Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:49
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 08:49:12
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10706.47 | 943.69 | 943.69 |
Net Site Energy | 10706.47 | 943.69 | 943.69 |
Total Source Energy | 22970.84 | 2024.70 | 2024.70 |
Net Source Energy | 22970.84 | 2024.70 | 2024.70 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 554.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1503.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 545.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 194.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 640.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 591.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 86.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 110.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 2906.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 44.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5456.09 | 5250.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 554.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1503.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 545.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 194.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 591.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 86.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 110.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 2906.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 554.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1503.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 545.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 194.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 640.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 591.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 86.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 110.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 2906.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 44.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 200.34 | 305.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 215.37 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 480.91 | 462.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 200.34 | 305.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 215.37 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 480.91 | 462.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5456.087 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5456.087 | 100.00 |
Total On-Site and Utility Electric Sources | 5456.087 | 100.00 |
Total Electricity End Uses | 5456.087 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 576.18 | 58.63 |
Air to Air Heat Recovery for Heating | 406.62 | 41.37 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 982.81 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 15.17 |
Time Setpoint Not Met During Occupied Cooling | 73.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8031.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:49 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.7179 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 9.6995 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.6995 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.2862 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 9.2569 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.0417 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4132 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8577 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8577 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.7179 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 4.2862 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.7049 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 9.2569 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.0417 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4132 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7327 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4132 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.8577 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.8577 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.7137 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 18-AUG-19:19 | 09-JAN-17:30 | - | - | - | - | - | - | - | - | - | - | 29-MAR-20:19 |
Heating | 0.00 | 168093.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 161123.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 45764.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86131.51 | 89612.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31529.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31351.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3776.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3963.80 | 242717.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1343.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 385588.52 | 500423.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 168093.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 161123.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 45764.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 14636.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1225.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 31351.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3776.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3963.80 | 242717.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 431.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 670.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 601.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4762.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1728.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 614.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5220.66 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2028.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1874.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 273.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 349.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.38 | 3151.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 139.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 17279.43 | 5691.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 53.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 419.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 152.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 165.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 30.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 277.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1523.05 | 501.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 53.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 419.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 152.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 165.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 30.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 277.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1523.05 | 501.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.23 | 0.675071 | 0.574000 | 1.28 | 1.00 | 0.500000 | 0.000564 | 0.000069 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.306705 | 0.166637 | 0.387000 | 0.118695 | 0.461603 | 0.500000 | 0.002286 | 0.000030 | 0.122693 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.226723 | 0.261040 | 0.607000 | 0.137621 | 0.696106 | 0.500000 | 0.001460 | 0.000014 | 0.137621 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.200318 | 0.624772 | 0.010000 | 0.002003 | 1.00 | 0.500000 | 0.000610 | 0.000019 | 0.077183 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.110086 | 0.655909 | 0.787000 | 0.086638 | 1.00 | 0.500000 | 0.000581 | 0.000013 | 0.086638 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.38 | 0.017591 | 0.010000 | 0.033806 | 0.300000 | 0.500000 | 0.021659 | 0.000024 | 0.099946 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.37 | 0.104845 | 0.739000 | 1.01 | 0.739000 | 0.500000 | 0.003634 | 0.000106 | 1.01 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.64 | 0.214800 | 0.612000 | 2.84 | 0.612000 | 0.500000 | 0.001774 | 0.000270 | 2.84 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.19 | 0.998210 | 0.599000 | 0.712231 | 1.00 | 0.500000 | 0.000382 | 0.000116 | 0.712231 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.21 | 0.114412 | 0.807000 | 1.78 | 0.807000 | 0.500000 | 0.003330 | 0.000133 | 1.78 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.32 | 0.108990 | 0.768000 | 1.78 | 0.768000 | 0.500000 | 0.003496 | 0.000134 | 1.78 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.24 | 0.063337 | 0.246000 | 0.549909 | 0.300000 | 0.500000 | 0.010819 | 0.000048 | 0.549909 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.682595 | 0.460066 | 0.276000 | 0.188396 | 1.00 | 0.500000 | 0.000828 | 0.000069 | 0.285831 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 7935.69 | 0.000069 | 167.36 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3383.90 | 0.000030 | 92.35 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1617.04 | 0.000014 | 36.19 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2128.58 | 0.000019 | 58.09 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1538.27 | 0.000013 | 36.91 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 2756.35 | 0.000024 | 75.22 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 12083.98 | 0.000106 | 270.94 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 30913.76 | 0.000270 | 685.29 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5973.77 | 0.000052 | 170.71 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5983.50 | 0.000052 | 170.99 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 34213.53 | 0.000299 | 977.70 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 34410.53 | 0.000301 | 983.33 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5953.66 | 0.000052 | 170.14 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5963.39 | 0.000052 | 170.42 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 13211.93 | 0.000116 | 320.08 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1820.97 | 0.000016 | 52.04 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1824.81 | 0.000016 | 52.14 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8720.13 | 0.000076 | 249.18 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 15197.31 | 0.000133 | 328.45 |
DINING_FLR_6 VAV BOX REHEAT COIL | 15321.34 | 0.000134 | 331.40 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 5461.20 | 0.000048 | 119.82 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7883.71 | 0.000069 | 215.16 |
VAV WITH REHEAT HEATING COIL | 169005.91 | 0.001479 | 2852.48 |
FLR_3_DOAS HEATING COIL | 16512.40 | 0.000144 | 278.70 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.946636 | 0.000052 | 0.000302 |
ROOM_2_FLR_3 FAN COIL | 0.935839 | 0.000052 | 0.000299 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.35 | 0.000299 | 0.001670 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.72 | 0.000301 | 0.001902 |
ROOM_5_FLR_3 FAN COIL | 0.853194 | 0.000052 | 0.000274 |
ROOM_6_FLR_3 FAN COIL | 0.845524 | 0.000052 | 0.000272 |
ROOM_1_FLR_6 FAN COIL | 0.249777 | 0.000016 | 0.000080 |
ROOM_2_FLR_6 FAN COIL | 0.246675 | 0.000016 | 0.000079 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.12 | 0.000076 | 0.000363 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 0.946636 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 0.935839 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.35 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.72 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.853194 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.845524 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.249777 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.246675 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.12 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008710 | 12.80 | 0.008500 | 0.000302 | 0.946636 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008713 | 12.80 | 0.008500 | 0.000299 | 0.935839 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008623 | 12.80 | 0.008500 | 0.001670 | 5.35 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008866 | 12.80 | 0.008500 | 0.001902 | 5.72 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008734 | 12.80 | 0.008500 | 0.000274 | 0.853194 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008736 | 12.80 | 0.008500 | 0.000272 | 0.845524 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008699 | 12.80 | 0.008500 | 0.000080 | 0.249777 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008702 | 12.80 | 0.008500 | 0.000079 | 0.246675 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008779 | 12.80 | 0.008500 | 0.000363 | 1.12 | |
VAV WITH REHEAT COOLING COIL | 28.61 | 6.70 | 0.011863 | 10.92 | 0.008500 | 0.018578 | 21.00 | 649583.23 |
FLR_3_DOAS COOLING COIL | 34.40 | 6.70 | 0.014473 | 11.91 | 0.008500 | 0.002607 | 2.05 | 91161.11 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 13.04 | 10.53 | 21.11 | 10.53 | 21.00 | 21.00 | 0.300000 | 0.501505 | 21.00 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 21.00 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 9.33 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 21.00 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.018578 | 0.000026 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001479 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002607 | 0.000183 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000144 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.026427 | 4271.93 | |
HEATSYS1 PUMP | 0.003585 | 1069.03 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003585 | 0.430230 |
COOLSYS1 | 0.026427 | 3.17 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 409815.66 | 409815.66 | 0.003585 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.026427 | 2957.60 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.026427 | 924009.68 | 924599.42 | 105.40 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.718 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.098 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 4.286 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.976 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.257 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.637 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.042 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.112 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 13293.583 | 6.718 | 124.824 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13293.583 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 650.557 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 650.557 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 753.347 | 9.699 | 60.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 753.347 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 406.155 | 4.286 | 199.096 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 406.155 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1748.285 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1748.285 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11828.200 | 9.042 | 28.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11828.200 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1718.521 | 4.413 | 82.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.521 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.035 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.035 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1818.789 | 4.413 | 82.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.789 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9589 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.167 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8756 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6894 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6793 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.56372661E-17 | 0.35603042E-16 | -0.14834456E-09 | -0.22354951E-17 |
29 | 8 | 0.21681598E-07 | 0.12895413E-12 | 0.37576420E-03 | -0.24652724E-09 |
30 | 7 | -0.12181032E-01 | 0.67087143E-08 | -0.22998674E-01 | 0.13850277E-03 |
31 | 6 | 0.40370585 | 0.23395349E-05 | 0.47069069 | -0.47283774E-02 |
32 | 5 | -5.1745154 | 0.87537405E-04 | -4.4305073 | 0.62984858E-01 |
33 | 4 | 32.931872 | 0.71743813E-03 | 21.398312 | -0.42118042 |
34 | 3 | -111.07522 | 0.15662534E-02 | -55.540939 | 1.5130129 |
35 | 2 | 196.98158 | 0.88235367E-03 | 77.798628 | -2.8983416 |
36 | 1 | -171.10930 | 0.94326468E-04 | -55.232514 | 2.7446195 |
37 | 0 | 57.057407 | 0.53780718E-06 | 15.562302 | |
38 | 9 | 0.13788181E-14 | 0.42316407E-16 | -0.13850765E-09 | -0.36591458E-17 |
39 | 8 | 0.20295421E-07 | 0.15509090E-12 | 0.36099725E-03 | -0.23076592E-09 |
40 | 7 | -0.11739701E-01 | 0.81955471E-08 | -0.22363010E-01 | 0.13348467E-03 |
41 | 6 | 0.39171309 | 0.28760220E-05 | 0.46045976 | -0.45870120E-02 |
42 | 5 | -5.0574682 | 0.10819265E-03 | -4.3518524 | 0.61533536E-01 |
43 | 4 | 32.414067 | 0.89103805E-03 | 21.090697 | -0.41430552 |
44 | 3 | -109.97331 | 0.19536482E-02 | -54.932704 | 1.4970936 |
45 | 2 | 195.88922 | 0.11048200E-02 | 77.241099 | -2.8809953 |
46 | 1 | -170.70571 | 0.11852782E-03 | -55.070977 | 2.7375462 |
47 | 0 | 57.057407 | 0.67841551E-06 | 15.589460 | |
48 | 9 | 0.13857471E-14 | 0.43057560E-16 | -0.13784678E-09 | -0.68945926E-17 |
49 | 8 | 0.20202246E-07 | 0.15680163E-12 | 0.35999259E-03 | -0.22970649E-09 |
50 | 7 | -0.11709634E-01 | 0.82948599E-08 | -0.22319691E-01 | 0.13314280E-03 |
51 | 6 | 0.39089600 | 0.29121450E-05 | 0.45976168 | -0.45773805E-02 |
52 | 5 | -5.0494928 | 0.10959277E-03 | -4.3464810 | 0.61434646E-01 |
53 | 4 | 32.378781 | 0.90287364E-03 | 21.069680 | -0.41383702 |
54 | 3 | -109.89821 | 0.19801908E-02 | -54.891143 | 1.4960086 |
55 | 2 | 195.81476 | 0.11201274E-02 | 77.203021 | -2.8798128 |
56 | 1 | -170.67819 | 0.12019965E-03 | -55.059979 | 2.7370639 |
57 | 0 | 57.057407 | 0.68811227E-06 | 15.591337 | |
58 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
59 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
60 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
61 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
62 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
63 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
64 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
65 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
66 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
67 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
68 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
69 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
70 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
71 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
72 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
73 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
74 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
75 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
76 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
77 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
78 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
79 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
80 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
81 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
82 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
83 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
84 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
85 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
86 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
87 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
88 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
89 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
90 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
91 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
92 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
93 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.43_SHGC_0.248 | 37 | 1 | VerySmooth | 2.443 | 2.443 | 1.000 | 0.249 | ||
2 | RESWINDOW_U_0.43_SHGC_0.248 | 38 | 1 | VerySmooth | 2.443 | 2.443 | 1.000 | 0.249 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.91147E-002 | 0.15938 | 0.62162 | 0.62162 | 0.27280 | 0.15674 | 0.22697 | 0.00000 | 0.84000 | 0.84000 | 0.12243 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.91147E-002 | 0.15938 | 0.62162 | 0.62162 | 0.27280 | 0.15674 | 0.22697 | 0.00000 | 0.84000 | 0.84000 | 0.12243 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.7749E-002 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.0000E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1093 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.3218E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.1393E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.5745E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.8929E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.5818E-003 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1071 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.9122E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1194 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.3048E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.8370E-002 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.2591E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2502E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3131E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.2924E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3032E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7730E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.8813E-003 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7162E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.8597E-003 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8489E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0072E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.2924E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3032E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7730E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.8813E-003 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7162E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.8597E-003 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8489E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0072E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 29639.36415 | 29639.36415 | 2.23364 | 2.23364 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 28.93750 | 1.44633E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1409.47211 | 1409.47211 | 6.26617E-002 | 0.85446 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4069.19549 | 4069.19549 | 0.30671 | 0.30671 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2759.94876 | 2759.94876 | 0.12269 | 0.12269 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3008.10186 | 3008.10186 | 0.22672 | 0.22672 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 31.88250 | 1.44687E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 917.17535 | 917.17535 | 4.07745E-002 | 9.17347E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2658.34472 | 2658.34472 | 0.20032 | 0.20032 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 31.17000 | 1.44674E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1736.15782 | 1736.15782 | 7.71834E-002 | 7.71834E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1460.89760 | 1460.89760 | 0.11009 | 0.11009 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 31.88250 | 1.44687E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1097.73684 | 1097.73684 | 4.88015E-002 | 5.77652E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44856.70184 | 44856.70184 | 3.38057 | 3.38057 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 33.92500 | 1.44724E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2248.27407 | 2248.27407 | 9.99464E-002 | 9.99464E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18195.99581 | 18195.99581 | 1.37262 | 1.37262 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40000 | 1.44733E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6924.78669 | 6924.78669 | 0.30784 | 0.67639 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 61555.17519 | 61555.17519 | 4.64076 | 4.64076 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 16469.86563 | 16469.86563 | 0.73219 | 1.89399 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 9321.38266 | 9321.38266 | 0.94664 | 0.94664 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5973.91821 | 5973.91821 | 0.26713 | 0.26713 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9215.05771 | 9215.05771 | 0.93584 | 0.93584 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5983.64462 | 5983.64462 | 0.26756 | 0.26756 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 52697.89836 | 52697.89836 | 5.35130 | 5.35130 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 34213.93716 | 34213.93716 | 1.52996 | 1.52996 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 56310.30829 | 56310.30829 | 5.71858 | 5.71858 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 34.02000 | 1.44726E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 34410.93486 | 34410.93486 | 1.53876 | 1.53876 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8401.25540 | 8401.25540 | 0.85319 | 0.85319 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5953.79948 | 5953.79948 | 0.26623 | 0.26623 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 8325.72996 | 8325.72996 | 0.84552 | 0.84552 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 31.26500 | 1.44675E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5963.53148 | 5963.53148 | 0.26666 | 0.26666 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 15778.12404 | 15778.12404 | 1.18903 | 1.18903 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9588.83422 | 9588.83422 | 0.42629 | 0.47476 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2459.52012 | 2459.52012 | 0.24978 | 0.24978 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.07000 | 1.44708E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1821.01668 | 1821.01668 | 8.14280E-002 | 8.14280E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2428.96898 | 2428.96898 | 0.24667 | 0.24667 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1824.84856 | 1824.84856 | 8.15994E-002 | 8.15994E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 10997.05567 | 10997.05567 | 1.11682 | 1.11682 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8720.28859 | 8720.28859 | 0.38994 | 0.38994 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29274.23476 | 29274.23476 | 2.20888 | 2.20888 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 6128.56303 | 6128.56303 | 0.27245 | 1.18780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30731.26783 | 30731.26783 | 2.31878 | 2.31878 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6261.49172 | 6261.49172 | 0.27836 | 1.18780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | -6.30000 | 2.29779E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29584.15966 | 29584.15966 | 2.23540 | 2.23540 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.54500 | 1.44717E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2668.88572 | 2668.88572 | 0.11864 | 0.36735 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -6.30000 | 2.29779E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9057.86495 | 9057.86495 | 0.68260 | 0.68260 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 34.40000 | 1.44733E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6429.41051 | 6429.41051 | 0.28583 | 0.28583 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | -6.30000 | 2.29779E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 387357.65 | 20.99541 | 20.99541 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 197959.73 | 7.37769 | 7.37769 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 51689.19 | 15.65139 | 2.05125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 55039.41 | 4.68927 | 2.05125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23364 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.67507 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57400 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28211 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.64385E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.94249E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28211 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7935.69349 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.94249E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 167.35947 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.30671 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16664 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.38700 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11869 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46160 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.28641E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.96039E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12269 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3383.90355 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.96039E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 92.35088 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22672 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26104 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.60700 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13762 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69611 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45955E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.41465E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13762 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1617.03537 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.41465E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.19040 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.20032 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.62477 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.00318E-003 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.09823E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.86218E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.71834E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2128.58221 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.86218E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 58.08999 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.11009 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.65591 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.78700 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.66378E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.80873E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.34575E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.66378E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1538.27110 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34575E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.90735 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.38057 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.75906E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.38057E-002 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16593E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.41137E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.99464E-002 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2756.34836 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.41137E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 75.22204 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.37262 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10485 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.73900 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01437 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73900 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.63393E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05716E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01437 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12083.98120 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05716E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 270.93832 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.64076 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21480 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.61200 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.84015 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61200 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.77374E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.70447E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.84015 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30913.75872 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.70447E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 685.29393 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.94664 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.94664 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.22612E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.02414E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70359 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71015E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.02414E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.94664 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5973.77354 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.22612E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 170.71175 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.93584 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.93584 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.23463E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.99181E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70359 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71290E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.99181E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.93584 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5983.49973 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.23463E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 170.98962 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.35130 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.35130 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.99315E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.67024E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70438 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62281E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.67024E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.35130 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 34213.53091 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.99315E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 977.70158 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.71858 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.71858 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.01038E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.90187E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70347 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.86565E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.90187E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.71858 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 34410.52645 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.01038E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 983.32970 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.85319 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.85319 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.20852E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.74255E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70355 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.73368E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.74255E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.85319 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5953.65525 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.20852E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 170.13699 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.84552 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.84552 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.21703E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.71947E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70355 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.73587E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.71947E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.84552 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5963.38703 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.21703E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 170.41501 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18903 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.99821 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59900 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71223 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81683E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.15584E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71223 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13211.93238 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15584E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 320.07548 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24978 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.24978 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.59307E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.95620E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70361 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.69912E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.95620E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.24978 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1820.97423 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.59307E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 52.03526 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24667 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.24667 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.59642E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.86298E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70361 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.70182E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.86298E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.24667 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1824.80603 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.59642E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 52.14473 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.11682 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.11682 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.62875E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.63261E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70341 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.77897E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.63261E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.11682 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8720.12539 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.62875E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 249.18032 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.20888 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11441 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.80700 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78256 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80700 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.33006E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.32953E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78256 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15197.30590 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.32953E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 328.44556 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.31878 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10899 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.76800 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78082 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76800 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.49575E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.34038E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78082 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15321.34022 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34038E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 331.40127 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23540 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.33372E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24600 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.54991 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08195E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.77770E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54991 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5461.20283 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.77770E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 119.82384 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68260 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.46007 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27600 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18840 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.28141E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.89701E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28583 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7883.70531 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.89701E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 215.16066 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 13.03930 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 10.52931 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.10612 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 10.52931 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 20.99541 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 20.99541 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50151 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 20.99541 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 20.99541 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 9.32920 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.61464 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.92058 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.18632E-002 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 649583.22623 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.85780E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 20.99541 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 169005.91272 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47854E-003 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2852.48243 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 20.99541 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.85780E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.56320E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.47854E-003 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 34.40000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.90668 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.44733E-002 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 91161.10877 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.60720E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 16512.40431 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44458E-004 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 278.69642 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.60720E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.82645E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.44458E-004 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.64266E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4271.93042 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.58525E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.43023 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.58525E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1069.02841 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 409815.65625 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 409815.66000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.58525E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.64266E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.17119 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.64266E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2957.60151 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.64266E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 924009.68141 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 924599.42000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 105.40433 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 7976.39 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3396.92 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1624.78 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2136.77 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1545.08 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 2766.95 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 12141.79 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 31063.30 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 6434.67 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 6445.15 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 36853.09 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 37065.25 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 6413.00 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 6423.48 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 13269.88 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1961.41 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1965.54 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9392.63 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 15273.60 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 15398.20 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 5488.28 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7914.04 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 125692.96 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 12280.59 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 15855.69 | 13333.43 | 2522.27 | 0.84 | 3442.16 | 34.91 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 15682.48 | 13183.88 | 2498.60 | 0.84 | 3401.47 | 34.50 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 88219.98 | 74903.27 | 13316.71 | 0.85 | 19725.11 | 200.06 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 98416.42 | 81443.27 | 16973.15 | 0.83 | 20415.50 | 207.07 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 14352.14 | 12038.46 | 2313.67 | 0.84 | 3094.86 | 31.39 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 14228.62 | 11932.08 | 2296.54 | 0.84 | 3066.04 | 31.10 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4175.43 | 3515.40 | 660.04 | 0.84 | 909.81 | 9.23 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4125.55 | 3472.39 | 653.16 | 0.84 | 898.12 | 9.11 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 18935.89 | 15808.26 | 3127.63 | 0.83 | 4025.38 | 40.83 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 610029.12 | 398862.57 | 211166.55 | 0.65 | 92084.32 | 933.97 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 64827.35 | 41208.20 | 23619.15 | 0.64 | 8819.06 | 89.45 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.7023024219E-002 | 2.1958455894E-002 | Pass | Pass | 5.2541085016E-003 | 1.6967467783E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.0093417171E-003 | 7.4379430186E-004 | Pass | Pass | 0.3314896878 | 1.9068126850 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.6077175226E-002 | 2.5354526284E-002 | Pass | Pass | 1.0552947960E-002 | 2.8294719668E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.6380026197E-002 | 1.7297755248E-002 | Pass | Pass | 5.4520252633E-003 | 1.7081014633E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.1662947387E-004 | 3.8267707821E-004 | Pass | Pass | 2.7511207871E-002 | 4.2056121977E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.5283171032E-004 | 2.5808945587E-004 | Pass | Pass | 2.0991829383E-002 | 6.1356651997E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.0638529476E-002 | 2.8199003502E-002 | Pass | Pass | 2.3725821040E-002 | 6.5639213790E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7661241852E-002 | 4.5482578570E-002 | Pass | Pass | 1.1788019912E-002 | 2.8544077175E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.8939743192E-002 | 0.1823948405 | Pass | Pass | 0.1369741067 | 0.5765411124 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.0526768998E-002 | 0.1882323782 | Pass | Pass | 0.1342235466 | 0.5669121183 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.4360810601E-002 | 4.2916044719E-002 | Pass | Pass | 7.2682661499E-003 | 7.1809990479E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.2527480296E-002 | 0.1015032807 | Pass | Pass | 0.2265788910 | 0.8784614809 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.7486259052E-002 | 0.1773776044 | Pass | Pass | 0.1450613325 | 0.6199772622 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.9058764476E-002 | 0.1831485778 | Pass | Pass | 0.1331024265 | 0.5471629522 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.9479003353E-004 | 3.0149655490E-004 | Pass | Pass | 5.8063588362E-002 | 0.1324523822 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.9559253796E-002 | 0.2493621801 | Pass | Pass | 9.0458606066E-002 | 0.3300242709 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.1051799541E-002 | 0.2549535638 | Pass | Pass | 8.8647301614E-002 | 0.3211513974 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.1066188843E-002 | 0.1281586760 | Pass | Pass | 8.5161095370E-002 | 0.2647463620 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.7902181747E-002 | 9.5742477149E-002 | Pass | Pass | 1.0511290252E-002 | 2.3147093384E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.9787740482E-002 | 9.2149722791E-002 | Pass | Pass | 8.9996260848E-003 | 2.0374856973E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.6518426365E-004 | 1.8965061258E-003 | Pass | Pass | 2.2571213309E-002 | 4.4888977297E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.3952635411E-003 | 5.8740096464E-003 | Pass | Pass | 3.3423212255E-002 | 5.0052067283E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3005.88 | 48.53 | 559.57 | 2157.91 | 6670.06 | 12441.95 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.443 | 0.249 | 0.274 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.443 | 0.249 | 0.274 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.443 | 0.249 | 0.274 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.443 | 0.249 | 0.274 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.443 | 0.249 | 0.274 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.443 | 0.249 | 0.274 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.443 | 0.249 | 0.274 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.443 | 0.249 | 0.274 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.443 | 0.249 | 0.274 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.443 | 0.249 | 0.274 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.443 | 0.249 | 0.274 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.443 | 0.249 | 0.274 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.443 | 0.249 | 0.274 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.443 | 0.249 | 0.274 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.443 | 0.249 | 0.274 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.443 | 0.249 | 0.274 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.443 | 0.249 | 0.274 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.443 | 0.249 | 0.274 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.443 | 0.249 | 0.274 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.443 | 0.249 | 0.274 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.443 | 0.249 | 0.274 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.443 | 0.249 | 0.274 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.443 | 0.249 | 0.274 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.443 | 0.249 | 0.274 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.443 | 0.249 | 0.274 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.443 | 0.249 | 0.274 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.443 | 0.249 | 0.274 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.443 | 0.249 | 0.274 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.443 | 0.249 | 0.274 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.443 | 0.249 | 0.274 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.443 | 0.249 | 0.274 | |||||||||||||||||
North Total or Average | 432.95 | 2.443 | 0.249 | 0.274 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.443 | 0.249 | 0.274 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.7179 | 1978.83 | 13293.58 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 122.93 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 9.6995 | 67.07 | 650.56 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.26 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 9.6995 | 77.67 | 753.35 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.25 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 4.2862 | 94.76 | 406.16 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 2.31 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.7049 | 78.04 | 445.21 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 9.2569 | 188.86 | 1748.29 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.29 | 0.0000 | Y | 12.90 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.0417 | 1308.19 | 11828.20 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.53 | 0.0000 | Y | 92.21 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.78 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.79 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4132 | 1557.62 | 6874.08 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 56.74 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 6.96 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.27 | 0.0000 | Y | 28.40 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.27 | 0.0000 | Y | 28.40 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7327 | 103.30 | 1212.04 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4132 | 412.12 | 1818.79 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 15.01 |
Interior Lighting Total | 5.8577 | 11345.29 | 66457.67 | 366.16 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.77 | 83.77 | 194.02 | |
Exterior Lighting Total | 12338.45 | 194.02 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 409815.66 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 924599.42 | 2.96 | 924761.94 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10574.17 | 15855.69 | 13333.43 | 2522.27 | 0.84 | - | 3442.16 | 34.91 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10461.12 | 15682.48 | 13183.88 | 2498.60 | 0.84 | - | 3401.47 | 34.50 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 58401.43 | 88219.98 | 74903.27 | 13316.71 | 0.85 | - | 19725.11 | 200.06 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 66500.62 | 98416.42 | 81443.27 | 16973.15 | 0.83 | - | 20415.50 | 207.07 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9589.57 | 14352.14 | 12038.46 | 2313.67 | 0.84 | - | 3094.86 | 31.39 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9508.84 | 14228.62 | 11932.08 | 2296.54 | 0.84 | - | 3066.04 | 31.10 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2781.95 | 4175.43 | 3515.40 | 660.04 | 0.84 | - | 909.81 | 9.23 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2749.36 | 4125.55 | 3472.39 | 653.16 | 0.84 | - | 898.12 | 9.11 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 12701.72 | 18935.89 | 15808.26 | 3127.63 | 0.83 | - | 4025.38 | 40.83 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 649583.23 | 610029.12 | 398862.57 | 211166.55 | 0.65 | - | 92084.32 | 933.97 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 91161.11 | 64827.35 | 41208.20 | 23619.15 | 0.64 | - | 8819.06 | 89.45 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 7935.69 | 7976.39 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3383.90 | 3396.92 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1617.04 | 1624.78 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2128.58 | 2136.77 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1538.27 | 1545.08 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2756.35 | 2766.95 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12083.98 | 12141.79 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 30913.76 | 31063.30 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5973.77 | 6434.67 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5983.50 | 6445.15 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 34213.53 | 36853.09 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 34410.53 | 37065.25 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5953.66 | 6413.00 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5963.39 | 6423.48 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13211.93 | 13269.88 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1820.97 | 1961.41 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1824.81 | 1965.54 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 8720.13 | 9392.63 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 15197.31 | 15273.60 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 15321.34 | 15398.20 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 5461.20 | 5488.28 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7883.71 | 7914.04 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 169005.91 | 125692.96 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 16512.40 | 12280.59 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.95 | 666.09 | 703.64 | 1.00 | 1.21 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.94 | 658.49 | 703.64 | 1.00 | 1.21 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.35 | 3765.37 | 703.64 | 1.00 | 0.97 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.72 | 4023.80 | 703.64 | 1.00 | 0.96 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.85 | 600.34 | 703.64 | 1.00 | 1.24 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.85 | 594.94 | 703.64 | 1.00 | 1.24 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.25 | 175.75 | 703.64 | 1.00 | 1.85 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.25 | 173.57 | 703.64 | 1.00 | 1.86 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.12 | 785.84 | 703.64 | 1.00 | 1.17 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 21.00 | 47043.13 | 2240.64 | 1.00 | 1.11 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.026427 | 4271.93 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003585 | 1069.03 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.026427 | 2957.60 | 111917.77 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 29639.36 | 29639.36 | 14.98 | 2.234 | 2.234 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 24.00 | 24.00 | 0.00931 | 28.94 | 0.01446 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4069.20 | 4069.20 | 60.67 | 0.307 | 0.307 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00926 | 34.40 | 0.01447 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3008.10 | 3008.10 | 38.73 | 0.227 | 0.227 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00952 | 31.88 | 0.01447 | 0.092 | 0.00 |
MECH_FLR_1 | 2658.34 | 2658.34 | 16.19 | 0.200 | 0.200 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 24.00 | 24.00 | 0.00896 | 31.17 | 0.01447 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1460.90 | 1460.90 | 15.42 | 0.110 | 0.110 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00906 | 31.88 | 0.01447 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44856.70 | 44856.70 | 574.80 | 3.381 | 3.381 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00856 | 33.92 | 0.01447 | 0.000 | 0.00 |
CAFE_FLR_1 | 18196.00 | 18196.00 | 96.35 | 1.373 | 1.373 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 23.99 | 0.01033 | 34.40 | 0.01447 | 0.676 | 0.00 |
LOBBY_FLR_1 | 61555.18 | 61555.18 | 47.05 | 4.641 | 4.641 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 23.99 | 0.01011 | 34.40 | 0.01447 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9321.38 | 9321.38 | 238.87 | 0.947 | 0.947 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00871 | 32.91 | 0.01447 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9215.06 | 9215.06 | 236.18 | 0.936 | 0.936 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00871 | 32.75 | 0.01447 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 52697.90 | 52697.90 | 2148.84 | 5.351 | 5.351 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00862 | 34.40 | 0.01447 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 56310.31 | 56310.31 | 2295.52 | 5.719 | 5.719 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 21.11 | 21.11 | 0.00887 | 34.02 | 0.01447 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8401.26 | 8401.26 | 215.30 | 0.853 | 0.853 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 21.11 | 21.11 | 0.00873 | 31.50 | 0.01447 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8325.73 | 8325.73 | 213.38 | 0.846 | 0.846 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 21.11 | 21.11 | 0.00874 | 31.26 | 0.01447 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 15778.12 | 15778.12 | 40.52 | 1.189 | 1.189 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00981 | 34.30 | 0.01447 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2459.52 | 2459.52 | 63.03 | 0.250 | 0.250 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00870 | 33.07 | 0.01447 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2428.97 | 2428.97 | 62.25 | 0.247 | 0.247 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00870 | 32.91 | 0.01447 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10997.06 | 10997.06 | 448.30 | 1.117 | 1.117 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00878 | 34.40 | 0.01447 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29274.23 | 29274.23 | 88.27 | 2.209 | 2.209 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.98 | 0.01045 | 34.40 | 0.01447 | 1.188 | 0.00 |
DINING_FLR_6 | 30731.27 | 30731.27 | 92.66 | 2.319 | 2.319 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.98 | 0.01036 | 34.40 | 0.01447 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29584.16 | 29584.16 | 286.38 | 2.235 | 2.235 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01016 | 33.55 | 0.01447 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9057.86 | 9057.86 | 21.98 | 0.683 | 0.683 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00915 | 34.40 | 0.01447 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1409.47 | 1409.47 | 0.71 | 0.063 | 0.854 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00796 | -6.30 | 0.00230 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2759.95 | 2759.95 | 41.15 | 0.123 | 0.123 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00754 | -6.30 | 0.00230 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 917.18 | 917.18 | 11.81 | 0.041 | 0.092 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00747 | -6.30 | 0.00230 | 0.092 | 0.00 |
MECH_FLR_1 | 1736.16 | 1736.16 | 10.57 | 0.077 | 0.077 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00736 | -6.30 | 0.00230 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1097.74 | 1097.74 | 11.58 | 0.049 | 0.058 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00741 | -6.30 | 0.00230 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2248.27 | 2248.27 | 28.81 | 0.100 | 0.100 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00733 | -6.30 | 0.00230 | 0.000 | 0.00 |
CAFE_FLR_1 | 6924.79 | 6924.79 | 36.67 | 0.308 | 0.676 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00759 | -6.30 | 0.00230 | 0.676 | 0.00 |
LOBBY_FLR_1 | 16469.87 | 16469.87 | 12.59 | 0.732 | 1.894 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00752 | -6.30 | 0.00230 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5973.92 | 5973.92 | 153.09 | 0.267 | 0.267 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00751 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5983.64 | 5983.64 | 153.36 | 0.268 | 0.268 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00751 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 34213.94 | 34213.94 | 1395.13 | 1.530 | 1.530 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00755 | -6.30 | 0.00230 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 34410.93 | 34410.93 | 1402.78 | 1.539 | 1.539 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00755 | -6.30 | 0.00230 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5953.80 | 5953.80 | 152.58 | 0.266 | 0.266 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00751 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5963.53 | 5963.53 | 152.84 | 0.267 | 0.267 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00751 | -6.30 | 0.00230 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 9588.83 | 9588.83 | 24.62 | 0.426 | 0.475 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00762 | -6.30 | 0.00230 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1821.02 | 1821.02 | 46.67 | 0.081 | 0.081 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00760 | -6.30 | 0.00230 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1824.85 | 1824.85 | 46.77 | 0.082 | 0.082 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00760 | -6.30 | 0.00230 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8720.29 | 8720.29 | 355.49 | 0.390 | 0.390 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00761 | -6.30 | 0.00230 | 0.099 | 0.00 |
BANQUET_FLR_6 | 6128.56 | 6128.56 | 18.48 | 0.272 | 1.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00770 | -6.30 | 0.00230 | 1.188 | 0.00 |
DINING_FLR_6 | 6261.49 | 6261.49 | 18.88 | 0.278 | 1.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 21.00 | 21.00 | 0.00770 | -6.30 | 0.00230 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2668.89 | 2668.89 | 25.84 | 0.119 | 0.367 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00697 | -6.30 | 0.00230 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6429.41 | 6429.41 | 15.60 | 0.286 | 0.286 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 21.00 | 21.00 | 0.00775 | -6.30 | 0.00230 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 21.00 | 21.00 | 7.38 | 7.38 | 20.9954 | 10.5293 | 20.9954 | 0.5015 | 0.3000 |
FLR_3_DOAS | 15.65 | 2.05 | 4.69 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 7935.693 | 7935.693 | 1.282112 | 0.00006942 | 167.359 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7935.69 | 7935.69 | 1.282112 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00795837 | 49.6062 | 1409.47 | 0.00 | 7980.12 | 7980.12 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3383.904 | 3383.904 | 0.122693 | 0.00002960 | 92.351 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 3383.90 | 3383.90 | 0.122693 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00754171 | 47.0423 | 2759.95 | 0.00 | 3400.68 | 3400.68 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1617.035 | 1617.035 | 0.137621 | 0.00001415 | 36.190 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1617.04 | 1617.04 | 0.137621 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00747448 | 46.6266 | 917.18 | 0.00 | 1625.79 | 1625.79 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2128.582 | 2128.582 | 0.077183 | 0.00001862 | 58.090 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2128.58 | 2128.58 | 0.077183 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00735855 | 45.9119 | 1736.16 | 0.00 | 2139.14 | 2139.14 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1538.271 | 1538.271 | 0.086638 | 0.00001346 | 36.907 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1538.27 | 1538.27 | 0.086638 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00740887 | 46.2222 | 1097.74 | 0.00 | 1546.32 | 1546.32 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 2756.348 | 2756.348 | 0.099946 | 0.00002411 | 75.222 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2756.35 | 2756.35 | 0.099946 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00732776 | 45.7234 | 2248.27 | 0.00 | 2770.02 | 2770.02 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 12083.981 | 12083.981 | 1.014367 | 0.00010572 | 270.938 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12083.98 | 12083.98 | 1.014367 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00759233 | 47.3538 | 6924.79 | 0.00 | 12149.39 | 12149.39 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 30913.759 | 30913.759 | 2.840147 | 0.00027045 | 685.294 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 30913.76 | 30913.76 | 2.840147 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00751721 | 46.8905 | 16469.87 | 0.00 | 31081.85 | 31081.85 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 10574.165 | -999.000 | 0.946636 | 0.00030241 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 10574.17 | 10079.24 | 0.946636 | 21.70 | 15.38 | 0.00871015 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00871015 | 53.8622 | 9321.38 | 0.00 | 10967.07 | 10967.07 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5973.774 | 5973.774 | 0.267128 | 0.00005226 | 170.712 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 5973.77 | 5973.77 | 0.267128 | 21.11 | 14.09 | 0.00751388 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00751388 | 46.5526 | 5973.92 | 0.00 | 6439.85 | 6439.85 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 10461.124 | -999.000 | 0.935839 | 0.00029918 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 10461.12 | 9965.40 | 0.935839 | 21.70 | 15.38 | 0.00871290 | 12.80 | 11.77 | 0.00850000 | 32.75 | 0.01447025 | 23.10 | 0.0000 | 21.11 | 0.00871290 | 53.8790 | 9215.06 | 0.00 | 10849.63 | 10849.63 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5983.500 | 5983.500 | 0.267563 | 0.00005235 | 170.990 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 5983.50 | 5983.50 | 0.267563 | 21.11 | 14.09 | 0.00751464 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00751464 | 46.5573 | 5983.64 | 0.00 | 6450.33 | 6450.33 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 58401.430 | -999.000 | 5.351299 | 0.00167024 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 58401.43 | 56772.41 | 5.351299 | 21.70 | 15.31 | 0.00862281 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 0.0000 | 21.11 | 0.00862281 | 53.3272 | 52697.90 | 0.00 | 60598.62 | 60598.62 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 34213.531 | 34213.531 | 1.529955 | 0.00029931 | 977.702 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 34213.53 | 34213.53 | 1.529955 | 21.11 | 14.12 | 0.00754717 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00754717 | 46.7550 | 34213.94 | 0.00 | 36883.17 | 36883.17 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 66500.620 | -999.000 | 5.718579 | 0.00190187 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | 7/21 15:40:00 | 66500.62 | 61266.17 | 5.718579 | 21.70 | 15.52 | 0.00886565 | 12.80 | 11.77 | 0.00850000 | 34.02 | 0.01447257 | 23.44 | 0.0000 | 21.11 | 0.00886565 | 54.8101 | 56310.31 | 0.00 | 68923.77 | 65349.75 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 34410.526 | 34410.526 | 1.538765 | 0.00030104 | 983.330 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 34410.53 | 34410.53 | 1.538765 | 21.11 | 14.13 | 0.00754944 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00754944 | 46.7690 | 34410.93 | 0.00 | 37095.54 | 37095.54 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9589.566 | -999.000 | 0.853194 | 0.00027426 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | 7/21 10:30:00 | 9589.57 | 9093.08 | 0.853194 | 21.70 | 15.40 | 0.00873368 | 12.80 | 11.77 | 0.00850000 | 31.50 | 0.01446797 | 22.76 | 0.0000 | 21.11 | 0.00873368 | 54.0057 | 8401.26 | 0.00 | 9945.85 | 9749.92 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5953.655 | 5953.655 | 0.266228 | 0.00005209 | 170.137 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 5953.66 | 5953.66 | 0.266228 | 21.11 | 14.09 | 0.00751238 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00751238 | 46.5434 | 5953.80 | 0.00 | 6418.16 | 6418.16 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9508.841 | -999.000 | 0.845524 | 0.00027195 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | 7/21 10:20:00 | 9508.84 | 9012.14 | 0.845524 | 21.70 | 15.40 | 0.00873587 | 12.80 | 11.77 | 0.00850000 | 31.26 | 0.01446754 | 22.70 | 0.0000 | 21.11 | 0.00873587 | 54.0191 | 8325.73 | 0.00 | 9861.98 | 9662.24 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5963.387 | 5963.387 | 0.266663 | 0.00005217 | 170.415 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 5963.39 | 5963.39 | 0.266663 | 21.11 | 14.09 | 0.00751314 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00751314 | 46.5481 | 5963.53 | 0.00 | 6428.65 | 6428.65 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 13211.932 | 13211.932 | 0.712231 | 0.00011558 | 320.075 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 13211.93 | 13211.93 | 0.712231 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00762387 | 47.5468 | 9588.83 | 0.00 | 13280.77 | 13280.77 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2781.951 | -999.000 | 0.249777 | 0.00007956 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 2781.95 | 2658.27 | 0.249777 | 21.70 | 15.37 | 0.00869912 | 12.80 | 11.77 | 0.00850000 | 33.07 | 0.01447082 | 23.19 | 0.0000 | 21.11 | 0.00869912 | 53.7949 | 2459.52 | 0.00 | 2885.53 | 2885.53 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1820.974 | 1820.974 | 0.081428 | 0.00001593 | 52.035 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1820.97 | 1820.97 | 0.081428 | 21.11 | 14.17 | 0.00759503 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00759503 | 47.0493 | 1821.02 | 0.00 | 1963.05 | 1963.05 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2749.357 | -999.000 | 0.246675 | 0.00007863 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 2749.36 | 2625.55 | 0.246675 | 21.70 | 15.37 | 0.00870182 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00870182 | 53.8114 | 2428.97 | 0.00 | 2851.67 | 2851.67 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1824.806 | 1824.806 | 0.081599 | 0.00001596 | 52.145 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1824.81 | 1824.81 | 0.081599 | 21.11 | 14.17 | 0.00759585 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00759585 | 47.0543 | 1824.85 | 0.00 | 1967.18 | 1967.18 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12701.716 | -999.000 | 1.116824 | 0.00036326 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 12701.72 | 11924.43 | 1.116824 | 21.70 | 15.44 | 0.00877897 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 0.0000 | 21.11 | 0.00877897 | 54.2822 | 10997.06 | 0.00 | 13169.71 | 12761.63 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8720.125 | 8720.125 | 0.389939 | 0.00007629 | 249.180 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8720.13 | 8720.13 | 0.389939 | 21.11 | 14.18 | 0.00760952 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00760952 | 47.1376 | 8720.29 | 0.00 | 9400.50 | 9400.50 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15197.306 | 15197.306 | 1.782565 | 0.00013295 | 328.446 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 15197.31 | 15197.31 | 1.782565 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00769868 | 48.0081 | 6128.56 | 0.00 | 15281.72 | 15281.72 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15321.340 | 15321.340 | 1.780823 | 0.00013404 | 331.401 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 15321.34 | 15321.34 | 1.780823 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00770475 | 48.0457 | 6261.49 | 0.00 | 15406.42 | 15406.42 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 5461.203 | 5461.203 | 0.549909 | 0.00004778 | 119.824 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 5461.20 | 5461.20 | 0.549909 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00696757 | 43.5061 | 2668.89 | 0.00 | 5491.41 | 5491.41 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7883.705 | 7883.705 | 0.285831 | 0.00006897 | 215.161 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 7883.71 | 7883.71 | 0.285831 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00774613 | 48.3003 | 6429.41 | 0.00 | 7922.80 | 7922.80 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 649583.226 | -999.000 | 20.995413 | 0.01857800 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 649583.23 | 439175.42 | 20.995413 | 28.61 | 20.15 | 0.01186321 | 10.92 | 10.92 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 44.4345 | 23.99 | 0.00978257 | 50.6935 | 278404.24 | 0.00 | 663646.45 | 437459.03 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 169005.913 | 169005.913 | 6.298624 | 0.00147854 | 2852.482 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 169005.91 | 169005.91 | 6.298624 | -6.30 | -6.30 | 0.00229779 | 16.70 | 12.85 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 148.1149 | 21.01 | 0.00758909 | 47.3132 | 63656.17 | 0.00 | 151988.69 | 151988.69 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 91161.109 | -999.000 | 2.051317 | 0.00260720 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 91161.11 | 55491.40 | 2.051317 | 34.40 | 23.54 | 0.01447326 | 11.91 | 11.41 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 99.9965 | 21.11 | 0.00874979 | 54.1028 | 153689.42 | 0.00 | 92683.44 | 56170.47 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 16512.404 | 16512.404 | 0.615395 | 0.00014446 | 278.696 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 16512.40 | 16512.40 | 0.615395 | -6.30 | -6.30 | 0.00229779 | 16.70 | 12.85 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 333.3216 | 21.11 | 0.00754861 | 46.7639 | 104865.92 | 0.00 | 14849.77 | 14849.77 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 7935.693 | 7935.693 | 1.282112 | 0.00006942 | 167.359 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 1.8982 | 1.936406 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7935.69 | 7935.69 | 1.0000 | 1.48850157 | 1.282112 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.06941783 | 60.00 | 32.22 | 27.78 | 0.000 | 7935.69 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00795837 | 21.00 | 0.00795837 | 49.6062 | 1409.47 | 0.00 | 7980.12 | 7980.12 | 1.48850157 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.86 | 15.17 | 0.00800000 | 42295.9 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3383.904 | 3383.904 | 0.122693 | 0.00002960 | 92.351 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 0.8094 | 0.825714 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 3383.90 | 3383.90 | 1.0000 | 0.14244389 | 0.122693 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.02960084 | 60.00 | 32.22 | 27.78 | 0.000 | 3383.90 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00754171 | 21.00 | 0.00754171 | 47.0423 | 2759.95 | 0.00 | 3400.68 | 3400.68 | 0.14244389 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60808.6 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1617.035 | 1617.035 | 0.137621 | 0.00001415 | 36.190 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 0.3868 | 0.394576 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1617.04 | 1617.04 | 1.0000 | 0.15977452 | 0.137621 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01414509 | 60.00 | 32.22 | 27.78 | 0.000 | 1617.04 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00747448 | 21.00 | 0.00747448 | 46.6266 | 917.18 | 0.00 | 1625.79 | 1625.79 | 0.15977452 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.58 | 16.87 | 0.00800000 | 47110.3 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2128.582 | 2128.582 | 0.077183 | 0.00001862 | 58.090 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 0.5092 | 0.519400 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2128.58 | 2128.58 | 1.0000 | 0.08960809 | 0.077183 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01861987 | 60.00 | 32.22 | 27.78 | 0.000 | 2128.58 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00735855 | 21.00 | 0.00735855 | 45.9119 | 1736.16 | 0.00 | 2139.14 | 2139.14 | 0.08960809 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60806.9 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1538.271 | 1538.271 | 0.086638 | 0.00001346 | 36.907 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 0.3680 | 0.375357 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1538.27 | 1538.27 | 1.0000 | 0.10058447 | 0.086638 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01345609 | 60.00 | 32.22 | 27.78 | 0.000 | 1538.27 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00740887 | 21.00 | 0.00740887 | 46.2222 | 1097.74 | 0.00 | 1546.32 | 1546.32 | 0.10058447 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.68 | 18.59 | 0.00800000 | 52308.0 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2756.348 | 2756.348 | 0.099946 | 0.00002411 | 75.222 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 0.6593 | 0.672582 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2756.35 | 2756.35 | 1.0000 | 0.11603543 | 0.099946 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.02411128 | 60.00 | 32.22 | 27.78 | 0.000 | 2756.35 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00732776 | 21.00 | 0.00732776 | 45.7234 | 2248.27 | 0.00 | 2770.02 | 2770.02 | 0.11603543 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60806.9 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12083.981 | 12083.981 | 1.014367 | 0.00010572 | 270.938 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 2.8905 | 2.948638 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 12083.98 | 12083.98 | 1.0000 | 1.17765584 | 1.014367 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.10570515 | 60.00 | 32.22 | 27.78 | 0.000 | 12083.98 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00759233 | 21.00 | 0.00759233 | 47.3538 | 6924.79 | 0.00 | 12149.39 | 12149.39 | 1.17765584 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.72 | 16.92 | 0.00800000 | 47251.3 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30913.759 | 30913.759 | 2.840147 | 0.00027045 | 685.294 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 7.3945 | 7.543333 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 30913.76 | 30913.76 | 1.0000 | 3.29734416 | 2.840147 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.27041946 | 60.00 | 32.22 | 27.78 | 0.000 | 30913.76 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00751721 | 21.00 | 0.00751721 | 46.8905 | 16469.87 | 0.00 | 31081.85 | 31081.85 | 3.29734416 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.84 | 16.61 | 0.00800000 | 46361.1 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10574.165 | -999.000 | 0.946636 | 0.00030241 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0317 | 1004.8586 | 1.1610 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.946636 | 1.09902269 | 4197.9300 | 999.8980 | 26.42386414 | 15.03 | 6.70 | 8.33 | 924009.68 | 1.1444 | 1.144357 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 10574.17 | 10079.24 | 1.0000 | 1.09902269 | 0.946636 | 21.70 | 15.38 | 0.00871015 | 43943.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.30238330 | 6.70 | 15.03 | 8.33 | 0.000 | 10574.17 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00871015 | 21.11 | 0.00871015 | 53.8622 | 9321.38 | 0.00 | 10967.07 | 10967.07 | 1.09902269 | 21.70 | 15.75 | 0.00871015 | 43943.6 | 11.93 | 11.93 | 0.00871015 | 33964.7 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5973.774 | 5973.774 | 0.267128 | 0.00005226 | 170.712 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.946636 | 1.09902269 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 1.4289 | 1.457673 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 5973.77 | 5973.77 | 1.0000 | 0.31012888 | 0.267128 | 21.11 | 14.09 | 0.00751388 | 40298.9 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05225585 | 60.00 | 32.22 | 27.78 | 0.000 | 5973.77 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00751388 | 21.11 | 0.00751388 | 46.5526 | 5973.92 | 0.00 | 6439.85 | 6439.85 | 0.31012888 | 16.60 | 12.68 | 0.00751388 | 35704.0 | 36.98 | 19.91 | 0.00751388 | 56469.1 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10461.124 | -999.000 | 0.935839 | 0.00029918 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0368 | 1004.8586 | 1.1610 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.935839 | 1.08648667 | 4197.9300 | 999.8980 | 26.42386414 | 15.03 | 6.70 | 8.33 | 924009.68 | 1.1321 | 1.132123 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 10461.12 | 9965.40 | 1.0000 | 1.08648667 | 0.935839 | 21.70 | 15.38 | 0.00871290 | 43950.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.29915070 | 6.70 | 15.03 | 8.33 | 0.000 | 10461.12 | 32.75 | 0.01447025 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00871290 | 21.11 | 0.00871290 | 53.8790 | 9215.06 | 0.00 | 10849.63 | 10849.63 | 1.08648667 | 21.70 | 15.75 | 0.00871290 | 43950.6 | 11.92 | 11.92 | 0.00871290 | 33964.6 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5983.500 | 5983.500 | 0.267563 | 0.00005235 | 170.990 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.935839 | 1.08648667 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 1.4312 | 1.460047 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 5983.50 | 5983.50 | 1.0000 | 0.31063381 | 0.267563 | 21.11 | 14.09 | 0.00751464 | 40300.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05234093 | 60.00 | 32.22 | 27.78 | 0.000 | 5983.50 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00751464 | 21.11 | 0.00751464 | 46.5573 | 5983.64 | 0.00 | 6450.33 | 6450.33 | 0.31063381 | 16.60 | 12.68 | 0.00751464 | 35705.9 | 36.98 | 19.91 | 0.00751464 | 56471.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 58401.430 | -999.000 | 5.351299 | 0.00167024 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8694 | 1004.8586 | 1.1610 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.351299 | 6.21273282 | 4197.9300 | 999.8980 | 26.42386414 | 15.03 | 6.70 | 8.33 | 924009.68 | 6.3204 | 6.320317 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 58401.43 | 56772.41 | 1.0000 | 6.21273282 | 5.351299 | 21.70 | 15.31 | 0.00862281 | 43722.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 1.67007192 | 6.70 | 15.03 | 8.33 | 0.000 | 58401.43 | 34.40 | 0.01447326 | 23.54 | 0.00000000 | 0.0000 | 21.11 | 0.00862281 | 21.11 | 0.00862281 | 53.3272 | 52697.90 | 0.00 | 60598.62 | 60598.62 | 6.21273282 | 21.70 | 15.67 | 0.00862281 | 43722.5 | 12.15 | 11.95 | 0.00862281 | 33968.5 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34213.531 | 34213.531 | 1.529955 | 0.00029931 | 977.702 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.351299 | 6.21273282 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 8.1838 | 8.348517 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 34213.53 | 34213.53 | 1.0000 | 1.77624243 | 1.529955 | 21.11 | 14.12 | 0.00754717 | 40384.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.29928436 | 60.00 | 32.22 | 27.78 | 0.000 | 34213.53 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00754717 | 21.11 | 0.00754717 | 46.7550 | 34213.94 | 0.00 | 36883.17 | 36883.17 | 1.77624243 | 16.60 | 12.71 | 0.00754717 | 35788.3 | 36.98 | 19.93 | 0.00754717 | 56553.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 66500.620 | -999.000 | 5.718579 | 0.00190187 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3208 | 1004.8586 | 1.1610 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.718579 | 6.63913557 | 4197.9300 | 999.8980 | 26.42386414 | 15.03 | 6.70 | 8.33 | 924009.68 | 7.1970 | 7.196827 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | unknown | unknown | 7/21 15:40:00 | Sensible | 66500.62 | 61266.17 | 1.0000 | 6.63913557 | 5.718579 | 21.70 | 15.52 | 0.00886565 | 44338.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 1.90167977 | 6.70 | 15.03 | 8.33 | 0.000 | 66500.62 | 34.02 | 0.01447257 | 23.44 | 0.00000000 | 0.0000 | 21.11 | 0.00886565 | 21.11 | 0.00886565 | 54.8101 | 56310.31 | 0.00 | 68923.77 | 65349.75 | 6.63913557 | 21.70 | 15.88 | 0.00886565 | 44338.7 | 12.07 | 11.95 | 0.00865231 | 33957.2 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34410.526 | 34410.526 | 1.538765 | 0.00030104 | 983.330 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.718579 | 6.63913557 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 8.2309 | 8.396587 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 34410.53 | 34410.53 | 1.0000 | 1.78646972 | 1.538765 | 21.11 | 14.13 | 0.00754944 | 40389.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.30100759 | 60.00 | 32.22 | 27.78 | 0.000 | 34410.53 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00754944 | 21.11 | 0.00754944 | 46.7690 | 34410.93 | 0.00 | 37095.54 | 37095.54 | 1.78646972 | 16.60 | 12.71 | 0.00754944 | 35794.0 | 36.98 | 19.93 | 0.00754944 | 56558.7 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9589.566 | -999.000 | 0.853194 | 0.00027426 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0755 | 1004.8586 | 1.1610 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.853194 | 0.99053863 | 4197.9300 | 999.8980 | 26.42386414 | 15.03 | 6.70 | 8.33 | 924009.68 | 1.0378 | 1.037802 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | unknown | unknown | 7/21 10:30:00 | Sensible | 9589.57 | 9093.08 | 1.0000 | 0.99053863 | 0.853194 | 21.70 | 15.40 | 0.00873368 | 44003.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.27422727 | 6.70 | 15.03 | 8.33 | 0.000 | 9589.57 | 31.50 | 0.01446797 | 22.76 | 0.00000000 | 0.0000 | 21.11 | 0.00873368 | 21.11 | 0.00873368 | 54.0057 | 8401.26 | 0.00 | 9945.85 | 9749.92 | 0.99053863 | 21.70 | 15.77 | 0.00873368 | 44003.4 | 12.06 | 11.95 | 0.00865529 | 33962.5 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5953.655 | 5953.655 | 0.266228 | 0.00005209 | 170.137 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.853194 | 0.99053863 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 1.4241 | 1.452764 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 5953.66 | 5953.66 | 1.0000 | 0.30908444 | 0.266228 | 21.11 | 14.09 | 0.00751238 | 40295.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05207986 | 60.00 | 32.22 | 27.78 | 0.000 | 5953.66 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00751238 | 21.11 | 0.00751238 | 46.5434 | 5953.80 | 0.00 | 6418.16 | 6418.16 | 0.30908444 | 16.60 | 12.67 | 0.00751238 | 35700.2 | 36.98 | 19.91 | 0.00751238 | 56465.2 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9508.841 | -999.000 | 0.845524 | 0.00027195 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0796 | 1004.8586 | 1.1610 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.845524 | 0.98163408 | 4197.9300 | 999.8980 | 26.42386414 | 15.03 | 6.70 | 8.33 | 924009.68 | 1.0291 | 1.029065 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | unknown | unknown | 7/21 10:20:00 | Sensible | 9508.84 | 9012.14 | 1.0000 | 0.98163408 | 0.845524 | 21.70 | 15.40 | 0.00873587 | 44008.9 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.27191883 | 6.70 | 15.03 | 8.33 | 0.000 | 9508.84 | 31.26 | 0.01446754 | 22.70 | 0.00000000 | 0.0000 | 21.11 | 0.00873587 | 21.11 | 0.00873587 | 54.0191 | 8325.73 | 0.00 | 9861.98 | 9662.24 | 0.98163408 | 21.70 | 15.77 | 0.00873587 | 44008.9 | 12.06 | 11.95 | 0.00865524 | 33962.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5963.387 | 5963.387 | 0.266663 | 0.00005217 | 170.415 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.845524 | 0.98163408 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 1.4264 | 1.455139 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 5963.39 | 5963.39 | 1.0000 | 0.30958966 | 0.266663 | 21.11 | 14.09 | 0.00751314 | 40297.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05216499 | 60.00 | 32.22 | 27.78 | 0.000 | 5963.39 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00751314 | 21.11 | 0.00751314 | 46.5481 | 5963.53 | 0.00 | 6428.65 | 6428.65 | 0.30958966 | 16.60 | 12.68 | 0.00751314 | 35702.1 | 36.98 | 19.91 | 0.00751314 | 56467.2 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13211.932 | 13211.932 | 0.712231 | 0.00011558 | 320.075 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 3.1603 | 3.223872 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 13211.93 | 13211.93 | 1.0000 | 0.82688401 | 0.712231 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.11557196 | 60.00 | 32.22 | 27.78 | 0.000 | 13211.93 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00762387 | 21.00 | 0.00762387 | 47.5468 | 9588.83 | 0.00 | 13280.77 | 13280.77 | 0.82688401 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.35 | 18.81 | 0.00800000 | 52996.0 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2781.951 | -999.000 | 0.249777 | 0.00007956 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0112 | 1004.8586 | 1.1610 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.249777 | 0.28998556 | 4197.9300 | 999.8980 | 26.42386414 | 15.03 | 6.70 | 8.33 | 924009.68 | 0.3011 | 0.301068 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 2781.95 | 2658.27 | 1.0000 | 0.28998556 | 0.249777 | 21.70 | 15.37 | 0.00869912 | 43915.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.07955384 | 6.70 | 15.03 | 8.33 | 0.000 | 2781.95 | 33.07 | 0.01447082 | 23.19 | 0.00000000 | 0.0000 | 21.11 | 0.00869912 | 21.11 | 0.00869912 | 53.7949 | 2459.52 | 0.00 | 2885.53 | 2885.53 | 0.28998556 | 21.70 | 15.74 | 0.00869912 | 43915.6 | 11.96 | 11.95 | 0.00869912 | 33965.0 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1820.974 | 1820.974 | 0.081428 | 0.00001593 | 52.035 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.249777 | 0.28998556 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 0.4356 | 0.444340 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1820.97 | 1820.97 | 1.0000 | 0.09453602 | 0.081428 | 21.11 | 14.17 | 0.00759503 | 40505.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01592905 | 60.00 | 32.22 | 27.78 | 0.000 | 1820.97 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00759503 | 21.11 | 0.00759503 | 47.0493 | 1821.02 | 0.00 | 1963.05 | 1963.05 | 0.09453602 | 16.60 | 12.76 | 0.00759503 | 35909.4 | 36.98 | 19.97 | 0.00759503 | 56674.5 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2749.357 | -999.000 | 0.246675 | 0.00007863 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0162 | 1004.8586 | 1.1610 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.246675 | 0.28638352 | 4197.9300 | 999.8980 | 26.42386414 | 15.03 | 6.70 | 8.33 | 924009.68 | 0.2975 | 0.297541 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 2749.36 | 2625.55 | 1.0000 | 0.28638352 | 0.246675 | 21.70 | 15.37 | 0.00870182 | 43922.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.07862178 | 6.70 | 15.03 | 8.33 | 0.000 | 2749.36 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00870182 | 21.11 | 0.00870182 | 53.8114 | 2428.97 | 0.00 | 2851.67 | 2851.67 | 0.28638352 | 21.70 | 15.74 | 0.00870182 | 43922.5 | 11.95 | 11.95 | 0.00870182 | 33964.9 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1824.806 | 1824.806 | 0.081599 | 0.00001596 | 52.145 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.246675 | 0.28638352 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 0.4365 | 0.445275 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1824.81 | 1824.81 | 1.0000 | 0.09473495 | 0.081599 | 21.11 | 14.17 | 0.00759585 | 40507.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01596257 | 60.00 | 32.22 | 27.78 | 0.000 | 1824.81 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00759585 | 21.11 | 0.00759585 | 47.0543 | 1824.85 | 0.00 | 1967.18 | 1967.18 | 0.09473495 | 16.60 | 12.76 | 0.00759585 | 35911.5 | 36.98 | 19.97 | 0.00759585 | 56676.6 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12701.716 | -999.000 | 1.116824 | 0.00036326 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1597 | 1004.8586 | 1.1610 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.116824 | 1.29660680 | 4197.9300 | 999.8980 | 26.42386414 | 15.03 | 6.70 | 8.33 | 924009.68 | 1.3746 | 1.374604 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 12701.72 | 11924.43 | 1.0000 | 1.29660680 | 1.116824 | 21.70 | 15.44 | 0.00877897 | 44118.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.36322362 | 6.70 | 15.03 | 8.33 | 0.000 | 12701.72 | 34.40 | 0.01447326 | 23.54 | 0.00000000 | 0.0000 | 21.11 | 0.00877897 | 21.11 | 0.00877897 | 54.2822 | 10997.06 | 0.00 | 13169.71 | 12761.63 | 1.29660680 | 21.70 | 15.81 | 0.00877897 | 44118.3 | 12.07 | 11.95 | 0.00865424 | 33961.3 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8720.125 | 8720.125 | 0.389939 | 0.00007629 | 249.180 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.116824 | 1.29660680 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 2.0858 | 2.127817 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 8720.13 | 8720.13 | 1.0000 | 0.45270999 | 0.389939 | 21.11 | 14.18 | 0.00760952 | 40542.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07627968 | 60.00 | 32.22 | 27.78 | 0.000 | 8720.13 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00760952 | 21.11 | 0.00760952 | 47.1376 | 8720.29 | 0.00 | 9400.50 | 9400.50 | 0.45270999 | 16.60 | 12.77 | 0.00760952 | 35946.1 | 36.98 | 19.98 | 0.00760952 | 56711.1 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15197.306 | 15197.306 | 1.782565 | 0.00013295 | 328.446 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 3.6352 | 3.708327 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 15197.31 | 15197.31 | 1.0000 | 2.06951595 | 1.782565 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.13293910 | 60.00 | 32.22 | 27.78 | 0.000 | 15197.31 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00769868 | 21.00 | 0.00769868 | 48.0081 | 6128.56 | 0.00 | 15281.72 | 15281.72 | 2.06951595 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.84 | 15.90 | 0.00800000 | 44318.9 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15321.340 | 15321.340 | 1.780823 | 0.00013404 | 331.401 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 3.6648 | 3.738593 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | Sensible | 15321.34 | 15321.34 | 1.0000 | 2.06749389 | 1.780823 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.13402409 | 60.00 | 32.22 | 27.78 | 0.000 | 15321.34 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00770475 | 21.00 | 0.00770475 | 48.0457 | 6261.49 | 0.00 | 15406.42 | 15406.42 | 2.06749389 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.91 | 15.92 | 0.00800000 | 44386.5 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5461.203 | 5461.203 | 0.549909 | 0.00004778 | 119.824 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 1.3063 | 1.332600 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 5461.20 | 5461.20 | 1.0000 | 0.63843186 | 0.549909 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.04777211 | 60.00 | 32.22 | 27.78 | 0.000 | 5461.20 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.62 | 0.00696757 | 21.00 | 0.00696757 | 43.5061 | 2668.89 | 0.00 | 5491.41 | 5491.41 | 0.63843186 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.04 | 16.33 | 0.00800000 | 45536.1 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7883.705 | 7883.705 | 0.285831 | 0.00006897 | 215.161 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 1.8858 | 1.923720 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | Sensible | 7883.71 | 7883.71 | 1.0000 | 0.33184270 | 0.285831 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.06896306 | 60.00 | 32.22 | 27.78 | 0.000 | 7883.71 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00774613 | 21.00 | 0.00774613 | 48.3003 | 6429.41 | 0.00 | 7922.80 | 7922.80 | 0.33184270 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60809.9 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 649583.226 | -999.000 | 20.995413 | 0.01857800 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.8931 | 1004.8586 | 1.1610 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.995413 | 24.37518154 | 4197.9300 | 999.8980 | 26.42386414 | 15.03 | 6.70 | 8.33 | 924009.68 | 70.3005 | 70.300478 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 649583.23 | 439175.42 | 1.0000 | 24.37518154 | 20.995413 | 28.61 | 20.15 | 0.01186321 | 59053.4 | 10.92 | 10.92 | 0.00850000 | 32404.0 | 18.57610289 | 6.70 | 15.03 | 8.33 | 47043.132 | 602540.09 | 34.40 | 0.01447326 | 23.54 | 9.32920000 | 44.4345 | 23.99 | 0.00977601 | 23.99 | 0.00978257 | 50.6935 | 278404.24 | 0.00 | 663646.45 | 437459.03 | 24.37518154 | 28.61 | 20.57 | 0.01186321 | 59053.4 | 11.14 | 11.08 | 0.00818330 | 31827.0 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 169005.913 | 169005.913 | 6.298624 | 0.00147854 | 2852.482 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.995413 | 24.37518154 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 40.4259 | 41.239496 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 169005.91 | 169005.91 | 1.0000 | 7.31255446 | 6.298624 | -6.30 | -6.30 | 0.00229779 | -610.8 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 1.47838663 | 60.00 | 32.22 | 27.78 | 0.000 | 169005.91 | -6.30 | 0.00229779 | -6.30 | 9.32920000 | 148.1149 | 20.98 | 0.00759702 | 21.01 | 0.00758909 | 47.3132 | 63656.17 | 0.00 | 151988.69 | 151988.69 | 7.31255446 | 2.80 | -0.72 | 0.00229779 | 8572.2 | 23.40 | 10.14 | 0.00229779 | 29356.8 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 91161.109 | -999.000 | 2.051317 | 0.00260720 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.7451 | 1004.8586 | 1.1610 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.38144746 | 4197.9300 | 999.8980 | 26.42386414 | 15.03 | 6.70 | 8.33 | 924009.68 | 9.8658 | 9.865817 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 91161.11 | 55491.40 | 1.0000 | 2.38153119 | 2.051317 | 34.40 | 23.54 | 0.01447326 | 71688.8 | 11.91 | 11.41 | 0.00850000 | 33410.4 | 2.60693021 | 6.70 | 15.03 | 8.33 | 2195.006 | 88966.10 | 34.40 | 0.01447326 | 23.54 | 2.05124512 | 99.9965 | 21.11 | 0.00875275 | 21.11 | 0.00874979 | 54.1028 | 153689.42 | 0.00 | 92683.44 | 56170.47 | 2.38153119 | 34.40 | 23.99 | 0.01447326 | 71688.8 | 11.54 | 11.47 | 0.00839502 | 32771.2 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 16512.404 | 16512.404 | 0.615395 | 0.00014446 | 278.696 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.38144746 | 4197.9300 | 999.8980 | 3.58488041 | 54.44 | 82.22 | 27.78 | 418063.36 | 3.9497 | 4.029227 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 16512.40 | 16512.40 | 1.0000 | 0.71445936 | 0.615395 | -6.30 | -6.30 | 0.00229779 | -610.8 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 0.14444298 | 60.00 | 32.22 | 27.78 | 0.000 | 16512.40 | -6.30 | 0.00229779 | -6.30 | 2.05124512 | 333.3216 | 21.11 | 0.00754712 | 21.11 | 0.00754861 | 46.7639 | 104865.92 | 0.00 | 14849.77 | 14849.77 | 0.71445936 | 2.80 | -0.72 | 0.00229779 | 8572.2 | 23.40 | 10.14 | 0.00229779 | 29356.8 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 21.00 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1078.00 | 6695.67 | 192.33 |
RETAIL_1_FLR_1 | 3988.83 | 5535.67 | 1401.33 |
RETAIL_2_FLR_1 | 1741.00 | 6933.83 | 753.50 |
MECH_FLR_1 | 3545.00 | 4375.17 | 287.00 |
STORAGE_FLR_1 | 642.50 | 8722.17 | 642.50 |
LAUNDRY_FLR_1 | 8760.00 | 4747.67 | 4747.67 |
CAFE_FLR_1 | 2015.67 | 7488.50 | 1423.83 |
LOBBY_FLR_1 | 2209.83 | 7125.00 | 1480.17 |
ROOM_1_FLR_3 | 1368.33 | 8149.67 | 1359.33 |
ROOM_2_FLR_3 | 2212.17 | 8050.17 | 2146.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1379.67 | 8756.17 | 1379.67 |
ROOM_5_FLR_3 | 1270.17 | 8077.67 | 1266.33 |
ROOM_6_FLR_3 | 2163.33 | 8033.83 | 2095.83 |
CORRIDOR_FLR_3 | 1481.00 | 8264.50 | 1451.67 |
ROOM_1_FLR_6 | 1992.83 | 7997.67 | 1922.17 |
ROOM_2_FLR_6 | 2824.17 | 7892.17 | 2689.00 |
ROOM_3_MULT9_FLR_6 | 856.83 | 8149.00 | 847.33 |
BANQUET_FLR_6 | 2714.50 | 6358.33 | 1387.17 |
DINING_FLR_6 | 3689.50 | 5276.17 | 1390.17 |
KITCHEN_FLR_6 | 8742.50 | 6432.33 | 6432.33 |
CORRIDOR_FLR_6 | 4042.50 | 5347.83 | 1200.50 |
Facility | 8760.00 | 8760.00 | 8031.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4.00 | 4.17 | 4.00 | 4.17 |
ROOM_2_FLR_3 | 9.33 | 8.33 | 9.33 | 8.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 2.83 | 26.50 | 2.83 | 26.50 |
ROOM_5_FLR_3 | 3.83 | 0.50 | 3.83 | 0.50 |
ROOM_6_FLR_3 | 9.83 | 31.00 | 9.83 | 31.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4.00 | 8.67 | 4.00 | 8.67 |
ROOM_2_FLR_6 | 8.50 | 11.83 | 8.50 | 11.83 |
ROOM_3_MULT9_FLR_6 | 2.67 | 12.33 | 2.67 | 12.33 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 11.83 | 0.00 | 11.83 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 15.17 | 73.50 | 15.17 | 73.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.738 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.330 | 0.136 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.219 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.148 | 0.051 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.624 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 15.817 | 0.146 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 3.674 | 0.106 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.498 | 0.044 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.341 | 0.175 | 0.000 | 0.068 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.342 | 0.175 | 0.000 | 0.069 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.388 | 0.078 | 0.000 | 0.108 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.341 | 0.175 | 0.000 | 0.068 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.342 | 0.175 | 0.000 | 0.069 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.407 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.341 | 0.175 | 0.000 | 0.082 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.342 | 0.175 | 0.000 | 0.081 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.388 | 0.142 | 0.000 | 0.130 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.805 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.830 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 15.919 | 0.146 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.496 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.510 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 0.914 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.901 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.006 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.439 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 5.900 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 2.621 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.138 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.286 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 3.592 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 3.620 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 4.252 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.311 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.79 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.56 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.09 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.25 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 30684444.44 | 0.00 | 30684444.44 | 0.00 | 30684444.44 | 26946214.98 | 4802.44 | 127.92 | 3829.64 | 0.00 |
RETAIL_1_FLR_1 | 3040705.37 | 0.00 | 3040705.37 | 310220.85 | 3350926.23 | 2498216.28 | 3565.45 | 124.91 | 5069.64 | 0.00 |
RETAIL_2_FLR_1 | 3232694.86 | 0.00 | 3232694.86 | 119745.64 | 3352440.50 | 2892943.94 | 5074.00 | 105.15 | 3580.85 | 0.00 |
MECH_FLR_1 | 821986.77 | 0.00 | 821986.77 | 283007.56 | 1104994.33 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2025158.20 | 0.00 | 2025158.20 | 163279.77 | 2188437.98 | 1821682.01 | 5206.15 | 69.86 | 3483.99 | 0.00 |
LAUNDRY_FLR_1 | 41981649.75 | 0.00 | 41981649.75 | 386432.37 | 42368082.11 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 23711868.75 | 0.00 | 23711868.75 | 685760.76 | 24397629.51 | 21330615.53 | 5206.31 | 70.20 | 3483.49 | 0.00 |
LOBBY_FLR_1 | 66816245.15 | 0.00 | 66816245.15 | 1959375.13 | 68775620.29 | 59728886.00 | 4968.86 | 180.28 | 3610.86 | 0.00 |
ROOM_1_FLR_3 | 1406076.84 | 70091.96 | 1476168.80 | 180061.18 | 1656229.97 | 1946875.62 | 2433.33 | 5505.17 | 821.50 | 0.00 |
ROOM_2_FLR_3 | 1405912.09 | 70643.58 | 1476555.68 | 180047.44 | 1656603.11 | 1946647.51 | 2433.33 | 5510.63 | 816.04 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 4568.02 | 1104479.99 | 50239.09 | 1154719.08 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 410.67 |
ROOM_4_MULT19_FLR_3 | 19070354.14 | 69486.50 | 19139840.64 | 50252.83 | 19190093.46 | 26405105.73 | 2433.33 | 5550.80 | 775.86 | 0.00 |
ROOM_5_FLR_3 | 1406076.84 | 70097.86 | 1476174.70 | 180061.18 | 1656235.87 | 1946875.62 | 2433.33 | 5505.17 | 821.50 | 0.00 |
ROOM_6_FLR_3 | 1405912.09 | 70068.41 | 1475980.51 | 180047.44 | 1656027.94 | 1946647.51 | 2433.33 | 5505.28 | 821.39 | 0.00 |
CORRIDOR_FLR_3 | 16648411.07 | 0.00 | 16648411.07 | 217730.19 | 16866141.26 | 14972100.18 | 5205.88 | 68.88 | 3485.24 | 0.00 |
ROOM_1_FLR_6 | 351519.21 | 83704.23 | 435223.44 | 180098.20 | 615321.64 | 486718.90 | 2190.81 | 5506.42 | 1062.77 | 0.00 |
ROOM_2_FLR_6 | 351478.02 | 82552.06 | 434030.08 | 180084.46 | 614114.54 | 486661.88 | 2193.47 | 5518.95 | 1047.58 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2258331.41 | 83891.70 | 2342223.11 | 92144.54 | 2434367.66 | 3126920.42 | 2433.33 | 5502.50 | 824.17 | 0.00 |
BANQUET_FLR_6 | 41822446.49 | 0.00 | 41822446.49 | 439754.55 | 42262201.04 | 37458366.31 | 5153.75 | 93.79 | 3512.46 | 0.00 |
DINING_FLR_6 | 41990540.57 | 0.00 | 41990540.57 | 439754.55 | 42430295.11 | 37458366.31 | 5052.25 | 98.56 | 3609.19 | 0.00 |
KITCHEN_FLR_6 | 42938491.43 | 0.00 | 42938491.43 | 393682.28 | 43332173.70 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 5357067.79 | 0.00 | 5357067.79 | 385314.24 | 5742382.03 | 3961413.96 | 2574.74 | 91.53 | 6093.72 | 0.00 |
Total Facility | 0.19E+10 | 7673032.52 | 0.20E+10 | 18144986.26 | 0.20E+10 | 0.43E+10 | 8760.00 | 6001.21 | 8760.00 | 410.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9730 | 0.0000 | 0.9730 | 0.0000 | 0.9730 | 0.8545 | 4802.44 | 127.92 | 3829.64 |
RETAIL_1_FLR_1 | 0.0964 | 0.0000 | 0.0964 | 0.0098 | 0.1063 | 0.0792 | 3565.45 | 124.91 | 5069.64 |
RETAIL_2_FLR_1 | 0.1025 | 0.0000 | 0.1025 | 0.0038 | 0.1063 | 0.0917 | 5074.00 | 105.15 | 3580.85 |
MECH_FLR_1 | 0.0261 | 0.0000 | 0.0261 | 0.0090 | 0.0350 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0642 | 0.0000 | 0.0642 | 0.0052 | 0.0694 | 0.0578 | 5206.15 | 69.86 | 3483.99 |
LAUNDRY_FLR_1 | 1.3312 | 0.0000 | 1.3312 | 0.0123 | 1.3435 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7519 | 0.0000 | 0.7519 | 0.0217 | 0.7736 | 0.6764 | 5206.31 | 70.20 | 3483.49 |
LOBBY_FLR_1 | 2.1187 | 0.0000 | 2.1187 | 0.0621 | 2.1809 | 1.8940 | 4968.86 | 180.28 | 3610.86 |
ROOM_1_FLR_3 | 0.0446 | 0.0022 | 0.0468 | 0.0057 | 0.0525 | 0.0617 | 2433.33 | 5505.17 | 821.50 |
ROOM_2_FLR_3 | 0.0446 | 0.0022 | 0.0468 | 0.0057 | 0.0525 | 0.0617 | 2433.33 | 5510.63 | 816.04 |
ROOM_4_MULT19_FLR_3 | 0.6047 | 0.0022 | 0.6069 | 0.0016 | 0.6085 | 0.8373 | 2433.33 | 5550.80 | 775.86 |
ROOM_5_FLR_3 | 0.0446 | 0.0022 | 0.0468 | 0.0057 | 0.0525 | 0.0617 | 2433.33 | 5505.17 | 821.50 |
ROOM_6_FLR_3 | 0.0446 | 0.0022 | 0.0468 | 0.0057 | 0.0525 | 0.0617 | 2433.33 | 5505.28 | 821.39 |
CORRIDOR_FLR_3 | 0.5279 | 0.0000 | 0.5279 | 0.0069 | 0.5348 | 0.4748 | 5205.88 | 68.88 | 3485.24 |
ROOM_1_FLR_6 | 0.0111 | 0.0027 | 0.0138 | 0.0057 | 0.0195 | 0.0154 | 2190.81 | 5506.42 | 1062.77 |
ROOM_2_FLR_6 | 0.0111 | 0.0026 | 0.0138 | 0.0057 | 0.0195 | 0.0154 | 2193.47 | 5518.95 | 1047.58 |
ROOM_3_MULT9_FLR_6 | 0.0716 | 0.0027 | 0.0743 | 0.0029 | 0.0772 | 0.0992 | 2433.33 | 5502.50 | 824.17 |
BANQUET_FLR_6 | 1.3262 | 0.0000 | 1.3262 | 0.0139 | 1.3401 | 1.1878 | 5153.75 | 93.79 | 3512.46 |
DINING_FLR_6 | 1.3315 | 0.0000 | 1.3315 | 0.0139 | 1.3455 | 1.1878 | 5052.25 | 98.56 | 3609.19 |
KITCHEN_FLR_6 | 1.3616 | 0.0000 | 1.3616 | 0.0125 | 1.3741 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.1699 | 0.0000 | 0.1699 | 0.0122 | 0.1821 | 0.1256 | 2574.74 | 91.53 | 6093.72 |
Total Facility | 59.1035 | 0.2323 | 59.3358 | 0.4543 | 59.7901 | 73.9670 | 8760.00 | 6001.21 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.43E+09 | 0.00 | 0.43E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 38758673.79 | 605104.33 | 39363778.13 | 64690340.46 | 8759.83 | 0.17 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 13.7227 | 0.0000 | 13.7227 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.2290 | 0.0192 | 1.2482 | 2.0513 | 8759.83 | 0.17 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 155.23 | 5083.41 | 0.00 | 0.00 | 0.00 | 3521.36 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6691.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 12.4837 | 15.4192 | 0.0000 | 0.0000 | 0.0000 | 11.3320 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6091 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1340 |
Defaulted Fields | 1181 |
Fields with Defaults | 4002 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5456.09 | 67517.84 | 24-MAR-03:00 | 385588.52 | 18-AUG-19:20 |
Electricity:Building | 2201.24 | 29107.25 | 02-JAN-02:10 | 132137.22 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 266.04 | 3144.96 | 02-JAN-02:10 | 19685.67 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2194.15 | 28966.11 | 02-JAN-02:10 | 131895.89 | 02-JAN-20:10 |
InteriorLights:Electricity | 545.70 | 5072.43 | 02-JAN-02:10 | 45764.37 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 122.93 | 1117.06 | 02-JAN-02:10 | 10053.14 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 545.70 | 5072.43 | 02-JAN-02:10 | 45764.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 545.70 | 5072.43 | 02-JAN-02:10 | 45764.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 122.93 | 1117.06 | 02-JAN-02:10 | 10053.14 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 545.70 | 5072.43 | 02-JAN-02:10 | 45764.37 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.45 | 201.26 | 02-JAN-02:10 | 1197.92 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.05 | 233.06 | 02-JAN-02:10 | 1387.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.91 | 71.95 | 02-JAN-02:10 | 430.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.31 | 20.97 | 02-JAN-02:10 | 188.71 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.31 | 20.97 | 02-JAN-02:10 | 188.71 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 27.24 | 378.04 | 02-JAN-02:10 | 2538.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.90 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.90 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 241.21 | 2998.53 | 02-JAN-02:10 | 18013.24 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 92.21 | 887.12 | 02-JAN-02:10 | 7984.04 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 92.21 | 887.12 | 02-JAN-02:10 | 7984.04 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 253.77 | 3619.58 | 02-JAN-10:10 | 20179.99 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 253.84 | 3620.57 | 02-JAN-10:10 | 20185.51 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 3.85 | 55.20 | 01-JAN-02:10 | 290.10 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 3.85 | 55.19 | 01-JAN-02:10 | 290.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 30.06 | 428.75 | 02-JAN-10:10 | 2390.39 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 204.26 | 2556.31 | 02-JAN-02:10 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.40 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.40 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 204.26 | 2556.31 | 02-JAN-02:10 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.40 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.40 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 44.20 | 732.86 | 13-FEB-23:30 | 2790.61 | 23-APR-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1718.09 | 2205.59 | 08-MAR-01:40 | 191153.48 | 08-JUL-15:30 |
LowTempRefrigeration:Refrigeration:Electricity | 15.86 | 0.00 | 01-JAN-11:10 | 1321.21 | 15-APR-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 21.25 | 636.00 | 14-FEB-04:30 | 716.76 | 28-OCT-13:10 |
Fans:Electricity | 591.93 | 12648.00 | 27-MAR-03:00 | 37841.83 | 18-AUG-21:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 723.70 | 13287.67 | 27-NOV-05:00 | 46928.64 | 18-AUG-21:20 |
ExteriorEquipment:Electricity | 640.55 | 9443.87 | 02-JAN-02:20 | 39153.73 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.52 | 379.07 | 02-JAN-02:20 | 1274.03 | 02-JAN-07:20 |
ElectricityPurchased:Facility | 5456.09 | 67517.84 | 24-MAR-03:00 | 385588.52 | 18-AUG-19:20 |
ElectricityPurchased:Plant | 5456.09 | 67517.84 | 24-MAR-03:00 | 385588.52 | 18-AUG-19:20 |
Cogeneration:ElectricityPurchased | 5456.09 | 67517.84 | 24-MAR-03:00 | 385588.52 | 18-AUG-19:20 |
General:Cogeneration:ElectricityPurchased | 5456.09 | 67517.84 | 24-MAR-03:00 | 385588.52 | 18-AUG-19:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5456.09 | 67517.84 | 24-MAR-03:00 | 385588.52 | 18-AUG-19:20 |
ElectricityNet:Plant | 5456.09 | 67517.84 | 24-MAR-03:00 | 385588.52 | 18-AUG-19:20 |
Cogeneration:ElectricityNet | 5456.09 | 67517.84 | 24-MAR-03:00 | 385588.52 | 18-AUG-19:20 |
General:Cogeneration:ElectricityNet | 5456.09 | 67517.84 | 24-MAR-03:00 | 385588.52 | 18-AUG-19:20 |
General:Fans:Electricity | 591.93 | 12648.00 | 27-MAR-03:00 | 37841.83 | 18-AUG-21:20 |
ExteriorLights:Electricity | 194.02 | 0.00 | 01-JAN-07:50 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 194.02 | 0.00 | 01-JAN-07:50 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 110.26 | 0.00 | 01-JAN-08:00 | 8265.52 | 01-JUN-09:00 |
General:HeatRecovery:Electricity | 110.26 | 0.00 | 01-JAN-08:00 | 8265.52 | 01-JUN-09:00 |
WaterSystems:Electricity | 90.74 | 1086.56 | 22-SEP-01:20 | 4738.76 | 23-FEB-19:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 22-SEP-01:20 | 4738.76 | 23-FEB-19:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1503.92 | 0.00 | 01-JAN-00:10 | 183539.50 | 08-JUL-15:30 |
General:Cooling:Electricity | 1503.92 | 0.00 | 01-JAN-00:10 | 183539.50 | 08-JUL-15:30 |
Pumps:Electricity | 86.32 | 47.91 | 22-FEB-08:00 | 4119.91 | 06-JUL-18:10 |
General:Pumps:Electricity | 86.32 | 47.91 | 22-FEB-08:00 | 4119.91 | 06-JUL-18:10 |
WIRED_LTG_ELECTRICITY | 19.21 | 0.00 | 01-JAN-00:10 | 1610.91 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5250.38 | 29270.80 | 01-MAR-02:10 | 500423.05 | 09-JAN-17:30 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3461.54 | 15908.90 | 08-MAR-16:20 | 410810.84 | 09-JAN-17:30 |
WaterSystems:NaturalGas | 2906.88 | 15908.90 | 11-JAN-16:20 | 271213.31 | 24-JAN-21:20 |
Water Heater:WaterSystems:NaturalGas | 2906.88 | 15908.90 | 11-JAN-16:20 | 271213.31 | 24-JAN-21:20 |
Heating:NaturalGas | 554.66 | 0.00 | 19-JAN-21:00 | 181957.97 | 09-JAN-16:20 |
Boiler:Heating:NaturalGas | 554.66 | 0.00 | 19-JAN-21:00 | 181957.97 | 09-JAN-16:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4761.99 | 0.00 | 01-JAN-00:10 | 605846.35 | 23-AUG-22:00 |
PlantLoopCoolingDemand:HVAC | 4761.99 | 0.00 | 01-JAN-00:10 | 605846.35 | 23-AUG-22:00 |
CoolingCoils:PlantLoopCoolingDemand | 4761.99 | 0.00 | 01-JAN-00:10 | 605846.35 | 23-AUG-22:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 23492.10 | 122992.03 | 17-MAR-13:30 | 2382432.78 | 06-JUL-18:10 |
EnergyTransfer:Building | 5062.49 | 76904.49 | 06-FEB-11:10 | 330761.21 | 07-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 699.31 | 7886.02 | 12-FEB-04:00 | 34948.41 | 08-JUL-10:40 |
Refrigeration:EnergyTransfer | 185.89 | 4017.17 | 13-FEB-23:10 | 10369.31 | 02-MAY-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.95 | 2008.59 | 13-FEB-23:10 | 5184.66 | 02-MAY-06:30 |
General:Refrigeration:EnergyTransfer | 92.95 | 2008.59 | 13-FEB-23:10 | 5184.66 | 02-MAY-06:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.95 | 2008.59 | 13-FEB-23:10 | 5184.66 | 02-MAY-06:30 |
EnergyTransfer:Plant | 12306.83 | 15305.38 | 08-MAR-01:20 | 1401855.72 | 23-AUG-22:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.67 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 71.28 | 1996.29 | 14-FEB-04:30 | 2559.98 | 28-OCT-13:10 |
EnergyTransfer:Zone:BASEMENT | 368.59 | 5068.30 | 09-APR-14:50 | 20580.86 | 08-NOV-22:00 |
Heating:EnergyTransfer | 92.95 | 0.00 | 01-JAN-08:00 | 71670.06 | 07-JAN-16:30 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 92.95 | 0.00 | 01-JAN-08:00 | 71670.06 | 07-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4876.59 | 63254.82 | 08-JAN-15:00 | 328062.55 | 07-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 368.59 | 5068.30 | 09-APR-14:50 | 20580.86 | 08-NOV-22:00 |
General:Cooling:EnergyTransfer | 4876.59 | 63254.82 | 08-JAN-15:00 | 328062.55 | 07-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 368.59 | 5068.30 | 09-APR-14:50 | 20580.86 | 08-NOV-22:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 35.42 | 0.04 | 11-FEB-17:20 | 3197.05 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.70 | 0.00 | 01-JAN-00:10 | 1522.03 | 12-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.70 | 0.00 | 01-JAN-00:10 | 1522.03 | 12-FEB-06:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 34.72 | 0.00 | 01-JAN-16:00 | 3197.05 | 10-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 34.72 | 0.00 | 01-JAN-16:00 | 3197.05 | 10-OCT-13:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.56 | 170.38 | 08-JAN-15:50 | 2073.52 | 18-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.56 | 170.38 | 08-JAN-15:50 | 2073.52 | 18-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.56 | 170.38 | 08-JAN-15:50 | 2073.52 | 18-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 12.60 | 0.01 | 07-FEB-17:40 | 1852.40 | 07-JUL-21:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.16 | 0.00 | 01-JAN-00:10 | 468.44 | 08-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.16 | 0.00 | 01-JAN-00:10 | 468.44 | 08-JAN-13:40 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 12.45 | 0.00 | 06-JAN-03:40 | 1852.40 | 07-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 12.45 | 0.00 | 06-JAN-03:40 | 1852.40 | 07-JUL-21:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 18.36 | 0.00 | 05-FEB-20:40 | 1038.48 | 19-AUG-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.32 | 0.00 | 01-JAN-00:10 | 442.99 | 12-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.32 | 0.00 | 01-JAN-00:10 | 442.99 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 18.03 | 0.00 | 03-JAN-09:40 | 1038.48 | 19-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 18.03 | 0.00 | 03-JAN-09:40 | 1038.48 | 19-AUG-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 590.89 | 7587.09 | 13-FEB-05:00 | 39496.96 | 07-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 590.89 | 7587.09 | 13-FEB-05:00 | 39496.96 | 07-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 590.89 | 7587.09 | 13-FEB-05:00 | 39496.96 | 07-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 250.22 | 16.73 | 10-JAN-09:40 | 11716.75 | 08-JUL-17:30 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 340.03 | 09-JAN-09:20 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 340.03 | 09-JAN-09:20 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 250.22 | 0.00 | 09-JAN-09:10 | 11716.75 | 08-JUL-17:30 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 250.22 | 0.00 | 09-JAN-09:10 | 11716.75 | 08-JUL-17:30 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 803.41 | 6699.94 | 08-JAN-16:00 | 39592.55 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 803.41 | 6699.94 | 08-JAN-16:00 | 39592.55 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 803.41 | 6699.94 | 08-JAN-16:00 | 39592.55 | 18-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 61.57 | 0.00 | 01-JAN-08:00 | 10013.11 | 18-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 9.70 | 0.00 | 01-JAN-08:00 | 5639.22 | 07-JAN-19:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 9.70 | 0.00 | 01-JAN-08:00 | 5639.22 | 07-JAN-19:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 51.87 | 0.00 | 01-JAN-00:10 | 10013.11 | 18-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 51.87 | 0.00 | 01-JAN-00:10 | 10013.11 | 18-AUG-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 54.72 | 0.00 | 01-JAN-08:00 | 10323.00 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 12.83 | 0.00 | 01-JAN-08:00 | 5705.33 | 12-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 12.83 | 0.00 | 01-JAN-08:00 | 5705.33 | 12-FEB-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 41.89 | 0.00 | 01-JAN-00:10 | 10323.00 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 41.89 | 0.00 | 01-JAN-00:10 | 10323.00 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 249.83 | 0.00 | 01-JAN-00:10 | 37097.98 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.15 | 0.00 | 01-JAN-00:10 | 5472.60 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.15 | 0.00 | 01-JAN-00:10 | 5472.60 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 249.68 | 0.00 | 01-JAN-00:10 | 37097.98 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 249.68 | 0.00 | 01-JAN-00:10 | 37097.98 | 10-OCT-13:40 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 408.36 | 0.00 | 01-JAN-08:00 | 67591.57 | 07-JUL-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 27.16 | 0.00 | 01-JAN-00:10 | 31118.48 | 03-FEB-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 27.16 | 0.00 | 01-JAN-00:10 | 31118.48 | 03-FEB-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 381.19 | 0.00 | 01-JAN-08:00 | 67591.57 | 07-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 381.19 | 0.00 | 01-JAN-08:00 | 67591.57 | 07-JUL-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 61.65 | 0.00 | 01-JAN-08:00 | 9081.70 | 07-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 9.65 | 0.00 | 01-JAN-08:00 | 5502.15 | 07-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 9.65 | 0.00 | 01-JAN-08:00 | 5502.15 | 07-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 52.00 | 0.00 | 01-JAN-00:10 | 9081.70 | 07-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 52.00 | 0.00 | 01-JAN-00:10 | 9081.70 | 07-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 54.97 | 0.00 | 01-JAN-08:00 | 9610.88 | 07-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 12.77 | 0.00 | 01-JAN-08:00 | 5556.58 | 12-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 12.77 | 0.00 | 01-JAN-08:00 | 5556.58 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 42.20 | 0.00 | 01-JAN-00:10 | 9610.88 | 07-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 42.20 | 0.00 | 01-JAN-00:10 | 9610.88 | 07-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 167.15 | 1.85 | 02-FEB-07:40 | 9085.40 | 19-AUG-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.92 | 0.00 | 01-JAN-00:10 | 3646.64 | 07-JAN-17:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.92 | 0.00 | 01-JAN-00:10 | 3646.64 | 07-JAN-17:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 166.24 | 0.00 | 02-JAN-09:10 | 9085.40 | 19-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 166.24 | 0.00 | 02-JAN-09:10 | 9085.40 | 19-AUG-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 16.88 | 0.00 | 01-JAN-08:00 | 2742.70 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 3.89 | 0.00 | 01-JAN-08:00 | 1718.31 | 12-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 3.89 | 0.00 | 01-JAN-08:00 | 1718.31 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.98 | 0.00 | 01-JAN-00:10 | 2742.70 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.98 | 0.00 | 01-JAN-00:10 | 2742.70 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 15.62 | 0.00 | 01-JAN-08:00 | 2764.58 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.93 | 0.00 | 01-JAN-08:00 | 1722.31 | 12-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.93 | 0.00 | 01-JAN-08:00 | 1722.31 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.68 | 0.00 | 01-JAN-00:10 | 2764.58 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.68 | 0.00 | 01-JAN-00:10 | 2764.58 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 87.72 | 0.00 | 01-JAN-08:00 | 13532.44 | 10-OCT-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 8.21 | 0.00 | 01-JAN-08:00 | 7808.62 | 07-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 8.21 | 0.00 | 01-JAN-08:00 | 7808.62 | 07-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 79.52 | 0.00 | 01-JAN-00:10 | 13532.44 | 10-OCT-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 79.52 | 0.00 | 01-JAN-00:10 | 13532.44 | 10-OCT-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 488.06 | 7574.76 | 13-FEB-09:20 | 22247.16 | 07-JUL-22:00 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 488.06 | 7574.76 | 13-FEB-09:20 | 22247.16 | 07-JUL-22:00 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 488.06 | 7574.76 | 13-FEB-09:20 | 22247.16 | 07-JUL-22:00 |
EnergyTransfer:Zone:DINING_FLR_6 | 511.33 | 9187.80 | 08-JAN-16:00 | 23650.69 | 07-JUL-21:30 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 511.33 | 9187.80 | 08-JAN-16:00 | 23650.69 | 07-JUL-21:30 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 511.33 | 9187.80 | 08-JAN-16:00 | 23650.69 | 07-JUL-21:30 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 606.36 | 5587.02 | 12-FEB-04:00 | 29885.11 | 08-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 606.36 | 5587.02 | 12-FEB-04:00 | 29885.11 | 08-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 68.27 | 0.01 | 05-JAN-21:50 | 6277.30 | 08-JUL-16:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.56 | 0.00 | 01-JAN-00:10 | 3214.76 | 12-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.56 | 0.00 | 01-JAN-00:10 | 3214.76 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 66.71 | 0.00 | 02-JAN-07:10 | 6277.30 | 08-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 66.71 | 0.00 | 02-JAN-07:10 | 6277.30 | 08-JUL-16:10 |
PlantLoopHeatingDemand:Facility | 1049.57 | 7488.09 | 04-AUG-00:50 | 165954.45 | 12-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 671.59 | 7488.09 | 04-AUG-00:50 | 51971.68 | 31-JAN-08:00 |
WaterSystems:PlantLoopHeatingDemand | 671.59 | 7488.09 | 04-AUG-00:50 | 51971.68 | 31-JAN-08:00 |
General:WaterSystems:PlantLoopHeatingDemand | 671.59 | 7488.09 | 04-AUG-00:50 | 51971.68 | 31-JAN-08:00 |
EnergyTransfer:HVAC | 6122.78 | 0.00 | 22-FEB-08:00 | 717664.16 | 06-JUL-18:10 |
HeatingCoils:EnergyTransfer | 377.98 | 0.00 | 19-JAN-21:00 | 141524.99 | 09-JAN-16:20 |
PlantLoopHeatingDemand:HVAC | 377.98 | 0.00 | 19-JAN-21:00 | 141524.99 | 09-JAN-16:20 |
HeatingCoils:PlantLoopHeatingDemand | 377.98 | 0.00 | 19-JAN-21:00 | 141524.99 | 09-JAN-16:20 |
CoolingCoils:EnergyTransfer | 4761.99 | 0.00 | 01-JAN-00:10 | 605846.35 | 23-AUG-22:00 |
HeatRecoveryForHeating:EnergyTransfer | 406.62 | 0.00 | 01-JAN-08:00 | 315772.20 | 12-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 576.18 | 0.00 | 01-JAN-00:10 | 161088.70 | 07-JUL-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 671.59 | 7488.09 | 04-AUG-00:50 | 51971.68 | 31-JAN-08:00 |
WaterUse:WaterSystems:EnergyTransfer | 671.59 | 7488.09 | 04-AUG-00:50 | 51971.68 | 31-JAN-08:00 |
Boilers:EnergyTransfer | 374.75 | 0.00 | 19-JAN-21:00 | 144250.71 | 09-JAN-16:20 |
Chillers:EnergyTransfer | 4831.81 | 0.00 | 01-JAN-00:10 | 610895.40 | 23-AUG-22:00 |
HeatRejection:EnergyTransfer | 6335.73 | 0.00 | 01-JAN-00:10 | 764314.87 | 23-AUG-22:00 |
General:HeatRejection:EnergyTransfer | 6335.73 | 0.00 | 01-JAN-00:10 | 764314.87 | 23-AUG-22:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -368.589 | 0.000 | 0.000 | 143.615 | 122.932 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -41.064 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.700 | -34.716 | 0.000 | 0.000 | 14.743 | 6.265 | 10.186 | 18.407 | 0.000 | 0.319 | 0.000 | 0.000 | -8.415 | 0.000 | -2.661 | -4.828 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -37.561 | 0.000 | 0.000 | 17.036 | 7.255 | 11.795 | 0.000 | 0.000 | 0.151 | 2.356 | 0.000 | 0.000 | 0.000 | -1.031 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.159 | -12.445 | 0.000 | 0.000 | 3.441 | 8.366 | 12.471 | 0.000 | 0.000 | 0.287 | 0.000 | 0.000 | 0.000 | 0.000 | -2.664 | -9.616 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.323 | -18.032 | 0.000 | 0.000 | 2.918 | 2.308 | 3.598 | 0.000 | 0.000 | 0.238 | 9.934 | 0.000 | 0.000 | 0.000 | -1.287 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -590.898 | 0.000 | 0.000 | 10.551 | 4.900 | 658.131 | 0.000 | 0.000 | 0.391 | 0.000 | 0.000 | 0.000 | 0.000 | -3.896 | -79.179 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.001 | -250.226 | 0.000 | 0.000 | 198.667 | 12.896 | 14.341 | 53.266 | 0.000 | 1.024 | 0.001 | 0.000 | -23.251 | 0.000 | -5.667 | -1.050 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -803.419 | 0.000 | 0.000 | 564.942 | 92.208 | 148.998 | 69.492 | 0.000 | 2.531 | 0.000 | 0.000 | -32.596 | 0.000 | -17.394 | -24.763 |
ROOM_1_FLR_3 | 12.513 | -43.233 | 0.000 | -11.457 | 0.000 | 0.000 | 9.687 | 4.922 | 10.478 | 38.850 | 0.000 | 1.301 | 0.970 | 0.000 | -17.732 | 0.000 | -6.300 | -0.001 |
ROOM_2_FLR_3 | 15.954 | -33.131 | 0.000 | -11.883 | 0.000 | 0.000 | 9.592 | 4.922 | 10.477 | 29.834 | 0.000 | 1.141 | 0.000 | 0.000 | -18.791 | 0.000 | -6.655 | -1.459 |
ROOM_3_MULT19_FLR_3 | 0.147 | -234.190 | 0.000 | -15.489 | 0.000 | 0.000 | 0.000 | 58.777 | 194.997 | 200.364 | 0.000 | 1.781 | 0.006 | 0.000 | -135.622 | 0.000 | -46.153 | -24.612 |
ROOM_4_MULT19_FLR_3 | 51.772 | -245.883 | 0.000 | -159.892 | 0.000 | 0.000 | 182.505 | 58.793 | 195.050 | 90.289 | 0.000 | 6.691 | 0.000 | 0.000 | -104.821 | 0.000 | -46.774 | -27.730 |
ROOM_5_FLR_3 | 12.462 | -43.349 | 0.000 | -11.466 | 0.000 | 0.000 | 9.680 | 4.922 | 10.478 | 38.715 | 0.000 | 1.300 | 0.714 | 0.000 | -17.135 | 0.000 | -6.323 | -0.001 |
ROOM_6_FLR_3 | 15.885 | -33.435 | 0.000 | -11.877 | 0.000 | 0.000 | 9.597 | 4.922 | 10.477 | 29.207 | 0.000 | 1.140 | 0.000 | 0.000 | -17.684 | 0.000 | -6.600 | -1.631 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.918 | -166.237 | 0.000 | 0.000 | 117.506 | 56.739 | 0.000 | 35.154 | 0.000 | 1.097 | 0.000 | 0.000 | -23.170 | 0.000 | -7.099 | -14.908 |
ROOM_1_FLR_6 | 4.713 | -10.941 | 0.000 | -2.861 | 0.000 | 0.000 | 2.425 | 1.231 | 2.620 | 9.647 | 0.000 | 0.326 | 0.000 | 0.000 | -4.378 | 0.000 | -1.600 | -1.182 |
ROOM_2_FLR_6 | 5.798 | -8.584 | 0.000 | -2.964 | 0.000 | 0.000 | 2.402 | 1.230 | 2.619 | 7.412 | 0.000 | 0.283 | 0.000 | 0.000 | -4.646 | 0.000 | -1.693 | -1.859 |
ROOM_3_MULT9_FLR_6 | 11.640 | -64.449 | 0.000 | -18.496 | 0.000 | 0.000 | 21.733 | 6.962 | 23.098 | 49.269 | 0.000 | 1.663 | 0.001 | 0.000 | -20.355 | 0.000 | -8.488 | -2.576 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -488.063 | 0.000 | 0.000 | 336.921 | 28.398 | 175.857 | 9.717 | 0.000 | 0.595 | 0.000 | 0.000 | -14.031 | 0.000 | -3.884 | -45.511 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -511.331 | 0.000 | 0.000 | 331.542 | 28.398 | 175.857 | 9.375 | 0.000 | 0.560 | 0.000 | 0.000 | -14.680 | 0.000 | -3.996 | -15.725 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -606.349 | 0.000 | 0.000 | 27.943 | 13.339 | 540.650 | 18.565 | 0.000 | 0.387 | 20.162 | 0.000 | -10.692 | 0.000 | -4.004 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 1.561 | -66.713 | 0.000 | 0.000 | 29.767 | 15.012 | 0.000 | 16.135 | 0.000 | 0.381 | 18.409 | 0.000 | -11.136 | 0.000 | -3.415 | -0.000 |
Total Facility | 130.883 | -717.195 | 3.663 | -4200.966 | 0.000 | 0.000 | 2047.214 | 545.696 | 2355.282 | 723.697 | 0.000 | 23.587 | 52.554 | 0.000 | -479.133 | 0.000 | -187.583 | -297.693 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 08-NOV-22:00 | 0.00 | 0.00 | 0.00 | -20581.83 | 0.00 | 0.00 | 5924.41 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3404.22 |
RETAIL_1_FLR_1 | 10-OCT-13:30 | 0.00 | 0.00 | 0.00 | -3197.05 | 0.00 | 0.00 | 150.60 | 142.31 | 252.59 | 4082.24 | 0.00 | 54.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1484.76 |
RETAIL_2_FLR_1 | 18-AUG-21:00 | 0.00 | 0.00 | 0.00 | -2073.56 | 0.00 | 0.00 | 697.61 | 527.34 | 752.15 | 0.00 | 0.00 | 30.30 | 66.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 07-JUL-21:00 | 0.00 | 0.00 | 0.00 | -1852.44 | 0.00 | 0.00 | 147.53 | 608.16 | 795.27 | 0.00 | 0.00 | 66.67 | 234.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 19-AUG-10:35 | 0.00 | 0.00 | 0.00 | -1041.45 | 0.00 | 0.00 | 45.45 | 52.42 | 89.22 | 0.00 | 0.00 | 52.93 | 801.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 07-JUL-20:00 | 0.00 | 0.00 | 0.00 | -39496.20 | 0.00 | 0.00 | 408.87 | 400.68 | 44299.38 | 0.00 | 0.00 | 97.79 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5710.52 |
CAFE_FLR_1 | 12-APR-15:17 | 0.00 | 0.00 | 0.00 | -12648.03 | 0.00 | 0.00 | 5265.71 | 96.16 | 355.63 | 5058.95 | 0.00 | 132.21 | 1739.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 18-AUG-21:10 | 0.00 | 0.00 | 0.00 | -39598.95 | 0.00 | 0.00 | 26440.12 | 5322.69 | 7389.94 | 619.20 | 0.00 | 476.59 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -649.60 |
ROOM_1_FLR_3 | 09-APR-15:11 | 0.00 | -12355.78 | 0.00 | -709.86 | 0.00 | 0.00 | 130.71 | 125.03 | 221.25 | 7170.19 | 0.00 | 0.00 | 5492.04 | 0.00 | -0.00 | 0.00 | -73.58 | 0.00 |
ROOM_2_FLR_3 | 09-MAY-20:41 | 0.00 | -12748.76 | 0.00 | -561.25 | 0.00 | 0.00 | 370.95 | 337.15 | 726.90 | 0.00 | 0.00 | 0.00 | 13539.02 | 0.00 | -1404.67 | 0.00 | -259.34 | 0.00 |
ROOM_3_MULT19_FLR_3 | 10-OCT-13:40 | 0.00 | -37095.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1266.71 | 2352.88 | 46190.96 | 0.00 | 318.31 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -13033.40 |
ROOM_4_MULT19_FLR_3 | 09-MAY-20:41 | 0.00 | -79767.42 | 0.00 | -7683.34 | 0.00 | 0.00 | 7188.62 | 4027.42 | 13532.74 | 0.00 | 0.00 | 0.00 | 71057.16 | 0.00 | -6968.00 | 0.00 | -1387.19 | 0.00 |
ROOM_5_FLR_3 | 13-MAR-15:11 | 0.00 | -11137.80 | 0.00 | -708.45 | 0.00 | 0.00 | 235.28 | 106.08 | 200.18 | 2724.07 | 0.00 | 39.16 | 8541.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 04-JUN-08:51 | 0.00 | -11096.48 | 0.00 | -924.92 | 0.00 | 0.00 | 107.79 | 212.14 | 653.15 | 6764.09 | 0.00 | 0.00 | 4311.63 | 0.00 | -0.00 | 0.00 | -27.40 | 0.00 |
CORRIDOR_FLR_3 | 19-AUG-10:35 | 0.00 | 0.00 | 0.00 | -9098.27 | 0.00 | 0.00 | 1799.43 | 1288.89 | 0.00 | 4769.59 | 0.00 | 261.74 | 978.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 09-APR-15:11 | 0.00 | -3261.75 | 0.00 | -177.71 | 0.00 | 0.00 | 32.68 | 31.26 | 55.31 | 1775.12 | 0.00 | 0.00 | 1566.98 | 0.00 | -0.00 | 0.00 | -21.89 | 0.00 |
ROOM_2_FLR_6 | 09-MAY-20:41 | 0.00 | -3426.28 | 0.00 | -146.58 | 0.00 | 0.00 | 90.21 | 84.29 | 181.72 | 0.00 | 0.00 | 0.00 | 3649.31 | 0.00 | -365.13 | 0.00 | -67.53 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13-MAR-15:11 | 0.00 | -14930.74 | 0.00 | -1165.60 | 0.00 | 0.00 | 529.39 | 150.05 | 441.28 | 6734.21 | 0.00 | 36.32 | 8205.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 07-JUL-22:00 | 0.00 | 0.00 | 0.00 | -22247.01 | 0.00 | 0.00 | 15644.56 | 1842.08 | 6747.90 | 222.65 | 0.00 | 83.66 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2293.85 |
DINING_FLR_6 | 07-JUL-21:30 | 0.00 | 0.00 | 0.00 | -23655.20 | 0.00 | 0.00 | 15640.58 | 1842.08 | 6747.90 | 252.42 | 0.00 | 92.87 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -920.65 |
KITCHEN_FLR_6 | 15-APR-10:36 | 0.00 | 0.00 | 0.00 | -31388.68 | 0.00 | 0.00 | 464.21 | 303.01 | 23951.61 | 3103.51 | 0.00 | 1.66 | 3564.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 08-JUL-16:10 | 0.00 | 0.00 | 0.00 | -6276.64 | 0.00 | 0.00 | 771.16 | 341.02 | 0.00 | 1527.90 | 0.00 | 165.03 | 3471.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-AUG-18:02 | 0.00 | -152912.56 | 0.00 | -200553.39 | 0.00 | 0.00 | 77759.04 | 36835.56 | 120174.13 | 32926.02 | 0.00 | 5275.20 | 80495.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 12-FEB-06:10 | 0.00 | 0.00 | 1522.04 | 0.00 | 0.00 | 0.00 | 628.94 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1593.72 | 0.00 | -436.65 | -580.05 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 08-JAN-13:40 | 0.00 | 0.00 | 468.43 | 0.00 | 0.00 | 0.00 | 43.84 | 152.04 | 265.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -245.91 | -683.49 |
STORAGE_FLR_1 | 12-FEB-07:00 | 0.00 | 0.00 | 443.00 | 0.00 | 0.00 | 0.00 | 118.04 | 62.90 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -234.35 | -491.55 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 09-JAN-09:04 | 0.00 | 0.00 | 377.48 | 0.00 | 0.00 | 0.00 | 2352.03 | 153.85 | 508.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2082.83 | 0.00 | -671.61 | -636.95 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 07-JAN-19:13 | 5857.27 | 350.87 | 0.00 | -350.87 | 0.00 | 0.00 | 323.25 | 378.87 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2864.39 | 0.00 | -761.84 | -3417.81 |
ROOM_2_FLR_3 | 12-FEB-09:02 | 5918.47 | 267.60 | 0.00 | -267.60 | 0.00 | 0.00 | 163.33 | 212.14 | 653.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2652.63 | 0.00 | -894.39 | -3400.07 |
ROOM_3_MULT19_FLR_3 | 09-JAN-05:10 | 5472.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 995.27 | 3333.24 | 0.00 | 0.00 | 0.00 | 3900.91 | 0.00 | -10969.33 | 0.00 | -2732.65 | 0.00 |
ROOM_4_MULT19_FLR_3 | 03-FEB-16:11 | 32892.15 | 3681.70 | 0.00 | -3681.70 | 0.00 | 0.00 | 5548.30 | 1267.05 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8050.55 | 0.00 | -2707.71 | -32675.65 |
ROOM_5_FLR_3 | 07-JAN-16:23 | 5695.38 | 344.97 | 0.00 | -344.97 | 0.00 | 0.00 | 149.90 | 125.03 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2136.23 | 0.00 | -723.17 | -3332.16 |
ROOM_6_FLR_3 | 07-JAN-16:23 | 5709.50 | 338.80 | 0.00 | -338.80 | 0.00 | 0.00 | 150.83 | 125.01 | 221.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2257.55 | 0.00 | -720.65 | -3228.38 |
CORRIDOR_FLR_3 | 09-JAN-09:04 | 0.00 | 0.00 | 3649.04 | 0.00 | 0.00 | 0.00 | 1385.75 | 2062.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2348.63 | 0.00 | -854.44 | -3893.94 |
ROOM_1_FLR_6 | 07-JAN-19:13 | 1747.22 | 84.77 | 0.00 | -84.77 | 0.00 | 0.00 | 81.74 | 94.72 | 121.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -711.11 | 0.00 | -189.75 | -1143.99 |
ROOM_2_FLR_6 | 12-FEB-09:13 | 1760.26 | 81.33 | 0.00 | -81.33 | 0.00 | 0.00 | 38.13 | 53.04 | 163.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -652.93 | 0.00 | -226.89 | -1134.89 |
ROOM_3_MULT9_FLR_6 | 07-JAN-16:23 | 8055.61 | 554.23 | 0.00 | -554.23 | 0.00 | 0.00 | 336.42 | 176.84 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2230.53 | 0.00 | -834.65 | -5991.43 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 12-FEB-06:00 | 0.00 | 0.00 | 3214.73 | 0.00 | 0.00 | 0.00 | 1283.31 | 272.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2134.91 | 0.00 | -543.09 | -2092.86 |
Total Facility | 07-JAN-16:23 | -4226.39 | 77603.87 | 7291.26 | -77603.87 | 0.00 | 0.00 | 36744.93 | 12231.35 | 74529.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -46951.19 | 0.00 | -17952.07 | -61667.84 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 21.1061 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 20.9954 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 13.0393 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.5293 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2336 | 2.2336 | 1.2821 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3067 | 0.3067 | 0.1187 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2267 | 0.2267 | 0.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2003 | 0.2003 | 0.0020 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1101 | 0.1101 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3806 | 3.3806 | 0.0338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3726 | 1.3726 | 1.0144 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6408 | 4.6408 | 2.8401 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1890 | 1.1890 | 0.7122 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2089 | 2.2089 | 1.7826 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3188 | 2.3188 | 1.7808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2354 | 2.2354 | 0.5499 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6826 | 0.6826 | 0.1884 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 21.1061 | 20.9954 | 21.1061 | 10.5293 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2821 | 1.2821 | 1.2821 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1534 | 0.1534 | 0.1187 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1376 | 0.1376 | 0.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1002 | 0.1002 | 0.0020 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0866 | 0.0866 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6903 | 1.6903 | 0.0338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0144 | 1.0144 | 1.0144 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8401 | 2.8401 | 2.8401 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7122 | 0.7122 | 0.7122 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7826 | 1.7826 | 1.7826 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7808 | 1.7808 | 1.7808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1177 | 1.1177 | 0.5499 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3413 | 0.3413 | 0.1884 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 13.0393 | 10.5293 | 10.5293 | 10.5293 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 15.17 |
Number of hours cooling loads not met | 73.50 |
Number of hours not met | 88.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 554.66 | 181957.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1503.92 | 183539.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 545.70 | 45764.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 194.02 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.52 | 1274.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 591.93 | 37841.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 86.32 | 4119.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 110.26 | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.76 | 2906.88 | 271213.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.86 | 1321.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.25 | 716.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1692.66 | 5456.09 |
Natural Gas | 1788.84 | 5250.38 |
Additional | 0.00 | 0.00 |
Total | 3481.49 | 10706.47 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 48.10 |
Space Heating | 0.00 |
Space Cooling | 132.56 |
Fans (All) | 52.17 |
Service Water Heating | 8.00 |
Receptacle Equipment | 145.30 |
Miscellaneous (All) | 480.91 |
Subtotal | 480.91 |
Natural Gas [MJ/m2] | |
Space Heating | 48.89 |
Service Water Heating | 256.22 |
Miscellaneous (All) | 462.78 |
Subtotal | 462.78 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.10 |
Space Heating | 5.18 |
Space Cooling | 14.05 |
Fans (All) | 5.53 |
Service Water Heating | 28.00 |
Receptacle Equipment | 32.10 |
Miscellaneous | 10.04 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 6915.33 | 1844.67 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 6915.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1844.67 | 0.00 | 0.00 | 0.00 |
Average | 8675.83 | 84.17 | 0.00 | 0.00 | 0.00 |
Sum | 190868.17 | 1851.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8528.50 | 231.50 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8735.33 | 24.67 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8742.00 | 18.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8364.67 | 395.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 7744.50 | 1015.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8750.00 | 10.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8547.67 | 212.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 6219.67 | 2540.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8604.83 | 155.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8507.83 | 252.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8733.83 | 26.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8517.33 | 242.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8736.17 | 23.83 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 7855.17 | 904.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 7771.50 | 988.50 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8614.17 | 145.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8513.67 | 246.33 | 0.00 | 0.00 | 0.00 |
Min | 6219.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2540.33 | 0.00 | 0.00 | 0.00 |
Average | 8421.17 | 338.83 | 0.00 | 0.00 | 0.00 |
Sum | 185265.67 | 7454.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 48149.17 | 2029.83 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58885.17 | 270.83 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8958.50 | 18.50 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 659814.33 | 50602.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1746631.67 | 368797.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4115.67 | 38.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4120.17 | 33.83 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4115.17 | 38.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100111.67 | 246.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4108.00 | 46.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1046686.50 | 199028.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1031611.83 | 214103.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107262.50 | 1006.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 101647.00 | 4299.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1746631.67 | 368797.33 | 0.00 | 0.00 | 0.00 |
Average | 250679.79 | 38207.26 | 0.00 | 0.00 | 0.00 |
Sum | 5514955.33 | 840559.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.289454E+11 | 12996.90 | 31-JAN-21:00 | 17.20 | 12.43 | 0.731740E+10 | 4565.03 | 27-JAN-22:10 | 17.20 | 12.43 |
February | 0.245214E+11 | 12527.08 | 01-FEB-21:00 | 9.40 | 8.81 | 0.628849E+10 | 4485.37 | 01-FEB-22:10 | 8.72 | 8.24 |
March | 0.254188E+11 | 12074.25 | 30-MAR-18:10 | 26.02 | 17.62 | 0.660577E+10 | 4253.97 | 01-MAR-22:10 | 26.02 | 17.62 |
April | 0.219602E+11 | 12802.98 | 14-APR-18:01 | 24.45 | 15.36 | 0.611651E+10 | 3914.77 | 14-APR-22:10 | 17.12 | 12.34 |
May | 0.259960E+11 | 13649.37 | 13-MAY-15:11 | 26.87 | 14.67 | 0.652479E+10 | 4072.95 | 26-MAY-22:10 | 18.12 | 17.79 |
June | 0.290910E+11 | 14110.69 | 25-JUN-10:35 | 29.80 | 23.29 | 0.690299E+10 | 4446.98 | 16-JUN-22:10 | 29.80 | 23.29 |
July | 0.324480E+11 | 14979.86 | 20-JUL-18:10 | 32.12 | 22.73 | 0.748654E+10 | 4685.28 | 28-JUL-22:10 | 17.70 | 17.38 |
August | 0.347966E+11 | 15842.19 | 27-AUG-10:35 | 29.47 | 22.52 | 0.792757E+10 | 4837.09 | 07-AUG-22:10 | 29.47 | 22.52 |
September | 0.363763E+11 | 19585.28 | 28-SEP-21:00 | 15.60 | 13.52 | 0.790523E+10 | 4837.39 | 15-SEP-21:10 | 15.60 | 13.52 |
October | 0.383179E+11 | 20541.38 | 12-OCT-21:00 | 12.20 | 9.05 | 0.819579E+10 | 4837.20 | 27-OCT-23:00 | 12.20 | 12.20 |
November | 0.368903E+11 | 20580.86 | 08-NOV-22:00 | 13.90 | 7.06 | 0.793174E+10 | 4837.16 | 30-NOV-00:10 | 8.98 | 7.61 |
December | 0.338250E+11 | 18415.35 | 01-DEC-22:00 | 3.90 | 0.00 | 0.804361E+10 | 4837.05 | 15-DEC-22:19 | 5.40 | 3.89 |
Annual Sum or Average | 0.368587E+12 | 0.872464E+11 | ||||||||
Minimum of Months | 0.219602E+11 | 12074.25 | 3.90 | 0.00 | 0.611651E+10 | 3914.77 | 5.40 | 3.89 | ||
Maximum of Months | 0.383179E+11 | 20580.86 | 32.12 | 23.29 | 0.819579E+10 | 4837.39 | 29.80 | 23.29 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111851E+10 | 1931.66 | 29-JAN-13:00 | 13.90 | 6.14 | 0.634708E+09 | 425.97 | 31-JAN-22:19 | 14.13 | 10.68 |
February | 0.147952E+10 | 2373.85 | 21-FEB-14:25 | 22.25 | 10.82 | 0.592375E+09 | 485.40 | 28-FEB-22:19 | 18.37 | 10.65 |
March | 0.257857E+10 | 2393.52 | 30-MAR-13:35 | 27.43 | 17.97 | 0.711950E+09 | 491.84 | 13-MAR-22:10 | 27.43 | 17.97 |
April | 0.281686E+10 | 2428.25 | 14-APR-13:05 | 26.78 | 15.32 | 0.715617E+09 | 491.84 | 12-APR-22:10 | 26.78 | 15.32 |
May | 0.323857E+10 | 2035.39 | 20-MAY-13:30 | 30.00 | 19.14 | 0.781404E+09 | 491.84 | 05-MAY-22:10 | 30.00 | 19.14 |
June | 0.376842E+10 | 2318.62 | 13-JUN-18:03 | 31.93 | 21.91 | 0.795203E+09 | 491.84 | 02-JUN-22:10 | 31.93 | 21.91 |
July | 0.424150E+10 | 2633.46 | 07-JUL-18:17 | 33.70 | 23.11 | 0.825038E+09 | 491.84 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.461671E+10 | 2952.71 | 19-AUG-13:40 | 33.70 | 23.70 | 0.837476E+09 | 491.84 | 07-AUG-22:10 | 33.70 | 23.70 |
September | 0.371738E+10 | 3036.25 | 24-SEP-12:40 | 28.70 | 19.86 | 0.777807E+09 | 491.88 | 15-SEP-21:10 | 28.70 | 19.86 |
October | 0.310296E+10 | 3197.05 | 10-OCT-13:30 | 28.85 | 20.88 | 0.742387E+09 | 491.84 | 11-OCT-22:10 | 14.40 | 8.97 |
November | 0.241575E+10 | 2500.51 | 08-NOV-13:40 | 20.20 | 9.59 | 0.666395E+09 | 468.70 | 08-NOV-22:19 | 13.33 | 6.86 |
December | 0.162110E+10 | 2264.48 | 10-DEC-13:00 | 15.60 | 7.72 | 0.650823E+09 | 472.45 | 12-DEC-22:40 | 18.30 | 14.79 |
Annual Sum or Average | 0.347158E+11 | 0.873118E+10 | ||||||||
Minimum of Months | 0.111851E+10 | 1931.66 | 13.90 | 6.14 | 0.592375E+09 | 425.97 | 13.33 | 6.86 | ||
Maximum of Months | 0.461671E+10 | 3197.05 | 33.70 | 23.70 | 0.837476E+09 | 491.88 | 33.70 | 23.70 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231811E+10 | 1304.92 | 31-JAN-21:00 | 17.20 | 12.43 | 0.755152E+09 | 514.33 | 31-JAN-23:10 | 12.22 | 9.67 |
February | 0.229947E+10 | 1445.61 | 28-FEB-21:00 | 20.60 | 11.78 | 0.705713E+09 | 552.51 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.300456E+10 | 1559.72 | 30-MAR-18:10 | 26.02 | 17.62 | 0.839114E+09 | 569.55 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.309403E+10 | 1698.73 | 14-APR-18:01 | 24.45 | 15.36 | 0.835375E+09 | 569.55 | 12-APR-22:10 | 24.45 | 15.36 |
May | 0.341100E+10 | 1706.27 | 19-MAY-21:00 | 23.90 | 16.26 | 0.891997E+09 | 569.55 | 05-MAY-22:10 | 23.90 | 16.26 |
June | 0.357602E+10 | 1852.66 | 27-JUN-21:00 | 27.20 | 20.99 | 0.899629E+09 | 569.55 | 08-JUN-22:10 | 27.20 | 20.99 |
July | 0.380028E+10 | 2026.02 | 07-JUL-21:00 | 30.60 | 22.80 | 0.933562E+09 | 569.55 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.387568E+10 | 2073.52 | 18-AUG-21:00 | 31.10 | 22.83 | 0.947431E+09 | 569.55 | 07-AUG-22:10 | 31.10 | 22.83 |
September | 0.346701E+10 | 1929.83 | 08-SEP-21:00 | 25.60 | 21.61 | 0.888228E+09 | 569.59 | 15-SEP-21:10 | 24.82 | 18.06 |
October | 0.321540E+10 | 1667.31 | 11-OCT-21:00 | 16.10 | 9.61 | 0.868171E+09 | 569.55 | 10-OCT-22:10 | 16.10 | 9.61 |
November | 0.285525E+10 | 1426.20 | 06-NOV-21:00 | 12.20 | 6.19 | 0.800114E+09 | 547.63 | 06-NOV-23:10 | 10.40 | 5.30 |
December | 0.264437E+10 | 1401.91 | 12-DEC-21:00 | 18.30 | 14.62 | 0.783264E+09 | 543.01 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.375612E+11 | 0.101477E+11 | ||||||||
Minimum of Months | 0.229947E+10 | 1304.92 | 12.20 | 6.19 | 0.705713E+09 | 514.33 | 10.40 | 5.30 | ||
Maximum of Months | 0.387568E+10 | 2073.52 | 31.10 | 22.83 | 0.947431E+09 | 569.59 | 31.10 | 22.83 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31296181.59 | 21.98 | 20-JAN-21:00 | 12.80 | 8.84 | 0.164998E+09 | 119.78 | 20-JAN-22:10 | 11.52 | 8.16 |
February | 60967156.50 | 652.01 | 28-FEB-22:00 | 18.90 | 10.96 | 0.159926E+09 | 120.45 | 22-FEB-22:10 | 18.90 | 10.96 |
March | 0.245526E+09 | 1052.42 | 30-MAR-21:00 | 23.90 | 16.89 | 0.197899E+09 | 120.45 | 13-MAR-21:00 | 23.90 | 16.89 |
April | 0.584754E+09 | 1063.68 | 19-APR-20:00 | 20.60 | 16.68 | 0.196604E+09 | 120.45 | 19-APR-21:19 | 18.53 | 16.00 |
May | 0.126258E+10 | 1340.45 | 19-MAY-21:00 | 23.90 | 16.26 | 0.205423E+09 | 120.45 | 19-MAY-01:10 | 23.90 | 16.26 |
June | 0.217118E+10 | 1656.21 | 13-JUN-21:00 | 28.30 | 21.76 | 0.199177E+09 | 120.45 | 08-JUN-21:00 | 28.30 | 21.76 |
July | 0.257230E+10 | 1852.40 | 07-JUL-21:00 | 30.60 | 22.80 | 0.205007E+09 | 120.45 | 24-JUL-21:30 | 26.15 | 20.09 |
August | 0.272476E+10 | 1824.48 | 18-AUG-21:00 | 31.10 | 22.83 | 0.205873E+09 | 120.45 | 25-AUG-21:30 | 25.85 | 18.41 |
September | 0.179908E+10 | 1635.43 | 07-SEP-20:00 | 27.20 | 22.45 | 0.198648E+09 | 120.46 | 15-SEP-21:10 | 24.82 | 18.06 |
October | 0.719231E+09 | 1214.31 | 18-OCT-21:00 | 23.30 | 22.56 | 0.203403E+09 | 120.45 | 12-OCT-21:40 | 23.30 | 22.56 |
November | 0.207346E+09 | 772.95 | 03-NOV-21:00 | 18.30 | 16.18 | 0.190073E+09 | 120.45 | 20-NOV-00:10 | 20.82 | 18.45 |
December | 66323237.66 | 576.44 | 13-DEC-22:00 | 13.30 | 12.92 | 0.180369E+09 | 120.45 | 11-DEC-22:10 | 13.30 | 12.92 |
Annual Sum or Average | 0.124453E+11 | 0.230740E+10 | ||||||||
Minimum of Months | 31296181.59 | 21.98 | 12.80 | 8.84 | 0.159926E+09 | 119.78 | 11.52 | 8.16 | ||
Maximum of Months | 0.272476E+10 | 1852.40 | 31.10 | 22.83 | 0.205873E+09 | 120.46 | 28.30 | 22.56 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286360E+09 | 669.55 | 31-JAN-21:00 | 17.20 | 12.43 | 0.116744E+09 | 70.84 | 31-JAN-23:10 | 12.22 | 9.67 |
February | 0.655711E+09 | 738.31 | 28-FEB-19:00 | 21.70 | 12.09 | 0.106060E+09 | 75.13 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.141438E+10 | 848.38 | 30-MAR-18:10 | 26.02 | 17.62 | 0.120467E+09 | 79.16 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.163130E+10 | 957.47 | 19-APR-15:11 | 26.70 | 17.30 | 0.120424E+09 | 79.45 | 18-APR-22:10 | 26.70 | 17.30 |
May | 0.189471E+10 | 972.83 | 13-MAY-15:11 | 26.87 | 14.67 | 0.130668E+09 | 82.24 | 19-MAY-22:10 | 21.93 | 15.69 |
June | 0.202826E+10 | 1006.16 | 25-JUN-10:35 | 29.80 | 23.29 | 0.134671E+09 | 85.88 | 28-JUN-22:10 | 26.10 | 21.34 |
July | 0.216544E+10 | 1038.14 | 08-JUL-10:35 | 33.17 | 24.62 | 0.141362E+09 | 88.12 | 07-JUL-22:10 | 33.17 | 24.62 |
August | 0.218809E+10 | 1041.36 | 19-AUG-10:35 | 32.03 | 24.19 | 0.143202E+09 | 88.21 | 18-AUG-21:00 | 32.03 | 24.19 |
September | 0.193966E+10 | 989.85 | 09-SEP-10:35 | 30.03 | 23.84 | 0.131672E+09 | 85.68 | 07-SEP-21:49 | 30.03 | 23.84 |
October | 0.171698E+10 | 876.08 | 11-OCT-10:35 | 24.67 | 19.78 | 0.125728E+09 | 81.21 | 18-OCT-22:10 | 22.80 | 22.03 |
November | 0.135333E+10 | 777.41 | 05-NOV-10:35 | 18.33 | 17.01 | 0.115823E+09 | 76.18 | 03-NOV-22:10 | 18.33 | 17.01 |
December | 0.757874E+09 | 738.49 | 13-DEC-11:35 | 19.80 | 17.47 | 0.117209E+09 | 74.32 | 13-DEC-23:10 | 12.62 | 12.25 |
Annual Sum or Average | 0.180321E+11 | 0.150403E+10 | ||||||||
Minimum of Months | 0.286360E+09 | 669.55 | 17.20 | 12.09 | 0.106060E+09 | 70.84 | 12.22 | 9.67 | ||
Maximum of Months | 0.218809E+10 | 1041.36 | 33.17 | 24.62 | 0.143202E+09 | 88.21 | 33.17 | 24.62 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.465022E+11 | 37441.47 | 31-JAN-21:00 | 17.20 | 12.43 | 0.649338E+09 | 381.58 | 11-JAN-22:19 | 17.20 | 12.43 |
February | 0.429563E+11 | 37966.75 | 28-FEB-21:00 | 20.60 | 11.78 | 0.587076E+09 | 381.58 | 08-FEB-23:10 | 20.60 | 11.78 |
March | 0.494345E+11 | 38398.04 | 30-MAR-20:00 | 24.40 | 16.98 | 0.652388E+09 | 381.59 | 28-MAR-21:19 | 24.40 | 16.98 |
April | 0.486837E+11 | 38560.12 | 17-APR-19:55 | 22.80 | 15.38 | 0.629508E+09 | 381.61 | 19-APR-21:19 | 18.53 | 16.00 |
May | 0.514786E+11 | 38897.31 | 19-MAY-20:00 | 25.60 | 17.28 | 0.650758E+09 | 381.69 | 17-MAY-21:10 | 25.60 | 17.28 |
June | 0.509374E+11 | 39272.32 | 13-JUN-20:00 | 29.40 | 21.98 | 0.630879E+09 | 381.67 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.528198E+11 | 39496.96 | 07-JUL-20:00 | 31.10 | 23.22 | 0.649339E+09 | 381.67 | 11-JUL-21:19 | 26.33 | 20.95 |
August | 0.531726E+11 | 39407.00 | 18-AUG-20:00 | 31.70 | 22.32 | 0.652093E+09 | 381.71 | 01-AUG-21:10 | 31.70 | 22.32 |
September | 0.500581E+11 | 39146.38 | 07-SEP-20:00 | 27.20 | 22.45 | 0.629197E+09 | 382.02 | 15-SEP-21:10 | 24.82 | 18.06 |
October | 0.500565E+11 | 38519.29 | 10-OCT-20:00 | 22.20 | 19.19 | 0.649646E+09 | 381.64 | 18-OCT-21:10 | 23.22 | 22.46 |
November | 0.473397E+11 | 37859.25 | 03-NOV-20:00 | 18.90 | 16.38 | 0.628131E+09 | 381.59 | 29-NOV-23:49 | 9.37 | 7.47 |
December | 0.474526E+11 | 37708.38 | 12-DEC-21:00 | 18.30 | 14.62 | 0.649344E+09 | 381.59 | 15-DEC-22:10 | 5.50 | 3.86 |
Annual Sum or Average | 0.590892E+12 | 0.765770E+10 | ||||||||
Minimum of Months | 0.429563E+11 | 37441.47 | 17.20 | 11.78 | 0.587076E+09 | 381.58 | 5.50 | 3.86 | ||
Maximum of Months | 0.531726E+11 | 39496.96 | 31.70 | 23.22 | 0.652388E+09 | 382.02 | 31.70 | 22.46 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157672E+11 | 10064.30 | 29-JAN-11:35 | 12.43 | 5.39 | 0.847735E+10 | 5742.91 | 31-JAN-22:40 | 13.37 | 10.31 |
February | 0.157273E+11 | 10572.79 | 26-FEB-11:35 | 22.07 | 11.70 | 0.787894E+10 | 6074.12 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.203386E+11 | 10878.49 | 30-MAR-15:13 | 27.80 | 17.21 | 0.918258E+10 | 6282.23 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.205538E+11 | 12648.31 | 12-APR-15:17 | 28.13 | 16.55 | 0.895092E+10 | 6201.50 | 17-APR-22:10 | 19.72 | 13.80 |
May | 0.224303E+11 | 11907.12 | 13-MAY-15:11 | 26.87 | 14.67 | 0.944687E+10 | 6246.03 | 18-MAY-21:40 | 22.07 | 16.54 |
June | 0.232277E+11 | 11145.95 | 24-JUN-17:20 | 32.60 | 22.26 | 0.948211E+10 | 6447.70 | 13-JUN-22:10 | 32.60 | 22.26 |
July | 0.246725E+11 | 11716.75 | 08-JUL-17:30 | 34.40 | 23.36 | 0.989521E+10 | 6460.40 | 14-JUL-22:10 | 27.80 | 21.43 |
August | 0.254372E+11 | 11711.99 | 02-AUG-18:10 | 32.80 | 23.11 | 0.101510E+11 | 6460.66 | 18-AUG-22:30 | 29.15 | 23.19 |
September | 0.229871E+11 | 11723.17 | 22-SEP-16:52 | 26.10 | 17.31 | 0.946942E+10 | 6460.42 | 25-SEP-22:10 | 23.03 | 19.17 |
October | 0.217911E+11 | 11429.57 | 10-OCT-15:23 | 29.45 | 20.61 | 0.941338E+10 | 6411.83 | 10-OCT-21:40 | 21.10 | 18.64 |
November | 0.194867E+11 | 10971.85 | 11-NOV-11:35 | 18.50 | 11.57 | 0.875085E+10 | 6030.17 | 08-NOV-22:40 | 18.50 | 11.57 |
December | 0.178043E+11 | 10432.64 | 10-DEC-11:35 | 12.93 | 6.50 | 0.870245E+10 | 6060.50 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.250224E+12 | 0.109801E+12 | ||||||||
Minimum of Months | 0.157273E+11 | 10064.30 | 12.43 | 5.39 | 0.787894E+10 | 5742.91 | 13.37 | 10.31 | ||
Maximum of Months | 0.254372E+11 | 12648.31 | 34.40 | 23.36 | 0.101510E+11 | 6460.66 | 32.60 | 23.19 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.547895E+11 | 28127.42 | 31-JAN-21:00 | 17.20 | 12.43 | 0.269151E+11 | 18322.09 | 31-JAN-22:40 | 13.37 | 10.31 |
February | 0.527399E+11 | 30149.08 | 28-FEB-21:00 | 20.60 | 11.78 | 0.250320E+11 | 19185.67 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.648202E+11 | 32111.23 | 30-MAR-21:53 | 22.80 | 16.45 | 0.293206E+11 | 19186.01 | 13-MAR-22:10 | 22.80 | 16.45 |
April | 0.653674E+11 | 34824.96 | 12-APR-15:17 | 28.13 | 16.55 | 0.287843E+11 | 19186.13 | 12-APR-22:10 | 17.88 | 13.25 |
May | 0.710357E+11 | 34410.68 | 13-MAY-15:11 | 26.87 | 14.67 | 0.304494E+11 | 19186.11 | 05-MAY-22:10 | 26.87 | 14.67 |
June | 0.735176E+11 | 36271.92 | 13-JUN-21:10 | 28.12 | 21.63 | 0.303835E+11 | 19186.18 | 08-JUN-22:10 | 28.12 | 21.63 |
July | 0.780526E+11 | 38564.24 | 07-JUL-21:10 | 30.40 | 22.79 | 0.314703E+11 | 19186.07 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.798888E+11 | 39592.55 | 18-AUG-21:10 | 30.82 | 22.88 | 0.318755E+11 | 19186.07 | 07-AUG-22:10 | 30.82 | 22.88 |
September | 0.722701E+11 | 37591.75 | 07-SEP-21:10 | 25.40 | 21.43 | 0.302518E+11 | 19186.25 | 15-SEP-21:10 | 24.82 | 18.06 |
October | 0.688313E+11 | 34383.58 | 10-OCT-21:10 | 21.10 | 18.77 | 0.301481E+11 | 19185.90 | 16-OCT-22:10 | 20.00 | 17.37 |
November | 0.624605E+11 | 29817.60 | 06-NOV-21:00 | 12.20 | 6.19 | 0.282155E+11 | 19111.88 | 08-NOV-22:49 | 12.48 | 6.54 |
December | 0.596397E+11 | 29684.88 | 12-DEC-21:00 | 18.30 | 14.62 | 0.279378E+11 | 19122.52 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.803413E+12 | 0.350784E+12 | ||||||||
Minimum of Months | 0.527399E+11 | 28127.42 | 12.20 | 6.19 | 0.250320E+11 | 18322.09 | 12.48 | 6.54 | ||
Maximum of Months | 0.798888E+11 | 39592.55 | 30.82 | 22.88 | 0.318755E+11 | 19186.25 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41989313.81 | 3160.63 | 28-JAN-16:11 | 12.20 | 4.56 | 93912768.02 | 56.69 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.168795E+09 | 3265.68 | 27-FEB-16:11 | 22.60 | 11.36 | 85946094.42 | 56.69 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.595024E+09 | 3265.16 | 13-MAR-15:11 | 24.07 | 13.32 | 97831193.42 | 58.75 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.104427E+10 | 3266.49 | 09-APR-15:11 | 21.70 | 11.19 | 95424168.35 | 56.69 | 18-APR-21:10 | 19.90 | 15.31 |
May | 0.151546E+10 | 3247.85 | 09-MAY-18:01 | 19.63 | 9.69 | 99192861.50 | 56.69 | 30-MAY-22:49 | 22.70 | 20.84 |
June | 0.204296E+10 | 2881.63 | 18-JUN-15:12 | 31.30 | 23.77 | 96326410.24 | 56.69 | 26-JUN-02:00 | 23.30 | 21.67 |
July | 0.229320E+10 | 2897.10 | 26-JUL-18:02 | 30.13 | 24.13 | 99463082.71 | 56.69 | 08-JUL-04:49 | 30.13 | 24.13 |
August | 0.241291E+10 | 2900.15 | 20-AUG-18:02 | 25.55 | 22.49 | 99633364.24 | 56.70 | 18-AUG-21:00 | 25.55 | 22.49 |
September | 0.162781E+10 | 2920.42 | 03-SEP-18:01 | 27.43 | 22.31 | 95960112.60 | 56.69 | 09-SEP-01:39 | 22.40 | 20.30 |
October | 0.842182E+09 | 3032.59 | 31-OCT-18:01 | 12.20 | 6.42 | 97985194.88 | 56.69 | 10-OCT-21:00 | 12.20 | 6.42 |
November | 0.299293E+09 | 3254.78 | 08-NOV-16:11 | 21.50 | 10.04 | 93815621.44 | 56.69 | 05-NOV-23:30 | 21.50 | 10.04 |
December | 84501215.10 | 3202.55 | 10-DEC-16:11 | 18.33 | 9.11 | 94925933.14 | 56.69 | 12-DEC-23:00 | 17.80 | 14.77 |
Annual Sum or Average | 0.129684E+11 | 0.115042E+10 | ||||||||
Minimum of Months | 41989313.81 | 2881.63 | 12.20 | 4.56 | 85946094.42 | 56.69 | 12.20 | 6.42 | ||
Maximum of Months | 0.241291E+10 | 3266.49 | 31.30 | 24.13 | 99633364.24 | 58.75 | 30.13 | 24.13 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11941121.21 | 597.47 | 16-JAN-16:13 | 10.60 | 3.49 | 92753244.96 | 56.69 | 28-JAN-03:00 | -3.3 | -5.3 |
February | 58762386.81 | 2876.63 | 20-FEB-19:21 | 13.60 | 7.91 | 85611487.61 | 65.70 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.311971E+09 | 3195.47 | 13-MAR-15:11 | 24.07 | 13.32 | 99257166.64 | 71.35 | 29-MAR-21:10 | 22.62 | 17.00 |
April | 0.734131E+09 | 3326.19 | 26-APR-18:41 | 14.60 | 7.53 | 99738227.15 | 73.87 | 14-APR-21:30 | 14.60 | 7.53 |
May | 0.125190E+10 | 3327.51 | 09-MAY-20:41 | 13.68 | 6.54 | 0.104804E+09 | 74.70 | 09-MAY-18:10 | 13.68 | 6.54 |
June | 0.189943E+10 | 2854.11 | 15-JUN-15:12 | 26.10 | 21.16 | 99829463.48 | 81.18 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.213949E+10 | 2943.99 | 02-JUL-21:51 | 22.80 | 18.09 | 0.102748E+09 | 79.25 | 18-JUL-21:10 | 22.80 | 21.57 |
August | 0.219296E+10 | 2863.28 | 28-AUG-15:12 | 29.60 | 22.39 | 0.101935E+09 | 75.01 | 23-AUG-21:00 | 29.60 | 22.39 |
September | 0.128867E+10 | 3177.17 | 18-SEP-16:01 | 25.40 | 17.60 | 0.100048E+09 | 74.74 | 11-SEP-21:00 | 25.40 | 17.60 |
October | 0.450951E+09 | 2986.95 | 15-OCT-16:21 | 24.15 | 17.28 | 0.100611E+09 | 71.59 | 10-OCT-21:10 | 24.15 | 17.28 |
November | 0.106144E+09 | 2480.67 | 05-NOV-15:12 | 24.07 | 18.30 | 93392073.24 | 61.51 | 02-NOV-21:40 | 24.07 | 18.30 |
December | 26434810.08 | 2582.19 | 07-DEC-16:11 | 14.80 | 6.67 | 93604019.71 | 59.61 | 12-DEC-22:19 | 18.30 | 14.70 |
Annual Sum or Average | 0.104728E+11 | 0.117433E+10 | ||||||||
Minimum of Months | 11941121.21 | 597.47 | 10.60 | 3.49 | 85611487.61 | 56.69 | -3.3 | -5.3 | ||
Maximum of Months | 0.219296E+10 | 3327.51 | 29.60 | 22.39 | 0.104804E+09 | 81.18 | 29.60 | 22.39 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11820267.58 | 176.62 | 31-JAN-15:05 | 20.92 | 13.08 | 0.00 | 0.00 | 01-JAN-00:10 | 20.92 | 13.08 |
February | 61896665.53 | 357.11 | 26-FEB-14:50 | 24.90 | 12.71 | 0.00 | 0.00 | 01-FEB-00:10 | 24.90 | 12.71 |
March | 0.184129E+09 | 348.27 | 30-MAR-13:35 | 27.43 | 17.97 | 0.00 | 0.00 | 01-MAR-00:10 | 27.43 | 17.97 |
April | 0.230249E+09 | 328.49 | 15-APR-13:52 | 27.80 | 15.01 | 0.00 | 0.00 | 01-APR-00:10 | 27.80 | 15.01 |
May | 0.309403E+09 | 272.10 | 19-MAY-17:20 | 30.20 | 19.07 | 0.00 | 0.00 | 01-MAY-00:10 | 30.20 | 19.07 |
June | 0.422304E+09 | 311.03 | 13-JUN-17:20 | 32.60 | 22.18 | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 22.18 |
July | 0.497628E+09 | 351.01 | 08-JUL-17:30 | 34.40 | 23.36 | 0.00 | 0.00 | 01-JUL-00:10 | 34.40 | 23.36 |
August | 0.579596E+09 | 390.34 | 19-AUG-13:40 | 33.70 | 23.70 | 0.00 | 0.00 | 01-AUG-00:10 | 33.70 | 23.70 |
September | 0.435481E+09 | 451.64 | 24-SEP-12:50 | 28.80 | 19.88 | 0.00 | 0.00 | 01-SEP-00:10 | 28.80 | 19.88 |
October | 0.308653E+09 | 488.13 | 10-OCT-13:40 | 29.03 | 20.94 | 0.00 | 0.00 | 01-OCT-00:10 | 29.03 | 20.94 |
November | 0.171569E+09 | 412.81 | 08-NOV-14:10 | 20.78 | 9.75 | 0.00 | 0.00 | 01-NOV-00:10 | 20.78 | 9.75 |
December | 72563605.91 | 382.14 | 10-DEC-14:30 | 17.50 | 8.24 | 0.00 | 0.00 | 01-DEC-00:10 | 17.50 | 8.24 |
Annual Sum or Average | 0.328529E+10 | 0.00 | ||||||||
Minimum of Months | 11820267.58 | 176.62 | 17.50 | 8.24 | 0.00 | 0.00 | 17.50 | 8.24 | ||
Maximum of Months | 0.579596E+09 | 488.13 | 34.40 | 23.70 | 0.00 | 0.00 | 34.40 | 23.70 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36598338.59 | 867.26 | 01-JAN-09:02 | 11.78 | 10.88 | 94387761.55 | 62.80 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.100037E+09 | 1068.45 | 28-FEB-22:52 | 17.30 | 10.02 | 86482894.31 | 67.75 | 28-FEB-22:00 | 17.30 | 10.02 |
March | 0.259253E+09 | 1075.28 | 13-MAR-15:11 | 24.07 | 13.32 | 98206424.20 | 69.80 | 28-MAR-21:10 | 22.02 | 17.20 |
April | 0.404867E+09 | 1073.53 | 09-APR-20:11 | 13.70 | 8.28 | 98185494.03 | 71.98 | 24-APR-21:10 | 13.22 | 9.86 |
May | 0.586854E+09 | 1150.67 | 09-MAY-20:41 | 13.68 | 6.54 | 0.103264E+09 | 73.33 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.776560E+09 | 1045.14 | 30-JUN-18:02 | 25.10 | 21.60 | 98865696.42 | 77.29 | 26-JUN-21:10 | 25.10 | 21.60 |
July | 0.848278E+09 | 1050.26 | 14-JUL-15:12 | 34.63 | 23.79 | 0.102065E+09 | 76.10 | 25-JUL-21:10 | 22.80 | 21.95 |
August | 0.844273E+09 | 1046.78 | 10-AUG-18:02 | 31.52 | 24.11 | 0.101295E+09 | 74.40 | 31-AUG-21:19 | 21.67 | 19.98 |
September | 0.588321E+09 | 1042.02 | 12-SEP-18:02 | 27.52 | 20.94 | 99267992.63 | 74.90 | 01-SEP-21:10 | 27.52 | 20.94 |
October | 0.328456E+09 | 1079.34 | 11-OCT-21:52 | 14.40 | 8.97 | 99674545.84 | 72.14 | 18-OCT-21:10 | 23.22 | 22.46 |
November | 0.174798E+09 | 1022.40 | 28-NOV-19:02 | 11.52 | 4.78 | 93942902.21 | 67.16 | 03-NOV-21:00 | 11.52 | 4.78 |
December | 67391899.81 | 865.73 | 23-DEC-09:02 | 7.80 | 7.80 | 95217060.60 | 64.05 | 12-DEC-22:00 | 7.80 | 7.80 |
Annual Sum or Average | 0.501569E+10 | 0.117086E+10 | ||||||||
Minimum of Months | 36598338.59 | 865.73 | 7.80 | 4.78 | 86482894.31 | 62.80 | 7.80 | 4.78 | ||
Maximum of Months | 0.848278E+09 | 1150.67 | 34.63 | 24.11 | 0.103264E+09 | 77.29 | 27.52 | 22.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32824180.38 | 2783.42 | 29-JAN-16:11 | 16.33 | 6.57 | 93990131.28 | 56.69 | 31-JAN-22:49 | 12.98 | 10.12 |
February | 0.183104E+09 | 2957.21 | 27-FEB-16:11 | 22.60 | 11.36 | 86073104.17 | 56.69 | 21-FEB-22:19 | 22.60 | 11.36 |
March | 0.531433E+09 | 2961.56 | 13-MAR-15:11 | 24.07 | 13.32 | 98002272.75 | 56.69 | 30-MAR-21:00 | 22.80 | 16.45 |
April | 0.100740E+10 | 2956.48 | 09-APR-15:11 | 21.70 | 11.19 | 95716652.37 | 56.69 | 19-APR-21:19 | 18.53 | 16.00 |
May | 0.154860E+10 | 2931.01 | 09-MAY-18:01 | 19.63 | 9.69 | 99418245.49 | 56.69 | 04-MAY-21:49 | 19.63 | 9.69 |
June | 0.208901E+10 | 2707.62 | 13-JUN-08:61 | 25.37 | 20.63 | 96443514.25 | 56.69 | 07-JUN-00:20 | 25.37 | 20.63 |
July | 0.237014E+10 | 2685.16 | 21-JUL-08:61 | 26.15 | 22.30 | 99517141.02 | 56.69 | 12-JUL-01:00 | 26.15 | 22.30 |
August | 0.242934E+10 | 2678.27 | 21-AUG-15:12 | 30.00 | 24.16 | 99671148.34 | 56.69 | 17-AUG-21:19 | 30.00 | 24.16 |
September | 0.163575E+10 | 2662.48 | 06-SEP-18:02 | 29.13 | 22.99 | 96054842.43 | 56.69 | 12-SEP-23:49 | 21.38 | 18.58 |
October | 0.820743E+09 | 2658.04 | 16-OCT-15:11 | 25.00 | 19.11 | 98161889.97 | 56.69 | 10-OCT-21:00 | 25.00 | 19.11 |
November | 0.275000E+09 | 2939.79 | 08-NOV-16:11 | 21.50 | 10.04 | 94028444.31 | 56.69 | 02-NOV-21:19 | 21.50 | 10.04 |
December | 77359116.34 | 2877.42 | 10-DEC-16:11 | 18.33 | 9.11 | 95045204.13 | 56.69 | 12-DEC-23:00 | 17.80 | 14.77 |
Annual Sum or Average | 0.130007E+11 | 0.115212E+10 | ||||||||
Minimum of Months | 32824180.38 | 2658.04 | 16.33 | 6.57 | 86073104.17 | 56.69 | 12.98 | 9.69 | ||
Maximum of Months | 0.242934E+10 | 2961.56 | 30.00 | 24.16 | 99671148.34 | 56.69 | 30.00 | 24.16 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12741613.37 | 536.95 | 29-JAN-09:02 | 5.65 | 1.66 | 92763017.98 | 56.69 | 08-JAN-03:49 | 5.65 | 1.66 |
February | 77886959.36 | 2632.90 | 24-FEB-09:02 | 7.57 | 2.82 | 85535327.51 | 65.02 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.291049E+09 | 2907.93 | 13-MAR-15:11 | 24.07 | 13.32 | 98485455.83 | 68.23 | 29-MAR-21:10 | 22.62 | 17.00 |
April | 0.723745E+09 | 2842.30 | 14-APR-08:51 | 19.40 | 14.17 | 99156908.69 | 71.50 | 17-APR-21:40 | 20.00 | 13.94 |
May | 0.128170E+10 | 2996.74 | 18-MAY-08:51 | 24.40 | 17.97 | 0.104631E+09 | 75.43 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.191633E+10 | 3005.47 | 04-JUN-08:51 | 24.40 | 18.28 | 0.100189E+09 | 78.01 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.218076E+10 | 2810.93 | 25-JUL-08:51 | 24.40 | 20.24 | 0.103335E+09 | 79.67 | 25-JUL-21:10 | 22.80 | 21.95 |
August | 0.219057E+10 | 2872.10 | 26-AUG-08:51 | 24.40 | 19.19 | 0.102226E+09 | 76.46 | 07-AUG-21:00 | 24.40 | 19.19 |
September | 0.128233E+10 | 2942.26 | 15-SEP-08:51 | 21.70 | 14.94 | 0.100132E+09 | 74.25 | 01-SEP-21:10 | 21.70 | 14.94 |
October | 0.458659E+09 | 2594.48 | 09-OCT-18:01 | 24.13 | 18.81 | 0.100040E+09 | 71.27 | 17-OCT-21:10 | 23.22 | 20.61 |
November | 0.109608E+09 | 2482.46 | 11-NOV-09:01 | 9.63 | 7.91 | 92943727.18 | 62.11 | 03-NOV-21:30 | 9.63 | 7.91 |
December | 24627217.98 | 803.21 | 10-DEC-09:02 | 8.35 | 3.66 | 93552172.91 | 59.09 | 12-DEC-22:19 | 18.30 | 14.70 |
Annual Sum or Average | 0.105500E+11 | 0.117299E+10 | ||||||||
Minimum of Months | 12741613.37 | 536.95 | 5.65 | 1.66 | 85535327.51 | 56.69 | 5.65 | 1.66 | ||
Maximum of Months | 0.219057E+10 | 3005.47 | 24.40 | 20.24 | 0.104631E+09 | 79.67 | 24.40 | 21.95 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128522E+10 | 1390.06 | 31-JAN-21:00 | 17.20 | 12.43 | 0.120031E+10 | 733.88 | 31-JAN-22:40 | 13.37 | 10.31 |
February | 0.180946E+10 | 1621.08 | 27-FEB-19:10 | 19.82 | 10.52 | 0.110174E+10 | 797.70 | 28-FEB-22:49 | 17.57 | 10.18 |
March | 0.342121E+10 | 1834.53 | 30-MAR-18:10 | 26.02 | 17.62 | 0.128607E+10 | 829.32 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.375964E+10 | 2137.30 | 17-APR-17:10 | 28.03 | 16.54 | 0.131598E+10 | 864.97 | 18-APR-22:10 | 19.32 | 14.41 |
May | 0.422538E+10 | 2142.56 | 13-MAY-15:11 | 26.87 | 14.67 | 0.142340E+10 | 883.43 | 19-MAY-22:10 | 21.93 | 15.69 |
June | 0.447812E+10 | 2183.93 | 25-JUN-10:35 | 29.80 | 23.29 | 0.146078E+10 | 926.83 | 29-JUN-21:49 | 25.18 | 21.75 |
July | 0.479211E+10 | 2263.96 | 08-JUL-17:50 | 34.40 | 23.36 | 0.153777E+10 | 942.47 | 07-JUL-21:49 | 34.40 | 23.36 |
August | 0.482113E+10 | 2274.40 | 19-AUG-10:35 | 32.03 | 24.19 | 0.155278E+10 | 951.83 | 18-AUG-21:49 | 32.03 | 24.19 |
September | 0.427757E+10 | 2156.28 | 09-SEP-10:35 | 30.03 | 23.84 | 0.142468E+10 | 916.09 | 08-SEP-21:49 | 30.03 | 23.84 |
October | 0.372390E+10 | 1902.38 | 11-OCT-18:10 | 21.73 | 13.14 | 0.134075E+10 | 861.35 | 11-OCT-21:40 | 14.97 | 9.20 |
November | 0.296594E+10 | 1605.12 | 11-NOV-11:35 | 18.50 | 11.57 | 0.120198E+10 | 779.53 | 06-NOV-22:49 | 18.50 | 11.57 |
December | 0.199924E+10 | 1492.40 | 12-DEC-11:35 | 19.83 | 16.13 | 0.120650E+10 | 763.11 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.415589E+11 | 0.160527E+11 | ||||||||
Minimum of Months | 0.128522E+10 | 1390.06 | 17.20 | 10.52 | 0.110174E+10 | 733.88 | 13.37 | 9.20 | ||
Maximum of Months | 0.482113E+10 | 2274.40 | 34.40 | 24.19 | 0.155278E+10 | 951.83 | 34.40 | 24.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30736649.96 | 3300.61 | 29-JAN-16:11 | 16.33 | 6.57 | 93256876.21 | 56.69 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.152156E+09 | 3434.05 | 27-FEB-16:11 | 22.60 | 11.36 | 85449091.59 | 56.69 | 22-FEB-02:39 | 22.60 | 11.36 |
March | 0.562390E+09 | 3429.29 | 13-MAR-15:11 | 24.07 | 13.32 | 97474383.66 | 57.33 | 23-MAR-21:19 | 15.20 | 10.46 |
April | 0.102619E+10 | 3439.55 | 09-APR-15:11 | 21.70 | 11.19 | 95226033.07 | 56.69 | 05-APR-01:49 | 21.70 | 11.19 |
May | 0.154593E+10 | 3426.02 | 10-MAY-18:01 | 20.92 | 10.48 | 99096568.86 | 56.69 | 17-MAY-22:19 | 21.33 | 15.92 |
June | 0.210313E+10 | 3044.85 | 18-JUN-18:02 | 26.93 | 22.05 | 96283802.68 | 56.69 | 22-JUN-22:49 | 20.10 | 19.76 |
July | 0.236745E+10 | 3090.58 | 07-JUL-18:02 | 33.80 | 23.16 | 99419564.73 | 56.69 | 08-JUL-03:09 | 24.22 | 22.00 |
August | 0.248688E+10 | 3088.69 | 02-AUG-18:02 | 32.80 | 23.11 | 99606952.34 | 56.70 | 18-AUG-21:40 | 29.97 | 23.01 |
September | 0.160128E+10 | 3060.45 | 04-SEP-15:12 | 28.13 | 22.40 | 95830586.55 | 56.69 | 25-SEP-23:40 | 23.17 | 18.79 |
October | 0.779005E+09 | 3209.54 | 31-OCT-18:01 | 12.20 | 6.42 | 97619836.42 | 56.70 | 23-OCT-03:00 | 12.20 | 6.42 |
November | 0.260074E+09 | 3418.35 | 08-NOV-16:11 | 21.50 | 10.04 | 93400986.10 | 56.69 | 04-NOV-02:30 | 21.50 | 10.04 |
December | 68682548.51 | 3359.56 | 10-DEC-16:11 | 18.33 | 9.11 | 94269040.14 | 56.69 | 11-DEC-23:49 | 15.60 | 13.95 |
Annual Sum or Average | 0.129839E+11 | 0.114693E+10 | ||||||||
Minimum of Months | 30736649.96 | 3044.85 | 12.20 | 6.42 | 85449091.59 | 56.69 | 12.20 | 6.42 | ||
Maximum of Months | 0.248688E+10 | 3439.55 | 33.80 | 23.16 | 99606952.34 | 57.33 | 29.97 | 23.01 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9320197.59 | 734.17 | 28-JAN-16:13 | 12.20 | 4.56 | 92296080.54 | 56.69 | 29-JAN-04:10 | 0.60 | -1.5 |
February | 48988117.20 | 3036.78 | 20-FEB-19:21 | 13.60 | 7.91 | 85216140.19 | 65.73 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.284757E+09 | 3347.90 | 13-MAR-15:11 | 24.07 | 13.32 | 98894676.75 | 71.66 | 29-MAR-21:10 | 22.62 | 17.00 |
April | 0.720946E+09 | 3507.87 | 26-APR-18:41 | 14.60 | 7.53 | 99875494.27 | 75.46 | 14-APR-21:30 | 14.60 | 7.53 |
May | 0.131058E+10 | 3572.86 | 09-MAY-20:41 | 13.68 | 6.54 | 0.104919E+09 | 77.98 | 09-MAY-18:10 | 13.68 | 6.54 |
June | 0.199066E+10 | 2994.07 | 05-JUN-18:02 | 30.82 | 19.88 | 99636099.88 | 82.59 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.224533E+10 | 3090.60 | 06-JUL-18:02 | 32.12 | 24.13 | 0.102464E+09 | 79.35 | 18-JUL-21:10 | 22.80 | 21.57 |
August | 0.228674E+10 | 3055.37 | 18-AUG-18:02 | 33.72 | 23.57 | 0.101705E+09 | 74.74 | 07-AUG-21:00 | 33.72 | 23.57 |
September | 0.128683E+10 | 3320.13 | 18-SEP-16:01 | 25.40 | 17.60 | 99700849.70 | 74.35 | 11-SEP-21:00 | 25.40 | 17.60 |
October | 0.398157E+09 | 3197.92 | 15-OCT-16:21 | 24.15 | 17.28 | 0.100169E+09 | 71.55 | 10-OCT-21:19 | 24.15 | 17.28 |
November | 81866032.86 | 2648.08 | 05-NOV-15:12 | 24.07 | 18.30 | 92811756.37 | 60.83 | 02-NOV-21:40 | 24.07 | 18.30 |
December | 19394397.35 | 1277.41 | 07-DEC-16:11 | 14.80 | 6.67 | 92944441.93 | 58.27 | 12-DEC-22:19 | 18.30 | 14.70 |
Annual Sum or Average | 0.106836E+11 | 0.117063E+10 | ||||||||
Minimum of Months | 9320197.59 | 734.17 | 12.20 | 4.56 | 85216140.19 | 56.69 | 0.60 | -1.5 | ||
Maximum of Months | 0.228674E+10 | 3572.86 | 33.72 | 24.13 | 0.104919E+09 | 82.59 | 33.72 | 23.57 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137600E+09 | 1740.00 | 28-JAN-16:11 | 12.20 | 4.56 | 95932813.54 | 57.00 | 19-JAN-22:49 | 12.20 | 4.56 |
February | 0.236144E+09 | 1784.09 | 27-FEB-16:11 | 22.60 | 11.36 | 87327622.57 | 60.29 | 16-FEB-22:49 | 22.60 | 11.36 |
March | 0.519087E+09 | 1788.47 | 13-MAR-15:11 | 24.07 | 13.32 | 98277143.62 | 61.67 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.661864E+09 | 1747.18 | 09-APR-18:01 | 20.45 | 11.08 | 95450153.50 | 56.69 | 20-APR-21:40 | 18.90 | 15.33 |
May | 0.867838E+09 | 1743.03 | 10-MAY-18:01 | 20.92 | 10.48 | 99115541.57 | 56.69 | 31-MAY-22:40 | 21.53 | 18.84 |
June | 0.112913E+10 | 1589.30 | 28-JUN-18:02 | 30.50 | 23.40 | 96279482.16 | 56.69 | 29-JUN-21:10 | 25.92 | 21.53 |
July | 0.129475E+10 | 1590.43 | 23-JUL-18:02 | 28.80 | 22.43 | 99414226.29 | 56.69 | 18-JUL-01:19 | 28.80 | 22.43 |
August | 0.144353E+10 | 1599.51 | 22-AUG-18:02 | 28.72 | 24.40 | 99616566.20 | 56.70 | 01-AUG-21:00 | 28.72 | 24.40 |
September | 0.107257E+10 | 1600.03 | 04-SEP-15:12 | 28.13 | 22.40 | 95938795.23 | 56.70 | 15-SEP-21:10 | 24.82 | 18.06 |
October | 0.751938E+09 | 1727.24 | 12-OCT-18:01 | 17.23 | 10.36 | 98398227.36 | 56.69 | 09-OCT-23:40 | 17.23 | 10.36 |
November | 0.470137E+09 | 1783.82 | 08-NOV-16:11 | 21.50 | 10.04 | 94982053.59 | 56.69 | 02-NOV-00:10 | 21.50 | 10.04 |
December | 0.250633E+09 | 1761.22 | 10-DEC-16:11 | 18.33 | 9.11 | 96771064.34 | 56.69 | 11-DEC-22:10 | 15.60 | 13.95 |
Annual Sum or Average | 0.883522E+10 | 0.115750E+10 | ||||||||
Minimum of Months | 0.137600E+09 | 1589.30 | 12.20 | 4.56 | 87327622.57 | 56.69 | 12.20 | 4.56 | ||
Maximum of Months | 0.144353E+10 | 1788.47 | 30.50 | 24.40 | 99616566.20 | 61.67 | 28.80 | 24.40 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342758E+11 | 17519.39 | 19-JAN-23:10 | 18.22 | 16.49 | 0.160536E+11 | 11103.78 | 19-JAN-23:10 | 18.22 | 16.49 |
February | 0.327999E+11 | 18301.69 | 28-FEB-22:00 | 18.90 | 10.96 | 0.148667E+11 | 11348.28 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.398790E+11 | 20852.25 | 30-MAR-21:07 | 23.72 | 16.82 | 0.172270E+11 | 11348.66 | 13-MAR-22:10 | 23.72 | 16.82 |
April | 0.407857E+11 | 21627.01 | 12-APR-15:17 | 28.13 | 16.55 | 0.170027E+11 | 11348.98 | 12-APR-22:10 | 17.88 | 13.25 |
May | 0.444137E+11 | 21822.98 | 13-MAY-15:11 | 26.87 | 14.67 | 0.179482E+11 | 11348.98 | 10-MAY-21:40 | 26.87 | 14.67 |
June | 0.448975E+11 | 21756.55 | 13-JUN-22:00 | 27.20 | 20.99 | 0.177037E+11 | 11349.06 | 07-JUN-22:10 | 27.20 | 20.99 |
July | 0.469550E+11 | 22247.16 | 07-JUL-22:00 | 29.40 | 22.70 | 0.182707E+11 | 11348.94 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.470008E+11 | 21982.52 | 18-AUG-22:00 | 29.40 | 23.06 | 0.183957E+11 | 11348.93 | 07-AUG-22:10 | 29.40 | 23.06 |
September | 0.429825E+11 | 20967.03 | 06-SEP-22:00 | 26.70 | 22.61 | 0.173835E+11 | 11348.93 | 11-SEP-22:10 | 23.22 | 19.91 |
October | 0.409654E+11 | 20402.80 | 18-OCT-21:10 | 23.22 | 22.46 | 0.173226E+11 | 11348.60 | 11-OCT-22:10 | 23.22 | 22.46 |
November | 0.371284E+11 | 18179.02 | 03-NOV-21:00 | 18.30 | 16.18 | 0.162665E+11 | 11348.32 | 03-NOV-22:10 | 17.80 | 16.05 |
December | 0.359751E+11 | 17915.33 | 12-DEC-23:10 | 18.22 | 14.85 | 0.163454E+11 | 11292.36 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.488059E+12 | 0.204786E+12 | ||||||||
Minimum of Months | 0.327999E+11 | 17519.39 | 18.22 | 10.96 | 0.148667E+11 | 11103.78 | 17.02 | 9.75 | ||
Maximum of Months | 0.470008E+11 | 22247.16 | 29.40 | 23.06 | 0.183957E+11 | 11349.06 | 29.40 | 23.06 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.368517E+11 | 18861.06 | 19-JAN-22:20 | 18.30 | 16.51 | 0.166204E+11 | 11347.44 | 31-JAN-22:49 | 12.98 | 10.12 |
February | 0.349617E+11 | 20247.72 | 28-FEB-22:10 | 18.63 | 10.80 | 0.153816E+11 | 11348.30 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.418677E+11 | 21444.93 | 30-MAR-21:53 | 22.80 | 16.45 | 0.177519E+11 | 11348.67 | 13-MAR-22:10 | 22.80 | 16.45 |
April | 0.425032E+11 | 22209.64 | 12-APR-15:17 | 28.13 | 16.55 | 0.174363E+11 | 11348.99 | 12-APR-22:10 | 17.88 | 13.25 |
May | 0.461035E+11 | 22435.55 | 13-MAY-15:11 | 26.87 | 14.67 | 0.183354E+11 | 11348.97 | 10-MAY-21:40 | 26.87 | 14.67 |
June | 0.466045E+11 | 23157.63 | 13-JUN-22:00 | 27.20 | 20.99 | 0.180378E+11 | 11349.07 | 07-JUN-22:10 | 27.20 | 20.99 |
July | 0.487547E+11 | 23650.69 | 07-JUL-21:30 | 30.00 | 22.76 | 0.185938E+11 | 11348.95 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.487974E+11 | 23369.60 | 18-AUG-21:20 | 30.53 | 22.93 | 0.187084E+11 | 11348.94 | 07-AUG-22:10 | 30.53 | 22.93 |
September | 0.445692E+11 | 22353.40 | 06-SEP-22:00 | 26.70 | 22.61 | 0.177488E+11 | 11348.94 | 11-SEP-22:10 | 23.22 | 19.91 |
October | 0.427416E+11 | 21419.49 | 18-OCT-21:53 | 22.80 | 21.95 | 0.177869E+11 | 11348.61 | 11-OCT-22:10 | 22.80 | 21.95 |
November | 0.391651E+11 | 20222.07 | 03-NOV-21:10 | 18.22 | 16.16 | 0.168156E+11 | 11348.35 | 02-NOV-22:10 | 18.22 | 16.16 |
December | 0.384067E+11 | 19956.51 | 12-DEC-22:10 | 18.30 | 14.66 | 0.169484E+11 | 11348.00 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.511327E+12 | 0.210165E+12 | ||||||||
Minimum of Months | 0.349617E+11 | 18861.06 | 18.22 | 10.80 | 0.153816E+11 | 11347.44 | 12.98 | 9.75 | ||
Maximum of Months | 0.487974E+11 | 23650.69 | 30.53 | 22.93 | 0.187084E+11 | 11349.07 | 30.53 | 22.93 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.452378E+11 | 25900.21 | 29-JAN-11:50 | 12.62 | 5.48 | 0.188679E+11 | 11319.66 | 07-JAN-18:10 | 12.62 | 5.48 |
February | 0.425020E+11 | 27108.95 | 26-FEB-11:50 | 22.43 | 11.86 | 0.170436E+11 | 11321.51 | 18-FEB-18:19 | 22.43 | 11.86 |
March | 0.501222E+11 | 27564.00 | 30-MAR-18:03 | 26.02 | 17.62 | 0.188763E+11 | 11319.57 | 11-MAR-18:10 | 26.02 | 17.62 |
April | 0.504598E+11 | 31385.35 | 15-APR-10:36 | 24.83 | 14.24 | 0.182645E+11 | 11326.36 | 15-APR-17:10 | 26.42 | 15.32 |
May | 0.540991E+11 | 30861.44 | 13-MAY-15:11 | 26.87 | 14.67 | 0.188727E+11 | 11325.96 | 13-MAY-17:10 | 26.02 | 14.15 |
June | 0.539683E+11 | 29466.18 | 25-JUN-10:40 | 29.80 | 23.29 | 0.182664E+11 | 11336.72 | 10-JUN-17:00 | 29.80 | 23.29 |
July | 0.562677E+11 | 29893.51 | 08-JUL-10:40 | 33.17 | 24.62 | 0.188682E+11 | 11319.67 | 15-JUL-17:10 | 33.30 | 24.04 |
August | 0.563534E+11 | 29776.45 | 27-AUG-10:50 | 30.03 | 22.67 | 0.188754E+11 | 11319.68 | 12-AUG-17:10 | 30.03 | 22.67 |
September | 0.523841E+11 | 30007.30 | 22-SEP-16:52 | 26.10 | 17.31 | 0.182621E+11 | 11321.52 | 30-SEP-17:19 | 17.60 | 15.56 |
October | 0.510826E+11 | 28130.67 | 09-OCT-10:50 | 24.03 | 18.11 | 0.188689E+11 | 11321.49 | 28-OCT-17:19 | 17.03 | 17.03 |
November | 0.472072E+11 | 26720.78 | 11-NOV-11:50 | 18.95 | 11.69 | 0.182586E+11 | 11319.41 | 04-NOV-17:10 | 18.95 | 11.69 |
December | 0.466743E+11 | 26236.62 | 12-DEC-11:50 | 20.22 | 16.28 | 0.188680E+11 | 11319.54 | 02-DEC-18:10 | 20.22 | 16.28 |
Annual Sum or Average | 0.606358E+12 | 0.222192E+12 | ||||||||
Minimum of Months | 0.425020E+11 | 25900.21 | 12.62 | 5.48 | 0.170436E+11 | 11319.41 | 12.62 | 5.48 | ||
Maximum of Months | 0.563534E+11 | 31385.35 | 33.17 | 24.62 | 0.188763E+11 | 11336.72 | 33.30 | 24.04 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150801E+10 | 1688.66 | 31-JAN-21:00 | 17.20 | 12.43 | 0.128371E+10 | 857.22 | 31-JAN-22:40 | 13.37 | 10.31 |
February | 0.229993E+10 | 2045.80 | 28-FEB-18:15 | 22.43 | 12.28 | 0.122352E+10 | 969.44 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.436347E+10 | 3495.82 | 30-MAR-15:10 | 27.80 | 17.14 | 0.151431E+10 | 1007.39 | 29-MAR-22:10 | 27.80 | 17.14 |
April | 0.520915E+10 | 4446.51 | 17-APR-15:10 | 28.90 | 16.41 | 0.156985E+10 | 1007.40 | 19-APR-21:19 | 18.53 | 16.00 |
May | 0.678081E+10 | 4910.19 | 30-MAY-15:10 | 30.13 | 21.49 | 0.169818E+10 | 1007.40 | 05-MAY-22:10 | 30.13 | 21.49 |
June | 0.861610E+10 | 5507.91 | 13-JUN-15:40 | 32.40 | 22.24 | 0.166261E+10 | 1007.40 | 08-JUN-22:10 | 32.40 | 22.24 |
July | 0.970190E+10 | 6277.30 | 08-JUL-16:10 | 36.32 | 23.83 | 0.171357E+10 | 1007.40 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.100244E+11 | 6236.53 | 18-AUG-15:10 | 34.50 | 23.13 | 0.172178E+10 | 1007.40 | 30-AUG-22:10 | 22.80 | 20.87 |
September | 0.698850E+10 | 5459.76 | 07-SEP-15:13 | 31.70 | 23.19 | 0.164761E+10 | 1007.44 | 15-SEP-21:10 | 24.82 | 18.06 |
October | 0.491573E+10 | 4167.79 | 10-OCT-15:10 | 29.08 | 20.63 | 0.158327E+10 | 1007.40 | 19-OCT-22:10 | 16.70 | 15.65 |
November | 0.374038E+10 | 2072.21 | 05-NOV-17:15 | 21.10 | 17.61 | 0.138319E+10 | 947.28 | 05-NOV-23:10 | 14.72 | 14.72 |
December | 0.256420E+10 | 1887.21 | 13-DEC-11:35 | 19.80 | 17.47 | 0.131218E+10 | 918.11 | 12-DEC-23:10 | 19.80 | 17.47 |
Annual Sum or Average | 0.667126E+11 | 0.183138E+11 | ||||||||
Minimum of Months | 0.150801E+10 | 1688.66 | 17.20 | 12.28 | 0.122352E+10 | 857.22 | 13.37 | 10.31 | ||
Maximum of Months | 0.100244E+11 | 6277.30 | 36.32 | 23.83 | 0.172178E+10 | 1007.44 | 32.40 | 22.24 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.406257E+09 | 1265.48 | 08-JAN-05:30 | -5.3 |
February | 0.204839E+09 | 1522.03 | 12-FEB-06:10 | -12.3 |
March | 2649099.50 | 148.27 | 22-MAR-09:20 | 4.40 |
April | 299102.71 | 85.48 | 06-APR-06:05 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 29245.05 | 28.75 | 31-OCT-08:08 | 7.80 |
November | 15323935.22 | 594.01 | 21-NOV-07:05 | -2.8 |
December | 70349085.34 | 766.01 | 01-DEC-07:20 | -3.7 |
Annual Sum or Average | 0.699747E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.3 | |
Maximum of Months | 0.406257E+09 | 1522.03 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102221E+09 | 468.44 | 08-JAN-13:40 | -0.8 |
February | 57200805.74 | 394.44 | 13-FEB-05:00 | -5.0 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.159422E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.102221E+09 | 468.44 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195692E+09 | 407.09 | 08-JAN-05:20 | -5.4 |
February | 0.118430E+09 | 442.99 | 12-FEB-07:00 | -12.8 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 9307866.15 | 133.30 | 18-DEC-08:05 | -5.0 |
Annual Sum or Average | 0.323430E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.195692E+09 | 442.99 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 773158.99 | 377.52 | 09-JAN-09:04 | -3.2 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 773158.99 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 773158.99 | 377.52 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.942508E+09 | 1464.31 | 07-JAN-19:13 | -5.6 |
February | 0.543272E+09 | 1462.84 | 12-FEB-09:02 | -10.2 |
March | 86769420.48 | 1394.56 | 23-MAR-08:62 | 6.97 |
April | 24660307.96 | 1377.17 | 06-APR-08:62 | 5.37 |
May | 1540262.74 | 1034.19 | 19-MAY-08:04 | 21.23 |
June | 475424.23 | 1091.78 | 02-JUN-08:04 | 22.48 |
July | 205784.87 | 641.68 | 28-JUL-18:05 | 18.90 |
August | 102101.36 | 629.41 | 25-AUG-08:04 | 22.15 |
September | 1207505.69 | 760.88 | 19-SEP-08:04 | 18.07 |
October | 54780341.69 | 1388.00 | 31-OCT-08:62 | 7.80 |
November | 0.192997E+09 | 1413.31 | 30-NOV-16:12 | 7.20 |
December | 0.575268E+09 | 1427.23 | 18-DEC-09:02 | -1.7 |
Annual Sum or Average | 0.242379E+10 | |||
Minimum of Months | 102101.36 | 629.41 | -10.2 | |
Maximum of Months | 0.942508E+09 | 1464.31 | 22.48 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119968E+10 | 1465.49 | 07-JAN-19:13 | -5.6 |
February | 0.699809E+09 | 1479.64 | 12-FEB-09:02 | -10.2 |
March | 0.118672E+09 | 1395.08 | 23-MAR-08:62 | 6.97 |
April | 28792427.52 | 1382.96 | 06-APR-08:62 | 5.37 |
May | 1303013.80 | 1072.99 | 13-MAY-08:53 | 20.00 |
June | 207909.49 | 542.49 | 08-JUN-08:53 | 19.40 |
July | 142113.02 | 485.54 | 28-JUL-21:55 | 17.80 |
August | 59333.83 | 278.66 | 25-AUG-08:54 | 24.40 |
September | 871528.26 | 765.29 | 15-SEP-08:53 | 21.70 |
October | 72144955.11 | 1403.18 | 26-OCT-08:62 | 5.05 |
November | 0.298219E+09 | 1437.93 | 22-NOV-09:02 | 1.05 |
December | 0.787087E+09 | 1449.27 | 18-DEC-09:02 | -1.7 |
Annual Sum or Average | 0.320699E+10 | |||
Minimum of Months | 59333.83 | 278.66 | -10.2 | |
Maximum of Months | 0.119968E+10 | 1479.64 | 24.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1938206.88 | 72.01 | 09-JAN-05:10 | -2.2 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 1938206.88 | |||
Minimum of Months | 0.00 | 0.00 | -2.2 | |
Maximum of Months | 1938206.88 | 72.01 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175994E+09 | 428.42 | 27-JAN-16:11 | 4.40 |
February | 95885218.82 | 432.79 | 03-FEB-16:11 | 1.50 |
March | 2786199.80 | 410.81 | 18-MAR-08:03 | 2.98 |
April | 519930.88 | 407.26 | 06-APR-15:13 | 15.60 |
May | 247533.15 | 383.98 | 10-MAY-08:05 | 11.57 |
June | 45059.92 | 149.68 | 03-JUN-21:56 | 20.60 |
July | 1841.36 | 18.41 | 28-JUL-21:58 | 17.80 |
August | 3807.22 | 44.42 | 30-AUG-21:56 | 22.80 |
September | 128578.31 | 225.69 | 19-SEP-08:54 | 19.40 |
October | 1169087.19 | 351.27 | 30-OCT-08:04 | 9.08 |
November | 13991985.29 | 403.40 | 22-NOV-16:11 | 11.83 |
December | 66636824.77 | 416.95 | 03-DEC-16:11 | 6.33 |
Annual Sum or Average | 0.357410E+09 | |||
Minimum of Months | 1841.36 | 18.41 | 1.50 | |
Maximum of Months | 0.175994E+09 | 432.79 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.946669E+09 | 1423.86 | 07-JAN-16:23 | -4.5 |
February | 0.534619E+09 | 1399.11 | 11-FEB-16:12 | -3.3 |
March | 93595647.57 | 1357.11 | 23-MAR-08:62 | 6.97 |
April | 24152927.12 | 1157.51 | 05-APR-18:03 | 8.72 |
May | 401679.73 | 673.31 | 26-MAY-08:05 | 20.10 |
June | 25426.53 | 178.92 | 23-JUN-08:06 | 24.18 |
July | 206606.23 | 428.28 | 28-JUL-18:05 | 18.90 |
August | 69673.38 | 252.65 | 24-AUG-08:06 | 23.80 |
September | 523629.28 | 660.24 | 30-SEP-15:15 | 17.97 |
October | 56956209.76 | 1352.56 | 31-OCT-08:62 | 7.80 |
November | 0.191355E+09 | 1379.77 | 30-NOV-16:12 | 7.20 |
December | 0.563414E+09 | 1389.80 | 25-DEC-16:12 | 5.93 |
Annual Sum or Average | 0.241199E+10 | |||
Minimum of Months | 25426.53 | 178.92 | -4.5 | |
Maximum of Months | 0.946669E+09 | 1423.86 | 24.18 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121034E+10 | 1427.39 | 07-JAN-16:23 | -4.5 |
February | 0.684660E+09 | 1419.50 | 03-FEB-16:11 | 1.50 |
March | 0.125144E+09 | 1358.26 | 23-MAR-08:62 | 6.97 |
April | 28927414.45 | 1171.00 | 06-APR-18:03 | 14.63 |
May | 504512.91 | 725.77 | 10-MAY-21:24 | 14.15 |
June | 48662.31 | 284.00 | 08-JUN-21:55 | 18.90 |
July | 53870.88 | 272.59 | 28-JUL-21:55 | 17.80 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 375318.03 | 576.57 | 29-SEP-08:04 | 14.78 |
October | 78026037.05 | 1352.29 | 31-OCT-08:62 | 7.80 |
November | 0.291919E+09 | 1384.16 | 30-NOV-16:12 | 7.20 |
December | 0.772370E+09 | 1410.81 | 03-DEC-16:11 | 6.33 |
Annual Sum or Average | 0.319237E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.5 | |
Maximum of Months | 0.121034E+10 | 1427.39 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158997E+09 | 912.29 | 09-JAN-09:04 | -3.2 |
February | 62111001.15 | 692.20 | 12-FEB-08:05 | -11.9 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 190328.12 | 107.65 | 22-NOV-07:10 | -3.2 |
December | 8253267.62 | 271.18 | 18-DEC-07:30 | -5.3 |
Annual Sum or Average | 0.229552E+09 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 0.158997E+09 | 912.29 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139677E+10 | 1747.22 | 07-JAN-19:13 | -5.6 |
February | 0.835037E+09 | 1738.92 | 12-FEB-09:02 | -10.2 |
March | 0.191412E+09 | 1665.60 | 23-MAR-08:62 | 6.97 |
April | 57367928.65 | 1655.21 | 06-APR-08:62 | 5.37 |
May | 2203538.77 | 941.53 | 13-MAY-08:03 | 17.67 |
June | 671968.16 | 934.47 | 04-JUN-08:04 | 22.57 |
July | 382101.94 | 523.69 | 28-JUL-18:05 | 18.90 |
August | 255988.37 | 887.79 | 25-AUG-08:04 | 22.15 |
September | 3260218.68 | 965.99 | 14-SEP-08:03 | 15.55 |
October | 0.127419E+09 | 1657.90 | 26-OCT-08:62 | 5.05 |
November | 0.363623E+09 | 1678.31 | 22-NOV-09:02 | 1.05 |
December | 0.916147E+09 | 1691.21 | 18-DEC-09:02 | -1.7 |
Annual Sum or Average | 0.389455E+10 | |||
Minimum of Months | 255988.37 | 523.69 | -10.2 | |
Maximum of Months | 0.139677E+10 | 1747.22 | 22.57 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172109E+10 | 1747.54 | 07-JAN-19:13 | -5.6 |
February | 0.103573E+10 | 1760.28 | 12-FEB-09:13 | -9.8 |
March | 0.242131E+09 | 1665.53 | 19-MAR-08:62 | 4.27 |
April | 61971203.21 | 1661.43 | 06-APR-08:62 | 5.37 |
May | 1620349.91 | 991.31 | 16-MAY-08:53 | 21.70 |
June | 483255.18 | 1098.17 | 10-JUN-08:53 | 20.60 |
July | 141328.19 | 429.88 | 29-JUL-21:55 | 20.60 |
August | 125077.37 | 485.98 | 30-AUG-21:54 | 22.80 |
September | 1981146.89 | 1017.25 | 14-SEP-08:03 | 15.55 |
October | 0.160889E+09 | 1673.42 | 26-OCT-08:62 | 5.05 |
November | 0.518802E+09 | 1701.63 | 22-NOV-09:02 | 1.05 |
December | 0.118809E+10 | 1718.85 | 18-DEC-09:02 | -1.7 |
Annual Sum or Average | 0.493306E+10 | |||
Minimum of Months | 125077.37 | 429.88 | -9.8 | |
Maximum of Months | 0.172109E+10 | 1760.28 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.383037E+09 | 895.07 | 07-JAN-16:23 | -4.5 |
February | 0.210724E+09 | 877.11 | 12-FEB-09:02 | -10.2 |
March | 34193658.26 | 841.20 | 23-MAR-08:62 | 6.97 |
April | 15234066.26 | 835.86 | 06-APR-08:62 | 5.37 |
May | 601789.76 | 564.02 | 10-MAY-18:04 | 20.92 |
June | 184496.10 | 292.46 | 08-JUN-08:03 | 17.57 |
July | 136510.95 | 232.45 | 28-JUL-18:05 | 18.90 |
August | 95969.94 | 155.55 | 21-AUG-08:06 | 22.88 |
September | 622485.24 | 437.36 | 30-SEP-15:15 | 17.97 |
October | 19487351.25 | 834.06 | 31-OCT-08:62 | 7.80 |
November | 55280743.67 | 857.28 | 30-NOV-16:12 | 7.20 |
December | 0.192347E+09 | 867.76 | 25-DEC-16:12 | 5.93 |
Annual Sum or Average | 0.911945E+09 | |||
Minimum of Months | 95969.94 | 155.55 | -10.2 | |
Maximum of Months | 0.383037E+09 | 895.07 | 22.88 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.930132E+09 | 2595.61 | 08-JAN-05:20 | -5.4 |
February | 0.471620E+09 | 3214.76 | 12-FEB-06:00 | -12.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 21751883.90 | 1081.30 | 22-NOV-07:10 | -3.2 |
December | 0.137661E+09 | 1749.08 | 18-DEC-07:40 | -5.4 |
Annual Sum or Average | 0.156117E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.930132E+09 | 3214.76 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104372E+11 | 10053.14 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.942384E+10 | 10053.14 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.104694E+11 | 10053.14 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.100833E+11 | 10053.14 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.104553E+11 | 10053.14 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.101296E+11 | 10053.14 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.104091E+11 | 10053.14 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.104734E+11 | 10053.14 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.100874E+11 | 10053.14 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.104332E+11 | 10053.14 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.101215E+11 | 10053.14 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.104091E+11 | 10053.14 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.122932E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.942384E+10 | 10053.14 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.104734E+11 | 10053.14 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531884E+09 | 512.31 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.480243E+09 | 512.31 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.533523E+09 | 512.31 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.513850E+09 | 512.31 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.532806E+09 | 512.31 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.516207E+09 | 512.31 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.530449E+09 | 512.31 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.533728E+09 | 512.31 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.514055E+09 | 512.31 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.531679E+09 | 512.31 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.515797E+09 | 512.31 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.530449E+09 | 512.31 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.626467E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.480243E+09 | 512.31 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.533728E+09 | 512.31 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.615923E+09 | 593.26 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.556123E+09 | 593.26 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.617822E+09 | 593.26 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.595041E+09 | 593.26 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.616991E+09 | 593.26 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.597770E+09 | 593.26 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.614262E+09 | 593.26 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.618059E+09 | 593.26 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.595278E+09 | 593.26 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.615686E+09 | 593.26 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.597295E+09 | 593.26 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.614262E+09 | 593.26 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.725451E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.556123E+09 | 593.26 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.618059E+09 | 593.26 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.195918E+09 | 188.71 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.176896E+09 | 188.71 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.196522E+09 | 188.71 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.189275E+09 | 188.71 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.196257E+09 | 188.71 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.190143E+09 | 188.71 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.195389E+09 | 188.71 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.196597E+09 | 188.71 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.189351E+09 | 188.71 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.195842E+09 | 188.71 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.189992E+09 | 188.71 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.195389E+09 | 188.71 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.230757E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.176896E+09 | 188.71 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.196597E+09 | 188.71 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417273E+09 | 400.68 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.402047E+09 | 400.68 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415830E+09 | 400.68 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489965E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.122979E+10 | 1573.46 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.110068E+10 | 1573.46 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.111972E+10 | 1573.46 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.997299E+09 | 1573.46 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.962420E+09 | 1573.46 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.899232E+09 | 1573.46 | 01-JUN-19:40 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.943564E+09 | 1573.46 | 03-JUL-19:49 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.997611E+09 | 1573.46 | 01-AUG-19:40 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.106266E+10 | 1573.46 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.118214E+10 | 1573.46 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.117360E+10 | 1573.46 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.122692E+10 | 1573.46 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.128956E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.899232E+09 | 1573.46 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.122979E+10 | 1573.46 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.793377E+10 | 7984.04 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.716042E+10 | 7984.04 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.786925E+10 | 7984.04 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.752002E+10 | 7984.04 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.773628E+10 | 7984.04 | 01-MAY-19:19 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.746635E+10 | 7984.04 | 01-JUN-19:40 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.768962E+10 | 7984.04 | 03-JUL-19:49 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.777186E+10 | 7984.04 | 01-AUG-19:40 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.757132E+10 | 7984.04 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.790113E+10 | 7984.04 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.767578E+10 | 7984.04 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.791266E+10 | 7984.04 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.922085E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.716042E+10 | 7984.04 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.793377E+10 | 7984.04 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65789991.58 | 59.53 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 59414784.75 | 59.53 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 65267117.48 | 59.53 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 63743496.62 | 59.53 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 65528554.53 | 59.53 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 63237765.93 | 59.53 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 66042856.93 | 59.53 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 65267117.48 | 59.53 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 63760640.03 | 59.53 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 65781419.88 | 59.53 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 63490631.27 | 59.53 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 66051428.64 | 59.53 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.773376E+09 | 0.256575E+10 | ||||
Minimum of Months | 59414784.75 | 59.53 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 66051428.64 | 59.53 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.120431E+10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.108739E+10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.120803E+10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.116348E+10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.120640E+10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.116882E+10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.120107E+10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.120849E+10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.116395E+10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.120385E+10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.116789E+10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.120107E+10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141847E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.108739E+10 | 1160.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120849E+10 | 1160.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.257076E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.231074E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.244775E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.226157E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.225174E+10 | 2763.12 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.214107E+10 | 2763.12 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.222655E+10 | 2763.12 | 03-JUL-19:49 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.229869E+10 | 2763.12 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.233007E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.252976E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.246628E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.256310E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.283981E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.214107E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.257076E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.257076E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.231074E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.244775E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.226157E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.225174E+10 | 2763.12 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.214107E+10 | 2763.12 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.222655E+10 | 2763.12 | 03-JUL-19:49 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.229869E+10 | 2763.12 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.233007E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.252976E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.246628E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.256310E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.283981E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.214107E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.257076E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113599E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109410E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113446E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109454E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113207E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133389E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.127458E+10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.115083E+10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.127851E+10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.123137E+10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.127679E+10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.123701E+10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.127114E+10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.127900E+10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.123186E+10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.127409E+10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.123603E+10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.127114E+10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150123E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.115083E+10 | 1227.68 | 0.00 | 0.00 | |
Maximum of Months | 0.127900E+10 | 1227.68 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.104372E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.942384E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.104694E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.100833E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.104553E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.101296E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.104091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.104734E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.100874E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.104332E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.101215E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.104091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.122932E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.942384E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.104734E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.531884E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574172E+09 |
February | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 133786.31 | 0.405459E+09 |
March | 0.199990E+10 | 0.533523E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1891832.81 | 0.275050E+09 |
April | 0.192973E+10 | 0.513850E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9361427.97 | 0.178185E+09 |
May | 0.199475E+10 | 0.532806E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24487082.84 | 0.100793E+09 |
June | 0.193394E+10 | 0.516207E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69878003.19 | 41653648.47 |
July | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90628073.93 | 25348104.60 |
August | 0.199896E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87776254.03 | 10934854.18 |
September | 0.192879E+10 | 0.514055E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29923253.25 | 61832645.53 |
October | 0.199148E+10 | 0.531679E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4679661.81 | 0.218927E+09 |
November | 0.192552E+10 | 0.515797E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 111500.28 | 0.316209E+09 |
December | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452223E+09 |
Annual Sum or Average | 0.234744E+11 | 0.626467E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318871E+09 | 0.266079E+10 |
Minimum of Months | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10934854.18 |
Maximum of Months | 0.199990E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90628073.93 | 0.574172E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.615923E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221766E+09 |
February | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 379517.49 | 0.157110E+09 |
March | 0.231589E+10 | 0.617822E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1588084.99 | 0.106165E+09 |
April | 0.223463E+10 | 0.595041E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6511701.92 | 70206374.69 |
May | 0.230993E+10 | 0.616991E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13939298.93 | 39293875.30 |
June | 0.223950E+10 | 0.597770E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31906933.88 | 16104941.68 |
July | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39442588.53 | 9418687.44 |
August | 0.231480E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38261468.88 | 3830678.10 |
September | 0.223354E+10 | 0.595278E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15333524.67 | 24072783.79 |
October | 0.230614E+10 | 0.615686E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3394159.20 | 84634918.45 |
November | 0.222975E+10 | 0.597295E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 283718.79 | 0.123030E+09 |
December | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18594.60 | 0.175416E+09 |
Annual Sum or Average | 0.271834E+11 | 0.725451E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151060E+09 | 0.103105E+10 |
Minimum of Months | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3830678.10 |
Maximum of Months | 0.231589E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39442588.53 | 0.221766E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534352E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 235228.27 | 0.389623E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1551204.93 | 0.284690E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7926758.95 | 0.194023E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20991732.85 | 0.111780E+09 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62954526.52 | 43686113.42 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82228258.35 | 27152958.19 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79930884.23 | 11065200.02 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26797022.77 | 68220603.53 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3953567.66 | 0.231338E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39667.05 | 0.326553E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441269E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286609E+09 | 0.266375E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11065200.02 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82228258.35 | 0.534352E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.195918E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 400.27 | 0.296301E+09 |
February | 0.339028E+09 | 0.176896E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 926484.55 | 0.205433E+09 |
March | 0.376747E+09 | 0.196522E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3379137.59 | 0.128779E+09 |
April | 0.363528E+09 | 0.189275E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11622863.18 | 82099572.80 |
May | 0.375778E+09 | 0.196257E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22609282.94 | 42612564.28 |
June | 0.364321E+09 | 0.190143E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48474040.25 | 15779292.29 |
July | 0.374985E+09 | 0.195389E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59169843.26 | 8262995.74 |
August | 0.376571E+09 | 0.196597E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59637678.80 | 2283454.91 |
September | 0.363352E+09 | 0.189351E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25471260.13 | 24613917.37 |
October | 0.375161E+09 | 0.195842E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6304763.24 | 0.100535E+09 |
November | 0.362735E+09 | 0.189992E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 715529.74 | 0.152262E+09 |
December | 0.374985E+09 | 0.195389E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99356.14 | 0.228499E+09 |
Annual Sum or Average | 0.442217E+10 | 0.230757E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238411E+09 | 0.128746E+10 |
Minimum of Months | 0.339028E+09 | 0.176896E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 400.27 | 2283454.91 |
Maximum of Months | 0.376747E+09 | 0.196597E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59637678.80 | 0.296301E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823571E+09 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 162539.28 | 0.591597E+09 |
March | 0.155131E+10 | 0.417273E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 1991469.75 | 0.408144E+09 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 10364826.24 | 0.269833E+09 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 28636401.45 | 0.152693E+09 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 85960696.06 | 59647738.58 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.112278E+09 | 37071990.15 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.109137E+09 | 15104618.95 |
September | 0.149615E+10 | 0.402047E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 36597566.70 | 93149153.18 |
October | 0.154478E+10 | 0.415830E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 5399233.56 | 0.320177E+09 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 19729.83 | 0.465360E+09 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659766E+09 |
Annual Sum or Average | 0.182090E+11 | 0.489965E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.390547E+09 | 0.389611E+10 |
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15104618.95 |
Maximum of Months | 0.155131E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.112278E+09 | 0.823571E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.122979E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126763E+10 |
February | 0.236489E+11 | 0.110068E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1591146.57 | 0.892466E+09 |
March | 0.262800E+11 | 0.111972E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9548773.10 | 0.583958E+09 |
April | 0.253579E+11 | 0.997299E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42466258.31 | 0.367270E+09 |
May | 0.262123E+11 | 0.962420E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98932537.00 | 0.190851E+09 |
June | 0.254132E+11 | 0.899232E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219297E+09 | 71296635.58 |
July | 0.261570E+11 | 0.943564E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263983E+09 | 35648059.31 |
August | 0.262677E+11 | 0.997611E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257803E+09 | 12157759.06 |
September | 0.253456E+11 | 0.106266E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106652E+09 | 0.109738E+09 |
October | 0.261693E+11 | 0.118214E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20960743.36 | 0.455761E+09 |
November | 0.253025E+11 | 0.117360E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2319409.66 | 0.684010E+09 |
December | 0.261570E+11 | 0.122692E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58054.09 | 0.995773E+09 |
Annual Sum or Average | 0.308468E+12 | 0.128956E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102361E+10 | 0.566656E+10 |
Minimum of Months | 0.236489E+11 | 0.899232E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12157759.06 |
Maximum of Months | 0.262800E+11 | 0.122979E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263983E+09 | 0.126763E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.793377E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371822E+10 |
February | 0.702046E+11 | 0.716042E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5164968.05 | 0.264410E+10 |
March | 0.780153E+11 | 0.786925E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23971428.22 | 0.179426E+10 |
April | 0.752779E+11 | 0.752002E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105628E+09 | 0.117911E+10 |
May | 0.778146E+11 | 0.773628E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234617E+09 | 0.660994E+09 |
June | 0.754422E+11 | 0.746635E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540036E+09 | 0.271945E+09 |
July | 0.776503E+11 | 0.768962E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664636E+09 | 0.160897E+09 |
August | 0.779788E+11 | 0.777186E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643789E+09 | 65445851.48 |
September | 0.752414E+11 | 0.757132E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256208E+09 | 0.408583E+09 |
October | 0.776868E+11 | 0.790113E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53286301.98 | 0.143302E+10 |
November | 0.751137E+11 | 0.767578E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3876464.00 | 0.208909E+10 |
December | 0.776503E+11 | 0.791266E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 183549.36 | 0.296836E+10 |
Annual Sum or Average | 0.915726E+12 | 0.922085E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253140E+10 | 0.173940E+11 |
Minimum of Months | 0.702046E+11 | 0.716042E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65445851.48 |
Maximum of Months | 0.780153E+11 | 0.793377E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664636E+09 | 0.371822E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324050E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 415506.08 | 0.226412E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2774056.83 | 0.146411E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9443651.29 | 89590115.12 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22730133.53 | 40782547.71 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60059914.65 | 10742993.68 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77665204.83 | 4474581.04 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82326372.58 | 664766.90 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32088956.82 | 20391483.05 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5873544.46 | 0.108504E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 357346.41 | 0.170925E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14589.45 | 0.252511E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293749E+09 | 0.139546E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 664766.90 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82326372.58 | 0.324050E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319500E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 344752.64 | 0.223875E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2293505.89 | 0.146670E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8634073.98 | 94508345.60 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21293604.12 | 47752476.66 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57563097.15 | 14349980.30 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74946565.20 | 7802470.06 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79315838.40 | 2128628.46 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29722123.29 | 24537057.38 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5031154.44 | 0.110386E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 254403.78 | 0.167869E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16662.37 | 0.247240E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279416E+09 | 0.140662E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2128628.46 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79315838.40 | 0.319500E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 65789991.58 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91467869.81 |
February | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73776552.25 |
March | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21169.41 | 64306383.88 |
April | 0.00 | 63743496.62 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 191049.15 | 46378691.65 |
May | 0.00 | 65528554.53 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1068690.59 | 30546176.42 |
June | 0.00 | 63237765.93 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5543758.14 | 14971811.61 |
July | 0.00 | 66042856.93 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7859263.74 | 11366246.37 |
August | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7082287.98 | 8100455.74 |
September | 0.00 | 63760640.03 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1555580.05 | 21778795.66 |
October | 0.00 | 65781419.88 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 116276.98 | 53202281.60 |
November | 0.00 | 63490631.27 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71737297.65 |
December | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89552409.40 |
Annual Sum or Average | 0.00 | 0.773376E+09 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23438076.03 | 0.577185E+09 |
Minimum of Months | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8100455.74 |
Maximum of Months | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7859263.74 | 91467869.81 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90657912.03 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 151473.46 | 63421018.11 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 738075.89 | 40632920.62 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2650417.51 | 25899129.10 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6134883.61 | 12783685.19 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16239982.13 | 3686694.84 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21093428.12 | 1960256.83 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22386714.32 | 437895.43 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8546000.18 | 6653349.72 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1603865.87 | 30641859.47 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 102775.11 | 47344165.60 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16477.74 | 70475944.93 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79664093.94 | 0.394595E+09 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437895.43 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22386714.32 | 90657912.03 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324643E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 417820.94 | 0.227254E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2798825.82 | 0.147794E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9451782.15 | 90842737.71 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22649195.66 | 41384758.90 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59960598.08 | 10990653.50 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77547256.68 | 4555575.61 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82215203.13 | 698950.39 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32052633.90 | 20633216.25 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5879037.26 | 0.109318E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 370888.98 | 0.171772E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14528.45 | 0.253154E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293358E+09 | 0.140304E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 698950.39 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82215203.13 | 0.324643E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319750E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 311399.67 | 0.224309E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2388519.27 | 0.146765E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8557707.60 | 94913755.19 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21135330.84 | 48496955.39 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57155405.17 | 15532223.40 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74492801.50 | 8969534.81 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79026843.04 | 2768447.30 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29517022.59 | 25227901.31 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5024478.03 | 0.110563E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 365848.60 | 0.167426E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39680.61 | 0.247449E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278015E+09 | 0.141217E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2768447.30 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79026843.04 | 0.319750E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.120431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.89 | 0.396211E+09 |
February | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894744.28 | 0.276396E+09 |
March | 0.387034E+10 | 0.120803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3609552.06 | 0.179209E+09 |
April | 0.373454E+10 | 0.116348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12092892.99 | 0.119285E+09 |
May | 0.386038E+10 | 0.120640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25113694.32 | 65104170.88 |
June | 0.374269E+10 | 0.116882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57281595.22 | 25939089.53 |
July | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70031593.51 | 15596694.04 |
August | 0.386853E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69237298.30 | 5495226.15 |
September | 0.373273E+10 | 0.116395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28245701.89 | 38742591.50 |
October | 0.385404E+10 | 0.120385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6762715.05 | 0.141087E+09 |
November | 0.372639E+10 | 0.116789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 872602.94 | 0.205780E+09 |
December | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101828.88 | 0.305952E+09 |
Annual Sum or Average | 0.454292E+11 | 0.141847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274244E+09 | 0.177480E+10 |
Minimum of Months | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.89 | 5495226.15 |
Maximum of Months | 0.387034E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70031593.51 | 0.396211E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322875E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 395538.27 | 0.225768E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2697001.61 | 0.146247E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9199956.25 | 89810907.67 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22288988.37 | 41190023.95 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59316939.17 | 10936852.07 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76791763.83 | 4558285.93 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81341774.25 | 672475.80 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31482914.70 | 20469165.30 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5712545.30 | 0.108292E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 331224.63 | 0.170596E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13244.55 | 0.251339E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289572E+09 | 0.139275E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672475.80 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81341774.25 | 0.322875E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319235E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 338512.54 | 0.223672E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2216808.51 | 0.146401E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8372919.17 | 95128319.32 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20898705.08 | 48323312.20 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56923825.84 | 14273686.08 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74209194.94 | 7548018.50 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78517253.70 | 1917049.36 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29224039.41 | 24231739.87 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4886730.41 | 0.109926E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 253683.16 | 0.167152E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21231.01 | 0.246205E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275863E+09 | 0.140401E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1917049.36 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78517253.70 | 0.319235E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170188E+09 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 198496.16 | 0.118905E+09 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1377381.06 | 76419116.25 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4705234.87 | 46440971.04 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11432543.25 | 21109230.71 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30395549.01 | 5600636.43 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39328632.63 | 2337644.97 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41619234.41 | 350176.44 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16080997.06 | 10604940.49 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2888798.92 | 56713676.76 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 162937.32 | 89948457.97 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6561.00 | 0.133062E+09 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148196E+09 | 0.731680E+09 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350176.44 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41619234.41 | 0.170188E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.257076E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840068E+09 |
February | 0.415303E+11 | 0.231074E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1629437.87 | 0.597100E+09 |
March | 0.461508E+11 | 0.244775E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5891927.80 | 0.401551E+09 |
April | 0.445315E+11 | 0.226157E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24039475.67 | 0.267032E+09 |
May | 0.460320E+11 | 0.225174E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52353939.09 | 0.149924E+09 |
June | 0.446286E+11 | 0.214107E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123746E+09 | 59960444.49 |
July | 0.459349E+11 | 0.222655E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153440E+09 | 34439492.62 |
August | 0.461292E+11 | 0.229869E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152939E+09 | 13097395.76 |
September | 0.445099E+11 | 0.233007E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64424002.94 | 87456631.89 |
October | 0.459565E+11 | 0.252976E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14906132.47 | 0.312238E+09 |
November | 0.444343E+11 | 0.246628E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1195048.31 | 0.458288E+09 |
December | 0.459349E+11 | 0.256310E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149267.92 | 0.662514E+09 |
Annual Sum or Average | 0.541708E+12 | 0.283981E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594715E+09 | 0.388367E+10 |
Minimum of Months | 0.415303E+11 | 0.214107E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13097395.76 |
Maximum of Months | 0.461508E+11 | 0.257076E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153440E+09 | 0.840068E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.257076E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.854383E+09 |
February | 0.415303E+11 | 0.231074E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1285409.10 | 0.610173E+09 |
March | 0.461508E+11 | 0.244775E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4969624.15 | 0.415162E+09 |
April | 0.445315E+11 | 0.226157E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21352406.58 | 0.276409E+09 |
May | 0.460320E+11 | 0.225174E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48071408.93 | 0.156438E+09 |
June | 0.446286E+11 | 0.214107E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117765E+09 | 63463907.54 |
July | 0.459349E+11 | 0.222655E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147256E+09 | 37658830.82 |
August | 0.461292E+11 | 0.229869E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145853E+09 | 15130150.44 |
September | 0.445099E+11 | 0.233007E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59696146.02 | 92816702.22 |
October | 0.459565E+11 | 0.252976E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13193958.47 | 0.323361E+09 |
November | 0.444343E+11 | 0.246628E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 817251.31 | 0.472887E+09 |
December | 0.459349E+11 | 0.256310E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88534.27 | 0.678375E+09 |
Annual Sum or Average | 0.541708E+12 | 0.283981E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560349E+09 | 0.399626E+10 |
Minimum of Months | 0.415303E+11 | 0.214107E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15130150.44 |
Maximum of Months | 0.461508E+11 | 0.257076E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147256E+09 | 0.854383E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842912E+09 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 136718.90 | 0.606124E+09 |
March | 0.410691E+10 | 0.113599E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1812306.47 | 0.419411E+09 |
April | 0.396281E+10 | 0.109410E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 9326680.52 | 0.278027E+09 |
May | 0.409635E+10 | 0.113446E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 27995059.68 | 0.158297E+09 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 85712381.89 | 62519068.13 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.112284E+09 | 39293386.10 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.108742E+09 | 16555162.53 |
September | 0.396089E+10 | 0.109454E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 35926626.07 | 97243615.22 |
October | 0.408962E+10 | 0.113207E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 5232382.47 | 0.329640E+09 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 12467.41 | 0.477719E+09 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675965E+09 |
Annual Sum or Average | 0.482060E+11 | 0.133389E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.387181E+09 | 0.400371E+10 |
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16555162.53 |
Maximum of Months | 0.410691E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.112284E+09 | 0.842912E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.127458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707453E+09 |
February | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412149.92 | 0.506052E+09 |
March | 0.409620E+10 | 0.127851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2289296.05 | 0.356762E+09 |
April | 0.395248E+10 | 0.123137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10616507.54 | 0.249227E+09 |
May | 0.408566E+10 | 0.127679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27578605.57 | 0.149935E+09 |
June | 0.396110E+10 | 0.123701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83824635.27 | 60527237.60 |
July | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109702E+09 | 38273795.00 |
August | 0.409429E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106211E+09 | 16265134.66 |
September | 0.395056E+10 | 0.123186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35213415.49 | 91675960.01 |
October | 0.407896E+10 | 0.127409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5167518.74 | 0.288733E+09 |
November | 0.394385E+10 | 0.123603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237899.42 | 0.396526E+09 |
December | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553917E+09 |
Annual Sum or Average | 0.480803E+11 | 0.150123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381253E+09 | 0.341535E+10 |
Minimum of Months | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16265134.66 |
Maximum of Months | 0.409620E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109702E+09 | 0.707453E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 10053.14 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 10053.14 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 10053.14 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 10053.14 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 10053.14 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 10053.14 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 10053.14 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 10053.14 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 10053.14 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 10053.14 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 10053.14 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 10053.14 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 512.31 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 354.83 | 27-JAN-07:55 |
February | 1169.53 | 01-FEB-00:10 | 512.31 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.26 | 28-FEB-14:00 | 444.20 | 12-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 512.31 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.41 | 30-MAR-14:30 | 246.24 | 19-MAR-06:57 |
April | 1169.53 | 01-APR-00:10 | 512.31 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.24 | 12-APR-14:00 | 259.86 | 06-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 512.31 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.35 | 19-MAY-14:00 | 162.36 | 11-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 512.31 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.65 | 06-JUN-15:00 | 132.63 | 10-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 512.31 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.14 | 08-JUL-15:00 | 70.38 | 28-JUL-23:00 |
August | 1169.53 | 01-AUG-00:10 | 512.31 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.79 | 02-AUG-16:00 | 59.76 | 25-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 512.31 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.81 | 07-SEP-16:00 | 122.37 | 14-SEP-05:00 |
October | 1169.53 | 01-OCT-23:10 | 512.31 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.53 | 10-OCT-16:00 | 230.87 | 26-OCT-06:53 |
November | 1169.53 | 01-NOV-00:10 | 512.31 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.06 | 19-NOV-15:40 | 303.45 | 22-NOV-06:50 |
December | 1169.53 | 01-DEC-00:10 | 512.31 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 338.31 | 18-DEC-07:56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.76 | |||||
Maximum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 138.14 | 444.20 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 593.26 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 137.61 | 27-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 593.26 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 | 26-FEB-15:00 | 171.86 | 12-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 593.26 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.62 | 30-MAR-14:05 | 98.74 | 19-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 593.26 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.04 | 12-APR-14:00 | 105.09 | 06-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 593.26 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.24 | 30-MAY-14:00 | 69.11 | 11-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 593.26 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.99 | 06-JUN-15:00 | 55.09 | 10-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 593.26 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.02 | 08-JUL-16:00 | 28.59 | 28-JUL-23:00 |
August | 1354.32 | 01-AUG-00:10 | 593.26 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.64 | 01-AUG-15:00 | 24.23 | 25-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 593.26 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.13 | 07-SEP-15:00 | 50.80 | 14-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 593.26 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.15 | 10-OCT-16:00 | 94.17 | 26-OCT-05:00 |
November | 1354.32 | 01-NOV-00:10 | 593.26 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 19-NOV-15:00 | 119.53 | 22-NOV-06:00 |
December | 1354.32 | 01-DEC-00:10 | 593.26 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 12-DEC-14:00 | 130.66 | 18-DEC-07:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.23 | |||||
Maximum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 57.02 | 171.86 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 325.13 | 27-JAN-07:52 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | 26-FEB-15:00 | 406.18 | 12-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.68 | 30-MAR-13:55 | 241.90 | 19-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.39 | 12-APR-14:00 | 260.52 | 06-APR-05:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.91 | 19-MAY-14:00 | 177.34 | 11-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.77 | 06-JUN-15:00 | 139.63 | 10-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.02 | 08-JUL-15:00 | 72.47 | 28-JUL-23:20 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.19 | 02-AUG-16:00 | 59.97 | 25-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.37 | 07-SEP-16:00 | 132.78 | 29-SEP-04:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.68 | 10-OCT-16:00 | 235.81 | 26-OCT-06:53 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.19 | 19-NOV-15:00 | 290.93 | 22-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 317.50 | 18-DEC-07:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.97 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 126.02 | 406.18 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 188.71 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 | 31-JAN-15:00 | 186.75 | 27-JAN-07:58 |
February | 220.32 | 01-FEB-00:10 | 188.71 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.94 | 26-FEB-15:00 | 234.35 | 12-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 188.71 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.92 | 30-MAR-16:00 | 129.60 | 19-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 188.71 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.16 | 12-APR-14:00 | 136.77 | 06-APR-05:00 |
May | 220.32 | 01-MAY-00:10 | 188.71 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.27 | 19-MAY-16:40 | 86.27 | 11-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 188.71 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.54 | 06-JUN-15:00 | 68.60 | 10-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 188.71 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.64 | 08-JUL-16:00 | 32.40 | 28-JUL-23:00 |
August | 220.32 | 01-AUG-00:10 | 188.71 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.43 | 01-AUG-16:50 | 27.23 | 25-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 188.71 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.26 | 07-SEP-16:00 | 63.67 | 29-SEP-04:00 |
October | 220.32 | 01-OCT-23:10 | 188.71 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.48 | 10-OCT-16:00 | 121.51 | 26-OCT-07:00 |
November | 220.32 | 01-NOV-00:10 | 188.71 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 | 19-NOV-15:00 | 159.70 | 22-NOV-06:50 |
December | 220.32 | 01-DEC-00:10 | 188.71 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.44 | 12-DEC-14:00 | 178.06 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 | 27.23 | |||||
Maximum of Months | 220.32 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 78.64 | 234.35 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 489.84 | 27-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 14.03 | 28-FEB-14:30 | 603.84 | 12-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 52.84 | 30-MAR-14:30 | 352.94 | 19-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 68.81 | 12-APR-14:00 | 369.95 | 06-APR-05:00 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 91.37 | 19-MAY-14:00 | 242.15 | 11-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 140.33 | 06-JUN-15:00 | 190.66 | 10-JUN-05:00 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 172.08 | 08-JUL-15:00 | 98.95 | 28-JUL-23:20 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 150.46 | 02-AUG-16:00 | 81.88 | 25-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 105.65 | 07-SEP-16:00 | 181.30 | 29-SEP-04:00 |
October | 907.20 | 01-OCT-23:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 82.87 | 10-OCT-16:00 | 333.45 | 26-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 5.60 | 05-NOV-16:00 | 424.58 | 22-NOV-06:00 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 468.93 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 81.88 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 172.08 | 603.84 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1573.46 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 784.40 | 27-JAN-07:52 |
February | 15368.40 | 01-FEB-00:10 | 1573.46 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.77 | 28-FEB-14:40 | 984.44 | 12-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1573.46 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.76 | 30-MAR-16:00 | 544.37 | 19-MAR-06:53 |
April | 15368.40 | 01-APR-00:10 | 1573.46 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.58 | 17-APR-14:00 | 587.64 | 06-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1573.46 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.14 | 19-MAY-17:00 | 366.77 | 11-MAY-06:00 |
June | 15368.40 | 01-JUN-00:10 | 1573.46 | 01-JUN-19:40 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.69 | 06-JUN-15:00 | 300.16 | 10-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1573.46 | 03-JUL-19:49 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.05 | 08-JUL-16:00 | 148.72 | 28-JUL-23:00 |
August | 15368.40 | 01-AUG-00:10 | 1573.46 | 01-AUG-19:40 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 301.63 | 01-AUG-17:00 | 113.96 | 25-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1573.46 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.39 | 07-SEP-12:00 | 277.15 | 29-SEP-04:00 |
October | 15368.40 | 01-OCT-23:10 | 1573.46 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.08 | 10-OCT-16:00 | 530.26 | 26-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1573.46 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.95 | 19-NOV-15:40 | 676.09 | 22-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1573.46 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 | 12-DEC-15:40 | 747.88 | 18-DEC-07:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.96 | |||||
Maximum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 346.05 | 984.44 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 7984.04 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2314.35 | 14-JAN-06:00 |
February | 45622.98 | 01-FEB-00:10 | 7984.04 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.24 | 28-FEB-14:40 | 2814.35 | 12-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 7984.04 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.94 | 30-MAR-14:05 | 1648.51 | 19-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 7984.04 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.76 | 12-APR-14:00 | 1773.22 | 06-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 7984.04 | 01-MAY-19:19 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 570.72 | 30-MAY-14:00 | 1148.36 | 11-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 7984.04 | 01-JUN-19:40 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 799.84 | 06-JUN-15:00 | 930.13 | 10-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 7984.04 | 03-JUL-19:49 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 955.92 | 08-JUL-16:00 | 492.74 | 28-JUL-23:00 |
August | 45622.98 | 01-AUG-00:10 | 7984.04 | 01-AUG-19:40 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 836.46 | 01-AUG-15:00 | 403.41 | 25-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 7984.04 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 593.98 | 07-SEP-15:00 | 871.17 | 29-SEP-04:00 |
October | 45622.98 | 01-OCT-23:10 | 7984.04 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 478.70 | 10-OCT-16:00 | 1598.44 | 26-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 7984.04 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.45 | 19-NOV-15:00 | 2023.96 | 22-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 7984.04 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.85 | 12-DEC-15:00 | 2174.82 | 18-DEC-05:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.41 | |||||
Maximum of Months | 45622.98 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 955.92 | 2814.35 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 207.05 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.24 | 26-FEB-16:19 | 259.60 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-16:00 | 143.22 | 19-MAR-06:50 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.16 | 17-APR-15:20 | 151.94 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.90 | 19-MAY-16:00 | 93.01 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.25 | 06-JUN-15:20 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.08 | 08-JUL-15:20 | 33.13 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.24 | 02-AUG-16:00 | 23.24 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.06 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.21 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 12-DEC-16:17 | 196.68 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.24 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 98.08 | 259.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 207.04 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.24 | 26-FEB-16:19 | 259.58 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-16:00 | 143.21 | 19-MAR-06:50 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.16 | 17-APR-15:20 | 151.92 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 19-MAY-16:00 | 93.00 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.24 | 06-JUN-15:20 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.06 | 08-JUL-15:20 | 34.91 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.24 | 02-AUG-16:00 | 27.77 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.05 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.20 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.91 | 12-DEC-14:00 | 196.66 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.77 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 98.06 | 259.58 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 59.53 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 59.85 | 27-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 59.53 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 65.85 | 03-FEB-08:00 |
March | 0.00 | 01-MAR-00:10 | 59.53 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 | 30-MAR-14:10 | 48.17 | 19-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 59.53 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 12-APR-14:00 | 49.44 | 06-APR-05:00 |
May | 0.00 | 01-MAY-00:10 | 59.53 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 19-MAY-14:00 | 35.93 | 11-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 59.53 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.49 | 06-JUN-15:00 | 29.39 | 10-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 59.53 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 08-JUL-15:00 | 17.99 | 28-JUL-23:10 |
August | 0.00 | 01-AUG-00:10 | 59.53 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 | 02-AUG-16:00 | 15.70 | 25-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 59.53 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.90 | 07-SEP-16:00 | 27.67 | 14-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 59.53 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.90 | 10-OCT-16:00 | 46.52 | 26-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 59.53 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 55.41 | 21-NOV-08:00 |
December | 0.00 | 01-DEC-00:10 | 59.53 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 61.32 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | |||||
Maximum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 65.85 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 57.79 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 28-FEB-14:00 | 72.45 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 30-MAR-15:50 | 40.20 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 17-APR-15:20 | 42.40 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 19-MAY-16:00 | 25.96 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.96 | 06-JUN-15:20 | 19.32 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.38 | 08-JUL-15:20 | 10.51 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.63 | 02-AUG-16:00 | 7.54 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.82 | 07-SEP-16:00 | 18.12 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 10-OCT-16:00 | 38.25 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 | 05-NOV-16:00 | 49.46 | 22-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 12-DEC-14:00 | 55.02 | 18-DEC-07:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.54 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.38 | 72.45 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 207.05 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.24 | 26-FEB-16:17 | 259.60 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-16:00 | 143.22 | 19-MAR-06:50 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.16 | 17-APR-15:18 | 151.94 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 19-MAY-16:00 | 93.01 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.25 | 06-JUN-15:20 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.12 | 08-JUL-15:20 | 32.98 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.25 | 02-AUG-16:00 | 23.98 | 25-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.06 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.21 | 22-NOV-06:30 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 12-DEC-16:17 | 196.68 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.98 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 98.12 | 259.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 207.04 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.24 | 26-FEB-16:19 | 259.58 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-16:00 | 143.21 | 19-MAR-06:50 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.16 | 17-APR-15:20 | 151.93 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 19-MAY-16:00 | 93.00 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.24 | 06-JUN-15:20 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 | 08-JUL-15:20 | 34.37 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.24 | 02-AUG-16:00 | 28.37 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.05 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.20 | 22-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 | 12-DEC-14:00 | 196.67 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.37 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 | 259.58 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 31-JAN-15:00 | 249.42 | 27-JAN-07:57 |
February | 2263.36 | 01-FEB-00:10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 | 26-FEB-15:00 | 312.90 | 12-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.60 | 30-MAR-13:55 | 173.19 | 19-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.27 | 12-APR-14:00 | 186.18 | 06-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.41 | 30-MAY-14:00 | 121.63 | 11-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.91 | 06-JUN-15:00 | 97.53 | 10-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.70 | 08-JUL-16:00 | 48.70 | 28-JUL-23:00 |
August | 2263.36 | 01-AUG-00:10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.66 | 01-AUG-17:00 | 40.61 | 25-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.50 | 07-SEP-15:00 | 89.99 | 29-SEP-04:00 |
October | 2263.36 | 01-OCT-23:10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.63 | 10-OCT-16:00 | 163.48 | 26-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.70 | 19-NOV-15:00 | 213.33 | 22-NOV-07:00 |
December | 2263.36 | 01-DEC-00:10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 12-DEC-15:00 | 237.82 | 18-DEC-07:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 40.61 | ||||
Maximum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.70 | 312.90 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 207.54 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.85 | 26-FEB-16:20 | 259.83 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 30-MAR-16:00 | 143.68 | 19-MAR-06:50 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.78 | 17-APR-15:20 | 152.39 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 | 19-MAY-16:00 | 93.44 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.89 | 06-JUN-15:20 | 69.66 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.68 | 08-JUL-16:00 | 30.83 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.84 | 02-AUG-16:00 | 22.09 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.04 | 07-SEP-16:00 | 65.36 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.56 | 10-OCT-16:00 | 135.52 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 05-NOV-16:00 | 177.68 | 22-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 12-DEC-16:20 | 197.16 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.09 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 97.68 | 259.83 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 207.52 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.85 | 26-FEB-16:17 | 258.82 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 30-MAR-16:00 | 143.67 | 19-MAR-06:50 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.78 | 17-APR-15:20 | 152.38 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 | 19-MAY-16:00 | 93.43 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.88 | 06-JUN-15:20 | 69.66 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.66 | 08-JUL-16:00 | 33.90 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.84 | 02-AUG-16:00 | 25.61 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 | 07-SEP-16:00 | 65.35 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.56 | 10-OCT-16:00 | 135.50 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 05-NOV-16:00 | 177.67 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 12-DEC-14:00 | 197.15 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.61 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 97.66 | 258.82 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 106.18 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.96 | 26-FEB-16:20 | 133.08 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 30-MAR-16:00 | 73.51 | 19-MAR-06:50 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.47 | 17-APR-15:20 | 77.97 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.97 | 19-MAY-16:00 | 47.81 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.90 | 06-JUN-15:20 | 35.64 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.99 | 08-JUL-15:20 | 16.65 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.96 | 02-AUG-16:00 | 11.66 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.30 | 07-SEP-16:00 | 33.44 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.91 | 10-OCT-16:00 | 69.33 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 05-NOV-16:00 | 90.91 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 | 12-DEC-16:20 | 100.87 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.66 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 49.99 | 133.08 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 522.83 | 14-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 | 28-FEB-14:00 | 641.78 | 12-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.94 | 30-MAR-14:05 | 375.70 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.98 | 12-APR-14:00 | 399.38 | 06-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.87 | 19-MAY-14:00 | 261.29 | 11-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.19 | 06-JUN-15:00 | 208.25 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:49 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.58 | 08-JUL-16:00 | 114.20 | 28-JUL-23:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.91 | 01-AUG-15:00 | 88.76 | 25-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.11 | 07-SEP-12:00 | 195.14 | 29-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.32 | 10-OCT-16:00 | 356.67 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.38 | 19-NOV-15:00 | 453.69 | 22-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 12-DEC-15:00 | 488.50 | 18-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.76 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 218.58 | 641.78 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 528.32 | 14-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.14 | 28-FEB-14:00 | 647.94 | 12-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.31 | 30-MAR-14:05 | 381.95 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.33 | 12-APR-14:00 | 404.00 | 06-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.54 | 19-MAY-14:00 | 265.52 | 11-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.87 | 06-JUN-15:00 | 211.68 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:49 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.85 | 08-JUL-16:00 | 114.20 | 28-JUL-23:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.55 | 01-AUG-15:00 | 92.38 | 25-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.58 | 07-SEP-12:00 | 198.62 | 29-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.92 | 10-OCT-16:00 | 361.80 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.97 | 19-NOV-15:00 | 459.15 | 22-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 | 12-DEC-15:00 | 493.97 | 18-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.38 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 213.85 | 647.94 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 500.66 | 27-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 12.96 | 28-FEB-14:50 | 616.75 | 12-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 52.27 | 30-MAR-15:14 | 361.08 | 19-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 68.76 | 12-APR-14:00 | 378.41 | 06-APR-05:00 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 91.80 | 19-MAY-15:50 | 248.12 | 11-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 141.70 | 06-JUN-15:00 | 195.70 | 10-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 174.05 | 08-JUL-15:00 | 102.27 | 28-JUL-23:40 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 152.07 | 02-AUG-16:00 | 84.80 | 25-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 106.41 | 07-SEP-16:00 | 186.18 | 29-SEP-04:00 |
October | 2401.70 | 01-OCT-23:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 83.20 | 10-OCT-16:00 | 341.21 | 26-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 4.44 | 05-NOV-16:00 | 434.09 | 22-NOV-06:00 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 479.33 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 84.80 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 174.05 | 616.75 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 442.35 | 27-JAN-07:55 |
February | 2395.44 | 01-FEB-00:10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 26-FEB-15:00 | 554.71 | 12-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.25 | 30-MAR-14:30 | 307.40 | 19-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.18 | 12-APR-14:00 | 334.85 | 06-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.69 | 19-MAY-14:00 | 226.24 | 11-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.54 | 06-JUN-15:00 | 184.54 | 10-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.20 | 08-JUL-15:00 | 100.14 | 28-JUL-23:20 |
August | 2395.44 | 01-AUG-00:10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.63 | 02-AUG-16:00 | 83.10 | 25-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.94 | 07-SEP-16:00 | 170.84 | 29-SEP-04:00 |
October | 2395.44 | 01-OCT-23:10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.22 | 10-OCT-16:00 | 293.15 | 26-OCT-05:00 |
November | 2395.44 | 01-NOV-00:10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.93 | 19-NOV-15:00 | 378.46 | 22-NOV-06:30 |
December | 2395.44 | 01-DEC-00:10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 421.82 | 18-DEC-07:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.10 | ||||
Maximum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.20 | 554.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12996.90 | 31-JAN-21:00 | 8945.92 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12527.08 | 01-FEB-21:00 | 8945.92 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12074.25 | 30-MAR-18:10 | 62621.41 | 62552.56 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12802.98 | 14-APR-18:01 | 62621.41 | 62552.56 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13649.37 | 13-MAY-15:11 | 26837.75 | 19548.08 | 24841.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14110.69 | 25-JUN-10:35 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14979.86 | 20-JUL-18:10 | 53675.50 | 53616.48 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15842.19 | 27-AUG-10:35 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19585.28 | 28-SEP-21:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20541.38 | 12-OCT-21:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20580.86 | 08-NOV-22:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18415.35 | 01-DEC-22:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12074.25 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20580.86 | 62621.41 | 62552.56 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1931.66 | 29-JAN-13:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.63 |
February | 2373.85 | 21-FEB-14:25 | 519.79 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 |
March | 2393.52 | 30-MAR-13:35 | 519.79 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 38.37 | 0.00 |
April | 2428.25 | 14-APR-13:05 | 519.79 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 32.02 | 0.00 |
May | 2035.39 | 20-MAY-13:30 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 66.79 | 0.00 |
June | 2318.62 | 13-JUN-18:03 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 87.44 | 0.00 |
July | 2633.46 | 07-JUL-18:17 | 2728.91 | 1366.17 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 106.32 | 0.00 |
August | 2952.71 | 19-AUG-13:40 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 106.27 | 0.00 |
September | 3036.25 | 24-SEP-12:40 | 259.90 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 52.55 | 0.00 |
October | 3197.05 | 10-OCT-13:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 54.06 | 0.00 |
November | 2500.51 | 08-NOV-13:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.78 |
December | 2264.48 | 10-DEC-13:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1931.66 | 259.90 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3197.05 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 106.32 | 120.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1304.92 | 31-JAN-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.60 |
February | 1445.61 | 28-FEB-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 |
March | 1559.72 | 30-MAR-18:10 | 7373.52 | 3691.40 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 12.34 | 0.00 |
April | 1698.73 | 14-APR-18:01 | 7373.52 | 3691.40 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 | 0.00 |
May | 1706.27 | 19-MAY-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
June | 1852.66 | 27-JUN-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.85 | 0.00 |
July | 2026.02 | 07-JUL-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 28.21 | 0.00 |
August | 2073.52 | 18-AUG-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 30.30 | 0.00 |
September | 1929.83 | 08-SEP-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 | 0.00 |
October | 1667.31 | 11-OCT-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.40 |
November | 1426.20 | 06-NOV-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.57 |
December | 1401.91 | 12-DEC-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1304.92 | 1053.36 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2073.52 | 7373.52 | 3691.40 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 30.30 | 50.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21.98 | 20-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.46 |
February | 652.01 | 28-FEB-22:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.51 |
March | 1052.42 | 30-MAR-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
April | 1063.68 | 19-APR-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.71 |
May | 1340.45 | 19-MAY-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
June | 1656.21 | 13-JUN-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 43.84 | 0.00 |
July | 1852.40 | 07-JUL-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 66.67 | 0.00 |
August | 1824.48 | 18-AUG-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 71.60 | 0.00 |
September | 1635.43 | 07-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 32.65 | 0.00 |
October | 1214.31 | 18-OCT-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.28 |
November | 772.95 | 03-NOV-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.44 |
December | 576.44 | 13-DEC-22:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 21.98 | 222.77 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1852.40 | 254.59 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 71.60 | 118.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 669.55 | 31-JAN-21:00 | 171.36 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.46 |
February | 738.31 | 28-FEB-19:00 | 122.40 | 125.81 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 | 0.00 |
March | 848.38 | 30-MAR-18:10 | 1199.52 | 1174.19 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 24.43 | 0.00 |
April | 957.47 | 19-APR-15:11 | 856.80 | 366.93 | 624.51 | 0.00 | 0.00 | 0.00 | 0.00 | 27.10 | 0.00 |
May | 972.83 | 13-MAY-15:11 | 514.08 | 366.93 | 624.51 | 0.00 | 0.00 | 0.00 | 0.00 | 29.96 | 0.00 |
June | 1006.16 | 25-JUN-10:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 41.87 | 0.00 |
July | 1038.14 | 08-JUL-10:35 | 146.88 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 59.72 | 0.00 |
August | 1041.36 | 19-AUG-10:35 | 146.88 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 52.93 | 0.00 |
September | 989.85 | 09-SEP-10:35 | 146.88 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 43.49 | 0.00 |
October | 876.08 | 11-OCT-10:35 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 15.86 | 0.00 |
November | 777.41 | 05-NOV-10:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 |
December | 738.49 | 13-DEC-11:35 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 669.55 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1041.36 | 1199.52 | 1174.19 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 59.72 | 24.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37441.47 | 31-JAN-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 99.23 |
February | 37966.75 | 28-FEB-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 |
March | 38398.04 | 30-MAR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 5.59 | 0.00 |
April | 38560.12 | 17-APR-19:55 | 1411.20 | 801.37 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 17.08 |
May | 38897.31 | 19-MAY-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 22.45 | 0.00 |
June | 39272.32 | 13-JUN-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 74.91 | 0.00 |
July | 39496.96 | 07-JUL-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 97.79 | 0.00 |
August | 39407.00 | 18-AUG-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 105.80 | 0.00 |
September | 39146.38 | 07-SEP-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 44.58 | 0.00 |
October | 38519.29 | 10-OCT-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 |
November | 37859.25 | 03-NOV-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 73.69 |
December | 37708.38 | 12-DEC-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 82.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37441.47 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39496.96 | 1411.20 | 801.37 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 105.80 | 99.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10064.30 | 29-JAN-11:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.51 |
February | 10572.79 | 26-FEB-11:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.75 |
March | 10878.49 | 30-MAR-15:13 | 59766.00 | 673.09 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 114.15 | 0.00 |
April | 12648.31 | 12-APR-15:17 | 59766.00 | 673.09 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 132.21 | 0.00 |
May | 11907.12 | 13-MAY-15:11 | 35859.60 | 673.09 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 115.40 | 0.00 |
June | 11145.95 | 24-JUN-17:20 | 20491.20 | 461.55 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 247.31 | 0.00 |
July | 11716.75 | 08-JUL-17:30 | 10245.60 | 230.77 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 283.45 | 0.00 |
August | 11711.99 | 02-AUG-18:10 | 71719.20 | 1846.19 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 244.43 | 0.00 |
September | 11723.17 | 22-SEP-16:52 | 51228.00 | 576.93 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 87.60 | 0.00 |
October | 11429.57 | 10-OCT-15:23 | 25614.00 | 288.47 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 138.44 | 0.00 |
November | 10971.85 | 11-NOV-11:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.60 |
December | 10432.64 | 10-DEC-11:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10064.30 | 10245.60 | 230.77 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12648.31 | 71719.20 | 1846.19 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 283.45 | 269.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28127.42 | 31-JAN-21:00 | 35484.54 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.07 |
February | 30149.08 | 28-FEB-21:00 | 35484.54 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.23 |
March | 32111.23 | 30-MAR-21:53 | 273737.88 | 31936.14 | 44339.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.17 |
April | 34824.96 | 12-APR-15:17 | 177422.70 | 13351.08 | 25864.80 | 0.00 | 0.00 | 0.00 | 0.00 | 390.20 | 0.00 |
May | 34410.68 | 13-MAY-15:11 | 106453.62 | 13351.08 | 25864.80 | 0.00 | 0.00 | 0.00 | 0.00 | 307.02 | 0.00 |
June | 36271.92 | 13-JUN-21:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 290.91 | 0.00 |
July | 38564.24 | 07-JUL-21:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 448.08 | 0.00 |
August | 39592.55 | 18-AUG-21:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 476.59 | 0.00 |
September | 37591.75 | 07-SEP-21:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 99.48 | 0.00 |
October | 34383.58 | 10-OCT-21:10 | 91245.96 | 10645.38 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.74 |
November | 29817.60 | 06-NOV-21:00 | 35484.54 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 835.19 |
December | 29684.88 | 12-DEC-21:00 | 35484.54 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 28127.42 | 35484.54 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39592.55 | 273737.88 | 31936.14 | 44339.66 | 0.00 | 0.00 | 0.00 | 0.00 | 476.59 | 835.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3160.63 | 28-JAN-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.06 |
February | 3265.68 | 27-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 0.00 |
March | 3265.16 | 13-MAR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 9.69 | 0.00 |
April | 3266.49 | 09-APR-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 |
May | 3247.85 | 09-MAY-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.48 |
June | 2881.63 | 18-JUN-15:12 | 324.00 | 187.54 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 55.85 | 0.00 |
July | 2897.10 | 26-JUL-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 48.61 | 0.00 |
August | 2900.15 | 20-AUG-18:02 | 702.00 | 568.30 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 19.52 | 0.00 |
September | 2920.42 | 03-SEP-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 | 0.00 |
October | 3032.59 | 31-OCT-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.12 |
November | 3254.78 | 08-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 |
December | 3202.55 | 10-DEC-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2881.63 | 324.00 | 185.64 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3266.49 | 970.20 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 55.85 | 71.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 597.47 | 16-JAN-16:13 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.32 |
February | 2876.63 | 20-FEB-19:21 | 819.00 | 662.94 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.81 |
March | 3195.47 | 13-MAR-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 10.48 | 0.00 |
April | 3326.19 | 26-APR-18:41 | 1247.40 | 758.59 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.78 |
May | 3327.51 | 09-MAY-20:41 | 1441.80 | 758.59 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.84 |
June | 2854.11 | 15-JUN-15:12 | 583.20 | 159.11 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 23.14 | 0.00 |
July | 2943.99 | 02-JUL-21:51 | 970.20 | 563.50 | 626.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 2863.28 | 28-AUG-15:12 | 583.20 | 159.11 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 44.69 | 0.00 |
September | 3177.17 | 18-SEP-16:01 | 972.00 | 265.18 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 0.00 |
October | 2986.95 | 15-OCT-16:21 | 858.60 | 281.28 | 948.12 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 | 0.00 |
November | 2480.67 | 05-NOV-15:12 | 324.00 | 187.52 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 0.00 |
December | 2582.19 | 07-DEC-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 597.47 | 324.00 | 159.11 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3327.51 | 1441.80 | 758.59 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 44.69 | 73.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 176.62 | 31-JAN-15:05 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.35 |
February | 357.11 | 26-FEB-14:50 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
March | 348.27 | 30-MAR-13:35 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 | 0.00 |
April | 328.49 | 15-APR-13:52 | 0.00 | 98.22 | 167.69 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 | 0.00 |
May | 272.10 | 19-MAY-17:20 | 0.00 | 79.76 | 247.67 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 | 0.00 |
June | 311.03 | 13-JUN-17:20 | 0.00 | 79.76 | 247.67 | 0.00 | 0.00 | 0.00 | 0.00 | 10.49 | 0.00 |
July | 351.01 | 08-JUL-17:30 | 0.00 | 50.60 | 123.84 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 | 0.00 |
August | 390.34 | 19-AUG-13:40 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 0.00 |
September | 451.64 | 24-SEP-12:50 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 0.00 |
October | 488.13 | 10-OCT-13:40 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | 0.00 |
November | 412.81 | 08-NOV-14:10 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.03 |
December | 382.14 | 10-DEC-14:30 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 176.62 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 488.13 | 0.00 | 98.22 | 247.67 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 | 17.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 867.26 | 01-JAN-09:02 | 216.00 | 133.37 | 639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.73 |
February | 1068.45 | 28-FEB-22:52 | 900.00 | 199.47 | 438.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 |
March | 1075.28 | 13-MAR-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 | 0.00 |
April | 1073.53 | 09-APR-20:11 | 1247.40 | 535.88 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 |
May | 1150.67 | 09-MAY-20:41 | 1441.80 | 476.93 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.25 |
June | 1045.14 | 30-JUN-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 0.00 |
July | 1050.26 | 14-JUL-15:12 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 20.88 | 0.00 |
August | 1046.78 | 10-AUG-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.49 | 0.00 |
September | 1042.02 | 12-SEP-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.42 | 0.00 |
October | 1079.34 | 11-OCT-21:52 | 1080.00 | 239.36 | 526.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.26 |
November | 1022.40 | 28-NOV-19:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 |
December | 865.73 | 23-DEC-09:02 | 270.00 | 166.72 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 865.73 | 216.00 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1150.67 | 1441.80 | 535.88 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 20.88 | 26.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2783.42 | 29-JAN-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.45 |
February | 2957.21 | 27-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 | 0.00 |
March | 2961.56 | 13-MAR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 9.79 | 0.00 |
April | 2956.48 | 09-APR-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.74 |
May | 2931.01 | 09-MAY-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 |
June | 2707.62 | 13-JUN-08:61 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 | 0.00 |
July | 2685.16 | 21-JUL-08:61 | 360.00 | 416.75 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 | 0.00 |
August | 2678.27 | 21-AUG-15:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 47.20 | 0.00 |
September | 2662.48 | 06-SEP-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 41.78 | 0.00 |
October | 2658.04 | 16-OCT-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 15.26 | 0.00 |
November | 2939.79 | 08-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.65 |
December | 2877.42 | 10-DEC-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2658.04 | 252.00 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2961.56 | 970.20 | 590.08 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 47.20 | 38.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 536.95 | 29-JAN-09:02 | 324.00 | 318.21 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.77 |
February | 2632.90 | 24-FEB-09:02 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.66 |
March | 2907.93 | 13-MAR-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 0.00 |
April | 2842.30 | 14-APR-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.62 |
May | 2996.74 | 18-MAY-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.92 |
June | 3005.47 | 04-JUN-08:51 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.85 |
July | 2810.93 | 25-JUL-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.14 |
August | 2872.10 | 26-AUG-08:51 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 |
September | 2942.26 | 15-SEP-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 |
October | 2594.48 | 09-OCT-18:01 | 819.00 | 662.94 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 10.12 | 0.00 |
November | 2482.46 | 11-NOV-09:01 | 378.00 | 371.25 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.75 |
December | 803.21 | 10-DEC-09:02 | 324.00 | 318.21 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 536.95 | 216.00 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3005.47 | 819.00 | 662.94 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 110.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1390.06 | 31-JAN-21:00 | 1760.39 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.45 |
February | 1621.08 | 27-FEB-19:10 | 12322.72 | 7217.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 |
March | 1834.53 | 30-MAR-18:10 | 12322.72 | 7217.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 | 0.00 |
April | 2137.30 | 17-APR-17:10 | 5029.68 | 3093.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.93 | 0.00 |
May | 2142.56 | 13-MAY-15:11 | 5281.16 | 2255.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.31 | 0.00 |
June | 2183.93 | 25-JUN-10:35 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.32 | 0.00 |
July | 2263.96 | 08-JUL-17:50 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.09 | 0.00 |
August | 2274.40 | 19-AUG-10:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.44 | 0.00 |
September | 2156.28 | 09-SEP-10:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.26 | 0.00 |
October | 1902.38 | 11-OCT-18:10 | 12322.72 | 7217.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 |
November | 1605.12 | 11-NOV-11:35 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.91 |
December | 1492.40 | 12-DEC-11:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1390.06 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2274.40 | 12322.72 | 7217.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.09 | 33.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3300.61 | 29-JAN-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.23 |
February | 3434.05 | 27-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
March | 3429.29 | 13-MAR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 9.40 | 0.00 |
April | 3439.55 | 09-APR-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.48 |
May | 3426.02 | 10-MAY-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.31 |
June | 3044.85 | 18-JUN-18:02 | 702.00 | 568.30 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 28.22 | 0.00 |
July | 3090.58 | 07-JUL-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 69.49 | 0.00 |
August | 3088.69 | 02-AUG-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 63.72 | 0.00 |
September | 3060.45 | 04-SEP-15:12 | 324.00 | 187.54 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 35.06 | 0.00 |
October | 3209.54 | 31-OCT-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.18 |
November | 3418.35 | 08-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 |
December | 3359.56 | 10-DEC-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3044.85 | 324.00 | 185.64 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3439.55 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 69.49 | 67.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 734.17 | 28-JAN-16:13 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.73 |
February | 3036.78 | 20-FEB-19:21 | 819.00 | 662.94 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.70 |
March | 3347.90 | 13-MAR-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 | 0.00 |
April | 3507.87 | 26-APR-18:41 | 1247.40 | 758.59 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.60 |
May | 3572.86 | 09-MAY-20:41 | 1441.80 | 758.59 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.53 |
June | 2994.07 | 05-JUN-18:02 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 50.71 | 0.00 |
July | 3090.60 | 06-JUL-18:02 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 59.16 | 0.00 |
August | 3055.37 | 18-AUG-18:02 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 68.85 | 0.00 |
September | 3320.13 | 18-SEP-16:01 | 972.00 | 265.18 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 | 0.00 |
October | 3197.92 | 15-OCT-16:21 | 858.60 | 281.28 | 948.12 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 0.00 |
November | 2648.08 | 05-NOV-15:12 | 324.00 | 187.52 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 9.56 | 0.00 |
December | 1277.41 | 07-DEC-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 734.17 | 324.00 | 185.62 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3572.86 | 1441.80 | 758.59 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 68.85 | 67.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1740.00 | 28-JAN-16:11 | 378.00 | 137.54 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.70 |
February | 1784.09 | 27-FEB-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 |
March | 1788.47 | 13-MAR-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 4.04 | 0.00 |
April | 1747.18 | 09-APR-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 |
May | 1743.03 | 10-MAY-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 |
June | 1589.30 | 28-JUN-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 25.46 | 0.00 |
July | 1590.43 | 23-JUL-18:02 | 702.00 | 357.25 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 | 0.00 |
August | 1599.51 | 22-AUG-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.73 | 0.00 |
September | 1600.03 | 04-SEP-15:12 | 324.00 | 117.89 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 17.69 | 0.00 |
October | 1727.24 | 12-OCT-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.60 |
November | 1783.82 | 08-NOV-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 |
December | 1761.22 | 10-DEC-16:11 | 378.00 | 137.54 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1589.30 | 324.00 | 116.70 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1788.47 | 970.20 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 25.46 | 37.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17519.39 | 19-JAN-23:10 | 26988.77 | 921.04 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.10 |
February | 18301.69 | 28-FEB-22:00 | 23990.02 | 2456.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.76 |
March | 20852.25 | 30-MAR-21:07 | 80966.30 | 5526.25 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.11 |
April | 21627.01 | 12-APR-15:17 | 104956.32 | 3223.64 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 87.69 | 0.00 |
May | 21822.98 | 13-MAY-15:11 | 62973.79 | 3223.64 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 65.60 | 0.00 |
June | 21756.55 | 13-JUN-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 | 0.00 |
July | 22247.16 | 07-JUL-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 83.66 | 0.00 |
August | 21982.52 | 18-AUG-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 83.67 | 0.00 |
September | 20967.03 | 06-SEP-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 41.34 | 0.00 |
October | 20402.80 | 18-OCT-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.14 |
November | 18179.02 | 03-NOV-21:00 | 23990.02 | 2456.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.93 |
December | 17915.33 | 12-DEC-23:10 | 26988.77 | 921.04 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17519.39 | 23990.02 | 921.04 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22247.16 | 104956.32 | 5526.25 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 87.69 | 95.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18861.06 | 19-JAN-22:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.92 |
February | 20247.72 | 28-FEB-22:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.09 |
March | 21444.93 | 30-MAR-21:53 | 161932.61 | 11052.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.96 |
April | 22209.64 | 12-APR-15:17 | 104956.32 | 3223.64 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 83.12 | 0.00 |
May | 22435.55 | 13-MAY-15:11 | 62973.79 | 3223.64 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 60.80 | 0.00 |
June | 23157.63 | 13-JUN-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 | 0.00 |
July | 23650.69 | 07-JUL-21:30 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 92.87 | 0.00 |
August | 23369.60 | 18-AUG-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 101.08 | 0.00 |
September | 22353.40 | 06-SEP-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 41.34 | 0.00 |
October | 21419.49 | 18-OCT-21:53 | 161932.61 | 11052.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 |
November | 20222.07 | 03-NOV-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.87 |
December | 19956.51 | 12-DEC-22:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18861.06 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23650.69 | 161932.61 | 11052.49 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 101.08 | 96.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25900.21 | 29-JAN-11:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 174.86 |
February | 27108.95 | 26-FEB-11:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 24.05 |
March | 27564.00 | 30-MAR-18:03 | 13075.94 | 6787.40 | 102231.89 | 104966.55 | 0.00 | 0.00 | 0.00 | 27.30 | 0.00 |
April | 31385.35 | 15-APR-10:36 | 4002.84 | 1515.04 | 73022.78 | 93720.13 | 0.00 | 0.00 | 0.00 | 1.66 | 0.00 |
May | 30861.44 | 13-MAY-15:11 | 5603.98 | 2121.06 | 102231.89 | 157449.82 | 0.00 | 0.00 | 0.00 | 36.53 | 0.00 |
June | 29466.18 | 25-JUN-10:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 80.73 | 0.00 |
July | 29893.51 | 08-JUL-10:40 | 1601.14 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 126.34 | 0.00 |
August | 29776.45 | 27-AUG-10:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 83.72 | 0.00 |
September | 30007.30 | 22-SEP-16:52 | 8005.68 | 1818.05 | 87627.33 | 134956.99 | 0.00 | 0.00 | 0.00 | 25.99 | 0.00 |
October | 28130.67 | 09-OCT-10:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 |
November | 26720.78 | 11-NOV-11:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 75.48 |
December | 26236.62 | 12-DEC-11:50 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 57.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25900.21 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31385.35 | 13075.94 | 6787.40 | 102231.89 | 157449.82 | 0.00 | 0.00 | 0.00 | 126.34 | 174.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1688.66 | 31-JAN-21:00 | 1863.12 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.25 |
February | 2045.80 | 28-FEB-18:15 | 2661.60 | 1636.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 |
March | 3495.82 | 30-MAR-15:10 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.23 | 0.00 |
April | 4446.51 | 17-APR-15:10 | 2661.60 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.48 | 0.00 |
May | 4910.19 | 30-MAY-15:10 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.13 | 0.00 |
June | 5507.91 | 13-JUN-15:40 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.54 | 0.00 |
July | 6277.30 | 08-JUL-16:10 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.03 | 0.00 |
August | 6236.53 | 18-AUG-15:10 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.30 | 0.00 |
September | 5459.76 | 07-SEP-15:13 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.91 | 0.00 |
October | 4167.79 | 10-OCT-15:10 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.80 | 0.00 |
November | 2072.21 | 05-NOV-17:15 | 2129.28 | 1364.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.14 |
December | 1887.21 | 13-DEC-11:35 | 1064.64 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1688.66 | 1064.64 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6277.30 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.03 | 74.25 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.339120E+12 | 262107.64 | 19-JAN-20:49 | 0.597386E+12 | 500423.05 | 09-JAN-17:30 |
February | 0.314617E+12 | 269309.63 | 28-FEB-20:49 | 0.490060E+12 | 490104.14 | 12-FEB-17:40 |
March | 0.374659E+12 | 311501.10 | 30-MAR-19:10 | 0.457014E+12 | 414069.85 | 22-MAR-16:49 |
April | 0.410809E+12 | 314823.36 | 04-APR-19:00 | 0.411842E+12 | 386780.56 | 05-APR-21:40 |
May | 0.497213E+12 | 341929.78 | 30-MAY-19:40 | 0.394583E+12 | 357790.56 | 15-MAY-17:10 |
June | 0.571236E+12 | 362347.10 | 28-JUN-19:49 | 0.369764E+12 | 336420.65 | 08-JUN-17:30 |
July | 0.640522E+12 | 383163.99 | 07-JUL-19:49 | 0.374586E+12 | 318180.51 | 03-JUL-17:49 |
August | 0.657961E+12 | 385588.52 | 18-AUG-19:19 | 0.374278E+12 | 318041.22 | 31-AUG-17:19 |
September | 0.533622E+12 | 365311.79 | 07-SEP-19:10 | 0.368454E+12 | 334331.63 | 29-SEP-17:19 |
October | 0.422039E+12 | 348605.18 | 18-OCT-19:40 | 0.405583E+12 | 362359.06 | 30-OCT-18:10 |
November | 0.355732E+12 | 296766.52 | 27-NOV-20:10 | 0.452285E+12 | 436596.85 | 21-NOV-19:10 |
December | 0.338557E+12 | 257898.59 | 12-DEC-20:10 | 0.554542E+12 | 485260.82 | 02-DEC-19:10 |
Annual Sum or Average | 0.545609E+13 | 0.525038E+13 | ||||
Minimum of Months | 0.314617E+12 | 257898.59 | 0.368454E+12 | 318041.22 | ||
Maximum of Months | 0.657961E+12 | 385588.52 | 0.597386E+12 | 500423.05 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.469146E+11 | 0.192036E+11 | 0.140003E+12 | 0.544022E+11 | 0.472051E+11 | 0.500336E+10 | 0.00 | 0.537918E+10 | 0.00 | 0.00 | 0.958493E+10 | 0.770429E+10 | 0.00 |
February | 0.423283E+11 | 0.163904E+11 | 0.126445E+12 | 0.491376E+11 | 0.424440E+11 | 0.484482E+10 | 0.00 | 0.169550E+11 | 0.00 | 0.00 | 0.574722E+10 | 0.696184E+10 | 0.00 |
March | 0.464568E+11 | 0.167606E+11 | 0.140056E+12 | 0.544045E+11 | 0.471032E+11 | 0.683384E+10 | 0.00 | 0.491078E+11 | 0.00 | 0.00 | 0.249706E+10 | 0.770285E+10 | 0.00 |
April | 0.445793E+11 | 0.148358E+11 | 0.135446E+12 | 0.526466E+11 | 0.469244E+11 | 0.772459E+10 | 0.00 | 0.935551E+11 | 0.00 | 0.00 | 0.400271E+10 | 0.746484E+10 | 0.00 |
May | 0.457970E+11 | 0.141251E+11 | 0.140035E+12 | 0.544028E+11 | 0.505991E+11 | 0.842017E+10 | 0.00 | 0.164389E+12 | 0.00 | 0.00 | 0.796481E+10 | 0.770423E+10 | 0.00 |
June | 0.441798E+11 | 0.131404E+11 | 0.135537E+12 | 0.526487E+11 | 0.524569E+11 | 0.852275E+10 | 0.00 | 0.238355E+12 | 0.00 | 0.00 | 0.152797E+11 | 0.745688E+10 | 0.00 |
July | 0.456894E+11 | 0.137771E+11 | 0.139944E+12 | 0.544003E+11 | 0.554301E+11 | 0.903946E+10 | 0.00 | 0.291109E+12 | 0.00 | 0.00 | 0.196514E+11 | 0.771239E+10 | 0.00 |
August | 0.459470E+11 | 0.147839E+11 | 0.140067E+12 | 0.544042E+11 | 0.564512E+11 | 0.915689E+10 | 0.00 | 0.305131E+12 | 0.00 | 0.00 | 0.205299E+11 | 0.770436E+10 | 0.00 |
September | 0.448439E+11 | 0.156205E+11 | 0.135457E+12 | 0.526469E+11 | 0.509163E+11 | 0.835948E+10 | 0.00 | 0.202624E+12 | 0.00 | 0.00 | 0.120245E+11 | 0.746621E+10 | 0.00 |
October | 0.467429E+11 | 0.175749E+11 | 0.139992E+12 | 0.544021E+11 | 0.491705E+11 | 0.760936E+10 | 0.00 | 0.899474E+11 | 0.00 | 0.00 | 0.513522E+10 | 0.770292E+10 | 0.00 |
November | 0.453465E+11 | 0.182634E+11 | 0.135531E+12 | 0.526480E+11 | 0.463611E+11 | 0.618816E+10 | 0.00 | 0.371690E+11 | 0.00 | 0.00 | 0.316467E+10 | 0.744869E+10 | 0.00 |
December | 0.468706E+11 | 0.195441E+11 | 0.139944E+12 | 0.544011E+11 | 0.468639E+11 | 0.461580E+10 | 0.00 | 0.102006E+11 | 0.00 | 0.00 | 0.467851E+10 | 0.771244E+10 | 0.00 |
Annual Sum or Average | 0.545696E+12 | 0.194020E+12 | 0.164846E+13 | 0.640545E+12 | 0.591926E+12 | 0.863187E+11 | 0.00 | 0.150392E+13 | 0.00 | 0.00 | 0.110261E+12 | 0.907420E+11 | 0.00 |
Minimum of Months | 0.423283E+11 | 0.131404E+11 | 0.126445E+12 | 0.491376E+11 | 0.424440E+11 | 0.461580E+10 | 0.00 | 0.537918E+10 | 0.00 | 0.00 | 0.249706E+10 | 0.696184E+10 | 0.00 |
Maximum of Months | 0.469146E+11 | 0.195441E+11 | 0.140067E+12 | 0.544045E+11 | 0.564512E+11 | 0.915689E+10 | 0.00 | 0.305131E+12 | 0.00 | 0.00 | 0.205299E+11 | 0.771244E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.174262E+12 | 0.00 | 0.271206E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.107513E+12 | 0.00 | 0.245343E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.392172E+11 | 0.00 | 0.265773E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.184020E+11 | 0.00 | 0.246485E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.103014E+10 | 0.00 | 0.241574E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.206007E+09 | 0.00 | 0.222444E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 34422287.60 | 0.00 | 0.222731E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 19858394.29 | 0.00 | 0.222219E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.500128E+09 | 0.00 | 0.220984E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.141941E+11 | 0.00 | 0.239486E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.607269E+11 | 0.00 | 0.244467E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.138554E+12 | 0.00 | 0.264167E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.554660E+12 | 0.00 | 0.290688E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 19858394.29 | 0.00 | 0.220984E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.174262E+12 | 0.00 | 0.271206E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 45764.37 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 39153.73 | 02-JAN-07:19 | 28627.71 | 07-JAN-19:10 | 3705.90 | 05-JAN-16:40 | 0.00 | 01-JAN-00:10 |
February | 45764.37 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 39153.73 | 01-FEB-07:19 | 27205.12 | 03-FEB-19:10 | 3700.41 | 12-FEB-17:40 | 0.00 | 01-FEB-00:10 |
March | 45764.37 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 39153.73 | 01-MAR-07:19 | 28778.63 | 30-MAR-21:00 | 3535.62 | 18-MAR-08:09 | 0.00 | 01-MAR-00:10 |
April | 45764.37 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 39153.73 | 03-APR-06:19 | 28898.13 | 17-APR-21:00 | 3861.69 | 12-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 45764.37 | 01-MAY-19:19 | 12338.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 39153.35 | 08-MAY-06:19 | 30671.85 | 19-MAY-21:00 | 3702.39 | 15-MAY-18:30 | 0.00 | 01-MAY-00:10 |
June | 45764.37 | 01-JUN-19:40 | 12338.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 39153.16 | 23-JUN-06:19 | 34356.27 | 13-JUN-21:30 | 3971.45 | 28-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 45764.37 | 03-JUL-19:49 | 12338.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 39153.27 | 28-JUL-06:19 | 36501.28 | 07-JUL-21:19 | 4119.91 | 06-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 45764.37 | 01-AUG-19:40 | 12338.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 39153.73 | 25-AUG-06:19 | 37841.83 | 18-AUG-21:19 | 4073.04 | 10-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 45764.37 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 39153.73 | 01-SEP-06:19 | 36227.44 | 07-SEP-21:19 | 3916.86 | 07-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 45764.37 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 39153.73 | 02-OCT-06:19 | 32296.06 | 10-OCT-21:00 | 3690.41 | 18-OCT-18:10 | 0.00 | 01-OCT-00:10 |
November | 45764.37 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 39153.73 | 01-NOV-06:19 | 27853.94 | 08-NOV-21:19 | 3662.17 | 21-NOV-09:39 | 0.00 | 01-NOV-00:10 |
December | 45764.37 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 39153.73 | 01-DEC-07:19 | 26559.67 | 13-DEC-21:10 | 3702.80 | 18-DEC-10:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45764.37 | 12338.45 | 88863.15 | 39153.16 | 26559.67 | 3535.62 | 0.00 | |||||||
Maximum of Months | 45764.37 | 12338.45 | 88863.15 | 39153.73 | 37841.83 | 4119.91 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 55014.96 | 19-JAN-20:00 | 0.00 | 0.00 | 8265.52 | 05-JAN-00:10 | 4738.72 | 12-JAN-19:10 | 0.00 |
February | 83924.32 | 26-FEB-16:19 | 0.00 | 0.00 | 8265.52 | 01-FEB-06:10 | 4738.76 | 23-FEB-19:10 | 0.00 |
March | 108257.72 | 30-MAR-15:30 | 0.00 | 0.00 | 8265.52 | 11-MAR-13:30 | 4738.59 | 02-MAR-19:10 | 0.00 |
April | 111058.47 | 12-APR-15:39 | 0.00 | 0.00 | 8265.52 | 02-APR-12:50 | 4738.51 | 25-APR-06:00 | 0.00 |
May | 134331.35 | 30-MAY-18:10 | 0.00 | 0.00 | 8265.52 | 01-MAY-15:39 | 4738.39 | 18-MAY-18:10 | 0.00 |
June | 162348.21 | 28-JUN-18:10 | 0.00 | 0.00 | 8265.52 | 01-JUN-08:00 | 4738.71 | 01-JUN-18:10 | 0.00 |
July | 183539.50 | 08-JUL-15:30 | 0.00 | 0.00 | 8265.52 | 01-JUL-08:39 | 4738.72 | 13-JUL-18:10 | 0.00 |
August | 176268.26 | 01-AUG-15:30 | 0.00 | 0.00 | 8265.52 | 05-AUG-08:00 | 4738.58 | 24-AUG-18:10 | 0.00 |
September | 160551.74 | 07-SEP-15:30 | 0.00 | 0.00 | 8265.52 | 11-SEP-21:00 | 4738.72 | 07-SEP-18:10 | 0.00 |
October | 133086.80 | 18-OCT-21:00 | 0.00 | 0.00 | 8265.52 | 01-OCT-12:00 | 4738.26 | 04-OCT-06:19 | 0.00 |
November | 96243.49 | 05-NOV-15:20 | 0.00 | 0.00 | 8265.52 | 05-NOV-12:00 | 4738.31 | 08-NOV-19:10 | 0.00 |
December | 66892.64 | 12-DEC-13:00 | 0.00 | 0.00 | 8265.52 | 01-DEC-00:49 | 4738.64 | 07-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 55014.96 | 0.00 | 0.00 | 8265.52 | 4738.26 | 0.00 | |||
Maximum of Months | 183539.50 | 0.00 | 0.00 | 8265.52 | 4738.76 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 262107.64 | 19-JAN-20:49 | 45764.37 | 86131.51 | 12338.45 | 31530.53 | 22986.80 | 3068.21 | 0.00 | 54596.22 | 0.00 |
February | 269309.63 | 28-FEB-20:49 | 45764.37 | 86131.51 | 12338.45 | 31530.53 | 23805.85 | 3077.34 | 0.00 | 61438.82 | 0.00 |
March | 311501.10 | 30-MAR-19:10 | 45764.37 | 86131.51 | 12338.45 | 31526.42 | 26697.42 | 3375.47 | 0.00 | 98623.81 | 0.00 |
April | 314823.36 | 04-APR-19:00 | 45764.37 | 86131.51 | 12338.45 | 31530.53 | 26236.35 | 3364.97 | 0.00 | 96224.13 | 0.00 |
May | 341929.78 | 30-MAY-19:40 | 45764.37 | 86131.51 | 12338.45 | 31530.06 | 27821.34 | 3637.32 | 0.00 | 121328.75 | 0.00 |
June | 362347.10 | 28-JUN-19:49 | 45764.37 | 86131.51 | 12338.45 | 31530.17 | 28517.34 | 3764.84 | 0.00 | 140821.68 | 0.00 |
July | 383163.99 | 07-JUL-19:49 | 45764.37 | 86131.51 | 12338.45 | 31530.03 | 30981.22 | 3809.01 | 0.00 | 159470.08 | 0.00 |
August | 385588.52 | 18-AUG-19:19 | 45764.37 | 86131.51 | 12338.45 | 31529.23 | 31351.71 | 3776.62 | 0.00 | 161123.56 | 0.00 |
September | 365311.79 | 07-SEP-19:10 | 45764.37 | 86131.51 | 12338.45 | 31526.42 | 29281.91 | 3799.22 | 0.00 | 142718.78 | 0.00 |
October | 348605.18 | 18-OCT-19:40 | 45764.37 | 86131.51 | 12338.45 | 31530.53 | 26298.76 | 3665.04 | 0.00 | 128891.96 | 0.00 |
November | 296766.52 | 27-NOV-20:10 | 45764.37 | 86131.51 | 12338.45 | 31526.42 | 24985.21 | 3212.86 | 0.00 | 80410.51 | 0.00 |
December | 257898.59 | 12-DEC-20:10 | 45764.37 | 86131.51 | 12338.45 | 31526.42 | 24347.56 | 3079.59 | 0.00 | 49684.31 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 257898.59 | 45764.37 | 86131.51 | 12338.45 | 31526.42 | 22986.80 | 3068.21 | 0.00 | 49684.31 | 0.00 | |
Maximum of Months | 385588.52 | 45764.37 | 86131.51 | 12338.45 | 31530.53 | 31351.71 | 3809.01 | 0.00 | 161123.56 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 181957.97 | 09-JAN-16:19 | 0.00 | 271213.31 | 24-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 170672.37 | 03-FEB-16:19 | 0.00 | 266866.58 | 02-FEB-18:00 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 142774.46 | 19-MAR-03:39 | 0.00 | 251742.84 | 03-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 154757.86 | 06-APR-02:39 | 0.00 | 246788.29 | 03-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 26534.79 | 11-MAY-04:00 | 0.00 | 244539.58 | 02-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 14335.91 | 10-JUN-12:39 | 0.00 | 234904.72 | 02-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 4970.93 | 28-JUL-21:00 | 0.00 | 214484.43 | 03-JUL-20:49 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 2804.90 | 30-AUG-21:00 | 0.00 | 214341.14 | 31-AUG-20:00 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 17323.67 | 22-SEP-16:10 | 0.00 | 230069.55 | 29-SEP-17:19 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 135856.87 | 26-OCT-04:00 | 0.00 | 244175.20 | 30-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 162157.75 | 25-NOV-05:49 | 0.00 | 246503.83 | 30-NOV-21:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 166449.32 | 21-DEC-09:09 | 0.00 | 248117.54 | 29-DEC-21:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 2804.90 | 0.00 | 214341.14 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 181957.97 | 0.00 | 271213.31 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 20.45 | 2.83 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
February | 1.17 | 20.48 | 1.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.71 | 1.83 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.74 | 1.67 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.00 | 20.46 | 4.00 | 20.46 | 4.17 | 20.89 | 4.17 | 21.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 20.48 | 2.83 | 20.48 | 1.83 | 21.74 | 1.83 | 21.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 20.43 | 4.67 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
February | 3.00 | 20.46 | 3.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.73 | 1.83 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.76 | 4.17 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.73 | 1.83 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.82 | 0.33 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.81 | 0.17 | 21.81 |
November | 0.33 | 20.52 | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
December | 1.33 | 20.52 | 1.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 9.33 | 20.46 | 9.33 | 20.46 | 8.33 | 20.86 | 8.33 | 21.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.67 | 20.52 | 4.67 | 20.52 | 4.17 | 21.82 | 4.17 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 20.36 | 2.17 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
February | 0.67 | 20.33 | 0.67 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.73 | 2.00 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 21.73 | 7.17 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 21.77 | 9.67 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 21.74 | 6.00 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.82 | 1.00 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.83 | 20.35 | 2.83 | 20.35 | 26.50 | 21.50 | 26.50 | 21.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 20.36 | 2.17 | 20.36 | 9.67 | 21.82 | 9.67 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 20.43 | 2.83 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
February | 1.00 | 20.51 | 1.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.83 | 20.45 | 3.83 | 20.45 | 0.50 | 20.53 | 0.50 | 20.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 20.51 | 2.83 | 20.51 | 0.33 | 21.69 | 0.33 | 21.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.00 | 20.45 | 6.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
February | 2.83 | 20.50 | 2.83 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.98 | 0.83 | 21.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 22.03 | 3.67 | 22.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 22.17 | 7.33 | 22.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 22.17 | 9.50 | 22.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 22.11 | 6.17 | 22.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 22.12 | 3.50 | 22.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 20.54 | 1.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Annual Sum or Average | 9.83 | 20.48 | 9.83 | 20.48 | 31.00 | 21.49 | 31.00 | 21.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 20.54 | 6.00 | 20.54 | 9.50 | 22.17 | 9.50 | 22.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 20.40 | 2.83 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
February | 1.17 | 20.46 | 1.17 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.72 | 1.50 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.77 | 2.83 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.82 | 2.00 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.79 | 1.00 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.00 | 20.42 | 4.00 | 20.42 | 8.67 | 21.12 | 8.67 | 21.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 20.46 | 2.83 | 20.46 | 2.83 | 21.82 | 2.83 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 20.37 | 4.50 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
February | 2.50 | 20.38 | 2.50 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.73 | 3.00 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.78 | 5.17 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.75 | 2.67 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.82 | 0.50 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.83 | 0.17 | 21.83 |
November | 0.33 | 20.53 | 0.33 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
December | 1.17 | 20.51 | 1.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Annual Sum or Average | 8.50 | 20.40 | 8.50 | 20.40 | 11.83 | 20.96 | 11.83 | 21.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 20.53 | 4.50 | 20.53 | 5.17 | 21.83 | 5.17 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 20.46 | 2.17 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
February | 0.50 | 20.54 | 0.50 | 20.54 | 0.50 | 20.96 | 0.50 | 21.17 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.74 | 1.50 | 21.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.73 | 1.17 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.82 | 2.50 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.80 | 2.67 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.83 | 2.83 | 21.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.67 | 20.48 | 2.67 | 20.48 | 12.33 | 21.40 | 12.33 | 21.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 20.54 | 2.17 | 20.54 | 2.83 | 21.83 | 2.83 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.72 | 8.33 | 24.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.72 | 1.50 | 24.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.58 | 0.83 | 24.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.68 | 1.17 | 24.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.83 | 24.71 | 11.83 | 24.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.72 | 8.33 | 24.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.67 | 0.00 | 22.67 | 0.00 | 22.67 |
February | 672.00 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
March | 744.00 | 21.61 | 2.67 | 21.61 | 2.67 | 21.60 |
April | 720.00 | 21.25 | 0.00 | 21.25 | 0.00 | 21.25 |
May | 744.00 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
June | 720.00 | 22.36 | 0.83 | 22.36 | 0.83 | 22.36 |
July | 735.00 | 22.89 | 10.50 | 22.89 | 10.50 | 22.89 |
August | 383.50 | 23.22 | 232.50 | 23.42 | 81.17 | 23.44 |
September | 87.67 | 23.87 | 443.67 | 23.94 | 72.17 | 23.94 |
October | 131.83 | 23.80 | 238.17 | 23.90 | 21.83 | 23.90 |
November | 376.67 | 23.89 | 124.33 | 23.91 | 3.17 | 23.91 |
December | 637.00 | 23.65 | 25.33 | 23.66 | 0.00 | 23.66 |
Annual Sum or Average | 6695.67 | 22.44 | 1078.00 | 22.64 | 192.33 | 22.67 |
Minimum of Months | 87.67 | 21.25 | 0.00 | 21.25 | 0.00 | 21.25 |
Maximum of Months | 744.00 | 23.89 | 443.67 | 23.94 | 81.17 | 23.94 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 734.83 | 21.32 | 291.00 | 21.23 | 291.00 | 21.18 |
February | 630.00 | 21.48 | 175.00 | 21.38 | 173.00 | 21.31 |
March | 617.17 | 22.03 | 66.33 | 22.17 | 11.17 | 22.15 |
April | 510.83 | 22.26 | 128.83 | 22.57 | 12.17 | 22.57 |
May | 361.50 | 22.71 | 363.33 | 23.21 | 75.67 | 23.19 |
June | 215.67 | 23.44 | 587.17 | 23.77 | 139.83 | 23.76 |
July | 205.33 | 23.64 | 699.67 | 23.84 | 184.83 | 23.82 |
August | 206.00 | 23.93 | 742.33 | 23.95 | 206.00 | 23.95 |
September | 261.17 | 23.05 | 532.67 | 23.58 | 130.17 | 23.58 |
October | 472.17 | 22.16 | 219.33 | 22.69 | 38.83 | 22.72 |
November | 624.17 | 21.87 | 58.67 | 21.96 | 23.83 | 21.93 |
December | 696.83 | 21.45 | 124.50 | 21.42 | 114.83 | 21.37 |
Annual Sum or Average | 5535.67 | 22.09 | 3988.83 | 22.65 | 1401.33 | 22.63 |
Minimum of Months | 205.33 | 21.32 | 58.67 | 21.23 | 11.17 | 21.18 |
Maximum of Months | 734.83 | 23.93 | 742.33 | 23.95 | 291.00 | 23.95 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.36 | 10.17 | 21.36 | 10.17 | 21.35 |
February | 672.00 | 21.65 | 19.50 | 21.63 | 19.50 | 21.61 |
March | 720.50 | 22.21 | 6.00 | 22.23 | 0.00 | 22.23 |
April | 652.83 | 22.46 | 22.33 | 22.49 | 12.00 | 22.49 |
May | 558.50 | 22.68 | 166.00 | 22.86 | 82.33 | 22.89 |
June | 423.83 | 23.10 | 307.17 | 23.38 | 128.67 | 23.43 |
July | 351.67 | 23.23 | 404.83 | 23.54 | 157.83 | 23.58 |
August | 292.67 | 23.51 | 455.50 | 23.71 | 187.33 | 23.74 |
September | 402.50 | 22.98 | 274.33 | 23.28 | 111.50 | 23.33 |
October | 659.17 | 22.53 | 68.00 | 22.62 | 37.00 | 22.65 |
November | 713.50 | 22.18 | 7.17 | 22.18 | 7.17 | 22.19 |
December | 742.67 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
Annual Sum or Average | 6933.83 | 22.30 | 1741.00 | 22.58 | 753.50 | 22.66 |
Minimum of Months | 292.67 | 21.36 | 0.00 | 21.36 | 0.00 | 21.35 |
Maximum of Months | 744.00 | 23.51 | 455.50 | 23.71 | 187.33 | 23.74 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.71 | 107.33 | 21.64 | 107.33 | 21.58 |
February | 670.00 | 22.37 | 106.17 | 22.23 | 106.17 | 22.13 |
March | 634.17 | 23.42 | 6.83 | 23.43 | 0.00 | 23.43 |
April | 411.00 | 23.76 | 98.50 | 23.80 | 10.00 | 23.81 |
May | 138.17 | 23.99 | 432.67 | 24.00 | 21.50 | 24.00 |
June | 74.33 | 24.00 | 543.50 | 24.00 | 0.00 | 24.00 |
July | 7.00 | 24.00 | 744.00 | 24.00 | 7.00 | 24.00 |
August | 0.00 | 0.00 | 744.00 | 24.00 | 0.00 | 24.00 |
September | 3.67 | 24.00 | 540.83 | 24.00 | 2.00 | 24.00 |
October | 405.17 | 23.80 | 180.50 | 23.86 | 33.00 | 23.87 |
November | 579.83 | 23.38 | 36.67 | 23.41 | 0.00 | 23.41 |
December | 707.83 | 22.51 | 4.00 | 22.52 | 0.00 | 22.52 |
Annual Sum or Average | 4375.17 | 22.91 | 3545.00 | 23.32 | 287.00 | 23.28 |
Minimum of Months | 0.00 | 0.00 | 4.00 | 21.64 | 0.00 | 21.58 |
Maximum of Months | 744.00 | 24.00 | 744.00 | 24.00 | 107.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 313.33 | 21.00 | 313.33 | 21.00 |
February | 672.00 | 21.04 | 186.50 | 21.03 | 186.50 | 21.02 |
March | 744.00 | 21.22 | 23.83 | 21.21 | 23.83 | 21.20 |
April | 720.00 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
May | 744.00 | 22.00 | 0.00 | 22.00 | 0.00 | 22.00 |
June | 720.00 | 22.60 | 0.00 | 22.60 | 0.00 | 22.60 |
July | 723.83 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
August | 726.33 | 22.88 | 0.00 | 22.88 | 0.00 | 22.88 |
September | 720.00 | 22.41 | 0.00 | 22.41 | 0.00 | 22.41 |
October | 744.00 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
November | 720.00 | 21.21 | 7.17 | 21.21 | 7.17 | 21.21 |
December | 744.00 | 21.03 | 111.67 | 21.03 | 111.67 | 21.03 |
Annual Sum or Average | 8722.17 | 21.78 | 642.50 | 21.73 | 642.50 | 21.68 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.88 | 313.33 | 22.88 | 313.33 | 22.88 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 160.33 | 24.00 | 744.00 | 24.00 | 160.33 | 24.00 |
February | 170.00 | 24.00 | 672.00 | 24.00 | 170.00 | 24.00 |
March | 259.50 | 24.00 | 744.00 | 24.00 | 259.50 | 24.00 |
April | 340.67 | 24.00 | 720.00 | 24.00 | 340.67 | 24.00 |
May | 539.67 | 24.00 | 744.00 | 24.00 | 539.67 | 24.00 |
June | 574.00 | 24.00 | 720.00 | 24.00 | 574.00 | 24.00 |
July | 651.83 | 24.00 | 744.00 | 24.00 | 651.83 | 24.00 |
August | 658.00 | 24.00 | 744.00 | 24.00 | 658.00 | 24.00 |
September | 567.50 | 24.00 | 720.00 | 24.00 | 567.50 | 24.00 |
October | 390.17 | 24.00 | 744.00 | 24.00 | 390.17 | 24.00 |
November | 249.17 | 24.00 | 720.00 | 24.00 | 249.17 | 24.00 |
December | 186.83 | 24.00 | 744.00 | 24.00 | 186.83 | 24.00 |
Annual Sum or Average | 4747.67 | 24.00 | 8760.00 | 24.00 | 4747.67 | 24.00 |
Minimum of Months | 160.33 | 24.00 | 672.00 | 24.00 | 160.33 | 24.00 |
Maximum of Months | 658.00 | 24.00 | 744.00 | 24.00 | 658.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 741.00 | 21.32 | 58.67 | 21.30 | 58.67 | 21.29 |
February | 660.50 | 21.52 | 29.33 | 21.50 | 29.33 | 21.49 |
March | 696.67 | 21.83 | 26.50 | 21.88 | 11.83 | 21.89 |
April | 655.17 | 21.87 | 60.83 | 21.94 | 53.33 | 21.99 |
May | 664.33 | 22.02 | 192.17 | 22.20 | 168.67 | 22.30 |
June | 568.83 | 22.37 | 246.67 | 22.63 | 202.67 | 22.76 |
July | 538.83 | 22.57 | 383.67 | 22.82 | 286.67 | 22.93 |
August | 455.00 | 22.87 | 480.83 | 23.06 | 286.67 | 23.16 |
September | 514.50 | 22.37 | 346.33 | 22.66 | 217.33 | 22.75 |
October | 610.83 | 22.05 | 140.67 | 22.23 | 78.50 | 22.30 |
November | 660.33 | 21.77 | 42.17 | 21.84 | 26.50 | 21.87 |
December | 722.50 | 21.50 | 7.83 | 21.52 | 3.67 | 21.52 |
Annual Sum or Average | 7488.50 | 21.95 | 2015.67 | 22.18 | 1423.83 | 22.29 |
Minimum of Months | 455.00 | 21.32 | 7.83 | 21.30 | 3.67 | 21.29 |
Maximum of Months | 741.00 | 22.87 | 480.83 | 23.06 | 286.67 | 23.16 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.79 | 4.67 | 21.80 | 4.67 | 21.81 |
February | 669.17 | 22.04 | 10.83 | 22.06 | 10.83 | 22.07 |
March | 698.83 | 22.48 | 34.67 | 22.54 | 20.67 | 22.56 |
April | 618.33 | 22.58 | 100.83 | 22.71 | 68.67 | 22.77 |
May | 608.50 | 22.82 | 269.17 | 23.06 | 193.17 | 23.15 |
June | 480.33 | 23.19 | 335.67 | 23.45 | 214.83 | 23.54 |
July | 467.83 | 23.39 | 431.50 | 23.59 | 299.17 | 23.66 |
August | 385.33 | 23.64 | 465.00 | 23.74 | 299.00 | 23.79 |
September | 457.00 | 23.21 | 382.00 | 23.46 | 243.00 | 23.53 |
October | 585.50 | 22.74 | 124.33 | 22.89 | 90.33 | 22.97 |
November | 686.00 | 22.54 | 40.50 | 22.59 | 31.83 | 22.62 |
December | 724.17 | 22.11 | 10.67 | 22.13 | 4.00 | 22.14 |
Annual Sum or Average | 7125.00 | 22.61 | 2209.83 | 22.88 | 1480.17 | 23.00 |
Minimum of Months | 385.33 | 21.79 | 4.67 | 21.80 | 4.00 | 21.81 |
Maximum of Months | 744.00 | 23.64 | 465.00 | 23.74 | 299.17 | 23.79 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.82 | 515.50 | 20.76 | 515.50 | 20.73 |
February | 671.67 | 21.03 | 296.17 | 20.90 | 296.17 | 20.83 |
March | 735.50 | 21.45 | 29.50 | 21.42 | 29.50 | 21.39 |
April | 696.17 | 21.58 | 10.67 | 21.58 | 10.67 | 21.59 |
May | 683.00 | 21.59 | 5.17 | 21.60 | 5.17 | 21.61 |
June | 606.67 | 21.50 | 7.83 | 21.52 | 7.83 | 21.54 |
July | 607.17 | 21.45 | 23.83 | 21.50 | 18.83 | 21.54 |
August | 592.00 | 21.41 | 14.17 | 21.45 | 10.83 | 21.47 |
September | 633.50 | 21.53 | 14.67 | 21.56 | 14.00 | 21.59 |
October | 718.33 | 21.47 | 42.17 | 21.47 | 42.17 | 21.46 |
November | 717.67 | 21.36 | 84.33 | 21.31 | 84.33 | 21.27 |
December | 744.00 | 21.03 | 324.33 | 20.94 | 324.33 | 20.89 |
Annual Sum or Average | 8149.67 | 21.34 | 1368.33 | 21.27 | 1359.33 | 21.21 |
Minimum of Months | 592.00 | 20.82 | 5.17 | 20.76 | 5.17 | 20.73 |
Maximum of Months | 744.00 | 21.59 | 515.50 | 21.60 | 515.50 | 21.61 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.58 | 602.17 | 20.54 | 602.17 | 20.52 |
February | 672.00 | 20.89 | 347.67 | 20.74 | 347.67 | 20.67 |
March | 735.17 | 21.49 | 58.83 | 21.42 | 58.83 | 21.36 |
April | 679.33 | 21.84 | 39.17 | 21.90 | 27.83 | 21.91 |
May | 637.33 | 21.94 | 72.33 | 22.12 | 53.00 | 22.19 |
June | 583.17 | 21.83 | 67.00 | 22.05 | 57.67 | 22.19 |
July | 592.50 | 21.82 | 110.67 | 22.10 | 100.17 | 22.29 |
August | 591.83 | 21.72 | 77.67 | 21.94 | 73.33 | 22.11 |
September | 638.83 | 21.95 | 77.33 | 22.11 | 71.83 | 22.23 |
October | 712.00 | 21.59 | 80.17 | 21.60 | 75.17 | 21.60 |
November | 720.00 | 21.20 | 168.33 | 21.11 | 168.33 | 21.05 |
December | 744.00 | 20.74 | 510.83 | 20.67 | 510.83 | 20.64 |
Annual Sum or Average | 8050.17 | 21.44 | 2212.17 | 21.38 | 2146.83 | 21.33 |
Minimum of Months | 583.17 | 20.58 | 39.17 | 20.54 | 27.83 | 20.52 |
Maximum of Months | 744.00 | 21.95 | 602.17 | 22.12 | 602.17 | 22.29 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.86 | 478.50 | 20.80 | 478.50 | 20.78 |
February | 672.00 | 21.07 | 236.33 | 20.96 | 236.33 | 20.90 |
March | 744.00 | 21.43 | 35.67 | 21.41 | 35.67 | 21.39 |
April | 719.83 | 21.82 | 8.17 | 21.83 | 8.17 | 21.85 |
May | 742.83 | 22.06 | 35.17 | 22.10 | 35.17 | 22.15 |
June | 719.17 | 22.04 | 52.83 | 22.13 | 52.83 | 22.21 |
July | 742.83 | 22.05 | 89.33 | 22.19 | 89.33 | 22.30 |
August | 743.83 | 21.97 | 70.17 | 22.08 | 70.17 | 22.17 |
September | 719.67 | 22.03 | 52.17 | 22.11 | 52.17 | 22.19 |
October | 744.00 | 21.62 | 32.67 | 21.65 | 32.67 | 21.68 |
November | 720.00 | 21.29 | 46.17 | 21.27 | 46.17 | 21.24 |
December | 744.00 | 21.02 | 242.50 | 20.96 | 242.50 | 20.92 |
Annual Sum or Average | 8756.17 | 21.61 | 1379.67 | 21.57 | 1379.67 | 21.54 |
Minimum of Months | 672.00 | 20.86 | 8.17 | 20.80 | 8.17 | 20.78 |
Maximum of Months | 744.00 | 22.06 | 478.50 | 22.19 | 478.50 | 22.30 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.85 | 490.67 | 20.79 | 490.67 | 20.76 |
February | 672.00 | 21.08 | 284.00 | 20.96 | 284.00 | 20.89 |
March | 743.33 | 21.54 | 32.33 | 21.51 | 32.33 | 21.48 |
April | 711.67 | 21.69 | 8.67 | 21.69 | 8.67 | 21.70 |
May | 683.67 | 21.64 | 4.17 | 21.65 | 4.17 | 21.65 |
June | 580.50 | 21.44 | 4.00 | 21.45 | 3.00 | 21.46 |
July | 561.67 | 21.31 | 16.33 | 21.35 | 14.17 | 21.39 |
August | 563.83 | 21.32 | 8.67 | 21.35 | 8.00 | 21.37 |
September | 626.00 | 21.52 | 12.17 | 21.55 | 12.17 | 21.57 |
October | 727.00 | 21.54 | 41.50 | 21.53 | 41.50 | 21.52 |
November | 720.00 | 21.41 | 76.17 | 21.37 | 76.17 | 21.33 |
December | 744.00 | 21.06 | 291.50 | 20.98 | 291.50 | 20.94 |
Annual Sum or Average | 8077.67 | 21.37 | 1270.17 | 21.29 | 1266.33 | 21.24 |
Minimum of Months | 561.67 | 20.85 | 4.00 | 20.79 | 3.00 | 20.76 |
Maximum of Months | 744.00 | 21.69 | 490.67 | 21.69 | 490.67 | 21.70 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.59 | 592.67 | 20.55 | 592.67 | 20.53 |
February | 672.00 | 20.92 | 336.17 | 20.77 | 336.17 | 20.70 |
March | 744.00 | 21.51 | 62.83 | 21.46 | 62.83 | 21.42 |
April | 711.67 | 21.97 | 26.83 | 22.00 | 23.17 | 22.01 |
May | 643.00 | 22.04 | 74.33 | 22.22 | 53.17 | 22.30 |
June | 547.00 | 21.83 | 75.83 | 22.15 | 58.00 | 22.34 |
July | 559.17 | 21.85 | 112.33 | 22.23 | 100.50 | 22.48 |
August | 565.33 | 21.71 | 77.50 | 22.00 | 73.33 | 22.21 |
September | 641.33 | 22.01 | 78.67 | 22.20 | 70.33 | 22.33 |
October | 742.33 | 21.70 | 72.00 | 21.70 | 71.50 | 21.70 |
November | 720.00 | 21.17 | 156.17 | 21.10 | 156.17 | 21.06 |
December | 744.00 | 20.75 | 498.00 | 20.69 | 498.00 | 20.66 |
Annual Sum or Average | 8033.83 | 21.47 | 2163.33 | 21.44 | 2095.83 | 21.40 |
Minimum of Months | 547.00 | 20.59 | 26.83 | 20.55 | 23.17 | 20.53 |
Maximum of Months | 744.00 | 22.04 | 592.67 | 22.23 | 592.67 | 22.48 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 171.67 | 21.01 | 171.67 | 21.01 |
February | 672.00 | 21.14 | 145.33 | 21.11 | 145.33 | 21.09 |
March | 744.00 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
April | 720.00 | 22.12 | 19.67 | 22.13 | 19.67 | 22.13 |
May | 744.00 | 22.57 | 112.33 | 22.58 | 112.33 | 22.58 |
June | 679.00 | 23.13 | 171.17 | 23.16 | 171.17 | 23.18 |
July | 516.67 | 23.30 | 264.00 | 23.35 | 247.17 | 23.37 |
August | 525.33 | 23.39 | 279.17 | 23.43 | 266.67 | 23.44 |
September | 711.50 | 22.92 | 171.17 | 22.95 | 171.17 | 22.96 |
October | 744.00 | 22.00 | 48.00 | 22.03 | 48.00 | 22.05 |
November | 720.00 | 21.30 | 11.50 | 21.30 | 11.50 | 21.30 |
December | 744.00 | 21.05 | 87.00 | 21.04 | 87.00 | 21.04 |
Annual Sum or Average | 8264.50 | 22.06 | 1481.00 | 22.14 | 1451.67 | 22.20 |
Minimum of Months | 516.67 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 23.39 | 279.17 | 23.43 | 266.67 | 23.44 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.70 | 589.67 | 20.64 | 589.67 | 20.62 |
February | 669.67 | 20.93 | 362.00 | 20.79 | 362.00 | 20.73 |
March | 732.50 | 21.38 | 86.83 | 21.30 | 86.83 | 21.25 |
April | 677.17 | 21.50 | 42.00 | 21.50 | 42.00 | 21.50 |
May | 648.00 | 21.49 | 24.17 | 21.50 | 23.67 | 21.51 |
June | 583.17 | 21.42 | 24.17 | 21.48 | 17.67 | 21.52 |
July | 588.17 | 21.39 | 63.17 | 21.53 | 36.33 | 21.58 |
August | 576.00 | 21.36 | 52.00 | 21.50 | 22.83 | 21.54 |
September | 613.83 | 21.45 | 43.17 | 21.52 | 35.67 | 21.57 |
October | 705.83 | 21.38 | 70.83 | 21.35 | 70.67 | 21.33 |
November | 715.33 | 21.27 | 170.67 | 21.19 | 170.67 | 21.14 |
December | 744.00 | 20.90 | 464.17 | 20.81 | 464.17 | 20.77 |
Annual Sum or Average | 7997.67 | 21.25 | 1992.83 | 21.18 | 1922.17 | 21.11 |
Minimum of Months | 576.00 | 20.70 | 24.17 | 20.64 | 17.67 | 20.62 |
Maximum of Months | 744.00 | 21.50 | 589.67 | 21.53 | 589.67 | 21.58 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.50 | 648.00 | 20.47 | 648.00 | 20.46 |
February | 670.17 | 20.80 | 409.83 | 20.67 | 409.83 | 20.61 |
March | 729.67 | 21.40 | 132.33 | 21.28 | 131.50 | 21.20 |
April | 651.33 | 21.74 | 80.67 | 21.84 | 60.83 | 21.83 |
May | 597.67 | 21.82 | 105.17 | 22.07 | 71.67 | 22.14 |
June | 564.17 | 21.75 | 83.50 | 22.00 | 67.67 | 22.14 |
July | 577.67 | 21.75 | 147.50 | 22.07 | 117.50 | 22.25 |
August | 576.00 | 21.65 | 103.67 | 21.91 | 85.33 | 22.07 |
September | 614.33 | 21.83 | 103.83 | 22.02 | 95.67 | 22.13 |
October | 703.83 | 21.48 | 123.83 | 21.49 | 115.17 | 21.47 |
November | 719.33 | 21.10 | 294.83 | 20.99 | 294.83 | 20.93 |
December | 744.00 | 20.63 | 591.00 | 20.57 | 591.00 | 20.54 |
Annual Sum or Average | 7892.17 | 21.33 | 2824.17 | 21.29 | 2689.00 | 21.23 |
Minimum of Months | 564.17 | 20.50 | 80.67 | 20.47 | 60.83 | 20.46 |
Maximum of Months | 744.00 | 21.83 | 648.00 | 22.07 | 648.00 | 22.25 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.21 | 309.83 | 21.07 | 309.83 | 20.99 |
February | 664.83 | 21.30 | 186.83 | 21.17 | 186.83 | 21.09 |
March | 728.17 | 21.54 | 23.67 | 21.51 | 23.67 | 21.48 |
April | 687.50 | 21.58 | 8.67 | 21.58 | 8.67 | 21.57 |
May | 696.00 | 21.62 | 9.17 | 21.62 | 9.17 | 21.63 |
June | 640.83 | 21.59 | 18.33 | 21.62 | 18.33 | 21.65 |
July | 633.17 | 21.51 | 35.17 | 21.57 | 35.17 | 21.62 |
August | 616.67 | 21.48 | 25.00 | 21.53 | 23.17 | 21.57 |
September | 632.00 | 21.52 | 19.00 | 21.56 | 17.00 | 21.58 |
October | 678.50 | 21.45 | 39.83 | 21.46 | 34.17 | 21.45 |
November | 691.83 | 21.51 | 33.67 | 21.48 | 33.67 | 21.45 |
December | 735.50 | 21.35 | 147.67 | 21.25 | 147.67 | 21.18 |
Annual Sum or Average | 8149.00 | 21.47 | 856.83 | 21.43 | 847.33 | 21.39 |
Minimum of Months | 616.67 | 21.21 | 8.67 | 21.07 | 8.67 | 20.99 |
Maximum of Months | 744.00 | 21.62 | 309.83 | 21.62 | 309.83 | 21.65 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 733.67 | 21.79 | 4.50 | 21.79 | 4.50 | 21.80 |
February | 651.50 | 21.98 | 14.17 | 22.01 | 10.83 | 22.03 |
March | 630.33 | 22.23 | 61.83 | 22.35 | 13.17 | 22.37 |
April | 495.67 | 22.39 | 159.33 | 22.67 | 60.50 | 22.74 |
May | 412.67 | 22.76 | 354.67 | 23.09 | 177.67 | 23.18 |
June | 318.00 | 23.21 | 451.67 | 23.36 | 206.33 | 23.45 |
July | 359.00 | 23.40 | 544.33 | 23.42 | 288.17 | 23.50 |
August | 359.50 | 23.43 | 535.83 | 23.45 | 287.00 | 23.54 |
September | 429.17 | 22.85 | 388.17 | 23.14 | 222.67 | 23.24 |
October | 582.33 | 22.32 | 138.00 | 22.54 | 82.50 | 22.63 |
November | 663.50 | 22.14 | 46.00 | 22.22 | 30.17 | 22.27 |
December | 723.00 | 21.92 | 16.00 | 21.96 | 3.67 | 21.96 |
Annual Sum or Average | 6358.33 | 22.39 | 2714.50 | 22.71 | 1387.17 | 22.84 |
Minimum of Months | 318.00 | 21.79 | 4.50 | 21.79 | 3.67 | 21.80 |
Maximum of Months | 733.67 | 23.43 | 544.33 | 23.45 | 288.17 | 23.54 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 709.00 | 22.05 | 19.83 | 22.09 | 4.67 | 22.11 |
February | 589.83 | 22.19 | 38.00 | 22.28 | 11.17 | 22.30 |
March | 515.33 | 22.42 | 114.83 | 22.63 | 15.67 | 22.66 |
April | 351.17 | 22.59 | 254.17 | 23.01 | 61.33 | 23.07 |
May | 280.50 | 23.20 | 491.17 | 23.36 | 180.67 | 23.43 |
June | 238.17 | 23.69 | 579.83 | 23.54 | 203.83 | 23.62 |
July | 294.50 | 23.82 | 667.33 | 23.57 | 285.17 | 23.64 |
August | 291.83 | 23.87 | 663.67 | 23.59 | 283.83 | 23.67 |
September | 304.67 | 23.33 | 509.50 | 23.43 | 225.33 | 23.50 |
October | 439.17 | 22.49 | 233.83 | 22.85 | 83.33 | 22.94 |
November | 582.83 | 22.38 | 85.00 | 22.52 | 31.33 | 22.57 |
December | 679.17 | 22.20 | 32.33 | 22.26 | 3.83 | 22.27 |
Annual Sum or Average | 5276.17 | 22.64 | 3689.50 | 22.99 | 1390.17 | 23.10 |
Minimum of Months | 238.17 | 22.05 | 19.83 | 22.09 | 3.83 | 22.11 |
Maximum of Months | 709.00 | 23.87 | 667.33 | 23.59 | 285.17 | 23.67 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 465.50 | 23.99 | 739.33 | 23.99 | 465.50 | 23.99 |
February | 442.00 | 23.99 | 660.17 | 23.99 | 442.00 | 23.99 |
March | 523.17 | 23.99 | 744.00 | 23.99 | 523.17 | 23.99 |
April | 526.33 | 24.02 | 720.00 | 24.01 | 526.33 | 24.02 |
May | 574.17 | 24.00 | 744.00 | 24.00 | 574.17 | 24.00 |
June | 575.33 | 23.99 | 720.00 | 23.99 | 575.33 | 23.99 |
July | 611.67 | 23.99 | 744.00 | 23.99 | 611.67 | 23.99 |
August | 614.33 | 23.99 | 744.00 | 23.99 | 614.33 | 23.99 |
September | 566.17 | 24.00 | 720.00 | 24.00 | 566.17 | 24.00 |
October | 545.50 | 23.99 | 744.00 | 23.99 | 545.50 | 23.99 |
November | 500.83 | 23.99 | 720.00 | 23.99 | 500.83 | 23.99 |
December | 487.33 | 23.99 | 743.00 | 23.99 | 487.33 | 23.99 |
Annual Sum or Average | 6432.33 | 23.99 | 8742.50 | 23.99 | 6432.33 | 23.99 |
Minimum of Months | 442.00 | 23.99 | 660.17 | 23.99 | 442.00 | 23.99 |
Maximum of Months | 614.33 | 24.02 | 744.00 | 24.01 | 614.33 | 24.02 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.11 | 229.17 | 21.08 | 229.17 | 21.07 |
February | 672.00 | 21.59 | 173.83 | 21.47 | 173.83 | 21.39 |
March | 674.00 | 22.50 | 26.50 | 22.55 | 1.83 | 22.55 |
April | 442.33 | 23.04 | 129.50 | 23.23 | 32.67 | 23.26 |
May | 215.17 | 23.65 | 534.67 | 23.86 | 118.50 | 23.85 |
June | 136.33 | 23.91 | 615.17 | 23.98 | 96.00 | 23.98 |
July | 122.83 | 23.98 | 743.83 | 23.99 | 122.83 | 23.99 |
August | 125.00 | 24.00 | 744.00 | 24.00 | 125.00 | 24.00 |
September | 204.17 | 23.77 | 578.17 | 23.92 | 150.50 | 23.92 |
October | 553.67 | 22.87 | 172.83 | 23.11 | 55.33 | 23.15 |
November | 714.33 | 22.12 | 17.00 | 22.12 | 17.00 | 22.13 |
December | 744.00 | 21.31 | 77.83 | 21.28 | 77.83 | 21.26 |
Annual Sum or Average | 5347.83 | 22.26 | 4042.50 | 22.84 | 1200.50 | 22.83 |
Minimum of Months | 122.83 | 21.11 | 17.00 | 21.08 | 1.83 | 21.07 |
Maximum of Months | 744.00 | 24.00 | 744.00 | 24.00 | 229.17 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.67082 | 30.14847 | -0.0705 | 5.28442 |
February | 672.00000 | 22.16048 | 32.97816 | -0.1817 | 5.93569 |
March | 744.00000 | 21.60856 | 40.02555 | -0.2775 | 6.88246 |
April | 720.00000 | 21.24615 | 51.10960 | -0.3099 | 7.21405 |
May | 744.00000 | 21.51315 | 61.04685 | -1.3359 | 42.22648 |
June | 720.00000 | 22.36384 | 59.44538 | -1.0332 | 27.80032 |
July | 744.00000 | 22.89483 | 61.15539 | -0.8256 | 19.59870 |
August | 744.00000 | 23.45002 | 59.33120 | -0.6321 | 13.61056 |
September | 720.00000 | 23.83952 | 56.74943 | -0.4997 | 10.35163 |
October | 744.00000 | 23.90060 | 47.04823 | 0.37427 | 8.03669 |
November | 720.00000 | 23.91573 | 35.86253 | 0.30019 | 7.06468 |
December | 744.00000 | 23.67301 | 31.51554 | 0.19843 | 6.01750 |
Annual Sum or Average | 8760.00000 | 22.77395 | 47.27892 | -0.3589 | 13.39858 |
Minimum of Months | 672.00000 | 21.24615 | 30.14847 | -1.3359 | 5.28442 |
Maximum of Months | 744.00000 | 23.91573 | 61.15539 | 0.37427 | 42.22648 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.35068 | 31.73481 | -0.4208 | 9.77928 |
February | 672.00000 | 21.63104 | 33.67238 | -0.3086 | 8.67617 |
March | 744.00000 | 22.33742 | 38.33745 | -0.0476 | 6.97787 |
April | 720.00000 | 22.70570 | 47.19053 | 0.11345 | 6.86319 |
May | 744.00000 | 23.25145 | 55.80740 | -0.6373 | 15.05622 |
June | 720.00000 | 23.76175 | 55.64855 | -0.4209 | 9.50292 |
July | 744.00000 | 23.84063 | 59.12979 | -0.3493 | 7.95803 |
August | 744.00000 | 23.95554 | 58.74650 | -0.2891 | 6.89250 |
September | 720.00000 | 23.54963 | 58.46386 | -0.4795 | 11.18696 |
October | 744.00000 | 22.78566 | 50.36872 | 0.16112 | 7.53908 |
November | 720.00000 | 22.14046 | 39.46229 | -0.0947 | 7.02263 |
December | 744.00000 | 21.60918 | 34.71561 | -0.3005 | 8.50920 |
Annual Sum or Average | 8760.00000 | 22.74916 | 47.01324 | -0.2561 | 8.83365 |
Minimum of Months | 672.00000 | 21.35068 | 31.73481 | -0.6373 | 6.86319 |
Maximum of Months | 744.00000 | 23.95554 | 59.12979 | 0.16112 | 15.05622 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.35880 | 32.13200 | -0.3538 | 7.97307 |
February | 672.00000 | 21.64758 | 33.88623 | -0.2635 | 7.14642 |
March | 744.00000 | 22.25358 | 38.85280 | -0.0645 | 5.83455 |
April | 720.00000 | 22.56514 | 47.88764 | 0.07590 | 5.81044 |
May | 744.00000 | 22.89530 | 57.01709 | -0.7723 | 18.32286 |
June | 720.00000 | 23.32099 | 57.01462 | -0.6082 | 13.42309 |
July | 744.00000 | 23.42307 | 60.24361 | -0.5452 | 11.75172 |
August | 744.00000 | 23.54291 | 59.92364 | -0.5010 | 10.63893 |
September | 720.00000 | 23.22846 | 59.46007 | -0.6285 | 13.92744 |
October | 744.00000 | 22.65131 | 50.92027 | 0.11893 | 5.95054 |
November | 720.00000 | 22.18925 | 39.69036 | -0.0773 | 5.74933 |
December | 744.00000 | 21.66932 | 34.89705 | -0.2474 | 6.85680 |
Annual Sum or Average | 8760.00000 | 22.56677 | 47.73692 | -0.3229 | 9.46463 |
Minimum of Months | 672.00000 | 21.35880 | 32.13200 | -0.7723 | 5.74933 |
Maximum of Months | 744.00000 | 23.54291 | 60.24361 | 0.11893 | 18.32286 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99977 | 24.28066 | 0.78955 | 18.99284 |
February | 672.00000 | 23.99991 | 26.14825 | 0.82608 | 20.32628 |
March | 744.00000 | 23.99979 | 31.51065 | 0.90381 | 23.13531 |
April | 720.00000 | 23.99979 | 40.33645 | 0.98518 | 26.27739 |
May | 744.00000 | 24.00049 | 49.46366 | 0.44391 | 10.73404 |
June | 720.00000 | 23.99979 | 50.56205 | 0.48588 | 11.54390 |
July | 744.00000 | 23.99975 | 53.79224 | 0.51708 | 12.05556 |
August | 744.00000 | 23.99983 | 53.80887 | 0.52448 | 12.26129 |
September | 720.00000 | 23.99960 | 52.63112 | 0.47522 | 11.24655 |
October | 744.00000 | 23.99980 | 43.22014 | 1.00022 | 26.81844 |
November | 720.00000 | 23.99985 | 32.16524 | 0.89756 | 22.85842 |
December | 744.00000 | 23.99986 | 27.10359 | 0.83152 | 20.46981 |
Annual Sum or Average | 8760.00000 | 23.99985 | 40.49746 | 0.72267 | 18.04222 |
Minimum of Months | 672.00000 | 23.99960 | 24.28066 | 0.44391 | 10.73404 |
Maximum of Months | 744.00000 | 24.00049 | 53.80887 | 1.00022 | 26.81844 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.32664 | 34.49016 | -0.3218 | 7.80630 |
February | 672.00000 | 21.54413 | 36.38565 | -0.2277 | 7.02503 |
March | 744.00000 | 21.90406 | 41.90704 | -0.0521 | 5.99201 |
April | 720.00000 | 21.96763 | 51.76249 | 0.03819 | 5.85847 |
May | 744.00000 | 22.11125 | 61.71682 | -0.8750 | 22.10509 |
June | 720.00000 | 22.43364 | 62.04131 | -0.7230 | 17.07560 |
July | 744.00000 | 22.58088 | 65.29852 | -0.6342 | 14.41699 |
August | 744.00000 | 22.81723 | 64.60303 | -0.5375 | 11.90067 |
September | 720.00000 | 22.51080 | 64.08939 | -0.6877 | 16.31474 |
October | 744.00000 | 22.21384 | 54.42068 | 0.12599 | 6.41424 |
November | 720.00000 | 21.87896 | 42.70125 | -0.0582 | 6.08975 |
December | 744.00000 | 21.54828 | 37.48570 | -0.2132 | 6.80013 |
Annual Sum or Average | 8760.00000 | 22.07270 | 51.49099 | -0.3481 | 10.67221 |
Minimum of Months | 672.00000 | 21.32664 | 34.49016 | -0.8750 | 5.85847 |
Maximum of Months | 744.00000 | 22.81723 | 65.29852 | 0.12599 | 22.10509 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.79111 | 34.20308 | -0.2235 | 6.58268 |
February | 672.00000 | 22.05183 | 35.94720 | -0.1374 | 6.24966 |
March | 744.00000 | 22.54891 | 41.09832 | 0.03848 | 5.79381 |
April | 720.00000 | 22.72714 | 50.26044 | 0.14896 | 6.17563 |
May | 744.00000 | 22.95258 | 59.57430 | -0.7073 | 16.45671 |
June | 720.00000 | 23.26751 | 59.83281 | -0.5738 | 12.79283 |
July | 744.00000 | 23.35610 | 62.99459 | -0.5125 | 11.19475 |
August | 744.00000 | 23.46361 | 62.62795 | -0.4694 | 10.16349 |
September | 720.00000 | 23.27726 | 61.94975 | -0.5597 | 12.29035 |
October | 744.00000 | 22.90485 | 52.99336 | 0.21709 | 6.60513 |
November | 720.00000 | 22.58376 | 41.70221 | 0.05064 | 5.71478 |
December | 744.00000 | 22.14941 | 36.87881 | -0.1035 | 5.86538 |
Annual Sum or Average | 8760.00000 | 22.75968 | 50.08318 | -0.2368 | 8.84033 |
Minimum of Months | 672.00000 | 21.79111 | 34.20308 | -0.7073 | 5.71478 |
Maximum of Months | 744.00000 | 23.46361 | 62.99459 | 0.21709 | 16.45671 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.82111 | 38.27756 | -0.5852 | 12.83486 |
February | 672.00000 | 21.03396 | 40.27511 | -0.4833 | 11.02085 |
March | 744.00000 | 21.47113 | 43.61186 | -0.2752 | 7.53284 |
April | 720.00000 | 21.63867 | 50.90625 | -0.1479 | 6.45898 |
May | 744.00000 | 21.73721 | 55.07709 | -1.1628 | 34.82501 |
June | 720.00000 | 21.78861 | 53.45412 | -1.0965 | 31.89661 |
July | 744.00000 | 21.79344 | 55.78545 | -1.0639 | 30.45876 |
August | 744.00000 | 21.80218 | 55.03174 | -1.0530 | 30.01268 |
September | 720.00000 | 21.74293 | 56.84745 | -1.1341 | 33.57107 |
October | 744.00000 | 21.53835 | 55.05325 | -0.1713 | 6.57387 |
November | 720.00000 | 21.36636 | 46.14243 | -0.3240 | 8.11279 |
December | 744.00000 | 21.02774 | 42.28450 | -0.4843 | 10.58513 |
Annual Sum or Average | 8760.00000 | 21.48212 | 49.44377 | -0.6665 | 18.70489 |
Minimum of Months | 672.00000 | 20.82111 | 38.27756 | -1.1628 | 6.45898 |
Maximum of Months | 744.00000 | 21.80218 | 56.84745 | -0.1479 | 34.82501 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.58044 | 38.79436 | -0.6663 | 15.02948 |
February | 672.00000 | 20.88926 | 40.61327 | -0.5439 | 12.46009 |
March | 744.00000 | 21.51516 | 44.03312 | -0.2911 | 7.92510 |
April | 720.00000 | 21.96973 | 50.96334 | -0.0920 | 6.62285 |
May | 744.00000 | 22.20844 | 55.50064 | -1.0279 | 29.38661 |
June | 720.00000 | 22.14388 | 53.98661 | -0.9896 | 27.81541 |
July | 744.00000 | 22.13276 | 56.80378 | -0.9597 | 26.55734 |
August | 744.00000 | 22.05421 | 56.23817 | -0.9845 | 27.43512 |
September | 720.00000 | 22.12186 | 58.32649 | -1.0352 | 29.53081 |
October | 744.00000 | 21.69290 | 56.13306 | -0.1622 | 6.83958 |
November | 720.00000 | 21.20039 | 47.01941 | -0.3917 | 9.13202 |
December | 744.00000 | 20.74433 | 43.03359 | -0.5752 | 12.60985 |
Annual Sum or Average | 8760.00000 | 21.60754 | 50.17174 | -0.6443 | 17.64710 |
Minimum of Months | 672.00000 | 20.58044 | 38.79436 | -1.0352 | 6.62285 |
Maximum of Months | 744.00000 | 22.20844 | 58.32649 | -0.0920 | 29.53081 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.86080 | 37.17409 | -0.5553 | 11.93802 |
February | 672.00000 | 21.07236 | 38.63109 | -0.4745 | 10.35150 |
March | 744.00000 | 21.43172 | 42.33941 | -0.3255 | 7.73860 |
April | 720.00000 | 21.81921 | 49.32807 | -0.1687 | 6.41157 |
May | 744.00000 | 22.05957 | 55.29842 | -1.1480 | 33.86299 |
June | 720.00000 | 22.04057 | 55.24840 | -1.1223 | 32.91327 |
July | 744.00000 | 22.05321 | 58.13875 | -1.0925 | 31.68608 |
August | 744.00000 | 21.97175 | 57.92003 | -1.1247 | 32.99777 |
September | 720.00000 | 22.02782 | 58.01446 | -1.1424 | 33.66703 |
October | 744.00000 | 21.61582 | 54.01133 | -0.2029 | 6.42809 |
November | 720.00000 | 21.28946 | 44.57493 | -0.3643 | 8.25307 |
December | 744.00000 | 21.02304 | 41.10518 | -0.4776 | 10.15208 |
Annual Sum or Average | 8760.00000 | 21.60776 | 49.37603 | -0.6848 | 18.92083 |
Minimum of Months | 672.00000 | 20.86080 | 37.17409 | -1.1480 | 6.41157 |
Maximum of Months | 744.00000 | 22.05957 | 58.13875 | -0.1687 | 33.86299 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.85172 | 38.19701 | -0.5790 | 12.66432 |
February | 672.00000 | 21.08289 | 40.17017 | -0.4691 | 10.75127 |
March | 744.00000 | 21.54400 | 43.36384 | -0.2639 | 7.43640 |
April | 720.00000 | 21.70898 | 50.32468 | -0.1352 | 6.41429 |
May | 744.00000 | 21.77512 | 54.09686 | -1.1485 | 34.24358 |
June | 720.00000 | 21.80875 | 52.86260 | -1.0851 | 31.47699 |
July | 744.00000 | 21.80465 | 55.08032 | -1.0543 | 30.13293 |
August | 744.00000 | 21.81039 | 54.68060 | -1.0489 | 29.90391 |
September | 720.00000 | 21.75898 | 56.27720 | -1.1291 | 33.39443 |
October | 744.00000 | 21.58247 | 54.31784 | -0.1652 | 6.56009 |
November | 720.00000 | 21.41250 | 45.98549 | -0.3154 | 7.95644 |
December | 744.00000 | 21.06136 | 42.16134 | -0.4761 | 10.36167 |
Annual Sum or Average | 8760.00000 | 21.51868 | 49.00574 | -0.6572 | 18.48956 |
Minimum of Months | 672.00000 | 20.85172 | 38.19701 | -1.1485 | 6.41429 |
Maximum of Months | 744.00000 | 21.81039 | 56.27720 | -0.1352 | 34.24358 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.59311 | 38.73345 | -0.6637 | 14.94999 |
February | 672.00000 | 20.91636 | 40.52717 | -0.5338 | 12.17199 |
March | 744.00000 | 21.51267 | 43.95368 | -0.2951 | 7.74270 |
April | 720.00000 | 21.99594 | 50.48584 | -0.0884 | 6.40896 |
May | 744.00000 | 22.25840 | 54.59886 | -1.0102 | 28.80713 |
June | 720.00000 | 22.23647 | 53.39015 | -0.9572 | 27.23617 |
July | 744.00000 | 22.22419 | 56.05986 | -0.9265 | 26.15616 |
August | 744.00000 | 22.10678 | 55.85482 | -0.9675 | 27.26736 |
September | 720.00000 | 22.17390 | 57.53716 | -1.0207 | 29.21513 |
October | 744.00000 | 21.70192 | 55.48688 | -0.1635 | 6.67948 |
November | 720.00000 | 21.16653 | 47.02402 | -0.3993 | 9.03911 |
December | 744.00000 | 20.75305 | 42.96265 | -0.5717 | 12.45730 |
Annual Sum or Average | 8760.00000 | 21.63972 | 49.76721 | -0.6341 | 17.37989 |
Minimum of Months | 672.00000 | 20.59311 | 38.73345 | -1.0207 | 6.40896 |
Maximum of Months | 744.00000 | 22.25840 | 57.53716 | -0.0884 | 29.21513 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.69509 | 39.19200 | -0.6492 | 14.60369 |
February | 672.00000 | 20.93473 | 41.25279 | -0.5322 | 12.32394 |
March | 744.00000 | 21.40591 | 44.53455 | -0.3021 | 8.09082 |
April | 720.00000 | 21.60525 | 52.08641 | -0.1571 | 6.73299 |
May | 744.00000 | 21.72536 | 56.10289 | -1.1590 | 34.86523 |
June | 720.00000 | 21.78489 | 54.08085 | -1.0876 | 31.72057 |
July | 744.00000 | 21.78943 | 56.66332 | -1.0522 | 30.16697 |
August | 744.00000 | 21.80039 | 55.71165 | -1.0416 | 29.72757 |
September | 720.00000 | 21.72383 | 58.31373 | -1.1380 | 33.92935 |
October | 744.00000 | 21.47556 | 56.65103 | -0.1939 | 6.95508 |
November | 720.00000 | 21.28811 | 47.28286 | -0.3603 | 8.85439 |
December | 744.00000 | 20.90236 | 43.42295 | -0.5407 | 11.95794 |
Annual Sum or Average | 8760.00000 | 21.42973 | 50.48938 | -0.6857 | 19.20432 |
Minimum of Months | 672.00000 | 20.69509 | 39.19200 | -1.1590 | 6.73299 |
Maximum of Months | 744.00000 | 21.80039 | 58.31373 | -0.1571 | 34.86523 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.50189 | 39.68844 | -0.7224 | 16.74854 |
February | 672.00000 | 20.81444 | 41.57882 | -0.5897 | 13.75747 |
March | 744.00000 | 21.44416 | 44.92618 | -0.3199 | 8.59226 |
April | 720.00000 | 21.96035 | 51.91120 | -0.0947 | 7.01166 |
May | 744.00000 | 22.20333 | 56.13798 | -1.0192 | 29.46289 |
June | 720.00000 | 22.11844 | 54.45422 | -0.9849 | 27.81358 |
July | 744.00000 | 22.10212 | 57.49936 | -0.9541 | 26.45723 |
August | 744.00000 | 22.02954 | 56.82743 | -0.9786 | 27.30396 |
September | 720.00000 | 22.07444 | 59.58856 | -1.0457 | 30.20296 |
October | 744.00000 | 21.61542 | 57.71543 | -0.1885 | 7.34571 |
November | 720.00000 | 21.09825 | 48.20783 | -0.4354 | 10.10234 |
December | 744.00000 | 20.62511 | 44.19455 | -0.6324 | 14.20017 |
Annual Sum or Average | 8760.00000 | 21.55210 | 51.11160 | -0.6647 | 18.28098 |
Minimum of Months | 672.00000 | 20.50189 | 39.68844 | -1.0457 | 7.01166 |
Maximum of Months | 744.00000 | 22.20333 | 59.58856 | -0.0947 | 30.20296 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.21157 | 39.02087 | -0.4562 | 10.64997 |
February | 672.00000 | 21.32565 | 40.73168 | -0.3860 | 9.42637 |
March | 744.00000 | 21.57526 | 43.42823 | -0.2464 | 7.40568 |
April | 720.00000 | 21.65961 | 51.04049 | -0.1619 | 6.64767 |
May | 744.00000 | 21.72590 | 55.96154 | -1.2036 | 36.79105 |
June | 720.00000 | 21.77995 | 54.79855 | -1.1474 | 34.20845 |
July | 744.00000 | 21.78557 | 57.04037 | -1.1121 | 32.58251 |
August | 744.00000 | 21.80082 | 55.79854 | -1.0917 | 31.75817 |
September | 720.00000 | 21.74175 | 56.80237 | -1.1563 | 34.70974 |
October | 744.00000 | 21.61900 | 53.92881 | -0.1469 | 6.57711 |
November | 720.00000 | 21.58169 | 45.52660 | -0.2420 | 7.42201 |
December | 744.00000 | 21.37047 | 42.38860 | -0.3633 | 8.90920 |
Annual Sum or Average | 8760.00000 | 21.59933 | 49.75371 | -0.6446 | 18.98208 |
Minimum of Months | 672.00000 | 21.21157 | 39.02087 | -1.2036 | 6.57711 |
Maximum of Months | 744.00000 | 21.80082 | 57.04037 | -0.1469 | 36.79105 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.80770 | 33.90291 | -0.1883 | 6.56361 |
February | 672.00000 | 22.02372 | 35.65585 | -0.0985 | 6.32104 |
March | 744.00000 | 22.40859 | 41.04957 | 0.07429 | 6.11928 |
April | 720.00000 | 22.67264 | 50.06467 | 0.22379 | 6.90280 |
May | 744.00000 | 22.89343 | 59.32028 | -0.5808 | 13.06987 |
June | 720.00000 | 23.07822 | 59.88733 | -0.4816 | 10.78602 |
July | 744.00000 | 23.11510 | 63.17574 | -0.4378 | 9.82105 |
August | 744.00000 | 23.12579 | 63.17284 | -0.4341 | 9.79864 |
September | 720.00000 | 22.90691 | 62.63982 | -0.5539 | 12.44301 |
October | 744.00000 | 22.52205 | 53.59686 | 0.19499 | 6.64384 |
November | 720.00000 | 22.22867 | 42.02369 | 0.01741 | 6.02072 |
December | 744.00000 | 21.96302 | 36.85767 | -0.1111 | 6.17379 |
Annual Sum or Average | 8760.00000 | 22.56483 | 50.19228 | -0.1988 | 8.39852 |
Minimum of Months | 672.00000 | 21.80770 | 33.90291 | -0.5808 | 6.02072 |
Maximum of Months | 744.00000 | 23.12579 | 63.17574 | 0.22379 | 13.06987 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.11658 | 33.46370 | -0.0820 | 6.11122 |
February | 672.00000 | 22.34977 | 35.14351 | 0.00881 | 6.21478 |
March | 744.00000 | 22.73381 | 40.44213 | 0.17495 | 6.56436 |
April | 720.00000 | 22.95489 | 49.36864 | 0.31091 | 7.78982 |
May | 744.00000 | 23.14162 | 58.53472 | -0.4715 | 10.51917 |
June | 720.00000 | 23.30687 | 59.12263 | -0.3789 | 8.77066 |
July | 744.00000 | 23.33460 | 62.37464 | -0.3380 | 8.02972 |
August | 744.00000 | 23.33948 | 62.38279 | -0.3364 | 8.04604 |
September | 720.00000 | 23.14819 | 61.82674 | -0.4478 | 10.07694 |
October | 744.00000 | 22.81156 | 52.82698 | 0.28428 | 7.46064 |
November | 720.00000 | 22.57339 | 41.36734 | 0.12486 | 6.32065 |
December | 744.00000 | 22.31136 | 36.30098 | 0.00227 | 5.98861 |
Annual Sum or Average | 8760.00000 | 22.84590 | 49.50872 | -0.0966 | 7.66320 |
Minimum of Months | 672.00000 | 22.11658 | 33.46370 | -0.4715 | 5.98861 |
Maximum of Months | 744.00000 | 23.33948 | 62.38279 | 0.31091 | 10.51917 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99092 | 32.36310 | 0.95688 | 25.81279 |
February | 672.00000 | 23.99121 | 33.92180 | 1.00509 | 27.88730 |
March | 744.00000 | 23.99346 | 38.72534 | 1.10152 | 32.03543 |
April | 720.00000 | 24.01234 | 47.20193 | 1.20286 | 36.74522 |
May | 744.00000 | 23.99903 | 55.98091 | 0.74578 | 20.19068 |
June | 720.00000 | 23.99480 | 56.95547 | 0.79722 | 21.73976 |
July | 744.00000 | 23.99199 | 60.06441 | 0.83243 | 22.71492 |
August | 744.00000 | 23.99199 | 60.04334 | 0.83296 | 22.66569 |
September | 720.00000 | 23.99649 | 59.00491 | 0.76496 | 20.45990 |
October | 744.00000 | 23.99165 | 50.06225 | 1.19523 | 36.18978 |
November | 720.00000 | 23.99114 | 39.48835 | 1.07849 | 30.96345 |
December | 744.00000 | 23.99093 | 34.84439 | 1.00335 | 27.74405 |
Annual Sum or Average | 8760.00000 | 23.99465 | 47.46281 | 0.95935 | 27.08506 |
Minimum of Months | 672.00000 | 23.99092 | 32.36310 | 0.74578 | 20.19068 |
Maximum of Months | 744.00000 | 24.01234 | 60.06441 | 1.20286 | 36.74522 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00300 | 29.50468 | -0.5057 | 10.50646 |
February | 672.00000 | 21.03856 | 31.79923 | -0.4629 | 9.74062 |
March | 744.00000 | 21.21666 | 37.81013 | -0.3487 | 7.96301 |
April | 720.00000 | 21.53674 | 47.35345 | -0.2052 | 6.37409 |
May | 744.00000 | 21.99771 | 56.83503 | -1.1202 | 31.71526 |
June | 720.00000 | 22.60208 | 56.54943 | -0.9046 | 22.59655 |
July | 744.00000 | 22.80031 | 59.98004 | -0.8114 | 19.05779 |
August | 744.00000 | 22.88980 | 59.90173 | -0.7798 | 17.89685 |
September | 720.00000 | 22.40820 | 59.43873 | -0.9556 | 24.52637 |
October | 744.00000 | 21.64724 | 50.67569 | -0.1554 | 5.91293 |
November | 720.00000 | 21.20920 | 38.59994 | -0.3458 | 7.88149 |
December | 744.00000 | 21.03423 | 32.90438 | -0.4475 | 9.43748 |
Annual Sum or Average | 8760.00000 | 21.78637 | 46.86188 | -0.5877 | 14.49665 |
Minimum of Months | 672.00000 | 21.00300 | 29.50468 | -1.1202 | 5.91293 |
Maximum of Months | 744.00000 | 22.88980 | 59.98004 | -0.1554 | 31.71526 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00829 | 33.77537 | -0.4906 | 10.15020 |
February | 672.00000 | 21.13559 | 35.90631 | -0.4369 | 9.22837 |
March | 744.00000 | 21.55405 | 41.37330 | -0.2823 | 7.09808 |
April | 720.00000 | 22.11906 | 50.05661 | -0.0865 | 5.67605 |
May | 744.00000 | 22.57259 | 59.25612 | -0.9706 | 25.16107 |
June | 720.00000 | 23.15519 | 58.97992 | -0.7636 | 17.56236 |
July | 744.00000 | 23.39078 | 62.01646 | -0.6589 | 14.28551 |
August | 744.00000 | 23.44930 | 61.99124 | -0.6384 | 13.62779 |
September | 720.00000 | 22.92796 | 61.85030 | -0.8260 | 19.63498 |
October | 744.00000 | 22.00115 | 53.92921 | -0.0930 | 5.67585 |
November | 720.00000 | 21.29804 | 42.65641 | -0.3417 | 7.73837 |
December | 744.00000 | 21.04855 | 37.11043 | -0.4490 | 9.42857 |
Annual Sum or Average | 8760.00000 | 22.14403 | 49.98545 | -0.5037 | 12.12325 |
Minimum of Months | 672.00000 | 21.00829 | 33.77537 | -0.9706 | 5.67585 |
Maximum of Months | 744.00000 | 23.44930 | 62.01646 | -0.0865 | 25.16107 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.10654 | 33.27499 | -0.4735 | 9.99195 |
February | 672.00000 | 21.58939 | 34.83101 | -0.3316 | 8.29196 |
March | 744.00000 | 22.61878 | 39.01109 | -0.0280 | 6.11141 |
April | 720.00000 | 23.37025 | 46.56257 | 0.21663 | 6.85257 |
May | 744.00000 | 23.86583 | 54.59240 | -0.5141 | 10.86111 |
June | 720.00000 | 23.97901 | 54.71555 | -0.4448 | 9.27887 |
July | 744.00000 | 23.99251 | 57.95309 | -0.4072 | 8.47297 |
August | 744.00000 | 23.99951 | 57.84291 | -0.4013 | 8.36432 |
September | 720.00000 | 23.90175 | 57.76524 | -0.4738 | 9.88904 |
October | 744.00000 | 23.12916 | 50.64800 | 0.17839 | 6.67547 |
November | 720.00000 | 22.13033 | 40.63221 | -0.1436 | 6.42291 |
December | 744.00000 | 21.30957 | 36.33163 | -0.3854 | 8.72315 |
Annual Sum or Average | 8760.00000 | 22.92225 | 47.08168 | -0.2675 | 8.33065 |
Minimum of Months | 672.00000 | 21.10654 | 33.27499 | -0.5141 | 6.11141 |
Maximum of Months | 744.00000 | 23.99951 | 57.95309 | 0.21663 | 10.86111 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.70899 | 33.45204 | -0.3279 | 8.14530 |
February | 672.00000 | 22.37756 | 36.12420 | -0.1535 | 7.26273 |
March | 744.00000 | 23.50658 | 39.80996 | 0.14365 | 5.93997 |
April | 720.00000 | 23.85942 | 45.69250 | 0.28009 | 6.95878 |
May | 744.00000 | 23.99817 | 52.88819 | -0.5411 | 11.24827 |
June | 720.00000 | 23.99987 | 53.38900 | -0.4940 | 10.19732 |
July | 744.00000 | 23.99983 | 57.35581 | -0.4542 | 9.31250 |
August | 744.00000 | 23.99981 | 57.41742 | -0.4477 | 9.18865 |
September | 720.00000 | 23.99988 | 55.82732 | -0.4903 | 10.08349 |
October | 744.00000 | 23.89132 | 49.10576 | 0.32011 | 7.31128 |
November | 720.00000 | 23.49383 | 40.54026 | 0.14899 | 6.05773 |
December | 744.00000 | 22.58150 | 37.26448 | -0.0940 | 5.94738 |
Annual Sum or Average | 8760.00000 | 23.45598 | 46.63302 | -0.1764 | 8.14293 |
Minimum of Months | 672.00000 | 21.70899 | 33.45204 | -0.5411 | 5.93997 |
Maximum of Months | 744.00000 | 23.99988 | 57.41742 | 0.32011 | 11.24827 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.537918E+10 | 62416.83 | 19-JAN-22:53 | 367.29 | 0.157712E+11 | 0.00 | 0.211504E+11 | 1.52 | 3.12 | 05-JAN-10:00 | 0.00 | 0.00 |
February | 0.169550E+11 | 96427.24 | 26-FEB-16:11 | 386.68 | 0.481102E+11 | 0.00 | 0.650652E+11 | 1.74 | 3.45 | 26-FEB-16:11 | 0.00 | 0.00 |
March | 0.491078E+11 | 118539.62 | 30-MAR-15:11 | 602.51 | 0.141758E+12 | 0.00 | 0.190866E+12 | 2.41 | 3.63 | 28-MAR-18:03 | 0.00 | 0.00 |
April | 0.935551E+11 | 124523.86 | 12-APR-15:14 | 686.67 | 0.275627E+12 | 0.00 | 0.369182E+12 | 2.83 | 3.75 | 02-APR-21:52 | 0.00 | 0.00 |
May | 0.164389E+12 | 143617.32 | 30-MAY-18:03 | 743.00 | 0.506527E+12 | 0.00 | 0.670916E+12 | 3.03 | 4.03 | 30-MAY-21:51 | 0.00 | 0.00 |
June | 0.238355E+12 | 169536.18 | 28-JUN-18:03 | 720.00 | 0.769456E+12 | 0.00 | 0.100781E+13 | 3.20 | 4.15 | 22-JUN-21:52 | 0.00 | 0.00 |
July | 0.291109E+12 | 186943.39 | 08-JUL-15:13 | 744.00 | 0.964166E+12 | 0.00 | 0.125528E+13 | 3.33 | 4.15 | 27-JUL-21:54 | 0.00 | 0.00 |
August | 0.305131E+12 | 182513.18 | 18-AUG-18:05 | 744.00 | 0.102510E+13 | 0.00 | 0.133024E+13 | 3.37 | 4.11 | 07-AUG-21:52 | 0.00 | 0.00 |
September | 0.202624E+12 | 164305.60 | 07-SEP-15:13 | 719.00 | 0.665134E+12 | 0.00 | 0.867759E+12 | 3.20 | 4.07 | 27-SEP-21:53 | 0.00 | 0.00 |
October | 0.899474E+11 | 141562.94 | 18-OCT-21:52 | 675.22 | 0.282446E+12 | 0.00 | 0.372394E+12 | 2.79 | 4.06 | 18-OCT-21:52 | 0.00 | 0.00 |
November | 0.371690E+11 | 107475.08 | 05-NOV-15:13 | 533.52 | 0.108257E+12 | 0.00 | 0.145426E+12 | 2.23 | 3.74 | 27-NOV-22:53 | 0.00 | 0.00 |
December | 0.102006E+11 | 67654.07 | 12-DEC-16:13 | 351.13 | 0.294530E+11 | 0.00 | 0.396536E+11 | 1.44 | 3.14 | 13-DEC-09:55 | 0.00 | 0.00 |
Annual Sum or Average | 0.150392E+13 | 7273.02 | 0.483181E+13 | 0.00 | 0.633573E+13 | 2.60 | 0.00 | 0.00 | ||||
Minimum of Months | 0.537918E+10 | 62416.83 | 351.13 | 0.157712E+11 | 0.00 | 0.211504E+11 | 1.44 | 3.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.305131E+12 | 186943.39 | 744.00 | 0.102510E+13 | 0.00 | 0.133024E+13 | 3.37 | 4.15 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.121285E+12 | 0.00 | 741.58 | 161895.96 | 03-JAN-09:02 | 0.00 | 37.86 | 59.89 | 0.48 | 0.00 | 0.11 | 0.40 | 03-JAN-09:02 |
February | 0.745291E+11 | 0.00 | 618.65 | 151662.49 | 14-FEB-09:02 | 0.00 | 40.59 | 58.95 | 0.33 | 0.00 | 0.08 | 0.37 | 14-FEB-09:02 |
March | 0.248928E+11 | 0.00 | 487.45 | 129238.21 | 18-MAR-08:03 | 0.00 | 41.45 | 54.13 | 0.10 | 0.00 | 0.02 | 0.32 | 18-MAR-08:03 |
April | 0.115657E+11 | 0.00 | 393.44 | 117218.89 | 06-APR-08:03 | 0.00 | 36.40 | 49.14 | 0.04 | 0.00 | 0.01 | 0.29 | 06-APR-08:03 |
May | 0.661338E+09 | 0.00 | 103.82 | 51438.91 | 13-MAY-15:11 | 0.00 | 33.45 | 37.19 | 0.00 | 0.00 | 0.00 | 0.13 | 13-MAY-15:11 |
June | 0.132231E+09 | 0.00 | 20.76 | 29449.94 | 03-JUN-21:56 | 0.00 | 36.93 | 37.70 | 0.00 | 0.00 | 0.00 | 0.07 | 03-JUN-21:56 |
July | 22362112.58 | 0.00 | 9.79 | 12188.86 | 28-JUL-21:58 | 0.00 | 41.86 | 42.11 | 0.00 | 0.00 | 0.00 | 0.03 | 28-JUL-21:58 |
August | 12444657.14 | 0.00 | 2.33 | 10715.67 | 30-AUG-21:56 | 0.00 | 43.13 | 43.18 | 0.00 | 0.00 | 0.00 | 0.03 | 30-AUG-21:56 |
September | 0.318453E+09 | 0.00 | 56.77 | 28224.62 | 21-SEP-08:54 | 0.00 | 40.75 | 42.22 | 0.00 | 0.00 | 0.00 | 0.07 | 21-SEP-08:54 |
October | 0.900867E+10 | 0.00 | 327.51 | 105650.49 | 31-OCT-08:03 | 0.00 | 45.08 | 52.35 | 0.04 | 0.00 | 0.01 | 0.26 | 31-OCT-08:03 |
November | 0.394239E+11 | 0.00 | 545.67 | 127928.71 | 22-NOV-09:03 | 0.00 | 43.60 | 56.93 | 0.17 | 0.00 | 0.04 | 0.31 | 22-NOV-09:03 |
December | 0.929005E+11 | 0.00 | 720.58 | 156317.01 | 21-DEC-09:02 | 0.00 | 38.85 | 59.63 | 0.37 | 0.00 | 0.08 | 0.38 | 21-DEC-09:02 |
Annual Sum or Average | 0.374752E+12 | 0.00 | 4028.36 | 0.00 | 40.00 | 49.41 | 0.13 | 0.00 | 0.03 | ||||
Minimum of Months | 12444657.14 | 0.00 | 2.33 | 10715.67 | 0.00 | 33.45 | 37.19 | 0.00 | 0.00 | 0.00 | 0.03 | ||
Maximum of Months | 0.121285E+12 | 0.00 | 741.58 | 161895.96 | 0.00 | 45.08 | 59.89 | 0.48 | 0.00 | 0.11 | 0.40 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.963208E+10 | 0.00 | 236.06 | 0.806135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142958.75 | 19-JAN-21:00 | 101451.48 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.323884E+11 | 0.00 | 220.91 | 0.318418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162866.96 | 28-FEB-17:00 | 162866.96 | 28-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.945528E+11 | 0.00 | 342.50 | 0.912379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 239424.38 | 30-MAR-15:17 | 239424.38 | 30-MAR-15:17 | 0.00 | 0.00 | 0.00 |
April | 0.194542E+12 | 0.00 | 499.67 | 0.171326E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 257776.52 | 21-APR-17:15 | 254460.37 | 17-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.371113E+12 | 0.00 | 686.17 | 0.279065E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 342601.49 | 30-MAY-21:10 | 274384.36 | 17-MAY-18:20 | 0.00 | 0.00 | 0.00 |
June | 0.576672E+12 | 0.00 | 702.17 | 0.392681E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 399894.88 | 26-JUN-18:10 | 291016.17 | 10-JUN-18:05 | 0.00 | 0.00 | 0.00 |
July | 0.735826E+12 | 0.00 | 744.00 | 0.445863E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 406073.05 | 18-JUL-19:50 | 256031.84 | 08-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.784141E+12 | 0.00 | 744.00 | 0.467398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 471846.57 | 23-AUG-21:00 | 254672.61 | 02-AUG-18:10 | 0.00 | 0.00 | 0.00 |
September | 0.503292E+12 | 0.00 | 698.00 | 0.335634E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 403800.35 | 27-SEP-18:07 | 236558.30 | 07-SEP-18:10 | 0.00 | 0.00 | 0.00 |
October | 0.201925E+12 | 0.00 | 422.67 | 0.144606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 430522.67 | 18-OCT-19:40 | 209836.94 | 11-OCT-16:00 | 0.00 | 0.00 | 0.00 |
November | 0.730198E+11 | 0.00 | 272.03 | 0.603285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 248878.09 | 27-NOV-19:05 | 160239.05 | 27-NOV-19:10 | 0.00 | 0.00 | 0.00 |
December | 0.163251E+11 | 0.00 | 138.38 | 0.138300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 186465.42 | 13-DEC-11:35 | 132686.23 | 12-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.359343E+13 | 0.00 | 5706.54 | 0.244187E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.963208E+10 | 0.00 | 138.38 | 0.806135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142958.75 | 101451.48 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.784141E+12 | 0.00 | 744.00 | 0.467398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 471846.57 | 291016.17 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.662235E+09 | 0.00 | 29.17 | 0.499543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13220.25 | 19-JAN-22:53 | 12205.06 | 31-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.183268E+10 | 0.00 | 83.00 | 0.181192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16177.52 | 28-FEB-16:12 | 16177.52 | 28-FEB-16:12 | 0.00 | 0.00 | 0.00 |
March | 0.676350E+10 | 0.00 | 233.67 | 0.617179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22768.58 | 28-MAR-15:11 | 18082.02 | 30-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.136285E+11 | 0.00 | 357.67 | 0.108963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28889.99 | 30-APR-15:13 | 18440.45 | 17-APR-15:12 | 0.00 | 0.00 | 0.00 |
May | 0.290408E+11 | 0.00 | 515.50 | 0.191737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39091.40 | 30-MAY-21:50 | 19094.27 | 19-MAY-15:12 | 0.00 | 0.00 | 0.00 |
June | 0.432391E+11 | 0.00 | 533.67 | 0.268732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45326.50 | 29-JUN-08:03 | 20526.96 | 06-JUN-15:12 | 0.00 | 0.00 | 0.00 |
July | 0.542752E+11 | 0.00 | 568.33 | 0.303240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49419.14 | 26-JUL-08:03 | 21490.91 | 08-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.557534E+11 | 0.00 | 568.33 | 0.314557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47641.65 | 11-AUG-08:03 | 20876.15 | 01-AUG-15:12 | 0.00 | 0.00 | 0.00 |
September | 0.387569E+11 | 0.00 | 531.00 | 0.234479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45948.22 | 17-SEP-08:03 | 19669.55 | 07-SEP-15:12 | 0.00 | 0.00 | 0.00 |
October | 0.155261E+11 | 0.00 | 294.00 | 0.952863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43943.87 | 18-OCT-21:52 | 18698.13 | 10-OCT-15:12 | 0.00 | 0.00 | 0.00 |
November | 0.542164E+10 | 0.00 | 161.83 | 0.391178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27191.71 | 19-NOV-24:00 | 16605.39 | 05-NOV-15:12 | 0.00 | 0.00 | 0.00 |
December | 0.111084E+10 | 0.00 | 48.50 | 0.884764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19411.65 | 12-DEC-13:30 | 14602.71 | 12-DEC-16:13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266011E+12 | 0.00 | 3924.67 | 0.164979E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.662235E+09 | 0.00 | 29.17 | 0.499543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13220.25 | 12205.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.557534E+11 | 0.00 | 568.33 | 0.314557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49419.14 | 21490.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 81089071.17 | 0.00 | 22.87 | 76578426.92 | 0.00 | 0.00 | 0.00 | 0.00 | 13883.73 | 28-JAN-16:11 | 13883.73 | 28-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.485075E+09 | 0.00 | 102.05 | 0.419468E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13899.02 | 28-FEB-19:01 | 13899.02 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.207768E+10 | 0.00 | 326.96 | 0.133154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14362.13 | 28-MAR-15:11 | 13895.40 | 25-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.401932E+10 | 0.00 | 522.35 | 0.215225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15017.37 | 02-APR-15:11 | 13896.31 | 09-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.644678E+10 | 0.00 | 658.36 | 0.323400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15339.43 | 27-MAY-08:62 | 13896.84 | 09-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.903191E+10 | 0.00 | 678.73 | 0.502052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16139.10 | 29-JUN-08:62 | 12364.12 | 15-JUN-15:12 | 0.00 | 0.00 | 0.00 |
July | 0.105136E+11 | 0.00 | 701.22 | 0.595931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16896.90 | 27-JUL-08:61 | 12419.21 | 26-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.111451E+11 | 0.00 | 710.73 | 0.637252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16516.45 | 29-AUG-08:62 | 12475.86 | 20-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.717685E+10 | 0.00 | 640.70 | 0.358195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16455.73 | 17-SEP-08:62 | 12513.99 | 10-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.328738E+10 | 0.00 | 451.05 | 0.156829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15985.05 | 18-OCT-08:62 | 13406.12 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.945786E+09 | 0.00 | 212.44 | 0.550300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15192.75 | 04-NOV-15:12 | 13897.50 | 18-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.227682E+09 | 0.00 | 62.05 | 0.145288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13894.44 | 07-DEC-16:11 | 13894.44 | 07-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.554383E+11 | 0.00 | 5089.52 | 0.304120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 81089071.17 | 0.00 | 22.87 | 76578426.92 | 0.00 | 0.00 | 0.00 | 0.00 | 13883.73 | 12364.12 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.111451E+11 | 0.00 | 710.73 | 0.637252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16896.90 | 13899.02 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2902106.93 | 0.00 | 1.97 | 1910726.47 | 0.00 | 0.00 | 0.00 | 0.00 | 2076.05 | 16-JAN-16:13 | 2076.05 | 16-JAN-16:13 | 0.00 | 0.00 | 0.00 |
February | 71714324.00 | 0.00 | 31.06 | 50750388.33 | 0.00 | 0.00 | 0.00 | 0.00 | 12704.15 | 20-FEB-19:21 | 12704.15 | 20-FEB-19:21 | 0.00 | 0.00 | 0.00 |
March | 0.834680E+09 | 0.00 | 169.97 | 0.429326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14063.20 | 28-MAR-18:01 | 13738.98 | 13-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.250084E+10 | 0.00 | 373.69 | 0.120691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15120.54 | 02-APR-15:11 | 14303.46 | 26-APR-18:41 | 0.00 | 0.00 | 0.00 |
May | 0.501023E+10 | 0.00 | 489.94 | 0.255562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16100.63 | 07-MAY-17:41 | 14286.07 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.818459E+10 | 0.00 | 563.32 | 0.479535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17155.28 | 26-JUN-08:21 | 12270.65 | 03-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.953962E+10 | 0.00 | 588.34 | 0.566797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17214.14 | 08-JUL-07:51 | 12663.26 | 02-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.994398E+10 | 0.00 | 619.35 | 0.576644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18399.16 | 20-AUG-07:52 | 13179.75 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.537090E+10 | 0.00 | 484.67 | 0.263702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16602.14 | 17-SEP-08:52 | 13260.22 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.143180E+10 | 0.00 | 254.71 | 0.544914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16039.17 | 18-OCT-21:52 | 12826.03 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.128466E+09 | 0.00 | 62.92 | 56316970.07 | 0.00 | 0.00 | 0.00 | 0.00 | 14374.66 | 05-NOV-15:12 | 10766.36 | 05-NOV-15:12 | 0.00 | 0.00 | 0.00 |
December | 15316954.87 | 0.00 | 8.52 | 10618591.01 | 0.00 | 0.00 | 0.00 | 0.00 | 11327.62 | 07-DEC-16:11 | 11327.62 | 07-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.430351E+11 | 0.00 | 3648.45 | 0.237231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2902106.93 | 0.00 | 1.97 | 1910726.47 | 0.00 | 0.00 | 0.00 | 0.00 | 2076.05 | 2076.05 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.994398E+10 | 0.00 | 619.35 | 0.576644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18399.16 | 14303.46 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.230854E+09 | 0.00 | 19.42 | 0.165350E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13833.19 | 29-JAN-16:10 | 13833.19 | 29-JAN-16:10 | 0.00 | 0.00 | 0.00 |
February | 0.397750E+10 | 0.00 | 102.04 | 0.391747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28033.74 | 26-FEB-14:50 | 28033.74 | 26-FEB-14:50 | 0.00 | 0.00 | 0.00 |
March | 0.134770E+11 | 0.00 | 388.78 | 0.891251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30773.32 | 30-MAR-13:30 | 27022.17 | 13-MAR-16:10 | 0.00 | 0.00 | 0.00 |
April | 0.174335E+11 | 0.00 | 509.68 | 0.778813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25990.49 | 15-APR-13:50 | 20130.48 | 10-APR-16:10 | 0.00 | 0.00 | 0.00 |
May | 0.252664E+11 | 0.00 | 659.62 | 0.885540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23846.33 | 30-MAY-16:20 | 12389.05 | 19-MAY-17:20 | 0.00 | 0.00 | 0.00 |
June | 0.359940E+11 | 0.00 | 700.83 | 0.140320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27751.34 | 13-JUN-17:15 | 16071.87 | 13-JUN-17:20 | 0.00 | 0.00 | 0.00 |
July | 0.438373E+11 | 0.00 | 736.76 | 0.180560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31121.86 | 14-JUL-16:20 | 20195.97 | 08-JUL-17:30 | 0.00 | 0.00 | 0.00 |
August | 0.513312E+11 | 0.00 | 743.00 | 0.232927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34736.74 | 19-AUG-15:10 | 24668.66 | 19-AUG-13:40 | 0.00 | 0.00 | 0.00 |
September | 0.368840E+11 | 0.00 | 677.47 | 0.163898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38179.17 | 24-SEP-12:30 | 32492.17 | 24-SEP-12:50 | 0.00 | 0.00 | 0.00 |
October | 0.242801E+11 | 0.00 | 503.83 | 0.125794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41514.30 | 10-OCT-13:30 | 37785.22 | 10-OCT-13:30 | 0.00 | 0.00 | 0.00 |
November | 0.124547E+11 | 0.00 | 342.41 | 0.960822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32930.73 | 06-NOV-13:40 | 32389.36 | 08-NOV-14:10 | 0.00 | 0.00 | 0.00 |
December | 0.473056E+10 | 0.00 | 148.40 | 0.350296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32138.41 | 12-DEC-12:30 | 29991.51 | 10-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269897E+12 | 0.00 | 5532.23 | 0.127100E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.230854E+09 | 0.00 | 19.42 | 0.165350E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13833.19 | 12389.05 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.513312E+11 | 0.00 | 743.00 | 0.232927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41514.30 | 37785.22 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.594536E+09 | 0.00 | 36.42 | 0.207006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74615.18 | 01-JAN-09:02 | 68968.26 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.308001E+10 | 0.00 | 130.80 | 0.180915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86832.78 | 18-FEB-09:02 | 82324.21 | 28-FEB-22:52 | 0.00 | 0.00 | 0.00 |
March | 0.108528E+11 | 0.00 | 293.89 | 0.634250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84796.28 | 29-MAR-15:11 | 82711.79 | 31-MAR-20:12 | 0.00 | 0.00 | 0.00 |
April | 0.231902E+11 | 0.00 | 365.18 | 0.128673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92131.02 | 30-APR-21:52 | 81714.46 | 25-APR-19:01 | 0.00 | 0.00 | 0.00 |
May | 0.395622E+11 | 0.00 | 430.10 | 0.227209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98542.99 | 07-MAY-17:41 | 86600.41 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.563784E+11 | 0.00 | 514.36 | 0.350265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103344.41 | 26-JUN-08:21 | 76917.77 | 30-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.640594E+11 | 0.00 | 544.14 | 0.396191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103423.55 | 23-JUL-08:51 | 76927.04 | 14-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.643146E+11 | 0.00 | 568.02 | 0.384188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114269.76 | 20-AUG-07:52 | 77190.22 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.405269E+11 | 0.00 | 428.99 | 0.221177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101680.27 | 17-SEP-08:52 | 76854.68 | 12-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.169079E+11 | 0.00 | 344.88 | 0.763472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 101176.27 | 18-OCT-21:52 | 83150.85 | 11-OCT-21:52 | 0.00 | 0.00 | 0.00 |
November | 0.611308E+10 | 0.00 | 206.60 | 0.316616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90306.94 | 05-NOV-21:52 | 79871.48 | 06-NOV-19:12 | 0.00 | 0.00 | 0.00 |
December | 0.145718E+10 | 0.00 | 80.59 | 0.608088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87386.11 | 13-DEC-21:03 | 68278.06 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327037E+12 | 0.00 | 3943.98 | 0.190538E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.594536E+09 | 0.00 | 36.42 | 0.207006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74615.18 | 68278.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.643146E+11 | 0.00 | 568.02 | 0.396191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114269.76 | 86600.41 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 42978905.27 | 0.00 | 21.54 | 34348860.07 | 0.00 | 0.00 | 0.00 | 0.00 | 12132.80 | 29-JAN-16:11 | 12132.80 | 29-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.546191E+09 | 0.00 | 117.37 | 0.454189E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12547.39 | 28-FEB-19:01 | 12547.39 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.180301E+10 | 0.00 | 354.82 | 0.106163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13153.59 | 30-MAR-08:62 | 12544.45 | 13-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.388573E+10 | 0.00 | 540.74 | 0.201688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13630.66 | 02-APR-15:11 | 12545.69 | 09-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.665101E+10 | 0.00 | 682.75 | 0.340728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13929.50 | 27-MAY-08:62 | 12544.35 | 09-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.927381E+10 | 0.00 | 697.59 | 0.521349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14545.45 | 23-JUN-08:61 | 11302.13 | 23-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.108950E+11 | 0.00 | 714.67 | 0.633599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15276.97 | 27-JUL-08:61 | 11316.07 | 31-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.112454E+11 | 0.00 | 720.80 | 0.654283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14577.44 | 24-AUG-08:61 | 11319.57 | 21-AUG-15:12 | 0.00 | 0.00 | 0.00 |
September | 0.724739E+10 | 0.00 | 650.44 | 0.369852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14892.17 | 17-SEP-08:62 | 11268.17 | 05-SEP-15:12 | 0.00 | 0.00 | 0.00 |
October | 0.324232E+10 | 0.00 | 462.51 | 0.153275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14541.10 | 01-OCT-15:11 | 11265.45 | 15-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.835185E+09 | 0.00 | 213.35 | 0.455549E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13675.35 | 04-NOV-15:12 | 12546.36 | 18-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.183977E+09 | 0.00 | 63.21 | 99432012.71 | 0.00 | 0.00 | 0.00 | 0.00 | 13056.71 | 13-DEC-16:12 | 12450.83 | 10-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.558520E+11 | 0.00 | 5239.78 | 0.308529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 42978905.27 | 0.00 | 21.54 | 34348860.07 | 0.00 | 0.00 | 0.00 | 0.00 | 12132.80 | 11265.45 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.112454E+11 | 0.00 | 720.80 | 0.654283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15276.97 | 12547.39 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4035185.33 | 0.00 | 2.41 | 2931619.37 | 0.00 | 0.00 | 0.00 | 0.00 | 1951.85 | 19-JAN-22:57 | 1855.65 | 29-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.143526E+09 | 0.00 | 39.85 | 96502021.26 | 0.00 | 0.00 | 0.00 | 0.00 | 11642.85 | 24-FEB-09:02 | 11642.85 | 24-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.745877E+09 | 0.00 | 175.11 | 0.356672E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12714.61 | 28-MAR-18:01 | 12433.51 | 13-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.249399E+10 | 0.00 | 392.11 | 0.122059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13806.34 | 02-APR-15:11 | 11870.95 | 25-APR-19:01 | 0.00 | 0.00 | 0.00 |
May | 0.519440E+10 | 0.00 | 510.53 | 0.269509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14681.53 | 30-MAY-08:51 | 12442.51 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.830402E+10 | 0.00 | 576.46 | 0.486695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16045.84 | 13-JUN-08:61 | 12271.09 | 04-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.977747E+10 | 0.00 | 598.72 | 0.592627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15840.69 | 31-JUL-08:51 | 11473.23 | 25-JUL-08:51 | 0.00 | 0.00 | 0.00 |
August | 0.998655E+10 | 0.00 | 627.44 | 0.582184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16738.45 | 20-AUG-07:52 | 11807.31 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.539521E+10 | 0.00 | 500.36 | 0.268991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15747.92 | 07-SEP-08:31 | 12137.35 | 15-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.151163E+10 | 0.00 | 272.97 | 0.621181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14563.57 | 18-OCT-21:52 | 11047.95 | 09-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.150792E+09 | 0.00 | 54.14 | 64755235.01 | 0.00 | 0.00 | 0.00 | 0.00 | 13793.89 | 05-NOV-15:12 | 10818.99 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 11482773.67 | 0.00 | 7.02 | 4718365.12 | 0.00 | 0.00 | 0.00 | 0.00 | 4517.07 | 12-DEC-22:53 | 2205.86 | 10-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.437190E+11 | 0.00 | 3757.12 | 0.243674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4035185.33 | 0.00 | 2.41 | 2931619.37 | 0.00 | 0.00 | 0.00 | 0.00 | 1951.85 | 1855.65 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.998655E+10 | 0.00 | 627.44 | 0.592627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16738.45 | 12442.51 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 14593164.50 | 0.00 | 14.20 | 13886904.86 | 0.00 | 0.00 | 0.00 | 0.00 | 3646.77 | 29-JAN-16:11 | 3646.77 | 29-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.114393E+09 | 0.00 | 82.20 | 0.101390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3664.62 | 28-FEB-19:01 | 3664.62 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.505273E+09 | 0.00 | 288.59 | 0.332029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3801.88 | 30-MAR-08:62 | 3664.16 | 25-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.998192E+09 | 0.00 | 471.07 | 0.566858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3966.59 | 02-APR-15:11 | 3664.33 | 09-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.164190E+10 | 0.00 | 642.16 | 0.858551E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4178.14 | 27-MAY-08:62 | 3665.24 | 10-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.232672E+10 | 0.00 | 676.55 | 0.130604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4448.94 | 23-JUN-08:61 | 3297.30 | 30-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.271433E+10 | 0.00 | 697.08 | 0.154913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4685.30 | 30-JUL-08:62 | 3290.44 | 22-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.287443E+10 | 0.00 | 708.45 | 0.164416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4545.97 | 29-AUG-08:62 | 3300.15 | 23-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.176153E+10 | 0.00 | 615.82 | 0.886064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4593.59 | 17-SEP-08:62 | 3272.82 | 04-SEP-15:12 | 0.00 | 0.00 | 0.00 |
October | 0.773979E+09 | 0.00 | 380.88 | 0.390119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4357.08 | 18-OCT-08:62 | 3565.58 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.216337E+09 | 0.00 | 159.84 | 0.132304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4052.24 | 04-NOV-15:12 | 3664.68 | 18-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 47116570.53 | 0.00 | 46.52 | 31462179.54 | 0.00 | 0.00 | 0.00 | 0.00 | 3663.94 | 07-DEC-16:11 | 3663.94 | 07-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139888E+11 | 0.00 | 4783.35 | 0.781199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 14593164.50 | 0.00 | 14.20 | 13886904.86 | 0.00 | 0.00 | 0.00 | 0.00 | 3646.77 | 3272.82 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.287443E+10 | 0.00 | 708.45 | 0.164416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4685.30 | 3665.24 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 739071.67 | 0.00 | 0.71 | 456071.37 | 0.00 | 0.00 | 0.00 | 0.00 | 678.53 | 19-JAN-22:57 | 661.46 | 28-JAN-16:13 | 0.00 | 0.00 | 0.00 |
February | 15686414.17 | 0.00 | 16.65 | 11000296.31 | 0.00 | 0.00 | 0.00 | 0.00 | 3372.92 | 20-FEB-19:21 | 3372.92 | 20-FEB-19:21 | 0.00 | 0.00 | 0.00 |
March | 0.195173E+09 | 0.00 | 142.34 | 0.103037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3683.34 | 28-MAR-18:01 | 3619.14 | 13-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.620732E+09 | 0.00 | 337.83 | 0.317212E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4004.60 | 02-APR-15:11 | 3788.45 | 26-APR-18:41 | 0.00 | 0.00 | 0.00 |
May | 0.131581E+10 | 0.00 | 490.05 | 0.698711E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4289.29 | 07-MAY-17:41 | 3849.77 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.214955E+10 | 0.00 | 565.00 | 0.127872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4681.20 | 26-JUN-08:21 | 3248.60 | 03-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.250579E+10 | 0.00 | 588.79 | 0.150427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4640.97 | 08-JUL-07:51 | 3266.47 | 02-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.259660E+10 | 0.00 | 619.80 | 0.151373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5028.30 | 20-AUG-07:52 | 3478.70 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.133919E+10 | 0.00 | 475.00 | 0.662902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4508.32 | 17-SEP-08:52 | 3482.47 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.321651E+09 | 0.00 | 196.12 | 0.130407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4371.25 | 18-OCT-21:52 | 3396.53 | 15-OCT-16:21 | 0.00 | 0.00 | 0.00 |
November | 22411895.11 | 0.00 | 31.11 | 10138061.47 | 0.00 | 0.00 | 0.00 | 0.00 | 3715.40 | 05-NOV-15:12 | 2885.73 | 05-NOV-15:12 | 0.00 | 0.00 | 0.00 |
December | 1818860.46 | 0.00 | 2.74 | 1129096.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1261.71 | 07-DEC-16:11 | 1261.71 | 07-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110852E+11 | 0.00 | 3466.12 | 0.623171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 739071.67 | 0.00 | 0.71 | 456071.37 | 0.00 | 0.00 | 0.00 | 0.00 | 678.53 | 661.46 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.259660E+10 | 0.00 | 619.80 | 0.151373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5028.30 | 3849.77 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.950092E+09 | 0.00 | 132.94 | 0.852129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16468.27 | 10-JAN-16:11 | 16468.27 | 10-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.171918E+10 | 0.00 | 195.25 | 0.148674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16743.10 | 20-FEB-19:21 | 16743.10 | 20-FEB-19:21 | 0.00 | 0.00 | 0.00 |
March | 0.410315E+10 | 0.00 | 437.43 | 0.279791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16593.07 | 30-MAR-08:62 | 16469.67 | 25-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.566064E+10 | 0.00 | 531.10 | 0.312554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17893.46 | 21-APR-18:01 | 16468.76 | 27-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.813516E+10 | 0.00 | 648.42 | 0.403916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18489.05 | 31-MAY-08:61 | 16466.02 | 10-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.110376E+11 | 0.00 | 671.31 | 0.591924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20602.38 | 29-JUN-08:62 | 14809.36 | 28-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.131912E+11 | 0.00 | 693.95 | 0.731396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21319.01 | 27-JUL-08:61 | 14859.57 | 23-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.147574E+11 | 0.00 | 706.25 | 0.869073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20821.57 | 29-AUG-08:62 | 14893.83 | 22-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.105107E+11 | 0.00 | 635.06 | 0.579087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20366.68 | 17-SEP-08:62 | 14891.95 | 04-SEP-15:12 | 0.00 | 0.00 | 0.00 |
October | 0.670404E+10 | 0.00 | 524.23 | 0.392214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19630.14 | 18-OCT-08:62 | 16469.18 | 26-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.378813E+10 | 0.00 | 398.91 | 0.258793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18029.27 | 04-NOV-15:12 | 16469.47 | 11-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 0.194498E+10 | 0.00 | 222.37 | 0.156370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17348.57 | 13-DEC-16:12 | 16466.53 | 10-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.825023E+11 | 0.00 | 5797.19 | 0.480900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.950092E+09 | 0.00 | 132.94 | 0.852129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16468.27 | 14809.36 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.147574E+11 | 0.00 | 706.25 | 0.869073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21319.01 | 16743.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 520.68 | 361.70 | 158.98 | 599.80 | 562.94 | 0.00 | 0.00 | 0.00 |
February | 485.02 | 323.58 | 161.44 | 607.66 | 470.52 | 0.00 | 0.00 | 0.00 |
March | 443.52 | 232.74 | 210.78 | 615.87 | 309.66 | 0.00 | 0.00 | 0.00 |
April | 333.78 | 111.36 | 222.42 | 518.95 | 248.21 | 0.00 | 0.00 | 0.00 |
May | 268.30 | 32.83 | 235.47 | 443.11 | 158.74 | 0.00 | 0.00 | 0.00 |
June | 246.36 | 13.75 | 232.60 | 474.17 | 96.38 | 0.00 | 0.00 | 0.00 |
July | 247.12 | 16.67 | 230.46 | 501.09 | 62.20 | 0.00 | 0.00 | 0.00 |
August | 297.77 | 55.96 | 241.81 | 607.41 | 50.66 | 0.00 | 0.00 | 0.00 |
September | 336.19 | 130.81 | 205.38 | 587.17 | 129.50 | 0.00 | 0.00 | 0.00 |
October | 472.07 | 305.12 | 166.95 | 711.63 | 281.59 | 0.00 | 0.00 | 0.00 |
November | 515.76 | 344.17 | 171.59 | 700.18 | 373.87 | 0.00 | 0.00 | 0.00 |
December | 517.01 | 363.70 | 153.31 | 637.73 | 470.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 389.87 | 190.39 | 199.48 | 583.68 | 266.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.36 | 13.75 | 153.31 | 443.11 | 50.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 520.68 | 363.70 | 241.81 | 711.63 | 562.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1466.20 | 1018.53 | 447.67 | 1685.48 | 1611.72 | 0.00 | 0.00 | 0.00 |
February | 1365.78 | 911.17 | 454.61 | 1713.78 | 1347.16 | 0.00 | 0.00 | 0.00 |
March | 1248.92 | 655.38 | 593.54 | 1759.22 | 865.53 | 0.00 | 0.00 | 0.00 |
April | 939.90 | 313.58 | 626.32 | 1505.36 | 672.19 | 0.00 | 0.00 | 0.00 |
May | 755.53 | 92.46 | 663.07 | 1322.87 | 405.44 | 0.00 | 0.00 | 0.00 |
June | 693.72 | 38.73 | 654.99 | 1436.51 | 229.62 | 0.00 | 0.00 | 0.00 |
July | 695.89 | 46.94 | 648.95 | 1511.78 | 140.46 | 0.00 | 0.00 | 0.00 |
August | 838.51 | 157.59 | 680.92 | 1800.77 | 110.01 | 0.00 | 0.00 | 0.00 |
September | 946.68 | 368.34 | 578.34 | 1717.80 | 323.01 | 0.00 | 0.00 | 0.00 |
October | 1329.32 | 859.19 | 470.13 | 2034.14 | 775.40 | 0.00 | 0.00 | 0.00 |
November | 1452.34 | 969.15 | 483.19 | 1983.64 | 1056.66 | 0.00 | 0.00 | 0.00 |
December | 1455.88 | 1024.16 | 431.72 | 1796.12 | 1347.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1097.86 | 536.13 | 561.73 | 1689.06 | 737.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 693.72 | 38.73 | 431.72 | 1322.87 | 110.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1466.20 | 1024.16 | 680.92 | 2034.14 | 1611.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1904.67 | 1323.13 | 581.55 | 2217.68 | 2210.31 | 0.00 | 0.00 | 0.00 |
February | 1774.23 | 1183.66 | 590.56 | 2255.48 | 1854.74 | 0.00 | 0.00 | 0.00 |
March | 1622.42 | 851.37 | 771.05 | 2306.68 | 1208.40 | 0.00 | 0.00 | 0.00 |
April | 1220.99 | 407.36 | 813.62 | 1961.78 | 954.05 | 0.00 | 0.00 | 0.00 |
May | 981.47 | 120.11 | 861.37 | 1707.06 | 591.95 | 0.00 | 0.00 | 0.00 |
June | 901.18 | 50.31 | 850.87 | 1846.68 | 343.32 | 0.00 | 0.00 | 0.00 |
July | 904.00 | 60.98 | 843.02 | 1947.51 | 215.93 | 0.00 | 0.00 | 0.00 |
August | 1089.28 | 204.72 | 884.56 | 2341.36 | 166.78 | 0.00 | 0.00 | 0.00 |
September | 1229.79 | 478.50 | 751.29 | 2232.89 | 475.94 | 0.00 | 0.00 | 0.00 |
October | 1726.86 | 1116.14 | 610.72 | 2667.13 | 1092.47 | 0.00 | 0.00 | 0.00 |
November | 1886.68 | 1258.98 | 627.69 | 2599.63 | 1474.14 | 0.00 | 0.00 | 0.00 |
December | 1891.27 | 1330.44 | 560.83 | 2358.28 | 1866.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1426.18 | 696.47 | 729.71 | 2203.56 | 1033.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 901.18 | 50.31 | 560.83 | 1707.06 | 166.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1904.67 | 1330.44 | 884.56 | 2667.13 | 2210.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.95 | 71.51 | 31.43 | 120.07 | 112.85 | 0.00 | 0.00 | 0.00 |
February | 95.90 | 63.98 | 31.92 | 121.49 | 92.88 | 0.00 | 0.00 | 0.00 |
March | 87.69 | 46.02 | 41.68 | 123.28 | 57.57 | 0.00 | 0.00 | 0.00 |
April | 65.99 | 22.02 | 43.98 | 104.68 | 44.42 | 0.00 | 0.00 | 0.00 |
May | 53.05 | 6.49 | 46.56 | 91.84 | 24.51 | 0.00 | 0.00 | 0.00 |
June | 48.71 | 2.72 | 45.99 | 102.48 | 11.37 | 0.00 | 0.00 | 0.00 |
July | 48.86 | 3.30 | 45.57 | 109.43 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 58.88 | 11.07 | 47.81 | 131.42 | 2.71 | 0.00 | 0.00 | 0.00 |
September | 66.47 | 25.86 | 40.61 | 122.34 | 16.89 | 0.00 | 0.00 | 0.00 |
October | 93.34 | 60.33 | 33.01 | 144.18 | 49.34 | 0.00 | 0.00 | 0.00 |
November | 101.97 | 68.05 | 33.93 | 141.08 | 70.35 | 0.00 | 0.00 | 0.00 |
December | 102.22 | 71.91 | 30.31 | 128.10 | 92.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.09 | 37.64 | 39.44 | 120.05 | 48.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.71 | 2.72 | 30.31 | 91.84 | 2.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.95 | 71.91 | 47.81 | 144.18 | 112.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.08 | 38.17 | 43.92 | 64.97 | 237.58 | 0.00 | 0.00 | 0.00 |
February | 94.04 | 44.07 | 49.96 | 97.44 | 192.38 | 0.00 | 0.00 | 0.00 |
March | 137.97 | 66.54 | 71.43 | 178.01 | 111.33 | 0.00 | 0.00 | 0.00 |
April | 155.47 | 71.11 | 84.36 | 233.77 | 81.77 | 0.00 | 0.00 | 0.00 |
May | 156.43 | 59.37 | 97.06 | 261.88 | 45.39 | 0.00 | 0.00 | 0.00 |
June | 164.35 | 63.28 | 101.07 | 313.76 | 21.11 | 0.00 | 0.00 | 0.00 |
July | 154.70 | 57.22 | 97.48 | 310.33 | 10.02 | 0.00 | 0.00 | 0.00 |
August | 151.95 | 56.83 | 95.12 | 306.91 | 5.05 | 0.00 | 0.00 | 0.00 |
September | 124.13 | 51.89 | 72.24 | 216.38 | 31.65 | 0.00 | 0.00 | 0.00 |
October | 110.45 | 57.43 | 53.02 | 157.90 | 97.10 | 0.00 | 0.00 | 0.00 |
November | 87.72 | 39.23 | 48.49 | 102.28 | 144.64 | 0.00 | 0.00 | 0.00 |
December | 72.66 | 31.83 | 40.83 | 63.24 | 194.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.48 | 53.12 | 71.36 | 192.75 | 97.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.66 | 31.83 | 40.83 | 63.24 | 5.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 164.35 | 71.11 | 101.07 | 313.76 | 237.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.39 | 0.00 | 19.39 | 3.11 | 134.05 | 0.00 | 0.00 | 0.00 |
February | 21.49 | 0.00 | 21.49 | 10.44 | 107.16 | 0.00 | 0.00 | 0.00 |
March | 30.18 | 0.00 | 30.18 | 23.89 | 61.49 | 0.00 | 0.00 | 0.00 |
April | 36.59 | 0.21 | 36.38 | 45.02 | 45.33 | 0.00 | 0.00 | 0.00 |
May | 43.66 | 1.37 | 42.29 | 68.35 | 24.81 | 0.00 | 0.00 | 0.00 |
June | 48.02 | 3.15 | 44.87 | 97.67 | 11.37 | 0.00 | 0.00 | 0.00 |
July | 45.48 | 2.33 | 43.15 | 99.71 | 5.89 | 0.00 | 0.00 | 0.00 |
August | 40.39 | 0.47 | 39.92 | 91.90 | 3.00 | 0.00 | 0.00 | 0.00 |
September | 30.49 | 0.01 | 30.48 | 52.96 | 18.32 | 0.00 | 0.00 | 0.00 |
October | 23.17 | 0.00 | 23.17 | 24.26 | 53.25 | 0.00 | 0.00 | 0.00 |
November | 20.73 | 0.00 | 20.73 | 13.43 | 77.94 | 0.00 | 0.00 | 0.00 |
December | 17.92 | 0.00 | 17.92 | 4.13 | 106.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.51 | 0.63 | 30.88 | 44.77 | 53.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.92 | 0.00 | 17.92 | 3.11 | 3.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.02 | 3.15 | 44.87 | 99.71 | 134.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.08 | 38.17 | 43.92 | 68.47 | 233.55 | 0.00 | 0.00 | 0.00 |
February | 94.04 | 44.07 | 49.96 | 100.79 | 189.53 | 0.00 | 0.00 | 0.00 |
March | 137.97 | 66.54 | 71.43 | 180.45 | 110.77 | 0.00 | 0.00 | 0.00 |
April | 155.47 | 71.11 | 84.36 | 233.61 | 84.09 | 0.00 | 0.00 | 0.00 |
May | 156.43 | 59.37 | 97.06 | 259.62 | 48.64 | 0.00 | 0.00 | 0.00 |
June | 164.35 | 63.28 | 101.07 | 311.07 | 22.76 | 0.00 | 0.00 | 0.00 |
July | 154.70 | 57.22 | 97.48 | 307.75 | 11.33 | 0.00 | 0.00 | 0.00 |
August | 151.95 | 56.83 | 95.12 | 305.68 | 5.68 | 0.00 | 0.00 | 0.00 |
September | 124.13 | 51.89 | 72.24 | 215.93 | 33.91 | 0.00 | 0.00 | 0.00 |
October | 110.45 | 57.43 | 53.02 | 160.10 | 97.44 | 0.00 | 0.00 | 0.00 |
November | 87.72 | 39.23 | 48.49 | 106.50 | 141.80 | 0.00 | 0.00 | 0.00 |
December | 72.66 | 31.83 | 40.83 | 67.42 | 190.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.48 | 53.12 | 71.36 | 193.62 | 97.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.66 | 31.83 | 40.83 | 67.42 | 5.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 164.35 | 71.11 | 101.07 | 311.07 | 233.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.34 | 57.20 | 25.14 | 92.85 | 93.16 | 0.00 | 0.00 | 0.00 |
February | 76.70 | 51.17 | 25.53 | 90.25 | 88.42 | 0.00 | 0.00 | 0.00 |
March | 70.14 | 36.81 | 33.33 | 85.96 | 70.07 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 17.61 | 35.17 | 71.06 | 57.50 | 0.00 | 0.00 | 0.00 |
May | 42.43 | 5.19 | 37.24 | 59.79 | 38.78 | 0.00 | 0.00 | 0.00 |
June | 38.96 | 2.18 | 36.78 | 65.97 | 24.41 | 0.00 | 0.00 | 0.00 |
July | 39.08 | 2.64 | 36.45 | 70.38 | 17.93 | 0.00 | 0.00 | 0.00 |
August | 47.09 | 8.85 | 38.24 | 87.58 | 15.53 | 0.00 | 0.00 | 0.00 |
September | 53.17 | 20.69 | 32.48 | 84.25 | 32.88 | 0.00 | 0.00 | 0.00 |
October | 74.65 | 48.25 | 26.40 | 103.18 | 63.82 | 0.00 | 0.00 | 0.00 |
November | 81.56 | 54.43 | 27.14 | 100.03 | 82.75 | 0.00 | 0.00 | 0.00 |
December | 81.76 | 57.52 | 24.25 | 92.11 | 95.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.66 | 30.11 | 31.55 | 83.60 | 56.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 38.96 | 2.18 | 24.25 | 59.79 | 15.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.34 | 57.52 | 38.24 | 103.18 | 95.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.51 | 0.00 | 15.51 | 2.23 | 112.22 | 0.00 | 0.00 | 0.00 |
February | 17.20 | 0.00 | 17.20 | 8.31 | 89.16 | 0.00 | 0.00 | 0.00 |
March | 24.15 | 0.00 | 24.15 | 20.13 | 49.12 | 0.00 | 0.00 | 0.00 |
April | 29.28 | 0.17 | 29.11 | 38.13 | 35.33 | 0.00 | 0.00 | 0.00 |
May | 34.93 | 1.10 | 33.84 | 57.55 | 18.71 | 0.00 | 0.00 | 0.00 |
June | 38.42 | 2.52 | 35.90 | 82.06 | 7.90 | 0.00 | 0.00 | 0.00 |
July | 36.39 | 1.86 | 34.52 | 84.05 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 32.32 | 0.38 | 31.94 | 78.32 | 1.63 | 0.00 | 0.00 | 0.00 |
September | 24.40 | 0.01 | 24.39 | 45.10 | 13.57 | 0.00 | 0.00 | 0.00 |
October | 18.54 | 0.00 | 18.54 | 20.57 | 42.52 | 0.00 | 0.00 | 0.00 |
November | 16.59 | 0.00 | 16.59 | 10.75 | 64.18 | 0.00 | 0.00 | 0.00 |
December | 14.34 | 0.00 | 14.34 | 2.84 | 89.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.21 | 0.51 | 24.71 | 37.67 | 43.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.34 | 0.00 | 14.34 | 2.23 | 1.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.42 | 2.52 | 35.90 | 84.05 | 112.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.11 | 36.47 | 43.63 | 55.29 | 230.61 | 0.00 | 0.00 | 0.00 |
February | 100.54 | 54.12 | 46.42 | 97.92 | 181.82 | 0.00 | 0.00 | 0.00 |
March | 126.49 | 57.70 | 68.79 | 150.56 | 103.41 | 0.00 | 0.00 | 0.00 |
April | 152.90 | 69.79 | 83.11 | 223.13 | 75.43 | 0.00 | 0.00 | 0.00 |
May | 167.50 | 70.84 | 96.67 | 276.16 | 41.90 | 0.00 | 0.00 | 0.00 |
June | 173.25 | 72.57 | 100.68 | 327.18 | 19.23 | 0.00 | 0.00 | 0.00 |
July | 168.87 | 70.85 | 98.02 | 333.33 | 9.65 | 0.00 | 0.00 | 0.00 |
August | 154.77 | 61.39 | 93.38 | 312.21 | 4.75 | 0.00 | 0.00 | 0.00 |
September | 126.85 | 56.05 | 70.80 | 219.97 | 30.11 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 56.47 | 52.02 | 147.69 | 90.68 | 0.00 | 0.00 | 0.00 |
November | 86.41 | 38.98 | 47.43 | 89.10 | 133.55 | 0.00 | 0.00 | 0.00 |
December | 74.98 | 34.13 | 40.85 | 55.92 | 182.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.89 | 56.60 | 70.29 | 191.20 | 91.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.98 | 34.13 | 40.85 | 55.29 | 4.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.25 | 72.57 | 100.68 | 333.33 | 230.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.95 | 71.51 | 31.43 | 119.51 | 112.56 | 0.00 | 0.00 | 0.00 |
February | 95.90 | 63.98 | 31.92 | 120.55 | 92.65 | 0.00 | 0.00 | 0.00 |
March | 87.69 | 46.02 | 41.68 | 122.40 | 57.05 | 0.00 | 0.00 | 0.00 |
April | 65.99 | 22.02 | 43.98 | 103.77 | 44.13 | 0.00 | 0.00 | 0.00 |
May | 53.05 | 6.49 | 46.56 | 90.98 | 24.36 | 0.00 | 0.00 | 0.00 |
June | 48.71 | 2.72 | 45.99 | 101.75 | 11.22 | 0.00 | 0.00 | 0.00 |
July | 48.86 | 3.30 | 45.57 | 108.80 | 5.33 | 0.00 | 0.00 | 0.00 |
August | 58.88 | 11.07 | 47.81 | 131.12 | 2.61 | 0.00 | 0.00 | 0.00 |
September | 66.47 | 25.86 | 40.61 | 121.89 | 16.71 | 0.00 | 0.00 | 0.00 |
October | 93.34 | 60.33 | 33.01 | 143.45 | 49.00 | 0.00 | 0.00 | 0.00 |
November | 101.97 | 68.05 | 33.93 | 140.45 | 70.04 | 0.00 | 0.00 | 0.00 |
December | 102.22 | 71.91 | 30.31 | 127.52 | 92.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.09 | 37.64 | 39.44 | 119.37 | 47.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.71 | 2.72 | 30.31 | 90.98 | 2.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.95 | 71.91 | 47.81 | 143.45 | 112.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.39 | 0.00 | 19.39 | 2.97 | 134.05 | 0.00 | 0.00 | 0.00 |
February | 21.49 | 0.00 | 21.49 | 10.01 | 107.27 | 0.00 | 0.00 | 0.00 |
March | 30.18 | 0.00 | 30.18 | 23.44 | 60.78 | 0.00 | 0.00 | 0.00 |
April | 36.59 | 0.21 | 36.38 | 44.17 | 44.75 | 0.00 | 0.00 | 0.00 |
May | 43.66 | 1.37 | 42.29 | 67.22 | 24.45 | 0.00 | 0.00 | 0.00 |
June | 48.02 | 3.15 | 44.87 | 96.39 | 11.15 | 0.00 | 0.00 | 0.00 |
July | 45.48 | 2.33 | 43.15 | 98.56 | 5.86 | 0.00 | 0.00 | 0.00 |
August | 40.39 | 0.47 | 39.92 | 91.30 | 2.90 | 0.00 | 0.00 | 0.00 |
September | 30.49 | 0.01 | 30.48 | 52.19 | 18.09 | 0.00 | 0.00 | 0.00 |
October | 23.17 | 0.00 | 23.17 | 23.56 | 52.69 | 0.00 | 0.00 | 0.00 |
November | 20.73 | 0.00 | 20.73 | 13.19 | 77.39 | 0.00 | 0.00 | 0.00 |
December | 17.92 | 0.00 | 17.92 | 3.95 | 106.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.51 | 0.63 | 30.88 | 44.11 | 53.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.92 | 0.00 | 17.92 | 2.97 | 2.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.02 | 3.15 | 44.87 | 98.56 | 134.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.11 | 36.47 | 43.63 | 57.32 | 224.89 | 0.00 | 0.00 | 0.00 |
February | 100.54 | 54.12 | 46.42 | 100.90 | 178.27 | 0.00 | 0.00 | 0.00 |
March | 126.49 | 57.70 | 68.79 | 153.63 | 102.18 | 0.00 | 0.00 | 0.00 |
April | 152.90 | 69.79 | 83.11 | 223.37 | 77.35 | 0.00 | 0.00 | 0.00 |
May | 167.50 | 70.84 | 96.67 | 273.46 | 44.81 | 0.00 | 0.00 | 0.00 |
June | 173.25 | 72.57 | 100.68 | 323.15 | 20.66 | 0.00 | 0.00 | 0.00 |
July | 168.87 | 70.85 | 98.02 | 329.38 | 10.90 | 0.00 | 0.00 | 0.00 |
August | 154.77 | 61.39 | 93.38 | 310.14 | 5.28 | 0.00 | 0.00 | 0.00 |
September | 126.85 | 56.05 | 70.80 | 218.68 | 32.13 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 56.47 | 52.02 | 150.04 | 90.44 | 0.00 | 0.00 | 0.00 |
November | 86.41 | 38.98 | 47.43 | 93.53 | 129.75 | 0.00 | 0.00 | 0.00 |
December | 74.98 | 34.13 | 40.85 | 58.98 | 177.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.89 | 56.60 | 70.29 | 191.53 | 90.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.98 | 34.13 | 40.85 | 57.32 | 5.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.25 | 72.57 | 100.68 | 329.38 | 224.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.56 | 0.00 | 24.56 | 3.41 | 183.40 | 0.00 | 0.00 | 0.00 |
February | 27.22 | 0.00 | 27.22 | 12.84 | 145.01 | 0.00 | 0.00 | 0.00 |
March | 38.22 | 0.00 | 38.22 | 31.50 | 80.92 | 0.00 | 0.00 | 0.00 |
April | 46.34 | 0.27 | 46.07 | 59.85 | 59.88 | 0.00 | 0.00 | 0.00 |
May | 55.29 | 1.73 | 53.56 | 90.06 | 34.02 | 0.00 | 0.00 | 0.00 |
June | 60.81 | 3.99 | 56.83 | 124.48 | 18.29 | 0.00 | 0.00 | 0.00 |
July | 57.59 | 2.95 | 54.64 | 124.85 | 11.42 | 0.00 | 0.00 | 0.00 |
August | 51.15 | 0.60 | 50.55 | 113.80 | 7.84 | 0.00 | 0.00 | 0.00 |
September | 38.61 | 0.02 | 38.60 | 67.53 | 27.86 | 0.00 | 0.00 | 0.00 |
October | 29.34 | 0.00 | 29.34 | 31.12 | 72.30 | 0.00 | 0.00 | 0.00 |
November | 26.26 | 0.00 | 26.26 | 16.67 | 104.42 | 0.00 | 0.00 | 0.00 |
December | 22.70 | 0.00 | 22.70 | 4.11 | 145.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.91 | 0.80 | 39.11 | 56.93 | 73.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.70 | 0.00 | 22.70 | 3.41 | 7.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.81 | 3.99 | 56.83 | 124.85 | 183.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.05 | 0.00 | 9.05 | 1.26 | 67.61 | 0.00 | 0.00 | 0.00 |
February | 10.03 | 0.00 | 10.03 | 4.73 | 53.46 | 0.00 | 0.00 | 0.00 |
March | 14.09 | 0.00 | 14.09 | 11.61 | 29.83 | 0.00 | 0.00 | 0.00 |
April | 17.08 | 0.10 | 16.98 | 22.06 | 22.07 | 0.00 | 0.00 | 0.00 |
May | 20.38 | 0.64 | 19.74 | 33.20 | 12.54 | 0.00 | 0.00 | 0.00 |
June | 22.42 | 1.47 | 20.95 | 45.89 | 6.74 | 0.00 | 0.00 | 0.00 |
July | 21.23 | 1.09 | 20.14 | 46.02 | 4.21 | 0.00 | 0.00 | 0.00 |
August | 18.86 | 0.22 | 18.64 | 41.95 | 2.89 | 0.00 | 0.00 | 0.00 |
September | 14.23 | 0.01 | 14.23 | 24.89 | 10.27 | 0.00 | 0.00 | 0.00 |
October | 10.82 | 0.00 | 10.82 | 11.47 | 26.65 | 0.00 | 0.00 | 0.00 |
November | 9.68 | 0.00 | 9.68 | 6.14 | 38.49 | 0.00 | 0.00 | 0.00 |
December | 8.37 | 0.00 | 8.37 | 1.52 | 53.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.71 | 0.30 | 14.42 | 20.99 | 27.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.37 | 0.00 | 8.37 | 1.26 | 2.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.42 | 1.47 | 20.95 | 46.02 | 67.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 48.03 | 33.37 | 14.67 | 55.49 | 55.29 | 0.00 | 0.00 | 0.00 |
February | 44.75 | 29.85 | 14.89 | 56.73 | 45.34 | 0.00 | 0.00 | 0.00 |
March | 40.92 | 21.47 | 19.45 | 58.63 | 27.90 | 0.00 | 0.00 | 0.00 |
April | 30.79 | 10.27 | 20.52 | 49.90 | 22.28 | 0.00 | 0.00 | 0.00 |
May | 24.75 | 3.03 | 21.72 | 43.67 | 13.29 | 0.00 | 0.00 | 0.00 |
June | 22.73 | 1.27 | 21.46 | 47.52 | 7.27 | 0.00 | 0.00 | 0.00 |
July | 22.80 | 1.54 | 21.26 | 49.94 | 4.40 | 0.00 | 0.00 | 0.00 |
August | 27.47 | 5.16 | 22.31 | 60.02 | 2.94 | 0.00 | 0.00 | 0.00 |
September | 31.01 | 12.07 | 18.95 | 57.08 | 10.18 | 0.00 | 0.00 | 0.00 |
October | 43.55 | 28.15 | 15.40 | 67.96 | 24.88 | 0.00 | 0.00 | 0.00 |
November | 47.58 | 31.75 | 15.83 | 66.63 | 33.97 | 0.00 | 0.00 | 0.00 |
December | 47.70 | 33.55 | 14.14 | 59.63 | 44.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.97 | 17.56 | 18.40 | 56.10 | 24.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.73 | 1.27 | 14.14 | 43.67 | 2.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.03 | 33.55 | 22.31 | 67.96 | 55.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 130.38 | 90.57 | 39.81 | 150.61 | 150.07 | 0.00 | 0.00 | 0.00 |
February | 121.45 | 81.02 | 40.42 | 153.98 | 123.05 | 0.00 | 0.00 | 0.00 |
March | 111.06 | 58.28 | 52.78 | 159.13 | 75.73 | 0.00 | 0.00 | 0.00 |
April | 83.58 | 27.88 | 55.69 | 135.43 | 60.48 | 0.00 | 0.00 | 0.00 |
May | 67.18 | 8.22 | 58.96 | 118.52 | 36.07 | 0.00 | 0.00 | 0.00 |
June | 61.69 | 3.44 | 58.24 | 128.98 | 19.73 | 0.00 | 0.00 | 0.00 |
July | 61.88 | 4.17 | 57.71 | 135.54 | 11.93 | 0.00 | 0.00 | 0.00 |
August | 74.56 | 14.01 | 60.55 | 162.91 | 7.99 | 0.00 | 0.00 | 0.00 |
September | 84.18 | 32.75 | 51.43 | 154.91 | 27.64 | 0.00 | 0.00 | 0.00 |
October | 118.21 | 76.40 | 41.80 | 184.45 | 67.54 | 0.00 | 0.00 | 0.00 |
November | 129.14 | 86.18 | 42.97 | 180.86 | 92.21 | 0.00 | 0.00 | 0.00 |
December | 129.46 | 91.07 | 38.39 | 161.85 | 121.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.62 | 47.67 | 49.95 | 152.27 | 65.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 61.69 | 3.44 | 38.39 | 118.52 | 7.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.38 | 91.07 | 60.55 | 184.45 | 150.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.95 | 71.51 | 31.43 | 119.74 | 112.16 | 0.00 | 0.00 | 0.00 |
February | 95.90 | 63.98 | 31.92 | 120.87 | 92.21 | 0.00 | 0.00 | 0.00 |
March | 87.69 | 46.02 | 41.68 | 122.24 | 56.92 | 0.00 | 0.00 | 0.00 |
April | 65.99 | 22.02 | 43.98 | 103.60 | 43.91 | 0.00 | 0.00 | 0.00 |
May | 53.05 | 6.49 | 46.56 | 90.72 | 24.11 | 0.00 | 0.00 | 0.00 |
June | 48.71 | 2.72 | 45.99 | 101.74 | 10.92 | 0.00 | 0.00 | 0.00 |
July | 48.86 | 3.30 | 45.57 | 108.75 | 5.03 | 0.00 | 0.00 | 0.00 |
August | 58.88 | 11.07 | 47.81 | 130.66 | 2.40 | 0.00 | 0.00 | 0.00 |
September | 66.47 | 25.86 | 40.61 | 121.53 | 16.29 | 0.00 | 0.00 | 0.00 |
October | 93.34 | 60.33 | 33.01 | 143.28 | 48.51 | 0.00 | 0.00 | 0.00 |
November | 101.97 | 68.05 | 33.93 | 140.45 | 69.53 | 0.00 | 0.00 | 0.00 |
December | 102.22 | 71.91 | 30.31 | 127.69 | 91.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.09 | 37.64 | 39.44 | 119.29 | 47.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.71 | 2.72 | 30.31 | 90.72 | 2.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.95 | 71.91 | 47.81 | 143.28 | 112.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.08 | 38.17 | 43.92 | 64.96 | 236.19 | 0.00 | 0.00 | 0.00 |
February | 94.04 | 44.07 | 49.96 | 96.87 | 190.83 | 0.00 | 0.00 | 0.00 |
March | 137.97 | 66.54 | 71.43 | 176.23 | 109.89 | 0.00 | 0.00 | 0.00 |
April | 155.47 | 71.11 | 84.36 | 231.44 | 80.76 | 0.00 | 0.00 | 0.00 |
May | 156.43 | 59.37 | 97.06 | 259.18 | 44.61 | 0.00 | 0.00 | 0.00 |
June | 164.35 | 63.28 | 101.07 | 311.30 | 20.20 | 0.00 | 0.00 | 0.00 |
July | 154.70 | 57.22 | 97.48 | 308.35 | 9.29 | 0.00 | 0.00 | 0.00 |
August | 151.95 | 56.83 | 95.12 | 305.04 | 4.48 | 0.00 | 0.00 | 0.00 |
September | 124.13 | 51.89 | 72.24 | 214.91 | 30.44 | 0.00 | 0.00 | 0.00 |
October | 110.45 | 57.43 | 53.02 | 156.69 | 95.30 | 0.00 | 0.00 | 0.00 |
November | 87.72 | 39.23 | 48.49 | 101.65 | 142.87 | 0.00 | 0.00 | 0.00 |
December | 72.66 | 31.83 | 40.83 | 63.24 | 192.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.48 | 53.12 | 71.36 | 191.33 | 95.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.66 | 31.83 | 40.83 | 63.24 | 4.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 164.35 | 71.11 | 101.07 | 311.30 | 236.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.39 | 0.00 | 19.39 | 3.23 | 133.39 | 0.00 | 0.00 | 0.00 |
February | 21.49 | 0.00 | 21.49 | 10.59 | 106.41 | 0.00 | 0.00 | 0.00 |
March | 30.18 | 0.00 | 30.18 | 23.82 | 60.85 | 0.00 | 0.00 | 0.00 |
April | 36.59 | 0.21 | 36.38 | 44.45 | 45.17 | 0.00 | 0.00 | 0.00 |
May | 43.66 | 1.37 | 42.29 | 67.38 | 24.76 | 0.00 | 0.00 | 0.00 |
June | 48.02 | 3.15 | 44.87 | 97.03 | 11.03 | 0.00 | 0.00 | 0.00 |
July | 45.48 | 2.33 | 43.15 | 99.15 | 5.59 | 0.00 | 0.00 | 0.00 |
August | 40.39 | 0.47 | 39.92 | 91.49 | 2.68 | 0.00 | 0.00 | 0.00 |
September | 30.49 | 0.01 | 30.48 | 52.70 | 17.70 | 0.00 | 0.00 | 0.00 |
October | 23.17 | 0.00 | 23.17 | 24.37 | 52.37 | 0.00 | 0.00 | 0.00 |
November | 20.73 | 0.00 | 20.73 | 13.73 | 76.84 | 0.00 | 0.00 | 0.00 |
December | 17.92 | 0.00 | 17.92 | 4.44 | 105.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.51 | 0.63 | 30.88 | 44.56 | 53.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.92 | 0.00 | 17.92 | 3.23 | 2.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.02 | 3.15 | 44.87 | 99.15 | 133.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.08 | 38.17 | 43.92 | 68.46 | 232.48 | 0.00 | 0.00 | 0.00 |
February | 94.04 | 44.07 | 49.96 | 100.35 | 188.12 | 0.00 | 0.00 | 0.00 |
March | 137.97 | 66.54 | 71.43 | 178.94 | 109.42 | 0.00 | 0.00 | 0.00 |
April | 155.47 | 71.11 | 84.36 | 231.12 | 83.67 | 0.00 | 0.00 | 0.00 |
May | 156.43 | 59.37 | 97.06 | 256.69 | 48.34 | 0.00 | 0.00 | 0.00 |
June | 164.35 | 63.28 | 101.07 | 308.62 | 21.94 | 0.00 | 0.00 | 0.00 |
July | 154.70 | 57.22 | 97.48 | 305.79 | 10.61 | 0.00 | 0.00 | 0.00 |
August | 151.95 | 56.83 | 95.12 | 303.87 | 5.06 | 0.00 | 0.00 | 0.00 |
September | 124.13 | 51.89 | 72.24 | 214.53 | 32.73 | 0.00 | 0.00 | 0.00 |
October | 110.45 | 57.43 | 53.02 | 159.21 | 95.70 | 0.00 | 0.00 | 0.00 |
November | 87.72 | 39.23 | 48.49 | 106.41 | 139.79 | 0.00 | 0.00 | 0.00 |
December | 72.66 | 31.83 | 40.83 | 67.81 | 188.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.48 | 53.12 | 71.36 | 192.31 | 95.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.66 | 31.83 | 40.83 | 67.81 | 5.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 164.35 | 71.11 | 101.07 | 308.62 | 232.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 150.98 | 104.88 | 46.10 | 167.80 | 171.80 | 0.00 | 0.00 | 0.00 |
February | 140.64 | 93.83 | 46.81 | 171.38 | 141.08 | 0.00 | 0.00 | 0.00 |
March | 128.61 | 67.49 | 61.12 | 176.50 | 85.26 | 0.00 | 0.00 | 0.00 |
April | 96.79 | 32.29 | 64.50 | 152.11 | 63.90 | 0.00 | 0.00 | 0.00 |
May | 77.80 | 9.52 | 68.28 | 135.35 | 34.14 | 0.00 | 0.00 | 0.00 |
June | 71.44 | 3.99 | 67.45 | 153.09 | 14.80 | 0.00 | 0.00 | 0.00 |
July | 71.66 | 4.83 | 66.83 | 163.65 | 6.56 | 0.00 | 0.00 | 0.00 |
August | 86.35 | 16.23 | 70.12 | 195.45 | 2.99 | 0.00 | 0.00 | 0.00 |
September | 97.49 | 37.93 | 59.55 | 179.20 | 23.43 | 0.00 | 0.00 | 0.00 |
October | 136.89 | 88.48 | 48.41 | 207.59 | 73.21 | 0.00 | 0.00 | 0.00 |
November | 149.56 | 99.80 | 49.76 | 200.64 | 106.66 | 0.00 | 0.00 | 0.00 |
December | 149.92 | 105.46 | 44.46 | 179.81 | 140.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 113.05 | 55.21 | 57.84 | 173.59 | 71.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.44 | 3.99 | 44.46 | 135.35 | 2.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 150.98 | 105.46 | 70.12 | 207.59 | 171.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.72 | 0.00 | 135.72 | 15.95 | 1068.41 | 0.00 | 0.00 | 0.00 |
February | 150.43 | 0.00 | 150.43 | 63.61 | 861.52 | 0.00 | 0.00 | 0.00 |
March | 211.25 | 0.00 | 211.25 | 156.77 | 500.09 | 0.00 | 0.00 | 0.00 |
April | 256.14 | 1.50 | 254.65 | 314.10 | 367.45 | 0.00 | 0.00 | 0.00 |
May | 305.61 | 9.59 | 296.03 | 481.39 | 216.07 | 0.00 | 0.00 | 0.00 |
June | 336.12 | 22.04 | 314.08 | 683.22 | 116.94 | 0.00 | 0.00 | 0.00 |
July | 318.33 | 16.31 | 302.02 | 693.09 | 73.36 | 0.00 | 0.00 | 0.00 |
August | 282.74 | 3.32 | 279.41 | 635.91 | 53.18 | 0.00 | 0.00 | 0.00 |
September | 213.42 | 0.08 | 213.34 | 373.09 | 170.79 | 0.00 | 0.00 | 0.00 |
October | 162.16 | 0.00 | 162.16 | 164.82 | 439.06 | 0.00 | 0.00 | 0.00 |
November | 145.13 | 0.00 | 145.13 | 80.79 | 632.94 | 0.00 | 0.00 | 0.00 |
December | 125.46 | 0.00 | 125.46 | 18.16 | 863.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 220.59 | 4.42 | 216.17 | 308.13 | 444.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 125.46 | 0.00 | 125.46 | 15.95 | 53.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 336.12 | 22.04 | 314.08 | 693.09 | 1068.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.72 | 0.00 | 135.72 | 14.05 | 1105.30 | 0.00 | 0.00 | 0.00 |
February | 150.43 | 0.00 | 150.43 | 58.74 | 895.52 | 0.00 | 0.00 | 0.00 |
March | 211.25 | 0.00 | 211.25 | 145.95 | 524.63 | 0.00 | 0.00 | 0.00 |
April | 256.14 | 1.50 | 254.65 | 300.93 | 384.25 | 0.00 | 0.00 | 0.00 |
May | 305.61 | 9.59 | 296.03 | 466.56 | 227.79 | 0.00 | 0.00 | 0.00 |
June | 336.12 | 22.04 | 314.08 | 666.31 | 125.33 | 0.00 | 0.00 | 0.00 |
July | 318.33 | 16.31 | 302.02 | 675.88 | 80.44 | 0.00 | 0.00 | 0.00 |
August | 282.74 | 3.32 | 279.41 | 619.15 | 60.30 | 0.00 | 0.00 | 0.00 |
September | 213.42 | 0.08 | 213.34 | 359.90 | 183.23 | 0.00 | 0.00 | 0.00 |
October | 162.16 | 0.00 | 162.16 | 155.72 | 460.87 | 0.00 | 0.00 | 0.00 |
November | 145.13 | 0.00 | 145.13 | 72.75 | 662.38 | 0.00 | 0.00 | 0.00 |
December | 125.46 | 0.00 | 125.46 | 15.18 | 901.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 220.59 | 4.42 | 216.17 | 297.28 | 465.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 125.46 | 0.00 | 125.46 | 14.05 | 60.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 336.12 | 22.04 | 314.08 | 675.88 | 1105.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.39 | 0.00 | 19.39 | 2.88 | 155.56 | 0.00 | 0.00 | 0.00 |
February | 21.49 | 0.00 | 21.49 | 10.83 | 125.98 | 0.00 | 0.00 | 0.00 |
March | 30.18 | 0.00 | 30.18 | 27.78 | 73.41 | 0.00 | 0.00 | 0.00 |
April | 36.59 | 0.21 | 36.38 | 54.57 | 53.89 | 0.00 | 0.00 | 0.00 |
May | 43.66 | 1.37 | 42.29 | 82.71 | 33.00 | 0.00 | 0.00 | 0.00 |
June | 48.02 | 3.15 | 44.87 | 114.11 | 19.37 | 0.00 | 0.00 | 0.00 |
July | 45.48 | 2.33 | 43.15 | 117.02 | 12.86 | 0.00 | 0.00 | 0.00 |
August | 40.39 | 0.47 | 39.92 | 108.63 | 9.86 | 0.00 | 0.00 | 0.00 |
September | 30.49 | 0.01 | 30.48 | 66.15 | 25.08 | 0.00 | 0.00 | 0.00 |
October | 23.17 | 0.00 | 23.17 | 30.00 | 63.25 | 0.00 | 0.00 | 0.00 |
November | 20.73 | 0.00 | 20.73 | 15.31 | 91.57 | 0.00 | 0.00 | 0.00 |
December | 17.92 | 0.00 | 17.92 | 3.55 | 125.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.51 | 0.63 | 30.88 | 53.03 | 65.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.92 | 0.00 | 17.92 | 2.88 | 9.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.02 | 3.15 | 44.87 | 117.02 | 155.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.20 | 72.94 | 87.26 | 112.13 | 525.25 | 0.00 | 0.00 | 0.00 |
February | 201.06 | 108.23 | 92.83 | 204.50 | 424.40 | 0.00 | 0.00 | 0.00 |
March | 252.96 | 115.39 | 137.58 | 326.68 | 252.46 | 0.00 | 0.00 | 0.00 |
April | 305.79 | 139.57 | 166.21 | 489.06 | 190.71 | 0.00 | 0.00 | 0.00 |
May | 334.98 | 141.66 | 193.32 | 605.56 | 122.12 | 0.00 | 0.00 | 0.00 |
June | 346.48 | 145.12 | 201.36 | 714.52 | 72.24 | 0.00 | 0.00 | 0.00 |
July | 337.71 | 141.68 | 196.02 | 727.09 | 48.38 | 0.00 | 0.00 | 0.00 |
August | 309.52 | 122.78 | 186.75 | 684.00 | 37.12 | 0.00 | 0.00 | 0.00 |
September | 253.68 | 112.09 | 141.59 | 492.18 | 92.28 | 0.00 | 0.00 | 0.00 |
October | 216.97 | 112.93 | 104.03 | 328.20 | 221.90 | 0.00 | 0.00 | 0.00 |
November | 172.80 | 77.95 | 94.85 | 196.34 | 309.80 | 0.00 | 0.00 | 0.00 |
December | 149.95 | 68.26 | 81.69 | 115.10 | 421.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 253.76 | 113.20 | 140.56 | 417.40 | 225.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 149.95 | 68.26 | 81.69 | 112.13 | 37.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 346.48 | 145.12 | 201.36 | 727.09 | 525.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.95 | 71.51 | 31.43 | 120.55 | 128.58 | 0.00 | 0.00 | 0.00 |
February | 95.90 | 63.98 | 31.92 | 123.36 | 108.00 | 0.00 | 0.00 | 0.00 |
March | 87.69 | 46.02 | 41.68 | 129.79 | 69.22 | 0.00 | 0.00 | 0.00 |
April | 65.99 | 22.02 | 43.98 | 114.65 | 54.24 | 0.00 | 0.00 | 0.00 |
May | 53.05 | 6.49 | 46.56 | 105.11 | 34.05 | 0.00 | 0.00 | 0.00 |
June | 48.71 | 2.72 | 45.99 | 117.59 | 20.09 | 0.00 | 0.00 | 0.00 |
July | 48.86 | 3.30 | 45.57 | 125.04 | 12.99 | 0.00 | 0.00 | 0.00 |
August | 58.88 | 11.07 | 47.81 | 147.34 | 9.87 | 0.00 | 0.00 | 0.00 |
September | 66.47 | 25.86 | 40.61 | 136.07 | 24.81 | 0.00 | 0.00 | 0.00 |
October | 93.34 | 60.33 | 33.01 | 152.99 | 59.66 | 0.00 | 0.00 | 0.00 |
November | 101.97 | 68.05 | 33.93 | 146.89 | 81.64 | 0.00 | 0.00 | 0.00 |
December | 102.22 | 71.91 | 30.31 | 129.69 | 106.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.09 | 37.64 | 39.44 | 129.14 | 58.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.71 | 2.72 | 30.31 | 105.11 | 9.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.95 | 71.91 | 47.81 | 152.99 | 128.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.56 | 0.00 | 24.56 | 2.94 | 187.63 | 0.00 | 0.00 | 0.00 |
February | 27.22 | 0.00 | 27.22 | 10.74 | 151.61 | 0.00 | 0.00 | 0.00 |
March | 38.22 | 0.00 | 38.22 | 25.46 | 90.67 | 0.00 | 0.00 | 0.00 |
April | 46.34 | 0.27 | 46.07 | 51.24 | 69.13 | 0.00 | 0.00 | 0.00 |
May | 55.29 | 1.73 | 53.56 | 79.22 | 42.07 | 0.00 | 0.00 | 0.00 |
June | 60.81 | 3.99 | 56.83 | 115.01 | 22.84 | 0.00 | 0.00 | 0.00 |
July | 57.59 | 2.95 | 54.64 | 116.61 | 14.75 | 0.00 | 0.00 | 0.00 |
August | 51.15 | 0.60 | 50.55 | 105.99 | 11.07 | 0.00 | 0.00 | 0.00 |
September | 38.61 | 0.02 | 38.60 | 59.77 | 34.67 | 0.00 | 0.00 | 0.00 |
October | 29.34 | 0.00 | 29.34 | 25.22 | 82.60 | 0.00 | 0.00 | 0.00 |
November | 26.26 | 0.00 | 26.26 | 12.94 | 113.40 | 0.00 | 0.00 | 0.00 |
December | 22.70 | 0.00 | 22.70 | 3.11 | 150.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.91 | 0.80 | 39.11 | 50.92 | 80.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.70 | 0.00 | 22.70 | 2.94 | 11.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.81 | 3.99 | 56.83 | 116.61 | 187.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.97 | 0.00 | 21.97 | 2.63 | 167.87 | 0.00 | 0.00 | 0.00 |
February | 24.35 | 0.00 | 24.35 | 9.61 | 135.64 | 0.00 | 0.00 | 0.00 |
March | 34.20 | 0.00 | 34.20 | 22.78 | 81.12 | 0.00 | 0.00 | 0.00 |
April | 41.46 | 0.24 | 41.22 | 45.85 | 61.85 | 0.00 | 0.00 | 0.00 |
May | 49.47 | 1.55 | 47.92 | 70.88 | 37.64 | 0.00 | 0.00 | 0.00 |
June | 54.41 | 3.57 | 50.84 | 102.90 | 20.44 | 0.00 | 0.00 | 0.00 |
July | 51.53 | 2.64 | 48.89 | 104.33 | 13.20 | 0.00 | 0.00 | 0.00 |
August | 45.77 | 0.54 | 45.23 | 94.83 | 9.91 | 0.00 | 0.00 | 0.00 |
September | 34.55 | 0.01 | 34.53 | 53.48 | 31.02 | 0.00 | 0.00 | 0.00 |
October | 26.25 | 0.00 | 26.25 | 22.56 | 73.91 | 0.00 | 0.00 | 0.00 |
November | 23.49 | 0.00 | 23.49 | 11.58 | 101.46 | 0.00 | 0.00 | 0.00 |
December | 20.31 | 0.00 | 20.31 | 2.78 | 134.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.71 | 0.72 | 34.99 | 45.56 | 72.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.31 | 0.00 | 20.31 | 2.63 | 9.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.41 | 3.57 | 50.84 | 104.33 | 167.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 384.33 | 266.99 | 117.35 | 435.13 | 450.38 | 0.00 | 0.00 | 0.00 |
February | 358.01 | 238.84 | 119.17 | 440.58 | 379.03 | 0.00 | 0.00 | 0.00 |
March | 327.38 | 171.79 | 155.59 | 444.51 | 249.11 | 0.00 | 0.00 | 0.00 |
April | 246.38 | 82.20 | 164.18 | 371.30 | 205.60 | 0.00 | 0.00 | 0.00 |
May | 198.05 | 24.24 | 173.81 | 318.18 | 131.70 | 0.00 | 0.00 | 0.00 |
June | 181.85 | 10.15 | 171.69 | 353.46 | 72.94 | 0.00 | 0.00 | 0.00 |
July | 182.41 | 12.30 | 170.11 | 375.77 | 45.82 | 0.00 | 0.00 | 0.00 |
August | 219.80 | 41.31 | 178.49 | 456.51 | 33.57 | 0.00 | 0.00 | 0.00 |
September | 248.15 | 96.55 | 151.60 | 431.72 | 101.43 | 0.00 | 0.00 | 0.00 |
October | 348.45 | 225.22 | 123.23 | 519.45 | 226.28 | 0.00 | 0.00 | 0.00 |
November | 380.70 | 254.04 | 126.66 | 514.29 | 293.76 | 0.00 | 0.00 | 0.00 |
December | 381.63 | 268.46 | 113.17 | 465.76 | 371.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 287.78 | 140.54 | 147.25 | 427.22 | 212.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 181.85 | 10.15 | 113.17 | 318.18 | 33.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 384.33 | 268.46 | 178.49 | 519.45 | 450.38 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139459E+10 | 0.968782E+09 | 0.425804E+09 | 0.160650E+10 | 0.150778E+10 |
February | 0.117336E+10 | 0.782797E+09 | 0.390560E+09 | 0.147005E+10 | 0.113829E+10 |
March | 0.118792E+10 | 0.623368E+09 | 0.564555E+09 | 0.164956E+10 | 0.829401E+09 |
April | 0.865158E+09 | 0.288646E+09 | 0.576512E+09 | 0.134513E+10 | 0.643365E+09 |
May | 0.718628E+09 | 87942952.17 | 0.630685E+09 | 0.118682E+10 | 0.425171E+09 |
June | 0.638554E+09 | 35650458.33 | 0.602904E+09 | 0.122906E+10 | 0.249813E+09 |
July | 0.661899E+09 | 44646457.89 | 0.617253E+09 | 0.134212E+10 | 0.166589E+09 |
August | 0.797559E+09 | 0.149894E+09 | 0.647665E+09 | 0.162689E+10 | 0.135680E+09 |
September | 0.871397E+09 | 0.339052E+09 | 0.532345E+09 | 0.152194E+10 | 0.335676E+09 |
October | 0.126439E+10 | 0.817230E+09 | 0.447163E+09 | 0.190603E+10 | 0.754209E+09 |
November | 0.133685E+10 | 0.892082E+09 | 0.444765E+09 | 0.181488E+10 | 0.969077E+09 |
December | 0.138477E+10 | 0.974137E+09 | 0.410633E+09 | 0.170809E+10 | 0.125971E+10 |
Annual Sum or Average | 0.122951E+11 | 0.600423E+10 | 0.629084E+10 | 0.184070E+11 | 0.841476E+10 |
Minimum of Months | 0.638554E+09 | 35650458.33 | 0.390560E+09 | 0.118682E+10 | 0.135680E+09 |
Maximum of Months | 0.139459E+10 | 0.974137E+09 | 0.647665E+09 | 0.190603E+10 | 0.150778E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.392706E+10 | 0.272803E+10 | 0.119904E+10 | 0.451439E+10 | 0.431683E+10 |
February | 0.330410E+10 | 0.220430E+10 | 0.109979E+10 | 0.414598E+10 | 0.325906E+10 |
March | 0.334511E+10 | 0.175536E+10 | 0.158975E+10 | 0.471189E+10 | 0.231824E+10 |
April | 0.243623E+10 | 0.812809E+09 | 0.162342E+10 | 0.390190E+10 | 0.174231E+10 |
May | 0.202361E+10 | 0.247642E+09 | 0.177597E+10 | 0.354317E+10 | 0.108594E+10 |
June | 0.179813E+10 | 0.100389E+09 | 0.169774E+10 | 0.372343E+10 | 0.595171E+09 |
July | 0.186386E+10 | 0.125721E+09 | 0.173814E+10 | 0.404915E+10 | 0.376197E+09 |
August | 0.224587E+10 | 0.422090E+09 | 0.182378E+10 | 0.482317E+10 | 0.294661E+09 |
September | 0.245380E+10 | 0.954749E+09 | 0.149905E+10 | 0.445253E+10 | 0.837231E+09 |
October | 0.356045E+10 | 0.230127E+10 | 0.125918E+10 | 0.544823E+10 | 0.207684E+10 |
November | 0.376447E+10 | 0.251204E+10 | 0.125243E+10 | 0.514160E+10 | 0.273886E+10 |
December | 0.389942E+10 | 0.274311E+10 | 0.115631E+10 | 0.481072E+10 | 0.360971E+10 |
Annual Sum or Average | 0.346221E+11 | 0.169075E+11 | 0.177146E+11 | 0.532662E+11 | 0.232510E+11 |
Minimum of Months | 0.179813E+10 | 0.100389E+09 | 0.109979E+10 | 0.354317E+10 | 0.294661E+09 |
Maximum of Months | 0.392706E+10 | 0.274311E+10 | 0.182378E+10 | 0.544823E+10 | 0.431683E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.510148E+10 | 0.354386E+10 | 0.155762E+10 | 0.593983E+10 | 0.592009E+10 |
February | 0.429221E+10 | 0.286352E+10 | 0.142869E+10 | 0.545646E+10 | 0.448699E+10 |
March | 0.434549E+10 | 0.228032E+10 | 0.206517E+10 | 0.617822E+10 | 0.323659E+10 |
April | 0.316480E+10 | 0.105589E+10 | 0.210891E+10 | 0.508494E+10 | 0.247290E+10 |
May | 0.262878E+10 | 0.321700E+09 | 0.230708E+10 | 0.457218E+10 | 0.158548E+10 |
June | 0.233587E+10 | 0.130411E+09 | 0.220546E+10 | 0.478660E+10 | 0.889883E+09 |
July | 0.242127E+10 | 0.163319E+09 | 0.225795E+10 | 0.521620E+10 | 0.578340E+09 |
August | 0.291752E+10 | 0.548319E+09 | 0.236920E+10 | 0.627111E+10 | 0.446707E+09 |
September | 0.318762E+10 | 0.124027E+10 | 0.194735E+10 | 0.578766E+10 | 0.123364E+10 |
October | 0.462523E+10 | 0.298948E+10 | 0.163575E+10 | 0.714364E+10 | 0.292608E+10 |
November | 0.489026E+10 | 0.326329E+10 | 0.162698E+10 | 0.673825E+10 | 0.382097E+10 |
December | 0.506557E+10 | 0.356345E+10 | 0.150212E+10 | 0.631642E+10 | 0.499797E+10 |
Annual Sum or Average | 0.449761E+11 | 0.219638E+11 | 0.230123E+11 | 0.694915E+11 | 0.325956E+11 |
Minimum of Months | 0.233587E+10 | 0.130411E+09 | 0.142869E+10 | 0.457218E+10 | 0.446707E+09 |
Maximum of Months | 0.510148E+10 | 0.356345E+10 | 0.236920E+10 | 0.714364E+10 | 0.592009E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275734E+09 | 0.191545E+09 | 84189446.79 | 0.321599E+09 | 0.302246E+09 |
February | 0.231994E+09 | 0.154772E+09 | 77221105.23 | 0.293919E+09 | 0.224700E+09 |
March | 0.234874E+09 | 0.123251E+09 | 0.111623E+09 | 0.330193E+09 | 0.154192E+09 |
April | 0.171058E+09 | 57070367.83 | 0.113987E+09 | 0.271319E+09 | 0.115140E+09 |
May | 0.142086E+09 | 17387832.05 | 0.124699E+09 | 0.245987E+09 | 65642008.27 |
June | 0.126255E+09 | 7048707.90 | 0.119206E+09 | 0.265629E+09 | 29479815.68 |
July | 0.130870E+09 | 8827371.52 | 0.122043E+09 | 0.293104E+09 | 14487559.76 |
August | 0.157692E+09 | 29636534.88 | 0.128056E+09 | 0.351986E+09 | 7254387.65 |
September | 0.172291E+09 | 67036435.04 | 0.105255E+09 | 0.317116E+09 | 43777744.04 |
October | 0.249993E+09 | 0.161580E+09 | 88412715.82 | 0.386184E+09 | 0.132152E+09 |
November | 0.264318E+09 | 0.176380E+09 | 87938230.82 | 0.365673E+09 | 0.182348E+09 |
December | 0.273793E+09 | 0.192604E+09 | 81189647.76 | 0.343112E+09 | 0.247264E+09 |
Annual Sum or Average | 0.243096E+10 | 0.118714E+10 | 0.124382E+10 | 0.378582E+10 | 0.151868E+10 |
Minimum of Months | 0.126255E+09 | 7048707.90 | 77221105.23 | 0.245987E+09 | 7254387.65 |
Maximum of Months | 0.275734E+09 | 0.192604E+09 | 0.128056E+09 | 0.386184E+09 | 0.302246E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219849E+09 | 0.102224E+09 | 0.117625E+09 | 0.174021E+09 | 0.636346E+09 |
February | 0.227500E+09 | 0.106626E+09 | 0.120874E+09 | 0.235722E+09 | 0.465398E+09 |
March | 0.369530E+09 | 0.178222E+09 | 0.191308E+09 | 0.476783E+09 | 0.298189E+09 |
April | 0.402975E+09 | 0.184312E+09 | 0.218663E+09 | 0.605924E+09 | 0.211955E+09 |
May | 0.418984E+09 | 0.159021E+09 | 0.259962E+09 | 0.701415E+09 | 0.121568E+09 |
June | 0.425988E+09 | 0.164024E+09 | 0.261964E+09 | 0.813277E+09 | 54722695.76 |
July | 0.414335E+09 | 0.153256E+09 | 0.261080E+09 | 0.831186E+09 | 26835565.28 |
August | 0.406982E+09 | 0.152218E+09 | 0.254764E+09 | 0.822028E+09 | 13521073.76 |
September | 0.321755E+09 | 0.134509E+09 | 0.187246E+09 | 0.560869E+09 | 82029038.49 |
October | 0.295829E+09 | 0.153811E+09 | 0.142018E+09 | 0.422920E+09 | 0.260067E+09 |
November | 0.227376E+09 | 0.101680E+09 | 0.125697E+09 | 0.265106E+09 | 0.374918E+09 |
December | 0.194602E+09 | 85244676.27 | 0.109357E+09 | 0.169373E+09 | 0.520718E+09 |
Annual Sum or Average | 0.392571E+10 | 0.167515E+10 | 0.225056E+10 | 0.607862E+10 | 0.306627E+10 |
Minimum of Months | 0.194602E+09 | 85244676.27 | 0.109357E+09 | 0.169373E+09 | 13521073.76 |
Maximum of Months | 0.425988E+09 | 0.184312E+09 | 0.261964E+09 | 0.831186E+09 | 0.636346E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51932557.31 | 0.00 | 51932557.31 | 8337781.09 | 0.359043E+09 |
February | 51991662.66 | 0.00 | 51991662.66 | 25247879.17 | 0.259236E+09 |
March | 80833881.57 | 1627.95 | 80832253.62 | 63995189.62 | 0.164690E+09 |
April | 94850140.82 | 553965.08 | 94296175.74 | 0.116695E+09 | 0.117494E+09 |
May | 0.116941E+09 | 3667679.90 | 0.113274E+09 | 0.183056E+09 | 66462398.92 |
June | 0.124466E+09 | 8162442.86 | 0.116304E+09 | 0.253149E+09 | 29460807.64 |
July | 0.121807E+09 | 6241532.89 | 0.115565E+09 | 0.267076E+09 | 15774048.78 |
August | 0.108187E+09 | 1270984.59 | 0.106916E+09 | 0.246158E+09 | 8041705.34 |
September | 79030084.51 | 31067.06 | 78999017.45 | 0.137273E+09 | 47478133.84 |
October | 62049703.82 | 0.00 | 62049703.82 | 64971993.85 | 0.142636E+09 |
November | 53740831.96 | 0.00 | 53740831.96 | 34819595.92 | 0.202008E+09 |
December | 48007784.18 | 0.00 | 48007784.18 | 11071765.24 | 0.285078E+09 |
Annual Sum or Average | 0.993838E+09 | 19929300.33 | 0.973909E+09 | 0.141185E+10 | 0.169740E+10 |
Minimum of Months | 48007784.18 | 0.00 | 48007784.18 | 8337781.09 | 8041705.34 |
Maximum of Months | 0.124466E+09 | 8162442.86 | 0.116304E+09 | 0.267076E+09 | 0.359043E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219849E+09 | 0.102224E+09 | 0.117625E+09 | 0.183403E+09 | 0.625546E+09 |
February | 0.227500E+09 | 0.106626E+09 | 0.120874E+09 | 0.243832E+09 | 0.458510E+09 |
March | 0.369530E+09 | 0.178222E+09 | 0.191308E+09 | 0.483324E+09 | 0.296698E+09 |
April | 0.402975E+09 | 0.184312E+09 | 0.218663E+09 | 0.605520E+09 | 0.217972E+09 |
May | 0.418984E+09 | 0.159021E+09 | 0.259962E+09 | 0.695378E+09 | 0.130290E+09 |
June | 0.425988E+09 | 0.164024E+09 | 0.261964E+09 | 0.806300E+09 | 58982455.28 |
July | 0.414335E+09 | 0.153256E+09 | 0.261080E+09 | 0.824273E+09 | 30339666.45 |
August | 0.406982E+09 | 0.152218E+09 | 0.254764E+09 | 0.818729E+09 | 15212175.30 |
September | 0.321755E+09 | 0.134509E+09 | 0.187246E+09 | 0.559698E+09 | 87903454.30 |
October | 0.295829E+09 | 0.153811E+09 | 0.142018E+09 | 0.428818E+09 | 0.260982E+09 |
November | 0.227376E+09 | 0.101680E+09 | 0.125697E+09 | 0.276036E+09 | 0.367556E+09 |
December | 0.194602E+09 | 85244676.27 | 0.109357E+09 | 0.180577E+09 | 0.509494E+09 |
Annual Sum or Average | 0.392571E+10 | 0.167515E+10 | 0.225056E+10 | 0.610589E+10 | 0.305949E+10 |
Minimum of Months | 0.194602E+09 | 85244676.27 | 0.109357E+09 | 0.180577E+09 | 15212175.30 |
Maximum of Months | 0.425988E+09 | 0.184312E+09 | 0.261964E+09 | 0.824273E+09 | 0.625546E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.220544E+09 | 0.153205E+09 | 67338165.69 | 0.248686E+09 | 0.249511E+09 |
February | 0.185558E+09 | 0.123793E+09 | 61764600.87 | 0.218330E+09 | 0.213912E+09 |
March | 0.187862E+09 | 98580876.18 | 89280789.68 | 0.230234E+09 | 0.187670E+09 |
April | 0.136819E+09 | 45647216.27 | 91171836.45 | 0.184177E+09 | 0.149039E+09 |
May | 0.113647E+09 | 13907499.81 | 99739018.35 | 0.160150E+09 | 0.103857E+09 |
June | 0.100984E+09 | 5637845.11 | 95345682.42 | 0.171007E+09 | 63271982.55 |
July | 0.104675E+09 | 7060493.07 | 97614864.41 | 0.188501E+09 | 48032493.25 |
August | 0.126129E+09 | 23704513.72 | 0.102424E+09 | 0.234565E+09 | 41593360.02 |
September | 0.137805E+09 | 53618484.76 | 84186968.45 | 0.218381E+09 | 85235321.39 |
October | 0.199955E+09 | 0.129239E+09 | 70716109.13 | 0.276354E+09 | 0.170947E+09 |
November | 0.211412E+09 | 0.141076E+09 | 70336596.60 | 0.259284E+09 | 0.214476E+09 |
December | 0.218991E+09 | 0.154052E+09 | 64938803.63 | 0.246699E+09 | 0.256961E+09 |
Annual Sum or Average | 0.194438E+10 | 0.949522E+09 | 0.994858E+09 | 0.263637E+10 | 0.178451E+10 |
Minimum of Months | 0.100984E+09 | 5637845.11 | 61764600.87 | 0.160150E+09 | 41593360.02 |
Maximum of Months | 0.220544E+09 | 0.154052E+09 | 0.102424E+09 | 0.276354E+09 | 0.256961E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41551553.01 | 0.00 | 41551553.01 | 5963379.34 | 0.300573E+09 |
February | 41598843.56 | 0.00 | 41598843.56 | 20098928.71 | 0.215687E+09 |
March | 64675677.25 | 1302.53 | 64674374.72 | 53923094.20 | 0.131552E+09 |
April | 75890171.00 | 443230.81 | 75446940.19 | 98837298.87 | 91578591.61 |
May | 93565486.34 | 2934532.86 | 90630953.48 | 0.154134E+09 | 50123733.84 |
June | 99586189.44 | 6530819.87 | 93055369.57 | 0.212705E+09 | 20472135.58 |
July | 97458282.54 | 4993888.19 | 92464394.35 | 0.225126E+09 | 10222376.45 |
August | 86561042.70 | 1016922.46 | 85544120.25 | 0.209766E+09 | 4376459.61 |
September | 63232448.32 | 24856.94 | 63207591.38 | 0.116898E+09 | 35179033.98 |
October | 49646343.09 | 0.00 | 49646343.09 | 55096364.46 | 0.113880E+09 |
November | 42998364.49 | 0.00 | 42998364.49 | 27855514.47 | 0.166355E+09 |
December | 38411318.30 | 0.00 | 38411318.30 | 7610609.99 | 0.239222E+09 |
Annual Sum or Average | 0.795176E+09 | 15945553.66 | 0.779230E+09 | 0.118802E+10 | 0.137922E+10 |
Minimum of Months | 38411318.30 | 0.00 | 38411318.30 | 5963379.34 | 4376459.61 |
Maximum of Months | 99586189.44 | 6530819.87 | 93055369.57 | 0.225126E+09 | 0.300573E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214559E+09 | 97692218.39 | 0.116866E+09 | 0.148093E+09 | 0.617663E+09 |
February | 0.243222E+09 | 0.130930E+09 | 0.112292E+09 | 0.236891E+09 | 0.439864E+09 |
March | 0.338793E+09 | 0.154540E+09 | 0.184254E+09 | 0.403259E+09 | 0.276980E+09 |
April | 0.396326E+09 | 0.180898E+09 | 0.215428E+09 | 0.578351E+09 | 0.195512E+09 |
May | 0.448639E+09 | 0.189725E+09 | 0.258913E+09 | 0.739677E+09 | 0.112226E+09 |
June | 0.449066E+09 | 0.188091E+09 | 0.260975E+09 | 0.848056E+09 | 49854780.43 |
July | 0.452288E+09 | 0.189756E+09 | 0.262532E+09 | 0.892784E+09 | 25842114.74 |
August | 0.414545E+09 | 0.164438E+09 | 0.250107E+09 | 0.836221E+09 | 12726676.08 |
September | 0.328787E+09 | 0.145278E+09 | 0.183509E+09 | 0.570155E+09 | 78041713.82 |
October | 0.290585E+09 | 0.151252E+09 | 0.139332E+09 | 0.395560E+09 | 0.242872E+09 |
November | 0.223962E+09 | 0.101027E+09 | 0.122935E+09 | 0.230948E+09 | 0.346159E+09 |
December | 0.200830E+09 | 91417601.72 | 0.109412E+09 | 0.149773E+09 | 0.489945E+09 |
Annual Sum or Average | 0.400160E+10 | 0.178505E+10 | 0.221656E+10 | 0.602977E+10 | 0.288769E+10 |
Minimum of Months | 0.200830E+09 | 91417601.72 | 0.109412E+09 | 0.148093E+09 | 12726676.08 |
Maximum of Months | 0.452288E+09 | 0.189756E+09 | 0.262532E+09 | 0.892784E+09 | 0.617663E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275734E+09 | 0.191545E+09 | 84189446.79 | 0.320100E+09 | 0.301473E+09 |
February | 0.231994E+09 | 0.154772E+09 | 77221105.23 | 0.291644E+09 | 0.224128E+09 |
March | 0.234874E+09 | 0.123251E+09 | 0.111623E+09 | 0.327833E+09 | 0.152815E+09 |
April | 0.171058E+09 | 57070367.83 | 0.113987E+09 | 0.268963E+09 | 0.114391E+09 |
May | 0.142086E+09 | 17387832.05 | 0.124699E+09 | 0.243669E+09 | 65235254.96 |
June | 0.126255E+09 | 7048707.90 | 0.119206E+09 | 0.263739E+09 | 29090287.57 |
July | 0.130870E+09 | 8827371.52 | 0.122043E+09 | 0.291409E+09 | 14283239.44 |
August | 0.157692E+09 | 29636534.88 | 0.128056E+09 | 0.351195E+09 | 6999602.82 |
September | 0.172291E+09 | 67036435.04 | 0.105255E+09 | 0.315952E+09 | 43309499.78 |
October | 0.249993E+09 | 0.161580E+09 | 88412715.82 | 0.384217E+09 | 0.131236E+09 |
November | 0.264318E+09 | 0.176380E+09 | 87938230.82 | 0.364038E+09 | 0.181534E+09 |
December | 0.273793E+09 | 0.192604E+09 | 81189647.76 | 0.341543E+09 | 0.246741E+09 |
Annual Sum or Average | 0.243096E+10 | 0.118714E+10 | 0.124382E+10 | 0.376430E+10 | 0.151124E+10 |
Minimum of Months | 0.126255E+09 | 7048707.90 | 77221105.23 | 0.243669E+09 | 6999602.82 |
Maximum of Months | 0.275734E+09 | 0.192604E+09 | 0.128056E+09 | 0.384217E+09 | 0.301473E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51932557.31 | 0.00 | 51932557.31 | 7942548.80 | 0.359049E+09 |
February | 51991662.66 | 0.00 | 51991662.66 | 24217163.07 | 0.259498E+09 |
March | 80833881.57 | 1627.95 | 80832253.62 | 62792683.66 | 0.162792E+09 |
April | 94850140.82 | 553965.08 | 94296175.74 | 0.114490E+09 | 0.115985E+09 |
May | 0.116941E+09 | 3667679.90 | 0.113274E+09 | 0.180039E+09 | 65482058.41 |
June | 0.124466E+09 | 8162442.86 | 0.116304E+09 | 0.249832E+09 | 28907538.86 |
July | 0.121807E+09 | 6241532.89 | 0.115565E+09 | 0.263982E+09 | 15693689.32 |
August | 0.108187E+09 | 1270984.59 | 0.106916E+09 | 0.244535E+09 | 7757199.51 |
September | 79030084.51 | 31067.06 | 78999017.45 | 0.135281E+09 | 46895700.69 |
October | 62049703.82 | 0.00 | 62049703.82 | 63115736.32 | 0.141133E+09 |
November | 53740831.96 | 0.00 | 53740831.96 | 34197546.94 | 0.200603E+09 |
December | 48007784.18 | 0.00 | 48007784.18 | 10566840.97 | 0.285136E+09 |
Annual Sum or Average | 0.993838E+09 | 19929300.33 | 0.973909E+09 | 0.139099E+10 | 0.168893E+10 |
Minimum of Months | 48007784.18 | 0.00 | 48007784.18 | 7942548.80 | 7757199.51 |
Maximum of Months | 0.124466E+09 | 8162442.86 | 0.116304E+09 | 0.263982E+09 | 0.359049E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214559E+09 | 97692218.39 | 0.116866E+09 | 0.153529E+09 | 0.602354E+09 |
February | 0.243222E+09 | 0.130930E+09 | 0.112292E+09 | 0.244108E+09 | 0.431280E+09 |
March | 0.338793E+09 | 0.154540E+09 | 0.184254E+09 | 0.411470E+09 | 0.273682E+09 |
April | 0.396326E+09 | 0.180898E+09 | 0.215428E+09 | 0.578980E+09 | 0.200481E+09 |
May | 0.448639E+09 | 0.189725E+09 | 0.258913E+09 | 0.732434E+09 | 0.120011E+09 |
June | 0.449066E+09 | 0.188091E+09 | 0.260975E+09 | 0.837601E+09 | 53555598.17 |
July | 0.452288E+09 | 0.189756E+09 | 0.262532E+09 | 0.882199E+09 | 29192936.96 |
August | 0.414545E+09 | 0.164438E+09 | 0.250107E+09 | 0.830677E+09 | 14142464.15 |
September | 0.328787E+09 | 0.145278E+09 | 0.183509E+09 | 0.566812E+09 | 83271310.13 |
October | 0.290585E+09 | 0.151252E+09 | 0.139332E+09 | 0.401880E+09 | 0.242237E+09 |
November | 0.223962E+09 | 0.101027E+09 | 0.122935E+09 | 0.242432E+09 | 0.336303E+09 |
December | 0.200830E+09 | 91417601.72 | 0.109412E+09 | 0.157972E+09 | 0.474857E+09 |
Annual Sum or Average | 0.400160E+10 | 0.178505E+10 | 0.221656E+10 | 0.604009E+10 | 0.286137E+10 |
Minimum of Months | 0.200830E+09 | 91417601.72 | 0.109412E+09 | 0.153529E+09 | 14142464.15 |
Maximum of Months | 0.452288E+09 | 0.189756E+09 | 0.262532E+09 | 0.882199E+09 | 0.602354E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 65769307.07 | 0.00 | 65769307.07 | 9122976.45 | 0.491226E+09 |
February | 65844160.26 | 0.00 | 65844160.26 | 31064889.17 | 0.350799E+09 |
March | 0.102371E+09 | 2061.70 | 0.102369E+09 | 84373111.23 | 0.216724E+09 |
April | 0.120122E+09 | 701561.82 | 0.119420E+09 | 0.155131E+09 | 0.155199E+09 |
May | 0.148099E+09 | 4644885.18 | 0.143454E+09 | 0.241205E+09 | 91106456.07 |
June | 0.157629E+09 | 10337218.86 | 0.147291E+09 | 0.322659E+09 | 47415134.59 |
July | 0.154261E+09 | 7904507.59 | 0.146356E+09 | 0.334397E+09 | 30584357.82 |
August | 0.137012E+09 | 1609621.79 | 0.135402E+09 | 0.304809E+09 | 21004204.39 |
September | 0.100087E+09 | 39344.47 | 0.100047E+09 | 0.175026E+09 | 72201377.71 |
October | 78582034.76 | 0.00 | 78582034.76 | 83348405.03 | 0.193648E+09 |
November | 68059372.82 | 0.00 | 68059372.82 | 43204429.71 | 0.270666E+09 |
December | 60798829.53 | 0.00 | 60798829.53 | 11007718.10 | 0.389030E+09 |
Annual Sum or Average | 0.125863E+10 | 25239201.40 | 0.123339E+10 | 0.179535E+10 | 0.232960E+10 |
Minimum of Months | 60798829.53 | 0.00 | 60798829.53 | 9122976.45 | 21004204.39 |
Maximum of Months | 0.157629E+09 | 10337218.86 | 0.147291E+09 | 0.334397E+09 | 0.491226E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24245289.88 | 0.00 | 24245289.88 | 3363106.87 | 0.181086E+09 |
February | 24272883.86 | 0.00 | 24272883.86 | 11451804.44 | 0.129319E+09 |
March | 37738193.39 | 760.03 | 37737433.36 | 31103422.42 | 79893380.47 |
April | 44281839.34 | 258624.74 | 44023214.60 | 57187838.31 | 57212664.06 |
May | 54595368.27 | 1712297.01 | 52883071.26 | 88917985.81 | 33585612.13 |
June | 58108442.55 | 3810726.90 | 54297715.64 | 0.118946E+09 | 17479181.92 |
July | 56866810.98 | 2913928.80 | 53952882.19 | 0.123273E+09 | 11274660.69 |
August | 50508282.37 | 593373.24 | 49914909.13 | 0.112365E+09 | 7743019.45 |
September | 36896070.74 | 14504.00 | 36881566.74 | 64521839.26 | 26616417.45 |
October | 28968591.84 | 0.00 | 28968591.84 | 30725673.28 | 71386509.59 |
November | 25089502.94 | 0.00 | 25089502.94 | 15926941.75 | 99778526.01 |
December | 22412966.05 | 0.00 | 22412966.05 | 4057900.68 | 0.143412E+09 |
Annual Sum or Average | 0.463984E+09 | 9304214.71 | 0.454680E+09 | 0.661840E+09 | 0.858788E+09 |
Minimum of Months | 22412966.05 | 0.00 | 22412966.05 | 3363106.87 | 7743019.45 |
Maximum of Months | 58108442.55 | 3810726.90 | 54297715.64 | 0.123273E+09 | 0.181086E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128657E+09 | 89374067.16 | 39282456.62 | 0.148622E+09 | 0.148090E+09 |
February | 0.108247E+09 | 72216185.45 | 36031056.52 | 0.137247E+09 | 0.109677E+09 |
March | 0.109591E+09 | 57508234.04 | 52082926.70 | 0.157033E+09 | 74734550.55 |
April | 79814893.20 | 26628803.66 | 53186089.54 | 0.129332E+09 | 57754608.55 |
May | 66296941.32 | 8113092.37 | 58183848.95 | 0.116959E+09 | 35597407.68 |
June | 58909847.01 | 3288898.70 | 55620948.31 | 0.123170E+09 | 18837743.70 |
July | 61063516.46 | 4118815.98 | 56944700.48 | 0.133751E+09 | 11772562.98 |
August | 73578575.46 | 13828287.75 | 59750287.71 | 0.160760E+09 | 7880692.16 |
September | 80390320.73 | 31278930.45 | 49111390.28 | 0.147938E+09 | 26392796.86 |
October | 0.116646E+09 | 75392769.76 | 41253016.93 | 0.182019E+09 | 66649735.46 |
November | 0.123330E+09 | 82298153.11 | 41031624.14 | 0.172714E+09 | 88054311.92 |
December | 0.127751E+09 | 89868054.48 | 37882762.48 | 0.159717E+09 | 0.120323E+09 |
Annual Sum or Average | 0.113428E+10 | 0.553914E+09 | 0.580361E+09 | 0.176926E+10 | 0.765764E+09 |
Minimum of Months | 58909847.01 | 3288898.70 | 36031056.52 | 0.116959E+09 | 7880692.16 |
Maximum of Months | 0.128657E+09 | 89868054.48 | 59750287.71 | 0.182019E+09 | 0.148090E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.349200E+09 | 0.242579E+09 | 0.106621E+09 | 0.403391E+09 | 0.401948E+09 |
February | 0.293805E+09 | 0.196009E+09 | 97795657.39 | 0.372517E+09 | 0.297685E+09 |
March | 0.297453E+09 | 0.156089E+09 | 0.141364E+09 | 0.426220E+09 | 0.202845E+09 |
April | 0.216634E+09 | 72276019.92 | 0.144358E+09 | 0.351034E+09 | 0.156758E+09 |
May | 0.179943E+09 | 22020592.18 | 0.157923E+09 | 0.317450E+09 | 96618645.72 |
June | 0.159893E+09 | 8926743.81 | 0.150967E+09 | 0.334308E+09 | 51129489.59 |
July | 0.165739E+09 | 11179309.05 | 0.154560E+09 | 0.363027E+09 | 31953143.95 |
August | 0.199707E+09 | 37532801.47 | 0.162175E+09 | 0.436335E+09 | 21389808.09 |
September | 0.218196E+09 | 84897415.22 | 0.133298E+09 | 0.401535E+09 | 71635449.20 |
October | 0.316601E+09 | 0.204631E+09 | 0.111969E+09 | 0.494037E+09 | 0.180901E+09 |
November | 0.334742E+09 | 0.223374E+09 | 0.111368E+09 | 0.468780E+09 | 0.238997E+09 |
December | 0.346742E+09 | 0.243920E+09 | 0.102822E+09 | 0.433505E+09 | 0.326581E+09 |
Annual Sum or Average | 0.307866E+10 | 0.150344E+10 | 0.157522E+10 | 0.480214E+10 | 0.207844E+10 |
Minimum of Months | 0.159893E+09 | 8926743.81 | 97795657.39 | 0.317450E+09 | 21389808.09 |
Maximum of Months | 0.349200E+09 | 0.243920E+09 | 0.162175E+09 | 0.494037E+09 | 0.401948E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275734E+09 | 0.191545E+09 | 84189446.79 | 0.320699E+09 | 0.300417E+09 |
February | 0.231994E+09 | 0.154772E+09 | 77221105.23 | 0.292403E+09 | 0.223086E+09 |
March | 0.234874E+09 | 0.123251E+09 | 0.111623E+09 | 0.327401E+09 | 0.152448E+09 |
April | 0.171058E+09 | 57070367.83 | 0.113987E+09 | 0.268535E+09 | 0.113823E+09 |
May | 0.142086E+09 | 17387832.05 | 0.124699E+09 | 0.242992E+09 | 64576079.83 |
June | 0.126255E+09 | 7048707.90 | 0.119206E+09 | 0.263721E+09 | 28305346.99 |
July | 0.130870E+09 | 8827371.52 | 0.122043E+09 | 0.291281E+09 | 13468064.25 |
August | 0.157692E+09 | 29636534.88 | 0.128056E+09 | 0.349968E+09 | 6428926.90 |
September | 0.172291E+09 | 67036435.04 | 0.105255E+09 | 0.315015E+09 | 42210839.50 |
October | 0.249993E+09 | 0.161580E+09 | 88412715.82 | 0.383757E+09 | 0.129937E+09 |
November | 0.264318E+09 | 0.176380E+09 | 87938230.82 | 0.364044E+09 | 0.180231E+09 |
December | 0.273793E+09 | 0.192604E+09 | 81189647.76 | 0.342009E+09 | 0.245016E+09 |
Annual Sum or Average | 0.243096E+10 | 0.118714E+10 | 0.124382E+10 | 0.376182E+10 | 0.149995E+10 |
Minimum of Months | 0.126255E+09 | 7048707.90 | 77221105.23 | 0.242992E+09 | 6428926.90 |
Maximum of Months | 0.275734E+09 | 0.192604E+09 | 0.128056E+09 | 0.383757E+09 | 0.300417E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219849E+09 | 0.102224E+09 | 0.117625E+09 | 0.173986E+09 | 0.632610E+09 |
February | 0.227500E+09 | 0.106626E+09 | 0.120874E+09 | 0.234353E+09 | 0.461664E+09 |
March | 0.369530E+09 | 0.178222E+09 | 0.191308E+09 | 0.472018E+09 | 0.294341E+09 |
April | 0.402975E+09 | 0.184312E+09 | 0.218663E+09 | 0.599881E+09 | 0.209334E+09 |
May | 0.418984E+09 | 0.159021E+09 | 0.259962E+09 | 0.694188E+09 | 0.119476E+09 |
June | 0.425988E+09 | 0.164024E+09 | 0.261964E+09 | 0.806887E+09 | 52354219.53 |
July | 0.414335E+09 | 0.153256E+09 | 0.261080E+09 | 0.825890E+09 | 24895690.24 |
August | 0.406982E+09 | 0.152218E+09 | 0.254764E+09 | 0.817032E+09 | 11989924.06 |
September | 0.321755E+09 | 0.134509E+09 | 0.187246E+09 | 0.557056E+09 | 78888588.88 |
October | 0.295829E+09 | 0.153811E+09 | 0.142018E+09 | 0.419669E+09 | 0.255260E+09 |
November | 0.227376E+09 | 0.101680E+09 | 0.125697E+09 | 0.263487E+09 | 0.370322E+09 |
December | 0.194602E+09 | 85244676.27 | 0.109357E+09 | 0.169390E+09 | 0.515588E+09 |
Annual Sum or Average | 0.392571E+10 | 0.167515E+10 | 0.225056E+10 | 0.603384E+10 | 0.302672E+10 |
Minimum of Months | 0.194602E+09 | 85244676.27 | 0.109357E+09 | 0.169390E+09 | 11989924.06 |
Maximum of Months | 0.425988E+09 | 0.184312E+09 | 0.261964E+09 | 0.825890E+09 | 0.632610E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51932557.31 | 0.00 | 51932557.31 | 8658783.01 | 0.357261E+09 |
February | 51991662.66 | 0.00 | 51991662.66 | 25611931.82 | 0.257422E+09 |
March | 80833881.57 | 1627.95 | 80832253.62 | 63804932.40 | 0.162973E+09 |
April | 94850140.82 | 553965.08 | 94296175.74 | 0.115206E+09 | 0.117091E+09 |
May | 0.116941E+09 | 3667679.90 | 0.113274E+09 | 0.180471E+09 | 66319811.71 |
June | 0.124466E+09 | 8162442.86 | 0.116304E+09 | 0.251513E+09 | 28578389.81 |
July | 0.121807E+09 | 6241532.89 | 0.115565E+09 | 0.265570E+09 | 14962128.34 |
August | 0.108187E+09 | 1270984.59 | 0.106916E+09 | 0.245052E+09 | 7183489.26 |
September | 79030084.51 | 31067.06 | 78999017.45 | 0.136599E+09 | 45887318.12 |
October | 62049703.82 | 0.00 | 62049703.82 | 65267578.73 | 0.140278E+09 |
November | 53740831.96 | 0.00 | 53740831.96 | 35588018.66 | 0.199158E+09 |
December | 48007784.18 | 0.00 | 48007784.18 | 11895586.04 | 0.281949E+09 |
Annual Sum or Average | 0.993838E+09 | 19929300.33 | 0.973909E+09 | 0.140524E+10 | 0.167906E+10 |
Minimum of Months | 48007784.18 | 0.00 | 48007784.18 | 8658783.01 | 7183489.26 |
Maximum of Months | 0.124466E+09 | 8162442.86 | 0.116304E+09 | 0.265570E+09 | 0.357261E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219849E+09 | 0.102224E+09 | 0.117625E+09 | 0.183371E+09 | 0.622675E+09 |
February | 0.227500E+09 | 0.106626E+09 | 0.120874E+09 | 0.242778E+09 | 0.455094E+09 |
March | 0.369530E+09 | 0.178222E+09 | 0.191308E+09 | 0.479271E+09 | 0.293062E+09 |
April | 0.402975E+09 | 0.184312E+09 | 0.218663E+09 | 0.599056E+09 | 0.216864E+09 |
May | 0.418984E+09 | 0.159021E+09 | 0.259962E+09 | 0.687522E+09 | 0.129478E+09 |
June | 0.425988E+09 | 0.164024E+09 | 0.261964E+09 | 0.799930E+09 | 56876229.26 |
July | 0.414335E+09 | 0.153256E+09 | 0.261080E+09 | 0.819031E+09 | 28423106.43 |
August | 0.406982E+09 | 0.152218E+09 | 0.254764E+09 | 0.813880E+09 | 13540732.63 |
September | 0.321755E+09 | 0.134509E+09 | 0.187246E+09 | 0.556055E+09 | 84846218.58 |
October | 0.295829E+09 | 0.153811E+09 | 0.142018E+09 | 0.426438E+09 | 0.256328E+09 |
November | 0.227376E+09 | 0.101680E+09 | 0.125697E+09 | 0.275810E+09 | 0.362341E+09 |
December | 0.194602E+09 | 85244676.27 | 0.109357E+09 | 0.181616E+09 | 0.504530E+09 |
Annual Sum or Average | 0.392571E+10 | 0.167515E+10 | 0.225056E+10 | 0.606476E+10 | 0.302406E+10 |
Minimum of Months | 0.194602E+09 | 85244676.27 | 0.109357E+09 | 0.181616E+09 | 13540732.63 |
Maximum of Months | 0.425988E+09 | 0.184312E+09 | 0.261964E+09 | 0.819031E+09 | 0.622675E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.404391E+09 | 0.280919E+09 | 0.123472E+09 | 0.449428E+09 | 0.460141E+09 |
February | 0.340241E+09 | 0.226989E+09 | 0.113252E+09 | 0.414606E+09 | 0.341292E+09 |
March | 0.344465E+09 | 0.180759E+09 | 0.163706E+09 | 0.472734E+09 | 0.228373E+09 |
April | 0.250873E+09 | 83699171.49 | 0.167174E+09 | 0.394258E+09 | 0.165616E+09 |
May | 0.208383E+09 | 25500924.42 | 0.182882E+09 | 0.362509E+09 | 91444489.64 |
June | 0.185164E+09 | 10337606.61 | 0.174827E+09 | 0.396808E+09 | 38364002.15 |
July | 0.191934E+09 | 12946187.50 | 0.178988E+09 | 0.438319E+09 | 17575740.95 |
August | 0.231271E+09 | 43464822.63 | 0.187806E+09 | 0.523489E+09 | 7999419.11 |
September | 0.252681E+09 | 98315365.50 | 0.154366E+09 | 0.464487E+09 | 60721067.03 |
October | 0.366639E+09 | 0.236973E+09 | 0.129666E+09 | 0.556017E+09 | 0.196093E+09 |
November | 0.387648E+09 | 0.258678E+09 | 0.128970E+09 | 0.520063E+09 | 0.276461E+09 |
December | 0.401544E+09 | 0.282472E+09 | 0.119072E+09 | 0.481591E+09 | 0.377564E+09 |
Annual Sum or Average | 0.356523E+10 | 0.174105E+10 | 0.182418E+10 | 0.547431E+10 | 0.226165E+10 |
Minimum of Months | 0.185164E+09 | 10337606.61 | 0.113252E+09 | 0.362509E+09 | 7999419.11 |
Maximum of Months | 0.404391E+09 | 0.282472E+09 | 0.187806E+09 | 0.556017E+09 | 0.460141E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.363514E+09 | 0.00 | 0.363514E+09 | 42731733.08 | 0.286163E+10 |
February | 0.363928E+09 | 0.00 | 0.363928E+09 | 0.153876E+09 | 0.208419E+10 |
March | 0.565816E+09 | 11395.24 | 0.565804E+09 | 0.419883E+09 | 0.133943E+10 |
April | 0.663926E+09 | 3877608.68 | 0.660048E+09 | 0.814147E+09 | 0.952427E+09 |
May | 0.818558E+09 | 25672786.98 | 0.792886E+09 | 0.128936E+10 | 0.578727E+09 |
June | 0.871231E+09 | 57134936.06 | 0.814096E+09 | 0.177090E+10 | 0.303106E+09 |
July | 0.852615E+09 | 43689075.52 | 0.808926E+09 | 0.185638E+10 | 0.196489E+09 |
August | 0.757280E+09 | 8896555.21 | 0.748384E+09 | 0.170321E+10 | 0.142433E+09 |
September | 0.553190E+09 | 217461.16 | 0.552972E+09 | 0.967048E+09 | 0.442692E+09 |
October | 0.434331E+09 | 0.00 | 0.434331E+09 | 0.441456E+09 | 0.117598E+10 |
November | 0.376172E+09 | 0.00 | 0.376172E+09 | 0.209409E+09 | 0.164057E+10 |
December | 0.336042E+09 | 0.00 | 0.336042E+09 | 48652920.99 | 0.231295E+10 |
Annual Sum or Average | 0.695660E+10 | 0.139500E+09 | 0.681710E+10 | 0.971706E+10 | 0.140306E+11 |
Minimum of Months | 0.336042E+09 | 0.00 | 0.336042E+09 | 42731733.08 | 0.142433E+09 |
Maximum of Months | 0.871231E+09 | 57134936.06 | 0.814096E+09 | 0.185638E+10 | 0.286163E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.363514E+09 | 0.00 | 0.363514E+09 | 37640511.60 | 0.296043E+10 |
February | 0.363928E+09 | 0.00 | 0.363928E+09 | 0.142101E+09 | 0.216645E+10 |
March | 0.565816E+09 | 11395.24 | 0.565804E+09 | 0.390918E+09 | 0.140516E+10 |
April | 0.663926E+09 | 3877608.68 | 0.660048E+09 | 0.780020E+09 | 0.995983E+09 |
May | 0.818558E+09 | 25672786.98 | 0.792886E+09 | 0.124962E+10 | 0.610113E+09 |
June | 0.871231E+09 | 57134936.06 | 0.814096E+09 | 0.172708E+10 | 0.324854E+09 |
July | 0.852615E+09 | 43689075.52 | 0.808926E+09 | 0.181027E+10 | 0.215439E+09 |
August | 0.757280E+09 | 8896555.21 | 0.748384E+09 | 0.165834E+10 | 0.161505E+09 |
September | 0.553190E+09 | 217461.16 | 0.552972E+09 | 0.932866E+09 | 0.474933E+09 |
October | 0.434331E+09 | 0.00 | 0.434331E+09 | 0.417069E+09 | 0.123439E+10 |
November | 0.376172E+09 | 0.00 | 0.376172E+09 | 0.188571E+09 | 0.171689E+10 |
December | 0.336042E+09 | 0.00 | 0.336042E+09 | 40670282.04 | 0.241415E+10 |
Annual Sum or Average | 0.695660E+10 | 0.139500E+09 | 0.681710E+10 | 0.937516E+10 | 0.146803E+11 |
Minimum of Months | 0.336042E+09 | 0.00 | 0.336042E+09 | 37640511.60 | 0.161505E+09 |
Maximum of Months | 0.871231E+09 | 57134936.06 | 0.814096E+09 | 0.181027E+10 | 0.296043E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51932557.31 | 0.00 | 51932557.31 | 7723473.96 | 0.416655E+09 |
February | 51991662.66 | 0.00 | 51991662.66 | 26209866.37 | 0.304774E+09 |
March | 80833881.57 | 1627.95 | 80832253.62 | 74398586.00 | 0.196629E+09 |
April | 94850140.82 | 553965.08 | 94296175.74 | 0.141438E+09 | 0.139671E+09 |
May | 0.116941E+09 | 3667679.90 | 0.113274E+09 | 0.221525E+09 | 88384334.18 |
June | 0.124466E+09 | 8162442.86 | 0.116304E+09 | 0.295767E+09 | 50213585.69 |
July | 0.121807E+09 | 6241532.89 | 0.115565E+09 | 0.313424E+09 | 34434077.96 |
August | 0.108187E+09 | 1270984.59 | 0.106916E+09 | 0.290943E+09 | 26412719.91 |
September | 79030084.51 | 31067.06 | 78999017.45 | 0.171459E+09 | 64995898.14 |
October | 62049703.82 | 0.00 | 62049703.82 | 80343189.86 | 0.169398E+09 |
November | 53740831.96 | 0.00 | 53740831.96 | 39681030.07 | 0.237360E+09 |
December | 48007784.18 | 0.00 | 48007784.18 | 9521541.73 | 0.336487E+09 |
Annual Sum or Average | 0.993838E+09 | 19929300.33 | 0.973909E+09 | 0.167243E+10 | 0.206542E+10 |
Minimum of Months | 48007784.18 | 0.00 | 48007784.18 | 7723473.96 | 26412719.91 |
Maximum of Months | 0.124466E+09 | 8162442.86 | 0.116304E+09 | 0.313424E+09 | 0.416655E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.429087E+09 | 0.195371E+09 | 0.233716E+09 | 0.300335E+09 | 0.140683E+10 |
February | 0.486410E+09 | 0.261841E+09 | 0.224569E+09 | 0.494718E+09 | 0.102672E+10 |
March | 0.677538E+09 | 0.309057E+09 | 0.368481E+09 | 0.874970E+09 | 0.676184E+09 |
April | 0.792596E+09 | 0.361770E+09 | 0.430826E+09 | 0.126766E+10 | 0.494311E+09 |
May | 0.897213E+09 | 0.379424E+09 | 0.517790E+09 | 0.162194E+10 | 0.327086E+09 |
June | 0.898068E+09 | 0.376155E+09 | 0.521913E+09 | 0.185205E+10 | 0.187234E+09 |
July | 0.904512E+09 | 0.379485E+09 | 0.525027E+09 | 0.194744E+10 | 0.129581E+09 |
August | 0.829031E+09 | 0.328853E+09 | 0.500178E+09 | 0.183202E+10 | 99408958.10 |
September | 0.657527E+09 | 0.290535E+09 | 0.366992E+09 | 0.127572E+10 | 0.239184E+09 |
October | 0.581128E+09 | 0.302483E+09 | 0.278645E+09 | 0.879047E+09 | 0.594337E+09 |
November | 0.447892E+09 | 0.202040E+09 | 0.245852E+09 | 0.508914E+09 | 0.803012E+09 |
December | 0.401631E+09 | 0.182822E+09 | 0.218809E+09 | 0.308284E+09 | 0.112888E+10 |
Annual Sum or Average | 0.800263E+10 | 0.356984E+10 | 0.443280E+10 | 0.131631E+11 | 0.711277E+10 |
Minimum of Months | 0.401631E+09 | 0.182822E+09 | 0.218809E+09 | 0.300335E+09 | 99408958.10 |
Maximum of Months | 0.904512E+09 | 0.379485E+09 | 0.525027E+09 | 0.194744E+10 | 0.140683E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275734E+09 | 0.191545E+09 | 84189446.79 | 0.322870E+09 | 0.344392E+09 |
February | 0.231994E+09 | 0.154772E+09 | 77221105.23 | 0.298428E+09 | 0.261271E+09 |
March | 0.234874E+09 | 0.123251E+09 | 0.111623E+09 | 0.347629E+09 | 0.185409E+09 |
April | 0.171058E+09 | 57070367.83 | 0.113987E+09 | 0.297178E+09 | 0.140601E+09 |
May | 0.142086E+09 | 17387832.05 | 0.124699E+09 | 0.281533E+09 | 91204690.25 |
June | 0.126255E+09 | 7048707.90 | 0.119206E+09 | 0.304801E+09 | 52085076.01 |
July | 0.130870E+09 | 8827371.52 | 0.122043E+09 | 0.334918E+09 | 34804630.75 |
August | 0.157692E+09 | 29636534.88 | 0.128056E+09 | 0.394630E+09 | 26439362.89 |
September | 0.172291E+09 | 67036435.04 | 0.105255E+09 | 0.352705E+09 | 64313113.92 |
October | 0.249993E+09 | 0.161580E+09 | 88412715.82 | 0.409766E+09 | 0.159793E+09 |
November | 0.264318E+09 | 0.176380E+09 | 87938230.82 | 0.380731E+09 | 0.211610E+09 |
December | 0.273793E+09 | 0.192604E+09 | 81189647.76 | 0.347358E+09 | 0.285581E+09 |
Annual Sum or Average | 0.243096E+10 | 0.118714E+10 | 0.124382E+10 | 0.407255E+10 | 0.185750E+10 |
Minimum of Months | 0.126255E+09 | 7048707.90 | 77221105.23 | 0.281533E+09 | 26439362.89 |
Maximum of Months | 0.275734E+09 | 0.192604E+09 | 0.128056E+09 | 0.409766E+09 | 0.344392E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 65769307.07 | 0.00 | 65769307.07 | 7866316.88 | 0.502541E+09 |
February | 65844160.26 | 0.00 | 65844160.26 | 25972857.55 | 0.366765E+09 |
March | 0.102371E+09 | 2061.70 | 0.102369E+09 | 68203034.55 | 0.242842E+09 |
April | 0.120122E+09 | 701561.82 | 0.119420E+09 | 0.132819E+09 | 0.179179E+09 |
May | 0.148099E+09 | 4644885.18 | 0.143454E+09 | 0.212181E+09 | 0.112684E+09 |
June | 0.157629E+09 | 10337218.86 | 0.147291E+09 | 0.298108E+09 | 59204945.40 |
July | 0.154261E+09 | 7904507.59 | 0.146356E+09 | 0.312339E+09 | 39518370.30 |
August | 0.137012E+09 | 1609621.79 | 0.135402E+09 | 0.283880E+09 | 29652573.41 |
September | 0.100087E+09 | 39344.47 | 0.100047E+09 | 0.154936E+09 | 89876634.84 |
October | 78582034.76 | 0.00 | 78582034.76 | 67546892.46 | 0.221247E+09 |
November | 68059372.82 | 0.00 | 68059372.82 | 33547162.77 | 0.293934E+09 |
December | 60798829.53 | 0.00 | 60798829.53 | 8317973.03 | 0.403737E+09 |
Annual Sum or Average | 0.125863E+10 | 25239201.40 | 0.123339E+10 | 0.160572E+10 | 0.254118E+10 |
Minimum of Months | 60798829.53 | 0.00 | 60798829.53 | 7866316.88 | 29652573.41 |
Maximum of Months | 0.157629E+09 | 10337218.86 | 0.147291E+09 | 0.312339E+09 | 0.502541E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58844048.24 | 0.00 | 58844048.24 | 7038023.52 | 0.449617E+09 |
February | 58911019.67 | 0.00 | 58911019.67 | 23238014.06 | 0.328146E+09 |
March | 91591731.14 | 1844.61 | 91589886.53 | 61021513.43 | 0.217271E+09 |
April | 0.107473E+09 | 627690.02 | 0.106846E+09 | 0.118834E+09 | 0.160312E+09 |
May | 0.132505E+09 | 4155796.37 | 0.128349E+09 | 0.189839E+09 | 0.100819E+09 |
June | 0.141031E+09 | 9248748.88 | 0.131782E+09 | 0.266719E+09 | 52970888.98 |
July | 0.138017E+09 | 7072192.89 | 0.130945E+09 | 0.279450E+09 | 35357235.64 |
August | 0.122585E+09 | 1440134.72 | 0.121145E+09 | 0.253989E+09 | 26530269.78 |
September | 89547874.12 | 35201.64 | 89512672.48 | 0.138622E+09 | 80412965.73 |
October | 70307644.25 | 0.00 | 70307644.25 | 60434460.62 | 0.197950E+09 |
November | 60892978.73 | 0.00 | 60892978.73 | 30014773.64 | 0.262982E+09 |
December | 54396943.15 | 0.00 | 54396943.15 | 7442121.99 | 0.361210E+09 |
Annual Sum or Average | 0.112610E+10 | 22581609.12 | 0.110352E+10 | 0.143664E+10 | 0.227358E+10 |
Minimum of Months | 54396943.15 | 0.00 | 54396943.15 | 7038023.52 | 26530269.78 |
Maximum of Months | 0.141031E+09 | 9248748.88 | 0.131782E+09 | 0.279450E+09 | 0.449617E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102940E+10 | 0.715094E+09 | 0.314304E+09 | 0.116546E+10 | 0.120630E+10 |
February | 0.866101E+09 | 0.577812E+09 | 0.288289E+09 | 0.106585E+10 | 0.916940E+09 |
March | 0.876854E+09 | 0.460131E+09 | 0.416723E+09 | 0.119057E+10 | 0.667217E+09 |
April | 0.638610E+09 | 0.213061E+09 | 0.425549E+09 | 0.962404E+09 | 0.532915E+09 |
May | 0.530451E+09 | 64913958.36 | 0.465537E+09 | 0.852220E+09 | 0.352750E+09 |
June | 0.471346E+09 | 26314927.01 | 0.445031E+09 | 0.916171E+09 | 0.189056E+09 |
July | 0.488578E+09 | 32955208.31 | 0.455622E+09 | 0.100645E+10 | 0.122717E+09 |
August | 0.588712E+09 | 0.110642E+09 | 0.478070E+09 | 0.122272E+10 | 89902104.38 |
September | 0.643214E+09 | 0.250267E+09 | 0.392947E+09 | 0.111901E+10 | 0.262915E+09 |
October | 0.933299E+09 | 0.603228E+09 | 0.330071E+09 | 0.139129E+10 | 0.606064E+09 |
November | 0.986778E+09 | 0.658479E+09 | 0.328300E+09 | 0.133304E+10 | 0.761432E+09 |
December | 0.102215E+10 | 0.719047E+09 | 0.303105E+09 | 0.124750E+10 | 0.993847E+09 |
Annual Sum or Average | 0.907549E+10 | 0.443194E+10 | 0.464355E+10 | 0.134727E+11 | 0.670205E+10 |
Minimum of Months | 0.471346E+09 | 26314927.01 | 0.288289E+09 | 0.852220E+09 | 89902104.38 |
Maximum of Months | 0.102940E+10 | 0.719047E+09 | 0.478070E+09 | 0.139129E+10 | 0.120630E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 599.80 | 562.94 | 520.68 | 361.70 | 158.98 | 0.00 | 0.00 |
February | 607.66 | 470.52 | 485.02 | 323.58 | 161.44 | 0.00 | 0.00 |
March | 615.87 | 309.66 | 443.52 | 232.74 | 210.78 | 0.00 | 0.00 |
April | 518.95 | 248.21 | 333.78 | 111.36 | 222.42 | 0.00 | 0.00 |
May | 443.11 | 158.74 | 268.30 | 32.83 | 235.47 | 0.00 | 0.00 |
June | 474.17 | 96.38 | 246.36 | 13.75 | 232.60 | 0.00 | 0.00 |
July | 501.09 | 62.20 | 247.12 | 16.67 | 230.46 | 0.00 | 0.00 |
August | 607.41 | 50.66 | 297.77 | 55.96 | 241.81 | 0.00 | 0.00 |
September | 587.17 | 129.50 | 336.19 | 130.81 | 205.38 | 0.00 | 0.00 |
October | 711.63 | 281.59 | 472.07 | 305.12 | 166.95 | 0.00 | 0.00 |
November | 700.18 | 373.87 | 515.76 | 344.17 | 171.59 | 0.00 | 0.00 |
December | 637.73 | 470.32 | 517.01 | 363.70 | 153.31 | 0.00 | 0.00 |
Annual Sum or Average | 583.68 | 266.83 | 389.87 | 190.39 | 199.48 | 0.00 | 0.00 |
Minimum of Months | 443.11 | 50.66 | 246.36 | 13.75 | 153.31 | 0.00 | 0.00 |
Maximum of Months | 711.63 | 562.94 | 520.68 | 363.70 | 241.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1685.48 | 1611.72 | 1466.20 | 1018.53 | 447.67 | 0.00 | 0.00 |
February | 1713.78 | 1347.16 | 1365.78 | 911.17 | 454.61 | 0.00 | 0.00 |
March | 1759.22 | 865.53 | 1248.92 | 655.38 | 593.54 | 0.00 | 0.00 |
April | 1505.36 | 672.19 | 939.90 | 313.58 | 626.32 | 0.00 | 0.00 |
May | 1322.87 | 405.44 | 755.53 | 92.46 | 663.07 | 0.00 | 0.00 |
June | 1436.51 | 229.62 | 693.72 | 38.73 | 654.99 | 0.00 | 0.00 |
July | 1511.78 | 140.46 | 695.89 | 46.94 | 648.95 | 0.00 | 0.00 |
August | 1800.77 | 110.01 | 838.51 | 157.59 | 680.92 | 0.00 | 0.00 |
September | 1717.80 | 323.01 | 946.68 | 368.34 | 578.34 | 0.00 | 0.00 |
October | 2034.14 | 775.40 | 1329.32 | 859.19 | 470.13 | 0.00 | 0.00 |
November | 1983.64 | 1056.66 | 1452.34 | 969.15 | 483.19 | 0.00 | 0.00 |
December | 1796.12 | 1347.71 | 1455.88 | 1024.16 | 431.72 | 0.00 | 0.00 |
Annual Sum or Average | 1689.06 | 737.29 | 1097.86 | 536.13 | 561.73 | 0.00 | 0.00 |
Minimum of Months | 1322.87 | 110.01 | 693.72 | 38.73 | 431.72 | 0.00 | 0.00 |
Maximum of Months | 2034.14 | 1611.72 | 1466.20 | 1024.16 | 680.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2217.68 | 2210.31 | 1904.67 | 1323.13 | 581.55 | 0.00 | 0.00 |
February | 2255.48 | 1854.74 | 1774.23 | 1183.66 | 590.56 | 0.00 | 0.00 |
March | 2306.68 | 1208.40 | 1622.42 | 851.37 | 771.05 | 0.00 | 0.00 |
April | 1961.78 | 954.05 | 1220.99 | 407.36 | 813.62 | 0.00 | 0.00 |
May | 1707.06 | 591.95 | 981.47 | 120.11 | 861.37 | 0.00 | 0.00 |
June | 1846.68 | 343.32 | 901.18 | 50.31 | 850.87 | 0.00 | 0.00 |
July | 1947.51 | 215.93 | 904.00 | 60.98 | 843.02 | 0.00 | 0.00 |
August | 2341.36 | 166.78 | 1089.28 | 204.72 | 884.56 | 0.00 | 0.00 |
September | 2232.89 | 475.94 | 1229.79 | 478.50 | 751.29 | 0.00 | 0.00 |
October | 2667.13 | 1092.47 | 1726.86 | 1116.14 | 610.72 | 0.00 | 0.00 |
November | 2599.63 | 1474.14 | 1886.68 | 1258.98 | 627.69 | 0.00 | 0.00 |
December | 2358.28 | 1866.03 | 1891.27 | 1330.44 | 560.83 | 0.00 | 0.00 |
Annual Sum or Average | 2203.56 | 1033.60 | 1426.18 | 696.47 | 729.71 | 0.00 | 0.00 |
Minimum of Months | 1707.06 | 166.78 | 901.18 | 50.31 | 560.83 | 0.00 | 0.00 |
Maximum of Months | 2667.13 | 2210.31 | 1904.67 | 1330.44 | 884.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 168.20 | 333.58 | 185.03 | 109.68 | 75.35 | 0.00 | 0.00 |
February | 206.27 | 272.59 | 189.94 | 108.05 | 81.88 | 0.00 | 0.00 |
March | 298.00 | 165.61 | 225.66 | 112.56 | 113.10 | 0.00 | 0.00 |
April | 337.29 | 125.04 | 221.46 | 93.13 | 128.34 | 0.00 | 0.00 |
May | 353.55 | 69.73 | 209.48 | 65.86 | 143.62 | 0.00 | 0.00 |
June | 416.22 | 32.46 | 213.06 | 66.00 | 147.06 | 0.00 | 0.00 |
July | 419.75 | 15.42 | 203.56 | 60.51 | 143.04 | 0.00 | 0.00 |
August | 438.33 | 7.76 | 210.83 | 67.90 | 142.93 | 0.00 | 0.00 |
September | 338.61 | 48.42 | 190.60 | 77.76 | 112.85 | 0.00 | 0.00 |
October | 299.45 | 143.80 | 203.79 | 117.75 | 86.03 | 0.00 | 0.00 |
November | 235.99 | 207.63 | 189.70 | 107.28 | 82.42 | 0.00 | 0.00 |
December | 177.38 | 272.77 | 174.88 | 103.74 | 71.14 | 0.00 | 0.00 |
Annual Sum or Average | 307.98 | 140.57 | 201.57 | 90.76 | 110.81 | 0.00 | 0.00 |
Minimum of Months | 168.20 | 7.76 | 174.88 | 60.51 | 71.14 | 0.00 | 0.00 |
Maximum of Months | 438.33 | 333.58 | 225.66 | 117.75 | 147.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 64.43 | 360.44 | 101.47 | 38.17 | 63.31 | 0.00 | 0.00 |
February | 106.22 | 291.68 | 115.53 | 44.07 | 71.46 | 0.00 | 0.00 |
March | 202.59 | 170.51 | 168.15 | 66.54 | 101.61 | 0.00 | 0.00 |
April | 277.78 | 128.57 | 192.06 | 71.32 | 120.74 | 0.00 | 0.00 |
May | 327.40 | 72.88 | 200.09 | 60.74 | 139.35 | 0.00 | 0.00 |
June | 408.02 | 33.40 | 212.37 | 66.43 | 145.94 | 0.00 | 0.00 |
July | 407.16 | 16.91 | 200.17 | 59.55 | 140.62 | 0.00 | 0.00 |
August | 397.52 | 8.62 | 192.34 | 57.31 | 135.04 | 0.00 | 0.00 |
September | 268.80 | 52.13 | 154.62 | 51.91 | 102.72 | 0.00 | 0.00 |
October | 183.32 | 149.65 | 133.62 | 57.43 | 76.19 | 0.00 | 0.00 |
November | 118.35 | 218.16 | 108.46 | 39.23 | 69.23 | 0.00 | 0.00 |
December | 68.01 | 293.12 | 90.58 | 31.83 | 58.75 | 0.00 | 0.00 |
Annual Sum or Average | 236.51 | 148.96 | 156.00 | 53.75 | 102.25 | 0.00 | 0.00 |
Minimum of Months | 64.43 | 8.62 | 90.58 | 31.83 | 58.75 | 0.00 | 0.00 |
Maximum of Months | 408.02 | 360.44 | 212.37 | 71.32 | 145.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 92.85 | 93.16 | 82.34 | 57.20 | 25.14 | 0.00 | 0.00 |
February | 90.25 | 88.42 | 76.70 | 51.17 | 25.53 | 0.00 | 0.00 |
March | 85.96 | 70.07 | 70.14 | 36.81 | 33.33 | 0.00 | 0.00 |
April | 71.06 | 57.50 | 52.79 | 17.61 | 35.17 | 0.00 | 0.00 |
May | 59.79 | 38.78 | 42.43 | 5.19 | 37.24 | 0.00 | 0.00 |
June | 65.97 | 24.41 | 38.96 | 2.18 | 36.78 | 0.00 | 0.00 |
July | 70.38 | 17.93 | 39.08 | 2.64 | 36.45 | 0.00 | 0.00 |
August | 87.58 | 15.53 | 47.09 | 8.85 | 38.24 | 0.00 | 0.00 |
September | 84.25 | 32.88 | 53.17 | 20.69 | 32.48 | 0.00 | 0.00 |
October | 103.18 | 63.82 | 74.65 | 48.25 | 26.40 | 0.00 | 0.00 |
November | 100.03 | 82.75 | 81.56 | 54.43 | 27.14 | 0.00 | 0.00 |
December | 92.11 | 95.94 | 81.76 | 57.52 | 24.25 | 0.00 | 0.00 |
Annual Sum or Average | 83.60 | 56.59 | 61.66 | 30.11 | 31.55 | 0.00 | 0.00 |
Minimum of Months | 59.79 | 15.53 | 38.96 | 2.18 | 24.25 | 0.00 | 0.00 |
Maximum of Months | 103.18 | 95.94 | 82.34 | 57.52 | 38.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.23 | 112.22 | 15.51 | 0.00 | 15.51 | 0.00 | 0.00 |
February | 8.31 | 89.16 | 17.20 | 0.00 | 17.20 | 0.00 | 0.00 |
March | 20.13 | 49.12 | 24.15 | 0.00 | 24.15 | 0.00 | 0.00 |
April | 38.13 | 35.33 | 29.28 | 0.17 | 29.11 | 0.00 | 0.00 |
May | 57.55 | 18.71 | 34.93 | 1.10 | 33.84 | 0.00 | 0.00 |
June | 82.06 | 7.90 | 38.42 | 2.52 | 35.90 | 0.00 | 0.00 |
July | 84.05 | 3.82 | 36.39 | 1.86 | 34.52 | 0.00 | 0.00 |
August | 78.32 | 1.63 | 32.32 | 0.38 | 31.94 | 0.00 | 0.00 |
September | 45.10 | 13.57 | 24.40 | 0.01 | 24.39 | 0.00 | 0.00 |
October | 20.57 | 42.52 | 18.54 | 0.00 | 18.54 | 0.00 | 0.00 |
November | 10.75 | 64.18 | 16.59 | 0.00 | 16.59 | 0.00 | 0.00 |
December | 2.84 | 89.32 | 14.34 | 0.00 | 14.34 | 0.00 | 0.00 |
Annual Sum or Average | 37.67 | 43.73 | 25.21 | 0.51 | 24.71 | 0.00 | 0.00 |
Minimum of Months | 2.23 | 1.63 | 14.34 | 0.00 | 14.34 | 0.00 | 0.00 |
Maximum of Months | 84.05 | 112.22 | 38.42 | 2.52 | 35.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 160.43 | 328.79 | 183.05 | 107.99 | 75.07 | 0.00 | 0.00 |
February | 210.45 | 266.44 | 196.44 | 118.10 | 78.34 | 0.00 | 0.00 |
March | 270.19 | 157.70 | 214.18 | 103.72 | 110.47 | 0.00 | 0.00 |
April | 323.65 | 116.31 | 218.90 | 91.81 | 127.09 | 0.00 | 0.00 |
May | 365.53 | 64.65 | 220.55 | 77.33 | 143.22 | 0.00 | 0.00 |
June | 428.12 | 29.64 | 221.96 | 75.29 | 146.67 | 0.00 | 0.00 |
July | 441.99 | 14.84 | 217.73 | 74.14 | 143.58 | 0.00 | 0.00 |
August | 443.28 | 7.31 | 213.65 | 72.46 | 141.19 | 0.00 | 0.00 |
September | 341.35 | 46.30 | 193.32 | 81.91 | 111.41 | 0.00 | 0.00 |
October | 289.52 | 138.06 | 201.83 | 116.80 | 85.03 | 0.00 | 0.00 |
November | 226.73 | 200.77 | 188.38 | 107.02 | 81.36 | 0.00 | 0.00 |
December | 175.38 | 266.99 | 177.20 | 106.04 | 71.16 | 0.00 | 0.00 |
Annual Sum or Average | 306.91 | 135.84 | 203.98 | 94.25 | 109.73 | 0.00 | 0.00 |
Minimum of Months | 160.43 | 7.31 | 177.20 | 72.46 | 71.16 | 0.00 | 0.00 |
Maximum of Months | 443.28 | 328.79 | 221.96 | 118.10 | 146.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 49.96 | 348.62 | 99.50 | 36.47 | 63.02 | 0.00 | 0.00 |
February | 100.83 | 275.45 | 122.03 | 54.12 | 67.91 | 0.00 | 0.00 |
March | 171.87 | 157.76 | 156.67 | 57.70 | 98.97 | 0.00 | 0.00 |
April | 264.36 | 118.91 | 189.50 | 70.00 | 119.49 | 0.00 | 0.00 |
May | 340.09 | 68.67 | 211.16 | 72.20 | 138.96 | 0.00 | 0.00 |
June | 419.43 | 31.71 | 221.27 | 75.71 | 145.56 | 0.00 | 0.00 |
July | 427.92 | 16.75 | 214.34 | 73.18 | 141.17 | 0.00 | 0.00 |
August | 401.42 | 8.16 | 195.17 | 61.87 | 133.30 | 0.00 | 0.00 |
September | 270.14 | 49.49 | 157.34 | 56.06 | 101.28 | 0.00 | 0.00 |
October | 169.72 | 139.25 | 131.66 | 56.47 | 75.19 | 0.00 | 0.00 |
November | 100.41 | 200.82 | 107.14 | 38.98 | 68.16 | 0.00 | 0.00 |
December | 53.74 | 274.57 | 92.91 | 34.13 | 58.77 | 0.00 | 0.00 |
Annual Sum or Average | 231.53 | 140.19 | 158.40 | 57.24 | 101.17 | 0.00 | 0.00 |
Minimum of Months | 49.96 | 8.16 | 92.91 | 34.13 | 58.77 | 0.00 | 0.00 |
Maximum of Months | 427.92 | 348.62 | 221.27 | 75.71 | 145.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 179.96 | 425.58 | 212.02 | 123.94 | 88.08 | 0.00 | 0.00 |
February | 208.52 | 347.08 | 203.44 | 110.87 | 92.57 | 0.00 | 0.00 |
March | 257.54 | 211.04 | 204.28 | 79.75 | 124.53 | 0.00 | 0.00 |
April | 266.87 | 164.34 | 177.80 | 38.53 | 139.27 | 0.00 | 0.00 |
May | 284.69 | 95.16 | 167.61 | 13.62 | 153.99 | 0.00 | 0.00 |
June | 345.87 | 51.03 | 167.65 | 10.17 | 157.48 | 0.00 | 0.00 |
July | 355.88 | 31.48 | 163.50 | 9.75 | 153.75 | 0.00 | 0.00 |
August | 378.57 | 21.55 | 172.05 | 20.00 | 152.05 | 0.00 | 0.00 |
September | 304.32 | 75.86 | 168.04 | 44.84 | 123.20 | 0.00 | 0.00 |
October | 291.52 | 187.89 | 201.91 | 104.55 | 97.36 | 0.00 | 0.00 |
November | 260.15 | 258.94 | 212.66 | 117.93 | 94.73 | 0.00 | 0.00 |
December | 205.48 | 344.02 | 208.22 | 124.62 | 83.60 | 0.00 | 0.00 |
Annual Sum or Average | 278.68 | 183.68 | 188.21 | 66.33 | 121.88 | 0.00 | 0.00 |
Minimum of Months | 179.96 | 21.55 | 163.50 | 9.75 | 83.60 | 0.00 | 0.00 |
Maximum of Months | 378.57 | 425.58 | 212.66 | 124.62 | 157.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 168.15 | 331.81 | 185.03 | 109.68 | 75.35 | 0.00 | 0.00 |
February | 205.31 | 270.62 | 189.94 | 108.05 | 81.88 | 0.00 | 0.00 |
March | 295.26 | 163.60 | 225.66 | 112.56 | 113.10 | 0.00 | 0.00 |
April | 333.86 | 123.49 | 221.46 | 93.13 | 128.34 | 0.00 | 0.00 |
May | 349.73 | 68.54 | 209.48 | 65.86 | 143.62 | 0.00 | 0.00 |
June | 413.02 | 31.09 | 213.06 | 66.00 | 147.06 | 0.00 | 0.00 |
July | 417.09 | 14.31 | 203.56 | 60.51 | 143.04 | 0.00 | 0.00 |
August | 435.71 | 6.88 | 210.83 | 67.90 | 142.93 | 0.00 | 0.00 |
September | 336.34 | 46.61 | 190.60 | 77.76 | 112.85 | 0.00 | 0.00 |
October | 297.43 | 141.28 | 203.79 | 117.75 | 86.03 | 0.00 | 0.00 |
November | 234.99 | 205.29 | 189.70 | 107.28 | 82.42 | 0.00 | 0.00 |
December | 177.32 | 270.36 | 174.88 | 103.74 | 71.14 | 0.00 | 0.00 |
Annual Sum or Average | 305.91 | 138.83 | 201.57 | 90.76 | 110.81 | 0.00 | 0.00 |
Minimum of Months | 168.15 | 6.88 | 174.88 | 60.51 | 71.14 | 0.00 | 0.00 |
Maximum of Months | 435.71 | 331.81 | 225.66 | 117.75 | 147.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 64.77 | 358.94 | 101.47 | 38.17 | 63.31 | 0.00 | 0.00 |
February | 106.02 | 289.60 | 115.53 | 44.07 | 71.46 | 0.00 | 0.00 |
March | 200.98 | 168.49 | 168.15 | 66.54 | 101.61 | 0.00 | 0.00 |
April | 274.64 | 127.92 | 192.06 | 71.32 | 120.74 | 0.00 | 0.00 |
May | 323.51 | 72.54 | 200.09 | 60.74 | 139.35 | 0.00 | 0.00 |
June | 404.99 | 32.31 | 212.37 | 66.43 | 145.94 | 0.00 | 0.00 |
July | 404.69 | 15.94 | 200.17 | 59.55 | 140.62 | 0.00 | 0.00 |
August | 395.31 | 7.69 | 192.34 | 57.31 | 135.04 | 0.00 | 0.00 |
September | 267.12 | 50.33 | 154.62 | 51.91 | 102.72 | 0.00 | 0.00 |
October | 182.52 | 147.01 | 133.62 | 57.43 | 76.19 | 0.00 | 0.00 |
November | 118.63 | 215.12 | 108.46 | 39.23 | 69.23 | 0.00 | 0.00 |
December | 68.94 | 290.32 | 90.58 | 31.83 | 58.75 | 0.00 | 0.00 |
Annual Sum or Average | 235.05 | 147.31 | 156.00 | 53.75 | 102.25 | 0.00 | 0.00 |
Minimum of Months | 64.77 | 7.69 | 90.58 | 31.83 | 58.75 | 0.00 | 0.00 |
Maximum of Months | 404.99 | 358.94 | 212.37 | 71.32 | 145.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 167.80 | 171.80 | 150.98 | 104.88 | 46.10 | 0.00 | 0.00 |
February | 171.38 | 141.08 | 140.64 | 93.83 | 46.81 | 0.00 | 0.00 |
March | 176.50 | 85.26 | 128.61 | 67.49 | 61.12 | 0.00 | 0.00 |
April | 152.11 | 63.90 | 96.79 | 32.29 | 64.50 | 0.00 | 0.00 |
May | 135.35 | 34.14 | 77.80 | 9.52 | 68.28 | 0.00 | 0.00 |
June | 153.09 | 14.80 | 71.44 | 3.99 | 67.45 | 0.00 | 0.00 |
July | 163.65 | 6.56 | 71.66 | 4.83 | 66.83 | 0.00 | 0.00 |
August | 195.45 | 2.99 | 86.35 | 16.23 | 70.12 | 0.00 | 0.00 |
September | 179.20 | 23.43 | 97.49 | 37.93 | 59.55 | 0.00 | 0.00 |
October | 207.59 | 73.21 | 136.89 | 88.48 | 48.41 | 0.00 | 0.00 |
November | 200.64 | 106.66 | 149.56 | 99.80 | 49.76 | 0.00 | 0.00 |
December | 179.81 | 140.97 | 149.92 | 105.46 | 44.46 | 0.00 | 0.00 |
Annual Sum or Average | 173.59 | 71.72 | 113.05 | 55.21 | 57.84 | 0.00 | 0.00 |
Minimum of Months | 135.35 | 2.99 | 71.44 | 3.99 | 44.46 | 0.00 | 0.00 |
Maximum of Months | 207.59 | 171.80 | 150.98 | 105.46 | 70.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 15.95 | 1068.41 | 135.72 | 0.00 | 135.72 | 0.00 | 0.00 |
February | 63.61 | 861.52 | 150.43 | 0.00 | 150.43 | 0.00 | 0.00 |
March | 156.77 | 500.09 | 211.25 | 0.00 | 211.25 | 0.00 | 0.00 |
April | 314.10 | 367.45 | 256.14 | 1.50 | 254.65 | 0.00 | 0.00 |
May | 481.39 | 216.07 | 305.61 | 9.59 | 296.03 | 0.00 | 0.00 |
June | 683.22 | 116.94 | 336.12 | 22.04 | 314.08 | 0.00 | 0.00 |
July | 693.09 | 73.36 | 318.33 | 16.31 | 302.02 | 0.00 | 0.00 |
August | 635.91 | 53.18 | 282.74 | 3.32 | 279.41 | 0.00 | 0.00 |
September | 373.09 | 170.79 | 213.42 | 0.08 | 213.34 | 0.00 | 0.00 |
October | 164.82 | 439.06 | 162.16 | 0.00 | 162.16 | 0.00 | 0.00 |
November | 80.79 | 632.94 | 145.13 | 0.00 | 145.13 | 0.00 | 0.00 |
December | 18.16 | 863.56 | 125.46 | 0.00 | 125.46 | 0.00 | 0.00 |
Annual Sum or Average | 308.13 | 444.91 | 220.59 | 4.42 | 216.17 | 0.00 | 0.00 |
Minimum of Months | 15.95 | 53.18 | 125.46 | 0.00 | 125.46 | 0.00 | 0.00 |
Maximum of Months | 693.09 | 1068.41 | 336.12 | 22.04 | 314.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.05 | 1105.30 | 135.72 | 0.00 | 135.72 | 0.00 | 0.00 |
February | 58.74 | 895.52 | 150.43 | 0.00 | 150.43 | 0.00 | 0.00 |
March | 145.95 | 524.63 | 211.25 | 0.00 | 211.25 | 0.00 | 0.00 |
April | 300.93 | 384.25 | 256.14 | 1.50 | 254.65 | 0.00 | 0.00 |
May | 466.56 | 227.79 | 305.61 | 9.59 | 296.03 | 0.00 | 0.00 |
June | 666.31 | 125.33 | 336.12 | 22.04 | 314.08 | 0.00 | 0.00 |
July | 675.88 | 80.44 | 318.33 | 16.31 | 302.02 | 0.00 | 0.00 |
August | 619.15 | 60.30 | 282.74 | 3.32 | 279.41 | 0.00 | 0.00 |
September | 359.90 | 183.23 | 213.42 | 0.08 | 213.34 | 0.00 | 0.00 |
October | 155.72 | 460.87 | 162.16 | 0.00 | 162.16 | 0.00 | 0.00 |
November | 72.75 | 662.38 | 145.13 | 0.00 | 145.13 | 0.00 | 0.00 |
December | 15.18 | 901.34 | 125.46 | 0.00 | 125.46 | 0.00 | 0.00 |
Annual Sum or Average | 297.28 | 465.51 | 220.59 | 4.42 | 216.17 | 0.00 | 0.00 |
Minimum of Months | 14.05 | 60.30 | 125.46 | 0.00 | 125.46 | 0.00 | 0.00 |
Maximum of Months | 675.88 | 1105.30 | 336.12 | 22.04 | 314.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 191.53 | 765.36 | 282.54 | 144.46 | 138.08 | 0.00 | 0.00 |
February | 310.48 | 630.18 | 318.45 | 172.21 | 146.24 | 0.00 | 0.00 |
March | 476.39 | 387.24 | 370.84 | 161.41 | 209.43 | 0.00 | 0.00 |
April | 652.76 | 293.32 | 408.37 | 161.80 | 246.57 | 0.00 | 0.00 |
May | 791.65 | 187.44 | 431.69 | 149.52 | 282.17 | 0.00 | 0.00 |
June | 945.38 | 110.86 | 443.21 | 150.99 | 292.22 | 0.00 | 0.00 |
July | 969.02 | 74.09 | 432.04 | 147.31 | 284.74 | 0.00 | 0.00 |
August | 939.93 | 56.82 | 408.79 | 134.32 | 274.47 | 0.00 | 0.00 |
September | 693.69 | 141.46 | 350.64 | 137.96 | 212.67 | 0.00 | 0.00 |
October | 506.12 | 339.74 | 333.47 | 173.26 | 160.21 | 0.00 | 0.00 |
November | 347.73 | 472.21 | 295.51 | 146.00 | 149.51 | 0.00 | 0.00 |
December | 221.80 | 627.19 | 270.10 | 140.17 | 129.93 | 0.00 | 0.00 |
Annual Sum or Average | 588.69 | 339.05 | 362.36 | 151.47 | 210.89 | 0.00 | 0.00 |
Minimum of Months | 191.53 | 56.82 | 270.10 | 134.32 | 129.93 | 0.00 | 0.00 |
Maximum of Months | 969.02 | 765.36 | 443.21 | 173.26 | 292.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 394.32 | 759.50 | 430.86 | 266.99 | 163.87 | 0.00 | 0.00 |
February | 430.47 | 635.82 | 409.58 | 238.84 | 170.74 | 0.00 | 0.00 |
March | 486.58 | 414.72 | 399.80 | 171.79 | 228.00 | 0.00 | 0.00 |
April | 467.60 | 335.79 | 334.18 | 82.71 | 251.47 | 0.00 | 0.00 |
May | 466.69 | 209.83 | 302.81 | 27.52 | 275.29 | 0.00 | 0.00 |
June | 569.25 | 114.09 | 297.07 | 17.71 | 279.36 | 0.00 | 0.00 |
July | 595.62 | 72.68 | 291.54 | 17.90 | 273.64 | 0.00 | 0.00 |
August | 657.00 | 54.21 | 316.72 | 42.45 | 274.27 | 0.00 | 0.00 |
September | 544.78 | 166.93 | 321.31 | 96.58 | 224.73 | 0.00 | 0.00 |
October | 560.75 | 376.31 | 404.04 | 225.22 | 178.82 | 0.00 | 0.00 |
November | 522.19 | 492.00 | 430.45 | 254.04 | 176.41 | 0.00 | 0.00 |
December | 438.22 | 623.23 | 424.64 | 268.46 | 156.18 | 0.00 | 0.00 |
Annual Sum or Average | 511.62 | 353.13 | 363.40 | 142.05 | 221.35 | 0.00 | 0.00 |
Minimum of Months | 394.32 | 54.21 | 291.54 | 17.71 | 156.18 | 0.00 | 0.00 |
Maximum of Months | 657.00 | 759.50 | 430.86 | 268.46 | 279.36 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160650E+10 | 0.150778E+10 | 0.139459E+10 | 0.968782E+09 | 0.425804E+09 | 0.00 | 0.00 |
February | 0.147005E+10 | 0.113829E+10 | 0.117336E+10 | 0.782797E+09 | 0.390560E+09 | 0.00 | 0.00 |
March | 0.164956E+10 | 0.829401E+09 | 0.118792E+10 | 0.623368E+09 | 0.564555E+09 | 0.00 | 0.00 |
April | 0.134513E+10 | 0.643365E+09 | 0.865158E+09 | 0.288646E+09 | 0.576512E+09 | 0.00 | 0.00 |
May | 0.118682E+10 | 0.425171E+09 | 0.718628E+09 | 87942952.17 | 0.630685E+09 | 0.00 | 0.00 |
June | 0.122906E+10 | 0.249813E+09 | 0.638554E+09 | 35650458.33 | 0.602904E+09 | 0.00 | 0.00 |
July | 0.134212E+10 | 0.166589E+09 | 0.661899E+09 | 44646457.89 | 0.617253E+09 | 0.00 | 0.00 |
August | 0.162689E+10 | 0.135680E+09 | 0.797559E+09 | 0.149894E+09 | 0.647665E+09 | 0.00 | 0.00 |
September | 0.152194E+10 | 0.335676E+09 | 0.871397E+09 | 0.339052E+09 | 0.532345E+09 | 0.00 | 0.00 |
October | 0.190603E+10 | 0.754209E+09 | 0.126439E+10 | 0.817230E+09 | 0.447163E+09 | 0.00 | 0.00 |
November | 0.181488E+10 | 0.969077E+09 | 0.133685E+10 | 0.892082E+09 | 0.444765E+09 | 0.00 | 0.00 |
December | 0.170809E+10 | 0.125971E+10 | 0.138477E+10 | 0.974137E+09 | 0.410633E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.184070E+11 | 0.841476E+10 | 0.122951E+11 | 0.600423E+10 | 0.629084E+10 | 0.00 | 0.00 |
Minimum of Months | 0.118682E+10 | 0.135680E+09 | 0.638554E+09 | 35650458.33 | 0.390560E+09 | 0.00 | 0.00 |
Maximum of Months | 0.190603E+10 | 0.150778E+10 | 0.139459E+10 | 0.974137E+09 | 0.647665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.451439E+10 | 0.431683E+10 | 0.392706E+10 | 0.272803E+10 | 0.119904E+10 | 0.00 | 0.00 |
February | 0.414598E+10 | 0.325906E+10 | 0.330410E+10 | 0.220430E+10 | 0.109979E+10 | 0.00 | 0.00 |
March | 0.471189E+10 | 0.231824E+10 | 0.334511E+10 | 0.175536E+10 | 0.158975E+10 | 0.00 | 0.00 |
April | 0.390190E+10 | 0.174231E+10 | 0.243623E+10 | 0.812809E+09 | 0.162342E+10 | 0.00 | 0.00 |
May | 0.354317E+10 | 0.108594E+10 | 0.202361E+10 | 0.247642E+09 | 0.177597E+10 | 0.00 | 0.00 |
June | 0.372343E+10 | 0.595171E+09 | 0.179813E+10 | 0.100389E+09 | 0.169774E+10 | 0.00 | 0.00 |
July | 0.404915E+10 | 0.376197E+09 | 0.186386E+10 | 0.125721E+09 | 0.173814E+10 | 0.00 | 0.00 |
August | 0.482317E+10 | 0.294661E+09 | 0.224587E+10 | 0.422090E+09 | 0.182378E+10 | 0.00 | 0.00 |
September | 0.445253E+10 | 0.837231E+09 | 0.245380E+10 | 0.954749E+09 | 0.149905E+10 | 0.00 | 0.00 |
October | 0.544823E+10 | 0.207684E+10 | 0.356045E+10 | 0.230127E+10 | 0.125918E+10 | 0.00 | 0.00 |
November | 0.514160E+10 | 0.273886E+10 | 0.376447E+10 | 0.251204E+10 | 0.125243E+10 | 0.00 | 0.00 |
December | 0.481072E+10 | 0.360971E+10 | 0.389942E+10 | 0.274311E+10 | 0.115631E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.532662E+11 | 0.232510E+11 | 0.346221E+11 | 0.169075E+11 | 0.177146E+11 | 0.00 | 0.00 |
Minimum of Months | 0.354317E+10 | 0.294661E+09 | 0.179813E+10 | 0.100389E+09 | 0.109979E+10 | 0.00 | 0.00 |
Maximum of Months | 0.544823E+10 | 0.431683E+10 | 0.392706E+10 | 0.274311E+10 | 0.182378E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.593983E+10 | 0.592009E+10 | 0.510148E+10 | 0.354386E+10 | 0.155762E+10 | 0.00 | 0.00 |
February | 0.545646E+10 | 0.448699E+10 | 0.429221E+10 | 0.286352E+10 | 0.142869E+10 | 0.00 | 0.00 |
March | 0.617822E+10 | 0.323659E+10 | 0.434549E+10 | 0.228032E+10 | 0.206517E+10 | 0.00 | 0.00 |
April | 0.508494E+10 | 0.247290E+10 | 0.316480E+10 | 0.105589E+10 | 0.210891E+10 | 0.00 | 0.00 |
May | 0.457218E+10 | 0.158548E+10 | 0.262878E+10 | 0.321700E+09 | 0.230708E+10 | 0.00 | 0.00 |
June | 0.478660E+10 | 0.889883E+09 | 0.233587E+10 | 0.130411E+09 | 0.220546E+10 | 0.00 | 0.00 |
July | 0.521620E+10 | 0.578340E+09 | 0.242127E+10 | 0.163319E+09 | 0.225795E+10 | 0.00 | 0.00 |
August | 0.627111E+10 | 0.446707E+09 | 0.291752E+10 | 0.548319E+09 | 0.236920E+10 | 0.00 | 0.00 |
September | 0.578766E+10 | 0.123364E+10 | 0.318762E+10 | 0.124027E+10 | 0.194735E+10 | 0.00 | 0.00 |
October | 0.714364E+10 | 0.292608E+10 | 0.462523E+10 | 0.298948E+10 | 0.163575E+10 | 0.00 | 0.00 |
November | 0.673825E+10 | 0.382097E+10 | 0.489026E+10 | 0.326329E+10 | 0.162698E+10 | 0.00 | 0.00 |
December | 0.631642E+10 | 0.499797E+10 | 0.506557E+10 | 0.356345E+10 | 0.150212E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.694915E+11 | 0.325956E+11 | 0.449761E+11 | 0.219638E+11 | 0.230123E+11 | 0.00 | 0.00 |
Minimum of Months | 0.457218E+10 | 0.446707E+09 | 0.233587E+10 | 0.130411E+09 | 0.142869E+10 | 0.00 | 0.00 |
Maximum of Months | 0.714364E+10 | 0.592009E+10 | 0.510148E+10 | 0.356345E+10 | 0.236920E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.450500E+09 | 0.893472E+09 | 0.495584E+09 | 0.293769E+09 | 0.201815E+09 | 0.00 | 0.00 |
February | 0.498997E+09 | 0.659453E+09 | 0.459494E+09 | 0.261398E+09 | 0.198096E+09 | 0.00 | 0.00 |
March | 0.798163E+09 | 0.443567E+09 | 0.604404E+09 | 0.301473E+09 | 0.302931E+09 | 0.00 | 0.00 |
April | 0.874250E+09 | 0.324103E+09 | 0.574032E+09 | 0.241382E+09 | 0.332650E+09 | 0.00 | 0.00 |
May | 0.946955E+09 | 0.186764E+09 | 0.561070E+09 | 0.176409E+09 | 0.384661E+09 | 0.00 | 0.00 |
June | 0.107884E+10 | 84135596.52 | 0.552243E+09 | 0.171073E+09 | 0.381170E+09 | 0.00 | 0.00 |
July | 0.112426E+10 | 41294069.14 | 0.545206E+09 | 0.162083E+09 | 0.383122E+09 | 0.00 | 0.00 |
August | 0.117401E+10 | 20774424.97 | 0.564675E+09 | 0.181855E+09 | 0.382820E+09 | 0.00 | 0.00 |
September | 0.877688E+09 | 0.125509E+09 | 0.494046E+09 | 0.201546E+09 | 0.292500E+09 | 0.00 | 0.00 |
October | 0.802052E+09 | 0.385167E+09 | 0.545822E+09 | 0.315392E+09 | 0.230431E+09 | 0.00 | 0.00 |
November | 0.611699E+09 | 0.538186E+09 | 0.491695E+09 | 0.278059E+09 | 0.213635E+09 | 0.00 | 0.00 |
December | 0.475097E+09 | 0.730595E+09 | 0.468395E+09 | 0.277848E+09 | 0.190547E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.971251E+10 | 0.443302E+10 | 0.635667E+10 | 0.286229E+10 | 0.349438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.450500E+09 | 20774424.97 | 0.459494E+09 | 0.162083E+09 | 0.190547E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117401E+10 | 0.893472E+09 | 0.604404E+09 | 0.315392E+09 | 0.384661E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.172563E+09 | 0.965412E+09 | 0.271782E+09 | 0.102224E+09 | 0.169558E+09 | 0.00 | 0.00 |
February | 0.256955E+09 | 0.705621E+09 | 0.279492E+09 | 0.106626E+09 | 0.172866E+09 | 0.00 | 0.00 |
March | 0.542627E+09 | 0.456696E+09 | 0.450364E+09 | 0.178224E+09 | 0.272140E+09 | 0.00 | 0.00 |
April | 0.719994E+09 | 0.333245E+09 | 0.497825E+09 | 0.184866E+09 | 0.312959E+09 | 0.00 | 0.00 |
May | 0.876897E+09 | 0.195215E+09 | 0.535925E+09 | 0.162689E+09 | 0.373236E+09 | 0.00 | 0.00 |
June | 0.105758E+10 | 86574309.81 | 0.550455E+09 | 0.172187E+09 | 0.378268E+09 | 0.00 | 0.00 |
July | 0.109053E+10 | 45294184.73 | 0.536142E+09 | 0.159497E+09 | 0.376645E+09 | 0.00 | 0.00 |
August | 0.106472E+10 | 23084015.19 | 0.515169E+09 | 0.153489E+09 | 0.361680E+09 | 0.00 | 0.00 |
September | 0.696723E+09 | 0.135132E+09 | 0.400785E+09 | 0.134540E+09 | 0.266245E+09 | 0.00 | 0.00 |
October | 0.490997E+09 | 0.400825E+09 | 0.357879E+09 | 0.153811E+09 | 0.204068E+09 | 0.00 | 0.00 |
November | 0.306770E+09 | 0.565478E+09 | 0.281117E+09 | 0.101680E+09 | 0.179438E+09 | 0.00 | 0.00 |
December | 0.182165E+09 | 0.785089E+09 | 0.242610E+09 | 85244676.27 | 0.157365E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.745852E+10 | 0.469767E+10 | 0.491954E+10 | 0.169508E+10 | 0.322447E+10 | 0.00 | 0.00 |
Minimum of Months | 0.172563E+09 | 23084015.19 | 0.242610E+09 | 85244676.27 | 0.157365E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109053E+10 | 0.965412E+09 | 0.550455E+09 | 0.184866E+09 | 0.378268E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.248686E+09 | 0.249511E+09 | 0.220544E+09 | 0.153205E+09 | 67338165.69 | 0.00 | 0.00 |
February | 0.218330E+09 | 0.213912E+09 | 0.185558E+09 | 0.123793E+09 | 61764600.87 | 0.00 | 0.00 |
March | 0.230234E+09 | 0.187670E+09 | 0.187862E+09 | 98580876.18 | 89280789.68 | 0.00 | 0.00 |
April | 0.184177E+09 | 0.149039E+09 | 0.136819E+09 | 45647216.27 | 91171836.45 | 0.00 | 0.00 |
May | 0.160150E+09 | 0.103857E+09 | 0.113647E+09 | 13907499.81 | 99739018.35 | 0.00 | 0.00 |
June | 0.171007E+09 | 63271982.55 | 0.100984E+09 | 5637845.11 | 95345682.42 | 0.00 | 0.00 |
July | 0.188501E+09 | 48032493.25 | 0.104675E+09 | 7060493.07 | 97614864.41 | 0.00 | 0.00 |
August | 0.234565E+09 | 41593360.02 | 0.126129E+09 | 23704513.72 | 0.102424E+09 | 0.00 | 0.00 |
September | 0.218381E+09 | 85235321.39 | 0.137805E+09 | 53618484.76 | 84186968.45 | 0.00 | 0.00 |
October | 0.276354E+09 | 0.170947E+09 | 0.199955E+09 | 0.129239E+09 | 70716109.13 | 0.00 | 0.00 |
November | 0.259284E+09 | 0.214476E+09 | 0.211412E+09 | 0.141076E+09 | 70336596.60 | 0.00 | 0.00 |
December | 0.246699E+09 | 0.256961E+09 | 0.218991E+09 | 0.154052E+09 | 64938803.63 | 0.00 | 0.00 |
Annual Sum or Average | 0.263637E+10 | 0.178451E+10 | 0.194438E+10 | 0.949522E+09 | 0.994858E+09 | 0.00 | 0.00 |
Minimum of Months | 0.160150E+09 | 41593360.02 | 0.100984E+09 | 5637845.11 | 61764600.87 | 0.00 | 0.00 |
Maximum of Months | 0.276354E+09 | 0.256961E+09 | 0.220544E+09 | 0.154052E+09 | 0.102424E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5963379.34 | 0.300573E+09 | 41551553.01 | 0.00 | 41551553.01 | 0.00 | 0.00 |
February | 20098928.71 | 0.215687E+09 | 41598843.56 | 0.00 | 41598843.56 | 0.00 | 0.00 |
March | 53923094.20 | 0.131552E+09 | 64675677.25 | 1302.53 | 64674374.72 | 0.00 | 0.00 |
April | 98837298.87 | 91578591.61 | 75890171.00 | 443230.81 | 75446940.19 | 0.00 | 0.00 |
May | 0.154134E+09 | 50123733.84 | 93565486.34 | 2934532.86 | 90630953.48 | 0.00 | 0.00 |
June | 0.212705E+09 | 20472135.58 | 99586189.44 | 6530819.87 | 93055369.57 | 0.00 | 0.00 |
July | 0.225126E+09 | 10222376.45 | 97458282.54 | 4993888.19 | 92464394.35 | 0.00 | 0.00 |
August | 0.209766E+09 | 4376459.61 | 86561042.70 | 1016922.46 | 85544120.25 | 0.00 | 0.00 |
September | 0.116898E+09 | 35179033.98 | 63232448.32 | 24856.94 | 63207591.38 | 0.00 | 0.00 |
October | 55096364.46 | 0.113880E+09 | 49646343.09 | 0.00 | 49646343.09 | 0.00 | 0.00 |
November | 27855514.47 | 0.166355E+09 | 42998364.49 | 0.00 | 42998364.49 | 0.00 | 0.00 |
December | 7610609.99 | 0.239222E+09 | 38411318.30 | 0.00 | 38411318.30 | 0.00 | 0.00 |
Annual Sum or Average | 0.118802E+10 | 0.137922E+10 | 0.795176E+09 | 15945553.66 | 0.779230E+09 | 0.00 | 0.00 |
Minimum of Months | 5963379.34 | 4376459.61 | 38411318.30 | 0.00 | 38411318.30 | 0.00 | 0.00 |
Maximum of Months | 0.225126E+09 | 0.300573E+09 | 99586189.44 | 6530819.87 | 93055369.57 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.429689E+09 | 0.880633E+09 | 0.490293E+09 | 0.289237E+09 | 0.201056E+09 | 0.00 | 0.00 |
February | 0.509125E+09 | 0.644583E+09 | 0.475216E+09 | 0.285702E+09 | 0.189513E+09 | 0.00 | 0.00 |
March | 0.723678E+09 | 0.422382E+09 | 0.573667E+09 | 0.277790E+09 | 0.295877E+09 | 0.00 | 0.00 |
April | 0.838897E+09 | 0.301486E+09 | 0.567384E+09 | 0.237968E+09 | 0.329416E+09 | 0.00 | 0.00 |
May | 0.979033E+09 | 0.173150E+09 | 0.590725E+09 | 0.207113E+09 | 0.383612E+09 | 0.00 | 0.00 |
June | 0.110968E+10 | 76826064.55 | 0.575320E+09 | 0.195140E+09 | 0.380181E+09 | 0.00 | 0.00 |
July | 0.118382E+10 | 39748061.83 | 0.583158E+09 | 0.198584E+09 | 0.384575E+09 | 0.00 | 0.00 |
August | 0.118728E+10 | 19590845.25 | 0.572237E+09 | 0.194075E+09 | 0.378163E+09 | 0.00 | 0.00 |
September | 0.884768E+09 | 0.120013E+09 | 0.501078E+09 | 0.212314E+09 | 0.288763E+09 | 0.00 | 0.00 |
October | 0.775453E+09 | 0.369783E+09 | 0.540578E+09 | 0.312833E+09 | 0.227745E+09 | 0.00 | 0.00 |
November | 0.587695E+09 | 0.520402E+09 | 0.488280E+09 | 0.277407E+09 | 0.210873E+09 | 0.00 | 0.00 |
December | 0.469727E+09 | 0.715098E+09 | 0.474623E+09 | 0.284021E+09 | 0.190602E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.967884E+10 | 0.428369E+10 | 0.643256E+10 | 0.297218E+10 | 0.346038E+10 | 0.00 | 0.00 |
Minimum of Months | 0.429689E+09 | 19590845.25 | 0.474623E+09 | 0.194075E+09 | 0.189513E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118728E+10 | 0.880633E+09 | 0.590725E+09 | 0.312833E+09 | 0.384575E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133800E+09 | 0.933731E+09 | 0.266491E+09 | 97692218.39 | 0.168799E+09 | 0.00 | 0.00 |
February | 0.243923E+09 | 0.666375E+09 | 0.295214E+09 | 0.130930E+09 | 0.164284E+09 | 0.00 | 0.00 |
March | 0.460344E+09 | 0.422555E+09 | 0.419627E+09 | 0.154541E+09 | 0.265086E+09 | 0.00 | 0.00 |
April | 0.685229E+09 | 0.308225E+09 | 0.491176E+09 | 0.181452E+09 | 0.309724E+09 | 0.00 | 0.00 |
May | 0.910904E+09 | 0.183924E+09 | 0.565580E+09 | 0.193393E+09 | 0.372187E+09 | 0.00 | 0.00 |
June | 0.108715E+10 | 82181042.81 | 0.573532E+09 | 0.196253E+09 | 0.377279E+09 | 0.00 | 0.00 |
July | 0.114615E+10 | 44858346.03 | 0.574095E+09 | 0.195998E+09 | 0.378097E+09 | 0.00 | 0.00 |
August | 0.107517E+10 | 21855521.99 | 0.522732E+09 | 0.165709E+09 | 0.357023E+09 | 0.00 | 0.00 |
September | 0.700206E+09 | 0.128279E+09 | 0.407817E+09 | 0.145309E+09 | 0.262508E+09 | 0.00 | 0.00 |
October | 0.454585E+09 | 0.372959E+09 | 0.352634E+09 | 0.151252E+09 | 0.201382E+09 | 0.00 | 0.00 |
November | 0.260255E+09 | 0.520531E+09 | 0.277703E+09 | 0.101027E+09 | 0.176676E+09 | 0.00 | 0.00 |
December | 0.143950E+09 | 0.735404E+09 | 0.248838E+09 | 91417601.72 | 0.157420E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.730167E+10 | 0.442088E+10 | 0.499544E+10 | 0.180497E+10 | 0.319046E+10 | 0.00 | 0.00 |
Minimum of Months | 0.133800E+09 | 21855521.99 | 0.248838E+09 | 91417601.72 | 0.157420E+09 | 0.00 | 0.00 |
Maximum of Months | 0.114615E+10 | 0.933731E+09 | 0.574095E+09 | 0.196253E+09 | 0.378097E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.482015E+09 | 0.113987E+10 | 0.567871E+09 | 0.331954E+09 | 0.235918E+09 | 0.00 | 0.00 |
February | 0.504446E+09 | 0.839644E+09 | 0.492169E+09 | 0.268226E+09 | 0.223944E+09 | 0.00 | 0.00 |
March | 0.689787E+09 | 0.565254E+09 | 0.547153E+09 | 0.213600E+09 | 0.333553E+09 | 0.00 | 0.00 |
April | 0.691723E+09 | 0.425962E+09 | 0.460852E+09 | 99865010.13 | 0.360987E+09 | 0.00 | 0.00 |
May | 0.762509E+09 | 0.254886E+09 | 0.448935E+09 | 36490866.73 | 0.412444E+09 | 0.00 | 0.00 |
June | 0.896488E+09 | 0.132267E+09 | 0.434540E+09 | 26363588.28 | 0.408177E+09 | 0.00 | 0.00 |
July | 0.953188E+09 | 84325701.68 | 0.437930E+09 | 26116561.42 | 0.411813E+09 | 0.00 | 0.00 |
August | 0.101396E+10 | 57706556.61 | 0.460806E+09 | 53564084.25 | 0.407242E+09 | 0.00 | 0.00 |
September | 0.788803E+09 | 0.196627E+09 | 0.435569E+09 | 0.116230E+09 | 0.319339E+09 | 0.00 | 0.00 |
October | 0.780797E+09 | 0.503253E+09 | 0.540797E+09 | 0.280024E+09 | 0.260773E+09 | 0.00 | 0.00 |
November | 0.674305E+09 | 0.671175E+09 | 0.551221E+09 | 0.305672E+09 | 0.245549E+09 | 0.00 | 0.00 |
December | 0.550362E+09 | 0.921420E+09 | 0.557704E+09 | 0.333788E+09 | 0.223916E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.878838E+10 | 0.579239E+10 | 0.593555E+10 | 0.209189E+10 | 0.384365E+10 | 0.00 | 0.00 |
Minimum of Months | 0.482015E+09 | 57706556.61 | 0.434540E+09 | 26116561.42 | 0.223916E+09 | 0.00 | 0.00 |
Maximum of Months | 0.101396E+10 | 0.113987E+10 | 0.567871E+09 | 0.333788E+09 | 0.412444E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.450378E+09 | 0.888720E+09 | 0.495584E+09 | 0.293769E+09 | 0.201815E+09 | 0.00 | 0.00 |
February | 0.496677E+09 | 0.654672E+09 | 0.459494E+09 | 0.261398E+09 | 0.198096E+09 | 0.00 | 0.00 |
March | 0.790812E+09 | 0.438182E+09 | 0.604404E+09 | 0.301473E+09 | 0.302931E+09 | 0.00 | 0.00 |
April | 0.865358E+09 | 0.320099E+09 | 0.574032E+09 | 0.241382E+09 | 0.332650E+09 | 0.00 | 0.00 |
May | 0.936705E+09 | 0.183576E+09 | 0.561070E+09 | 0.176409E+09 | 0.384661E+09 | 0.00 | 0.00 |
June | 0.107054E+10 | 80587390.21 | 0.552243E+09 | 0.171073E+09 | 0.381170E+09 | 0.00 | 0.00 |
July | 0.111714E+10 | 38333427.54 | 0.545206E+09 | 0.162083E+09 | 0.383122E+09 | 0.00 | 0.00 |
August | 0.116700E+10 | 18416831.90 | 0.564675E+09 | 0.181855E+09 | 0.382820E+09 | 0.00 | 0.00 |
September | 0.871792E+09 | 0.120821E+09 | 0.494046E+09 | 0.201546E+09 | 0.292500E+09 | 0.00 | 0.00 |
October | 0.796625E+09 | 0.378396E+09 | 0.545822E+09 | 0.315392E+09 | 0.230431E+09 | 0.00 | 0.00 |
November | 0.609089E+09 | 0.532112E+09 | 0.491695E+09 | 0.278059E+09 | 0.213635E+09 | 0.00 | 0.00 |
December | 0.474923E+09 | 0.724128E+09 | 0.468395E+09 | 0.277848E+09 | 0.190547E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.964703E+10 | 0.437804E+10 | 0.635667E+10 | 0.286229E+10 | 0.349438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.450378E+09 | 18416831.90 | 0.459494E+09 | 0.162083E+09 | 0.190547E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116700E+10 | 0.888720E+09 | 0.604404E+09 | 0.315392E+09 | 0.384661E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.173467E+09 | 0.961373E+09 | 0.271782E+09 | 0.102224E+09 | 0.169558E+09 | 0.00 | 0.00 |
February | 0.256476E+09 | 0.700601E+09 | 0.279492E+09 | 0.106626E+09 | 0.172866E+09 | 0.00 | 0.00 |
March | 0.538316E+09 | 0.451275E+09 | 0.450364E+09 | 0.178224E+09 | 0.272140E+09 | 0.00 | 0.00 |
April | 0.711878E+09 | 0.331571E+09 | 0.497825E+09 | 0.184866E+09 | 0.312959E+09 | 0.00 | 0.00 |
May | 0.866478E+09 | 0.194283E+09 | 0.535925E+09 | 0.162689E+09 | 0.373236E+09 | 0.00 | 0.00 |
June | 0.104973E+10 | 83740386.25 | 0.550455E+09 | 0.172187E+09 | 0.378268E+09 | 0.00 | 0.00 |
July | 0.108392E+10 | 42705607.92 | 0.536142E+09 | 0.159497E+09 | 0.376645E+09 | 0.00 | 0.00 |
August | 0.105880E+10 | 20595965.52 | 0.515169E+09 | 0.153489E+09 | 0.361680E+09 | 0.00 | 0.00 |
September | 0.692376E+09 | 0.130455E+09 | 0.400785E+09 | 0.134540E+09 | 0.266245E+09 | 0.00 | 0.00 |
October | 0.488861E+09 | 0.393761E+09 | 0.357879E+09 | 0.153811E+09 | 0.204068E+09 | 0.00 | 0.00 |
November | 0.307500E+09 | 0.557601E+09 | 0.281117E+09 | 0.101680E+09 | 0.179438E+09 | 0.00 | 0.00 |
December | 0.184636E+09 | 0.777603E+09 | 0.242610E+09 | 85244676.27 | 0.157365E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.741244E+10 | 0.464556E+10 | 0.491954E+10 | 0.169508E+10 | 0.322447E+10 | 0.00 | 0.00 |
Minimum of Months | 0.173467E+09 | 20595965.52 | 0.242610E+09 | 85244676.27 | 0.157365E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108392E+10 | 0.961373E+09 | 0.550455E+09 | 0.184866E+09 | 0.378268E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.449428E+09 | 0.460141E+09 | 0.404391E+09 | 0.280919E+09 | 0.123472E+09 | 0.00 | 0.00 |
February | 0.414606E+09 | 0.341292E+09 | 0.340241E+09 | 0.226989E+09 | 0.113252E+09 | 0.00 | 0.00 |
March | 0.472734E+09 | 0.228373E+09 | 0.344465E+09 | 0.180759E+09 | 0.163706E+09 | 0.00 | 0.00 |
April | 0.394258E+09 | 0.165616E+09 | 0.250873E+09 | 83699171.49 | 0.167174E+09 | 0.00 | 0.00 |
May | 0.362509E+09 | 91444489.64 | 0.208383E+09 | 25500924.42 | 0.182882E+09 | 0.00 | 0.00 |
June | 0.396808E+09 | 38364002.15 | 0.185164E+09 | 10337606.61 | 0.174827E+09 | 0.00 | 0.00 |
July | 0.438319E+09 | 17575740.95 | 0.191934E+09 | 12946187.50 | 0.178988E+09 | 0.00 | 0.00 |
August | 0.523489E+09 | 7999419.11 | 0.231271E+09 | 43464822.63 | 0.187806E+09 | 0.00 | 0.00 |
September | 0.464487E+09 | 60721067.03 | 0.252681E+09 | 98315365.50 | 0.154366E+09 | 0.00 | 0.00 |
October | 0.556017E+09 | 0.196093E+09 | 0.366639E+09 | 0.236973E+09 | 0.129666E+09 | 0.00 | 0.00 |
November | 0.520063E+09 | 0.276461E+09 | 0.387648E+09 | 0.258678E+09 | 0.128970E+09 | 0.00 | 0.00 |
December | 0.481591E+09 | 0.377564E+09 | 0.401544E+09 | 0.282472E+09 | 0.119072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.547431E+10 | 0.226165E+10 | 0.356523E+10 | 0.174105E+10 | 0.182418E+10 | 0.00 | 0.00 |
Minimum of Months | 0.362509E+09 | 7999419.11 | 0.185164E+09 | 10337606.61 | 0.113252E+09 | 0.00 | 0.00 |
Maximum of Months | 0.556017E+09 | 0.460141E+09 | 0.404391E+09 | 0.282472E+09 | 0.187806E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 42731733.08 | 0.286163E+10 | 0.363514E+09 | 0.00 | 0.363514E+09 | 0.00 | 0.00 |
February | 0.153876E+09 | 0.208419E+10 | 0.363928E+09 | 0.00 | 0.363928E+09 | 0.00 | 0.00 |
March | 0.419883E+09 | 0.133943E+10 | 0.565816E+09 | 11395.24 | 0.565804E+09 | 0.00 | 0.00 |
April | 0.814147E+09 | 0.952427E+09 | 0.663926E+09 | 3877608.68 | 0.660048E+09 | 0.00 | 0.00 |
May | 0.128936E+10 | 0.578727E+09 | 0.818558E+09 | 25672786.98 | 0.792886E+09 | 0.00 | 0.00 |
June | 0.177090E+10 | 0.303106E+09 | 0.871231E+09 | 57134936.06 | 0.814096E+09 | 0.00 | 0.00 |
July | 0.185638E+10 | 0.196489E+09 | 0.852615E+09 | 43689075.52 | 0.808926E+09 | 0.00 | 0.00 |
August | 0.170321E+10 | 0.142433E+09 | 0.757280E+09 | 8896555.21 | 0.748384E+09 | 0.00 | 0.00 |
September | 0.967048E+09 | 0.442692E+09 | 0.553190E+09 | 217461.16 | 0.552972E+09 | 0.00 | 0.00 |
October | 0.441456E+09 | 0.117598E+10 | 0.434331E+09 | 0.00 | 0.434331E+09 | 0.00 | 0.00 |
November | 0.209409E+09 | 0.164057E+10 | 0.376172E+09 | 0.00 | 0.376172E+09 | 0.00 | 0.00 |
December | 48652920.99 | 0.231295E+10 | 0.336042E+09 | 0.00 | 0.336042E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.971706E+10 | 0.140306E+11 | 0.695660E+10 | 0.139500E+09 | 0.681710E+10 | 0.00 | 0.00 |
Minimum of Months | 42731733.08 | 0.142433E+09 | 0.336042E+09 | 0.00 | 0.336042E+09 | 0.00 | 0.00 |
Maximum of Months | 0.185638E+10 | 0.286163E+10 | 0.871231E+09 | 57134936.06 | 0.814096E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 37640511.60 | 0.296043E+10 | 0.363514E+09 | 0.00 | 0.363514E+09 | 0.00 | 0.00 |
February | 0.142101E+09 | 0.216645E+10 | 0.363928E+09 | 0.00 | 0.363928E+09 | 0.00 | 0.00 |
March | 0.390918E+09 | 0.140516E+10 | 0.565816E+09 | 11395.24 | 0.565804E+09 | 0.00 | 0.00 |
April | 0.780020E+09 | 0.995983E+09 | 0.663926E+09 | 3877608.68 | 0.660048E+09 | 0.00 | 0.00 |
May | 0.124962E+10 | 0.610113E+09 | 0.818558E+09 | 25672786.98 | 0.792886E+09 | 0.00 | 0.00 |
June | 0.172708E+10 | 0.324854E+09 | 0.871231E+09 | 57134936.06 | 0.814096E+09 | 0.00 | 0.00 |
July | 0.181027E+10 | 0.215439E+09 | 0.852615E+09 | 43689075.52 | 0.808926E+09 | 0.00 | 0.00 |
August | 0.165834E+10 | 0.161505E+09 | 0.757280E+09 | 8896555.21 | 0.748384E+09 | 0.00 | 0.00 |
September | 0.932866E+09 | 0.474933E+09 | 0.553190E+09 | 217461.16 | 0.552972E+09 | 0.00 | 0.00 |
October | 0.417069E+09 | 0.123439E+10 | 0.434331E+09 | 0.00 | 0.434331E+09 | 0.00 | 0.00 |
November | 0.188571E+09 | 0.171689E+10 | 0.376172E+09 | 0.00 | 0.376172E+09 | 0.00 | 0.00 |
December | 40670282.04 | 0.241415E+10 | 0.336042E+09 | 0.00 | 0.336042E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.937516E+10 | 0.146803E+11 | 0.695660E+10 | 0.139500E+09 | 0.681710E+10 | 0.00 | 0.00 |
Minimum of Months | 37640511.60 | 0.161505E+09 | 0.336042E+09 | 0.00 | 0.336042E+09 | 0.00 | 0.00 |
Maximum of Months | 0.181027E+10 | 0.296043E+10 | 0.871231E+09 | 57134936.06 | 0.814096E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.512985E+09 | 0.204993E+10 | 0.756754E+09 | 0.386915E+09 | 0.369838E+09 | 0.00 | 0.00 |
February | 0.751115E+09 | 0.152452E+10 | 0.770395E+09 | 0.416614E+09 | 0.353782E+09 | 0.00 | 0.00 |
March | 0.127597E+10 | 0.103720E+10 | 0.993246E+09 | 0.432310E+09 | 0.560936E+09 | 0.00 | 0.00 |
April | 0.169196E+10 | 0.760276E+09 | 0.105850E+10 | 0.419394E+09 | 0.639109E+09 | 0.00 | 0.00 |
May | 0.212035E+10 | 0.502031E+09 | 0.115624E+10 | 0.400479E+09 | 0.755762E+09 | 0.00 | 0.00 |
June | 0.245043E+10 | 0.287347E+09 | 0.114879E+10 | 0.391366E+09 | 0.757422E+09 | 0.00 | 0.00 |
July | 0.259541E+10 | 0.198454E+09 | 0.115719E+10 | 0.394554E+09 | 0.762635E+09 | 0.00 | 0.00 |
August | 0.251751E+10 | 0.152178E+09 | 0.109491E+10 | 0.359761E+09 | 0.735150E+09 | 0.00 | 0.00 |
September | 0.179805E+10 | 0.366658E+09 | 0.908848E+09 | 0.357603E+09 | 0.551245E+09 | 0.00 | 0.00 |
October | 0.135559E+10 | 0.909966E+09 | 0.893171E+09 | 0.464063E+09 | 0.429108E+09 | 0.00 | 0.00 |
November | 0.901316E+09 | 0.122397E+10 | 0.765951E+09 | 0.378420E+09 | 0.387531E+09 | 0.00 | 0.00 |
December | 0.594081E+09 | 0.167987E+10 | 0.723432E+09 | 0.375426E+09 | 0.348007E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.185648E+11 | 0.106924E+11 | 0.114274E+11 | 0.477691E+10 | 0.665052E+10 | 0.00 | 0.00 |
Minimum of Months | 0.512985E+09 | 0.152178E+09 | 0.723432E+09 | 0.357603E+09 | 0.348007E+09 | 0.00 | 0.00 |
Maximum of Months | 0.259541E+10 | 0.204993E+10 | 0.115719E+10 | 0.464063E+09 | 0.762635E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105615E+10 | 0.203424E+10 | 0.115401E+10 | 0.715094E+09 | 0.438918E+09 | 0.00 | 0.00 |
February | 0.104139E+10 | 0.153817E+10 | 0.990856E+09 | 0.577812E+09 | 0.413045E+09 | 0.00 | 0.00 |
March | 0.130326E+10 | 0.111080E+10 | 0.107082E+10 | 0.460135E+09 | 0.610681E+09 | 0.00 | 0.00 |
April | 0.121202E+10 | 0.870369E+09 | 0.866205E+09 | 0.214390E+09 | 0.651815E+09 | 0.00 | 0.00 |
May | 0.124999E+10 | 0.562000E+09 | 0.811054E+09 | 73714639.91 | 0.737340E+09 | 0.00 | 0.00 |
June | 0.147549E+10 | 0.295722E+09 | 0.770005E+09 | 45900894.75 | 0.724104E+09 | 0.00 | 0.00 |
July | 0.159532E+10 | 0.194667E+09 | 0.780855E+09 | 47931908.78 | 0.732924E+09 | 0.00 | 0.00 |
August | 0.175971E+10 | 0.145206E+09 | 0.848309E+09 | 0.113692E+09 | 0.734618E+09 | 0.00 | 0.00 |
September | 0.141206E+10 | 0.432691E+09 | 0.832848E+09 | 0.250342E+09 | 0.582507E+09 | 0.00 | 0.00 |
October | 0.150192E+10 | 0.100791E+10 | 0.108219E+10 | 0.603228E+09 | 0.478961E+09 | 0.00 | 0.00 |
November | 0.135352E+10 | 0.127527E+10 | 0.111573E+10 | 0.658479E+09 | 0.457252E+09 | 0.00 | 0.00 |
December | 0.117372E+10 | 0.166925E+10 | 0.113735E+10 | 0.719047E+09 | 0.418301E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.161345E+11 | 0.111363E+11 | 0.114602E+11 | 0.447976E+10 | 0.698046E+10 | 0.00 | 0.00 |
Minimum of Months | 0.104139E+10 | 0.145206E+09 | 0.770005E+09 | 45900894.75 | 0.413045E+09 | 0.00 | 0.00 |
Maximum of Months | 0.175971E+10 | 0.203424E+10 | 0.115401E+10 | 0.719047E+09 | 0.737340E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770419E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161414156.5 | 81.21 | 0.00 | 0.00 |
February | 0.696176E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145792614.9 | 81.21 | 0.00 | 0.00 |
March | 0.770287E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161406626.9 | 81.21 | 0.00 | 0.00 |
April | 0.746474E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156148561.5 | 81.21 | 0.00 | 0.00 |
May | 0.770418E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161389650.9 | 81.21 | 0.00 | 0.00 |
June | 0.745673E+10 | -0.730054E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156195573.3 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161411272.7 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161411387.9 | 81.21 | 0.00 | 0.00 |
September | 0.746613E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156192191.4 | 81.21 | 0.00 | 0.00 |
October | 0.770285E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161412138.8 | 81.21 | 0.00 | 0.00 |
November | 0.744863E+10 | -0.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156206480.5 | 81.21 | 0.00 | 0.00 |
December | 0.771227E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161414084.1 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907408E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190039E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696176E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161414156.5 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771227E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145792614.9 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.116072E+12 | -0.114306E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176605E+10 | 81.26 | 0.00 | 0.00 |
February | 0.104992E+12 | -0.103383E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.160902E+10 | 81.26 | 0.00 | 0.00 |
March | 0.113675E+12 | -0.111877E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179807E+10 | 81.26 | 0.00 | 0.00 |
April | 0.105403E+12 | -0.103652E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175049E+10 | 81.25 | 0.00 | 0.00 |
May | 0.103248E+12 | -0.101447E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180070E+10 | 81.25 | 0.00 | 0.00 |
June | 0.950281E+11 | -0.933104E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171767E+10 | 81.25 | 0.00 | 0.00 |
July | 0.951464E+11 | -0.933875E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175884E+10 | 81.24 | 0.00 | 0.00 |
August | 0.949148E+11 | -0.931727E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174213E+10 | 81.24 | 0.00 | 0.00 |
September | 0.944221E+11 | -0.927477E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167445E+10 | 81.24 | 0.00 | 0.00 |
October | 0.102386E+12 | -0.100658E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172840E+10 | 81.24 | 0.00 | 0.00 |
November | 0.104562E+12 | -0.102890E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167235E+10 | 81.25 | 0.00 | 0.00 |
December | 0.113040E+12 | -0.111304E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173571E+10 | 81.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.124289E+13 | -0.122214E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.207539E+11 | 81.25 | 0.00 | 0.00 |
Minimum of Months | 0.944221E+11 | -0.114306E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.180070E+10 | 81.24 | 0.00 | 0.00 |
Maximum of Months | 0.116072E+12 | -0.927477E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.160902E+10 | 81.26 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.676154E+11 | -0.660981E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151727E+10 | 58.98 | 0.00 | 0.00 |
February | 0.612220E+11 | -0.598323E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.138969E+10 | 58.98 | 0.00 | 0.00 |
March | 0.656294E+11 | -0.640677E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156165E+10 | 58.98 | 0.00 | 0.00 |
April | 0.595160E+11 | -0.579901E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152589E+10 | 58.98 | 0.00 | 0.00 |
May | 0.566166E+11 | -0.550510E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156556E+10 | 58.98 | 0.00 | 0.00 |
June | 0.505747E+11 | -0.490940E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.148063E+10 | 58.98 | 0.00 | 0.00 |
July | 0.495731E+11 | -0.480653E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150774E+10 | 58.98 | 0.00 | 0.00 |
August | 0.494139E+11 | -0.479294E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148454E+10 | 58.98 | 0.00 | 0.00 |
September | 0.500064E+11 | -0.485855E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142091E+10 | 58.98 | 0.00 | 0.00 |
October | 0.558034E+11 | -0.543377E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146576E+10 | 58.98 | 0.00 | 0.00 |
November | 0.587272E+11 | -0.573092E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141793E+10 | 58.98 | 0.00 | 0.00 |
December | 0.649878E+11 | -0.635124E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147537E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.689686E+12 | -0.671873E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.178129E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.494139E+11 | -0.660981E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.156556E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.676154E+11 | -0.479294E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.138969E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.87 | 0.86 | 01-JAN-09:09 | 5249.07 | 34.02 | 271.17 | 275.67 | 809.35 | 25.49 | 166.00 | 246.00 |
February | 263.00 | 0.87 | 0.86 | 01-FEB-13:39 | 4656.01 | 30.85 | 192.00 | 250.00 | 570.23 | 21.88 | 110.17 | 205.00 |
March | 351.67 | 0.87 | 0.86 | 01-MAR-08:50 | 1153.27 | 19.53 | 11.17 | 322.17 | 443.53 | 20.94 | 161.00 | 256.83 |
April | 369.33 | 0.87 | 0.86 | 01-APR-08:30 | 922.31 | 19.03 | 0.00 | 328.33 | 365.46 | 20.76 | 149.50 | 250.17 |
May | 407.00 | 0.87 | 0.86 | 01-MAY-07:49 | 873.68 | 18.99 | 0.00 | 362.67 | 346.48 | 20.72 | 187.67 | 278.00 |
June | 411.67 | 0.87 | 0.86 | 01-JUN-07:19 | 806.51 | 18.76 | 0.00 | 363.50 | 324.41 | 20.50 | 172.50 | 260.83 |
July | 411.00 | 0.87 | 0.86 | 01-JUL-08:30 | 853.43 | 18.85 | 0.00 | 368.67 | 340.34 | 20.58 | 205.17 | 277.00 |
August | 390.50 | 0.87 | 0.86 | 01-AUG-07:40 | 1056.86 | 19.51 | 0.67 | 355.17 | 413.23 | 21.22 | 233.50 | 289.33 |
September | 298.50 | 0.87 | 0.86 | 01-SEP-07:49 | 1111.59 | 19.45 | 0.17 | 312.50 | 438.85 | 21.18 | 174.83 | 238.50 |
October | 293.50 | 0.87 | 0.86 | 01-OCT-10:39 | 2681.40 | 24.71 | 106.17 | 294.17 | 453.66 | 21.01 | 107.00 | 221.00 |
November | 299.00 | 0.87 | 0.86 | 01-NOV-08:30 | 5220.85 | 34.77 | 286.00 | 275.67 | 655.98 | 25.15 | 178.50 | 245.67 |
December | 285.17 | 0.87 | 0.86 | 01-DEC-07:00 | 4912.35 | 34.52 | 270.50 | 271.50 | 907.09 | 26.64 | 174.00 | 236.67 |
Annual Sum or Average | 4071.00 | 0.87 | 2217.69 | 23.58 | 1137.83 | 3780.00 | 484.14 | 21.96 | 2019.83 | 3005.00 | ||
Minimum of Months | 263.00 | 0.87 | 0.86 | 806.51 | 18.76 | 0.00 | 250.00 | 324.41 | 20.50 | 107.00 | 205.00 | |
Maximum of Months | 411.67 | 0.87 | 0.86 | 5249.07 | 34.77 | 286.00 | 368.67 | 907.09 | 26.64 | 233.50 | 289.33 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.24 | 0.22 | 01-JAN-08:00 | 5565.96 | 34.15 | 272.83 | 283.00 | 1125.55 | 25.40 | 176.17 | 265.50 |
February | 263.00 | 0.26 | 0.22 | 01-FEB-10:20 | 4957.35 | 30.95 | 193.17 | 260.83 | 870.96 | 21.95 | 110.17 | 226.17 |
March | 351.67 | 0.26 | 0.22 | 01-MAR-08:20 | 1398.59 | 19.97 | 32.67 | 334.00 | 688.05 | 21.23 | 179.50 | 301.17 |
April | 369.33 | 0.26 | 0.22 | 01-APR-07:00 | 1103.12 | 19.70 | 12.83 | 344.67 | 545.69 | 21.22 | 189.83 | 305.83 |
May | 407.00 | 0.26 | 0.22 | 01-MAY-07:10 | 1019.64 | 19.81 | 15.33 | 383.00 | 491.90 | 21.32 | 255.17 | 334.67 |
June | 411.67 | 0.26 | 0.22 | 01-JUN-06:49 | 940.08 | 19.62 | 10.83 | 382.83 | 457.49 | 21.14 | 240.17 | 336.17 |
July | 411.00 | 0.26 | 0.22 | 01-JUL-06:40 | 991.12 | 19.70 | 18.67 | 386.50 | 477.51 | 21.20 | 256.50 | 338.17 |
August | 390.50 | 0.25 | 0.22 | 01-AUG-06:00 | 1226.51 | 20.24 | 52.83 | 369.17 | 582.24 | 21.74 | 277.17 | 332.33 |
September | 298.50 | 0.26 | 0.22 | 01-SEP-07:10 | 1321.83 | 20.03 | 34.00 | 325.33 | 648.41 | 21.56 | 197.67 | 291.17 |
October | 293.50 | 0.26 | 0.22 | 01-OCT-07:00 | 2976.12 | 24.82 | 114.33 | 306.50 | 745.51 | 21.07 | 118.50 | 267.67 |
November | 299.00 | 0.25 | 0.22 | 01-NOV-07:00 | 5524.60 | 34.85 | 287.17 | 282.50 | 957.69 | 25.12 | 182.33 | 266.83 |
December | 285.17 | 0.24 | 0.22 | 01-DEC-07:49 | 5234.59 | 34.63 | 272.33 | 280.17 | 1227.09 | 26.56 | 180.50 | 259.67 |
Annual Sum or Average | 4071.00 | 0.26 | 2437.19 | 24.09 | 1317.00 | 3938.50 | 702.66 | 22.29 | 2363.67 | 3525.33 | ||
Minimum of Months | 263.00 | 0.24 | 0.22 | 940.08 | 19.62 | 10.83 | 260.83 | 457.49 | 21.07 | 110.17 | 226.17 | |
Maximum of Months | 411.67 | 0.26 | 0.22 | 5565.96 | 34.85 | 287.17 | 386.50 | 1227.09 | 26.56 | 277.17 | 338.17 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.67 | 0.60 | 01-JAN-10:00 | 329.20 | 14.06 | 0.00 | 212.83 | 152.64 | 17.48 | 0.00 | 56.67 |
February | 263.00 | 0.68 | 0.60 | 01-FEB-13:39 | 339.50 | 14.24 | 0.00 | 200.83 | 160.98 | 17.63 | 0.00 | 75.50 |
March | 351.67 | 0.64 | 0.60 | 01-MAR-08:00 | 439.69 | 15.76 | 0.00 | 315.67 | 205.17 | 19.01 | 0.00 | 174.83 |
April | 369.33 | 0.63 | 0.60 | 01-APR-08:30 | 534.57 | 16.66 | 0.00 | 341.67 | 243.39 | 19.86 | 6.33 | 226.67 |
May | 407.00 | 0.61 | 0.60 | 01-MAY-07:19 | 680.64 | 18.16 | 18.33 | 391.50 | 310.35 | 21.68 | 106.83 | 348.33 |
June | 411.67 | 0.61 | 0.60 | 01-JUN-06:30 | 756.99 | 19.76 | 55.67 | 393.67 | 347.48 | 23.17 | 185.83 | 366.83 |
July | 411.00 | 0.62 | 0.60 | 01-JUL-05:00 | 769.25 | 18.68 | 27.50 | 395.00 | 336.08 | 22.54 | 173.67 | 355.67 |
August | 390.50 | 0.62 | 0.60 | 01-AUG-06:40 | 675.47 | 17.55 | 0.00 | 370.67 | 305.92 | 20.72 | 73.17 | 327.00 |
September | 298.50 | 0.63 | 0.60 | 01-SEP-07:30 | 494.94 | 16.49 | 0.00 | 316.00 | 232.62 | 19.67 | 0.00 | 204.00 |
October | 293.50 | 0.67 | 0.60 | 01-OCT-10:39 | 345.34 | 14.69 | 0.00 | 230.00 | 169.25 | 18.09 | 0.00 | 100.17 |
November | 299.00 | 0.66 | 0.60 | 01-NOV-09:50 | 340.60 | 14.31 | 0.00 | 242.17 | 160.46 | 17.68 | 0.00 | 58.17 |
December | 285.17 | 0.67 | 0.60 | 01-DEC-09:00 | 318.83 | 14.11 | 0.00 | 213.83 | 149.97 | 17.56 | 0.00 | 38.00 |
Annual Sum or Average | 4071.00 | 0.64 | 527.50 | 16.49 | 101.50 | 3623.83 | 242.09 | 19.88 | 545.83 | 2331.83 | ||
Minimum of Months | 263.00 | 0.61 | 0.60 | 318.83 | 14.06 | 0.00 | 200.83 | 149.97 | 17.48 | 0.00 | 38.00 | |
Maximum of Months | 411.67 | 0.68 | 0.60 | 769.25 | 19.76 | 55.67 | 395.00 | 347.48 | 23.17 | 185.83 | 366.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.67 | 0.60 | 01-JAN-10:00 | 329.20 | 14.06 | 0.00 | 212.83 | 152.64 | 17.48 | 0.00 | 56.67 |
February | 263.00 | 0.68 | 0.60 | 01-FEB-13:39 | 339.50 | 14.24 | 0.00 | 200.83 | 160.98 | 17.63 | 0.00 | 75.50 |
March | 351.67 | 0.64 | 0.60 | 01-MAR-08:00 | 439.69 | 15.76 | 0.00 | 315.67 | 205.17 | 19.01 | 0.00 | 174.83 |
April | 369.33 | 0.63 | 0.60 | 01-APR-08:30 | 534.57 | 16.66 | 0.00 | 341.67 | 243.39 | 19.86 | 6.33 | 226.67 |
May | 407.00 | 0.61 | 0.60 | 01-MAY-07:19 | 680.64 | 18.16 | 18.33 | 391.50 | 310.35 | 21.68 | 106.67 | 348.33 |
June | 411.67 | 0.61 | 0.60 | 01-JUN-06:30 | 756.99 | 19.76 | 55.67 | 393.67 | 347.48 | 23.17 | 185.83 | 366.83 |
July | 411.00 | 0.62 | 0.60 | 01-JUL-05:00 | 769.25 | 18.68 | 27.50 | 395.00 | 336.08 | 22.54 | 173.67 | 355.67 |
August | 390.50 | 0.62 | 0.60 | 01-AUG-06:40 | 675.47 | 17.55 | 0.00 | 370.67 | 305.92 | 20.72 | 73.17 | 327.00 |
September | 298.50 | 0.63 | 0.60 | 01-SEP-07:30 | 494.94 | 16.49 | 0.00 | 316.00 | 232.62 | 19.67 | 0.00 | 204.00 |
October | 293.50 | 0.67 | 0.60 | 01-OCT-10:39 | 345.34 | 14.69 | 0.00 | 230.00 | 169.25 | 18.09 | 0.00 | 100.17 |
November | 299.00 | 0.66 | 0.60 | 01-NOV-09:50 | 340.60 | 14.31 | 0.00 | 242.17 | 160.46 | 17.68 | 0.00 | 58.17 |
December | 285.17 | 0.67 | 0.60 | 01-DEC-09:00 | 318.83 | 14.11 | 0.00 | 213.83 | 149.97 | 17.56 | 0.00 | 38.00 |
Annual Sum or Average | 4071.00 | 0.64 | 527.50 | 16.49 | 101.50 | 3623.83 | 242.09 | 19.88 | 545.67 | 2331.83 | ||
Minimum of Months | 263.00 | 0.61 | 0.60 | 318.83 | 14.06 | 0.00 | 200.83 | 149.97 | 17.48 | 0.00 | 38.00 | |
Maximum of Months | 411.67 | 0.68 | 0.60 | 769.25 | 19.76 | 55.67 | 395.00 | 347.48 | 23.17 | 185.83 | 366.83 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.554999E+11 | 91049.79 | 14-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362903E+11 | 86071.06 | 03-FEB-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185087E+11 | 85034.88 | 19-MAR-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.807754E+10 | 85931.43 | 06-APR-02:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.326375E+09 | 26969.73 | 13-MAY-16:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 78983923.68 | 29062.14 | 08-JUN-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31781.21 | 52.79 | 24-JUL-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 106829.79 | 169.21 | 25-AUG-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141605E+09 | 17246.27 | 22-SEP-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.523493E+10 | 72958.39 | 26-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.269314E+11 | 91475.62 | 21-NOV-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.557178E+11 | 88085.63 | 09-DEC-02:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206808E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 31781.21 | 52.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.557178E+11 | 91475.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2963588.58 | 1382.82 | 27-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165625E+10 | 5226.40 | 10-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 83939150.52 | 3814.04 | 01-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.165625E+10 | 5226.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.148005E+10 | 2018.74 | 08-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.874784E+09 | 2476.38 | 12-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149930E+09 | 943.70 | 22-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 50835961.46 | 839.36 | 06-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87791668.11 | 804.53 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205015E+09 | 1347.81 | 21-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797333E+09 | 1517.30 | 01-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148005E+10 | 2476.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.218759E+09 | 703.42 | 08-JAN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131383E+09 | 584.78 | 13-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6051693.42 | 382.89 | 23-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 268486.77 | 179.57 | 06-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1271334.51 | 218.12 | 31-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2391656.50 | 222.84 | 22-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 43815094.80 | 360.62 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.403941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.218759E+09 | 703.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131878E+09 | 601.25 | 08-JAN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 73764035.84 | 507.31 | 13-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131878E+09 | 601.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140741E+10 | 957.36 | 08-JAN-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.840958E+09 | 992.39 | 12-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.194730E+09 | 536.81 | 23-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40798439.70 | 436.11 | 07-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28216639.32 | 328.95 | 26-OCT-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183964E+09 | 567.13 | 22-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.768132E+09 | 693.22 | 18-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140741E+10 | 992.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.283828E+10 | 6817.83 | 09-JAN-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.189987E+10 | 5932.67 | 07-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.741376E+09 | 5170.82 | 22-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.400026E+09 | 4105.72 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158161E+09 | 2559.91 | 10-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32150963.32 | 2425.39 | 08-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13203840.78 | 2077.67 | 28-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1026290.99 | 1007.35 | 31-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83922273.11 | 3173.40 | 29-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.502946E+09 | 4923.48 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.623673E+09 | 4821.02 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163099E+10 | 4945.16 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.892562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1026290.99 | 1007.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.283828E+10 | 6817.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.149648E+10 | 11342.14 | 08-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.756965E+09 | 8585.45 | 06-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 40701043.96 | 3500.05 | 22-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7495293.30 | 2192.04 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7259084.76 | 1590.82 | 30-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.202916E+09 | 5265.10 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149648E+10 | 11342.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.782877E+10 | 8162.55 | 09-JAN-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.454711E+10 | 7275.04 | 12-FEB-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.320824E+09 | 4259.50 | 23-MAR-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 109195.44 | 181.99 | 07-APR-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.270863E+09 | 4149.14 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.982501E+09 | 4955.36 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.454699E+10 | 5597.17 | 18-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.782877E+10 | 8162.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.274206E+10 | 3788.97 | 08-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146991E+10 | 4776.59 | 12-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17743979.55 | 770.09 | 23-MAR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160457E+09 | 2276.07 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103855E+10 | 2939.24 | 18-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.542872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.274206E+10 | 4776.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114537E+10 | 4522.74 | 27-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.636124E+09 | 4525.99 | 13-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 56829203.38 | 3047.07 | 20-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14877140.84 | 2923.34 | 07-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 422326.41 | 374.82 | 11-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32249666.50 | 2904.80 | 26-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136981E+09 | 3290.26 | 22-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.532435E+09 | 3927.94 | 04-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114537E+10 | 4525.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.286861E+09 | 2881.64 | 27-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142574E+09 | 3207.12 | 13-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1734171.02 | 1144.04 | 20-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1250398.61 | 893.63 | 06-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1776612.93 | 1296.98 | 26-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5425789.90 | 1584.05 | 22-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 48421176.70 | 2238.73 | 04-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.488043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.286861E+09 | 3207.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.706109E+09 | 4582.92 | 07-JAN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.585755E+09 | 5400.24 | 12-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5547.33 | 0.26 | 09-MAR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8510.40 | 0.26 | 29-APR-23:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10182.59 | 0.26 | 29-MAY-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8518.74 | 0.26 | 04-JUN-19:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9236.31 | 0.26 | 09-JUL-20:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8966.66 | 0.26 | 16-AUG-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12672.93 | 0.26 | 16-SEP-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12008.64 | 0.26 | 14-OCT-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35680551.68 | 1146.47 | 22-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120005E+09 | 2081.67 | 18-DEC-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5547.33 | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.706109E+09 | 5400.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.417620E+10 | 5866.18 | 04-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249908E+10 | 5866.40 | 07-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.572698E+09 | 5789.48 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161623E+09 | 5732.71 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8192993.52 | 4272.65 | 19-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2647974.76 | 4492.45 | 02-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1455261.47 | 2885.79 | 28-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 781157.43 | 2875.53 | 25-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10785510.14 | 3311.07 | 19-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.372435E+09 | 5766.60 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108695E+10 | 5843.02 | 30-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.275393E+10 | 5865.98 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 781157.43 | 2875.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.417620E+10 | 5866.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.516708E+10 | 5859.57 | 04-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.312712E+10 | 5859.95 | 10-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.740817E+09 | 5789.44 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179296E+09 | 5746.03 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6655594.80 | 4431.92 | 13-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1433780.13 | 2520.30 | 08-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1019183.64 | 2259.82 | 28-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 635871.55 | 1597.62 | 25-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6203244.70 | 3460.57 | 15-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.468424E+09 | 5802.82 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156424E+10 | 5858.15 | 21-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.360234E+10 | 5859.92 | 31-DEC-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 635871.55 | 1597.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.516708E+10 | 5859.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.132585E+09 | 5029.71 | 09-JAN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.132585E+09 | 5029.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.202452E+11 | 34109.07 | 07-JAN-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113285E+11 | 33987.20 | 03-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126366E+10 | 32256.25 | 13-MAR-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.307436E+09 | 32271.95 | 06-APR-15:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43218979.07 | 30555.23 | 10-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8876433.13 | 18184.78 | 03-JUN-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1511726.51 | 7469.85 | 28-JUL-21:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2369619.38 | 10709.86 | 30-AUG-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27426367.99 | 22328.45 | 19-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.475168E+09 | 28390.20 | 30-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.336111E+10 | 32955.14 | 22-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109506E+11 | 33415.69 | 03-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.480150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1511726.51 | 7469.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.202452E+11 | 34109.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.420003E+10 | 5719.62 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246833E+10 | 5720.14 | 07-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.599513E+09 | 5640.13 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165642E+09 | 4615.57 | 05-APR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5628836.40 | 3072.81 | 26-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 189731.18 | 1225.10 | 23-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1192500.46 | 2092.36 | 27-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 504458.04 | 1509.74 | 24-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8047693.55 | 2946.19 | 30-SEP-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.388573E+09 | 5623.65 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108398E+10 | 5703.24 | 30-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271167E+10 | 5720.25 | 31-DEC-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 189731.18 | 1225.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.420003E+10 | 5720.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.521044E+10 | 5715.11 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.306761E+10 | 5715.64 | 07-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.764931E+09 | 5642.39 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188995E+09 | 4669.18 | 06-APR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4185172.42 | 3125.82 | 10-MAY-21:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 442212.88 | 1547.15 | 08-JUN-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414110.81 | 1450.97 | 28-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34885.29 | 365.75 | 31-AUG-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3943856.47 | 2555.13 | 29-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.496296E+09 | 5622.01 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154593E+10 | 5714.81 | 30-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.355839E+10 | 5715.78 | 31-DEC-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 34885.29 | 365.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.521044E+10 | 5715.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147555E+10 | 1732.31 | 18-JAN-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.909328E+09 | 1734.65 | 01-FEB-21:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.262230E+09 | 1732.21 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86390799.93 | 1724.79 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6656109.72 | 1009.06 | 24-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 868295.11 | 1019.15 | 04-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 634094.07 | 614.28 | 28-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 425596.72 | 978.31 | 25-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9372683.19 | 1009.08 | 14-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181905E+09 | 1727.03 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.454201E+09 | 1732.23 | 30-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102130E+10 | 1732.08 | 31-DEC-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.440886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 425596.72 | 614.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.147555E+10 | 1734.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.178236E+10 | 1730.10 | 01-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110626E+10 | 1737.70 | 01-FEB-21:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.316832E+09 | 1729.92 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88112290.07 | 1728.31 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2964231.58 | 1082.20 | 16-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 672922.49 | 1140.58 | 10-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 239461.55 | 537.60 | 29-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 257088.88 | 586.29 | 30-AUG-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5466591.89 | 1058.52 | 14-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220968E+09 | 1729.71 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.615226E+09 | 1729.94 | 30-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128675E+10 | 1729.93 | 07-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.542611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 239461.55 | 537.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.178236E+10 | 1737.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.412102E+10 | 8157.85 | 03-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.240701E+10 | 8158.08 | 07-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.567730E+09 | 7976.66 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.246226E+09 | 7935.99 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18096231.22 | 5491.80 | 10-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3283371.30 | 3210.98 | 08-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2784608.52 | 2763.21 | 28-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2653058.97 | 2217.90 | 21-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21185843.69 | 4474.69 | 30-SEP-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336128E+09 | 7932.58 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.805644E+09 | 8074.11 | 30-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235212E+10 | 8134.76 | 25-DEC-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2653058.97 | 2217.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.412102E+10 | 8158.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.963208E+10 | 0.806135E+10 | 142958.75 | 19-JAN-21:00 | 77555.83 | 0.05 |
February | 0.00 | 0.00 | 0.323884E+11 | 0.318418E+11 | 162866.96 | 28-FEB-17:00 | 162866.96 | 0.07 |
March | 0.00 | 0.00 | 0.945528E+11 | 0.912379E+11 | 239424.38 | 30-MAR-15:17 | 239424.38 | 0.27 |
April | 0.00 | 0.00 | 0.194542E+12 | 0.171326E+12 | 257776.52 | 21-APR-17:15 | 157199.93 | 0.58 |
May | 0.00 | 0.00 | 0.371113E+12 | 0.279065E+12 | 342601.49 | 30-MAY-21:10 | 187563.89 | 0.88 |
June | 0.00 | 0.00 | 0.576672E+12 | 0.392681E+12 | 399894.88 | 26-JUN-18:10 | 198140.30 | 0.91 |
July | 0.00 | 0.00 | 0.735826E+12 | 0.445863E+12 | 406073.05 | 18-JUL-19:50 | 193795.88 | 1.00 |
August | 0.00 | 0.00 | 0.784141E+12 | 0.467398E+12 | 471846.57 | 23-AUG-21:00 | 206006.10 | 1.00 |
September | 0.00 | 0.00 | 0.503292E+12 | 0.335634E+12 | 403800.35 | 27-SEP-18:07 | 193372.50 | 0.97 |
October | 0.00 | 0.00 | 0.201925E+12 | 0.144606E+12 | 430522.67 | 18-OCT-19:40 | 199901.08 | 0.47 |
November | 0.00 | 0.00 | 0.730198E+11 | 0.603285E+11 | 248878.09 | 27-NOV-19:05 | 160156.12 | 0.21 |
December | 0.00 | 0.00 | 0.163251E+11 | 0.138300E+11 | 186465.42 | 13-DEC-11:35 | 103810.12 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.359343E+13 | 0.244187E+13 | 0.54 | |||
Minimum of Months | 0.00 | 0.00 | 0.963208E+10 | 0.806135E+10 | 142958.75 | 77555.83 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.784141E+12 | 0.467398E+12 | 471846.57 | 239424.38 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.662235E+09 | 0.499543E+09 | 13220.25 | 19-JAN-22:53 | 7342.46 | 0.03 |
February | 0.00 | 0.00 | 0.183268E+10 | 0.181192E+10 | 16177.52 | 28-FEB-16:12 | 16177.52 | 0.04 |
March | 0.00 | 0.00 | 0.676350E+10 | 0.617179E+10 | 22768.58 | 28-MAR-15:11 | 16444.45 | 0.19 |
April | 0.00 | 0.00 | 0.136285E+11 | 0.108963E+11 | 28889.99 | 30-APR-15:13 | 15803.14 | 0.44 |
May | 0.00 | 0.00 | 0.290408E+11 | 0.191737E+11 | 39091.40 | 30-MAY-21:50 | 15428.16 | 0.67 |
June | 0.00 | 0.00 | 0.432391E+11 | 0.268732E+11 | 45326.50 | 29-JUN-08:03 | 17336.41 | 0.71 |
July | 0.00 | 0.00 | 0.542752E+11 | 0.303240E+11 | 49419.14 | 26-JUL-08:03 | 16840.26 | 0.76 |
August | 0.00 | 0.00 | 0.557534E+11 | 0.314557E+11 | 47641.65 | 11-AUG-08:03 | 16944.83 | 0.76 |
September | 0.00 | 0.00 | 0.387569E+11 | 0.234479E+11 | 45948.22 | 17-SEP-08:03 | 17077.80 | 0.74 |
October | 0.00 | 0.00 | 0.155261E+11 | 0.952863E+10 | 43943.87 | 18-OCT-21:52 | 15925.77 | 0.34 |
November | 0.00 | 0.00 | 0.542164E+10 | 0.391178E+10 | 27191.71 | 19-NOV-24:00 | 13347.24 | 0.15 |
December | 0.00 | 0.00 | 0.111084E+10 | 0.884764E+09 | 19411.65 | 12-DEC-13:30 | 14243.30 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.266011E+12 | 0.164979E+12 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 0.662235E+09 | 0.499543E+09 | 13220.25 | 7342.46 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.557534E+11 | 0.314557E+11 | 49419.14 | 17336.41 | 0.76 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 81089071.17 | 76578426.92 | 13883.73 | 28-JAN-16:11 | 13883.73 | 0.01 |
February | 0.00 | 0.00 | 0.485075E+09 | 0.419468E+09 | 13899.02 | 28-FEB-19:01 | 13899.02 | 0.05 |
March | 0.00 | 0.00 | 0.207768E+10 | 0.133154E+10 | 14362.13 | 28-MAR-15:11 | 11018.81 | 0.28 |
April | 0.00 | 0.00 | 0.401932E+10 | 0.215225E+10 | 15017.37 | 02-APR-15:11 | 10512.50 | 0.67 |
May | 0.00 | 0.00 | 0.644678E+10 | 0.323400E+10 | 15339.43 | 27-MAY-08:62 | 9626.55 | 0.85 |
June | 0.00 | 0.00 | 0.903191E+10 | 0.502052E+10 | 16139.10 | 29-JUN-08:62 | 9630.46 | 0.94 |
July | 0.00 | 0.00 | 0.105136E+11 | 0.595931E+10 | 16896.90 | 27-JUL-08:61 | 9015.05 | 0.94 |
August | 0.00 | 0.00 | 0.111451E+11 | 0.637252E+10 | 16516.45 | 29-AUG-08:62 | 9322.77 | 0.96 |
September | 0.00 | 0.00 | 0.717685E+10 | 0.358195E+10 | 16455.73 | 17-SEP-08:62 | 9362.62 | 0.89 |
October | 0.00 | 0.00 | 0.328738E+10 | 0.156829E+10 | 15985.05 | 18-OCT-08:62 | 8912.84 | 0.60 |
November | 0.00 | 0.00 | 0.945786E+09 | 0.550300E+09 | 15192.75 | 04-NOV-15:12 | 9508.22 | 0.21 |
December | 0.00 | 0.00 | 0.227682E+09 | 0.145288E+09 | 13894.44 | 07-DEC-16:11 | 13894.44 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.554383E+11 | 0.304120E+11 | 0.54 | |||
Minimum of Months | 0.00 | 0.00 | 81089071.17 | 76578426.92 | 13883.73 | 8912.84 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.111451E+11 | 0.637252E+10 | 16896.90 | 13899.02 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2902106.93 | 1910726.47 | 2076.05 | 16-JAN-16:13 | 2076.05 | 0.00 |
February | 0.00 | 0.00 | 71714324.00 | 50750388.33 | 12704.15 | 20-FEB-19:21 | 12704.15 | 0.02 |
March | 0.00 | 0.00 | 0.834680E+09 | 0.429326E+09 | 14063.20 | 28-MAR-18:01 | 11002.03 | 0.17 |
April | 0.00 | 0.00 | 0.250084E+10 | 0.120691E+10 | 15120.54 | 02-APR-15:11 | 10186.56 | 0.48 |
May | 0.00 | 0.00 | 0.501023E+10 | 0.255562E+10 | 16100.63 | 07-MAY-17:41 | 11601.44 | 0.63 |
June | 0.00 | 0.00 | 0.818459E+10 | 0.479535E+10 | 17155.28 | 26-JUN-08:21 | 9777.03 | 0.78 |
July | 0.00 | 0.00 | 0.953962E+10 | 0.566797E+10 | 17214.14 | 08-JUL-07:51 | 11169.17 | 0.79 |
August | 0.00 | 0.00 | 0.994398E+10 | 0.576644E+10 | 18399.16 | 20-AUG-07:52 | 9445.46 | 0.83 |
September | 0.00 | 0.00 | 0.537090E+10 | 0.263702E+10 | 16602.14 | 17-SEP-08:52 | 8769.50 | 0.67 |
October | 0.00 | 0.00 | 0.143180E+10 | 0.544914E+09 | 16039.17 | 18-OCT-21:52 | 9139.81 | 0.34 |
November | 0.00 | 0.00 | 0.128466E+09 | 56316970.07 | 14374.66 | 05-NOV-15:12 | 10766.36 | 0.07 |
December | 0.00 | 0.00 | 15316954.87 | 10618591.01 | 11327.62 | 07-DEC-16:11 | 11327.62 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.430351E+11 | 0.237231E+11 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 2902106.93 | 1910726.47 | 2076.05 | 2076.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.994398E+10 | 0.576644E+10 | 18399.16 | 12704.15 | 0.83 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.230854E+09 | 0.165350E+09 | 13833.19 | 29-JAN-16:10 | 13833.19 | 0.01 |
February | 0.00 | 0.00 | 0.397750E+10 | 0.391747E+10 | 28033.74 | 26-FEB-14:50 | 28033.74 | 0.01 |
March | 0.00 | 0.00 | 0.134770E+11 | 0.891251E+10 | 30773.32 | 30-MAR-13:30 | 19770.43 | 0.28 |
April | 0.00 | 0.00 | 0.174335E+11 | 0.778813E+10 | 25990.49 | 15-APR-13:50 | 17505.44 | 0.61 |
May | 0.00 | 0.00 | 0.252664E+11 | 0.885540E+10 | 23846.33 | 30-MAY-16:20 | 11618.22 | 0.87 |
June | 0.00 | 0.00 | 0.359940E+11 | 0.140320E+11 | 27751.34 | 13-JUN-17:15 | 16070.56 | 0.97 |
July | 0.00 | 0.00 | 0.438373E+11 | 0.180560E+11 | 31121.86 | 14-JUL-16:20 | 19107.13 | 0.99 |
August | 0.00 | 0.00 | 0.513312E+11 | 0.232927E+11 | 34736.74 | 19-AUG-15:10 | 23481.74 | 1.00 |
September | 0.00 | 0.00 | 0.368840E+11 | 0.163898E+11 | 38179.17 | 24-SEP-12:30 | 32305.82 | 0.94 |
October | 0.00 | 0.00 | 0.242801E+11 | 0.125794E+11 | 41514.30 | 10-OCT-13:30 | 37785.22 | 0.64 |
November | 0.00 | 0.00 | 0.124547E+11 | 0.960822E+10 | 32930.73 | 06-NOV-13:40 | 26155.13 | 0.21 |
December | 0.00 | 0.00 | 0.473056E+10 | 0.350296E+10 | 32138.41 | 12-DEC-12:30 | 20855.19 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.269897E+12 | 0.127100E+12 | 0.55 | |||
Minimum of Months | 0.00 | 0.00 | 0.230854E+09 | 0.165350E+09 | 13833.19 | 11618.22 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.513312E+11 | 0.232927E+11 | 41514.30 | 37785.22 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.594536E+09 | 0.207006E+09 | 74615.18 | 01-JAN-09:02 | 68968.26 | 0.04 |
February | 0.00 | 0.00 | 0.308001E+10 | 0.180915E+10 | 86832.78 | 18-FEB-09:02 | 63385.98 | 0.12 |
March | 0.00 | 0.00 | 0.108528E+11 | 0.634250E+10 | 84796.28 | 29-MAR-15:11 | 70521.99 | 0.26 |
April | 0.00 | 0.00 | 0.231902E+11 | 0.128673E+11 | 92131.02 | 30-APR-21:52 | 63502.43 | 0.46 |
May | 0.00 | 0.00 | 0.395622E+11 | 0.227209E+11 | 98542.99 | 07-MAY-17:41 | 68828.42 | 0.55 |
June | 0.00 | 0.00 | 0.563784E+11 | 0.350265E+11 | 103344.41 | 26-JUN-08:21 | 58337.60 | 0.71 |
July | 0.00 | 0.00 | 0.640594E+11 | 0.396191E+11 | 103423.55 | 23-JUL-08:51 | 59568.91 | 0.73 |
August | 0.00 | 0.00 | 0.643146E+11 | 0.384188E+11 | 114269.76 | 20-AUG-07:52 | 55491.28 | 0.76 |
September | 0.00 | 0.00 | 0.405269E+11 | 0.221177E+11 | 101680.27 | 17-SEP-08:52 | 56052.32 | 0.60 |
October | 0.00 | 0.00 | 0.169079E+11 | 0.763472E+10 | 101176.27 | 18-OCT-21:52 | 57937.33 | 0.46 |
November | 0.00 | 0.00 | 0.611308E+10 | 0.316616E+10 | 90306.94 | 05-NOV-21:52 | 61418.74 | 0.18 |
December | 0.00 | 0.00 | 0.145718E+10 | 0.608088E+09 | 87386.11 | 13-DEC-21:03 | 61389.19 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.327037E+12 | 0.190538E+12 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 0.594536E+09 | 0.207006E+09 | 74615.18 | 55491.28 | 0.04 | |
Maximum of Months | 0.00 | 0.00 | 0.643146E+11 | 0.396191E+11 | 114269.76 | 70521.99 | 0.76 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 42978905.27 | 34348860.07 | 12132.80 | 29-JAN-16:11 | 12132.80 | 0.01 |
February | 0.00 | 0.00 | 0.546191E+09 | 0.454189E+09 | 12547.39 | 28-FEB-19:01 | 12547.39 | 0.06 |
March | 0.00 | 0.00 | 0.180301E+10 | 0.106163E+10 | 13153.59 | 30-MAR-08:62 | 9483.68 | 0.31 |
April | 0.00 | 0.00 | 0.388573E+10 | 0.201688E+10 | 13630.66 | 02-APR-15:11 | 9467.43 | 0.70 |
May | 0.00 | 0.00 | 0.665101E+10 | 0.340728E+10 | 13929.50 | 27-MAY-08:62 | 8795.99 | 0.89 |
June | 0.00 | 0.00 | 0.927381E+10 | 0.521349E+10 | 14545.45 | 23-JUN-08:61 | 8759.91 | 0.97 |
July | 0.00 | 0.00 | 0.108950E+11 | 0.633599E+10 | 15276.97 | 27-JUL-08:61 | 8165.64 | 0.96 |
August | 0.00 | 0.00 | 0.112454E+11 | 0.654283E+10 | 14577.44 | 24-AUG-08:61 | 8723.45 | 0.97 |
September | 0.00 | 0.00 | 0.724739E+10 | 0.369852E+10 | 14892.17 | 17-SEP-08:62 | 8465.89 | 0.90 |
October | 0.00 | 0.00 | 0.324232E+10 | 0.153275E+10 | 14541.10 | 01-OCT-15:11 | 8745.61 | 0.62 |
November | 0.00 | 0.00 | 0.835185E+09 | 0.455549E+09 | 13675.35 | 04-NOV-15:12 | 8512.41 | 0.21 |
December | 0.00 | 0.00 | 0.183977E+09 | 99432012.71 | 13056.71 | 13-DEC-16:12 | 8528.63 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.558520E+11 | 0.308529E+11 | 0.56 | |||
Minimum of Months | 0.00 | 0.00 | 42978905.27 | 34348860.07 | 12132.80 | 8165.64 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.112454E+11 | 0.654283E+10 | 15276.97 | 12547.39 | 0.97 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4035185.33 | 2931619.37 | 1951.85 | 19-JAN-22:57 | 388.05 | 0.00 |
February | 0.00 | 0.00 | 0.143526E+09 | 96502021.26 | 11642.85 | 24-FEB-09:02 | 11642.85 | 0.03 |
March | 0.00 | 0.00 | 0.745877E+09 | 0.356672E+09 | 12714.61 | 28-MAR-18:01 | 9992.88 | 0.19 |
April | 0.00 | 0.00 | 0.249399E+10 | 0.122059E+10 | 13806.34 | 02-APR-15:11 | 9156.66 | 0.51 |
May | 0.00 | 0.00 | 0.519440E+10 | 0.269509E+10 | 14681.53 | 30-MAY-08:51 | 11365.72 | 0.66 |
June | 0.00 | 0.00 | 0.830402E+10 | 0.486695E+10 | 16045.84 | 13-JUN-08:61 | 11596.10 | 0.80 |
July | 0.00 | 0.00 | 0.977747E+10 | 0.592627E+10 | 15840.69 | 31-JUL-08:51 | 9948.46 | 0.80 |
August | 0.00 | 0.00 | 0.998655E+10 | 0.582184E+10 | 16738.45 | 20-AUG-07:52 | 8636.73 | 0.84 |
September | 0.00 | 0.00 | 0.539521E+10 | 0.268991E+10 | 15747.92 | 07-SEP-08:31 | 10492.99 | 0.69 |
October | 0.00 | 0.00 | 0.151163E+10 | 0.621181E+09 | 14563.57 | 18-OCT-21:52 | 8298.56 | 0.37 |
November | 0.00 | 0.00 | 0.150792E+09 | 64755235.01 | 13793.89 | 05-NOV-15:12 | 9050.78 | 0.06 |
December | 0.00 | 0.00 | 11482773.67 | 4718365.12 | 4517.07 | 12-DEC-22:53 | 1994.51 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.437190E+11 | 0.243674E+11 | 0.42 | |||
Minimum of Months | 0.00 | 0.00 | 4035185.33 | 2931619.37 | 1951.85 | 388.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.998655E+10 | 0.592627E+10 | 16738.45 | 11642.85 | 0.84 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 14593164.50 | 13886904.86 | 3646.77 | 29-JAN-16:11 | 3646.77 | 0.00 |
February | 0.00 | 0.00 | 0.114393E+09 | 0.101390E+09 | 3664.62 | 28-FEB-19:01 | 3664.62 | 0.04 |
March | 0.00 | 0.00 | 0.505273E+09 | 0.332029E+09 | 3801.88 | 30-MAR-08:62 | 2465.99 | 0.26 |
April | 0.00 | 0.00 | 0.998192E+09 | 0.566858E+09 | 3966.59 | 02-APR-15:11 | 2761.69 | 0.61 |
May | 0.00 | 0.00 | 0.164190E+10 | 0.858551E+09 | 4178.14 | 27-MAY-08:62 | 2318.29 | 0.84 |
June | 0.00 | 0.00 | 0.232672E+10 | 0.130604E+10 | 4448.94 | 23-JUN-08:61 | 2376.85 | 0.94 |
July | 0.00 | 0.00 | 0.271433E+10 | 0.154913E+10 | 4685.30 | 30-JUL-08:62 | 2149.54 | 0.94 |
August | 0.00 | 0.00 | 0.287443E+10 | 0.164416E+10 | 4545.97 | 29-AUG-08:62 | 2294.12 | 0.95 |
September | 0.00 | 0.00 | 0.176153E+10 | 0.886064E+09 | 4593.59 | 17-SEP-08:62 | 2251.52 | 0.86 |
October | 0.00 | 0.00 | 0.773979E+09 | 0.390119E+09 | 4357.08 | 18-OCT-08:62 | 2133.55 | 0.50 |
November | 0.00 | 0.00 | 0.216337E+09 | 0.132304E+09 | 4052.24 | 04-NOV-15:12 | 2455.17 | 0.16 |
December | 0.00 | 0.00 | 47116570.53 | 31462179.54 | 3663.94 | 07-DEC-16:11 | 3663.94 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.139888E+11 | 0.781199E+10 | 0.51 | |||
Minimum of Months | 0.00 | 0.00 | 14593164.50 | 13886904.86 | 3646.77 | 2133.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.287443E+10 | 0.164416E+10 | 4685.30 | 3664.62 | 0.95 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 739071.67 | 456071.37 | 678.53 | 19-JAN-22:57 | 139.59 | 0.00 |
February | 0.00 | 0.00 | 15686414.17 | 11000296.31 | 3372.92 | 20-FEB-19:21 | 3372.92 | 0.01 |
March | 0.00 | 0.00 | 0.195173E+09 | 0.103037E+09 | 3683.34 | 28-MAR-18:01 | 2909.77 | 0.15 |
April | 0.00 | 0.00 | 0.620732E+09 | 0.317212E+09 | 4004.60 | 02-APR-15:11 | 2660.96 | 0.44 |
May | 0.00 | 0.00 | 0.131581E+10 | 0.698711E+09 | 4289.29 | 07-MAY-17:41 | 3111.59 | 0.64 |
June | 0.00 | 0.00 | 0.214955E+10 | 0.127872E+10 | 4681.20 | 26-JUN-08:21 | 2412.64 | 0.78 |
July | 0.00 | 0.00 | 0.250579E+10 | 0.150427E+10 | 4640.97 | 08-JUL-07:51 | 2798.84 | 0.79 |
August | 0.00 | 0.00 | 0.259660E+10 | 0.151373E+10 | 5028.30 | 20-AUG-07:52 | 2262.18 | 0.83 |
September | 0.00 | 0.00 | 0.133919E+10 | 0.662902E+09 | 4508.32 | 17-SEP-08:52 | 2159.59 | 0.66 |
October | 0.00 | 0.00 | 0.321651E+09 | 0.130407E+09 | 4371.25 | 18-OCT-21:52 | 2286.59 | 0.26 |
November | 0.00 | 0.00 | 22411895.11 | 10138061.47 | 3715.40 | 05-NOV-15:12 | 2885.73 | 0.03 |
December | 0.00 | 0.00 | 1818860.46 | 1129096.14 | 1261.71 | 07-DEC-16:11 | 1261.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.110852E+11 | 0.623171E+10 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 739071.67 | 456071.37 | 678.53 | 139.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.259660E+10 | 0.151373E+10 | 5028.30 | 3372.92 | 0.83 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.950092E+09 | 0.852129E+09 | 16468.27 | 10-JAN-16:11 | 16468.27 | 0.04 |
February | 0.00 | 0.00 | 0.171918E+10 | 0.148674E+10 | 16743.10 | 20-FEB-19:21 | 16743.10 | 0.11 |
March | 0.00 | 0.00 | 0.410315E+10 | 0.279791E+10 | 16593.07 | 30-MAR-08:62 | 11571.42 | 0.37 |
April | 0.00 | 0.00 | 0.566064E+10 | 0.312554E+10 | 17893.46 | 21-APR-18:01 | 12530.80 | 0.68 |
May | 0.00 | 0.00 | 0.813516E+10 | 0.403916E+10 | 18489.05 | 31-MAY-08:61 | 11587.59 | 0.84 |
June | 0.00 | 0.00 | 0.110376E+11 | 0.591924E+10 | 20602.38 | 29-JUN-08:62 | 10388.43 | 0.93 |
July | 0.00 | 0.00 | 0.131912E+11 | 0.731396E+10 | 21319.01 | 27-JUL-08:61 | 9673.69 | 0.93 |
August | 0.00 | 0.00 | 0.147574E+11 | 0.869073E+10 | 20821.57 | 29-AUG-08:62 | 10207.28 | 0.95 |
September | 0.00 | 0.00 | 0.105107E+11 | 0.579087E+10 | 20366.68 | 17-SEP-08:62 | 10566.10 | 0.88 |
October | 0.00 | 0.00 | 0.670404E+10 | 0.392214E+10 | 19630.14 | 18-OCT-08:62 | 10068.28 | 0.69 |
November | 0.00 | 0.00 | 0.378813E+10 | 0.258793E+10 | 18029.27 | 04-NOV-15:12 | 11826.55 | 0.39 |
December | 0.00 | 0.00 | 0.194498E+10 | 0.156370E+10 | 17348.57 | 13-DEC-16:12 | 12068.82 | 0.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.825023E+11 | 0.480900E+11 | 0.58 | |||
Minimum of Months | 0.00 | 0.00 | 0.950092E+09 | 0.852129E+09 | 16468.27 | 9673.69 | 0.04 | |
Maximum of Months | 0.00 | 0.00 | 0.147574E+11 | 0.869073E+10 | 21319.01 | 16743.10 | 0.95 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 45282.52 | 161895.96 | 03-JAN-09:02 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 30807.32 | 151662.49 | 14-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 9293.90 | 129238.21 | 18-MAR-08:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4462.07 | 117218.89 | 06-APR-08:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 246.92 | 51438.91 | 13-MAY-15:11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 51.02 | 29449.94 | 03-JUN-21:56 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 8.35 | 12188.86 | 28-JUL-21:58 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 4.65 | 10715.67 | 30-AUG-21:56 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 122.86 | 28224.62 | 21-SEP-08:54 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3363.45 | 105650.49 | 31-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15209.82 | 127928.71 | 22-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 34685.08 | 156317.01 | 21-DEC-09:02 |
Annual Sum or Average | 0.00 | 11883.31 | ||||
Minimum of Months | 0.00 | 0.00 | 4.65 | 10715.67 | ||
Maximum of Months | 0.00 | 0.00 | 45282.52 | 161895.96 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5888.31 | 191814.17 | 19-JAN-22:53 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 19886.81 | 332830.55 | 26-FEB-16:11 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 52926.44 | 409812.65 | 30-MAR-18:03 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 106337.61 | 420405.42 | 02-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 189115.36 | 509975.91 | 30-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 296857.84 | 568806.74 | 26-JUN-21:52 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 359978.53 | 587468.30 | 25-JUL-21:52 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 382730.09 | 651032.50 | 23-AUG-21:52 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 256610.53 | 577240.45 | 16-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 105453.34 | 574138.52 | 18-OCT-21:52 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 41765.85 | 390561.99 | 05-NOV-15:13 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 10996.48 | 201098.64 | 13-DEC-11:35 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 153215.70 | 0.00 | ||||
Minimum of Months | 5888.31 | 191814.17 | 0.00 | 0.00 | ||
Maximum of Months | 382730.09 | 651032.50 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 26247.48 | 53499.38 | 27-JAN-07:57 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 26301.35 | 53539.43 | 03-FEB-07:57 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25489.79 | 52644.73 | 01-MAR-07:55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23943.90 | 49789.34 | 03-APR-06:32 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22131.26 | 46409.95 | 01-MAY-06:55 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20523.10 | 42540.19 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19532.19 | 39755.25 | 03-JUL-06:54 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 19481.35 | 39561.63 | 30-AUG-06:55 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 20327.78 | 42005.61 | 29-SEP-06:53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21867.81 | 45784.74 | 31-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 23685.38 | 49454.89 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 25284.05 | 52180.79 | 28-DEC-07:53 |
Annual Sum or Average | 0.00 | 22881.90 | ||||
Minimum of Months | 0.00 | 0.00 | 19481.35 | 39561.63 | ||
Maximum of Months | 0.00 | 0.00 | 26301.35 | 53539.43 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261333E+10 | 0.69 | 1299.30 | 01-JAN-00:05 | 0.91 |
February | 0.236042E+10 | 0.69 | 1299.30 | 01-FEB-00:05 | 0.91 |
March | 0.261333E+10 | 0.69 | 1299.30 | 01-MAR-00:05 | 0.91 |
April | 0.252903E+10 | 0.69 | 1299.30 | 01-APR-00:10 | 0.91 |
May | 0.261333E+10 | 0.69 | 1299.30 | 01-MAY-00:10 | 0.90 |
June | 0.252903E+10 | 0.69 | 1299.30 | 01-JUN-00:10 | 0.90 |
July | 0.261333E+10 | 0.69 | 1299.30 | 01-JUL-00:10 | 0.90 |
August | 0.261333E+10 | 0.69 | 1299.30 | 01-AUG-00:10 | 0.90 |
September | 0.252903E+10 | 0.69 | 1299.30 | 01-SEP-00:10 | 0.90 |
October | 0.261333E+10 | 0.69 | 1299.30 | 01-OCT-00:10 | 0.90 |
November | 0.252903E+10 | 0.69 | 1299.30 | 01-NOV-00:10 | 0.91 |
December | 0.261333E+10 | 0.69 | 1299.30 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.307698E+11 | 0.69 | |||
Minimum of Months | 0.236042E+10 | 0.69 | 1299.30 | 0.90 | |
Maximum of Months | 0.261333E+10 | 0.69 | 1299.30 | 0.91 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.397188E+11 | 0.94 | 21180.34 | 30-JAN-20:10 | 1.15 |
February | 0.363540E+11 | 0.94 | 21304.56 | 28-FEB-22:10 | 1.16 |
March | 0.411738E+11 | 0.95 | 24982.64 | 30-MAR-21:07 | 1.27 |
April | 0.404413E+11 | 0.96 | 25117.41 | 18-APR-21:10 | 1.27 |
May | 0.427432E+11 | 0.97 | 25804.87 | 19-MAY-21:05 | 1.30 |
June | 0.430365E+11 | 0.99 | 28792.86 | 13-JUN-21:30 | 1.38 |
July | 0.451122E+11 | 1.00 | 30245.18 | 07-JUL-21:20 | 1.43 |
August | 0.458495E+11 | 1.01 | 31617.91 | 18-AUG-21:20 | 1.47 |
September | 0.427587E+11 | 0.98 | 31232.92 | 07-SEP-21:20 | 1.45 |
October | 0.426426E+11 | 0.97 | 28063.07 | 10-OCT-21:10 | 1.36 |
November | 0.406015E+11 | 0.96 | 23252.60 | 07-NOV-19:40 | 1.23 |
December | 0.404042E+11 | 0.94 | 22494.06 | 01-DEC-19:20 | 1.20 |
Annual Sum or Average | 0.500836E+12 | 0.97 | |||
Minimum of Months | 0.363540E+11 | 0.94 | 21180.34 | 1.15 | |
Maximum of Months | 0.458495E+11 | 1.01 | 31617.91 | 1.47 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:05 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:05 | 0.27 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:05 | 0.28 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:10 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:10 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:10 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:10 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:10 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:05 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | -0.0 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | -0.0 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:10 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.28 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.305604E+09 | 0.43 | 666.09 | 01-JAN-16:12 | 0.59 |
February | 0.217287E+09 | 0.43 | 666.09 | 01-FEB-09:02 | 0.60 |
March | 0.152388E+09 | 0.45 | 666.09 | 03-MAR-16:11 | 0.60 |
April | 0.195756E+09 | 0.49 | 666.09 | 01-APR-15:12 | 0.59 |
May | 0.267220E+09 | 0.53 | 666.09 | 01-MAY-15:11 | 0.59 |
June | 0.364991E+09 | 0.56 | 666.09 | 01-JUN-08:61 | 0.59 |
July | 0.417295E+09 | 0.56 | 666.09 | 01-JUL-08:61 | 0.59 |
August | 0.436486E+09 | 0.57 | 666.09 | 01-AUG-08:61 | 0.59 |
September | 0.286499E+09 | 0.54 | 666.09 | 01-SEP-08:62 | 0.59 |
October | 0.181607E+09 | 0.48 | 666.09 | 01-OCT-15:11 | 0.59 |
November | 0.140260E+09 | 0.44 | 666.09 | 01-NOV-08:62 | 0.59 |
December | 0.217167E+09 | 0.42 | 666.09 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.318256E+10 | 0.49 | |||
Minimum of Months | 0.140260E+09 | 0.42 | 666.09 | 0.59 | |
Maximum of Months | 0.436486E+09 | 0.57 | 666.09 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.384559E+09 | 0.47 | 658.49 | 01-JAN-16:12 | 0.59 |
February | 0.250650E+09 | 0.42 | 658.49 | 01-FEB-09:02 | 0.60 |
March | 0.108332E+09 | 0.34 | 658.49 | 03-MAR-09:02 | 0.59 |
April | 0.130028E+09 | 0.36 | 658.49 | 01-APR-08:62 | 0.59 |
May | 0.208279E+09 | 0.39 | 658.49 | 01-MAY-21:51 | 0.59 |
June | 0.335423E+09 | 0.46 | 658.49 | 01-JUN-08:51 | 0.59 |
July | 0.386541E+09 | 0.47 | 658.49 | 01-JUL-08:31 | 0.59 |
August | 0.392447E+09 | 0.49 | 658.49 | 01-AUG-07:51 | 0.59 |
September | 0.213235E+09 | 0.40 | 658.49 | 01-SEP-08:51 | 0.59 |
October | 0.106560E+09 | 0.34 | 658.49 | 01-OCT-21:52 | 0.59 |
November | 0.134074E+09 | 0.36 | 658.49 | 01-NOV-08:62 | 0.59 |
December | 0.256072E+09 | 0.41 | 658.49 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.290620E+10 | 0.41 | |||
Minimum of Months | 0.106560E+09 | 0.34 | 658.49 | 0.59 | |
Maximum of Months | 0.392447E+09 | 0.49 | 658.49 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 26225255.02 | 0.03 | 494.02 | 29-JAN-16:10 | 0.60 |
February | 0.146352E+09 | 0.09 | 893.05 | 26-FEB-14:50 | 0.60 |
March | 0.497806E+09 | 0.31 | 902.49 | 30-MAR-13:35 | 0.59 |
April | 0.632902E+09 | 0.42 | 843.29 | 15-APR-13:50 | 0.59 |
May | 0.854427E+09 | 0.53 | 719.40 | 19-MAY-17:20 | 0.59 |
June | 0.114934E+10 | 0.58 | 816.65 | 13-JUN-17:15 | 0.59 |
July | 0.133890E+10 | 0.59 | 909.68 | 08-JUL-17:30 | 0.59 |
August | 0.154090E+10 | 0.59 | 999.57 | 19-AUG-13:40 | 0.59 |
September | 0.116553E+10 | 0.56 | 1138.64 | 24-SEP-12:40 | 0.59 |
October | 0.828676E+09 | 0.40 | 1225.24 | 10-OCT-13:30 | 0.59 |
November | 0.451753E+09 | 0.28 | 1024.64 | 06-NOV-14:00 | 0.59 |
December | 0.176330E+09 | 0.12 | 948.87 | 10-DEC-14:30 | 0.60 |
Annual Sum or Average | 0.880914E+10 | 0.38 | |||
Minimum of Months | 26225255.02 | 0.03 | 494.02 | 0.59 | |
Maximum of Months | 0.154090E+10 | 0.59 | 1225.24 | 0.60 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.155154E+10 | 0.39 | 4023.80 | 01-JAN-09:02 | 0.59 |
February | 0.102828E+10 | 0.37 | 4023.80 | 01-FEB-16:12 | 0.60 |
March | 0.640190E+09 | 0.32 | 4023.80 | 01-MAR-09:02 | 0.60 |
April | 0.100814E+10 | 0.32 | 4023.80 | 01-APR-08:62 | 0.60 |
May | 0.161160E+10 | 0.34 | 4023.80 | 01-MAY-08:53 | 0.59 |
June | 0.237943E+10 | 0.42 | 4023.80 | 01-JUN-08:51 | 0.59 |
July | 0.264153E+10 | 0.43 | 4023.80 | 01-JUL-08:31 | 0.59 |
August | 0.261930E+10 | 0.45 | 4023.80 | 01-AUG-07:51 | 0.59 |
September | 0.160069E+10 | 0.35 | 4023.80 | 01-SEP-08:51 | 0.59 |
October | 0.753449E+09 | 0.32 | 4023.80 | 01-OCT-08:53 | 0.59 |
November | 0.605605E+09 | 0.34 | 4023.80 | 01-NOV-21:53 | 0.59 |
December | 0.984241E+09 | 0.39 | 4023.80 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.174240E+11 | 0.37 | |||
Minimum of Months | 0.605605E+09 | 0.32 | 4023.80 | 0.59 | |
Maximum of Months | 0.264153E+10 | 0.45 | 4023.80 | 0.60 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.297078E+09 | 0.43 | 600.34 | 01-JAN-16:12 | 0.59 |
February | 0.211067E+09 | 0.43 | 600.34 | 01-FEB-09:02 | 0.60 |
March | 0.136607E+09 | 0.46 | 600.34 | 02-MAR-16:12 | 0.59 |
April | 0.183994E+09 | 0.51 | 600.34 | 01-APR-15:12 | 0.59 |
May | 0.268201E+09 | 0.55 | 600.34 | 01-MAY-15:11 | 0.59 |
June | 0.372894E+09 | 0.57 | 600.34 | 01-JUN-08:61 | 0.59 |
July | 0.430488E+09 | 0.57 | 600.34 | 01-JUL-08:61 | 0.59 |
August | 0.438674E+09 | 0.57 | 600.34 | 01-AUG-08:61 | 0.59 |
September | 0.284632E+09 | 0.54 | 600.34 | 01-SEP-08:62 | 0.59 |
October | 0.171013E+09 | 0.49 | 600.34 | 01-OCT-08:62 | 0.59 |
November | 0.128231E+09 | 0.44 | 600.34 | 01-NOV-08:62 | 0.59 |
December | 0.196805E+09 | 0.41 | 600.34 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.311968E+10 | 0.50 | |||
Minimum of Months | 0.128231E+09 | 0.41 | 600.34 | 0.59 | |
Maximum of Months | 0.438674E+09 | 0.57 | 600.34 | 0.60 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.381164E+09 | 0.46 | 594.94 | 01-JAN-16:12 | 0.59 |
February | 0.237769E+09 | 0.42 | 594.94 | 01-FEB-09:02 | 0.60 |
March | 99514603.44 | 0.34 | 594.94 | 03-MAR-09:02 | 0.59 |
April | 0.125269E+09 | 0.39 | 594.94 | 02-APR-15:11 | 0.59 |
May | 0.212198E+09 | 0.41 | 594.94 | 01-MAY-08:53 | 0.59 |
June | 0.340848E+09 | 0.48 | 594.94 | 01-JUN-08:51 | 0.59 |
July | 0.395494E+09 | 0.48 | 594.94 | 01-JUL-08:31 | 0.59 |
August | 0.395631E+09 | 0.50 | 594.94 | 01-AUG-07:51 | 0.59 |
September | 0.210517E+09 | 0.42 | 594.94 | 01-SEP-08:51 | 0.59 |
October | 0.105526E+09 | 0.36 | 594.94 | 01-OCT-21:52 | 0.59 |
November | 0.124417E+09 | 0.34 | 594.94 | 01-NOV-08:62 | 0.59 |
December | 0.241564E+09 | 0.41 | 594.94 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.286991E+10 | 0.42 | |||
Minimum of Months | 99514603.44 | 0.34 | 594.94 | 0.59 | |
Maximum of Months | 0.395631E+09 | 0.50 | 594.94 | 0.60 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.105178E+09 | 0.45 | 175.75 | 01-JAN-09:02 | 0.59 |
February | 71699238.73 | 0.45 | 175.75 | 01-FEB-09:02 | 0.60 |
March | 44925051.56 | 0.45 | 175.75 | 02-MAR-09:02 | 0.59 |
April | 52650722.28 | 0.49 | 175.75 | 01-APR-15:12 | 0.59 |
May | 69614638.34 | 0.53 | 175.75 | 01-MAY-15:11 | 0.59 |
June | 95540853.55 | 0.56 | 175.75 | 01-JUN-08:61 | 0.59 |
July | 0.109757E+09 | 0.56 | 175.75 | 01-JUL-08:61 | 0.59 |
August | 0.114372E+09 | 0.56 | 175.75 | 01-AUG-08:61 | 0.59 |
September | 72262473.62 | 0.53 | 175.75 | 01-SEP-08:62 | 0.59 |
October | 49541569.29 | 0.48 | 175.75 | 01-OCT-15:11 | 0.59 |
November | 44222160.60 | 0.44 | 175.75 | 01-NOV-08:62 | 0.59 |
December | 70219075.29 | 0.43 | 175.75 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.899983E+09 | 0.49 | |||
Minimum of Months | 44222160.60 | 0.43 | 175.75 | 0.59 | |
Maximum of Months | 0.114372E+09 | 0.56 | 175.75 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.130355E+09 | 0.50 | 173.57 | 01-JAN-09:02 | 0.59 |
February | 81893186.75 | 0.44 | 173.57 | 01-FEB-09:02 | 0.60 |
March | 33852108.07 | 0.35 | 173.57 | 02-MAR-09:02 | 0.59 |
April | 35554369.25 | 0.37 | 173.57 | 02-APR-15:11 | 0.59 |
May | 55512656.70 | 0.40 | 173.57 | 01-MAY-21:51 | 0.59 |
June | 89739011.02 | 0.47 | 173.57 | 01-JUN-08:51 | 0.59 |
July | 0.103535E+09 | 0.47 | 173.57 | 01-JUL-08:31 | 0.59 |
August | 0.103845E+09 | 0.49 | 173.57 | 01-AUG-07:51 | 0.59 |
September | 54399323.02 | 0.40 | 173.57 | 01-SEP-08:51 | 0.59 |
October | 31748579.41 | 0.34 | 173.57 | 01-OCT-21:52 | 0.59 |
November | 45432377.68 | 0.36 | 173.57 | 01-NOV-08:62 | 0.59 |
December | 84526471.58 | 0.44 | 173.57 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.850394E+09 | 0.42 | |||
Minimum of Months | 31748579.41 | 0.34 | 173.57 | 0.59 | |
Maximum of Months | 0.130355E+09 | 0.50 | 173.57 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.323259E+09 | 0.46 | 785.84 | 01-JAN-16:12 | 0.59 |
February | 0.248914E+09 | 0.45 | 785.84 | 01-FEB-09:02 | 0.60 |
March | 0.234437E+09 | 0.48 | 785.84 | 02-MAR-16:12 | 0.59 |
April | 0.265906E+09 | 0.50 | 785.84 | 01-APR-08:62 | 0.59 |
May | 0.327515E+09 | 0.53 | 785.84 | 01-MAY-15:11 | 0.59 |
June | 0.439308E+09 | 0.55 | 785.84 | 01-JUN-08:61 | 0.59 |
July | 0.512974E+09 | 0.55 | 785.84 | 01-JUL-08:61 | 0.59 |
August | 0.578637E+09 | 0.56 | 785.84 | 01-AUG-08:61 | 0.59 |
September | 0.416858E+09 | 0.53 | 785.84 | 01-SEP-08:62 | 0.59 |
October | 0.318431E+09 | 0.51 | 785.84 | 01-OCT-08:62 | 0.59 |
November | 0.232678E+09 | 0.49 | 785.84 | 01-NOV-15:11 | 0.59 |
December | 0.251488E+09 | 0.46 | 785.84 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.415040E+10 | 0.51 | |||
Minimum of Months | 0.232678E+09 | 0.45 | 785.84 | 0.59 | |
Maximum of Months | 0.578637E+09 | 0.56 | 785.84 | 0.60 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.960079E+09 | 0.872712E+09 | 747.62 | 03-JAN-09:02 | 679.59 | 679.59 | 32.56 | 1.41 |
February | 0.596634E+09 | 0.542340E+09 | 719.82 | 14-FEB-09:02 | 654.31 | 654.31 | 31.82 | 1.29 |
March | 0.213088E+09 | 0.193697E+09 | 653.34 | 18-MAR-08:03 | 593.89 | 593.89 | 30.70 | 1.06 |
April | 94777450.27 | 86152702.29 | 655.95 | 06-APR-03:50 | 596.26 | 596.26 | 40.28 | 1.06 |
May | 5608252.93 | 5097901.92 | 358.83 | 13-MAY-15:11 | 326.18 | 326.18 | 32.28 | 0.44 |
June | 1128780.07 | 1026061.08 | 221.70 | 03-JUN-21:56 | 201.52 | 201.52 | 32.14 | 0.25 |
July | 272475.77 | 247680.47 | 131.04 | 28-JUL-21:58 | 119.11 | 119.11 | 39.52 | 0.14 |
August | 178106.33 | 161898.65 | 162.75 | 30-AUG-21:56 | 147.94 | 147.94 | 45.69 | 0.18 |
September | 3885130.56 | 3531583.68 | 250.63 | 29-SEP-08:06 | 227.82 | 227.82 | 50.32 | 0.29 |
October | 96643662.48 | 87849089.19 | 613.29 | 26-OCT-05:00 | 557.48 | 557.48 | 36.75 | 0.94 |
November | 0.339342E+09 | 0.308462E+09 | 741.35 | 22-NOV-09:02 | 673.89 | 673.89 | 39.04 | 1.38 |
December | 0.738924E+09 | 0.671682E+09 | 724.43 | 21-DEC-09:02 | 658.50 | 658.50 | 31.38 | 1.31 |
Annual Sum or Average | 0.305056E+10 | 0.277296E+10 | ||||||
Minimum of Months | 178106.33 | 161898.65 | 131.04 | 119.11 | 119.11 | 30.70 | 0.14 | |
Maximum of Months | 0.960079E+09 | 0.872712E+09 | 747.62 | 679.59 | 679.59 | 50.32 | 1.41 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 4251210.13 | 3864350.01 | 87.31 | 19-JAN-22:53 | 79.36 | 79.36 | 6.72 | 4.77 |
February | 15150643.85 | 13771935.26 | 244.70 | 26-FEB-16:13 | 222.43 | 222.43 | 6.72 | 7.84 |
March | 77314419.16 | 70278807.01 | 531.19 | 30-MAR-15:11 | 482.85 | 482.85 | 6.72 | 11.13 |
April | 0.194450E+09 | 0.176755E+09 | 816.94 | 13-APR-15:50 | 742.60 | 742.60 | 6.72 | 13.41 |
May | 0.375251E+09 | 0.341103E+09 | 773.51 | 14-MAY-18:03 | 703.12 | 703.12 | 6.72 | 13.10 |
June | 0.731344E+09 | 0.664791E+09 | 1023.76 | 28-JUN-18:03 | 930.59 | 930.59 | 6.72 | 14.76 |
July | 0.989235E+09 | 0.899214E+09 | 1157.49 | 06-JUL-18:03 | 1052.16 | 1052.16 | 6.72 | 15.54 |
August | 0.110676E+10 | 0.100604E+10 | 1149.19 | 10-AUG-18:03 | 1044.61 | 1044.61 | 6.72 | 15.49 |
September | 0.575967E+09 | 0.523554E+09 | 996.60 | 07-SEP-18:03 | 905.91 | 905.91 | 6.72 | 14.59 |
October | 0.195120E+09 | 0.177364E+09 | 818.91 | 18-OCT-18:03 | 744.39 | 744.39 | 6.72 | 13.42 |
November | 44033023.27 | 40026018.16 | 363.60 | 05-NOV-15:12 | 330.51 | 330.51 | 6.72 | 9.40 |
December | 9943953.93 | 9039054.12 | 126.35 | 13-DEC-09:55 | 114.85 | 114.85 | 6.72 | 5.73 |
Annual Sum or Average | 0.431882E+10 | 0.392581E+10 | ||||||
Minimum of Months | 4251210.13 | 3864350.01 | 87.31 | 79.36 | 79.36 | 6.72 | 4.77 | |
Maximum of Months | 0.110676E+10 | 0.100604E+10 | 1157.49 | 1052.16 | 1052.16 | 6.72 | 15.54 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.391072E+10 | 0.355484E+10 | 2957.60 | 01-JAN-01:00 | 2688.46 | 2688.46 | 6.73 | 26.42 |
February | 0.411714E+10 | 0.374248E+10 | 2957.60 | 01-FEB-00:05 | 2688.46 | 2688.46 | 6.75 | 26.42 |
March | 0.641513E+10 | 0.583135E+10 | 2957.60 | 01-MAR-00:05 | 2688.46 | 2688.46 | 7.08 | 26.42 |
April | 0.731119E+10 | 0.664587E+10 | 2957.60 | 01-APR-00:10 | 2688.46 | 2688.46 | 6.83 | 26.42 |
May | 0.791099E+10 | 0.719109E+10 | 2957.60 | 01-MAY-00:10 | 2688.46 | 2688.46 | 7.86 | 26.42 |
June | 0.766610E+10 | 0.696849E+10 | 2957.60 | 01-JUN-00:10 | 2688.46 | 2688.46 | 9.00 | 26.42 |
July | 0.792164E+10 | 0.720077E+10 | 2957.60 | 01-JUL-00:10 | 2688.46 | 2688.46 | 9.98 | 26.42 |
August | 0.792164E+10 | 0.720077E+10 | 2957.60 | 01-AUG-00:10 | 2688.46 | 2688.46 | 9.65 | 26.42 |
September | 0.765546E+10 | 0.695881E+10 | 2957.60 | 01-SEP-00:10 | 2688.46 | 2688.46 | 8.86 | 26.42 |
October | 0.718928E+10 | 0.653505E+10 | 2957.60 | 01-OCT-00:10 | 2688.46 | 2688.46 | 7.40 | 26.42 |
November | 0.568061E+10 | 0.516367E+10 | 2957.60 | 01-NOV-05:10 | 2688.46 | 2688.46 | 6.74 | 26.42 |
December | 0.373862E+10 | 0.339840E+10 | 2957.60 | 01-DEC-01:40 | 2688.46 | 2688.46 | 6.72 | 26.42 |
Annual Sum or Average | 0.774385E+11 | 0.703916E+11 | ||||||
Minimum of Months | 0.373862E+10 | 0.339840E+10 | 2957.60 | 2688.46 | 2688.46 | 6.72 | 26.42 | |
Maximum of Months | 0.792164E+10 | 0.720077E+10 | 2957.60 | 2688.46 | 2688.46 | 9.98 | 26.42 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 48.98 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 49.50 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 49.19 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.28 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 52.51 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 53.16 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.47 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 54.36 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 53.37 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.34 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 52.92 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 50.39 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.98 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.36 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 36.53 | 60.00 | 45282.52 | 161895.96 | 03-JAN-09:02 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 49.90 | 60.00 | 30807.32 | 151662.49 | 14-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 48.33 | 48.33 | 9293.90 | 129238.21 | 18-MAR-08:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 33.47 | 60.00 | 4462.07 | 117218.89 | 06-APR-08:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 33.56 | 33.56 | 246.92 | 51438.91 | 13-MAY-15:11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 36.60 | 36.60 | 51.02 | 29449.94 | 03-JUN-21:56 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 40.89 | 40.89 | 8.35 | 12188.86 | 28-JUL-21:58 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 41.04 | 41.04 | 4.65 | 10715.67 | 30-AUG-21:56 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 45.29 | 45.29 | 122.86 | 28224.62 | 21-SEP-08:54 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 50.19 | 60.00 | 3363.45 | 105650.49 | 31-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 49.49 | 60.00 | 15209.82 | 127928.71 | 22-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 36.49 | 60.00 | 34685.08 | 156317.01 | 21-DEC-09:02 |
Annual Sum or Average | 0.00 | 11883.31 | ||||||
Minimum of Months | 0.00 | 0.00 | 33.47 | 33.56 | 4.65 | 10715.67 | ||
Maximum of Months | 0.00 | 0.00 | 50.19 | 60.00 | 45282.52 | 161895.96 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5888.31 | 191814.17 | 19-JAN-22:53 | 8.43 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 19886.81 | 332830.55 | 26-FEB-16:11 | 9.71 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 52926.44 | 409812.65 | 30-MAR-18:03 | 10.40 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 106337.61 | 420405.42 | 02-APR-18:03 | 10.50 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 189115.36 | 509975.91 | 30-MAY-18:03 | 11.31 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 296857.84 | 568806.74 | 26-JUN-21:52 | 11.84 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 359978.53 | 587468.30 | 25-JUL-21:52 | 12.01 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 382730.09 | 651032.50 | 23-AUG-21:52 | 12.58 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 256610.53 | 577240.45 | 16-SEP-18:03 | 11.92 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 105453.34 | 574138.52 | 18-OCT-21:52 | 11.89 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 41765.85 | 390561.99 | 05-NOV-15:13 | 10.23 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 10996.48 | 201098.64 | 13-DEC-11:35 | 8.52 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 153215.70 | 0.00 | ||||||
Minimum of Months | 5888.31 | 191814.17 | 8.43 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 382730.09 | 651032.50 | 12.58 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 48.98 | 59.72 | 26247.48 | 53499.38 | 27-JAN-07:57 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 49.50 | 59.03 | 26301.35 | 53539.43 | 03-FEB-07:57 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 49.19 | 58.22 | 25489.79 | 52644.73 | 01-MAR-07:55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.28 | 58.70 | 23943.90 | 49789.34 | 03-APR-06:32 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 52.51 | 58.39 | 22131.26 | 46409.95 | 01-MAY-06:55 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 53.16 | 58.56 | 20523.10 | 42540.19 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.47 | 58.48 | 19532.19 | 39755.25 | 03-JUL-06:54 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 54.36 | 59.72 | 19481.35 | 39561.63 | 30-AUG-06:55 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 53.37 | 58.32 | 20327.78 | 42005.61 | 29-SEP-06:53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.34 | 58.30 | 21867.81 | 45784.74 | 31-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 52.92 | 58.81 | 23685.38 | 49454.89 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 50.39 | 59.63 | 25284.05 | 52180.79 | 28-DEC-07:53 |
Annual Sum or Average | 0.00 | 22881.90 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.98 | 58.22 | 19481.35 | 39561.63 | ||
Maximum of Months | 0.00 | 0.00 | 54.36 | 59.72 | 26301.35 | 53539.43 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.750759E+11 | 0.00 | 0.963208E+10 | 0.397188E+11 | 0.00 | 0.00 |
February | 0.476637E+11 | 0.00 | 0.323884E+11 | 0.363540E+11 | 0.00 | 0.00 |
March | 0.200416E+11 | 0.00 | 0.945528E+11 | 0.411738E+11 | 0.00 | 0.00 |
April | 0.102420E+11 | 0.00 | 0.194542E+12 | 0.404413E+11 | 0.00 | 0.00 |
May | 0.568897E+09 | 0.00 | 0.371113E+12 | 0.427432E+11 | 0.00 | 0.00 |
June | 0.111135E+09 | 0.00 | 0.576672E+12 | 0.430365E+11 | 0.00 | 0.00 |
July | 13235621.99 | 0.00 | 0.735826E+12 | 0.451122E+11 | 0.00 | 0.00 |
August | 1133120.78 | 0.00 | 0.784141E+12 | 0.458495E+11 | 0.00 | 0.00 |
September | 0.225528E+09 | 0.00 | 0.503292E+12 | 0.427587E+11 | 0.00 | 0.00 |
October | 0.616754E+10 | 0.00 | 0.201925E+12 | 0.426426E+11 | 0.00 | 0.00 |
November | 0.292390E+11 | 0.00 | 0.730198E+11 | 0.406015E+11 | 0.00 | 0.00 |
December | 0.653274E+11 | 0.00 | 0.163251E+11 | 0.404042E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.254677E+12 | 0.00 | 0.359343E+13 | 0.500836E+12 | 0.00 | 0.00 |
Minimum of Months | 1133120.78 | 0.00 | 0.963208E+10 | 0.363540E+11 | 0.00 | 0.00 |
Maximum of Months | 0.750759E+11 | 0.00 | 0.784141E+12 | 0.458495E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.706109E+09 | 0.00 | 0.662235E+09 | 0.261333E+10 | 0.00 | 0.00 |
February | 0.585755E+09 | 0.00 | 0.183268E+10 | 0.236042E+10 | 0.00 | 0.00 |
March | 5547.33 | 0.00 | 0.676350E+10 | 0.261333E+10 | 0.00 | 0.00 |
April | 8510.40 | 0.00 | 0.136285E+11 | 0.252903E+10 | 0.00 | 0.00 |
May | 10182.59 | 0.00 | 0.290408E+11 | 0.261333E+10 | 0.00 | 0.00 |
June | 8518.74 | 0.00 | 0.432391E+11 | 0.252903E+10 | 0.00 | 0.00 |
July | 9236.31 | 0.00 | 0.542752E+11 | 0.261333E+10 | 0.00 | 0.00 |
August | 8966.66 | 0.00 | 0.557534E+11 | 0.261333E+10 | 0.00 | 0.00 |
September | 12672.93 | 0.00 | 0.387569E+11 | 0.252903E+10 | 0.00 | 0.00 |
October | 12008.64 | 0.00 | 0.155261E+11 | 0.261333E+10 | 0.00 | 0.00 |
November | 35680551.68 | 0.00 | 0.542164E+10 | 0.252903E+10 | 0.00 | 0.00 |
December | 0.120005E+09 | 0.00 | 0.111084E+10 | 0.261333E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.144762E+10 | 0.00 | 0.266011E+12 | 0.307698E+11 | 0.00 | 0.00 |
Minimum of Months | 5547.33 | 0.00 | 0.662235E+09 | 0.236042E+10 | 0.00 | 0.00 |
Maximum of Months | 0.706109E+09 | 0.00 | 0.557534E+11 | 0.261333E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.397188E+11 | 0.963208E+10 | 0.750759E+11 | 0.142650E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363540E+11 | 0.323884E+11 | 0.476637E+11 | 0.772396E+11 | 30237814.83 | 0.00 | 0.00 | 0.00 |
March | 0.411738E+11 | 0.945528E+11 | 0.200416E+11 | 0.825880E+09 | 0.476020E+09 | 0.00 | 0.00 | 0.00 |
April | 0.404413E+11 | 0.194542E+12 | 0.102420E+11 | 0.124787E+10 | 0.340781E+10 | 0.00 | 0.00 | 0.00 |
May | 0.427432E+11 | 0.371113E+12 | 0.568897E+09 | 0.00 | 0.216190E+11 | 0.00 | 0.00 | 0.00 |
June | 0.430365E+11 | 0.576672E+12 | 0.111135E+09 | 0.00 | 0.838756E+11 | 0.00 | 0.00 | 0.00 |
July | 0.451122E+11 | 0.735826E+12 | 13235621.99 | 0.00 | 0.135099E+12 | 0.00 | 0.00 | 0.00 |
August | 0.458495E+11 | 0.784141E+12 | 1133120.78 | 0.00 | 0.168744E+12 | 0.00 | 0.00 | 0.00 |
September | 0.427587E+11 | 0.503292E+12 | 0.225528E+09 | 0.00 | 0.518628E+11 | 0.00 | 0.00 | 0.00 |
October | 0.426426E+11 | 0.201925E+12 | 0.616754E+10 | 0.00 | 0.934362E+10 | 0.00 | 0.00 | 0.00 |
November | 0.406015E+11 | 0.730198E+11 | 0.292390E+11 | 0.105765E+11 | 0.175876E+09 | 0.00 | 0.00 | 0.00 |
December | 0.404042E+11 | 0.163251E+11 | 0.653274E+11 | 0.374844E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.500836E+12 | 0.359343E+13 | 0.254677E+12 | 0.270024E+12 | 0.474634E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.363540E+11 | 0.963208E+10 | 1133120.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.458495E+11 | 0.784141E+12 | 0.750759E+11 | 0.142650E+12 | 0.168744E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261333E+10 | 0.662235E+09 | 0.706109E+09 | 0.402180E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.183268E+10 | 0.585755E+09 | 0.252703E+11 | 2004059.51 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.676350E+10 | 5547.33 | 0.116090E+11 | 0.361293E+09 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.136285E+11 | 8510.40 | 0.540703E+10 | 0.718155E+09 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 0.290408E+11 | 10182.59 | 0.955019E+09 | 0.416506E+10 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 0.432391E+11 | 8518.74 | 0.281672E+09 | 0.170097E+11 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 0.542752E+11 | 9236.31 | 0.00 | 0.279830E+11 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 0.557534E+11 | 8966.66 | 101164.39 | 0.363492E+11 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 0.387569E+11 | 12672.93 | 0.185519E+09 | 0.128075E+11 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 0.155261E+11 | 12008.64 | 0.716340E+10 | 0.206789E+10 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 0.542164E+10 | 35680551.68 | 0.163739E+11 | 83111065.62 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.111084E+10 | 0.120005E+09 | 0.291367E+11 | 2330569.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.266011E+12 | 0.144762E+10 | 0.136601E+12 | 0.101549E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 0.662235E+09 | 5547.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.557534E+11 | 0.706109E+09 | 0.402180E+11 | 0.363492E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.397188E+11 | 0.750759E+11 | 0.963208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363540E+11 | 0.476637E+11 | 0.323884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.411738E+11 | 0.200416E+11 | 0.945528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.404413E+11 | 0.102420E+11 | 0.194542E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.427432E+11 | 0.568897E+09 | 0.371113E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.430365E+11 | 0.111135E+09 | 0.576672E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.451122E+11 | 13235621.99 | 0.735826E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.458495E+11 | 1133120.78 | 0.784141E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.427587E+11 | 0.225528E+09 | 0.503292E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.426426E+11 | 0.616754E+10 | 0.201925E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.406015E+11 | 0.292390E+11 | 0.730198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.404042E+11 | 0.653274E+11 | 0.163251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.500836E+12 | 0.254677E+12 | 0.359343E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.363540E+11 | 1133120.78 | 0.963208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.458495E+11 | 0.750759E+11 | 0.784141E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.261333E+10 | 0.706109E+09 | 0.662235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.585755E+09 | 0.183268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 5547.33 | 0.676350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 8510.40 | 0.136285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 10182.59 | 0.290408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 8518.74 | 0.432391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 9236.31 | 0.542752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 8966.66 | 0.557534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 12672.93 | 0.387569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 12008.64 | 0.155261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 35680551.68 | 0.542164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.120005E+09 | 0.111084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.144762E+10 | 0.266011E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 5547.33 | 0.662235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.706109E+09 | 0.557534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.459713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
February | 0.388588E+11 | 0.00 | 0.00 | 0.00 | 1280638.30 | 0.00 | 0.00 | 0.00 | 0.72 |
March | 0.373173E+11 | 0.00 | 0.00 | 0.00 | 34405251.59 | 0.00 | 0.00 | 0.00 | 0.80 |
April | 0.271505E+11 | 0.00 | 0.00 | 0.00 | 0.454207E+09 | 0.00 | 0.00 | 0.00 | 0.83 |
May | 0.155051E+11 | 0.00 | 0.00 | 0.00 | 0.258715E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
June | 0.547227E+10 | 0.00 | 0.00 | 0.00 | 0.105039E+11 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.664837E+09 | 0.482879E+09 | 0.00 | 37070.95 | 0.171159E+11 | 0.00 | 13256500.57 | 0.00 | 0.60 |
August | 35107891.01 | 0.847723E+10 | 0.00 | 467661.49 | 0.121892E+11 | 0.00 | 0.274416E+09 | 0.00 | 0.60 |
September | 0.184088E+09 | 0.717195E+10 | 0.00 | 23630837.05 | 0.140839E+10 | 0.00 | 0.101312E+11 | 0.00 | 0.78 |
October | 0.563351E+09 | 0.208037E+10 | 0.00 | 52547316.21 | 0.163933E+09 | 0.00 | 0.333148E+11 | 0.00 | 0.87 |
November | 0.653357E+09 | 48553799.37 | 0.00 | 58536048.92 | 9041588.50 | 0.00 | 0.429647E+11 | 0.00 | 0.85 |
December | 0.135895E+11 | 0.00 | 0.00 | 24594977.76 | 48671.96 | 0.00 | 0.342973E+11 | 0.00 | 0.69 |
Annual Sum or Average | 0.185965E+12 | 0.182610E+11 | 0.00 | 0.159814E+09 | 0.444674E+11 | 0.00 | 0.120996E+12 | 0.00 | 0.74 |
Minimum of Months | 35107891.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.459713E+11 | 0.847723E+10 | 0.00 | 58536048.92 | 0.171159E+11 | 0.00 | 0.429647E+11 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.259659E+10 | 0.00 | 0.00 | 155619.31 | 0.00 | 0.150257E+10 | 0.167320E+09 | 0.00 | 1.07 |
February | 0.258331E+10 | 150290.71 | 0.00 | 563004.04 | 0.00 | 0.834521E+09 | 0.204143E+09 | 0.00 | 1.24 |
March | 0.299039E+10 | 3226052.76 | 0.00 | 1044406.74 | 903897.59 | 61099051.26 | 0.434046E+09 | 0.00 | 1.39 |
April | 0.218889E+10 | 17239440.32 | 0.00 | 1124975.28 | 28410384.75 | 11690924.16 | 0.322688E+09 | 0.00 | 1.46 |
May | 0.109850E+10 | 0.217658E+09 | 0.00 | 990517.45 | 45206337.11 | 0.00 | 0.345351E+09 | 0.00 | 1.41 |
June | 0.300245E+09 | 0.116722E+10 | 0.00 | 681386.67 | 39718769.63 | 0.00 | 0.211875E+09 | 0.00 | 1.30 |
July | 36894915.83 | 0.198338E+10 | 0.00 | 97813.66 | 0.116159E+09 | 0.00 | 26341688.38 | 0.00 | 1.26 |
August | 2752491.68 | 0.259920E+10 | 0.00 | 81232.43 | 19585610.16 | 0.00 | 26619495.14 | 0.00 | 1.34 |
September | 0.582747E+09 | 0.834953E+09 | 0.00 | 1412639.56 | 0.117404E+09 | 0.00 | 0.322608E+09 | 0.00 | 1.45 |
October | 0.215372E+10 | 0.167276E+09 | 0.00 | 2178313.16 | 60028910.12 | 2797056.77 | 0.760683E+09 | 0.00 | 1.48 |
November | 0.310345E+10 | 2242752.02 | 0.00 | 1185659.96 | 3341035.07 | 0.126089E+09 | 0.494658E+09 | 0.00 | 1.38 |
December | 0.347582E+10 | 0.00 | 0.00 | 530961.85 | 4505.94 | 0.582845E+09 | 0.338442E+09 | 0.00 | 1.16 |
Annual Sum or Average | 0.211133E+11 | 0.699254E+10 | 0.00 | 10046530.11 | 0.430762E+09 | 0.312161E+10 | 0.365478E+10 | 0.00 | 1.33 |
Minimum of Months | 2752491.68 | 0.00 | 0.00 | 81232.43 | 0.00 | 0.00 | 26341688.38 | 0.00 | 1.07 |
Maximum of Months | 0.347582E+10 | 0.259920E+10 | 0.00 | 2178313.16 | 0.117404E+09 | 0.150257E+10 | 0.760683E+09 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.493452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
February | 0.412441E+10 | 0.00 | 0.00 | 18196.85 | 137462.65 | 0.00 | 46642077.31 | 0.00 | 1.21 |
March | 0.379520E+10 | 9981.40 | 0.00 | 130010.47 | 3683049.68 | 0.00 | 0.210377E+09 | 0.00 | 1.35 |
April | 0.248729E+10 | 64412.67 | 0.00 | 401165.19 | 48689816.66 | 0.00 | 0.427298E+09 | 0.00 | 1.41 |
May | 0.110932E+10 | 41010723.48 | 0.00 | 743295.48 | 0.236979E+09 | 0.00 | 0.555983E+09 | 0.00 | 1.36 |
June | 0.186324E+09 | 0.475862E+09 | 0.00 | 621616.86 | 0.666161E+09 | 0.00 | 0.402935E+09 | 0.00 | 1.15 |
July | 20237745.33 | 0.950675E+09 | 0.00 | 121633.01 | 0.974071E+09 | 0.00 | 52452319.81 | 0.00 | 1.04 |
August | 2484612.02 | 0.138837E+10 | 0.00 | 92632.61 | 0.881692E+09 | 0.00 | 30820624.38 | 0.00 | 1.03 |
September | 0.441221E+09 | 0.348651E+09 | 0.00 | 729647.09 | 0.542257E+09 | 0.00 | 0.591194E+09 | 0.00 | 1.25 |
October | 0.268695E+10 | 68860277.63 | 0.00 | 392539.29 | 0.152621E+09 | 0.00 | 0.596938E+09 | 0.00 | 1.33 |
November | 0.407846E+10 | 0.00 | 0.00 | 30970.54 | 6030228.09 | 0.00 | 0.125373E+09 | 0.00 | 1.30 |
December | 0.502075E+10 | 0.00 | 0.00 | 4191.69 | 5224.41 | 0.00 | 23180192.32 | 0.00 | 1.14 |
Annual Sum or Average | 0.288872E+11 | 0.327350E+10 | 0.00 | 3285899.07 | 0.351233E+10 | 0.00 | 0.306319E+10 | 0.00 | 1.22 |
Minimum of Months | 2484612.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
Maximum of Months | 0.502075E+10 | 0.138837E+10 | 0.00 | 743295.48 | 0.974071E+09 | 0.00 | 0.596938E+09 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 56468824.93 | 0.00 | 0.00 | 0.00 | 0.00 | 55860688.02 | 0.00 | 0.00 | 0.01 |
February | 49597475.25 | 0.00 | 0.00 | 60020.75 | 2000.88 | 34252730.98 | 26676059.71 | 0.00 | 0.02 |
March | 44680381.47 | 529072.88 | 0.00 | 427869.92 | 6157.86 | 0.00 | 0.162494E+09 | 0.00 | 0.05 |
April | 16409167.42 | 6413568.66 | 0.00 | 1135405.95 | 188000.77 | 0.00 | 0.374644E+09 | 0.00 | 0.11 |
May | 751494.79 | 95934611.95 | 0.00 | 1724955.72 | 0.00 | 0.00 | 0.471117E+09 | 0.00 | 0.21 |
June | 0.00 | 0.669672E+09 | 0.00 | 1049518.14 | 0.00 | 0.00 | 0.262068E+09 | 0.00 | 0.30 |
July | 0.00 | 0.120445E+10 | 0.00 | 180712.13 | 0.00 | 0.00 | 34532976.56 | 0.00 | 0.31 |
August | 0.00 | 0.151066E+10 | 0.00 | 128936.11 | 0.00 | 0.00 | 19960826.18 | 0.00 | 0.32 |
September | 0.00 | 0.464621E+09 | 0.00 | 1366682.68 | 0.00 | 0.00 | 0.396775E+09 | 0.00 | 0.27 |
October | 17832175.84 | 84612165.59 | 0.00 | 1055118.60 | 0.00 | 0.00 | 0.447157E+09 | 0.00 | 0.12 |
November | 46641714.08 | 336920.05 | 0.00 | 342117.71 | 45630.71 | 0.00 | 0.163466E+09 | 0.00 | 0.04 |
December | 71246360.72 | 0.00 | 0.00 | 48010.28 | 76.05 | 0.00 | 24827426.06 | 0.00 | 0.01 |
Annual Sum or Average | 0.303628E+09 | 0.403723E+10 | 0.00 | 7519347.99 | 241866.26 | 90113419.00 | 0.238372E+10 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Maximum of Months | 71246360.72 | 0.151066E+10 | 0.00 | 1724955.72 | 188000.77 | 55860688.02 | 0.471117E+09 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142839E+10 | 0.00 | 0.00 | 0.55 |
February | 0.175027E+10 | 0.00 | 0.00 | 0.00 | 86538.26 | 0.875582E+09 | 0.00 | 0.00 | 0.62 |
March | 0.252169E+10 | 0.00 | 0.00 | 0.00 | 2324911.34 | 0.00 | 0.00 | 0.00 | 0.69 |
April | 0.183468E+10 | 0.00 | 0.00 | 0.00 | 30692744.87 | 0.00 | 0.00 | 0.00 | 0.72 |
May | 0.104774E+10 | 0.00 | 0.00 | 0.00 | 0.174825E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
June | 0.369785E+09 | 0.00 | 0.00 | 0.00 | 0.709792E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 45824198.95 | 0.00 | 0.00 | 0.00 | 0.118922E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
August | 20940035.83 | 0.00 | 0.00 | 0.00 | 0.139267E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
September | 0.647736E+09 | 0.00 | 0.00 | 0.00 | 0.554876E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
October | 0.206646E+10 | 0.00 | 0.00 | 0.00 | 0.139354E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
November | 0.264650E+10 | 0.00 | 0.00 | 0.00 | 3796270.70 | 0.00 | 0.00 | 0.00 | 0.67 |
December | 0.298997E+10 | 0.00 | 0.00 | 0.00 | 3288.97 | 0.185387E+09 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.176197E+11 | 0.00 | 0.00 | 0.00 | 0.419765E+10 | 0.248936E+10 | 0.00 | 0.00 | 0.62 |
Minimum of Months | 20940035.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.298997E+10 | 0.00 | 0.00 | 0.00 | 0.139267E+10 | 0.142839E+10 | 0.00 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.102009E+09 | 0.00 | 0.00 | 0.620352E+11 | 0.00 | 13.47 |
February | 0.00 | 1501457.06 | 0.00 | 93550889.35 | 0.00 | 0.00 | 0.528281E+11 | 0.00 | 15.50 |
March | 0.00 | 43928179.16 | 0.00 | 0.104448E+09 | 0.00 | 0.00 | 0.514749E+11 | 0.00 | 17.82 |
April | 0.00 | 0.577028E+09 | 0.00 | 99074577.57 | 0.00 | 0.00 | 0.370988E+11 | 0.00 | 18.63 |
May | 0.00 | 0.356075E+10 | 0.00 | 75194221.93 | 0.00 | 0.00 | 0.203086E+11 | 0.00 | 17.86 |
June | 0.00 | 0.150471E+11 | 0.00 | 30513916.79 | 0.00 | 0.00 | 0.706326E+10 | 0.00 | 14.94 |
July | 0.00 | 0.250787E+11 | 0.00 | 4362747.53 | 0.00 | 0.00 | 0.762525E+09 | 0.00 | 13.29 |
August | 0.00 | 0.295773E+11 | 0.00 | 2644610.63 | 0.00 | 0.00 | 0.358948E+09 | 0.00 | 13.18 |
September | 0.00 | 0.118082E+11 | 0.00 | 45747340.39 | 0.00 | 0.00 | 0.131257E+11 | 0.00 | 16.30 |
October | 0.00 | 0.298741E+10 | 0.00 | 91337334.00 | 0.00 | 0.00 | 0.426668E+11 | 0.00 | 17.53 |
November | 0.00 | 72379036.29 | 0.00 | 98551392.24 | 0.00 | 0.00 | 0.545760E+11 | 0.00 | 16.91 |
December | 0.00 | 54103.92 | 0.00 | 0.101451E+09 | 0.00 | 0.00 | 0.639155E+11 | 0.00 | 14.46 |
Annual Sum or Average | 0.00 | 0.887543E+11 | 0.00 | 0.848885E+09 | 0.00 | 0.00 | 0.406215E+12 | 0.00 | 15.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2644610.63 | 0.00 | 0.00 | 0.358948E+09 | 0.00 | 13.18 |
Maximum of Months | 0.00 | 0.295773E+11 | 0.00 | 0.104448E+09 | 0.00 | 0.00 | 0.639155E+11 | 0.00 | 18.63 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.338447E+11 | 0.00 | 0.00 | 421852.84 | 0.00 | 48124044.64 | 0.247779E+10 | 0.00 | 3.25 |
February | 0.256520E+11 | 257828.14 | 0.00 | 1658278.52 | 755372.79 | 0.00 | 0.509023E+10 | 0.00 | 3.66 |
March | 0.180807E+11 | 10528615.56 | 0.00 | 4019798.93 | 16691742.41 | 0.00 | 0.114396E+11 | 0.00 | 4.08 |
April | 0.115586E+11 | 45109472.05 | 0.00 | 4546380.56 | 0.314245E+09 | 0.00 | 0.991746E+10 | 0.00 | 4.26 |
May | 0.373044E+10 | 0.505959E+09 | 0.00 | 6060266.55 | 0.154091E+10 | 0.00 | 0.853061E+10 | 0.00 | 4.11 |
June | 0.121928E+10 | 0.424178E+10 | 0.00 | 2920861.73 | 0.406855E+10 | 0.00 | 0.310729E+10 | 0.00 | 3.44 |
July | 61986235.89 | 0.807923E+10 | 0.00 | 784949.32 | 0.584561E+10 | 0.00 | 0.473744E+09 | 0.00 | 3.09 |
August | 37131148.67 | 0.118979E+11 | 0.00 | 552520.24 | 0.441560E+10 | 0.00 | 0.207485E+09 | 0.00 | 3.04 |
September | 0.225667E+10 | 0.366532E+10 | 0.00 | 5241369.19 | 0.283180E+10 | 0.00 | 0.532186E+10 | 0.00 | 3.77 |
October | 0.118760E+11 | 0.854652E+09 | 0.00 | 6469076.03 | 0.776920E+09 | 0.00 | 0.123119E+11 | 0.00 | 4.04 |
November | 0.202402E+11 | 7034923.90 | 0.00 | 4312634.23 | 37412296.80 | 0.00 | 0.107411E+11 | 0.00 | 3.93 |
December | 0.314236E+11 | 0.00 | 0.00 | 1583889.66 | 38507.73 | 0.00 | 0.575231E+10 | 0.00 | 3.44 |
Annual Sum or Average | 0.159981E+12 | 0.293078E+11 | 0.00 | 38571877.80 | 0.198485E+11 | 48124044.64 | 0.753713E+11 | 0.00 | 3.67 |
Minimum of Months | 37131148.67 | 0.00 | 0.00 | 421852.84 | 0.00 | 0.00 | 0.207485E+09 | 0.00 | 3.04 |
Maximum of Months | 0.338447E+11 | 0.118979E+11 | 0.00 | 6469076.03 | 0.584561E+10 | 48124044.64 | 0.123119E+11 | 0.00 | 4.26 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100282E+12 | 0.00 | 0.00 | 402768.42 | 0.00 | 0.00 | 0.155400E+10 | 0.00 | 1.32 |
February | 0.765986E+11 | 0.00 | 0.00 | 3512369.11 | 2836883.30 | 0.00 | 0.947844E+10 | 0.00 | 1.48 |
March | 0.562383E+11 | 799387.93 | 0.00 | 13534175.39 | 75415483.56 | 0.00 | 0.264216E+11 | 0.00 | 1.66 |
April | 0.312561E+11 | 23984055.34 | 0.00 | 21247076.55 | 0.982181E+09 | 0.00 | 0.289094E+11 | 0.00 | 1.73 |
May | 0.851077E+10 | 0.958062E+09 | 0.00 | 33175106.37 | 0.478406E+10 | 0.00 | 0.258646E+11 | 0.00 | 1.67 |
June | 0.212166E+10 | 0.100909E+11 | 0.00 | 18172208.22 | 0.134942E+11 | 0.00 | 0.100425E+11 | 0.00 | 1.41 |
July | 76120968.24 | 0.204993E+11 | 0.00 | 4559457.80 | 0.192266E+11 | 0.00 | 0.142848E+10 | 0.00 | 1.28 |
August | 45061074.98 | 0.296371E+11 | 0.00 | 2588162.50 | 0.174733E+11 | 0.00 | 0.655023E+09 | 0.00 | 1.27 |
September | 0.532966E+10 | 0.909604E+10 | 0.00 | 26743944.27 | 0.931302E+10 | 0.00 | 0.160252E+11 | 0.00 | 1.54 |
October | 0.343661E+11 | 0.189306E+10 | 0.00 | 23638552.34 | 0.269938E+10 | 0.00 | 0.334375E+11 | 0.00 | 1.64 |
November | 0.593204E+11 | 4622433.15 | 0.00 | 11268370.89 | 0.119826E+09 | 0.00 | 0.274255E+11 | 0.00 | 1.59 |
December | 0.945765E+11 | 0.00 | 0.00 | 3110803.01 | 107818.63 | 0.00 | 0.951457E+10 | 0.00 | 1.39 |
Annual Sum or Average | 0.468721E+12 | 0.722039E+11 | 0.00 | 0.161953E+09 | 0.681709E+11 | 0.00 | 0.190757E+12 | 0.00 | 1.50 |
Minimum of Months | 45061074.98 | 0.00 | 0.00 | 402768.42 | 0.00 | 0.00 | 0.655023E+09 | 0.00 | 1.27 |
Maximum of Months | 0.100282E+12 | 0.296371E+11 | 0.00 | 33175106.37 | 0.192266E+11 | 0.00 | 0.334375E+11 | 0.00 | 1.73 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 63537046.78 | 0.00 | 0.00 | 561034.68 | 0.00 | 0.117258E+10 | 84789515.49 | 0.00 | 0.34 |
February | 69796330.20 | 18740.50 | 12162.75 | 1752752.47 | 0.00 | 0.850863E+09 | 0.239155E+09 | 2010.84 | 0.34 |
March | 67610051.51 | 9495853.49 | 2052.96 | 4919726.11 | 152441.79 | 0.374857E+09 | 0.609611E+09 | 3133.87 | 0.34 |
April | 21900645.93 | 39836483.19 | 46500.49 | 7395640.73 | 2704555.58 | 97893239.57 | 0.626946E+09 | 9606.66 | 0.34 |
May | 1475174.17 | 0.239014E+09 | 33204.35 | 5170911.12 | 950263.01 | 949209.17 | 0.270773E+09 | 4831.47 | 0.34 |
June | 141140.00 | 0.732044E+09 | 101531.36 | 2524244.77 | 0.00 | 232277.52 | 0.118259E+09 | 5476.48 | 0.34 |
July | 0.00 | 0.104117E+10 | 236869.32 | 218015.27 | 2520141.18 | 82936.74 | 3780301.36 | 3395.42 | 0.34 |
August | 0.00 | 0.113750E+10 | 141474.13 | 67883.03 | 0.00 | 10469.03 | 270850.01 | 1871.99 | 0.34 |
September | 1431980.42 | 0.542733E+09 | 344029.39 | 2776910.47 | 4213822.99 | 828796.45 | 0.159760E+09 | 12624.68 | 0.34 |
October | 36545256.01 | 0.140871E+09 | 101581.52 | 5499499.77 | 2498197.42 | 0.253721E+09 | 0.556082E+09 | 9209.72 | 0.34 |
November | 39929709.94 | 7300143.14 | 505.30 | 3043091.52 | 1364894.45 | 0.582636E+09 | 0.482413E+09 | 1978.00 | 0.34 |
December | 69280632.03 | 272511.64 | 0.00 | 1062868.61 | 342215.09 | 0.106961E+10 | 0.158788E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.371648E+09 | 0.389025E+10 | 1019911.57 | 34992578.55 | 14746531.51 | 0.440426E+10 | 0.331063E+10 | 54139.12 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 67883.03 | 0.00 | 10469.03 | 270850.01 | 0.00 | 0.34 |
Maximum of Months | 69796330.20 | 0.113750E+10 | 344029.39 | 7395640.73 | 4213822.99 | 0.117258E+10 | 0.626946E+09 | 12624.68 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 49968714.33 | 0.00 | 0.00 | 45338.48 | 0.00 | 0.125199E+10 | 19311693.89 | 0.00 | 0.34 |
February | 92123422.22 | 18738.31 | 12082.81 | 354772.03 | 0.00 | 0.939560E+09 | 0.129394E+09 | 2089.12 | 0.34 |
March | 0.197675E+09 | 7696563.09 | 13315.11 | 1549420.80 | 1934369.26 | 0.462018E+09 | 0.395632E+09 | 8103.61 | 0.34 |
April | 0.145821E+09 | 31496674.31 | 100402.34 | 4770250.11 | 10986617.95 | 0.101972E+09 | 0.501483E+09 | 8460.43 | 0.34 |
May | 90301769.11 | 0.203535E+09 | 289869.04 | 2828690.91 | 36121702.58 | 645110.42 | 0.184560E+09 | 27542.55 | 0.34 |
June | 24531061.17 | 0.623943E+09 | 176888.80 | 2086576.98 | 0.107940E+09 | 71367.21 | 94453927.27 | 5243.45 | 0.34 |
July | 3927683.24 | 0.894275E+09 | 251071.80 | 62502.87 | 0.149274E+09 | 13593.06 | 76996.03 | 4253.40 | 0.34 |
August | 349161.15 | 0.102613E+10 | 146182.77 | 0.00 | 0.111223E+09 | 0.00 | 0.00 | 3305.53 | 0.34 |
September | 57047454.01 | 0.436537E+09 | 319433.59 | 1651408.59 | 0.110363E+09 | 532530.83 | 0.105547E+09 | 20530.66 | 0.34 |
October | 0.144991E+09 | 0.108865E+09 | 342146.80 | 1639738.06 | 34238169.19 | 0.318124E+09 | 0.386994E+09 | 18088.87 | 0.34 |
November | 0.135082E+09 | 4460962.62 | 15333.54 | 471365.26 | 4188186.56 | 0.748285E+09 | 0.224054E+09 | 2022.65 | 0.34 |
December | 85590973.51 | 253029.42 | 0.00 | 166416.99 | 361625.29 | 0.116804E+10 | 44796688.80 | 0.00 | 0.34 |
Annual Sum or Average | 0.102741E+10 | 0.333722E+10 | 1666726.61 | 15626481.06 | 0.566631E+09 | 0.499124E+10 | 0.208630E+10 | 99640.28 | 0.34 |
Minimum of Months | 349161.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.197675E+09 | 0.102613E+10 | 342146.80 | 4770250.11 | 0.149274E+09 | 0.125199E+10 | 0.501483E+09 | 27542.55 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.803455E+09 | 0.00 | 0.00 | 42185.22 | 2628633.08 | 0.00 | 47413729.04 | 0.00 | 0.02 |
February | 0.574202E+09 | 0.00 | 0.00 | 632379.56 | 0.00 | 0.00 | 0.192043E+09 | 0.00 | 0.02 |
March | 0.389417E+09 | 20431015.70 | 0.00 | 1571899.45 | 0.00 | 0.00 | 0.581559E+09 | 0.00 | 0.02 |
April | 0.174348E+09 | 65243533.46 | 0.00 | 1503732.38 | 21112353.43 | 0.00 | 0.252012E+09 | 0.00 | 0.02 |
May | 17194402.79 | 0.289871E+09 | 0.00 | 377013.17 | 2848785.21 | 0.00 | 0.100338E+09 | 0.00 | 0.02 |
June | 1853783.28 | 0.546434E+09 | 0.00 | 124924.48 | 0.00 | 0.00 | 41246818.44 | 0.00 | 0.02 |
July | 0.00 | 0.774447E+09 | 0.00 | 0.00 | 39551989.18 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.906247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
September | 36386134.29 | 0.590333E+09 | 0.00 | 402155.68 | 20952398.29 | 0.00 | 21160239.36 | 0.00 | 0.02 |
October | 0.207904E+09 | 0.211983E+09 | 0.00 | 1907633.12 | 10416697.60 | 0.00 | 0.427714E+09 | 0.00 | 0.02 |
November | 0.377952E+09 | 39499135.49 | 0.00 | 1771824.80 | 3687245.07 | 0.00 | 0.573528E+09 | 0.00 | 0.02 |
December | 0.755902E+09 | 0.00 | 0.00 | 835906.37 | 0.00 | 0.00 | 0.389251E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.333861E+10 | 0.344449E+10 | 0.00 | 9169654.21 | 0.101198E+09 | 0.00 | 0.262627E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.803455E+09 | 0.906247E+09 | 0.00 | 1907633.12 | 39551989.18 | 0.00 | 0.581559E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116655E+10 | 0.00 | 0.00 | 4476060.78 | 0.00 | 0.130048E+11 | 0.374702E+10 | 0.00 | 0.38 |
February | 0.154594E+10 | 384042.49 | 45217.84 | 14725480.52 | 0.00 | 0.729625E+10 | 0.689721E+10 | 17147.28 | 0.39 |
March | 0.268134E+10 | 0.101033E+09 | 211296.54 | 33541119.88 | 29640786.52 | 0.804044E+09 | 0.108169E+11 | 43164.33 | 0.39 |
April | 0.198521E+10 | 0.407492E+09 | 223853.91 | 64337141.59 | 0.170010E+09 | 71233839.71 | 0.810741E+10 | 11563.07 | 0.39 |
May | 0.124127E+10 | 0.260584E+10 | 1779166.06 | 36449055.69 | 0.647419E+09 | 5301191.94 | 0.249243E+10 | 67106.13 | 0.39 |
June | 0.351998E+09 | 0.844569E+10 | 251589.57 | 21364037.71 | 0.148407E+10 | 171646.59 | 0.126970E+10 | 18983.78 | 0.39 |
July | 53276666.92 | 0.121015E+11 | 0.00 | 1189279.40 | 0.205705E+10 | 36147.72 | 851173.38 | 0.00 | 0.39 |
August | 4736161.59 | 0.138337E+11 | 502228.08 | 0.00 | 0.159543E+10 | 0.00 | 0.00 | 3169.08 | 0.39 |
September | 0.779719E+09 | 0.563281E+10 | 1889495.18 | 22902064.73 | 0.178823E+10 | 3631959.96 | 0.142887E+10 | 42948.30 | 0.39 |
October | 0.196671E+10 | 0.141327E+10 | 2690106.04 | 35192400.29 | 0.529987E+09 | 0.293088E+09 | 0.925846E+10 | 52283.60 | 0.39 |
November | 0.183230E+10 | 60236945.03 | 497768.14 | 24550420.82 | 56810238.16 | 0.227718E+10 | 0.108939E+11 | 10994.93 | 0.39 |
December | 0.128396E+10 | 3432192.28 | 0.00 | 9456556.28 | 4905230.06 | 0.897640E+10 | 0.734478E+10 | 0.00 | 0.39 |
Annual Sum or Average | 0.148930E+11 | 0.446054E+11 | 8090721.35 | 0.268184E+09 | 0.836356E+10 | 0.327321E+11 | 0.622575E+11 | 267360.51 | 0.39 |
Minimum of Months | 4736161.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.268134E+10 | 0.138337E+11 | 2690106.04 | 64337141.59 | 0.205705E+10 | 0.130048E+11 | 0.108939E+11 | 67106.13 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 63120228.19 | 0.00 | 0.00 | 286860.97 | 0.00 | 0.117044E+10 | 87620717.32 | 0.00 | 0.34 |
February | 64894185.77 | 30919.62 | 584.37 | 1932043.52 | 0.00 | 0.842890E+09 | 0.251851E+09 | 1410.11 | 0.34 |
March | 56465402.93 | 9515920.75 | 13237.13 | 4584653.84 | 121828.18 | 0.382112E+09 | 0.613835E+09 | 2496.04 | 0.34 |
April | 14398463.13 | 40238349.73 | 45239.39 | 7596510.35 | 2311641.15 | 91986957.08 | 0.640153E+09 | 1915.64 | 0.34 |
May | 64511.98 | 0.239052E+09 | 0.00 | 5694409.72 | 950263.01 | 864354.25 | 0.271745E+09 | 0.00 | 0.34 |
June | 0.00 | 0.732136E+09 | 14372.99 | 2823196.62 | 0.00 | 0.00 | 0.118334E+09 | 1181.27 | 0.34 |
July | 0.00 | 0.104131E+10 | 96175.94 | 215218.82 | 2520141.18 | 82936.74 | 3783097.81 | 3893.39 | 0.34 |
August | 0.00 | 0.113753E+10 | 111289.64 | 85902.70 | 0.00 | 0.00 | 263299.37 | 3246.37 | 0.34 |
September | 1431980.42 | 0.542880E+09 | 206365.18 | 3060406.01 | 4213822.99 | 576406.71 | 0.159729E+09 | 3807.52 | 0.34 |
October | 26230713.40 | 0.140913E+09 | 66098.42 | 5387873.03 | 2498197.42 | 0.271230E+09 | 0.548999E+09 | 2794.46 | 0.34 |
November | 39019378.72 | 7628432.14 | 11838.28 | 3021421.65 | 1024563.49 | 0.572482E+09 | 0.493499E+09 | 2686.98 | 0.34 |
December | 68818336.21 | 254274.79 | 0.00 | 802636.01 | 360451.94 | 0.104686E+10 | 0.182257E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.334443E+09 | 0.389148E+10 | 565201.34 | 35491133.24 | 14000909.38 | 0.437953E+10 | 0.337207E+10 | 23431.80 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 85902.70 | 0.00 | 0.00 | 263299.37 | 0.00 | 0.34 |
Maximum of Months | 68818336.21 | 0.113753E+10 | 206365.18 | 7596510.35 | 4213822.99 | 0.117044E+10 | 0.640153E+09 | 3893.39 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 56823779.76 | 0.00 | 0.00 | 38458.37 | 0.00 | 0.124626E+10 | 18193297.73 | 0.00 | 0.34 |
February | 94368237.03 | 18738.31 | 12096.22 | 653953.39 | 0.00 | 0.919748E+09 | 0.146661E+09 | 2075.71 | 0.34 |
March | 0.196601E+09 | 7693296.63 | 17680.81 | 1700338.28 | 1931695.25 | 0.468836E+09 | 0.389736E+09 | 9678.37 | 0.34 |
April | 0.143244E+09 | 32101836.43 | 104621.45 | 5142161.10 | 10382929.01 | 0.104747E+09 | 0.500913E+09 | 2768.15 | 0.34 |
May | 88842442.21 | 0.204448E+09 | 125371.23 | 3088859.01 | 35395298.84 | 291940.82 | 0.186112E+09 | 5519.69 | 0.34 |
June | 24330934.72 | 0.626119E+09 | 45185.72 | 2284672.37 | 0.105900E+09 | 54502.62 | 94472822.92 | 1173.32 | 0.34 |
July | 3927683.24 | 0.897715E+09 | 34520.93 | 61321.52 | 0.146054E+09 | 16338.04 | 75432.40 | 722.37 | 0.34 |
August | 349161.15 | 0.102724E+10 | 0.00 | 0.00 | 0.110272E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
September | 56668775.01 | 0.438864E+09 | 168317.21 | 1783766.40 | 0.108203E+09 | 520530.38 | 0.105806E+09 | 4304.03 | 0.34 |
October | 0.143919E+09 | 0.111071E+09 | 280908.70 | 1985629.88 | 32102490.99 | 0.327007E+09 | 0.378836E+09 | 8900.01 | 0.34 |
November | 0.135082E+09 | 4453782.41 | 22708.70 | 685958.39 | 4188186.56 | 0.746822E+09 | 0.225303E+09 | 1827.70 | 0.34 |
December | 85621059.96 | 253029.42 | 0.00 | 109315.95 | 361625.29 | 0.117134E+10 | 41524137.29 | 0.00 | 0.34 |
Annual Sum or Average | 0.102978E+10 | 0.334997E+10 | 811410.96 | 17534434.67 | 0.554792E+09 | 0.498564E+10 | 0.208763E+10 | 36969.36 | 0.34 |
Minimum of Months | 349161.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.196601E+09 | 0.102724E+10 | 280908.70 | 5142161.10 | 0.146054E+09 | 0.124626E+10 | 0.500913E+09 | 9678.37 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.212995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423827E+10 | 0.00 | 0.00 | 0.36 |
February | 0.189592E+11 | 0.00 | 0.00 | 0.00 | 711412.98 | 0.262742E+10 | 0.00 | 0.00 | 0.40 |
March | 0.207303E+11 | 0.00 | 0.00 | 0.00 | 19112611.79 | 0.00 | 0.00 | 0.00 | 0.45 |
April | 0.150825E+11 | 0.00 | 0.00 | 0.00 | 0.252319E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 0.861328E+10 | 0.00 | 0.00 | 0.00 | 0.143720E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 0.303993E+10 | 0.00 | 0.00 | 0.00 | 0.583505E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.376711E+09 | 0.729156E+09 | 0.00 | 0.00 | 0.904720E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
August | 0.172144E+09 | 0.767210E+09 | 0.00 | 0.00 | 0.106817E+11 | 0.00 | 0.00 | 0.00 | 0.34 |
September | 0.532490E+10 | 0.00 | 0.00 | 0.00 | 0.456152E+10 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 0.169879E+11 | 0.00 | 0.00 | 0.00 | 0.114560E+10 | 0.00 | 0.00 | 0.00 | 0.45 |
November | 0.217290E+11 | 0.00 | 0.00 | 0.00 | 31208350.57 | 27381505.14 | 0.00 | 0.00 | 0.43 |
December | 0.250873E+11 | 0.00 | 0.00 | 0.00 | 27037.97 | 0.101672E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.157403E+12 | 0.149637E+10 | 0.00 | 0.00 | 0.330117E+11 | 0.790979E+10 | 0.00 | 0.00 | 0.41 |
Minimum of Months | 0.172144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.250873E+11 | 0.767210E+09 | 0.00 | 0.00 | 0.106817E+11 | 0.423827E+10 | 0.00 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 15387482.83 | 0.00 | 0.00 | 96542.27 | 0.00 | 0.299706E+09 | 15176635.26 | 0.00 | 0.34 |
February | 15789743.04 | 4685.13 | 3024.68 | 396009.40 | 0.00 | 0.230786E+09 | 43420394.60 | 518.72 | 0.34 |
March | 16729057.08 | 2379531.26 | 316.25 | 1123968.36 | 32542.56 | 0.140934E+09 | 0.105462E+09 | 980.46 | 0.34 |
April | 5327255.24 | 9965190.33 | 11277.84 | 1701311.62 | 670069.36 | 46384545.56 | 0.135121E+09 | 2748.95 | 0.34 |
May | 357101.26 | 59894912.22 | 8493.36 | 1179465.76 | 96080.04 | 3744597.79 | 64310914.64 | 1015.59 | 0.34 |
June | 0.00 | 0.183006E+09 | 28937.19 | 590298.70 | 0.00 | 58314.88 | 29640668.40 | 2928.76 | 0.34 |
July | 0.00 | 0.260223E+09 | 77302.81 | 44619.83 | 677569.04 | 21567.93 | 954125.58 | 3485.61 | 0.34 |
August | 0.00 | 0.284328E+09 | 79888.43 | 15519.32 | 0.00 | 2617.26 | 69163.94 | 1951.42 | 0.34 |
September | 357995.11 | 0.135550E+09 | 88957.76 | 582550.06 | 1182430.33 | 4892192.96 | 35366791.56 | 4937.81 | 0.34 |
October | 9320737.39 | 35193235.07 | 49322.35 | 1218807.81 | 624549.35 | 95682726.46 | 0.106740E+09 | 3013.06 | 0.34 |
November | 10139041.21 | 1900290.71 | 144.36 | 664101.91 | 265968.69 | 0.185086E+09 | 81116594.50 | 476.47 | 0.34 |
December | 15342888.17 | 68127.91 | 0.00 | 221293.84 | 85553.77 | 0.283400E+09 | 25721441.98 | 0.00 | 0.34 |
Annual Sum or Average | 88751301.32 | 0.972513E+09 | 347665.03 | 7834488.89 | 3634763.15 | 0.129070E+10 | 0.643099E+09 | 22056.85 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 15519.32 | 0.00 | 2617.26 | 69163.94 | 0.00 | 0.34 |
Maximum of Months | 16729057.08 | 0.284328E+09 | 88957.76 | 1701311.62 | 1182430.33 | 0.299706E+09 | 0.135121E+09 | 4937.81 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 9552079.32 | 0.00 | 0.00 | 8501.99 | 0.00 | 0.319281E+09 | 1486244.91 | 0.00 | 0.34 |
February | 22258020.22 | 4684.58 | 3033.91 | 70030.17 | 0.00 | 0.251524E+09 | 16506204.95 | 509.07 | 0.34 |
March | 48888630.58 | 1924140.77 | 3047.14 | 306777.35 | 483592.31 | 0.155737E+09 | 59286524.24 | 2307.54 | 0.34 |
April | 36445261.90 | 7906061.07 | 24821.45 | 1085690.87 | 2714761.99 | 43013427.17 | 0.107967E+09 | 2394.25 | 0.34 |
May | 22321290.58 | 50933665.68 | 57543.06 | 659384.48 | 8993833.25 | 278235.64 | 46325015.02 | 8429.29 | 0.34 |
June | 6097484.42 | 0.155967E+09 | 61794.37 | 496315.16 | 26985024.46 | 29196.46 | 23662737.12 | 2560.79 | 0.34 |
July | 981920.81 | 0.223587E+09 | 44592.33 | 13147.33 | 37318553.18 | 6301.98 | 18823.68 | 708.41 | 0.34 |
August | 87290.29 | 0.256491E+09 | 78177.24 | 0.00 | 27805852.09 | 0.00 | 0.00 | 1443.72 | 0.34 |
September | 14177112.01 | 0.108957E+09 | 91623.99 | 339000.60 | 27754959.61 | 2490871.83 | 24187718.12 | 6197.14 | 0.34 |
October | 36111581.46 | 27408487.27 | 109068.32 | 287266.75 | 8342137.23 | 0.113237E+09 | 63301567.69 | 6224.30 | 0.34 |
November | 32541030.66 | 1115240.66 | 3995.95 | 64927.43 | 1047046.64 | 0.216463E+09 | 27903968.18 | 343.10 | 0.34 |
December | 17802010.26 | 63257.35 | 0.00 | 23622.49 | 90406.32 | 0.299804E+09 | 7017951.09 | 0.00 | 0.34 |
Annual Sum or Average | 0.247264E+09 | 0.834358E+09 | 477697.76 | 3354664.60 | 0.141536E+09 | 0.140186E+10 | 0.377664E+09 | 31117.61 | 0.34 |
Minimum of Months | 87290.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 48888630.58 | 0.256491E+09 | 109068.32 | 1085690.87 | 37318553.18 | 0.319281E+09 | 0.107967E+09 | 8429.29 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 68986010.04 | 0.00 | 0.00 | 3274971.12 | 0.00 | 0.154379E+10 | 0.506385E+09 | 0.00 | 0.38 |
February | 85150354.90 | 45478.72 | 3153.58 | 5062001.04 | 0.00 | 0.108345E+10 | 0.691958E+09 | 4231.77 | 0.39 |
March | 55269288.16 | 15389542.09 | 0.00 | 9049864.87 | 115131.15 | 0.398963E+09 | 0.123439E+10 | 0.00 | 0.39 |
April | 27221077.11 | 64647976.75 | 0.00 | 10228169.63 | 3768250.73 | 0.158927E+09 | 0.101486E+10 | 0.00 | 0.39 |
May | 1289628.48 | 0.383946E+09 | 0.00 | 6574741.84 | 1526238.64 | 3387058.88 | 0.435842E+09 | 0.00 | 0.39 |
June | 0.00 | 0.117563E+10 | 281955.43 | 2893627.53 | 0.00 | 359139.80 | 0.191340E+09 | 10334.83 | 0.39 |
July | 0.00 | 0.167184E+10 | 468102.72 | 281704.89 | 4353035.06 | 133206.55 | 6140080.75 | 9094.78 | 0.39 |
August | 0.00 | 0.182640E+10 | 784535.10 | 101374.72 | 0.00 | 0.00 | 459486.53 | 9814.37 | 0.39 |
September | 2299935.74 | 0.870939E+09 | 336176.24 | 4141682.58 | 7755868.85 | 4656363.69 | 0.253588E+09 | 5380.26 | 0.39 |
October | 26069820.89 | 0.226379E+09 | 53721.28 | 10792356.02 | 4012410.67 | 0.218822E+09 | 0.111249E+10 | 2408.79 | 0.39 |
November | 28248906.41 | 12493054.89 | 0.00 | 9425380.25 | 1428044.01 | 0.494105E+09 | 0.124784E+10 | 0.00 | 0.39 |
December | 50840299.90 | 987326.33 | 0.00 | 5141082.22 | 0.00 | 0.122823E+10 | 0.801728E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.345375E+09 | 0.624870E+10 | 1927644.34 | 66966956.71 | 22958979.12 | 0.513482E+10 | 0.749701E+10 | 41264.81 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 101374.72 | 0.00 | 0.00 | 459486.53 | 0.00 | 0.38 |
Maximum of Months | 85150354.90 | 0.182640E+10 | 784535.10 | 10792356.02 | 7755868.85 | 0.154379E+10 | 0.124784E+10 | 10334.83 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.315338E+11 | 0.00 | 0.00 | 12357576.32 | 0.00 | 0.00 | 0.323693E+11 | 0.00 | 4.23 |
February | 0.219452E+11 | 0.00 | 0.00 | 15792584.41 | 1780516.36 | 0.00 | 0.320687E+11 | 0.00 | 4.77 |
March | 0.143929E+11 | 23454378.81 | 0.00 | 27107144.46 | 24380449.56 | 0.00 | 0.374836E+11 | 0.00 | 5.33 |
April | 0.635904E+10 | 0.379045E+09 | 0.00 | 31758468.62 | 0.252455E+09 | 0.00 | 0.314577E+11 | 0.00 | 5.57 |
May | 0.163140E+10 | 0.288532E+10 | 0.00 | 34600930.41 | 0.723177E+09 | 0.00 | 0.200321E+11 | 0.00 | 5.40 |
June | 0.414995E+09 | 0.129030E+11 | 0.00 | 14776721.48 | 0.182495E+10 | 0.00 | 0.724224E+10 | 0.00 | 4.53 |
July | 5892560.12 | 0.219669E+11 | 0.00 | 3268750.23 | 0.271741E+10 | 0.00 | 0.939160E+09 | 0.00 | 4.06 |
August | 10943792.78 | 0.260119E+11 | 0.00 | 1620792.66 | 0.294483E+10 | 0.00 | 0.420228E+09 | 0.00 | 4.00 |
September | 0.115959E+10 | 0.968321E+10 | 0.00 | 18917360.69 | 0.178843E+10 | 0.00 | 0.122147E+11 | 0.00 | 4.93 |
October | 0.101777E+11 | 0.217265E+10 | 0.00 | 25229813.53 | 0.711175E+09 | 0.00 | 0.323414E+11 | 0.00 | 5.26 |
November | 0.173765E+11 | 29411055.56 | 0.00 | 21233598.32 | 48696850.87 | 0.00 | 0.370545E+11 | 0.00 | 5.12 |
December | 0.266522E+11 | 0.00 | 0.00 | 15736511.33 | 67670.33 | 0.00 | 0.386648E+11 | 0.00 | 4.48 |
Annual Sum or Average | 0.131660E+12 | 0.760549E+11 | 0.00 | 0.222400E+09 | 0.110374E+11 | 0.00 | 0.282289E+12 | 0.00 | 4.81 |
Minimum of Months | 5892560.12 | 0.00 | 0.00 | 1620792.66 | 0.00 | 0.00 | 0.420228E+09 | 0.00 | 4.00 |
Maximum of Months | 0.315338E+11 | 0.260119E+11 | 0.00 | 34600930.41 | 0.294483E+10 | 0.00 | 0.386648E+11 | 0.00 | 5.57 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.259329E+11 | 0.00 | 0.00 | 18681449.40 | 0.00 | 0.00 | 0.379128E+11 | 0.00 | 4.24 |
February | 0.173379E+11 | 1375454.25 | 0.00 | 22608380.01 | 403322.43 | 0.00 | 0.366707E+11 | 0.00 | 4.77 |
March | 0.104856E+11 | 34995758.10 | 0.00 | 35785724.14 | 12792332.40 | 0.00 | 0.414792E+11 | 0.00 | 5.35 |
April | 0.394450E+10 | 0.498248E+09 | 0.00 | 40093074.95 | 0.132699E+09 | 0.00 | 0.340277E+11 | 0.00 | 5.60 |
May | 0.736656E+09 | 0.312881E+10 | 0.00 | 41397279.89 | 0.487840E+09 | 0.00 | 0.210634E+11 | 0.00 | 5.44 |
June | 0.279401E+09 | 0.136413E+11 | 0.00 | 17549001.46 | 0.120184E+10 | 0.00 | 0.742748E+10 | 0.00 | 4.57 |
July | 5074158.42 | 0.232499E+11 | 0.00 | 3700905.05 | 0.163875E+10 | 0.00 | 0.946287E+09 | 0.00 | 4.11 |
August | 1841923.45 | 0.273843E+11 | 0.00 | 1916151.38 | 0.186469E+10 | 0.00 | 0.430425E+09 | 0.00 | 4.05 |
September | 0.564735E+09 | 0.104175E+11 | 0.00 | 22651411.63 | 0.110558E+10 | 0.00 | 0.128924E+11 | 0.00 | 4.96 |
October | 0.712563E+10 | 0.247308E+10 | 0.00 | 32556200.56 | 0.424699E+09 | 0.00 | 0.354698E+11 | 0.00 | 5.28 |
November | 0.132259E+11 | 48051523.95 | 0.00 | 29102966.65 | 29980065.77 | 0.00 | 0.412055E+11 | 0.00 | 5.13 |
December | 0.211226E+11 | 0.00 | 0.00 | 23289643.26 | 67604.21 | 0.00 | 0.441456E+11 | 0.00 | 4.49 |
Annual Sum or Average | 0.100763E+12 | 0.808775E+11 | 0.00 | 0.289332E+09 | 0.689933E+10 | 0.00 | 0.313671E+12 | 0.00 | 4.83 |
Minimum of Months | 1841923.45 | 0.00 | 0.00 | 1916151.38 | 0.00 | 0.00 | 0.430425E+09 | 0.00 | 4.05 |
Maximum of Months | 0.259329E+11 | 0.273843E+11 | 0.00 | 41397279.89 | 0.186469E+10 | 0.00 | 0.441456E+11 | 0.00 | 5.60 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.101373E+09 | 0.00 | 0.00 | 0.594301E+11 | 0.00 | 13.02 |
February | 0.00 | 2184466.71 | 0.00 | 94167449.74 | 0.00 | 0.00 | 0.502010E+11 | 0.00 | 15.32 |
March | 0.00 | 59864840.81 | 0.00 | 0.106064E+09 | 0.00 | 0.00 | 0.493894E+11 | 0.00 | 17.89 |
April | 0.00 | 0.784742E+09 | 0.00 | 97243347.36 | 0.00 | 0.00 | 0.343887E+11 | 0.00 | 18.67 |
May | 0.00 | 0.443306E+10 | 0.00 | 71132471.62 | 0.00 | 0.00 | 0.184901E+11 | 0.00 | 17.90 |
June | 0.00 | 0.169976E+11 | 0.00 | 29438981.35 | 0.00 | 0.00 | 0.648377E+10 | 0.00 | 15.32 |
July | 0.00 | 0.279059E+11 | 0.00 | 3971217.94 | 0.00 | 0.00 | 0.708032E+09 | 0.00 | 13.86 |
August | 0.00 | 0.320275E+11 | 0.00 | 2660577.40 | 0.00 | 0.00 | 0.359381E+09 | 0.00 | 13.73 |
September | 0.00 | 0.130951E+11 | 0.00 | 45421024.29 | 0.00 | 0.00 | 0.119487E+11 | 0.00 | 16.54 |
October | 0.00 | 0.325983E+10 | 0.00 | 92349378.91 | 0.00 | 0.00 | 0.400671E+11 | 0.00 | 17.61 |
November | 0.00 | 95927697.23 | 0.00 | 99529146.62 | 0.00 | 0.00 | 0.511081E+11 | 0.00 | 16.96 |
December | 0.00 | 84823.76 | 0.00 | 0.101941E+09 | 0.00 | 0.00 | 0.608755E+11 | 0.00 | 14.27 |
Annual Sum or Average | 0.00 | 0.986618E+11 | 0.00 | 0.845292E+09 | 0.00 | 0.00 | 0.383450E+12 | 0.00 | 15.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2660577.40 | 0.00 | 0.00 | 0.359381E+09 | 0.00 | 13.02 |
Maximum of Months | 0.00 | 0.320275E+11 | 0.00 | 0.106064E+09 | 0.00 | 0.00 | 0.608755E+11 | 0.00 | 18.67 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.428757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246755E+10 | 0.00 | 0.00 | 0.36 |
February | 0.442736E+10 | 0.00 | 0.00 | 0.00 | 188179.76 | 0.128809E+10 | 0.00 | 0.00 | 0.41 |
March | 0.529932E+10 | 3645872.10 | 0.00 | 329223.05 | 2166445.59 | 0.00 | 0.190209E+09 | 0.00 | 0.46 |
April | 0.315335E+10 | 44714805.34 | 0.00 | 2691886.70 | 33532830.48 | 0.00 | 0.920448E+09 | 0.00 | 0.52 |
May | 0.905215E+09 | 0.591320E+09 | 0.00 | 4757164.62 | 6309015.00 | 0.00 | 0.152641E+10 | 0.00 | 0.57 |
June | 0.212527E+09 | 0.279968E+10 | 0.00 | 2924755.92 | 71281.97 | 0.00 | 0.706927E+09 | 0.00 | 0.61 |
July | 4721798.19 | 0.478803E+10 | 0.00 | 454569.02 | 4817058.18 | 0.00 | 0.110201E+09 | 0.00 | 0.60 |
August | 0.00 | 0.567963E+10 | 0.00 | 345284.49 | 0.00 | 0.00 | 57739322.04 | 0.00 | 0.61 |
September | 0.701837E+09 | 0.182736E+10 | 0.00 | 3079687.92 | 3792776.92 | 0.00 | 0.795318E+09 | 0.00 | 0.55 |
October | 0.398071E+10 | 0.297517E+09 | 0.00 | 1277804.74 | 62730794.38 | 0.00 | 0.539441E+09 | 0.00 | 0.46 |
November | 0.558909E+10 | 601679.60 | 0.00 | 0.00 | 7653412.65 | 0.165799E+09 | 0.00 | 0.00 | 0.44 |
December | 0.618451E+10 | 0.00 | 0.00 | 0.00 | 7151.96 | 0.720398E+09 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.347462E+11 | 0.160325E+11 | 0.00 | 15860376.46 | 0.121269E+09 | 0.464184E+10 | 0.484670E+10 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.618451E+10 | 0.567963E+10 | 0.00 | 4757164.62 | 62730794.38 | 0.246755E+10 | 0.152641E+10 | 0.00 | 0.61 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.177804E+12 | 0.171855E+11 | 0.222399E+12 | 0.612489E+12 | 0.860053E+11 |
February | 0.185683E+12 | 0.126093E+11 | 0.159928E+12 | 0.478188E+12 | 0.108716E+12 |
March | 0.276245E+12 | 0.927240E+10 | 0.113945E+12 | 0.388437E+12 | 0.217138E+12 |
April | 0.312454E+12 | 0.574426E+10 | 0.678256E+11 | 0.274713E+12 | 0.389056E+12 |
May | 0.344148E+12 | 0.138591E+10 | 0.121704E+11 | 0.103441E+12 | 0.685700E+12 |
June | 0.351022E+12 | -0.475700E+10 | -0.711680E+11 | -0.149998E+12 | 0.102216E+13 |
July | 0.326496E+12 | -0.916149E+10 | -0.129817E+12 | -0.329286E+12 | 0.126967E+13 |
August | 0.301318E+12 | -0.110010E+11 | -0.151020E+12 | -0.403529E+12 | 0.134451E+13 |
September | 0.225963E+12 | -0.252359E+10 | -0.384281E+11 | -0.510973E+11 | 0.881654E+12 |
October | 0.215054E+12 | 0.599355E+10 | 0.720764E+11 | 0.287829E+12 | 0.390306E+12 |
November | 0.148550E+12 | 0.997810E+10 | 0.123871E+12 | 0.422394E+12 | 0.178155E+12 |
December | 0.141149E+12 | 0.138029E+11 | 0.177784E+12 | 0.524263E+12 | 0.969844E+11 |
Annual Sum or Average | 0.300588E+13 | 0.485288E+11 | 0.559566E+12 | 0.215784E+13 | 0.667005E+13 |
Minimum of Months | 0.141149E+12 | -0.110010E+11 | -0.151020E+12 | -0.403529E+12 | 0.860053E+11 |
Maximum of Months | 0.351022E+12 | 0.171855E+11 | 0.222399E+12 | 0.612489E+12 | 0.134451E+13 |