0.00 20.21 0.00 20.21
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 32.50 20.21 32.50 20.21 0.00 20.21 0.00 20.21



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 56.50 19.62 56.50 19.62 0.00 19.62 0.00 19.62
February 10.17 20.22 10.17 20.22 0.00 20.22 0.00 20.22
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 15.00 20.11 15.00 20.11 0.00 20.11 0.00 20.11
                 
Annual Sum or Average 81.67 19.78 81.67 19.78 0.00 19.78 0.00 19.78
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 56.50 20.22 56.50 20.22 0.00 20.22 0.00 20.22



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 36.17 19.20 36.17 19.20 0.00 19.20 0.00 19.20
February 1.33 20.16 1.33 20.16 0.00 20.16 0.00 20.16
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 3.83 20.24 3.83 20.24 0.00 20.24 0.00 20.24
December 11.33 19.39 11.33 19.39 0.00 19.39 0.00 19.39
                 
Annual Sum or Average 52.67 19.34 52.67 19.34 0.00 19.34 0.00 19.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 36.17 20.24 36.17 20.24 0.00 20.24 0.00 20.24



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 19.67 19.94 19.67 19.94 0.00 19.94 0.00 19.94
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 5.83 20.14 5.83 20.14 0.00 20.14 0.00 20.14
                 
Annual Sum or Average 25.50 19.98 25.50 19.98 0.00 19.98 0.00 19.98
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19.67 20.14 19.67 20.14 0.00 20.14 0.00 20.14



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 31.00 20.26 31.00 20.26 0.00 20.26 0.00 20.26
February 2.83 20.38 2.83 20.38 0.00 20.38 0.00 20.38
March 0.17 20.45 0.17 20.45 0.00 20.45 0.00 20.45
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 21.73 0.17 21.73
June 0.00 0.00 0.00 0.00 0.83 21.80 0.83 21.80
July 0.00 0.00 0.00 0.00 0.83 21.74 0.83 21.74
August 0.00 0.00 0.00 0.00 0.67 21.78 0.67 21.78
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 5.83 20.29 5.83 20.29 0.00 20.29 0.00 20.29
December 14.17 20.33 14.17 20.33 0.00 20.33 0.00 20.33
                 
Annual Sum or Average 54.00 20.29 54.00 20.29 2.50 20.32 2.50 20.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31.00 20.45 31.00 20.45 0.83 21.80 0.83 21.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 39.67 20.08 39.67 20.08 0.00 20.08 0.00 20.08
February 6.00 20.35 6.00 20.35 0.00 20.35 0.00 20.35
March 0.50 20.35 0.50 20.35 0.00 20.35 0.00 20.35
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.33 21.78 1.33 21.78
June 0.00 0.00 0.00 0.00 3.00 22.03 3.00 22.03
July 0.00 0.00 0.00 0.00 2.17 21.87 2.17 21.87
August 0.00 0.00 0.00 0.00 0.33 21.86 0.33 21.86
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 10.33 20.30 10.33 20.30 0.00 20.30 0.00 20.30
December 17.67 20.29 17.67 20.29 0.00 20.29 0.00 20.29
                 
Annual Sum or Average 74.17 20.18 74.17 20.18 6.83 20.26 6.83 20.33
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 39.67 20.35 39.67 20.35 3.00 22.03 3.00 22.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 52.67 19.66 52.67 19.66 0.00 19.66 0.00 19.66
February 26.00 20.17 26.00 20.17 0.00 20.17 0.00 20.17
March 3.67 20.29 3.67 20.29 0.00 20.29 0.00 20.29
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.00 21.74 1.00 21.74
June 0.00 0.00 0.00 0.00 8.33 21.88 8.33 21.88
July 0.00 0.00 0.00 0.00 7.67 21.83 7.67 21.83
August 0.00 0.00 0.00 0.00 2.17 21.74 2.17 21.74
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 1.50 20.28 1.50 20.28 0.00 20.28 0.00 20.28
November 42.17 20.21 42.17 20.21 0.00 20.21 0.00 20.21
December 50.00 20.17 50.00 20.17 0.00 20.17 0.00 20.17
                 
Annual Sum or Average 176.00 20.03 176.00 20.03 19.17 20.12 19.17 20.21
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 52.67 20.29 52.67 20.29 8.33 21.88 8.33 21.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 35.33 20.18 35.33 20.18 0.00 20.18 0.00 20.18
February 2.17 20.42 2.17 20.42 0.00 20.42 0.00 20.42
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.67 21.78 1.67 21.78
June 0.00 0.00 0.00 0.00 0.83 21.82 0.83 21.82
July 0.00 0.00 0.00 0.00 1.33 21.85 1.33 21.85
August 0.00 0.00 0.00 0.00 0.50 21.73 0.50 21.73
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 8.17 20.33 8.17 20.33 0.00 20.33 0.00 20.33
December 16.67 20.32 16.67 20.32 0.00 20.32 0.00 20.32
                 
Annual Sum or Average 62.33 20.25 62.33 20.25 4.33 20.30 4.33 20.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 35.33 20.42 35.33 20.42 1.67 21.85 1.67 21.85



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 41.67 20.00 41.67 20.00 0.00 20.00 0.00 20.00
February 5.50 20.40 5.50 20.40 0.00 20.40 0.00 20.40
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 2.33 21.87 2.33 21.87
June 0.00 0.00 0.00 0.00 5.00 22.09 5.00 22.09
July 0.00 0.00 0.00 0.00 7.00 22.30 7.00 22.30
August 0.00 0.00 0.00 0.00 0.50 21.90 0.50 21.90
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 11.67 20.29 11.67 20.29 0.00 20.29 0.00 20.29
December 19.00 20.26 19.00 20.26 0.00 20.26 0.00 20.26
                 
Annual Sum or Average 77.83 20.13 77.83 20.13 14.83 20.31 14.83 20.46
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 41.67 20.40 41.67 20.40 7.00 22.30 7.00 22.30



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 41.17 20.14 41.17 20.14 0.00 20.14 0.00 20.14
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 6.67 20.32 6.67 20.32 0.00 20.32 0.00 20.32
                 
Annual Sum or Average 47.83 20.16 47.83 20.16 0.00 20.16 0.00 20.16
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 41.17 20.32 41.17 20.32 0.00 20.32 0.00 20.32



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 41.33 19.95 41.33 19.95 0.00 19.95 0.00 19.95
February 3.50 20.34 3.50 20.34 0.00 20.34 0.00 20.34
March 0.33 20.46 0.33 20.46 0.00 20.46 0.00 20.46
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 21.88 0.17 21.88
June 0.00 0.00 0.00 0.00 1.33 21.81 1.33 21.81
July 0.00 0.00 0.00 0.00 1.33 21.74 1.33 21.74
August 0.00 0.00 0.00 0.00 0.50 21.82 0.50 21.82
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 9.17 20.26 9.17 20.26 0.00 20.26 0.00 20.26
December 20.33 20.27 20.33 20.27 0.00 20.27 0.00 20.27
                 
Annual Sum or Average 74.67 20.09 74.67 20.09 3.33 20.13 3.33 20.17
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 41.33 20.46 41.33 20.46 1.33 21.88 1.33 21.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 45.83 19.66 45.83 19.66 0.00 19.66 0.00 19.66
February 10.50 20.33 10.50 20.33 0.00 20.33 0.00 20.33
March 1.17 20.40 1.17 20.40 0.00 20.40 0.00 20.40
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.50 21.92 1.50 21.92
June 0.00 0.00 0.00 0.00 5.00 22.02 5.00 22.02
July 0.00 0.00 0.00 0.00 3.67 21.92 3.67 21.92
August 0.00 0.00 0.00 0.00 0.83 21.92 0.83 21.92
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 18.67 20.26 18.67 20.26 0.00 20.26 0.00 20.26
December 26.67 20.20 26.67 20.20 0.00 20.20 0.00 20.20
                 
Annual Sum or Average 102.83 19.99 102.83 19.99 11.00 20.09 11.00 20.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 45.83 20.40 45.83 20.40 5.00 22.02 5.00 22.02



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 12.83 20.20 12.83 20.20 0.00 20.20 0.00 20.20
February 1.00 20.47 1.00 20.47 0.00 20.47 0.00 20.47
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.33 21.76 0.33 21.76
June 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
July 0.00 0.00 0.00 0.00 0.50 21.77 0.50 21.77
August 0.00 0.00 0.00 0.00 1.17 21.76 1.17 21.76
September 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 4.17 20.34 4.17 20.34 0.00 20.34 0.00 20.34
December 11.50 20.31 11.50 20.31 0.00 20.31 0.00 20.31
                 
Annual Sum or Average 29.50 20.27 29.50 20.27 2.33 20.33 2.33 20.38
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12.83 20.47 12.83 20.47 1.17 21.77 1.17 21.77



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 12.67 19.27 12.67 19.27 0.00 19.27 0.00 19.27
February 0.17 20.44 0.17 20.44 0.00 20.44 0.00 20.44
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 4.83 19.94 4.83 19.94 0.00 19.94 0.00 19.94
                 
Annual Sum or Average 17.67 19.46 17.67 19.46 0.00 19.46 0.00 19.46
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12.67 20.44 12.67 20.44 0.00 20.44 0.00 20.44



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 7.33 19.31 7.33 19.31 0.00 19.31 0.00 19.31
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 20.28 0.17 20.28 0.00 20.28 0.00 20.28
                 
Annual Sum or Average 7.50 19.33 7.50 19.33 0.00 19.33 0.00 19.33
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7.33 20.28 7.33 20.28 0.00 20.28 0.00 20.28



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 57.33 19.57 57.33 19.57 0.00 19.57 0.00 19.57
February 4.00 20.32 4.00 20.32 0.00 20.32 0.00 20.32
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 13.17 20.05 13.17 20.05 0.00 20.05 0.00 20.05
                 
Annual Sum or Average 74.50 19.70 74.50 19.70 0.00 19.70 0.00 19.70
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 57.33 20.32 57.33 20.32 0.00 20.32 0.00 20.32



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 22.09 46.33 22.02 46.33 21.97
February 672.00 21.55 103.00 21.48 103.00 21.43
March 744.00 21.45 98.67 21.41 98.67 21.37
April 720.00 21.65 1.33 21.65 1.33 21.65
May 744.00 21.74 0.00 21.74 0.00 21.74
June 720.00 22.00 0.00 22.00 0.00 22.00
July 744.00 22.58 0.00 22.58 0.00 22.58
August 722.83 23.21 0.00 23.21 0.00 23.21
September 699.83 23.54 0.00 23.54 0.00 23.54
October 744.00 23.57 0.00 23.57 0.00 23.57
November 720.00 23.27 0.00 23.27 0.00 23.27
December 744.00 22.64 0.00 22.64 0.00 22.64
             
Annual Sum or Average 8718.67 22.44 249.33 22.40 249.33 22.37
Minimum of Months 672.00 21.45 0.00 21.41 0.00 21.37
Maximum of Months 744.00 23.57 103.00 23.57 103.00 23.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.84 738.50 20.84 738.50 20.84
February 672.00 21.06 601.17 21.03 601.17 21.01
March 685.00 21.23 416.67 21.14 416.67 21.11
April 552.67 21.88 115.67 21.97 61.50 21.89
May 485.83 22.54 83.83 22.75 0.00 22.75
June 269.33 22.90 233.50 23.40 0.00 23.40
July 242.33 22.81 370.17 23.51 0.00 23.51
August 366.33 22.64 236.33 23.17 0.00 23.17
September 620.83 21.76 51.00 21.91 5.83 21.90
October 722.33 21.16 346.67 21.12 343.17 21.09
November 720.00 21.00 704.67 20.99 704.67 20.99
December 744.00 20.95 744.00 20.95 744.00 20.95
             
Annual Sum or Average 6824.67 21.50 4642.17 21.55 3615.50 21.41
Minimum of Months 242.33 20.84 51.00 20.84 0.00 20.84
Maximum of Months 744.00 22.90 744.00 23.51 744.00 23.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.97 406.00 20.95 406.00 20.93
February 672.00 21.06 260.83 21.04 260.83 21.03
March 744.00 21.21 99.00 21.19 99.00 21.17
April 720.00 22.01 1.17 22.01 1.17 22.01
May 742.67 22.57 0.00 22.57 0.00 22.57
June 624.33 22.88 14.67 22.90 0.00 22.90
July 560.17 22.79 47.33 22.87 0.00 22.87
August 641.17 22.74 18.17 22.77 0.00 22.77
September 720.00 22.09 0.00 22.09 0.00 22.09
October 744.00 21.38 20.00 21.37 20.00 21.36
November 720.00 21.03 364.50 21.02 364.50 21.01
December 744.00 21.00 512.83 20.99 512.83 20.99
             
Annual Sum or Average 8376.33 21.77 1744.50 21.66 1664.33 21.56
Minimum of Months 560.17 20.97 0.00 20.95 0.00 20.93
Maximum of Months 744.00 22.88 512.83 22.90 512.83 22.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.97 677.67 20.97 677.67 20.96
February 672.00 21.08 506.50 21.05 506.50 21.03
March 744.00 21.32 367.83 21.22 367.83 21.17
April 720.00 22.80 60.50 22.67 60.50 22.55
May 744.00 23.93 0.00 23.93 0.00 23.93
June 501.67 24.00 3.33 24.00 0.00 24.00
July 122.83 23.99 10.00 24.00 0.00 24.00
August 314.33 23.98 5.83 23.98 0.00 23.98
September 720.00 23.62 0.00 23.62 0.00 23.62
October 744.00 22.18 128.83 22.01 128.83 21.88
November 720.00 21.02 683.83 21.01 683.83 21.01
December 744.00 21.00 696.50 21.00 696.50 21.00
             
Annual Sum or Average 7490.83 22.25 3140.83 21.88 3121.67 21.68
Minimum of Months 122.83 20.97 0.00 20.97 0.00 20.96
Maximum of Months 744.00 24.00 696.50 24.00 696.50 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.89 723.17 20.89 723.17 20.89
February 672.00 20.98 605.50 20.98 605.50 20.98
March 744.00 21.00 575.50 21.00 575.50 21.00
April 720.00 21.03 174.50 21.03 174.50 21.02
May 744.00 21.39 0.00 21.39 0.00 21.39
June 720.00 21.97 0.00 21.97 0.00 21.97
July 744.00 22.03 0.00 22.03 0.00 22.03
August 744.00 21.79 0.00 21.79 0.00 21.79
September 720.00 21.12 0.00 21.12 0.00 21.12
October 744.00 21.00 247.67 21.00 247.67 21.00
November 720.00 20.99 708.83 20.99 708.83 20.99
December 744.00 20.97 739.17 20.97 739.17 20.97
             
Annual Sum or Average 8760.00 21.27 3774.33 21.18 3774.33 21.13
Minimum of Months 672.00 20.89 0.00 20.89 0.00 20.89
Maximum of Months 744.00 22.03 739.17 22.03 739.17 22.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 127.17 24.00 719.50 24.00 127.17 24.00
February 121.17 24.00 652.83 24.00 121.17 24.00
March 148.83 24.00 730.17 24.00 148.83 24.00
April 169.83 24.00 720.00 24.00 169.83 24.00
May 238.83 24.00 744.00 24.00 238.83 24.00
June 342.00 24.00 720.00 24.00 342.00 24.00
July 462.83 24.00 744.00 24.00 462.83 24.00
August 359.50 24.00 744.00 24.00 359.50 24.00
September 236.33 24.00 720.00 24.00 236.33 24.00
October 169.00 24.00 744.00 24.00 169.00 24.00
November 122.17 24.00 699.00 24.00 122.17 24.00
December 124.50 24.00 708.33 24.00 124.50 24.00
             
Annual Sum or Average 2622.17 24.00 8645.83 24.00 2622.17 24.00
Minimum of Months 121.17 24.00 652.83 24.00 121.17 24.00
Maximum of Months 462.83 24.00 744.00 24.00 462.83 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.91 651.50 20.91 651.50 20.90
February 672.00 21.04 362.33 21.02 362.33 21.02
March 704.17 21.28 105.00 21.28 94.67 21.25
April 601.67 21.90 73.33 22.10 4.67 22.09
May 605.50 22.21 64.33 22.37 0.00 22.37
June 410.67 22.30 143.17 22.63 0.00 22.63
July 353.17 22.07 249.83 22.65 5.00 22.66
August 467.50 22.09 172.00 22.51 3.00 22.51
September 656.67 21.77 38.33 21.89 0.00 21.89
October 729.00 21.26 70.50 21.26 65.67 21.24
November 720.00 21.00 617.00 21.00 617.00 21.00
December 744.00 20.97 703.83 20.97 703.83 20.97
             
Annual Sum or Average 7408.33 21.48 3251.17 21.51 2507.67 21.41
Minimum of Months 353.17 20.91 38.33 20.91 0.00 20.90
Maximum of Months 744.00 22.30 703.83 22.65 703.83 22.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.17 291.83 21.10 291.83 21.06
February 672.00 21.30 163.67 21.24 163.67 21.20
March 744.00 21.66 21.83 21.64 21.83 21.62
April 714.50 22.51 0.00 22.51 0.00 22.51
May 700.50 22.90 0.00 22.90 0.00 22.90
June 391.83 22.83 64.67 22.98 0.00 22.98
July 316.17 22.74 227.33 23.18 11.50 23.20
August 379.50 22.72 120.00 23.00 5.50 23.00
September 697.50 22.53 0.00 22.53 0.00 22.53
October 744.00 21.86 0.00 21.86 0.00 21.86
November 720.00 21.23 241.50 21.17 241.50 21.14
December 744.00 21.11 386.00 21.07 386.00 21.05
             
Annual Sum or Average 7568.00 21.94 1516.83 21.91 1121.83 21.81
Minimum of Months 316.17 21.11 0.00 21.07 0.00 21.05
Maximum of Months 744.00 22.90 386.00 23.18 386.00 23.20



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.37 744.00 20.37 744.00 20.37
February 672.00 20.44 672.00 20.44 672.00 20.44
March 744.00 20.72 659.50 20.68 659.50 20.67
April 712.83 21.39 201.50 21.27 201.50 21.19
May 729.83 21.67 0.00 21.67 0.00 21.67
June 647.00 21.59 4.33 21.60 0.00 21.60
July 649.00 21.53 5.00 21.55 0.00 21.55
August 684.50 21.57 0.33 21.57 0.00 21.57
September 717.83 21.31 112.83 21.22 112.83 21.15
October 744.00 20.67 578.50 20.61 578.50 20.59
November 720.00 20.40 720.00 20.40 720.00 20.40
December 744.00 20.39 744.00 20.39 744.00 20.39
             
Annual Sum or Average 8509.00 20.99 4442.00 20.82 4432.33 20.73
Minimum of Months 647.00 20.37 0.00 20.37 0.00 20.37
Maximum of Months 744.00 21.67 744.00 21.67 744.00 21.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.35 744.00 20.35 744.00 20.35
February 672.00 20.41 672.00 20.41 672.00 20.41
March 744.00 20.48 728.00 20.48 728.00 20.47
April 719.83 21.05 321.17 20.92 321.17 20.86
May 687.50 21.69 37.00 21.92 2.67 21.93
June 587.00 22.17 102.67 22.78 27.67 22.98
July 577.67 21.90 109.50 22.45 6.67 22.50
August 660.00 21.86 58.17 22.18 6.00 22.23
September 717.33 21.09 167.00 20.98 166.33 20.91
October 744.00 20.53 665.50 20.50 665.50 20.49
November 720.00 20.39 720.00 20.39 720.00 20.39
December 744.00 20.39 744.00 20.39 744.00 20.39
             
Annual Sum or Average 8317.33 20.98 5069.00 20.90 4804.00 20.79
Minimum of Months 577.67 20.35 37.00 20.35 2.67 20.35
Maximum of Months 744.00 22.17 744.00 22.78 744.00 22.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.41 744.00 20.41 744.00 20.41
February 672.00 20.52 662.17 20.52 662.17 20.52
March 744.00 20.72 651.33 20.69 651.33 20.68
April 720.00 21.12 245.83 21.05 245.83 21.01
May 744.00 21.66 0.00 21.66 0.00 21.66
June 712.50 22.11 0.00 22.11 0.00 22.11
July 717.00 22.07 1.33 22.07 0.00 22.07
August 741.17 21.86 0.00 21.86 0.00 21.86
September 720.00 21.25 30.17 21.22 30.17 21.19
October 744.00 20.85 408.17 20.77 408.17 20.73
November 720.00 20.46 720.00 20.46 720.00 20.46
December 744.00 20.43 742.33 20.43 742.33 20.43
             
Annual Sum or Average 8722.67 21.12 4205.33 20.93 4204.00 20.83
Minimum of Months 672.00 20.41 0.00 20.41 0.00 20.41
Maximum of Months 744.00 22.11 744.00 22.11 744.00 22.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.36 744.00 20.36 744.00 20.36
February 672.00 20.48 664.83 20.47 664.83 20.47
March 744.00 21.00 553.50 20.90 553.50 20.86
April 713.83 21.53 173.00 21.42 173.00 21.35
May 667.67 21.60 0.83 21.60 0.83 21.60
June 594.50 21.47 7.33 21.49 0.00 21.49
July 602.83 21.44 17.50 21.49 0.00 21.49
August 662.33 21.58 5.17 21.59 0.00 21.59
September 713.17 21.44 65.83 21.39 65.83 21.35
October 744.00 20.79 518.17 20.70 518.17 20.66
November 720.00 20.40 720.00 20.40 720.00 20.40
December 744.00 20.39 744.00 20.39 744.00 20.39
             
Annual Sum or Average 8322.33 21.02 4214.17 20.85 4184.17 20.76
Minimum of Months 594.50 20.36 0.83 20.36 0.00 20.36
Maximum of Months 744.00 21.60 744.00 21.60 744.00 21.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.35 744.00 20.35 744.00 20.35
February 672.00 20.42 671.83 20.42 671.83 20.42
March 744.00 20.66 664.83 20.63 664.83 20.62
April 720.00 21.30 278.67 21.16 278.67 21.08
May 714.67 21.91 2.17 21.91 1.50 21.91
June 547.83 21.91 34.67 22.10 1.83 22.11
July 515.83 21.85 104.33 22.38 11.33 22.48
August 659.00 21.93 16.83 22.00 0.00 22.00
September 720.00 21.32 129.83 21.23 129.83 21.17
October 744.00 20.63 588.33 20.57 588.33 20.55
November 720.00 20.39 720.00 20.39 720.00 20.39
December 744.00 20.38 744.00 20.38 744.00 20.38
             
Annual Sum or Average 8245.33 21.04 4699.50 20.89 4556.17 20.78
Minimum of Months 515.83 20.35 2.17 20.35 0.00 20.35
Maximum of Months 744.00 21.93 744.00 22.38 744.00 22.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.94 655.50 20.94 655.50 20.94
February 672.00 21.00 525.67 21.00 525.67 21.00
March 744.00 21.00 419.83 21.00 419.83 21.00
April 720.00 21.53 62.00 21.49 62.00 21.45
May 744.00 22.56 0.00 22.56 0.00 22.56
June 706.33 23.28 0.00 23.28 0.00 23.28
July 652.83 23.18 0.00 23.18 0.00 23.18
August 743.00 22.82 0.00 22.82 0.00 22.82
September 720.00 21.54 1.83 21.54 1.83 21.54
October 744.00 21.01 215.33 21.01 215.33 21.01
November 720.00 21.00 650.17 21.00 650.17 21.00
December 744.00 20.98 698.33 20.98 698.33 20.98
             
Annual Sum or Average 8654.17 21.73 3228.67 21.52 3228.67 21.41
Minimum of Months 652.83 20.94 0.00 20.94 0.00 20.94
Maximum of Months 744.00 23.28 698.33 23.28 698.33 23.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.34 744.00 20.34 744.00 20.34
February 672.00 20.41 672.00 20.41 672.00 20.41
March 744.00 20.60 693.17 20.58 693.17 20.57
April 709.33 21.28 282.83 21.14 282.83 21.06
May 719.33 21.61 16.67 21.59 16.67 21.57
June 634.00 21.54 9.00 21.56 0.00 21.56
July 632.83 21.47 11.50 21.51 0.00 21.51
August 676.00 21.51 11.83 21.51 8.33 21.51
September 716.33 21.20 182.50 21.08 182.50 21.00
October 744.00 20.58 660.50 20.55 660.50 20.53
November 720.00 20.39 720.00 20.39 720.00 20.39
December 744.00 20.38 744.00 20.38 744.00 20.38
             
Annual Sum or Average 8455.83 20.92 4748.00 20.76 4724.00 20.68
Minimum of Months 632.83 20.34 9.00 20.34 0.00 20.34
Maximum of Months 744.00 21.61 744.00 21.59 744.00 21.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.31 744.00 20.31 744.00 20.31
February 672.00 20.39 672.00 20.39 672.00 20.39
March 744.00 20.45 738.83 20.44 738.83 20.44
April 719.00 20.96 396.00 20.83 396.00 20.77
May 688.17 21.69 65.00 21.94 31.67 21.97
June 590.33 22.32 116.67 23.02 44.33 23.33
July 566.33 21.93 117.17 22.56 15.83 22.68
August 655.67 21.87 85.83 22.24 32.67 22.32
September 716.83 20.96 241.00 20.85 240.00 20.78
October 744.00 20.47 729.83 20.47 729.83 20.46
November 720.00 20.37 720.00 20.37 720.00 20.37
December 744.00 20.36 744.00 20.36 744.00 20.36
             
Annual Sum or Average 8304.33 20.96 5370.33 20.89 5109.17 20.79
Minimum of Months 566.33 20.31 65.00 20.31 15.83 20.31
Maximum of Months 744.00 22.32 744.00 23.02 744.00 23.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.41 744.00 20.41 744.00 20.41
February 672.00 20.77 611.33 20.70 611.33 20.67
March 730.50 21.18 502.17 21.04 502.17 20.98
April 659.67 21.44 133.00 21.37 129.17 21.31
May 667.00 21.54 3.00 21.55 0.17 21.55
June 618.50 21.50 15.50 21.55 0.00 21.55
July 630.67 21.48 33.50 21.57 0.00 21.57
August 648.17 21.50 39.00 21.60 0.00 21.60
September 678.83 21.41 38.33 21.38 35.00 21.35
October 733.83 20.98 446.83 20.86 446.83 20.80
November 720.00 20.48 713.00 20.47 713.00 20.47
December 744.00 20.40 744.00 20.40 744.00 20.40
             
Annual Sum or Average 8247.17 21.07 4023.67 20.92 3925.67 20.83
Minimum of Months 618.50 20.40 3.00 20.40 0.00 20.40
Maximum of Months 744.00 21.54 744.00 21.60 744.00 21.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.36 209.50 21.25 209.50 21.18
February 672.00 21.44 146.33 21.36 146.33 21.31
March 744.00 21.63 42.50 21.60 42.50 21.57
April 711.17 22.03 0.00 22.03 0.00 22.03
May 644.00 22.40 3.83 22.41 0.00 22.41
June 344.67 22.24 190.17 22.76 0.00 22.76
July 311.17 22.17 287.50 22.85 9.00 22.86
August 432.00 22.17 140.17 22.52 4.33 22.53
September 680.33 22.15 2.00 22.16 0.00 22.16
October 744.00 21.81 0.00 21.81 0.00 21.81
November 720.00 21.38 190.50 21.30 190.50 21.25
December 744.00 21.31 255.00 21.23 255.00 21.18
             
Annual Sum or Average 7491.33 21.78 1467.50 21.83 857.17 21.76
Minimum of Months 311.17 21.31 0.00 21.23 0.00 21.18
Maximum of Months 744.00 22.40 287.50 22.85 255.00 22.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.58 102.67 21.48 102.67 21.41
February 672.00 21.66 49.17 21.61 49.17 21.57
March 740.00 21.89 8.33 21.88 8.33 21.87
April 682.67 22.30 0.00 22.30 0.00 22.30
May 517.50 22.51 20.17 22.56 0.00 22.56
June 232.00 22.34 307.50 23.16 0.00 23.16
July 176.67 22.25 399.00 23.21 5.83 23.21
August 319.33 22.28 263.67 22.90 4.83 22.91
September 573.83 22.34 28.50 22.41 0.00 22.41
October 730.67 22.11 0.00 22.11 0.00 22.11
November 720.00 21.59 74.33 21.53 74.33 21.49
December 744.00 21.50 110.00 21.43 110.00 21.38
             
Annual Sum or Average 6852.67 21.95 1363.33 22.12 355.17 22.08
Minimum of Months 176.67 21.50 0.00 21.43 0.00 21.38
Maximum of Months 744.00 22.51 399.00 23.21 110.00 23.21



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 371.83 23.92 692.83 23.97 359.83 23.97
February 371.33 23.96 619.17 23.98 365.33 23.98
March 466.00 23.99 716.17 23.99 464.00 23.99
April 487.67 23.99 720.00 23.99 487.67 23.99
May 544.67 23.99 744.00 23.99 544.67 23.99
June 544.83 23.99 720.00 23.99 544.83 23.99
July 571.67 23.99 744.00 23.99 571.67 23.99
August 559.33 23.99 744.00 23.99 559.33 23.99
September 506.33 23.99 720.00 23.99 506.33 23.99
October 484.17 23.99 743.67 23.99 484.17 23.99
November 361.67 23.98 671.00 23.99 355.17 23.99
December 337.67 23.96 661.50 23.98 328.17 23.98
             
Annual Sum or Average 5607.17 23.98 8496.33 23.99 5571.17 23.99
Minimum of Months 337.67 23.92 619.17 23.97 328.17 23.97
Maximum of Months 571.67 23.99 744.00 23.99 571.67 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.89 728.50 20.89 728.50 20.89
February 672.00 20.99 606.33 20.99 606.33 20.99
March 744.00 21.05 487.00 21.03 487.00 21.02
April 720.00 22.07 87.00 21.96 87.00 21.86
May 723.50 23.53 0.00 23.53 0.00 23.53
June 114.50 23.74 62.83 23.83 0.00 23.83
July 63.17 23.57 245.33 23.91 0.00 23.91
August 309.83 23.44 55.17 23.52 0.00 23.52
September 717.67 22.29 0.00 22.29 0.00 22.29
October 744.00 21.12 246.17 21.09 246.17 21.07
November 720.00 20.99 718.17 20.99 718.17 20.99
December 744.00 20.98 740.00 20.98 740.00 20.98
             
Annual Sum or Average 7016.67 21.68 3976.50 21.52 3613.17 21.39
Minimum of Months 63.17 20.89 0.00 20.89 0.00 20.89
Maximum of Months 744.00 23.74 740.00 23.91 740.00 23.91



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.08817 19.08679 -0.2818 6.98583
February 672.00000 21.54620 20.04541 -0.4131 8.83885
March 744.00000 21.45390 22.07987 -0.4250 8.94067
April 720.00000 21.65314 23.55526 -0.3657 7.94984
May 744.00000 21.74232 27.78977 -1.4532 48.41074
June 720.00000 22.00493 42.64413 -1.2675 38.77050
July 744.00000 22.57789 50.72114 -1.0093 26.76018
August 744.00000 23.22608 43.83532 -0.8202 19.43131
September 720.00000 23.55440 32.11974 -0.7810 18.05842
October 744.00000 23.57193 25.39179 0.13161 5.47582
November 720.00000 23.27294 17.75639 0.00635 5.25286
December 744.00000 22.63803 17.10310 -0.1564 5.72627
           
Annual Sum or Average 8760.00000 22.44960 28.57474 -0.5705 16.77285
Minimum of Months 672.00000 21.45390 17.10310 -1.4532 5.25286
Maximum of Months 744.00000 23.57193 50.72114 0.13161 48.41074



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.84088 18.97062 -0.7842 18.55596
February 672.00000 21.05908 19.57768 -0.6517 14.48266
March 744.00000 21.45115 21.28385 -0.4453 11.03984
April 720.00000 22.37127 22.25296 -0.1101 7.92677
May 744.00000 23.03710 25.84051 -0.8612 23.52484
June 720.00000 23.54908 39.02071 -0.5697 13.25746
July 744.00000 23.52042 47.83348 -0.5201 12.33404
August 744.00000 23.27284 43.28744 -0.6530 16.46381
September 720.00000 22.06534 34.24628 -1.2111 38.58489
October 744.00000 21.24495 27.60227 -0.4705 10.59020
November 720.00000 20.99570 18.42358 -0.7321 16.44598
December 744.00000 20.94950 17.21817 -0.7996 18.68070
           
Annual Sum or Average 8760.00000 22.03539 28.02632 -0.6507 16.81874
Minimum of Months 672.00000 20.84088 17.21817 -1.2111 7.92677
Maximum of Months 744.00000 23.54908 47.83348 -0.1101 38.58489



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.96661 19.90345 -0.5644 11.87853
February 672.00000 21.05751 20.41041 -0.5187 10.77152
March 744.00000 21.21328 22.23319 -0.4454 9.34805
April 720.00000 22.01185 23.23142 -0.2188 6.57622
May 744.00000 22.57606 26.96512 -1.0761 29.93278
June 720.00000 22.99541 40.81383 -0.8329 20.18870
July 744.00000 22.99323 49.85695 -0.7740 18.22529
August 744.00000 22.86619 44.82211 -0.8561 21.19497
September 720.00000 22.08950 34.63703 -1.2091 36.29905
October 744.00000 21.38450 28.07994 -0.3644 8.07170
November 720.00000 21.02784 19.33552 -0.5424 11.24197
December 744.00000 20.99795 18.16709 -0.5767 12.06465
           
Annual Sum or Average 8760.00000 21.85282 29.10381 -0.6657 16.33692
Minimum of Months 672.00000 20.96661 18.16709 -1.2091 6.57622
Maximum of Months 744.00000 22.99541 49.85695 -0.2188 36.29905



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.99978 13.76905 0.69927 16.11829
February 672.00000 23.99976 14.17050 0.71843 16.70302
March 744.00000 23.99982 15.83573 0.75995 17.99647
April 720.00000 23.99981 17.26268 0.81024 19.60156
May 744.00000 23.99977 21.11223 0.24378 7.86863
June 720.00000 23.99988 34.59522 0.36294 9.39608
July 744.00000 23.99982 43.17388 0.42201 10.39188
August 744.00000 23.99984 38.12894 0.37522 9.64325
September 720.00000 23.99980 27.50136 0.25221 7.98498
October 744.00000 23.99985 20.92468 0.80721 19.50294
November 720.00000 23.99978 13.27105 0.70270 16.19756
December 744.00000 23.99978 12.30051 0.68095 15.57067
           
Annual Sum or Average 8760.00000 23.99981 22.73501 0.56876 13.89848
Minimum of Months 672.00000 23.99976 12.30051 0.24378 7.86863
Maximum of Months 744.00000 23.99988 43.17388 0.81024 19.60156



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.91191 22.11681 -0.6704 14.90986
February 672.00000 21.03833 22.65204 -0.5487 11.67116
March 744.00000 21.39773 24.40636 -0.3466 8.75222
April 720.00000 22.18967 25.41066 -0.0519 6.86373
May 744.00000 22.44987 29.47108 -0.9185 24.87377
June 720.00000 22.74052 43.77971 -0.6998 16.87764
July 744.00000 22.70282 53.00918 -0.6522 15.91653
August 744.00000 22.58676 47.89076 -0.7413 19.15891
September 720.00000 21.92481 37.26573 -1.1275 33.73836
October 744.00000 21.30577 30.44283 -0.3515 8.30606
November 720.00000 20.99945 21.55925 -0.6294 13.49568
December 744.00000 20.97141 20.39209 -0.7001 15.53991
           
Annual Sum or Average 8760.00000 21.77211 31.60088 -0.6203 15.85542
Minimum of Months 672.00000 20.91191 20.39209 -1.1275 6.86373
Maximum of Months 744.00000 22.74052 53.00918 -0.0519 33.73836



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.16814 22.33152 -0.4927 10.44372
February 672.00000 21.30140 22.80992 -0.4304 9.24159
March 744.00000 21.65500 24.50941 -0.3059 7.39517
April 720.00000 22.51911 25.50212 -0.0593 5.66564
May 744.00000 22.95751 29.30051 -0.8939 22.45325
June 720.00000 23.24109 43.07745 -0.6905 15.61906
July 744.00000 23.24353 51.94339 -0.6295 13.99076
August 744.00000 23.17168 46.92938 -0.6954 15.97607
September 720.00000 22.56991 36.61504 -1.0018 27.10898
October 744.00000 21.85560 30.16489 -0.2212 6.62398
November 720.00000 21.22723 21.77579 -0.4700 9.89092
December 744.00000 21.11425 20.68078 -0.5251 10.98791
           
Annual Sum or Average 8760.00000 22.17341 31.36835 -0.5353 12.96246
Minimum of Months 672.00000 21.11425 20.68078 -1.0018 5.66564
Maximum of Months 744.00000 23.24353 51.94339 -0.0593 27.10898



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.37009 21.54457 -0.9116 23.20404
February 672.00000 20.43907 22.36088 -0.8449 20.59840
March 744.00000 20.72231 24.08392 -0.6969 15.82354
April 720.00000 21.40643 28.37867 -0.3777 9.38581
May 744.00000 21.69818 34.26026 -1.3122 42.17019
June 720.00000 21.76615 45.39052 -1.1488 34.36212
July 744.00000 21.76346 51.14188 -1.1312 33.55253
August 744.00000 21.70923 49.12618 -1.2101 37.21201
September 720.00000 21.31125 42.43162 -1.5331 53.08710
October 744.00000 20.67187 32.60388 -0.6636 14.96269
November 720.00000 20.40210 20.70203 -0.8946 22.44629
December 744.00000 20.39243 19.95482 -0.9319 23.97380
           
Annual Sum or Average 8760.00000 21.05761 32.73252 -0.9722 27.59742
Minimum of Months 672.00000 20.37009 19.95482 -1.5331 9.38581
Maximum of Months 744.00000 21.76615 51.14188 -0.3777 53.08710



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.35207 21.57796 -0.9223 23.67322
February 672.00000 20.40602 22.44825 -0.8785 21.92067
March 744.00000 20.48351 24.39412 -0.7900 18.75850
April 720.00000 21.05425 28.85822 -0.5015 11.32804
May 744.00000 21.97820 34.02748 -1.2749 41.75137
June 720.00000 22.67007 43.83475 -0.9108 28.36865
July 744.00000 22.49851 50.20362 -0.9418 27.96923
August 744.00000 22.20138 48.60164 -1.1089 34.48198
September 720.00000 21.09919 42.89829 -1.6405 58.42399
October 744.00000 20.53153 32.89266 -0.7179 16.50177
November 720.00000 20.39457 20.74712 -0.9088 23.04073
December 744.00000 20.38679 19.96379 -0.9352 24.11544
           
Annual Sum or Average 8760.00000 21.17617 32.60329 -0.9613 27.54361
Minimum of Months 672.00000 20.35207 19.96379 -1.6405 11.32804
Maximum of Months 744.00000 22.67007 50.20362 -0.5015 58.42399



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.41329 20.32598 -0.7969 19.16870
February 672.00000 20.52162 21.15930 -0.7569 17.69727
March 744.00000 20.71903 23.19594 -0.6788 15.14575
April 720.00000 21.12169 27.99838 -0.5091 10.74112
May 744.00000 21.66135 32.88423 -1.4394 47.88247
June 720.00000 22.13157 43.33174 -1.1751 35.05783
July 744.00000 22.14789 49.86327 -1.1346 33.41978
August 744.00000 21.87355 47.04486 -1.2797 39.99901
September 720.00000 21.24803 41.45323 -1.5807 55.29888
October 744.00000 20.85208 31.57910 -0.5824 12.54726
November 720.00000 20.45770 19.57978 -0.7876 18.70395
December 744.00000 20.42662 18.62514 -0.8103 19.50848
           
Annual Sum or Average 8760.00000 21.13502 31.48611 -0.9621 27.14354
Minimum of Months 672.00000 20.41329 18.62514 -1.5807 10.74112
Maximum of Months 744.00000 22.14789 49.86327 -0.5091 55.29888



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.36442 21.54217 -0.9103 23.15689
February 672.00000 20.47628 22.27430 -0.8255 19.93902
March 744.00000 20.99618 23.73857 -0.6087 13.70360
April 720.00000 21.54876 28.24111 -0.3442 9.00075
May 744.00000 21.77524 34.21140 -1.2349 38.81418
June 720.00000 21.79191 44.89892 -1.1150 33.06732
July 744.00000 21.79471 49.94381 -1.0866 31.84896
August 744.00000 21.77157 48.10174 -1.1647 35.31507
September 720.00000 21.45789 42.05592 -1.4615 49.62090
October 744.00000 20.78965 32.36129 -0.6214 14.00518
November 720.00000 20.40210 20.69694 -0.8941 22.43755
December 744.00000 20.39023 19.95247 -0.9320 23.97494
           
Annual Sum or Average 8760.00000 21.13342 32.39962 -0.9339 26.26705
Minimum of Months 672.00000 20.36442 19.95247 -1.4615 9.00075
Maximum of Months 744.00000 21.79471 49.94381 -0.3442 49.62090



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.34614 21.56176 -0.9211 23.62775
February 672.00000 20.41591 22.37722 -0.8647 21.40539
March 744.00000 20.65892 24.09335 -0.7216 16.58182
April 720.00000 21.29733 28.49563 -0.4495 10.43641
May 744.00000 21.97657 33.82673 -1.2203 37.98102
June 720.00000 22.41861 43.81841 -0.9601 27.16290
July 744.00000 22.50263 49.20303 -0.9045 26.39707
August 744.00000 22.15733 47.68295 -1.0948 32.34356
September 720.00000 21.31596 42.35244 -1.5485 53.79452
October 744.00000 20.63040 32.64294 -0.6796 15.42586
November 720.00000 20.39302 20.72685 -0.9087 23.04431
December 744.00000 20.38290 19.96199 -0.9356 24.12889
           
Annual Sum or Average 8760.00000 21.21286 32.29183 -0.9343 26.03715
Minimum of Months 672.00000 20.34614 19.96199 -1.5485 10.43641
Maximum of Months 744.00000 22.50263 49.20303 -0.4495 53.79452



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.33752 21.88873 -0.9808 26.02196
February 672.00000 20.40892 22.71917 -0.9119 23.11232
March 744.00000 20.60357 24.50875 -0.7703 18.16854
April 720.00000 21.31410 28.86260 -0.4215 10.43428
May 744.00000 21.66521 34.66944 -1.3411 43.77036
June 720.00000 21.74953 45.94196 -1.1598 35.06190
July 744.00000 21.74800 52.24729 -1.1387 34.07755
August 744.00000 21.67635 50.18193 -1.2324 38.44967
September 720.00000 21.20859 43.37481 -1.5999 56.48323
October 744.00000 20.58127 33.27022 -0.7267 16.85768
November 720.00000 20.38941 21.03433 -0.9608 25.05608
December 744.00000 20.37658 20.25937 -0.9985 26.69175
           
Annual Sum or Average 8760.00000 21.00806 33.31601 -1.0209 29.54349
Minimum of Months 672.00000 20.33752 20.25937 -1.5999 10.43428
Maximum of Months 744.00000 21.74953 52.24729 -0.4215 56.48323



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.31188 21.88925 -0.9929 26.59508
February 672.00000 20.38917 22.81510 -0.9422 24.39318
March 744.00000 20.44632 24.76330 -0.8500 20.87361
April 720.00000 20.96106 29.38437 -0.5511 12.63319
May 744.00000 21.97880 34.45100 -1.2939 43.51031
June 720.00000 22.74604 44.19462 -0.8852 29.10726
July 744.00000 22.54669 50.85980 -0.9250 28.36820
August 744.00000 22.21793 49.47373 -1.1133 35.75130
September 720.00000 20.97957 43.92968 -1.7183 62.32267
October 744.00000 20.47103 33.53142 -0.7760 18.38984
November 720.00000 20.37475 21.06199 -0.9760 25.72920
December 744.00000 20.36007 20.25571 -1.0041 26.94531
           
Annual Sum or Average 8760.00000 21.15357 33.11751 -1.0025 29.56225
Minimum of Months 672.00000 20.31188 20.25571 -1.7183 12.63319
Maximum of Months 744.00000 22.74604 50.85980 -0.5511 62.32267



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.41031 23.48040 -0.8864 22.20226
February 672.00000 20.77021 24.14097 -0.7281 17.29818
March 744.00000 21.21905 25.79352 -0.5231 12.48841
April 720.00000 21.60222 30.16669 -0.2959 8.71976
May 744.00000 21.72756 35.46196 -1.2980 42.03961
June 720.00000 21.75912 45.85811 -1.1824 36.30308
July 744.00000 21.76229 51.35763 -1.1479 34.70478
August 744.00000 21.73479 48.94827 -1.1969 37.11191
September 720.00000 21.51722 42.95981 -1.4237 48.03778
October 744.00000 21.00763 33.79046 -0.5477 12.57641
November 720.00000 20.47713 22.67360 -0.8560 21.05911
December 744.00000 20.39619 21.97806 -0.9233 23.64013
           
Annual Sum or Average 8760.00000 21.20063 33.94743 -0.9188 26.39893
Minimum of Months 672.00000 20.39619 21.97806 -1.4237 8.71976
Maximum of Months 744.00000 21.76229 51.35763 -0.2959 48.03778



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.36002 22.01327 -0.4262 9.53577
February 672.00000 21.44337 22.52411 -0.3865 8.77271
March 744.00000 21.63135 24.34803 -0.2977 7.50088
April 720.00000 22.04993 25.66092 -0.1314 6.08957
May 744.00000 22.57502 29.44584 -0.9110 23.47753
June 720.00000 22.88809 43.45037 -0.6713 15.55420
July 744.00000 22.85309 52.67458 -0.6255 14.19660
August 744.00000 22.68264 47.72046 -0.7461 17.94872
September 720.00000 22.23327 36.87703 -1.0348 28.70207
October 744.00000 21.81368 30.02027 -0.2000 6.54593
November 720.00000 21.38412 21.49426 -0.4211 9.23872
December 744.00000 21.31314 20.39431 -0.4553 9.79937
           
Annual Sum or Average 8760.00000 22.02239 31.45280 -0.5263 13.12965
Minimum of Months 672.00000 21.31314 20.39431 -1.0348 6.08957
Maximum of Months 744.00000 22.88809 52.67458 -0.1314 28.70207



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.57566 21.85019 -0.3349 8.22491
February 672.00000 21.65661 22.35119 -0.2974 7.69694
March 744.00000 21.90418 24.10912 -0.1975 6.64657
April 720.00000 22.37708 25.36710 -0.0268 5.75190
May 744.00000 22.85334 29.09694 -0.7897 19.05072
June 720.00000 23.13648 42.89795 -0.5616 12.57837
July 744.00000 23.10246 51.98648 -0.5159 11.45066
August 744.00000 22.93946 47.10852 -0.6335 14.56295
September 720.00000 22.57939 36.33049 -0.8825 22.61394
October 744.00000 22.13623 29.64087 -0.0885 6.02303
November 720.00000 21.58627 21.34296 -0.3335 8.03862
December 744.00000 21.49843 20.27146 -0.3713 8.50066
           
Annual Sum or Average 8760.00000 22.28237 31.09578 -0.4201 10.94039
Minimum of Months 672.00000 21.49843 20.27146 -0.8825 5.75190
Maximum of Months 744.00000 23.13648 51.98648 -0.0268 22.61394



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.95337 23.32178 0.82680 20.97111
February 672.00000 23.97144 23.29389 0.86456 22.36976
March 744.00000 23.98780 24.18726 0.93751 25.16048
April 720.00000 23.99083 24.89491 1.02167 28.61480
May 744.00000 23.99081 28.31139 0.58093 15.78616
June 720.00000 23.99133 41.37698 0.71515 19.11459
July 744.00000 23.99169 49.75692 0.77184 21.09012
August 744.00000 23.99138 44.92161 0.69284 18.63590
September 720.00000 23.99105 34.72913 0.52325 14.09736
October 744.00000 23.99094 28.84999 0.97821 26.53395
November 720.00000 23.98139 22.62607 0.83451 21.04572
December 744.00000 23.97373 21.96622 0.80731 20.15737
           
Annual Sum or Average 8760.00000 23.98386 30.74469 0.79590 21.12580
Minimum of Months 672.00000 23.95337 21.96622 0.52325 14.09736
Maximum of Months 744.00000 23.99169 49.75692 1.02167 28.61480



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.89118 16.65652 -0.6620 14.48575
February 672.00000 20.98256 17.17521 -0.6274 13.37279
March 744.00000 20.99828 19.08934 -0.5863 12.27595
April 720.00000 21.03263 21.01948 -0.5103 10.53476
May 744.00000 21.38536 25.32627 -1.5201 52.01018
June 720.00000 21.97130 39.81140 -1.2280 36.74821
July 744.00000 22.03192 49.29828 -1.1483 32.92292
August 744.00000 21.79278 44.17870 -1.2647 38.67571
September 720.00000 21.11730 33.25224 -1.5793 55.22943
October 744.00000 21.00148 25.34644 -0.5181 10.67983
November 720.00000 20.98756 16.06296 -0.6383 13.62098
December 744.00000 20.97222 14.88686 -0.6620 14.29721
           
Annual Sum or Average 8760.00000 21.26588 26.91382 -0.9136 25.46360
Minimum of Months 672.00000 20.89118 14.88686 -1.5793 10.53476
Maximum of Months 744.00000 22.03192 49.29828 -0.5103 55.22943



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.94143 20.95281 -0.6192 13.19457
February 672.00000 20.99944 21.53423 -0.5872 12.29210
March 744.00000 21.00498 23.46057 -0.5477 11.32060
April 720.00000 21.52681 24.82187 -0.3889 8.52734
May 744.00000 22.56395 28.12815 -1.1674 33.94419
June 720.00000 23.29213 41.44459 -0.8274 19.66537
July 744.00000 23.25070 50.40978 -0.7824 18.22518
August 744.00000 22.82169 46.15083 -0.9629 25.08037
September 720.00000 21.54290 36.67227 -1.4718 49.51472
October 744.00000 21.01286 29.62990 -0.5123 10.53542
November 720.00000 20.99772 20.42447 -0.6055 12.74011
December 744.00000 20.98308 19.19305 -0.6253 13.27570
           
Annual Sum or Average 8760.00000 21.74989 30.30009 -0.7589 19.04236
Minimum of Months 672.00000 20.94143 19.19305 -1.4718 8.52734
Maximum of Months 744.00000 23.29213 50.40978 -0.3889 49.51472



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.88855 20.23147 -0.6772 15.00431
February 672.00000 20.99348 21.01537 -0.6255 13.32005
March 744.00000 21.04625 22.96608 -0.5575 11.62214
April 720.00000 22.07264 23.99673 -0.2622 7.51902
May 744.00000 23.53840 26.57173 -0.8305 20.07847
June 720.00000 23.94579 38.73732 -0.5774 12.09597
July 744.00000 23.93762 47.48356 -0.5205 10.79119
August 744.00000 23.74315 43.42727 -0.6371 14.01981
September 720.00000 22.29704 35.16684 -1.2167 37.02771
October 744.00000 21.11963 29.12328 -0.4953 10.30669
November 720.00000 20.99218 19.75556 -0.6533 14.04605
December 744.00000 20.97524 18.40953 -0.6796 14.82930
           
Annual Sum or Average 8760.00000 22.13633 28.96637 -0.6442 15.04064
Minimum of Months 672.00000 20.88855 18.40953 -1.2167 7.51902
Maximum of Months 744.00000 23.94579 47.48356 -0.2622 37.02771



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.97426 16.30190 -0.6204 13.20585
February 672.00000 21.08179 17.31354 -0.5805 12.22288
March 744.00000 21.32127 19.19411 -0.4979 10.54797
April 720.00000 22.80487 22.93563 -0.1261 6.38253
May 744.00000 23.92572 26.14148 -0.7740 17.68702
June 720.00000 23.99937 36.94883 -0.6389 13.61894
July 744.00000 23.99913 45.49317 -0.5761 11.99174
August 744.00000 23.99280 41.43483 -0.6209 13.16748
September 720.00000 23.62241 34.90863 -0.8265 19.94540
October 744.00000 22.18467 27.13216 -0.2438 7.33937
November 720.00000 21.02193 15.63542 -0.6050 12.72234
December 744.00000 21.00428 14.77526 -0.6289 13.35838
           
Annual Sum or Average 8760.00000 22.50195 26.58163 -0.5616 12.68095
Minimum of Months 672.00000 20.97426 14.77526 -0.8265 6.38253
Maximum of Months 744.00000 23.99937 45.49317 -0.1261 19.94540



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.168998E+09 7328.55 23-JAN-19:07 65.49 0.526587E+09 0.00 0.695585E+09 0.27 3.12 05-JAN-03:20 0.00 0.00
February 0.304866E+09 10034.43 07-FEB-19:04 102.61 0.949941E+09 0.00 0.125481E+10 0.48 3.12 11-FEB-19:08 0.00 0.00
March 0.151012E+10 15083.90 22-MAR-18:02 284.50 0.470541E+10 0.00 0.621553E+10 1.19 3.12 23-MAR-01:00 0.00 0.00
April 0.155664E+11 53602.11 22-APR-15:13 575.31 0.484579E+11 0.00 0.640243E+11 2.49 3.95 22-APR-15:13 0.00 0.00
May 0.426516E+11 66711.47 31-MAY-15:23 732.17 0.132110E+12 0.00 0.174762E+12 3.05 3.90 18-MAY-15:13 0.00 0.00
June 0.841202E+11 108728.13 20-JUN-18:03 718.83 0.271066E+12 0.00 0.355186E+12 3.13 4.03 30-JUN-18:03 0.00 0.00
July 0.964043E+11 122306.93 29-JUL-18:03 743.83 0.316246E+12 0.00 0.412650E+12 3.17 3.94 22-JUL-08:53 0.00 0.00
August 0.658300E+11 103859.18 11-AUG-18:03 738.11 0.210937E+12 0.00 0.276767E+12 3.10 3.86 24-AUG-15:13 0.00 0.00
September 0.133062E+11 49597.89 09-SEP-18:03 540.33 0.408516E+11 0.00 0.541578E+11 2.33 3.68 09-SEP-15:13 0.00 0.00
October 0.184319E+10 23397.93 03-OCT-18:01 310.84 0.574239E+10 0.00 0.758559E+10 1.30 3.12 22-OCT-13:20 0.00 0.00
November 0.128703E+09 6796.82 05-NOV-18:07 50.22 0.401029E+09 0.00 0.529732E+09 0.22 3.12 01-NOV-02:30 0.00 0.00
December 0.124281E+09 9864.15 24-DEC-19:05 47.84 0.387250E+09 0.00 0.511530E+09 0.20 3.12 19-DEC-19:40 0.00 0.00
                         
Annual Sum or Average 0.321959E+12     4910.07 0.103238E+13 0.00 0.135434E+13 1.75     0.00 0.00
Minimum of Months 0.124281E+09 6796.82   47.84 0.387250E+09 0.00 0.511530E+09 0.20 3.12   0.00 0.00
Maximum of Months 0.964043E+11 122306.93   743.83 0.316246E+12 0.00 0.412650E+12 3.17 4.03   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.560389E+12 0.00 744.00 643026.81 12-JAN-10:20 0.00 40.02 60.00 2.46 0.00 0.25 0.77 12-JAN-10:20
February 0.434378E+12 0.00 672.00 605297.09 27-FEB-07:05 0.00 40.25 60.00 2.13 0.00 0.22 0.73 27-FEB-07:05
March 0.239766E+12 0.00 744.00 555678.12 01-MAR-07:10 0.00 40.78 60.00 1.09 0.00 0.11 0.67 01-MAR-07:10
April 0.885165E+11 0.00 660.39 202976.61 03-APR-08:62 0.00 39.23 58.25 0.39 0.00 0.04 0.24 03-APR-08:62
May 0.416609E+11 0.00 343.43 118633.03 27-MAY-15:14 0.00 28.68 43.01 0.12 0.00 0.02 0.14 27-MAY-15:14
June 0.300132E+10 0.00 69.55 64359.88 02-JUN-04:00 0.00 29.60 32.48 0.01 0.00 0.00 0.08 02-JUN-04:00
July 0.138648E+10 0.00 53.07 58041.58 05-JUL-08:04 0.00 33.05 35.15 0.00 0.00 0.00 0.07 05-JUL-08:04
August 0.116765E+11 0.00 169.04 127020.71 31-AUG-08:03 0.00 34.18 40.00 0.04 0.00 0.01 0.15 31-AUG-08:03
September 0.852409E+11 0.00 584.72 188083.46 27-SEP-15:11 0.00 34.94 55.07 0.32 0.00 0.04 0.23 27-SEP-15:11
October 0.148440E+12 0.00 744.00 213028.04 30-OCT-08:05 0.00 40.01 60.00 0.65 0.00 0.07 0.26 30-OCT-08:05
November 0.510542E+12 0.00 720.00 595088.79 29-NOV-10:10 0.00 39.64 60.00 2.32 0.00 0.24 0.71 29-NOV-10:10
December 0.659953E+12 0.00 744.00 617417.82 15-DEC-10:50 0.00 39.67 60.00 2.88 0.00 0.30 0.74 15-DEC-10:50
                           
Annual Sum or Average 0.278495E+13 0.00 6248.20     0.00 36.65 51.94 1.03 0.00 0.11    
Minimum of Months 0.138648E+10 0.00 53.07 58041.58   0.00 28.68 32.48 0.00 0.00 0.00 0.07  
Maximum of Months 0.659953E+12 0.00 744.00 643026.81   0.00 40.78 60.00 2.88 0.00 0.30 0.77  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 75168325.83 0.00 65.18 75168325.83 0.00 0.00 0.00 0.00 3903.82 20-JAN-06:10 3903.82 20-JAN-06:10 0.00 0.00 0.00
February 85185202.38 0.00 83.78 85185202.38 0.00 0.00 0.00 0.00 3956.80 07-FEB-06:10 3956.80 07-FEB-06:10 0.00 0.00 0.00
March 0.156560E+09 0.00 143.90 0.156560E+09 0.00 0.00 0.00 0.00 4012.86 21-MAR-05:10 4012.86 21-MAR-05:10 0.00 0.00 0.00
April 0.736317E+09 0.00 183.77 0.736317E+09 0.00 0.00 0.00 0.00 22928.05 22-APR-16:10 22928.05 22-APR-16:10 0.00 0.00 0.00
May 0.354295E+11 0.00 205.81 0.354295E+11 0.00 0.00 0.00 0.00 157352.54 31-MAY-17:50 157352.54 31-MAY-17:50 0.00 0.00 0.00
June 0.131458E+12 0.00 440.33 0.130430E+12 0.00 0.00 0.00 0.00 226960.36 29-JUN-20:00 212175.31 29-JUN-19:10 0.00 0.00 0.00
July 0.166461E+12 0.00 480.50 0.164044E+12 0.00 0.00 0.00 0.00 251880.33 29-JUL-17:15 219473.22 29-JUL-17:15 0.00 0.00 0.00
August 0.980209E+11 0.00 358.00 0.979070E+11 0.00 0.00 0.00 0.00 205466.83 11-AUG-19:20 205466.83 11-AUG-19:20 0.00 0.00 0.00
September 0.479464E+10 0.00 88.76 0.479464E+10 0.00 0.00 0.00 0.00 61221.95 02-SEP-17:50 61221.95 02-SEP-17:50 0.00 0.00 0.00
October 0.209132E+09 0.00 194.00 0.209132E+09 0.00 0.00 0.00 0.00 4092.39 17-OCT-05:10 4092.39 17-OCT-05:10 0.00 0.00 0.00
November 51529095.41 0.00 49.14 51529095.41 0.00 0.00 0.00 0.00 3846.30 02-NOV-05:10 3846.30 02-NOV-05:10 0.00 0.00 0.00
December 54200966.70 0.00 47.76 54200966.70 0.00 0.00 0.00 0.00 3890.95 26-DEC-06:10 3890.95 26-DEC-06:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.437532E+12 0.00 2340.94 0.433972E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 51529095.41 0.00 47.76 51529095.41 0.00 0.00 0.00 0.00 3846.30   3846.30   0.00 0.00 0.00
Maximum of Months 0.166461E+12 0.00 480.50 0.164044E+12 0.00 0.00 0.00 0.00 251880.33   219473.22   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00
April 2616969.90 0.00 2.17 2616969.90 0.00 0.00 0.00 0.00 594.90 22-APR-14:20 594.90 22-APR-14:20 0.00 0.00 0.00
May 0.174643E+10 0.00 109.67 0.174643E+10 0.00 0.00 0.00 0.00 14983.87 31-MAY-15:55 14983.87 31-MAY-15:55 0.00 0.00 0.00
June 0.831331E+10 0.00 304.50 0.823859E+10 0.00 0.00 0.00 0.00 19533.33 30-JUN-12:20 17976.49 20-JUN-18:02 0.00 0.00 0.00
July 0.101207E+11 0.00 335.83 0.994242E+10 0.00 0.00 0.00 0.00 19236.07 29-JUL-18:02 19076.55 29-JUL-15:12 0.00 0.00 0.00
August 0.609004E+10 0.00 240.33 0.605039E+10 0.00 0.00 0.00 0.00 17533.36 11-AUG-18:02 17533.36 11-AUG-18:02 0.00 0.00 0.00
September 0.172724E+09 0.00 27.67 0.172724E+09 0.00 0.00 0.00 0.00 4990.84 07-SEP-16:00 4990.84 07-SEP-16:00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.264459E+11 0.00 1020.17 0.261532E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.101207E+11 0.00 335.83 0.994242E+10 0.00 0.00 0.00 0.00 19533.33   19076.55   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 239058.60 0.00 0.10 239058.60 0.00 0.00 0.00 0.00 1241.63 15-FEB-16:14 1241.63 15-FEB-16:14 0.00 0.00 0.00
March 0.121475E+09 0.00 16.32 0.121475E+09 0.00 0.00 0.00 0.00 16500.21 22-MAR-15:11 16500.21 22-MAR-15:11 0.00 0.00 0.00
April 0.234628E+10 0.00 261.47 0.233699E+10 0.00 0.00 0.00 0.00 16741.34 30-APR-15:11 16741.34 30-APR-15:11 0.00 0.00 0.00
May 0.455038E+10 0.00 569.31 0.419884E+10 0.00 0.00 0.00 0.00 16743.06 20-MAY-18:01 16743.06 20-MAY-18:01 0.00 0.00 0.00
June 0.738088E+10 0.00 657.73 0.482457E+10 0.00 0.00 0.00 0.00 16743.29 12-JUN-18:02 16743.29 12-JUN-18:02 0.00 0.00 0.00
July 0.744636E+10 0.00 671.92 0.407821E+10 0.00 0.00 0.00 0.00 16410.33 17-JUL-18:01 15175.96 26-JUL-18:01 0.00 0.00 0.00
August 0.527977E+10 0.00 611.74 0.290887E+10 0.00 0.00 0.00 0.00 16728.75 30-AUG-18:01 16728.75 30-AUG-18:01 0.00 0.00 0.00
September 0.103972E+10 0.00 190.18 0.653860E+09 0.00 0.00 0.00 0.00 16741.06 07-SEP-15:11 16741.06 07-SEP-15:11 0.00 0.00 0.00
October 35399910.38 0.00 8.60 31397051.30 0.00 0.00 0.00 0.00 14597.76 13-OCT-15:12 14597.76 13-OCT-15:12 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.282005E+11 0.00 2987.37 0.191544E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.744636E+10 0.00 671.92 0.482457E+10 0.00 0.00 0.00 0.00 16743.29   16743.29   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 35837.71 0.00 0.07 35837.71 0.00 0.00 0.00 0.00 249.08 08-FEB-19:06 249.08 08-FEB-19:06 0.00 0.00 0.00
March 2391357.31 0.00 1.33 2391357.31 0.00 0.00 0.00 0.00 2609.18 26-MAR-15:14 2609.18 26-MAR-15:14 0.00 0.00 0.00
April 0.116807E+10 0.00 145.22 0.116693E+10 0.00 0.00 0.00 0.00 15059.55 30-APR-18:01 15059.55 30-APR-18:01 0.00 0.00 0.00
May 0.249851E+10 0.00 419.11 0.222751E+10 0.00 0.00 0.00 0.00 17098.74 14-MAY-20:41 17098.74 14-MAY-20:41 0.00 0.00 0.00
June 0.485174E+10 0.00 498.39 0.282049E+10 0.00 0.00 0.00 0.00 16101.25 30-JUN-21:51 15835.88 01-JUN-18:41 0.00 0.00 0.00
July 0.492373E+10 0.00 503.46 0.255313E+10 0.00 0.00 0.00 0.00 16670.32 08-JUL-21:51 15738.74 06-JUL-17:32 0.00 0.00 0.00
August 0.271824E+10 0.00 421.00 0.122702E+10 0.00 0.00 0.00 0.00 15489.33 12-AUG-21:52 15049.71 30-AUG-18:01 0.00 0.00 0.00
September 0.354650E+09 0.00 95.19 0.195425E+09 0.00 0.00 0.00 0.00 15051.55 07-SEP-18:01 15051.55 07-SEP-18:01 0.00 0.00 0.00
October 5109649.15 0.00 1.39 4276050.31 0.00 0.00 0.00 0.00 6395.47 03-OCT-15:11 6395.47 03-OCT-15:11 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.165225E+11 0.00 2085.16 0.101972E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.492373E+10 0.00 503.46 0.282049E+10 0.00 0.00 0.00 0.00 17098.74   17098.74   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 0.00 0.00
March 0.212467E+09 0.00 8.94 0.212467E+09 0.00 0.00 0.00 0.00 14969.98 31-MAR-15:10 14969.98 31-MAR-15:10 0.00 0.00 0.00
April 0.247679E+11 0.00 360.72 0.247679E+11 0.00 0.00 0.00 0.00 58278.29 22-APR-13:20 58278.29 22-APR-13:20 0.00 0.00 0.00
May 0.372354E+11 0.00 606.00 0.372354E+11 0.00 0.00 0.00 0.00 56484.24 12-MAY-13:20 56484.24 12-MAY-13:20 0.00 0.00 0.00
June 0.444233E+11 0.00 700.06 0.272788E+11 0.00 0.00 0.00 0.00 53162.71 30-JUN-12:30 48595.15 08-JUN-12:30 0.00 0.00 0.00
July 0.469766E+11 0.00 719.06 0.210376E+11 0.00 0.00 0.00 0.00 60514.68 23-JUL-13:30 55543.62 23-JUL-13:30 0.00 0.00 0.00
August 0.422681E+11 0.00 679.20 0.223085E+11 0.00 0.00 0.00 0.00 64029.71 25-AUG-13:15 62093.69 25-AUG-13:15 0.00 0.00 0.00
September 0.167611E+11 0.00 355.20 0.142584E+11 0.00 0.00 0.00 0.00 54028.67 09-SEP-13:10 54028.67 09-SEP-13:10 0.00 0.00 0.00
October 0.157266E+10 0.00 52.23 0.157266E+10 0.00 0.00 0.00 0.00 36234.56 03-OCT-13:00 36234.56 03-OCT-13:00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.214218E+12 0.00 3481.42 0.148672E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.469766E+11 0.00 719.06 0.372354E+11 0.00 0.00 0.00 0.00 64029.71   62093.69   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 4818929.20 0.00 0.33 4818929.20 0.00 0.00 0.00 0.00 9429.63 20-JAN-19:07 9429.63 20-JAN-19:07 0.00 0.00 0.00
February 9858592.53 0.00 0.41 9477873.12 0.00 0.00 0.00 0.00 14637.49 07-FEB-19:04 14637.49 07-FEB-19:04 0.00 0.00 0.00
March 74322653.10 0.00 6.47 74322653.10 0.00 0.00 0.00 0.00 49075.48 22-MAR-18:02 49075.48 22-MAR-18:02 0.00 0.00 0.00
April 0.474493E+10 0.00 167.07 0.473413E+10 0.00 0.00 0.00 0.00 77065.74 30-APR-18:01 77065.74 30-APR-18:01 0.00 0.00 0.00
May 0.229546E+11 0.00 444.17 0.217586E+11 0.00 0.00 0.00 0.00 80617.29 31-MAY-21:51 80617.29 31-MAY-21:51 0.00 0.00 0.00
June 0.387976E+11 0.00 431.14 0.295245E+11 0.00 0.00 0.00 0.00 82902.55 07-JUN-21:51 82902.55 07-JUN-21:51 0.00 0.00 0.00
July 0.416771E+11 0.00 449.00 0.283365E+11 0.00 0.00 0.00 0.00 84577.35 15-JUL-20:41 74975.72 19-JUL-21:51 0.00 0.00 0.00
August 0.268728E+11 0.00 398.46 0.165825E+11 0.00 0.00 0.00 0.00 81733.36 12-AUG-21:52 80292.13 10-AUG-21:51 0.00 0.00 0.00
September 0.700923E+10 0.00 295.98 0.398892E+10 0.00 0.00 0.00 0.00 75809.53 10-SEP-18:01 75809.53 10-SEP-18:01 0.00 0.00 0.00
October 0.697399E+09 0.00 47.10 0.589480E+09 0.00 0.00 0.00 0.00 72355.50 06-OCT-18:02 72355.50 06-OCT-18:02 0.00 0.00 0.00
November 4137477.13 0.00 0.22 4137477.13 0.00 0.00 0.00 0.00 11765.86 01-NOV-18:06 11765.86 01-NOV-18:06 0.00 0.00 0.00
December 2148308.83 0.00 0.11 2148308.83 0.00 0.00 0.00 0.00 13359.93 24-DEC-19:05 13359.93 24-DEC-19:05 0.00 0.00 0.00
                               
Annual Sum or Average 0.142849E+12 0.00 2240.46 0.105610E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 2148308.83 0.00 0.11 2148308.83 0.00 0.00 0.00 0.00 9429.63   9429.63   0.00 0.00 0.00
Maximum of Months 0.416771E+11 0.00 449.00 0.295245E+11 0.00 0.00 0.00 0.00 84577.35   82902.55   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 172056.54 0.00 0.08 172056.54 0.00 0.00 0.00 0.00 1405.44 09-FEB-16:15 1405.44 09-FEB-16:15 0.00 0.00 0.00
March 0.181465E+09 0.00 39.51 0.181465E+09 0.00 0.00 0.00 0.00 15785.00 22-MAR-15:11 15785.00 22-MAR-15:11 0.00 0.00 0.00
April 0.215278E+10 0.00 301.34 0.211546E+10 0.00 0.00 0.00 0.00 15793.05 21-APR-08:61 15793.05 21-APR-08:61 0.00 0.00 0.00
May 0.639102E+10 0.00 637.64 0.593863E+10 0.00 0.00 0.00 0.00 15794.49 01-MAY-08:61 15794.49 01-MAY-08:61 0.00 0.00 0.00
June 0.838478E+10 0.00 680.38 0.571507E+10 0.00 0.00 0.00 0.00 15793.60 12-JUN-18:02 15793.60 12-JUN-18:02 0.00 0.00 0.00
July 0.915083E+10 0.00 700.10 0.559681E+10 0.00 0.00 0.00 0.00 15326.17 17-JUL-18:01 14371.21 18-JUL-08:62 0.00 0.00 0.00
August 0.639467E+10 0.00 652.20 0.376906E+10 0.00 0.00 0.00 0.00 15792.73 10-AUG-18:02 15792.73 10-AUG-18:02 0.00 0.00 0.00
September 0.146635E+10 0.00 266.69 0.869586E+09 0.00 0.00 0.00 0.00 15794.30 10-SEP-15:11 15794.30 10-SEP-15:11 0.00 0.00 0.00
October 90488886.65 0.00 27.17 69210499.31 0.00 0.00 0.00 0.00 14865.37 04-OCT-08:62 14865.37 04-OCT-08:62 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.342126E+11 0.00 3305.11 0.242554E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.915083E+10 0.00 700.10 0.593863E+10 0.00 0.00 0.00 0.00 15794.49   15794.49   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 56694.67 0.00 0.05 56694.67 0.00 0.00 0.00 0.00 396.82 08-FEB-19:06 396.82 08-FEB-19:06 0.00 0.00 0.00
March 38074067.69 0.00 11.98 38074067.69 0.00 0.00 0.00 0.00 4053.41 11-MAR-09:01 4053.41 11-MAR-09:01 0.00 0.00 0.00
April 0.866029E+09 0.00 167.81 0.843367E+09 0.00 0.00 0.00 0.00 14286.57 21-APR-08:61 14286.57 21-APR-08:61 0.00 0.00 0.00
May 0.444477E+10 0.00 531.93 0.409156E+10 0.00 0.00 0.00 0.00 14918.07 14-MAY-20:41 14918.07 14-MAY-20:41 0.00 0.00 0.00
June 0.620928E+10 0.00 522.70 0.412035E+10 0.00 0.00 0.00 0.00 15281.45 10-JUN-21:51 15281.45 10-JUN-21:51 0.00 0.00 0.00
July 0.660214E+10 0.00 539.49 0.401721E+10 0.00 0.00 0.00 0.00 15884.02 22-JUL-08:32 15884.02 22-JUL-08:32 0.00 0.00 0.00
August 0.397859E+10 0.00 490.71 0.219822E+10 0.00 0.00 0.00 0.00 14698.62 12-AUG-21:52 14283.08 31-AUG-08:62 0.00 0.00 0.00
September 0.629718E+09 0.00 158.45 0.351970E+09 0.00 0.00 0.00 0.00 14287.47 10-SEP-15:11 14287.47 10-SEP-15:11 0.00 0.00 0.00
October 17137540.84 0.00 4.93 9636001.69 0.00 0.00 0.00 0.00 9034.91 04-OCT-08:62 9034.91 04-OCT-08:62 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.227858E+11 0.00 2428.05 0.156704E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.660214E+10 0.00 539.49 0.412035E+10 0.00 0.00 0.00 0.00 15884.02   15884.02   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 28110.05 0.00 0.03 28110.05 0.00 0.00 0.00 0.00 281.10 09-FEB-16:15 281.10 09-FEB-16:15 0.00 0.00 0.00
March 23407078.62 0.00 15.33 23407078.62 0.00 0.00 0.00 0.00 4272.96 22-MAR-15:11 4272.96 22-MAR-15:11 0.00 0.00 0.00
April 0.592936E+09 0.00 220.93 0.591891E+09 0.00 0.00 0.00 0.00 4365.35 30-APR-15:11 4365.35 30-APR-15:11 0.00 0.00 0.00
May 0.107858E+10 0.00 482.62 0.995272E+09 0.00 0.00 0.00 0.00 4365.44 25-MAY-18:01 4365.44 25-MAY-18:01 0.00 0.00 0.00
June 0.179621E+10 0.00 635.19 0.120425E+10 0.00 0.00 0.00 0.00 4365.56 07-JUN-15:12 4365.56 07-JUN-15:12 0.00 0.00 0.00
July 0.180304E+10 0.00 650.77 0.101463E+10 0.00 0.00 0.00 0.00 4327.39 27-JUL-08:62 3948.19 10-JUL-08:61 0.00 0.00 0.00
August 0.123910E+10 0.00 554.42 0.715334E+09 0.00 0.00 0.00 0.00 4455.86 13-AUG-08:61 4365.20 10-AUG-18:02 0.00 0.00 0.00
September 0.237541E+09 0.00 143.91 0.159291E+09 0.00 0.00 0.00 0.00 4365.26 07-SEP-15:11 4365.26 07-SEP-15:11 0.00 0.00 0.00
October 6009999.33 0.00 6.18 5061386.68 0.00 0.00 0.00 0.00 2923.30 03-OCT-15:11 2923.30 03-OCT-15:11 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.677685E+10 0.00 2709.38 0.470916E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.180304E+10 0.00 650.77 0.120425E+10 0.00 0.00 0.00 0.00 4455.86   4365.56   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 0.00 0.00
March 574359.98 0.00 0.33 574359.98 0.00 0.00 0.00 0.00 803.37 22-MAR-15:13 803.37 22-MAR-15:13 0.00 0.00 0.00
April 0.283154E+09 0.00 119.78 0.283046E+09 0.00 0.00 0.00 0.00 3885.22 30-APR-18:01 3885.22 30-APR-18:01 0.00 0.00 0.00
May 0.553345E+09 0.00 354.30 0.491217E+09 0.00 0.00 0.00 0.00 4951.68 09-MAY-19:42 4951.68 09-MAY-19:42 0.00 0.00 0.00
June 0.120055E+10 0.00 484.40 0.698772E+09 0.00 0.00 0.00 0.00 4500.20 28-JUN-21:32 4391.61 28-JUN-21:32 0.00 0.00 0.00
July 0.120564E+10 0.00 495.88 0.632238E+09 0.00 0.00 0.00 0.00 4343.00 24-JUL-21:51 4034.61 06-JUL-17:32 0.00 0.00 0.00
August 0.607548E+09 0.00 381.99 0.280564E+09 0.00 0.00 0.00 0.00 4056.72 12-AUG-21:52 3882.72 30-AUG-18:01 0.00 0.00 0.00
September 67063246.82 0.00 62.82 38725715.22 0.00 0.00 0.00 0.00 3882.93 07-SEP-18:01 3882.93 07-SEP-18:01 0.00 0.00 0.00
October 734556.32 0.00 0.64 588538.99 0.00 0.00 0.00 0.00 980.10 01-OCT-15:13 734.35 01-OCT-15:13 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.391861E+10 0.00 1900.15 0.242573E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.120564E+10 0.00 495.88 0.698772E+09 0.00 0.00 0.00 0.00 4951.68   4951.68   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.128249E+09 0.00 21.17 0.128249E+09 0.00 0.00 0.00 0.00 26299.81 15-FEB-16:11 26299.81 15-FEB-16:11 0.00 0.00 0.00
March 0.184839E+10 0.00 130.04 0.184668E+10 0.00 0.00 0.00 0.00 26329.21 22-MAR-15:11 26329.21 22-MAR-15:11 0.00 0.00 0.00
April 0.588844E+10 0.00 377.99 0.581264E+10 0.00 0.00 0.00 0.00 26331.24 18-APR-18:01 26331.24 18-APR-18:01 0.00 0.00 0.00
May 0.802667E+10 0.00 605.88 0.714754E+10 0.00 0.00 0.00 0.00 26333.09 03-MAY-15:11 26333.09 03-MAY-15:11 0.00 0.00 0.00
June 0.102020E+11 0.00 652.63 0.642163E+10 0.00 0.00 0.00 0.00 26333.28 15-JUN-18:01 26333.28 15-JUN-18:01 0.00 0.00 0.00
July 0.114212E+11 0.00 672.32 0.625876E+10 0.00 0.00 0.00 0.00 26333.35 13-JUL-18:02 26333.35 13-JUL-18:02 0.00 0.00 0.00
August 0.967647E+10 0.00 636.05 0.573077E+10 0.00 0.00 0.00 0.00 26329.06 21-AUG-18:01 26329.06 21-AUG-18:01 0.00 0.00 0.00
September 0.374639E+10 0.00 355.10 0.241095E+10 0.00 0.00 0.00 0.00 26328.69 30-SEP-15:11 26328.69 30-SEP-15:11 0.00 0.00 0.00
October 0.858165E+09 0.00 85.10 0.771096E+09 0.00 0.00 0.00 0.00 26316.20 14-OCT-15:11 26316.20 14-OCT-15:11 0.00 0.00 0.00
November 2758308.64 0.00 0.89 2758308.64 0.00 0.00 0.00 0.00 9089.92 08-NOV-16:12 9089.92 08-NOV-16:12 0.00 0.00 0.00
December 120642.89 0.00 0.03 120642.89 0.00 0.00 0.00 0.00 1206.43 24-DEC-09:05 1206.43 24-DEC-09:05 0.00 0.00 0.00
                               
Annual Sum or Average 0.517989E+11 0.00 3537.19 0.365312E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.114212E+11 0.00 672.32 0.714754E+10 0.00 0.00 0.00 0.00 26333.35   26333.35   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 176.52 117.52 58.99 102.91 1000.41 0.00 0.00 0.00
February 589.72 409.50 180.23 501.59 803.78 0.00 0.00 0.00
March 998.33 675.44 322.89 995.01 616.98 0.00 0.00 0.00
April 1223.24 761.28 461.96 1366.06 400.60 0.00 0.00 0.00
May 1009.91 524.21 485.70 1167.56 205.82 0.00 0.00 0.00
June 917.57 374.46 543.11 1094.30 104.39 0.00 0.00 0.00
July 882.71 382.16 500.55 1080.85 108.87 0.00 0.00 0.00
August 919.67 507.44 412.23 1104.50 167.27 0.00 0.00 0.00
September 734.19 438.88 295.31 798.53 301.64 0.00 0.00 0.00
October 543.72 344.94 198.78 502.12 523.29 0.00 0.00 0.00
November 294.87 207.83 87.04 192.57 934.34 0.00 0.00 0.00
December 52.15 36.76 15.39 9.11 1113.78 0.00 0.00 0.00
                 
Annual Sum or Average 695.02 397.76 297.26 743.60 522.09 0.00 0.00 0.00
Minimum of Months 52.15 36.76 15.39 9.11 104.39 0.00 0.00 0.00
Maximum of Months 1223.24 761.28 543.11 1366.06 1113.78 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 497.06 330.94 166.12 287.42 2804.84 0.00 0.00 0.00
February 1660.62 1153.11 507.51 1407.24 2249.66 0.00 0.00 0.00
March 2811.24 1902.01 909.23 2798.59 1727.56 0.00 0.00 0.00
April 3444.56 2143.70 1300.86 3851.83 1114.97 0.00 0.00 0.00
May 2843.85 1476.14 1367.70 3312.12 553.41 0.00 0.00 0.00
June 2583.83 1054.45 1529.37 3121.81 266.43 0.00 0.00 0.00
July 2485.64 1076.13 1409.52 3083.28 277.66 0.00 0.00 0.00
August 2589.74 1428.93 1160.81 3138.63 440.56 0.00 0.00 0.00
September 2067.42 1235.86 831.57 2254.61 836.67 0.00 0.00 0.00
October 1531.07 971.33 559.74 1409.52 1468.93 0.00 0.00 0.00
November 830.33 585.24 245.09 538.18 2614.56 0.00 0.00 0.00
December 146.85 103.52 43.33 25.30 3117.90 0.00 0.00 0.00
                 
Annual Sum or Average 1957.12 1120.06 837.06 2104.37 1452.29 0.00 0.00 0.00
Minimum of Months 146.85 103.52 43.33 25.30 266.43 0.00 0.00 0.00
Maximum of Months 3444.56 2143.70 1529.37 3851.83 3117.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 645.71 429.91 215.80 371.63 3793.08 0.00 0.00 0.00
February 2157.24 1497.96 659.28 1839.52 3034.08 0.00 0.00 0.00
March 3651.96 2470.82 1181.14 3682.64 2328.53 0.00 0.00 0.00
April 4474.68 2784.79 1689.89 5073.12 1507.73 0.00 0.00 0.00
May 3694.32 1917.59 1776.73 4351.22 766.17 0.00 0.00 0.00
June 3356.54 1369.79 1986.74 4096.14 375.73 0.00 0.00 0.00
July 3228.99 1397.95 1831.04 4042.29 393.12 0.00 0.00 0.00
August 3364.22 1856.26 1507.96 4113.50 616.56 0.00 0.00 0.00
September 2685.70 1605.45 1080.25 2952.68 1163.15 0.00 0.00 0.00
October 1988.95 1261.81 727.14 1842.31 2012.55 0.00 0.00 0.00
November 1078.64 760.26 318.39 698.42 3531.89 0.00 0.00 0.00
December 190.76 134.47 56.29 31.95 4206.53 0.00 0.00 0.00
                 
Annual Sum or Average 2542.42 1455.03 1087.39 2760.60 1972.39 0.00 0.00 0.00
Minimum of Months 190.76 134.47 56.29 31.95 375.73 0.00 0.00 0.00
Maximum of Months 4474.68 2784.79 1986.74 5073.12 4206.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 34.90 23.24 11.66 20.75 200.44 0.00 0.00 0.00
February 116.60 80.96 35.63 101.37 160.51 0.00 0.00 0.00
March 197.39 133.55 63.84 200.23 123.39 0.00 0.00 0.00
April 241.86 150.52 91.34 272.91 78.49 0.00 0.00 0.00
May 199.68 103.65 96.03 233.67 37.75 0.00 0.00 0.00
June 181.42 74.04 107.38 220.68 16.95 0.00 0.00 0.00
July 174.53 75.56 98.97 218.44 17.67 0.00 0.00 0.00
August 181.84 100.33 81.51 222.18 28.89 0.00 0.00 0.00
September 145.16 86.77 58.39 160.51 57.96 0.00 0.00 0.00
October 107.50 68.20 39.30 101.32 103.99 0.00 0.00 0.00
November 58.30 41.09 17.21 39.32 185.68 0.00 0.00 0.00
December 10.31 7.27 3.04 1.89 222.49 0.00 0.00 0.00
                 
Annual Sum or Average 137.42 78.64 58.77 149.57 102.57 0.00 0.00 0.00
Minimum of Months 10.31 7.27 3.04 1.89 16.95 0.00 0.00 0.00
Maximum of Months 241.86 150.52 107.38 272.91 222.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 7.18 1.22 5.96 0.00 413.15 0.00 0.00 0.00
February 42.80 14.91 27.89 8.57 352.25 0.00 0.00 0.00
March 128.77 55.61 73.16 74.25 255.60 0.00 0.00 0.00
April 305.14 158.43 146.71 298.06 142.44 0.00 0.00 0.00
May 296.02 135.07 160.95 313.24 64.70 0.00 0.00 0.00
June 324.24 138.44 185.79 378.11 29.23 0.00 0.00 0.00
July 270.84 102.34 168.49 320.83 31.25 0.00 0.00 0.00
August 223.47 95.02 128.44 248.38 51.97 0.00 0.00 0.00
September 134.45 56.06 78.40 114.74 110.97 0.00 0.00 0.00
October 52.71 15.78 36.93 19.54 222.46 0.00 0.00 0.00
November 21.30 7.81 13.50 2.17 391.49 0.00 0.00 0.00
December 1.89 0.19 1.70 0.00 435.53 0.00 0.00 0.00
                 
Annual Sum or Average 151.12 65.21 85.91 148.75 207.67 0.00 0.00 0.00
Minimum of Months 1.89 0.19 1.70 0.00 29.23 0.00 0.00 0.00
Maximum of Months 324.24 158.43 185.79 378.11 435.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2.79 0.00 2.79 0.00 222.29 0.00 0.00 0.00
February 12.35 0.00 12.35 0.00 198.03 0.00 0.00 0.00
March 33.09 0.01 33.09 3.04 147.00 0.00 0.00 0.00
April 60.43 1.72 58.70 25.35 77.47 0.00 0.00 0.00
May 92.39 14.81 77.58 75.86 30.31 0.00 0.00 0.00
June 119.61 26.54 93.08 123.88 12.53 0.00 0.00 0.00
July 101.14 16.90 84.23 108.94 14.96 0.00 0.00 0.00
August 65.18 3.91 61.28 57.73 27.13 0.00 0.00 0.00
September 35.94 0.12 35.82 15.70 60.84 0.00 0.00 0.00
October 17.39 0.00 17.39 1.49 123.74 0.00 0.00 0.00
November 5.40 0.00 5.40 0.00 216.35 0.00 0.00 0.00
December 0.85 0.00 0.85 0.00 232.79 0.00 0.00 0.00
                 
Annual Sum or Average 45.71 5.36 40.35 34.54 113.16 0.00 0.00 0.00
Minimum of Months 0.85 0.00 0.85 0.00 12.53 0.00 0.00 0.00
Maximum of Months 119.61 26.54 93.08 123.88 232.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 7.18 1.22 5.96 0.00 413.03 0.00 0.00 0.00
February 42.80 14.91 27.89 9.02 351.63 0.00 0.00 0.00
March 128.77 55.61 73.16 76.98 253.20 0.00 0.00 0.00
April 305.14 158.43 146.71 303.93 140.49 0.00 0.00 0.00
May 296.02 135.07 160.95 313.69 64.44 0.00 0.00 0.00
June 324.24 138.44 185.79 372.63 29.79 0.00 0.00 0.00
July 270.84 102.34 168.49 317.32 32.20 0.00 0.00 0.00
August 223.47 95.02 128.44 247.82 53.18 0.00 0.00 0.00
September 134.45 56.06 78.40 117.76 109.45 0.00 0.00 0.00
October 52.71 15.78 36.93 20.82 221.06 0.00 0.00 0.00
November 21.30 7.81 13.50 2.27 391.28 0.00 0.00 0.00
December 1.89 0.19 1.70 0.00 435.45 0.00 0.00 0.00
                 
Annual Sum or Average 151.12 65.21 85.91 149.11 207.19 0.00 0.00 0.00
Minimum of Months 1.89 0.19 1.70 0.00 29.79 0.00 0.00 0.00
Maximum of Months 324.24 158.43 185.79 372.63 435.45 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 27.91 18.59 9.33 17.83 141.78 0.00 0.00 0.00
February 93.26 64.76 28.50 84.01 113.75 0.00 0.00 0.00
March 157.88 106.82 51.06 158.90 97.83 0.00 0.00 0.00
April 193.45 120.39 73.06 209.01 77.86 0.00 0.00 0.00
May 159.71 82.90 76.81 176.75 43.31 0.00 0.00 0.00
June 145.11 59.22 85.89 164.74 23.35 0.00 0.00 0.00
July 139.59 60.44 79.16 163.09 24.27 0.00 0.00 0.00
August 145.44 80.25 65.19 167.64 35.99 0.00 0.00 0.00
September 116.11 69.41 46.70 119.59 62.40 0.00 0.00 0.00
October 85.98 54.55 31.44 77.12 89.02 0.00 0.00 0.00
November 46.63 32.87 13.76 33.55 131.16 0.00 0.00 0.00
December 8.25 5.81 2.43 1.79 158.31 0.00 0.00 0.00
                 
Annual Sum or Average 109.91 62.90 47.01 114.56 83.11 0.00 0.00 0.00
Minimum of Months 8.25 5.81 2.43 1.79 23.35 0.00 0.00 0.00
Maximum of Months 193.45 120.39 85.89 209.01 158.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2.24 0.00 2.24 0.00 181.89 0.00 0.00 0.00
February 9.88 0.00 9.88 0.00 162.51 0.00 0.00 0.00
March 26.48 0.00 26.47 2.09 120.71 0.00 0.00 0.00
April 48.35 1.38 46.97 20.95 62.06 0.00 0.00 0.00
May 73.92 11.85 62.07 63.53 23.69 0.00 0.00 0.00
June 95.70 21.23 74.47 103.68 9.41 0.00 0.00 0.00
July 80.92 13.52 67.40 90.50 11.34 0.00 0.00 0.00
August 52.15 3.13 49.03 48.54 20.81 0.00 0.00 0.00
September 28.75 0.09 28.66 12.41 49.63 0.00 0.00 0.00
October 13.92 0.00 13.92 0.97 102.71 0.00 0.00 0.00
November 4.32 0.00 4.32 0.00 177.27 0.00 0.00 0.00
December 0.68 0.00 0.68 0.00 190.26 0.00 0.00 0.00
                 
Annual Sum or Average 36.57 4.29 32.29 28.73 92.31 0.00 0.00 0.00
Minimum of Months 0.68 0.00 0.68 0.00 9.41 0.00 0.00 0.00
Maximum of Months 95.70 21.23 74.47 103.68 190.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.45 5.72 9.73 1.99 403.57 0.00 0.00 0.00
February 80.16 38.43 41.73 42.19 334.86 0.00 0.00 0.00
March 224.83 113.84 110.99 193.71 248.90 0.00 0.00 0.00
April 299.11 151.52 147.59 281.37 133.56 0.00 0.00 0.00
May 435.61 245.90 189.70 495.42 60.48 0.00 0.00 0.00
June 398.91 186.31 212.60 475.73 25.20 0.00 0.00 0.00
July 379.95 184.76 195.18 465.48 28.48 0.00 0.00 0.00
August 305.29 149.62 155.67 355.46 49.21 0.00 0.00 0.00
September 191.08 86.44 104.64 185.89 107.64 0.00 0.00 0.00
October 103.49 41.93 61.56 76.52 212.21 0.00 0.00 0.00
November 21.45 7.79 13.66 1.58 390.36 0.00 0.00 0.00
December 3.05 0.72 2.33 0.00 433.56 0.00 0.00 0.00
                 
Annual Sum or Average 205.64 101.52 104.12 215.79 201.66 0.00 0.00 0.00
Minimum of Months 3.05 0.72 2.33 0.00 25.20 0.00 0.00 0.00
Maximum of Months 435.61 245.90 212.60 495.42 433.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 34.90 23.24 11.66 20.68 200.45 0.00 0.00 0.00
February 116.60 80.96 35.63 100.81 160.68 0.00 0.00 0.00
March 197.39 133.55 63.84 197.89 123.96 0.00 0.00 0.00
April 241.86 150.52 91.34 271.72 78.13 0.00 0.00 0.00
May 199.68 103.65 96.03 231.77 37.31 0.00 0.00 0.00
June 181.42 74.04 107.38 219.76 16.12 0.00 0.00 0.00
July 174.53 75.56 98.97 217.16 17.25 0.00 0.00 0.00
August 181.84 100.33 81.51 221.01 28.84 0.00 0.00 0.00
September 145.16 86.77 58.39 159.13 58.27 0.00 0.00 0.00
October 107.50 68.20 39.30 100.24 104.37 0.00 0.00 0.00
November 58.30 41.09 17.21 39.28 185.67 0.00 0.00 0.00
December 10.31 7.27 3.04 1.89 222.49 0.00 0.00 0.00
                 
Annual Sum or Average 137.42 78.64 58.77 148.57 102.52 0.00 0.00 0.00
Minimum of Months 10.31 7.27 3.04 1.89 16.12 0.00 0.00 0.00
Maximum of Months 241.86 150.52 107.38 271.72 222.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2.79 0.00 2.79 0.00 222.05 0.00 0.00 0.00
February 12.35 0.00 12.35 0.00 197.76 0.00 0.00 0.00
March 33.09 0.01 33.09 2.56 148.29 0.00 0.00 0.00
April 60.43 1.72 58.70 24.02 77.44 0.00 0.00 0.00
May 92.39 14.81 77.58 73.72 30.15 0.00 0.00 0.00
June 119.61 26.54 93.08 123.99 12.25 0.00 0.00 0.00
July 101.14 16.90 84.23 107.39 14.82 0.00 0.00 0.00
August 65.18 3.91 61.28 56.60 26.89 0.00 0.00 0.00
September 35.94 0.12 35.82 14.44 61.58 0.00 0.00 0.00
October 17.39 0.00 17.39 1.23 124.27 0.00 0.00 0.00
November 5.40 0.00 5.40 0.00 216.36 0.00 0.00 0.00
December 0.85 0.00 0.85 0.00 232.74 0.00 0.00 0.00
                 
Annual Sum or Average 45.71 5.36 40.35 33.86 113.26 0.00 0.00 0.00
Minimum of Months 0.85 0.00 0.85 0.00 12.25 0.00 0.00 0.00
Maximum of Months 119.61 26.54 93.08 123.99 232.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.45 5.72 9.73 2.03 403.00 0.00 0.00 0.00
February 80.16 38.43 41.73 42.80 333.24 0.00 0.00 0.00
March 224.83 113.84 110.99 196.12 244.71 0.00 0.00 0.00
April 299.11 151.52 147.59 285.93 130.95 0.00 0.00 0.00
May 435.61 245.90 189.70 496.72 60.71 0.00 0.00 0.00
June 398.91 186.31 212.60 473.41 26.74 0.00 0.00 0.00
July 379.95 184.76 195.18 462.50 30.13 0.00 0.00 0.00
August 305.29 149.62 155.67 355.96 50.39 0.00 0.00 0.00
September 191.08 86.44 104.64 188.15 105.90 0.00 0.00 0.00
October 103.49 41.93 61.56 77.75 210.04 0.00 0.00 0.00
November 21.45 7.79 13.66 1.63 390.08 0.00 0.00 0.00
December 3.05 0.72 2.33 0.00 433.35 0.00 0.00 0.00
                 
Annual Sum or Average 205.64 101.52 104.12 216.43 200.94 0.00 0.00 0.00
Minimum of Months 3.05 0.72 2.33 0.00 26.74 0.00 0.00 0.00
Maximum of Months 435.61 245.90 212.60 496.72 433.35 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3.54 0.00 3.54 0.00 294.87 0.00 0.00 0.00
February 15.65 0.00 15.65 0.00 264.12 0.00 0.00 0.00
March 41.91 0.01 41.90 2.91 196.58 0.00 0.00 0.00
April 76.53 2.18 74.34 30.93 102.11 0.00 0.00 0.00
May 117.00 18.75 98.25 96.29 41.03 0.00 0.00 0.00
June 151.48 33.61 117.88 158.55 17.71 0.00 0.00 0.00
July 128.08 21.40 106.68 138.31 21.18 0.00 0.00 0.00
August 82.55 4.95 77.60 72.91 37.12 0.00 0.00 0.00
September 45.51 0.15 45.37 18.57 81.87 0.00 0.00 0.00
October 22.03 0.00 22.03 1.44 166.51 0.00 0.00 0.00
November 6.84 0.00 6.84 0.00 287.60 0.00 0.00 0.00
December 1.07 0.00 1.07 0.00 308.33 0.00 0.00 0.00
                 
Annual Sum or Average 57.89 6.79 51.11 43.59 150.98 0.00 0.00 0.00
Minimum of Months 1.07 0.00 1.07 0.00 17.71 0.00 0.00 0.00
Maximum of Months 151.48 33.61 117.88 158.55 308.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1.30 0.00 1.30 0.00 108.69 0.00 0.00 0.00
February 5.77 0.00 5.77 0.00 97.37 0.00 0.00 0.00
March 15.45 0.00 15.45 1.07 72.47 0.00 0.00 0.00
April 28.21 0.80 27.41 11.40 37.64 0.00 0.00 0.00
May 43.13 6.91 36.22 35.50 15.12 0.00 0.00 0.00
June 55.84 12.39 43.45 58.45 6.53 0.00 0.00 0.00
July 47.22 7.89 39.33 50.99 7.81 0.00 0.00 0.00
August 30.43 1.82 28.61 26.88 13.69 0.00 0.00 0.00
September 16.78 0.05 16.72 6.85 30.18 0.00 0.00 0.00
October 8.12 0.00 8.12 0.53 61.38 0.00 0.00 0.00
November 2.52 0.00 2.52 0.00 106.01 0.00 0.00 0.00
December 0.40 0.00 0.40 0.00 113.63 0.00 0.00 0.00
                 
Annual Sum or Average 21.34 2.50 18.84 16.07 55.65 0.00 0.00 0.00
Minimum of Months 0.40 0.00 0.40 0.00 6.53 0.00 0.00 0.00
Maximum of Months 55.84 12.39 43.45 58.45 113.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.28 10.84 5.44 9.27 97.80 0.00 0.00 0.00
February 54.40 37.78 16.63 46.33 77.97 0.00 0.00 0.00
March 92.10 62.31 29.79 92.84 59.39 0.00 0.00 0.00
April 112.85 70.23 42.62 128.31 37.46 0.00 0.00 0.00
May 93.17 48.36 44.81 109.54 19.10 0.00 0.00 0.00
June 84.65 34.55 50.10 102.60 9.52 0.00 0.00 0.00
July 81.43 35.26 46.18 101.50 9.89 0.00 0.00 0.00
August 84.84 46.81 38.03 103.81 15.18 0.00 0.00 0.00
September 67.73 40.49 27.24 75.12 28.19 0.00 0.00 0.00
October 50.16 31.82 18.34 46.62 50.58 0.00 0.00 0.00
November 27.20 19.17 8.03 17.60 90.39 0.00 0.00 0.00
December 4.81 3.39 1.42 0.79 108.66 0.00 0.00 0.00
                 
Annual Sum or Average 64.12 36.69 27.42 69.59 50.22 0.00 0.00 0.00
Minimum of Months 4.81 3.39 1.42 0.79 9.52 0.00 0.00 0.00
Maximum of Months 112.85 70.23 50.10 128.31 108.66 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.20 29.43 14.77 25.17 265.46 0.00 0.00 0.00
February 147.66 102.54 45.13 125.76 211.63 0.00 0.00 0.00
March 249.98 169.13 80.85 251.98 161.20 0.00 0.00 0.00
April 306.30 190.62 115.67 348.26 101.67 0.00 0.00 0.00
May 252.88 131.26 121.62 297.31 51.84 0.00 0.00 0.00
June 229.76 93.76 135.99 278.49 25.84 0.00 0.00 0.00
July 221.03 95.69 125.34 275.48 26.86 0.00 0.00 0.00
August 230.28 127.06 103.22 281.76 41.21 0.00 0.00 0.00
September 183.84 109.89 73.94 203.90 76.52 0.00 0.00 0.00
October 136.14 86.37 49.77 126.55 137.30 0.00 0.00 0.00
November 73.83 52.04 21.79 47.78 245.34 0.00 0.00 0.00
December 13.06 9.20 3.85 2.14 294.93 0.00 0.00 0.00
                 
Annual Sum or Average 174.03 99.60 74.43 188.89 136.30 0.00 0.00 0.00
Minimum of Months 13.06 9.20 3.85 2.14 25.84 0.00 0.00 0.00
Maximum of Months 306.30 190.62 135.99 348.26 294.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 34.90 23.24 11.66 20.85 199.09 0.00 0.00 0.00
February 116.60 80.96 35.63 101.69 159.48 0.00 0.00 0.00
March 197.39 133.55 63.84 200.42 122.84 0.00 0.00 0.00
April 241.86 150.52 91.34 272.36 78.19 0.00 0.00 0.00
May 199.68 103.65 96.03 232.88 37.42 0.00 0.00 0.00
June 181.42 74.04 107.38 219.79 16.70 0.00 0.00 0.00
July 174.53 75.56 98.97 217.66 17.40 0.00 0.00 0.00
August 181.84 100.33 81.51 221.62 28.52 0.00 0.00 0.00
September 145.16 86.77 58.39 160.60 57.32 0.00 0.00 0.00
October 107.50 68.20 39.30 101.56 103.32 0.00 0.00 0.00
November 58.30 41.09 17.21 39.63 183.99 0.00 0.00 0.00
December 10.31 7.27 3.04 1.92 221.12 0.00 0.00 0.00
                 
Annual Sum or Average 137.42 78.64 58.77 149.38 101.84 0.00 0.00 0.00
Minimum of Months 10.31 7.27 3.04 1.92 16.70 0.00 0.00 0.00
Maximum of Months 241.86 150.52 107.38 272.36 221.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 7.18 1.22 5.96 0.00 410.39 0.00 0.00 0.00
February 42.80 14.91 27.89 8.72 349.80 0.00 0.00 0.00
March 128.77 55.61 73.16 74.50 254.05 0.00 0.00 0.00
April 305.14 158.43 146.71 296.99 141.67 0.00 0.00 0.00
May 296.02 135.07 160.95 312.13 64.05 0.00 0.00 0.00
June 324.24 138.44 185.79 376.64 28.74 0.00 0.00 0.00
July 270.84 102.34 168.49 319.63 30.72 0.00 0.00 0.00
August 223.47 95.02 128.44 247.59 51.21 0.00 0.00 0.00
September 134.45 56.06 78.40 115.00 109.50 0.00 0.00 0.00
October 52.71 15.78 36.93 19.89 220.80 0.00 0.00 0.00
November 21.30 7.81 13.50 2.24 387.74 0.00 0.00 0.00
December 1.89 0.19 1.70 0.00 432.85 0.00 0.00 0.00
                 
Annual Sum or Average 151.12 65.21 85.91 148.37 206.06 0.00 0.00 0.00
Minimum of Months 1.89 0.19 1.70 0.00 28.74 0.00 0.00 0.00
Maximum of Months 324.24 158.43 185.79 376.64 432.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2.79 0.00 2.79 0.00 220.88 0.00 0.00 0.00
February 12.35 0.00 12.35 0.00 196.80 0.00 0.00 0.00
March 33.09 0.01 33.09 3.13 146.31 0.00 0.00 0.00
April 60.43 1.72 58.70 25.57 77.12 0.00 0.00 0.00
May 92.39 14.81 77.58 75.59 30.21 0.00 0.00 0.00
June 119.61 26.54 93.08 122.84 12.59 0.00 0.00 0.00
July 101.14 16.90 84.23 108.22 14.99 0.00 0.00 0.00
August 65.18 3.91 61.28 57.56 27.08 0.00 0.00 0.00
September 35.94 0.12 35.82 16.13 59.93 0.00 0.00 0.00
October 17.39 0.00 17.39 1.63 122.92 0.00 0.00 0.00
November 5.40 0.00 5.40 0.00 214.40 0.00 0.00 0.00
December 0.85 0.00 0.85 0.00 231.33 0.00 0.00 0.00
                 
Annual Sum or Average 45.71 5.36 40.35 34.43 112.43 0.00 0.00 0.00
Minimum of Months 0.85 0.00 0.85 0.00 12.59 0.00 0.00 0.00
Maximum of Months 119.61 26.54 93.08 122.84 231.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 7.18 1.22 5.96 0.00 410.21 0.00 0.00 0.00
February 42.80 14.91 27.89 9.14 349.28 0.00 0.00 0.00
March 128.77 55.61 73.16 77.16 252.03 0.00 0.00 0.00
April 305.14 158.43 146.71 303.37 139.66 0.00 0.00 0.00
May 296.02 135.07 160.95 312.43 63.96 0.00 0.00 0.00
June 324.24 138.44 185.79 370.05 29.79 0.00 0.00 0.00
July 270.84 102.34 168.49 315.41 32.10 0.00 0.00 0.00
August 223.47 95.02 128.44 246.71 52.85 0.00 0.00 0.00
September 134.45 56.06 78.40 118.43 107.83 0.00 0.00 0.00
October 52.71 15.78 36.93 21.19 219.58 0.00 0.00 0.00
November 21.30 7.81 13.50 2.35 387.50 0.00 0.00 0.00
December 1.89 0.19 1.70 0.00 432.65 0.00 0.00 0.00
                 
Annual Sum or Average 151.12 65.21 85.91 148.61 205.72 0.00 0.00 0.00
Minimum of Months 1.89 0.19 1.70 0.00 29.79 0.00 0.00 0.00
Maximum of Months 324.24 158.43 185.79 370.05 432.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 51.18 34.08 17.11 29.69 296.46 0.00 0.00 0.00
February 171.00 118.74 52.26 144.65 238.83 0.00 0.00 0.00
March 289.49 195.86 93.63 286.57 184.93 0.00 0.00 0.00
April 354.71 220.75 133.96 395.07 116.28 0.00 0.00 0.00
May 292.85 152.01 140.84 340.23 54.90 0.00 0.00 0.00
June 266.07 108.58 157.49 323.03 24.05 0.00 0.00 0.00
July 255.96 110.81 145.15 319.34 25.25 0.00 0.00 0.00
August 266.68 147.14 119.54 323.78 41.92 0.00 0.00 0.00
September 212.89 127.26 85.63 231.72 86.43 0.00 0.00 0.00
October 157.66 100.02 57.64 144.26 155.82 0.00 0.00 0.00
November 85.50 60.26 25.24 56.38 273.92 0.00 0.00 0.00
December 15.12 10.66 4.46 2.70 328.53 0.00 0.00 0.00
                 
Annual Sum or Average 201.54 115.34 86.20 216.66 151.86 0.00 0.00 0.00
Minimum of Months 15.12 10.66 4.46 2.70 24.05 0.00 0.00 0.00
Maximum of Months 354.71 220.75 157.49 395.07 328.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.56 0.00 19.56 0.00 1591.97 0.00 0.00 0.00
February 86.48 0.00 86.48 0.00 1423.72 0.00 0.00 0.00
March 231.64 0.04 231.60 16.96 1065.25 0.00 0.00 0.00
April 422.97 12.07 410.90 178.89 557.89 0.00 0.00 0.00
May 646.69 103.65 543.03 549.36 220.06 0.00 0.00 0.00
June 837.27 185.76 651.51 907.00 90.97 0.00 0.00 0.00
July 707.92 118.31 589.61 795.00 108.00 0.00 0.00 0.00
August 456.27 27.35 428.92 424.70 193.33 0.00 0.00 0.00
September 251.56 0.82 250.74 106.77 447.50 0.00 0.00 0.00
October 121.74 0.00 121.74 8.06 911.97 0.00 0.00 0.00
November 37.78 0.00 37.78 0.00 1544.27 0.00 0.00 0.00
December 5.93 0.00 5.93 0.00 1660.49 0.00 0.00 0.00
                 
Annual Sum or Average 319.97 37.50 282.47 250.40 814.70 0.00 0.00 0.00
Minimum of Months 5.93 0.00 5.93 0.00 90.97 0.00 0.00 0.00
Maximum of Months 837.27 185.76 651.51 907.00 1660.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.56 0.00 19.56 0.00 1613.86 0.00 0.00 0.00
February 86.48 0.00 86.48 0.00 1445.00 0.00 0.00 0.00
March 231.64 0.04 231.60 15.46 1087.41 0.00 0.00 0.00
April 422.97 12.07 410.90 170.91 574.16 0.00 0.00 0.00
May 646.69 103.65 543.03 536.18 226.52 0.00 0.00 0.00
June 837.27 185.76 651.51 893.17 94.71 0.00 0.00 0.00
July 707.92 118.31 589.61 782.07 112.49 0.00 0.00 0.00
August 456.27 27.35 428.92 413.99 200.55 0.00 0.00 0.00
September 251.56 0.82 250.74 100.56 465.50 0.00 0.00 0.00
October 121.74 0.00 121.74 6.76 936.77 0.00 0.00 0.00
November 37.78 0.00 37.78 0.00 1565.05 0.00 0.00 0.00
December 5.93 0.00 5.93 0.00 1680.78 0.00 0.00 0.00
                 
Annual Sum or Average 319.97 37.50 282.47 244.73 830.28 0.00 0.00 0.00
Minimum of Months 5.93 0.00 5.93 0.00 94.71 0.00 0.00 0.00
Maximum of Months 837.27 185.76 651.51 893.17 1680.78 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2.79 0.00 2.79 0.00 194.90 0.00 0.00 0.00
February 12.35 0.00 12.35 0.01 170.61 0.00 0.00 0.00
March 33.09 0.01 33.09 8.11 126.65 0.00 0.00 0.00
April 60.43 1.72 58.70 48.30 69.90 0.00 0.00 0.00
May 92.39 14.81 77.58 113.27 29.72 0.00 0.00 0.00
June 119.61 26.54 93.08 170.17 12.95 0.00 0.00 0.00
July 101.14 16.90 84.23 153.71 14.90 0.00 0.00 0.00
August 65.18 3.91 61.28 96.75 24.53 0.00 0.00 0.00
September 35.94 0.12 35.82 36.56 49.25 0.00 0.00 0.00
October 17.39 0.00 17.39 5.72 102.10 0.00 0.00 0.00
November 5.40 0.00 5.40 0.00 187.34 0.00 0.00 0.00
December 0.85 0.00 0.85 0.00 204.63 0.00 0.00 0.00
                 
Annual Sum or Average 45.71 5.36 40.35 53.03 98.58 0.00 0.00 0.00
Minimum of Months 0.85 0.00 0.85 0.00 12.95 0.00 0.00 0.00
Maximum of Months 119.61 26.54 93.08 170.17 204.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.91 11.45 19.46 7.12 708.42 0.00 0.00 0.00
February 160.31 76.85 83.45 106.57 584.77 0.00 0.00 0.00
March 449.63 227.67 221.96 444.13 435.55 0.00 0.00 0.00
April 598.18 303.01 295.16 679.16 246.49 0.00 0.00 0.00
May 871.15 491.77 379.38 1137.85 114.51 0.00 0.00 0.00
June 797.76 372.59 425.17 1114.90 51.35 0.00 0.00 0.00
July 759.84 369.50 390.34 1095.47 57.36 0.00 0.00 0.00
August 610.54 299.21 311.32 863.69 91.85 0.00 0.00 0.00
September 382.14 172.86 209.27 476.14 180.23 0.00 0.00 0.00
October 206.96 83.85 123.11 195.62 358.42 0.00 0.00 0.00
November 42.90 15.58 27.32 6.68 675.16 0.00 0.00 0.00
December 6.11 1.45 4.66 0.00 763.00 0.00 0.00 0.00
                 
Annual Sum or Average 411.25 203.03 208.22 513.29 354.45 0.00 0.00 0.00
Minimum of Months 6.11 1.45 4.66 0.00 51.35 0.00 0.00 0.00
Maximum of Months 871.15 491.77 425.17 1137.85 763.00 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 34.90 23.24 11.66 24.78 176.86 0.00 0.00 0.00
February 116.60 80.96 35.63 112.53 142.90 0.00 0.00 0.00
March 197.39 133.55 63.84 219.11 112.33 0.00 0.00 0.00
April 241.86 150.52 91.34 302.46 70.99 0.00 0.00 0.00
May 199.68 103.65 96.03 270.35 34.73 0.00 0.00 0.00
June 181.42 74.04 107.38 263.60 17.08 0.00 0.00 0.00
July 174.53 75.56 98.97 261.11 17.64 0.00 0.00 0.00
August 181.84 100.33 81.51 260.48 25.86 0.00 0.00 0.00
September 145.16 86.77 58.39 187.57 48.81 0.00 0.00 0.00
October 107.50 68.20 39.30 116.50 90.81 0.00 0.00 0.00
November 58.30 41.09 17.21 46.19 162.81 0.00 0.00 0.00
December 10.31 7.27 3.04 2.94 195.47 0.00 0.00 0.00
                 
Annual Sum or Average 137.42 78.64 58.77 172.49 91.11 0.00 0.00 0.00
Minimum of Months 10.31 7.27 3.04 2.94 17.08 0.00 0.00 0.00
Maximum of Months 241.86 150.52 107.38 302.46 195.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3.54 0.00 3.54 0.00 294.14 0.00 0.00 0.00
February 15.65 0.00 15.65 0.00 264.15 0.00 0.00 0.00
March 41.91 0.01 41.90 2.66 198.13 0.00 0.00 0.00
April 76.53 2.18 74.34 27.64 105.33 0.00 0.00 0.00
May 117.00 18.75 98.25 89.34 44.07 0.00 0.00 0.00
June 151.48 33.61 117.88 152.05 19.23 0.00 0.00 0.00
July 128.08 21.40 106.68 132.18 23.09 0.00 0.00 0.00
August 82.55 4.95 77.60 67.16 40.62 0.00 0.00 0.00
September 45.51 0.15 45.37 15.97 86.70 0.00 0.00 0.00
October 22.03 0.00 22.03 1.17 168.72 0.00 0.00 0.00
November 6.84 0.00 6.84 0.00 286.36 0.00 0.00 0.00
December 1.07 0.00 1.07 0.00 307.58 0.00 0.00 0.00
                 
Annual Sum or Average 57.89 6.79 51.11 40.93 152.58 0.00 0.00 0.00
Minimum of Months 1.07 0.00 1.07 0.00 19.23 0.00 0.00 0.00
Maximum of Months 151.48 33.61 117.88 152.05 307.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3.17 0.00 3.17 0.00 263.17 0.00 0.00 0.00
February 14.00 0.00 14.00 0.00 236.28 0.00 0.00 0.00
March 37.50 0.01 37.49 2.38 177.27 0.00 0.00 0.00
April 68.47 1.95 66.52 24.73 94.24 0.00 0.00 0.00
May 104.68 16.78 87.90 79.93 39.43 0.00 0.00 0.00
June 135.53 30.07 105.46 136.04 17.21 0.00 0.00 0.00
July 114.59 19.15 95.44 118.26 20.66 0.00 0.00 0.00
August 73.86 4.43 69.43 60.09 36.34 0.00 0.00 0.00
September 40.72 0.13 40.59 14.29 77.58 0.00 0.00 0.00
October 19.71 0.00 19.71 1.05 150.93 0.00 0.00 0.00
November 6.12 0.00 6.12 0.00 256.21 0.00 0.00 0.00
December 0.96 0.00 0.96 0.00 275.20 0.00 0.00 0.00
                 
Annual Sum or Average 51.80 6.07 45.73 36.62 136.51 0.00 0.00 0.00
Minimum of Months 0.96 0.00 0.96 0.00 17.21 0.00 0.00 0.00
Maximum of Months 135.53 30.07 105.46 136.04 275.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 130.29 86.75 43.54 74.07 780.71 0.00 0.00 0.00
February 435.30 302.26 133.03 369.69 623.56 0.00 0.00 0.00
March 736.91 498.57 238.34 738.03 477.42 0.00 0.00 0.00
April 902.92 561.93 340.99 1013.45 307.92 0.00 0.00 0.00
May 745.46 386.94 358.52 857.40 164.97 0.00 0.00 0.00
June 677.30 276.40 400.90 803.12 83.53 0.00 0.00 0.00
July 651.56 282.08 369.48 794.73 87.01 0.00 0.00 0.00
August 678.85 374.56 304.28 813.52 133.50 0.00 0.00 0.00
September 541.93 323.95 217.98 589.88 237.86 0.00 0.00 0.00
October 401.34 254.61 146.73 369.27 409.38 0.00 0.00 0.00
November 217.65 153.41 64.25 141.00 720.18 0.00 0.00 0.00
December 38.49 27.13 11.36 6.35 867.73 0.00 0.00 0.00
                 
Annual Sum or Average 513.02 293.60 219.42 548.03 406.81 0.00 0.00 0.00
Minimum of Months 38.49 27.13 11.36 6.35 83.53 0.00 0.00 0.00
Maximum of Months 902.92 561.93 400.90 1013.45 867.73 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.472780E+09 0.314774E+09 0.158006E+09 0.275631E+09 0.267949E+10
February 0.142666E+10 0.990652E+09 0.436005E+09 0.121345E+10 0.194451E+10
March 0.267393E+10 0.180911E+10 0.864824E+09 0.266503E+10 0.165253E+10
April 0.317064E+10 0.197323E+10 0.119741E+10 0.354083E+10 0.103835E+10
May 0.270495E+10 0.140405E+10 0.130090E+10 0.312720E+10 0.551265E+09
June 0.237835E+10 0.970599E+09 0.140775E+10 0.283644E+10 0.270589E+09
July 0.236424E+10 0.102357E+10 0.134067E+10 0.289496E+10 0.291596E+09
August 0.246326E+10 0.135914E+10 0.110412E+10 0.295829E+10 0.448026E+09
September 0.190301E+10 0.113758E+10 0.765436E+09 0.206980E+10 0.781848E+09
October 0.145629E+10 0.923887E+09 0.532405E+09 0.134487E+10 0.140158E+10
November 0.764297E+09 0.538697E+09 0.225599E+09 0.499149E+09 0.242182E+10
December 0.139675E+09 98460044.66 41214694.35 24395650.64 0.298314E+10
           
Annual Sum or Average 0.219181E+11 0.125437E+11 0.937435E+10 0.234500E+11 0.164648E+11
Minimum of Months 0.139675E+09 98460044.66 41214694.35 24395650.64 0.270589E+09
Maximum of Months 0.317064E+10 0.197323E+10 0.140775E+10 0.354083E+10 0.298314E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.133132E+10 0.886384E+09 0.444935E+09 0.769828E+09 0.751249E+10
February 0.401737E+10 0.278961E+10 0.122776E+10 0.340440E+10 0.544237E+10
March 0.752962E+10 0.509434E+10 0.243529E+10 0.749574E+10 0.462710E+10
April 0.892830E+10 0.555648E+10 0.337183E+10 0.998394E+10 0.288999E+10
May 0.761696E+10 0.395370E+10 0.366326E+10 0.887119E+10 0.148225E+10
June 0.669728E+10 0.273314E+10 0.396414E+10 0.809173E+10 0.690589E+09
July 0.665755E+10 0.288230E+10 0.377525E+10 0.825827E+10 0.743680E+09
August 0.693636E+10 0.382724E+10 0.310912E+10 0.840650E+10 0.117999E+10
September 0.535876E+10 0.320335E+10 0.215542E+10 0.584396E+10 0.216866E+10
October 0.410082E+10 0.260160E+10 0.149922E+10 0.377525E+10 0.393440E+10
November 0.215221E+10 0.151694E+10 0.635273E+09 0.139497E+10 0.677694E+10
December 0.393315E+09 0.277257E+09 0.116058E+09 67758619.82 0.835098E+10
           
Annual Sum or Average 0.617199E+11 0.353223E+11 0.263975E+11 0.663635E+11 0.457994E+11
Minimum of Months 0.393315E+09 0.277257E+09 0.116058E+09 67758619.82 0.690589E+09
Maximum of Months 0.892830E+10 0.555648E+10 0.396414E+10 0.998394E+10 0.835098E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.172946E+10 0.115146E+10 0.577995E+09 0.995372E+09 0.101594E+11
February 0.521879E+10 0.362386E+10 0.159493E+10 0.445016E+10 0.734005E+10
March 0.978141E+10 0.661783E+10 0.316358E+10 0.986360E+10 0.623674E+10
April 0.115984E+11 0.721818E+10 0.438019E+10 0.131495E+11 0.390802E+10
May 0.989487E+10 0.513608E+10 0.475878E+10 0.116543E+11 0.205212E+10
June 0.870015E+10 0.355051E+10 0.514964E+10 0.106172E+11 0.973892E+09
July 0.864853E+10 0.374427E+10 0.490426E+10 0.108269E+11 0.105294E+10
August 0.901073E+10 0.497180E+10 0.403893E+10 0.110176E+11 0.165138E+10
September 0.696134E+10 0.416133E+10 0.280001E+10 0.765336E+10 0.301488E+10
October 0.532720E+10 0.337963E+10 0.194757E+10 0.493445E+10 0.539040E+10
November 0.279584E+10 0.197059E+10 0.825256E+09 0.181032E+10 0.915465E+10
December 0.510938E+09 0.360173E+09 0.150766E+09 85571057.55 0.112668E+11
           
Annual Sum or Average 0.801776E+11 0.458857E+11 0.342919E+11 0.870583E+11 0.622012E+11
Minimum of Months 0.510938E+09 0.360173E+09 0.150766E+09 85571057.55 0.973892E+09
Maximum of Months 0.115984E+11 0.721818E+10 0.514964E+10 0.131495E+11 0.112668E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 93476878.82 62236309.34 31240569.48 55568334.69 0.536845E+09
February 0.282075E+09 0.195869E+09 86205933.23 0.245236E+09 0.388294E+09
March 0.528684E+09 0.357692E+09 0.170991E+09 0.536308E+09 0.330486E+09
April 0.626891E+09 0.390141E+09 0.236750E+09 0.707387E+09 0.203442E+09
May 0.534817E+09 0.277604E+09 0.257213E+09 0.625861E+09 0.101099E+09
June 0.470243E+09 0.191904E+09 0.278339E+09 0.572005E+09 43933599.29
July 0.467453E+09 0.202377E+09 0.265076E+09 0.585076E+09 47326459.57
August 0.487029E+09 0.268725E+09 0.218305E+09 0.595079E+09 77391693.48
September 0.376259E+09 0.224919E+09 0.151341E+09 0.416041E+09 0.150237E+09
October 0.287934E+09 0.182668E+09 0.105266E+09 0.271379E+09 0.278529E+09
November 0.151115E+09 0.106510E+09 44604980.56 0.101910E+09 0.481290E+09
December 27616108.81 19467241.87 8148866.95 5069897.82 0.595911E+09
           
Annual Sum or Average 0.433359E+10 0.248011E+10 0.185348E+10 0.471692E+10 0.323479E+10
Minimum of Months 27616108.81 19467241.87 8148866.95 5069897.82 43933599.29
Maximum of Months 0.626891E+09 0.390141E+09 0.278339E+09 0.707387E+09 0.595911E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 19232962.10 3269712.17 15963249.93 0.00 0.110658E+10
February 0.103533E+09 36059635.70 67473741.62 20728151.13 0.852155E+09
March 0.344892E+09 0.148950E+09 0.195941E+09 0.198860E+09 0.684599E+09
April 0.790929E+09 0.410659E+09 0.380270E+09 0.772561E+09 0.369199E+09
May 0.792860E+09 0.361774E+09 0.431086E+09 0.838972E+09 0.173285E+09
June 0.840418E+09 0.358839E+09 0.481579E+09 0.980068E+09 75763190.00
July 0.725411E+09 0.274115E+09 0.451296E+09 0.859319E+09 83711422.43
August 0.598536E+09 0.254509E+09 0.344027E+09 0.665257E+09 0.139209E+09
September 0.348505E+09 0.145298E+09 0.203206E+09 0.297413E+09 0.287637E+09
October 0.141175E+09 42266213.40 98908372.99 52330327.89 0.595828E+09
November 55219401.28 20239990.41 34979410.87 5613811.51 0.101474E+10
December 5057197.14 512230.40 4544966.74 0.00 0.116653E+10
           
Annual Sum or Average 0.476577E+10 0.205649E+10 0.270928E+10 0.469112E+10 0.654924E+10
Minimum of Months 5057197.14 512230.40 4544966.74 0.00 75763190.00
Maximum of Months 0.840418E+09 0.410659E+09 0.481579E+09 0.980068E+09 0.116653E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 7485397.50 0.00 7485397.50 0.00 0.595382E+09
February 29886918.80 0.00 29886918.80 0.00 0.479074E+09
March 88635339.19 15040.35 88620298.84 8135622.54 0.393716E+09
April 0.156626E+09 4468630.01 0.152157E+09 65706360.06 0.200790E+09
May 0.247451E+09 39662063.78 0.207788E+09 0.203190E+09 81182481.19
June 0.310041E+09 68787424.57 0.241253E+09 0.321104E+09 32482509.71
July 0.270880E+09 45269352.45 0.225611E+09 0.291796E+09 40074517.83
August 0.174589E+09 10464841.60 0.164124E+09 0.154627E+09 72652353.90
September 93150850.77 302442.08 92848408.69 40685892.30 0.157710E+09
October 46581866.67 0.00 46581866.67 3994309.61 0.331434E+09
November 13989674.44 0.00 13989674.44 0.00 0.560771E+09
December 2270676.37 0.00 2270676.37 0.00 0.623503E+09
           
Annual Sum or Average 0.144159E+10 0.168970E+09 0.127262E+10 0.108924E+10 0.356877E+10
Minimum of Months 2270676.37 0.00 2270676.37 0.00 32482509.71
Maximum of Months 0.310041E+09 68787424.57 0.241253E+09 0.321104E+09 0.623503E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 19232962.10 3269712.17 15963249.93 0.00 0.110625E+10
February 0.103533E+09 36059635.70 67473741.62 21819236.64 0.850667E+09
March 0.344892E+09 0.148950E+09 0.195941E+09 0.206195E+09 0.678177E+09
April 0.790929E+09 0.410659E+09 0.380270E+09 0.787793E+09 0.364153E+09
May 0.792860E+09 0.361774E+09 0.431086E+09 0.840197E+09 0.172596E+09
June 0.840418E+09 0.358839E+09 0.481579E+09 0.965869E+09 77221590.29
July 0.725411E+09 0.274115E+09 0.451296E+09 0.849918E+09 86232436.18
August 0.598536E+09 0.254509E+09 0.344027E+09 0.663761E+09 0.142439E+09
September 0.348505E+09 0.145298E+09 0.203206E+09 0.305223E+09 0.283703E+09
October 0.141175E+09 42266213.40 98908372.99 55758432.53 0.592090E+09
November 55219401.28 20239990.41 34979410.87 5895841.25 0.101419E+10
December 5057197.14 512230.40 4544966.74 0.00 0.116631E+10
           
Annual Sum or Average 0.476577E+10 0.205649E+10 0.270928E+10 0.470243E+10 0.653402E+10
Minimum of Months 5057197.14 512230.40 4544966.74 0.00 77221590.29
Maximum of Months 0.840418E+09 0.410659E+09 0.481579E+09 0.965869E+09 0.116631E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 74766633.98 49779147.74 24987486.24 47747523.40 0.379756E+09
February 0.225615E+09 0.156664E+09 68951034.08 0.203225E+09 0.275196E+09
March 0.422863E+09 0.286097E+09 0.136766E+09 0.425589E+09 0.262023E+09
April 0.501413E+09 0.312051E+09 0.189362E+09 0.541751E+09 0.201817E+09
May 0.427769E+09 0.222039E+09 0.205730E+09 0.473397E+09 0.116002E+09
June 0.376120E+09 0.153493E+09 0.222627E+09 0.427008E+09 60516053.44
July 0.373888E+09 0.161869E+09 0.212019E+09 0.436808E+09 64995240.45
August 0.389546E+09 0.214937E+09 0.174609E+09 0.449019E+09 96399448.82
September 0.300948E+09 0.179899E+09 0.121048E+09 0.309980E+09 0.161753E+09
October 0.230302E+09 0.146106E+09 84196004.15 0.206563E+09 0.238438E+09
November 0.120868E+09 85190798.59 35676889.28 86965820.71 0.339965E+09
December 22088494.24 15570696.90 6517797.34 4781178.45 0.424016E+09
           
Annual Sum or Average 0.346619E+10 0.198370E+10 0.148249E+10 0.361284E+10 0.262088E+10
Minimum of Months 22088494.24 15570696.90 6517797.34 4781178.45 60516053.44
Maximum of Months 0.501413E+09 0.312051E+09 0.222627E+09 0.541751E+09 0.424016E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 5989111.78 0.00 5989111.78 0.00 0.487170E+09
February 23912704.39 0.00 23912704.39 0.00 0.393152E+09
March 70917670.65 12033.88 70905636.77 5595453.47 0.323321E+09
April 0.125317E+09 3575377.89 0.121742E+09 54308737.50 0.160851E+09
May 0.197987E+09 31733856.97 0.166253E+09 0.170152E+09 63442162.58
June 0.248066E+09 55037234.19 0.193028E+09 0.268736E+09 24389931.96
July 0.216733E+09 36220282.52 0.180513E+09 0.242408E+09 30369191.96
August 0.139690E+09 8372983.02 0.131317E+09 0.130005E+09 55729906.41
September 74530558.75 241985.74 74288573.01 32158376.38 0.128640E+09
October 37270433.09 0.00 37270433.09 2604877.21 0.275091E+09
November 11193223.08 0.00 11193223.08 0.00 0.459478E+09
December 1816781.89 0.00 1816781.89 0.00 0.509602E+09
           
Annual Sum or Average 0.115342E+10 0.135194E+09 0.101823E+10 0.905967E+09 0.291124E+10
Minimum of Months 1816781.89 0.00 1816781.89 0.00 24389931.96
Maximum of Months 0.248066E+09 55037234.19 0.193028E+09 0.268736E+09 0.509602E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 41391987.23 15330505.74 26061481.50 5321119.16 0.108093E+10
February 0.193920E+09 92969590.80 0.100950E+09 0.102072E+09 0.810085E+09
March 0.602190E+09 0.304922E+09 0.297268E+09 0.518843E+09 0.666652E+09
April 0.775293E+09 0.392733E+09 0.382560E+09 0.729313E+09 0.346179E+09
May 0.116673E+10 0.658628E+09 0.508102E+09 0.132693E+10 0.161979E+09
June 0.103397E+10 0.482910E+09 0.551065E+09 0.123309E+10 65322056.73
July 0.101765E+10 0.494870E+09 0.522778E+09 0.124674E+10 76280835.16
August 0.817688E+09 0.400734E+09 0.416954E+09 0.952060E+09 0.131816E+09
September 0.495284E+09 0.224047E+09 0.271237E+09 0.481833E+09 0.279011E+09
October 0.277184E+09 0.112303E+09 0.164881E+09 0.204956E+09 0.568384E+09
November 55596086.02 20188305.78 35407780.24 4104381.26 0.101181E+10
December 8178712.01 1936245.93 6242466.08 0.00 0.116124E+10
           
Annual Sum or Average 0.648508E+10 0.320157E+10 0.328351E+10 0.680527E+10 0.635969E+10
Minimum of Months 8178712.01 1936245.93 6242466.08 0.00 65322056.73
Maximum of Months 0.116673E+10 0.658628E+09 0.551065E+09 0.132693E+10 0.116124E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 93476878.82 62236309.34 31240569.48 55392809.31 0.536876E+09
February 0.282075E+09 0.195869E+09 86205933.23 0.243890E+09 0.388721E+09
March 0.528684E+09 0.357692E+09 0.170991E+09 0.530031E+09 0.332014E+09
April 0.626891E+09 0.390141E+09 0.236750E+09 0.704294E+09 0.202508E+09
May 0.534817E+09 0.277604E+09 0.257213E+09 0.620773E+09 99935122.88
June 0.470243E+09 0.191904E+09 0.278339E+09 0.569618E+09 41783537.90
July 0.467453E+09 0.202377E+09 0.265076E+09 0.581633E+09 46209908.01
August 0.487029E+09 0.268725E+09 0.218305E+09 0.591953E+09 77247293.33
September 0.376259E+09 0.224919E+09 0.151341E+09 0.412471E+09 0.151031E+09
October 0.287934E+09 0.182668E+09 0.105266E+09 0.268494E+09 0.279551E+09
November 0.151115E+09 0.106510E+09 44604980.56 0.101811E+09 0.481245E+09
December 27616108.81 19467241.87 8148866.95 5061752.74 0.595918E+09
           
Annual Sum or Average 0.433359E+10 0.248011E+10 0.185348E+10 0.468542E+10 0.323304E+10
Minimum of Months 27616108.81 19467241.87 8148866.95 5061752.74 41783537.90
Maximum of Months 0.626891E+09 0.390141E+09 0.278339E+09 0.704294E+09 0.595918E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 7485397.50 0.00 7485397.50 0.00 0.594733E+09
February 29886918.80 0.00 29886918.80 0.00 0.478420E+09
March 88635339.19 15040.35 88620298.84 6844528.81 0.397182E+09
April 0.156626E+09 4468630.01 0.152157E+09 62254684.12 0.200721E+09
May 0.247451E+09 39662063.78 0.207788E+09 0.197461E+09 80753975.33
June 0.310041E+09 68787424.57 0.241253E+09 0.321391E+09 31746027.10
July 0.270880E+09 45269352.45 0.225611E+09 0.287626E+09 39688382.49
August 0.174589E+09 10464841.60 0.164124E+09 0.151599E+09 72027478.75
September 93150850.77 302442.08 92848408.69 37419807.25 0.159604E+09
October 46581866.67 0.00 46581866.67 3302909.36 0.332848E+09
November 13989674.44 0.00 13989674.44 0.00 0.560818E+09
December 2270676.37 0.00 2270676.37 0.00 0.623373E+09
           
Annual Sum or Average 0.144159E+10 0.168970E+09 0.127262E+10 0.106790E+10 0.357191E+10
Minimum of Months 2270676.37 0.00 2270676.37 0.00 31746027.10
Maximum of Months 0.310041E+09 68787424.57 0.241253E+09 0.321391E+09 0.623373E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 41391987.23 15330505.74 26061481.50 5439810.98 0.107940E+10
February 0.193920E+09 92969590.80 0.100950E+09 0.103552E+09 0.806175E+09
March 0.602190E+09 0.304922E+09 0.297268E+09 0.525276E+09 0.655422E+09
April 0.775293E+09 0.392733E+09 0.382560E+09 0.741118E+09 0.339432E+09
May 0.116673E+10 0.658628E+09 0.508102E+09 0.133041E+10 0.162608E+09
June 0.103397E+10 0.482910E+09 0.551065E+09 0.122707E+10 69310804.08
July 0.101765E+10 0.494870E+09 0.522778E+09 0.123877E+10 80705427.89
August 0.817688E+09 0.400734E+09 0.416954E+09 0.953398E+09 0.134971E+09
September 0.495284E+09 0.224047E+09 0.271237E+09 0.487689E+09 0.274504E+09
October 0.277184E+09 0.112303E+09 0.164881E+09 0.208240E+09 0.562579E+09
November 55596086.02 20188305.78 35407780.24 4229581.13 0.101108E+10
December 8178712.01 1936245.93 6242466.08 0.00 0.116068E+10
           
Annual Sum or Average 0.648508E+10 0.320157E+10 0.328351E+10 0.682519E+10 0.633687E+10
Minimum of Months 8178712.01 1936245.93 6242466.08 0.00 69310804.08
Maximum of Months 0.116673E+10 0.658628E+09 0.551065E+09 0.133041E+10 0.116068E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 9479783.63 0.00 9479783.63 0.00 0.789777E+09
February 37849896.91 0.00 37849896.91 0.00 0.638959E+09
March 0.112251E+09 19047.66 0.112232E+09 7803494.40 0.526530E+09
April 0.198357E+09 5659237.96 0.192698E+09 80171882.60 0.264658E+09
May 0.313380E+09 50229501.24 0.263151E+09 0.257910E+09 0.109886E+09
June 0.392647E+09 87114932.98 0.305532E+09 0.410958E+09 45906023.94
July 0.343053E+09 57330778.54 0.285722E+09 0.370458E+09 56716084.96
August 0.221106E+09 13253061.60 0.207853E+09 0.195275E+09 99432123.32
September 0.117970E+09 383023.81 0.117587E+09 48135575.03 0.212196E+09
October 58992994.98 0.00 58992994.98 3865061.12 0.445982E+09
November 17717039.98 0.00 17717039.98 0.00 0.745447E+09
December 2875668.35 0.00 2875668.35 0.00 0.825837E+09
           
Annual Sum or Average 0.182568E+10 0.213990E+09 0.161169E+10 0.137458E+10 0.476132E+10
Minimum of Months 2875668.35 0.00 2875668.35 0.00 45906023.94
Maximum of Months 0.392647E+09 87114932.98 0.305532E+09 0.410958E+09 0.825837E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 3494640.77 0.00 3494640.77 0.00 0.291115E+09
February 13953039.24 0.00 13953039.24 0.00 0.235547E+09
March 41380390.33 7021.76 41373368.57 2876691.15 0.194101E+09
April 73122547.54 2086229.44 71036318.10 29554675.58 97564034.44
May 0.115525E+09 18516674.00 97008340.02 95076230.51 40508417.05
June 0.144746E+09 32114171.44 0.112632E+09 0.151496E+09 16922861.24
July 0.126463E+09 21134498.85 0.105329E+09 0.136566E+09 20907897.34
August 81508690.92 4885627.27 76623063.65 71986621.70 36654797.82
September 43488506.95 141198.44 43347308.51 17744766.09 78224051.33
October 21747260.66 0.00 21747260.66 1424821.57 0.164408E+09
November 6531234.54 0.00 6531234.54 0.00 0.274783E+09
December 1060090.42 0.00 1060090.42 0.00 0.304348E+09
           
Annual Sum or Average 0.673021E+09 78885421.19 0.594136E+09 0.506726E+09 0.175508E+10
Minimum of Months 1060090.42 0.00 1060090.42 0.00 16922861.24
Maximum of Months 0.144746E+09 32114171.44 0.112632E+09 0.151496E+09 0.304348E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 43615934.97 29039211.14 14576723.83 24833587.50 0.261959E+09
February 0.131615E+09 91391623.88 40223341.06 0.112092E+09 0.188629E+09
March 0.246682E+09 0.166898E+09 79783921.36 0.248661E+09 0.159070E+09
April 0.292505E+09 0.182038E+09 0.110467E+09 0.332584E+09 97094594.37
May 0.249544E+09 0.129529E+09 0.120015E+09 0.293389E+09 51159562.90
June 0.219413E+09 89541663.22 0.129872E+09 0.265948E+09 24676204.40
July 0.218112E+09 94428198.97 0.123684E+09 0.271845E+09 26500907.62
August 0.227246E+09 0.125386E+09 0.101860E+09 0.278041E+09 40670111.97
September 0.175561E+09 0.104946E+09 70614949.65 0.194720E+09 73074226.44
October 0.134349E+09 85232282.71 49116661.35 0.124880E+09 0.135486E+09
November 70509489.77 49696985.59 20812504.18 45631230.40 0.234297E+09
December 12885565.09 9083336.61 3802228.48 2116323.37 0.291036E+09
           
Annual Sum or Average 0.202204E+10 0.115721E+10 0.864827E+09 0.219474E+10 0.158365E+10
Minimum of Months 12885565.09 9083336.61 3802228.48 2116323.37 24676204.40
Maximum of Months 0.292505E+09 0.182038E+09 0.129872E+09 0.332584E+09 0.291036E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.118383E+09 78818358.88 39564210.07 67403436.06 0.711009E+09
February 0.357230E+09 0.248056E+09 0.109174E+09 0.304242E+09 0.511978E+09
March 0.669545E+09 0.452995E+09 0.216550E+09 0.674917E+09 0.431750E+09
April 0.793918E+09 0.494089E+09 0.299829E+09 0.902701E+09 0.263534E+09
May 0.677312E+09 0.351568E+09 0.325744E+09 0.796319E+09 0.138858E+09
June 0.595533E+09 0.243034E+09 0.352499E+09 0.721838E+09 66976266.15
July 0.592000E+09 0.256297E+09 0.335703E+09 0.737842E+09 71928883.92
August 0.616792E+09 0.340323E+09 0.276469E+09 0.754659E+09 0.110387E+09
September 0.476509E+09 0.284845E+09 0.191663E+09 0.528510E+09 0.198338E+09
October 0.364651E+09 0.231338E+09 0.133313E+09 0.338950E+09 0.367736E+09
November 0.191377E+09 0.134888E+09 56489393.46 0.123852E+09 0.635929E+09
December 34974059.33 24654033.51 10320025.82 5744134.52 0.789932E+09
           
Annual Sum or Average 0.548822E+10 0.314091E+10 0.234732E+10 0.595698E+10 0.429836E+10
Minimum of Months 34974059.33 24654033.51 10320025.82 5744134.52 66976266.15
Maximum of Months 0.793918E+09 0.494089E+09 0.352499E+09 0.902701E+09 0.789932E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 93476878.82 62236309.34 31240569.48 55840822.26 0.533244E+09
February 0.282075E+09 0.195869E+09 86205933.23 0.245999E+09 0.385815E+09
March 0.528684E+09 0.357692E+09 0.170991E+09 0.536808E+09 0.329011E+09
April 0.626891E+09 0.390141E+09 0.236750E+09 0.705961E+09 0.202663E+09
May 0.534817E+09 0.277604E+09 0.257213E+09 0.623733E+09 0.100215E+09
June 0.470243E+09 0.191904E+09 0.278339E+09 0.569708E+09 43275611.27
July 0.467453E+09 0.202377E+09 0.265076E+09 0.582991E+09 46599677.15
August 0.487029E+09 0.268725E+09 0.218305E+09 0.593596E+09 76393024.06
September 0.376259E+09 0.224919E+09 0.151341E+09 0.416288E+09 0.148568E+09
October 0.287934E+09 0.182668E+09 0.105266E+09 0.272031E+09 0.276722E+09
November 0.151115E+09 0.106510E+09 44604980.56 0.102731E+09 0.476914E+09
December 27616108.81 19467241.87 8148866.95 5148771.83 0.592235E+09
           
Annual Sum or Average 0.433359E+10 0.248011E+10 0.185348E+10 0.471083E+10 0.321166E+10
Minimum of Months 27616108.81 19467241.87 8148866.95 5148771.83 43275611.27
Maximum of Months 0.626891E+09 0.390141E+09 0.278339E+09 0.705961E+09 0.592235E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 19232962.10 3269712.17 15963249.93 0.00 0.109919E+10
February 0.103533E+09 36059635.70 67473741.62 21089159.44 0.846229E+09
March 0.344892E+09 0.148950E+09 0.195941E+09 0.199549E+09 0.680460E+09
April 0.790929E+09 0.410659E+09 0.380270E+09 0.769803E+09 0.367218E+09
May 0.792860E+09 0.361774E+09 0.431086E+09 0.836020E+09 0.171547E+09
June 0.840418E+09 0.358839E+09 0.481579E+09 0.976239E+09 74505074.84
July 0.725411E+09 0.274115E+09 0.451296E+09 0.856093E+09 82282135.88
August 0.598536E+09 0.254509E+09 0.344027E+09 0.663146E+09 0.137161E+09
September 0.348505E+09 0.145298E+09 0.203206E+09 0.298087E+09 0.283833E+09
October 0.141175E+09 42266213.40 98908372.99 53284599.65 0.591401E+09
November 55219401.28 20239990.41 34979410.87 5804267.94 0.100502E+10
December 5057197.14 512230.40 4544966.74 0.00 0.115934E+10
           
Annual Sum or Average 0.476577E+10 0.205649E+10 0.270928E+10 0.467912E+10 0.649819E+10
Minimum of Months 5057197.14 512230.40 4544966.74 0.00 74505074.84
Maximum of Months 0.840418E+09 0.410659E+09 0.481579E+09 0.976239E+09 0.115934E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 7485397.50 0.00 7485397.50 0.00 0.591601E+09
February 29886918.80 0.00 29886918.80 0.00 0.476090E+09
March 88635339.19 15040.35 88620298.84 8389320.35 0.391877E+09
April 0.156626E+09 4468630.01 0.152157E+09 66282387.55 0.199887E+09
May 0.247451E+09 39662063.78 0.207788E+09 0.202463E+09 80922387.91
June 0.310041E+09 68787424.57 0.241253E+09 0.318401E+09 32623002.65
July 0.270880E+09 45269352.45 0.225611E+09 0.289862E+09 40151621.43
August 0.174589E+09 10464841.60 0.164124E+09 0.154158E+09 72540831.90
September 93150850.77 302442.08 92848408.69 41804877.78 0.155327E+09
October 46581866.67 0.00 46581866.67 4364832.43 0.329216E+09
November 13989674.44 0.00 13989674.44 0.00 0.555716E+09
December 2270676.37 0.00 2270676.37 0.00 0.619598E+09
           
Annual Sum or Average 0.144159E+10 0.168970E+09 0.127262E+10 0.108573E+10 0.354555E+10
Minimum of Months 2270676.37 0.00 2270676.37 0.00 32623002.65
Maximum of Months 0.310041E+09 68787424.57 0.241253E+09 0.318401E+09 0.619598E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 19232962.10 3269712.17 15963249.93 0.00 0.109870E+10
February 0.103533E+09 36059635.70 67473741.62 22100833.55 0.844967E+09
March 0.344892E+09 0.148950E+09 0.195941E+09 0.206660E+09 0.675025E+09
April 0.790929E+09 0.410659E+09 0.380270E+09 0.786334E+09 0.362011E+09
May 0.792860E+09 0.361774E+09 0.431086E+09 0.836815E+09 0.171305E+09
June 0.840418E+09 0.358839E+09 0.481579E+09 0.959180E+09 77228363.12
July 0.725411E+09 0.274115E+09 0.451296E+09 0.844789E+09 85984559.34
August 0.598536E+09 0.254509E+09 0.344027E+09 0.660799E+09 0.141564E+09
September 0.348505E+09 0.145298E+09 0.203206E+09 0.306977E+09 0.279490E+09
October 0.141175E+09 42266213.40 98908372.99 56766107.00 0.588115E+09
November 55219401.28 20239990.41 34979410.87 6095626.12 0.100441E+10
December 5057197.14 512230.40 4544966.74 0.00 0.115881E+10
           
Annual Sum or Average 0.476577E+10 0.205649E+10 0.270928E+10 0.468652E+10 0.648761E+10
Minimum of Months 5057197.14 512230.40 4544966.74 0.00 77228363.12
Maximum of Months 0.840418E+09 0.410659E+09 0.481579E+09 0.959180E+09 0.115881E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.137093E+09 91275520.48 45817293.31 79520464.71 0.794045E+09
February 0.413690E+09 0.287260E+09 0.126429E+09 0.349949E+09 0.577766E+09
March 0.775365E+09 0.524590E+09 0.250775E+09 0.767553E+09 0.495324E+09
April 0.919396E+09 0.572179E+09 0.347217E+09 0.102402E+10 0.301408E+09
May 0.784361E+09 0.407133E+09 0.377228E+09 0.911283E+09 0.147050E+09
June 0.689656E+09 0.281446E+09 0.408211E+09 0.837290E+09 62327972.47
July 0.685565E+09 0.296805E+09 0.388760E+09 0.855320E+09 67617451.01
August 0.714275E+09 0.394111E+09 0.320165E+09 0.867204E+09 0.112285E+09
September 0.551821E+09 0.329865E+09 0.221956E+09 0.600606E+09 0.224023E+09
October 0.422283E+09 0.267901E+09 0.154383E+09 0.386396E+09 0.417358E+09
November 0.221624E+09 0.156207E+09 65417484.74 0.146134E+09 0.709999E+09
December 40501673.90 28550578.47 11951095.42 7227570.70 0.879928E+09
           
Annual Sum or Average 0.635563E+10 0.363732E+10 0.271831E+10 0.683251E+10 0.478913E+10
Minimum of Months 40501673.90 28550578.47 11951095.42 7227570.70 62327972.47
Maximum of Months 0.919396E+09 0.572179E+09 0.408211E+09 0.102402E+10 0.879928E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52395798.00 0.00 52395798.00 0.00 0.426393E+10
February 0.209201E+09 0.00 0.209201E+09 0.00 0.344426E+10
March 0.620424E+09 105278.48 0.620319E+09 45419103.36 0.285317E+10
April 0.109634E+10 31279225.42 0.106506E+10 0.463676E+09 0.144606E+10
May 0.173209E+10 0.277624E+09 0.145446E+10 0.147142E+10 0.589404E+09
June 0.217020E+10 0.481494E+09 0.168871E+10 0.235094E+10 0.235799E+09
July 0.189609E+10 0.316873E+09 0.157922E+10 0.212932E+10 0.289274E+09
August 0.122207E+10 73251116.88 0.114882E+10 0.113750E+10 0.517812E+09
September 0.652031E+09 2117014.40 0.649914E+09 0.276741E+09 0.115993E+10
October 0.326061E+09 0.00 0.326061E+09 21586760.77 0.244263E+10
November 97924012.29 0.00 97924012.29 0.00 0.400274E+10
December 15894132.59 0.00 15894132.59 0.00 0.444745E+10
           
Annual Sum or Average 0.100907E+11 0.118274E+10 0.890798E+10 0.789661E+10 0.256925E+11
Minimum of Months 15894132.59 0.00 15894132.59 0.00 0.235799E+09
Maximum of Months 0.217020E+10 0.481494E+09 0.168871E+10 0.235094E+10 0.444745E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52395798.00 0.00 52395798.00 0.00 0.432257E+10
February 0.209201E+09 0.00 0.209201E+09 0.00 0.349573E+10
March 0.620424E+09 105278.48 0.620319E+09 41401029.33 0.291251E+10
April 0.109634E+10 31279225.42 0.106506E+10 0.443006E+09 0.148821E+10
May 0.173209E+10 0.277624E+09 0.145446E+10 0.143610E+10 0.606724E+09
June 0.217020E+10 0.481494E+09 0.168871E+10 0.231510E+10 0.245483E+09
July 0.189609E+10 0.316873E+09 0.157922E+10 0.209470E+10 0.301303E+09
August 0.122207E+10 73251116.88 0.114882E+10 0.110883E+10 0.537154E+09
September 0.652031E+09 2117014.40 0.649914E+09 0.260650E+09 0.120656E+10
October 0.326061E+09 0.00 0.326061E+09 18107006.94 0.250905E+10
November 97924012.29 0.00 97924012.29 0.00 0.405661E+10
December 15894132.59 0.00 15894132.59 0.00 0.450179E+10
           
Annual Sum or Average 0.100907E+11 0.118274E+10 0.890798E+10 0.771790E+10 0.261837E+11
Minimum of Months 15894132.59 0.00 15894132.59 0.00 0.245483E+09
Maximum of Months 0.217020E+10 0.481494E+09 0.168871E+10 0.231510E+10 0.450179E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 7485397.50 0.00 7485397.50 0.00 0.522023E+09
February 29886918.80 0.00 29886918.80 25057.12 0.412740E+09
March 88635339.19 15040.35 88620298.84 21730326.06 0.339225E+09
April 0.156626E+09 4468630.01 0.152157E+09 0.125206E+09 0.181187E+09
May 0.247451E+09 39662063.78 0.207788E+09 0.303394E+09 79610118.31
June 0.310041E+09 68787424.57 0.241253E+09 0.441069E+09 33562839.60
July 0.270880E+09 45269352.45 0.225611E+09 0.411702E+09 39912117.72
August 0.174589E+09 10464841.60 0.164124E+09 0.259130E+09 65714152.52
September 93150850.77 302442.08 92848408.69 94751647.14 0.127658E+09
October 46581866.67 0.00 46581866.67 15319707.01 0.273471E+09
November 13989674.44 0.00 13989674.44 0.00 0.485583E+09
December 2270676.37 0.00 2270676.37 0.00 0.548084E+09
           
Annual Sum or Average 0.144159E+10 0.168970E+09 0.127262E+10 0.167233E+10 0.310877E+10
Minimum of Months 2270676.37 0.00 2270676.37 0.00 33562839.60
Maximum of Months 0.310041E+09 68787424.57 0.241253E+09 0.441069E+09 0.548084E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 82778095.76 30658834.16 52119261.60 19061291.42 0.189743E+10
February 0.387812E+09 0.185926E+09 0.201886E+09 0.257808E+09 0.141469E+10
March 0.120429E+10 0.609801E+09 0.594493E+09 0.118956E+10 0.116658E+10
April 0.155048E+10 0.785409E+09 0.765066E+09 0.176038E+10 0.638902E+09
May 0.233329E+10 0.131716E+10 0.101613E+10 0.304763E+10 0.306703E+09
June 0.206780E+10 0.965751E+09 0.110205E+10 0.288981E+10 0.133104E+09
July 0.203515E+10 0.989670E+09 0.104548E+10 0.293411E+10 0.153627E+09
August 0.163526E+10 0.801412E+09 0.833849E+09 0.231331E+10 0.246011E+09
September 0.990497E+09 0.448062E+09 0.542436E+09 0.123415E+10 0.467165E+09
October 0.554329E+09 0.224591E+09 0.329739E+09 0.523959E+09 0.959987E+09
November 0.111184E+09 40373744.31 70810531.68 17325857.55 0.175003E+10
December 16356262.43 3872216.86 12484045.58 0.00 0.204363E+10
           
Annual Sum or Average 0.129692E+11 0.640269E+10 0.656655E+10 0.161871E+11 0.111778E+11
Minimum of Months 16356262.43 3872216.86 12484045.58 0.00 0.133104E+09
Maximum of Months 0.233329E+10 0.131716E+10 0.110205E+10 0.304763E+10 0.204363E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 93476878.82 62236309.34 31240569.48 66382000.20 0.473714E+09
February 0.282075E+09 0.195869E+09 86205933.23 0.272234E+09 0.345696E+09
March 0.528684E+09 0.357692E+09 0.170991E+09 0.586859E+09 0.300864E+09
April 0.626891E+09 0.390141E+09 0.236750E+09 0.783967E+09 0.184004E+09
May 0.534817E+09 0.277604E+09 0.257213E+09 0.724105E+09 93025136.86
June 0.470243E+09 0.191904E+09 0.278339E+09 0.683254E+09 44263990.70
July 0.467453E+09 0.202377E+09 0.265076E+09 0.699362E+09 47240875.18
August 0.487029E+09 0.268725E+09 0.218305E+09 0.697667E+09 69251695.19
September 0.376259E+09 0.224919E+09 0.151341E+09 0.486189E+09 0.126513E+09
October 0.287934E+09 0.182668E+09 0.105266E+09 0.312023E+09 0.243219E+09
November 0.151115E+09 0.106510E+09 44604980.56 0.119723E+09 0.422001E+09
December 27616108.81 19467241.87 8148866.95 7882349.61 0.523535E+09
           
Annual Sum or Average 0.433359E+10 0.248011E+10 0.185348E+10 0.543965E+10 0.287333E+10
Minimum of Months 27616108.81 19467241.87 8148866.95 7882349.61 44263990.70
Maximum of Months 0.626891E+09 0.390141E+09 0.278339E+09 0.783967E+09 0.523535E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 9479783.63 0.00 9479783.63 0.00 0.787815E+09
February 37849896.91 0.00 37849896.91 0.00 0.639034E+09
March 0.112251E+09 19047.66 0.112232E+09 7133449.82 0.530681E+09
April 0.198357E+09 5659237.96 0.192698E+09 71643878.44 0.273021E+09
May 0.313380E+09 50229501.24 0.263151E+09 0.239277E+09 0.118036E+09
June 0.392647E+09 87114932.98 0.305532E+09 0.394122E+09 49848154.53
July 0.343053E+09 57330778.54 0.285722E+09 0.354027E+09 61846111.28
August 0.221106E+09 13253061.60 0.207853E+09 0.179893E+09 0.108797E+09
September 0.117970E+09 383023.81 0.117587E+09 41391320.93 0.224739E+09
October 58992994.98 0.00 58992994.98 3144275.64 0.451900E+09
November 17717039.98 0.00 17717039.98 0.00 0.742241E+09
December 2875668.35 0.00 2875668.35 0.00 0.823831E+09
           
Annual Sum or Average 0.182568E+10 0.213990E+09 0.161169E+10 0.129063E+10 0.481179E+10
Minimum of Months 2875668.35 0.00 2875668.35 0.00 49848154.53
Maximum of Months 0.392647E+09 87114932.98 0.305532E+09 0.394122E+09 0.823831E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 8481598.33 0.00 8481598.33 0.00 0.704861E+09
February 33864446.17 0.00 33864446.17 0.00 0.571604E+09
March 0.100431E+09 17042.01 0.100414E+09 6382324.58 0.474803E+09
April 0.177471E+09 5063341.64 0.172407E+09 64100049.50 0.244273E+09
May 0.280383E+09 44940525.07 0.235442E+09 0.214082E+09 0.105607E+09
June 0.351303E+09 77942060.61 0.273361E+09 0.352623E+09 44599332.73
July 0.306931E+09 51294064.78 0.255637E+09 0.316749E+09 55333950.09
August 0.197824E+09 11857564.43 0.185966E+09 0.160951E+09 97341434.20
September 0.105548E+09 342692.86 0.105205E+09 37032971.67 0.201075E+09
October 52781256.13 0.00 52781256.13 2813195.33 0.404239E+09
November 15851502.80 0.00 15851502.80 0.00 0.664085E+09
December 2572871.37 0.00 2572871.37 0.00 0.737084E+09
           
Annual Sum or Average 0.163344E+10 0.191457E+09 0.144198E+10 0.115473E+10 0.430491E+10
Minimum of Months 2572871.37 0.00 2572871.37 0.00 44599332.73
Maximum of Months 0.351303E+09 77942060.61 0.273361E+09 0.352623E+09 0.737084E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.348977E+09 0.232347E+09 0.116630E+09 0.198391E+09 0.209104E+10
February 0.105307E+10 0.731237E+09 0.321832E+09 0.894347E+09 0.150851E+10
March 0.197373E+10 0.133537E+10 0.638362E+09 0.197674E+10 0.127871E+10
April 0.234037E+10 0.145651E+10 0.883858E+09 0.262687E+10 0.798121E+09
May 0.199663E+10 0.103638E+10 0.960253E+09 0.229647E+10 0.441848E+09
June 0.175556E+10 0.716435E+09 0.103912E+10 0.208169E+10 0.216504E+09
July 0.174514E+10 0.755533E+09 0.989609E+09 0.212859E+10 0.233055E+09
August 0.181823E+10 0.100323E+10 0.814997E+09 0.217894E+10 0.357561E+09
September 0.140469E+10 0.839689E+09 0.565000E+09 0.152898E+10 0.616521E+09
October 0.107494E+10 0.681955E+09 0.392989E+09 0.989056E+09 0.109648E+10
November 0.564156E+09 0.397632E+09 0.166524E+09 0.365467E+09 0.186670E+10
December 0.103099E+09 72677014.83 30422148.55 16996515.98 0.232414E+10
           
Annual Sum or Average 0.161786E+11 0.925900E+10 0.691960E+10 0.172825E+11 0.128292E+11
Minimum of Months 0.103099E+09 72677014.83 30422148.55 16996515.98 0.216504E+09
Maximum of Months 0.234037E+10 0.145651E+10 0.103912E+10 0.262687E+10 0.232414E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 102.91 1000.41 176.52 117.52 58.99 0.00 0.00
February 501.59 803.78 589.72 409.50 180.23 0.00 0.00
March 995.01 616.98 998.33 675.44 322.89 0.00 0.00
April 1366.06 400.60 1223.24 761.28 461.96 0.00 0.00
May 1167.56 205.82 1009.91 524.21 485.70 0.00 0.00
June 1094.30 104.39 917.57 374.46 543.11 0.00 0.00
July 1080.85 108.87 882.71 382.16 500.55 0.00 0.00
August 1104.50 167.27 919.67 507.44 412.23 0.00 0.00
September 798.53 301.64 734.19 438.88 295.31 0.00 0.00
October 502.12 523.29 543.72 344.94 198.78 0.00 0.00
November 192.57 934.34 294.87 207.83 87.04 0.00 0.00
December 9.11 1113.78 52.15 36.76 15.39 0.00 0.00
               
Annual Sum or Average 743.60 522.09 695.02 397.76 297.26 0.00 0.00
Minimum of Months 9.11 104.39 52.15 36.76 15.39 0.00 0.00
Maximum of Months 1366.06 1113.78 1223.24 761.28 543.11 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 287.42 2804.84 497.06 330.94 166.12 0.00 0.00
February 1407.24 2249.66 1660.62 1153.11 507.51 0.00 0.00
March 2798.59 1727.56 2811.24 1902.01 909.23 0.00 0.00
April 3851.83 1114.97 3444.56 2143.70 1300.86 0.00 0.00
May 3312.12 553.41 2843.85 1476.14 1367.70 0.00 0.00
June 3121.81 266.43 2583.83 1054.45 1529.37 0.00 0.00
July 3083.28 277.66 2485.64 1076.13 1409.52 0.00 0.00
August 3138.63 440.56 2589.74 1428.93 1160.81 0.00 0.00
September 2254.61 836.67 2067.42 1235.86 831.57 0.00 0.00
October 1409.52 1468.93 1531.07 971.33 559.74 0.00 0.00
November 538.18 2614.56 830.33 585.24 245.09 0.00 0.00
December 25.30 3117.90 146.85 103.52 43.33 0.00 0.00
               
Annual Sum or Average 2104.37 1452.29 1957.12 1120.06 837.06 0.00 0.00
Minimum of Months 25.30 266.43 146.85 103.52 43.33 0.00 0.00
Maximum of Months 3851.83 3117.90 3444.56 2143.70 1529.37 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 371.63 3793.08 645.71 429.91 215.80 0.00 0.00
February 1839.52 3034.08 2157.24 1497.96 659.28 0.00 0.00
March 3682.64 2328.53 3651.96 2470.82 1181.14 0.00 0.00
April 5073.12 1507.73 4474.68 2784.79 1689.89 0.00 0.00
May 4351.22 766.17 3694.32 1917.59 1776.73 0.00 0.00
June 4096.14 375.73 3356.54 1369.79 1986.74 0.00 0.00
July 4042.29 393.12 3228.99 1397.95 1831.04 0.00 0.00
August 4113.50 616.56 3364.22 1856.26 1507.96 0.00 0.00
September 2952.68 1163.15 2685.70 1605.45 1080.25 0.00 0.00
October 1842.31 2012.55 1988.95 1261.81 727.14 0.00 0.00
November 698.42 3531.89 1078.64 760.26 318.39 0.00 0.00
December 31.95 4206.53 190.76 134.47 56.29 0.00 0.00
               
Annual Sum or Average 2760.60 1972.39 2542.42 1455.03 1087.39 0.00 0.00
Minimum of Months 31.95 375.73 190.76 134.47 56.29 0.00 0.00
Maximum of Months 5073.12 4206.53 4474.68 2784.79 1986.74 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 5.47 598.31 42.08 24.46 17.62 0.00 0.00
February 73.96 476.78 159.39 95.87 63.52 0.00 0.00
March 252.30 356.81 326.16 189.16 137.00 0.00 0.00
April 563.25 213.20 547.00 308.95 238.05 0.00 0.00
May 544.88 100.42 495.70 238.72 256.98 0.00 0.00
June 598.02 45.41 505.66 212.48 293.18 0.00 0.00
July 538.78 48.42 445.36 177.90 267.46 0.00 0.00
August 469.52 79.83 405.30 195.35 209.95 0.00 0.00
September 271.62 165.30 279.62 142.83 136.79 0.00 0.00
October 101.32 306.90 160.21 83.98 76.23 0.00 0.00
November 21.19 556.88 79.60 48.90 30.70 0.00 0.00
December 0.00 656.13 12.20 7.46 4.74 0.00 0.00
               
Annual Sum or Average 287.60 299.52 288.54 143.85 144.68 0.00 0.00
Minimum of Months 0.00 45.41 12.20 7.46 4.74 0.00 0.00
Maximum of Months 598.02 656.13 547.00 308.95 293.18 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 635.32 9.98 1.22 8.75 0.00 0.00
February 4.19 544.84 55.15 14.91 40.24 0.00 0.00
March 71.46 391.64 161.86 55.62 106.24 0.00 0.00
April 324.75 213.42 365.57 160.16 205.41 0.00 0.00
May 381.54 86.74 388.41 149.88 238.53 0.00 0.00
June 491.55 37.36 443.85 164.98 278.87 0.00 0.00
July 423.07 43.96 371.97 119.24 252.73 0.00 0.00
August 301.94 76.70 288.65 98.93 189.72 0.00 0.00
September 131.16 168.01 170.39 56.17 114.22 0.00 0.00
October 19.20 341.70 70.10 15.78 54.32 0.00 0.00
November 0.83 606.18 26.70 7.81 18.89 0.00 0.00
December 0.00 668.24 2.74 0.19 2.54 0.00 0.00
               
Annual Sum or Average 179.95 316.65 196.83 70.57 126.26 0.00 0.00
Minimum of Months 0.00 37.36 2.74 0.19 2.54 0.00 0.00
Maximum of Months 491.55 668.24 443.85 164.98 278.87 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 17.83 141.78 27.91 18.59 9.33 0.00 0.00
February 84.01 113.75 93.26 64.76 28.50 0.00 0.00
March 158.90 97.83 157.88 106.82 51.06 0.00 0.00
April 209.01 77.86 193.45 120.39 73.06 0.00 0.00
May 176.75 43.31 159.71 82.90 76.81 0.00 0.00
June 164.74 23.35 145.11 59.22 85.89 0.00 0.00
July 163.09 24.27 139.59 60.44 79.16 0.00 0.00
August 167.64 35.99 145.44 80.25 65.19 0.00 0.00
September 119.59 62.40 116.11 69.41 46.70 0.00 0.00
October 77.12 89.02 85.98 54.55 31.44 0.00 0.00
November 33.55 131.16 46.63 32.87 13.76 0.00 0.00
December 1.79 158.31 8.25 5.81 2.43 0.00 0.00
               
Annual Sum or Average 114.56 83.11 109.91 62.90 47.01 0.00 0.00
Minimum of Months 1.79 23.35 8.25 5.81 2.43 0.00 0.00
Maximum of Months 209.01 158.31 193.45 120.39 85.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 181.89 2.24 0.00 2.24 0.00 0.00
February 0.00 162.51 9.88 0.00 9.88 0.00 0.00
March 2.09 120.71 26.48 0.00 26.47 0.00 0.00
April 20.95 62.06 48.35 1.38 46.97 0.00 0.00
May 63.53 23.69 73.92 11.85 62.07 0.00 0.00
June 103.68 9.41 95.70 21.23 74.47 0.00 0.00
July 90.50 11.34 80.92 13.52 67.40 0.00 0.00
August 48.54 20.81 52.15 3.13 49.03 0.00 0.00
September 12.41 49.63 28.75 0.09 28.66 0.00 0.00
October 0.97 102.71 13.92 0.00 13.92 0.00 0.00
November 0.00 177.27 4.32 0.00 4.32 0.00 0.00
December 0.00 190.26 0.68 0.00 0.68 0.00 0.00
               
Annual Sum or Average 28.73 92.31 36.57 4.29 32.29 0.00 0.00
Minimum of Months 0.00 9.41 0.68 0.00 0.68 0.00 0.00
Maximum of Months 103.68 190.26 95.70 21.23 74.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 12.08 593.43 50.35 28.96 21.39 0.00 0.00
February 119.64 472.18 196.76 119.39 77.36 0.00 0.00
March 373.14 354.40 422.22 247.39 174.83 0.00 0.00
April 543.96 202.56 540.97 302.03 238.93 0.00 0.00
May 722.50 93.10 635.28 349.55 285.74 0.00 0.00
June 693.32 39.16 580.33 260.34 319.99 0.00 0.00
July 681.09 44.18 554.47 260.32 294.15 0.00 0.00
August 573.82 75.40 487.13 249.95 237.18 0.00 0.00
September 340.29 161.18 336.24 173.21 163.03 0.00 0.00
October 165.85 305.67 210.99 110.13 100.86 0.00 0.00
November 19.90 555.06 79.75 48.88 30.87 0.00 0.00
December 0.00 654.16 13.36 7.99 5.37 0.00 0.00
               
Annual Sum or Average 355.22 295.04 343.06 180.16 162.89 0.00 0.00
Minimum of Months 0.00 39.16 13.36 7.99 5.37 0.00 0.00
Maximum of Months 722.50 654.16 635.28 349.55 319.99 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.71 623.73 18.25 5.72 12.52 0.00 0.00
February 29.07 517.27 92.51 38.43 54.08 0.00 0.00
March 181.62 375.95 257.92 113.85 144.07 0.00 0.00
April 301.66 200.11 359.54 153.24 206.30 0.00 0.00
May 569.00 89.42 527.99 260.71 267.28 0.00 0.00
June 595.91 37.50 518.52 212.85 305.68 0.00 0.00
July 569.13 44.19 481.08 201.67 279.42 0.00 0.00
August 411.85 76.58 370.47 153.52 216.95 0.00 0.00
September 197.77 162.66 227.02 86.55 140.47 0.00 0.00
October 69.06 324.40 120.88 41.93 78.95 0.00 0.00
November 0.49 605.30 26.85 7.79 19.06 0.00 0.00
December 0.00 666.09 3.90 0.72 3.18 0.00 0.00
               
Annual Sum or Average 245.29 309.21 251.35 106.88 144.47 0.00 0.00
Minimum of Months 0.00 37.50 3.90 0.72 3.18 0.00 0.00
Maximum of Months 595.91 666.09 527.99 260.71 305.68 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 15.55 747.93 65.33 40.27 25.06 0.00 0.00
February 119.77 598.76 223.48 140.31 83.17 0.00 0.00
March 312.61 453.44 399.44 231.45 167.99 0.00 0.00
April 512.30 272.27 523.88 263.84 260.04 0.00 0.00
May 528.09 116.55 506.18 205.29 300.90 0.00 0.00
June 589.76 51.27 521.74 174.31 347.43 0.00 0.00
July 561.17 60.63 477.76 160.24 317.52 0.00 0.00
August 481.20 103.06 428.11 180.65 247.46 0.00 0.00
September 299.02 211.33 313.86 150.58 163.28 0.00 0.00
October 146.32 386.95 216.45 118.19 98.26 0.00 0.00
November 33.18 697.13 110.39 71.21 39.18 0.00 0.00
December 0.11 822.72 19.34 12.60 6.74 0.00 0.00
               
Annual Sum or Average 300.76 375.77 317.38 145.58 171.80 0.00 0.00
Minimum of Months 0.11 51.27 19.34 12.60 6.74 0.00 0.00
Maximum of Months 589.76 822.72 523.88 263.84 347.43 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 5.61 594.24 42.08 24.46 17.62 0.00 0.00
February 74.79 473.66 159.39 95.87 63.52 0.00 0.00
March 253.21 355.18 326.16 189.16 137.00 0.00 0.00
April 561.66 212.17 547.00 308.95 238.05 0.00 0.00
May 542.96 99.41 495.70 238.72 256.98 0.00 0.00
June 595.65 44.66 505.66 212.48 293.18 0.00 0.00
July 536.79 47.61 445.36 177.90 267.46 0.00 0.00
August 468.18 78.69 405.30 195.35 209.95 0.00 0.00
September 272.07 163.29 279.62 142.83 136.79 0.00 0.00
October 102.23 304.89 160.21 83.98 76.23 0.00 0.00
November 21.65 551.51 79.60 48.90 30.70 0.00 0.00
December 0.00 652.04 12.20 7.46 4.74 0.00 0.00
               
Annual Sum or Average 287.13 297.28 288.54 143.85 144.68 0.00 0.00
Minimum of Months 0.00 44.66 12.20 7.46 4.74 0.00 0.00
Maximum of Months 595.65 652.04 547.00 308.95 293.18 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 631.09 9.98 1.22 8.75 0.00 0.00
February 4.32 541.26 55.15 14.91 40.24 0.00 0.00
March 71.83 389.88 161.86 55.62 106.24 0.00 0.00
April 324.39 212.23 365.57 160.16 205.41 0.00 0.00
May 380.18 86.33 388.41 149.88 238.53 0.00 0.00
June 488.02 37.51 443.85 164.98 278.87 0.00 0.00
July 420.51 43.98 371.97 119.24 252.73 0.00 0.00
August 300.67 76.33 288.65 98.93 189.72 0.00 0.00
September 132.33 165.52 170.39 56.17 114.22 0.00 0.00
October 19.77 339.44 70.10 15.78 54.32 0.00 0.00
November 0.86 600.41 26.70 7.81 18.89 0.00 0.00
December 0.00 663.98 2.74 0.19 2.54 0.00 0.00
               
Annual Sum or Average 179.37 314.49 196.83 70.57 126.26 0.00 0.00
Minimum of Months 0.00 37.51 2.74 0.19 2.54 0.00 0.00
Maximum of Months 488.02 663.98 443.85 164.98 278.87 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 29.69 296.46 51.18 34.08 17.11 0.00 0.00
February 144.65 238.83 171.00 118.74 52.26 0.00 0.00
March 286.57 184.93 289.49 195.86 93.63 0.00 0.00
April 395.07 116.28 354.71 220.75 133.96 0.00 0.00
May 340.23 54.90 292.85 152.01 140.84 0.00 0.00
June 323.03 24.05 266.07 108.58 157.49 0.00 0.00
July 319.34 25.25 255.96 110.81 145.15 0.00 0.00
August 323.78 41.92 266.68 147.14 119.54 0.00 0.00
September 231.72 86.43 212.89 127.26 85.63 0.00 0.00
October 144.26 155.82 157.66 100.02 57.64 0.00 0.00
November 56.38 273.92 85.50 60.26 25.24 0.00 0.00
December 2.70 328.53 15.12 10.66 4.46 0.00 0.00
               
Annual Sum or Average 216.66 151.86 201.54 115.34 86.20 0.00 0.00
Minimum of Months 2.70 24.05 15.12 10.66 4.46 0.00 0.00
Maximum of Months 395.07 328.53 354.71 220.75 157.49 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 1591.97 19.56 0.00 19.56 0.00 0.00
February 0.00 1423.72 86.48 0.00 86.48 0.00 0.00
March 16.96 1065.25 231.64 0.04 231.60 0.00 0.00
April 178.89 557.89 422.97 12.07 410.90 0.00 0.00
May 549.36 220.06 646.69 103.65 543.03 0.00 0.00
June 907.00 90.97 837.27 185.76 651.51 0.00 0.00
July 795.00 108.00 707.92 118.31 589.61 0.00 0.00
August 424.70 193.33 456.27 27.35 428.92 0.00 0.00
September 106.77 447.50 251.56 0.82 250.74 0.00 0.00
October 8.06 911.97 121.74 0.00 121.74 0.00 0.00
November 0.00 1544.27 37.78 0.00 37.78 0.00 0.00
December 0.00 1660.49 5.93 0.00 5.93 0.00 0.00
               
Annual Sum or Average 250.40 814.70 319.97 37.50 282.47 0.00 0.00
Minimum of Months 0.00 90.97 5.93 0.00 5.93 0.00 0.00
Maximum of Months 907.00 1660.49 837.27 185.76 651.51 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 1613.86 19.56 0.00 19.56 0.00 0.00
February 0.00 1445.00 86.48 0.00 86.48 0.00 0.00
March 15.46 1087.41 231.64 0.04 231.60 0.00 0.00
April 170.91 574.16 422.97 12.07 410.90 0.00 0.00
May 536.18 226.52 646.69 103.65 543.03 0.00 0.00
June 893.17 94.71 837.27 185.76 651.51 0.00 0.00
July 782.07 112.49 707.92 118.31 589.61 0.00 0.00
August 413.99 200.55 456.27 27.35 428.92 0.00 0.00
September 100.56 465.50 251.56 0.82 250.74 0.00 0.00
October 6.76 936.77 121.74 0.00 121.74 0.00 0.00
November 0.00 1565.05 37.78 0.00 37.78 0.00 0.00
December 0.00 1680.78 5.93 0.00 5.93 0.00 0.00
               
Annual Sum or Average 244.73 830.28 319.97 37.50 282.47 0.00 0.00
Minimum of Months 0.00 94.71 5.93 0.00 5.93 0.00 0.00
Maximum of Months 893.17 1680.78 837.27 185.76 651.51 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 14.09 1062.37 68.60 34.68 33.92 0.00 0.00
February 172.00 851.17 289.26 157.82 131.44 0.00 0.00
March 642.71 645.89 680.11 361.23 318.89 0.00 0.00
April 1020.31 377.77 900.46 455.25 445.21 0.00 0.00
May 1516.70 174.18 1163.22 610.23 552.99 0.00 0.00
June 1544.96 77.67 1098.80 473.16 625.63 0.00 0.00
July 1508.20 87.80 1035.50 461.96 573.54 0.00 0.00
August 1219.52 140.84 857.56 403.45 454.11 0.00 0.00
September 697.98 276.00 563.24 259.75 303.48 0.00 0.00
October 298.62 532.11 331.86 152.05 179.80 0.00 0.00
November 18.23 990.67 106.59 56.67 49.92 0.00 0.00
December 0.00 1160.16 17.27 8.71 8.55 0.00 0.00
               
Annual Sum or Average 724.53 529.86 594.38 287.03 307.35 0.00 0.00
Minimum of Months 0.00 77.67 17.27 8.71 8.55 0.00 0.00
Maximum of Months 1544.96 1160.16 1163.22 610.23 625.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 44.09 1308.02 137.00 86.75 50.25 0.00 0.00
February 293.49 1047.79 464.94 302.26 162.68 0.00 0.00
March 689.62 799.36 816.31 498.58 317.73 0.00 0.00
April 1055.77 497.44 1047.92 566.06 481.85 0.00 0.00
May 1003.63 225.43 967.14 422.47 544.67 0.00 0.00
June 1072.05 100.80 964.32 340.08 624.23 0.00 0.00
July 1033.32 118.92 894.24 322.64 571.60 0.00 0.00
August 932.09 201.77 835.26 383.94 451.32 0.00 0.00
September 611.19 393.19 628.17 324.23 303.93 0.00 0.00
October 328.72 686.25 443.07 254.61 188.46 0.00 0.00
November 90.72 1212.47 230.60 153.41 77.20 0.00 0.00
December 1.43 1445.60 40.53 27.13 13.39 0.00 0.00
               
Annual Sum or Average 597.61 667.95 622.71 306.46 316.25 0.00 0.00
Minimum of Months 1.43 100.80 40.53 27.13 13.39 0.00 0.00
Maximum of Months 1072.05 1445.60 1047.92 566.06 624.23 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.275631E+09 0.267949E+10 0.472780E+09 0.314774E+09 0.158006E+09 0.00 0.00
February 0.121345E+10 0.194451E+10 0.142666E+10 0.990652E+09 0.436005E+09 0.00 0.00
March 0.266503E+10 0.165253E+10 0.267393E+10 0.180911E+10 0.864824E+09 0.00 0.00
April 0.354083E+10 0.103835E+10 0.317064E+10 0.197323E+10 0.119741E+10 0.00 0.00
May 0.312720E+10 0.551265E+09 0.270495E+10 0.140405E+10 0.130090E+10 0.00 0.00
June 0.283644E+10 0.270589E+09 0.237835E+10 0.970599E+09 0.140775E+10 0.00 0.00
July 0.289496E+10 0.291596E+09 0.236424E+10 0.102357E+10 0.134067E+10 0.00 0.00
August 0.295829E+10 0.448026E+09 0.246326E+10 0.135914E+10 0.110412E+10 0.00 0.00
September 0.206980E+10 0.781848E+09 0.190301E+10 0.113758E+10 0.765436E+09 0.00 0.00
October 0.134487E+10 0.140158E+10 0.145629E+10 0.923887E+09 0.532405E+09 0.00 0.00
November 0.499149E+09 0.242182E+10 0.764297E+09 0.538697E+09 0.225599E+09 0.00 0.00
December 24395650.64 0.298314E+10 0.139675E+09 98460044.66 41214694.35 0.00 0.00
               
Annual Sum or Average 0.234500E+11 0.164648E+11 0.219181E+11 0.125437E+11 0.937435E+10 0.00 0.00
Minimum of Months 24395650.64 0.270589E+09 0.139675E+09 98460044.66 41214694.35 0.00 0.00
Maximum of Months 0.354083E+10 0.298314E+10 0.317064E+10 0.197323E+10 0.140775E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.769828E+09 0.751249E+10 0.133132E+10 0.886384E+09 0.444935E+09 0.00 0.00
February 0.340440E+10 0.544237E+10 0.401737E+10 0.278961E+10 0.122776E+10 0.00 0.00
March 0.749574E+10 0.462710E+10 0.752962E+10 0.509434E+10 0.243529E+10 0.00 0.00
April 0.998394E+10 0.288999E+10 0.892830E+10 0.555648E+10 0.337183E+10 0.00 0.00
May 0.887119E+10 0.148225E+10 0.761696E+10 0.395370E+10 0.366326E+10 0.00 0.00
June 0.809173E+10 0.690589E+09 0.669728E+10 0.273314E+10 0.396414E+10 0.00 0.00
July 0.825827E+10 0.743680E+09 0.665755E+10 0.288230E+10 0.377525E+10 0.00 0.00
August 0.840650E+10 0.117999E+10 0.693636E+10 0.382724E+10 0.310912E+10 0.00 0.00
September 0.584396E+10 0.216866E+10 0.535876E+10 0.320335E+10 0.215542E+10 0.00 0.00
October 0.377525E+10 0.393440E+10 0.410082E+10 0.260160E+10 0.149922E+10 0.00 0.00
November 0.139497E+10 0.677694E+10 0.215221E+10 0.151694E+10 0.635273E+09 0.00 0.00
December 67758619.82 0.835098E+10 0.393315E+09 0.277257E+09 0.116058E+09 0.00 0.00
               
Annual Sum or Average 0.663635E+11 0.457994E+11 0.617199E+11 0.353223E+11 0.263975E+11 0.00 0.00
Minimum of Months 67758619.82 0.690589E+09 0.393315E+09 0.277257E+09 0.116058E+09 0.00 0.00
Maximum of Months 0.998394E+10 0.835098E+10 0.892830E+10 0.555648E+10 0.396414E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.995372E+09 0.101594E+11 0.172946E+10 0.115146E+10 0.577995E+09 0.00 0.00
February 0.445016E+10 0.734005E+10 0.521879E+10 0.362386E+10 0.159493E+10 0.00 0.00
March 0.986360E+10 0.623674E+10 0.978141E+10 0.661783E+10 0.316358E+10 0.00 0.00
April 0.131495E+11 0.390802E+10 0.115984E+11 0.721818E+10 0.438019E+10 0.00 0.00
May 0.116543E+11 0.205212E+10 0.989487E+10 0.513608E+10 0.475878E+10 0.00 0.00
June 0.106172E+11 0.973892E+09 0.870015E+10 0.355051E+10 0.514964E+10 0.00 0.00
July 0.108269E+11 0.105294E+10 0.864853E+10 0.374427E+10 0.490426E+10 0.00 0.00
August 0.110176E+11 0.165138E+10 0.901073E+10 0.497180E+10 0.403893E+10 0.00 0.00
September 0.765336E+10 0.301488E+10 0.696134E+10 0.416133E+10 0.280001E+10 0.00 0.00
October 0.493445E+10 0.539040E+10 0.532720E+10 0.337963E+10 0.194757E+10 0.00 0.00
November 0.181032E+10 0.915465E+10 0.279584E+10 0.197059E+10 0.825256E+09 0.00 0.00
December 85571057.55 0.112668E+11 0.510938E+09 0.360173E+09 0.150766E+09 0.00 0.00
               
Annual Sum or Average 0.870583E+11 0.622012E+11 0.801776E+11 0.458857E+11 0.342919E+11 0.00 0.00
Minimum of Months 85571057.55 0.973892E+09 0.510938E+09 0.360173E+09 0.150766E+09 0.00 0.00
Maximum of Months 0.131495E+11 0.112668E+11 0.115984E+11 0.721818E+10 0.514964E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 14647972.17 0.160251E+10 0.112710E+09 65506021.51 47203819.41 0.00 0.00
February 0.178935E+09 0.115342E+10 0.385608E+09 0.231929E+09 0.153680E+09 0.00 0.00
March 0.675760E+09 0.955677E+09 0.873575E+09 0.506643E+09 0.366933E+09 0.00 0.00
April 0.145993E+10 0.552626E+09 0.141782E+10 0.800800E+09 0.617020E+09 0.00 0.00
May 0.145941E+10 0.268965E+09 0.132768E+10 0.639378E+09 0.688299E+09 0.00 0.00
June 0.155007E+10 0.117696E+09 0.131066E+10 0.550743E+09 0.759918E+09 0.00 0.00
July 0.144306E+10 0.129699E+09 0.119286E+10 0.476491E+09 0.716372E+09 0.00 0.00
August 0.125755E+10 0.213819E+09 0.108557E+10 0.523234E+09 0.562332E+09 0.00 0.00
September 0.704047E+09 0.428467E+09 0.724764E+09 0.370217E+09 0.354547E+09 0.00 0.00
October 0.271363E+09 0.822011E+09 0.429109E+09 0.224934E+09 0.204174E+09 0.00 0.00
November 54927268.53 0.144343E+10 0.206334E+09 0.126750E+09 79584391.43 0.00 0.00
December 0.00 0.175737E+10 32673305.95 19979472.27 12693833.69 0.00 0.00
               
Annual Sum or Average 0.906971E+10 0.944569E+10 0.909936E+10 0.453660E+10 0.456276E+10 0.00 0.00
Minimum of Months 0.00 0.117696E+09 32673305.95 19979472.27 12693833.69 0.00 0.00
Maximum of Months 0.155007E+10 0.175737E+10 0.141782E+10 0.800800E+09 0.759918E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.170163E+10 26718359.59 3269712.17 23448647.42 0.00 0.00
February 10147194.45 0.131807E+10 0.133420E+09 36059635.70 97360660.42 0.00 0.00
March 0.191402E+09 0.104896E+10 0.433527E+09 0.148966E+09 0.284562E+09 0.00 0.00
April 0.841752E+09 0.553195E+09 0.947555E+09 0.415128E+09 0.532427E+09 0.00 0.00
May 0.102192E+10 0.232312E+09 0.104031E+10 0.401436E+09 0.638875E+09 0.00 0.00
June 0.127409E+10 96824501.94 0.115046E+10 0.427626E+09 0.722833E+09 0.00 0.00
July 0.113316E+10 0.117754E+09 0.996291E+09 0.319384E+09 0.676907E+09 0.00 0.00
August 0.808722E+09 0.205425E+09 0.773125E+09 0.264974E+09 0.508151E+09 0.00 0.00
September 0.339972E+09 0.435476E+09 0.441656E+09 0.145601E+09 0.296055E+09 0.00 0.00
October 51435956.66 0.915207E+09 0.187756E+09 42266213.40 0.145490E+09 0.00 0.00
November 2162781.86 0.157123E+10 69209075.72 20239990.41 48969085.31 0.00 0.00
December 0.00 0.178981E+10 7327873.51 512230.40 6815643.11 0.00 0.00
               
Annual Sum or Average 0.567477E+10 0.998590E+10 0.620735E+10 0.222546E+10 0.398189E+10 0.00 0.00
Minimum of Months 0.00 96824501.94 7327873.51 512230.40 6815643.11 0.00 0.00
Maximum of Months 0.127409E+10 0.178981E+10 0.115046E+10 0.427626E+09 0.722833E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 47747523.40 0.379756E+09 74766633.98 49779147.74 24987486.24 0.00 0.00
February 0.203225E+09 0.275196E+09 0.225615E+09 0.156664E+09 68951034.08 0.00 0.00
March 0.425589E+09 0.262023E+09 0.422863E+09 0.286097E+09 0.136766E+09 0.00 0.00
April 0.541751E+09 0.201817E+09 0.501413E+09 0.312051E+09 0.189362E+09 0.00 0.00
May 0.473397E+09 0.116002E+09 0.427769E+09 0.222039E+09 0.205730E+09 0.00 0.00
June 0.427008E+09 60516053.44 0.376120E+09 0.153493E+09 0.222627E+09 0.00 0.00
July 0.436808E+09 64995240.45 0.373888E+09 0.161869E+09 0.212019E+09 0.00 0.00
August 0.449019E+09 96399448.82 0.389546E+09 0.214937E+09 0.174609E+09 0.00 0.00
September 0.309980E+09 0.161753E+09 0.300948E+09 0.179899E+09 0.121048E+09 0.00 0.00
October 0.206563E+09 0.238438E+09 0.230302E+09 0.146106E+09 84196004.15 0.00 0.00
November 86965820.71 0.339965E+09 0.120868E+09 85190798.59 35676889.28 0.00 0.00
December 4781178.45 0.424016E+09 22088494.24 15570696.90 6517797.34 0.00 0.00
               
Annual Sum or Average 0.361284E+10 0.262088E+10 0.346619E+10 0.198370E+10 0.148249E+10 0.00 0.00
Minimum of Months 4781178.45 60516053.44 22088494.24 15570696.90 6517797.34 0.00 0.00
Maximum of Months 0.541751E+09 0.424016E+09 0.501413E+09 0.312051E+09 0.222627E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.487170E+09 5989111.78 0.00 5989111.78 0.00 0.00
February 0.00 0.393152E+09 23912704.39 0.00 23912704.39 0.00 0.00
March 5595453.47 0.323321E+09 70917670.65 12033.88 70905636.77 0.00 0.00
April 54308737.50 0.160851E+09 0.125317E+09 3575377.89 0.121742E+09 0.00 0.00
May 0.170152E+09 63442162.58 0.197987E+09 31733856.97 0.166253E+09 0.00 0.00
June 0.268736E+09 24389931.96 0.248066E+09 55037234.19 0.193028E+09 0.00 0.00
July 0.242408E+09 30369191.96 0.216733E+09 36220282.52 0.180513E+09 0.00 0.00
August 0.130005E+09 55729906.41 0.139690E+09 8372983.02 0.131317E+09 0.00 0.00
September 32158376.38 0.128640E+09 74530558.75 241985.74 74288573.01 0.00 0.00
October 2604877.21 0.275091E+09 37270433.09 0.00 37270433.09 0.00 0.00
November 0.00 0.459478E+09 11193223.08 0.00 11193223.08 0.00 0.00
December 0.00 0.509602E+09 1816781.89 0.00 1816781.89 0.00 0.00
               
Annual Sum or Average 0.905967E+09 0.291124E+10 0.115342E+10 0.135194E+09 0.101823E+10 0.00 0.00
Minimum of Months 0.00 24389931.96 1816781.89 0.00 1816781.89 0.00 0.00
Maximum of Months 0.268736E+09 0.509602E+09 0.248066E+09 55037234.19 0.193028E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 32352024.27 0.158945E+10 0.134869E+09 77566815.08 57302050.97 0.00 0.00
February 0.289444E+09 0.114229E+10 0.475995E+09 0.288838E+09 0.187156E+09 0.00 0.00
March 0.999429E+09 0.949221E+09 0.113087E+10 0.662614E+09 0.468259E+09 0.00 0.00
April 0.140994E+10 0.525025E+09 0.140218E+10 0.782874E+09 0.619310E+09 0.00 0.00
May 0.193514E+10 0.249348E+09 0.170155E+10 0.936232E+09 0.765315E+09 0.00 0.00
June 0.179710E+10 0.101492E+09 0.150422E+10 0.674814E+09 0.829404E+09 0.00 0.00
July 0.182422E+10 0.118338E+09 0.148510E+10 0.697247E+09 0.787854E+09 0.00 0.00
August 0.153691E+10 0.201957E+09 0.130472E+10 0.669459E+09 0.635259E+09 0.00 0.00
September 0.882043E+09 0.417780E+09 0.871543E+09 0.448966E+09 0.422578E+09 0.00 0.00
October 0.444221E+09 0.818707E+09 0.565118E+09 0.294972E+09 0.270147E+09 0.00 0.00
November 51571616.30 0.143871E+10 0.206711E+09 0.126698E+09 80012760.80 0.00 0.00
December 0.00 0.175210E+10 35794820.82 21403487.79 14391333.03 0.00 0.00
               
Annual Sum or Average 0.112024E+11 0.930441E+10 0.108187E+11 0.568168E+10 0.513699E+10 0.00 0.00
Minimum of Months 0.00 0.101492E+09 35794820.82 21403487.79 14391333.03 0.00 0.00
Maximum of Months 0.193514E+10 0.175210E+10 0.170155E+10 0.936232E+09 0.829404E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 1898272.60 0.167059E+10 48877384.73 15330505.74 33546878.99 0.00 0.00
February 70332384.55 0.125138E+10 0.223807E+09 92969590.80 0.130837E+09 0.00 0.00
March 0.486448E+09 0.100693E+10 0.690825E+09 0.304937E+09 0.385888E+09 0.00 0.00
April 0.781895E+09 0.518675E+09 0.931919E+09 0.397201E+09 0.534718E+09 0.00 0.00
May 0.152400E+10 0.239493E+09 0.141418E+10 0.698290E+09 0.715890E+09 0.00 0.00
June 0.154461E+10 97201310.87 0.134402E+10 0.551697E+09 0.792319E+09 0.00 0.00
July 0.152437E+10 0.118368E+09 0.128853E+10 0.540140E+09 0.748389E+09 0.00 0.00
August 0.110310E+10 0.205100E+09 0.992277E+09 0.411199E+09 0.581078E+09 0.00 0.00
September 0.512616E+09 0.421614E+09 0.588435E+09 0.224349E+09 0.364086E+09 0.00 0.00
October 0.184978E+09 0.868862E+09 0.323766E+09 0.112303E+09 0.211463E+09 0.00 0.00
November 1270184.85 0.156894E+10 69585760.46 20188305.78 49397454.68 0.00 0.00
December 0.00 0.178406E+10 10449388.38 1936245.93 8513142.45 0.00 0.00
               
Annual Sum or Average 0.773552E+10 0.975121E+10 0.792667E+10 0.337054E+10 0.455612E+10 0.00 0.00
Minimum of Months 0.00 97201310.87 10449388.38 1936245.93 8513142.45 0.00 0.00
Maximum of Months 0.154461E+10 0.178406E+10 0.141418E+10 0.698290E+09 0.792319E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 41644246.73 0.200327E+10 0.174973E+09 0.107858E+09 67115358.30 0.00 0.00
February 0.289748E+09 0.144853E+10 0.540648E+09 0.339447E+09 0.201201E+09 0.00 0.00
March 0.837294E+09 0.121449E+10 0.106986E+10 0.619919E+09 0.449939E+09 0.00 0.00
April 0.132789E+10 0.705725E+09 0.135790E+10 0.683873E+09 0.674030E+09 0.00 0.00
May 0.141444E+10 0.312154E+09 0.135576E+10 0.549843E+09 0.805918E+09 0.00 0.00
June 0.152865E+10 0.132889E+09 0.135234E+10 0.451805E+09 0.900535E+09 0.00 0.00
July 0.150305E+10 0.162391E+09 0.127963E+10 0.429191E+09 0.850437E+09 0.00 0.00
August 0.128885E+10 0.276036E+09 0.114665E+10 0.483847E+09 0.662805E+09 0.00 0.00
September 0.775056E+09 0.547777E+09 0.813528E+09 0.390316E+09 0.423212E+09 0.00 0.00
October 0.391908E+09 0.103640E+10 0.579740E+09 0.316570E+09 0.263170E+09 0.00 0.00
November 85992146.61 0.180696E+10 0.286135E+09 0.184585E+09 0.101550E+09 0.00 0.00
December 283828.78 0.220358E+10 51795383.19 33737370.12 18058013.07 0.00 0.00
               
Annual Sum or Average 0.948480E+10 0.118502E+11 0.100090E+11 0.459099E+10 0.541797E+10 0.00 0.00
Minimum of Months 283828.78 0.132889E+09 51795383.19 33737370.12 18058013.07 0.00 0.00
Maximum of Months 0.152865E+10 0.220358E+10 0.135790E+10 0.683873E+09 0.900535E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 15012448.75 0.159161E+10 0.112710E+09 65506021.51 47203819.41 0.00 0.00
February 0.180925E+09 0.114588E+10 0.385608E+09 0.231929E+09 0.153680E+09 0.00 0.00
March 0.678192E+09 0.951305E+09 0.873575E+09 0.506643E+09 0.366933E+09 0.00 0.00
April 0.145583E+10 0.549945E+09 0.141782E+10 0.800800E+09 0.617020E+09 0.00 0.00
May 0.145426E+10 0.266271E+09 0.132768E+10 0.639378E+09 0.688299E+09 0.00 0.00
June 0.154394E+10 0.115771E+09 0.131066E+10 0.550743E+09 0.759918E+09 0.00 0.00
July 0.143773E+10 0.127524E+09 0.119286E+10 0.476491E+09 0.716372E+09 0.00 0.00
August 0.125396E+10 0.210772E+09 0.108557E+10 0.523234E+09 0.562332E+09 0.00 0.00
September 0.705212E+09 0.423239E+09 0.724764E+09 0.370217E+09 0.354547E+09 0.00 0.00
October 0.273805E+09 0.816612E+09 0.429109E+09 0.224934E+09 0.204174E+09 0.00 0.00
November 56123651.49 0.142953E+10 0.206334E+09 0.126750E+09 79584391.43 0.00 0.00
December 0.00 0.174643E+10 32673305.95 19979472.27 12693833.69 0.00 0.00
               
Annual Sum or Average 0.905498E+10 0.937488E+10 0.909936E+10 0.453660E+10 0.456276E+10 0.00 0.00
Minimum of Months 0.00 0.115771E+09 32673305.95 19979472.27 12693833.69 0.00 0.00
Maximum of Months 0.154394E+10 0.174643E+10 0.141782E+10 0.800800E+09 0.759918E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.169030E+10 26718359.59 3269712.17 23448647.42 0.00 0.00
February 10459592.78 0.130941E+10 0.133420E+09 36059635.70 97360660.42 0.00 0.00
March 0.192390E+09 0.104424E+10 0.433527E+09 0.148966E+09 0.284562E+09 0.00 0.00
April 0.840821E+09 0.550102E+09 0.947555E+09 0.415128E+09 0.532427E+09 0.00 0.00
May 0.101826E+10 0.231213E+09 0.104031E+10 0.401436E+09 0.638875E+09 0.00 0.00
June 0.126495E+10 97215469.41 0.115046E+10 0.427626E+09 0.722833E+09 0.00 0.00
July 0.112630E+10 0.117789E+09 0.996291E+09 0.319384E+09 0.676907E+09 0.00 0.00
August 0.805307E+09 0.204455E+09 0.773125E+09 0.264974E+09 0.508151E+09 0.00 0.00
September 0.342993E+09 0.429028E+09 0.441656E+09 0.145601E+09 0.296055E+09 0.00 0.00
October 52962647.49 0.909163E+09 0.187756E+09 42266213.40 0.145490E+09 0.00 0.00
November 2230903.84 0.155626E+10 69209075.72 20239990.41 48969085.31 0.00 0.00
December 0.00 0.177841E+10 7327873.51 512230.40 6815643.11 0.00 0.00
               
Annual Sum or Average 0.565668E+10 0.991760E+10 0.620735E+10 0.222546E+10 0.398189E+10 0.00 0.00
Minimum of Months 0.00 97215469.41 7327873.51 512230.40 6815643.11 0.00 0.00
Maximum of Months 0.126495E+10 0.177841E+10 0.115046E+10 0.427626E+09 0.722833E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 79520464.71 0.794045E+09 0.137093E+09 91275520.48 45817293.31 0.00 0.00
February 0.349949E+09 0.577766E+09 0.413690E+09 0.287260E+09 0.126429E+09 0.00 0.00
March 0.767553E+09 0.495324E+09 0.775365E+09 0.524590E+09 0.250775E+09 0.00 0.00
April 0.102402E+10 0.301408E+09 0.919396E+09 0.572179E+09 0.347217E+09 0.00 0.00
May 0.911283E+09 0.147050E+09 0.784361E+09 0.407133E+09 0.377228E+09 0.00 0.00
June 0.837290E+09 62327972.47 0.689656E+09 0.281446E+09 0.408211E+09 0.00 0.00
July 0.855320E+09 67617451.01 0.685565E+09 0.296805E+09 0.388760E+09 0.00 0.00
August 0.867204E+09 0.112285E+09 0.714275E+09 0.394111E+09 0.320165E+09 0.00 0.00
September 0.600606E+09 0.224023E+09 0.551821E+09 0.329865E+09 0.221956E+09 0.00 0.00
October 0.386396E+09 0.417358E+09 0.422283E+09 0.267901E+09 0.154383E+09 0.00 0.00
November 0.146134E+09 0.709999E+09 0.221624E+09 0.156207E+09 65417484.74 0.00 0.00
December 7227570.70 0.879928E+09 40501673.90 28550578.47 11951095.42 0.00 0.00
               
Annual Sum or Average 0.683251E+10 0.478913E+10 0.635563E+10 0.363732E+10 0.271831E+10 0.00 0.00
Minimum of Months 7227570.70 62327972.47 40501673.90 28550578.47 11951095.42 0.00 0.00
Maximum of Months 0.102402E+10 0.879928E+09 0.919396E+09 0.572179E+09 0.408211E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.426393E+10 52395798.00 0.00 52395798.00 0.00 0.00
February 0.00 0.344426E+10 0.209201E+09 0.00 0.209201E+09 0.00 0.00
March 45419103.36 0.285317E+10 0.620424E+09 105278.48 0.620319E+09 0.00 0.00
April 0.463676E+09 0.144606E+10 0.109634E+10 31279225.42 0.106506E+10 0.00 0.00
May 0.147142E+10 0.589404E+09 0.173209E+10 0.277624E+09 0.145446E+10 0.00 0.00
June 0.235094E+10 0.235799E+09 0.217020E+10 0.481494E+09 0.168871E+10 0.00 0.00
July 0.212932E+10 0.289274E+09 0.189609E+10 0.316873E+09 0.157922E+10 0.00 0.00
August 0.113750E+10 0.517812E+09 0.122207E+10 73251116.88 0.114882E+10 0.00 0.00
September 0.276741E+09 0.115993E+10 0.652031E+09 2117014.40 0.649914E+09 0.00 0.00
October 21586760.77 0.244263E+10 0.326061E+09 0.00 0.326061E+09 0.00 0.00
November 0.00 0.400274E+10 97924012.29 0.00 97924012.29 0.00 0.00
December 0.00 0.444745E+10 15894132.59 0.00 15894132.59 0.00 0.00
               
Annual Sum or Average 0.789661E+10 0.256925E+11 0.100907E+11 0.118274E+10 0.890798E+10 0.00 0.00
Minimum of Months 0.00 0.235799E+09 15894132.59 0.00 15894132.59 0.00 0.00
Maximum of Months 0.235094E+10 0.444745E+10 0.217020E+10 0.481494E+09 0.168871E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.432257E+10 52395798.00 0.00 52395798.00 0.00 0.00
February 0.00 0.349573E+10 0.209201E+09 0.00 0.209201E+09 0.00 0.00
March 41401029.33 0.291251E+10 0.620424E+09 105278.48 0.620319E+09 0.00 0.00
April 0.443006E+09 0.148821E+10 0.109634E+10 31279225.42 0.106506E+10 0.00 0.00
May 0.143610E+10 0.606724E+09 0.173209E+10 0.277624E+09 0.145446E+10 0.00 0.00
June 0.231510E+10 0.245483E+09 0.217020E+10 0.481494E+09 0.168871E+10 0.00 0.00
July 0.209470E+10 0.301303E+09 0.189609E+10 0.316873E+09 0.157922E+10 0.00 0.00
August 0.110883E+10 0.537154E+09 0.122207E+10 73251116.88 0.114882E+10 0.00 0.00
September 0.260650E+09 0.120656E+10 0.652031E+09 2117014.40 0.649914E+09 0.00 0.00
October 18107006.94 0.250905E+10 0.326061E+09 0.00 0.326061E+09 0.00 0.00
November 0.00 0.405661E+10 97924012.29 0.00 97924012.29 0.00 0.00
December 0.00 0.450179E+10 15894132.59 0.00 15894132.59 0.00 0.00
               
Annual Sum or Average 0.771790E+10 0.261837E+11 0.100907E+11 0.118274E+10 0.890798E+10 0.00 0.00
Minimum of Months 0.00 0.245483E+09 15894132.59 0.00 15894132.59 0.00 0.00
Maximum of Months 0.231510E+10 0.450179E+10 0.217020E+10 0.481494E+09 0.168871E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 37737953.02 0.284546E+10 0.183740E+09 92895143.50 90845228.58 0.00 0.00
February 0.416094E+09 0.205915E+10 0.699774E+09 0.381795E+09 0.317979E+09 0.00 0.00
March 0.172143E+10 0.172995E+10 0.182161E+10 0.967508E+09 0.854105E+09 0.00 0.00
April 0.264463E+10 0.979178E+09 0.233399E+10 0.118002E+10 0.115397E+10 0.00 0.00
May 0.406232E+10 0.466531E+09 0.311556E+10 0.163443E+10 0.148113E+10 0.00 0.00
June 0.400452E+10 0.201323E+09 0.284809E+10 0.122644E+10 0.162164E+10 0.00 0.00
July 0.403956E+10 0.235170E+09 0.277348E+10 0.123732E+10 0.153617E+10 0.00 0.00
August 0.326636E+10 0.377224E+09 0.229688E+10 0.108060E+10 0.121628E+10 0.00 0.00
September 0.180915E+10 0.715402E+09 0.145991E+10 0.673283E+09 0.786625E+09 0.00 0.00
October 0.799832E+09 0.142521E+10 0.888845E+09 0.407259E+09 0.481586E+09 0.00 0.00
November 47257584.40 0.256782E+10 0.276289E+09 0.146883E+09 0.129405E+09 0.00 0.00
December 0.00 0.310736E+10 46243047.61 23339458.72 22903588.89 0.00 0.00
               
Annual Sum or Average 0.228489E+11 0.167098E+11 0.187444E+11 0.905177E+10 0.969265E+10 0.00 0.00
Minimum of Months 0.00 0.201323E+09 46243047.61 23339458.72 22903588.89 0.00 0.00
Maximum of Months 0.406232E+10 0.310736E+10 0.311556E+10 0.163443E+10 0.162164E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.118083E+09 0.350341E+10 0.366938E+09 0.232347E+09 0.134592E+09 0.00 0.00
February 0.710013E+09 0.253481E+10 0.112478E+10 0.731237E+09 0.393547E+09 0.00 0.00
March 0.184707E+10 0.214101E+10 0.218642E+10 0.133541E+10 0.851008E+09 0.00 0.00
April 0.273656E+10 0.128936E+10 0.271620E+10 0.146724E+10 0.124896E+10 0.00 0.00
May 0.268812E+10 0.603784E+09 0.259040E+10 0.113155E+10 0.145885E+10 0.00 0.00
June 0.277875E+10 0.261262E+09 0.249951E+10 0.881492E+09 0.161802E+10 0.00 0.00
July 0.276764E+10 0.318505E+09 0.239513E+10 0.864158E+09 0.153097E+10 0.00 0.00
August 0.249651E+10 0.540425E+09 0.223716E+10 0.102834E+10 0.120882E+10 0.00 0.00
September 0.158421E+10 0.101915E+10 0.162821E+10 0.840415E+09 0.787792E+09 0.00 0.00
October 0.880445E+09 0.183805E+10 0.118672E+10 0.681955E+09 0.504763E+09 0.00 0.00
November 0.235156E+09 0.314272E+10 0.597725E+09 0.397632E+09 0.200092E+09 0.00 0.00
December 3832976.99 0.387189E+10 0.108548E+09 72677014.83 35870688.26 0.00 0.00
               
Annual Sum or Average 0.188464E+11 0.210644E+11 0.196377E+11 0.966444E+10 0.997327E+10 0.00 0.00
Minimum of Months 3832976.99 0.261262E+09 0.108548E+09 72677014.83 35870688.26 0.00 0.00
Maximum of Months 0.277875E+10 0.387189E+10 0.271620E+10 0.146724E+10 0.161802E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -17.6 -17.9 -19.9 1.62 -32.2 4.20 17.57 0.00
February -15.4 -16.0 -18.9 1.58 -31.2 17.68 68.90 0.00
March -10.3 -11.6 -17.1 2.46 -25.4 47.11 147.56 0.00
April 0.73 -2.7 -8.8 3.74 -14.2 75.81 230.75 0.00
May 10.60 5.25 -1.5 3.99 -2.1 92.54 252.99 0.00
June 15.96 10.88 6.41 3.45 5.66 116.77 222.76 0.00
July 16.86 12.85 9.90 2.85 7.58 107.92 197.90 0.00
August 14.24 10.70 7.59 2.94 4.33 81.01 176.65 0.00
September 6.72 4.45 1.76 2.11 -4.1 51.38 110.92 0.00
October -3.1 -4.4 -7.1 2.79 -14.3 26.50 62.95 0.00
November -17.6 -18.1 -20.3 0.70 -32.8 8.03 31.72 0.00
December -19.3 -19.6 -21.9 1.25 -33.6 1.27 5.23 0.00
                 
Annual Sum or Average -1.4 -3.8 -7.4 2.46 -14.3 52.69 127.40 0.00
Minimum of Months -19.3 -19.6 -21.9 0.70 -33.6 1.27 5.23 0.00
Maximum of Months 16.86 12.85 9.90 3.99 7.58 116.77 252.99 0.00



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -1.1 21-JAN-20:00 -2.7 -5.6 0.00 -9.0 0.00 0.00
February 2.80 08-FEB-15:09 -0.7 -6.5 2.68 -7.9 21.67 32.33
March 6.70 20-MAR-14:09 2.60 -3.5 1.37 -7.5 138.33 487.67
April 15.60 22-APR-13:00 7.03 -3.3 4.10 -0.8 117.50 760.50
May 22.20 31-MAY-15:00 10.79 -1.1 3.10 7.75 143.50 516.50
June 28.30 30-JUN-14:00 17.30 10.60 6.20 17.57 223.50 277.50
July 30.00 29-JUL-16:19 18.34 11.70 4.67 18.88 163.67 322.83
August 25.60 11-AUG-15:00 14.77 6.70 6.20 12.22 99.50 604.00
September 17.20 07-SEP-15:00 8.91 0.00 1.50 2.64 77.00 480.50
October 13.90 01-OCT-14:00 8.01 1.70 2.60 1.58 78.50 227.50
November -3.9 18-NOV-03:00 -5.6 -8.9 1.50 -12.4 0.00 0.00
December 1.70 24-DEC-11:00 -0.1 -2.8 2.60 -8.8 13.50 31.50
                 
Annual Sum or Average                
Minimum of Months -3.9   -5.6 -8.9 0.00 -12.4 0.00 0.00
Maximum of Months 30.00   18.34 11.70 6.20 18.88 223.50 760.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -38.3 12-JAN-05:00 -38.4 -40.4 0.00 -60.9 0.00 0.00
February -36.1 27-FEB-04:00 -36.2 -39.4 0.00 -58.7 0.00 0.00
March -28.9 01-MAR-00:10 -29.2 -34.0 0.65 -51.0 0.00 0.00
April -21.7 03-APR-05:00 -22.3 -27.2 2.60 -42.7 0.00 0.00
May 0.00 27-MAY-03:00 -1.1 -2.8 6.20 -7.1 29.00 14.00
June 3.30 02-JUN-03:00 2.38 1.10 1.50 -11.2 45.50 266.00
July 7.20 31-JUL-03:49 6.67 6.10 2.18 -7.6 0.00 0.00
August -1.7 31-AUG-05:00 -2.9 -5.0 2.60 -18.6 25.00 538.50
September -5.6 29-SEP-06:00 -6.1 -7.2 2.60 -21.6 0.00 0.00
October -20.6 22-OCT-05:00 -20.8 -22.2 2.60 -40.2 0.00 0.00
November -30.0 29-NOV-09:00 -30.2 -33.3 0.00 -51.8 0.00 0.00
December -33.9 15-DEC-07:00 -34.0 -37.8 0.00 -56.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -38.3   -38.4 -40.4 0.00 -60.9 0.00 0.00
Maximum of Months 7.20   6.67 6.10 6.20 -7.1 45.50 538.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -2.7 21-JAN-20:00 -1.1 -5.6 0.00 -9.0 0.00 0.00
February 1.24 09-FEB-01:00 2.80 -1.1 8.80 -4.1 0.00 0.00
March 2.65 20-MAR-13:00 6.70 -3.3 0.00 -7.6 139.00 515.00
April 7.03 22-APR-13:00 15.60 -3.3 4.10 -0.8 117.50 760.50
May 10.97 31-MAY-17:00 21.70 0.00 2.60 11.07 73.50 187.00
June 18.33 30-JUN-11:00 25.60 14.40 1.50 15.21 221.00 616.00
July 18.36 29-JUL-17:19 29.07 12.23 3.10 19.29 141.00 225.33
August 16.14 04-AUG-19:00 21.70 12.80 3.10 14.28 25.50 28.50
September 10.82 01-SEP-15:00 15.60 6.70 2.60 4.31 145.50 176.00
October 8.01 01-OCT-14:00 13.90 1.70 2.60 1.58 78.50 227.50
November -5.6 18-NOV-03:00 -3.9 -8.9 1.50 -12.4 0.00 0.00
December -0.1 24-DEC-11:00 1.70 -2.8 2.60 -8.8 13.50 31.50
                 
Annual Sum or Average                
Minimum of Months -5.6   -3.9 -8.9 0.00 -12.4 0.00 0.00
Maximum of Months 18.36   29.07 14.40 8.80 19.29 221.00 760.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -4.4 06-JAN-19:00 -1.7 -2.7 2.60 -12.4 0.00 0.00
February -0.6 09-FEB-00:00 1.70 0.78 3.60 -5.0 0.00 0.00
March 0.00 21-MAR-15:00 1.10 0.62 2.10 -5.5 70.50 4.00
April 0.00 30-APR-07:00 3.30 1.91 2.60 -8.3 198.00 170.00
May 6.10 16-MAY-19:00 8.90 7.49 5.20 3.69 16.00 15.00
June 15.60 30-JUN-17:00 18.90 16.75 3.60 12.22 99.50 223.00
July 17.80 03-JUL-14:00 19.40 18.27 1.50 10.11 223.00 401.50
August 15.00 12-AUG-22:00 16.10 15.38 0.00 12.79 0.00 0.00
September 8.90 04-SEP-11:00 10.00 9.41 2.60 5.33 238.50 0.50
October 5.60 02-OCT-11:09 7.30 6.41 4.95 0.30 123.67 16.00
November -8.3 18-NOV-04:00 -5.0 -6.1 1.50 -13.4 0.00 0.00
December -2.8 24-DEC-09:00 1.10 -0.5 3.10 -6.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -8.3   -5.0 -6.1 0.00 -13.4 0.00 0.00
Maximum of Months 17.80   19.40 18.27 5.20 12.79 238.50 401.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 0.00 1.10 0.00
February 18.00 13.00 16.00 0.00 5.89 0.00
March 18.00 13.00 16.00 0.00 18.25 0.00
April 18.00 13.00 16.00 0.00 35.02 0.00
May 18.00 13.00 16.00 0.44 43.39 0.00
June 18.00 13.00 16.00 2.62 46.67 0.00
July 18.00 13.00 16.00 4.74 42.09 0.00
August 18.00 13.00 16.00 6.08 32.30 0.00
September 18.00 13.00 16.00 6.25 18.21 0.00
October 18.00 13.00 16.00 5.21 8.04 0.00
November 18.00 13.00 16.00 3.27 2.12 0.00
December 18.00 13.00 16.00 0.94 0.28 0.00
             
Annual Sum or Average 18.00 13.00 16.00 2.48 21.19 0.00
Minimum of Months 18.00 13.00 16.00 0.00 0.28 0.00
Maximum of Months 18.00 13.00 16.00 6.25 46.67 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770429E+10 -0.754277E+10 0.00 0.00 744.00 0.00 -161519206.9 81.21 0.00 0.00
February 0.696181E+10 -0.681597E+10 0.00 0.00 672.00 0.00 -145841884.6 81.21 0.00 0.00
March 0.770288E+10 -0.754146E+10 0.00 0.00 744.00 0.00 -161422803.2 81.21 0.00 0.00
April 0.746480E+10 -0.730859E+10 0.00 0.00 720.00 0.00 -156207525.4 81.21 0.00 0.00
May 0.770421E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161414473.7 81.21 0.00 0.00
June 0.745674E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -156206303.3 81.21 0.00 0.00
July 0.771226E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -161411933.5 81.21 0.00 0.00
August 0.770422E+10 -0.754281E+10 0.00 0.00 744.00 0.00 -161412947.0 81.21 0.00 0.00
September 0.746614E+10 -0.730994E+10 0.00 0.00 720.00 0.00 -156206838.2 81.21 0.00 0.00
October 0.770285E+10 -0.754144E+10 0.00 0.00 744.00 0.00 -161414149.2 81.21 0.00 0.00
November 0.744866E+10 -0.729243E+10 0.00 0.00 720.00 0.00 -156232325.3 81.21 0.00 0.00
December 0.771231E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -161461200.4 81.21 0.00 0.00
                     
Annual Sum or Average 0.907412E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.190075E+10 81.21 0.00 0.00
Minimum of Months 0.696181E+10 -0.755085E+10 0.00 0.00 672.00 0.00 -161519206.9 81.21 0.00 0.00
Maximum of Months 0.771231E+10 -0.681597E+10 0.00 0.00 744.00 0.00 -145841884.6 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.129588E+12 -0.127854E+12 0.00 0.00 744.00 0.00 -0.173372E+10 79.61 0.00 0.00
February 0.117057E+12 -0.115477E+12 0.00 0.00 672.00 0.00 -0.158068E+10 79.61 0.00 0.00
March 0.129601E+12 -0.127849E+12 0.00 0.00 744.00 0.00 -0.175285E+10 79.61 0.00 0.00
April 0.125416E+12 -0.123726E+12 0.00 0.00 720.00 0.00 -0.169049E+10 79.61 0.00 0.00
May 0.129531E+12 -0.127784E+12 0.00 0.00 744.00 0.00 -0.174767E+10 79.72 0.00 0.00
June 0.125046E+12 -0.123346E+12 0.00 0.00 720.00 0.00 -0.170038E+10 80.30 0.00 0.00
July 0.128899E+12 -0.127142E+12 0.00 0.00 744.00 0.00 -0.175655E+10 80.85 0.00 0.00
August 0.128691E+12 -0.126944E+12 0.00 0.00 744.00 0.00 -0.174758E+10 81.20 0.00 0.00
September 0.124510E+12 -0.122827E+12 0.00 0.00 720.00 0.00 -0.168286E+10 81.25 0.00 0.00
October 0.128809E+12 -0.127079E+12 0.00 0.00 744.00 0.00 -0.173023E+10 80.97 0.00 0.00
November 0.124931E+12 -0.123262E+12 0.00 0.00 720.00 0.00 -0.166823E+10 80.46 0.00 0.00
December 0.129442E+12 -0.127718E+12 0.00 0.00 744.00 0.00 -0.172458E+10 79.85 0.00 0.00
                     
Annual Sum or Average 0.152152E+13 -0.150101E+13 0.00 0.00 8760.00 0.00 -0.205158E+11 80.26 0.00 0.00
Minimum of Months 0.117057E+12 -0.127854E+12 0.00 0.00 672.00 0.00 -0.175655E+10 79.61 0.00 0.00
Maximum of Months 0.129601E+12 -0.115477E+12 0.00 0.00 744.00 0.00 -0.158068E+10 81.25 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.877390E+11 -0.861972E+11 0.00 0.00 744.00 0.00 -0.154177E+10 58.99 0.00 0.00
February 0.792838E+11 -0.778708E+11 0.00 0.00 672.00 0.00 -0.141301E+10 58.99 0.00 0.00
March 0.878429E+11 -0.862747E+11 0.00 0.00 744.00 0.00 -0.156827E+10 58.99 0.00 0.00
April 0.849544E+11 -0.834448E+11 0.00 0.00 720.00 0.00 -0.150964E+10 58.99 0.00 0.00
May 0.871491E+11 -0.855929E+11 0.00 0.00 744.00 0.00 -0.155624E+10 58.99 0.00 0.00
June 0.812773E+11 -0.797819E+11 0.00 0.00 720.00 0.00 -0.149545E+10 58.99 0.00 0.00
July 0.807876E+11 -0.792663E+11 0.00 0.00 744.00 0.00 -0.152132E+10 58.99 0.00 0.00
August 0.788778E+11 -0.773836E+11 0.00 0.00 744.00 0.00 -0.149420E+10 58.98 0.00 0.00
September 0.760422E+11 -0.746095E+11 0.00 0.00 720.00 0.00 -0.143268E+10 58.98 0.00 0.00
October 0.800508E+11 -0.785710E+11 0.00 0.00 744.00 0.00 -0.147972E+10 58.99 0.00 0.00
November 0.802340E+11 -0.787899E+11 0.00 0.00 720.00 0.00 -0.144409E+10 58.99 0.00 0.00
December 0.863375E+11 -0.848187E+11 0.00 0.00 744.00 0.00 -0.151880E+10 58.99 0.00 0.00
                     
Annual Sum or Average 0.990576E+12 -0.972601E+12 0.00 0.00 8760.00 0.00 -0.179752E+11 58.99 0.00 0.00
Minimum of Months 0.760422E+11 -0.862747E+11 0.00 0.00 672.00 0.00 -0.156827E+10 58.98 0.00 0.00
Maximum of Months 0.878429E+11 -0.746095E+11 0.00 0.00 744.00 0.00 -0.141301E+10 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.90 0.86 10-JAN-10:00 574.83 26.35 72.17 74.33 408.93 27.92 72.67 43.00
February 205.83 0.87 0.86 01-FEB-11:50 2146.87 35.17 190.33 182.00 1724.43 36.18 191.33 154.83
March 329.50 0.87 0.86 01-MAR-08:39 5075.51 33.29 283.33 307.33 2725.07 31.18 283.33 272.33
April 421.83 0.87 0.86 01-APR-07:49 7136.28 30.35 272.83 386.17 787.27 21.92 305.67 321.00
May 545.00 0.88 0.86 01-MAY-05:49 3204.18 21.47 177.00 457.50 581.02 20.58 325.17 361.67
June 583.50 0.88 0.86 01-JUN-05:40 1417.82 18.34 156.50 481.33 555.06 20.17 311.33 371.50
July 562.83 0.88 0.86 01-JUL-05:10 1759.90 19.00 151.67 478.50 565.76 20.28 314.83 366.50
August 467.17 0.88 0.86 01-AUG-06:10 4901.94 25.99 236.00 409.33 627.27 20.86 271.67 330.00
September 356.33 0.87 0.86 01-SEP-06:40 4159.93 30.91 277.50 323.83 1125.69 23.34 221.17 266.67
October 265.50 0.87 0.86 01-OCT-07:49 2258.87 32.89 241.17 238.83 1774.34 33.88 244.50 209.00
November 135.83 0.88 0.86 01-NOV-09:50 845.09 32.53 117.50 126.50 617.82 33.80 117.67 91.00
December 71.17 0.94 0.86 05-DEC-11:20 136.87 5.67 0.00 11.33 81.03 8.76 0.00 0.83
                         
Annual Sum or Average 4053.17 0.88     3268.50 25.58 2176.00 3477.00 948.22 23.85 2659.33 2788.33
Minimum of Months 71.17 0.87 0.86   136.87 5.67 0.00 11.33 81.03 8.76 0.00 0.83
Maximum of Months 583.50 0.94 0.86   7136.28 35.17 283.33 481.33 2725.07 36.18 325.17 371.50



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.37 0.22 03-JAN-11:50 675.72 26.83 72.50 86.00 508.21 28.37 72.67 61.17
February 205.83 0.28 0.22 01-FEB-11:20 2418.17 35.29 190.33 190.17 1994.94 36.29 192.33 174.67
March 329.50 0.26 0.22 01-MAR-08:30 5482.07 33.48 286.50 313.67 3132.52 31.22 276.50 295.50
April 421.83 0.27 0.22 01-APR-07:19 7562.54 30.76 288.67 401.83 1211.96 21.95 300.83 362.00
May 545.00 0.29 0.22 01-MAY-04:00 3502.88 22.00 205.83 479.33 878.57 20.84 336.50 427.83
June 583.50 0.30 0.22 01-JUN-04:49 1670.72 18.92 158.00 512.33 806.92 20.58 342.67 443.83
July 562.83 0.29 0.22 01-JUL-04:30 2019.32 19.58 175.17 505.50 824.49 20.66 326.33 433.67
August 467.17 0.28 0.22 01-AUG-04:00 5213.60 26.54 261.50 429.50 938.32 21.13 283.33 383.33
September 356.33 0.28 0.22 01-SEP-06:10 4454.49 31.18 281.83 336.17 1417.69 23.63 234.83 300.17
October 265.50 0.27 0.22 01-OCT-07:40 2498.81 33.02 242.17 248.33 2012.33 33.99 246.00 227.67
November 135.83 0.29 0.22 01-NOV-09:30 994.65 32.77 117.50 137.50 766.86 34.01 117.67 112.17
December 71.17 0.60 0.22 04-DEC-11:09 154.59 7.11 0.00 23.83 97.57 10.14 0.00 7.83
                         
Annual Sum or Average 4053.17 0.29     3557.85 26.02 2280.00 3664.17 1236.53 24.12 2729.67 3229.83
Minimum of Months 71.17 0.26 0.22   154.59 7.11 0.00 23.83 97.57 10.14 0.00 7.83
Maximum of Months 583.50 0.60 0.22   7562.54 35.29 288.67 512.33 3132.52 36.29 342.67 443.83



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.84 0.66 31-JAN-11:30 119.83 7.97 0.00 12.17 57.96 11.51 0.00 0.00
February 205.83 0.71 0.60 05-FEB-12:20 264.91 12.35 0.00 139.67 126.49 15.90 0.00 17.33
March 329.50 0.64 0.60 01-MAR-09:30 471.58 15.38 0.00 289.17 221.65 18.78 3.00 186.83
April 421.83 0.62 0.60 01-APR-07:40 596.33 17.55 10.17 407.33 296.58 20.89 72.83 346.17
May 545.00 0.62 0.60 01-MAY-04:49 751.80 19.62 89.00 505.00 362.25 23.20 213.67 463.17
June 583.50 0.62 0.60 01-JUN-03:30 937.57 21.18 149.00 546.33 441.02 23.50 287.67 502.83
July 562.83 0.62 0.60 01-JUL-03:30 846.81 20.42 125.33 536.00 381.38 22.73 225.17 473.17
August 467.17 0.63 0.60 01-AUG-04:40 635.34 17.84 35.00 435.33 302.90 21.44 103.00 356.50
September 356.33 0.65 0.60 01-SEP-05:00 462.55 15.27 0.00 316.67 210.54 18.54 5.33 189.00
October 265.50 0.68 0.60 01-OCT-07:00 330.00 13.35 0.00 211.50 144.48 16.69 0.00 22.17
November 135.83 0.79 0.60 06-NOV-12:30 162.37 9.90 0.00 46.00 76.57 13.70 0.00 0.00
December 71.17 0.94 0.82 04-DEC-11:30 44.09 3.23 0.00 0.00 22.01 6.32 0.00 0.00
                         
Annual Sum or Average 4053.17 0.65     612.45 17.10 408.50 3445.17 287.86 20.24 910.67 2557.17
Minimum of Months 71.17 0.62 0.60   44.09 3.23 0.00 0.00 22.01 6.32 0.00 0.00
Maximum of Months 583.50 0.94 0.82   937.57 21.18 149.00 546.33 441.02 23.50 287.67 502.83



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.84 0.66 31-JAN-11:30 119.83 7.97 0.00 12.17 57.96 11.51 0.00 0.00
February 205.83 0.71 0.60 05-FEB-12:20 264.91 12.35 0.00 139.67 126.49 15.90 0.00 17.33
March 329.50 0.64 0.60 01-MAR-09:30 471.58 15.38 0.00 289.17 221.65 18.78 3.00 186.83
April 421.83 0.62 0.60 01-APR-07:40 596.33 17.55 10.17 407.33 296.58 20.89 73.00 346.17
May 545.00 0.62 0.60 01-MAY-04:49 751.80 19.62 89.00 505.00 362.25 23.20 213.67 463.17
June 583.50 0.62 0.60 01-JUN-03:30 937.57 21.18 149.00 546.33 441.02 23.50 287.67 502.83
July 562.83 0.62 0.60 01-JUL-03:30 846.81 20.42 125.33 536.00 381.38 22.73 225.17 473.17
August 467.17 0.63 0.60 01-AUG-04:40 635.34 17.84 35.00 435.33 302.90 21.44 103.00 356.50
September 356.33 0.65 0.60 01-SEP-05:00 462.55 15.27 0.00 316.67 210.54 18.54 5.33 189.00
October 265.50 0.68 0.60 01-OCT-07:00 330.00 13.35 0.00 211.50 144.48 16.69 0.00 22.17
November 135.83 0.79 0.60 06-NOV-12:30 162.37 9.90 0.00 46.00 76.57 13.70 0.00 0.00
December 71.17 0.94 0.82 04-DEC-11:30 44.09 3.23 0.00 0.00 22.01 6.32 0.00 0.00
                         
Annual Sum or Average 4053.17 0.65     612.45 17.10 408.50 3445.17 287.86 20.24 910.83 2557.17
Minimum of Months 71.17 0.62 0.60   44.09 3.23 0.00 0.00 22.01 6.32 0.00 0.00
Maximum of Months 583.50 0.94 0.82   937.57 21.18 149.00 546.33 441.02 23.50 287.67 502.83



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.276081E+12 373210.10 12-JAN-21:00 0.00 0.00 0.00 0.00 0.00
February 0.242711E+12 356814.75 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.127665E+12 345790.96 01-MAR-07:30 0.00 0.00 0.00 0.00 0.00
April 0.632566E+11 109446.71 10-APR-22:40 0.00 0.00 0.00 0.00 0.00
May 0.406960E+11 95656.33 27-MAY-07:00 0.00 0.00 0.00 0.00 0.00
June 0.287538E+10 64215.61 02-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 0.130801E+10 28101.20 31-JUL-03:00 0.00 0.00 0.00 0.00 0.00
August 0.110795E+11 103116.66 31-AUG-04:10 0.00 0.00 0.00 0.00 0.00
September 0.733214E+11 104685.95 29-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.711826E+11 109118.75 14-OCT-22:20 0.00 0.00 0.00 0.00 0.00
November 0.260753E+12 352420.76 30-NOV-21:00 0.00 0.00 0.00 0.00 0.00
December 0.342364E+12 359739.73 15-DEC-07:52 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.151329E+13     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.130801E+10 28101.20   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.342364E+12 373210.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.530355E+09 6792.49 12-JAN-10:00 0.00 0.00 0.00 0.00 0.00
February 0.384526E+09 6471.68 27-FEB-09:10 0.00 0.00 0.00 0.00 0.00
March 0.122939E+09 2514.03 01-MAR-11:40 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.103782E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.530355E+09 6792.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.581441E+10 4560.49 12-JAN-06:35 0.00 0.00 0.00 0.00 0.00
February 0.357954E+10 4429.27 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.197105E+10 4183.05 01-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 0.359434E+09 1559.51 03-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 15526340.28 458.73 28-MAY-03:00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 1002054.07 166.49 30-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.241917E+09 1016.10 30-SEP-06:57 0.00 0.00 0.00 0.00 0.00
October 0.176255E+10 2176.05 30-OCT-08:30 0.00 0.00 0.00 0.00 0.00
November 0.504439E+10 4214.13 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.657227E+10 4390.20 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.253621E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.657227E+10 4560.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.138529E+10 1546.88 12-JAN-06:35 0.00 0.00 0.00 0.00 0.00
February 0.858508E+09 1503.51 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.394894E+09 1079.22 01-MAR-08:07 0.00 0.00 0.00 0.00 0.00
April 29317657.62 529.41 03-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 10219450.03 274.49 25-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.239576E+09 671.70 29-OCT-15:00 0.00 0.00 0.00 0.00 0.00
November 0.110728E+10 1432.28 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.152808E+10 1490.62 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.555316E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.152808E+10 1546.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.173018E+10 2067.60 12-JAN-06:35 0.00 0.00 0.00 0.00 0.00
February 0.111966E+10 2009.11 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.436866E+09 1507.48 01-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 11852877.53 301.70 03-APR-09:30 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 95018495.31 504.19 31-OCT-09:53 0.00 0.00 0.00 0.00 0.00
November 0.131358E+10 1720.25 30-NOV-10:53 0.00 0.00 0.00 0.00 0.00
December 0.195592E+10 1991.69 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.666307E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.195592E+10 2067.60   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.299126E+10 1662.92 12-JAN-06:35 0.00 0.00 0.00 0.00 0.00
February 0.245883E+10 1615.74 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.209444E+10 1527.07 01-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 0.732290E+09 961.28 03-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 23991729.75 320.06 27-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 910174.10 202.57 31-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.231109E+09 583.96 30-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.134752E+10 1049.82 27-OCT-09:10 0.00 0.00 0.00 0.00 0.00
November 0.277347E+10 1538.25 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.318442E+10 1601.67 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.158382E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.318442E+10 1662.92   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.132778E+11 12035.94 12-JAN-06:35 0.00 0.00 0.00 0.00 0.00
February 0.784396E+10 11698.17 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.353267E+10 10343.61 01-MAR-07:20 0.00 0.00 0.00 0.00 0.00
April 0.748477E+09 5620.89 03-APR-08:08 0.00 0.00 0.00 0.00 0.00
May 76710763.91 3185.62 27-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 44896117.20 1921.73 27-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 30185571.01 2995.09 05-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 78834890.33 2674.43 07-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 0.949468E+09 4681.58 27-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.375947E+10 7719.18 30-OCT-08:40 0.00 0.00 0.00 0.00 0.00
November 0.113941E+11 11143.45 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.149128E+11 11597.77 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.566494E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 30185571.01 1921.73   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.149128E+11 12035.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.173344E+11 29386.87 12-JAN-06:35 0.00 0.00 0.00 0.00 0.00
February 0.847825E+10 27945.09 27-FEB-09:10 0.00 0.00 0.00 0.00 0.00
March 0.225701E+10 18472.17 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.148626E+09 6455.25 04-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 20475331.01 2912.25 27-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.179811E+10 11212.96 29-OCT-15:00 0.00 0.00 0.00 0.00 0.00
November 0.126249E+11 27212.48 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.185143E+11 28319.53 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.611761E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.185143E+11 29386.87   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.213043E+11 13221.94 12-JAN-06:35 0.00 0.00 0.00 0.00 0.00
February 0.148666E+11 12847.15 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.895259E+10 11818.23 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.143036E+10 6263.28 03-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.101788E+10 4598.25 27-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.828138E+10 8846.03 30-OCT-08:30 0.00 0.00 0.00 0.00 0.00
November 0.190750E+11 12231.62 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.231428E+11 12735.39 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.980710E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.231428E+11 13221.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.115680E+11 8667.71 12-JAN-06:35 0.00 0.00 0.00 0.00 0.00
February 0.780043E+10 8422.13 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.434270E+10 7960.60 01-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 0.628384E+09 3582.33 03-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.113185E+09 1480.85 30-SEP-06:55 0.00 0.00 0.00 0.00 0.00
October 0.304574E+10 4258.46 27-OCT-08:15 0.00 0.00 0.00 0.00 0.00
November 0.106005E+11 8018.97 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.129478E+11 8349.01 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.510468E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.129478E+11 8667.71   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.623401E+10 14119.65 12-JAN-06:35 0.00 0.00 0.00 0.00 0.00
February 0.397823E+10 13550.90 27-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.216717E+10 9408.07 01-MAR-09:03 0.00 0.00 0.00 0.00 0.00
April 0.424603E+09 5115.49 03-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 19653608.25 2685.72 02-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 318558.12 530.93 02-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 1304222.49 811.33 31-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 19125783.75 3364.40 31-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.148582E+09 4343.79 28-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.133177E+10 5657.80 30-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.479534E+10 13078.44 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.582636E+10 13608.68 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.249465E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 318558.12 530.93   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.623401E+10 14119.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.454455E+10 14243.02 12-JAN-06:35 0.00 0.00 0.00 0.00 0.00
February 0.246566E+10 13546.63 27-FEB-09:10 0.00 0.00 0.00 0.00 0.00
March 0.958061E+09 8022.29 01-MAR-09:03 0.00 0.00 0.00 0.00 0.00
April 88176139.38 3430.51 03-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 323537.72 476.58 02-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 3096685.33 2514.32 31-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 7351548.96 2394.41 28-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.420131E+09 3841.75 30-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.309800E+10 12100.71 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.397340E+10 13652.60 15-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.155588E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.454455E+10 14243.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 7134034.86 1285.92 12-JAN-04:00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 7134034.86     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 7134034.86 1285.92   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.275460E+11 42369.95 12-JAN-07:50 0.00 0.00 0.00 0.00 0.00
February 0.243633E+11 41625.35 27-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.141195E+11 39115.13 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.211243E+10 9202.18 03-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 9958.87 0.62 14-MAY-15:40 0.00 0.00 0.00 0.00 0.00
June 25530.76 0.63 28-JUN-23:40 0.00 0.00 0.00 0.00 0.00
July 30044.83 0.64 13-JUL-23:50 0.00 0.00 0.00 0.00 0.00
August 2765664.03 497.09 31-AUG-06:00 0.00 0.00 0.00 0.00 0.00
September 0.118221E+09 2133.03 29-SEP-08:61 0.00 0.00 0.00 0.00 0.00
October 0.417806E+10 9436.78 27-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.266023E+11 39496.77 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.329465E+11 40833.59 15-DEC-07:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.131989E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 9958.87 0.62   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.329465E+11 42369.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.123620E+11 8805.26 22-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.903707E+10 8806.33 09-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.606276E+10 8804.25 10-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 0.150197E+10 8803.48 05-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 0.123359E+09 5131.86 01-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 10819188.38 4764.30 08-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 13403439.01 4877.46 06-JUL-08:03 0.00 0.00 0.00 0.00 0.00
August 61912437.55 5429.39 19-AUG-08:03 0.00 0.00 0.00 0.00 0.00
September 0.113468E+10 8738.30 28-SEP-08:61 0.00 0.00 0.00 0.00 0.00
October 0.510992E+10 8806.47 20-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.112556E+11 8803.93 02-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.134376E+11 8805.58 24-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.601110E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 10819188.38 4764.30   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.134376E+11 8806.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.126773E+11 8562.87 22-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.100999E+11 8564.02 09-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.761930E+10 8562.38 20-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.215148E+10 8560.98 05-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 0.159385E+09 4700.51 01-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 6943824.78 4392.28 06-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 9658459.22 4871.98 05-JUL-18:04 0.00 0.00 0.00 0.00 0.00
August 83377725.73 4977.87 14-AUG-18:04 0.00 0.00 0.00 0.00 0.00
September 0.151811E+10 8558.99 29-SEP-08:61 0.00 0.00 0.00 0.00 0.00
October 0.598699E+10 8564.16 20-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.118096E+11 8561.45 02-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.135499E+11 8563.21 24-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.656719E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 6943824.78 4392.28   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135499E+11 8564.16   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.387947E+11 42780.72 12-JAN-16:00 0.00 0.00 0.00 0.00 0.00
February 0.137650E+11 25045.30 27-FEB-16:00 0.00 0.00 0.00 0.00 0.00
March 0.122738E+10 22341.83 01-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.979265E+09 12661.95 30-OCT-04:00 0.00 0.00 0.00 0.00 0.00
November 0.302639E+11 28404.57 30-NOV-16:00 0.00 0.00 0.00 0.00 0.00
December 0.484757E+11 39578.74 15-DEC-15:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.133506E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.484757E+11 42780.72   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.581511E+11 47353.45 12-JAN-14:00 0.00 0.00 0.00 0.00 0.00
February 0.468199E+11 47020.00 03-FEB-16:12 0.00 0.00 0.00 0.00 0.00
March 0.340691E+11 47010.29 04-MAR-16:12 0.00 0.00 0.00 0.00 0.00
April 0.870046E+10 46346.05 02-APR-15:11 0.00 0.00 0.00 0.00 0.00
May 89930104.63 39030.38 26-MAY-15:14 0.00 0.00 0.00 0.00 0.00
June 10833959.68 22655.38 01-JUN-18:46 0.00 0.00 0.00 0.00 0.00
July 12607704.01 19597.30 31-JUL-21:56 0.00 0.00 0.00 0.00 0.00
August 97832494.84 22539.83 31-AUG-08:03 0.00 0.00 0.00 0.00 0.00
September 0.237003E+10 45470.92 30-SEP-15:11 0.00 0.00 0.00 0.00 0.00
October 0.200204E+11 47021.51 29-OCT-15:12 0.00 0.00 0.00 0.00 0.00
November 0.541283E+11 47022.57 18-NOV-16:12 0.00 0.00 0.00 0.00 0.00
December 0.638348E+11 47030.68 23-DEC-16:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.288305E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 10833959.68 19597.30   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.638348E+11 47353.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.122430E+11 8666.43 22-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.860333E+10 8667.53 09-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.515749E+10 8665.04 09-MAR-19:01 0.00 0.00 0.00 0.00 0.00
April 0.147574E+10 8664.05 04-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 83081806.44 4944.25 27-MAY-18:03 0.00 0.00 0.00 0.00 0.00
June 5145527.16 4627.74 24-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 8406528.47 4867.67 04-JUL-18:04 0.00 0.00 0.00 0.00 0.00
August 47741083.31 4775.48 14-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 0.938244E+09 8508.52 27-SEP-15:11 0.00 0.00 0.00 0.00 0.00
October 0.461289E+10 8667.67 20-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.112293E+11 8665.05 02-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.134172E+11 8666.75 24-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.578215E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5145527.16 4627.74   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.134172E+11 8667.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.125499E+11 8431.11 22-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.961334E+10 8432.29 09-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.651030E+10 8429.65 09-MAR-19:01 0.00 0.00 0.00 0.00 0.00
April 0.214612E+10 8428.60 04-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 0.117271E+09 5146.57 28-MAY-20:43 0.00 0.00 0.00 0.00 0.00
June 4316124.73 4667.66 24-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 5641907.39 4588.90 26-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 62050829.30 4901.69 14-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 0.124851E+10 8352.77 27-SEP-15:11 0.00 0.00 0.00 0.00 0.00
October 0.539894E+10 8432.42 20-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.117945E+11 8429.65 02-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.135326E+11 8431.46 24-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.629834E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 4316124.73 4588.90   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135326E+11 8432.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.399833E+10 2593.56 22-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.299501E+10 2594.02 09-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.208538E+10 2593.71 22-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.586231E+09 2593.45 07-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 84459318.80 1828.79 27-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 5469407.09 1224.88 25-JUN-18:03 0.00 0.00 0.00 0.00 0.00
July 6894374.18 1076.25 12-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 41061117.23 2517.72 30-AUG-08:62 0.00 0.00 0.00 0.00 0.00
September 0.477699E+09 2593.70 28-SEP-08:61 0.00 0.00 0.00 0.00 0.00
October 0.179569E+10 2594.06 20-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.368421E+10 2593.10 02-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.432767E+10 2593.72 24-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.200881E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5469407.09 1076.25   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.432767E+10 2594.06   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.409387E+10 2505.46 22-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.329370E+10 2505.94 09-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.256018E+10 2505.62 22-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.810101E+09 2505.48 06-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 98520552.26 2044.85 27-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 3452832.71 1153.11 28-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 4999706.70 1143.94 04-JUL-18:04 0.00 0.00 0.00 0.00 0.00
August 47704242.26 2444.35 31-AUG-08:62 0.00 0.00 0.00 0.00 0.00
September 0.618892E+09 2506.03 27-SEP-08:61 0.00 0.00 0.00 0.00 0.00
October 0.205885E+10 2506.14 03-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.384940E+10 2504.97 02-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.436445E+10 2505.63 24-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.218041E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3452832.71 1143.94   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.436445E+10 2506.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.167088E+11 13179.78 07-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.104084E+11 13179.29 07-FEB-19:01 0.00 0.00 0.00 0.00 0.00
March 0.596717E+10 13178.96 09-MAR-19:01 0.00 0.00 0.00 0.00 0.00
April 0.132860E+10 13176.27 03-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 0.130525E+09 8380.65 01-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 13700106.18 6326.89 25-JUN-15:14 0.00 0.00 0.00 0.00 0.00
July 15481483.66 5883.92 06-JUL-08:03 0.00 0.00 0.00 0.00 0.00
August 58482608.76 6689.15 20-AUG-08:03 0.00 0.00 0.00 0.00 0.00
September 0.860328E+09 12853.93 28-SEP-08:61 0.00 0.00 0.00 0.00 0.00
October 0.523497E+10 13180.21 24-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.147051E+11 13178.40 02-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.189992E+11 13180.39 24-DEC-19:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.744308E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 13700106.18 5883.92   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189992E+11 13180.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 75168325.83 75168325.83 3903.82 20-JAN-06:10 3903.82 0.00
February 0.00 0.00 85185202.38 85185202.38 3956.80 07-FEB-06:10 3956.80 0.00
March 0.00 0.00 0.156560E+09 0.156560E+09 4012.86 21-MAR-05:10 4012.86 0.00
April 0.00 0.00 0.736317E+09 0.736317E+09 22928.05 22-APR-16:10 22928.05 0.00
May 0.00 0.00 0.354295E+11 0.354295E+11 157352.54 31-MAY-17:50 157352.54 0.00
June 0.00 0.00 0.131458E+12 0.130430E+12 226960.36 29-JUN-20:00 209096.86 0.25
July 0.00 0.00 0.166461E+12 0.164044E+12 251880.33 29-JUL-17:15 219473.22 0.60
August 0.00 0.00 0.980209E+11 0.979070E+11 205466.83 11-AUG-19:20 205466.83 0.39
September 0.00 0.00 0.479464E+10 0.479464E+10 61221.95 02-SEP-17:50 61221.95 0.00
October 0.00 0.00 0.209132E+09 0.209132E+09 4092.39 17-OCT-05:10 4092.39 0.00
November 0.00 0.00 51529095.41 51529095.41 3846.30 02-NOV-05:10 3846.30 0.00
December 0.00 0.00 54200966.70 54200966.70 3890.95 26-DEC-06:10 3890.95 0.00
                 
Annual Sum or Average 0.00 0.00 0.437532E+12 0.433972E+12       0.11
Minimum of Months 0.00 0.00 51529095.41 51529095.41 3846.30   3846.30 0.00
Maximum of Months 0.00 0.00 0.166461E+12 0.164044E+12 251880.33   219473.22 0.60



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 2616969.90 2616969.90 594.90 22-APR-14:20 594.90 0.00
May 0.00 0.00 0.174643E+10 0.174643E+10 14983.87 31-MAY-15:55 14983.87 0.00
June 0.00 0.00 0.831331E+10 0.823859E+10 19533.33 30-JUN-12:20 17636.60 0.18
July 0.00 0.00 0.101207E+11 0.994242E+10 19236.07 29-JUL-18:02 18188.68 0.42
August 0.00 0.00 0.609004E+10 0.605039E+10 17533.36 11-AUG-18:02 17533.36 0.27
September 0.00 0.00 0.172724E+09 0.172724E+09 4990.84 07-SEP-16:00 4990.84 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.264459E+11 0.261532E+11       0.07
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.101207E+11 0.994242E+10 19533.33   18188.68 0.42



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 239058.60 239058.60 1241.63 15-FEB-16:14 1241.63 0.00
March 0.00 0.00 0.121475E+09 0.121475E+09 16500.21 22-MAR-15:11 16500.21 0.00
April 0.00 0.00 0.234628E+10 0.233699E+10 16741.34 30-APR-15:11 16741.34 0.01
May 0.00 0.00 0.455038E+10 0.419884E+10 16743.06 20-MAY-18:01 16743.06 0.15
June 0.00 0.00 0.738088E+10 0.482457E+10 16743.29 12-JUN-18:02 16743.29 0.80
July 0.00 0.00 0.744636E+10 0.407821E+10 16410.33 17-JUL-18:01 14161.22 0.90
August 0.00 0.00 0.527977E+10 0.290887E+10 16728.75 30-AUG-18:01 16728.75 0.78
September 0.00 0.00 0.103972E+10 0.653860E+09 16741.06 07-SEP-15:11 16741.06 0.21
October 0.00 0.00 35399910.38 31397051.30 14597.76 13-OCT-15:12 14597.76 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.282005E+11 0.191544E+11       0.24
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.744636E+10 0.482457E+10 16743.29   16743.29 0.90



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 35837.71 35837.71 249.08 08-FEB-19:06 249.08 0.00
March 0.00 0.00 2391357.31 2391357.31 2609.18 26-MAR-15:14 2609.18 0.00
April 0.00 0.00 0.116807E+10 0.116693E+10 15059.55 30-APR-18:01 15059.55 0.00
May 0.00 0.00 0.249851E+10 0.222751E+10 17098.74 14-MAY-20:41 17098.74 0.13
June 0.00 0.00 0.485174E+10 0.282049E+10 16101.25 30-JUN-21:51 13376.38 0.68
July 0.00 0.00 0.492373E+10 0.255313E+10 16670.32 08-JUL-21:51 14485.14 0.68
August 0.00 0.00 0.271824E+10 0.122702E+10 15489.33 12-AUG-21:52 12011.76 0.55
September 0.00 0.00 0.354650E+09 0.195425E+09 15051.55 07-SEP-18:01 15051.55 0.11
October 0.00 0.00 5109649.15 4276050.31 6395.47 03-OCT-15:11 6395.47 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.165225E+11 0.101972E+11       0.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.492373E+10 0.282049E+10 17098.74   17098.74 0.68



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 0.212467E+09 0.212467E+09 14969.98 31-MAR-15:10 14969.98 0.00
April 0.00 0.00 0.247679E+11 0.247679E+11 58278.29 22-APR-13:20 58278.29 0.00
May 0.00 0.00 0.372354E+11 0.372354E+11 56484.24 12-MAY-13:20 56484.24 0.00
June 0.00 0.00 0.444233E+11 0.272788E+11 53162.71 30-JUN-12:30 40132.61 0.69
July 0.00 0.00 0.469766E+11 0.210376E+11 60514.68 23-JUL-13:30 55543.62 0.97
August 0.00 0.00 0.422681E+11 0.223085E+11 64029.71 25-AUG-13:15 62093.69 0.84
September 0.00 0.00 0.167611E+11 0.142584E+11 54028.67 09-SEP-13:10 54028.67 0.15
October 0.00 0.00 0.157266E+10 0.157266E+10 36234.56 03-OCT-13:00 36234.56 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.214218E+12 0.148672E+12       0.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.469766E+11 0.372354E+11 64029.71   62093.69 0.97



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 4818929.20 4818929.20 9429.63 20-JAN-19:07 9429.63 0.00
February 0.00 0.00 9858592.53 9477873.12 14637.49 07-FEB-19:04 14637.49 0.00
March 0.00 0.00 74322653.10 74322653.10 49075.48 22-MAR-18:02 49075.48 0.00
April 0.00 0.00 0.474493E+10 0.473413E+10 77065.74 30-APR-18:01 77065.74 0.00
May 0.00 0.00 0.229546E+11 0.217586E+11 80617.29 31-MAY-21:51 80617.29 0.10
June 0.00 0.00 0.387976E+11 0.295245E+11 82902.55 07-JUN-21:51 82902.55 0.57
July 0.00 0.00 0.416771E+11 0.283365E+11 84577.35 15-JUL-20:41 68414.14 0.60
August 0.00 0.00 0.268728E+11 0.165825E+11 81733.36 12-AUG-21:52 64436.87 0.50
September 0.00 0.00 0.700923E+10 0.398892E+10 75809.53 10-SEP-18:01 75809.53 0.33
October 0.00 0.00 0.697399E+09 0.589480E+09 72355.50 06-OCT-18:02 72355.50 0.02
November 0.00 0.00 4137477.13 4137477.13 11765.86 01-NOV-18:06 11765.86 0.00
December 0.00 0.00 2148308.83 2148308.83 13359.93 24-DEC-19:05 13359.93 0.00
                 
Annual Sum or Average 0.00 0.00 0.142849E+12 0.105610E+12       0.18
Minimum of Months 0.00 0.00 2148308.83 2148308.83 9429.63   9429.63 0.00
Maximum of Months 0.00 0.00 0.416771E+11 0.295245E+11 84577.35   82902.55 0.60



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 172056.54 172056.54 1405.44 09-FEB-16:15 1405.44 0.00
March 0.00 0.00 0.181465E+09 0.181465E+09 15785.00 22-MAR-15:11 15785.00 0.00
April 0.00 0.00 0.215278E+10 0.211546E+10 15793.05 21-APR-08:61 15793.05 0.01
May 0.00 0.00 0.639102E+10 0.593863E+10 15794.49 01-MAY-08:61 15794.49 0.19
June 0.00 0.00 0.838478E+10 0.571507E+10 15793.60 12-JUN-18:02 15793.60 0.84
July 0.00 0.00 0.915083E+10 0.559681E+10 15326.17 17-JUL-18:01 13018.03 0.94
August 0.00 0.00 0.639467E+10 0.376906E+10 15792.73 10-AUG-18:02 15792.73 0.82
September 0.00 0.00 0.146635E+10 0.869586E+09 15794.30 10-SEP-15:11 15794.30 0.31
October 0.00 0.00 90488886.65 69210499.31 14865.37 04-OCT-08:62 14865.37 0.01
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.342126E+11 0.242554E+11       0.26
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.915083E+10 0.593863E+10 15794.49   15794.49 0.94



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 56694.67 56694.67 396.82 08-FEB-19:06 396.82 0.00
March 0.00 0.00 38074067.69 38074067.69 4053.41 11-MAR-09:01 4053.41 0.00
April 0.00 0.00 0.866029E+09 0.843367E+09 14286.57 21-APR-08:61 14286.57 0.01
May 0.00 0.00 0.444477E+10 0.409156E+10 14918.07 14-MAY-20:41 14918.07 0.17
June 0.00 0.00 0.620928E+10 0.412035E+10 15281.45 10-JUN-21:51 15281.45 0.71
July 0.00 0.00 0.660214E+10 0.401721E+10 15884.02 22-JUL-08:32 15884.02 0.73
August 0.00 0.00 0.397859E+10 0.219822E+10 14698.62 12-AUG-21:52 11401.24 0.62
September 0.00 0.00 0.629718E+09 0.351970E+09 14287.47 10-SEP-15:11 14287.47 0.19
October 0.00 0.00 17137540.84 9636001.69 9034.91 04-OCT-08:62 9034.91 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.227858E+11 0.156704E+11       0.20
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.660214E+10 0.412035E+10 15884.02   15884.02 0.73



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 28110.05 28110.05 281.10 09-FEB-16:15 281.10 0.00
March 0.00 0.00 23407078.62 23407078.62 4272.96 22-MAR-15:11 4272.96 0.00
April 0.00 0.00 0.592936E+09 0.591891E+09 4365.35 30-APR-15:11 4365.35 0.00
May 0.00 0.00 0.107858E+10 0.995272E+09 4365.44 25-MAY-18:01 4365.44 0.14
June 0.00 0.00 0.179621E+10 0.120425E+10 4365.56 07-JUN-15:12 4365.56 0.77
July 0.00 0.00 0.180304E+10 0.101463E+10 4327.39 27-JUL-08:62 3338.43 0.87
August 0.00 0.00 0.123910E+10 0.715334E+09 4455.86 13-AUG-08:61 3427.41 0.71
September 0.00 0.00 0.237541E+09 0.159291E+09 4365.26 07-SEP-15:11 4365.26 0.16
October 0.00 0.00 6009999.33 5061386.68 2923.30 03-OCT-15:11 2923.30 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.677685E+10 0.470916E+10       0.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.180304E+10 0.120425E+10 4455.86   4365.56 0.87



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 574359.98 574359.98 803.37 22-MAR-15:13 803.37 0.00
April 0.00 0.00 0.283154E+09 0.283046E+09 3885.22 30-APR-18:01 3885.22 0.00
May 0.00 0.00 0.553345E+09 0.491217E+09 4951.68 09-MAY-19:42 4951.68 0.12
June 0.00 0.00 0.120055E+10 0.698772E+09 4500.20 28-JUN-21:32 4391.61 0.66
July 0.00 0.00 0.120564E+10 0.632238E+09 4343.00 24-JUL-21:51 3550.69 0.67
August 0.00 0.00 0.607548E+09 0.280564E+09 4056.72 12-AUG-21:52 3013.19 0.50
September 0.00 0.00 67063246.82 38725715.22 3882.93 07-SEP-18:01 3882.93 0.07
October 0.00 0.00 734556.32 588538.99 980.10 01-OCT-15:13 734.35 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.391861E+10 0.242573E+10       0.17
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.120564E+10 0.698772E+09 4951.68   4951.68 0.67



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.128249E+09 0.128249E+09 26299.81 15-FEB-16:11 26299.81 0.00
March 0.00 0.00 0.184839E+10 0.184668E+10 26329.21 22-MAR-15:11 26329.21 0.00
April 0.00 0.00 0.588844E+10 0.581264E+10 26331.24 18-APR-18:01 26331.24 0.02
May 0.00 0.00 0.802667E+10 0.714754E+10 26333.09 03-MAY-15:11 26333.09 0.23
June 0.00 0.00 0.102020E+11 0.642163E+10 26333.28 15-JUN-18:01 26333.28 0.78
July 0.00 0.00 0.114212E+11 0.625876E+10 26333.35 13-JUL-18:02 26333.35 0.90
August 0.00 0.00 0.967647E+10 0.573077E+10 26329.06 21-AUG-18:01 26329.06 0.80
September 0.00 0.00 0.374639E+10 0.241095E+10 26328.69 30-SEP-15:11 26328.69 0.42
October 0.00 0.00 0.858165E+09 0.771096E+09 26316.20 14-OCT-15:11 26316.20 0.03
November 0.00 0.00 2758308.64 2758308.64 9089.92 08-NOV-16:12 9089.92 0.00
December 0.00 0.00 120642.89 120642.89 1206.43 24-DEC-09:05 1206.43 0.00
                 
Annual Sum or Average 0.00 0.00 0.517989E+11 0.365312E+11       0.27
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.114212E+11 0.714754E+10 26333.35   26333.35 0.90



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 209225.35 643026.81 12-JAN-10:20
February 0.00 0.00 01-FEB-00:05 179554.27 605297.09 27-FEB-07:05
March 0.00 0.00 01-MAR-00:10 89518.50 555678.12 01-MAR-07:10
April 0.00 0.00 01-APR-00:10 34149.88 202976.61 03-APR-08:62
May 0.00 0.00 01-MAY-00:10 15554.42 118633.03 27-MAY-15:14
June 0.00 0.00 01-JUN-00:10 1157.92 64359.88 02-JUN-04:00
July 0.00 0.00 01-JUL-00:10 517.66 58041.58 05-JUL-08:04
August 0.00 0.00 01-AUG-00:10 4359.52 127020.71 31-AUG-08:03
September 0.00 0.00 01-SEP-00:10 32886.16 188083.46 27-SEP-15:11
October 0.00 0.00 01-OCT-00:10 55421.32 213028.04 30-OCT-08:05
November 0.00 0.00 01-NOV-00:10 196968.51 595088.79 29-NOV-10:10
December 0.00 0.00 01-DEC-00:10 246398.29 617417.82 15-DEC-10:50
             
Annual Sum or Average 0.00     88310.25    
Minimum of Months 0.00 0.00   517.66 58041.58  
Maximum of Months 0.00 0.00   246398.29 643026.81  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 196.60 22835.25 23-JAN-19:07 0.00 0.00 01-JAN-00:05
February 392.67 31266.61 07-FEB-19:04 0.00 0.00 01-FEB-00:05
March 1756.80 47000.40 22-MAR-18:02 0.00 0.00 01-MAR-00:10
April 18695.18 211563.01 22-APR-15:13 0.00 0.00 01-APR-00:10
May 49324.29 248598.70 31-MAY-18:02 0.00 0.00 01-MAY-00:10
June 104577.89 399350.55 29-JUN-18:03 0.00 0.00 01-JUN-00:10
July 118072.74 450467.32 29-JUL-18:03 0.00 0.00 01-JUL-00:10
August 78755.03 394305.12 23-AUG-18:03 0.00 0.00 01-AUG-00:10
September 15760.66 182546.90 09-SEP-15:13 0.00 0.00 01-SEP-00:10
October 2143.96 72906.33 03-OCT-18:01 0.00 0.00 01-OCT-00:10
November 154.72 21178.42 05-NOV-18:07 0.00 0.00 01-NOV-00:10
December 144.58 30736.02 24-DEC-19:05 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 32736.61     0.00    
Minimum of Months 144.58 21178.42   0.00 0.00  
Maximum of Months 118072.74 450467.32   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 33737.59 68885.44 30-JAN-07:56
February 0.00 0.00 01-FEB-00:05 33743.90 68880.69 28-FEB-07:54
March 0.00 0.00 01-MAR-00:10 33766.52 68884.17 01-MAR-07:54
April 0.00 0.00 01-APR-00:10 33748.43 68848.30 03-APR-06:58
May 0.00 0.00 01-MAY-00:10 33512.34 68873.68 12-MAY-07:00
June 0.00 0.00 01-JUN-00:10 32336.82 67157.39 01-JUN-06:59
July 0.00 0.00 01-JUL-00:10 31153.87 64354.24 03-JUL-06:58
August 0.00 0.00 01-AUG-00:10 30452.18 62404.47 01-AUG-06:55
September 0.00 0.00 01-SEP-00:10 30345.67 61949.66 29-SEP-07:00
October 0.00 0.00 01-OCT-00:10 30894.82 63842.68 31-OCT-07:00
November 0.00 0.00 01-NOV-00:10 31955.31 66397.06 30-NOV-07:59
December 0.00 0.00 01-DEC-00:10 33223.08 68859.25 28-DEC-07:57
             
Annual Sum or Average 0.00     32398.27    
Minimum of Months 0.00 0.00   30345.67 61949.66  
Maximum of Months 0.00 0.00   33766.52 68885.44  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.261333E+10 0.68 1299.30 01-JAN-00:20 0.89
February 0.236042E+10 0.68 1299.30 01-FEB-00:05 0.89
March 0.261333E+10 0.68 1299.30 01-MAR-00:10 0.90
April 0.252903E+10 0.68 1299.30 01-APR-00:10 0.89
May 0.261333E+10 0.68 1299.30 01-MAY-00:20 0.89
June 0.252903E+10 0.68 1299.30 01-JUN-00:40 0.89
July 0.261333E+10 0.68 1299.30 01-JUL-01:20 0.88
August 0.261333E+10 0.68 1299.30 01-AUG-00:50 0.88
September 0.252903E+10 0.68 1299.30 01-SEP-08:61 0.89
October 0.261333E+10 0.68 1299.30 01-OCT-00:30 0.89
November 0.252903E+10 0.68 1299.30 01-NOV-00:10 0.89
December 0.261333E+10 0.68 1299.30 01-DEC-00:10 0.90
           
Annual Sum or Average 0.307698E+11 0.68      
Minimum of Months 0.236042E+10 0.68 1299.30   0.88
Maximum of Months 0.261333E+10 0.68 1299.30   0.90



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.348854E+11 0.82 19036.49 19-JAN-19:40 1.02
February 0.318998E+11 0.83 19136.82 02-FEB-19:40 1.03
March 0.364471E+11 0.84 19143.91 19-MAR-19:10 1.03
April 0.363504E+11 0.86 19844.83 21-APR-21:10 1.05
May 0.386459E+11 0.87 22348.34 31-MAY-21:10 1.12
June 0.386350E+11 0.88 25012.64 22-JUN-21:10 1.20
July 0.398222E+11 0.88 24975.33 12-JUL-21:10 1.20
August 0.392660E+11 0.87 24549.47 11-AUG-21:10 1.19
September 0.365455E+11 0.86 19265.50 09-SEP-21:00 1.03
October 0.367588E+11 0.85 19233.49 18-OCT-19:00 1.03
November 0.338869E+11 0.83 19082.26 02-NOV-18:40 1.03
December 0.347454E+11 0.82 18929.17 24-DEC-20:10 1.02
           
Annual Sum or Average 0.437889E+12 0.85      
Minimum of Months 0.318998E+11 0.82 18929.17   1.02
Maximum of Months 0.398222E+11 0.88 25012.64   1.20



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.27 76.61 01-JAN-00:05 0.27
February 0.185347E+09 0.27 76.61 01-FEB-00:05 0.27
March 0.205205E+09 0.27 76.61 01-MAR-00:10 0.27
April 0.198586E+09 0.27 76.61 01-APR-00:10 0.27
May 0.205205E+09 0.27 76.61 01-MAY-00:10 0.27
June 0.198586E+09 0.27 76.61 01-JUN-00:10 0.27
July 0.205205E+09 0.27 76.61 01-JUL-00:10 0.27
August 0.205205E+09 0.27 76.61 01-AUG-00:10 0.27
September 0.198586E+09 0.27 76.61 01-SEP-00:10 0.27
October 0.205205E+09 0.27 76.61 01-OCT-00:10 0.27
November 0.198586E+09 0.27 76.61 01-NOV-00:10 0.27
December 0.205205E+09 0.27 76.61 01-DEC-00:10 0.27
           
Annual Sum or Average 0.241613E+10 0.27      
Minimum of Months 0.185347E+09 0.27 76.61   0.27
Maximum of Months 0.205205E+09 0.27 76.61   0.27



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:05 0.00
March 0.00 -0.0 0.00 01-MAR-00:10 0.00
April 0.00 0.00 0.00 01-APR-00:10 -0.0
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 -0.0 0.00 01-JUN-00:10 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 -0.0
December 0.00 -0.0 0.00 01-DEC-00:10 -0.0
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:05 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:10 0.00
December 0.00 -0.0 0.00 01-DEC-00:10 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:05 0.00
March 0.00 -0.0 0.00 01-MAR-00:10 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 -0.0 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:10 0.00
December 0.00 -0.0 0.00 01-DEC-00:10 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:10 0.27
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.27
March 0.116283E+10 0.19 612.92 01-MAR-07:10 0.27
April 0.112532E+10 0.19 612.92 01-APR-06:10 0.27
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.27
June 0.112532E+10 0.19 612.92 01-JUN-06:05 0.27
July 0.116283E+10 0.19 612.92 01-JUL-06:05 0.27
August 0.116283E+10 0.19 612.92 01-AUG-06:05 0.27
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.27
October 0.116283E+10 0.19 612.92 01-OCT-06:10 0.27
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.27
December 0.116283E+10 0.19 612.92 01-DEC-07:05 0.27
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.27
Maximum of Months 0.116283E+10 0.19 612.92   0.27



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.825012E+09 0.57 824.33 01-JAN-09:02 0.59
February 0.594607E+09 0.54 824.33 01-FEB-09:02 0.59
March 0.393278E+09 0.45 824.33 01-MAR-09:02 0.59
April 0.231194E+09 0.46 824.33 01-APR-08:62 0.59
May 0.246499E+09 0.51 824.33 01-MAY-15:11 0.58
June 0.364506E+09 0.53 824.33 01-JUN-08:61 0.58
July 0.342306E+09 0.53 824.33 01-JUL-08:61 0.58
August 0.262372E+09 0.51 824.33 01-AUG-08:61 0.58
September 0.158279E+09 0.43 824.33 01-SEP-15:11 0.58
October 0.330937E+09 0.47 824.33 01-OCT-15:11 0.58
November 0.729952E+09 0.57 824.33 01-NOV-08:62 0.59
December 0.960061E+09 0.57 824.33 01-DEC-09:02 0.59
           
Annual Sum or Average 0.543900E+10 0.51      
Minimum of Months 0.158279E+09 0.43 824.33   0.58
Maximum of Months 0.960061E+09 0.57 824.33   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.849937E+09 0.57 741.40 01-JAN-09:02 0.59
February 0.668302E+09 0.57 741.40 01-FEB-09:02 0.59
March 0.459478E+09 0.52 741.40 01-MAR-09:02 0.59
April 0.204717E+09 0.43 741.40 01-APR-08:62 0.59
May 0.150040E+09 0.40 741.40 01-MAY-15:11 0.58
June 0.230032E+09 0.40 741.40 01-JUN-08:61 0.58
July 0.221672E+09 0.40 741.40 01-JUL-08:61 0.58
August 0.136908E+09 0.36 741.40 01-AUG-08:61 0.58
September 0.139865E+09 0.39 741.40 01-SEP-15:11 0.58
October 0.354188E+09 0.50 741.40 02-OCT-08:62 0.58
November 0.784925E+09 0.57 741.40 01-NOV-08:62 0.59
December 0.954708E+09 0.57 741.40 01-DEC-09:02 0.59
           
Annual Sum or Average 0.515477E+10 0.47      
Minimum of Months 0.136908E+09 0.36 741.40   0.58
Maximum of Months 0.954708E+09 0.57 741.40   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.271249E+10 0.58 3573.14 12-JAN-16:00 0.59
February 0.111635E+10 0.37 1478.30 27-FEB-16:00 0.59
March 0.111027E+09 0.04 1372.58 01-MAR-05:00 0.59
April 0.908658E+09 0.29 1812.44 22-APR-13:20 0.59
May 0.139977E+10 0.48 1762.02 12-MAY-13:20 0.59
June 0.171517E+10 0.57 1656.59 10-JUN-14:00 0.58
July 0.172784E+10 0.56 1894.45 23-JUL-13:30 0.58
August 0.158891E+10 0.53 2002.22 25-AUG-13:15 0.58
September 0.678681E+09 0.29 1692.05 09-SEP-13:10 0.58
October 0.172700E+09 0.09 1202.56 03-OCT-13:00 0.59
November 0.225202E+10 0.56 1605.29 30-NOV-16:00 0.59
December 0.317435E+10 0.59 3389.07 15-DEC-15:10 0.59
           
Annual Sum or Average 0.175580E+11 0.41      
Minimum of Months 0.111027E+09 0.04 1202.56   0.58
Maximum of Months 0.317435E+10 0.59 3573.14   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.390950E+10 0.50 3844.18 01-JAN-09:02 0.59
February 0.324552E+10 0.47 3844.18 01-FEB-09:02 0.59
March 0.215643E+10 0.42 3844.18 01-MAR-00:10 0.59
April 0.841152E+09 0.40 3844.18 01-APR-08:62 0.59
May 0.113246E+10 0.36 3844.18 01-MAY-08:61 0.58
June 0.192269E+10 0.35 3844.18 01-JUN-08:61 0.58
July 0.187989E+10 0.35 3844.18 01-JUL-08:61 0.58
August 0.119734E+10 0.32 3844.18 01-AUG-08:61 0.58
September 0.596508E+09 0.39 3844.18 01-SEP-08:61 0.58
October 0.127781E+10 0.41 3844.18 01-OCT-08:62 0.58
November 0.356481E+10 0.50 3844.18 01-NOV-08:62 0.59
December 0.448793E+10 0.51 3844.18 01-DEC-00:10 0.59
           
Annual Sum or Average 0.262120E+11 0.41      
Minimum of Months 0.596508E+09 0.32 3844.18   0.58
Maximum of Months 0.448793E+10 0.51 3844.18   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.808108E+09 0.57 777.46 01-JAN-09:02 0.59
February 0.551305E+09 0.53 777.46 01-FEB-09:02 0.59
March 0.332684E+09 0.43 777.46 01-MAR-09:02 0.59
April 0.213952E+09 0.49 777.46 01-APR-08:62 0.59
May 0.326899E+09 0.55 777.46 01-MAY-08:61 0.58
June 0.398819E+09 0.55 777.46 01-JUN-08:61 0.58
July 0.413637E+09 0.55 777.46 01-JUL-08:61 0.58
August 0.301906E+09 0.53 777.46 01-AUG-08:61 0.58
September 0.159864E+09 0.45 777.46 01-SEP-08:61 0.58
October 0.294634E+09 0.45 777.46 01-OCT-08:62 0.58
November 0.730469E+09 0.57 777.46 01-NOV-08:62 0.59
December 0.953016E+09 0.57 777.46 01-DEC-09:02 0.59
           
Annual Sum or Average 0.548529E+10 0.52      
Minimum of Months 0.159864E+09 0.43 777.46   0.58
Maximum of Months 0.953016E+09 0.57 777.46   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.831654E+09 0.57 703.10 01-JAN-09:02 0.59
February 0.622058E+09 0.56 703.10 01-FEB-09:02 0.59
March 0.386485E+09 0.46 703.10 01-MAR-09:02 0.59
April 0.183989E+09 0.43 703.10 01-APR-08:62 0.59
May 0.243541E+09 0.48 703.10 01-MAY-08:61 0.58
June 0.301872E+09 0.42 703.10 01-JUN-08:61 0.58
July 0.297050E+09 0.42 703.10 01-JUL-08:61 0.58
August 0.192699E+09 0.41 703.10 01-AUG-08:61 0.58
September 0.132327E+09 0.40 703.10 01-SEP-08:61 0.58
October 0.312856E+09 0.47 703.10 02-OCT-15:12 0.58
November 0.773189E+09 0.57 703.10 01-NOV-08:62 0.59
December 0.939302E+09 0.57 703.10 01-DEC-09:02 0.59
           
Annual Sum or Average 0.521702E+10 0.48      
Minimum of Months 0.132327E+09 0.40 703.10   0.58
Maximum of Months 0.939302E+09 0.57 703.10   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.264264E+09 0.58 214.96 01-JAN-09:02 0.59
February 0.190202E+09 0.56 214.96 01-FEB-09:02 0.59
March 0.122231E+09 0.49 214.96 01-MAR-09:02 0.59
April 67782293.07 0.46 214.96 01-APR-08:62 0.59
May 62891568.22 0.51 214.96 01-MAY-15:11 0.58
June 90231958.94 0.53 214.96 01-JUN-08:61 0.58
July 84941539.61 0.52 214.96 01-JUL-08:61 0.58
August 64679666.25 0.50 214.96 01-AUG-08:61 0.58
September 48713934.41 0.43 214.96 01-SEP-15:11 0.58
October 0.102393E+09 0.50 214.96 02-OCT-08:62 0.58
November 0.241242E+09 0.58 214.96 01-NOV-08:62 0.59
December 0.296111E+09 0.58 214.96 01-DEC-09:02 0.59
           
Annual Sum or Average 0.163568E+10 0.52      
Minimum of Months 48713934.41 0.43 214.96   0.58
Maximum of Months 0.296111E+09 0.58 214.96   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.262206E+09 0.58 191.29 01-JAN-09:02 0.59
February 0.209659E+09 0.57 191.29 01-FEB-09:02 0.59
March 0.147028E+09 0.55 191.29 01-MAR-09:02 0.59
April 61825664.90 0.45 191.29 01-APR-08:62 0.59
May 38132197.80 0.40 191.29 01-MAY-15:11 0.58
June 58222604.59 0.40 191.29 01-JUN-08:61 0.58
July 55442252.27 0.40 191.29 01-JUL-08:61 0.58
August 32980040.70 0.36 191.29 01-AUG-08:61 0.58
September 44977925.49 0.41 191.29 01-SEP-15:11 0.58
October 0.112662E+09 0.52 191.29 01-OCT-08:62 0.58
November 0.244999E+09 0.58 191.29 01-NOV-08:62 0.59
December 0.285892E+09 0.58 191.29 01-DEC-09:02 0.59
           
Annual Sum or Average 0.155403E+10 0.48      
Minimum of Months 32980040.70 0.36 191.29   0.58
Maximum of Months 0.285892E+09 0.58 191.29   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.115635E+10 0.55 1292.62 01-JAN-09:02 0.59
February 0.722376E+09 0.49 1292.62 01-FEB-09:02 0.59
March 0.494752E+09 0.47 1292.62 01-MAR-09:02 0.59
April 0.393187E+09 0.51 1292.62 01-APR-08:62 0.59
May 0.407994E+09 0.53 1292.62 01-MAY-15:11 0.58
June 0.481477E+09 0.53 1292.62 01-JUN-08:61 0.58
July 0.508521E+09 0.53 1292.62 01-JUL-08:61 0.58
August 0.458263E+09 0.52 1292.62 01-AUG-08:61 0.58
September 0.278774E+09 0.47 1292.62 01-SEP-08:61 0.58
October 0.413326E+09 0.45 1292.62 01-OCT-15:11 0.58
November 0.973881E+09 0.54 1292.62 01-NOV-08:62 0.59
December 0.136186E+10 0.57 1292.62 01-DEC-09:02 0.59
           
Annual Sum or Average 0.765076E+10 0.51      
Minimum of Months 0.278774E+09 0.45 1292.62   0.58
Maximum of Months 0.136186E+10 0.57 1292.62   0.59



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.950081E+09 0.863624E+09 2083.42 12-JAN-10:50 1893.83 1893.83 38.37 7.10
February 0.717941E+09 0.652609E+09 1928.74 27-FEB-09:13 1753.22 1753.22 39.11 6.88
March 0.261141E+09 0.237378E+09 1601.33 01-MAR-07:10 1455.61 1455.61 39.21 6.39
April 18818331.96 17105863.75 79.71 03-APR-08:03 72.46 72.46 32.16 1.74
May 4957563.76 4506425.45 28.95 28-MAY-02:30 26.32 26.32 42.93 1.05
June 221345.89 201203.41 7.50 02-JUN-04:00 6.82 6.82 28.69 0.49
July 90743.97 82486.27 5.69 04-JUL-18:04 5.17 5.17 42.16 0.41
August 1620827.50 1473332.20 31.81 31-AUG-04:10 28.91 28.91 35.89 1.10
September 15337732.66 13941998.99 54.30 27-SEP-15:11 49.36 49.36 28.92 1.45
October 41427040.05 37657179.40 112.25 30-OCT-08:05 102.03 102.03 35.12 2.05
November 0.811998E+09 0.738106E+09 1956.34 29-NOV-10:10 1778.31 1778.31 39.43 6.92
December 0.117065E+10 0.106412E+10 2011.77 15-DEC-10:50 1828.70 1828.70 38.90 7.00
                 
Annual Sum or Average 0.399429E+10 0.363081E+10            
Minimum of Months 90743.97 82486.27 5.69   5.17 5.17 28.69 0.41
Maximum of Months 0.117065E+10 0.106412E+10 2083.42   1893.83 1893.83 42.93 7.10



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 1357982.75 1234406.32 340.40 20-JAN-19:07 309.42 309.42 6.72 0.68
February 6298852.83 5725657.22 477.80 07-FEB-19:04 434.32 434.32 6.72 0.98
March 79050122.19 71856561.07 1091.09 22-MAR-18:02 991.80 991.80 6.72 2.54
April 0.101890E+10 0.926178E+09 2009.75 22-APR-15:11 1826.86 1826.86 6.72 6.46
May 0.238809E+10 0.217077E+10 1974.27 31-MAY-15:10 1794.61 1794.61 6.72 6.22
June 0.355992E+10 0.323597E+10 2465.77 21-JUN-18:03 2241.38 2241.38 6.72 12.56
July 0.388296E+10 0.352961E+10 2502.20 20-JUL-18:03 2274.50 2274.50 6.72 13.29
August 0.306703E+10 0.278793E+10 2465.30 11-AUG-15:12 2240.95 2240.95 6.72 12.55
September 0.914495E+09 0.831276E+09 2010.28 09-SEP-15:11 1827.34 1827.34 6.72 6.46
October 0.108564E+09 98684319.81 1407.71 03-OCT-18:01 1279.61 1279.61 6.72 3.56
November 1082003.22 983540.93 400.29 01-NOV-18:06 363.86 363.86 6.72 0.81
December 926033.48 841764.43 445.18 24-DEC-19:05 404.67 404.67 6.72 0.91
                 
Annual Sum or Average 0.150287E+11 0.136611E+11            
Minimum of Months 926033.48 841764.43 340.40   309.42 309.42 6.72 0.68
Maximum of Months 0.388296E+10 0.352961E+10 2502.20   2274.50 2274.50 6.72 13.29



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.499597E+09 0.454133E+09 2119.18 01-JAN-00:05 1926.33 1926.33 6.73 18.93
February 0.782795E+09 0.711560E+09 2119.18 02-FEB-00:05 1926.33 1926.33 6.73 18.93
March 0.217044E+10 0.197293E+10 2119.18 01-MAR-12:30 1926.33 1926.33 6.74 18.93
April 0.438905E+10 0.398964E+10 2119.18 01-APR-00:40 1926.33 1926.33 6.72 18.93
May 0.558573E+10 0.507743E+10 2119.18 01-MAY-00:10 1926.33 1926.33 6.78 18.93
June 0.548401E+10 0.498497E+10 2119.18 01-JUN-00:10 1926.33 1926.33 7.27 18.93
July 0.567474E+10 0.515834E+10 2119.18 01-JUL-00:10 1926.33 1926.33 7.50 18.93
August 0.563108E+10 0.511866E+10 2119.18 01-AUG-00:10 1926.33 1926.33 7.69 18.93
September 0.412218E+10 0.374706E+10 2119.18 01-SEP-00:10 1926.33 1926.33 6.83 18.93
October 0.237144E+10 0.215564E+10 2119.18 01-OCT-08:00 1926.33 1926.33 6.75 18.93
November 0.383117E+09 0.348254E+09 2119.18 01-NOV-00:20 1926.33 1926.33 6.73 18.93
December 0.364983E+09 0.331770E+09 2119.18 19-DEC-18:20 1926.33 1926.33 6.74 18.93
                 
Annual Sum or Average 0.374592E+11 0.340504E+11            
Minimum of Months 0.364983E+09 0.331770E+09 2119.18   1926.33 1926.33 6.72 18.93
Maximum of Months 0.567474E+10 0.515834E+10 2119.18   1926.33 1926.33 7.69 18.93



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:05 14.37 14.37 45.59 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:05 14.37 14.37 46.58 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:10 14.37 14.37 47.14 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 49.92 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:10 14.37 14.37 49.97 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:10 14.37 14.37 50.36 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 50.31 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:10 14.37 14.37 51.05 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:10 14.37 14.37 50.80 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 50.04 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:10 14.37 14.37 50.31 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:10 14.37 14.37 47.50 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 45.59 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 51.05 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 41.16 60.00 209225.35 643026.81 12-JAN-10:20
February 0.00 0.00 01-FEB-00:05 38.92 60.00 179554.27 605297.09 27-FEB-07:05
March 0.00 0.00 01-MAR-00:10 39.59 60.00 89518.50 555678.12 01-MAR-07:10
April 0.00 0.00 01-APR-00:10 47.29 60.00 34149.88 202976.61 03-APR-08:62
May 0.00 0.00 01-MAY-00:10 29.71 60.00 15554.42 118633.03 27-MAY-15:14
June 0.00 0.00 01-JUN-00:10 29.13 29.13 1157.92 64359.88 02-JUN-04:00
July 0.00 0.00 01-JUL-00:10 42.41 42.41 517.66 58041.58 05-JUL-08:04
August 0.00 0.00 01-AUG-00:10 26.96 26.96 4359.52 127020.71 31-AUG-08:03
September 0.00 0.00 01-SEP-00:10 30.76 60.00 32886.16 188083.46 27-SEP-15:11
October 0.00 0.00 01-OCT-00:10 37.27 60.00 55421.32 213028.04 30-OCT-08:05
November 0.00 0.00 01-NOV-00:10 45.46 60.00 196968.51 595088.79 29-NOV-10:10
December 0.00 0.00 01-DEC-00:10 40.09 60.00 246398.29 617417.82 15-DEC-10:50
                 
Annual Sum or Average 0.00         88310.25    
Minimum of Months 0.00 0.00   26.96 26.96 517.66 58041.58  
Maximum of Months 0.00 0.00   47.29 60.00 246398.29 643026.81  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 196.60 22835.25 23-JAN-19:07 6.99 6.70 0.00 0.00 01-JAN-00:05
February 392.67 31266.61 07-FEB-19:04 7.09 6.70 0.00 0.00 01-FEB-00:05
March 1756.80 47000.40 22-MAR-18:02 7.29 6.70 0.00 0.00 01-MAR-00:10
April 18695.18 211563.01 22-APR-15:13 9.37 6.70 0.00 0.00 01-APR-00:10
May 49324.29 248598.70 31-MAY-18:02 9.83 6.70 0.00 0.00 01-MAY-00:10
June 104577.89 399350.55 29-JUN-18:03 11.74 6.70 0.00 0.00 01-JUN-00:10
July 118072.74 450467.32 29-JUL-18:03 12.38 6.70 0.00 0.00 01-JUL-00:10
August 78755.03 394305.12 23-AUG-18:03 11.67 6.70 0.00 0.00 01-AUG-00:10
September 15760.66 182546.90 09-SEP-15:13 9.00 6.70 0.00 0.00 01-SEP-00:10
October 2143.96 72906.33 03-OCT-18:01 7.62 6.70 0.00 0.00 01-OCT-00:10
November 154.72 21178.42 05-NOV-18:07 6.97 6.70 0.00 0.00 01-NOV-00:10
December 144.58 30736.02 24-DEC-19:05 7.09 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 32736.61         0.00    
Minimum of Months 144.58 21178.42   6.97 6.70 0.00 0.00  
Maximum of Months 118072.74 450467.32   12.38 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 45.59 59.63 33737.59 68885.44 30-JAN-07:56
February 0.00 0.00 01-FEB-00:05 46.58 58.88 33743.90 68880.69 28-FEB-07:54
March 0.00 0.00 01-MAR-00:10 47.14 59.43 33766.52 68884.17 01-MAR-07:54
April 0.00 0.00 01-APR-00:10 49.92 59.12 33748.43 68848.30 03-APR-06:58
May 0.00 0.00 01-MAY-00:10 49.97 59.20 33512.34 68873.68 12-MAY-07:00
June 0.00 0.00 01-JUN-00:10 50.36 59.46 32336.82 67157.39 01-JUN-06:59
July 0.00 0.00 01-JUL-00:10 50.31 58.74 31153.87 64354.24 03-JUL-06:58
August 0.00 0.00 01-AUG-00:10 51.05 59.57 30452.18 62404.47 01-AUG-06:55
September 0.00 0.00 01-SEP-00:10 50.80 58.89 30345.67 61949.66 29-SEP-07:00
October 0.00 0.00 01-OCT-00:10 50.04 59.45 30894.82 63842.68 31-OCT-07:00
November 0.00 0.00 01-NOV-00:10 50.31 58.59 31955.31 66397.06 30-NOV-07:59
December 0.00 0.00 01-DEC-00:10 47.50 59.27 33223.08 68859.25 28-DEC-07:57
                 
Annual Sum or Average 0.00         32398.27    
Minimum of Months 0.00 0.00   45.59 58.59 30345.67 61949.66  
Maximum of Months 0.00 0.00   51.05 59.63 33766.52 68885.44  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.362802E+12 0.00 75168325.83 0.348854E+11 0.00 0.00
February 0.296546E+12 0.00 85185202.38 0.318998E+11 0.00 0.00
March 0.154895E+12 0.00 0.156560E+09 0.364471E+11 0.00 0.00
April 0.678582E+11 0.00 0.736317E+09 0.363504E+11 0.00 0.00
May 0.408322E+11 0.00 0.354295E+11 0.386459E+11 0.00 0.00
June 0.292059E+10 0.00 0.131458E+12 0.386350E+11 0.00 0.00
July 0.133950E+10 0.00 0.166461E+12 0.398222E+11 0.00 0.00
August 0.111824E+11 0.00 0.980209E+11 0.392660E+11 0.00 0.00
September 0.760616E+11 0.00 0.479464E+10 0.365455E+11 0.00 0.00
October 0.932639E+11 0.00 0.209132E+09 0.367588E+11 0.00 0.00
November 0.332580E+12 0.00 51529095.41 0.338869E+11 0.00 0.00
December 0.434922E+12 0.00 54200966.70 0.347454E+11 0.00 0.00
             
Annual Sum or Average 0.187520E+13 0.00 0.437532E+12 0.437889E+12 0.00 0.00
Minimum of Months 0.133950E+10 0.00 51529095.41 0.318998E+11 0.00 0.00
Maximum of Months 0.434922E+12 0.00 0.166461E+12 0.398222E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.275460E+11 0.00 0.00 0.261333E+10 0.00 0.00
February 0.243633E+11 0.00 0.00 0.236042E+10 0.00 0.00
March 0.141195E+11 0.00 0.00 0.261333E+10 0.00 0.00
April 0.211243E+10 0.00 2616969.90 0.252903E+10 0.00 0.00
May 9958.87 0.00 0.174643E+10 0.261333E+10 0.00 0.00
June 25530.76 0.00 0.831331E+10 0.252903E+10 0.00 0.00
July 30044.83 0.00 0.101207E+11 0.261333E+10 0.00 0.00
August 2765664.03 0.00 0.609004E+10 0.261333E+10 0.00 0.00
September 0.118221E+09 0.00 0.172724E+09 0.252903E+10 0.00 0.00
October 0.417806E+10 0.00 0.00 0.261333E+10 0.00 0.00
November 0.266023E+11 0.00 0.00 0.252903E+10 0.00 0.00
December 0.329465E+11 0.00 0.00 0.261333E+10 0.00 0.00
             
Annual Sum or Average 0.131989E+12 0.00 0.264459E+11 0.307698E+11 0.00 0.00
Minimum of Months 9958.87 0.00 0.00 0.236042E+10 0.00 0.00
Maximum of Months 0.329465E+11 0.00 0.101207E+11 0.261333E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.348854E+11 75168325.83 0.362802E+12 0.491262E+12 0.00 0.00 0.00 0.00
February 0.318998E+11 85185202.38 0.296546E+12 0.407406E+12 0.00 0.00 0.00 0.00
March 0.364471E+11 0.156560E+09 0.154895E+12 0.471966E+12 0.00 0.00 0.00 0.00
April 0.363504E+11 0.736317E+09 0.678582E+11 0.200715E+12 0.00 0.00 0.00 0.00
May 0.386459E+11 0.354295E+11 0.408322E+11 0.346330E+09 0.00 0.00 0.00 0.00
June 0.386350E+11 0.131458E+12 0.292059E+10 0.180840E+10 79790083.12 0.00 0.00 0.00
July 0.398222E+11 0.166461E+12 0.133950E+10 0.399419E+10 0.383766E+09 0.00 0.00 0.00
August 0.392660E+11 0.980209E+11 0.111824E+11 0.286841E+10 0.00 0.00 0.00 0.00
September 0.365455E+11 0.479464E+10 0.760616E+11 0.243175E+11 0.00 0.00 0.00 0.00
October 0.367588E+11 0.209132E+09 0.932639E+11 0.317974E+12 0.00 0.00 0.00 0.00
November 0.338869E+11 51529095.41 0.332580E+12 0.495558E+12 0.00 0.00 0.00 0.00
December 0.347454E+11 54200966.70 0.434922E+12 0.466905E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.437889E+12 0.437532E+12 0.187520E+13 0.288512E+13 0.463556E+09 0.00 0.00 0.00
Minimum of Months 0.318998E+11 51529095.41 0.133950E+10 0.346330E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.398222E+11 0.166461E+12 0.434922E+12 0.495558E+12 0.383766E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.261333E+10 0.00 0.275460E+11 0.651611E+11 0.00 0.00 0.00 0.00
February 0.236042E+10 0.00 0.243633E+11 0.544731E+11 0.00 0.00 0.00 0.00
March 0.261333E+10 0.00 0.141195E+11 0.672616E+11 0.00 0.00 0.00 0.00
April 0.252903E+10 2616969.90 0.211243E+10 0.490923E+11 0.00 0.00 0.00 0.00
May 0.261333E+10 0.174643E+10 9958.87 0.207932E+11 0.00 0.00 0.00 0.00
June 0.252903E+10 0.831331E+10 25530.76 0.514383E+10 0.112554E+09 0.00 0.00 0.00
July 0.261333E+10 0.101207E+11 30044.83 0.421613E+10 0.294708E+09 0.00 0.00 0.00
August 0.261333E+10 0.609004E+10 2765664.03 0.932308E+10 40011200.84 0.00 0.00 0.00
September 0.252903E+10 0.172724E+09 0.118221E+09 0.309535E+11 0.00 0.00 0.00 0.00
October 0.261333E+10 0.00 0.417806E+10 0.589529E+11 0.00 0.00 0.00 0.00
November 0.252903E+10 0.00 0.266023E+11 0.649096E+11 0.00 0.00 0.00 0.00
December 0.261333E+10 0.00 0.329465E+11 0.623056E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.307698E+11 0.264459E+11 0.131989E+12 0.492586E+12 0.447273E+09 0.00 0.00 0.00
Minimum of Months 0.236042E+10 0.00 9958.87 0.421613E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.261333E+10 0.101207E+11 0.329465E+11 0.672616E+11 0.294708E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.348854E+11 0.362802E+12 75168325.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.318998E+11 0.296546E+12 85185202.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.364471E+11 0.154895E+12 0.156560E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363504E+11 0.678582E+11 0.736317E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.386459E+11 0.408322E+11 0.354295E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.386350E+11 0.292059E+10 0.131458E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.398222E+11 0.133950E+10 0.166461E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.392660E+11 0.111824E+11 0.980209E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.365455E+11 0.760616E+11 0.479464E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.367588E+11 0.932639E+11 0.209132E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.338869E+11 0.332580E+12 51529095.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.347454E+11 0.434922E+12 54200966.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.437889E+12 0.187520E+13 0.437532E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.318998E+11 0.133950E+10 51529095.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.398222E+11 0.434922E+12 0.166461E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.261333E+10 0.275460E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.236042E+10 0.243633E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.261333E+10 0.141195E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.252903E+10 0.211243E+10 2616969.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.261333E+10 9958.87 0.174643E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.252903E+10 25530.76 0.831331E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.261333E+10 30044.83 0.101207E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.261333E+10 2765664.03 0.609004E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.252903E+10 0.118221E+09 0.172724E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.261333E+10 0.417806E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.252903E+10 0.266023E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.261333E+10 0.329465E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.307698E+11 0.131989E+12 0.264459E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.236042E+10 9958.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.261333E+10 0.329465E+11 0.101207E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.687475E+11 0.00 0.00 0.00 0.00 35315824.65 0.00 0.00 0.60
February 0.607504E+11 0.00 0.00 0.00 0.00 65955757.37 0.00 0.00 0.60
March 0.535778E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.60
April 0.482911E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.62
May 0.473171E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.76
June 0.351338E+11 0.00 0.00 0.00 4183801.43 0.00 0.00 0.00 0.87
July 0.336822E+11 0.00 0.00 0.00 17056338.06 0.00 0.00 0.00 0.86
August 0.333702E+11 0.00 0.00 3909204.79 0.00 0.00 0.677915E+10 0.00 0.83
September 0.201162E+11 0.00 0.00 15608995.69 0.00 0.00 0.303884E+11 0.00 0.67
October 0.200616E+11 0.00 0.00 16450341.91 0.00 0.00 0.293428E+11 0.00 0.61
November 0.543252E+11 0.00 0.00 5644099.48 0.00 0.00 0.113503E+11 0.00 0.61
December 0.748166E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.61
                   
Annual Sum or Average 0.550190E+12 0.00 0.00 41612641.86 21240139.49 0.101272E+09 0.778607E+11 0.00 0.69
Minimum of Months 0.200616E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.60
Maximum of Months 0.748166E+11 0.00 0.00 16450341.91 17056338.06 65955757.37 0.303884E+11 0.00 0.87



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 67334539.13 0.00 0.00 0.00 0.00 0.772762E+10 0.00 0.00 1.12
February 0.692430E+09 0.00 0.00 7992.96 0.00 0.518105E+10 16142772.35 0.00 1.03
March 0.191186E+10 0.00 0.00 829715.58 0.00 0.267956E+10 0.587668E+09 0.00 1.05
April 0.283001E+10 0.00 0.00 3455158.79 0.00 0.304166E+09 0.214797E+10 0.00 1.30
May 0.266711E+10 0.00 0.00 5297441.81 0.00 0.00 0.242435E+10 0.00 1.66
June 0.139720E+10 1027577.58 0.00 7976440.73 0.00 0.00 0.242414E+10 0.00 1.95
July 0.147199E+10 3332902.34 0.00 7888083.76 0.00 0.00 0.200279E+10 0.00 1.88
August 0.205940E+10 0.00 0.00 6256734.72 0.00 0.00 0.223857E+10 0.00 1.84
September 0.387423E+10 0.00 0.00 1689748.24 0.00 54398988.85 0.106703E+10 0.00 1.24
October 0.260294E+10 0.00 0.00 304979.37 0.00 0.179010E+10 0.236564E+09 0.00 1.03
November 0.143359E+09 0.00 0.00 0.00 0.00 0.657850E+10 0.00 0.00 1.06
December 0.00 0.00 0.00 0.00 0.00 0.850905E+10 0.00 0.00 1.14
                   
Annual Sum or Average 0.197179E+11 4360479.92 0.00 33706295.95 0.00 0.328244E+11 0.131452E+11 0.00 1.36
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.03
Maximum of Months 0.387423E+10 3332902.34 0.00 7976440.73 0.00 0.850905E+10 0.242435E+10 0.00 1.95



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.599882E+10 0.00 0.00 0.00 0.00 0.138057E+10 0.00 0.00 1.01
February 0.633275E+10 0.00 0.00 0.00 0.00 0.191959E+09 0.00 0.00 1.01
March 0.574811E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.00
April 0.496315E+10 0.00 0.00 57346.59 0.00 0.00 0.217722E+09 0.00 1.05
May 0.445826E+10 0.00 0.00 281857.25 0.00 0.00 0.617895E+09 0.00 1.28
June 0.259235E+10 0.00 0.00 1254470.05 448860.93 0.00 0.118004E+10 0.00 1.46
July 0.237496E+10 413982.95 0.00 1224567.71 1415913.58 0.00 0.124263E+10 0.00 1.44
August 0.323986E+10 0.00 0.00 827409.97 0.00 0.00 0.107026E+10 0.00 1.40
September 0.526748E+10 0.00 0.00 20888.19 0.00 0.00 0.118491E+09 0.00 1.12
October 0.526260E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.01
November 0.675765E+10 0.00 0.00 0.00 0.00 0.287305E+09 0.00 0.00 1.01
December 0.659297E+10 0.00 0.00 0.00 0.00 0.143376E+10 0.00 0.00 1.01
                   
Annual Sum or Average 0.595890E+11 413982.95 0.00 3666539.76 1864774.51 0.329360E+10 0.444704E+10 0.00 1.15
Minimum of Months 0.237496E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.00
Maximum of Months 0.675765E+10 413982.95 0.00 1254470.05 1415913.58 0.143376E+10 0.124263E+10 0.00 1.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 5792171.98 0.00 0.00 0.00 0.00 0.171478E+10 0.00 0.00 0.08
February 13777471.76 0.00 0.00 0.00 0.00 0.104636E+10 0.00 0.00 0.06
March 36643397.60 0.00 0.00 0.00 0.00 0.345837E+09 0.00 0.00 0.02
April 58675992.91 0.00 0.00 99377.95 0.00 5693165.30 67909481.94 0.00 0.01
May 21900786.52 0.00 0.00 1328609.92 0.00 0.00 0.623717E+09 0.00 0.09
June 373886.40 149037.46 0.00 3409522.16 0.00 0.00 0.117755E+10 0.00 0.24
July 703608.87 720995.99 0.00 3843681.44 0.00 0.00 0.121365E+10 0.00 0.25
August 4697724.30 0.00 0.00 2619441.81 0.00 0.00 0.108407E+10 0.00 0.19
September 51067094.27 0.00 0.00 360139.53 0.00 0.00 0.222208E+09 0.00 0.03
October 56374067.85 0.00 0.00 7817.33 0.00 45415608.75 6250896.79 0.00 0.01
November 8148371.38 0.00 0.00 0.00 0.00 0.110476E+10 0.00 0.00 0.06
December 3598663.47 0.00 0.00 0.00 0.00 0.174054E+10 0.00 0.00 0.09
                   
Annual Sum or Average 0.261753E+09 870033.45 0.00 11668590.14 0.00 0.600339E+10 0.439536E+10 0.00 0.10
Minimum of Months 373886.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01
Maximum of Months 58675992.91 720995.99 0.00 3843681.44 0.00 0.174054E+10 0.121365E+10 0.00 0.25



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.464725E+10 0.00 0.00 0.52
February 75067699.55 0.00 0.00 0.00 0.00 0.403393E+10 0.00 0.00 0.52
March 0.561023E+09 0.00 0.00 0.00 0.00 0.305891E+10 0.00 0.00 0.52
April 0.282384E+10 0.00 0.00 0.00 0.00 0.438905E+09 0.00 0.00 0.54
May 0.319694E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.66
June 0.237378E+10 0.00 0.00 0.00 282674.80 0.00 0.00 0.00 0.75
July 0.227571E+10 0.00 0.00 0.00 1152396.21 0.00 0.00 0.00 0.74
August 0.271292E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.72
September 0.339188E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
October 0.207477E+10 0.00 0.00 0.00 0.00 0.123940E+10 0.00 0.00 0.52
November 0.00 0.00 0.00 0.00 0.00 0.443663E+10 0.00 0.00 0.52
December 0.00 0.00 0.00 0.00 0.00 0.505492E+10 0.00 0.00 0.52
                   
Annual Sum or Average 0.194859E+11 0.00 0.00 0.00 1435071.00 0.229099E+11 0.00 0.00 0.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.52
Maximum of Months 0.339188E+10 0.00 0.00 0.00 1152396.21 0.505492E+10 0.00 0.00 0.75



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.101490E+09 0.00 0.00 0.815901E+11 0.00 11.69
February 0.00 0.00 0.00 95071065.46 0.00 0.00 0.755997E+11 0.00 11.92
March 0.00 0.00 0.00 0.107692E+09 0.00 0.00 0.697572E+11 0.00 12.37
April 0.00 0.00 0.00 0.106040E+09 0.00 0.00 0.666234E+11 0.00 13.30
May 0.00 0.00 0.00 0.123619E+09 0.00 0.00 0.647279E+11 0.00 16.77
June 0.00 4412399.63 0.00 0.133189E+09 0.00 0.00 0.475222E+11 0.00 19.31
July 0.00 23219977.02 0.00 0.139851E+09 0.00 0.00 0.455562E+11 0.00 18.90
August 0.00 0.00 0.00 0.124978E+09 0.00 0.00 0.550538E+11 0.00 18.48
September 0.00 0.00 0.00 0.103530E+09 0.00 0.00 0.689942E+11 0.00 14.50
October 0.00 0.00 0.00 0.105660E+09 0.00 0.00 0.671203E+11 0.00 12.70
November 0.00 0.00 0.00 99564903.98 0.00 0.00 0.811940E+11 0.00 11.85
December 0.00 0.00 0.00 0.101026E+09 0.00 0.00 0.901050E+11 0.00 11.62
                   
Annual Sum or Average 0.00 27632376.65 0.00 0.134171E+10 0.00 0.00 0.813844E+12 0.00 14.47
Minimum of Months 0.00 0.00 0.00 95071065.46 0.00 0.00 0.455562E+11 0.00 11.62
Maximum of Months 0.00 23219977.02 0.00 0.139851E+09 0.00 0.00 0.901050E+11 0.00 19.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.366024E+11 0.00 0.00 0.00 0.00 0.178141E+11 0.00 0.00 3.07
February 0.444710E+11 0.00 0.00 28.11 0.00 0.363531E+10 7556385.94 0.00 3.06
March 0.382899E+11 0.00 0.00 2529443.50 0.00 0.312169E+09 0.378933E+10 0.00 3.05
April 0.190388E+11 0.00 0.00 11644923.28 0.00 0.00 0.195080E+11 0.00 3.22
May 0.132933E+11 0.00 0.00 14273104.39 0.00 0.00 0.242856E+11 0.00 3.92
June 0.795945E+10 3331964.42 0.00 20373736.09 0.00 0.00 0.198483E+11 0.00 4.45
July 0.811775E+10 13199906.48 0.00 20813575.89 624036.68 0.00 0.185391E+11 0.00 4.40
August 0.109364E+11 0.00 0.00 19900988.83 0.00 0.00 0.210054E+11 0.00 4.30
September 0.244397E+11 0.00 0.00 6383356.10 0.00 0.00 0.153578E+11 0.00 3.40
October 0.350557E+11 0.00 0.00 1059312.52 0.00 0.140146E+09 0.361289E+10 0.00 3.07
November 0.395291E+11 0.00 0.00 0.00 0.00 0.124212E+11 0.00 0.00 3.07
December 0.361026E+11 0.00 0.00 0.00 0.00 0.230875E+11 0.00 0.00 3.07
                   
Annual Sum or Average 0.313836E+12 16531870.90 0.00 96978468.71 624036.68 0.574104E+11 0.125954E+12 0.00 3.51
Minimum of Months 0.795945E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.05
Maximum of Months 0.444710E+11 13199906.48 0.00 20813575.89 624036.68 0.230875E+11 0.242856E+11 0.00 4.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.139284E+12 0.00 0.00 0.00 0.00 0.130161E+11 0.00 0.00 1.24
February 0.134460E+12 0.00 0.00 0.00 0.00 0.200415E+09 0.00 0.00 1.24
March 0.118209E+12 0.00 0.00 49832.84 0.00 0.00 0.424217E+09 0.00 1.23
April 0.762760E+11 0.00 0.00 10619724.68 0.00 0.00 0.306549E+11 0.00 1.29
May 0.498958E+11 0.00 0.00 30559562.06 0.00 0.00 0.549692E+11 0.00 1.57
June 0.285768E+11 1000657.29 0.00 59636273.13 8263199.55 0.00 0.496699E+11 0.00 1.81
July 0.242483E+11 19713487.55 0.00 60337393.32 18052997.42 0.00 0.508563E+11 0.00 1.79
August 0.342614E+11 0.00 0.00 52521935.21 0.00 0.00 0.550957E+11 0.00 1.73
September 0.767792E+11 0.00 0.00 11108756.37 0.00 0.00 0.343690E+11 0.00 1.37
October 0.104166E+12 0.00 0.00 840943.08 0.00 0.00 0.444606E+10 0.00 1.24
November 0.144918E+12 0.00 0.00 0.00 0.00 0.479969E+09 0.00 0.00 1.24
December 0.157904E+12 0.00 0.00 0.00 0.00 0.775600E+10 0.00 0.00 1.24
                   
Annual Sum or Average 0.108898E+13 20714144.84 0.00 0.225674E+09 26316196.97 0.214524E+11 0.280485E+12 0.00 1.42
Minimum of Months 0.242483E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.23
Maximum of Months 0.157904E+12 19713487.55 0.00 60337393.32 18052997.42 0.130161E+11 0.550957E+11 0.00 1.81



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.313387E+10 0.00 0.00 0.34
February 12640658.57 0.00 0.00 4541.26 0.00 0.284209E+10 354934.37 0.00 0.34
March 63369411.89 0.00 0.00 562297.55 0.00 0.208861E+10 50963930.53 0.00 0.34
April 47139578.48 0.00 0.00 6774063.91 0.00 0.744521E+09 0.615220E+09 0.00 0.34
May 12904981.40 0.00 0.00 12934212.44 0.00 83612760.21 0.124994E+10 0.00 0.34
June 5618808.80 1456554.35 0.00 18843644.67 0.00 2704411.04 0.978328E+09 0.00 0.34
July 9694162.79 5149425.80 0.00 17137761.31 0.00 2356254.88 0.812175E+09 0.00 0.34
August 16650340.72 27665.92 0.00 13242422.38 0.00 43790182.52 0.985567E+09 0.00 0.34
September 58982010.66 0.00 0.00 3922157.21 0.00 0.648064E+09 0.609088E+09 0.00 0.34
October 46005693.63 0.00 0.00 259024.23 0.00 0.143549E+10 41795600.62 0.00 0.34
November 494681.81 0.00 0.00 0.00 0.00 0.298986E+10 0.00 0.00 0.34
December 0.00 0.00 0.00 0.00 0.00 0.348444E+10 0.00 0.00 0.34
                   
Annual Sum or Average 0.273500E+09 6633646.08 0.00 73680124.95 0.00 0.174994E+11 0.534344E+10 0.00 0.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 2356254.88 0.00 0.00 0.34
Maximum of Months 63369411.89 5149425.80 0.00 18843644.67 0.00 0.348444E+10 0.124994E+10 0.00 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.313350E+10 0.00 0.00 0.34
February 0.00 0.00 0.00 1708.11 0.00 0.285453E+10 227902.04 0.00 0.34
March 13127976.94 0.00 0.00 40138.42 0.00 0.217113E+10 18948573.25 0.00 0.34
April 66123620.37 0.00 0.00 4075094.30 0.00 0.919780E+09 0.423511E+09 0.00 0.34
May 0.187995E+09 0.00 0.00 9154944.97 0.00 0.130093E+09 0.103199E+10 0.00 0.34
June 0.212795E+09 1296630.43 0.00 14202825.29 159753.26 2042959.14 0.776336E+09 0.00 0.34
July 0.186239E+09 4502080.36 1407.51 12620072.38 643308.23 1779979.24 0.640626E+09 2026.38 0.35
August 0.211206E+09 27094.47 0.00 7825900.45 568.21 60415445.80 0.779679E+09 0.00 0.34
September 0.100747E+09 0.00 0.00 1871578.20 0.00 0.827389E+09 0.389894E+09 0.00 0.34
October 22435678.90 0.00 0.00 66350.54 0.00 0.148782E+10 13047715.95 0.00 0.34
November 0.00 0.00 0.00 0.00 0.00 0.299001E+10 0.00 0.00 0.34
December 0.00 0.00 0.00 0.00 0.00 0.348403E+10 0.00 0.00 0.34
                   
Annual Sum or Average 0.100067E+10 5825805.26 1407.51 49858612.66 803629.70 0.180625E+11 0.407426E+10 2026.38 0.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 1779979.24 0.00 0.00 0.34
Maximum of Months 0.212795E+09 4502080.36 1407.51 14202825.29 643308.23 0.348403E+10 0.103199E+10 2026.38 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 28764303.50 0.00 0.00 0.00 0.00 0.158675E+10 0.00 0.00 0.02
February 0.567568E+09 0.00 0.00 0.00 0.00 0.475325E+09 0.00 0.00 0.02
March 0.961912E+09 0.00 0.00 86222.31 0.00 0.00 53291289.49 0.00 0.02
April 0.194916E+09 0.00 0.00 5136256.78 0.00 0.00 0.121437E+10 0.00 0.02
May 46112482.36 0.00 0.00 5377539.20 0.00 0.00 0.132243E+10 0.00 0.02
June 42805097.32 2236465.14 0.00 5353004.40 0.00 0.00 0.982247E+09 0.00 0.02
July 0.00 9384865.07 0.00 5409255.29 0.00 0.00 0.690395E+09 0.00 0.02
August 37188853.91 0.00 0.00 5818697.36 0.00 0.00 0.923439E+09 0.00 0.02
September 0.487607E+09 0.00 0.00 2644482.81 0.00 0.00 0.867000E+09 0.00 0.02
October 0.932175E+09 0.00 0.00 354613.80 0.00 29297128.40 0.166652E+09 0.00 0.02
November 0.189592E+09 0.00 0.00 0.00 0.00 0.129851E+10 0.00 0.00 0.02
December 0.00 0.00 0.00 0.00 0.00 0.195678E+10 0.00 0.00 0.02
                   
Annual Sum or Average 0.348864E+10 11621330.21 0.00 30180071.94 0.00 0.534666E+10 0.621982E+10 0.00 0.02
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 0.961912E+09 9384865.07 0.00 5818697.36 0.00 0.195678E+10 0.132243E+10 0.00 0.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.232636E+09 0.00 0.00 125750.46 0.00 0.422508E+11 20467435.01 0.00 0.39
February 0.368893E+09 0.00 0.00 218223.68 0.00 0.382320E+11 0.121913E+09 0.00 0.39
March 0.912534E+09 0.00 0.00 1572366.72 0.00 0.275520E+11 0.141962E+10 0.00 0.39
April 0.106766E+10 0.00 0.00 29370184.84 0.00 0.711856E+10 0.109575E+11 0.00 0.39
May 0.278238E+10 0.00 0.00 0.108592E+09 0.00 32751995.42 0.155135E+11 0.00 0.39
June 0.356138E+10 14968626.21 0.00 0.169453E+09 4786344.92 6628031.60 0.989987E+10 0.00 0.39
July 0.283483E+10 59766092.83 74931.06 0.162926E+09 9994579.82 4464216.87 0.840903E+10 5084.35 0.39
August 0.305329E+10 367520.27 0.00 0.105566E+09 7707.42 28436865.92 0.111791E+11 0.00 0.39
September 0.138744E+10 0.00 0.00 40139616.19 0.00 0.165144E+10 0.148247E+11 0.00 0.39
October 0.922142E+09 0.00 0.00 6909414.21 0.00 0.142571E+11 0.547749E+10 0.00 0.39
November 0.220110E+09 0.00 0.00 98825.12 0.00 0.403217E+11 15719662.05 0.00 0.39
December 0.115059E+09 0.00 0.00 58577.20 0.00 0.471294E+11 14301530.25 0.00 0.39
                   
Annual Sum or Average 0.174584E+11 75102239.31 74931.06 0.625030E+09 14788632.16 0.218585E+12 0.778532E+11 5084.35 0.39
Minimum of Months 0.115059E+09 0.00 0.00 58577.20 0.00 4464216.87 14301530.25 0.00 0.39
Maximum of Months 0.356138E+10 59766092.83 74931.06 0.169453E+09 9994579.82 0.471294E+11 0.155135E+11 5084.35 0.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.313387E+10 0.00 0.00 0.34
February 22308634.69 0.00 0.00 3306.06 0.00 0.283256E+10 223448.12 0.00 0.34
March 72762362.28 0.00 0.00 702812.56 0.00 0.200986E+10 0.120186E+09 0.00 0.34
April 28132213.48 0.00 0.00 5917291.54 0.00 0.732093E+09 0.647512E+09 0.00 0.34
May 7432446.57 0.00 0.00 15748256.27 0.00 53652835.55 0.128256E+10 0.00 0.34
June 6647829.48 1456554.35 0.00 20184114.72 0.00 1165167.77 0.977498E+09 0.00 0.34
July 6935351.99 5149425.80 0.00 21163730.34 0.00 1500060.01 0.811764E+09 0.00 0.34
August 10158602.98 27665.92 0.00 14826089.45 0.00 36139200.31 0.998126E+09 0.00 0.34
September 44652208.57 0.00 0.00 4680380.60 0.00 0.573798E+09 0.696926E+09 0.00 0.34
October 51298893.15 0.00 0.00 442456.30 0.00 0.136964E+10 0.102174E+09 0.00 0.34
November 0.00 0.00 0.00 0.00 0.00 0.299036E+10 0.00 0.00 0.34
December 0.00 0.00 0.00 0.00 0.00 0.348444E+10 0.00 0.00 0.34
                   
Annual Sum or Average 0.250329E+09 6633646.08 0.00 83668437.83 0.00 0.172191E+11 0.563697E+10 0.00 0.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 1165167.77 0.00 0.00 0.34
Maximum of Months 72762362.28 5149425.80 0.00 21163730.34 0.00 0.348444E+10 0.128256E+10 0.00 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.313350E+10 0.00 0.00 0.34
February 387220.50 0.00 0.00 1528.83 0.00 0.285420E+10 163155.25 0.00 0.34
March 50651267.24 0.00 0.00 154738.45 0.00 0.210464E+10 47804235.81 0.00 0.34
April 66981693.11 0.00 0.00 3271633.25 0.00 0.885082E+09 0.458154E+09 0.00 0.34
May 0.134517E+09 0.00 0.00 12372248.94 0.00 91191782.88 0.112115E+10 0.00 0.34
June 0.214467E+09 1296630.43 0.00 16561262.50 159753.26 1199552.14 0.773149E+09 0.00 0.34
July 0.175165E+09 4505514.25 0.00 16027053.88 643308.23 1147814.54 0.648925E+09 0.00 0.35
August 0.192106E+09 27094.47 0.00 9988794.38 568.21 47077371.87 0.809954E+09 0.00 0.34
September 98442966.53 0.00 0.00 2633481.51 0.00 0.698711E+09 0.520115E+09 0.00 0.34
October 33857838.16 0.00 0.00 121830.70 0.00 0.145315E+10 36246534.54 0.00 0.34
November 0.00 0.00 0.00 0.00 0.00 0.299001E+10 0.00 0.00 0.34
December 0.00 0.00 0.00 0.00 0.00 0.348403E+10 0.00 0.00 0.34
                   
Annual Sum or Average 0.966577E+09 5829239.15 0.00 61132572.44 803629.70 0.177439E+11 0.441566E+10 0.00 0.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 1147814.54 0.00 0.00 0.34
Maximum of Months 0.214467E+09 4505514.25 0.00 16561262.50 643308.23 0.348403E+10 0.112115E+10 0.00 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.168547E+10 0.00 0.00 0.00 0.00 0.365050E+11 0.00 0.00 0.34
February 0.633459E+10 0.00 0.00 0.00 0.00 0.274211E+11 0.00 0.00 0.34
March 0.199994E+11 0.00 0.00 0.00 0.00 0.973677E+10 0.00 0.00 0.34
April 0.263226E+11 0.00 0.00 0.00 0.00 0.479409E+09 0.00 0.00 0.35
May 0.262615E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
June 0.186425E+11 0.00 0.00 822544.34 2322051.30 0.00 0.857846E+09 0.00 0.49
July 0.177581E+11 0.00 0.00 1316674.56 9466436.83 0.00 0.936327E+09 0.00 0.48
August 0.222225E+11 0.00 0.00 12170.59 0.00 0.00 62989477.14 0.00 0.47
September 0.278629E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.37
October 0.207886E+11 0.00 0.00 0.00 0.00 0.643589E+10 0.00 0.00 0.34
November 0.186790E+10 0.00 0.00 0.00 0.00 0.345823E+11 0.00 0.00 0.34
December 0.574796E+09 0.00 0.00 0.00 0.00 0.409644E+11 0.00 0.00 0.34
                   
Annual Sum or Average 0.190321E+12 0.00 0.00 2151389.49 11788488.14 0.156125E+12 0.185716E+10 0.00 0.39
Minimum of Months 0.574796E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.34
Maximum of Months 0.278629E+11 0.00 0.00 1316674.56 9466436.83 0.409644E+11 0.936327E+09 0.00 0.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.783467E+09 0.00 0.00 0.34
February 567183.29 0.00 0.00 365.04 0.00 0.713190E+09 15147.66 0.00 0.34
March 12213429.75 0.00 0.00 106464.41 0.00 0.526844E+09 11713716.55 0.00 0.34
April 12091816.86 0.00 0.00 1648569.64 0.00 0.217364E+09 0.122310E+09 0.00 0.34
May 3588818.51 0.00 0.00 3049945.30 0.00 59946852.13 0.273263E+09 0.00 0.34
June 1693031.96 364138.59 0.00 4565174.39 0.00 1039878.61 0.244076E+09 0.00 0.34
July 2518502.87 1287356.45 0.00 4096127.75 0.00 4621512.04 0.199105E+09 0.00 0.34
August 3895421.61 6916.48 0.00 3096436.32 0.00 25729868.44 0.232091E+09 0.00 0.34
September 15452391.91 0.00 0.00 871141.95 0.00 0.219110E+09 94580506.68 0.00 0.34
October 6501049.03 0.00 0.00 42969.00 0.00 0.369379E+09 4965262.71 0.00 0.34
November 0.00 0.00 0.00 0.00 0.00 0.747590E+09 0.00 0.00 0.34
December 0.00 0.00 0.00 0.00 0.00 0.871110E+09 0.00 0.00 0.34
                   
Annual Sum or Average 58521645.78 1658411.52 0.00 17477193.80 0.00 0.453939E+10 0.118212E+10 0.00 0.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 1039878.61 0.00 0.00 0.34
Maximum of Months 15452391.91 1287356.45 0.00 4565174.39 0.00 0.871110E+09 0.273263E+09 0.00 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.783375E+09 0.00 0.00 0.34
February 0.00 0.00 0.00 0.00 0.00 0.713689E+09 0.00 0.00 0.34
March 1474486.05 0.00 0.00 7078.41 0.00 0.548735E+09 596380.18 0.00 0.34
April 14593872.47 0.00 0.00 948546.98 0.00 0.256786E+09 81044020.90 0.00 0.34
May 46374692.67 0.00 0.00 2150043.97 0.00 67161534.57 0.224123E+09 0.00 0.34
June 52832584.27 324157.61 0.00 3664651.11 39938.32 572881.84 0.194274E+09 0.00 0.34
July 46112567.74 1125520.09 170.43 3136227.94 160827.06 1928364.75 0.159139E+09 688.05 0.35
August 52338142.89 6773.62 0.00 1803952.02 142.05 27814640.95 0.182825E+09 0.00 0.34
September 22400833.85 0.00 0.00 370720.03 0.00 0.251363E+09 55840526.44 0.00 0.34
October 4128134.65 0.00 0.00 8354.00 0.00 0.375999E+09 707796.59 0.00 0.34
November 0.00 0.00 0.00 0.00 0.00 0.747502E+09 0.00 0.00 0.34
December 0.00 0.00 0.00 0.00 0.00 0.871008E+09 0.00 0.00 0.34
                   
Annual Sum or Average 0.240255E+09 1456451.32 170.43 12089574.46 200907.43 0.464593E+10 0.898549E+09 688.05 0.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 572881.84 0.00 0.00 0.34
Maximum of Months 52832584.27 1125520.09 170.43 3664651.11 160827.06 0.871008E+09 0.224123E+09 688.05 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 36792372.58 0.00 0.00 121.05 0.00 0.499644E+10 136415.75 0.00 0.39
February 80621724.30 0.00 0.00 386581.95 0.00 0.445207E+10 52550668.54 0.00 0.39
March 51047271.12 0.00 0.00 4099478.72 0.00 0.308348E+10 0.400474E+09 0.00 0.39
April 15759379.45 0.00 0.00 12847706.07 0.00 0.893397E+09 0.134850E+10 0.00 0.39
May 8077007.15 0.00 0.00 19526452.04 0.00 83589621.97 0.207216E+10 0.00 0.39
June 9626638.52 2339404.48 0.00 24434574.58 0.00 4289031.67 0.157660E+10 0.00 0.39
July 12075863.43 8270607.80 0.00 24306018.30 0.00 3779994.84 0.131117E+10 0.00 0.39
August 16065049.89 44434.86 0.00 21072409.35 0.00 38726296.94 0.162542E+10 0.00 0.39
September 45421094.03 0.00 0.00 9760404.75 0.00 0.574933E+09 0.149006E+10 0.00 0.39
October 79072066.50 0.00 0.00 2286774.19 0.00 0.195408E+10 0.411576E+09 0.00 0.39
November 32293890.49 0.00 0.00 13637.23 0.00 0.476514E+10 5432276.23 0.00 0.39
December 0.00 0.00 0.00 1786.04 0.00 0.559633E+10 107329.63 0.00 0.39
                   
Annual Sum or Average 0.386852E+09 10654447.13 0.00 0.118736E+09 0.00 0.264463E+11 0.102942E+11 0.00 0.39
Minimum of Months 0.00 0.00 0.00 121.05 0.00 3779994.84 107329.63 0.00 0.39
Maximum of Months 80621724.30 8270607.80 0.00 24434574.58 0.00 0.559633E+10 0.207216E+10 0.00 0.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.683196E+11 0.00 0.00 4570356.48 0.00 0.370547E+10 0.235200E+11 0.00 4.00
February 0.618846E+11 0.00 0.00 4931365.21 0.00 0.150583E+09 0.224428E+11 0.00 3.98
March 0.443573E+11 0.00 0.00 8838017.26 0.00 0.00 0.300614E+11 0.00 3.97
April 0.262573E+11 0.00 0.00 17619803.53 0.00 0.00 0.408087E+11 0.00 4.13
May 0.157394E+11 0.00 0.00 32708130.36 0.00 0.00 0.500025E+11 0.00 5.05
June 0.611795E+10 5570698.88 0.00 47625921.49 241225.77 0.00 0.428998E+11 0.00 5.80
July 0.553344E+10 20699123.26 0.00 46880084.19 2994676.08 0.00 0.414249E+11 0.00 5.71
August 0.115354E+11 0.00 0.00 37928731.18 0.00 0.00 0.443210E+11 0.00 5.52
September 0.234017E+11 0.00 0.00 21789200.89 0.00 0.00 0.463153E+11 0.00 4.41
October 0.322478E+11 0.00 0.00 12780647.29 0.00 0.00 0.358803E+11 0.00 4.00
November 0.681014E+11 0.00 0.00 4225023.88 0.00 0.00 0.231135E+11 0.00 3.99
December 0.818921E+11 0.00 0.00 2888962.24 0.00 0.129748E+10 0.207390E+11 0.00 4.00
                   
Annual Sum or Average 0.445388E+12 26269822.15 0.00 0.242786E+09 3235901.84 0.515354E+10 0.421529E+12 0.00 4.55
Minimum of Months 0.553344E+10 0.00 0.00 2888962.24 0.00 0.00 0.207390E+11 0.00 3.97
Maximum of Months 0.818921E+11 20699123.26 0.00 47625921.49 2994676.08 0.370547E+10 0.500025E+11 0.00 5.80



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.603580E+11 0.00 0.00 8371684.78 0.00 0.222041E+10 0.329301E+11 0.00 4.00
February 0.528331E+11 0.00 0.00 8634520.97 0.00 5730074.97 0.316066E+11 0.00 3.98
March 0.362062E+11 0.00 0.00 14370663.25 0.00 0.00 0.381814E+11 0.00 3.97
April 0.209573E+11 0.00 0.00 24846990.10 0.00 0.00 0.460969E+11 0.00 4.14
May 0.755733E+10 0.00 0.00 42596454.56 0.00 0.00 0.584029E+11 0.00 5.08
June 0.363338E+10 5809936.93 0.00 59037815.65 0.00 0.00 0.457097E+11 0.00 5.84
July 0.303711E+10 21463092.83 0.00 59298059.72 2222603.02 0.00 0.442144E+11 0.00 5.75
August 0.606467E+10 0.00 0.00 47803809.68 0.00 0.00 0.500364E+11 0.00 5.55
September 0.176909E+11 0.00 0.00 30025059.00 0.00 0.00 0.520449E+11 0.00 4.41
October 0.267653E+11 0.00 0.00 19863237.32 0.00 0.00 0.413325E+11 0.00 4.00
November 0.603846E+11 0.00 0.00 7857906.73 0.00 0.00 0.307955E+11 0.00 3.99
December 0.689999E+11 0.00 0.00 6054475.14 0.00 46520973.92 0.348434E+11 0.00 4.00
                   
Annual Sum or Average 0.364488E+12 27273029.76 0.00 0.328761E+09 2222603.02 0.227266E+10 0.506195E+12 0.00 4.56
Minimum of Months 0.303711E+10 0.00 0.00 6054475.14 0.00 0.00 0.307955E+11 0.00 3.97
Maximum of Months 0.689999E+11 21463092.83 0.00 59298059.72 2222603.02 0.222041E+10 0.584029E+11 0.00 5.84



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 92272228.10 0.00 0.00 96895471.23 0.00 0.00 0.743857E+11 0.00 10.74
February 11899587.72 0.00 0.00 93130648.72 0.00 0.00 0.693276E+11 0.00 11.20
March 0.00 0.00 0.00 0.109519E+09 0.00 0.00 0.668453E+11 0.00 12.03
April 0.00 0.00 0.00 0.112715E+09 0.00 0.00 0.668572E+11 0.00 13.53
May 0.00 0.00 0.00 0.134423E+09 0.00 0.00 0.663469E+11 0.00 17.90
June 0.00 7409603.40 0.00 0.144879E+09 0.00 0.00 0.496202E+11 0.00 20.48
July 0.00 30187877.60 0.00 0.153078E+09 0.00 0.00 0.461950E+11 0.00 20.03
August 0.00 0.00 0.00 0.134162E+09 0.00 0.00 0.559166E+11 0.00 19.31
September 0.00 0.00 0.00 0.108578E+09 0.00 0.00 0.688321E+11 0.00 14.78
October 0.00 0.00 0.00 0.106228E+09 0.00 0.00 0.648923E+11 0.00 12.34
November 0.00 0.00 0.00 95440412.85 0.00 0.00 0.739820E+11 0.00 10.87
December 3851347.53 0.00 0.00 96001866.70 0.00 0.00 0.816969E+11 0.00 10.58
                   
Annual Sum or Average 0.108023E+09 37597481.00 0.00 0.138505E+10 0.00 0.00 0.784898E+12 0.00 14.50
Minimum of Months 0.00 0.00 0.00 93130648.72 0.00 0.00 0.461950E+11 0.00 10.58
Maximum of Months 92272228.10 30187877.60 0.00 0.153078E+09 0.00 0.00 0.816969E+11 0.00 20.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.125984E+11 0.00 0.00 0.38
February 0.408901E+09 0.00 0.00 0.00 0.00 0.913686E+10 0.00 0.00 0.35
March 0.285876E+10 0.00 0.00 0.00 0.00 0.516057E+10 0.00 0.00 0.34
April 0.622892E+10 0.00 0.00 424563.21 0.00 0.559441E+09 0.324207E+09 0.00 0.35
May 0.442568E+10 0.00 0.00 6092260.42 0.00 0.00 0.300400E+10 0.00 0.49
June 0.533391E+09 1489331.48 0.00 18379798.09 0.00 0.00 0.623831E+10 0.00 0.73
July 0.755628E+09 5492376.63 0.00 18860544.51 0.00 0.00 0.543919E+10 0.00 0.70
August 0.274952E+10 0.00 0.00 9834497.72 0.00 0.00 0.379377E+10 0.00 0.58
September 0.726908E+10 0.00 0.00 96456.87 0.00 25366450.36 75275534.35 0.00 0.37
October 0.439043E+10 0.00 0.00 0.00 0.00 0.280920E+10 0.00 0.00 0.34
November 0.00 0.00 0.00 0.00 0.00 0.113880E+11 0.00 0.00 0.37
December 0.00 0.00 0.00 0.00 0.00 0.138187E+11 0.00 0.00 0.39
                   
Annual Sum or Average 0.296203E+11 6981708.11 0.00 53688120.83 0.00 0.554966E+11 0.188747E+11 0.00 0.45
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.34
Maximum of Months 0.726908E+10 5492376.63 0.00 18860544.51 0.00 0.138187E+11 0.623831E+10 0.00 0.73



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:50:54

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January -0.402264E+11 0.365448E+11 0.460464E+12 0.115280E+13 0.153320E+12
February 0.175456E+11 0.314498E+11 0.387962E+12 0.100022E+13 0.127717E+12
March 0.183981E+12 0.305779E+11 0.376632E+12 0.100343E+13 0.105048E+12
April 0.364412E+12 0.200873E+11 0.246242E+12 0.705375E+12 0.124908E+12
May 0.490351E+12 0.122555E+11 0.144263E+12 0.504706E+12 0.209174E+12
June 0.510199E+12 0.788036E+10 0.911228E+11 0.374074E+12 0.369855E+12
July 0.454258E+12 0.707193E+10 0.852626E+11 0.352413E+12 0.427920E+12
August 0.332988E+12 0.929579E+10 0.111685E+12 0.423167E+12 0.296046E+12
September 0.141376E+12 0.145408E+11 0.186278E+12 0.549386E+12 0.114095E+12
October 0.460282E+11 0.238644E+11 0.308681E+12 0.812811E+12 0.937236E+11
November -0.161029E+11 0.356349E+11 0.443467E+12 0.113102E+13 0.143308E+12
December -0.528910E+11 0.379835E+11 0.471476E+12 0.119130E+13 0.168424E+12
           
Annual Sum or Average 0.243192E+13 0.267187E+12 0.331354E+13 0.920070E+13 0.233354E+13
Minimum of Months -0.528910E+11 0.707193E+10 0.852626E+11 0.352413E+12 0.937236E+11
Maximum of Months 0.510199E+12 0.379835E+11 0.471476E+12 0.119130E+13 0.427920E+12