Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:50
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 08:50:54
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 13275.18 | 1170.11 | 1170.11 |
Net Site Energy | 13275.18 | 1170.11 | 1170.11 |
Total Source Energy | 23227.47 | 2047.32 | 2047.32 |
Net Source Energy | 23227.47 | 2047.32 | 2047.32 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3615.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 321.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 545.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 192.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 640.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 560.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 57.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 140.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 3628.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 43.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4242.52 | 9032.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3615.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 321.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 545.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 192.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 560.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 57.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 140.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 3628.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 20.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3615.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 321.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 545.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 192.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 640.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 560.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 57.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 140.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 3628.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 43.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 90.91 | 638.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 218.04 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 373.95 | 796.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 90.91 | 638.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 218.04 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 373.95 | 796.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4242.520 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4242.520 | 100.00 |
Total On-Site and Utility Electric Sources | 4242.520 | 100.00 |
Total Electricity End Uses | 4242.520 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 0.91 | 0.03 |
Air to Air Heat Recovery for Heating | 3377.71 | 99.97 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3378.62 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 213.50 |
Time Setpoint Not Met During Occupied Cooling | 37.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7936.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:50 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.7179 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 9.6995 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.6995 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.2862 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 9.2569 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.0417 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4132 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8577 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8577 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.7179 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 4.2862 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.7049 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 9.2569 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.0417 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4132 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7327 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4132 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.8577 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.8577 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.7137 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-19:10 | 12-JAN-21:49 | - | - | - | - | - | - | - | - | - | - | 09-MAY-20:10 |
Heating | 0.00 | 753329.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 97264.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 41208.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86131.51 | 75123.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31523.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27000.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4539.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3827.07 | 308165.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1682.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 301443.71 | 1136619.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 753329.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 97264.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 41208.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1219.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 27000.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4539.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3827.07 | 308165.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 771.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 670.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3919.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1019.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1726.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 609.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5220.66 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2028.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1775.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 183.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.38 | 3932.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 138.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 13436.06 | 9791.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 345.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 89.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 152.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 53.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 16.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 39.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 346.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1184.29 | 863.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 345.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 89.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 152.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 53.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 16.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 39.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 346.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1184.29 | 863.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.19 | 0.687865 | 0.585000 | 1.28 | 1.00 | 0.500000 | 0.000554 | 0.000080 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.502143 | 0.101781 | 0.237000 | 0.119008 | 0.300000 | 0.500000 | 0.003743 | 0.000046 | 0.186280 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.226656 | 0.261116 | 0.607000 | 0.137580 | 0.696310 | 0.500000 | 0.001459 | 0.000018 | 0.137580 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.177999 | 0.703111 | 0.010000 | 0.001780 | 1.00 | 0.500000 | 0.000542 | 0.000027 | 0.108496 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.097024 | 0.744211 | 0.893000 | 0.086643 | 1.00 | 0.500000 | 0.000512 | 0.000019 | 0.086643 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.32 | 0.017936 | 0.010000 | 0.033154 | 0.300000 | 0.500000 | 0.021242 | 0.000036 | 0.145178 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.95 | 0.073763 | 0.520000 | 1.01 | 0.520000 | 0.500000 | 0.005165 | 0.000141 | 1.01 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.28 | 0.188873 | 0.538000 | 2.84 | 0.538000 | 0.500000 | 0.002017 | 0.000344 | 2.84 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.43 | 0.832147 | 0.499000 | 0.711732 | 1.00 | 0.500000 | 0.000458 | 0.000154 | 0.711732 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.11 | 0.119877 | 0.845000 | 1.78 | 0.845000 | 0.500000 | 0.003178 | 0.000166 | 1.78 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.21 | 0.114242 | 0.805000 | 1.78 | 0.805000 | 0.500000 | 0.003335 | 0.000167 | 1.78 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.27 | 0.062288 | 0.242000 | 0.550083 | 0.300000 | 0.500000 | 0.011002 | 0.000068 | 0.550083 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.765123 | 0.410442 | 0.246000 | 0.188220 | 1.00 | 0.500000 | 0.000928 | 0.000109 | 0.444154 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 9126.48 | 0.000080 | 194.04 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5245.74 | 0.000046 | 143.16 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2069.27 | 0.000018 | 47.90 |
MECH_FLR_1 VAV BOX REHEAT COIL | 3055.03 | 0.000027 | 83.37 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 2215.30 | 0.000019 | 58.36 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 4087.90 | 0.000036 | 111.56 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 16095.40 | 0.000141 | 376.13 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 39328.83 | 0.000344 | 898.36 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 9434.70 | 0.000083 | 269.61 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 9427.28 | 0.000082 | 269.40 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 53045.55 | 0.000464 | 1515.87 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 52941.23 | 0.000463 | 1512.89 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 9421.16 | 0.000082 | 269.23 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 9413.73 | 0.000082 | 269.02 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 17602.31 | 0.000154 | 458.58 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2902.68 | 0.000025 | 82.95 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2900.22 | 0.000025 | 82.87 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 13914.30 | 0.000122 | 397.60 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 18919.19 | 0.000166 | 417.19 |
DINING_FLR_6 VAV BOX REHEAT COIL | 19083.83 | 0.000167 | 421.25 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7752.66 | 0.000068 | 177.57 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 12508.55 | 0.000109 | 341.38 |
VAV WITH REHEAT HEATING COIL | 469047.49 | 0.004103 | 6161.67 |
FLR_3_DOAS HEATING COIL | 42957.20 | 0.000376 | 564.31 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.17 | 0.000083 | 0.000364 |
ROOM_2_FLR_3 FAN COIL | 1.05 | 0.000082 | 0.000328 |
ROOM_3_MULT19_FLR_3 FAN COIL | 8.74 | 0.000464 | 0.002691 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.46 | 0.000463 | 0.001787 |
ROOM_5_FLR_3 FAN COIL | 1.10 | 0.000082 | 0.000344 |
ROOM_6_FLR_3 FAN COIL | 0.999244 | 0.000082 | 0.000311 |
ROOM_1_FLR_6 FAN COIL | 0.305501 | 0.000025 | 0.000095 |
ROOM_2_FLR_6 FAN COIL | 0.271862 | 0.000025 | 0.000085 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.84 | 0.000122 | 0.000576 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.17 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.05 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.74 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.46 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.10 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.999244 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.305501 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.271862 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.84 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008535 | 12.80 | 0.008500 | 0.000364 | 1.17 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008539 | 12.80 | 0.008500 | 0.000328 | 1.05 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008480 | 12.80 | 0.008480 | 0.002691 | 8.74 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008724 | 12.80 | 0.008500 | 0.001787 | 5.46 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008537 | 12.80 | 0.008500 | 0.000344 | 1.10 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008541 | 12.80 | 0.008500 | 0.000311 | 0.999244 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008534 | 12.80 | 0.008500 | 0.000095 | 0.305501 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008538 | 12.80 | 0.008500 | 0.000085 | 0.271862 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008571 | 12.80 | 0.008500 | 0.000576 | 1.84 | |
VAV WITH REHEAT COOLING COIL | 25.41 | 6.70 | 0.008526 | 10.95 | 0.008500 | 0.011259 | 22.40 | 393686.75 |
FLR_3_DOAS COOLING COIL | 27.40 | 6.70 | 0.007007 | 11.91 | 0.007007 | 0.001096 | 2.05 | 38332.30 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 13.15 | 10.53 | 22.53 | 10.53 | 22.40 | 22.40 | 0.300000 | 0.469983 | 22.40 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 22.40 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 9.33 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.40 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.011259 | 0.000042 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.004103 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001096 | 0.000434 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000376 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.018935 | 3060.92 | |
HEATSYS1 PUMP | 0.007283 | 2171.62 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.007283 | 0.873965 |
COOLSYS1 | 0.018935 | 2.27 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 832496.05 | 832496.05 | 0.007283 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.018935 | 2119.18 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.018935 | 662071.15 | 662692.73 | 75.55 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.718 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.098 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 4.286 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.976 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.257 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.637 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.042 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.112 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 13293.583 | 6.718 | 124.824 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13293.583 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 650.557 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 650.557 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 753.347 | 9.699 | 60.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 753.347 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 406.155 | 4.286 | 199.096 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 406.155 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1748.285 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1748.285 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11828.200 | 9.042 | 28.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11828.200 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1718.521 | 4.413 | 82.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.521 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.035 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.035 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1818.789 | 4.413 | 82.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.789 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.4398 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.6205 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.6325 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.6205 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.6325 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.106 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.444 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.414 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.444 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.414 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
21 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
22 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
23 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
24 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
25 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
26 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
27 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
28 | 9 | 0.17371606E-14 | -0.23506564E-15 | -0.17234884E-09 | -0.32590245E-16 |
29 | 8 | 0.25047502E-07 | 0.60224990E-13 | 0.41035840E-03 | -0.28479873E-09 |
30 | 7 | -0.13210747E-01 | 0.30368709E-08 | -0.24480499E-01 | 0.15021102E-03 |
31 | 6 | 0.43168160 | 0.10447339E-05 | 0.49445446 | -0.50581458E-02 |
32 | 5 | -5.4474818 | 0.38634567E-04 | -4.6127458 | 0.66369558E-01 |
33 | 4 | 34.139005 | 0.31329049E-03 | 22.110007 | -0.43720821 |
34 | 3 | -113.64276 | 0.67747045E-03 | -56.947664 | 1.5501088 |
35 | 2 | 199.52538 | 0.37841992E-03 | 79.089894 | -2.9387388 |
36 | 1 | -172.04857 | 0.40136815E-04 | -55.610049 | 2.7610814 |
37 | 0 | 57.057407 | 0.22679332E-06 | 15.501623 | |
38 | 9 | 0.70813426E-15 | -0.32338650E-15 | -0.16410183E-09 | -0.10141964E-16 |
39 | 8 | 0.23891456E-07 | 0.84468069E-13 | 0.39866366E-03 | -0.27165407E-09 |
40 | 7 | -0.12863276E-01 | 0.43065613E-08 | -0.23980655E-01 | 0.14626015E-03 |
41 | 6 | 0.42224223 | 0.14881230E-05 | 0.48645144 | -0.49468774E-02 |
42 | 5 | -5.3553902 | 0.55242587E-04 | -4.5514413 | 0.65227641E-01 |
43 | 4 | 33.731817 | 0.44953144E-03 | 21.870751 | -0.43180164 |
44 | 3 | -112.77687 | 0.97513266E-03 | -56.474829 | 1.5375981 |
45 | 2 | 198.66772 | 0.54621935E-03 | 78.655599 | -2.9251182 |
46 | 1 | -171.73197 | 0.58085406E-04 | -55.482564 | 2.7555327 |
47 | 0 | 57.057407 | 0.32916664E-06 | 15.521701 | |
48 | 9 | 0.43401517E-15 | -0.32871761E-15 | -0.16354826E-09 | -0.10464702E-16 |
49 | 8 | 0.23813808E-07 | 0.86070585E-13 | 0.39787146E-03 | -0.27077120E-09 |
50 | 7 | -0.12839716E-01 | 0.43915450E-08 | -0.23946756E-01 | 0.14599225E-03 |
51 | 6 | 0.42160216 | 0.15179544E-05 | 0.48590822 | -0.49393324E-02 |
52 | 5 | -5.3491452 | 0.56364894E-04 | -4.5472777 | 0.65150204E-01 |
53 | 4 | 33.704202 | 0.45877426E-03 | 21.854496 | -0.43143498 |
54 | 3 | -112.71814 | 0.99539661E-03 | -56.442701 | 1.5367495 |
55 | 2 | 198.60954 | 0.55767767E-03 | 78.626100 | -2.9241943 |
56 | 1 | -171.71049 | 0.59314468E-04 | -55.473923 | 2.7551562 |
57 | 0 | 57.057407 | 0.33620339E-06 | 15.523077 | |
58 | 9 | 0.70813426E-15 | -0.32338650E-15 | -0.16410183E-09 | -0.10141964E-16 |
59 | 8 | 0.23891456E-07 | 0.84468069E-13 | 0.39866366E-03 | -0.27165407E-09 |
60 | 7 | -0.12863276E-01 | 0.43065613E-08 | -0.23980655E-01 | 0.14626015E-03 |
61 | 6 | 0.42224223 | 0.14881230E-05 | 0.48645144 | -0.49468774E-02 |
62 | 5 | -5.3553902 | 0.55242587E-04 | -4.5514413 | 0.65227641E-01 |
63 | 4 | 33.731817 | 0.44953144E-03 | 21.870751 | -0.43180164 |
64 | 3 | -112.77687 | 0.97513266E-03 | -56.474829 | 1.5375981 |
65 | 2 | 198.66772 | 0.54621935E-03 | 78.655599 | -2.9251182 |
66 | 1 | -171.73197 | 0.58085406E-04 | -55.482564 | 2.7555327 |
67 | 0 | 57.057407 | 0.32916664E-06 | 15.521701 | |
68 | 9 | 0.43401517E-15 | -0.32871761E-15 | -0.16354826E-09 | -0.10464702E-16 |
69 | 8 | 0.23813808E-07 | 0.86070585E-13 | 0.39787146E-03 | -0.27077120E-09 |
70 | 7 | -0.12839716E-01 | 0.43915450E-08 | -0.23946756E-01 | 0.14599225E-03 |
71 | 6 | 0.42160216 | 0.15179544E-05 | 0.48590822 | -0.49393324E-02 |
72 | 5 | -5.3491452 | 0.56364894E-04 | -4.5472777 | 0.65150204E-01 |
73 | 4 | 33.704202 | 0.45877426E-03 | 21.854496 | -0.43143498 |
74 | 3 | -112.71814 | 0.99539661E-03 | -56.442701 | 1.5367495 |
75 | 2 | 198.60954 | 0.55767767E-03 | 78.626100 | -2.9241943 |
76 | 1 | -171.71049 | 0.59314468E-04 | -55.473923 | 2.7551562 |
77 | 0 | 57.057407 | 0.33620339E-06 | 15.523077 | |
78 | 7 | -0.16359629E-14 | -0.14530353E-16 | -0.22331004E-13 | 0.54056000E-15 |
79 | 6 | 0.18262352E-10 | 0.22801053E-11 | 0.52333849E-09 | -0.18642118E-10 |
80 | 5 | -0.59540244E-07 | 0.11129510E-07 | -0.21928235E-05 | 0.17164558E-06 |
81 | 4 | 0.60861605E-04 | 0.41961443E-05 | 0.17683552E-02 | -0.28248824E-03 |
82 | 3 | -0.87523238E-02 | 0.14809838E-03 | -0.21562890 | 0.43346081E-01 |
83 | 2 | 0.12409989 | 0.64146884E-03 | 2.9009744 | -0.61915653 |
84 | 1 | -0.31397648 | 0.40472017E-03 | -7.1381115 | 1.5697592 |
85 | 0 | 0.19977219 | 0.56546383E-05 | 4.4522022 | |
86 | 7 | -0.22331004E-13 | -0.14530353E-16 | -0.16359629E-14 | 0.54056000E-15 |
87 | 6 | 0.52333849E-09 | 0.22801053E-11 | 0.18262352E-10 | -0.18642118E-10 |
88 | 5 | -0.21928235E-05 | 0.11129510E-07 | -0.59540244E-07 | 0.17164558E-06 |
89 | 4 | 0.17683552E-02 | 0.41961443E-05 | 0.60861605E-04 | -0.28248824E-03 |
90 | 3 | -0.21562890 | 0.14809838E-03 | -0.87523238E-02 | 0.43346081E-01 |
91 | 2 | 2.9009744 | 0.64146884E-03 | 0.12409989 | -0.61915653 |
92 | 1 | -7.1381115 | 0.40472017E-03 | -0.31397648 | 1.5697592 |
93 | 0 | 4.4522022 | 0.56546383E-05 | 0.19977219 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
103 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
104 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
105 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
106 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
107 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
108 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
109 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
110 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
111 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
112 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
113 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
114 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
115 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
116 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
117 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
118 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
119 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
120 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
121 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
122 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
123 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
124 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
125 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
126 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
127 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
128 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
129 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
130 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
131 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
132 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
133 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.265_SHGC_0.397 | 37 | 1 | VerySmooth | 1.505 | 1.505 | 1.000 | 0.398 | ||
2 | RESWINDOW_U_0.265_SHGC_0.397 | 38 | 1 | VerySmooth | 1.505 | 1.505 | 1.000 | 0.398 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 4.45510E-002 | 0.31125 | 0.49414 | 0.49414 | 0.43670 | 0.13422 | 0.17096 | 0.00000 | 0.84000 | 0.84000 | 9.10299E-002 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 4.45510E-002 | 0.31125 | 0.49414 | 0.49414 | 0.43670 | 0.13422 | 0.17096 | 0.00000 | 0.84000 | 0.84000 | 9.10299E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1618 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.9145E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1912 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 0.1206 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 8.8707E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.6335E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.5774E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.5208E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1805 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1184 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2133 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1435 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 9.8133E-002 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.5682E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 5.1377E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.0772E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 5.3245E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 3.0425E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.2478E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.3992E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.6410E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.4310E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.5051E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.5975E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 5.3245E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 3.0425E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.2478E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.3992E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.6410E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.4310E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.5051E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.5975E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 29701.04068 | 29701.04068 | 2.19210 | 2.19210 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 2460.87529 | 2460.87529 | 0.10715 | 0.85446 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 6803.19995 | 6803.19995 | 0.50214 | 0.50214 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40000 | 7.00714E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 4278.84844 | 4278.84844 | 0.18628 | 0.18628 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3070.68963 | 3070.68963 | 0.22666 | 0.22666 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 27.09400 | 7.00668E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1355.06407 | 1355.06407 | 5.89971E-002 | 9.17347E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2412.01970 | 2412.01970 | 0.17800 | 0.17800 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 27.19600 | 7.00683E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 2491.98324 | 2491.98324 | 0.10850 | 0.10850 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1314.73765 | 1314.73765 | 9.70243E-002 | 9.70243E-002 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 27.29800 | 7.00699E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1765.55742 | 1765.55742 | 7.68688E-002 | 7.68688E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44922.78253 | 44922.78253 | 3.31544 | 3.31544 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 27.40000 | 7.00714E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 3334.75999 | 3334.75999 | 0.14518 | 0.14518 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 26412.30239 | 26412.30239 | 1.95103 | 1.95103 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40000 | 7.00714E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 10828.40276 | 10828.40276 | 0.47143 | 0.67639 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 71483.66120 | 71483.66120 | 5.27782 | 5.27782 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 24587.22809 | 24587.22809 | 1.07048 | 1.89399 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11780.01525 | 11780.01525 | 1.17152 | 1.17152 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 25.46200 | 7.00420E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 9434.70327 | 9434.70327 | 0.41315 | 0.41315 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10594.88687 | 10594.88687 | 1.05366 | 1.05366 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.95200 | 7.00344E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 9427.27697 | 9427.27697 | 0.41282 | 0.41282 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 87935.67797 | 87935.67797 | 8.74492 | 8.74492 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 53045.54502 | 53045.54502 | 2.32303 | 2.32303 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 54932.70618 | 54932.70618 | 5.46330 | 5.46330 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 21.07600 | 6.99765E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 52941.23198 | 52941.23198 | 2.31847 | 2.31847 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 11110.32139 | 11110.32139 | 1.10492 | 1.10492 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 24.54400 | 7.00282E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 9421.16021 | 9421.16021 | 0.41255 | 0.41255 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10047.69937 | 10047.69937 | 0.99924 | 0.99924 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 22.65700 | 7.00000E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 9413.73476 | 9413.73476 | 0.41223 | 0.41223 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 19325.95338 | 19325.95338 | 1.42632 | 1.42632 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40000 | 7.00714E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 13906.07876 | 13906.07876 | 0.60546 | 0.60546 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3071.90582 | 3071.90582 | 0.30550 | 0.30550 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 25.46200 | 7.00420E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2902.67805 | 2902.67805 | 0.12711 | 0.12711 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2733.65042 | 2733.65042 | 0.27186 | 0.27186 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.95200 | 7.00344E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2900.22342 | 2900.22342 | 0.12700 | 0.12700 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 18471.58814 | 18471.58814 | 1.83705 | 1.83705 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 13914.30126 | 13914.30126 | 0.60933 | 0.60933 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28529.60356 | 28529.60356 | 2.10818 | 2.10818 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40000 | 7.00714E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 9666.90151 | 9666.90151 | 0.42088 | 1.18780 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 29937.44794 | 29937.44794 | 2.21218 | 2.21218 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40000 | 7.00714E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 9834.61259 | 9834.61259 | 0.42818 | 1.18780 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30720.33760 | 30720.33760 | 2.27307 | 2.27307 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.48200 | 7.00575E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 4899.56140 | 4899.56140 | 0.21329 | 0.36735 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -41.90000 | 6.45023E-005 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10367.19036 | 10367.19036 | 0.76512 | 0.76512 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40000 | 7.00714E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 10201.33996 | 10201.33996 | 0.44415 | 0.44415 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 336440.91 | 22.39823 | 22.39823 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 546284.84 | 7.82595 | 7.82595 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 35674.24 | 19.11046 | 2.05125 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 143185.63 | 7.15569 | 2.05125 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.19210 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.68787 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28238 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.53887E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.98425E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28238 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9126.48309 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.98425E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 194.03701 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.50214 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10178 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23700 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11901 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.74335E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.58920E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.18628 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5245.73533 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.58920E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 143.16083 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22666 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26112 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.60700 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13758 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69631 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45912E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.81029E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13758 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2069.27138 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.81029E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 47.90402 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.17800 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.70311 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.77999E-003 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.41878E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.67267E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.10850 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3055.03124 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.67267E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 83.37174 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.70243E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.74421 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.89300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.66427E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.11951E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.93805E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.66427E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2215.30457 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.93805E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 58.35675 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.31544 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.79361E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.31544E-002 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.12421E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.57628E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.14518 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4087.90463 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.57628E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 111.55863 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.95103 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.37626E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01453 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.16522E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40810E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01453 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16095.39746 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40810E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 376.13494 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.27782 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18887 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.53800 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.83947 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53800 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.01723E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.44066E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.83947 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 39328.83397 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.44066E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 898.36214 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.17152 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.17152 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.25389E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.64047E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69232 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.53540E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.64047E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.17152 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9434.70327 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.25389E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 269.61444 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.05366 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.05366 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.24739E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.27756E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69232 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.53908E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.27756E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.05366 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9427.27697 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.24739E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 269.40228 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.74492 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.74492 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.64066E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.69079E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69265 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.48040E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.48040E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.69079E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.74492 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 53045.54502 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.64066E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1515.87384 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.46330 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.46330 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.63153E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.78652E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69176 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72431E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.78652E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.46330 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 52941.23198 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.63153E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1512.89382 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.10492 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.10492 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.24204E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.43528E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69232 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.53726E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.43528E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.10492 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9421.16021 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.24204E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 269.22753 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.99924 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.99924 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.23555E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.10982E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69232 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54085E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.10982E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.99924 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9413.73476 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.23555E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 269.01539 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.42632 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.83215 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49900 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71173 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.57852E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.53993E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71173 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17602.31255 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.53993E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 458.57951 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.30550 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.30550 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.53939E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.48958E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69233 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.53396E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.48958E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.30550 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2902.67805 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.53939E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 82.94508 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.27186 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.27186 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.53724E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.45385E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69232 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.53789E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.45385E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.27186 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2900.22342 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.53724E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 82.87496 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.83705 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.83705 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.21728E-004 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.76405E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69206 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57055E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.76405E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.83705 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 13914.30126 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21728E-004 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 397.60459 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.10818 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11988 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.84500 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78141 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84500 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.17825E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.65513E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78141 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18919.18870 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.65513E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 417.18767 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.21218 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11424 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.80500 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78080 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80500 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.33504E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.66954E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78080 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19083.82741 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66954E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 421.25031 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.27307 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.22877E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24200 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55008 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10018E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.78236E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55008 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7752.65879 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.78236E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 177.57011 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76512 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.41044 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24600 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18822 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.28267E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.09430E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.44415 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12508.54800 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.09430E-004 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 341.37987 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 13.15287 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 10.52680 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.52508 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 10.52680 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.39823 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.39823 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.46998 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.39823 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.39823 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 9.32920 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.40988 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.94818 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.52627E-003 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 393686.74908 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.12594E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.39823 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 469047.49414 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.10343E-003 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6161.67446 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.39823 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.12594E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.22927E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.10343E-003 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.40000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91318 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00714E-003 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00714E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 38332.29647 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.09630E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 42957.20027 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.75808E-004 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 564.31020 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.09630E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.34362E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.75808E-004 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 1.89352E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 3060.92234 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 7.28304E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.87396 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 7.28304E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 2171.61523 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 832496.04648 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 832496.05000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 7.28304E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 1.89352E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.27222 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 1.89352E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2119.17977 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 1.89352E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 662071.14732 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 662692.73000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 75.54697 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 9172.84 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5265.64 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2078.82 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 3066.63 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 2224.02 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 4103.42 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 16169.02 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 39512.71 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 10162.01 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 10154.01 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 57135.45 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 57023.11 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 10147.43 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 10139.43 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 17672.39 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 3126.35 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 3123.70 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 14986.51 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 19010.84 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 19176.18 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7788.81 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 12556.01 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 249140.71 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 22817.28 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 18984.45 | 16439.49 | 2544.96 | 0.87 | 3822.11 | 38.77 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 17086.46 | 14789.65 | 2296.81 | 0.87 | 3436.34 | 34.85 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 141001.87 | 122583.63 | 18418.24 | 0.87 | 29025.18 | 294.39 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 91686.99 | 77770.16 | 13916.84 | 0.85 | 17617.50 | 178.69 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 17911.50 | 15507.04 | 2404.45 | 0.87 | 3604.16 | 36.56 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 16209.44 | 14027.65 | 2181.79 | 0.87 | 3258.29 | 33.05 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4949.27 | 4286.51 | 662.76 | 0.87 | 996.84 | 10.11 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4407.58 | 3815.63 | 591.95 | 0.87 | 886.73 | 8.99 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 29971.11 | 25849.07 | 4122.04 | 0.86 | 5979.88 | 60.65 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 506235.27 | 371653.32 | 134581.95 | 0.73 | 87553.70 | 888.02 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 51661.93 | 36376.38 | 15285.55 | 0.70 | 12474.20 | 126.52 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.270 | 0.259 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.270 | 0.259 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.270 | 0.259 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.270 | 0.259 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.440 | 0.413 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.440 | 0.413 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.440 | 0.413 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.440 | 0.413 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.440 | 0.413 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.440 | 0.413 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.440 | 0.413 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.440 | 0.413 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.440 | 0.413 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.440 | 0.413 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.440 | 0.413 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.440 | 0.413 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.440 | 0.413 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.620 | 0.568 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.620 | 0.568 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.620 | 0.568 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.620 | 0.568 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.620 | 0.568 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.620 | 0.568 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.620 | 0.568 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.620 | 0.568 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.620 | 0.568 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.620 | 0.568 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.620 | 0.568 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.620 | 0.568 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.620 | 0.568 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.620 | 0.568 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.632 | 0.578 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.632 | 0.578 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.632 | 0.578 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.632 | 0.578 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.632 | 0.578 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.632 | 0.578 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.632 | 0.578 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.632 | 0.578 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.632 | 0.578 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.632 | 0.578 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.632 | 0.578 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.632 | 0.578 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.632 | 0.578 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.265_SHGC_0.397 | N/A | 1.505 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.5976410071E-002 | 2.2068658109E-002 | Pass | Pass | 2.8385090679E-003 | 4.3747118270E-003 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.3397202587E-003 | 9.7341006521E-004 | Pass | Pass | 1.4902626463E-002 | 2.9478826606E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.0545900547E-003 | 7.3175543349E-004 | Pass | Pass | 0.1584874076 | 0.5630940109 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.4716639992E-004 | 1.3164959363E-004 | Pass | Pass | 5.7365483739E-002 | 0.1787574262 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.8284205990E-004 | 5.9315158049E-004 | Pass | Pass | 1.1554399896E-002 | 2.0032521407E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.7152823520E-005 | 1.8390113676E-004 | Pass | Pass | 2.2146044275E-002 | 6.4188317491E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.4523794265E-003 | 1.7343410283E-003 | Pass | Pass | 0.1041080862 | 0.4133446710 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.9502520188E-003 | 2.3314888525E-002 | Pass | Pass | 3.6860355151E-002 | 0.1247453876 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2668924261E-002 | 0.3375437075 | Pass | Pass | 8.8053682342E-002 | 0.2586923529 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2615861714E-002 | 0.3352696843 | Pass | Pass | 8.7178041793E-002 | 0.2584866893 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.1479375711E-005 | 7.8365681880E-005 | Pass | Pass | 2.7368823866E-002 | 6.7011317454E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.6700713128E-002 | 0.1955729645 | Pass | Pass | 6.1502858559E-002 | 0.1685786513 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2646771239E-002 | 0.3362727000 | Pass | Pass | 8.8428912455E-002 | 0.2590759066 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2620840536E-002 | 0.3339086719 | Pass | Pass | 8.7585452872E-002 | 0.2587892378 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.8378376593E-004 | 3.6268418901E-004 | Pass | Pass | 3.3676771184E-002 | 8.7674124706E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2649842892E-002 | 0.3503953903 | Pass | Pass | 7.2420936697E-002 | 0.2506751852 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2621299199E-002 | 0.3468688887 | Pass | Pass | 7.1235333738E-002 | 0.2499687522 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2621882893E-002 | 0.3355796779 | Pass | Pass | 8.4253731462E-002 | 0.2419094019 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.9962503875E-002 | 8.0710668325E-002 | Pass | Pass | 1.4126887031E-002 | 4.5461597815E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.5050606701E-002 | 8.8367655108E-002 | Pass | Pass | 1.2468308750E-002 | 3.6772731818E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.0984219081E-003 | 2.0161186087E-003 | Pass | Pass | 2.5954222309E-002 | 5.0619353392E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.5868771653E-004 | 4.2397210559E-004 | Pass | Pass | 1.1758676205E-002 | 2.0544750272E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2431.92 | 267.19 | 3313.54 | 9200.84 | 2333.55 | 17547.03 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.261 | 0.270 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.261 | 0.270 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.261 | 0.270 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.261 | 0.270 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.413 | 0.440 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.413 | 0.440 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.413 | 0.440 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.413 | 0.440 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.413 | 0.440 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.413 | 0.440 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.413 | 0.440 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.413 | 0.440 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.413 | 0.440 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.413 | 0.440 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.413 | 0.440 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.413 | 0.440 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.413 | 0.440 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.568 | 0.620 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.568 | 0.620 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.568 | 0.620 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.568 | 0.620 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.568 | 0.620 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.568 | 0.620 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.568 | 0.620 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.568 | 0.620 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.568 | 0.620 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.568 | 0.620 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.568 | 0.620 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.568 | 0.620 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.568 | 0.620 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.568 | 0.620 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.578 | 0.632 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.578 | 0.632 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.578 | 0.632 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.578 | 0.632 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.578 | 0.632 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.578 | 0.632 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.578 | 0.632 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.578 | 0.632 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.578 | 0.632 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.578 | 0.632 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.578 | 0.632 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.578 | 0.632 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.578 | 0.632 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.265_SHGC_0.397 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 1.505 | 0.398 | 0.438 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.265_SHGC_0.397 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 1.505 | 0.398 | 0.438 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.265_SHGC_0.397 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 1.505 | 0.398 | 0.438 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.265_SHGC_0.397 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.505 | 0.398 | 0.438 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.265_SHGC_0.397 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.505 | 0.398 | 0.438 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.265_SHGC_0.397 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.505 | 0.398 | 0.438 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.265_SHGC_0.397 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.505 | 0.398 | 0.438 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.265_SHGC_0.397 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 1.505 | 0.398 | 0.438 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.265_SHGC_0.397 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 1.505 | 0.398 | 0.438 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.265_SHGC_0.397 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.505 | 0.398 | 0.438 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.265_SHGC_0.397 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.505 | 0.398 | 0.438 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.265_SHGC_0.397 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.505 | 0.398 | 0.438 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.265_SHGC_0.397 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.505 | 0.398 | 0.438 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.265_SHGC_0.397 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.505 | 0.398 | 0.438 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.265_SHGC_0.397 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 1.505 | 0.398 | 0.438 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.265_SHGC_0.397 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 1.505 | 0.398 | 0.438 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.265_SHGC_0.397 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.505 | 0.398 | 0.438 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.265_SHGC_0.397 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.505 | 0.398 | 0.438 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.265_SHGC_0.397 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.505 | 0.398 | 0.438 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.265_SHGC_0.397 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.505 | 0.398 | 0.438 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.265_SHGC_0.397 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.505 | 0.398 | 0.438 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.265_SHGC_0.397 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 1.505 | 0.398 | 0.438 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.265_SHGC_0.397 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.505 | 0.398 | 0.438 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.265_SHGC_0.397 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.505 | 0.398 | 0.438 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.265_SHGC_0.397 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.505 | 0.398 | 0.438 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.265_SHGC_0.397 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.505 | 0.398 | 0.438 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.265_SHGC_0.397 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.505 | 0.398 | 0.438 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.265_SHGC_0.397 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 1.505 | 0.398 | 0.438 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.265_SHGC_0.397 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 1.505 | 0.398 | 0.438 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.265_SHGC_0.397 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.505 | 0.398 | 0.438 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 1.505 | 0.398 | 0.438 | |||||||||||||||||
North Total or Average | 432.95 | 1.505 | 0.398 | 0.438 | |||||||||||||||||
Non-North Total or Average | 780.84 | 1.505 | 0.398 | 0.438 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.7179 | 1978.83 | 13293.58 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 122.93 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 9.6995 | 67.07 | 650.56 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.26 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 9.6995 | 77.67 | 753.35 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.25 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 4.2862 | 94.76 | 406.16 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 2.31 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.7049 | 78.04 | 445.21 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 9.2569 | 188.86 | 1748.29 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.04 | 0.0000 | Y | 12.81 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.0417 | 1308.19 | 11828.20 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.50 | 0.0000 | Y | 92.14 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.78 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.79 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4132 | 1557.62 | 6874.08 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 56.74 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 6.96 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.88 | 0.0000 | Y | 28.17 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.88 | 0.0000 | Y | 28.17 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7327 | 103.30 | 1212.04 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4132 | 412.12 | 1818.79 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 15.01 |
Interior Lighting Total | 5.8577 | 11345.29 | 66457.67 | 365.55 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.06 | 83.06 | 192.37 | |
Exterior Lighting Total | 12338.45 | 192.37 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 832496.05 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 662692.73 | 2.96 | 662809.21 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12729.22 | 18984.45 | 16439.49 | 2544.96 | 0.87 | - | 3822.11 | 38.77 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11460.28 | 17086.46 | 14789.65 | 2296.81 | 0.87 | - | 3436.34 | 34.85 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 94085.77 | 141001.87 | 122583.63 | 18418.24 | 0.87 | - | 29025.18 | 294.39 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 62467.09 | 91686.99 | 77770.16 | 13916.84 | 0.85 | - | 17617.50 | 178.69 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12011.74 | 17911.50 | 15507.04 | 2404.45 | 0.87 | - | 3604.16 | 36.56 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10873.73 | 16209.44 | 14027.65 | 2181.79 | 0.87 | - | 3258.29 | 33.05 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3318.11 | 4949.27 | 4286.51 | 662.76 | 0.87 | - | 996.84 | 10.11 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2955.96 | 4407.58 | 3815.63 | 591.95 | 0.87 | - | 886.73 | 8.99 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 20154.49 | 29971.11 | 25849.07 | 4122.04 | 0.86 | - | 5979.88 | 60.65 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 393686.75 | 506235.27 | 371653.32 | 134581.95 | 0.73 | - | 87553.70 | 888.02 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 38332.30 | 51661.93 | 36376.38 | 15285.55 | 0.70 | - | 12474.20 | 126.52 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 9126.48 | 9172.84 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 5245.74 | 5265.64 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2069.27 | 2078.82 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3055.03 | 3066.63 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2215.30 | 2224.02 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4087.90 | 4103.42 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16095.40 | 16169.02 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 39328.83 | 39512.71 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9434.70 | 10162.01 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9427.28 | 10154.01 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 53045.55 | 57135.45 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 52941.23 | 57023.11 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9421.16 | 10147.43 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9413.73 | 10139.43 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17602.31 | 17672.39 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2902.68 | 3126.35 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2900.22 | 3123.70 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 13914.30 | 14986.51 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 18919.19 | 19010.84 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 19083.83 | 19176.18 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7752.66 | 7788.81 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12508.55 | 12556.01 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 469047.49 | 249140.71 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 42957.20 | 22817.28 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.17 | 824.33 | 703.64 | 1.00 | 1.16 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.05 | 741.40 | 703.64 | 1.00 | 1.18 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 8.74 | 6153.24 | 703.64 | 1.00 | 0.94 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.46 | 3844.18 | 703.64 | 1.00 | 0.96 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.10 | 777.46 | 703.64 | 1.00 | 1.17 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.00 | 703.10 | 703.64 | 1.00 | 1.20 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.31 | 214.96 | 703.64 | 1.00 | 1.70 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.27 | 191.29 | 703.64 | 1.00 | 1.78 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.84 | 1292.62 | 703.64 | 1.00 | 1.08 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 22.40 | 50186.34 | 2240.64 | 1.00 | 1.11 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.018935 | 3060.92 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.007283 | 2171.62 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.018935 | 2119.18 | 111917.77 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 29701.04 | 29701.04 | 15.01 | 2.192 | 2.192 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00931 | 23.42 | 0.00700 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 6803.20 | 6803.20 | 101.43 | 0.502 | 0.502 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00883 | 27.40 | 0.00701 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3070.69 | 3070.69 | 39.54 | 0.227 | 0.227 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00939 | 27.09 | 0.00701 | 0.092 | 0.00 |
MECH_FLR_1 | 2412.02 | 2412.02 | 14.69 | 0.178 | 0.178 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00867 | 27.20 | 0.00701 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1314.74 | 1314.74 | 13.87 | 0.097 | 0.097 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00876 | 27.30 | 0.00701 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44922.78 | 44922.78 | 575.64 | 3.315 | 3.315 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00854 | 27.40 | 0.00701 | 0.000 | 0.00 |
CAFE_FLR_1 | 26412.30 | 26412.30 | 139.85 | 1.951 | 1.951 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 23.99 | 0.00969 | 27.40 | 0.00701 | 0.676 | 0.00 |
LOBBY_FLR_1 | 71483.66 | 71483.66 | 54.64 | 5.278 | 5.278 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.00981 | 27.40 | 0.00701 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11780.02 | 11780.02 | 301.88 | 1.172 | 1.172 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 21.11 | 21.11 | 0.00854 | 25.46 | 0.00700 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10594.89 | 10594.89 | 271.54 | 1.054 | 1.054 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 21.11 | 21.11 | 0.00854 | 24.95 | 0.00700 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 87935.68 | 87935.68 | 3585.72 | 8.745 | 8.745 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00848 | 27.40 | 0.00701 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 54932.71 | 54932.71 | 2239.36 | 5.463 | 5.463 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 21.11 | 21.11 | 0.00872 | 21.08 | 0.00700 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 11110.32 | 11110.32 | 284.72 | 1.105 | 1.105 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 21.11 | 21.11 | 0.00854 | 24.54 | 0.00700 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10047.70 | 10047.70 | 257.52 | 0.999 | 0.999 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 21.11 | 21.11 | 0.00854 | 22.66 | 0.00700 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 19325.95 | 19325.95 | 49.63 | 1.426 | 1.426 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00945 | 27.40 | 0.00701 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3071.91 | 3071.91 | 78.72 | 0.306 | 0.306 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 21.11 | 21.11 | 0.00853 | 25.46 | 0.00700 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2733.65 | 2733.65 | 70.06 | 0.272 | 0.272 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 21.11 | 21.11 | 0.00854 | 24.95 | 0.00700 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 18471.59 | 18471.59 | 753.00 | 1.837 | 1.837 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00857 | 27.40 | 0.00701 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28529.60 | 28529.60 | 86.02 | 2.108 | 2.108 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.98 | 0.01046 | 27.40 | 0.00701 | 1.188 | 0.00 |
DINING_FLR_6 | 29937.45 | 29937.45 | 90.27 | 2.212 | 2.212 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.99 | 0.01037 | 27.40 | 0.00701 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30720.34 | 30720.34 | 297.38 | 2.273 | 2.273 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01006 | 26.48 | 0.00701 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10367.19 | 10367.19 | 25.16 | 0.765 | 0.765 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00896 | 27.40 | 0.00701 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 2460.88 | 2460.88 | 1.24 | 0.107 | 0.854 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4278.85 | 4278.85 | 63.80 | 0.186 | 0.186 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00750 | -41.90 | 0.00006 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1355.06 | 1355.06 | 17.45 | 0.059 | 0.092 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00740 | -41.90 | 0.00006 | 0.092 | 0.00 |
MECH_FLR_1 | 2491.98 | 2491.98 | 15.17 | 0.108 | 0.108 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00725 | -41.90 | 0.00006 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1765.56 | 1765.56 | 18.63 | 0.077 | 0.077 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00738 | -41.90 | 0.00006 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 3334.76 | 3334.76 | 42.73 | 0.145 | 0.145 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00724 | -41.90 | 0.00006 | 0.000 | 0.00 |
CAFE_FLR_1 | 10828.40 | 10828.40 | 57.34 | 0.471 | 0.676 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00756 | -41.90 | 0.00006 | 0.676 | 0.00 |
LOBBY_FLR_1 | 24587.23 | 24587.23 | 18.79 | 1.070 | 1.894 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00746 | -41.90 | 0.00006 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9434.70 | 9434.70 | 241.78 | 0.413 | 0.413 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00748 | -41.90 | 0.00006 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9427.28 | 9427.28 | 241.62 | 0.413 | 0.413 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00748 | -41.90 | 0.00006 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 53045.55 | 53045.55 | 2163.02 | 2.323 | 2.323 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00751 | -41.90 | 0.00006 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 52941.23 | 52941.23 | 2158.18 | 2.318 | 2.318 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00751 | -41.90 | 0.00006 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9421.16 | 9421.16 | 241.43 | 0.413 | 0.413 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00748 | -41.90 | 0.00006 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9413.73 | 9413.73 | 241.27 | 0.412 | 0.412 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00748 | -41.90 | 0.00006 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 13906.08 | 13906.08 | 35.71 | 0.605 | 0.605 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00757 | -41.90 | 0.00006 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2902.68 | 2902.68 | 74.39 | 0.127 | 0.127 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00757 | -41.90 | 0.00006 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2900.22 | 2900.22 | 74.33 | 0.127 | 0.127 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00757 | -41.90 | 0.00006 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13914.30 | 13914.30 | 567.22 | 0.609 | 0.609 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00759 | -41.90 | 0.00006 | 0.099 | 0.00 |
BANQUET_FLR_6 | 9666.90 | 9666.90 | 29.15 | 0.421 | 1.188 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00768 | -41.90 | 0.00006 | 1.188 | 0.00 |
DINING_FLR_6 | 9834.61 | 9834.61 | 29.65 | 0.428 | 1.188 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00769 | -41.90 | 0.00006 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 4899.56 | 4899.56 | 47.43 | 0.213 | 0.367 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00724 | -41.90 | 0.00006 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10201.34 | 10201.34 | 24.75 | 0.444 | 0.444 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00773 | -41.90 | 0.00006 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 22.40 | 22.40 | 7.83 | 7.83 | 22.3982 | 10.5268 | 22.3982 | 0.4700 | 0.3000 |
FLR_3_DOAS | 19.11 | 2.05 | 7.16 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 9126.483 | 9126.483 | 1.282378 | 0.00007984 | 194.037 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9126.48 | 9126.48 | 1.282378 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00799839 | 50.9029 | 2460.88 | 0.00 | 9177.43 | 9177.43 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 5245.735 | 5245.735 | 0.186280 | 0.00004589 | 143.161 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 5245.74 | 5245.74 | 0.186280 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00750379 | 47.7992 | 4278.85 | 0.00 | 5271.75 | 5271.75 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 2069.271 | 2069.271 | 0.137580 | 0.00001810 | 47.904 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2069.27 | 2069.27 | 0.137580 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00740339 | 47.1633 | 1355.06 | 0.00 | 2080.35 | 2080.35 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 3055.031 | 3055.031 | 0.108496 | 0.00002673 | 83.372 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3055.03 | 3055.03 | 0.108496 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00724936 | 46.1937 | 2491.98 | 0.00 | 3070.18 | 3070.18 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 2215.305 | 2215.305 | 0.086643 | 0.00001938 | 58.357 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2215.30 | 2215.30 | 0.086643 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00737781 | 47.0025 | 1765.56 | 0.00 | 2226.40 | 2226.40 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 4087.905 | 4087.905 | 0.145178 | 0.00003576 | 111.559 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4087.90 | 4087.90 | 0.145178 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00723550 | 46.1104 | 3334.76 | 0.00 | 4108.18 | 4108.18 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 16095.397 | 16095.397 | 1.014534 | 0.00014081 | 376.135 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 16095.40 | 16095.40 | 1.014534 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00756312 | 48.1714 | 10828.40 | 0.00 | 16181.29 | 16181.29 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 39328.834 | 39328.834 | 2.839466 | 0.00034407 | 898.362 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 39328.83 | 39328.83 | 2.839466 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00745798 | 47.5070 | 24587.23 | 0.00 | 39540.27 | 39540.27 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12729.220 | -999.000 | 1.171523 | 0.00036405 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | unknown | 7/21 17:30:00 | 12729.22 | 12621.54 | 1.171523 | 21.69 | 15.43 | 0.00853540 | 12.80 | 11.96 | 0.00850000 | 25.46 | 0.00700420 | 15.45 | 0.0000 | 21.11 | 0.00853540 | 53.9060 | 11780.02 | 0.00 | 12933.81 | 12933.81 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 9434.703 | 9434.703 | 0.413147 | 0.00008254 | 269.614 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9434.70 | 9434.70 | 0.413147 | 21.11 | 14.26 | 0.00748206 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00748206 | 47.3394 | 9434.70 | 0.00 | 10170.52 | 10170.52 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11460.281 | -999.000 | 1.053662 | 0.00032776 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | unknown | 7/21 18:00:00 | 11460.28 | 11353.34 | 1.053662 | 21.69 | 15.44 | 0.00853908 | 12.80 | 11.96 | 0.00850000 | 24.95 | 0.00700344 | 15.26 | 0.0000 | 21.11 | 0.00853908 | 53.9290 | 10594.89 | 0.00 | 11644.31 | 11644.31 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 9427.277 | 9427.277 | 0.412822 | 0.00008247 | 269.402 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9427.28 | 9427.28 | 0.412822 | 21.11 | 14.26 | 0.00748172 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00748172 | 47.3373 | 9427.28 | 0.00 | 10162.52 | 10162.52 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 94085.773 | -999.000 | 8.744916 | 0.00269079 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 94085.77 | 94085.77 | 8.744916 | 21.69 | 15.38 | 0.00848040 | 12.80 | 11.94 | 0.00848040 | 27.40 | 0.00700714 | 16.15 | 0.0000 | 21.11 | 0.00848040 | 53.5625 | 87935.68 | 0.00 | 95619.94 | 95619.94 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 53045.545 | 53045.545 | 2.323034 | 0.00046407 | 1515.874 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 53045.55 | 53045.55 | 2.323034 | 21.11 | 14.29 | 0.00750985 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00750985 | 47.5093 | 53045.55 | 0.00 | 57183.87 | 57183.87 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 62467.092 | -999.000 | 5.463305 | 0.00178652 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | unknown | 7/21 21:20:00 | 62467.09 | 59263.01 | 5.463305 | 21.69 | 15.60 | 0.00872431 | 12.80 | 11.96 | 0.00850000 | 21.08 | 0.00699765 | 13.80 | 0.0000 | 21.11 | 0.00872431 | 55.0838 | 54932.71 | 0.00 | 63458.03 | 63458.03 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 52941.232 | 52941.232 | 2.318466 | 0.00046315 | 1512.894 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 52941.23 | 52941.23 | 2.318466 | 21.11 | 14.29 | 0.00750882 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00750882 | 47.5029 | 52941.23 | 0.00 | 57071.41 | 57071.41 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 12011.743 | -999.000 | 1.104922 | 0.00034353 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | unknown | 7/21 10:40:00 | 12011.74 | 11904.84 | 1.104922 | 21.69 | 15.43 | 0.00853726 | 12.80 | 11.96 | 0.00850000 | 24.54 | 0.00700282 | 15.11 | 0.0000 | 21.11 | 0.00853726 | 53.9176 | 11110.32 | 0.00 | 12204.72 | 12204.72 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9421.160 | 9421.160 | 0.412554 | 0.00008242 | 269.228 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9421.16 | 9421.16 | 0.412554 | 21.11 | 14.26 | 0.00748137 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00748137 | 47.3351 | 9421.16 | 0.00 | 10155.92 | 10155.92 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10873.731 | -999.000 | 0.999244 | 0.00031098 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | 7/21 09:30:00 | 10873.73 | 10767.71 | 0.999244 | 21.69 | 15.44 | 0.00854085 | 12.80 | 11.96 | 0.00850000 | 22.66 | 0.00700000 | 14.41 | 0.0000 | 21.11 | 0.00854085 | 53.9400 | 10047.70 | 0.00 | 11048.27 | 11048.27 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9413.735 | 9413.735 | 0.412229 | 0.00008236 | 269.015 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9413.73 | 9413.73 | 0.412229 | 21.11 | 14.26 | 0.00748102 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00748102 | 47.3329 | 9413.73 | 0.00 | 10147.92 | 10147.92 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 17602.313 | 17602.313 | 0.711732 | 0.00015399 | 458.580 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 17602.31 | 17602.31 | 0.711732 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00756770 | 48.1961 | 13906.08 | 0.00 | 17690.82 | 17690.82 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3318.110 | -999.000 | 0.305501 | 0.00009490 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | unknown | 7/21 17:30:00 | 3318.11 | 3291.17 | 0.305501 | 21.69 | 15.43 | 0.00853396 | 12.80 | 11.96 | 0.00850000 | 25.46 | 0.00700420 | 15.45 | 0.0000 | 21.11 | 0.00853396 | 53.8971 | 3071.91 | 0.00 | 3371.46 | 3371.46 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2902.678 | 2902.678 | 0.127109 | 0.00002539 | 82.945 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2902.68 | 2902.68 | 0.127109 | 21.11 | 14.35 | 0.00757382 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00757382 | 47.9128 | 2902.68 | 0.00 | 3129.06 | 3129.06 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2955.960 | -999.000 | 0.271862 | 0.00008454 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | unknown | 7/21 18:00:00 | 2955.96 | 2929.21 | 0.271862 | 21.69 | 15.43 | 0.00853789 | 12.80 | 11.96 | 0.00850000 | 24.95 | 0.00700344 | 15.26 | 0.0000 | 21.11 | 0.00853789 | 53.9216 | 2733.65 | 0.00 | 3003.44 | 3003.44 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2900.223 | 2900.223 | 0.127002 | 0.00002537 | 82.875 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2900.22 | 2900.22 | 0.127002 | 21.11 | 14.35 | 0.00757351 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00757351 | 47.9108 | 2900.22 | 0.00 | 3126.42 | 3126.42 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 20154.488 | -999.000 | 1.837050 | 0.00057641 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 20154.49 | 19817.50 | 1.837050 | 21.69 | 15.46 | 0.00857055 | 12.80 | 11.96 | 0.00850000 | 27.40 | 0.00700714 | 16.15 | 0.0000 | 21.11 | 0.00857055 | 54.1258 | 18471.59 | 0.00 | 20478.89 | 20478.89 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13914.301 | 13914.301 | 0.609327 | 0.00012173 | 397.605 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 13914.30 | 13914.30 | 0.609327 | 21.11 | 14.36 | 0.00758975 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00758975 | 48.0110 | 13914.30 | 0.00 | 14999.63 | 14999.63 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 18919.189 | 18919.189 | 1.781414 | 0.00016551 | 417.188 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 18919.19 | 18919.19 | 1.781414 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00768122 | 48.9117 | 9666.90 | 0.00 | 19022.28 | 19022.28 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 19083.827 | 19083.827 | 1.780805 | 0.00016695 | 421.250 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 19083.83 | 19083.83 | 1.780805 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00768645 | 48.9445 | 9834.61 | 0.00 | 19187.77 | 19187.77 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7752.659 | 7752.659 | 0.550083 | 0.00006782 | 177.570 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 7752.66 | 7752.66 | 0.550083 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00723894 | 46.1346 | 4899.56 | 0.00 | 7794.30 | 7794.30 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 12508.548 | 12508.548 | 0.444154 | 0.00010943 | 341.380 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12508.55 | 12508.55 | 0.444154 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00773351 | 49.2397 | 10201.34 | 0.00 | 12570.58 | 12570.58 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 393686.749 | -999.000 | 22.398229 | 0.01125939 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 393686.75 | 391856.94 | 22.398229 | 25.41 | 16.74 | 0.00852627 | 10.95 | 10.95 | 0.00850000 | 27.40 | 0.00700714 | 16.15 | 41.6515 | 23.99 | 0.00958523 | 50.7307 | 303286.48 | 0.00 | 398973.93 | 380437.75 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 469047.494 | 469047.494 | 6.719469 | 0.00410343 | 6161.674 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 469047.49 | 469047.49 | 6.719469 | -41.90 | -41.90 | 0.00006450 | 16.70 | 13.04 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 138.8384 | 21.00 | 0.00754875 | 48.0781 | 98659.87 | 0.00 | 300789.46 | 300789.46 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 38332.296 | -999.000 | 2.051317 | 0.00109630 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38332.30 | 38332.30 | 2.051317 | 27.40 | 16.15 | 0.00700714 | 11.91 | 10.04 | 0.00700714 | 27.40 | 0.00700714 | 16.15 | 99.9965 | 21.11 | 0.00857689 | 54.1644 | 192161.44 | 0.00 | 38875.86 | 38875.86 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 42957.200 | 42957.200 | 0.615395 | 0.00037581 | 564.310 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 42957.20 | 42957.20 | 0.615395 | -41.90 | -41.90 | 0.00006450 | 16.70 | 13.04 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 333.3216 | 21.11 | 0.00751009 | 47.5109 | 163400.85 | 0.00 | 27547.47 | 27547.47 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 9126.483 | 9126.483 | 1.282378 | 0.00007984 | 194.037 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 1.0747 | 1.096279 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9126.48 | 9126.48 | 1.0000 | 1.52018081 | 1.282378 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.07983431 | 60.00 | 32.22 | 27.78 | 0.000 | 9126.48 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00799839 | 21.00 | 0.00799839 | 50.9029 | 2460.88 | 0.00 | 9177.43 | 9177.43 | 1.52018081 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.52 | 15.42 | 0.00800000 | 42971.8 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5245.735 | 5245.735 | 0.186280 | 0.00004589 | 143.161 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 0.6177 | 0.630121 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 5245.74 | 5245.74 | 1.0000 | 0.22082364 | 0.186280 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.04588730 | 60.00 | 32.22 | 27.78 | 0.000 | 5245.74 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00750379 | 21.00 | 0.00750379 | 47.7992 | 4278.85 | 0.00 | 5271.75 | 5271.75 | 0.22082364 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60807.9 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2069.271 | 2069.271 | 0.137580 | 0.00001810 | 47.904 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 0.2437 | 0.248562 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2069.27 | 2069.27 | 1.0000 | 0.16309325 | 0.137580 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.01810104 | 60.00 | 32.22 | 27.78 | 0.000 | 2069.27 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00740339 | 21.00 | 0.00740339 | 47.1633 | 1355.06 | 0.00 | 2080.35 | 2080.35 | 0.16309325 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.11 | 17.74 | 0.00800000 | 49690.3 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3055.031 | 3055.031 | 0.108496 | 0.00002673 | 83.372 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 0.3597 | 0.366972 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3055.03 | 3055.03 | 1.0000 | 0.12861512 | 0.108496 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.02672402 | 60.00 | 32.22 | 27.78 | 0.000 | 3055.03 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00724936 | 21.00 | 0.00724936 | 46.1937 | 2491.98 | 0.00 | 3070.18 | 3070.18 | 0.12861512 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60805.8 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2215.305 | 2215.305 | 0.086643 | 0.00001938 | 58.357 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 0.2609 | 0.266104 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2215.30 | 2215.30 | 1.0000 | 0.10270966 | 0.086643 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.01937847 | 60.00 | 32.22 | 27.78 | 0.000 | 2215.30 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00737781 | 21.00 | 0.00737781 | 47.0025 | 1765.56 | 0.00 | 2226.40 | 2226.40 | 0.10270966 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 37.86 | 20.54 | 0.00800000 | 58611.4 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4087.905 | 4087.905 | 0.145178 | 0.00003576 | 111.559 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 0.4814 | 0.491042 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 4087.90 | 4087.90 | 1.0000 | 0.17209931 | 0.145178 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.03575912 | 60.00 | 32.22 | 27.78 | 0.000 | 4087.90 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00723550 | 21.00 | 0.00723550 | 46.1104 | 3334.76 | 0.00 | 4108.18 | 4108.18 | 0.17209931 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60805.7 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16095.397 | 16095.397 | 1.014534 | 0.00014081 | 376.135 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 1.8952 | 1.933390 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 16095.40 | 16095.40 | 1.0000 | 1.20266792 | 1.014534 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.14079519 | 60.00 | 32.22 | 27.78 | 0.000 | 16095.40 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00756312 | 21.00 | 0.00756312 | 48.1714 | 10828.40 | 0.00 | 16181.29 | 16181.29 | 1.20266792 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.79 | 17.97 | 0.00800000 | 50389.2 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 39328.834 | 39328.834 | 2.839466 | 0.00034407 | 898.362 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 4.6310 | 4.724207 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 39328.83 | 39328.83 | 1.0000 | 3.36601476 | 2.839466 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.34403070 | 60.00 | 32.22 | 27.78 | 0.000 | 39328.83 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00745798 | 21.00 | 0.00745798 | 47.5070 | 24587.23 | 0.00 | 39540.27 | 39540.27 | 3.36601476 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.12 | 17.40 | 0.00800000 | 48681.6 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12729.220 | -999.000 | 1.171523 | 0.00036405 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7069 | 1004.8586 | 1.1854 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.171523 | 1.38876947 | 4197.9300 | 999.8980 | 18.93321942 | 15.03 | 6.70 | 8.33 | 662071.15 | 1.9226 | 1.922600 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | unknown | unknown | unknown | 7/21 17:30:00 | Sensible | 12729.22 | 12621.54 | 1.0000 | 1.38876947 | 1.171523 | 21.69 | 15.43 | 0.00853540 | 43488.0 | 12.80 | 11.96 | 0.00850000 | 34322.2 | 0.36401016 | 6.70 | 15.03 | 8.33 | 0.000 | 12729.22 | 25.46 | 0.00700420 | 15.45 | 0.00000000 | 0.0000 | 21.11 | 0.00853540 | 21.11 | 0.00853540 | 53.9060 | 11780.02 | 0.00 | 12933.81 | 12933.81 | 1.38876947 | 21.69 | 15.59 | 0.00853540 | 43488.0 | 12.57 | 12.04 | 0.00853540 | 34174.9 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9434.703 | 9434.703 | 0.413147 | 0.00008254 | 269.614 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.171523 | 1.38876947 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 1.1109 | 1.133303 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9434.70 | 9434.70 | 1.0000 | 0.48976050 | 0.413147 | 21.11 | 14.26 | 0.00748206 | 40216.4 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.08253048 | 60.00 | 32.22 | 27.78 | 0.000 | 9434.70 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00748206 | 21.11 | 0.00748206 | 47.3394 | 9434.70 | 0.00 | 10170.52 | 10170.52 | 0.48976050 | 16.60 | 12.64 | 0.00748206 | 35623.4 | 36.98 | 19.88 | 0.00748206 | 56389.7 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11460.281 | -999.000 | 1.053662 | 0.00032776 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7137 | 1004.8586 | 1.1854 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.053662 | 1.24905293 | 4197.9300 | 999.8980 | 18.93321942 | 15.03 | 6.70 | 8.33 | 662071.15 | 1.7310 | 1.730942 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | unknown | unknown | unknown | 7/21 18:00:00 | Sensible | 11460.28 | 11353.34 | 1.0000 | 1.24905293 | 1.053662 | 21.69 | 15.44 | 0.00853908 | 43497.4 | 12.80 | 11.96 | 0.00850000 | 34322.2 | 0.32772304 | 6.70 | 15.03 | 8.33 | 0.000 | 11460.28 | 24.95 | 0.00700344 | 15.26 | 0.00000000 | 0.0000 | 21.11 | 0.00853908 | 21.11 | 0.00853908 | 53.9290 | 10594.89 | 0.00 | 11644.31 | 11644.31 | 1.24905293 | 21.69 | 15.59 | 0.00853908 | 43497.4 | 12.56 | 12.04 | 0.00853908 | 34174.9 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9427.277 | 9427.277 | 0.412822 | 0.00008247 | 269.402 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.053662 | 1.24905293 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 1.1101 | 1.132411 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9427.28 | 9427.28 | 1.0000 | 0.48937499 | 0.412822 | 21.11 | 14.26 | 0.00748172 | 40215.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.08246552 | 60.00 | 32.22 | 27.78 | 0.000 | 9427.28 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00748172 | 21.11 | 0.00748172 | 47.3373 | 9427.28 | 0.00 | 10162.52 | 10162.52 | 0.48937499 | 16.60 | 12.64 | 0.00748172 | 35622.5 | 36.98 | 19.88 | 0.00748172 | 56388.9 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 94085.773 | -999.000 | 8.744916 | 0.00269079 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6046 | 1004.8586 | 1.1854 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.744916 | 10.36656735 | 4197.9300 | 999.8980 | 18.93321942 | 15.03 | 6.70 | 8.33 | 662071.15 | 14.2108 | 14.210560 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 94085.77 | 94085.77 | 1.0000 | 10.36656735 | 8.744916 | 21.69 | 15.38 | 0.00848040 | 43348.6 | 12.80 | 11.94 | 0.00848040 | 34272.7 | 2.69051645 | 6.70 | 15.03 | 8.33 | 0.000 | 94085.77 | 27.40 | 0.00700714 | 16.15 | 0.00000000 | 0.0000 | 21.11 | 0.00848040 | 21.11 | 0.00848040 | 53.5625 | 87935.68 | 0.00 | 95619.94 | 95619.94 | 10.36656735 | 21.69 | 15.54 | 0.00848040 | 43348.6 | 12.65 | 12.02 | 0.00848040 | 34124.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 53045.545 | 53045.545 | 2.323034 | 0.00046407 | 1515.874 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.744916 | 10.36656735 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 6.2462 | 6.371868 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 53045.55 | 53045.55 | 1.0000 | 2.75381579 | 2.323034 | 21.11 | 14.29 | 0.00750985 | 40288.4 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.46401823 | 60.00 | 32.22 | 27.78 | 0.000 | 53045.55 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00750985 | 21.11 | 0.00750985 | 47.5093 | 53045.55 | 0.00 | 57183.87 | 57183.87 | 2.75381579 | 16.60 | 12.67 | 0.00750985 | 35693.8 | 36.98 | 19.90 | 0.00750985 | 56459.1 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 62467.092 | -999.000 | 5.463305 | 0.00178652 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0581 | 1004.8586 | 1.1854 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.463305 | 6.47641600 | 4197.9300 | 999.8980 | 18.93321942 | 15.03 | 6.70 | 8.33 | 662071.15 | 9.4351 | 9.434926 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | unknown | unknown | unknown | 7/21 21:20:00 | Sensible | 62467.09 | 59263.01 | 1.0000 | 6.47641600 | 5.463305 | 21.69 | 15.60 | 0.00872431 | 43967.5 | 12.80 | 11.96 | 0.00850000 | 34322.2 | 1.78633531 | 6.70 | 15.03 | 8.33 | 0.000 | 62467.09 | 21.08 | 0.00699765 | 13.80 | 0.00000000 | 0.0000 | 21.11 | 0.00872431 | 21.11 | 0.00872431 | 55.0838 | 54932.71 | 0.00 | 63458.03 | 63458.03 | 6.47641600 | 21.69 | 15.76 | 0.00872431 | 43967.5 | 12.10 | 12.03 | 0.00872431 | 34169.2 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 52941.232 | 52941.232 | 2.318466 | 0.00046315 | 1512.894 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.463305 | 6.47641600 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 6.2339 | 6.359337 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 52941.23 | 52941.23 | 1.0000 | 2.74840043 | 2.318466 | 21.11 | 14.29 | 0.00750882 | 40285.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.46310575 | 60.00 | 32.22 | 27.78 | 0.000 | 52941.23 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00750882 | 21.11 | 0.00750882 | 47.5029 | 52941.23 | 0.00 | 57071.41 | 57071.41 | 2.74840043 | 16.60 | 12.67 | 0.00750882 | 35691.2 | 36.98 | 19.90 | 0.00750882 | 56456.5 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12011.743 | -999.000 | 1.104922 | 0.00034353 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7103 | 1004.8586 | 1.1854 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.104922 | 1.30981774 | 4197.9300 | 999.8980 | 18.93321942 | 15.03 | 6.70 | 8.33 | 662071.15 | 1.8143 | 1.814234 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | unknown | unknown | unknown | 7/21 10:40:00 | Sensible | 12011.74 | 11904.84 | 1.0000 | 1.30981774 | 1.104922 | 21.69 | 15.43 | 0.00853726 | 43492.7 | 12.80 | 11.96 | 0.00850000 | 34322.2 | 0.34349288 | 6.70 | 15.03 | 8.33 | 0.000 | 12011.74 | 24.54 | 0.00700282 | 15.11 | 0.00000000 | 0.0000 | 21.11 | 0.00853726 | 21.11 | 0.00853726 | 53.9176 | 11110.32 | 0.00 | 12204.72 | 12204.72 | 1.30981774 | 21.69 | 15.59 | 0.00853726 | 43492.7 | 12.56 | 12.04 | 0.00853726 | 34174.9 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9421.160 | 9421.160 | 0.412554 | 0.00008242 | 269.228 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.104922 | 1.30981774 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 1.1094 | 1.131676 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9421.16 | 9421.16 | 1.0000 | 0.48905746 | 0.412554 | 21.11 | 14.26 | 0.00748137 | 40214.6 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.08241201 | 60.00 | 32.22 | 27.78 | 0.000 | 9421.16 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00748137 | 21.11 | 0.00748137 | 47.3351 | 9421.16 | 0.00 | 10155.92 | 10155.92 | 0.48905746 | 16.60 | 12.64 | 0.00748137 | 35621.7 | 36.98 | 19.88 | 0.00748137 | 56388.0 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10873.731 | -999.000 | 0.999244 | 0.00031098 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7170 | 1004.8586 | 1.1854 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.999244 | 1.18454324 | 4197.9300 | 999.8980 | 18.93321942 | 15.03 | 6.70 | 8.33 | 662071.15 | 1.6424 | 1.642350 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | unknown | unknown | 7/21 09:30:00 | Sensible | 10873.73 | 10767.71 | 1.0000 | 1.18454324 | 0.999244 | 21.69 | 15.44 | 0.00854085 | 43501.9 | 12.80 | 11.96 | 0.00850000 | 34322.2 | 0.31094979 | 6.70 | 15.03 | 8.33 | 0.000 | 10873.73 | 22.66 | 0.00700000 | 14.41 | 0.00000000 | 0.0000 | 21.11 | 0.00854085 | 21.11 | 0.00854085 | 53.9400 | 10047.70 | 0.00 | 11048.27 | 11048.27 | 1.18454324 | 21.69 | 15.59 | 0.00854085 | 43501.9 | 12.55 | 12.04 | 0.00854085 | 34174.9 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9413.735 | 9413.735 | 0.412229 | 0.00008236 | 269.015 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.999244 | 1.18454324 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 1.1085 | 1.130784 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9413.73 | 9413.73 | 1.0000 | 0.48867200 | 0.412229 | 21.11 | 14.26 | 0.00748102 | 40213.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.08234706 | 60.00 | 32.22 | 27.78 | 0.000 | 9413.73 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00748102 | 21.11 | 0.00748102 | 47.3329 | 9413.73 | 0.00 | 10147.92 | 10147.92 | 0.48867200 | 16.60 | 12.64 | 0.00748102 | 35620.8 | 36.98 | 19.88 | 0.00748102 | 56387.1 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17602.313 | 17602.313 | 0.711732 | 0.00015399 | 458.580 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 2.0727 | 2.114402 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 17602.31 | 17602.31 | 1.0000 | 0.84371543 | 0.711732 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.15397700 | 60.00 | 32.22 | 27.78 | 0.000 | 17602.31 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00756770 | 21.00 | 0.00756770 | 48.1961 | 13906.08 | 0.00 | 17690.82 | 17690.82 | 0.84371543 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 37.16 | 20.33 | 0.00800000 | 57902.5 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3318.110 | -999.000 | 0.305501 | 0.00009490 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7042 | 1004.8586 | 1.1854 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.305501 | 0.36215304 | 4197.9300 | 999.8980 | 18.93321942 | 15.03 | 6.70 | 8.33 | 662071.15 | 0.5012 | 0.501162 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | unknown | unknown | unknown | 7/21 17:30:00 | Sensible | 3318.11 | 3291.17 | 1.0000 | 0.36215304 | 0.305501 | 21.69 | 15.43 | 0.00853396 | 43484.4 | 12.80 | 11.96 | 0.00850000 | 34322.2 | 0.09488607 | 6.70 | 15.03 | 8.33 | 0.000 | 3318.11 | 25.46 | 0.00700420 | 15.45 | 0.00000000 | 0.0000 | 21.11 | 0.00853396 | 21.11 | 0.00853396 | 53.8971 | 3071.91 | 0.00 | 3371.46 | 3371.46 | 0.36215304 | 21.69 | 15.59 | 0.00853396 | 43484.4 | 12.57 | 12.04 | 0.00853396 | 34174.9 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2902.678 | 2902.678 | 0.127109 | 0.00002539 | 82.945 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.305501 | 0.36215304 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 0.3418 | 0.348672 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2902.68 | 2902.68 | 1.0000 | 0.15068018 | 0.127109 | 21.11 | 14.35 | 0.00757382 | 40449.6 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.02539130 | 60.00 | 32.22 | 27.78 | 0.000 | 2902.68 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00757382 | 21.11 | 0.00757382 | 47.9128 | 2902.68 | 0.00 | 3129.06 | 3129.06 | 0.15068018 | 16.60 | 12.73 | 0.00757382 | 35855.7 | 36.98 | 19.95 | 0.00757382 | 56622.0 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2955.960 | -999.000 | 0.271862 | 0.00008454 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7115 | 1004.8586 | 1.1854 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.271862 | 0.32227561 | 4197.9300 | 999.8980 | 18.93321942 | 15.03 | 6.70 | 8.33 | 662071.15 | 0.4465 | 0.446463 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | unknown | unknown | unknown | 7/21 18:00:00 | Sensible | 2955.96 | 2929.21 | 1.0000 | 0.32227561 | 0.271862 | 21.69 | 15.43 | 0.00853789 | 43494.3 | 12.80 | 11.96 | 0.00850000 | 34322.2 | 0.08452987 | 6.70 | 15.03 | 8.33 | 0.000 | 2955.96 | 24.95 | 0.00700344 | 15.26 | 0.00000000 | 0.0000 | 21.11 | 0.00853789 | 21.11 | 0.00853789 | 53.9216 | 2733.65 | 0.00 | 3003.44 | 3003.44 | 0.32227561 | 21.69 | 15.59 | 0.00853789 | 43494.3 | 12.56 | 12.04 | 0.00853789 | 34174.9 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2900.223 | 2900.223 | 0.127002 | 0.00002537 | 82.875 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.271862 | 0.32227561 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 0.3415 | 0.348377 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2900.22 | 2900.22 | 1.0000 | 0.15055276 | 0.127002 | 21.11 | 14.35 | 0.00757351 | 40448.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.02536983 | 60.00 | 32.22 | 27.78 | 0.000 | 2900.22 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00757351 | 21.11 | 0.00757351 | 47.9108 | 2900.22 | 0.00 | 3126.42 | 3126.42 | 0.15055276 | 16.60 | 12.73 | 0.00757351 | 35854.9 | 36.98 | 19.95 | 0.00757351 | 56621.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20154.488 | -999.000 | 1.837050 | 0.00057641 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7722 | 1004.8586 | 1.1854 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.837050 | 2.17771181 | 4197.9300 | 999.8980 | 18.93321942 | 15.03 | 6.70 | 8.33 | 662071.15 | 3.0442 | 3.044101 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 20154.49 | 19817.50 | 1.0000 | 2.17771181 | 1.837050 | 21.69 | 15.46 | 0.00857055 | 43577.1 | 12.80 | 11.96 | 0.00850000 | 34322.2 | 0.57634624 | 6.70 | 15.03 | 8.33 | 0.000 | 20154.49 | 27.40 | 0.00700714 | 16.15 | 0.00000000 | 0.0000 | 21.11 | 0.00857055 | 21.11 | 0.00857055 | 54.1258 | 18471.59 | 0.00 | 20478.89 | 20478.89 | 2.17771181 | 21.69 | 15.62 | 0.00857055 | 43577.1 | 12.48 | 12.04 | 0.00857055 | 34173.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13914.301 | 13914.301 | 0.609327 | 0.00012173 | 397.605 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.837050 | 2.17771181 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 1.6384 | 1.671395 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 13914.30 | 13914.30 | 1.0000 | 0.72231993 | 0.609327 | 21.11 | 14.36 | 0.00758975 | 40490.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.12171596 | 60.00 | 32.22 | 27.78 | 0.000 | 13914.30 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00758975 | 21.11 | 0.00758975 | 48.0110 | 13914.30 | 0.00 | 14999.63 | 14999.63 | 0.72231993 | 16.60 | 12.75 | 0.00758975 | 35896.1 | 36.98 | 19.96 | 0.00758975 | 56662.0 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18919.189 | 18919.189 | 1.781414 | 0.00016551 | 417.188 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 2.2278 | 2.272586 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 18919.19 | 18919.19 | 1.0000 | 2.11175804 | 1.781414 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.16549643 | 60.00 | 32.22 | 27.78 | 0.000 | 18919.19 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00768122 | 21.00 | 0.00768122 | 48.9117 | 9666.90 | 0.00 | 19022.28 | 19022.28 | 2.11175804 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.43 | 16.47 | 0.00800000 | 45942.5 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19083.827 | 19083.827 | 1.780805 | 0.00016695 | 421.250 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 2.2471 | 2.292363 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 19083.83 | 19083.83 | 1.0000 | 2.11103580 | 1.780805 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.16693662 | 60.00 | 32.22 | 27.78 | 0.000 | 19083.83 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00768645 | 21.00 | 0.00768645 | 48.9445 | 9834.61 | 0.00 | 19187.77 | 19187.77 | 2.11103580 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.51 | 16.50 | 0.00800000 | 46024.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7752.659 | 7752.659 | 0.550083 | 0.00006782 | 177.570 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 0.9129 | 0.931255 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 7752.66 | 7752.66 | 1.0000 | 0.65209011 | 0.550083 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.06781672 | 60.00 | 32.22 | 27.78 | 0.000 | 7752.66 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.79 | 0.00723894 | 21.00 | 0.00723894 | 46.1346 | 4899.56 | 0.00 | 7794.30 | 7794.30 | 0.65209011 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.32 | 17.47 | 0.00800000 | 48887.5 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12508.548 | 12508.548 | 0.444154 | 0.00010943 | 341.380 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 1.4729 | 1.502535 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 12508.55 | 12508.55 | 1.0000 | 0.52651719 | 0.444154 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.10941907 | 60.00 | 32.22 | 27.78 | 0.000 | 12508.55 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00773351 | 21.00 | 0.00773351 | 49.2397 | 10201.34 | 0.00 | 12570.58 | 12570.58 | 0.52651719 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60809.7 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 393686.749 | -999.000 | 22.398229 | 0.01125939 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6899 | 1004.8586 | 1.1854 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.398229 | 26.55174082 | 4197.9300 | 999.8980 | 18.93321942 | 15.03 | 6.70 | 8.33 | 662071.15 | 59.4629 | 59.462907 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | Sensible | 393686.75 | 391856.94 | 1.0000 | 26.55174082 | 22.398229 | 25.41 | 16.74 | 0.00852627 | 47259.3 | 10.95 | 10.95 | 0.00850000 | 32432.2 | 11.25824261 | 6.70 | 15.03 | 8.33 | 50186.337 | 343500.41 | 27.40 | 0.00700714 | 16.15 | 9.32920000 | 41.6515 | 23.99 | 0.00961069 | 23.99 | 0.00958523 | 50.7307 | 303286.48 | 0.00 | 398973.93 | 380437.75 | 26.55174082 | 25.41 | 16.91 | 0.00852627 | 47259.3 | 11.37 | 11.25 | 0.00824947 | 32233.0 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 469047.494 | 469047.494 | 6.719469 | 0.00410343 | 6161.674 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.398229 | 26.55174082 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 55.2308 | 56.342309 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 469047.49 | 469047.49 | 1.0000 | 7.96552225 | 6.719469 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 4.10301350 | 60.00 | 32.22 | 27.78 | 0.000 | 469047.49 | -41.90 | 0.00006450 | -41.90 | 9.32920000 | 138.8384 | 20.98 | 0.00759042 | 21.00 | 0.00754875 | 48.0781 | 98659.87 | 0.00 | 300789.46 | 300789.46 | 7.96552225 | 2.80 | -4.37 | 0.00006450 | 2975.2 | 40.38 | 14.79 | 0.00006450 | 40736.6 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 38332.296 | -999.000 | 2.051317 | 0.00109630 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8659 | 1004.8586 | 1.1854 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.43162656 | 4197.9300 | 999.8980 | 18.93321942 | 15.03 | 6.70 | 8.33 | 662071.15 | 5.7898 | 5.789755 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 38332.30 | 38332.30 | 1.0000 | 2.43171206 | 2.051317 | 27.40 | 16.15 | 0.00700714 | 45414.0 | 11.91 | 10.04 | 0.00700714 | 29650.5 | 1.09618699 | 6.70 | 15.03 | 8.33 | 2195.006 | 36137.29 | 27.40 | 0.00700714 | 16.15 | 2.05124512 | 99.9965 | 21.11 | 0.00857181 | 21.11 | 0.00857689 | 54.1644 | 192161.44 | 0.00 | 38875.86 | 38875.86 | 2.43171206 | 27.40 | 16.31 | 0.00700714 | 45414.0 | 11.69 | 10.08 | 0.00700714 | 29426.9 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 42957.200 | 42957.200 | 0.615395 | 0.00037581 | 564.310 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.43162656 | 4197.9300 | 999.8980 | 7.28229564 | 54.44 | 82.22 | 27.78 | 849250.36 | 5.0582 | 5.160049 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 42957.20 | 42957.20 | 1.0000 | 0.72951362 | 0.615395 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 0.37576999 | 60.00 | 32.22 | 27.78 | 0.000 | 42957.20 | -41.90 | 0.00006450 | -41.90 | 2.05124512 | 333.3216 | 21.11 | 0.00751206 | 21.11 | 0.00751009 | 47.5109 | 163400.85 | 0.00 | 27547.47 | 27547.47 | 0.72951362 | 2.80 | -4.37 | 0.00006450 | 2975.2 | 40.38 | 14.79 | 0.00006450 | 40736.6 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 22.40 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 249.33 | 8718.67 | 249.33 |
RETAIL_1_FLR_1 | 4642.17 | 6824.67 | 3615.50 |
RETAIL_2_FLR_1 | 1744.50 | 8376.33 | 1664.33 |
MECH_FLR_1 | 3140.83 | 7490.83 | 3121.67 |
STORAGE_FLR_1 | 3774.33 | 8760.00 | 3774.33 |
LAUNDRY_FLR_1 | 8645.83 | 2622.17 | 2622.17 |
CAFE_FLR_1 | 3251.17 | 7408.33 | 2507.67 |
LOBBY_FLR_1 | 1516.83 | 7568.00 | 1121.83 |
ROOM_1_FLR_3 | 4442.00 | 8509.00 | 4432.33 |
ROOM_2_FLR_3 | 5069.00 | 8317.33 | 4804.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4205.33 | 8722.67 | 4204.00 |
ROOM_5_FLR_3 | 4214.17 | 8322.33 | 4184.17 |
ROOM_6_FLR_3 | 4699.50 | 8245.33 | 4556.17 |
CORRIDOR_FLR_3 | 3228.67 | 8654.17 | 3228.67 |
ROOM_1_FLR_6 | 4748.00 | 8455.83 | 4724.00 |
ROOM_2_FLR_6 | 5370.33 | 8304.33 | 5109.17 |
ROOM_3_MULT9_FLR_6 | 4023.67 | 8247.17 | 3925.67 |
BANQUET_FLR_6 | 1467.50 | 7491.33 | 857.17 |
DINING_FLR_6 | 1363.33 | 6852.67 | 355.17 |
KITCHEN_FLR_6 | 8496.33 | 5607.17 | 5571.17 |
CORRIDOR_FLR_6 | 3976.50 | 7016.67 | 3613.17 |
Facility | 8760.00 | 8760.00 | 7936.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 86.17 | 0.00 | 86.17 | 0.00 |
RETAIL_2_FLR_1 | 37.67 | 0.00 | 37.67 | 0.00 |
MECH_FLR_1 | 32.50 | 0.00 | 32.50 | 0.00 |
STORAGE_FLR_1 | 81.67 | 0.00 | 81.67 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 52.67 | 0.00 | 52.67 | 0.00 |
LOBBY_FLR_1 | 25.50 | 0.00 | 25.50 | 0.00 |
ROOM_1_FLR_3 | 54.00 | 2.50 | 54.00 | 2.50 |
ROOM_2_FLR_3 | 74.17 | 6.83 | 74.17 | 6.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 176.00 | 19.17 | 176.00 | 19.17 |
ROOM_5_FLR_3 | 62.33 | 4.33 | 62.33 | 4.33 |
ROOM_6_FLR_3 | 77.83 | 14.83 | 77.83 | 14.83 |
CORRIDOR_FLR_3 | 47.83 | 0.00 | 47.83 | 0.00 |
ROOM_1_FLR_6 | 74.67 | 3.33 | 74.67 | 3.33 |
ROOM_2_FLR_6 | 102.83 | 11.00 | 102.83 | 11.00 |
ROOM_3_MULT9_FLR_6 | 29.50 | 2.33 | 29.50 | 2.33 |
BANQUET_FLR_6 | 17.67 | 0.00 | 17.67 | 0.00 |
DINING_FLR_6 | 7.50 | 0.00 | 7.50 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 74.50 | 0.00 | 74.50 | 0.00 |
Facility | 213.50 | 37.17 | 213.50 | 37.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.686 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.362 | 0.145 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.152 | 0.048 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.095 | 0.054 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.593 | 0.054 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 14.469 | 0.156 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 3.510 | 0.114 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.417 | 0.047 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.343 | 0.188 | 0.000 | 0.031 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.343 | 0.188 | 0.000 | 0.027 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.390 | 0.083 | 0.000 | 0.055 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.343 | 0.188 | 0.000 | 0.031 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.343 | 0.188 | 0.000 | 0.035 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.386 | 0.023 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.343 | 0.188 | 0.000 | 0.037 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.343 | 0.188 | 0.000 | 0.028 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.390 | 0.153 | 0.000 | 0.058 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.551 | 0.054 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.564 | 0.054 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 14.504 | 0.157 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.451 | 0.038 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.552 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 0.941 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.939 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.006 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.479 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 2.978 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 2.830 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.152 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.313 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 3.685 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 3.708 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 4.148 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.315 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.79 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.56 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.09 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.25 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 28424984.44 | 0.00 | 28424984.44 | 0.00 | 28424984.44 | 26946214.98 | 6170.48 | 140.13 | 2449.39 | 0.00 |
RETAIL_1_FLR_1 | 3108025.73 | 0.00 | 3108025.73 | 331381.90 | 3439407.63 | 2498216.28 | 5621.61 | 103.04 | 3035.35 | 0.00 |
RETAIL_2_FLR_1 | 3048110.08 | 0.00 | 3048110.08 | 127913.83 | 3176023.92 | 2892943.94 | 6198.02 | 124.21 | 2437.78 | 0.00 |
MECH_FLR_1 | 529963.06 | 0.00 | 529963.06 | 302312.31 | 832275.37 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1918650.33 | 0.00 | 1918650.33 | 174417.55 | 2093067.88 | 1821682.01 | 6197.21 | 124.59 | 2438.19 | 0.00 |
LAUNDRY_FLR_1 | 38236832.75 | 0.00 | 38236832.75 | 412792.02 | 38649624.76 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 22572973.55 | 0.00 | 22572973.55 | 732538.45 | 23305512.00 | 21330615.53 | 6154.79 | 129.93 | 2475.28 | 0.00 |
LOBBY_FLR_1 | 63045529.46 | 0.00 | 63045529.46 | 2093029.67 | 65138559.13 | 59728886.00 | 6200.29 | 121.48 | 2438.23 | 0.00 |
ROOM_1_FLR_3 | 1406076.84 | 32123.72 | 1438200.56 | 192345.67 | 1630546.23 | 1946875.62 | 2433.33 | 5953.83 | 372.83 | 0.00 |
ROOM_2_FLR_3 | 1405912.09 | 26939.40 | 1432851.49 | 192330.99 | 1625182.49 | 1946647.51 | 2433.33 | 6063.58 | 263.08 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 53666.60 | 1153578.57 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19070354.14 | 35105.57 | 19105459.70 | 53681.27 | 19159140.98 | 26405105.73 | 2433.33 | 5962.04 | 364.63 | 0.00 |
ROOM_5_FLR_3 | 1406076.84 | 32130.98 | 1438207.82 | 192345.67 | 1630553.48 | 1946875.62 | 2433.33 | 5953.86 | 372.81 | 0.00 |
ROOM_6_FLR_3 | 1405912.09 | 35735.01 | 1441647.10 | 192330.99 | 1633978.10 | 1946647.51 | 2433.33 | 5959.00 | 367.67 | 0.00 |
CORRIDOR_FLR_3 | 15761920.08 | 0.00 | 15761920.08 | 232584.61 | 15994504.69 | 14972100.18 | 6200.71 | 122.48 | 2436.81 | 0.00 |
ROOM_1_FLR_6 | 351519.21 | 37610.25 | 389129.45 | 192388.03 | 581517.48 | 486718.90 | 2322.96 | 5956.00 | 481.04 | 0.00 |
ROOM_2_FLR_6 | 351478.02 | 28370.50 | 379848.52 | 192373.35 | 572221.87 | 486661.88 | 2353.17 | 6091.18 | 315.65 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2258331.41 | 37587.69 | 2295919.11 | 98432.45 | 2394351.55 | 3126920.42 | 2433.33 | 5953.50 | 373.17 | 0.00 |
BANQUET_FLR_6 | 39504601.53 | 0.00 | 39504601.53 | 469763.21 | 39974364.75 | 37458366.31 | 6197.49 | 124.37 | 2438.14 | 0.00 |
DINING_FLR_6 | 39580367.41 | 0.00 | 39580367.41 | 469763.21 | 40050130.62 | 37458366.31 | 6194.21 | 121.73 | 2444.06 | 0.00 |
KITCHEN_FLR_6 | 38947420.13 | 0.00 | 38947420.13 | 420546.99 | 39367967.12 | 11584760.86 | 39.81 | 54.33 | 8665.86 | 0.00 |
CORRIDOR_FLR_6 | 4859397.73 | 0.00 | 4859397.73 | 411607.93 | 5271005.65 | 3961413.96 | 5544.85 | 95.69 | 3119.46 | 0.00 |
Total Facility | 0.19E+10 | 3580009.69 | 0.19E+10 | 19382910.50 | 0.19E+10 | 0.43E+10 | 8760.00 | 6491.29 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9014 | 0.0000 | 0.9014 | 0.0000 | 0.9014 | 0.8545 | 6170.48 | 140.13 | 2449.39 |
RETAIL_1_FLR_1 | 0.0986 | 0.0000 | 0.0986 | 0.0105 | 0.1091 | 0.0792 | 5621.61 | 103.04 | 3035.35 |
RETAIL_2_FLR_1 | 0.0967 | 0.0000 | 0.0967 | 0.0041 | 0.1007 | 0.0917 | 6198.02 | 124.21 | 2437.78 |
MECH_FLR_1 | 0.0168 | 0.0000 | 0.0168 | 0.0096 | 0.0264 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0608 | 0.0000 | 0.0608 | 0.0055 | 0.0664 | 0.0578 | 6197.21 | 124.59 | 2438.19 |
LAUNDRY_FLR_1 | 1.2125 | 0.0000 | 1.2125 | 0.0131 | 1.2256 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7158 | 0.0000 | 0.7158 | 0.0232 | 0.7390 | 0.6764 | 6154.79 | 129.93 | 2475.28 |
LOBBY_FLR_1 | 1.9992 | 0.0000 | 1.9992 | 0.0664 | 2.0655 | 1.8940 | 6200.29 | 121.48 | 2438.23 |
ROOM_1_FLR_3 | 0.0446 | 0.0010 | 0.0456 | 0.0061 | 0.0517 | 0.0617 | 2433.33 | 5953.83 | 372.83 |
ROOM_2_FLR_3 | 0.0446 | 0.0009 | 0.0454 | 0.0061 | 0.0515 | 0.0617 | 2433.33 | 6063.58 | 263.08 |
ROOM_4_MULT19_FLR_3 | 0.6047 | 0.0011 | 0.6058 | 0.0017 | 0.6075 | 0.8373 | 2433.33 | 5962.04 | 364.63 |
ROOM_5_FLR_3 | 0.0446 | 0.0010 | 0.0456 | 0.0061 | 0.0517 | 0.0617 | 2433.33 | 5953.86 | 372.81 |
ROOM_6_FLR_3 | 0.0446 | 0.0011 | 0.0457 | 0.0061 | 0.0518 | 0.0617 | 2433.33 | 5959.00 | 367.67 |
CORRIDOR_FLR_3 | 0.4998 | 0.0000 | 0.4998 | 0.0074 | 0.5072 | 0.4748 | 6200.71 | 122.48 | 2436.81 |
ROOM_1_FLR_6 | 0.0111 | 0.0012 | 0.0123 | 0.0061 | 0.0184 | 0.0154 | 2322.96 | 5956.00 | 481.04 |
ROOM_2_FLR_6 | 0.0111 | 0.0009 | 0.0120 | 0.0061 | 0.0181 | 0.0154 | 2353.17 | 6091.18 | 315.65 |
ROOM_3_MULT9_FLR_6 | 0.0716 | 0.0012 | 0.0728 | 0.0031 | 0.0759 | 0.0992 | 2433.33 | 5953.50 | 373.17 |
BANQUET_FLR_6 | 1.2527 | 0.0000 | 1.2527 | 0.0149 | 1.2676 | 1.1878 | 6197.49 | 124.37 | 2438.14 |
DINING_FLR_6 | 1.2551 | 0.0000 | 1.2551 | 0.0149 | 1.2700 | 1.1878 | 6194.21 | 121.73 | 2444.06 |
KITCHEN_FLR_6 | 1.2350 | 0.0000 | 1.2350 | 0.0133 | 1.2484 | 0.3674 | 39.81 | 54.33 | 8665.86 |
CORRIDOR_FLR_6 | 0.1541 | 0.0000 | 0.1541 | 0.0131 | 0.1671 | 0.1256 | 5544.85 | 95.69 | 3119.46 |
Total Facility | 58.3364 | 0.1135 | 58.4499 | 0.4853 | 58.9352 | 73.9670 | 8760.00 | 6491.29 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.42E+09 | 0.00 | 0.42E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 40409237.68 | 265603.13 | 40674840.81 | 64690340.46 | 8756.31 | 3.52 | 0.17 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 13.3477 | 0.0000 | 13.3477 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.2814 | 0.0084 | 1.2898 | 2.0513 | 8756.31 | 3.52 | 0.17 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 8.00 | 4054.30 | 0.00 | 0.00 | 0.00 | 4697.70 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6691.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 15.0260 | 15.5699 | 0.0000 | 0.0000 | 0.0000 | 11.4328 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6776 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1340 |
Defaulted Fields | 1181 |
Fields with Defaults | 4002 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4242.52 | 55300.31 | 27-MAY-03:20 | 301443.71 | 29-JUN-19:10 |
Electricity:Building | 2200.64 | 28601.08 | 10-JUN-05:00 | 132137.22 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 266.04 | 3144.96 | 02-JAN-02:10 | 19685.67 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2193.54 | 28459.93 | 10-JUN-05:00 | 131895.89 | 02-JAN-20:10 |
InteriorLights:Electricity | 545.09 | 4566.26 | 10-JUN-05:00 | 45764.37 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 122.93 | 1117.06 | 02-JAN-02:10 | 10053.14 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 545.09 | 4566.26 | 10-JUN-05:00 | 45764.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 545.09 | 4566.26 | 10-JUN-05:00 | 45764.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 122.93 | 1117.06 | 02-JAN-02:10 | 10053.14 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 545.09 | 4566.26 | 10-JUN-05:00 | 45764.37 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.45 | 201.26 | 02-JAN-02:10 | 1197.92 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.05 | 233.06 | 02-JAN-02:10 | 1387.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.91 | 71.95 | 02-JAN-02:10 | 430.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.31 | 20.97 | 02-JAN-02:10 | 188.71 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.31 | 20.97 | 02-JAN-02:10 | 188.71 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 27.15 | 241.68 | 06-MAY-05:00 | 2538.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.81 | 38.46 | 06-MAY-05:00 | 1573.46 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.81 | 38.46 | 06-MAY-05:00 | 1573.46 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 241.14 | 2874.33 | 10-JUN-05:00 | 18013.24 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 92.14 | 762.92 | 10-JUN-05:00 | 7984.04 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 92.14 | 762.92 | 10-JUN-05:00 | 7984.04 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 253.77 | 3619.58 | 02-JAN-10:10 | 20179.99 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 253.84 | 3620.57 | 02-JAN-10:10 | 20185.51 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 3.85 | 55.20 | 01-JAN-02:10 | 290.10 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 3.85 | 55.19 | 01-JAN-02:10 | 290.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 30.06 | 428.75 | 02-JAN-10:10 | 2390.39 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 204.03 | 2433.51 | 06-MAY-04:50 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.17 | 184.21 | 06-MAY-04:50 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.17 | 184.21 | 06-MAY-04:50 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 204.03 | 2433.51 | 06-MAY-04:50 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.17 | 184.21 | 06-MAY-04:50 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.17 | 184.21 | 06-MAY-04:50 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 43.74 | 732.79 | 12-JAN-23:30 | 2786.65 | 16-JUL-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 507.35 | 2112.54 | 15-APR-01:10 | 123275.95 | 29-JUL-15:30 |
LowTempRefrigeration:Refrigeration:Electricity | 15.79 | 0.00 | 01-JAN-11:10 | 1309.03 | 22-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 20.86 | 598.29 | 12-JAN-05:00 | 714.07 | 25-JUL-13:10 |
Fans:Electricity | 560.67 | 11931.39 | 19-SEP-03:00 | 31412.10 | 22-JUN-22:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 723.14 | 13832.27 | 19-SEP-03:00 | 39377.03 | 13-JAN-19:20 |
ExteriorEquipment:Electricity | 640.54 | 9443.81 | 17-JUN-03:00 | 39153.73 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.51 | 378.98 | 10-JUN-05:00 | 1274.03 | 02-JAN-08:00 |
ElectricityPurchased:Facility | 4242.52 | 55300.31 | 27-MAY-03:20 | 301443.71 | 29-JUN-19:10 |
ElectricityPurchased:Plant | 4242.52 | 55300.31 | 27-MAY-03:20 | 301443.71 | 29-JUN-19:10 |
Cogeneration:ElectricityPurchased | 4242.52 | 55300.31 | 27-MAY-03:20 | 301443.71 | 29-JUN-19:10 |
General:Cogeneration:ElectricityPurchased | 4242.52 | 55300.31 | 27-MAY-03:20 | 301443.71 | 29-JUN-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4242.52 | 55300.31 | 27-MAY-03:20 | 301443.71 | 29-JUN-19:10 |
ElectricityNet:Plant | 4242.52 | 55300.31 | 27-MAY-03:20 | 301443.71 | 29-JUN-19:10 |
Cogeneration:ElectricityNet | 4242.52 | 55300.31 | 27-MAY-03:20 | 301443.71 | 29-JUN-19:10 |
General:Cogeneration:ElectricityNet | 4242.52 | 55300.31 | 27-MAY-03:20 | 301443.71 | 29-JUN-19:10 |
General:Fans:Electricity | 560.67 | 11931.39 | 19-SEP-03:00 | 31412.10 | 22-JUN-22:00 |
ExteriorLights:Electricity | 192.37 | 0.00 | 01-JAN-11:20 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 192.37 | 0.00 | 01-JAN-11:20 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 140.95 | 0.00 | 07-FEB-11:00 | 8265.52 | 01-JAN-00:10 |
General:HeatRecovery:Electricity | 140.95 | 0.00 | 07-FEB-11:00 | 8265.52 | 01-JAN-00:10 |
WaterSystems:Electricity | 90.74 | 1086.56 | 06-APR-01:00 | 4738.77 | 26-JAN-19:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 06-APR-01:00 | 4738.77 | 26-JAN-19:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 321.96 | 0.00 | 01-JAN-00:20 | 114978.03 | 29-JUL-15:30 |
General:Cooling:Electricity | 321.96 | 0.00 | 01-JAN-00:20 | 114978.03 | 29-JUL-15:30 |
Pumps:Electricity | 57.99 | 47.91 | 05-JUL-14:10 | 4641.78 | 21-JUL-15:20 |
General:Pumps:Electricity | 57.99 | 47.91 | 05-JUL-14:10 | 4641.78 | 21-JUL-15:20 |
WIRED_LTG_ELECTRICITY | 19.19 | 0.00 | 01-JAN-00:10 | 1610.91 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 9032.66 | 29270.80 | 08-MAY-01:10 | 1136619.19 | 12-JAN-21:50 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 7243.82 | 15908.90 | 18-JUL-10:00 | 1061495.44 | 12-JAN-21:50 |
WaterSystems:NaturalGas | 3628.21 | 15908.90 | 21-MAR-15:20 | 312595.80 | 03-MAR-21:30 |
Water Heater:WaterSystems:NaturalGas | 3628.21 | 15908.90 | 21-MAR-15:20 | 312595.80 | 03-MAR-21:30 |
Heating:NaturalGas | 3615.61 | 0.00 | 17-APR-20:10 | 783717.68 | 12-JAN-10:20 |
Boiler:Heating:NaturalGas | 3615.61 | 0.00 | 17-APR-20:10 | 783717.68 | 12-JAN-10:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 985.26 | 0.00 | 01-JAN-00:20 | 399956.06 | 29-JUL-18:10 |
PlantLoopCoolingDemand:HVAC | 985.26 | 0.00 | 01-JAN-00:20 | 399956.06 | 29-JUL-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 985.26 | 0.00 | 01-JAN-00:20 | 399956.06 | 29-JUL-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 09-MAY-20:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 09-MAY-20:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 09-MAY-20:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 09-MAY-20:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 09-MAY-20:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 09-MAY-20:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 18321.89 | 133633.26 | 06-OCT-13:50 | 1695593.12 | 29-JUL-18:10 |
EnergyTransfer:Building | 4932.38 | 76706.45 | 05-MAR-15:00 | 328183.58 | 12-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 662.16 | 7739.05 | 26-FEB-04:00 | 36204.52 | 22-JUL-10:50 |
Refrigeration:EnergyTransfer | 180.12 | 3939.28 | 12-JAN-03:20 | 10327.07 | 25-JUL-07:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.06 | 1969.64 | 12-JAN-03:20 | 5163.54 | 25-JUL-07:20 |
General:Refrigeration:EnergyTransfer | 90.06 | 1969.64 | 12-JAN-03:20 | 5163.54 | 25-JUL-07:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.06 | 1969.64 | 12-JAN-03:20 | 5163.54 | 25-JUL-07:20 |
EnergyTransfer:Plant | 6233.72 | 22232.52 | 20-SEP-15:10 | 961136.78 | 29-JUL-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.52 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.54 | 1733.07 | 12-JAN-05:00 | 2541.24 | 25-JUL-13:10 |
EnergyTransfer:Zone:BASEMENT | 348.23 | 6035.70 | 01-MAR-15:00 | 18811.57 | 12-JAN-21:00 |
Heating:EnergyTransfer | 783.48 | 0.00 | 18-MAR-17:10 | 144975.79 | 13-JAN-16:30 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 783.48 | 0.00 | 18-MAR-17:10 | 144975.79 | 13-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4058.85 | 42066.56 | 13-JAN-15:00 | 325486.44 | 11-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 348.23 | 6035.70 | 01-MAR-15:00 | 18811.57 | 12-JAN-21:00 |
General:Cooling:EnergyTransfer | 4058.85 | 42066.56 | 13-JAN-15:00 | 325486.44 | 11-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 348.23 | 6035.70 | 01-MAR-15:00 | 18811.57 | 12-JAN-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 37.40 | 0.00 | 06-APR-06:30 | 4950.54 | 25-AUG-13:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 13.14 | 0.00 | 23-JAN-12:00 | 2589.64 | 13-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 13.14 | 0.00 | 23-JAN-12:00 | 2589.64 | 13-JAN-16:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 24.26 | 0.00 | 01-JAN-00:10 | 4950.54 | 25-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 24.26 | 0.00 | 01-JAN-00:10 | 4950.54 | 25-AUG-13:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 28.86 | 0.00 | 04-DEC-15:50 | 1727.17 | 21-JUN-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 439.82 | 13-JAN-16:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 439.82 | 13-JAN-16:00 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 28.82 | 0.00 | 01-JAN-14:20 | 1727.17 | 21-JUN-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 28.82 | 0.00 | 01-JAN-14:20 | 1727.17 | 21-JUN-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 9.62 | 0.03 | 08-FEB-05:50 | 1335.82 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 4.92 | 0.00 | 02-JAN-21:00 | 1277.24 | 13-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 4.92 | 0.00 | 02-JAN-21:00 | 1277.24 | 13-JAN-16:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 4.70 | 0.00 | 01-JAN-00:10 | 1335.82 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 4.70 | 0.00 | 01-JAN-00:10 | 1335.82 | 21-JUL-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 16.18 | 0.30 | 05-APR-14:50 | 986.47 | 13-JAN-16:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 6.18 | 0.00 | 07-FEB-20:20 | 986.47 | 13-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 6.18 | 0.00 | 07-FEB-20:20 | 986.47 | 13-JAN-16:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 10.00 | 0.00 | 01-JAN-00:10 | 971.23 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 10.00 | 0.00 | 01-JAN-00:10 | 971.23 | 23-JUL-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 569.14 | 6793.92 | 13-JAN-05:00 | 39145.83 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 569.14 | 6793.92 | 13-JAN-05:00 | 39145.83 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 569.14 | 6793.92 | 13-JAN-05:00 | 39145.83 | 21-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 200.76 | 0.68 | 17-NOV-07:10 | 15671.27 | 25-AUG-14:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 3.04 | 0.00 | 01-JAN-00:10 | 3954.95 | 13-JAN-15:00 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 3.04 | 0.00 | 01-JAN-00:10 | 3954.95 | 13-JAN-15:00 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 197.72 | 0.00 | 01-JAN-11:10 | 15671.27 | 25-AUG-14:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 197.72 | 0.00 | 01-JAN-11:10 | 15671.27 | 25-AUG-14:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 684.09 | 2.35 | 03-DEC-15:10 | 37197.75 | 11-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 4274.50 | 13-JAN-14:40 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 4274.50 | 13-JAN-14:40 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 684.04 | 0.00 | 13-JAN-10:20 | 37197.75 | 11-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 684.04 | 0.00 | 13-JAN-10:20 | 37197.75 | 11-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 86.11 | 0.00 | 02-JAN-08:00 | 11755.18 | 16-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 56.33 | 0.00 | 02-JAN-08:00 | 8680.74 | 13-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 56.33 | 0.00 | 02-JAN-08:00 | 8680.74 | 13-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 29.78 | 0.00 | 01-JAN-00:10 | 11755.18 | 16-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 29.78 | 0.00 | 01-JAN-00:10 | 11755.18 | 16-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 80.92 | 0.00 | 02-JAN-08:00 | 12246.54 | 06-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 61.92 | 0.00 | 02-JAN-08:00 | 8470.83 | 13-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 61.92 | 0.00 | 02-JAN-08:00 | 8470.83 | 13-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 19.00 | 0.00 | 01-JAN-00:10 | 12246.54 | 06-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 19.00 | 0.00 | 01-JAN-00:10 | 12246.54 | 06-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 356.69 | 0.00 | 22-JAN-08:20 | 61051.15 | 25-AUG-13:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 142.47 | 0.00 | 22-JAN-08:20 | 35054.39 | 12-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 142.47 | 0.00 | 22-JAN-08:20 | 35054.39 | 12-JAN-04:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 214.22 | 0.00 | 01-JAN-00:10 | 61051.15 | 25-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 214.22 | 0.00 | 01-JAN-00:10 | 61051.15 | 25-AUG-13:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 406.82 | 0.00 | 01-JAN-08:00 | 66733.18 | 10-JUL-22:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 212.63 | 0.00 | 01-JAN-08:00 | 45213.46 | 13-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 212.63 | 0.00 | 01-JAN-08:00 | 45213.46 | 13-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 194.19 | 0.00 | 01-JAN-00:10 | 66733.18 | 10-JUL-22:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 194.19 | 0.00 | 01-JAN-00:10 | 66733.18 | 10-JUL-22:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 89.53 | 0.00 | 02-JAN-08:00 | 12006.16 | 22-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 54.03 | 0.00 | 02-JAN-08:00 | 8546.59 | 13-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 54.03 | 0.00 | 02-JAN-08:00 | 8546.59 | 13-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 35.50 | 0.00 | 01-JAN-00:10 | 12006.16 | 22-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 35.50 | 0.00 | 01-JAN-00:10 | 12006.16 | 22-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 84.08 | 0.00 | 02-JAN-08:00 | 12732.49 | 11-JUL-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 59.17 | 0.00 | 02-JAN-08:00 | 8342.86 | 13-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 59.17 | 0.00 | 02-JAN-08:00 | 8342.86 | 13-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 24.91 | 0.00 | 01-JAN-00:10 | 12732.49 | 11-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 24.91 | 0.00 | 01-JAN-00:10 | 12732.49 | 11-JUL-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 137.04 | 0.30 | 12-FEB-11:40 | 9206.10 | 22-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 30.21 | 0.00 | 04-JAN-22:10 | 7583.94 | 13-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 30.21 | 0.00 | 04-JAN-22:10 | 7583.94 | 13-JAN-16:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 106.82 | 0.00 | 01-JAN-00:10 | 9206.10 | 22-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 106.82 | 0.00 | 01-JAN-00:10 | 9206.10 | 22-JUL-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 26.44 | 0.00 | 19-JAN-08:00 | 3137.05 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.33 | 0.00 | 19-JAN-08:00 | 2593.88 | 13-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.33 | 0.00 | 19-JAN-08:00 | 2593.88 | 13-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 7.10 | 0.00 | 01-JAN-00:10 | 3137.05 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 7.10 | 0.00 | 01-JAN-00:10 | 3137.05 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 25.56 | 0.00 | 19-JAN-08:00 | 3186.28 | 06-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 21.07 | 0.00 | 19-JAN-08:00 | 2516.69 | 13-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 21.07 | 0.00 | 19-JAN-08:00 | 2516.69 | 13-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.49 | 0.00 | 01-JAN-00:10 | 3186.28 | 06-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.49 | 0.00 | 01-JAN-00:10 | 3186.28 | 06-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 122.88 | 0.00 | 01-JAN-08:00 | 18988.46 | 20-APR-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 67.91 | 0.00 | 01-JAN-08:00 | 12993.09 | 13-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 67.91 | 0.00 | 01-JAN-08:00 | 12993.09 | 13-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 54.97 | 0.00 | 01-JAN-00:10 | 18988.46 | 20-APR-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 54.97 | 0.00 | 01-JAN-00:10 | 18988.46 | 20-APR-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 431.76 | 2918.58 | 13-JAN-13:20 | 21165.66 | 11-JUL-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 431.76 | 2918.58 | 13-JAN-13:20 | 21165.66 | 11-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 431.76 | 2918.58 | 13-JAN-13:20 | 21165.66 | 11-JUL-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 459.62 | 4477.30 | 13-JAN-12:20 | 22591.54 | 11-JUL-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 459.62 | 4477.30 | 13-JAN-12:20 | 22591.54 | 11-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 459.62 | 4477.30 | 13-JAN-12:20 | 22591.54 | 11-JUL-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 572.11 | 5504.98 | 30-JAN-04:00 | 31141.48 | 22-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 572.11 | 5504.98 | 30-JAN-04:00 | 31141.48 | 22-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 68.51 | 0.16 | 27-MAR-22:50 | 6315.14 | 23-JUL-13:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 31.03 | 0.00 | 02-FEB-22:50 | 5609.02 | 13-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 31.03 | 0.00 | 02-FEB-22:50 | 5609.02 | 13-JAN-16:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 37.48 | 0.00 | 01-JAN-00:10 | 6315.14 | 23-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 37.48 | 0.00 | 01-JAN-00:10 | 6315.14 | 23-JUL-13:40 |
PlantLoopHeatingDemand:Facility | 3763.90 | 12256.92 | 28-AUG-00:30 | 701240.02 | 12-JAN-07:50 |
PlantLoopHeatingDemand:Plant | 971.99 | 12245.70 | 07-SEP-00:30 | 67261.32 | 16-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 971.99 | 12245.70 | 07-SEP-00:30 | 67261.32 | 16-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 971.99 | 12245.70 | 07-SEP-00:30 | 67261.32 | 16-FEB-07:10 |
EnergyTransfer:HVAC | 7155.79 | 0.00 | 18-AUG-15:10 | 645664.29 | 12-JAN-10:20 |
HeatingCoils:EnergyTransfer | 2791.91 | 0.00 | 17-APR-20:10 | 645664.29 | 12-JAN-10:20 |
PlantLoopHeatingDemand:HVAC | 2791.91 | 0.00 | 17-APR-20:10 | 645664.29 | 12-JAN-10:20 |
HeatingCoils:PlantLoopHeatingDemand | 2791.91 | 0.00 | 17-APR-20:10 | 645664.29 | 12-JAN-10:20 |
CoolingCoils:EnergyTransfer | 985.26 | 0.00 | 01-JAN-00:20 | 399956.06 | 29-JUL-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 3377.71 | 0.00 | 03-JAN-07:40 | 425314.40 | 07-NOV-06:20 |
HeatRecoveryForCooling:EnergyTransfer | 0.91 | 0.00 | 01-JAN-00:10 | 30863.28 | 29-JUL-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 971.99 | 12245.70 | 07-SEP-00:30 | 67261.32 | 16-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 971.99 | 12245.70 | 07-SEP-00:30 | 67261.32 | 16-FEB-07:10 |
Boilers:EnergyTransfer | 2784.95 | 0.00 | 17-APR-20:10 | 643026.81 | 12-JAN-10:20 |
Chillers:EnergyTransfer | 1032.38 | 0.00 | 01-JAN-00:20 | 404049.38 | 29-JUL-18:10 |
HeatRejection:EnergyTransfer | 1354.34 | 0.00 | 01-JAN-00:20 | 515260.49 | 29-JUL-18:10 |
General:HeatRejection:EnergyTransfer | 1354.34 | 0.00 | 01-JAN-00:20 | 515260.49 | 29-JUL-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -348.229 | 0.000 | 0.000 | 146.307 | 122.932 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -64.115 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 13.139 | -24.261 | 0.000 | 0.000 | 15.359 | 6.265 | 10.186 | 23.450 | 0.000 | 0.006 | 0.000 | 0.000 | -16.465 | 0.000 | -9.626 | -18.055 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.043 | -28.816 | 0.000 | 0.000 | 17.799 | 7.255 | 11.795 | 0.000 | 0.000 | 0.004 | 0.000 | 0.000 | 0.000 | 0.000 | -3.692 | -4.388 |
MECH_FLR_1 | 0.000 | 0.000 | 4.923 | -4.698 | 0.000 | 0.000 | 3.642 | 8.366 | 12.471 | 0.000 | 0.000 | 0.006 | 0.000 | 0.000 | 0.000 | 0.000 | -8.946 | -15.764 |
STORAGE_FLR_1 | 0.000 | 0.000 | 6.182 | -9.999 | 0.000 | 0.000 | 3.002 | 2.308 | 3.598 | 0.000 | 0.000 | 0.010 | 0.000 | 0.000 | 0.000 | 0.000 | -4.920 | -0.180 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -569.140 | 0.000 | 0.000 | 10.551 | 4.900 | 658.131 | 0.000 | 0.000 | 0.008 | 0.000 | 0.000 | 0.000 | 0.000 | -12.989 | -91.461 |
CAFE_FLR_1 | 0.000 | 0.000 | 3.043 | -197.719 | 0.000 | 0.000 | 203.386 | 12.811 | 14.341 | 66.364 | 0.000 | 0.019 | 0.000 | 0.000 | -45.799 | 0.000 | -21.068 | -35.377 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.052 | -684.040 | 0.000 | 0.000 | 586.681 | 92.142 | 148.998 | 87.058 | 0.000 | 0.061 | 0.000 | 0.000 | -62.201 | 0.000 | -61.195 | -107.556 |
ROOM_1_FLR_3 | 63.944 | -25.518 | 0.000 | -11.875 | 0.000 | 0.000 | 9.795 | 4.922 | 10.478 | 36.279 | 0.000 | 0.077 | 0.000 | 0.000 | -37.783 | 0.000 | -22.014 | -28.306 |
ROOM_2_FLR_3 | 69.802 | -14.621 | 0.000 | -12.265 | 0.000 | 0.000 | 9.687 | 4.922 | 10.477 | 22.699 | 0.000 | 0.035 | 0.000 | 0.000 | -39.944 | 0.000 | -22.335 | -28.457 |
ROOM_3_MULT19_FLR_3 | 142.965 | -204.833 | 0.043 | -9.921 | 0.000 | 0.000 | 0.000 | 58.777 | 194.997 | 274.575 | 0.000 | 0.008 | 0.000 | 0.000 | -199.187 | 0.000 | -117.527 | -139.898 |
ROOM_4_MULT19_FLR_3 | 306.626 | -125.144 | 0.000 | -163.046 | 0.000 | 0.000 | 185.081 | 58.793 | 195.050 | 68.853 | 0.000 | 0.269 | 0.000 | 0.000 | -221.254 | 0.000 | -127.388 | -177.841 |
ROOM_5_FLR_3 | 61.473 | -31.048 | 0.000 | -11.898 | 0.000 | 0.000 | 9.779 | 4.922 | 10.478 | 44.809 | 0.000 | 0.078 | 0.000 | 0.000 | -37.218 | 0.000 | -22.083 | -29.293 |
ROOM_6_FLR_3 | 66.885 | -20.428 | 0.000 | -12.198 | 0.000 | 0.000 | 9.708 | 4.922 | 10.477 | 30.942 | 0.000 | 0.035 | 0.000 | 0.000 | -39.005 | 0.000 | -22.498 | -28.840 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 30.214 | -106.822 | 0.000 | 0.000 | 120.210 | 56.739 | 0.000 | 37.939 | 0.000 | 0.024 | 0.000 | 0.000 | -47.401 | 0.000 | -26.774 | -64.129 |
ROOM_1_FLR_6 | 21.326 | -6.133 | 0.000 | -2.964 | 0.000 | 0.000 | 2.452 | 1.231 | 2.620 | 9.055 | 0.000 | 0.020 | 0.000 | 0.000 | -9.375 | 0.000 | -5.526 | -12.705 |
ROOM_2_FLR_6 | 23.104 | -3.456 | 0.000 | -3.071 | 0.000 | 0.000 | 2.421 | 1.230 | 2.619 | 5.657 | 0.000 | 0.009 | 0.000 | 0.000 | -9.918 | 0.000 | -5.604 | -12.991 |
ROOM_3_MULT9_FLR_6 | 79.340 | -47.212 | 0.000 | -19.186 | 0.000 | 0.000 | 21.966 | 6.962 | 23.098 | 61.493 | 0.000 | 0.136 | 0.000 | 0.000 | -43.102 | 0.000 | -26.247 | -57.246 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -431.764 | 0.000 | 0.000 | 348.526 | 28.170 | 175.857 | 7.897 | 0.000 | 0.021 | 0.000 | 0.000 | -25.692 | 0.000 | -13.723 | -89.292 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -459.624 | 0.000 | 0.000 | 343.086 | 28.170 | 175.857 | 7.718 | 0.000 | 0.018 | 0.000 | 0.000 | -26.184 | 0.000 | -13.865 | -55.177 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -572.093 | 0.000 | 0.000 | 27.968 | 13.339 | 540.650 | 22.849 | 0.000 | 0.008 | 0.001 | 0.000 | -16.710 | 0.000 | -13.275 | -2.735 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 31.029 | -37.483 | 0.000 | 0.000 | 31.151 | 15.012 | 0.000 | 18.846 | 0.000 | 0.007 | 0.000 | 0.000 | -21.064 | 0.000 | -12.053 | -25.446 |
Total Facility | 835.464 | -478.393 | 88.667 | -3721.109 | 0.000 | 0.000 | 2108.557 | 545.088 | 2355.282 | 826.484 | 0.000 | 0.860 | 0.001 | 0.000 | -898.301 | 0.000 | -573.346 | -1089.254 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 12-JAN-21:00 | 0.00 | 0.00 | 0.00 | -18811.97 | 0.00 | 0.00 | 6150.25 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7023.95 |
RETAIL_1_FLR_1 | 25-AUG-13:30 | 0.00 | 0.00 | 0.00 | -4951.14 | 0.00 | 0.00 | 150.60 | 142.31 | 252.59 | 7149.23 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -26.97 | -2716.62 |
RETAIL_2_FLR_1 | 21-JUN-21:00 | 0.00 | 0.00 | 0.00 | -1727.34 | 0.00 | 0.00 | 697.60 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -0.46 | -249.30 |
MECH_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -1336.15 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 10.31 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -326.86 |
STORAGE_FLR_1 | 23-JUL-10:35 | 0.00 | 0.00 | 0.00 | -973.80 | 0.00 | 0.00 | 47.70 | 62.90 | 101.96 | 0.00 | 0.00 | 0.85 | 760.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -39150.87 | 0.00 | 0.00 | 408.79 | 400.68 | 44299.38 | 0.00 | 0.00 | 14.05 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5972.04 |
CAFE_FLR_1 | 25-AUG-14:10 | 0.00 | 0.00 | 0.00 | -15674.10 | 0.00 | 0.00 | 2968.49 | 96.16 | 355.63 | 17690.51 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -28.84 | -5407.84 |
LOBBY_FLR_1 | 11-AUG-21:10 | 0.00 | 0.00 | 0.00 | -37181.54 | 0.00 | 0.00 | 26439.58 | 5309.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -406.68 | 0.00 | -121.41 | -1429.13 |
ROOM_1_FLR_3 | 16-JUN-18:01 | 0.00 | -14948.85 | 0.00 | -673.69 | 0.00 | 0.00 | 335.50 | 337.19 | 484.65 | 9122.13 | 0.00 | 0.00 | 5715.06 | 0.00 | -0.00 | 0.00 | -372.00 | 0.00 |
ROOM_2_FLR_3 | 09-MAY-20:01 | 0.00 | -15329.91 | 0.00 | -691.44 | 0.00 | 0.00 | 329.27 | 337.15 | 726.90 | 2834.09 | 0.00 | 0.00 | 12110.80 | 0.00 | -0.00 | 0.00 | -316.85 | 0.00 |
ROOM_3_MULT19_FLR_3 | 25-AUG-13:30 | 0.00 | -61051.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1266.71 | 2352.88 | 85637.85 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -722.33 | -27483.27 |
ROOM_4_MULT19_FLR_3 | 10-JUN-21:51 | 0.00 | -75829.49 | 0.00 | -10062.11 | 0.00 | 0.00 | 6134.24 | 3846.41 | 6668.31 | 0.00 | 0.00 | 0.00 | 69855.41 | 0.00 | -11.41 | 0.00 | -601.36 | 0.00 |
ROOM_5_FLR_3 | 13-MAY-08:61 | 0.00 | -14142.23 | 0.00 | -533.46 | 0.00 | 0.00 | 130.71 | 212.17 | 653.23 | 11238.66 | 0.00 | 0.00 | 2664.07 | 0.00 | -0.00 | 0.00 | -223.15 | 0.00 |
ROOM_6_FLR_3 | 22-JUL-08:32 | 0.00 | -13989.06 | 0.00 | -1033.19 | 0.00 | 0.00 | 88.30 | 212.14 | 653.15 | 11153.57 | 0.00 | 0.00 | 3091.76 | 0.00 | -0.00 | 0.00 | -176.68 | 0.00 |
CORRIDOR_FLR_3 | 23-JUL-10:35 | 0.00 | 0.00 | 0.00 | -9215.55 | 0.00 | 0.00 | 1807.14 | 1546.67 | 0.00 | 8097.80 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -42.19 | -2193.87 |
ROOM_1_FLR_6 | 16-JUN-18:01 | 0.00 | -3893.69 | 0.00 | -168.20 | 0.00 | 0.00 | 83.87 | 84.30 | 121.16 | 2270.48 | 0.00 | 0.00 | 1606.21 | 0.00 | -0.00 | 0.00 | -104.13 | 0.00 |
ROOM_2_FLR_6 | 09-MAY-19:42 | 0.00 | -4252.93 | 0.00 | -202.69 | 0.00 | 0.00 | 56.95 | 94.71 | 163.29 | 1053.80 | 0.00 | 0.00 | 3171.00 | 0.00 | -0.00 | 0.00 | -84.12 | 0.00 |
ROOM_3_MULT9_FLR_6 | 20-APR-15:11 | 0.00 | -23502.32 | 0.00 | -852.38 | 0.00 | 0.00 | 529.39 | 150.05 | 441.28 | 13803.79 | 0.00 | 0.00 | 9718.01 | 0.00 | -0.00 | 0.00 | -287.81 | 0.00 |
BANQUET_FLR_6 | 21-JUN-21:03 | 0.00 | 0.00 | 0.00 | -21786.22 | 0.00 | 0.00 | 15718.76 | 1105.25 | 6747.90 | 902.06 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -9.33 | -2678.41 |
DINING_FLR_6 | 11-JUL-21:10 | 0.00 | 0.00 | 0.00 | -22592.53 | 0.00 | 0.00 | 15642.30 | 1105.25 | 6747.90 | 1875.21 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -37.24 | -2740.90 |
KITCHEN_FLR_6 | 22-JUL-10:40 | 0.00 | 0.00 | 0.00 | -31151.69 | 0.00 | 0.00 | 464.18 | 303.01 | 23951.61 | 5124.87 | 0.00 | 0.00 | 1315.63 | 0.00 | -0.00 | 0.00 | -7.62 | 0.00 |
CORRIDOR_FLR_6 | 23-JUL-13:40 | 0.00 | 0.00 | 0.00 | -6314.42 | 0.00 | 0.00 | 308.46 | 272.82 | 0.00 | 5168.70 | 0.00 | 12.74 | 551.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-JUL-18:02 | 0.00 | -162863.98 | 0.00 | -193622.02 | 0.00 | 0.00 | 66211.97 | 34560.19 | 113070.18 | 35945.27 | 0.00 | 2180.02 | 104518.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 13-JAN-16:10 | 0.00 | 0.00 | 2589.94 | 0.00 | 0.00 | 0.00 | 467.29 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1241.38 | 0.00 | -604.28 | -1606.46 |
RETAIL_2_FLR_1 | 13-JAN-16:00 | 0.00 | 0.00 | 439.84 | 0.00 | 0.00 | 0.00 | 312.61 | 164.79 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -238.75 | -971.00 |
MECH_FLR_1 | 13-JAN-16:10 | 0.00 | 0.00 | 1277.28 | 0.00 | 0.00 | 0.00 | 112.08 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -555.62 | -1333.06 |
STORAGE_FLR_1 | 13-JAN-16:10 | 0.00 | 0.00 | 986.52 | 0.00 | 0.00 | 0.00 | 88.14 | 52.42 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -317.15 | -899.14 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 13-JAN-15:00 | 0.00 | 0.00 | 3955.00 | 0.00 | 0.00 | 0.00 | 2441.25 | 433.14 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3694.95 | 0.00 | -1406.58 | -2083.49 |
LOBBY_FLR_1 | 13-JAN-14:40 | 0.00 | 0.00 | 4274.54 | 0.00 | 0.00 | 0.00 | 6996.14 | 2213.80 | 3694.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5028.40 | 0.00 | -4122.15 | -8028.90 |
ROOM_1_FLR_3 | 13-JAN-16:23 | 8893.64 | 338.19 | 0.00 | -338.19 | 0.00 | 0.00 | 274.12 | 106.08 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2812.66 | 0.00 | -1379.26 | -5282.10 |
ROOM_2_FLR_3 | 12-JAN-17:54 | 9356.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.59 | 106.07 | 505.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3729.75 | 0.00 | -1877.32 | -4646.60 |
ROOM_3_MULT19_FLR_3 | 12-JAN-04:10 | 35054.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.64 | 3333.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19419.21 | 0.00 | -9512.98 | -9952.99 |
ROOM_4_MULT19_FLR_3 | 12-JAN-10:53 | 48182.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2089.16 | 1267.05 | 2353.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19073.54 | 0.00 | -10080.03 | -24738.85 |
ROOM_5_FLR_3 | 13-JAN-16:23 | 8743.71 | 334.35 | 0.00 | -334.35 | 0.00 | 0.00 | 274.99 | 106.08 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2810.05 | 0.00 | -1377.60 | -5137.31 |
ROOM_6_FLR_3 | 12-JAN-17:54 | 9147.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.95 | 106.07 | 505.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3724.16 | 0.00 | -1878.15 | -4444.04 |
CORRIDOR_FLR_3 | 13-JAN-16:10 | 0.00 | 0.00 | 7584.40 | 0.00 | 0.00 | 0.00 | 3597.97 | 1288.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3586.84 | 0.00 | -1699.47 | -7184.95 |
ROOM_1_FLR_6 | 15-DEC-17:54 | 2776.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.97 | 26.52 | 126.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -839.49 | 0.00 | -393.25 | -1765.25 |
ROOM_2_FLR_6 | 12-JAN-07:53 | 2720.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.17 | 53.04 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -944.80 | 0.00 | -487.38 | -1635.31 |
ROOM_3_MULT9_FLR_6 | 13-JAN-16:23 | 13321.26 | 554.49 | 0.00 | -554.49 | 0.00 | 0.00 | 612.41 | 150.05 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3247.12 | 0.00 | -1593.73 | -9684.15 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 13-JAN-16:10 | 0.00 | 0.00 | 5609.42 | 0.00 | 0.00 | 0.00 | 968.22 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1555.39 | 0.00 | -746.61 | -4616.66 |
Total Facility | 13-JAN-16:23 | 65041.73 | 67843.24 | 20105.92 | -67843.24 | 0.00 | 0.00 | 62406.91 | 12737.46 | 73604.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -63516.09 | 0.00 | -34167.69 | -136212.53 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.5251 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.3982 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 13.1529 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.5268 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1921 | 2.1921 | 1.2824 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5021 | 0.5021 | 0.1190 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2267 | 0.2267 | 0.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1780 | 0.1780 | 0.0018 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0970 | 0.0970 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3154 | 3.3154 | 0.0332 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9510 | 1.9510 | 1.0145 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2778 | 5.2778 | 2.8395 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4263 | 1.4263 | 0.7117 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1082 | 2.1082 | 1.7814 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2122 | 2.2122 | 1.7808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2731 | 2.2731 | 0.5501 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7651 | 0.7651 | 0.1882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.5251 | 22.3982 | 22.5251 | 10.5268 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2824 | 1.2824 | 1.2824 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2511 | 0.2511 | 0.1190 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1376 | 0.1376 | 0.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0890 | 0.0890 | 0.0018 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0866 | 0.0866 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6577 | 1.6577 | 0.0332 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0145 | 1.0145 | 1.0145 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8395 | 2.8395 | 2.8395 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7132 | 0.7132 | 0.7117 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7814 | 1.7814 | 1.7814 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7808 | 1.7808 | 1.7808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1365 | 1.1365 | 0.5501 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3826 | 0.3826 | 0.1882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 13.1529 | 10.5268 | 10.5268 | 10.5268 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 213.50 |
Number of hours cooling loads not met | 37.17 |
Number of hours not met | 250.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 3615.61 | 783717.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 321.96 | 114978.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 545.09 | 45764.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 192.37 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.51 | 1274.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 560.67 | 31412.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 57.99 | 4641.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 140.95 | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.77 | 3628.21 | 312595.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.79 | 1309.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 20.86 | 714.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1692.20 | 4242.52 |
Natural Gas | 1788.84 | 9032.66 |
Additional | 0.00 | 0.00 |
Total | 3481.04 | 13275.18 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 48.05 |
Space Heating | 0.00 |
Space Cooling | 28.38 |
Fans (All) | 49.42 |
Service Water Heating | 8.00 |
Receptacle Equipment | 145.30 |
Miscellaneous (All) | 373.95 |
Subtotal | 373.95 |
Natural Gas [MJ/m2] | |
Space Heating | 318.69 |
Service Water Heating | 319.80 |
Miscellaneous (All) | 796.16 |
Subtotal | 796.16 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 4.11 |
Space Heating | 27.24 |
Space Cooling | 2.43 |
Fans (All) | 4.22 |
Service Water Heating | 28.01 |
Receptacle Equipment | 25.89 |
Miscellaneous | 8.10 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8715.33 | 44.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8697.33 | 62.67 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8748.83 | 11.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8673.83 | 86.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8673.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 86.17 | 0.00 | 0.00 | 0.00 |
Average | 8750.70 | 9.30 | 0.00 | 0.00 | 0.00 |
Sum | 192515.33 | 204.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4134.33 | 19.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4108.33 | 45.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 45.67 | 0.00 | 0.00 | 0.00 |
Average | 288884.08 | 2.97 | 0.00 | 0.00 | 0.00 |
Sum | 6355449.67 | 65.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8719.33 | 40.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8607.83 | 152.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8746.50 | 13.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8686.17 | 73.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8607.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 152.17 | 0.00 | 0.00 | 0.00 |
Average | 8746.63 | 13.37 | 0.00 | 0.00 | 0.00 |
Sum | 192425.83 | 294.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2113655.67 | 1773.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4129.17 | 24.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4152.83 | 1.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4104.83 | 49.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1244408.33 | 1306.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245113.67 | 601.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108261.67 | 7.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2113655.67 | 1773.33 | 0.00 | 0.00 | 0.00 |
Average | 288715.96 | 171.08 | 0.00 | 0.00 | 0.00 |
Sum | 6351751.17 | 3763.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:54
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281319E+11 | 18811.57 | 12-JAN-21:00 | -37.2 | -37.3 | 0.690401E+10 | 4387.03 | 27-JAN-22:10 | -13.2 | -13.7 |
February | 0.227837E+11 | 13886.81 | 28-FEB-21:00 | -30.0 | -30.1 | 0.590134E+10 | 4286.07 | 01-FEB-22:10 | -30.0 | -30.1 |
March | 0.245773E+11 | 11960.44 | 01-MAR-00:10 | -28.9 | -29.2 | 0.649723E+10 | 4045.95 | 31-MAR-21:10 | -13.2 | -14.9 |
April | 0.250945E+11 | 12500.19 | 22-APR-10:35 | 11.87 | 5.55 | 0.640179E+10 | 4111.07 | 14-APR-22:10 | 11.87 | 5.55 |
May | 0.270932E+11 | 12922.07 | 14-MAY-10:35 | 16.83 | 8.94 | 0.668479E+10 | 4156.36 | 26-MAY-22:10 | 2.12 | 0.59 |
June | 0.276682E+11 | 13443.91 | 29-JUN-10:35 | 21.83 | 15.68 | 0.665788E+10 | 4270.87 | 23-JUN-22:10 | 21.83 | 15.68 |
July | 0.310965E+11 | 14699.86 | 23-JUL-10:35 | 22.23 | 15.22 | 0.725733E+10 | 4540.12 | 28-JUL-22:10 | 17.02 | 13.67 |
August | 0.333072E+11 | 15325.78 | 26-AUG-10:35 | 15.93 | 12.30 | 0.776005E+10 | 4816.67 | 31-AUG-22:10 | 8.20 | 4.96 |
September | 0.329187E+11 | 15889.16 | 20-SEP-21:00 | 8.30 | 7.74 | 0.771448E+10 | 4837.04 | 19-SEP-21:19 | 8.30 | 7.74 |
October | 0.335096E+11 | 16105.84 | 06-OCT-21:00 | 7.80 | 3.59 | 0.797739E+10 | 4837.04 | 19-OCT-21:19 | -1.7 | -1.8 |
November | 0.316262E+11 | 15365.95 | 28-NOV-23:00 | -28.9 | -29.1 | 0.750404E+10 | 4836.95 | 02-NOV-21:19 | -28.9 | -29.1 |
December | 0.304213E+11 | 17194.65 | 15-DEC-07:52 | -33.9 | -34.0 | 0.729415E+10 | 4590.06 | 01-DEC-22:10 | -33.9 | -34.0 |
Annual Sum or Average | 0.348228E+12 | 0.845545E+11 | ||||||||
Minimum of Months | 0.227837E+11 | 11960.44 | -37.2 | -37.3 | 0.590134E+10 | 4045.95 | -33.9 | -34.0 | ||
Maximum of Months | 0.335096E+11 | 18811.57 | 22.23 | 15.68 | 0.797739E+10 | 4837.04 | 21.83 | 15.68 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9958775.32 | 677.82 | 30-JAN-12:30 | -23.9 | -24.3 | 0.609917E+09 | 364.20 | 26-JAN-01:39 | -23.9 | -24.3 |
February | 0.203149E+09 | 1165.62 | 15-FEB-13:40 | -8.7 | -9.6 | 0.561043E+09 | 364.29 | 18-FEB-05:19 | -23.5 | -23.8 |
March | 0.108159E+10 | 2749.85 | 27-MAR-13:30 | -5.5 | -8.7 | 0.640644E+09 | 404.96 | 22-MAR-21:19 | -5.5 | -8.7 |
April | 0.293207E+10 | 4520.09 | 22-APR-13:30 | 15.30 | 6.96 | 0.681470E+09 | 491.83 | 21-APR-21:19 | 15.30 | 6.96 |
May | 0.380003E+10 | 4452.42 | 12-MAY-13:30 | 20.60 | 9.86 | 0.755823E+09 | 491.84 | 11-MAY-21:40 | 20.60 | 9.86 |
June | 0.421834E+10 | 4196.48 | 30-JUN-12:30 | 26.15 | 17.75 | 0.775987E+09 | 491.85 | 16-JUN-21:10 | 26.15 | 17.75 |
July | 0.439111E+10 | 4773.49 | 23-JUL-13:30 | 25.00 | 15.26 | 0.796202E+09 | 491.86 | 21-JUL-22:00 | 25.00 | 15.26 |
August | 0.411290E+10 | 4950.54 | 25-AUG-13:30 | 21.70 | 14.78 | 0.780823E+09 | 491.84 | 03-AUG-22:10 | 21.70 | 14.78 |
September | 0.252726E+10 | 4083.46 | 09-SEP-13:30 | 13.35 | 8.71 | 0.665719E+09 | 473.58 | 08-SEP-21:19 | 13.35 | 8.71 |
October | 0.948958E+09 | 2993.55 | 03-OCT-13:20 | 10.57 | 6.12 | 0.631207E+09 | 431.97 | 03-OCT-21:30 | 7.20 | 2.97 |
November | 35097267.84 | 965.23 | 08-NOV-13:40 | -13.5 | -14.3 | 0.598988E+09 | 364.21 | 08-NOV-02:20 | -13.5 | -14.3 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 0.617147E+09 | 364.21 | 09-DEC-00:40 | -24.2 | -24.5 |
Annual Sum or Average | 0.242605E+11 | 0.811497E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.561043E+09 | 364.20 | -24.2 | -24.5 | ||
Maximum of Months | 0.439111E+10 | 4950.54 | 26.15 | 17.75 | 0.796202E+09 | 491.86 | 26.15 | 17.75 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120556E+10 | 1053.46 | 23-JAN-21:00 | -16.1 | -16.4 | 0.716517E+09 | 444.14 | 20-JAN-23:10 | -16.1 | -16.4 |
February | 0.143197E+10 | 1145.53 | 09-FEB-21:00 | -8.9 | -9.2 | 0.654410E+09 | 464.09 | 09-FEB-22:49 | -10.4 | -10.7 |
March | 0.214822E+10 | 1270.01 | 22-MAR-20:00 | 2.80 | 0.30 | 0.743686E+09 | 494.66 | 22-MAR-22:10 | 1.42 | -0.3 |
April | 0.281663E+10 | 1519.36 | 21-APR-20:00 | 12.20 | 5.22 | 0.787552E+09 | 557.93 | 21-APR-21:40 | 8.13 | 2.71 |
May | 0.327638E+10 | 1565.04 | 31-MAY-18:10 | 21.13 | 10.92 | 0.861832E+09 | 566.44 | 31-MAY-22:10 | 15.05 | 9.19 |
June | 0.340152E+10 | 1727.17 | 21-JUN-21:00 | 23.90 | 13.75 | 0.871116E+09 | 569.56 | 16-JUN-21:10 | 23.90 | 13.75 |
July | 0.352840E+10 | 1685.27 | 11-JUL-20:05 | 23.62 | 14.00 | 0.895626E+09 | 569.56 | 10-JUL-22:10 | 23.62 | 14.00 |
August | 0.341687E+10 | 1675.15 | 11-AUG-21:00 | 22.80 | 14.12 | 0.889016E+09 | 569.55 | 01-AUG-22:10 | 22.80 | 14.12 |
September | 0.286939E+10 | 1472.57 | 10-SEP-10:35 | 13.87 | 7.59 | 0.793320E+09 | 543.83 | 01-SEP-22:10 | 13.87 | 7.59 |
October | 0.235912E+10 | 1340.83 | 03-OCT-20:00 | 6.10 | 2.72 | 0.756465E+09 | 514.51 | 03-OCT-22:10 | 7.30 | 3.10 |
November | 0.132657E+10 | 1084.55 | 01-NOV-20:00 | -8.9 | -9.5 | 0.696924E+09 | 451.97 | 01-NOV-22:10 | -9.0 | -9.5 |
December | 0.103504E+10 | 1023.62 | 19-DEC-21:00 | -6.1 | -7.0 | 0.717758E+09 | 436.67 | 19-DEC-23:10 | -8.7 | -9.2 |
Annual Sum or Average | 0.288157E+11 | 0.938422E+10 | ||||||||
Minimum of Months | 0.103504E+10 | 1023.62 | -16.1 | -16.4 | 0.654410E+09 | 436.67 | -16.1 | -16.4 | ||
Maximum of Months | 0.352840E+10 | 1727.17 | 23.90 | 14.12 | 0.895626E+09 | 569.56 | 23.90 | 14.12 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2814799.82 | 14.04 | 19-JAN-21:00 | -10.0 | -10.4 | 0.151463E+09 | 94.11 | 20-JAN-22:10 | -11.2 | -11.4 |
February | 7183762.00 | 15.78 | 09-FEB-21:00 | -8.9 | -9.2 | 0.138715E+09 | 101.02 | 09-FEB-22:10 | -9.6 | -9.9 |
March | 19438898.79 | 18.30 | 22-MAR-20:00 | 2.80 | 0.30 | 0.158716E+09 | 111.47 | 22-MAR-21:10 | 2.12 | 0.08 |
April | 85080700.14 | 536.74 | 21-APR-20:00 | 12.20 | 5.22 | 0.178792E+09 | 120.45 | 27-APR-22:40 | 4.07 | 1.37 |
May | 0.545107E+09 | 984.76 | 31-MAY-20:55 | 16.70 | 9.87 | 0.204136E+09 | 120.45 | 11-MAY-22:10 | 16.70 | 9.87 |
June | 0.128460E+10 | 1300.63 | 21-JUN-20:00 | 25.00 | 13.79 | 0.199174E+09 | 120.46 | 02-JUN-22:10 | 25.00 | 13.79 |
July | 0.142764E+10 | 1335.82 | 21-JUL-20:00 | 25.00 | 16.11 | 0.205000E+09 | 120.46 | 21-JUL-23:10 | 19.72 | 15.53 |
August | 0.108213E+10 | 1248.92 | 11-AUG-20:00 | 24.40 | 14.81 | 0.205762E+09 | 120.45 | 03-AUG-21:00 | 24.40 | 14.81 |
September | 0.201636E+09 | 672.06 | 01-SEP-20:00 | 12.20 | 9.06 | 0.192515E+09 | 120.45 | 01-SEP-00:10 | 12.20 | 9.06 |
October | 36938552.40 | 204.53 | 06-OCT-21:00 | 7.80 | 3.59 | 0.173327E+09 | 120.45 | 03-OCT-21:19 | 7.80 | 3.59 |
November | 3681757.61 | 14.54 | 03-NOV-20:00 | -6.1 | -7.8 | 0.147234E+09 | 96.36 | 03-NOV-21:10 | -6.6 | -8.2 |
December | 1716904.07 | 13.48 | 19-DEC-21:00 | -6.1 | -7.0 | 0.151835E+09 | 91.74 | 19-DEC-22:10 | -8.3 | -8.9 |
Annual Sum or Average | 0.469797E+10 | 0.210667E+10 | ||||||||
Minimum of Months | 1716904.07 | 13.48 | -10.0 | -10.4 | 0.138715E+09 | 91.74 | -11.2 | -11.4 | ||
Maximum of Months | 0.142764E+10 | 1335.82 | 25.00 | 16.11 | 0.205762E+09 | 120.46 | 25.00 | 15.53 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 | -15.4 | 0.115446E+09 | 68.58 | 26-JAN-01:10 | -23.9 | -24.2 |
February | 2199585.50 | 124.97 | 08-FEB-22:00 | 1.10 | -1.7 | 0.105325E+09 | 68.59 | 18-FEB-05:19 | -23.5 | -23.8 |
March | 51106523.24 | 442.10 | 22-MAR-21:00 | 2.20 | 0.09 | 0.117211E+09 | 68.59 | 13-MAR-04:10 | 2.20 | 0.09 |
April | 0.858039E+09 | 792.31 | 23-APR-10:35 | 9.80 | 3.70 | 0.113613E+09 | 72.82 | 21-APR-21:40 | 9.80 | 3.70 |
May | 0.170541E+10 | 890.59 | 14-MAY-10:35 | 16.83 | 8.94 | 0.122356E+09 | 77.30 | 31-MAY-22:10 | 15.05 | 9.19 |
June | 0.185852E+10 | 934.17 | 22-JUN-10:35 | 21.33 | 12.72 | 0.126296E+09 | 81.68 | 21-JUN-21:00 | 21.33 | 12.72 |
July | 0.194568E+10 | 973.77 | 23-JUL-10:35 | 22.23 | 15.22 | 0.130732E+09 | 82.03 | 11-JUL-21:49 | 22.23 | 15.22 |
August | 0.184566E+10 | 906.95 | 26-AUG-10:35 | 15.93 | 12.30 | 0.128135E+09 | 80.53 | 11-AUG-21:40 | 15.93 | 12.30 |
September | 0.131766E+10 | 816.00 | 10-SEP-10:35 | 13.87 | 7.59 | 0.114800E+09 | 73.70 | 01-SEP-22:10 | 13.87 | 7.59 |
October | 0.414539E+09 | 668.94 | 03-OCT-19:50 | 6.47 | 2.89 | 0.116772E+09 | 69.94 | 03-OCT-22:10 | 7.30 | 3.10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.112768E+09 | 68.58 | 16-NOV-23:19 | -23.9 | -24.1 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 0.116434E+09 | 68.58 | 19-DEC-01:19 | -24.1 | -24.3 |
Annual Sum or Average | 0.999881E+10 | 0.141989E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.105325E+09 | 68.58 | -24.1 | -24.3 | ||
Maximum of Months | 0.194568E+10 | 973.77 | 22.23 | 15.22 | 0.130732E+09 | 82.03 | 22.23 | 15.22 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.448652E+11 | 36315.77 | 19-JAN-21:00 | -10.0 | -10.4 | 0.649339E+09 | 381.60 | 03-JAN-22:19 | -10.0 | -10.4 |
February | 0.411466E+11 | 36795.81 | 08-FEB-21:00 | -1.1 | -2.8 | 0.587073E+09 | 381.59 | 18-FEB-05:40 | -22.6 | -23.0 |
March | 0.470190E+11 | 37524.30 | 22-MAR-20:00 | 2.80 | 0.30 | 0.652392E+09 | 381.58 | 22-MAR-23:40 | -0.4 | -1.6 |
April | 0.474538E+11 | 38299.96 | 21-APR-20:00 | 12.20 | 5.22 | 0.629503E+09 | 381.58 | 07-APR-01:10 | 12.20 | 5.22 |
May | 0.509801E+11 | 38784.04 | 31-MAY-20:00 | 17.20 | 10.12 | 0.650710E+09 | 381.58 | 17-MAY-21:10 | 17.20 | 10.12 |
June | 0.502711E+11 | 39064.60 | 29-JUN-20:00 | 25.00 | 16.66 | 0.630881E+09 | 381.73 | 16-JUN-21:10 | 25.00 | 16.66 |
July | 0.518566E+11 | 39145.83 | 21-JUL-20:00 | 25.00 | 16.11 | 0.649340E+09 | 381.71 | 01-JUL-00:10 | 25.00 | 16.11 |
August | 0.515433E+11 | 38993.39 | 11-AUG-20:00 | 24.40 | 14.81 | 0.652089E+09 | 381.65 | 23-AUG-21:10 | 18.43 | 14.55 |
September | 0.481290E+11 | 38196.84 | 01-SEP-20:00 | 12.20 | 9.06 | 0.629195E+09 | 381.57 | 27-SEP-23:30 | -0.9 | -1.3 |
October | 0.477494E+11 | 37764.55 | 03-OCT-20:00 | 6.10 | 2.72 | 0.649650E+09 | 381.57 | 15-OCT-23:30 | -0.9 | -1.3 |
November | 0.437015E+11 | 36439.02 | 01-NOV-20:00 | -8.9 | -9.5 | 0.628127E+09 | 381.57 | 07-NOV-23:49 | -23.0 | -23.3 |
December | 0.444227E+11 | 36102.41 | 19-DEC-21:00 | -6.1 | -7.0 | 0.649339E+09 | 381.63 | 15-DEC-22:10 | -6.1 | -7.0 |
Annual Sum or Average | 0.569138E+12 | 0.765764E+10 | ||||||||
Minimum of Months | 0.411466E+11 | 36102.41 | -10.0 | -10.4 | 0.587073E+09 | 381.57 | -23.0 | -23.3 | ||
Maximum of Months | 0.518566E+11 | 39145.83 | 25.00 | 16.66 | 0.652392E+09 | 381.73 | 25.00 | 16.66 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.641482E+10 | 6830.07 | 06-JAN-23:10 | -3.0 | -4.1 | 0.809580E+10 | 4872.66 | 06-JAN-23:10 | -3.0 | -4.1 |
February | 0.906924E+10 | 8118.57 | 15-FEB-13:40 | -8.7 | -9.6 | 0.738971E+10 | 5108.11 | 08-FEB-22:40 | -8.7 | -9.6 |
March | 0.158398E+11 | 11277.68 | 27-MAR-15:10 | -4.9 | -8.2 | 0.849383E+10 | 5635.62 | 22-MAR-21:40 | -4.9 | -8.2 |
April | 0.211005E+11 | 15392.11 | 22-APR-13:30 | 15.30 | 6.96 | 0.895886E+10 | 6273.25 | 21-APR-21:40 | 15.30 | 6.96 |
May | 0.238965E+11 | 14529.06 | 13-MAY-13:10 | 18.98 | 8.91 | 0.957402E+10 | 6384.91 | 31-MAY-21:40 | 15.77 | 9.56 |
June | 0.242914E+11 | 13637.51 | 20-JUN-15:10 | 25.10 | 14.57 | 0.961814E+10 | 6462.77 | 29-JUN-22:10 | 22.23 | 16.21 |
July | 0.252245E+11 | 14930.83 | 23-JUL-13:30 | 25.00 | 15.26 | 0.985994E+10 | 6462.78 | 31-JUL-22:10 | 19.35 | 13.65 |
August | 0.246171E+11 | 15671.27 | 25-AUG-14:10 | 22.88 | 15.43 | 0.979699E+10 | 6462.77 | 10-AUG-22:10 | 22.88 | 15.43 |
September | 0.198480E+11 | 14331.43 | 09-SEP-13:30 | 13.35 | 8.71 | 0.881657E+10 | 6090.33 | 08-SEP-21:40 | 13.35 | 8.71 |
October | 0.151638E+11 | 10832.31 | 03-OCT-14:10 | 11.88 | 6.64 | 0.846928E+10 | 5865.82 | 03-OCT-21:40 | 7.20 | 3.00 |
November | 0.695734E+10 | 7007.21 | 08-NOV-13:30 | -13.6 | -14.4 | 0.787764E+10 | 4941.68 | 01-NOV-21:40 | -13.6 | -14.4 |
December | 0.529372E+10 | 6450.73 | 19-DEC-22:20 | -8.3 | -8.9 | 0.813178E+10 | 4788.22 | 09-DEC-02:49 | -8.3 | -8.9 |
Annual Sum or Average | 0.197717E+12 | 0.105083E+12 | ||||||||
Minimum of Months | 0.529372E+10 | 6450.73 | -13.6 | -14.4 | 0.738971E+10 | 4788.22 | -13.6 | -14.4 | ||
Maximum of Months | 0.252245E+11 | 15671.27 | 25.10 | 15.43 | 0.985994E+10 | 6462.78 | 22.88 | 16.21 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.377948E+11 | 23170.94 | 06-JAN-22:00 | -3.9 | -4.8 | 0.249048E+11 | 16210.03 | 06-JAN-23:10 | -3.0 | -4.1 |
February | 0.408345E+11 | 25632.20 | 28-FEB-22:10 | -29.6 | -29.7 | 0.228866E+11 | 16809.98 | 09-FEB-22:49 | -29.6 | -29.7 |
March | 0.543183E+11 | 27690.85 | 22-MAR-20:00 | 2.80 | 0.30 | 0.265529E+11 | 17867.23 | 22-MAR-22:10 | 1.42 | -0.3 |
April | 0.631408E+11 | 32430.90 | 21-APR-21:10 | 9.53 | 3.30 | 0.280224E+11 | 19183.57 | 21-APR-21:49 | 7.67 | 2.50 |
May | 0.712673E+11 | 33441.26 | 14-MAY-10:35 | 16.83 | 8.94 | 0.302551E+11 | 19186.29 | 11-MAY-21:40 | 16.83 | 8.94 |
June | 0.728980E+11 | 36499.76 | 21-JUN-21:03 | 23.53 | 13.66 | 0.301812E+11 | 19186.57 | 30-JUN-23:00 | 15.10 | 14.10 |
July | 0.757055E+11 | 37118.51 | 21-JUL-21:10 | 22.70 | 14.59 | 0.310378E+11 | 19186.91 | 01-JUL-00:10 | 22.70 | 14.59 |
August | 0.738103E+11 | 37197.75 | 11-AUG-21:10 | 22.33 | 14.00 | 0.309800E+11 | 19186.28 | 01-AUG-22:10 | 22.33 | 14.00 |
September | 0.637322E+11 | 32349.03 | 10-SEP-10:35 | 13.87 | 7.59 | 0.282492E+11 | 19166.58 | 08-SEP-22:10 | 13.87 | 7.59 |
October | 0.562002E+11 | 29166.58 | 03-OCT-20:00 | 6.10 | 2.72 | 0.271187E+11 | 18536.84 | 03-OCT-22:10 | 7.30 | 3.10 |
November | 0.393453E+11 | 24696.59 | 28-NOV-22:10 | -27.5 | -27.7 | 0.242342E+11 | 16454.19 | 01-NOV-22:10 | -27.5 | -27.7 |
December | 0.349880E+11 | 24579.25 | 27-DEC-22:00 | -26.1 | -26.3 | 0.246218E+11 | 15929.03 | 19-DEC-23:10 | -26.1 | -26.3 |
Annual Sum or Average | 0.684035E+12 | 0.329045E+12 | ||||||||
Minimum of Months | 0.349880E+11 | 23170.94 | -29.6 | -29.7 | 0.228866E+11 | 15929.03 | -29.6 | -29.7 | ||
Maximum of Months | 0.757055E+11 | 37197.75 | 23.53 | 14.59 | 0.310378E+11 | 19186.91 | 22.70 | 14.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 | -15.4 | 91489037.36 | 56.69 | 04-JAN-04:40 | -15.7 | -15.9 |
February | 1351660.47 | 399.49 | 15-FEB-16:14 | -7.4 | -8.8 | 83100413.63 | 56.69 | 23-FEB-04:10 | -22.7 | -22.9 |
March | 41574402.00 | 3641.70 | 22-MAR-15:11 | 5.60 | 2.35 | 93625230.06 | 56.69 | 06-MAR-04:00 | 5.60 | 2.35 |
April | 0.645337E+09 | 3849.09 | 20-APR-18:01 | 12.02 | 5.14 | 94184485.19 | 56.69 | 20-APR-22:10 | 5.13 | 1.65 |
May | 0.126368E+10 | 3866.01 | 10-MAY-18:01 | 18.30 | 8.81 | 98946875.13 | 56.69 | 30-MAY-21:40 | 17.23 | 9.55 |
June | 0.191296E+10 | 3905.68 | 16-JUN-18:01 | 19.40 | 10.53 | 96188312.06 | 56.70 | 19-JUN-21:10 | 21.23 | 12.32 |
July | 0.184579E+10 | 3384.01 | 26-JUL-18:01 | 18.85 | 14.91 | 99280711.37 | 56.70 | 24-JUL-21:49 | 18.85 | 14.91 |
August | 0.138901E+10 | 3800.10 | 31-AUG-15:11 | 14.27 | 5.23 | 99051722.82 | 56.70 | 02-AUG-21:49 | 14.27 | 5.23 |
September | 0.327738E+09 | 3786.95 | 07-SEP-15:11 | 16.47 | 8.91 | 93626765.35 | 56.69 | 01-SEP-01:30 | 16.47 | 8.91 |
October | 18025482.60 | 3190.98 | 13-OCT-15:12 | 1.70 | -2.0 | 93204827.97 | 56.69 | 23-OCT-23:19 | -5.0 | -5.2 |
November | 5104.65 | 8.51 | 08-NOV-14:00 | -13.3 | -14.1 | 88940645.20 | 56.69 | 17-NOV-04:49 | -21.4 | -21.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 91745250.24 | 56.69 | 23-DEC-04:10 | -6.4 | -7.4 |
Annual Sum or Average | 0.744547E+10 | 0.112338E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 83100413.63 | 56.69 | -22.7 | -22.9 | ||
Maximum of Months | 0.191296E+10 | 3905.68 | 19.40 | 14.91 | 99280711.37 | 56.70 | 21.23 | 14.91 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 | -15.4 | 91299737.14 | 56.69 | 19-JAN-00:20 | -9.2 | -9.3 |
February | 37239.91 | 160.93 | 08-FEB-19:06 | 0.22 | -1.6 | 82984710.28 | 56.69 | 06-FEB-05:19 | 0.22 | -1.6 |
March | 3416761.81 | 729.51 | 26-MAR-15:14 | -8.5 | -10.4 | 92504987.36 | 56.69 | 15-MAR-04:40 | -8.5 | -10.4 |
April | 0.338516E+09 | 3476.84 | 21-APR-18:01 | 14.22 | 5.92 | 92609244.44 | 56.69 | 21-APR-21:40 | 8.13 | 2.71 |
May | 0.785253E+09 | 4005.33 | 09-MAY-20:01 | 13.35 | 5.95 | 0.103126E+09 | 87.50 | 10-MAY-21:10 | 14.13 | 6.05 |
June | 0.135125E+10 | 3654.07 | 01-JUN-18:41 | 14.60 | 7.96 | 0.107716E+09 | 102.02 | 28-JUN-21:10 | 19.72 | 14.76 |
July | 0.130442E+10 | 3486.46 | 06-JUL-21:51 | 18.90 | 13.76 | 0.108481E+09 | 91.12 | 11-JUL-21:10 | 21.83 | 13.37 |
August | 0.820277E+09 | 3419.69 | 30-AUG-18:01 | 8.80 | 3.00 | 0.105880E+09 | 90.65 | 10-AUG-21:10 | 8.80 | 3.00 |
September | 0.142070E+09 | 3378.34 | 07-SEP-18:01 | 14.13 | 7.59 | 92773059.19 | 56.69 | 02-SEP-23:19 | 14.13 | 7.59 |
October | 4716579.76 | 1554.82 | 03-OCT-15:11 | 12.43 | 6.74 | 92554780.90 | 56.69 | 31-OCT-23:19 | -10.3 | -11.2 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 88904232.44 | 56.69 | 18-NOV-00:20 | -14.1 | -14.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 91703378.92 | 56.69 | 23-DEC-05:10 | -4.8 | -6.0 |
Annual Sum or Average | 0.474996E+10 | 0.115054E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 82984710.28 | 56.69 | -14.1 | -14.7 | ||
Maximum of Months | 0.135125E+10 | 4005.33 | 18.90 | 13.76 | 0.108481E+09 | 102.02 | 21.83 | 14.76 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2841.25 | 2.68 | 23-JAN-15:20 | -10.4 | -10.8 | 0.00 | 0.00 | 01-JAN-00:10 | -10.4 | -10.8 |
February | 1494973.18 | 99.61 | 26-FEB-16:00 | -23.9 | -24.3 | 0.00 | 0.00 | 01-FEB-00:10 | -23.9 | -24.3 |
March | 11107318.83 | 189.07 | 31-MAR-15:10 | -9.9 | -12.2 | 0.00 | 0.00 | 01-MAR-00:10 | -9.9 | -12.2 |
April | 0.329434E+09 | 742.97 | 22-APR-13:20 | 15.20 | 6.93 | 0.00 | 0.00 | 01-APR-00:10 | 15.20 | 6.93 |
May | 0.488510E+09 | 720.03 | 12-MAY-13:20 | 20.60 | 9.86 | 0.00 | 0.00 | 01-MAY-00:10 | 20.60 | 9.86 |
June | 0.577568E+09 | 637.89 | 30-JUN-12:30 | 26.15 | 17.75 | 0.00 | 0.00 | 01-JUN-00:10 | 26.15 | 17.75 |
July | 0.604793E+09 | 758.42 | 23-JUL-13:30 | 25.00 | 15.26 | 0.00 | 0.00 | 01-JUL-00:10 | 25.00 | 15.26 |
August | 0.549388E+09 | 803.30 | 25-AUG-13:30 | 21.70 | 14.78 | 0.00 | 0.00 | 01-AUG-00:10 | 21.70 | 14.78 |
September | 0.226712E+09 | 688.64 | 09-SEP-13:10 | 12.98 | 8.62 | 0.00 | 0.00 | 01-SEP-00:10 | 12.98 | 8.62 |
October | 29459955.09 | 460.95 | 03-OCT-13:00 | 10.00 | 5.88 | 0.00 | 0.00 | 01-OCT-00:10 | 10.00 | 5.88 |
November | 173296.67 | 34.63 | 08-NOV-15:20 | -14.6 | -15.2 | 0.00 | 0.00 | 01-NOV-00:10 | -14.6 | -15.2 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.281864E+10 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -25.8 | -26.0 | ||
Maximum of Months | 0.604793E+09 | 803.30 | 26.15 | 17.75 | 0.00 | 0.00 | 26.15 | 17.75 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 923372.62 | 192.28 | 20-JAN-19:07 | -13.1 | -13.2 | 91498747.59 | 56.69 | 03-JAN-23:10 | -13.1 | -13.2 |
February | 2127801.16 | 258.12 | 07-FEB-19:04 | -1.1 | -2.8 | 83463105.98 | 56.69 | 23-FEB-00:20 | -22.8 | -23.0 |
March | 11585850.95 | 670.44 | 22-MAR-18:02 | 2.98 | 0.38 | 93744988.86 | 56.69 | 05-MAR-00:20 | 2.98 | 0.38 |
April | 0.131113E+09 | 1012.96 | 30-APR-18:01 | 9.72 | 3.97 | 92726524.36 | 56.69 | 21-APR-21:10 | 9.72 | 3.97 |
May | 0.437826E+09 | 1082.43 | 31-MAY-21:51 | 15.30 | 9.39 | 99605959.73 | 73.05 | 31-MAY-21:00 | 15.30 | 9.39 |
June | 0.629473E+09 | 1130.15 | 10-JUN-21:51 | 19.40 | 11.22 | 0.101035E+09 | 79.14 | 19-JUN-21:19 | 20.77 | 12.16 |
July | 0.637853E+09 | 1042.09 | 19-JUL-21:51 | 19.40 | 14.19 | 0.104237E+09 | 77.99 | 10-JUL-21:40 | 19.40 | 14.19 |
August | 0.463553E+09 | 1082.01 | 10-AUG-21:51 | 16.10 | 9.68 | 0.102090E+09 | 75.03 | 02-AUG-21:30 | 16.10 | 9.68 |
September | 0.198290E+09 | 992.59 | 10-SEP-18:01 | 15.32 | 9.12 | 93377776.06 | 56.69 | 01-SEP-21:10 | 15.32 | 9.12 |
October | 41136566.06 | 930.36 | 03-OCT-18:01 | 9.72 | 4.62 | 94379460.49 | 56.69 | 04-OCT-21:19 | 3.30 | 1.35 |
November | 689931.38 | 221.72 | 01-NOV-18:06 | -8.9 | -9.7 | 89101710.39 | 56.69 | 08-NOV-00:20 | -23.0 | -23.2 |
December | 600156.75 | 242.15 | 24-DEC-19:05 | -4.0 | -4.2 | 91705120.44 | 56.69 | 16-DEC-00:20 | -4.0 | -4.2 |
Annual Sum or Average | 0.255517E+10 | 0.113697E+10 | ||||||||
Minimum of Months | 600156.75 | 192.28 | -13.1 | -13.2 | 83463105.98 | 56.69 | -23.0 | -23.2 | ||
Maximum of Months | 0.637853E+09 | 1130.15 | 19.40 | 14.19 | 0.104237E+09 | 79.14 | 20.77 | 14.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 | -15.4 | 91411705.62 | 56.69 | 04-JAN-05:49 | -14.5 | -14.6 |
February | 2008662.58 | 438.21 | 09-FEB-16:15 | -0.3 | -1.2 | 83222644.13 | 56.69 | 23-FEB-00:20 | -22.8 | -23.0 |
March | 66077198.85 | 3512.45 | 22-MAR-15:11 | 5.60 | 2.35 | 94742376.09 | 56.69 | 06-MAR-05:19 | 5.60 | 2.35 |
April | 0.602966E+09 | 3602.76 | 22-APR-15:11 | 14.60 | 6.32 | 94760348.72 | 56.69 | 21-APR-21:30 | 14.60 | 6.32 |
May | 0.170807E+10 | 3669.04 | 13-MAY-08:61 | 14.60 | 6.29 | 99399335.99 | 56.69 | 31-MAY-21:30 | 16.00 | 9.64 |
June | 0.214547E+10 | 3610.79 | 07-JUN-15:12 | 19.40 | 10.06 | 96331100.85 | 56.70 | 30-JUN-21:49 | 17.82 | 14.24 |
July | 0.222979E+10 | 3220.36 | 08-JUL-08:61 | 15.78 | 13.66 | 99454241.27 | 56.70 | 14-JUL-21:40 | 16.47 | 14.16 |
August | 0.163958E+10 | 3596.89 | 10-AUG-18:02 | 22.62 | 12.07 | 99417119.08 | 56.70 | 25-AUG-21:49 | 15.65 | 12.71 |
September | 0.442299E+09 | 3564.18 | 07-SEP-15:11 | 16.47 | 8.91 | 94328750.07 | 56.69 | 01-SEP-01:30 | 16.47 | 8.91 |
October | 38849386.62 | 3174.85 | 04-OCT-08:62 | 7.88 | 2.97 | 93721498.94 | 56.69 | 27-OCT-04:10 | -17.7 | -18.2 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 88935062.76 | 56.69 | 11-NOV-00:20 | -20.0 | -20.3 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 91729677.55 | 56.69 | 23-DEC-04:30 | -5.8 | -6.9 |
Annual Sum or Average | 0.887511E+10 | 0.112745E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 83222644.13 | 56.69 | -22.8 | -23.0 | ||
Maximum of Months | 0.222979E+10 | 3669.04 | 22.62 | 13.66 | 99454241.27 | 56.70 | 17.82 | 14.24 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 | -15.4 | 91226102.46 | 56.69 | 16-JAN-00:30 | -10.3 | -10.8 |
February | 61280.75 | 196.08 | 08-FEB-19:06 | 0.22 | -1.6 | 82997933.60 | 56.69 | 02-FEB-04:19 | 0.22 | -1.6 |
March | 19350295.39 | 1049.32 | 11-MAR-09:01 | -8.9 | -9.9 | 93167931.52 | 56.69 | 05-MAR-00:20 | -8.9 | -9.9 |
April | 0.272874E+09 | 3260.03 | 22-APR-08:62 | 5.55 | 1.86 | 93399611.29 | 56.69 | 27-APR-21:10 | 7.43 | 3.48 |
May | 0.124810E+10 | 3475.58 | 14-MAY-20:41 | 13.68 | 7.57 | 0.101859E+09 | 76.64 | 12-MAY-21:10 | 13.68 | 7.57 |
June | 0.166285E+10 | 3603.84 | 10-JUN-21:51 | 19.40 | 11.22 | 0.103700E+09 | 81.28 | 22-JUN-21:30 | 20.00 | 11.87 |
July | 0.168524E+10 | 3755.51 | 22-JUL-08:32 | 20.37 | 15.09 | 0.107457E+09 | 83.28 | 07-JUL-21:19 | 20.37 | 15.09 |
August | 0.110198E+10 | 3262.55 | 31-AUG-08:62 | 2.48 | -0.9 | 0.104314E+09 | 78.64 | 02-AUG-21:19 | 2.48 | -0.9 |
September | 0.226259E+09 | 3212.72 | 10-SEP-15:11 | 15.40 | 8.69 | 93620231.43 | 56.69 | 01-SEP-01:10 | 15.40 | 8.69 |
October | 11400225.28 | 2093.35 | 04-OCT-08:62 | 7.88 | 2.97 | 92971089.06 | 56.69 | 31-OCT-23:19 | -10.3 | -11.2 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 88889631.39 | 56.69 | 18-NOV-04:10 | -4.1 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 91668437.16 | 56.69 | 23-DEC-05:00 | -3.9 | -5.1 |
Annual Sum or Average | 0.622812E+10 | 0.114527E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 82997933.60 | 56.69 | -10.3 | -11.2 | ||
Maximum of Months | 0.168524E+10 | 3755.51 | 20.37 | 15.09 | 0.107457E+09 | 83.28 | 20.37 | 15.09 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18971946.30 | 303.40 | 06-JAN-23:00 | -2.8 | -3.9 | 0.119250E+10 | 704.47 | 26-JAN-00:49 | -23.8 | -24.1 |
February | 0.164888E+09 | 728.20 | 08-FEB-22:05 | 0.73 | -1.8 | 0.108379E+10 | 704.48 | 18-FEB-05:10 | -23.9 | -24.3 |
March | 0.110287E+10 | 1391.81 | 22-MAR-20:00 | 2.80 | 0.30 | 0.120506E+10 | 721.70 | 22-MAR-21:49 | 1.78 | 0.04 |
April | 0.306202E+10 | 1918.37 | 22-APR-10:35 | 11.87 | 5.55 | 0.123315E+10 | 826.24 | 21-APR-21:30 | 11.87 | 5.55 |
May | 0.423172E+10 | 2144.00 | 14-MAY-10:35 | 16.83 | 8.94 | 0.141724E+10 | 897.63 | 12-MAY-21:40 | 16.83 | 8.94 |
June | 0.455865E+10 | 2255.11 | 13-JUN-10:35 | 21.83 | 12.30 | 0.147787E+10 | 951.85 | 22-JUN-22:10 | 19.22 | 11.60 |
July | 0.470584E+10 | 2303.78 | 23-JUL-10:35 | 22.23 | 15.22 | 0.151416E+10 | 951.85 | 12-JUL-22:10 | 22.23 | 15.22 |
August | 0.439048E+10 | 2152.95 | 01-AUG-10:35 | 15.93 | 12.83 | 0.145908E+10 | 933.42 | 02-AUG-21:40 | 19.80 | 14.37 |
September | 0.316658E+10 | 1871.14 | 10-SEP-10:35 | 13.87 | 7.59 | 0.123521E+10 | 832.02 | 01-SEP-21:49 | 13.87 | 7.59 |
October | 0.127064E+10 | 1502.19 | 03-OCT-10:40 | 5.37 | 3.67 | 0.120145E+10 | 734.09 | 03-OCT-22:10 | 7.30 | 3.10 |
November | 27219319.25 | 429.25 | 01-NOV-21:30 | -8.9 | -9.5 | 0.115952E+10 | 704.48 | 08-NOV-02:00 | -24.4 | -24.7 |
December | 5515665.36 | 313.09 | 24-DEC-22:50 | -3.6 | -4.0 | 0.119768E+10 | 704.48 | 22-DEC-00:00 | -3.6 | -4.0 |
Annual Sum or Average | 0.267054E+11 | 0.153767E+11 | ||||||||
Minimum of Months | 5515665.36 | 303.40 | -8.9 | -9.5 | 0.108379E+10 | 704.47 | -24.4 | -24.7 | ||
Maximum of Months | 0.470584E+10 | 2303.78 | 22.23 | 15.22 | 0.151416E+10 | 951.85 | 22.23 | 15.22 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 | -15.4 | 91178396.97 | 56.69 | 17-JAN-04:10 | -7.2 | -7.4 |
February | 282909.30 | 372.97 | 09-FEB-16:15 | -0.3 | -1.2 | 82993068.35 | 56.69 | 02-FEB-05:10 | -0.3 | -1.2 |
March | 32598466.11 | 3747.69 | 22-MAR-15:11 | 5.60 | 2.35 | 93091569.29 | 56.69 | 05-MAR-04:00 | 5.60 | 2.35 |
April | 0.635595E+09 | 4017.61 | 21-APR-18:01 | 14.22 | 5.92 | 93730934.36 | 56.69 | 28-APR-21:10 | 3.53 | 1.78 |
May | 0.118277E+10 | 4026.53 | 10-MAY-18:01 | 18.30 | 8.81 | 98738828.36 | 56.69 | 30-MAY-21:40 | 17.23 | 9.55 |
June | 0.186166E+10 | 4061.94 | 16-JUN-18:01 | 19.40 | 10.53 | 96076343.43 | 56.70 | 29-JUN-22:40 | 20.53 | 15.75 |
July | 0.179445E+10 | 3466.63 | 10-JUL-08:61 | 15.97 | 12.32 | 99169286.28 | 56.70 | 10-JUL-21:40 | 18.33 | 14.30 |
August | 0.130469E+10 | 4050.87 | 10-AUG-18:02 | 22.62 | 12.07 | 98850941.23 | 56.70 | 09-AUG-21:30 | 22.62 | 12.07 |
September | 0.280310E+09 | 3938.40 | 07-SEP-15:11 | 16.47 | 8.91 | 93109305.31 | 56.69 | 08-SEP-22:00 | 6.70 | 5.41 |
October | 11485333.65 | 2555.67 | 03-OCT-15:11 | 12.43 | 6.74 | 92748766.05 | 56.69 | 31-OCT-23:19 | -10.3 | -11.2 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 88890547.47 | 56.69 | 18-NOV-04:30 | -4.5 | -5.9 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 91650291.40 | 56.69 | 23-DEC-03:39 | -8.4 | -9.2 |
Annual Sum or Average | 0.710384E+10 | 0.112023E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 82993068.35 | 56.69 | -10.3 | -11.2 | ||
Maximum of Months | 0.186166E+10 | 4061.94 | 22.62 | 12.32 | 99169286.28 | 56.70 | 22.62 | 15.75 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 | -15.4 | 90909864.66 | 56.69 | 19-JAN-00:20 | -9.2 | -9.3 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -20.2 | -20.7 | 82886554.04 | 56.69 | 06-FEB-05:40 | -11.9 | -12.3 |
March | 1183789.20 | 872.60 | 22-MAR-15:13 | 5.60 | 2.35 | 92308802.05 | 56.69 | 11-MAR-05:10 | 5.60 | 2.35 |
April | 0.317578E+09 | 3590.06 | 21-APR-18:01 | 14.22 | 5.92 | 92140004.35 | 56.69 | 20-APR-21:19 | 14.22 | 5.92 |
May | 0.696887E+09 | 4455.62 | 09-MAY-19:42 | 14.27 | 6.45 | 0.103504E+09 | 95.37 | 10-MAY-21:10 | 14.13 | 6.05 |
June | 0.133876E+10 | 4006.52 | 28-JUN-21:32 | 18.87 | 14.85 | 0.108998E+09 | 113.08 | 28-JUN-21:10 | 18.87 | 14.85 |
July | 0.128203E+10 | 3731.21 | 06-JUL-21:51 | 18.90 | 13.76 | 0.109320E+09 | 94.09 | 11-JUL-21:10 | 21.83 | 13.37 |
August | 0.746637E+09 | 3567.27 | 01-AUG-21:51 | 16.70 | 13.45 | 0.106495E+09 | 99.37 | 10-AUG-21:10 | 17.93 | 10.68 |
September | 0.103624E+09 | 3481.93 | 07-SEP-18:01 | 14.13 | 7.59 | 92165495.78 | 56.69 | 12-SEP-21:10 | 11.02 | 7.51 |
October | 2635556.62 | 1042.66 | 01-OCT-15:13 | 13.70 | 7.69 | 92236014.68 | 56.69 | 30-OCT-03:49 | -14.2 | -15.0 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 88782533.85 | 56.69 | 11-NOV-00:20 | -20.0 | -20.3 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 91495824.34 | 56.69 | 23-DEC-04:49 | -5.3 | -6.4 |
Annual Sum or Average | 0.448934E+10 | 0.115124E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 82886554.04 | 56.69 | -20.0 | -20.3 | ||
Maximum of Months | 0.133876E+10 | 4455.62 | 18.90 | 14.85 | 0.109320E+09 | 113.08 | 21.83 | 14.85 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1130290.19 | 216.92 | 30-JAN-13:55 | -23.9 | -24.3 | 91761548.52 | 56.69 | 04-JAN-00:20 | -23.9 | -24.3 |
February | 20162811.98 | 2556.60 | 15-FEB-16:11 | -7.4 | -8.8 | 84452988.52 | 56.69 | 23-FEB-00:20 | -22.8 | -23.0 |
March | 0.220535E+09 | 2648.70 | 31-MAR-15:11 | -9.8 | -12.1 | 96010761.20 | 56.69 | 22-MAR-21:19 | -9.8 | -12.1 |
April | 0.704859E+09 | 2706.14 | 20-APR-15:11 | 13.70 | 6.18 | 95117722.94 | 56.69 | 27-APR-21:49 | 5.97 | 2.67 |
May | 0.984298E+09 | 2667.74 | 09-MAY-15:12 | 17.40 | 7.98 | 99104056.28 | 56.69 | 31-MAY-23:30 | 13.10 | 8.38 |
June | 0.119537E+10 | 2630.90 | 16-JUN-18:01 | 19.40 | 10.53 | 96140997.24 | 56.70 | 29-JUN-21:49 | 22.88 | 16.35 |
July | 0.126502E+10 | 2617.41 | 13-JUL-18:02 | 23.90 | 13.18 | 99259940.65 | 56.70 | 20-JUL-21:40 | 18.53 | 13.35 |
August | 0.111637E+10 | 2674.48 | 31-AUG-15:11 | 14.27 | 5.23 | 99183993.78 | 56.70 | 25-AUG-21:40 | 14.27 | 5.23 |
September | 0.481911E+09 | 2650.57 | 30-SEP-15:11 | 2.97 | -0.7 | 94693602.61 | 56.69 | 07-SEP-21:49 | 2.97 | -0.7 |
October | 0.115909E+09 | 2609.90 | 14-OCT-15:11 | 3.90 | -0.9 | 94905963.24 | 56.69 | 04-OCT-21:19 | 3.90 | -0.9 |
November | 1980536.36 | 1000.97 | 08-NOV-16:12 | -16.8 | -17.1 | 89224968.88 | 56.69 | 11-NOV-00:20 | -20.0 | -20.3 |
December | 20059.26 | 200.59 | 24-DEC-09:05 | 0.18 | -1.3 | 91755967.49 | 56.69 | 16-DEC-00:20 | 0.18 | -1.3 |
Annual Sum or Average | 0.610756E+10 | 0.113161E+10 | ||||||||
Minimum of Months | 20059.26 | 200.59 | -23.9 | -24.3 | 84452988.52 | 56.69 | -23.9 | -24.3 | ||
Maximum of Months | 0.126502E+10 | 2706.14 | 23.90 | 13.18 | 99259940.65 | 56.70 | 22.88 | 16.35 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294390E+11 | 15803.07 | 06-JAN-23:10 | -3.0 | -4.1 | 0.151823E+11 | 10227.17 | 06-JAN-23:10 | -3.0 | -4.1 |
February | 0.276973E+11 | 17046.71 | 28-FEB-23:00 | -29.3 | -29.5 | 0.138371E+11 | 10479.75 | 08-FEB-23:00 | -29.3 | -29.5 |
March | 0.331924E+11 | 16917.46 | 22-MAR-21:00 | 2.20 | 0.09 | 0.157688E+11 | 10739.94 | 22-MAR-22:10 | 1.42 | -0.3 |
April | 0.366709E+11 | 18234.40 | 21-APR-20:30 | 11.10 | 4.35 | 0.159829E+11 | 11193.81 | 21-APR-22:10 | 6.83 | 2.10 |
May | 0.424683E+11 | 19751.91 | 31-MAY-21:10 | 16.47 | 9.79 | 0.174305E+11 | 11349.23 | 11-MAY-21:40 | 16.47 | 9.79 |
June | 0.436547E+11 | 21790.55 | 21-JUN-21:03 | 23.53 | 13.66 | 0.174136E+11 | 11349.24 | 28-JUN-22:10 | 18.12 | 14.78 |
July | 0.450334E+11 | 21345.72 | 11-JUL-21:10 | 21.83 | 13.37 | 0.178403E+11 | 11349.25 | 10-JUL-22:10 | 21.83 | 13.37 |
August | 0.432581E+11 | 20862.44 | 02-AUG-21:10 | 20.40 | 14.60 | 0.176628E+11 | 11349.22 | 01-AUG-22:10 | 20.40 | 14.60 |
September | 0.379714E+11 | 18233.24 | 01-SEP-21:00 | 11.10 | 8.75 | 0.163009E+11 | 11230.72 | 01-SEP-22:10 | 9.90 | 8.27 |
October | 0.348139E+11 | 17303.40 | 06-OCT-21:00 | 7.80 | 3.59 | 0.160714E+11 | 10897.88 | 06-OCT-22:10 | 7.12 | 3.42 |
November | 0.286843E+11 | 16833.76 | 28-NOV-23:00 | -28.9 | -29.1 | 0.146789E+11 | 10246.55 | 03-NOV-22:10 | -28.9 | -29.1 |
December | 0.288775E+11 | 16997.92 | 14-DEC-22:30 | -28.6 | -28.8 | 0.150128E+11 | 10088.04 | 19-DEC-23:10 | -8.7 | -9.2 |
Annual Sum or Average | 0.431761E+12 | 0.193182E+12 | ||||||||
Minimum of Months | 0.276973E+11 | 15803.07 | -29.3 | -29.5 | 0.138371E+11 | 10088.04 | -29.3 | -29.5 | ||
Maximum of Months | 0.450334E+11 | 21790.55 | 23.53 | 14.60 | 0.178403E+11 | 11349.25 | 21.83 | 14.78 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323551E+11 | 17547.30 | 11-JAN-22:20 | -34.8 | -34.9 | 0.156117E+11 | 10612.60 | 06-JAN-23:10 | -34.8 | -34.9 |
February | 0.303060E+11 | 18062.94 | 28-FEB-22:20 | -29.5 | -29.7 | 0.142301E+11 | 10880.89 | 08-FEB-23:00 | -29.5 | -29.7 |
March | 0.359562E+11 | 17807.53 | 22-MAR-21:00 | 2.20 | 0.09 | 0.162946E+11 | 11151.35 | 22-MAR-22:10 | 1.42 | -0.3 |
April | 0.388227E+11 | 18993.45 | 21-APR-21:10 | 9.53 | 3.30 | 0.165187E+11 | 11344.42 | 21-APR-22:10 | 6.83 | 2.10 |
May | 0.442450E+11 | 21096.18 | 10-MAY-21:07 | 14.13 | 6.05 | 0.178726E+11 | 11349.22 | 11-MAY-21:40 | 12.20 | 6.17 |
June | 0.453390E+11 | 22463.08 | 21-JUN-21:03 | 23.53 | 13.66 | 0.177910E+11 | 11349.24 | 28-JUN-22:10 | 18.12 | 14.78 |
July | 0.467377E+11 | 22593.61 | 11-JUL-21:10 | 21.83 | 13.37 | 0.182326E+11 | 11349.25 | 10-JUL-22:10 | 21.83 | 13.37 |
August | 0.449517E+11 | 21453.76 | 02-AUG-21:52 | 19.40 | 14.21 | 0.180691E+11 | 11349.22 | 01-AUG-22:10 | 19.40 | 14.21 |
September | 0.400629E+11 | 19324.19 | 01-SEP-21:10 | 10.92 | 8.67 | 0.168542E+11 | 11344.94 | 07-SEP-22:49 | 9.50 | 6.17 |
October | 0.375676E+11 | 18245.71 | 06-OCT-21:00 | 7.80 | 3.59 | 0.166646E+11 | 11334.72 | 06-OCT-22:10 | 7.12 | 3.42 |
November | 0.314944E+11 | 17517.53 | 28-NOV-23:00 | -28.9 | -29.1 | 0.150857E+11 | 10636.69 | 03-NOV-22:10 | -28.9 | -29.1 |
December | 0.317834E+11 | 18201.94 | 14-DEC-23:00 | -29.4 | -29.6 | 0.153970E+11 | 10460.67 | 19-DEC-23:10 | -8.7 | -9.2 |
Annual Sum or Average | 0.459622E+12 | 0.198622E+12 | ||||||||
Minimum of Months | 0.303060E+11 | 17517.53 | -34.8 | -34.9 | 0.142301E+11 | 10460.67 | -34.8 | -34.9 | ||
Maximum of Months | 0.467377E+11 | 22593.61 | 23.53 | 14.21 | 0.182326E+11 | 11349.25 | 21.83 | 14.78 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.415668E+11 | 23874.83 | 22-JAN-11:50 | -6.6 | -6.9 | 0.188593E+11 | 11319.72 | 14-JAN-18:10 | -6.6 | -6.9 |
February | 0.389675E+11 | 25252.06 | 09-FEB-11:50 | -2.0 | -2.3 | 0.170395E+11 | 11319.71 | 25-FEB-18:10 | -23.0 | -23.5 |
March | 0.462139E+11 | 27437.33 | 22-MAR-10:40 | 2.43 | 0.50 | 0.188753E+11 | 11319.66 | 04-MAR-18:10 | 2.43 | 0.50 |
April | 0.486483E+11 | 29522.37 | 22-APR-10:50 | 12.33 | 5.78 | 0.182622E+11 | 11319.68 | 22-APR-17:10 | 14.13 | 6.18 |
May | 0.543257E+11 | 30010.71 | 12-MAY-10:40 | 17.43 | 8.33 | 0.188716E+11 | 11319.65 | 06-MAY-17:10 | 17.43 | 8.33 |
June | 0.543051E+11 | 30530.16 | 29-JUN-10:50 | 22.02 | 15.69 | 0.182659E+11 | 11319.68 | 10-JUN-17:10 | 22.02 | 15.69 |
July | 0.561862E+11 | 31170.94 | 22-JUL-10:40 | 23.67 | 16.46 | 0.188681E+11 | 11319.69 | 29-JUL-17:10 | 29.53 | 18.36 |
August | 0.545745E+11 | 30259.49 | 10-AUG-10:50 | 19.13 | 11.78 | 0.188753E+11 | 11319.69 | 26-AUG-17:10 | 21.02 | 13.58 |
September | 0.492294E+11 | 29105.14 | 10-SEP-10:50 | 14.13 | 7.69 | 0.182615E+11 | 11319.66 | 09-SEP-17:10 | 14.13 | 7.69 |
October | 0.468001E+11 | 27324.65 | 03-OCT-10:40 | 5.37 | 3.67 | 0.188688E+11 | 11319.66 | 28-OCT-17:10 | -8.9 | -9.3 |
November | 0.404333E+11 | 23589.03 | 01-NOV-18:03 | -8.9 | -9.7 | 0.182564E+11 | 11319.72 | 25-NOV-18:10 | -21.0 | -21.2 |
December | 0.408543E+11 | 24019.42 | 24-DEC-11:50 | 1.60 | -0.2 | 0.188639E+11 | 11319.71 | 16-DEC-18:10 | 1.60 | -0.2 |
Annual Sum or Average | 0.572105E+12 | 0.222168E+12 | ||||||||
Minimum of Months | 0.389675E+11 | 23589.03 | -8.9 | -9.7 | 0.170395E+11 | 11319.65 | -23.0 | -23.5 | ||
Maximum of Months | 0.561862E+11 | 31170.94 | 23.67 | 16.46 | 0.188753E+11 | 11319.72 | 29.53 | 18.36 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 | -15.4 | 0.125506E+10 | 745.68 | 26-JAN-01:10 | -23.9 | -24.2 |
February | 55987551.74 | 1246.35 | 09-FEB-13:40 | -0.4 | -1.6 | 0.114623E+10 | 745.76 | 18-FEB-05:10 | -23.9 | -24.3 |
March | 0.901630E+09 | 1655.72 | 22-MAR-10:35 | 2.43 | 0.50 | 0.127967E+10 | 801.35 | 22-MAR-21:49 | 1.78 | 0.04 |
April | 0.349424E+10 | 3183.74 | 22-APR-14:00 | 15.60 | 7.03 | 0.137628E+10 | 978.46 | 21-APR-21:30 | 15.60 | 7.03 |
May | 0.567114E+10 | 5096.20 | 31-MAY-14:10 | 20.18 | 10.25 | 0.164058E+10 | 1007.40 | 11-MAY-21:40 | 20.18 | 10.25 |
June | 0.767092E+10 | 5931.37 | 29-JUN-14:20 | 25.77 | 16.19 | 0.165700E+10 | 1007.43 | 02-JUN-22:10 | 25.77 | 16.19 |
July | 0.790840E+10 | 6315.14 | 23-JUL-13:40 | 25.00 | 15.26 | 0.170383E+10 | 1007.44 | 01-JUL-00:10 | 25.00 | 15.26 |
August | 0.637706E+10 | 5364.19 | 10-AUG-15:10 | 22.30 | 12.06 | 0.168106E+10 | 1007.42 | 01-AUG-01:10 | 22.30 | 12.06 |
September | 0.395224E+10 | 2301.80 | 02-SEP-15:13 | 16.70 | 10.68 | 0.141031E+10 | 958.60 | 01-SEP-21:40 | 16.70 | 10.68 |
October | 0.145080E+10 | 1685.84 | 03-OCT-10:40 | 5.37 | 3.67 | 0.128640E+10 | 829.45 | 03-OCT-22:10 | 7.30 | 3.10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.122671E+10 | 745.71 | 08-NOV-02:30 | -24.1 | -24.4 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 0.126655E+10 | 745.68 | 19-DEC-03:30 | -24.5 | -24.7 |
Annual Sum or Average | 0.374824E+11 | 0.169297E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.114623E+10 | 745.68 | -24.5 | -24.7 | ||
Maximum of Months | 0.790840E+10 | 6315.14 | 25.77 | 16.19 | 0.170383E+10 | 1007.44 | 25.77 | 16.19 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333037E+10 | 2589.64 | 13-JAN-16:10 | -23.6 |
February | 0.174687E+10 | 1924.71 | 28-FEB-08:07 | -25.6 |
March | 0.619540E+09 | 1918.99 | 01-MAR-08:10 | -28.1 |
April | 44499695.96 | 790.38 | 03-APR-06:05 | -21.5 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 2738455.82 | 244.79 | 30-SEP-06:55 | -5.0 |
October | 0.463743E+09 | 1407.96 | 30-OCT-08:30 | -16.7 |
November | 0.286098E+10 | 2097.70 | 30-NOV-16:00 | -25.6 |
December | 0.407073E+10 | 2311.02 | 06-DEC-14:30 | -25.0 |
Annual Sum or Average | 0.131395E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.1 | |
Maximum of Months | 0.407073E+10 | 2589.64 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12908882.70 | 439.82 | 13-JAN-16:00 | -23.9 |
February | 951349.31 | 93.14 | 27-FEB-12:30 | -30.9 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 3557497.93 | 178.81 | 29-NOV-10:51 | -28.3 |
December | 25435423.02 | 185.79 | 14-DEC-14:40 | -24.6 |
Annual Sum or Average | 42853152.96 | |||
Minimum of Months | 0.00 | 0.00 | -30.9 | |
Maximum of Months | 25435423.02 | 439.82 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122038E+10 | 1277.24 | 13-JAN-16:10 | -23.6 |
February | 0.831381E+09 | 1085.11 | 27-FEB-13:30 | -29.4 |
March | 0.333420E+09 | 991.78 | 01-MAR-05:00 | -28.3 |
April | 9079511.80 | 235.30 | 03-APR-09:30 | -13.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 73842027.46 | 393.43 | 31-OCT-09:53 | -16.7 |
November | 0.994050E+09 | 1037.62 | 30-NOV-10:53 | -28.9 |
December | 0.146059E+10 | 1070.44 | 15-DEC-17:51 | -29.4 |
Annual Sum or Average | 0.492274E+10 | |||
Minimum of Months | 0.00 | 0.00 | -29.4 | |
Maximum of Months | 0.146059E+10 | 1277.24 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138978E+10 | 986.47 | 13-JAN-16:10 | -23.6 |
February | 0.103922E+10 | 870.14 | 27-FEB-17:51 | -25.6 |
March | 0.605453E+09 | 849.20 | 01-MAR-09:35 | -24.6 |
April | 63752961.80 | 380.05 | 03-APR-08:03 | -17.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.233946E+09 | 488.26 | 27-OCT-09:10 | -19.5 |
November | 0.125498E+10 | 878.76 | 29-NOV-14:00 | -24.4 |
December | 0.159443E+10 | 896.56 | 06-DEC-14:00 | -24.4 |
Annual Sum or Average | 0.618157E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.159443E+10 | 986.47 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.857207E+09 | 3954.95 | 13-JAN-15:00 | -25.6 |
February | 81533719.75 | 1772.98 | 27-FEB-15:00 | -28.3 |
March | 3744601.69 | 912.71 | 01-MAR-08:10 | -28.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 6007962.70 | 1160.89 | 30-OCT-08:40 | -16.7 |
November | 0.516771E+09 | 2702.08 | 27-NOV-10:20 | -27.2 |
December | 0.157794E+10 | 3656.05 | 14-DEC-15:00 | -24.4 |
Annual Sum or Average | 0.304321E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.3 | |
Maximum of Months | 0.157794E+10 | 3954.95 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34442525.68 | 4274.50 | 13-JAN-14:40 | -26.0 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 820086.16 | 398.81 | 30-NOV-10:20 | -28.5 |
December | 16776189.05 | 847.86 | 14-DEC-14:40 | -24.6 |
Annual Sum or Average | 52038800.89 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 34442525.68 | 4274.50 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296761E+10 | 2223.41 | 13-JAN-16:23 | -23.0 |
February | 0.211034E+10 | 2167.82 | 25-FEB-16:23 | -21.9 |
March | 0.137986E+10 | 2138.48 | 06-MAR-09:01 | -15.2 |
April | 0.297655E+09 | 2108.88 | 03-APR-08:62 | -17.1 |
May | 13333393.82 | 1252.93 | 01-MAY-08:03 | 10.87 |
June | 2479320.86 | 1156.69 | 08-JUN-08:04 | 13.68 |
July | 2783032.57 | 1194.51 | 06-JUL-08:03 | 14.60 |
August | 7377653.88 | 1333.39 | 19-AUG-08:03 | 8.98 |
September | 0.197054E+09 | 2086.24 | 28-SEP-08:61 | -2.0 |
October | 0.116663E+10 | 2147.27 | 27-OCT-08:62 | -18.2 |
November | 0.269030E+10 | 2182.86 | 26-NOV-16:23 | -22.8 |
December | 0.324781E+10 | 2198.85 | 06-DEC-16:23 | -23.1 |
Annual Sum or Average | 0.140832E+11 | |||
Minimum of Months | 2479320.86 | 1156.69 | -23.1 | |
Maximum of Months | 0.324781E+10 | 2223.41 | 14.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305446E+10 | 2339.03 | 12-JAN-17:54 | -36.7 |
February | 0.239343E+10 | 2119.38 | 24-FEB-16:12 | -21.9 |
March | 0.177767E+10 | 2108.18 | 03-MAR-09:02 | -21.0 |
April | 0.443303E+09 | 2068.87 | 03-APR-08:62 | -17.1 |
May | 17439668.52 | 1132.51 | 01-MAY-08:03 | 10.87 |
June | 1543271.04 | 1057.52 | 06-JUN-08:04 | 11.28 |
July | 2042581.17 | 1177.97 | 05-JUL-18:04 | 11.10 |
August | 10755612.94 | 1207.02 | 14-AUG-18:04 | 15.40 |
September | 0.273024E+09 | 2055.06 | 30-SEP-08:61 | -5.0 |
October | 0.138646E+10 | 2096.13 | 27-OCT-08:62 | -18.2 |
November | 0.284319E+10 | 2126.85 | 26-NOV-16:23 | -22.8 |
December | 0.327559E+10 | 2135.80 | 06-DEC-16:23 | -23.1 |
Annual Sum or Average | 0.154789E+11 | |||
Minimum of Months | 1543271.04 | 1057.52 | -36.7 | |
Maximum of Months | 0.327559E+10 | 2339.03 | 15.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.544109E+09 | 461.24 | 12-JAN-04:10 | -37.3 |
February | 0.195410E+09 | 339.16 | 27-FEB-05:10 | -36.1 |
March | 17478172.67 | 312.03 | 01-MAR-05:00 | -28.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 14248893.44 | 179.19 | 30-OCT-04:00 | -14.4 |
November | 0.426378E+09 | 368.86 | 29-NOV-05:00 | -28.9 |
December | 0.676985E+09 | 431.28 | 15-DEC-05:00 | -33.3 |
Annual Sum or Average | 0.187461E+10 | |||
Minimum of Months | 0.00 | 0.00 | -37.3 | |
Maximum of Months | 0.676985E+09 | 461.24 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.590621E+09 | 633.98 | 12-JAN-10:53 | -37.2 |
February | 0.452629E+09 | 600.70 | 28-FEB-16:12 | -22.6 |
March | 0.314882E+09 | 598.96 | 02-MAR-16:11 | -12.2 |
April | 56219212.37 | 579.76 | 02-APR-15:11 | -6.9 |
May | 534998.05 | 488.00 | 26-MAY-15:14 | 5.73 |
June | 59950.34 | 238.75 | 01-JUN-18:46 | 14.60 |
July | 56146.91 | 169.60 | 31-JUL-21:56 | 19.60 |
August | 188723.77 | 240.02 | 31-AUG-08:03 | 2.48 |
September | 7051874.42 | 558.00 | 30-SEP-15:11 | 2.97 |
October | 0.170012E+09 | 596.74 | 22-OCT-15:11 | -9.4 |
November | 0.548273E+09 | 598.98 | 25-NOV-16:12 | -20.4 |
December | 0.657189E+09 | 595.26 | 08-DEC-16:12 | -22.1 |
Annual Sum or Average | 0.279772E+10 | |||
Minimum of Months | 56146.91 | 169.60 | -37.2 | |
Maximum of Months | 0.657189E+09 | 633.98 | 19.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293459E+10 | 2185.92 | 13-JAN-16:23 | -23.0 |
February | 0.199225E+10 | 2133.67 | 25-FEB-16:23 | -21.9 |
March | 0.114733E+10 | 2097.97 | 01-MAR-19:02 | -19.7 |
April | 0.291994E+09 | 2057.73 | 04-APR-08:62 | -8.0 |
May | 8652388.29 | 1200.08 | 27-MAY-18:03 | 7.52 |
June | 1123697.34 | 1117.16 | 24-JUN-18:04 | 12.12 |
July | 1816418.12 | 1180.46 | 04-JUL-18:04 | 12.12 |
August | 5500449.36 | 1155.64 | 14-AUG-08:04 | 11.88 |
September | 0.157511E+09 | 2026.75 | 27-SEP-15:11 | 3.50 |
October | 0.104024E+10 | 2114.45 | 27-OCT-08:62 | -18.2 |
November | 0.268427E+10 | 2146.65 | 26-NOV-16:23 | -22.8 |
December | 0.324152E+10 | 2161.25 | 06-DEC-16:23 | -23.1 |
Annual Sum or Average | 0.135068E+11 | |||
Minimum of Months | 1123697.34 | 1117.16 | -23.1 | |
Maximum of Months | 0.324152E+10 | 2185.92 | 12.12 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301886E+10 | 2286.87 | 12-JAN-17:54 | -36.7 |
February | 0.226094E+10 | 2091.27 | 28-FEB-16:12 | -22.6 |
March | 0.148929E+10 | 2074.91 | 02-MAR-16:11 | -12.2 |
April | 0.444176E+09 | 2022.65 | 03-APR-15:11 | -5.4 |
May | 12143178.51 | 1286.09 | 28-MAY-20:43 | 13.68 |
June | 934058.07 | 1127.58 | 24-JUN-18:04 | 12.12 |
July | 1147723.14 | 1105.36 | 26-JUL-08:04 | 12.38 |
August | 7614152.65 | 1187.76 | 14-AUG-08:04 | 11.88 |
September | 0.219846E+09 | 1999.08 | 27-SEP-15:11 | 3.50 |
October | 0.123281E+10 | 2064.52 | 27-OCT-08:62 | -18.2 |
November | 0.283689E+10 | 2095.19 | 25-NOV-16:12 | -20.4 |
December | 0.326801E+10 | 2186.73 | 15-DEC-10:55 | -33.3 |
Annual Sum or Average | 0.147927E+11 | |||
Minimum of Months | 934058.07 | 1105.36 | -36.7 | |
Maximum of Months | 0.326801E+10 | 2286.87 | 13.68 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202894E+10 | 1895.98 | 13-JAN-16:10 | -23.6 |
February | 0.953700E+09 | 1555.00 | 27-FEB-16:00 | -27.2 |
March | 0.173309E+09 | 1277.60 | 01-MAR-08:63 | -28.1 |
April | 7257784.76 | 417.85 | 03-APR-08:03 | -17.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.194908E+09 | 1064.76 | 30-OCT-08:03 | -16.7 |
November | 0.167360E+10 | 1646.35 | 27-NOV-15:00 | -23.9 |
December | 0.252186E+10 | 1759.91 | 06-DEC-14:00 | -24.4 |
Annual Sum or Average | 0.755357E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.1 | |
Maximum of Months | 0.252186E+10 | 1895.98 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.393384E+10 | 2744.39 | 12-JAN-17:54 | -36.7 |
February | 0.288585E+10 | 2572.58 | 25-FEB-16:23 | -21.9 |
March | 0.197155E+10 | 2525.60 | 15-MAR-08:62 | -22.4 |
April | 0.502266E+09 | 2484.92 | 03-APR-08:62 | -17.1 |
May | 46188933.31 | 1702.56 | 27-MAY-08:62 | 0.68 |
June | 2257436.84 | 1197.15 | 25-JUN-18:03 | 13.98 |
July | 3127910.67 | 1020.10 | 06-JUL-08:03 | 14.60 |
August | 22922525.50 | 2333.73 | 30-AUG-08:62 | 2.07 |
September | 0.375172E+09 | 2472.10 | 30-SEP-08:61 | -5.0 |
October | 0.170025E+10 | 2536.14 | 27-OCT-08:62 | -18.2 |
November | 0.361824E+10 | 2593.74 | 26-NOV-16:23 | -22.8 |
December | 0.427074E+10 | 2776.01 | 15-DEC-17:54 | -29.4 |
Annual Sum or Average | 0.193324E+11 | |||
Minimum of Months | 2257436.84 | 1020.10 | -36.7 | |
Maximum of Months | 0.427074E+10 | 2776.01 | 14.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.402945E+10 | 2720.15 | 12-JAN-07:53 | -38.3 |
February | 0.320415E+10 | 2496.66 | 25-FEB-16:23 | -21.9 |
March | 0.246234E+10 | 2476.72 | 03-MAR-09:02 | -21.0 |
April | 0.713959E+09 | 2425.44 | 03-APR-08:62 | -17.1 |
May | 58149913.41 | 1901.72 | 27-MAY-08:62 | 0.68 |
June | 2138945.89 | 1108.56 | 28-JUN-08:04 | 11.97 |
July | 2240753.16 | 1099.73 | 04-JUL-18:04 | 12.12 |
August | 29659854.82 | 2281.80 | 31-AUG-08:62 | 2.48 |
September | 0.505275E+09 | 2406.98 | 30-SEP-08:61 | -5.0 |
October | 0.197062E+10 | 2460.91 | 27-OCT-08:62 | -18.2 |
November | 0.378858E+10 | 2510.57 | 26-NOV-16:23 | -22.8 |
December | 0.429932E+10 | 2523.05 | 06-DEC-16:23 | -23.1 |
Annual Sum or Average | 0.210659E+11 | |||
Minimum of Months | 2138945.89 | 1099.73 | -38.3 | |
Maximum of Months | 0.429932E+10 | 2720.15 | 12.12 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175070E+10 | 1480.13 | 13-JAN-16:23 | -23.0 |
February | 0.102894E+10 | 1432.45 | 01-FEB-16:23 | -12.2 |
March | 0.556892E+09 | 1389.15 | 13-MAR-08:62 | -23.0 |
April | 0.102204E+09 | 1375.43 | 03-APR-08:62 | -17.1 |
May | 5898444.86 | 915.41 | 01-MAY-08:03 | 10.87 |
June | 1313406.90 | 679.19 | 25-JUN-15:14 | 12.77 |
July | 1297586.01 | 631.95 | 06-JUL-08:03 | 14.60 |
August | 2542250.64 | 719.20 | 20-AUG-08:03 | 6.78 |
September | 55700719.46 | 1342.21 | 28-SEP-08:61 | -2.0 |
October | 0.503194E+09 | 1406.99 | 30-OCT-08:62 | -16.7 |
November | 0.152528E+10 | 1448.78 | 17-NOV-16:23 | -18.6 |
December | 0.201149E+10 | 1471.86 | 06-DEC-16:23 | -23.1 |
Annual Sum or Average | 0.754546E+10 | |||
Minimum of Months | 1297586.01 | 631.95 | -23.1 | |
Maximum of Months | 0.201149E+10 | 1480.13 | 14.60 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.748353E+10 | 5609.02 | 13-JAN-16:10 | -23.6 |
February | 0.462283E+10 | 4497.06 | 28-FEB-07:10 | -25.6 |
March | 0.183869E+10 | 4512.47 | 01-MAR-08:25 | -27.8 |
April | 0.172076E+09 | 2370.44 | 03-APR-06:10 | -21.5 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 1554212.19 | 261.05 | 30-SEP-06:55 | -5.0 |
October | 0.110514E+10 | 3050.48 | 27-OCT-08:15 | -18.5 |
November | 0.693957E+10 | 4896.51 | 30-NOV-16:00 | -25.6 |
December | 0.886588E+10 | 5119.37 | 06-DEC-15:30 | -24.5 |
Annual Sum or Average | 0.310293E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.8 | |
Maximum of Months | 0.886588E+10 | 5609.02 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104372E+11 | 10053.14 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.942384E+10 | 10053.14 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.104694E+11 | 10053.14 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.100833E+11 | 10053.14 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.104553E+11 | 10053.14 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.101296E+11 | 10053.14 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.104091E+11 | 10053.14 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.104734E+11 | 10053.14 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.100874E+11 | 10053.14 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.104332E+11 | 10053.14 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.101215E+11 | 10053.14 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.104091E+11 | 10053.14 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.122932E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.942384E+10 | 10053.14 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.104734E+11 | 10053.14 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531884E+09 | 512.31 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.480243E+09 | 512.31 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.533523E+09 | 512.31 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.513850E+09 | 512.31 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.532806E+09 | 512.31 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.516207E+09 | 512.31 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.530449E+09 | 512.31 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.533728E+09 | 512.31 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.514055E+09 | 512.31 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.531679E+09 | 512.31 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.515797E+09 | 512.31 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.530449E+09 | 512.31 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.626467E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.480243E+09 | 512.31 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.533728E+09 | 512.31 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.615923E+09 | 593.26 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.556123E+09 | 593.26 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.617822E+09 | 593.26 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.595041E+09 | 593.26 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.616991E+09 | 593.26 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.597770E+09 | 593.26 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.614262E+09 | 593.26 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.618059E+09 | 593.26 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.595278E+09 | 593.26 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.615686E+09 | 593.26 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.597295E+09 | 593.26 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.614262E+09 | 593.26 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.725451E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.556123E+09 | 593.26 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.618059E+09 | 593.26 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.195918E+09 | 188.71 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.176896E+09 | 188.71 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.196522E+09 | 188.71 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.189275E+09 | 188.71 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.196257E+09 | 188.71 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.190143E+09 | 188.71 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.195389E+09 | 188.71 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.196597E+09 | 188.71 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.189351E+09 | 188.71 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.195842E+09 | 188.71 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.189992E+09 | 188.71 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.195389E+09 | 188.71 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.230757E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.176896E+09 | 188.71 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.196597E+09 | 188.71 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417273E+09 | 400.68 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.402047E+09 | 400.68 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415830E+09 | 400.68 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489965E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.150742E+10 | 1573.46 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.121599E+10 | 1573.46 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.116335E+10 | 1573.46 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.815738E+09 | 1573.46 | 03-APR-19:40 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.719412E+09 | 1398.63 | 04-MAY-20:30 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.589381E+09 | 1214.60 | 02-JUN-20:00 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.655449E+09 | 1263.59 | 28-JUL-20:00 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.835107E+09 | 1573.46 | 29-AUG-19:30 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.104808E+10 | 1573.46 | 01-SEP-19:30 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.129369E+10 | 1573.46 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.139489E+10 | 1573.46 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.157259E+10 | 1573.46 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.128111E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.589381E+09 | 1214.60 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.157259E+10 | 1573.46 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.818709E+10 | 7984.04 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.725700E+10 | 7984.04 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.789805E+10 | 7984.04 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.735588E+10 | 7984.04 | 03-APR-19:40 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.752271E+10 | 7809.31 | 02-MAY-19:00 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.719448E+10 | 7667.15 | 02-JUN-19:00 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.744075E+10 | 7625.65 | 28-JUL-19:00 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.763635E+10 | 7984.04 | 29-AUG-19:30 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.755492E+10 | 7984.04 | 01-SEP-19:30 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.798827E+10 | 7984.04 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.787865E+10 | 7984.04 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.822770E+10 | 7984.04 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.921419E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.719448E+10 | 7625.65 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.822770E+10 | 7984.04 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65789991.58 | 59.53 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 59414784.75 | 59.53 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 65267117.48 | 59.53 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 63743496.62 | 59.53 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 65528554.53 | 59.53 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 63237765.93 | 59.53 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 66042856.93 | 59.53 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 65267117.48 | 59.53 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 63760640.03 | 59.53 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 65781419.88 | 59.53 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 63490631.27 | 59.53 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 66051428.64 | 59.53 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.773376E+09 | 0.256575E+10 | ||||
Minimum of Months | 59414784.75 | 59.53 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 66051428.64 | 59.53 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.120431E+10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.108739E+10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.120803E+10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.116348E+10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.120640E+10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.116882E+10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.120107E+10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.120849E+10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.116395E+10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.120385E+10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.116789E+10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.120107E+10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141847E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.108739E+10 | 1160.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120849E+10 | 1160.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.281025E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.241048E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.248641E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.207938E+10 | 2763.12 | 03-APR-19:40 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.199717E+10 | 2456.11 | 04-MAY-20:30 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.183788E+10 | 2332.05 | 02-JUN-19:00 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.194254E+10 | 2341.32 | 26-JUL-20:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.214270E+10 | 2763.12 | 29-AUG-19:30 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.232873E+10 | 2763.12 | 01-SEP-19:30 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.260940E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.268158E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.284327E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.281698E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.183788E+10 | 2332.05 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.284327E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.281025E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.241048E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.248641E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.207938E+10 | 2763.12 | 03-APR-19:40 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.199717E+10 | 2456.11 | 04-MAY-20:30 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.183788E+10 | 2332.05 | 02-JUN-19:00 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.194254E+10 | 2341.32 | 26-JUL-20:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.214270E+10 | 2763.12 | 29-AUG-19:30 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.232873E+10 | 2763.12 | 01-SEP-19:30 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.260940E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.268158E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.284327E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.281698E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.183788E+10 | 2332.05 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.284327E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113599E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109410E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113446E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109454E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113207E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133389E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.127458E+10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.115083E+10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.127851E+10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.123137E+10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.127679E+10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.123701E+10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.127114E+10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.127900E+10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.123186E+10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.127409E+10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.123603E+10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.127114E+10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150123E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.115083E+10 | 1227.68 | 0.00 | 0.00 | |
Maximum of Months | 0.127900E+10 | 1227.68 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.104372E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.942384E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.104694E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.100833E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.104553E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.101296E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.104091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.104734E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.100874E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.104332E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.101215E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.104091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.122932E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.942384E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.104734E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.531884E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137302E+10 |
February | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118001E+10 |
March | 0.199990E+10 | 0.533523E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111435E+10 |
April | 0.192973E+10 | 0.513850E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702452E+09 |
May | 0.199475E+10 | 0.532806E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403260E+09 |
June | 0.193394E+10 | 0.516207E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1755291.53 | 0.236969E+09 |
July | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4086284.89 | 0.216818E+09 |
August | 0.199896E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 439955.11 | 0.293593E+09 |
September | 0.192879E+10 | 0.514055E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487487E+09 |
October | 0.199148E+10 | 0.531679E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830476E+09 |
November | 0.192552E+10 | 0.515797E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133921E+10 |
December | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144790E+10 |
Annual Sum or Average | 0.234744E+11 | 0.626467E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6281531.53 | 0.962554E+10 |
Minimum of Months | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216818E+09 |
Maximum of Months | 0.199990E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4086284.89 | 0.144790E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.615923E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531835E+09 |
February | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455473E+09 |
March | 0.231589E+10 | 0.617822E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426985E+09 |
April | 0.223463E+10 | 0.595041E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266867E+09 |
May | 0.230993E+10 | 0.616991E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150089E+09 |
June | 0.223950E+10 | 0.597770E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1206917.68 | 85518103.07 |
July | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2858419.49 | 78640572.41 |
August | 0.231480E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 433322.44 | 0.108656E+09 |
September | 0.223354E+10 | 0.595278E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188571E+09 |
October | 0.230614E+10 | 0.615686E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322343E+09 |
November | 0.222975E+10 | 0.597295E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517365E+09 |
December | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559591E+09 |
Annual Sum or Average | 0.271834E+11 | 0.725451E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4498659.62 | 0.369193E+10 |
Minimum of Months | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78640572.41 |
Maximum of Months | 0.231589E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2858419.49 | 0.559591E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125721E+10 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107714E+10 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101240E+10 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653740E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394381E+09 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1600967.05 | 0.229003E+09 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3727217.93 | 0.211808E+09 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 401223.34 | 0.289266E+09 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489836E+09 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785919E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122255E+10 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132275E+10 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5729408.32 | 0.894601E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211808E+09 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3727217.93 | 0.132275E+10 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.195918E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723699E+09 |
February | 0.339028E+09 | 0.176896E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619799E+09 |
March | 0.376747E+09 | 0.196522E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578310E+09 |
April | 0.363528E+09 | 0.189275E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347397E+09 |
May | 0.375778E+09 | 0.196257E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8214.90 | 0.184450E+09 |
June | 0.364321E+09 | 0.190143E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2686101.48 | 0.101094E+09 |
July | 0.374985E+09 | 0.195389E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5912628.39 | 93253469.73 |
August | 0.376571E+09 | 0.196597E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1389973.87 | 0.130784E+09 |
September | 0.363352E+09 | 0.189351E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240986E+09 |
October | 0.375161E+09 | 0.195842E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432844E+09 |
November | 0.362735E+09 | 0.189992E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704723E+09 |
December | 0.374985E+09 | 0.195389E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762534E+09 |
Annual Sum or Average | 0.442217E+10 | 0.230757E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9996918.64 | 0.491987E+10 |
Minimum of Months | 0.339028E+09 | 0.176896E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93253469.73 |
Maximum of Months | 0.376747E+09 | 0.196597E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5912628.39 | 0.762534E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185049E+10 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158760E+10 |
March | 0.155131E+10 | 0.417273E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149894E+10 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.941208E+09 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541521E+09 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 2185083.87 | 0.312710E+09 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 5088899.19 | 0.289240E+09 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 547482.99 | 0.395271E+09 |
September | 0.149615E+10 | 0.402047E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683902E+09 |
October | 0.154478E+10 | 0.415830E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115064E+10 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179738E+10 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193988E+10 |
Annual Sum or Average | 0.182090E+11 | 0.489965E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 7821466.05 | 0.129888E+11 |
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289240E+09 |
Maximum of Months | 0.155131E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 5088899.19 | 0.193988E+10 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.150742E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304118E+10 |
February | 0.236489E+11 | 0.121599E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260706E+10 |
March | 0.262800E+11 | 0.116335E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245929E+10 |
April | 0.253579E+11 | 0.815738E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154048E+10 |
May | 0.262123E+11 | 0.719412E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850178E+09 |
June | 0.254132E+11 | 0.589381E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5439920.53 | 0.470701E+09 |
July | 0.261570E+11 | 0.655449E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12421232.90 | 0.425801E+09 |
August | 0.262677E+11 | 0.835107E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1438477.37 | 0.601122E+09 |
September | 0.253456E+11 | 0.104808E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106834E+10 |
October | 0.261693E+11 | 0.129369E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184024E+10 |
November | 0.253025E+11 | 0.139489E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296069E+10 |
December | 0.261570E+11 | 0.157259E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320248E+10 |
Annual Sum or Average | 0.308468E+12 | 0.128111E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19299630.81 | 0.210676E+11 |
Minimum of Months | 0.236489E+11 | 0.589381E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425801E+09 |
Maximum of Months | 0.262800E+11 | 0.157259E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12421232.90 | 0.320248E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.818709E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874719E+10 |
February | 0.702046E+11 | 0.725700E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750182E+10 |
March | 0.780153E+11 | 0.789805E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708362E+10 |
April | 0.752779E+11 | 0.735588E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447004E+10 |
May | 0.778146E+11 | 0.752271E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253378E+10 |
June | 0.754422E+11 | 0.719448E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17131326.56 | 0.144453E+10 |
July | 0.776503E+11 | 0.744075E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39144578.78 | 0.132925E+10 |
August | 0.779788E+11 | 0.763635E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4688172.14 | 0.183779E+10 |
September | 0.752414E+11 | 0.755492E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318183E+10 |
October | 0.776868E+11 | 0.798827E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537467E+10 |
November | 0.751137E+11 | 0.787865E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850843E+10 |
December | 0.776503E+11 | 0.822770E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918240E+10 |
Annual Sum or Average | 0.915726E+12 | 0.921419E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 60964077.47 | 0.611954E+11 |
Minimum of Months | 0.702046E+11 | 0.719448E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132925E+10 |
Maximum of Months | 0.780153E+11 | 0.822770E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39144578.78 | 0.918240E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788375E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674275E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633059E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390699E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28767.82 | 0.209961E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3090449.08 | 0.108655E+09 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6264298.59 | 98352082.08 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1549567.31 | 0.143436E+09 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270003E+09 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471608E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766345E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829794E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10933082.81 | 0.538456E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98352082.08 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6264298.59 | 0.829794E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787916E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673618E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628260E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384151E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214990E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2376378.09 | 0.123821E+09 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4649347.16 | 0.110051E+09 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 955550.47 | 0.151804E+09 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266103E+09 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468879E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766132E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829609E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7981275.72 | 0.540533E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110051E+09 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4649347.16 | 0.829609E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 65789991.58 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192391E+09 |
February | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165042E+09 |
March | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173017E+09 |
April | 0.00 | 63743496.62 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133550E+09 |
May | 0.00 | 65528554.53 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84203316.54 |
June | 0.00 | 63237765.93 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10042.37 | 53826389.58 |
July | 0.00 | 66042856.93 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 100490.30 | 50869418.33 |
August | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65297923.64 |
September | 0.00 | 63760640.03 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100091E+09 |
October | 0.00 | 65781419.88 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137710E+09 |
November | 0.00 | 63490631.27 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186954E+09 |
December | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203455E+09 |
Annual Sum or Average | 0.00 | 0.773376E+09 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 110532.67 | 0.154641E+10 |
Minimum of Months | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50869418.33 |
Maximum of Months | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 100490.30 | 0.203455E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220236E+09 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188592E+09 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176658E+09 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107589E+09 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58395673.06 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 681239.70 | 31934696.88 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1361955.02 | 29008190.78 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 294479.14 | 40725598.82 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75048904.00 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132604E+09 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214171E+09 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231760E+09 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2337673.86 | 0.150672E+10 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29008190.78 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1361955.02 | 0.231760E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788246E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674970E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638554E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393381E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28804.87 | 0.211410E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3112325.72 | 0.109142E+09 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6286096.78 | 98950205.64 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1567928.81 | 0.144638E+09 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272715E+09 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473893E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766344E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829746E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10995156.18 | 0.540199E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98950205.64 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6286096.78 | 0.829746E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787783E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673801E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631756E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388659E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215024E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2398054.54 | 0.119435E+09 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4661347.93 | 0.110155E+09 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 969229.19 | 0.151077E+09 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270094E+09 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470773E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766100E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829525E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8028631.65 | 0.541418E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110155E+09 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4661347.93 | 0.829525E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.120431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.967479E+09 |
February | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.827868E+09 |
March | 0.387034E+10 | 0.120803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772382E+09 |
April | 0.373454E+10 | 0.116348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475215E+09 |
May | 0.386038E+10 | 0.120640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273521E+09 |
June | 0.374269E+10 | 0.116882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1575069.12 | 0.162143E+09 |
July | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3675556.35 | 0.148058E+09 |
August | 0.386853E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 698177.95 | 0.197373E+09 |
September | 0.373273E+10 | 0.116395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331660E+09 |
October | 0.385404E+10 | 0.120385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578464E+09 |
November | 0.372639E+10 | 0.116789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.941041E+09 |
December | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101821E+10 |
Annual Sum or Average | 0.454292E+11 | 0.141847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5948803.43 | 0.669341E+10 |
Minimum of Months | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148058E+09 |
Maximum of Months | 0.387034E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3675556.35 | 0.101821E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789070E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674989E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632031E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390161E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26191.37 | 0.210494E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2991336.03 | 0.109336E+09 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6092368.48 | 99001643.36 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1489640.46 | 0.143894E+09 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269263E+09 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471136E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767457E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830891E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10599536.35 | 0.538772E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99001643.36 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6092368.48 | 0.830891E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788443E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674563E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628874E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383617E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216135E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2318815.86 | 0.126176E+09 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4536465.41 | 0.111914E+09 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 928138.32 | 0.153198E+09 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265065E+09 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469001E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767094E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830471E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7783419.59 | 0.541455E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111914E+09 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4536465.41 | 0.830471E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404517E+09 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348766E+09 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329692E+09 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202389E+09 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12305.08 | 0.108294E+09 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1544413.62 | 56044315.56 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3126964.38 | 50798915.65 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 765146.05 | 74188563.17 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140666E+09 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245308E+09 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393557E+09 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425322E+09 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5448829.13 | 0.277954E+10 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50798915.65 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3126964.38 | 0.425322E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.281025E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197789E+10 |
February | 0.415303E+11 | 0.241048E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169480E+10 |
March | 0.461508E+11 | 0.248641E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159377E+10 |
April | 0.445315E+11 | 0.207938E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986740E+09 |
May | 0.460320E+11 | 0.199717E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556073E+09 |
June | 0.446286E+11 | 0.183788E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5438587.81 | 0.315008E+09 |
July | 0.459349E+11 | 0.194254E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13330239.94 | 0.290141E+09 |
August | 0.461292E+11 | 0.214270E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2719115.51 | 0.396631E+09 |
September | 0.445099E+11 | 0.232873E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703727E+09 |
October | 0.459565E+11 | 0.260940E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120936E+10 |
November | 0.444343E+11 | 0.268158E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192230E+10 |
December | 0.459349E+11 | 0.284327E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207617E+10 |
Annual Sum or Average | 0.541708E+12 | 0.281698E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 21487943.27 | 0.137226E+11 |
Minimum of Months | 0.415303E+11 | 0.183788E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290141E+09 |
Maximum of Months | 0.461508E+11 | 0.284327E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13330239.94 | 0.207617E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.281025E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198868E+10 |
February | 0.415303E+11 | 0.241048E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170445E+10 |
March | 0.461508E+11 | 0.248641E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160718E+10 |
April | 0.445315E+11 | 0.207938E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100166E+10 |
May | 0.460320E+11 | 0.199717E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568777E+09 |
June | 0.446286E+11 | 0.183788E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4679667.92 | 0.325049E+09 |
July | 0.459349E+11 | 0.194254E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11551548.76 | 0.299508E+09 |
August | 0.461292E+11 | 0.214270E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2197862.50 | 0.407807E+09 |
September | 0.445099E+11 | 0.232873E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719246E+09 |
October | 0.459565E+11 | 0.260940E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122474E+10 |
November | 0.444343E+11 | 0.268158E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193212E+10 |
December | 0.459349E+11 | 0.284327E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208552E+10 |
Annual Sum or Average | 0.541708E+12 | 0.281698E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 18429079.18 | 0.138647E+11 |
Minimum of Months | 0.415303E+11 | 0.183788E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299508E+09 |
Maximum of Months | 0.461508E+11 | 0.284327E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11551548.76 | 0.208552E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188764E+10 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162041E+10 |
March | 0.410691E+10 | 0.113599E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153109E+10 |
April | 0.396281E+10 | 0.109410E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962691E+09 |
May | 0.409635E+10 | 0.113446E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555491E+09 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 2084756.42 | 0.322079E+09 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 4923429.70 | 0.298169E+09 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 497177.36 | 0.406445E+09 |
September | 0.396089E+10 | 0.109454E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700485E+09 |
October | 0.408962E+10 | 0.113207E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117625E+10 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183483E+10 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197978E+10 |
Annual Sum or Average | 0.482060E+11 | 0.133389E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 7505363.48 | 0.132754E+11 |
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298169E+09 |
Maximum of Months | 0.410691E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 4923429.70 | 0.197978E+10 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.127458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171226E+10 |
February | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146722E+10 |
March | 0.409620E+10 | 0.127851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137120E+10 |
April | 0.395248E+10 | 0.123137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864783E+09 |
May | 0.408566E+10 | 0.127679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525326E+09 |
June | 0.396110E+10 | 0.123701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2023960.79 | 0.313435E+09 |
July | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4788101.88 | 0.289623E+09 |
August | 0.409429E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479178.95 | 0.387671E+09 |
September | 0.395056E+10 | 0.123186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618662E+09 |
October | 0.407896E+10 | 0.127409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103050E+10 |
November | 0.394385E+10 | 0.123603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166769E+10 |
December | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180423E+10 |
Annual Sum or Average | 0.480803E+11 | 0.150123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7291241.62 | 0.120526E+11 |
Minimum of Months | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289623E+09 |
Maximum of Months | 0.409620E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4788101.88 | 0.180423E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 10053.14 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 10053.14 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 10053.14 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 10053.14 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 10053.14 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 10053.14 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 10053.14 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 10053.14 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 10053.14 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 10053.14 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 10053.14 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 10053.14 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 512.31 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 829.48 | 12-JAN-06:00 |
February | 1169.53 | 01-FEB-00:10 | 512.31 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 799.85 | 27-FEB-05:00 |
March | 1169.53 | 01-MAR-00:10 | 512.31 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 705.22 | 01-MAR-00:10 |
April | 1169.53 | 01-APR-00:10 | 512.31 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 580.56 | 03-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 512.31 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 262.46 | 28-MAY-02:00 |
June | 1169.53 | 01-JUN-00:10 | 512.31 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.62 | 30-JUN-15:00 | 236.06 | 02-JUN-04:00 |
July | 1169.53 | 01-JUL-00:10 | 512.31 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.83 | 29-JUL-16:50 | 191.69 | 31-JUL-03:00 |
August | 1169.53 | 01-AUG-00:10 | 512.31 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 11-AUG-16:00 | 293.47 | 31-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 512.31 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 337.83 | 30-SEP-09:00 |
October | 1169.53 | 01-OCT-23:10 | 512.31 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 567.75 | 22-OCT-06:20 |
November | 1169.53 | 01-NOV-00:10 | 512.31 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 704.43 | 29-NOV-02:00 |
December | 1169.53 | 01-DEC-00:10 | 512.31 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 766.38 | 15-DEC-07:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.69 | |||||
Maximum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 67.83 | 829.48 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 593.26 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 331.57 | 12-JAN-06:00 |
February | 1354.32 | 01-FEB-00:10 | 593.26 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 315.63 | 27-FEB-05:50 |
March | 1354.32 | 01-MAR-00:10 | 593.26 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 272.30 | 01-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 593.26 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 224.59 | 03-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 593.26 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 105.85 | 27-MAY-04:00 |
June | 1354.32 | 01-JUN-00:10 | 593.26 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 30-JUN-15:00 | 94.33 | 02-JUN-04:00 |
July | 1354.32 | 01-JUL-00:10 | 593.26 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 29-JUL-16:00 | 76.14 | 31-JUL-04:40 |
August | 1354.32 | 01-AUG-00:10 | 593.26 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 | 11-AUG-17:00 | 119.45 | 31-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 593.26 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 131.88 | 29-SEP-06:53 |
October | 1354.32 | 01-OCT-23:10 | 593.26 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 219.14 | 22-OCT-06:30 |
November | 1354.32 | 01-NOV-00:10 | 593.26 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 276.75 | 29-NOV-10:00 |
December | 1354.32 | 01-DEC-00:10 | 593.26 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 303.89 | 15-DEC-07:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.14 | |||||
Maximum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 331.57 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 785.92 | 12-JAN-07:40 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 742.21 | 27-FEB-05:40 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 643.54 | 01-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 529.63 | 03-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 266.40 | 27-MAY-06:55 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.36 | 30-JUN-15:00 | 236.82 | 02-JUN-04:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.88 | 29-JUL-17:00 | 190.17 | 31-JUL-03:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.64 | 11-AUG-16:00 | 297.85 | 31-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 326.37 | 29-SEP-06:53 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 520.45 | 22-OCT-07:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 654.14 | 29-NOV-10:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 721.33 | 15-DEC-07:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.17 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 61.88 | 785.92 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 188.71 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 445.86 | 12-JAN-06:00 |
February | 220.32 | 01-FEB-00:10 | 188.71 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 423.82 | 27-FEB-05:00 |
March | 220.32 | 01-MAR-00:10 | 188.71 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 370.71 | 01-MAR-00:10 |
April | 220.32 | 01-APR-00:10 | 188.71 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 305.57 | 03-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 188.71 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 | 31-MAY-16:00 | 138.14 | 28-MAY-02:00 |
June | 220.32 | 01-JUN-00:10 | 188.71 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.60 | 30-JUN-15:00 | 120.92 | 02-JUN-04:00 |
July | 220.32 | 01-JUL-00:10 | 188.71 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.68 | 29-JUL-17:00 | 96.61 | 31-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 188.71 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.37 | 11-AUG-17:00 | 153.65 | 31-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 188.71 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 176.14 | 30-SEP-09:00 |
October | 220.32 | 01-OCT-23:10 | 188.71 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 298.80 | 22-OCT-06:50 |
November | 220.32 | 01-NOV-00:10 | 188.71 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 374.41 | 29-NOV-10:00 |
December | 220.32 | 01-DEC-00:10 | 188.71 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 410.11 | 15-DEC-07:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.61 | |||||
Maximum of Months | 220.32 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 46.68 | 445.86 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1138.69 | 12-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1072.02 | 27-FEB-06:00 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 931.53 | 01-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 773.97 | 03-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 373.64 | 28-MAY-02:00 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 60.57 | 30-JUN-15:00 | 323.35 | 02-JUN-04:00 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 84.50 | 29-JUL-16:20 | 259.66 | 31-JUL-04:00 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 22.72 | 11-AUG-16:00 | 409.10 | 31-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 464.94 | 30-SEP-09:00 |
October | 907.20 | 01-OCT-23:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 758.14 | 22-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 945.72 | 29-NOV-10:00 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1038.82 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 259.66 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 84.50 | 1138.69 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1573.46 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1902.07 | 12-JAN-06:00 |
February | 15368.40 | 01-FEB-00:10 | 1573.46 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1807.80 | 27-FEB-05:00 |
March | 15368.40 | 01-MAR-00:10 | 1573.46 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1559.49 | 01-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1573.46 | 03-APR-19:40 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1283.38 | 03-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1398.63 | 04-MAY-20:30 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 603.49 | 27-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1214.60 | 02-JUN-20:00 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.01 | 30-JUN-15:00 | 535.35 | 02-JUN-04:00 |
July | 15368.40 | 01-JUL-00:10 | 1263.59 | 28-JUL-20:00 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.57 | 29-JUL-17:00 | 429.36 | 31-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1573.46 | 29-AUG-19:30 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.96 | 11-AUG-18:00 | 664.40 | 31-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1573.46 | 01-SEP-19:30 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 739.83 | 30-SEP-09:00 |
October | 15368.40 | 01-OCT-23:10 | 1573.46 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1255.09 | 22-OCT-06:20 |
November | 15368.40 | 01-NOV-00:10 | 1573.46 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1561.09 | 29-NOV-02:00 |
December | 15368.40 | 01-DEC-00:10 | 1573.46 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1728.23 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1214.60 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.36 | |||||
Maximum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 164.57 | 1902.07 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 7984.04 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5495.91 | 12-JAN-06:00 |
February | 45622.98 | 01-FEB-00:10 | 7984.04 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5164.62 | 27-FEB-05:40 |
March | 45622.98 | 01-MAR-00:10 | 7984.04 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4455.56 | 01-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 7984.04 | 03-APR-19:40 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3728.22 | 03-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 7809.31 | 02-MAY-19:00 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1798.69 | 27-MAY-04:00 |
June | 45622.98 | 01-JUN-00:10 | 7667.15 | 02-JUN-19:00 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.21 | 30-JUN-15:00 | 1593.49 | 02-JUN-04:00 |
July | 45622.98 | 01-JUL-00:10 | 7625.65 | 28-JUL-19:00 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 487.38 | 29-JUL-16:00 | 1290.45 | 31-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 7984.04 | 29-AUG-19:30 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.12 | 11-AUG-17:00 | 1996.07 | 31-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 7984.04 | 01-SEP-19:30 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2208.33 | 30-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 7984.04 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3618.05 | 22-OCT-07:00 |
November | 45622.98 | 01-NOV-00:10 | 7984.04 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4527.09 | 29-NOV-10:00 |
December | 45622.98 | 01-DEC-00:10 | 7984.04 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4986.56 | 15-DEC-07:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 7625.65 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1290.45 | |||||
Maximum of Months | 45622.98 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 487.38 | 5495.91 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 501.67 | 12-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 475.87 | 27-FEB-05:10 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 410.70 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 338.18 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 31-MAY-16:00 | 153.45 | 28-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.58 | 20-JUN-18:10 | 129.96 | 02-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.05 | 29-JUL-16:40 | 100.50 | 31-JUL-03:10 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.46 | 11-AUG-16:00 | 169.51 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 195.38 | 30-SEP-09:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 330.72 | 22-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 417.15 | 29-NOV-10:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 459.30 | 15-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.50 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 58.05 | 501.67 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 498.76 | 12-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 474.46 | 27-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 410.66 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 338.16 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 153.44 | 28-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.58 | 20-JUN-18:50 | 129.95 | 02-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.05 | 29-JUL-16:10 | 100.49 | 31-JUL-03:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.46 | 11-AUG-16:00 | 169.50 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 195.37 | 30-SEP-09:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 330.70 | 22-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 415.25 | 29-NOV-10:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 459.26 | 15-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.49 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 58.05 | 498.76 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 59.53 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 128.08 | 12-JAN-07:54 |
February | 0.00 | 01-FEB-00:10 | 59.53 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 119.89 | 27-FEB-06:00 |
March | 0.00 | 01-MAR-00:10 | 59.53 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 109.21 | 31-MAR-06:00 |
April | 0.00 | 01-APR-00:10 | 59.53 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 99.85 | 03-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 59.53 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 52.96 | 27-MAY-07:20 |
June | 0.00 | 01-JUN-00:10 | 59.53 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.91 | 30-JUN-15:00 | 47.18 | 02-JUN-04:00 |
July | 0.00 | 01-JUL-00:10 | 59.53 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.02 | 29-JUL-17:00 | 39.20 | 31-JUL-03:00 |
August | 0.00 | 01-AUG-00:10 | 59.53 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 58.48 | 31-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 59.53 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 63.60 | 30-SEP-09:00 |
October | 0.00 | 01-OCT-00:10 | 59.53 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 85.20 | 22-OCT-09:00 |
November | 0.00 | 01-NOV-00:10 | 59.53 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 103.83 | 29-NOV-10:00 |
December | 0.00 | 01-DEC-00:10 | 59.53 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 115.46 | 15-DEC-07:54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.20 | |||||
Maximum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 6.02 | 128.08 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 137.71 | 12-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 130.26 | 27-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 114.23 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 94.38 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 44.64 | 27-MAY-07:20 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.21 | 20-JUN-18:50 | 36.27 | 02-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.20 | 29-JUL-16:00 | 28.05 | 31-JUL-04:10 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.22 | 11-AUG-16:00 | 47.31 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 55.18 | 30-SEP-08:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 92.30 | 22-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 114.32 | 29-NOV-10:00 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 126.84 | 15-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.05 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 16.20 | 137.71 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 500.23 | 12-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 475.87 | 27-FEB-05:20 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 410.70 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 338.18 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 31-MAY-16:00 | 154.44 | 27-MAY-07:10 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.59 | 20-JUN-18:10 | 129.96 | 02-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.05 | 29-JUL-16:50 | 100.50 | 31-JUL-03:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.46 | 11-AUG-16:00 | 177.10 | 31-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 202.70 | 30-SEP-08:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 330.72 | 22-OCT-06:30 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 416.36 | 29-NOV-10:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 459.30 | 15-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.50 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 58.05 | 500.23 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 497.42 | 12-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 473.21 | 27-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 410.66 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 338.16 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 154.14 | 27-MAY-07:10 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.58 | 20-JUN-18:10 | 129.95 | 02-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.05 | 29-JUL-16:10 | 100.49 | 31-JUL-03:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.46 | 11-AUG-16:00 | 176.84 | 31-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 199.43 | 30-SEP-08:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 330.70 | 22-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 414.50 | 29-NOV-10:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 459.19 | 15-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.49 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 58.05 | 497.42 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 605.29 | 12-JAN-06:00 |
February | 2263.36 | 01-FEB-00:10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 574.21 | 27-FEB-05:00 |
March | 2263.36 | 01-MAR-00:10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 495.55 | 01-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 407.89 | 03-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 192.40 | 27-MAY-04:00 |
June | 2263.36 | 01-JUN-00:10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 | 30-JUN-15:00 | 171.75 | 02-JUN-04:00 |
July | 2263.36 | 01-JUL-00:10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.34 | 29-JUL-17:00 | 139.91 | 31-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.56 | 23-AUG-17:50 | 215.44 | 31-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 235.27 | 30-SEP-09:00 |
October | 2263.36 | 01-OCT-23:10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 398.87 | 22-OCT-06:50 |
November | 2263.36 | 01-NOV-00:10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 501.10 | 29-NOV-10:00 |
December | 2263.36 | 01-DEC-00:10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 552.15 | 15-DEC-07:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.91 | ||||
Maximum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.34 | 605.29 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 497.07 | 12-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 476.06 | 27-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 411.28 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 338.74 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.60 | 31-MAY-16:00 | 153.91 | 28-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.20 | 20-JUN-18:10 | 130.42 | 02-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 | 29-JUL-16:50 | 100.95 | 31-JUL-03:50 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.07 | 11-AUG-16:10 | 169.99 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 195.87 | 30-SEP-09:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 331.27 | 22-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 415.13 | 29-NOV-10:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 459.91 | 15-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.95 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 | 497.07 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 492.93 | 12-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 471.71 | 27-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 411.26 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 338.71 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 153.90 | 28-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.19 | 20-JUN-19:00 | 130.41 | 02-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 | 29-JUL-16:00 | 100.94 | 31-JUL-03:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.07 | 11-AUG-16:00 | 169.98 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 195.86 | 30-SEP-09:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 331.25 | 22-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 412.65 | 29-NOV-10:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 456.87 | 15-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.94 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 | 492.93 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 259.20 | 12-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 243.78 | 27-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 210.42 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 173.31 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.37 | 31-MAY-16:00 | 78.75 | 28-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 | 20-JUN-18:40 | 66.72 | 02-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.51 | 29-JUL-16:50 | 51.65 | 31-JUL-03:20 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 | 11-AUG-16:00 | 86.97 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 100.21 | 30-SEP-09:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 169.49 | 22-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 213.80 | 29-NOV-10:00 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 235.30 | 15-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.65 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 29.51 | 259.20 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1232.49 | 12-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1161.38 | 27-FEB-05:20 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1002.19 | 01-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:40 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 839.11 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2456.11 | 04-MAY-20:30 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 406.15 | 27-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2332.05 | 02-JUN-19:00 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.70 | 30-JUN-15:00 | 359.82 | 02-JUN-04:00 |
July | 26988.77 | 01-JUL-00:10 | 2341.32 | 26-JUL-20:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.17 | 29-JUL-16:00 | 289.58 | 31-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 29-AUG-19:30 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.18 | 11-AUG-18:00 | 446.11 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:30 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 499.18 | 30-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 823.56 | 22-OCT-07:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1017.58 | 29-NOV-10:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1118.63 | 15-DEC-07:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2332.05 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.58 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 127.17 | 1232.49 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1235.79 | 12-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1161.38 | 27-FEB-05:20 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1003.16 | 01-MAR-00:10 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:40 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 845.68 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2456.11 | 04-MAY-20:30 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 410.65 | 27-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2332.05 | 02-JUN-19:00 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.34 | 30-JUN-15:00 | 363.81 | 02-JUN-04:00 |
July | 26988.77 | 01-JUL-00:10 | 2341.32 | 26-JUL-20:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.52 | 29-JUL-16:00 | 293.60 | 31-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 29-AUG-19:30 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.45 | 11-AUG-18:00 | 451.15 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:30 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 506.07 | 30-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 830.81 | 22-OCT-07:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1018.65 | 29-NOV-10:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1123.11 | 15-DEC-07:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2332.05 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.60 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 122.52 | 1235.79 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1161.95 | 12-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1084.61 | 27-FEB-06:20 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 950.69 | 01-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 790.15 | 03-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 382.21 | 28-MAY-02:00 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 60.39 | 30-JUN-15:00 | 330.98 | 02-JUN-04:00 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 84.83 | 29-JUL-16:00 | 266.08 | 31-JUL-03:50 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 21.90 | 11-AUG-16:00 | 418.30 | 31-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 475.18 | 30-SEP-09:00 |
October | 2401.70 | 01-OCT-23:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 774.12 | 22-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 965.09 | 29-NOV-10:00 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1060.18 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 266.08 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 84.83 | 1161.95 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1055.39 | 12-JAN-06:00 |
February | 2395.44 | 01-FEB-00:10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1007.45 | 27-FEB-05:00 |
March | 2395.44 | 01-MAR-00:10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 877.73 | 01-MAR-00:10 |
April | 2395.44 | 01-APR-00:10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 722.86 | 03-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 348.71 | 27-MAY-04:00 |
June | 2395.44 | 01-JUN-00:10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.96 | 30-JUN-15:00 | 317.08 | 02-JUN-04:00 |
July | 2395.44 | 01-JUL-00:10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.81 | 29-JUL-16:50 | 257.53 | 31-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.21 | 11-AUG-16:00 | 385.46 | 31-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 417.31 | 30-SEP-09:00 |
October | 2395.44 | 01-OCT-23:10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 706.91 | 22-OCT-06:40 |
November | 2395.44 | 01-NOV-00:10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 883.44 | 29-NOV-10:00 |
December | 2395.44 | 01-DEC-00:10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 968.81 | 15-DEC-07:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.53 | ||||
Maximum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.81 | 1055.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18811.57 | 12-JAN-21:00 | 8945.92 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13886.81 | 28-FEB-21:00 | 8945.92 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11960.44 | 01-MAR-00:10 | 11501.89 | 2233.99 | 3041.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12500.19 | 22-APR-10:35 | 7667.93 | 5585.17 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12922.07 | 14-MAY-10:35 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13443.91 | 29-JUN-10:35 | 5111.95 | 5585.17 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14699.86 | 23-JUL-10:35 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15325.78 | 26-AUG-10:35 | 7667.93 | 5585.17 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15889.16 | 20-SEP-21:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16105.84 | 06-OCT-21:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15365.95 | 28-NOV-23:00 | 11501.89 | 6702.09 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17194.65 | 15-DEC-07:52 | 40895.62 | 44680.27 | 48669.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11960.44 | 5111.95 | 2233.99 | 3041.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18811.57 | 40895.62 | 44680.27 | 48669.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 677.82 | 30-JAN-12:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606.40 |
February | 1165.62 | 15-FEB-13:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.10 |
March | 2749.85 | 27-MAR-13:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.05 |
April | 4520.09 | 22-APR-13:30 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.01 |
May | 4452.42 | 12-MAY-13:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.23 |
June | 4196.48 | 30-JUN-12:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 24.49 | 0.00 |
July | 4773.49 | 23-JUL-13:30 | 259.90 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 | 0.00 |
August | 4950.54 | 25-AUG-13:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.97 |
September | 4083.46 | 09-SEP-13:30 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.32 |
October | 2993.55 | 03-OCT-13:20 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.50 |
November | 965.23 | 08-NOV-13:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.75 |
December | 0.00 | 01-DEC-00:10 | 1169.53 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 639.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 259.90 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4950.54 | 1169.53 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 24.49 | 639.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1053.46 | 23-JAN-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.61 |
February | 1145.53 | 09-FEB-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.45 |
March | 1270.01 | 22-MAR-20:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.44 |
April | 1519.36 | 21-APR-20:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.26 |
May | 1565.04 | 31-MAY-18:10 | 6320.16 | 3164.06 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 |
June | 1727.17 | 21-JUN-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 1685.27 | 11-JUL-20:05 | 9630.72 | 4218.74 | 6017.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.72 |
August | 1675.15 | 11-AUG-21:00 | 2407.68 | 1054.69 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.34 |
September | 1472.57 | 10-SEP-10:35 | 902.88 | 395.51 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.11 |
October | 1340.83 | 03-OCT-20:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.58 |
November | 1084.55 | 01-NOV-20:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.26 |
December | 1023.62 | 19-DEC-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1023.62 | 902.88 | 395.51 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | |
Maximum of Months | 1727.17 | 9630.72 | 4218.74 | 6017.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14.04 | 19-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.24 |
February | 15.78 | 09-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.39 |
March | 18.30 | 22-MAR-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.70 |
April | 536.74 | 21-APR-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.29 |
May | 984.76 | 31-MAY-20:55 | 509.18 | 1216.31 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.35 |
June | 1300.63 | 21-JUN-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 | 0.00 |
July | 1335.82 | 21-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 10.31 | 0.00 |
August | 1248.92 | 11-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 4.15 | 0.00 |
September | 672.06 | 01-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.52 |
October | 204.53 | 06-OCT-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.85 |
November | 14.54 | 03-NOV-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.39 |
December | 13.48 | 19-DEC-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13.48 | 222.77 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1335.82 | 509.18 | 1216.31 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 | 370.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 342.72 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.19 |
February | 124.97 | 08-FEB-22:00 | 195.84 | 167.74 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.12 |
March | 442.10 | 22-MAR-21:00 | 195.84 | 167.74 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.57 |
April | 792.31 | 23-APR-10:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.24 |
May | 890.59 | 14-MAY-10:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 |
June | 934.17 | 22-JUN-10:35 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.93 |
July | 973.77 | 23-JUL-10:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 |
August | 906.95 | 26-AUG-10:35 | 146.88 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.01 |
September | 816.00 | 10-SEP-10:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.36 |
October | 668.94 | 03-OCT-19:50 | 171.36 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.96 |
November | 0.00 | 01-NOV-00:10 | 220.32 | 31.45 | 63.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.90 |
December | 0.00 | 01-DEC-00:10 | 220.32 | 41.94 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 97.92 | 31.45 | 63.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 973.77 | 342.72 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 | 336.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36315.77 | 19-JAN-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 543.76 |
February | 36795.81 | 08-FEB-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 391.14 |
March | 37524.30 | 22-MAR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 328.71 |
April | 38299.96 | 21-APR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 175.18 |
May | 38784.04 | 31-MAY-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 99.49 |
June | 39064.60 | 29-JUN-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.18 | 0.00 |
July | 39145.83 | 21-JUL-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.05 | 0.00 |
August | 38993.39 | 11-AUG-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 5.65 | 0.00 |
September | 38196.84 | 01-SEP-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 175.50 |
October | 37764.55 | 03-OCT-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 271.29 |
November | 36439.02 | 01-NOV-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 516.00 |
December | 36102.41 | 19-DEC-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 465.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36102.41 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39145.83 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.18 | 543.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6830.07 | 06-JAN-23:10 | 15368.40 | 524.49 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.16 |
February | 8118.57 | 15-FEB-13:40 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 892.05 |
March | 11277.68 | 27-MAR-15:10 | 17076.00 | 192.31 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 810.17 |
April | 15392.11 | 22-APR-13:30 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.48 |
May | 14529.06 | 13-MAY-13:10 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.12 |
June | 13637.51 | 20-JUN-15:10 | 8538.00 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 27.78 | 0.00 |
July | 14930.83 | 23-JUL-13:30 | 3415.20 | 76.92 | 304.82 | 0.00 | 0.00 | 0.00 | 0.00 | 25.29 | 0.00 |
August | 15671.27 | 25-AUG-14:10 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.84 |
September | 14331.43 | 09-SEP-13:30 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.42 |
October | 10832.31 | 03-OCT-14:10 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.23 |
November | 7007.21 | 08-NOV-13:30 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1010.33 |
December | 6450.73 | 19-DEC-22:20 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 810.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6450.73 | 3415.20 | 76.92 | 304.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15671.27 | 17076.00 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.78 | 1010.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23170.94 | 06-JAN-22:00 | 40553.76 | 7096.92 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2013.41 |
February | 25632.20 | 28-FEB-22:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4508.59 |
March | 27690.85 | 22-MAR-20:00 | 35484.54 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.34 |
April | 32430.90 | 21-APR-21:10 | 91245.96 | 10645.38 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1098.93 |
May | 33441.26 | 14-MAY-10:35 | 30415.32 | 4577.51 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.48 |
June | 36499.76 | 21-JUN-21:03 | 273737.88 | 30244.55 | 44339.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.23 |
July | 37118.51 | 21-JUL-21:10 | 91245.96 | 10442.30 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.98 |
August | 37197.75 | 11-AUG-21:10 | 45622.98 | 5309.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.41 |
September | 32349.03 | 10-SEP-10:35 | 30415.32 | 4577.51 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 665.81 |
October | 29166.58 | 03-OCT-20:00 | 35484.54 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1302.20 |
November | 24696.59 | 28-NOV-22:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4261.34 |
December | 24579.25 | 27-DEC-22:00 | 40553.76 | 7096.92 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4208.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23170.94 | 30415.32 | 4577.51 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.23 | |
Maximum of Months | 37197.75 | 273737.88 | 30244.55 | 44339.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4508.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 360.00 | 49.25 | 89.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.44 |
February | 399.49 | 15-FEB-16:14 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.68 |
March | 3641.70 | 22-MAR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.04 |
April | 3849.09 | 20-APR-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.82 |
May | 3866.01 | 10-MAY-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.15 |
June | 3905.68 | 16-JUN-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 |
July | 3384.01 | 26-JUL-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.73 |
August | 3800.10 | 31-AUG-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.29 |
September | 3786.95 | 07-SEP-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.96 |
October | 3190.98 | 13-OCT-15:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.90 |
November | 8.51 | 08-NOV-14:00 | 36.00 | 26.52 | 31.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.20 |
December | 0.00 | 01-DEC-00:10 | 180.00 | 20.84 | 44.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 36.00 | 20.84 | 31.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | |
Maximum of Months | 3905.68 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 360.00 | 49.25 | 89.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.42 |
February | 160.93 | 08-FEB-19:06 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.02 |
March | 729.51 | 26-MAR-15:14 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.80 |
April | 3476.84 | 21-APR-18:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.94 |
May | 4005.33 | 09-MAY-20:01 | 1602.00 | 842.88 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.21 |
June | 3654.07 | 01-JUN-18:41 | 1247.40 | 758.59 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.42 |
July | 3486.46 | 06-JUL-21:51 | 1800.00 | 634.53 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.47 |
August | 3419.69 | 30-AUG-18:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.83 |
September | 3378.34 | 07-SEP-18:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.72 |
October | 1554.82 | 03-OCT-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.50 |
November | 0.00 | 01-NOV-00:10 | 180.00 | 16.10 | 44.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.71 |
December | 0.00 | 01-DEC-00:10 | 180.00 | 20.84 | 44.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 180.00 | 16.10 | 44.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.47 | |
Maximum of Months | 4005.33 | 1800.00 | 842.88 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2.68 | 23-JAN-15:20 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.84 |
February | 99.61 | 26-FEB-16:00 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.11 |
March | 189.07 | 31-MAR-15:10 | 0.00 | 33.33 | 98.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.23 |
April | 742.97 | 22-APR-13:20 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.87 |
May | 720.03 | 12-MAY-13:20 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.41 |
June | 637.89 | 30-JUN-12:30 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 |
July | 758.42 | 23-JUL-13:30 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 |
August | 803.30 | 25-AUG-13:30 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 |
September | 688.64 | 09-SEP-13:10 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.62 |
October | 460.95 | 03-OCT-13:00 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.61 |
November | 34.63 | 08-NOV-15:20 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.64 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 13.10 | 43.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 13.10 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 | |
Maximum of Months | 803.30 | 0.00 | 33.33 | 98.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 192.28 | 20-JAN-19:07 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.86 |
February | 258.12 | 07-FEB-19:04 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.74 |
March | 670.44 | 22-MAR-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.57 |
April | 1012.96 | 30-APR-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.12 |
May | 1082.43 | 31-MAY-21:51 | 1800.00 | 398.93 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 |
June | 1130.15 | 10-JUN-21:51 | 1386.00 | 506.11 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.91 |
July | 1042.09 | 19-JUL-21:51 | 1800.00 | 398.93 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.12 |
August | 1082.01 | 10-AUG-21:51 | 1800.00 | 398.93 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 |
September | 992.59 | 10-SEP-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 |
October | 930.36 | 03-OCT-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 |
November | 221.72 | 01-NOV-18:06 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.23 |
December | 242.15 | 24-DEC-19:05 | 702.00 | 357.25 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 192.28 | 702.00 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.91 | |
Maximum of Months | 1130.15 | 1800.00 | 506.11 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 360.00 | 49.25 | 89.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.44 |
February | 438.21 | 09-FEB-16:15 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.02 |
March | 3512.45 | 22-MAR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.95 |
April | 3602.76 | 22-APR-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.05 |
May | 3669.04 | 13-MAY-08:61 | 378.00 | 371.29 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.79 |
June | 3610.79 | 07-JUN-15:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.82 |
July | 3220.36 | 08-JUL-08:61 | 378.00 | 371.29 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.78 |
August | 3596.89 | 10-AUG-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 0.00 |
September | 3564.18 | 07-SEP-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.64 |
October | 3174.85 | 04-OCT-08:62 | 180.00 | 208.38 | 566.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.10 |
November | 0.00 | 01-NOV-00:10 | 180.00 | 16.10 | 44.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.72 |
December | 0.00 | 01-DEC-00:10 | 180.00 | 20.84 | 44.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 180.00 | 16.10 | 44.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3669.04 | 831.60 | 505.79 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 372.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 360.00 | 49.25 | 89.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.42 |
February | 196.08 | 08-FEB-19:06 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.02 |
March | 1049.32 | 11-MAR-09:01 | 378.00 | 371.25 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.17 |
April | 3260.03 | 22-APR-08:62 | 324.00 | 318.21 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.86 |
May | 3475.58 | 14-MAY-20:41 | 1386.00 | 947.05 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.57 |
June | 3603.84 | 10-JUN-21:51 | 1386.00 | 805.00 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.55 |
July | 3755.51 | 22-JUL-08:32 | 324.00 | 318.21 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.17 |
August | 3262.55 | 31-AUG-08:62 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.07 |
September | 3212.72 | 10-SEP-15:11 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.14 |
October | 2093.35 | 04-OCT-08:62 | 180.00 | 208.35 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.18 |
November | 0.00 | 01-NOV-00:10 | 180.00 | 16.10 | 44.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.71 |
December | 0.00 | 01-DEC-00:10 | 180.00 | 20.84 | 44.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 180.00 | 16.10 | 44.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.55 | |
Maximum of Months | 3755.51 | 1386.00 | 947.05 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 303.40 | 06-JAN-23:00 | 2263.36 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.15 |
February | 728.20 | 08-FEB-22:05 | 4526.71 | 1546.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.35 |
March | 1391.81 | 22-MAR-20:00 | 1760.39 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.02 |
April | 1918.37 | 22-APR-10:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.31 |
May | 2144.00 | 14-MAY-10:35 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.49 |
June | 2255.11 | 13-JUN-10:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 |
July | 2303.78 | 23-JUL-10:35 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.55 |
August | 2152.95 | 01-AUG-10:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.37 |
September | 1871.14 | 10-SEP-10:35 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.30 |
October | 1502.19 | 03-OCT-10:40 | 502.97 | 322.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.95 |
November | 429.25 | 01-NOV-21:30 | 2263.36 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.75 |
December | 313.09 | 24-DEC-22:50 | 2011.87 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 303.40 | 502.97 | 322.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.55 | |
Maximum of Months | 2303.78 | 4526.71 | 1546.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 360.00 | 49.25 | 89.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.95 |
February | 372.97 | 09-FEB-16:15 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.48 |
March | 3747.69 | 22-MAR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.42 |
April | 4017.61 | 21-APR-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.51 |
May | 4026.53 | 10-MAY-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 |
June | 4061.94 | 16-JUN-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 |
July | 3466.63 | 10-JUL-08:61 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.04 |
August | 4050.87 | 10-AUG-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 3938.40 | 07-SEP-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.28 |
October | 2555.67 | 03-OCT-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.80 |
November | 0.00 | 01-NOV-00:10 | 180.00 | 16.10 | 44.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.22 |
December | 0.00 | 01-DEC-00:10 | 180.00 | 20.84 | 44.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 180.00 | 16.10 | 44.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 | |
Maximum of Months | 4061.94 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 360.00 | 49.25 | 89.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.93 |
February | 0.00 | 01-FEB-00:05 | 360.00 | 41.67 | 89.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.92 |
March | 872.60 | 22-MAR-15:13 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.36 |
April | 3590.06 | 21-APR-18:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.49 |
May | 4455.62 | 09-MAY-19:42 | 831.60 | 568.23 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.12 |
June | 4006.52 | 28-JUN-21:32 | 1080.00 | 380.72 | 537.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.24 |
July | 3731.21 | 06-JUL-21:51 | 1800.00 | 634.53 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 |
August | 3567.27 | 01-AUG-21:51 | 1800.00 | 634.53 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.52 |
September | 3481.93 | 07-SEP-18:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.14 |
October | 1042.66 | 01-OCT-15:13 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.46 |
November | 0.00 | 01-NOV-00:10 | 180.00 | 16.10 | 44.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.20 |
December | 0.00 | 01-DEC-00:10 | 180.00 | 20.84 | 44.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 180.00 | 16.10 | 44.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | |
Maximum of Months | 4455.62 | 1800.00 | 634.53 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 216.92 | 30-JAN-13:55 | 72.00 | 33.34 | 61.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.47 |
February | 2556.60 | 15-FEB-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.80 |
March | 2648.70 | 31-MAR-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.08 |
April | 2706.14 | 20-APR-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.98 |
May | 2667.74 | 09-MAY-15:12 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 |
June | 2630.90 | 16-JUN-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.27 |
July | 2617.41 | 13-JUL-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 | 0.00 |
August | 2674.48 | 31-AUG-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.72 |
September | 2650.57 | 30-SEP-15:11 | 378.00 | 137.54 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.75 |
October | 2609.90 | 14-OCT-15:11 | 378.00 | 137.54 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.95 |
November | 1000.97 | 08-NOV-16:12 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.50 |
December | 200.59 | 24-DEC-09:05 | 324.00 | 200.06 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 200.59 | 72.00 | 33.34 | 61.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2706.14 | 970.20 | 370.95 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 | 173.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15803.07 | 06-JAN-23:10 | 26988.77 | 921.04 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.44 |
February | 17046.71 | 28-FEB-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1008.82 |
March | 16917.46 | 22-MAR-21:00 | 23990.02 | 2456.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.58 |
April | 18234.40 | 21-APR-20:30 | 23990.02 | 2298.49 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.74 |
May | 19751.91 | 31-MAY-21:10 | 53977.54 | 3322.39 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.86 |
June | 21790.55 | 21-JUN-21:03 | 161932.61 | 6631.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 |
July | 21345.72 | 11-JUL-21:10 | 53977.54 | 2210.50 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.19 |
August | 20862.44 | 02-AUG-21:10 | 53977.54 | 3586.89 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.39 |
September | 18233.24 | 01-SEP-21:00 | 23990.02 | 2456.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.70 |
October | 17303.40 | 06-OCT-21:00 | 23990.02 | 2456.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.41 |
November | 16833.76 | 28-NOV-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 992.57 |
December | 16997.92 | 14-DEC-22:30 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 998.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15803.07 | 23990.02 | 921.04 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | |
Maximum of Months | 21790.55 | 161932.61 | 6631.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1008.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17547.30 | 11-JAN-22:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1145.73 |
February | 18062.94 | 28-FEB-22:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1015.64 |
March | 17807.53 | 22-MAR-21:00 | 23990.02 | 2456.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.96 |
April | 18993.45 | 21-APR-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.70 |
May | 21096.18 | 10-MAY-21:07 | 80966.30 | 5184.14 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.47 |
June | 22463.08 | 21-JUN-21:03 | 161932.61 | 6631.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 |
July | 22593.61 | 11-JUL-21:10 | 53977.54 | 2210.50 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.24 |
August | 21453.76 | 02-AUG-21:52 | 269887.68 | 18420.82 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.54 |
September | 19324.19 | 01-SEP-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.04 |
October | 18245.71 | 06-OCT-21:00 | 23990.02 | 2456.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.77 |
November | 17517.53 | 28-NOV-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 998.97 |
December | 18201.94 | 14-DEC-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1020.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17517.53 | 23990.02 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | |
Maximum of Months | 22593.61 | 269887.68 | 18420.82 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1145.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23874.83 | 22-JAN-11:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 488.71 |
February | 25252.06 | 09-FEB-11:50 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 421.32 |
March | 27437.33 | 22-MAR-10:40 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 341.57 |
April | 29522.37 | 22-APR-10:50 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 177.20 |
May | 30010.71 | 12-MAY-10:40 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 98.60 |
June | 30530.16 | 29-JUN-10:50 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 |
July | 31170.94 | 22-JUL-10:40 | 1601.14 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 7.62 |
August | 30259.49 | 10-AUG-10:50 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 74.42 |
September | 29105.14 | 10-SEP-10:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 148.57 |
October | 27324.65 | 03-OCT-10:40 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 291.35 |
November | 23589.03 | 01-NOV-18:03 | 13075.94 | 6787.40 | 102231.89 | 104966.55 | 0.00 | 0.00 | 0.00 | 0.00 | 526.70 |
December | 24019.42 | 24-DEC-11:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 346.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 23589.03 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 7.62 | |
Maximum of Months | 31170.94 | 13075.94 | 6787.40 | 102231.89 | 104966.55 | 0.00 | 0.00 | 0.00 | 0.00 | 526.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 3726.24 | 818.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.90 |
February | 1246.35 | 09-FEB-13:40 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.15 |
March | 1655.72 | 22-MAR-10:35 | 1064.64 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.29 |
April | 3183.74 | 22-APR-14:00 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.63 |
May | 5096.20 | 31-MAY-14:10 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.75 |
June | 5931.37 | 29-JUN-14:20 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.53 | 0.00 |
July | 6315.14 | 23-JUL-13:40 | 532.32 | 272.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 | 0.00 |
August | 5364.19 | 10-AUG-15:10 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 |
September | 2301.80 | 02-SEP-15:13 | 4790.88 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.89 |
October | 1685.84 | 03-OCT-10:40 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.25 |
November | 0.00 | 01-NOV-00:10 | 2395.44 | 204.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.34 |
December | 0.00 | 01-DEC-00:10 | 2395.44 | 272.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 795.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 532.32 | 204.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6315.14 | 4790.88 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.53 | 795.86 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.353691E+12 | 219453.60 | 30-JAN-20:10 | 0.116586E+13 | 1136619.19 | 12-JAN-21:49 |
February | 0.312477E+12 | 217953.92 | 27-FEB-20:10 | 0.969741E+12 | 1012829.02 | 28-FEB-21:30 |
March | 0.338534E+12 | 214793.80 | 27-MAR-19:30 | 0.791647E+12 | 908419.52 | 01-MAR-21:00 |
April | 0.330201E+12 | 221464.02 | 21-APR-18:10 | 0.587894E+12 | 542868.23 | 24-APR-20:49 |
May | 0.358584E+12 | 241332.49 | 30-MAY-19:10 | 0.527557E+12 | 447290.86 | 27-MAY-21:00 |
June | 0.390446E+12 | 301443.71 | 29-JUN-19:10 | 0.449176E+12 | 405661.34 | 01-JUN-17:49 |
July | 0.415649E+12 | 298855.31 | 11-JUL-19:10 | 0.457369E+12 | 400484.44 | 03-JUL-17:19 |
August | 0.386479E+12 | 291274.84 | 11-AUG-19:10 | 0.470804E+12 | 410844.44 | 30-AUG-21:00 |
September | 0.323874E+12 | 222050.45 | 07-SEP-19:49 | 0.571620E+12 | 526297.35 | 29-SEP-18:10 |
October | 0.335988E+12 | 214886.85 | 23-OCT-19:30 | 0.677125E+12 | 554242.99 | 16-OCT-18:10 |
November | 0.339345E+12 | 218267.18 | 30-NOV-20:10 | 0.108518E+13 | 1028344.24 | 30-NOV-17:49 |
December | 0.357251E+12 | 220062.21 | 15-DEC-20:40 | 0.127869E+13 | 1065951.65 | 15-DEC-17:19 |
Annual Sum or Average | 0.424252E+13 | 0.903266E+13 | ||||
Minimum of Months | 0.312477E+12 | 214793.80 | 0.449176E+12 | 400484.44 | ||
Maximum of Months | 0.415649E+12 | 301443.71 | 0.127869E+13 | 1136619.19 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.479245E+11 | 0.265474E+11 | 0.140003E+12 | 0.544027E+11 | 0.504863E+11 | 0.157935E+10 | 0.00 | 0.168998E+09 | 0.00 | 0.00 | 0.211760E+11 | 0.770438E+10 | 0.00 |
February | 0.427397E+11 | 0.198624E+11 | 0.126445E+12 | 0.491378E+11 | 0.434162E+11 | 0.162293E+10 | 0.00 | 0.304866E+09 | 0.00 | 0.00 | 0.186452E+11 | 0.696187E+10 | 0.00 |
March | 0.466066E+11 | 0.173306E+11 | 0.140056E+12 | 0.544046E+11 | 0.450319E+11 | 0.263895E+10 | 0.00 | 0.151012E+10 | 0.00 | 0.00 | 0.195497E+11 | 0.770289E+10 | 0.00 |
April | 0.438692E+11 | 0.122003E+11 | 0.135446E+12 | 0.526461E+11 | 0.433098E+11 | 0.555094E+10 | 0.00 | 0.155664E+11 | 0.00 | 0.00 | 0.105698E+11 | 0.746489E+10 | 0.00 |
May | 0.448313E+11 | 0.797311E+10 | 0.140035E+12 | 0.544021E+11 | 0.466355E+11 | 0.810709E+10 | 0.00 | 0.426516E+11 | 0.00 | 0.00 | 0.253306E+10 | 0.770426E+10 | 0.00 |
June | 0.429917E+11 | 0.444184E+10 | 0.135537E+12 | 0.526479E+11 | 0.480510E+11 | 0.916833E+10 | 0.00 | 0.841202E+11 | 0.00 | 0.00 | 0.240789E+10 | 0.745688E+10 | 0.00 |
July | 0.445844E+11 | 0.617416E+10 | 0.139944E+12 | 0.543996E+11 | 0.493349E+11 | 0.968611E+10 | 0.00 | 0.964043E+11 | 0.00 | 0.00 | 0.366446E+10 | 0.771241E+10 | 0.00 |
August | 0.453370E+11 | 0.106530E+11 | 0.140067E+12 | 0.544038E+11 | 0.474834E+11 | 0.882805E+10 | 0.00 | 0.658300E+11 | 0.00 | 0.00 | 0.242194E+10 | 0.770435E+10 | 0.00 |
September | 0.448103E+11 | 0.148135E+11 | 0.135457E+12 | 0.526468E+11 | 0.426364E+11 | 0.517618E+10 | 0.00 | 0.133062E+11 | 0.00 | 0.00 | 0.395411E+10 | 0.746623E+10 | 0.00 |
October | 0.471009E+11 | 0.199809E+11 | 0.139992E+12 | 0.544023E+11 | 0.441117E+11 | 0.264974E+10 | 0.00 | 0.184319E+10 | 0.00 | 0.00 | 0.144926E+11 | 0.770291E+10 | 0.00 |
November | 0.462012E+11 | 0.239637E+11 | 0.135531E+12 | 0.526484E+11 | 0.480353E+11 | 0.132037E+10 | 0.00 | 0.128703E+09 | 0.00 | 0.00 | 0.204929E+11 | 0.744881E+10 | 0.00 |
December | 0.480916E+11 | 0.284278E+11 | 0.139944E+12 | 0.544017E+11 | 0.521399E+11 | 0.166487E+10 | 0.00 | 0.124281E+09 | 0.00 | 0.00 | 0.210465E+11 | 0.771240E+10 | 0.00 |
Annual Sum or Average | 0.545088E+12 | 0.192369E+12 | 0.164846E+13 | 0.640544E+12 | 0.560672E+12 | 0.579929E+11 | 0.00 | 0.321959E+12 | 0.00 | 0.00 | 0.140954E+12 | 0.907423E+11 | 0.00 |
Minimum of Months | 0.427397E+11 | 0.444184E+10 | 0.126445E+12 | 0.491378E+11 | 0.426364E+11 | 0.132037E+10 | 0.00 | 0.124281E+09 | 0.00 | 0.00 | 0.240789E+10 | 0.696187E+10 | 0.00 |
Maximum of Months | 0.480916E+11 | 0.284278E+11 | 0.140067E+12 | 0.544046E+11 | 0.521399E+11 | 0.968611E+10 | 0.00 | 0.964043E+11 | 0.00 | 0.00 | 0.211760E+11 | 0.771241E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.700893E+12 | 0.00 | 0.313050E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.549684E+12 | 0.00 | 0.282853E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.326345E+12 | 0.00 | 0.313278E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.137854E+12 | 0.00 | 0.303085E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.632802E+11 | 0.00 | 0.312299E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.404414E+10 | 0.00 | 0.298018E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.197136E+10 | 0.00 | 0.303577E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.178130E+11 | 0.00 | 0.300952E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.133828E+12 | 0.00 | 0.290821E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.222658E+12 | 0.00 | 0.302564E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.641541E+12 | 0.00 | 0.296546E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.815702E+12 | 0.00 | 0.311166E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.361561E+13 | 0.00 | 0.362821E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.197136E+10 | 0.00 | 0.282853E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.815702E+12 | 0.00 | 0.313278E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 45764.37 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 39153.73 | 02-JAN-07:19 | 30078.80 | 13-JAN-19:19 | 2269.36 | 27-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 45764.37 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 39153.73 | 01-FEB-07:19 | 28724.20 | 25-FEB-19:19 | 2333.70 | 15-FEB-16:19 | 0.00 | 01-FEB-00:10 |
March | 45764.37 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 39153.73 | 01-MAR-07:19 | 27092.94 | 01-MAR-19:19 | 2933.16 | 31-MAR-15:30 | 0.00 | 01-MAR-00:10 |
April | 45764.37 | 03-APR-19:40 | 12338.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 39153.73 | 03-APR-06:19 | 25482.39 | 21-APR-18:10 | 3975.30 | 22-APR-15:39 | 0.00 | 01-APR-00:10 |
May | 44592.48 | 02-MAY-19:00 | 12338.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 39151.70 | 16-MAY-06:19 | 27231.89 | 31-MAY-21:00 | 4141.36 | 31-MAY-15:09 | 0.00 | 01-MAY-00:10 |
June | 44070.94 | 02-JUN-19:00 | 12338.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 39151.68 | 27-JUN-06:19 | 31412.10 | 22-JUN-21:00 | 4603.18 | 21-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 43720.36 | 26-JUL-19:00 | 12338.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 39151.86 | 25-JUL-06:19 | 31376.78 | 11-JUL-21:00 | 4641.78 | 21-JUL-15:20 | 0.00 | 01-JUL-00:10 |
August | 45764.37 | 29-AUG-19:30 | 12338.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 39151.85 | 29-AUG-06:19 | 29235.16 | 02-AUG-21:00 | 4618.33 | 11-AUG-15:30 | 0.00 | 01-AUG-00:10 |
September | 45764.37 | 01-SEP-19:30 | 12338.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 39153.73 | 13-SEP-06:19 | 25101.81 | 08-SEP-18:10 | 3941.06 | 01-SEP-16:10 | 0.00 | 01-SEP-00:10 |
October | 45764.37 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 39153.73 | 02-OCT-06:19 | 25760.76 | 30-OCT-18:10 | 3141.10 | 03-OCT-15:20 | 0.00 | 01-OCT-00:10 |
November | 45764.37 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 39153.73 | 01-NOV-06:19 | 28334.49 | 09-NOV-19:19 | 2262.14 | 18-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 45764.37 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 39153.73 | 01-DEC-07:19 | 29742.02 | 04-DEC-19:19 | 2275.31 | 24-DEC-19:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 43720.36 | 12338.45 | 88863.15 | 39151.68 | 25101.81 | 2262.14 | 0.00 | |||||||
Maximum of Months | 45764.37 | 12338.45 | 88863.15 | 39153.73 | 31412.10 | 4641.78 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 1729.45 | 23-JAN-06:10 | 0.00 | 0.00 | 8265.52 | 01-JAN-00:10 | 4738.77 | 26-JAN-19:10 | 0.00 |
February | 2104.95 | 15-FEB-16:19 | 0.00 | 0.00 | 8265.52 | 01-FEB-00:10 | 4738.68 | 02-FEB-19:10 | 0.00 |
March | 11686.39 | 31-MAR-15:20 | 0.00 | 0.00 | 8265.52 | 01-MAR-00:10 | 4738.62 | 30-MAR-18:10 | 0.00 |
April | 44322.28 | 22-APR-15:20 | 0.00 | 0.00 | 8265.52 | 01-APR-00:10 | 4737.65 | 04-APR-06:30 | 0.00 |
May | 65881.34 | 31-MAY-15:00 | 0.00 | 0.00 | 8265.52 | 28-MAY-01:39 | 4738.25 | 03-MAY-06:19 | 0.00 |
June | 100655.74 | 20-JUN-18:19 | 0.00 | 0.00 | 8265.52 | 03-JUN-15:50 | 4738.58 | 08-JUN-18:10 | 0.00 |
July | 114978.03 | 29-JUL-15:30 | 0.00 | 0.00 | 8265.52 | 06-JUL-15:00 | 4738.73 | 13-JUL-18:10 | 0.00 |
August | 95788.47 | 11-AUG-18:10 | 0.00 | 0.00 | 8265.52 | 11-AUG-15:20 | 4738.47 | 10-AUG-18:10 | 0.00 |
September | 41613.96 | 09-SEP-15:20 | 0.00 | 0.00 | 8265.52 | 09-SEP-05:49 | 4738.28 | 20-SEP-06:19 | 0.00 |
October | 16412.27 | 03-OCT-15:20 | 0.00 | 0.00 | 8265.52 | 03-OCT-03:00 | 4738.75 | 12-OCT-18:10 | 0.00 |
November | 1591.73 | 04-NOV-05:10 | 0.00 | 0.00 | 8265.52 | 01-NOV-00:10 | 4738.69 | 15-NOV-19:10 | 0.00 |
December | 2225.97 | 24-DEC-19:10 | 0.00 | 0.00 | 8265.52 | 01-DEC-00:10 | 4738.24 | 18-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1591.73 | 0.00 | 0.00 | 8265.52 | 4737.65 | 0.00 | |||
Maximum of Months | 114978.03 | 0.00 | 0.00 | 8265.52 | 4738.77 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 219453.60 | 30-JAN-20:10 | 45764.37 | 86131.51 | 12338.45 | 31526.42 | 28492.05 | 1258.35 | 0.00 | 0.00 | 0.00 |
February | 217953.92 | 27-FEB-20:10 | 45764.37 | 86131.51 | 12338.45 | 31526.42 | 27067.22 | 1365.71 | 0.00 | 0.00 | 0.00 |
March | 214793.80 | 27-MAR-19:30 | 45764.37 | 86131.51 | 12338.45 | 31530.53 | 21852.30 | 2216.86 | 0.00 | 976.19 | 0.00 |
April | 221464.02 | 21-APR-18:10 | 36642.55 | 77265.07 | 0.00 | 31327.27 | 25482.39 | 3833.48 | 0.00 | 39612.46 | 0.00 |
May | 241332.49 | 30-MAY-19:10 | 41336.01 | 86131.51 | 0.00 | 31523.14 | 23131.12 | 3872.57 | 0.00 | 50349.26 | 0.00 |
June | 301443.71 | 29-JUN-19:10 | 41208.81 | 86131.51 | 0.00 | 31523.14 | 27000.70 | 4539.97 | 0.00 | 97264.07 | 0.00 |
July | 298855.31 | 11-JUL-19:10 | 41208.81 | 86131.51 | 0.00 | 31523.14 | 27976.01 | 4548.89 | 0.00 | 94204.09 | 0.00 |
August | 291274.84 | 11-AUG-19:10 | 41728.69 | 86131.51 | 0.00 | 31523.32 | 26902.92 | 4536.68 | 0.00 | 87255.36 | 0.00 |
September | 222050.45 | 07-SEP-19:49 | 45764.37 | 86131.51 | 12338.45 | 31530.53 | 22653.62 | 3206.71 | 0.00 | 13224.36 | 0.00 |
October | 214886.85 | 23-OCT-19:30 | 45764.37 | 86131.51 | 12338.45 | 31530.53 | 22330.91 | 2182.27 | 0.00 | 626.22 | 0.00 |
November | 218267.18 | 30-NOV-20:10 | 45764.37 | 86131.51 | 12338.45 | 31526.42 | 27414.31 | 1462.14 | 0.00 | 0.00 | 0.00 |
December | 220062.21 | 15-DEC-20:40 | 45764.37 | 86131.51 | 12338.45 | 31530.53 | 29323.64 | 1446.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 214793.80 | 36642.55 | 77265.07 | 0.00 | 31327.27 | 21852.30 | 1258.35 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 301443.71 | 45764.37 | 86131.51 | 12338.45 | 31530.53 | 29323.64 | 4548.89 | 0.00 | 97264.07 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 783717.68 | 12-JAN-10:20 | 0.00 | 312560.72 | 02-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 731428.99 | 27-FEB-07:10 | 0.00 | 312582.23 | 22-FEB-21:49 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 671924.99 | 01-MAR-07:10 | 0.00 | 312595.80 | 03-MAR-21:30 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 227329.63 | 03-APR-08:09 | 0.00 | 312582.66 | 26-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 163922.45 | 28-MAY-01:30 | 0.00 | 312572.74 | 11-MAY-20:19 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 101790.53 | 02-JUN-03:00 | 0.00 | 309321.80 | 01-JUN-20:30 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 34137.35 | 31-JUL-03:00 | 0.00 | 303583.36 | 03-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 175525.59 | 31-AUG-04:10 | 0.00 | 299470.38 | 01-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 198423.78 | 27-SEP-08:09 | 0.00 | 298487.16 | 29-SEP-20:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 250492.98 | 27-OCT-08:20 | 0.00 | 302464.30 | 31-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 719883.22 | 29-NOV-10:09 | 0.00 | 307602.61 | 29-NOV-21:49 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 750826.70 | 15-DEC-10:50 | 0.00 | 312495.03 | 29-DEC-21:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 34137.35 | 0.00 | 298487.16 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 783717.68 | 0.00 | 312595.80 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 56.17 | 18.90 | 56.17 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
February | 6.67 | 19.90 | 6.67 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.17 | 20.28 | 4.17 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
December | 19.17 | 19.55 | 19.17 | 19.55 | 0.00 | 19.55 | 0.00 | 19.55 |
Annual Sum or Average | 86.17 | 19.18 | 86.17 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 56.17 | 20.28 | 56.17 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.00 | 19.97 | 31.00 | 19.97 | 0.00 | 19.97 | 0.00 | 19.97 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.67 | 20.15 | 6.67 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 |
Annual Sum or Average | 37.67 | 20.00 | 37.67 | 20.00 | 0.00 | 20.00 | 0.00 | 20.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.00 | 20.15 | 31.00 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.50 | 20.21 | 32.50 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.50 | 20.21 | 32.50 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.50 | 20.21 | 32.50 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 56.50 | 19.62 | 56.50 | 19.62 | 0.00 | 19.62 | 0.00 | 19.62 |
February | 10.17 | 20.22 | 10.17 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15.00 | 20.11 | 15.00 | 20.11 | 0.00 | 20.11 | 0.00 | 20.11 |
Annual Sum or Average | 81.67 | 19.78 | 81.67 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 56.50 | 20.22 | 56.50 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.17 | 19.20 | 36.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
February | 1.33 | 20.16 | 1.33 | 20.16 | 0.00 | 20.16 | 0.00 | 20.16 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.83 | 20.24 | 3.83 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
December | 11.33 | 19.39 | 11.33 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Annual Sum or Average | 52.67 | 19.34 | 52.67 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 36.17 | 20.24 | 36.17 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.67 | 19.94 | 19.67 | 19.94 | 0.00 | 19.94 | 0.00 | 19.94 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.83 | 20.14 | 5.83 | 20.14 | 0.00 | 20.14 | 0.00 | 20.14 |
Annual Sum or Average | 25.50 | 19.98 | 25.50 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 19.67 | 20.14 | 19.67 | 20.14 | 0.00 | 20.14 | 0.00 | 20.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.00 | 20.26 | 31.00 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
February | 2.83 | 20.38 | 2.83 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
March | 0.17 | 20.45 | 0.17 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.80 | 0.83 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.78 | 0.67 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5.83 | 20.29 | 5.83 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
December | 14.17 | 20.33 | 14.17 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Annual Sum or Average | 54.00 | 20.29 | 54.00 | 20.29 | 2.50 | 20.32 | 2.50 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.00 | 20.45 | 31.00 | 20.45 | 0.83 | 21.80 | 0.83 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 39.67 | 20.08 | 39.67 | 20.08 | 0.00 | 20.08 | 0.00 | 20.08 |
February | 6.00 | 20.35 | 6.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
March | 0.50 | 20.35 | 0.50 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.78 | 1.33 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 22.03 | 3.00 | 22.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.87 | 2.17 | 21.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.86 | 0.33 | 21.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.33 | 20.30 | 10.33 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
December | 17.67 | 20.29 | 17.67 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
Annual Sum or Average | 74.17 | 20.18 | 74.17 | 20.18 | 6.83 | 20.26 | 6.83 | 20.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.67 | 20.35 | 39.67 | 20.35 | 3.00 | 22.03 | 3.00 | 22.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.67 | 19.66 | 52.67 | 19.66 | 0.00 | 19.66 | 0.00 | 19.66 |
February | 26.00 | 20.17 | 26.00 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 |
March | 3.67 | 20.29 | 3.67 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.74 | 1.00 | 21.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 21.88 | 8.33 | 21.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 21.83 | 7.67 | 21.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.74 | 2.17 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.50 | 20.28 | 1.50 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
November | 42.17 | 20.21 | 42.17 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
December | 50.00 | 20.17 | 50.00 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 |
Annual Sum or Average | 176.00 | 20.03 | 176.00 | 20.03 | 19.17 | 20.12 | 19.17 | 20.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.67 | 20.29 | 52.67 | 20.29 | 8.33 | 21.88 | 8.33 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.33 | 20.18 | 35.33 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
February | 2.17 | 20.42 | 2.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.78 | 1.67 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.82 | 0.83 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.85 | 1.33 | 21.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.73 | 0.50 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8.17 | 20.33 | 8.17 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
December | 16.67 | 20.32 | 16.67 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 62.33 | 20.25 | 62.33 | 20.25 | 4.33 | 20.30 | 4.33 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 35.33 | 20.42 | 35.33 | 20.42 | 1.67 | 21.85 | 1.67 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.67 | 20.00 | 41.67 | 20.00 | 0.00 | 20.00 | 0.00 | 20.00 |
February | 5.50 | 20.40 | 5.50 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.87 | 2.33 | 21.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 22.09 | 5.00 | 22.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 22.30 | 7.00 | 22.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.90 | 0.50 | 21.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.67 | 20.29 | 11.67 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
December | 19.00 | 20.26 | 19.00 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
Annual Sum or Average | 77.83 | 20.13 | 77.83 | 20.13 | 14.83 | 20.31 | 14.83 | 20.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.67 | 20.40 | 41.67 | 20.40 | 7.00 | 22.30 | 7.00 | 22.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.17 | 20.14 | 41.17 | 20.14 | 0.00 | 20.14 | 0.00 | 20.14 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.67 | 20.32 | 6.67 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 47.83 | 20.16 | 47.83 | 20.16 | 0.00 | 20.16 | 0.00 | 20.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.17 | 20.32 | 41.17 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.33 | 19.95 | 41.33 | 19.95 | 0.00 | 19.95 | 0.00 | 19.95 |
February | 3.50 | 20.34 | 3.50 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
March | 0.33 | 20.46 | 0.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.88 | 0.17 | 21.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.81 | 1.33 | 21.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.74 | 1.33 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.82 | 0.50 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9.17 | 20.26 | 9.17 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
December | 20.33 | 20.27 | 20.33 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
Annual Sum or Average | 74.67 | 20.09 | 74.67 | 20.09 | 3.33 | 20.13 | 3.33 | 20.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.33 | 20.46 | 41.33 | 20.46 | 1.33 | 21.88 | 1.33 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 45.83 | 19.66 | 45.83 | 19.66 | 0.00 | 19.66 | 0.00 | 19.66 |
February | 10.50 | 20.33 | 10.50 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
March | 1.17 | 20.40 | 1.17 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.92 | 1.50 | 21.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 22.02 | 5.00 | 22.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.92 | 3.67 | 21.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.92 | 0.83 | 21.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18.67 | 20.26 | 18.67 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
December | 26.67 | 20.20 | 26.67 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
Annual Sum or Average | 102.83 | 19.99 | 102.83 | 19.99 | 11.00 | 20.09 | 11.00 | 20.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.83 | 20.40 | 45.83 | 20.40 | 5.00 | 22.02 | 5.00 | 22.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.83 | 20.20 | 12.83 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
February | 1.00 | 20.47 | 1.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.76 | 1.17 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.17 | 20.34 | 4.17 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
December | 11.50 | 20.31 | 11.50 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
Annual Sum or Average | 29.50 | 20.27 | 29.50 | 20.27 | 2.33 | 20.33 | 2.33 | 20.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.83 | 20.47 | 12.83 | 20.47 | 1.17 | 21.77 | 1.17 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.67 | 19.27 | 12.67 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
February | 0.17 | 20.44 | 0.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.83 | 19.94 | 4.83 | 19.94 | 0.00 | 19.94 | 0.00 | 19.94 |
Annual Sum or Average | 17.67 | 19.46 | 17.67 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.67 | 20.44 | 12.67 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.33 | 19.31 | 7.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.28 | 0.17 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
Annual Sum or Average | 7.50 | 19.33 | 7.50 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.33 | 20.28 | 7.33 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 57.33 | 19.57 | 57.33 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
February | 4.00 | 20.32 | 4.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13.17 | 20.05 | 13.17 | 20.05 | 0.00 | 20.05 | 0.00 | 20.05 |
Annual Sum or Average | 74.50 | 19.70 | 74.50 | 19.70 | 0.00 | 19.70 | 0.00 | 19.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.33 | 20.32 | 57.33 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.09 | 46.33 | 22.02 | 46.33 | 21.97 |
February | 672.00 | 21.55 | 103.00 | 21.48 | 103.00 | 21.43 |
March | 744.00 | 21.45 | 98.67 | 21.41 | 98.67 | 21.37 |
April | 720.00 | 21.65 | 1.33 | 21.65 | 1.33 | 21.65 |
May | 744.00 | 21.74 | 0.00 | 21.74 | 0.00 | 21.74 |
June | 720.00 | 22.00 | 0.00 | 22.00 | 0.00 | 22.00 |
July | 744.00 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
August | 722.83 | 23.21 | 0.00 | 23.21 | 0.00 | 23.21 |
September | 699.83 | 23.54 | 0.00 | 23.54 | 0.00 | 23.54 |
October | 744.00 | 23.57 | 0.00 | 23.57 | 0.00 | 23.57 |
November | 720.00 | 23.27 | 0.00 | 23.27 | 0.00 | 23.27 |
December | 744.00 | 22.64 | 0.00 | 22.64 | 0.00 | 22.64 |
Annual Sum or Average | 8718.67 | 22.44 | 249.33 | 22.40 | 249.33 | 22.37 |
Minimum of Months | 672.00 | 21.45 | 0.00 | 21.41 | 0.00 | 21.37 |
Maximum of Months | 744.00 | 23.57 | 103.00 | 23.57 | 103.00 | 23.57 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.84 | 738.50 | 20.84 | 738.50 | 20.84 |
February | 672.00 | 21.06 | 601.17 | 21.03 | 601.17 | 21.01 |
March | 685.00 | 21.23 | 416.67 | 21.14 | 416.67 | 21.11 |
April | 552.67 | 21.88 | 115.67 | 21.97 | 61.50 | 21.89 |
May | 485.83 | 22.54 | 83.83 | 22.75 | 0.00 | 22.75 |
June | 269.33 | 22.90 | 233.50 | 23.40 | 0.00 | 23.40 |
July | 242.33 | 22.81 | 370.17 | 23.51 | 0.00 | 23.51 |
August | 366.33 | 22.64 | 236.33 | 23.17 | 0.00 | 23.17 |
September | 620.83 | 21.76 | 51.00 | 21.91 | 5.83 | 21.90 |
October | 722.33 | 21.16 | 346.67 | 21.12 | 343.17 | 21.09 |
November | 720.00 | 21.00 | 704.67 | 20.99 | 704.67 | 20.99 |
December | 744.00 | 20.95 | 744.00 | 20.95 | 744.00 | 20.95 |
Annual Sum or Average | 6824.67 | 21.50 | 4642.17 | 21.55 | 3615.50 | 21.41 |
Minimum of Months | 242.33 | 20.84 | 51.00 | 20.84 | 0.00 | 20.84 |
Maximum of Months | 744.00 | 22.90 | 744.00 | 23.51 | 744.00 | 23.51 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.97 | 406.00 | 20.95 | 406.00 | 20.93 |
February | 672.00 | 21.06 | 260.83 | 21.04 | 260.83 | 21.03 |
March | 744.00 | 21.21 | 99.00 | 21.19 | 99.00 | 21.17 |
April | 720.00 | 22.01 | 1.17 | 22.01 | 1.17 | 22.01 |
May | 742.67 | 22.57 | 0.00 | 22.57 | 0.00 | 22.57 |
June | 624.33 | 22.88 | 14.67 | 22.90 | 0.00 | 22.90 |
July | 560.17 | 22.79 | 47.33 | 22.87 | 0.00 | 22.87 |
August | 641.17 | 22.74 | 18.17 | 22.77 | 0.00 | 22.77 |
September | 720.00 | 22.09 | 0.00 | 22.09 | 0.00 | 22.09 |
October | 744.00 | 21.38 | 20.00 | 21.37 | 20.00 | 21.36 |
November | 720.00 | 21.03 | 364.50 | 21.02 | 364.50 | 21.01 |
December | 744.00 | 21.00 | 512.83 | 20.99 | 512.83 | 20.99 |
Annual Sum or Average | 8376.33 | 21.77 | 1744.50 | 21.66 | 1664.33 | 21.56 |
Minimum of Months | 560.17 | 20.97 | 0.00 | 20.95 | 0.00 | 20.93 |
Maximum of Months | 744.00 | 22.88 | 512.83 | 22.90 | 512.83 | 22.90 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.97 | 677.67 | 20.97 | 677.67 | 20.96 |
February | 672.00 | 21.08 | 506.50 | 21.05 | 506.50 | 21.03 |
March | 744.00 | 21.32 | 367.83 | 21.22 | 367.83 | 21.17 |
April | 720.00 | 22.80 | 60.50 | 22.67 | 60.50 | 22.55 |
May | 744.00 | 23.93 | 0.00 | 23.93 | 0.00 | 23.93 |
June | 501.67 | 24.00 | 3.33 | 24.00 | 0.00 | 24.00 |
July | 122.83 | 23.99 | 10.00 | 24.00 | 0.00 | 24.00 |
August | 314.33 | 23.98 | 5.83 | 23.98 | 0.00 | 23.98 |
September | 720.00 | 23.62 | 0.00 | 23.62 | 0.00 | 23.62 |
October | 744.00 | 22.18 | 128.83 | 22.01 | 128.83 | 21.88 |
November | 720.00 | 21.02 | 683.83 | 21.01 | 683.83 | 21.01 |
December | 744.00 | 21.00 | 696.50 | 21.00 | 696.50 | 21.00 |
Annual Sum or Average | 7490.83 | 22.25 | 3140.83 | 21.88 | 3121.67 | 21.68 |
Minimum of Months | 122.83 | 20.97 | 0.00 | 20.97 | 0.00 | 20.96 |
Maximum of Months | 744.00 | 24.00 | 696.50 | 24.00 | 696.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.89 | 723.17 | 20.89 | 723.17 | 20.89 |
February | 672.00 | 20.98 | 605.50 | 20.98 | 605.50 | 20.98 |
March | 744.00 | 21.00 | 575.50 | 21.00 | 575.50 | 21.00 |
April | 720.00 | 21.03 | 174.50 | 21.03 | 174.50 | 21.02 |
May | 744.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
June | 720.00 | 21.97 | 0.00 | 21.97 | 0.00 | 21.97 |
July | 744.00 | 22.03 | 0.00 | 22.03 | 0.00 | 22.03 |
August | 744.00 | 21.79 | 0.00 | 21.79 | 0.00 | 21.79 |
September | 720.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
October | 744.00 | 21.00 | 247.67 | 21.00 | 247.67 | 21.00 |
November | 720.00 | 20.99 | 708.83 | 20.99 | 708.83 | 20.99 |
December | 744.00 | 20.97 | 739.17 | 20.97 | 739.17 | 20.97 |
Annual Sum or Average | 8760.00 | 21.27 | 3774.33 | 21.18 | 3774.33 | 21.13 |
Minimum of Months | 672.00 | 20.89 | 0.00 | 20.89 | 0.00 | 20.89 |
Maximum of Months | 744.00 | 22.03 | 739.17 | 22.03 | 739.17 | 22.03 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 127.17 | 24.00 | 719.50 | 24.00 | 127.17 | 24.00 |
February | 121.17 | 24.00 | 652.83 | 24.00 | 121.17 | 24.00 |
March | 148.83 | 24.00 | 730.17 | 24.00 | 148.83 | 24.00 |
April | 169.83 | 24.00 | 720.00 | 24.00 | 169.83 | 24.00 |
May | 238.83 | 24.00 | 744.00 | 24.00 | 238.83 | 24.00 |
June | 342.00 | 24.00 | 720.00 | 24.00 | 342.00 | 24.00 |
July | 462.83 | 24.00 | 744.00 | 24.00 | 462.83 | 24.00 |
August | 359.50 | 24.00 | 744.00 | 24.00 | 359.50 | 24.00 |
September | 236.33 | 24.00 | 720.00 | 24.00 | 236.33 | 24.00 |
October | 169.00 | 24.00 | 744.00 | 24.00 | 169.00 | 24.00 |
November | 122.17 | 24.00 | 699.00 | 24.00 | 122.17 | 24.00 |
December | 124.50 | 24.00 | 708.33 | 24.00 | 124.50 | 24.00 |
Annual Sum or Average | 2622.17 | 24.00 | 8645.83 | 24.00 | 2622.17 | 24.00 |
Minimum of Months | 121.17 | 24.00 | 652.83 | 24.00 | 121.17 | 24.00 |
Maximum of Months | 462.83 | 24.00 | 744.00 | 24.00 | 462.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.91 | 651.50 | 20.91 | 651.50 | 20.90 |
February | 672.00 | 21.04 | 362.33 | 21.02 | 362.33 | 21.02 |
March | 704.17 | 21.28 | 105.00 | 21.28 | 94.67 | 21.25 |
April | 601.67 | 21.90 | 73.33 | 22.10 | 4.67 | 22.09 |
May | 605.50 | 22.21 | 64.33 | 22.37 | 0.00 | 22.37 |
June | 410.67 | 22.30 | 143.17 | 22.63 | 0.00 | 22.63 |
July | 353.17 | 22.07 | 249.83 | 22.65 | 5.00 | 22.66 |
August | 467.50 | 22.09 | 172.00 | 22.51 | 3.00 | 22.51 |
September | 656.67 | 21.77 | 38.33 | 21.89 | 0.00 | 21.89 |
October | 729.00 | 21.26 | 70.50 | 21.26 | 65.67 | 21.24 |
November | 720.00 | 21.00 | 617.00 | 21.00 | 617.00 | 21.00 |
December | 744.00 | 20.97 | 703.83 | 20.97 | 703.83 | 20.97 |
Annual Sum or Average | 7408.33 | 21.48 | 3251.17 | 21.51 | 2507.67 | 21.41 |
Minimum of Months | 353.17 | 20.91 | 38.33 | 20.91 | 0.00 | 20.90 |
Maximum of Months | 744.00 | 22.30 | 703.83 | 22.65 | 703.83 | 22.66 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.17 | 291.83 | 21.10 | 291.83 | 21.06 |
February | 672.00 | 21.30 | 163.67 | 21.24 | 163.67 | 21.20 |
March | 744.00 | 21.66 | 21.83 | 21.64 | 21.83 | 21.62 |
April | 714.50 | 22.51 | 0.00 | 22.51 | 0.00 | 22.51 |
May | 700.50 | 22.90 | 0.00 | 22.90 | 0.00 | 22.90 |
June | 391.83 | 22.83 | 64.67 | 22.98 | 0.00 | 22.98 |
July | 316.17 | 22.74 | 227.33 | 23.18 | 11.50 | 23.20 |
August | 379.50 | 22.72 | 120.00 | 23.00 | 5.50 | 23.00 |
September | 697.50 | 22.53 | 0.00 | 22.53 | 0.00 | 22.53 |
October | 744.00 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
November | 720.00 | 21.23 | 241.50 | 21.17 | 241.50 | 21.14 |
December | 744.00 | 21.11 | 386.00 | 21.07 | 386.00 | 21.05 |
Annual Sum or Average | 7568.00 | 21.94 | 1516.83 | 21.91 | 1121.83 | 21.81 |
Minimum of Months | 316.17 | 21.11 | 0.00 | 21.07 | 0.00 | 21.05 |
Maximum of Months | 744.00 | 22.90 | 386.00 | 23.18 | 386.00 | 23.20 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.37 | 744.00 | 20.37 | 744.00 | 20.37 |
February | 672.00 | 20.44 | 672.00 | 20.44 | 672.00 | 20.44 |
March | 744.00 | 20.72 | 659.50 | 20.68 | 659.50 | 20.67 |
April | 712.83 | 21.39 | 201.50 | 21.27 | 201.50 | 21.19 |
May | 729.83 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
June | 647.00 | 21.59 | 4.33 | 21.60 | 0.00 | 21.60 |
July | 649.00 | 21.53 | 5.00 | 21.55 | 0.00 | 21.55 |
August | 684.50 | 21.57 | 0.33 | 21.57 | 0.00 | 21.57 |
September | 717.83 | 21.31 | 112.83 | 21.22 | 112.83 | 21.15 |
October | 744.00 | 20.67 | 578.50 | 20.61 | 578.50 | 20.59 |
November | 720.00 | 20.40 | 720.00 | 20.40 | 720.00 | 20.40 |
December | 744.00 | 20.39 | 744.00 | 20.39 | 744.00 | 20.39 |
Annual Sum or Average | 8509.00 | 20.99 | 4442.00 | 20.82 | 4432.33 | 20.73 |
Minimum of Months | 647.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Maximum of Months | 744.00 | 21.67 | 744.00 | 21.67 | 744.00 | 21.67 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.35 | 744.00 | 20.35 | 744.00 | 20.35 |
February | 672.00 | 20.41 | 672.00 | 20.41 | 672.00 | 20.41 |
March | 744.00 | 20.48 | 728.00 | 20.48 | 728.00 | 20.47 |
April | 719.83 | 21.05 | 321.17 | 20.92 | 321.17 | 20.86 |
May | 687.50 | 21.69 | 37.00 | 21.92 | 2.67 | 21.93 |
June | 587.00 | 22.17 | 102.67 | 22.78 | 27.67 | 22.98 |
July | 577.67 | 21.90 | 109.50 | 22.45 | 6.67 | 22.50 |
August | 660.00 | 21.86 | 58.17 | 22.18 | 6.00 | 22.23 |
September | 717.33 | 21.09 | 167.00 | 20.98 | 166.33 | 20.91 |
October | 744.00 | 20.53 | 665.50 | 20.50 | 665.50 | 20.49 |
November | 720.00 | 20.39 | 720.00 | 20.39 | 720.00 | 20.39 |
December | 744.00 | 20.39 | 744.00 | 20.39 | 744.00 | 20.39 |
Annual Sum or Average | 8317.33 | 20.98 | 5069.00 | 20.90 | 4804.00 | 20.79 |
Minimum of Months | 577.67 | 20.35 | 37.00 | 20.35 | 2.67 | 20.35 |
Maximum of Months | 744.00 | 22.17 | 744.00 | 22.78 | 744.00 | 22.98 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.41 | 744.00 | 20.41 | 744.00 | 20.41 |
February | 672.00 | 20.52 | 662.17 | 20.52 | 662.17 | 20.52 |
March | 744.00 | 20.72 | 651.33 | 20.69 | 651.33 | 20.68 |
April | 720.00 | 21.12 | 245.83 | 21.05 | 245.83 | 21.01 |
May | 744.00 | 21.66 | 0.00 | 21.66 | 0.00 | 21.66 |
June | 712.50 | 22.11 | 0.00 | 22.11 | 0.00 | 22.11 |
July | 717.00 | 22.07 | 1.33 | 22.07 | 0.00 | 22.07 |
August | 741.17 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
September | 720.00 | 21.25 | 30.17 | 21.22 | 30.17 | 21.19 |
October | 744.00 | 20.85 | 408.17 | 20.77 | 408.17 | 20.73 |
November | 720.00 | 20.46 | 720.00 | 20.46 | 720.00 | 20.46 |
December | 744.00 | 20.43 | 742.33 | 20.43 | 742.33 | 20.43 |
Annual Sum or Average | 8722.67 | 21.12 | 4205.33 | 20.93 | 4204.00 | 20.83 |
Minimum of Months | 672.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Maximum of Months | 744.00 | 22.11 | 744.00 | 22.11 | 744.00 | 22.11 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.36 | 744.00 | 20.36 | 744.00 | 20.36 |
February | 672.00 | 20.48 | 664.83 | 20.47 | 664.83 | 20.47 |
March | 744.00 | 21.00 | 553.50 | 20.90 | 553.50 | 20.86 |
April | 713.83 | 21.53 | 173.00 | 21.42 | 173.00 | 21.35 |
May | 667.67 | 21.60 | 0.83 | 21.60 | 0.83 | 21.60 |
June | 594.50 | 21.47 | 7.33 | 21.49 | 0.00 | 21.49 |
July | 602.83 | 21.44 | 17.50 | 21.49 | 0.00 | 21.49 |
August | 662.33 | 21.58 | 5.17 | 21.59 | 0.00 | 21.59 |
September | 713.17 | 21.44 | 65.83 | 21.39 | 65.83 | 21.35 |
October | 744.00 | 20.79 | 518.17 | 20.70 | 518.17 | 20.66 |
November | 720.00 | 20.40 | 720.00 | 20.40 | 720.00 | 20.40 |
December | 744.00 | 20.39 | 744.00 | 20.39 | 744.00 | 20.39 |
Annual Sum or Average | 8322.33 | 21.02 | 4214.17 | 20.85 | 4184.17 | 20.76 |
Minimum of Months | 594.50 | 20.36 | 0.83 | 20.36 | 0.00 | 20.36 |
Maximum of Months | 744.00 | 21.60 | 744.00 | 21.60 | 744.00 | 21.60 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.35 | 744.00 | 20.35 | 744.00 | 20.35 |
February | 672.00 | 20.42 | 671.83 | 20.42 | 671.83 | 20.42 |
March | 744.00 | 20.66 | 664.83 | 20.63 | 664.83 | 20.62 |
April | 720.00 | 21.30 | 278.67 | 21.16 | 278.67 | 21.08 |
May | 714.67 | 21.91 | 2.17 | 21.91 | 1.50 | 21.91 |
June | 547.83 | 21.91 | 34.67 | 22.10 | 1.83 | 22.11 |
July | 515.83 | 21.85 | 104.33 | 22.38 | 11.33 | 22.48 |
August | 659.00 | 21.93 | 16.83 | 22.00 | 0.00 | 22.00 |
September | 720.00 | 21.32 | 129.83 | 21.23 | 129.83 | 21.17 |
October | 744.00 | 20.63 | 588.33 | 20.57 | 588.33 | 20.55 |
November | 720.00 | 20.39 | 720.00 | 20.39 | 720.00 | 20.39 |
December | 744.00 | 20.38 | 744.00 | 20.38 | 744.00 | 20.38 |
Annual Sum or Average | 8245.33 | 21.04 | 4699.50 | 20.89 | 4556.17 | 20.78 |
Minimum of Months | 515.83 | 20.35 | 2.17 | 20.35 | 0.00 | 20.35 |
Maximum of Months | 744.00 | 21.93 | 744.00 | 22.38 | 744.00 | 22.48 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.94 | 655.50 | 20.94 | 655.50 | 20.94 |
February | 672.00 | 21.00 | 525.67 | 21.00 | 525.67 | 21.00 |
March | 744.00 | 21.00 | 419.83 | 21.00 | 419.83 | 21.00 |
April | 720.00 | 21.53 | 62.00 | 21.49 | 62.00 | 21.45 |
May | 744.00 | 22.56 | 0.00 | 22.56 | 0.00 | 22.56 |
June | 706.33 | 23.28 | 0.00 | 23.28 | 0.00 | 23.28 |
July | 652.83 | 23.18 | 0.00 | 23.18 | 0.00 | 23.18 |
August | 743.00 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
September | 720.00 | 21.54 | 1.83 | 21.54 | 1.83 | 21.54 |
October | 744.00 | 21.01 | 215.33 | 21.01 | 215.33 | 21.01 |
November | 720.00 | 21.00 | 650.17 | 21.00 | 650.17 | 21.00 |
December | 744.00 | 20.98 | 698.33 | 20.98 | 698.33 | 20.98 |
Annual Sum or Average | 8654.17 | 21.73 | 3228.67 | 21.52 | 3228.67 | 21.41 |
Minimum of Months | 652.83 | 20.94 | 0.00 | 20.94 | 0.00 | 20.94 |
Maximum of Months | 744.00 | 23.28 | 698.33 | 23.28 | 698.33 | 23.28 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.34 | 744.00 | 20.34 | 744.00 | 20.34 |
February | 672.00 | 20.41 | 672.00 | 20.41 | 672.00 | 20.41 |
March | 744.00 | 20.60 | 693.17 | 20.58 | 693.17 | 20.57 |
April | 709.33 | 21.28 | 282.83 | 21.14 | 282.83 | 21.06 |
May | 719.33 | 21.61 | 16.67 | 21.59 | 16.67 | 21.57 |
June | 634.00 | 21.54 | 9.00 | 21.56 | 0.00 | 21.56 |
July | 632.83 | 21.47 | 11.50 | 21.51 | 0.00 | 21.51 |
August | 676.00 | 21.51 | 11.83 | 21.51 | 8.33 | 21.51 |
September | 716.33 | 21.20 | 182.50 | 21.08 | 182.50 | 21.00 |
October | 744.00 | 20.58 | 660.50 | 20.55 | 660.50 | 20.53 |
November | 720.00 | 20.39 | 720.00 | 20.39 | 720.00 | 20.39 |
December | 744.00 | 20.38 | 744.00 | 20.38 | 744.00 | 20.38 |
Annual Sum or Average | 8455.83 | 20.92 | 4748.00 | 20.76 | 4724.00 | 20.68 |
Minimum of Months | 632.83 | 20.34 | 9.00 | 20.34 | 0.00 | 20.34 |
Maximum of Months | 744.00 | 21.61 | 744.00 | 21.59 | 744.00 | 21.57 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.31 | 744.00 | 20.31 | 744.00 | 20.31 |
February | 672.00 | 20.39 | 672.00 | 20.39 | 672.00 | 20.39 |
March | 744.00 | 20.45 | 738.83 | 20.44 | 738.83 | 20.44 |
April | 719.00 | 20.96 | 396.00 | 20.83 | 396.00 | 20.77 |
May | 688.17 | 21.69 | 65.00 | 21.94 | 31.67 | 21.97 |
June | 590.33 | 22.32 | 116.67 | 23.02 | 44.33 | 23.33 |
July | 566.33 | 21.93 | 117.17 | 22.56 | 15.83 | 22.68 |
August | 655.67 | 21.87 | 85.83 | 22.24 | 32.67 | 22.32 |
September | 716.83 | 20.96 | 241.00 | 20.85 | 240.00 | 20.78 |
October | 744.00 | 20.47 | 729.83 | 20.47 | 729.83 | 20.46 |
November | 720.00 | 20.37 | 720.00 | 20.37 | 720.00 | 20.37 |
December | 744.00 | 20.36 | 744.00 | 20.36 | 744.00 | 20.36 |
Annual Sum or Average | 8304.33 | 20.96 | 5370.33 | 20.89 | 5109.17 | 20.79 |
Minimum of Months | 566.33 | 20.31 | 65.00 | 20.31 | 15.83 | 20.31 |
Maximum of Months | 744.00 | 22.32 | 744.00 | 23.02 | 744.00 | 23.33 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.41 | 744.00 | 20.41 | 744.00 | 20.41 |
February | 672.00 | 20.77 | 611.33 | 20.70 | 611.33 | 20.67 |
March | 730.50 | 21.18 | 502.17 | 21.04 | 502.17 | 20.98 |
April | 659.67 | 21.44 | 133.00 | 21.37 | 129.17 | 21.31 |
May | 667.00 | 21.54 | 3.00 | 21.55 | 0.17 | 21.55 |
June | 618.50 | 21.50 | 15.50 | 21.55 | 0.00 | 21.55 |
July | 630.67 | 21.48 | 33.50 | 21.57 | 0.00 | 21.57 |
August | 648.17 | 21.50 | 39.00 | 21.60 | 0.00 | 21.60 |
September | 678.83 | 21.41 | 38.33 | 21.38 | 35.00 | 21.35 |
October | 733.83 | 20.98 | 446.83 | 20.86 | 446.83 | 20.80 |
November | 720.00 | 20.48 | 713.00 | 20.47 | 713.00 | 20.47 |
December | 744.00 | 20.40 | 744.00 | 20.40 | 744.00 | 20.40 |
Annual Sum or Average | 8247.17 | 21.07 | 4023.67 | 20.92 | 3925.67 | 20.83 |
Minimum of Months | 618.50 | 20.40 | 3.00 | 20.40 | 0.00 | 20.40 |
Maximum of Months | 744.00 | 21.54 | 744.00 | 21.60 | 744.00 | 21.60 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.36 | 209.50 | 21.25 | 209.50 | 21.18 |
February | 672.00 | 21.44 | 146.33 | 21.36 | 146.33 | 21.31 |
March | 744.00 | 21.63 | 42.50 | 21.60 | 42.50 | 21.57 |
April | 711.17 | 22.03 | 0.00 | 22.03 | 0.00 | 22.03 |
May | 644.00 | 22.40 | 3.83 | 22.41 | 0.00 | 22.41 |
June | 344.67 | 22.24 | 190.17 | 22.76 | 0.00 | 22.76 |
July | 311.17 | 22.17 | 287.50 | 22.85 | 9.00 | 22.86 |
August | 432.00 | 22.17 | 140.17 | 22.52 | 4.33 | 22.53 |
September | 680.33 | 22.15 | 2.00 | 22.16 | 0.00 | 22.16 |
October | 744.00 | 21.81 | 0.00 | 21.81 | 0.00 | 21.81 |
November | 720.00 | 21.38 | 190.50 | 21.30 | 190.50 | 21.25 |
December | 744.00 | 21.31 | 255.00 | 21.23 | 255.00 | 21.18 |
Annual Sum or Average | 7491.33 | 21.78 | 1467.50 | 21.83 | 857.17 | 21.76 |
Minimum of Months | 311.17 | 21.31 | 0.00 | 21.23 | 0.00 | 21.18 |
Maximum of Months | 744.00 | 22.40 | 287.50 | 22.85 | 255.00 | 22.86 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.58 | 102.67 | 21.48 | 102.67 | 21.41 |
February | 672.00 | 21.66 | 49.17 | 21.61 | 49.17 | 21.57 |
March | 740.00 | 21.89 | 8.33 | 21.88 | 8.33 | 21.87 |
April | 682.67 | 22.30 | 0.00 | 22.30 | 0.00 | 22.30 |
May | 517.50 | 22.51 | 20.17 | 22.56 | 0.00 | 22.56 |
June | 232.00 | 22.34 | 307.50 | 23.16 | 0.00 | 23.16 |
July | 176.67 | 22.25 | 399.00 | 23.21 | 5.83 | 23.21 |
August | 319.33 | 22.28 | 263.67 | 22.90 | 4.83 | 22.91 |
September | 573.83 | 22.34 | 28.50 | 22.41 | 0.00 | 22.41 |
October | 730.67 | 22.11 | 0.00 | 22.11 | 0.00 | 22.11 |
November | 720.00 | 21.59 | 74.33 | 21.53 | 74.33 | 21.49 |
December | 744.00 | 21.50 | 110.00 | 21.43 | 110.00 | 21.38 |
Annual Sum or Average | 6852.67 | 21.95 | 1363.33 | 22.12 | 355.17 | 22.08 |
Minimum of Months | 176.67 | 21.50 | 0.00 | 21.43 | 0.00 | 21.38 |
Maximum of Months | 744.00 | 22.51 | 399.00 | 23.21 | 110.00 | 23.21 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.83 | 23.92 | 692.83 | 23.97 | 359.83 | 23.97 |
February | 371.33 | 23.96 | 619.17 | 23.98 | 365.33 | 23.98 |
March | 466.00 | 23.99 | 716.17 | 23.99 | 464.00 | 23.99 |
April | 487.67 | 23.99 | 720.00 | 23.99 | 487.67 | 23.99 |
May | 544.67 | 23.99 | 744.00 | 23.99 | 544.67 | 23.99 |
June | 544.83 | 23.99 | 720.00 | 23.99 | 544.83 | 23.99 |
July | 571.67 | 23.99 | 744.00 | 23.99 | 571.67 | 23.99 |
August | 559.33 | 23.99 | 744.00 | 23.99 | 559.33 | 23.99 |
September | 506.33 | 23.99 | 720.00 | 23.99 | 506.33 | 23.99 |
October | 484.17 | 23.99 | 743.67 | 23.99 | 484.17 | 23.99 |
November | 361.67 | 23.98 | 671.00 | 23.99 | 355.17 | 23.99 |
December | 337.67 | 23.96 | 661.50 | 23.98 | 328.17 | 23.98 |
Annual Sum or Average | 5607.17 | 23.98 | 8496.33 | 23.99 | 5571.17 | 23.99 |
Minimum of Months | 337.67 | 23.92 | 619.17 | 23.97 | 328.17 | 23.97 |
Maximum of Months | 571.67 | 23.99 | 744.00 | 23.99 | 571.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.89 | 728.50 | 20.89 | 728.50 | 20.89 |
February | 672.00 | 20.99 | 606.33 | 20.99 | 606.33 | 20.99 |
March | 744.00 | 21.05 | 487.00 | 21.03 | 487.00 | 21.02 |
April | 720.00 | 22.07 | 87.00 | 21.96 | 87.00 | 21.86 |
May | 723.50 | 23.53 | 0.00 | 23.53 | 0.00 | 23.53 |
June | 114.50 | 23.74 | 62.83 | 23.83 | 0.00 | 23.83 |
July | 63.17 | 23.57 | 245.33 | 23.91 | 0.00 | 23.91 |
August | 309.83 | 23.44 | 55.17 | 23.52 | 0.00 | 23.52 |
September | 717.67 | 22.29 | 0.00 | 22.29 | 0.00 | 22.29 |
October | 744.00 | 21.12 | 246.17 | 21.09 | 246.17 | 21.07 |
November | 720.00 | 20.99 | 718.17 | 20.99 | 718.17 | 20.99 |
December | 744.00 | 20.98 | 740.00 | 20.98 | 740.00 | 20.98 |
Annual Sum or Average | 7016.67 | 21.68 | 3976.50 | 21.52 | 3613.17 | 21.39 |
Minimum of Months | 63.17 | 20.89 | 0.00 | 20.89 | 0.00 | 20.89 |
Maximum of Months | 744.00 | 23.74 | 740.00 | 23.91 | 740.00 | 23.91 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.08817 | 19.08679 | -0.2818 | 6.98583 |
February | 672.00000 | 21.54620 | 20.04541 | -0.4131 | 8.83885 |
March | 744.00000 | 21.45390 | 22.07987 | -0.4250 | 8.94067 |
April | 720.00000 | 21.65314 | 23.55526 | -0.3657 | 7.94984 |
May | 744.00000 | 21.74232 | 27.78977 | -1.4532 | 48.41074 |
June | 720.00000 | 22.00493 | 42.64413 | -1.2675 | 38.77050 |
July | 744.00000 | 22.57789 | 50.72114 | -1.0093 | 26.76018 |
August | 744.00000 | 23.22608 | 43.83532 | -0.8202 | 19.43131 |
September | 720.00000 | 23.55440 | 32.11974 | -0.7810 | 18.05842 |
October | 744.00000 | 23.57193 | 25.39179 | 0.13161 | 5.47582 |
November | 720.00000 | 23.27294 | 17.75639 | 0.00635 | 5.25286 |
December | 744.00000 | 22.63803 | 17.10310 | -0.1564 | 5.72627 |
Annual Sum or Average | 8760.00000 | 22.44960 | 28.57474 | -0.5705 | 16.77285 |
Minimum of Months | 672.00000 | 21.45390 | 17.10310 | -1.4532 | 5.25286 |
Maximum of Months | 744.00000 | 23.57193 | 50.72114 | 0.13161 | 48.41074 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.84088 | 18.97062 | -0.7842 | 18.55596 |
February | 672.00000 | 21.05908 | 19.57768 | -0.6517 | 14.48266 |
March | 744.00000 | 21.45115 | 21.28385 | -0.4453 | 11.03984 |
April | 720.00000 | 22.37127 | 22.25296 | -0.1101 | 7.92677 |
May | 744.00000 | 23.03710 | 25.84051 | -0.8612 | 23.52484 |
June | 720.00000 | 23.54908 | 39.02071 | -0.5697 | 13.25746 |
July | 744.00000 | 23.52042 | 47.83348 | -0.5201 | 12.33404 |
August | 744.00000 | 23.27284 | 43.28744 | -0.6530 | 16.46381 |
September | 720.00000 | 22.06534 | 34.24628 | -1.2111 | 38.58489 |
October | 744.00000 | 21.24495 | 27.60227 | -0.4705 | 10.59020 |
November | 720.00000 | 20.99570 | 18.42358 | -0.7321 | 16.44598 |
December | 744.00000 | 20.94950 | 17.21817 | -0.7996 | 18.68070 |
Annual Sum or Average | 8760.00000 | 22.03539 | 28.02632 | -0.6507 | 16.81874 |
Minimum of Months | 672.00000 | 20.84088 | 17.21817 | -1.2111 | 7.92677 |
Maximum of Months | 744.00000 | 23.54908 | 47.83348 | -0.1101 | 38.58489 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.96661 | 19.90345 | -0.5644 | 11.87853 |
February | 672.00000 | 21.05751 | 20.41041 | -0.5187 | 10.77152 |
March | 744.00000 | 21.21328 | 22.23319 | -0.4454 | 9.34805 |
April | 720.00000 | 22.01185 | 23.23142 | -0.2188 | 6.57622 |
May | 744.00000 | 22.57606 | 26.96512 | -1.0761 | 29.93278 |
June | 720.00000 | 22.99541 | 40.81383 | -0.8329 | 20.18870 |
July | 744.00000 | 22.99323 | 49.85695 | -0.7740 | 18.22529 |
August | 744.00000 | 22.86619 | 44.82211 | -0.8561 | 21.19497 |
September | 720.00000 | 22.08950 | 34.63703 | -1.2091 | 36.29905 |
October | 744.00000 | 21.38450 | 28.07994 | -0.3644 | 8.07170 |
November | 720.00000 | 21.02784 | 19.33552 | -0.5424 | 11.24197 |
December | 744.00000 | 20.99795 | 18.16709 | -0.5767 | 12.06465 |
Annual Sum or Average | 8760.00000 | 21.85282 | 29.10381 | -0.6657 | 16.33692 |
Minimum of Months | 672.00000 | 20.96661 | 18.16709 | -1.2091 | 6.57622 |
Maximum of Months | 744.00000 | 22.99541 | 49.85695 | -0.2188 | 36.29905 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99978 | 13.76905 | 0.69927 | 16.11829 |
February | 672.00000 | 23.99976 | 14.17050 | 0.71843 | 16.70302 |
March | 744.00000 | 23.99982 | 15.83573 | 0.75995 | 17.99647 |
April | 720.00000 | 23.99981 | 17.26268 | 0.81024 | 19.60156 |
May | 744.00000 | 23.99977 | 21.11223 | 0.24378 | 7.86863 |
June | 720.00000 | 23.99988 | 34.59522 | 0.36294 | 9.39608 |
July | 744.00000 | 23.99982 | 43.17388 | 0.42201 | 10.39188 |
August | 744.00000 | 23.99984 | 38.12894 | 0.37522 | 9.64325 |
September | 720.00000 | 23.99980 | 27.50136 | 0.25221 | 7.98498 |
October | 744.00000 | 23.99985 | 20.92468 | 0.80721 | 19.50294 |
November | 720.00000 | 23.99978 | 13.27105 | 0.70270 | 16.19756 |
December | 744.00000 | 23.99978 | 12.30051 | 0.68095 | 15.57067 |
Annual Sum or Average | 8760.00000 | 23.99981 | 22.73501 | 0.56876 | 13.89848 |
Minimum of Months | 672.00000 | 23.99976 | 12.30051 | 0.24378 | 7.86863 |
Maximum of Months | 744.00000 | 23.99988 | 43.17388 | 0.81024 | 19.60156 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.91191 | 22.11681 | -0.6704 | 14.90986 |
February | 672.00000 | 21.03833 | 22.65204 | -0.5487 | 11.67116 |
March | 744.00000 | 21.39773 | 24.40636 | -0.3466 | 8.75222 |
April | 720.00000 | 22.18967 | 25.41066 | -0.0519 | 6.86373 |
May | 744.00000 | 22.44987 | 29.47108 | -0.9185 | 24.87377 |
June | 720.00000 | 22.74052 | 43.77971 | -0.6998 | 16.87764 |
July | 744.00000 | 22.70282 | 53.00918 | -0.6522 | 15.91653 |
August | 744.00000 | 22.58676 | 47.89076 | -0.7413 | 19.15891 |
September | 720.00000 | 21.92481 | 37.26573 | -1.1275 | 33.73836 |
October | 744.00000 | 21.30577 | 30.44283 | -0.3515 | 8.30606 |
November | 720.00000 | 20.99945 | 21.55925 | -0.6294 | 13.49568 |
December | 744.00000 | 20.97141 | 20.39209 | -0.7001 | 15.53991 |
Annual Sum or Average | 8760.00000 | 21.77211 | 31.60088 | -0.6203 | 15.85542 |
Minimum of Months | 672.00000 | 20.91191 | 20.39209 | -1.1275 | 6.86373 |
Maximum of Months | 744.00000 | 22.74052 | 53.00918 | -0.0519 | 33.73836 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.16814 | 22.33152 | -0.4927 | 10.44372 |
February | 672.00000 | 21.30140 | 22.80992 | -0.4304 | 9.24159 |
March | 744.00000 | 21.65500 | 24.50941 | -0.3059 | 7.39517 |
April | 720.00000 | 22.51911 | 25.50212 | -0.0593 | 5.66564 |
May | 744.00000 | 22.95751 | 29.30051 | -0.8939 | 22.45325 |
June | 720.00000 | 23.24109 | 43.07745 | -0.6905 | 15.61906 |
July | 744.00000 | 23.24353 | 51.94339 | -0.6295 | 13.99076 |
August | 744.00000 | 23.17168 | 46.92938 | -0.6954 | 15.97607 |
September | 720.00000 | 22.56991 | 36.61504 | -1.0018 | 27.10898 |
October | 744.00000 | 21.85560 | 30.16489 | -0.2212 | 6.62398 |
November | 720.00000 | 21.22723 | 21.77579 | -0.4700 | 9.89092 |
December | 744.00000 | 21.11425 | 20.68078 | -0.5251 | 10.98791 |
Annual Sum or Average | 8760.00000 | 22.17341 | 31.36835 | -0.5353 | 12.96246 |
Minimum of Months | 672.00000 | 21.11425 | 20.68078 | -1.0018 | 5.66564 |
Maximum of Months | 744.00000 | 23.24353 | 51.94339 | -0.0593 | 27.10898 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.37009 | 21.54457 | -0.9116 | 23.20404 |
February | 672.00000 | 20.43907 | 22.36088 | -0.8449 | 20.59840 |
March | 744.00000 | 20.72231 | 24.08392 | -0.6969 | 15.82354 |
April | 720.00000 | 21.40643 | 28.37867 | -0.3777 | 9.38581 |
May | 744.00000 | 21.69818 | 34.26026 | -1.3122 | 42.17019 |
June | 720.00000 | 21.76615 | 45.39052 | -1.1488 | 34.36212 |
July | 744.00000 | 21.76346 | 51.14188 | -1.1312 | 33.55253 |
August | 744.00000 | 21.70923 | 49.12618 | -1.2101 | 37.21201 |
September | 720.00000 | 21.31125 | 42.43162 | -1.5331 | 53.08710 |
October | 744.00000 | 20.67187 | 32.60388 | -0.6636 | 14.96269 |
November | 720.00000 | 20.40210 | 20.70203 | -0.8946 | 22.44629 |
December | 744.00000 | 20.39243 | 19.95482 | -0.9319 | 23.97380 |
Annual Sum or Average | 8760.00000 | 21.05761 | 32.73252 | -0.9722 | 27.59742 |
Minimum of Months | 672.00000 | 20.37009 | 19.95482 | -1.5331 | 9.38581 |
Maximum of Months | 744.00000 | 21.76615 | 51.14188 | -0.3777 | 53.08710 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.35207 | 21.57796 | -0.9223 | 23.67322 |
February | 672.00000 | 20.40602 | 22.44825 | -0.8785 | 21.92067 |
March | 744.00000 | 20.48351 | 24.39412 | -0.7900 | 18.75850 |
April | 720.00000 | 21.05425 | 28.85822 | -0.5015 | 11.32804 |
May | 744.00000 | 21.97820 | 34.02748 | -1.2749 | 41.75137 |
June | 720.00000 | 22.67007 | 43.83475 | -0.9108 | 28.36865 |
July | 744.00000 | 22.49851 | 50.20362 | -0.9418 | 27.96923 |
August | 744.00000 | 22.20138 | 48.60164 | -1.1089 | 34.48198 |
September | 720.00000 | 21.09919 | 42.89829 | -1.6405 | 58.42399 |
October | 744.00000 | 20.53153 | 32.89266 | -0.7179 | 16.50177 |
November | 720.00000 | 20.39457 | 20.74712 | -0.9088 | 23.04073 |
December | 744.00000 | 20.38679 | 19.96379 | -0.9352 | 24.11544 |
Annual Sum or Average | 8760.00000 | 21.17617 | 32.60329 | -0.9613 | 27.54361 |
Minimum of Months | 672.00000 | 20.35207 | 19.96379 | -1.6405 | 11.32804 |
Maximum of Months | 744.00000 | 22.67007 | 50.20362 | -0.5015 | 58.42399 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.41329 | 20.32598 | -0.7969 | 19.16870 |
February | 672.00000 | 20.52162 | 21.15930 | -0.7569 | 17.69727 |
March | 744.00000 | 20.71903 | 23.19594 | -0.6788 | 15.14575 |
April | 720.00000 | 21.12169 | 27.99838 | -0.5091 | 10.74112 |
May | 744.00000 | 21.66135 | 32.88423 | -1.4394 | 47.88247 |
June | 720.00000 | 22.13157 | 43.33174 | -1.1751 | 35.05783 |
July | 744.00000 | 22.14789 | 49.86327 | -1.1346 | 33.41978 |
August | 744.00000 | 21.87355 | 47.04486 | -1.2797 | 39.99901 |
September | 720.00000 | 21.24803 | 41.45323 | -1.5807 | 55.29888 |
October | 744.00000 | 20.85208 | 31.57910 | -0.5824 | 12.54726 |
November | 720.00000 | 20.45770 | 19.57978 | -0.7876 | 18.70395 |
December | 744.00000 | 20.42662 | 18.62514 | -0.8103 | 19.50848 |
Annual Sum or Average | 8760.00000 | 21.13502 | 31.48611 | -0.9621 | 27.14354 |
Minimum of Months | 672.00000 | 20.41329 | 18.62514 | -1.5807 | 10.74112 |
Maximum of Months | 744.00000 | 22.14789 | 49.86327 | -0.5091 | 55.29888 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.36442 | 21.54217 | -0.9103 | 23.15689 |
February | 672.00000 | 20.47628 | 22.27430 | -0.8255 | 19.93902 |
March | 744.00000 | 20.99618 | 23.73857 | -0.6087 | 13.70360 |
April | 720.00000 | 21.54876 | 28.24111 | -0.3442 | 9.00075 |
May | 744.00000 | 21.77524 | 34.21140 | -1.2349 | 38.81418 |
June | 720.00000 | 21.79191 | 44.89892 | -1.1150 | 33.06732 |
July | 744.00000 | 21.79471 | 49.94381 | -1.0866 | 31.84896 |
August | 744.00000 | 21.77157 | 48.10174 | -1.1647 | 35.31507 |
September | 720.00000 | 21.45789 | 42.05592 | -1.4615 | 49.62090 |
October | 744.00000 | 20.78965 | 32.36129 | -0.6214 | 14.00518 |
November | 720.00000 | 20.40210 | 20.69694 | -0.8941 | 22.43755 |
December | 744.00000 | 20.39023 | 19.95247 | -0.9320 | 23.97494 |
Annual Sum or Average | 8760.00000 | 21.13342 | 32.39962 | -0.9339 | 26.26705 |
Minimum of Months | 672.00000 | 20.36442 | 19.95247 | -1.4615 | 9.00075 |
Maximum of Months | 744.00000 | 21.79471 | 49.94381 | -0.3442 | 49.62090 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.34614 | 21.56176 | -0.9211 | 23.62775 |
February | 672.00000 | 20.41591 | 22.37722 | -0.8647 | 21.40539 |
March | 744.00000 | 20.65892 | 24.09335 | -0.7216 | 16.58182 |
April | 720.00000 | 21.29733 | 28.49563 | -0.4495 | 10.43641 |
May | 744.00000 | 21.97657 | 33.82673 | -1.2203 | 37.98102 |
June | 720.00000 | 22.41861 | 43.81841 | -0.9601 | 27.16290 |
July | 744.00000 | 22.50263 | 49.20303 | -0.9045 | 26.39707 |
August | 744.00000 | 22.15733 | 47.68295 | -1.0948 | 32.34356 |
September | 720.00000 | 21.31596 | 42.35244 | -1.5485 | 53.79452 |
October | 744.00000 | 20.63040 | 32.64294 | -0.6796 | 15.42586 |
November | 720.00000 | 20.39302 | 20.72685 | -0.9087 | 23.04431 |
December | 744.00000 | 20.38290 | 19.96199 | -0.9356 | 24.12889 |
Annual Sum or Average | 8760.00000 | 21.21286 | 32.29183 | -0.9343 | 26.03715 |
Minimum of Months | 672.00000 | 20.34614 | 19.96199 | -1.5485 | 10.43641 |
Maximum of Months | 744.00000 | 22.50263 | 49.20303 | -0.4495 | 53.79452 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.33752 | 21.88873 | -0.9808 | 26.02196 |
February | 672.00000 | 20.40892 | 22.71917 | -0.9119 | 23.11232 |
March | 744.00000 | 20.60357 | 24.50875 | -0.7703 | 18.16854 |
April | 720.00000 | 21.31410 | 28.86260 | -0.4215 | 10.43428 |
May | 744.00000 | 21.66521 | 34.66944 | -1.3411 | 43.77036 |
June | 720.00000 | 21.74953 | 45.94196 | -1.1598 | 35.06190 |
July | 744.00000 | 21.74800 | 52.24729 | -1.1387 | 34.07755 |
August | 744.00000 | 21.67635 | 50.18193 | -1.2324 | 38.44967 |
September | 720.00000 | 21.20859 | 43.37481 | -1.5999 | 56.48323 |
October | 744.00000 | 20.58127 | 33.27022 | -0.7267 | 16.85768 |
November | 720.00000 | 20.38941 | 21.03433 | -0.9608 | 25.05608 |
December | 744.00000 | 20.37658 | 20.25937 | -0.9985 | 26.69175 |
Annual Sum or Average | 8760.00000 | 21.00806 | 33.31601 | -1.0209 | 29.54349 |
Minimum of Months | 672.00000 | 20.33752 | 20.25937 | -1.5999 | 10.43428 |
Maximum of Months | 744.00000 | 21.74953 | 52.24729 | -0.4215 | 56.48323 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.31188 | 21.88925 | -0.9929 | 26.59508 |
February | 672.00000 | 20.38917 | 22.81510 | -0.9422 | 24.39318 |
March | 744.00000 | 20.44632 | 24.76330 | -0.8500 | 20.87361 |
April | 720.00000 | 20.96106 | 29.38437 | -0.5511 | 12.63319 |
May | 744.00000 | 21.97880 | 34.45100 | -1.2939 | 43.51031 |
June | 720.00000 | 22.74604 | 44.19462 | -0.8852 | 29.10726 |
July | 744.00000 | 22.54669 | 50.85980 | -0.9250 | 28.36820 |
August | 744.00000 | 22.21793 | 49.47373 | -1.1133 | 35.75130 |
September | 720.00000 | 20.97957 | 43.92968 | -1.7183 | 62.32267 |
October | 744.00000 | 20.47103 | 33.53142 | -0.7760 | 18.38984 |
November | 720.00000 | 20.37475 | 21.06199 | -0.9760 | 25.72920 |
December | 744.00000 | 20.36007 | 20.25571 | -1.0041 | 26.94531 |
Annual Sum or Average | 8760.00000 | 21.15357 | 33.11751 | -1.0025 | 29.56225 |
Minimum of Months | 672.00000 | 20.31188 | 20.25571 | -1.7183 | 12.63319 |
Maximum of Months | 744.00000 | 22.74604 | 50.85980 | -0.5511 | 62.32267 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.41031 | 23.48040 | -0.8864 | 22.20226 |
February | 672.00000 | 20.77021 | 24.14097 | -0.7281 | 17.29818 |
March | 744.00000 | 21.21905 | 25.79352 | -0.5231 | 12.48841 |
April | 720.00000 | 21.60222 | 30.16669 | -0.2959 | 8.71976 |
May | 744.00000 | 21.72756 | 35.46196 | -1.2980 | 42.03961 |
June | 720.00000 | 21.75912 | 45.85811 | -1.1824 | 36.30308 |
July | 744.00000 | 21.76229 | 51.35763 | -1.1479 | 34.70478 |
August | 744.00000 | 21.73479 | 48.94827 | -1.1969 | 37.11191 |
September | 720.00000 | 21.51722 | 42.95981 | -1.4237 | 48.03778 |
October | 744.00000 | 21.00763 | 33.79046 | -0.5477 | 12.57641 |
November | 720.00000 | 20.47713 | 22.67360 | -0.8560 | 21.05911 |
December | 744.00000 | 20.39619 | 21.97806 | -0.9233 | 23.64013 |
Annual Sum or Average | 8760.00000 | 21.20063 | 33.94743 | -0.9188 | 26.39893 |
Minimum of Months | 672.00000 | 20.39619 | 21.97806 | -1.4237 | 8.71976 |
Maximum of Months | 744.00000 | 21.76229 | 51.35763 | -0.2959 | 48.03778 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.36002 | 22.01327 | -0.4262 | 9.53577 |
February | 672.00000 | 21.44337 | 22.52411 | -0.3865 | 8.77271 |
March | 744.00000 | 21.63135 | 24.34803 | -0.2977 | 7.50088 |
April | 720.00000 | 22.04993 | 25.66092 | -0.1314 | 6.08957 |
May | 744.00000 | 22.57502 | 29.44584 | -0.9110 | 23.47753 |
June | 720.00000 | 22.88809 | 43.45037 | -0.6713 | 15.55420 |
July | 744.00000 | 22.85309 | 52.67458 | -0.6255 | 14.19660 |
August | 744.00000 | 22.68264 | 47.72046 | -0.7461 | 17.94872 |
September | 720.00000 | 22.23327 | 36.87703 | -1.0348 | 28.70207 |
October | 744.00000 | 21.81368 | 30.02027 | -0.2000 | 6.54593 |
November | 720.00000 | 21.38412 | 21.49426 | -0.4211 | 9.23872 |
December | 744.00000 | 21.31314 | 20.39431 | -0.4553 | 9.79937 |
Annual Sum or Average | 8760.00000 | 22.02239 | 31.45280 | -0.5263 | 13.12965 |
Minimum of Months | 672.00000 | 21.31314 | 20.39431 | -1.0348 | 6.08957 |
Maximum of Months | 744.00000 | 22.88809 | 52.67458 | -0.1314 | 28.70207 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.57566 | 21.85019 | -0.3349 | 8.22491 |
February | 672.00000 | 21.65661 | 22.35119 | -0.2974 | 7.69694 |
March | 744.00000 | 21.90418 | 24.10912 | -0.1975 | 6.64657 |
April | 720.00000 | 22.37708 | 25.36710 | -0.0268 | 5.75190 |
May | 744.00000 | 22.85334 | 29.09694 | -0.7897 | 19.05072 |
June | 720.00000 | 23.13648 | 42.89795 | -0.5616 | 12.57837 |
July | 744.00000 | 23.10246 | 51.98648 | -0.5159 | 11.45066 |
August | 744.00000 | 22.93946 | 47.10852 | -0.6335 | 14.56295 |
September | 720.00000 | 22.57939 | 36.33049 | -0.8825 | 22.61394 |
October | 744.00000 | 22.13623 | 29.64087 | -0.0885 | 6.02303 |
November | 720.00000 | 21.58627 | 21.34296 | -0.3335 | 8.03862 |
December | 744.00000 | 21.49843 | 20.27146 | -0.3713 | 8.50066 |
Annual Sum or Average | 8760.00000 | 22.28237 | 31.09578 | -0.4201 | 10.94039 |
Minimum of Months | 672.00000 | 21.49843 | 20.27146 | -0.8825 | 5.75190 |
Maximum of Months | 744.00000 | 23.13648 | 51.98648 | -0.0268 | 22.61394 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.95337 | 23.32178 | 0.82680 | 20.97111 |
February | 672.00000 | 23.97144 | 23.29389 | 0.86456 | 22.36976 |
March | 744.00000 | 23.98780 | 24.18726 | 0.93751 | 25.16048 |
April | 720.00000 | 23.99083 | 24.89491 | 1.02167 | 28.61480 |
May | 744.00000 | 23.99081 | 28.31139 | 0.58093 | 15.78616 |
June | 720.00000 | 23.99133 | 41.37698 | 0.71515 | 19.11459 |
July | 744.00000 | 23.99169 | 49.75692 | 0.77184 | 21.09012 |
August | 744.00000 | 23.99138 | 44.92161 | 0.69284 | 18.63590 |
September | 720.00000 | 23.99105 | 34.72913 | 0.52325 | 14.09736 |
October | 744.00000 | 23.99094 | 28.84999 | 0.97821 | 26.53395 |
November | 720.00000 | 23.98139 | 22.62607 | 0.83451 | 21.04572 |
December | 744.00000 | 23.97373 | 21.96622 | 0.80731 | 20.15737 |
Annual Sum or Average | 8760.00000 | 23.98386 | 30.74469 | 0.79590 | 21.12580 |
Minimum of Months | 672.00000 | 23.95337 | 21.96622 | 0.52325 | 14.09736 |
Maximum of Months | 744.00000 | 23.99169 | 49.75692 | 1.02167 | 28.61480 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.89118 | 16.65652 | -0.6620 | 14.48575 |
February | 672.00000 | 20.98256 | 17.17521 | -0.6274 | 13.37279 |
March | 744.00000 | 20.99828 | 19.08934 | -0.5863 | 12.27595 |
April | 720.00000 | 21.03263 | 21.01948 | -0.5103 | 10.53476 |
May | 744.00000 | 21.38536 | 25.32627 | -1.5201 | 52.01018 |
June | 720.00000 | 21.97130 | 39.81140 | -1.2280 | 36.74821 |
July | 744.00000 | 22.03192 | 49.29828 | -1.1483 | 32.92292 |
August | 744.00000 | 21.79278 | 44.17870 | -1.2647 | 38.67571 |
September | 720.00000 | 21.11730 | 33.25224 | -1.5793 | 55.22943 |
October | 744.00000 | 21.00148 | 25.34644 | -0.5181 | 10.67983 |
November | 720.00000 | 20.98756 | 16.06296 | -0.6383 | 13.62098 |
December | 744.00000 | 20.97222 | 14.88686 | -0.6620 | 14.29721 |
Annual Sum or Average | 8760.00000 | 21.26588 | 26.91382 | -0.9136 | 25.46360 |
Minimum of Months | 672.00000 | 20.89118 | 14.88686 | -1.5793 | 10.53476 |
Maximum of Months | 744.00000 | 22.03192 | 49.29828 | -0.5103 | 55.22943 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.94143 | 20.95281 | -0.6192 | 13.19457 |
February | 672.00000 | 20.99944 | 21.53423 | -0.5872 | 12.29210 |
March | 744.00000 | 21.00498 | 23.46057 | -0.5477 | 11.32060 |
April | 720.00000 | 21.52681 | 24.82187 | -0.3889 | 8.52734 |
May | 744.00000 | 22.56395 | 28.12815 | -1.1674 | 33.94419 |
June | 720.00000 | 23.29213 | 41.44459 | -0.8274 | 19.66537 |
July | 744.00000 | 23.25070 | 50.40978 | -0.7824 | 18.22518 |
August | 744.00000 | 22.82169 | 46.15083 | -0.9629 | 25.08037 |
September | 720.00000 | 21.54290 | 36.67227 | -1.4718 | 49.51472 |
October | 744.00000 | 21.01286 | 29.62990 | -0.5123 | 10.53542 |
November | 720.00000 | 20.99772 | 20.42447 | -0.6055 | 12.74011 |
December | 744.00000 | 20.98308 | 19.19305 | -0.6253 | 13.27570 |
Annual Sum or Average | 8760.00000 | 21.74989 | 30.30009 | -0.7589 | 19.04236 |
Minimum of Months | 672.00000 | 20.94143 | 19.19305 | -1.4718 | 8.52734 |
Maximum of Months | 744.00000 | 23.29213 | 50.40978 | -0.3889 | 49.51472 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.88855 | 20.23147 | -0.6772 | 15.00431 |
February | 672.00000 | 20.99348 | 21.01537 | -0.6255 | 13.32005 |
March | 744.00000 | 21.04625 | 22.96608 | -0.5575 | 11.62214 |
April | 720.00000 | 22.07264 | 23.99673 | -0.2622 | 7.51902 |
May | 744.00000 | 23.53840 | 26.57173 | -0.8305 | 20.07847 |
June | 720.00000 | 23.94579 | 38.73732 | -0.5774 | 12.09597 |
July | 744.00000 | 23.93762 | 47.48356 | -0.5205 | 10.79119 |
August | 744.00000 | 23.74315 | 43.42727 | -0.6371 | 14.01981 |
September | 720.00000 | 22.29704 | 35.16684 | -1.2167 | 37.02771 |
October | 744.00000 | 21.11963 | 29.12328 | -0.4953 | 10.30669 |
November | 720.00000 | 20.99218 | 19.75556 | -0.6533 | 14.04605 |
December | 744.00000 | 20.97524 | 18.40953 | -0.6796 | 14.82930 |
Annual Sum or Average | 8760.00000 | 22.13633 | 28.96637 | -0.6442 | 15.04064 |
Minimum of Months | 672.00000 | 20.88855 | 18.40953 | -1.2167 | 7.51902 |
Maximum of Months | 744.00000 | 23.94579 | 47.48356 | -0.2622 | 37.02771 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.97426 | 16.30190 | -0.6204 | 13.20585 |
February | 672.00000 | 21.08179 | 17.31354 | -0.5805 | 12.22288 |
March | 744.00000 | 21.32127 | 19.19411 | -0.4979 | 10.54797 |
April | 720.00000 | 22.80487 | 22.93563 | -0.1261 | 6.38253 |
May | 744.00000 | 23.92572 | 26.14148 | -0.7740 | 17.68702 |
June | 720.00000 | 23.99937 | 36.94883 | -0.6389 | 13.61894 |
July | 744.00000 | 23.99913 | 45.49317 | -0.5761 | 11.99174 |
August | 744.00000 | 23.99280 | 41.43483 | -0.6209 | 13.16748 |
September | 720.00000 | 23.62241 | 34.90863 | -0.8265 | 19.94540 |
October | 744.00000 | 22.18467 | 27.13216 | -0.2438 | 7.33937 |
November | 720.00000 | 21.02193 | 15.63542 | -0.6050 | 12.72234 |
December | 744.00000 | 21.00428 | 14.77526 | -0.6289 | 13.35838 |
Annual Sum or Average | 8760.00000 | 22.50195 | 26.58163 | -0.5616 | 12.68095 |
Minimum of Months | 672.00000 | 20.97426 | 14.77526 | -0.8265 | 6.38253 |
Maximum of Months | 744.00000 | 23.99937 | 45.49317 | -0.1261 | 19.94540 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.168998E+09 | 7328.55 | 23-JAN-19:07 | 65.49 | 0.526587E+09 | 0.00 | 0.695585E+09 | 0.27 | 3.12 | 05-JAN-03:20 | 0.00 | 0.00 |
February | 0.304866E+09 | 10034.43 | 07-FEB-19:04 | 102.61 | 0.949941E+09 | 0.00 | 0.125481E+10 | 0.48 | 3.12 | 11-FEB-19:08 | 0.00 | 0.00 |
March | 0.151012E+10 | 15083.90 | 22-MAR-18:02 | 284.50 | 0.470541E+10 | 0.00 | 0.621553E+10 | 1.19 | 3.12 | 23-MAR-01:00 | 0.00 | 0.00 |
April | 0.155664E+11 | 53602.11 | 22-APR-15:13 | 575.31 | 0.484579E+11 | 0.00 | 0.640243E+11 | 2.49 | 3.95 | 22-APR-15:13 | 0.00 | 0.00 |
May | 0.426516E+11 | 66711.47 | 31-MAY-15:23 | 732.17 | 0.132110E+12 | 0.00 | 0.174762E+12 | 3.05 | 3.90 | 18-MAY-15:13 | 0.00 | 0.00 |
June | 0.841202E+11 | 108728.13 | 20-JUN-18:03 | 718.83 | 0.271066E+12 | 0.00 | 0.355186E+12 | 3.13 | 4.03 | 30-JUN-18:03 | 0.00 | 0.00 |
July | 0.964043E+11 | 122306.93 | 29-JUL-18:03 | 743.83 | 0.316246E+12 | 0.00 | 0.412650E+12 | 3.17 | 3.94 | 22-JUL-08:53 | 0.00 | 0.00 |
August | 0.658300E+11 | 103859.18 | 11-AUG-18:03 | 738.11 | 0.210937E+12 | 0.00 | 0.276767E+12 | 3.10 | 3.86 | 24-AUG-15:13 | 0.00 | 0.00 |
September | 0.133062E+11 | 49597.89 | 09-SEP-18:03 | 540.33 | 0.408516E+11 | 0.00 | 0.541578E+11 | 2.33 | 3.68 | 09-SEP-15:13 | 0.00 | 0.00 |
October | 0.184319E+10 | 23397.93 | 03-OCT-18:01 | 310.84 | 0.574239E+10 | 0.00 | 0.758559E+10 | 1.30 | 3.12 | 22-OCT-13:20 | 0.00 | 0.00 |
November | 0.128703E+09 | 6796.82 | 05-NOV-18:07 | 50.22 | 0.401029E+09 | 0.00 | 0.529732E+09 | 0.22 | 3.12 | 01-NOV-02:30 | 0.00 | 0.00 |
December | 0.124281E+09 | 9864.15 | 24-DEC-19:05 | 47.84 | 0.387250E+09 | 0.00 | 0.511530E+09 | 0.20 | 3.12 | 19-DEC-19:40 | 0.00 | 0.00 |
Annual Sum or Average | 0.321959E+12 | 4910.07 | 0.103238E+13 | 0.00 | 0.135434E+13 | 1.75 | 0.00 | 0.00 | ||||
Minimum of Months | 0.124281E+09 | 6796.82 | 47.84 | 0.387250E+09 | 0.00 | 0.511530E+09 | 0.20 | 3.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.964043E+11 | 122306.93 | 743.83 | 0.316246E+12 | 0.00 | 0.412650E+12 | 3.17 | 4.03 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.560389E+12 | 0.00 | 744.00 | 643026.81 | 12-JAN-10:20 | 0.00 | 40.02 | 60.00 | 2.46 | 0.00 | 0.25 | 0.77 | 12-JAN-10:20 |
February | 0.434378E+12 | 0.00 | 672.00 | 605297.09 | 27-FEB-07:05 | 0.00 | 40.25 | 60.00 | 2.13 | 0.00 | 0.22 | 0.73 | 27-FEB-07:05 |
March | 0.239766E+12 | 0.00 | 744.00 | 555678.12 | 01-MAR-07:10 | 0.00 | 40.78 | 60.00 | 1.09 | 0.00 | 0.11 | 0.67 | 01-MAR-07:10 |
April | 0.885165E+11 | 0.00 | 660.39 | 202976.61 | 03-APR-08:62 | 0.00 | 39.23 | 58.25 | 0.39 | 0.00 | 0.04 | 0.24 | 03-APR-08:62 |
May | 0.416609E+11 | 0.00 | 343.43 | 118633.03 | 27-MAY-15:14 | 0.00 | 28.68 | 43.01 | 0.12 | 0.00 | 0.02 | 0.14 | 27-MAY-15:14 |
June | 0.300132E+10 | 0.00 | 69.55 | 64359.88 | 02-JUN-04:00 | 0.00 | 29.60 | 32.48 | 0.01 | 0.00 | 0.00 | 0.08 | 02-JUN-04:00 |
July | 0.138648E+10 | 0.00 | 53.07 | 58041.58 | 05-JUL-08:04 | 0.00 | 33.05 | 35.15 | 0.00 | 0.00 | 0.00 | 0.07 | 05-JUL-08:04 |
August | 0.116765E+11 | 0.00 | 169.04 | 127020.71 | 31-AUG-08:03 | 0.00 | 34.18 | 40.00 | 0.04 | 0.00 | 0.01 | 0.15 | 31-AUG-08:03 |
September | 0.852409E+11 | 0.00 | 584.72 | 188083.46 | 27-SEP-15:11 | 0.00 | 34.94 | 55.07 | 0.32 | 0.00 | 0.04 | 0.23 | 27-SEP-15:11 |
October | 0.148440E+12 | 0.00 | 744.00 | 213028.04 | 30-OCT-08:05 | 0.00 | 40.01 | 60.00 | 0.65 | 0.00 | 0.07 | 0.26 | 30-OCT-08:05 |
November | 0.510542E+12 | 0.00 | 720.00 | 595088.79 | 29-NOV-10:10 | 0.00 | 39.64 | 60.00 | 2.32 | 0.00 | 0.24 | 0.71 | 29-NOV-10:10 |
December | 0.659953E+12 | 0.00 | 744.00 | 617417.82 | 15-DEC-10:50 | 0.00 | 39.67 | 60.00 | 2.88 | 0.00 | 0.30 | 0.74 | 15-DEC-10:50 |
Annual Sum or Average | 0.278495E+13 | 0.00 | 6248.20 | 0.00 | 36.65 | 51.94 | 1.03 | 0.00 | 0.11 | ||||
Minimum of Months | 0.138648E+10 | 0.00 | 53.07 | 58041.58 | 0.00 | 28.68 | 32.48 | 0.00 | 0.00 | 0.00 | 0.07 | ||
Maximum of Months | 0.659953E+12 | 0.00 | 744.00 | 643026.81 | 0.00 | 40.78 | 60.00 | 2.88 | 0.00 | 0.30 | 0.77 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 75168325.83 | 0.00 | 65.18 | 75168325.83 | 0.00 | 0.00 | 0.00 | 0.00 | 3903.82 | 20-JAN-06:10 | 3903.82 | 20-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 85185202.38 | 0.00 | 83.78 | 85185202.38 | 0.00 | 0.00 | 0.00 | 0.00 | 3956.80 | 07-FEB-06:10 | 3956.80 | 07-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.156560E+09 | 0.00 | 143.90 | 0.156560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4012.86 | 21-MAR-05:10 | 4012.86 | 21-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.736317E+09 | 0.00 | 183.77 | 0.736317E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22928.05 | 22-APR-16:10 | 22928.05 | 22-APR-16:10 | 0.00 | 0.00 | 0.00 |
May | 0.354295E+11 | 0.00 | 205.81 | 0.354295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 157352.54 | 31-MAY-17:50 | 157352.54 | 31-MAY-17:50 | 0.00 | 0.00 | 0.00 |
June | 0.131458E+12 | 0.00 | 440.33 | 0.130430E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 226960.36 | 29-JUN-20:00 | 212175.31 | 29-JUN-19:10 | 0.00 | 0.00 | 0.00 |
July | 0.166461E+12 | 0.00 | 480.50 | 0.164044E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 251880.33 | 29-JUL-17:15 | 219473.22 | 29-JUL-17:15 | 0.00 | 0.00 | 0.00 |
August | 0.980209E+11 | 0.00 | 358.00 | 0.979070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 205466.83 | 11-AUG-19:20 | 205466.83 | 11-AUG-19:20 | 0.00 | 0.00 | 0.00 |
September | 0.479464E+10 | 0.00 | 88.76 | 0.479464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61221.95 | 02-SEP-17:50 | 61221.95 | 02-SEP-17:50 | 0.00 | 0.00 | 0.00 |
October | 0.209132E+09 | 0.00 | 194.00 | 0.209132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4092.39 | 17-OCT-05:10 | 4092.39 | 17-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 51529095.41 | 0.00 | 49.14 | 51529095.41 | 0.00 | 0.00 | 0.00 | 0.00 | 3846.30 | 02-NOV-05:10 | 3846.30 | 02-NOV-05:10 | 0.00 | 0.00 | 0.00 |
December | 54200966.70 | 0.00 | 47.76 | 54200966.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3890.95 | 26-DEC-06:10 | 3890.95 | 26-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.437532E+12 | 0.00 | 2340.94 | 0.433972E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 51529095.41 | 0.00 | 47.76 | 51529095.41 | 0.00 | 0.00 | 0.00 | 0.00 | 3846.30 | 3846.30 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.166461E+12 | 0.00 | 480.50 | 0.164044E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 251880.33 | 219473.22 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 2616969.90 | 0.00 | 2.17 | 2616969.90 | 0.00 | 0.00 | 0.00 | 0.00 | 594.90 | 22-APR-14:20 | 594.90 | 22-APR-14:20 | 0.00 | 0.00 | 0.00 |
May | 0.174643E+10 | 0.00 | 109.67 | 0.174643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14983.87 | 31-MAY-15:55 | 14983.87 | 31-MAY-15:55 | 0.00 | 0.00 | 0.00 |
June | 0.831331E+10 | 0.00 | 304.50 | 0.823859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19533.33 | 30-JUN-12:20 | 17976.49 | 20-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.101207E+11 | 0.00 | 335.83 | 0.994242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19236.07 | 29-JUL-18:02 | 19076.55 | 29-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.609004E+10 | 0.00 | 240.33 | 0.605039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17533.36 | 11-AUG-18:02 | 17533.36 | 11-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.172724E+09 | 0.00 | 27.67 | 0.172724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4990.84 | 07-SEP-16:00 | 4990.84 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264459E+11 | 0.00 | 1020.17 | 0.261532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101207E+11 | 0.00 | 335.83 | 0.994242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19533.33 | 19076.55 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 239058.60 | 0.00 | 0.10 | 239058.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1241.63 | 15-FEB-16:14 | 1241.63 | 15-FEB-16:14 | 0.00 | 0.00 | 0.00 |
March | 0.121475E+09 | 0.00 | 16.32 | 0.121475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16500.21 | 22-MAR-15:11 | 16500.21 | 22-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.234628E+10 | 0.00 | 261.47 | 0.233699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16741.34 | 30-APR-15:11 | 16741.34 | 30-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.455038E+10 | 0.00 | 569.31 | 0.419884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16743.06 | 20-MAY-18:01 | 16743.06 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.738088E+10 | 0.00 | 657.73 | 0.482457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16743.29 | 12-JUN-18:02 | 16743.29 | 12-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.744636E+10 | 0.00 | 671.92 | 0.407821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16410.33 | 17-JUL-18:01 | 15175.96 | 26-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.527977E+10 | 0.00 | 611.74 | 0.290887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16728.75 | 30-AUG-18:01 | 16728.75 | 30-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.103972E+10 | 0.00 | 190.18 | 0.653860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16741.06 | 07-SEP-15:11 | 16741.06 | 07-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 35399910.38 | 0.00 | 8.60 | 31397051.30 | 0.00 | 0.00 | 0.00 | 0.00 | 14597.76 | 13-OCT-15:12 | 14597.76 | 13-OCT-15:12 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282005E+11 | 0.00 | 2987.37 | 0.191544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.744636E+10 | 0.00 | 671.92 | 0.482457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16743.29 | 16743.29 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 35837.71 | 0.00 | 0.07 | 35837.71 | 0.00 | 0.00 | 0.00 | 0.00 | 249.08 | 08-FEB-19:06 | 249.08 | 08-FEB-19:06 | 0.00 | 0.00 | 0.00 |
March | 2391357.31 | 0.00 | 1.33 | 2391357.31 | 0.00 | 0.00 | 0.00 | 0.00 | 2609.18 | 26-MAR-15:14 | 2609.18 | 26-MAR-15:14 | 0.00 | 0.00 | 0.00 |
April | 0.116807E+10 | 0.00 | 145.22 | 0.116693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15059.55 | 30-APR-18:01 | 15059.55 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.249851E+10 | 0.00 | 419.11 | 0.222751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17098.74 | 14-MAY-20:41 | 17098.74 | 14-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.485174E+10 | 0.00 | 498.39 | 0.282049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16101.25 | 30-JUN-21:51 | 15835.88 | 01-JUN-18:41 | 0.00 | 0.00 | 0.00 |
July | 0.492373E+10 | 0.00 | 503.46 | 0.255313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16670.32 | 08-JUL-21:51 | 15738.74 | 06-JUL-17:32 | 0.00 | 0.00 | 0.00 |
August | 0.271824E+10 | 0.00 | 421.00 | 0.122702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15489.33 | 12-AUG-21:52 | 15049.71 | 30-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.354650E+09 | 0.00 | 95.19 | 0.195425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15051.55 | 07-SEP-18:01 | 15051.55 | 07-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 5109649.15 | 0.00 | 1.39 | 4276050.31 | 0.00 | 0.00 | 0.00 | 0.00 | 6395.47 | 03-OCT-15:11 | 6395.47 | 03-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165225E+11 | 0.00 | 2085.16 | 0.101972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.492373E+10 | 0.00 | 503.46 | 0.282049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17098.74 | 17098.74 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 |
March | 0.212467E+09 | 0.00 | 8.94 | 0.212467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14969.98 | 31-MAR-15:10 | 14969.98 | 31-MAR-15:10 | 0.00 | 0.00 | 0.00 |
April | 0.247679E+11 | 0.00 | 360.72 | 0.247679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58278.29 | 22-APR-13:20 | 58278.29 | 22-APR-13:20 | 0.00 | 0.00 | 0.00 |
May | 0.372354E+11 | 0.00 | 606.00 | 0.372354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56484.24 | 12-MAY-13:20 | 56484.24 | 12-MAY-13:20 | 0.00 | 0.00 | 0.00 |
June | 0.444233E+11 | 0.00 | 700.06 | 0.272788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53162.71 | 30-JUN-12:30 | 48595.15 | 08-JUN-12:30 | 0.00 | 0.00 | 0.00 |
July | 0.469766E+11 | 0.00 | 719.06 | 0.210376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60514.68 | 23-JUL-13:30 | 55543.62 | 23-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.422681E+11 | 0.00 | 679.20 | 0.223085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64029.71 | 25-AUG-13:15 | 62093.69 | 25-AUG-13:15 | 0.00 | 0.00 | 0.00 |
September | 0.167611E+11 | 0.00 | 355.20 | 0.142584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54028.67 | 09-SEP-13:10 | 54028.67 | 09-SEP-13:10 | 0.00 | 0.00 | 0.00 |
October | 0.157266E+10 | 0.00 | 52.23 | 0.157266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36234.56 | 03-OCT-13:00 | 36234.56 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214218E+12 | 0.00 | 3481.42 | 0.148672E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.469766E+11 | 0.00 | 719.06 | 0.372354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64029.71 | 62093.69 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4818929.20 | 0.00 | 0.33 | 4818929.20 | 0.00 | 0.00 | 0.00 | 0.00 | 9429.63 | 20-JAN-19:07 | 9429.63 | 20-JAN-19:07 | 0.00 | 0.00 | 0.00 |
February | 9858592.53 | 0.00 | 0.41 | 9477873.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14637.49 | 07-FEB-19:04 | 14637.49 | 07-FEB-19:04 | 0.00 | 0.00 | 0.00 |
March | 74322653.10 | 0.00 | 6.47 | 74322653.10 | 0.00 | 0.00 | 0.00 | 0.00 | 49075.48 | 22-MAR-18:02 | 49075.48 | 22-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.474493E+10 | 0.00 | 167.07 | 0.473413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77065.74 | 30-APR-18:01 | 77065.74 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.229546E+11 | 0.00 | 444.17 | 0.217586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80617.29 | 31-MAY-21:51 | 80617.29 | 31-MAY-21:51 | 0.00 | 0.00 | 0.00 |
June | 0.387976E+11 | 0.00 | 431.14 | 0.295245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82902.55 | 07-JUN-21:51 | 82902.55 | 07-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.416771E+11 | 0.00 | 449.00 | 0.283365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84577.35 | 15-JUL-20:41 | 74975.72 | 19-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.268728E+11 | 0.00 | 398.46 | 0.165825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81733.36 | 12-AUG-21:52 | 80292.13 | 10-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.700923E+10 | 0.00 | 295.98 | 0.398892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75809.53 | 10-SEP-18:01 | 75809.53 | 10-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.697399E+09 | 0.00 | 47.10 | 0.589480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72355.50 | 06-OCT-18:02 | 72355.50 | 06-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 4137477.13 | 0.00 | 0.22 | 4137477.13 | 0.00 | 0.00 | 0.00 | 0.00 | 11765.86 | 01-NOV-18:06 | 11765.86 | 01-NOV-18:06 | 0.00 | 0.00 | 0.00 |
December | 2148308.83 | 0.00 | 0.11 | 2148308.83 | 0.00 | 0.00 | 0.00 | 0.00 | 13359.93 | 24-DEC-19:05 | 13359.93 | 24-DEC-19:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142849E+12 | 0.00 | 2240.46 | 0.105610E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2148308.83 | 0.00 | 0.11 | 2148308.83 | 0.00 | 0.00 | 0.00 | 0.00 | 9429.63 | 9429.63 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.416771E+11 | 0.00 | 449.00 | 0.295245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84577.35 | 82902.55 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 172056.54 | 0.00 | 0.08 | 172056.54 | 0.00 | 0.00 | 0.00 | 0.00 | 1405.44 | 09-FEB-16:15 | 1405.44 | 09-FEB-16:15 | 0.00 | 0.00 | 0.00 |
March | 0.181465E+09 | 0.00 | 39.51 | 0.181465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15785.00 | 22-MAR-15:11 | 15785.00 | 22-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.215278E+10 | 0.00 | 301.34 | 0.211546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15793.05 | 21-APR-08:61 | 15793.05 | 21-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.639102E+10 | 0.00 | 637.64 | 0.593863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15794.49 | 01-MAY-08:61 | 15794.49 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.838478E+10 | 0.00 | 680.38 | 0.571507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15793.60 | 12-JUN-18:02 | 15793.60 | 12-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.915083E+10 | 0.00 | 700.10 | 0.559681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15326.17 | 17-JUL-18:01 | 14371.21 | 18-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.639467E+10 | 0.00 | 652.20 | 0.376906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15792.73 | 10-AUG-18:02 | 15792.73 | 10-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.146635E+10 | 0.00 | 266.69 | 0.869586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15794.30 | 10-SEP-15:11 | 15794.30 | 10-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 90488886.65 | 0.00 | 27.17 | 69210499.31 | 0.00 | 0.00 | 0.00 | 0.00 | 14865.37 | 04-OCT-08:62 | 14865.37 | 04-OCT-08:62 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342126E+11 | 0.00 | 3305.11 | 0.242554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.915083E+10 | 0.00 | 700.10 | 0.593863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15794.49 | 15794.49 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 56694.67 | 0.00 | 0.05 | 56694.67 | 0.00 | 0.00 | 0.00 | 0.00 | 396.82 | 08-FEB-19:06 | 396.82 | 08-FEB-19:06 | 0.00 | 0.00 | 0.00 |
March | 38074067.69 | 0.00 | 11.98 | 38074067.69 | 0.00 | 0.00 | 0.00 | 0.00 | 4053.41 | 11-MAR-09:01 | 4053.41 | 11-MAR-09:01 | 0.00 | 0.00 | 0.00 |
April | 0.866029E+09 | 0.00 | 167.81 | 0.843367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14286.57 | 21-APR-08:61 | 14286.57 | 21-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.444477E+10 | 0.00 | 531.93 | 0.409156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14918.07 | 14-MAY-20:41 | 14918.07 | 14-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.620928E+10 | 0.00 | 522.70 | 0.412035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15281.45 | 10-JUN-21:51 | 15281.45 | 10-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.660214E+10 | 0.00 | 539.49 | 0.401721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15884.02 | 22-JUL-08:32 | 15884.02 | 22-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.397859E+10 | 0.00 | 490.71 | 0.219822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14698.62 | 12-AUG-21:52 | 14283.08 | 31-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.629718E+09 | 0.00 | 158.45 | 0.351970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14287.47 | 10-SEP-15:11 | 14287.47 | 10-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 17137540.84 | 0.00 | 4.93 | 9636001.69 | 0.00 | 0.00 | 0.00 | 0.00 | 9034.91 | 04-OCT-08:62 | 9034.91 | 04-OCT-08:62 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227858E+11 | 0.00 | 2428.05 | 0.156704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.660214E+10 | 0.00 | 539.49 | 0.412035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15884.02 | 15884.02 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 28110.05 | 0.00 | 0.03 | 28110.05 | 0.00 | 0.00 | 0.00 | 0.00 | 281.10 | 09-FEB-16:15 | 281.10 | 09-FEB-16:15 | 0.00 | 0.00 | 0.00 |
March | 23407078.62 | 0.00 | 15.33 | 23407078.62 | 0.00 | 0.00 | 0.00 | 0.00 | 4272.96 | 22-MAR-15:11 | 4272.96 | 22-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.592936E+09 | 0.00 | 220.93 | 0.591891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4365.35 | 30-APR-15:11 | 4365.35 | 30-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.107858E+10 | 0.00 | 482.62 | 0.995272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4365.44 | 25-MAY-18:01 | 4365.44 | 25-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.179621E+10 | 0.00 | 635.19 | 0.120425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4365.56 | 07-JUN-15:12 | 4365.56 | 07-JUN-15:12 | 0.00 | 0.00 | 0.00 |
July | 0.180304E+10 | 0.00 | 650.77 | 0.101463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4327.39 | 27-JUL-08:62 | 3948.19 | 10-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.123910E+10 | 0.00 | 554.42 | 0.715334E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4455.86 | 13-AUG-08:61 | 4365.20 | 10-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.237541E+09 | 0.00 | 143.91 | 0.159291E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4365.26 | 07-SEP-15:11 | 4365.26 | 07-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 6009999.33 | 0.00 | 6.18 | 5061386.68 | 0.00 | 0.00 | 0.00 | 0.00 | 2923.30 | 03-OCT-15:11 | 2923.30 | 03-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.677685E+10 | 0.00 | 2709.38 | 0.470916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.180304E+10 | 0.00 | 650.77 | 0.120425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4455.86 | 4365.56 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 |
March | 574359.98 | 0.00 | 0.33 | 574359.98 | 0.00 | 0.00 | 0.00 | 0.00 | 803.37 | 22-MAR-15:13 | 803.37 | 22-MAR-15:13 | 0.00 | 0.00 | 0.00 |
April | 0.283154E+09 | 0.00 | 119.78 | 0.283046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3885.22 | 30-APR-18:01 | 3885.22 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.553345E+09 | 0.00 | 354.30 | 0.491217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4951.68 | 09-MAY-19:42 | 4951.68 | 09-MAY-19:42 | 0.00 | 0.00 | 0.00 |
June | 0.120055E+10 | 0.00 | 484.40 | 0.698772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4500.20 | 28-JUN-21:32 | 4391.61 | 28-JUN-21:32 | 0.00 | 0.00 | 0.00 |
July | 0.120564E+10 | 0.00 | 495.88 | 0.632238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4343.00 | 24-JUL-21:51 | 4034.61 | 06-JUL-17:32 | 0.00 | 0.00 | 0.00 |
August | 0.607548E+09 | 0.00 | 381.99 | 0.280564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4056.72 | 12-AUG-21:52 | 3882.72 | 30-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 67063246.82 | 0.00 | 62.82 | 38725715.22 | 0.00 | 0.00 | 0.00 | 0.00 | 3882.93 | 07-SEP-18:01 | 3882.93 | 07-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 734556.32 | 0.00 | 0.64 | 588538.99 | 0.00 | 0.00 | 0.00 | 0.00 | 980.10 | 01-OCT-15:13 | 734.35 | 01-OCT-15:13 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391861E+10 | 0.00 | 1900.15 | 0.242573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.120564E+10 | 0.00 | 495.88 | 0.698772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4951.68 | 4951.68 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.128249E+09 | 0.00 | 21.17 | 0.128249E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26299.81 | 15-FEB-16:11 | 26299.81 | 15-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.184839E+10 | 0.00 | 130.04 | 0.184668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26329.21 | 22-MAR-15:11 | 26329.21 | 22-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.588844E+10 | 0.00 | 377.99 | 0.581264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26331.24 | 18-APR-18:01 | 26331.24 | 18-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.802667E+10 | 0.00 | 605.88 | 0.714754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26333.09 | 03-MAY-15:11 | 26333.09 | 03-MAY-15:11 | 0.00 | 0.00 | 0.00 |
June | 0.102020E+11 | 0.00 | 652.63 | 0.642163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26333.28 | 15-JUN-18:01 | 26333.28 | 15-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.114212E+11 | 0.00 | 672.32 | 0.625876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26333.35 | 13-JUL-18:02 | 26333.35 | 13-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.967647E+10 | 0.00 | 636.05 | 0.573077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26329.06 | 21-AUG-18:01 | 26329.06 | 21-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.374639E+10 | 0.00 | 355.10 | 0.241095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26328.69 | 30-SEP-15:11 | 26328.69 | 30-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 0.858165E+09 | 0.00 | 85.10 | 0.771096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26316.20 | 14-OCT-15:11 | 26316.20 | 14-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 2758308.64 | 0.00 | 0.89 | 2758308.64 | 0.00 | 0.00 | 0.00 | 0.00 | 9089.92 | 08-NOV-16:12 | 9089.92 | 08-NOV-16:12 | 0.00 | 0.00 | 0.00 |
December | 120642.89 | 0.00 | 0.03 | 120642.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1206.43 | 24-DEC-09:05 | 1206.43 | 24-DEC-09:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.517989E+11 | 0.00 | 3537.19 | 0.365312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.114212E+11 | 0.00 | 672.32 | 0.714754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26333.35 | 26333.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 176.52 | 117.52 | 58.99 | 102.91 | 1000.41 | 0.00 | 0.00 | 0.00 |
February | 589.72 | 409.50 | 180.23 | 501.59 | 803.78 | 0.00 | 0.00 | 0.00 |
March | 998.33 | 675.44 | 322.89 | 995.01 | 616.98 | 0.00 | 0.00 | 0.00 |
April | 1223.24 | 761.28 | 461.96 | 1366.06 | 400.60 | 0.00 | 0.00 | 0.00 |
May | 1009.91 | 524.21 | 485.70 | 1167.56 | 205.82 | 0.00 | 0.00 | 0.00 |
June | 917.57 | 374.46 | 543.11 | 1094.30 | 104.39 | 0.00 | 0.00 | 0.00 |
July | 882.71 | 382.16 | 500.55 | 1080.85 | 108.87 | 0.00 | 0.00 | 0.00 |
August | 919.67 | 507.44 | 412.23 | 1104.50 | 167.27 | 0.00 | 0.00 | 0.00 |
September | 734.19 | 438.88 | 295.31 | 798.53 | 301.64 | 0.00 | 0.00 | 0.00 |
October | 543.72 | 344.94 | 198.78 | 502.12 | 523.29 | 0.00 | 0.00 | 0.00 |
November | 294.87 | 207.83 | 87.04 | 192.57 | 934.34 | 0.00 | 0.00 | 0.00 |
December | 52.15 | 36.76 | 15.39 | 9.11 | 1113.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 695.02 | 397.76 | 297.26 | 743.60 | 522.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.15 | 36.76 | 15.39 | 9.11 | 104.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1223.24 | 761.28 | 543.11 | 1366.06 | 1113.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 497.06 | 330.94 | 166.12 | 287.42 | 2804.84 | 0.00 | 0.00 | 0.00 |
February | 1660.62 | 1153.11 | 507.51 | 1407.24 | 2249.66 | 0.00 | 0.00 | 0.00 |
March | 2811.24 | 1902.01 | 909.23 | 2798.59 | 1727.56 | 0.00 | 0.00 | 0.00 |
April | 3444.56 | 2143.70 | 1300.86 | 3851.83 | 1114.97 | 0.00 | 0.00 | 0.00 |
May | 2843.85 | 1476.14 | 1367.70 | 3312.12 | 553.41 | 0.00 | 0.00 | 0.00 |
June | 2583.83 | 1054.45 | 1529.37 | 3121.81 | 266.43 | 0.00 | 0.00 | 0.00 |
July | 2485.64 | 1076.13 | 1409.52 | 3083.28 | 277.66 | 0.00 | 0.00 | 0.00 |
August | 2589.74 | 1428.93 | 1160.81 | 3138.63 | 440.56 | 0.00 | 0.00 | 0.00 |
September | 2067.42 | 1235.86 | 831.57 | 2254.61 | 836.67 | 0.00 | 0.00 | 0.00 |
October | 1531.07 | 971.33 | 559.74 | 1409.52 | 1468.93 | 0.00 | 0.00 | 0.00 |
November | 830.33 | 585.24 | 245.09 | 538.18 | 2614.56 | 0.00 | 0.00 | 0.00 |
December | 146.85 | 103.52 | 43.33 | 25.30 | 3117.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1957.12 | 1120.06 | 837.06 | 2104.37 | 1452.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 146.85 | 103.52 | 43.33 | 25.30 | 266.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3444.56 | 2143.70 | 1529.37 | 3851.83 | 3117.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 645.71 | 429.91 | 215.80 | 371.63 | 3793.08 | 0.00 | 0.00 | 0.00 |
February | 2157.24 | 1497.96 | 659.28 | 1839.52 | 3034.08 | 0.00 | 0.00 | 0.00 |
March | 3651.96 | 2470.82 | 1181.14 | 3682.64 | 2328.53 | 0.00 | 0.00 | 0.00 |
April | 4474.68 | 2784.79 | 1689.89 | 5073.12 | 1507.73 | 0.00 | 0.00 | 0.00 |
May | 3694.32 | 1917.59 | 1776.73 | 4351.22 | 766.17 | 0.00 | 0.00 | 0.00 |
June | 3356.54 | 1369.79 | 1986.74 | 4096.14 | 375.73 | 0.00 | 0.00 | 0.00 |
July | 3228.99 | 1397.95 | 1831.04 | 4042.29 | 393.12 | 0.00 | 0.00 | 0.00 |
August | 3364.22 | 1856.26 | 1507.96 | 4113.50 | 616.56 | 0.00 | 0.00 | 0.00 |
September | 2685.70 | 1605.45 | 1080.25 | 2952.68 | 1163.15 | 0.00 | 0.00 | 0.00 |
October | 1988.95 | 1261.81 | 727.14 | 1842.31 | 2012.55 | 0.00 | 0.00 | 0.00 |
November | 1078.64 | 760.26 | 318.39 | 698.42 | 3531.89 | 0.00 | 0.00 | 0.00 |
December | 190.76 | 134.47 | 56.29 | 31.95 | 4206.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2542.42 | 1455.03 | 1087.39 | 2760.60 | 1972.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 190.76 | 134.47 | 56.29 | 31.95 | 375.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4474.68 | 2784.79 | 1986.74 | 5073.12 | 4206.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.90 | 23.24 | 11.66 | 20.75 | 200.44 | 0.00 | 0.00 | 0.00 |
February | 116.60 | 80.96 | 35.63 | 101.37 | 160.51 | 0.00 | 0.00 | 0.00 |
March | 197.39 | 133.55 | 63.84 | 200.23 | 123.39 | 0.00 | 0.00 | 0.00 |
April | 241.86 | 150.52 | 91.34 | 272.91 | 78.49 | 0.00 | 0.00 | 0.00 |
May | 199.68 | 103.65 | 96.03 | 233.67 | 37.75 | 0.00 | 0.00 | 0.00 |
June | 181.42 | 74.04 | 107.38 | 220.68 | 16.95 | 0.00 | 0.00 | 0.00 |
July | 174.53 | 75.56 | 98.97 | 218.44 | 17.67 | 0.00 | 0.00 | 0.00 |
August | 181.84 | 100.33 | 81.51 | 222.18 | 28.89 | 0.00 | 0.00 | 0.00 |
September | 145.16 | 86.77 | 58.39 | 160.51 | 57.96 | 0.00 | 0.00 | 0.00 |
October | 107.50 | 68.20 | 39.30 | 101.32 | 103.99 | 0.00 | 0.00 | 0.00 |
November | 58.30 | 41.09 | 17.21 | 39.32 | 185.68 | 0.00 | 0.00 | 0.00 |
December | 10.31 | 7.27 | 3.04 | 1.89 | 222.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.42 | 78.64 | 58.77 | 149.57 | 102.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.31 | 7.27 | 3.04 | 1.89 | 16.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 241.86 | 150.52 | 107.38 | 272.91 | 222.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.18 | 1.22 | 5.96 | 0.00 | 413.15 | 0.00 | 0.00 | 0.00 |
February | 42.80 | 14.91 | 27.89 | 8.57 | 352.25 | 0.00 | 0.00 | 0.00 |
March | 128.77 | 55.61 | 73.16 | 74.25 | 255.60 | 0.00 | 0.00 | 0.00 |
April | 305.14 | 158.43 | 146.71 | 298.06 | 142.44 | 0.00 | 0.00 | 0.00 |
May | 296.02 | 135.07 | 160.95 | 313.24 | 64.70 | 0.00 | 0.00 | 0.00 |
June | 324.24 | 138.44 | 185.79 | 378.11 | 29.23 | 0.00 | 0.00 | 0.00 |
July | 270.84 | 102.34 | 168.49 | 320.83 | 31.25 | 0.00 | 0.00 | 0.00 |
August | 223.47 | 95.02 | 128.44 | 248.38 | 51.97 | 0.00 | 0.00 | 0.00 |
September | 134.45 | 56.06 | 78.40 | 114.74 | 110.97 | 0.00 | 0.00 | 0.00 |
October | 52.71 | 15.78 | 36.93 | 19.54 | 222.46 | 0.00 | 0.00 | 0.00 |
November | 21.30 | 7.81 | 13.50 | 2.17 | 391.49 | 0.00 | 0.00 | 0.00 |
December | 1.89 | 0.19 | 1.70 | 0.00 | 435.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.12 | 65.21 | 85.91 | 148.75 | 207.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.89 | 0.19 | 1.70 | 0.00 | 29.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.24 | 158.43 | 185.79 | 378.11 | 435.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.79 | 0.00 | 2.79 | 0.00 | 222.29 | 0.00 | 0.00 | 0.00 |
February | 12.35 | 0.00 | 12.35 | 0.00 | 198.03 | 0.00 | 0.00 | 0.00 |
March | 33.09 | 0.01 | 33.09 | 3.04 | 147.00 | 0.00 | 0.00 | 0.00 |
April | 60.43 | 1.72 | 58.70 | 25.35 | 77.47 | 0.00 | 0.00 | 0.00 |
May | 92.39 | 14.81 | 77.58 | 75.86 | 30.31 | 0.00 | 0.00 | 0.00 |
June | 119.61 | 26.54 | 93.08 | 123.88 | 12.53 | 0.00 | 0.00 | 0.00 |
July | 101.14 | 16.90 | 84.23 | 108.94 | 14.96 | 0.00 | 0.00 | 0.00 |
August | 65.18 | 3.91 | 61.28 | 57.73 | 27.13 | 0.00 | 0.00 | 0.00 |
September | 35.94 | 0.12 | 35.82 | 15.70 | 60.84 | 0.00 | 0.00 | 0.00 |
October | 17.39 | 0.00 | 17.39 | 1.49 | 123.74 | 0.00 | 0.00 | 0.00 |
November | 5.40 | 0.00 | 5.40 | 0.00 | 216.35 | 0.00 | 0.00 | 0.00 |
December | 0.85 | 0.00 | 0.85 | 0.00 | 232.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.71 | 5.36 | 40.35 | 34.54 | 113.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.85 | 0.00 | 0.85 | 0.00 | 12.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.61 | 26.54 | 93.08 | 123.88 | 232.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.18 | 1.22 | 5.96 | 0.00 | 413.03 | 0.00 | 0.00 | 0.00 |
February | 42.80 | 14.91 | 27.89 | 9.02 | 351.63 | 0.00 | 0.00 | 0.00 |
March | 128.77 | 55.61 | 73.16 | 76.98 | 253.20 | 0.00 | 0.00 | 0.00 |
April | 305.14 | 158.43 | 146.71 | 303.93 | 140.49 | 0.00 | 0.00 | 0.00 |
May | 296.02 | 135.07 | 160.95 | 313.69 | 64.44 | 0.00 | 0.00 | 0.00 |
June | 324.24 | 138.44 | 185.79 | 372.63 | 29.79 | 0.00 | 0.00 | 0.00 |
July | 270.84 | 102.34 | 168.49 | 317.32 | 32.20 | 0.00 | 0.00 | 0.00 |
August | 223.47 | 95.02 | 128.44 | 247.82 | 53.18 | 0.00 | 0.00 | 0.00 |
September | 134.45 | 56.06 | 78.40 | 117.76 | 109.45 | 0.00 | 0.00 | 0.00 |
October | 52.71 | 15.78 | 36.93 | 20.82 | 221.06 | 0.00 | 0.00 | 0.00 |
November | 21.30 | 7.81 | 13.50 | 2.27 | 391.28 | 0.00 | 0.00 | 0.00 |
December | 1.89 | 0.19 | 1.70 | 0.00 | 435.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.12 | 65.21 | 85.91 | 149.11 | 207.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.89 | 0.19 | 1.70 | 0.00 | 29.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.24 | 158.43 | 185.79 | 372.63 | 435.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.91 | 18.59 | 9.33 | 17.83 | 141.78 | 0.00 | 0.00 | 0.00 |
February | 93.26 | 64.76 | 28.50 | 84.01 | 113.75 | 0.00 | 0.00 | 0.00 |
March | 157.88 | 106.82 | 51.06 | 158.90 | 97.83 | 0.00 | 0.00 | 0.00 |
April | 193.45 | 120.39 | 73.06 | 209.01 | 77.86 | 0.00 | 0.00 | 0.00 |
May | 159.71 | 82.90 | 76.81 | 176.75 | 43.31 | 0.00 | 0.00 | 0.00 |
June | 145.11 | 59.22 | 85.89 | 164.74 | 23.35 | 0.00 | 0.00 | 0.00 |
July | 139.59 | 60.44 | 79.16 | 163.09 | 24.27 | 0.00 | 0.00 | 0.00 |
August | 145.44 | 80.25 | 65.19 | 167.64 | 35.99 | 0.00 | 0.00 | 0.00 |
September | 116.11 | 69.41 | 46.70 | 119.59 | 62.40 | 0.00 | 0.00 | 0.00 |
October | 85.98 | 54.55 | 31.44 | 77.12 | 89.02 | 0.00 | 0.00 | 0.00 |
November | 46.63 | 32.87 | 13.76 | 33.55 | 131.16 | 0.00 | 0.00 | 0.00 |
December | 8.25 | 5.81 | 2.43 | 1.79 | 158.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.91 | 62.90 | 47.01 | 114.56 | 83.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.25 | 5.81 | 2.43 | 1.79 | 23.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 193.45 | 120.39 | 85.89 | 209.01 | 158.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.24 | 0.00 | 2.24 | 0.00 | 181.89 | 0.00 | 0.00 | 0.00 |
February | 9.88 | 0.00 | 9.88 | 0.00 | 162.51 | 0.00 | 0.00 | 0.00 |
March | 26.48 | 0.00 | 26.47 | 2.09 | 120.71 | 0.00 | 0.00 | 0.00 |
April | 48.35 | 1.38 | 46.97 | 20.95 | 62.06 | 0.00 | 0.00 | 0.00 |
May | 73.92 | 11.85 | 62.07 | 63.53 | 23.69 | 0.00 | 0.00 | 0.00 |
June | 95.70 | 21.23 | 74.47 | 103.68 | 9.41 | 0.00 | 0.00 | 0.00 |
July | 80.92 | 13.52 | 67.40 | 90.50 | 11.34 | 0.00 | 0.00 | 0.00 |
August | 52.15 | 3.13 | 49.03 | 48.54 | 20.81 | 0.00 | 0.00 | 0.00 |
September | 28.75 | 0.09 | 28.66 | 12.41 | 49.63 | 0.00 | 0.00 | 0.00 |
October | 13.92 | 0.00 | 13.92 | 0.97 | 102.71 | 0.00 | 0.00 | 0.00 |
November | 4.32 | 0.00 | 4.32 | 0.00 | 177.27 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.00 | 0.68 | 0.00 | 190.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.57 | 4.29 | 32.29 | 28.73 | 92.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.00 | 0.68 | 0.00 | 9.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 95.70 | 21.23 | 74.47 | 103.68 | 190.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.45 | 5.72 | 9.73 | 1.99 | 403.57 | 0.00 | 0.00 | 0.00 |
February | 80.16 | 38.43 | 41.73 | 42.19 | 334.86 | 0.00 | 0.00 | 0.00 |
March | 224.83 | 113.84 | 110.99 | 193.71 | 248.90 | 0.00 | 0.00 | 0.00 |
April | 299.11 | 151.52 | 147.59 | 281.37 | 133.56 | 0.00 | 0.00 | 0.00 |
May | 435.61 | 245.90 | 189.70 | 495.42 | 60.48 | 0.00 | 0.00 | 0.00 |
June | 398.91 | 186.31 | 212.60 | 475.73 | 25.20 | 0.00 | 0.00 | 0.00 |
July | 379.95 | 184.76 | 195.18 | 465.48 | 28.48 | 0.00 | 0.00 | 0.00 |
August | 305.29 | 149.62 | 155.67 | 355.46 | 49.21 | 0.00 | 0.00 | 0.00 |
September | 191.08 | 86.44 | 104.64 | 185.89 | 107.64 | 0.00 | 0.00 | 0.00 |
October | 103.49 | 41.93 | 61.56 | 76.52 | 212.21 | 0.00 | 0.00 | 0.00 |
November | 21.45 | 7.79 | 13.66 | 1.58 | 390.36 | 0.00 | 0.00 | 0.00 |
December | 3.05 | 0.72 | 2.33 | 0.00 | 433.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.64 | 101.52 | 104.12 | 215.79 | 201.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.05 | 0.72 | 2.33 | 0.00 | 25.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 435.61 | 245.90 | 212.60 | 495.42 | 433.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.90 | 23.24 | 11.66 | 20.68 | 200.45 | 0.00 | 0.00 | 0.00 |
February | 116.60 | 80.96 | 35.63 | 100.81 | 160.68 | 0.00 | 0.00 | 0.00 |
March | 197.39 | 133.55 | 63.84 | 197.89 | 123.96 | 0.00 | 0.00 | 0.00 |
April | 241.86 | 150.52 | 91.34 | 271.72 | 78.13 | 0.00 | 0.00 | 0.00 |
May | 199.68 | 103.65 | 96.03 | 231.77 | 37.31 | 0.00 | 0.00 | 0.00 |
June | 181.42 | 74.04 | 107.38 | 219.76 | 16.12 | 0.00 | 0.00 | 0.00 |
July | 174.53 | 75.56 | 98.97 | 217.16 | 17.25 | 0.00 | 0.00 | 0.00 |
August | 181.84 | 100.33 | 81.51 | 221.01 | 28.84 | 0.00 | 0.00 | 0.00 |
September | 145.16 | 86.77 | 58.39 | 159.13 | 58.27 | 0.00 | 0.00 | 0.00 |
October | 107.50 | 68.20 | 39.30 | 100.24 | 104.37 | 0.00 | 0.00 | 0.00 |
November | 58.30 | 41.09 | 17.21 | 39.28 | 185.67 | 0.00 | 0.00 | 0.00 |
December | 10.31 | 7.27 | 3.04 | 1.89 | 222.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.42 | 78.64 | 58.77 | 148.57 | 102.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.31 | 7.27 | 3.04 | 1.89 | 16.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 241.86 | 150.52 | 107.38 | 271.72 | 222.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.79 | 0.00 | 2.79 | 0.00 | 222.05 | 0.00 | 0.00 | 0.00 |
February | 12.35 | 0.00 | 12.35 | 0.00 | 197.76 | 0.00 | 0.00 | 0.00 |
March | 33.09 | 0.01 | 33.09 | 2.56 | 148.29 | 0.00 | 0.00 | 0.00 |
April | 60.43 | 1.72 | 58.70 | 24.02 | 77.44 | 0.00 | 0.00 | 0.00 |
May | 92.39 | 14.81 | 77.58 | 73.72 | 30.15 | 0.00 | 0.00 | 0.00 |
June | 119.61 | 26.54 | 93.08 | 123.99 | 12.25 | 0.00 | 0.00 | 0.00 |
July | 101.14 | 16.90 | 84.23 | 107.39 | 14.82 | 0.00 | 0.00 | 0.00 |
August | 65.18 | 3.91 | 61.28 | 56.60 | 26.89 | 0.00 | 0.00 | 0.00 |
September | 35.94 | 0.12 | 35.82 | 14.44 | 61.58 | 0.00 | 0.00 | 0.00 |
October | 17.39 | 0.00 | 17.39 | 1.23 | 124.27 | 0.00 | 0.00 | 0.00 |
November | 5.40 | 0.00 | 5.40 | 0.00 | 216.36 | 0.00 | 0.00 | 0.00 |
December | 0.85 | 0.00 | 0.85 | 0.00 | 232.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.71 | 5.36 | 40.35 | 33.86 | 113.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.85 | 0.00 | 0.85 | 0.00 | 12.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.61 | 26.54 | 93.08 | 123.99 | 232.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.45 | 5.72 | 9.73 | 2.03 | 403.00 | 0.00 | 0.00 | 0.00 |
February | 80.16 | 38.43 | 41.73 | 42.80 | 333.24 | 0.00 | 0.00 | 0.00 |
March | 224.83 | 113.84 | 110.99 | 196.12 | 244.71 | 0.00 | 0.00 | 0.00 |
April | 299.11 | 151.52 | 147.59 | 285.93 | 130.95 | 0.00 | 0.00 | 0.00 |
May | 435.61 | 245.90 | 189.70 | 496.72 | 60.71 | 0.00 | 0.00 | 0.00 |
June | 398.91 | 186.31 | 212.60 | 473.41 | 26.74 | 0.00 | 0.00 | 0.00 |
July | 379.95 | 184.76 | 195.18 | 462.50 | 30.13 | 0.00 | 0.00 | 0.00 |
August | 305.29 | 149.62 | 155.67 | 355.96 | 50.39 | 0.00 | 0.00 | 0.00 |
September | 191.08 | 86.44 | 104.64 | 188.15 | 105.90 | 0.00 | 0.00 | 0.00 |
October | 103.49 | 41.93 | 61.56 | 77.75 | 210.04 | 0.00 | 0.00 | 0.00 |
November | 21.45 | 7.79 | 13.66 | 1.63 | 390.08 | 0.00 | 0.00 | 0.00 |
December | 3.05 | 0.72 | 2.33 | 0.00 | 433.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.64 | 101.52 | 104.12 | 216.43 | 200.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.05 | 0.72 | 2.33 | 0.00 | 26.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 435.61 | 245.90 | 212.60 | 496.72 | 433.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3.54 | 0.00 | 3.54 | 0.00 | 294.87 | 0.00 | 0.00 | 0.00 |
February | 15.65 | 0.00 | 15.65 | 0.00 | 264.12 | 0.00 | 0.00 | 0.00 |
March | 41.91 | 0.01 | 41.90 | 2.91 | 196.58 | 0.00 | 0.00 | 0.00 |
April | 76.53 | 2.18 | 74.34 | 30.93 | 102.11 | 0.00 | 0.00 | 0.00 |
May | 117.00 | 18.75 | 98.25 | 96.29 | 41.03 | 0.00 | 0.00 | 0.00 |
June | 151.48 | 33.61 | 117.88 | 158.55 | 17.71 | 0.00 | 0.00 | 0.00 |
July | 128.08 | 21.40 | 106.68 | 138.31 | 21.18 | 0.00 | 0.00 | 0.00 |
August | 82.55 | 4.95 | 77.60 | 72.91 | 37.12 | 0.00 | 0.00 | 0.00 |
September | 45.51 | 0.15 | 45.37 | 18.57 | 81.87 | 0.00 | 0.00 | 0.00 |
October | 22.03 | 0.00 | 22.03 | 1.44 | 166.51 | 0.00 | 0.00 | 0.00 |
November | 6.84 | 0.00 | 6.84 | 0.00 | 287.60 | 0.00 | 0.00 | 0.00 |
December | 1.07 | 0.00 | 1.07 | 0.00 | 308.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.89 | 6.79 | 51.11 | 43.59 | 150.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.07 | 0.00 | 1.07 | 0.00 | 17.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 151.48 | 33.61 | 117.88 | 158.55 | 308.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.30 | 0.00 | 1.30 | 0.00 | 108.69 | 0.00 | 0.00 | 0.00 |
February | 5.77 | 0.00 | 5.77 | 0.00 | 97.37 | 0.00 | 0.00 | 0.00 |
March | 15.45 | 0.00 | 15.45 | 1.07 | 72.47 | 0.00 | 0.00 | 0.00 |
April | 28.21 | 0.80 | 27.41 | 11.40 | 37.64 | 0.00 | 0.00 | 0.00 |
May | 43.13 | 6.91 | 36.22 | 35.50 | 15.12 | 0.00 | 0.00 | 0.00 |
June | 55.84 | 12.39 | 43.45 | 58.45 | 6.53 | 0.00 | 0.00 | 0.00 |
July | 47.22 | 7.89 | 39.33 | 50.99 | 7.81 | 0.00 | 0.00 | 0.00 |
August | 30.43 | 1.82 | 28.61 | 26.88 | 13.69 | 0.00 | 0.00 | 0.00 |
September | 16.78 | 0.05 | 16.72 | 6.85 | 30.18 | 0.00 | 0.00 | 0.00 |
October | 8.12 | 0.00 | 8.12 | 0.53 | 61.38 | 0.00 | 0.00 | 0.00 |
November | 2.52 | 0.00 | 2.52 | 0.00 | 106.01 | 0.00 | 0.00 | 0.00 |
December | 0.40 | 0.00 | 0.40 | 0.00 | 113.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.34 | 2.50 | 18.84 | 16.07 | 55.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.40 | 0.00 | 0.40 | 0.00 | 6.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.84 | 12.39 | 43.45 | 58.45 | 113.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.28 | 10.84 | 5.44 | 9.27 | 97.80 | 0.00 | 0.00 | 0.00 |
February | 54.40 | 37.78 | 16.63 | 46.33 | 77.97 | 0.00 | 0.00 | 0.00 |
March | 92.10 | 62.31 | 29.79 | 92.84 | 59.39 | 0.00 | 0.00 | 0.00 |
April | 112.85 | 70.23 | 42.62 | 128.31 | 37.46 | 0.00 | 0.00 | 0.00 |
May | 93.17 | 48.36 | 44.81 | 109.54 | 19.10 | 0.00 | 0.00 | 0.00 |
June | 84.65 | 34.55 | 50.10 | 102.60 | 9.52 | 0.00 | 0.00 | 0.00 |
July | 81.43 | 35.26 | 46.18 | 101.50 | 9.89 | 0.00 | 0.00 | 0.00 |
August | 84.84 | 46.81 | 38.03 | 103.81 | 15.18 | 0.00 | 0.00 | 0.00 |
September | 67.73 | 40.49 | 27.24 | 75.12 | 28.19 | 0.00 | 0.00 | 0.00 |
October | 50.16 | 31.82 | 18.34 | 46.62 | 50.58 | 0.00 | 0.00 | 0.00 |
November | 27.20 | 19.17 | 8.03 | 17.60 | 90.39 | 0.00 | 0.00 | 0.00 |
December | 4.81 | 3.39 | 1.42 | 0.79 | 108.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.12 | 36.69 | 27.42 | 69.59 | 50.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.81 | 3.39 | 1.42 | 0.79 | 9.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.85 | 70.23 | 50.10 | 128.31 | 108.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.20 | 29.43 | 14.77 | 25.17 | 265.46 | 0.00 | 0.00 | 0.00 |
February | 147.66 | 102.54 | 45.13 | 125.76 | 211.63 | 0.00 | 0.00 | 0.00 |
March | 249.98 | 169.13 | 80.85 | 251.98 | 161.20 | 0.00 | 0.00 | 0.00 |
April | 306.30 | 190.62 | 115.67 | 348.26 | 101.67 | 0.00 | 0.00 | 0.00 |
May | 252.88 | 131.26 | 121.62 | 297.31 | 51.84 | 0.00 | 0.00 | 0.00 |
June | 229.76 | 93.76 | 135.99 | 278.49 | 25.84 | 0.00 | 0.00 | 0.00 |
July | 221.03 | 95.69 | 125.34 | 275.48 | 26.86 | 0.00 | 0.00 | 0.00 |
August | 230.28 | 127.06 | 103.22 | 281.76 | 41.21 | 0.00 | 0.00 | 0.00 |
September | 183.84 | 109.89 | 73.94 | 203.90 | 76.52 | 0.00 | 0.00 | 0.00 |
October | 136.14 | 86.37 | 49.77 | 126.55 | 137.30 | 0.00 | 0.00 | 0.00 |
November | 73.83 | 52.04 | 21.79 | 47.78 | 245.34 | 0.00 | 0.00 | 0.00 |
December | 13.06 | 9.20 | 3.85 | 2.14 | 294.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 174.03 | 99.60 | 74.43 | 188.89 | 136.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.06 | 9.20 | 3.85 | 2.14 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 306.30 | 190.62 | 135.99 | 348.26 | 294.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.90 | 23.24 | 11.66 | 20.85 | 199.09 | 0.00 | 0.00 | 0.00 |
February | 116.60 | 80.96 | 35.63 | 101.69 | 159.48 | 0.00 | 0.00 | 0.00 |
March | 197.39 | 133.55 | 63.84 | 200.42 | 122.84 | 0.00 | 0.00 | 0.00 |
April | 241.86 | 150.52 | 91.34 | 272.36 | 78.19 | 0.00 | 0.00 | 0.00 |
May | 199.68 | 103.65 | 96.03 | 232.88 | 37.42 | 0.00 | 0.00 | 0.00 |
June | 181.42 | 74.04 | 107.38 | 219.79 | 16.70 | 0.00 | 0.00 | 0.00 |
July | 174.53 | 75.56 | 98.97 | 217.66 | 17.40 | 0.00 | 0.00 | 0.00 |
August | 181.84 | 100.33 | 81.51 | 221.62 | 28.52 | 0.00 | 0.00 | 0.00 |
September | 145.16 | 86.77 | 58.39 | 160.60 | 57.32 | 0.00 | 0.00 | 0.00 |
October | 107.50 | 68.20 | 39.30 | 101.56 | 103.32 | 0.00 | 0.00 | 0.00 |
November | 58.30 | 41.09 | 17.21 | 39.63 | 183.99 | 0.00 | 0.00 | 0.00 |
December | 10.31 | 7.27 | 3.04 | 1.92 | 221.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.42 | 78.64 | 58.77 | 149.38 | 101.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.31 | 7.27 | 3.04 | 1.92 | 16.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 241.86 | 150.52 | 107.38 | 272.36 | 221.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.18 | 1.22 | 5.96 | 0.00 | 410.39 | 0.00 | 0.00 | 0.00 |
February | 42.80 | 14.91 | 27.89 | 8.72 | 349.80 | 0.00 | 0.00 | 0.00 |
March | 128.77 | 55.61 | 73.16 | 74.50 | 254.05 | 0.00 | 0.00 | 0.00 |
April | 305.14 | 158.43 | 146.71 | 296.99 | 141.67 | 0.00 | 0.00 | 0.00 |
May | 296.02 | 135.07 | 160.95 | 312.13 | 64.05 | 0.00 | 0.00 | 0.00 |
June | 324.24 | 138.44 | 185.79 | 376.64 | 28.74 | 0.00 | 0.00 | 0.00 |
July | 270.84 | 102.34 | 168.49 | 319.63 | 30.72 | 0.00 | 0.00 | 0.00 |
August | 223.47 | 95.02 | 128.44 | 247.59 | 51.21 | 0.00 | 0.00 | 0.00 |
September | 134.45 | 56.06 | 78.40 | 115.00 | 109.50 | 0.00 | 0.00 | 0.00 |
October | 52.71 | 15.78 | 36.93 | 19.89 | 220.80 | 0.00 | 0.00 | 0.00 |
November | 21.30 | 7.81 | 13.50 | 2.24 | 387.74 | 0.00 | 0.00 | 0.00 |
December | 1.89 | 0.19 | 1.70 | 0.00 | 432.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.12 | 65.21 | 85.91 | 148.37 | 206.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.89 | 0.19 | 1.70 | 0.00 | 28.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.24 | 158.43 | 185.79 | 376.64 | 432.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.79 | 0.00 | 2.79 | 0.00 | 220.88 | 0.00 | 0.00 | 0.00 |
February | 12.35 | 0.00 | 12.35 | 0.00 | 196.80 | 0.00 | 0.00 | 0.00 |
March | 33.09 | 0.01 | 33.09 | 3.13 | 146.31 | 0.00 | 0.00 | 0.00 |
April | 60.43 | 1.72 | 58.70 | 25.57 | 77.12 | 0.00 | 0.00 | 0.00 |
May | 92.39 | 14.81 | 77.58 | 75.59 | 30.21 | 0.00 | 0.00 | 0.00 |
June | 119.61 | 26.54 | 93.08 | 122.84 | 12.59 | 0.00 | 0.00 | 0.00 |
July | 101.14 | 16.90 | 84.23 | 108.22 | 14.99 | 0.00 | 0.00 | 0.00 |
August | 65.18 | 3.91 | 61.28 | 57.56 | 27.08 | 0.00 | 0.00 | 0.00 |
September | 35.94 | 0.12 | 35.82 | 16.13 | 59.93 | 0.00 | 0.00 | 0.00 |
October | 17.39 | 0.00 | 17.39 | 1.63 | 122.92 | 0.00 | 0.00 | 0.00 |
November | 5.40 | 0.00 | 5.40 | 0.00 | 214.40 | 0.00 | 0.00 | 0.00 |
December | 0.85 | 0.00 | 0.85 | 0.00 | 231.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.71 | 5.36 | 40.35 | 34.43 | 112.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.85 | 0.00 | 0.85 | 0.00 | 12.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.61 | 26.54 | 93.08 | 122.84 | 231.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.18 | 1.22 | 5.96 | 0.00 | 410.21 | 0.00 | 0.00 | 0.00 |
February | 42.80 | 14.91 | 27.89 | 9.14 | 349.28 | 0.00 | 0.00 | 0.00 |
March | 128.77 | 55.61 | 73.16 | 77.16 | 252.03 | 0.00 | 0.00 | 0.00 |
April | 305.14 | 158.43 | 146.71 | 303.37 | 139.66 | 0.00 | 0.00 | 0.00 |
May | 296.02 | 135.07 | 160.95 | 312.43 | 63.96 | 0.00 | 0.00 | 0.00 |
June | 324.24 | 138.44 | 185.79 | 370.05 | 29.79 | 0.00 | 0.00 | 0.00 |
July | 270.84 | 102.34 | 168.49 | 315.41 | 32.10 | 0.00 | 0.00 | 0.00 |
August | 223.47 | 95.02 | 128.44 | 246.71 | 52.85 | 0.00 | 0.00 | 0.00 |
September | 134.45 | 56.06 | 78.40 | 118.43 | 107.83 | 0.00 | 0.00 | 0.00 |
October | 52.71 | 15.78 | 36.93 | 21.19 | 219.58 | 0.00 | 0.00 | 0.00 |
November | 21.30 | 7.81 | 13.50 | 2.35 | 387.50 | 0.00 | 0.00 | 0.00 |
December | 1.89 | 0.19 | 1.70 | 0.00 | 432.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.12 | 65.21 | 85.91 | 148.61 | 205.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.89 | 0.19 | 1.70 | 0.00 | 29.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.24 | 158.43 | 185.79 | 370.05 | 432.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.18 | 34.08 | 17.11 | 29.69 | 296.46 | 0.00 | 0.00 | 0.00 |
February | 171.00 | 118.74 | 52.26 | 144.65 | 238.83 | 0.00 | 0.00 | 0.00 |
March | 289.49 | 195.86 | 93.63 | 286.57 | 184.93 | 0.00 | 0.00 | 0.00 |
April | 354.71 | 220.75 | 133.96 | 395.07 | 116.28 | 0.00 | 0.00 | 0.00 |
May | 292.85 | 152.01 | 140.84 | 340.23 | 54.90 | 0.00 | 0.00 | 0.00 |
June | 266.07 | 108.58 | 157.49 | 323.03 | 24.05 | 0.00 | 0.00 | 0.00 |
July | 255.96 | 110.81 | 145.15 | 319.34 | 25.25 | 0.00 | 0.00 | 0.00 |
August | 266.68 | 147.14 | 119.54 | 323.78 | 41.92 | 0.00 | 0.00 | 0.00 |
September | 212.89 | 127.26 | 85.63 | 231.72 | 86.43 | 0.00 | 0.00 | 0.00 |
October | 157.66 | 100.02 | 57.64 | 144.26 | 155.82 | 0.00 | 0.00 | 0.00 |
November | 85.50 | 60.26 | 25.24 | 56.38 | 273.92 | 0.00 | 0.00 | 0.00 |
December | 15.12 | 10.66 | 4.46 | 2.70 | 328.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 201.54 | 115.34 | 86.20 | 216.66 | 151.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.12 | 10.66 | 4.46 | 2.70 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 354.71 | 220.75 | 157.49 | 395.07 | 328.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.56 | 0.00 | 19.56 | 0.00 | 1591.97 | 0.00 | 0.00 | 0.00 |
February | 86.48 | 0.00 | 86.48 | 0.00 | 1423.72 | 0.00 | 0.00 | 0.00 |
March | 231.64 | 0.04 | 231.60 | 16.96 | 1065.25 | 0.00 | 0.00 | 0.00 |
April | 422.97 | 12.07 | 410.90 | 178.89 | 557.89 | 0.00 | 0.00 | 0.00 |
May | 646.69 | 103.65 | 543.03 | 549.36 | 220.06 | 0.00 | 0.00 | 0.00 |
June | 837.27 | 185.76 | 651.51 | 907.00 | 90.97 | 0.00 | 0.00 | 0.00 |
July | 707.92 | 118.31 | 589.61 | 795.00 | 108.00 | 0.00 | 0.00 | 0.00 |
August | 456.27 | 27.35 | 428.92 | 424.70 | 193.33 | 0.00 | 0.00 | 0.00 |
September | 251.56 | 0.82 | 250.74 | 106.77 | 447.50 | 0.00 | 0.00 | 0.00 |
October | 121.74 | 0.00 | 121.74 | 8.06 | 911.97 | 0.00 | 0.00 | 0.00 |
November | 37.78 | 0.00 | 37.78 | 0.00 | 1544.27 | 0.00 | 0.00 | 0.00 |
December | 5.93 | 0.00 | 5.93 | 0.00 | 1660.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 319.97 | 37.50 | 282.47 | 250.40 | 814.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.93 | 0.00 | 5.93 | 0.00 | 90.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 837.27 | 185.76 | 651.51 | 907.00 | 1660.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.56 | 0.00 | 19.56 | 0.00 | 1613.86 | 0.00 | 0.00 | 0.00 |
February | 86.48 | 0.00 | 86.48 | 0.00 | 1445.00 | 0.00 | 0.00 | 0.00 |
March | 231.64 | 0.04 | 231.60 | 15.46 | 1087.41 | 0.00 | 0.00 | 0.00 |
April | 422.97 | 12.07 | 410.90 | 170.91 | 574.16 | 0.00 | 0.00 | 0.00 |
May | 646.69 | 103.65 | 543.03 | 536.18 | 226.52 | 0.00 | 0.00 | 0.00 |
June | 837.27 | 185.76 | 651.51 | 893.17 | 94.71 | 0.00 | 0.00 | 0.00 |
July | 707.92 | 118.31 | 589.61 | 782.07 | 112.49 | 0.00 | 0.00 | 0.00 |
August | 456.27 | 27.35 | 428.92 | 413.99 | 200.55 | 0.00 | 0.00 | 0.00 |
September | 251.56 | 0.82 | 250.74 | 100.56 | 465.50 | 0.00 | 0.00 | 0.00 |
October | 121.74 | 0.00 | 121.74 | 6.76 | 936.77 | 0.00 | 0.00 | 0.00 |
November | 37.78 | 0.00 | 37.78 | 0.00 | 1565.05 | 0.00 | 0.00 | 0.00 |
December | 5.93 | 0.00 | 5.93 | 0.00 | 1680.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 319.97 | 37.50 | 282.47 | 244.73 | 830.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.93 | 0.00 | 5.93 | 0.00 | 94.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 837.27 | 185.76 | 651.51 | 893.17 | 1680.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.79 | 0.00 | 2.79 | 0.00 | 194.90 | 0.00 | 0.00 | 0.00 |
February | 12.35 | 0.00 | 12.35 | 0.01 | 170.61 | 0.00 | 0.00 | 0.00 |
March | 33.09 | 0.01 | 33.09 | 8.11 | 126.65 | 0.00 | 0.00 | 0.00 |
April | 60.43 | 1.72 | 58.70 | 48.30 | 69.90 | 0.00 | 0.00 | 0.00 |
May | 92.39 | 14.81 | 77.58 | 113.27 | 29.72 | 0.00 | 0.00 | 0.00 |
June | 119.61 | 26.54 | 93.08 | 170.17 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 101.14 | 16.90 | 84.23 | 153.71 | 14.90 | 0.00 | 0.00 | 0.00 |
August | 65.18 | 3.91 | 61.28 | 96.75 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 35.94 | 0.12 | 35.82 | 36.56 | 49.25 | 0.00 | 0.00 | 0.00 |
October | 17.39 | 0.00 | 17.39 | 5.72 | 102.10 | 0.00 | 0.00 | 0.00 |
November | 5.40 | 0.00 | 5.40 | 0.00 | 187.34 | 0.00 | 0.00 | 0.00 |
December | 0.85 | 0.00 | 0.85 | 0.00 | 204.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.71 | 5.36 | 40.35 | 53.03 | 98.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.85 | 0.00 | 0.85 | 0.00 | 12.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.61 | 26.54 | 93.08 | 170.17 | 204.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.91 | 11.45 | 19.46 | 7.12 | 708.42 | 0.00 | 0.00 | 0.00 |
February | 160.31 | 76.85 | 83.45 | 106.57 | 584.77 | 0.00 | 0.00 | 0.00 |
March | 449.63 | 227.67 | 221.96 | 444.13 | 435.55 | 0.00 | 0.00 | 0.00 |
April | 598.18 | 303.01 | 295.16 | 679.16 | 246.49 | 0.00 | 0.00 | 0.00 |
May | 871.15 | 491.77 | 379.38 | 1137.85 | 114.51 | 0.00 | 0.00 | 0.00 |
June | 797.76 | 372.59 | 425.17 | 1114.90 | 51.35 | 0.00 | 0.00 | 0.00 |
July | 759.84 | 369.50 | 390.34 | 1095.47 | 57.36 | 0.00 | 0.00 | 0.00 |
August | 610.54 | 299.21 | 311.32 | 863.69 | 91.85 | 0.00 | 0.00 | 0.00 |
September | 382.14 | 172.86 | 209.27 | 476.14 | 180.23 | 0.00 | 0.00 | 0.00 |
October | 206.96 | 83.85 | 123.11 | 195.62 | 358.42 | 0.00 | 0.00 | 0.00 |
November | 42.90 | 15.58 | 27.32 | 6.68 | 675.16 | 0.00 | 0.00 | 0.00 |
December | 6.11 | 1.45 | 4.66 | 0.00 | 763.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 411.25 | 203.03 | 208.22 | 513.29 | 354.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.11 | 1.45 | 4.66 | 0.00 | 51.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 871.15 | 491.77 | 425.17 | 1137.85 | 763.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.90 | 23.24 | 11.66 | 24.78 | 176.86 | 0.00 | 0.00 | 0.00 |
February | 116.60 | 80.96 | 35.63 | 112.53 | 142.90 | 0.00 | 0.00 | 0.00 |
March | 197.39 | 133.55 | 63.84 | 219.11 | 112.33 | 0.00 | 0.00 | 0.00 |
April | 241.86 | 150.52 | 91.34 | 302.46 | 70.99 | 0.00 | 0.00 | 0.00 |
May | 199.68 | 103.65 | 96.03 | 270.35 | 34.73 | 0.00 | 0.00 | 0.00 |
June | 181.42 | 74.04 | 107.38 | 263.60 | 17.08 | 0.00 | 0.00 | 0.00 |
July | 174.53 | 75.56 | 98.97 | 261.11 | 17.64 | 0.00 | 0.00 | 0.00 |
August | 181.84 | 100.33 | 81.51 | 260.48 | 25.86 | 0.00 | 0.00 | 0.00 |
September | 145.16 | 86.77 | 58.39 | 187.57 | 48.81 | 0.00 | 0.00 | 0.00 |
October | 107.50 | 68.20 | 39.30 | 116.50 | 90.81 | 0.00 | 0.00 | 0.00 |
November | 58.30 | 41.09 | 17.21 | 46.19 | 162.81 | 0.00 | 0.00 | 0.00 |
December | 10.31 | 7.27 | 3.04 | 2.94 | 195.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.42 | 78.64 | 58.77 | 172.49 | 91.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.31 | 7.27 | 3.04 | 2.94 | 17.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 241.86 | 150.52 | 107.38 | 302.46 | 195.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3.54 | 0.00 | 3.54 | 0.00 | 294.14 | 0.00 | 0.00 | 0.00 |
February | 15.65 | 0.00 | 15.65 | 0.00 | 264.15 | 0.00 | 0.00 | 0.00 |
March | 41.91 | 0.01 | 41.90 | 2.66 | 198.13 | 0.00 | 0.00 | 0.00 |
April | 76.53 | 2.18 | 74.34 | 27.64 | 105.33 | 0.00 | 0.00 | 0.00 |
May | 117.00 | 18.75 | 98.25 | 89.34 | 44.07 | 0.00 | 0.00 | 0.00 |
June | 151.48 | 33.61 | 117.88 | 152.05 | 19.23 | 0.00 | 0.00 | 0.00 |
July | 128.08 | 21.40 | 106.68 | 132.18 | 23.09 | 0.00 | 0.00 | 0.00 |
August | 82.55 | 4.95 | 77.60 | 67.16 | 40.62 | 0.00 | 0.00 | 0.00 |
September | 45.51 | 0.15 | 45.37 | 15.97 | 86.70 | 0.00 | 0.00 | 0.00 |
October | 22.03 | 0.00 | 22.03 | 1.17 | 168.72 | 0.00 | 0.00 | 0.00 |
November | 6.84 | 0.00 | 6.84 | 0.00 | 286.36 | 0.00 | 0.00 | 0.00 |
December | 1.07 | 0.00 | 1.07 | 0.00 | 307.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.89 | 6.79 | 51.11 | 40.93 | 152.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.07 | 0.00 | 1.07 | 0.00 | 19.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 151.48 | 33.61 | 117.88 | 152.05 | 307.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3.17 | 0.00 | 3.17 | 0.00 | 263.17 | 0.00 | 0.00 | 0.00 |
February | 14.00 | 0.00 | 14.00 | 0.00 | 236.28 | 0.00 | 0.00 | 0.00 |
March | 37.50 | 0.01 | 37.49 | 2.38 | 177.27 | 0.00 | 0.00 | 0.00 |
April | 68.47 | 1.95 | 66.52 | 24.73 | 94.24 | 0.00 | 0.00 | 0.00 |
May | 104.68 | 16.78 | 87.90 | 79.93 | 39.43 | 0.00 | 0.00 | 0.00 |
June | 135.53 | 30.07 | 105.46 | 136.04 | 17.21 | 0.00 | 0.00 | 0.00 |
July | 114.59 | 19.15 | 95.44 | 118.26 | 20.66 | 0.00 | 0.00 | 0.00 |
August | 73.86 | 4.43 | 69.43 | 60.09 | 36.34 | 0.00 | 0.00 | 0.00 |
September | 40.72 | 0.13 | 40.59 | 14.29 | 77.58 | 0.00 | 0.00 | 0.00 |
October | 19.71 | 0.00 | 19.71 | 1.05 | 150.93 | 0.00 | 0.00 | 0.00 |
November | 6.12 | 0.00 | 6.12 | 0.00 | 256.21 | 0.00 | 0.00 | 0.00 |
December | 0.96 | 0.00 | 0.96 | 0.00 | 275.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.80 | 6.07 | 45.73 | 36.62 | 136.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.96 | 0.00 | 0.96 | 0.00 | 17.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 135.53 | 30.07 | 105.46 | 136.04 | 275.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 130.29 | 86.75 | 43.54 | 74.07 | 780.71 | 0.00 | 0.00 | 0.00 |
February | 435.30 | 302.26 | 133.03 | 369.69 | 623.56 | 0.00 | 0.00 | 0.00 |
March | 736.91 | 498.57 | 238.34 | 738.03 | 477.42 | 0.00 | 0.00 | 0.00 |
April | 902.92 | 561.93 | 340.99 | 1013.45 | 307.92 | 0.00 | 0.00 | 0.00 |
May | 745.46 | 386.94 | 358.52 | 857.40 | 164.97 | 0.00 | 0.00 | 0.00 |
June | 677.30 | 276.40 | 400.90 | 803.12 | 83.53 | 0.00 | 0.00 | 0.00 |
July | 651.56 | 282.08 | 369.48 | 794.73 | 87.01 | 0.00 | 0.00 | 0.00 |
August | 678.85 | 374.56 | 304.28 | 813.52 | 133.50 | 0.00 | 0.00 | 0.00 |
September | 541.93 | 323.95 | 217.98 | 589.88 | 237.86 | 0.00 | 0.00 | 0.00 |
October | 401.34 | 254.61 | 146.73 | 369.27 | 409.38 | 0.00 | 0.00 | 0.00 |
November | 217.65 | 153.41 | 64.25 | 141.00 | 720.18 | 0.00 | 0.00 | 0.00 |
December | 38.49 | 27.13 | 11.36 | 6.35 | 867.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 513.02 | 293.60 | 219.42 | 548.03 | 406.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 38.49 | 27.13 | 11.36 | 6.35 | 83.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 902.92 | 561.93 | 400.90 | 1013.45 | 867.73 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.472780E+09 | 0.314774E+09 | 0.158006E+09 | 0.275631E+09 | 0.267949E+10 |
February | 0.142666E+10 | 0.990652E+09 | 0.436005E+09 | 0.121345E+10 | 0.194451E+10 |
March | 0.267393E+10 | 0.180911E+10 | 0.864824E+09 | 0.266503E+10 | 0.165253E+10 |
April | 0.317064E+10 | 0.197323E+10 | 0.119741E+10 | 0.354083E+10 | 0.103835E+10 |
May | 0.270495E+10 | 0.140405E+10 | 0.130090E+10 | 0.312720E+10 | 0.551265E+09 |
June | 0.237835E+10 | 0.970599E+09 | 0.140775E+10 | 0.283644E+10 | 0.270589E+09 |
July | 0.236424E+10 | 0.102357E+10 | 0.134067E+10 | 0.289496E+10 | 0.291596E+09 |
August | 0.246326E+10 | 0.135914E+10 | 0.110412E+10 | 0.295829E+10 | 0.448026E+09 |
September | 0.190301E+10 | 0.113758E+10 | 0.765436E+09 | 0.206980E+10 | 0.781848E+09 |
October | 0.145629E+10 | 0.923887E+09 | 0.532405E+09 | 0.134487E+10 | 0.140158E+10 |
November | 0.764297E+09 | 0.538697E+09 | 0.225599E+09 | 0.499149E+09 | 0.242182E+10 |
December | 0.139675E+09 | 98460044.66 | 41214694.35 | 24395650.64 | 0.298314E+10 |
Annual Sum or Average | 0.219181E+11 | 0.125437E+11 | 0.937435E+10 | 0.234500E+11 | 0.164648E+11 |
Minimum of Months | 0.139675E+09 | 98460044.66 | 41214694.35 | 24395650.64 | 0.270589E+09 |
Maximum of Months | 0.317064E+10 | 0.197323E+10 | 0.140775E+10 | 0.354083E+10 | 0.298314E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133132E+10 | 0.886384E+09 | 0.444935E+09 | 0.769828E+09 | 0.751249E+10 |
February | 0.401737E+10 | 0.278961E+10 | 0.122776E+10 | 0.340440E+10 | 0.544237E+10 |
March | 0.752962E+10 | 0.509434E+10 | 0.243529E+10 | 0.749574E+10 | 0.462710E+10 |
April | 0.892830E+10 | 0.555648E+10 | 0.337183E+10 | 0.998394E+10 | 0.288999E+10 |
May | 0.761696E+10 | 0.395370E+10 | 0.366326E+10 | 0.887119E+10 | 0.148225E+10 |
June | 0.669728E+10 | 0.273314E+10 | 0.396414E+10 | 0.809173E+10 | 0.690589E+09 |
July | 0.665755E+10 | 0.288230E+10 | 0.377525E+10 | 0.825827E+10 | 0.743680E+09 |
August | 0.693636E+10 | 0.382724E+10 | 0.310912E+10 | 0.840650E+10 | 0.117999E+10 |
September | 0.535876E+10 | 0.320335E+10 | 0.215542E+10 | 0.584396E+10 | 0.216866E+10 |
October | 0.410082E+10 | 0.260160E+10 | 0.149922E+10 | 0.377525E+10 | 0.393440E+10 |
November | 0.215221E+10 | 0.151694E+10 | 0.635273E+09 | 0.139497E+10 | 0.677694E+10 |
December | 0.393315E+09 | 0.277257E+09 | 0.116058E+09 | 67758619.82 | 0.835098E+10 |
Annual Sum or Average | 0.617199E+11 | 0.353223E+11 | 0.263975E+11 | 0.663635E+11 | 0.457994E+11 |
Minimum of Months | 0.393315E+09 | 0.277257E+09 | 0.116058E+09 | 67758619.82 | 0.690589E+09 |
Maximum of Months | 0.892830E+10 | 0.555648E+10 | 0.396414E+10 | 0.998394E+10 | 0.835098E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172946E+10 | 0.115146E+10 | 0.577995E+09 | 0.995372E+09 | 0.101594E+11 |
February | 0.521879E+10 | 0.362386E+10 | 0.159493E+10 | 0.445016E+10 | 0.734005E+10 |
March | 0.978141E+10 | 0.661783E+10 | 0.316358E+10 | 0.986360E+10 | 0.623674E+10 |
April | 0.115984E+11 | 0.721818E+10 | 0.438019E+10 | 0.131495E+11 | 0.390802E+10 |
May | 0.989487E+10 | 0.513608E+10 | 0.475878E+10 | 0.116543E+11 | 0.205212E+10 |
June | 0.870015E+10 | 0.355051E+10 | 0.514964E+10 | 0.106172E+11 | 0.973892E+09 |
July | 0.864853E+10 | 0.374427E+10 | 0.490426E+10 | 0.108269E+11 | 0.105294E+10 |
August | 0.901073E+10 | 0.497180E+10 | 0.403893E+10 | 0.110176E+11 | 0.165138E+10 |
September | 0.696134E+10 | 0.416133E+10 | 0.280001E+10 | 0.765336E+10 | 0.301488E+10 |
October | 0.532720E+10 | 0.337963E+10 | 0.194757E+10 | 0.493445E+10 | 0.539040E+10 |
November | 0.279584E+10 | 0.197059E+10 | 0.825256E+09 | 0.181032E+10 | 0.915465E+10 |
December | 0.510938E+09 | 0.360173E+09 | 0.150766E+09 | 85571057.55 | 0.112668E+11 |
Annual Sum or Average | 0.801776E+11 | 0.458857E+11 | 0.342919E+11 | 0.870583E+11 | 0.622012E+11 |
Minimum of Months | 0.510938E+09 | 0.360173E+09 | 0.150766E+09 | 85571057.55 | 0.973892E+09 |
Maximum of Months | 0.115984E+11 | 0.721818E+10 | 0.514964E+10 | 0.131495E+11 | 0.112668E+11 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93476878.82 | 62236309.34 | 31240569.48 | 55568334.69 | 0.536845E+09 |
February | 0.282075E+09 | 0.195869E+09 | 86205933.23 | 0.245236E+09 | 0.388294E+09 |
March | 0.528684E+09 | 0.357692E+09 | 0.170991E+09 | 0.536308E+09 | 0.330486E+09 |
April | 0.626891E+09 | 0.390141E+09 | 0.236750E+09 | 0.707387E+09 | 0.203442E+09 |
May | 0.534817E+09 | 0.277604E+09 | 0.257213E+09 | 0.625861E+09 | 0.101099E+09 |
June | 0.470243E+09 | 0.191904E+09 | 0.278339E+09 | 0.572005E+09 | 43933599.29 |
July | 0.467453E+09 | 0.202377E+09 | 0.265076E+09 | 0.585076E+09 | 47326459.57 |
August | 0.487029E+09 | 0.268725E+09 | 0.218305E+09 | 0.595079E+09 | 77391693.48 |
September | 0.376259E+09 | 0.224919E+09 | 0.151341E+09 | 0.416041E+09 | 0.150237E+09 |
October | 0.287934E+09 | 0.182668E+09 | 0.105266E+09 | 0.271379E+09 | 0.278529E+09 |
November | 0.151115E+09 | 0.106510E+09 | 44604980.56 | 0.101910E+09 | 0.481290E+09 |
December | 27616108.81 | 19467241.87 | 8148866.95 | 5069897.82 | 0.595911E+09 |
Annual Sum or Average | 0.433359E+10 | 0.248011E+10 | 0.185348E+10 | 0.471692E+10 | 0.323479E+10 |
Minimum of Months | 27616108.81 | 19467241.87 | 8148866.95 | 5069897.82 | 43933599.29 |
Maximum of Months | 0.626891E+09 | 0.390141E+09 | 0.278339E+09 | 0.707387E+09 | 0.595911E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 19232962.10 | 3269712.17 | 15963249.93 | 0.00 | 0.110658E+10 |
February | 0.103533E+09 | 36059635.70 | 67473741.62 | 20728151.13 | 0.852155E+09 |
March | 0.344892E+09 | 0.148950E+09 | 0.195941E+09 | 0.198860E+09 | 0.684599E+09 |
April | 0.790929E+09 | 0.410659E+09 | 0.380270E+09 | 0.772561E+09 | 0.369199E+09 |
May | 0.792860E+09 | 0.361774E+09 | 0.431086E+09 | 0.838972E+09 | 0.173285E+09 |
June | 0.840418E+09 | 0.358839E+09 | 0.481579E+09 | 0.980068E+09 | 75763190.00 |
July | 0.725411E+09 | 0.274115E+09 | 0.451296E+09 | 0.859319E+09 | 83711422.43 |
August | 0.598536E+09 | 0.254509E+09 | 0.344027E+09 | 0.665257E+09 | 0.139209E+09 |
September | 0.348505E+09 | 0.145298E+09 | 0.203206E+09 | 0.297413E+09 | 0.287637E+09 |
October | 0.141175E+09 | 42266213.40 | 98908372.99 | 52330327.89 | 0.595828E+09 |
November | 55219401.28 | 20239990.41 | 34979410.87 | 5613811.51 | 0.101474E+10 |
December | 5057197.14 | 512230.40 | 4544966.74 | 0.00 | 0.116653E+10 |
Annual Sum or Average | 0.476577E+10 | 0.205649E+10 | 0.270928E+10 | 0.469112E+10 | 0.654924E+10 |
Minimum of Months | 5057197.14 | 512230.40 | 4544966.74 | 0.00 | 75763190.00 |
Maximum of Months | 0.840418E+09 | 0.410659E+09 | 0.481579E+09 | 0.980068E+09 | 0.116653E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7485397.50 | 0.00 | 7485397.50 | 0.00 | 0.595382E+09 |
February | 29886918.80 | 0.00 | 29886918.80 | 0.00 | 0.479074E+09 |
March | 88635339.19 | 15040.35 | 88620298.84 | 8135622.54 | 0.393716E+09 |
April | 0.156626E+09 | 4468630.01 | 0.152157E+09 | 65706360.06 | 0.200790E+09 |
May | 0.247451E+09 | 39662063.78 | 0.207788E+09 | 0.203190E+09 | 81182481.19 |
June | 0.310041E+09 | 68787424.57 | 0.241253E+09 | 0.321104E+09 | 32482509.71 |
July | 0.270880E+09 | 45269352.45 | 0.225611E+09 | 0.291796E+09 | 40074517.83 |
August | 0.174589E+09 | 10464841.60 | 0.164124E+09 | 0.154627E+09 | 72652353.90 |
September | 93150850.77 | 302442.08 | 92848408.69 | 40685892.30 | 0.157710E+09 |
October | 46581866.67 | 0.00 | 46581866.67 | 3994309.61 | 0.331434E+09 |
November | 13989674.44 | 0.00 | 13989674.44 | 0.00 | 0.560771E+09 |
December | 2270676.37 | 0.00 | 2270676.37 | 0.00 | 0.623503E+09 |
Annual Sum or Average | 0.144159E+10 | 0.168970E+09 | 0.127262E+10 | 0.108924E+10 | 0.356877E+10 |
Minimum of Months | 2270676.37 | 0.00 | 2270676.37 | 0.00 | 32482509.71 |
Maximum of Months | 0.310041E+09 | 68787424.57 | 0.241253E+09 | 0.321104E+09 | 0.623503E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 19232962.10 | 3269712.17 | 15963249.93 | 0.00 | 0.110625E+10 |
February | 0.103533E+09 | 36059635.70 | 67473741.62 | 21819236.64 | 0.850667E+09 |
March | 0.344892E+09 | 0.148950E+09 | 0.195941E+09 | 0.206195E+09 | 0.678177E+09 |
April | 0.790929E+09 | 0.410659E+09 | 0.380270E+09 | 0.787793E+09 | 0.364153E+09 |
May | 0.792860E+09 | 0.361774E+09 | 0.431086E+09 | 0.840197E+09 | 0.172596E+09 |
June | 0.840418E+09 | 0.358839E+09 | 0.481579E+09 | 0.965869E+09 | 77221590.29 |
July | 0.725411E+09 | 0.274115E+09 | 0.451296E+09 | 0.849918E+09 | 86232436.18 |
August | 0.598536E+09 | 0.254509E+09 | 0.344027E+09 | 0.663761E+09 | 0.142439E+09 |
September | 0.348505E+09 | 0.145298E+09 | 0.203206E+09 | 0.305223E+09 | 0.283703E+09 |
October | 0.141175E+09 | 42266213.40 | 98908372.99 | 55758432.53 | 0.592090E+09 |
November | 55219401.28 | 20239990.41 | 34979410.87 | 5895841.25 | 0.101419E+10 |
December | 5057197.14 | 512230.40 | 4544966.74 | 0.00 | 0.116631E+10 |
Annual Sum or Average | 0.476577E+10 | 0.205649E+10 | 0.270928E+10 | 0.470243E+10 | 0.653402E+10 |
Minimum of Months | 5057197.14 | 512230.40 | 4544966.74 | 0.00 | 77221590.29 |
Maximum of Months | 0.840418E+09 | 0.410659E+09 | 0.481579E+09 | 0.965869E+09 | 0.116631E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 74766633.98 | 49779147.74 | 24987486.24 | 47747523.40 | 0.379756E+09 |
February | 0.225615E+09 | 0.156664E+09 | 68951034.08 | 0.203225E+09 | 0.275196E+09 |
March | 0.422863E+09 | 0.286097E+09 | 0.136766E+09 | 0.425589E+09 | 0.262023E+09 |
April | 0.501413E+09 | 0.312051E+09 | 0.189362E+09 | 0.541751E+09 | 0.201817E+09 |
May | 0.427769E+09 | 0.222039E+09 | 0.205730E+09 | 0.473397E+09 | 0.116002E+09 |
June | 0.376120E+09 | 0.153493E+09 | 0.222627E+09 | 0.427008E+09 | 60516053.44 |
July | 0.373888E+09 | 0.161869E+09 | 0.212019E+09 | 0.436808E+09 | 64995240.45 |
August | 0.389546E+09 | 0.214937E+09 | 0.174609E+09 | 0.449019E+09 | 96399448.82 |
September | 0.300948E+09 | 0.179899E+09 | 0.121048E+09 | 0.309980E+09 | 0.161753E+09 |
October | 0.230302E+09 | 0.146106E+09 | 84196004.15 | 0.206563E+09 | 0.238438E+09 |
November | 0.120868E+09 | 85190798.59 | 35676889.28 | 86965820.71 | 0.339965E+09 |
December | 22088494.24 | 15570696.90 | 6517797.34 | 4781178.45 | 0.424016E+09 |
Annual Sum or Average | 0.346619E+10 | 0.198370E+10 | 0.148249E+10 | 0.361284E+10 | 0.262088E+10 |
Minimum of Months | 22088494.24 | 15570696.90 | 6517797.34 | 4781178.45 | 60516053.44 |
Maximum of Months | 0.501413E+09 | 0.312051E+09 | 0.222627E+09 | 0.541751E+09 | 0.424016E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 5989111.78 | 0.00 | 5989111.78 | 0.00 | 0.487170E+09 |
February | 23912704.39 | 0.00 | 23912704.39 | 0.00 | 0.393152E+09 |
March | 70917670.65 | 12033.88 | 70905636.77 | 5595453.47 | 0.323321E+09 |
April | 0.125317E+09 | 3575377.89 | 0.121742E+09 | 54308737.50 | 0.160851E+09 |
May | 0.197987E+09 | 31733856.97 | 0.166253E+09 | 0.170152E+09 | 63442162.58 |
June | 0.248066E+09 | 55037234.19 | 0.193028E+09 | 0.268736E+09 | 24389931.96 |
July | 0.216733E+09 | 36220282.52 | 0.180513E+09 | 0.242408E+09 | 30369191.96 |
August | 0.139690E+09 | 8372983.02 | 0.131317E+09 | 0.130005E+09 | 55729906.41 |
September | 74530558.75 | 241985.74 | 74288573.01 | 32158376.38 | 0.128640E+09 |
October | 37270433.09 | 0.00 | 37270433.09 | 2604877.21 | 0.275091E+09 |
November | 11193223.08 | 0.00 | 11193223.08 | 0.00 | 0.459478E+09 |
December | 1816781.89 | 0.00 | 1816781.89 | 0.00 | 0.509602E+09 |
Annual Sum or Average | 0.115342E+10 | 0.135194E+09 | 0.101823E+10 | 0.905967E+09 | 0.291124E+10 |
Minimum of Months | 1816781.89 | 0.00 | 1816781.89 | 0.00 | 24389931.96 |
Maximum of Months | 0.248066E+09 | 55037234.19 | 0.193028E+09 | 0.268736E+09 | 0.509602E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41391987.23 | 15330505.74 | 26061481.50 | 5321119.16 | 0.108093E+10 |
February | 0.193920E+09 | 92969590.80 | 0.100950E+09 | 0.102072E+09 | 0.810085E+09 |
March | 0.602190E+09 | 0.304922E+09 | 0.297268E+09 | 0.518843E+09 | 0.666652E+09 |
April | 0.775293E+09 | 0.392733E+09 | 0.382560E+09 | 0.729313E+09 | 0.346179E+09 |
May | 0.116673E+10 | 0.658628E+09 | 0.508102E+09 | 0.132693E+10 | 0.161979E+09 |
June | 0.103397E+10 | 0.482910E+09 | 0.551065E+09 | 0.123309E+10 | 65322056.73 |
July | 0.101765E+10 | 0.494870E+09 | 0.522778E+09 | 0.124674E+10 | 76280835.16 |
August | 0.817688E+09 | 0.400734E+09 | 0.416954E+09 | 0.952060E+09 | 0.131816E+09 |
September | 0.495284E+09 | 0.224047E+09 | 0.271237E+09 | 0.481833E+09 | 0.279011E+09 |
October | 0.277184E+09 | 0.112303E+09 | 0.164881E+09 | 0.204956E+09 | 0.568384E+09 |
November | 55596086.02 | 20188305.78 | 35407780.24 | 4104381.26 | 0.101181E+10 |
December | 8178712.01 | 1936245.93 | 6242466.08 | 0.00 | 0.116124E+10 |
Annual Sum or Average | 0.648508E+10 | 0.320157E+10 | 0.328351E+10 | 0.680527E+10 | 0.635969E+10 |
Minimum of Months | 8178712.01 | 1936245.93 | 6242466.08 | 0.00 | 65322056.73 |
Maximum of Months | 0.116673E+10 | 0.658628E+09 | 0.551065E+09 | 0.132693E+10 | 0.116124E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93476878.82 | 62236309.34 | 31240569.48 | 55392809.31 | 0.536876E+09 |
February | 0.282075E+09 | 0.195869E+09 | 86205933.23 | 0.243890E+09 | 0.388721E+09 |
March | 0.528684E+09 | 0.357692E+09 | 0.170991E+09 | 0.530031E+09 | 0.332014E+09 |
April | 0.626891E+09 | 0.390141E+09 | 0.236750E+09 | 0.704294E+09 | 0.202508E+09 |
May | 0.534817E+09 | 0.277604E+09 | 0.257213E+09 | 0.620773E+09 | 99935122.88 |
June | 0.470243E+09 | 0.191904E+09 | 0.278339E+09 | 0.569618E+09 | 41783537.90 |
July | 0.467453E+09 | 0.202377E+09 | 0.265076E+09 | 0.581633E+09 | 46209908.01 |
August | 0.487029E+09 | 0.268725E+09 | 0.218305E+09 | 0.591953E+09 | 77247293.33 |
September | 0.376259E+09 | 0.224919E+09 | 0.151341E+09 | 0.412471E+09 | 0.151031E+09 |
October | 0.287934E+09 | 0.182668E+09 | 0.105266E+09 | 0.268494E+09 | 0.279551E+09 |
November | 0.151115E+09 | 0.106510E+09 | 44604980.56 | 0.101811E+09 | 0.481245E+09 |
December | 27616108.81 | 19467241.87 | 8148866.95 | 5061752.74 | 0.595918E+09 |
Annual Sum or Average | 0.433359E+10 | 0.248011E+10 | 0.185348E+10 | 0.468542E+10 | 0.323304E+10 |
Minimum of Months | 27616108.81 | 19467241.87 | 8148866.95 | 5061752.74 | 41783537.90 |
Maximum of Months | 0.626891E+09 | 0.390141E+09 | 0.278339E+09 | 0.704294E+09 | 0.595918E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7485397.50 | 0.00 | 7485397.50 | 0.00 | 0.594733E+09 |
February | 29886918.80 | 0.00 | 29886918.80 | 0.00 | 0.478420E+09 |
March | 88635339.19 | 15040.35 | 88620298.84 | 6844528.81 | 0.397182E+09 |
April | 0.156626E+09 | 4468630.01 | 0.152157E+09 | 62254684.12 | 0.200721E+09 |
May | 0.247451E+09 | 39662063.78 | 0.207788E+09 | 0.197461E+09 | 80753975.33 |
June | 0.310041E+09 | 68787424.57 | 0.241253E+09 | 0.321391E+09 | 31746027.10 |
July | 0.270880E+09 | 45269352.45 | 0.225611E+09 | 0.287626E+09 | 39688382.49 |
August | 0.174589E+09 | 10464841.60 | 0.164124E+09 | 0.151599E+09 | 72027478.75 |
September | 93150850.77 | 302442.08 | 92848408.69 | 37419807.25 | 0.159604E+09 |
October | 46581866.67 | 0.00 | 46581866.67 | 3302909.36 | 0.332848E+09 |
November | 13989674.44 | 0.00 | 13989674.44 | 0.00 | 0.560818E+09 |
December | 2270676.37 | 0.00 | 2270676.37 | 0.00 | 0.623373E+09 |
Annual Sum or Average | 0.144159E+10 | 0.168970E+09 | 0.127262E+10 | 0.106790E+10 | 0.357191E+10 |
Minimum of Months | 2270676.37 | 0.00 | 2270676.37 | 0.00 | 31746027.10 |
Maximum of Months | 0.310041E+09 | 68787424.57 | 0.241253E+09 | 0.321391E+09 | 0.623373E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41391987.23 | 15330505.74 | 26061481.50 | 5439810.98 | 0.107940E+10 |
February | 0.193920E+09 | 92969590.80 | 0.100950E+09 | 0.103552E+09 | 0.806175E+09 |
March | 0.602190E+09 | 0.304922E+09 | 0.297268E+09 | 0.525276E+09 | 0.655422E+09 |
April | 0.775293E+09 | 0.392733E+09 | 0.382560E+09 | 0.741118E+09 | 0.339432E+09 |
May | 0.116673E+10 | 0.658628E+09 | 0.508102E+09 | 0.133041E+10 | 0.162608E+09 |
June | 0.103397E+10 | 0.482910E+09 | 0.551065E+09 | 0.122707E+10 | 69310804.08 |
July | 0.101765E+10 | 0.494870E+09 | 0.522778E+09 | 0.123877E+10 | 80705427.89 |
August | 0.817688E+09 | 0.400734E+09 | 0.416954E+09 | 0.953398E+09 | 0.134971E+09 |
September | 0.495284E+09 | 0.224047E+09 | 0.271237E+09 | 0.487689E+09 | 0.274504E+09 |
October | 0.277184E+09 | 0.112303E+09 | 0.164881E+09 | 0.208240E+09 | 0.562579E+09 |
November | 55596086.02 | 20188305.78 | 35407780.24 | 4229581.13 | 0.101108E+10 |
December | 8178712.01 | 1936245.93 | 6242466.08 | 0.00 | 0.116068E+10 |
Annual Sum or Average | 0.648508E+10 | 0.320157E+10 | 0.328351E+10 | 0.682519E+10 | 0.633687E+10 |
Minimum of Months | 8178712.01 | 1936245.93 | 6242466.08 | 0.00 | 69310804.08 |
Maximum of Months | 0.116673E+10 | 0.658628E+09 | 0.551065E+09 | 0.133041E+10 | 0.116068E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 9479783.63 | 0.00 | 9479783.63 | 0.00 | 0.789777E+09 |
February | 37849896.91 | 0.00 | 37849896.91 | 0.00 | 0.638959E+09 |
March | 0.112251E+09 | 19047.66 | 0.112232E+09 | 7803494.40 | 0.526530E+09 |
April | 0.198357E+09 | 5659237.96 | 0.192698E+09 | 80171882.60 | 0.264658E+09 |
May | 0.313380E+09 | 50229501.24 | 0.263151E+09 | 0.257910E+09 | 0.109886E+09 |
June | 0.392647E+09 | 87114932.98 | 0.305532E+09 | 0.410958E+09 | 45906023.94 |
July | 0.343053E+09 | 57330778.54 | 0.285722E+09 | 0.370458E+09 | 56716084.96 |
August | 0.221106E+09 | 13253061.60 | 0.207853E+09 | 0.195275E+09 | 99432123.32 |
September | 0.117970E+09 | 383023.81 | 0.117587E+09 | 48135575.03 | 0.212196E+09 |
October | 58992994.98 | 0.00 | 58992994.98 | 3865061.12 | 0.445982E+09 |
November | 17717039.98 | 0.00 | 17717039.98 | 0.00 | 0.745447E+09 |
December | 2875668.35 | 0.00 | 2875668.35 | 0.00 | 0.825837E+09 |
Annual Sum or Average | 0.182568E+10 | 0.213990E+09 | 0.161169E+10 | 0.137458E+10 | 0.476132E+10 |
Minimum of Months | 2875668.35 | 0.00 | 2875668.35 | 0.00 | 45906023.94 |
Maximum of Months | 0.392647E+09 | 87114932.98 | 0.305532E+09 | 0.410958E+09 | 0.825837E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 3494640.77 | 0.00 | 3494640.77 | 0.00 | 0.291115E+09 |
February | 13953039.24 | 0.00 | 13953039.24 | 0.00 | 0.235547E+09 |
March | 41380390.33 | 7021.76 | 41373368.57 | 2876691.15 | 0.194101E+09 |
April | 73122547.54 | 2086229.44 | 71036318.10 | 29554675.58 | 97564034.44 |
May | 0.115525E+09 | 18516674.00 | 97008340.02 | 95076230.51 | 40508417.05 |
June | 0.144746E+09 | 32114171.44 | 0.112632E+09 | 0.151496E+09 | 16922861.24 |
July | 0.126463E+09 | 21134498.85 | 0.105329E+09 | 0.136566E+09 | 20907897.34 |
August | 81508690.92 | 4885627.27 | 76623063.65 | 71986621.70 | 36654797.82 |
September | 43488506.95 | 141198.44 | 43347308.51 | 17744766.09 | 78224051.33 |
October | 21747260.66 | 0.00 | 21747260.66 | 1424821.57 | 0.164408E+09 |
November | 6531234.54 | 0.00 | 6531234.54 | 0.00 | 0.274783E+09 |
December | 1060090.42 | 0.00 | 1060090.42 | 0.00 | 0.304348E+09 |
Annual Sum or Average | 0.673021E+09 | 78885421.19 | 0.594136E+09 | 0.506726E+09 | 0.175508E+10 |
Minimum of Months | 1060090.42 | 0.00 | 1060090.42 | 0.00 | 16922861.24 |
Maximum of Months | 0.144746E+09 | 32114171.44 | 0.112632E+09 | 0.151496E+09 | 0.304348E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43615934.97 | 29039211.14 | 14576723.83 | 24833587.50 | 0.261959E+09 |
February | 0.131615E+09 | 91391623.88 | 40223341.06 | 0.112092E+09 | 0.188629E+09 |
March | 0.246682E+09 | 0.166898E+09 | 79783921.36 | 0.248661E+09 | 0.159070E+09 |
April | 0.292505E+09 | 0.182038E+09 | 0.110467E+09 | 0.332584E+09 | 97094594.37 |
May | 0.249544E+09 | 0.129529E+09 | 0.120015E+09 | 0.293389E+09 | 51159562.90 |
June | 0.219413E+09 | 89541663.22 | 0.129872E+09 | 0.265948E+09 | 24676204.40 |
July | 0.218112E+09 | 94428198.97 | 0.123684E+09 | 0.271845E+09 | 26500907.62 |
August | 0.227246E+09 | 0.125386E+09 | 0.101860E+09 | 0.278041E+09 | 40670111.97 |
September | 0.175561E+09 | 0.104946E+09 | 70614949.65 | 0.194720E+09 | 73074226.44 |
October | 0.134349E+09 | 85232282.71 | 49116661.35 | 0.124880E+09 | 0.135486E+09 |
November | 70509489.77 | 49696985.59 | 20812504.18 | 45631230.40 | 0.234297E+09 |
December | 12885565.09 | 9083336.61 | 3802228.48 | 2116323.37 | 0.291036E+09 |
Annual Sum or Average | 0.202204E+10 | 0.115721E+10 | 0.864827E+09 | 0.219474E+10 | 0.158365E+10 |
Minimum of Months | 12885565.09 | 9083336.61 | 3802228.48 | 2116323.37 | 24676204.40 |
Maximum of Months | 0.292505E+09 | 0.182038E+09 | 0.129872E+09 | 0.332584E+09 | 0.291036E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118383E+09 | 78818358.88 | 39564210.07 | 67403436.06 | 0.711009E+09 |
February | 0.357230E+09 | 0.248056E+09 | 0.109174E+09 | 0.304242E+09 | 0.511978E+09 |
March | 0.669545E+09 | 0.452995E+09 | 0.216550E+09 | 0.674917E+09 | 0.431750E+09 |
April | 0.793918E+09 | 0.494089E+09 | 0.299829E+09 | 0.902701E+09 | 0.263534E+09 |
May | 0.677312E+09 | 0.351568E+09 | 0.325744E+09 | 0.796319E+09 | 0.138858E+09 |
June | 0.595533E+09 | 0.243034E+09 | 0.352499E+09 | 0.721838E+09 | 66976266.15 |
July | 0.592000E+09 | 0.256297E+09 | 0.335703E+09 | 0.737842E+09 | 71928883.92 |
August | 0.616792E+09 | 0.340323E+09 | 0.276469E+09 | 0.754659E+09 | 0.110387E+09 |
September | 0.476509E+09 | 0.284845E+09 | 0.191663E+09 | 0.528510E+09 | 0.198338E+09 |
October | 0.364651E+09 | 0.231338E+09 | 0.133313E+09 | 0.338950E+09 | 0.367736E+09 |
November | 0.191377E+09 | 0.134888E+09 | 56489393.46 | 0.123852E+09 | 0.635929E+09 |
December | 34974059.33 | 24654033.51 | 10320025.82 | 5744134.52 | 0.789932E+09 |
Annual Sum or Average | 0.548822E+10 | 0.314091E+10 | 0.234732E+10 | 0.595698E+10 | 0.429836E+10 |
Minimum of Months | 34974059.33 | 24654033.51 | 10320025.82 | 5744134.52 | 66976266.15 |
Maximum of Months | 0.793918E+09 | 0.494089E+09 | 0.352499E+09 | 0.902701E+09 | 0.789932E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93476878.82 | 62236309.34 | 31240569.48 | 55840822.26 | 0.533244E+09 |
February | 0.282075E+09 | 0.195869E+09 | 86205933.23 | 0.245999E+09 | 0.385815E+09 |
March | 0.528684E+09 | 0.357692E+09 | 0.170991E+09 | 0.536808E+09 | 0.329011E+09 |
April | 0.626891E+09 | 0.390141E+09 | 0.236750E+09 | 0.705961E+09 | 0.202663E+09 |
May | 0.534817E+09 | 0.277604E+09 | 0.257213E+09 | 0.623733E+09 | 0.100215E+09 |
June | 0.470243E+09 | 0.191904E+09 | 0.278339E+09 | 0.569708E+09 | 43275611.27 |
July | 0.467453E+09 | 0.202377E+09 | 0.265076E+09 | 0.582991E+09 | 46599677.15 |
August | 0.487029E+09 | 0.268725E+09 | 0.218305E+09 | 0.593596E+09 | 76393024.06 |
September | 0.376259E+09 | 0.224919E+09 | 0.151341E+09 | 0.416288E+09 | 0.148568E+09 |
October | 0.287934E+09 | 0.182668E+09 | 0.105266E+09 | 0.272031E+09 | 0.276722E+09 |
November | 0.151115E+09 | 0.106510E+09 | 44604980.56 | 0.102731E+09 | 0.476914E+09 |
December | 27616108.81 | 19467241.87 | 8148866.95 | 5148771.83 | 0.592235E+09 |
Annual Sum or Average | 0.433359E+10 | 0.248011E+10 | 0.185348E+10 | 0.471083E+10 | 0.321166E+10 |
Minimum of Months | 27616108.81 | 19467241.87 | 8148866.95 | 5148771.83 | 43275611.27 |
Maximum of Months | 0.626891E+09 | 0.390141E+09 | 0.278339E+09 | 0.705961E+09 | 0.592235E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 19232962.10 | 3269712.17 | 15963249.93 | 0.00 | 0.109919E+10 |
February | 0.103533E+09 | 36059635.70 | 67473741.62 | 21089159.44 | 0.846229E+09 |
March | 0.344892E+09 | 0.148950E+09 | 0.195941E+09 | 0.199549E+09 | 0.680460E+09 |
April | 0.790929E+09 | 0.410659E+09 | 0.380270E+09 | 0.769803E+09 | 0.367218E+09 |
May | 0.792860E+09 | 0.361774E+09 | 0.431086E+09 | 0.836020E+09 | 0.171547E+09 |
June | 0.840418E+09 | 0.358839E+09 | 0.481579E+09 | 0.976239E+09 | 74505074.84 |
July | 0.725411E+09 | 0.274115E+09 | 0.451296E+09 | 0.856093E+09 | 82282135.88 |
August | 0.598536E+09 | 0.254509E+09 | 0.344027E+09 | 0.663146E+09 | 0.137161E+09 |
September | 0.348505E+09 | 0.145298E+09 | 0.203206E+09 | 0.298087E+09 | 0.283833E+09 |
October | 0.141175E+09 | 42266213.40 | 98908372.99 | 53284599.65 | 0.591401E+09 |
November | 55219401.28 | 20239990.41 | 34979410.87 | 5804267.94 | 0.100502E+10 |
December | 5057197.14 | 512230.40 | 4544966.74 | 0.00 | 0.115934E+10 |
Annual Sum or Average | 0.476577E+10 | 0.205649E+10 | 0.270928E+10 | 0.467912E+10 | 0.649819E+10 |
Minimum of Months | 5057197.14 | 512230.40 | 4544966.74 | 0.00 | 74505074.84 |
Maximum of Months | 0.840418E+09 | 0.410659E+09 | 0.481579E+09 | 0.976239E+09 | 0.115934E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7485397.50 | 0.00 | 7485397.50 | 0.00 | 0.591601E+09 |
February | 29886918.80 | 0.00 | 29886918.80 | 0.00 | 0.476090E+09 |
March | 88635339.19 | 15040.35 | 88620298.84 | 8389320.35 | 0.391877E+09 |
April | 0.156626E+09 | 4468630.01 | 0.152157E+09 | 66282387.55 | 0.199887E+09 |
May | 0.247451E+09 | 39662063.78 | 0.207788E+09 | 0.202463E+09 | 80922387.91 |
June | 0.310041E+09 | 68787424.57 | 0.241253E+09 | 0.318401E+09 | 32623002.65 |
July | 0.270880E+09 | 45269352.45 | 0.225611E+09 | 0.289862E+09 | 40151621.43 |
August | 0.174589E+09 | 10464841.60 | 0.164124E+09 | 0.154158E+09 | 72540831.90 |
September | 93150850.77 | 302442.08 | 92848408.69 | 41804877.78 | 0.155327E+09 |
October | 46581866.67 | 0.00 | 46581866.67 | 4364832.43 | 0.329216E+09 |
November | 13989674.44 | 0.00 | 13989674.44 | 0.00 | 0.555716E+09 |
December | 2270676.37 | 0.00 | 2270676.37 | 0.00 | 0.619598E+09 |
Annual Sum or Average | 0.144159E+10 | 0.168970E+09 | 0.127262E+10 | 0.108573E+10 | 0.354555E+10 |
Minimum of Months | 2270676.37 | 0.00 | 2270676.37 | 0.00 | 32623002.65 |
Maximum of Months | 0.310041E+09 | 68787424.57 | 0.241253E+09 | 0.318401E+09 | 0.619598E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 19232962.10 | 3269712.17 | 15963249.93 | 0.00 | 0.109870E+10 |
February | 0.103533E+09 | 36059635.70 | 67473741.62 | 22100833.55 | 0.844967E+09 |
March | 0.344892E+09 | 0.148950E+09 | 0.195941E+09 | 0.206660E+09 | 0.675025E+09 |
April | 0.790929E+09 | 0.410659E+09 | 0.380270E+09 | 0.786334E+09 | 0.362011E+09 |
May | 0.792860E+09 | 0.361774E+09 | 0.431086E+09 | 0.836815E+09 | 0.171305E+09 |
June | 0.840418E+09 | 0.358839E+09 | 0.481579E+09 | 0.959180E+09 | 77228363.12 |
July | 0.725411E+09 | 0.274115E+09 | 0.451296E+09 | 0.844789E+09 | 85984559.34 |
August | 0.598536E+09 | 0.254509E+09 | 0.344027E+09 | 0.660799E+09 | 0.141564E+09 |
September | 0.348505E+09 | 0.145298E+09 | 0.203206E+09 | 0.306977E+09 | 0.279490E+09 |
October | 0.141175E+09 | 42266213.40 | 98908372.99 | 56766107.00 | 0.588115E+09 |
November | 55219401.28 | 20239990.41 | 34979410.87 | 6095626.12 | 0.100441E+10 |
December | 5057197.14 | 512230.40 | 4544966.74 | 0.00 | 0.115881E+10 |
Annual Sum or Average | 0.476577E+10 | 0.205649E+10 | 0.270928E+10 | 0.468652E+10 | 0.648761E+10 |
Minimum of Months | 5057197.14 | 512230.40 | 4544966.74 | 0.00 | 77228363.12 |
Maximum of Months | 0.840418E+09 | 0.410659E+09 | 0.481579E+09 | 0.959180E+09 | 0.115881E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137093E+09 | 91275520.48 | 45817293.31 | 79520464.71 | 0.794045E+09 |
February | 0.413690E+09 | 0.287260E+09 | 0.126429E+09 | 0.349949E+09 | 0.577766E+09 |
March | 0.775365E+09 | 0.524590E+09 | 0.250775E+09 | 0.767553E+09 | 0.495324E+09 |
April | 0.919396E+09 | 0.572179E+09 | 0.347217E+09 | 0.102402E+10 | 0.301408E+09 |
May | 0.784361E+09 | 0.407133E+09 | 0.377228E+09 | 0.911283E+09 | 0.147050E+09 |
June | 0.689656E+09 | 0.281446E+09 | 0.408211E+09 | 0.837290E+09 | 62327972.47 |
July | 0.685565E+09 | 0.296805E+09 | 0.388760E+09 | 0.855320E+09 | 67617451.01 |
August | 0.714275E+09 | 0.394111E+09 | 0.320165E+09 | 0.867204E+09 | 0.112285E+09 |
September | 0.551821E+09 | 0.329865E+09 | 0.221956E+09 | 0.600606E+09 | 0.224023E+09 |
October | 0.422283E+09 | 0.267901E+09 | 0.154383E+09 | 0.386396E+09 | 0.417358E+09 |
November | 0.221624E+09 | 0.156207E+09 | 65417484.74 | 0.146134E+09 | 0.709999E+09 |
December | 40501673.90 | 28550578.47 | 11951095.42 | 7227570.70 | 0.879928E+09 |
Annual Sum or Average | 0.635563E+10 | 0.363732E+10 | 0.271831E+10 | 0.683251E+10 | 0.478913E+10 |
Minimum of Months | 40501673.90 | 28550578.47 | 11951095.42 | 7227570.70 | 62327972.47 |
Maximum of Months | 0.919396E+09 | 0.572179E+09 | 0.408211E+09 | 0.102402E+10 | 0.879928E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52395798.00 | 0.00 | 52395798.00 | 0.00 | 0.426393E+10 |
February | 0.209201E+09 | 0.00 | 0.209201E+09 | 0.00 | 0.344426E+10 |
March | 0.620424E+09 | 105278.48 | 0.620319E+09 | 45419103.36 | 0.285317E+10 |
April | 0.109634E+10 | 31279225.42 | 0.106506E+10 | 0.463676E+09 | 0.144606E+10 |
May | 0.173209E+10 | 0.277624E+09 | 0.145446E+10 | 0.147142E+10 | 0.589404E+09 |
June | 0.217020E+10 | 0.481494E+09 | 0.168871E+10 | 0.235094E+10 | 0.235799E+09 |
July | 0.189609E+10 | 0.316873E+09 | 0.157922E+10 | 0.212932E+10 | 0.289274E+09 |
August | 0.122207E+10 | 73251116.88 | 0.114882E+10 | 0.113750E+10 | 0.517812E+09 |
September | 0.652031E+09 | 2117014.40 | 0.649914E+09 | 0.276741E+09 | 0.115993E+10 |
October | 0.326061E+09 | 0.00 | 0.326061E+09 | 21586760.77 | 0.244263E+10 |
November | 97924012.29 | 0.00 | 97924012.29 | 0.00 | 0.400274E+10 |
December | 15894132.59 | 0.00 | 15894132.59 | 0.00 | 0.444745E+10 |
Annual Sum or Average | 0.100907E+11 | 0.118274E+10 | 0.890798E+10 | 0.789661E+10 | 0.256925E+11 |
Minimum of Months | 15894132.59 | 0.00 | 15894132.59 | 0.00 | 0.235799E+09 |
Maximum of Months | 0.217020E+10 | 0.481494E+09 | 0.168871E+10 | 0.235094E+10 | 0.444745E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52395798.00 | 0.00 | 52395798.00 | 0.00 | 0.432257E+10 |
February | 0.209201E+09 | 0.00 | 0.209201E+09 | 0.00 | 0.349573E+10 |
March | 0.620424E+09 | 105278.48 | 0.620319E+09 | 41401029.33 | 0.291251E+10 |
April | 0.109634E+10 | 31279225.42 | 0.106506E+10 | 0.443006E+09 | 0.148821E+10 |
May | 0.173209E+10 | 0.277624E+09 | 0.145446E+10 | 0.143610E+10 | 0.606724E+09 |
June | 0.217020E+10 | 0.481494E+09 | 0.168871E+10 | 0.231510E+10 | 0.245483E+09 |
July | 0.189609E+10 | 0.316873E+09 | 0.157922E+10 | 0.209470E+10 | 0.301303E+09 |
August | 0.122207E+10 | 73251116.88 | 0.114882E+10 | 0.110883E+10 | 0.537154E+09 |
September | 0.652031E+09 | 2117014.40 | 0.649914E+09 | 0.260650E+09 | 0.120656E+10 |
October | 0.326061E+09 | 0.00 | 0.326061E+09 | 18107006.94 | 0.250905E+10 |
November | 97924012.29 | 0.00 | 97924012.29 | 0.00 | 0.405661E+10 |
December | 15894132.59 | 0.00 | 15894132.59 | 0.00 | 0.450179E+10 |
Annual Sum or Average | 0.100907E+11 | 0.118274E+10 | 0.890798E+10 | 0.771790E+10 | 0.261837E+11 |
Minimum of Months | 15894132.59 | 0.00 | 15894132.59 | 0.00 | 0.245483E+09 |
Maximum of Months | 0.217020E+10 | 0.481494E+09 | 0.168871E+10 | 0.231510E+10 | 0.450179E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7485397.50 | 0.00 | 7485397.50 | 0.00 | 0.522023E+09 |
February | 29886918.80 | 0.00 | 29886918.80 | 25057.12 | 0.412740E+09 |
March | 88635339.19 | 15040.35 | 88620298.84 | 21730326.06 | 0.339225E+09 |
April | 0.156626E+09 | 4468630.01 | 0.152157E+09 | 0.125206E+09 | 0.181187E+09 |
May | 0.247451E+09 | 39662063.78 | 0.207788E+09 | 0.303394E+09 | 79610118.31 |
June | 0.310041E+09 | 68787424.57 | 0.241253E+09 | 0.441069E+09 | 33562839.60 |
July | 0.270880E+09 | 45269352.45 | 0.225611E+09 | 0.411702E+09 | 39912117.72 |
August | 0.174589E+09 | 10464841.60 | 0.164124E+09 | 0.259130E+09 | 65714152.52 |
September | 93150850.77 | 302442.08 | 92848408.69 | 94751647.14 | 0.127658E+09 |
October | 46581866.67 | 0.00 | 46581866.67 | 15319707.01 | 0.273471E+09 |
November | 13989674.44 | 0.00 | 13989674.44 | 0.00 | 0.485583E+09 |
December | 2270676.37 | 0.00 | 2270676.37 | 0.00 | 0.548084E+09 |
Annual Sum or Average | 0.144159E+10 | 0.168970E+09 | 0.127262E+10 | 0.167233E+10 | 0.310877E+10 |
Minimum of Months | 2270676.37 | 0.00 | 2270676.37 | 0.00 | 33562839.60 |
Maximum of Months | 0.310041E+09 | 68787424.57 | 0.241253E+09 | 0.441069E+09 | 0.548084E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82778095.76 | 30658834.16 | 52119261.60 | 19061291.42 | 0.189743E+10 |
February | 0.387812E+09 | 0.185926E+09 | 0.201886E+09 | 0.257808E+09 | 0.141469E+10 |
March | 0.120429E+10 | 0.609801E+09 | 0.594493E+09 | 0.118956E+10 | 0.116658E+10 |
April | 0.155048E+10 | 0.785409E+09 | 0.765066E+09 | 0.176038E+10 | 0.638902E+09 |
May | 0.233329E+10 | 0.131716E+10 | 0.101613E+10 | 0.304763E+10 | 0.306703E+09 |
June | 0.206780E+10 | 0.965751E+09 | 0.110205E+10 | 0.288981E+10 | 0.133104E+09 |
July | 0.203515E+10 | 0.989670E+09 | 0.104548E+10 | 0.293411E+10 | 0.153627E+09 |
August | 0.163526E+10 | 0.801412E+09 | 0.833849E+09 | 0.231331E+10 | 0.246011E+09 |
September | 0.990497E+09 | 0.448062E+09 | 0.542436E+09 | 0.123415E+10 | 0.467165E+09 |
October | 0.554329E+09 | 0.224591E+09 | 0.329739E+09 | 0.523959E+09 | 0.959987E+09 |
November | 0.111184E+09 | 40373744.31 | 70810531.68 | 17325857.55 | 0.175003E+10 |
December | 16356262.43 | 3872216.86 | 12484045.58 | 0.00 | 0.204363E+10 |
Annual Sum or Average | 0.129692E+11 | 0.640269E+10 | 0.656655E+10 | 0.161871E+11 | 0.111778E+11 |
Minimum of Months | 16356262.43 | 3872216.86 | 12484045.58 | 0.00 | 0.133104E+09 |
Maximum of Months | 0.233329E+10 | 0.131716E+10 | 0.110205E+10 | 0.304763E+10 | 0.204363E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93476878.82 | 62236309.34 | 31240569.48 | 66382000.20 | 0.473714E+09 |
February | 0.282075E+09 | 0.195869E+09 | 86205933.23 | 0.272234E+09 | 0.345696E+09 |
March | 0.528684E+09 | 0.357692E+09 | 0.170991E+09 | 0.586859E+09 | 0.300864E+09 |
April | 0.626891E+09 | 0.390141E+09 | 0.236750E+09 | 0.783967E+09 | 0.184004E+09 |
May | 0.534817E+09 | 0.277604E+09 | 0.257213E+09 | 0.724105E+09 | 93025136.86 |
June | 0.470243E+09 | 0.191904E+09 | 0.278339E+09 | 0.683254E+09 | 44263990.70 |
July | 0.467453E+09 | 0.202377E+09 | 0.265076E+09 | 0.699362E+09 | 47240875.18 |
August | 0.487029E+09 | 0.268725E+09 | 0.218305E+09 | 0.697667E+09 | 69251695.19 |
September | 0.376259E+09 | 0.224919E+09 | 0.151341E+09 | 0.486189E+09 | 0.126513E+09 |
October | 0.287934E+09 | 0.182668E+09 | 0.105266E+09 | 0.312023E+09 | 0.243219E+09 |
November | 0.151115E+09 | 0.106510E+09 | 44604980.56 | 0.119723E+09 | 0.422001E+09 |
December | 27616108.81 | 19467241.87 | 8148866.95 | 7882349.61 | 0.523535E+09 |
Annual Sum or Average | 0.433359E+10 | 0.248011E+10 | 0.185348E+10 | 0.543965E+10 | 0.287333E+10 |
Minimum of Months | 27616108.81 | 19467241.87 | 8148866.95 | 7882349.61 | 44263990.70 |
Maximum of Months | 0.626891E+09 | 0.390141E+09 | 0.278339E+09 | 0.783967E+09 | 0.523535E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 9479783.63 | 0.00 | 9479783.63 | 0.00 | 0.787815E+09 |
February | 37849896.91 | 0.00 | 37849896.91 | 0.00 | 0.639034E+09 |
March | 0.112251E+09 | 19047.66 | 0.112232E+09 | 7133449.82 | 0.530681E+09 |
April | 0.198357E+09 | 5659237.96 | 0.192698E+09 | 71643878.44 | 0.273021E+09 |
May | 0.313380E+09 | 50229501.24 | 0.263151E+09 | 0.239277E+09 | 0.118036E+09 |
June | 0.392647E+09 | 87114932.98 | 0.305532E+09 | 0.394122E+09 | 49848154.53 |
July | 0.343053E+09 | 57330778.54 | 0.285722E+09 | 0.354027E+09 | 61846111.28 |
August | 0.221106E+09 | 13253061.60 | 0.207853E+09 | 0.179893E+09 | 0.108797E+09 |
September | 0.117970E+09 | 383023.81 | 0.117587E+09 | 41391320.93 | 0.224739E+09 |
October | 58992994.98 | 0.00 | 58992994.98 | 3144275.64 | 0.451900E+09 |
November | 17717039.98 | 0.00 | 17717039.98 | 0.00 | 0.742241E+09 |
December | 2875668.35 | 0.00 | 2875668.35 | 0.00 | 0.823831E+09 |
Annual Sum or Average | 0.182568E+10 | 0.213990E+09 | 0.161169E+10 | 0.129063E+10 | 0.481179E+10 |
Minimum of Months | 2875668.35 | 0.00 | 2875668.35 | 0.00 | 49848154.53 |
Maximum of Months | 0.392647E+09 | 87114932.98 | 0.305532E+09 | 0.394122E+09 | 0.823831E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 8481598.33 | 0.00 | 8481598.33 | 0.00 | 0.704861E+09 |
February | 33864446.17 | 0.00 | 33864446.17 | 0.00 | 0.571604E+09 |
March | 0.100431E+09 | 17042.01 | 0.100414E+09 | 6382324.58 | 0.474803E+09 |
April | 0.177471E+09 | 5063341.64 | 0.172407E+09 | 64100049.50 | 0.244273E+09 |
May | 0.280383E+09 | 44940525.07 | 0.235442E+09 | 0.214082E+09 | 0.105607E+09 |
June | 0.351303E+09 | 77942060.61 | 0.273361E+09 | 0.352623E+09 | 44599332.73 |
July | 0.306931E+09 | 51294064.78 | 0.255637E+09 | 0.316749E+09 | 55333950.09 |
August | 0.197824E+09 | 11857564.43 | 0.185966E+09 | 0.160951E+09 | 97341434.20 |
September | 0.105548E+09 | 342692.86 | 0.105205E+09 | 37032971.67 | 0.201075E+09 |
October | 52781256.13 | 0.00 | 52781256.13 | 2813195.33 | 0.404239E+09 |
November | 15851502.80 | 0.00 | 15851502.80 | 0.00 | 0.664085E+09 |
December | 2572871.37 | 0.00 | 2572871.37 | 0.00 | 0.737084E+09 |
Annual Sum or Average | 0.163344E+10 | 0.191457E+09 | 0.144198E+10 | 0.115473E+10 | 0.430491E+10 |
Minimum of Months | 2572871.37 | 0.00 | 2572871.37 | 0.00 | 44599332.73 |
Maximum of Months | 0.351303E+09 | 77942060.61 | 0.273361E+09 | 0.352623E+09 | 0.737084E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.348977E+09 | 0.232347E+09 | 0.116630E+09 | 0.198391E+09 | 0.209104E+10 |
February | 0.105307E+10 | 0.731237E+09 | 0.321832E+09 | 0.894347E+09 | 0.150851E+10 |
March | 0.197373E+10 | 0.133537E+10 | 0.638362E+09 | 0.197674E+10 | 0.127871E+10 |
April | 0.234037E+10 | 0.145651E+10 | 0.883858E+09 | 0.262687E+10 | 0.798121E+09 |
May | 0.199663E+10 | 0.103638E+10 | 0.960253E+09 | 0.229647E+10 | 0.441848E+09 |
June | 0.175556E+10 | 0.716435E+09 | 0.103912E+10 | 0.208169E+10 | 0.216504E+09 |
July | 0.174514E+10 | 0.755533E+09 | 0.989609E+09 | 0.212859E+10 | 0.233055E+09 |
August | 0.181823E+10 | 0.100323E+10 | 0.814997E+09 | 0.217894E+10 | 0.357561E+09 |
September | 0.140469E+10 | 0.839689E+09 | 0.565000E+09 | 0.152898E+10 | 0.616521E+09 |
October | 0.107494E+10 | 0.681955E+09 | 0.392989E+09 | 0.989056E+09 | 0.109648E+10 |
November | 0.564156E+09 | 0.397632E+09 | 0.166524E+09 | 0.365467E+09 | 0.186670E+10 |
December | 0.103099E+09 | 72677014.83 | 30422148.55 | 16996515.98 | 0.232414E+10 |
Annual Sum or Average | 0.161786E+11 | 0.925900E+10 | 0.691960E+10 | 0.172825E+11 | 0.128292E+11 |
Minimum of Months | 0.103099E+09 | 72677014.83 | 30422148.55 | 16996515.98 | 0.216504E+09 |
Maximum of Months | 0.234037E+10 | 0.145651E+10 | 0.103912E+10 | 0.262687E+10 | 0.232414E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 102.91 | 1000.41 | 176.52 | 117.52 | 58.99 | 0.00 | 0.00 |
February | 501.59 | 803.78 | 589.72 | 409.50 | 180.23 | 0.00 | 0.00 |
March | 995.01 | 616.98 | 998.33 | 675.44 | 322.89 | 0.00 | 0.00 |
April | 1366.06 | 400.60 | 1223.24 | 761.28 | 461.96 | 0.00 | 0.00 |
May | 1167.56 | 205.82 | 1009.91 | 524.21 | 485.70 | 0.00 | 0.00 |
June | 1094.30 | 104.39 | 917.57 | 374.46 | 543.11 | 0.00 | 0.00 |
July | 1080.85 | 108.87 | 882.71 | 382.16 | 500.55 | 0.00 | 0.00 |
August | 1104.50 | 167.27 | 919.67 | 507.44 | 412.23 | 0.00 | 0.00 |
September | 798.53 | 301.64 | 734.19 | 438.88 | 295.31 | 0.00 | 0.00 |
October | 502.12 | 523.29 | 543.72 | 344.94 | 198.78 | 0.00 | 0.00 |
November | 192.57 | 934.34 | 294.87 | 207.83 | 87.04 | 0.00 | 0.00 |
December | 9.11 | 1113.78 | 52.15 | 36.76 | 15.39 | 0.00 | 0.00 |
Annual Sum or Average | 743.60 | 522.09 | 695.02 | 397.76 | 297.26 | 0.00 | 0.00 |
Minimum of Months | 9.11 | 104.39 | 52.15 | 36.76 | 15.39 | 0.00 | 0.00 |
Maximum of Months | 1366.06 | 1113.78 | 1223.24 | 761.28 | 543.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 287.42 | 2804.84 | 497.06 | 330.94 | 166.12 | 0.00 | 0.00 |
February | 1407.24 | 2249.66 | 1660.62 | 1153.11 | 507.51 | 0.00 | 0.00 |
March | 2798.59 | 1727.56 | 2811.24 | 1902.01 | 909.23 | 0.00 | 0.00 |
April | 3851.83 | 1114.97 | 3444.56 | 2143.70 | 1300.86 | 0.00 | 0.00 |
May | 3312.12 | 553.41 | 2843.85 | 1476.14 | 1367.70 | 0.00 | 0.00 |
June | 3121.81 | 266.43 | 2583.83 | 1054.45 | 1529.37 | 0.00 | 0.00 |
July | 3083.28 | 277.66 | 2485.64 | 1076.13 | 1409.52 | 0.00 | 0.00 |
August | 3138.63 | 440.56 | 2589.74 | 1428.93 | 1160.81 | 0.00 | 0.00 |
September | 2254.61 | 836.67 | 2067.42 | 1235.86 | 831.57 | 0.00 | 0.00 |
October | 1409.52 | 1468.93 | 1531.07 | 971.33 | 559.74 | 0.00 | 0.00 |
November | 538.18 | 2614.56 | 830.33 | 585.24 | 245.09 | 0.00 | 0.00 |
December | 25.30 | 3117.90 | 146.85 | 103.52 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 2104.37 | 1452.29 | 1957.12 | 1120.06 | 837.06 | 0.00 | 0.00 |
Minimum of Months | 25.30 | 266.43 | 146.85 | 103.52 | 43.33 | 0.00 | 0.00 |
Maximum of Months | 3851.83 | 3117.90 | 3444.56 | 2143.70 | 1529.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 371.63 | 3793.08 | 645.71 | 429.91 | 215.80 | 0.00 | 0.00 |
February | 1839.52 | 3034.08 | 2157.24 | 1497.96 | 659.28 | 0.00 | 0.00 |
March | 3682.64 | 2328.53 | 3651.96 | 2470.82 | 1181.14 | 0.00 | 0.00 |
April | 5073.12 | 1507.73 | 4474.68 | 2784.79 | 1689.89 | 0.00 | 0.00 |
May | 4351.22 | 766.17 | 3694.32 | 1917.59 | 1776.73 | 0.00 | 0.00 |
June | 4096.14 | 375.73 | 3356.54 | 1369.79 | 1986.74 | 0.00 | 0.00 |
July | 4042.29 | 393.12 | 3228.99 | 1397.95 | 1831.04 | 0.00 | 0.00 |
August | 4113.50 | 616.56 | 3364.22 | 1856.26 | 1507.96 | 0.00 | 0.00 |
September | 2952.68 | 1163.15 | 2685.70 | 1605.45 | 1080.25 | 0.00 | 0.00 |
October | 1842.31 | 2012.55 | 1988.95 | 1261.81 | 727.14 | 0.00 | 0.00 |
November | 698.42 | 3531.89 | 1078.64 | 760.26 | 318.39 | 0.00 | 0.00 |
December | 31.95 | 4206.53 | 190.76 | 134.47 | 56.29 | 0.00 | 0.00 |
Annual Sum or Average | 2760.60 | 1972.39 | 2542.42 | 1455.03 | 1087.39 | 0.00 | 0.00 |
Minimum of Months | 31.95 | 375.73 | 190.76 | 134.47 | 56.29 | 0.00 | 0.00 |
Maximum of Months | 5073.12 | 4206.53 | 4474.68 | 2784.79 | 1986.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.47 | 598.31 | 42.08 | 24.46 | 17.62 | 0.00 | 0.00 |
February | 73.96 | 476.78 | 159.39 | 95.87 | 63.52 | 0.00 | 0.00 |
March | 252.30 | 356.81 | 326.16 | 189.16 | 137.00 | 0.00 | 0.00 |
April | 563.25 | 213.20 | 547.00 | 308.95 | 238.05 | 0.00 | 0.00 |
May | 544.88 | 100.42 | 495.70 | 238.72 | 256.98 | 0.00 | 0.00 |
June | 598.02 | 45.41 | 505.66 | 212.48 | 293.18 | 0.00 | 0.00 |
July | 538.78 | 48.42 | 445.36 | 177.90 | 267.46 | 0.00 | 0.00 |
August | 469.52 | 79.83 | 405.30 | 195.35 | 209.95 | 0.00 | 0.00 |
September | 271.62 | 165.30 | 279.62 | 142.83 | 136.79 | 0.00 | 0.00 |
October | 101.32 | 306.90 | 160.21 | 83.98 | 76.23 | 0.00 | 0.00 |
November | 21.19 | 556.88 | 79.60 | 48.90 | 30.70 | 0.00 | 0.00 |
December | 0.00 | 656.13 | 12.20 | 7.46 | 4.74 | 0.00 | 0.00 |
Annual Sum or Average | 287.60 | 299.52 | 288.54 | 143.85 | 144.68 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 45.41 | 12.20 | 7.46 | 4.74 | 0.00 | 0.00 |
Maximum of Months | 598.02 | 656.13 | 547.00 | 308.95 | 293.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 635.32 | 9.98 | 1.22 | 8.75 | 0.00 | 0.00 |
February | 4.19 | 544.84 | 55.15 | 14.91 | 40.24 | 0.00 | 0.00 |
March | 71.46 | 391.64 | 161.86 | 55.62 | 106.24 | 0.00 | 0.00 |
April | 324.75 | 213.42 | 365.57 | 160.16 | 205.41 | 0.00 | 0.00 |
May | 381.54 | 86.74 | 388.41 | 149.88 | 238.53 | 0.00 | 0.00 |
June | 491.55 | 37.36 | 443.85 | 164.98 | 278.87 | 0.00 | 0.00 |
July | 423.07 | 43.96 | 371.97 | 119.24 | 252.73 | 0.00 | 0.00 |
August | 301.94 | 76.70 | 288.65 | 98.93 | 189.72 | 0.00 | 0.00 |
September | 131.16 | 168.01 | 170.39 | 56.17 | 114.22 | 0.00 | 0.00 |
October | 19.20 | 341.70 | 70.10 | 15.78 | 54.32 | 0.00 | 0.00 |
November | 0.83 | 606.18 | 26.70 | 7.81 | 18.89 | 0.00 | 0.00 |
December | 0.00 | 668.24 | 2.74 | 0.19 | 2.54 | 0.00 | 0.00 |
Annual Sum or Average | 179.95 | 316.65 | 196.83 | 70.57 | 126.26 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 37.36 | 2.74 | 0.19 | 2.54 | 0.00 | 0.00 |
Maximum of Months | 491.55 | 668.24 | 443.85 | 164.98 | 278.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 17.83 | 141.78 | 27.91 | 18.59 | 9.33 | 0.00 | 0.00 |
February | 84.01 | 113.75 | 93.26 | 64.76 | 28.50 | 0.00 | 0.00 |
March | 158.90 | 97.83 | 157.88 | 106.82 | 51.06 | 0.00 | 0.00 |
April | 209.01 | 77.86 | 193.45 | 120.39 | 73.06 | 0.00 | 0.00 |
May | 176.75 | 43.31 | 159.71 | 82.90 | 76.81 | 0.00 | 0.00 |
June | 164.74 | 23.35 | 145.11 | 59.22 | 85.89 | 0.00 | 0.00 |
July | 163.09 | 24.27 | 139.59 | 60.44 | 79.16 | 0.00 | 0.00 |
August | 167.64 | 35.99 | 145.44 | 80.25 | 65.19 | 0.00 | 0.00 |
September | 119.59 | 62.40 | 116.11 | 69.41 | 46.70 | 0.00 | 0.00 |
October | 77.12 | 89.02 | 85.98 | 54.55 | 31.44 | 0.00 | 0.00 |
November | 33.55 | 131.16 | 46.63 | 32.87 | 13.76 | 0.00 | 0.00 |
December | 1.79 | 158.31 | 8.25 | 5.81 | 2.43 | 0.00 | 0.00 |
Annual Sum or Average | 114.56 | 83.11 | 109.91 | 62.90 | 47.01 | 0.00 | 0.00 |
Minimum of Months | 1.79 | 23.35 | 8.25 | 5.81 | 2.43 | 0.00 | 0.00 |
Maximum of Months | 209.01 | 158.31 | 193.45 | 120.39 | 85.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 181.89 | 2.24 | 0.00 | 2.24 | 0.00 | 0.00 |
February | 0.00 | 162.51 | 9.88 | 0.00 | 9.88 | 0.00 | 0.00 |
March | 2.09 | 120.71 | 26.48 | 0.00 | 26.47 | 0.00 | 0.00 |
April | 20.95 | 62.06 | 48.35 | 1.38 | 46.97 | 0.00 | 0.00 |
May | 63.53 | 23.69 | 73.92 | 11.85 | 62.07 | 0.00 | 0.00 |
June | 103.68 | 9.41 | 95.70 | 21.23 | 74.47 | 0.00 | 0.00 |
July | 90.50 | 11.34 | 80.92 | 13.52 | 67.40 | 0.00 | 0.00 |
August | 48.54 | 20.81 | 52.15 | 3.13 | 49.03 | 0.00 | 0.00 |
September | 12.41 | 49.63 | 28.75 | 0.09 | 28.66 | 0.00 | 0.00 |
October | 0.97 | 102.71 | 13.92 | 0.00 | 13.92 | 0.00 | 0.00 |
November | 0.00 | 177.27 | 4.32 | 0.00 | 4.32 | 0.00 | 0.00 |
December | 0.00 | 190.26 | 0.68 | 0.00 | 0.68 | 0.00 | 0.00 |
Annual Sum or Average | 28.73 | 92.31 | 36.57 | 4.29 | 32.29 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 9.41 | 0.68 | 0.00 | 0.68 | 0.00 | 0.00 |
Maximum of Months | 103.68 | 190.26 | 95.70 | 21.23 | 74.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12.08 | 593.43 | 50.35 | 28.96 | 21.39 | 0.00 | 0.00 |
February | 119.64 | 472.18 | 196.76 | 119.39 | 77.36 | 0.00 | 0.00 |
March | 373.14 | 354.40 | 422.22 | 247.39 | 174.83 | 0.00 | 0.00 |
April | 543.96 | 202.56 | 540.97 | 302.03 | 238.93 | 0.00 | 0.00 |
May | 722.50 | 93.10 | 635.28 | 349.55 | 285.74 | 0.00 | 0.00 |
June | 693.32 | 39.16 | 580.33 | 260.34 | 319.99 | 0.00 | 0.00 |
July | 681.09 | 44.18 | 554.47 | 260.32 | 294.15 | 0.00 | 0.00 |
August | 573.82 | 75.40 | 487.13 | 249.95 | 237.18 | 0.00 | 0.00 |
September | 340.29 | 161.18 | 336.24 | 173.21 | 163.03 | 0.00 | 0.00 |
October | 165.85 | 305.67 | 210.99 | 110.13 | 100.86 | 0.00 | 0.00 |
November | 19.90 | 555.06 | 79.75 | 48.88 | 30.87 | 0.00 | 0.00 |
December | 0.00 | 654.16 | 13.36 | 7.99 | 5.37 | 0.00 | 0.00 |
Annual Sum or Average | 355.22 | 295.04 | 343.06 | 180.16 | 162.89 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 39.16 | 13.36 | 7.99 | 5.37 | 0.00 | 0.00 |
Maximum of Months | 722.50 | 654.16 | 635.28 | 349.55 | 319.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.71 | 623.73 | 18.25 | 5.72 | 12.52 | 0.00 | 0.00 |
February | 29.07 | 517.27 | 92.51 | 38.43 | 54.08 | 0.00 | 0.00 |
March | 181.62 | 375.95 | 257.92 | 113.85 | 144.07 | 0.00 | 0.00 |
April | 301.66 | 200.11 | 359.54 | 153.24 | 206.30 | 0.00 | 0.00 |
May | 569.00 | 89.42 | 527.99 | 260.71 | 267.28 | 0.00 | 0.00 |
June | 595.91 | 37.50 | 518.52 | 212.85 | 305.68 | 0.00 | 0.00 |
July | 569.13 | 44.19 | 481.08 | 201.67 | 279.42 | 0.00 | 0.00 |
August | 411.85 | 76.58 | 370.47 | 153.52 | 216.95 | 0.00 | 0.00 |
September | 197.77 | 162.66 | 227.02 | 86.55 | 140.47 | 0.00 | 0.00 |
October | 69.06 | 324.40 | 120.88 | 41.93 | 78.95 | 0.00 | 0.00 |
November | 0.49 | 605.30 | 26.85 | 7.79 | 19.06 | 0.00 | 0.00 |
December | 0.00 | 666.09 | 3.90 | 0.72 | 3.18 | 0.00 | 0.00 |
Annual Sum or Average | 245.29 | 309.21 | 251.35 | 106.88 | 144.47 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 37.50 | 3.90 | 0.72 | 3.18 | 0.00 | 0.00 |
Maximum of Months | 595.91 | 666.09 | 527.99 | 260.71 | 305.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 15.55 | 747.93 | 65.33 | 40.27 | 25.06 | 0.00 | 0.00 |
February | 119.77 | 598.76 | 223.48 | 140.31 | 83.17 | 0.00 | 0.00 |
March | 312.61 | 453.44 | 399.44 | 231.45 | 167.99 | 0.00 | 0.00 |
April | 512.30 | 272.27 | 523.88 | 263.84 | 260.04 | 0.00 | 0.00 |
May | 528.09 | 116.55 | 506.18 | 205.29 | 300.90 | 0.00 | 0.00 |
June | 589.76 | 51.27 | 521.74 | 174.31 | 347.43 | 0.00 | 0.00 |
July | 561.17 | 60.63 | 477.76 | 160.24 | 317.52 | 0.00 | 0.00 |
August | 481.20 | 103.06 | 428.11 | 180.65 | 247.46 | 0.00 | 0.00 |
September | 299.02 | 211.33 | 313.86 | 150.58 | 163.28 | 0.00 | 0.00 |
October | 146.32 | 386.95 | 216.45 | 118.19 | 98.26 | 0.00 | 0.00 |
November | 33.18 | 697.13 | 110.39 | 71.21 | 39.18 | 0.00 | 0.00 |
December | 0.11 | 822.72 | 19.34 | 12.60 | 6.74 | 0.00 | 0.00 |
Annual Sum or Average | 300.76 | 375.77 | 317.38 | 145.58 | 171.80 | 0.00 | 0.00 |
Minimum of Months | 0.11 | 51.27 | 19.34 | 12.60 | 6.74 | 0.00 | 0.00 |
Maximum of Months | 589.76 | 822.72 | 523.88 | 263.84 | 347.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.61 | 594.24 | 42.08 | 24.46 | 17.62 | 0.00 | 0.00 |
February | 74.79 | 473.66 | 159.39 | 95.87 | 63.52 | 0.00 | 0.00 |
March | 253.21 | 355.18 | 326.16 | 189.16 | 137.00 | 0.00 | 0.00 |
April | 561.66 | 212.17 | 547.00 | 308.95 | 238.05 | 0.00 | 0.00 |
May | 542.96 | 99.41 | 495.70 | 238.72 | 256.98 | 0.00 | 0.00 |
June | 595.65 | 44.66 | 505.66 | 212.48 | 293.18 | 0.00 | 0.00 |
July | 536.79 | 47.61 | 445.36 | 177.90 | 267.46 | 0.00 | 0.00 |
August | 468.18 | 78.69 | 405.30 | 195.35 | 209.95 | 0.00 | 0.00 |
September | 272.07 | 163.29 | 279.62 | 142.83 | 136.79 | 0.00 | 0.00 |
October | 102.23 | 304.89 | 160.21 | 83.98 | 76.23 | 0.00 | 0.00 |
November | 21.65 | 551.51 | 79.60 | 48.90 | 30.70 | 0.00 | 0.00 |
December | 0.00 | 652.04 | 12.20 | 7.46 | 4.74 | 0.00 | 0.00 |
Annual Sum or Average | 287.13 | 297.28 | 288.54 | 143.85 | 144.68 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 44.66 | 12.20 | 7.46 | 4.74 | 0.00 | 0.00 |
Maximum of Months | 595.65 | 652.04 | 547.00 | 308.95 | 293.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 631.09 | 9.98 | 1.22 | 8.75 | 0.00 | 0.00 |
February | 4.32 | 541.26 | 55.15 | 14.91 | 40.24 | 0.00 | 0.00 |
March | 71.83 | 389.88 | 161.86 | 55.62 | 106.24 | 0.00 | 0.00 |
April | 324.39 | 212.23 | 365.57 | 160.16 | 205.41 | 0.00 | 0.00 |
May | 380.18 | 86.33 | 388.41 | 149.88 | 238.53 | 0.00 | 0.00 |
June | 488.02 | 37.51 | 443.85 | 164.98 | 278.87 | 0.00 | 0.00 |
July | 420.51 | 43.98 | 371.97 | 119.24 | 252.73 | 0.00 | 0.00 |
August | 300.67 | 76.33 | 288.65 | 98.93 | 189.72 | 0.00 | 0.00 |
September | 132.33 | 165.52 | 170.39 | 56.17 | 114.22 | 0.00 | 0.00 |
October | 19.77 | 339.44 | 70.10 | 15.78 | 54.32 | 0.00 | 0.00 |
November | 0.86 | 600.41 | 26.70 | 7.81 | 18.89 | 0.00 | 0.00 |
December | 0.00 | 663.98 | 2.74 | 0.19 | 2.54 | 0.00 | 0.00 |
Annual Sum or Average | 179.37 | 314.49 | 196.83 | 70.57 | 126.26 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 37.51 | 2.74 | 0.19 | 2.54 | 0.00 | 0.00 |
Maximum of Months | 488.02 | 663.98 | 443.85 | 164.98 | 278.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 29.69 | 296.46 | 51.18 | 34.08 | 17.11 | 0.00 | 0.00 |
February | 144.65 | 238.83 | 171.00 | 118.74 | 52.26 | 0.00 | 0.00 |
March | 286.57 | 184.93 | 289.49 | 195.86 | 93.63 | 0.00 | 0.00 |
April | 395.07 | 116.28 | 354.71 | 220.75 | 133.96 | 0.00 | 0.00 |
May | 340.23 | 54.90 | 292.85 | 152.01 | 140.84 | 0.00 | 0.00 |
June | 323.03 | 24.05 | 266.07 | 108.58 | 157.49 | 0.00 | 0.00 |
July | 319.34 | 25.25 | 255.96 | 110.81 | 145.15 | 0.00 | 0.00 |
August | 323.78 | 41.92 | 266.68 | 147.14 | 119.54 | 0.00 | 0.00 |
September | 231.72 | 86.43 | 212.89 | 127.26 | 85.63 | 0.00 | 0.00 |
October | 144.26 | 155.82 | 157.66 | 100.02 | 57.64 | 0.00 | 0.00 |
November | 56.38 | 273.92 | 85.50 | 60.26 | 25.24 | 0.00 | 0.00 |
December | 2.70 | 328.53 | 15.12 | 10.66 | 4.46 | 0.00 | 0.00 |
Annual Sum or Average | 216.66 | 151.86 | 201.54 | 115.34 | 86.20 | 0.00 | 0.00 |
Minimum of Months | 2.70 | 24.05 | 15.12 | 10.66 | 4.46 | 0.00 | 0.00 |
Maximum of Months | 395.07 | 328.53 | 354.71 | 220.75 | 157.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1591.97 | 19.56 | 0.00 | 19.56 | 0.00 | 0.00 |
February | 0.00 | 1423.72 | 86.48 | 0.00 | 86.48 | 0.00 | 0.00 |
March | 16.96 | 1065.25 | 231.64 | 0.04 | 231.60 | 0.00 | 0.00 |
April | 178.89 | 557.89 | 422.97 | 12.07 | 410.90 | 0.00 | 0.00 |
May | 549.36 | 220.06 | 646.69 | 103.65 | 543.03 | 0.00 | 0.00 |
June | 907.00 | 90.97 | 837.27 | 185.76 | 651.51 | 0.00 | 0.00 |
July | 795.00 | 108.00 | 707.92 | 118.31 | 589.61 | 0.00 | 0.00 |
August | 424.70 | 193.33 | 456.27 | 27.35 | 428.92 | 0.00 | 0.00 |
September | 106.77 | 447.50 | 251.56 | 0.82 | 250.74 | 0.00 | 0.00 |
October | 8.06 | 911.97 | 121.74 | 0.00 | 121.74 | 0.00 | 0.00 |
November | 0.00 | 1544.27 | 37.78 | 0.00 | 37.78 | 0.00 | 0.00 |
December | 0.00 | 1660.49 | 5.93 | 0.00 | 5.93 | 0.00 | 0.00 |
Annual Sum or Average | 250.40 | 814.70 | 319.97 | 37.50 | 282.47 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 90.97 | 5.93 | 0.00 | 5.93 | 0.00 | 0.00 |
Maximum of Months | 907.00 | 1660.49 | 837.27 | 185.76 | 651.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1613.86 | 19.56 | 0.00 | 19.56 | 0.00 | 0.00 |
February | 0.00 | 1445.00 | 86.48 | 0.00 | 86.48 | 0.00 | 0.00 |
March | 15.46 | 1087.41 | 231.64 | 0.04 | 231.60 | 0.00 | 0.00 |
April | 170.91 | 574.16 | 422.97 | 12.07 | 410.90 | 0.00 | 0.00 |
May | 536.18 | 226.52 | 646.69 | 103.65 | 543.03 | 0.00 | 0.00 |
June | 893.17 | 94.71 | 837.27 | 185.76 | 651.51 | 0.00 | 0.00 |
July | 782.07 | 112.49 | 707.92 | 118.31 | 589.61 | 0.00 | 0.00 |
August | 413.99 | 200.55 | 456.27 | 27.35 | 428.92 | 0.00 | 0.00 |
September | 100.56 | 465.50 | 251.56 | 0.82 | 250.74 | 0.00 | 0.00 |
October | 6.76 | 936.77 | 121.74 | 0.00 | 121.74 | 0.00 | 0.00 |
November | 0.00 | 1565.05 | 37.78 | 0.00 | 37.78 | 0.00 | 0.00 |
December | 0.00 | 1680.78 | 5.93 | 0.00 | 5.93 | 0.00 | 0.00 |
Annual Sum or Average | 244.73 | 830.28 | 319.97 | 37.50 | 282.47 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 94.71 | 5.93 | 0.00 | 5.93 | 0.00 | 0.00 |
Maximum of Months | 893.17 | 1680.78 | 837.27 | 185.76 | 651.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.09 | 1062.37 | 68.60 | 34.68 | 33.92 | 0.00 | 0.00 |
February | 172.00 | 851.17 | 289.26 | 157.82 | 131.44 | 0.00 | 0.00 |
March | 642.71 | 645.89 | 680.11 | 361.23 | 318.89 | 0.00 | 0.00 |
April | 1020.31 | 377.77 | 900.46 | 455.25 | 445.21 | 0.00 | 0.00 |
May | 1516.70 | 174.18 | 1163.22 | 610.23 | 552.99 | 0.00 | 0.00 |
June | 1544.96 | 77.67 | 1098.80 | 473.16 | 625.63 | 0.00 | 0.00 |
July | 1508.20 | 87.80 | 1035.50 | 461.96 | 573.54 | 0.00 | 0.00 |
August | 1219.52 | 140.84 | 857.56 | 403.45 | 454.11 | 0.00 | 0.00 |
September | 697.98 | 276.00 | 563.24 | 259.75 | 303.48 | 0.00 | 0.00 |
October | 298.62 | 532.11 | 331.86 | 152.05 | 179.80 | 0.00 | 0.00 |
November | 18.23 | 990.67 | 106.59 | 56.67 | 49.92 | 0.00 | 0.00 |
December | 0.00 | 1160.16 | 17.27 | 8.71 | 8.55 | 0.00 | 0.00 |
Annual Sum or Average | 724.53 | 529.86 | 594.38 | 287.03 | 307.35 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 77.67 | 17.27 | 8.71 | 8.55 | 0.00 | 0.00 |
Maximum of Months | 1544.96 | 1160.16 | 1163.22 | 610.23 | 625.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 44.09 | 1308.02 | 137.00 | 86.75 | 50.25 | 0.00 | 0.00 |
February | 293.49 | 1047.79 | 464.94 | 302.26 | 162.68 | 0.00 | 0.00 |
March | 689.62 | 799.36 | 816.31 | 498.58 | 317.73 | 0.00 | 0.00 |
April | 1055.77 | 497.44 | 1047.92 | 566.06 | 481.85 | 0.00 | 0.00 |
May | 1003.63 | 225.43 | 967.14 | 422.47 | 544.67 | 0.00 | 0.00 |
June | 1072.05 | 100.80 | 964.32 | 340.08 | 624.23 | 0.00 | 0.00 |
July | 1033.32 | 118.92 | 894.24 | 322.64 | 571.60 | 0.00 | 0.00 |
August | 932.09 | 201.77 | 835.26 | 383.94 | 451.32 | 0.00 | 0.00 |
September | 611.19 | 393.19 | 628.17 | 324.23 | 303.93 | 0.00 | 0.00 |
October | 328.72 | 686.25 | 443.07 | 254.61 | 188.46 | 0.00 | 0.00 |
November | 90.72 | 1212.47 | 230.60 | 153.41 | 77.20 | 0.00 | 0.00 |
December | 1.43 | 1445.60 | 40.53 | 27.13 | 13.39 | 0.00 | 0.00 |
Annual Sum or Average | 597.61 | 667.95 | 622.71 | 306.46 | 316.25 | 0.00 | 0.00 |
Minimum of Months | 1.43 | 100.80 | 40.53 | 27.13 | 13.39 | 0.00 | 0.00 |
Maximum of Months | 1072.05 | 1445.60 | 1047.92 | 566.06 | 624.23 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.275631E+09 | 0.267949E+10 | 0.472780E+09 | 0.314774E+09 | 0.158006E+09 | 0.00 | 0.00 |
February | 0.121345E+10 | 0.194451E+10 | 0.142666E+10 | 0.990652E+09 | 0.436005E+09 | 0.00 | 0.00 |
March | 0.266503E+10 | 0.165253E+10 | 0.267393E+10 | 0.180911E+10 | 0.864824E+09 | 0.00 | 0.00 |
April | 0.354083E+10 | 0.103835E+10 | 0.317064E+10 | 0.197323E+10 | 0.119741E+10 | 0.00 | 0.00 |
May | 0.312720E+10 | 0.551265E+09 | 0.270495E+10 | 0.140405E+10 | 0.130090E+10 | 0.00 | 0.00 |
June | 0.283644E+10 | 0.270589E+09 | 0.237835E+10 | 0.970599E+09 | 0.140775E+10 | 0.00 | 0.00 |
July | 0.289496E+10 | 0.291596E+09 | 0.236424E+10 | 0.102357E+10 | 0.134067E+10 | 0.00 | 0.00 |
August | 0.295829E+10 | 0.448026E+09 | 0.246326E+10 | 0.135914E+10 | 0.110412E+10 | 0.00 | 0.00 |
September | 0.206980E+10 | 0.781848E+09 | 0.190301E+10 | 0.113758E+10 | 0.765436E+09 | 0.00 | 0.00 |
October | 0.134487E+10 | 0.140158E+10 | 0.145629E+10 | 0.923887E+09 | 0.532405E+09 | 0.00 | 0.00 |
November | 0.499149E+09 | 0.242182E+10 | 0.764297E+09 | 0.538697E+09 | 0.225599E+09 | 0.00 | 0.00 |
December | 24395650.64 | 0.298314E+10 | 0.139675E+09 | 98460044.66 | 41214694.35 | 0.00 | 0.00 |
Annual Sum or Average | 0.234500E+11 | 0.164648E+11 | 0.219181E+11 | 0.125437E+11 | 0.937435E+10 | 0.00 | 0.00 |
Minimum of Months | 24395650.64 | 0.270589E+09 | 0.139675E+09 | 98460044.66 | 41214694.35 | 0.00 | 0.00 |
Maximum of Months | 0.354083E+10 | 0.298314E+10 | 0.317064E+10 | 0.197323E+10 | 0.140775E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.769828E+09 | 0.751249E+10 | 0.133132E+10 | 0.886384E+09 | 0.444935E+09 | 0.00 | 0.00 |
February | 0.340440E+10 | 0.544237E+10 | 0.401737E+10 | 0.278961E+10 | 0.122776E+10 | 0.00 | 0.00 |
March | 0.749574E+10 | 0.462710E+10 | 0.752962E+10 | 0.509434E+10 | 0.243529E+10 | 0.00 | 0.00 |
April | 0.998394E+10 | 0.288999E+10 | 0.892830E+10 | 0.555648E+10 | 0.337183E+10 | 0.00 | 0.00 |
May | 0.887119E+10 | 0.148225E+10 | 0.761696E+10 | 0.395370E+10 | 0.366326E+10 | 0.00 | 0.00 |
June | 0.809173E+10 | 0.690589E+09 | 0.669728E+10 | 0.273314E+10 | 0.396414E+10 | 0.00 | 0.00 |
July | 0.825827E+10 | 0.743680E+09 | 0.665755E+10 | 0.288230E+10 | 0.377525E+10 | 0.00 | 0.00 |
August | 0.840650E+10 | 0.117999E+10 | 0.693636E+10 | 0.382724E+10 | 0.310912E+10 | 0.00 | 0.00 |
September | 0.584396E+10 | 0.216866E+10 | 0.535876E+10 | 0.320335E+10 | 0.215542E+10 | 0.00 | 0.00 |
October | 0.377525E+10 | 0.393440E+10 | 0.410082E+10 | 0.260160E+10 | 0.149922E+10 | 0.00 | 0.00 |
November | 0.139497E+10 | 0.677694E+10 | 0.215221E+10 | 0.151694E+10 | 0.635273E+09 | 0.00 | 0.00 |
December | 67758619.82 | 0.835098E+10 | 0.393315E+09 | 0.277257E+09 | 0.116058E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.663635E+11 | 0.457994E+11 | 0.617199E+11 | 0.353223E+11 | 0.263975E+11 | 0.00 | 0.00 |
Minimum of Months | 67758619.82 | 0.690589E+09 | 0.393315E+09 | 0.277257E+09 | 0.116058E+09 | 0.00 | 0.00 |
Maximum of Months | 0.998394E+10 | 0.835098E+10 | 0.892830E+10 | 0.555648E+10 | 0.396414E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.995372E+09 | 0.101594E+11 | 0.172946E+10 | 0.115146E+10 | 0.577995E+09 | 0.00 | 0.00 |
February | 0.445016E+10 | 0.734005E+10 | 0.521879E+10 | 0.362386E+10 | 0.159493E+10 | 0.00 | 0.00 |
March | 0.986360E+10 | 0.623674E+10 | 0.978141E+10 | 0.661783E+10 | 0.316358E+10 | 0.00 | 0.00 |
April | 0.131495E+11 | 0.390802E+10 | 0.115984E+11 | 0.721818E+10 | 0.438019E+10 | 0.00 | 0.00 |
May | 0.116543E+11 | 0.205212E+10 | 0.989487E+10 | 0.513608E+10 | 0.475878E+10 | 0.00 | 0.00 |
June | 0.106172E+11 | 0.973892E+09 | 0.870015E+10 | 0.355051E+10 | 0.514964E+10 | 0.00 | 0.00 |
July | 0.108269E+11 | 0.105294E+10 | 0.864853E+10 | 0.374427E+10 | 0.490426E+10 | 0.00 | 0.00 |
August | 0.110176E+11 | 0.165138E+10 | 0.901073E+10 | 0.497180E+10 | 0.403893E+10 | 0.00 | 0.00 |
September | 0.765336E+10 | 0.301488E+10 | 0.696134E+10 | 0.416133E+10 | 0.280001E+10 | 0.00 | 0.00 |
October | 0.493445E+10 | 0.539040E+10 | 0.532720E+10 | 0.337963E+10 | 0.194757E+10 | 0.00 | 0.00 |
November | 0.181032E+10 | 0.915465E+10 | 0.279584E+10 | 0.197059E+10 | 0.825256E+09 | 0.00 | 0.00 |
December | 85571057.55 | 0.112668E+11 | 0.510938E+09 | 0.360173E+09 | 0.150766E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.870583E+11 | 0.622012E+11 | 0.801776E+11 | 0.458857E+11 | 0.342919E+11 | 0.00 | 0.00 |
Minimum of Months | 85571057.55 | 0.973892E+09 | 0.510938E+09 | 0.360173E+09 | 0.150766E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131495E+11 | 0.112668E+11 | 0.115984E+11 | 0.721818E+10 | 0.514964E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 14647972.17 | 0.160251E+10 | 0.112710E+09 | 65506021.51 | 47203819.41 | 0.00 | 0.00 |
February | 0.178935E+09 | 0.115342E+10 | 0.385608E+09 | 0.231929E+09 | 0.153680E+09 | 0.00 | 0.00 |
March | 0.675760E+09 | 0.955677E+09 | 0.873575E+09 | 0.506643E+09 | 0.366933E+09 | 0.00 | 0.00 |
April | 0.145993E+10 | 0.552626E+09 | 0.141782E+10 | 0.800800E+09 | 0.617020E+09 | 0.00 | 0.00 |
May | 0.145941E+10 | 0.268965E+09 | 0.132768E+10 | 0.639378E+09 | 0.688299E+09 | 0.00 | 0.00 |
June | 0.155007E+10 | 0.117696E+09 | 0.131066E+10 | 0.550743E+09 | 0.759918E+09 | 0.00 | 0.00 |
July | 0.144306E+10 | 0.129699E+09 | 0.119286E+10 | 0.476491E+09 | 0.716372E+09 | 0.00 | 0.00 |
August | 0.125755E+10 | 0.213819E+09 | 0.108557E+10 | 0.523234E+09 | 0.562332E+09 | 0.00 | 0.00 |
September | 0.704047E+09 | 0.428467E+09 | 0.724764E+09 | 0.370217E+09 | 0.354547E+09 | 0.00 | 0.00 |
October | 0.271363E+09 | 0.822011E+09 | 0.429109E+09 | 0.224934E+09 | 0.204174E+09 | 0.00 | 0.00 |
November | 54927268.53 | 0.144343E+10 | 0.206334E+09 | 0.126750E+09 | 79584391.43 | 0.00 | 0.00 |
December | 0.00 | 0.175737E+10 | 32673305.95 | 19979472.27 | 12693833.69 | 0.00 | 0.00 |
Annual Sum or Average | 0.906971E+10 | 0.944569E+10 | 0.909936E+10 | 0.453660E+10 | 0.456276E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.117696E+09 | 32673305.95 | 19979472.27 | 12693833.69 | 0.00 | 0.00 |
Maximum of Months | 0.155007E+10 | 0.175737E+10 | 0.141782E+10 | 0.800800E+09 | 0.759918E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.170163E+10 | 26718359.59 | 3269712.17 | 23448647.42 | 0.00 | 0.00 |
February | 10147194.45 | 0.131807E+10 | 0.133420E+09 | 36059635.70 | 97360660.42 | 0.00 | 0.00 |
March | 0.191402E+09 | 0.104896E+10 | 0.433527E+09 | 0.148966E+09 | 0.284562E+09 | 0.00 | 0.00 |
April | 0.841752E+09 | 0.553195E+09 | 0.947555E+09 | 0.415128E+09 | 0.532427E+09 | 0.00 | 0.00 |
May | 0.102192E+10 | 0.232312E+09 | 0.104031E+10 | 0.401436E+09 | 0.638875E+09 | 0.00 | 0.00 |
June | 0.127409E+10 | 96824501.94 | 0.115046E+10 | 0.427626E+09 | 0.722833E+09 | 0.00 | 0.00 |
July | 0.113316E+10 | 0.117754E+09 | 0.996291E+09 | 0.319384E+09 | 0.676907E+09 | 0.00 | 0.00 |
August | 0.808722E+09 | 0.205425E+09 | 0.773125E+09 | 0.264974E+09 | 0.508151E+09 | 0.00 | 0.00 |
September | 0.339972E+09 | 0.435476E+09 | 0.441656E+09 | 0.145601E+09 | 0.296055E+09 | 0.00 | 0.00 |
October | 51435956.66 | 0.915207E+09 | 0.187756E+09 | 42266213.40 | 0.145490E+09 | 0.00 | 0.00 |
November | 2162781.86 | 0.157123E+10 | 69209075.72 | 20239990.41 | 48969085.31 | 0.00 | 0.00 |
December | 0.00 | 0.178981E+10 | 7327873.51 | 512230.40 | 6815643.11 | 0.00 | 0.00 |
Annual Sum or Average | 0.567477E+10 | 0.998590E+10 | 0.620735E+10 | 0.222546E+10 | 0.398189E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 96824501.94 | 7327873.51 | 512230.40 | 6815643.11 | 0.00 | 0.00 |
Maximum of Months | 0.127409E+10 | 0.178981E+10 | 0.115046E+10 | 0.427626E+09 | 0.722833E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 47747523.40 | 0.379756E+09 | 74766633.98 | 49779147.74 | 24987486.24 | 0.00 | 0.00 |
February | 0.203225E+09 | 0.275196E+09 | 0.225615E+09 | 0.156664E+09 | 68951034.08 | 0.00 | 0.00 |
March | 0.425589E+09 | 0.262023E+09 | 0.422863E+09 | 0.286097E+09 | 0.136766E+09 | 0.00 | 0.00 |
April | 0.541751E+09 | 0.201817E+09 | 0.501413E+09 | 0.312051E+09 | 0.189362E+09 | 0.00 | 0.00 |
May | 0.473397E+09 | 0.116002E+09 | 0.427769E+09 | 0.222039E+09 | 0.205730E+09 | 0.00 | 0.00 |
June | 0.427008E+09 | 60516053.44 | 0.376120E+09 | 0.153493E+09 | 0.222627E+09 | 0.00 | 0.00 |
July | 0.436808E+09 | 64995240.45 | 0.373888E+09 | 0.161869E+09 | 0.212019E+09 | 0.00 | 0.00 |
August | 0.449019E+09 | 96399448.82 | 0.389546E+09 | 0.214937E+09 | 0.174609E+09 | 0.00 | 0.00 |
September | 0.309980E+09 | 0.161753E+09 | 0.300948E+09 | 0.179899E+09 | 0.121048E+09 | 0.00 | 0.00 |
October | 0.206563E+09 | 0.238438E+09 | 0.230302E+09 | 0.146106E+09 | 84196004.15 | 0.00 | 0.00 |
November | 86965820.71 | 0.339965E+09 | 0.120868E+09 | 85190798.59 | 35676889.28 | 0.00 | 0.00 |
December | 4781178.45 | 0.424016E+09 | 22088494.24 | 15570696.90 | 6517797.34 | 0.00 | 0.00 |
Annual Sum or Average | 0.361284E+10 | 0.262088E+10 | 0.346619E+10 | 0.198370E+10 | 0.148249E+10 | 0.00 | 0.00 |
Minimum of Months | 4781178.45 | 60516053.44 | 22088494.24 | 15570696.90 | 6517797.34 | 0.00 | 0.00 |
Maximum of Months | 0.541751E+09 | 0.424016E+09 | 0.501413E+09 | 0.312051E+09 | 0.222627E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.487170E+09 | 5989111.78 | 0.00 | 5989111.78 | 0.00 | 0.00 |
February | 0.00 | 0.393152E+09 | 23912704.39 | 0.00 | 23912704.39 | 0.00 | 0.00 |
March | 5595453.47 | 0.323321E+09 | 70917670.65 | 12033.88 | 70905636.77 | 0.00 | 0.00 |
April | 54308737.50 | 0.160851E+09 | 0.125317E+09 | 3575377.89 | 0.121742E+09 | 0.00 | 0.00 |
May | 0.170152E+09 | 63442162.58 | 0.197987E+09 | 31733856.97 | 0.166253E+09 | 0.00 | 0.00 |
June | 0.268736E+09 | 24389931.96 | 0.248066E+09 | 55037234.19 | 0.193028E+09 | 0.00 | 0.00 |
July | 0.242408E+09 | 30369191.96 | 0.216733E+09 | 36220282.52 | 0.180513E+09 | 0.00 | 0.00 |
August | 0.130005E+09 | 55729906.41 | 0.139690E+09 | 8372983.02 | 0.131317E+09 | 0.00 | 0.00 |
September | 32158376.38 | 0.128640E+09 | 74530558.75 | 241985.74 | 74288573.01 | 0.00 | 0.00 |
October | 2604877.21 | 0.275091E+09 | 37270433.09 | 0.00 | 37270433.09 | 0.00 | 0.00 |
November | 0.00 | 0.459478E+09 | 11193223.08 | 0.00 | 11193223.08 | 0.00 | 0.00 |
December | 0.00 | 0.509602E+09 | 1816781.89 | 0.00 | 1816781.89 | 0.00 | 0.00 |
Annual Sum or Average | 0.905967E+09 | 0.291124E+10 | 0.115342E+10 | 0.135194E+09 | 0.101823E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 24389931.96 | 1816781.89 | 0.00 | 1816781.89 | 0.00 | 0.00 |
Maximum of Months | 0.268736E+09 | 0.509602E+09 | 0.248066E+09 | 55037234.19 | 0.193028E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 32352024.27 | 0.158945E+10 | 0.134869E+09 | 77566815.08 | 57302050.97 | 0.00 | 0.00 |
February | 0.289444E+09 | 0.114229E+10 | 0.475995E+09 | 0.288838E+09 | 0.187156E+09 | 0.00 | 0.00 |
March | 0.999429E+09 | 0.949221E+09 | 0.113087E+10 | 0.662614E+09 | 0.468259E+09 | 0.00 | 0.00 |
April | 0.140994E+10 | 0.525025E+09 | 0.140218E+10 | 0.782874E+09 | 0.619310E+09 | 0.00 | 0.00 |
May | 0.193514E+10 | 0.249348E+09 | 0.170155E+10 | 0.936232E+09 | 0.765315E+09 | 0.00 | 0.00 |
June | 0.179710E+10 | 0.101492E+09 | 0.150422E+10 | 0.674814E+09 | 0.829404E+09 | 0.00 | 0.00 |
July | 0.182422E+10 | 0.118338E+09 | 0.148510E+10 | 0.697247E+09 | 0.787854E+09 | 0.00 | 0.00 |
August | 0.153691E+10 | 0.201957E+09 | 0.130472E+10 | 0.669459E+09 | 0.635259E+09 | 0.00 | 0.00 |
September | 0.882043E+09 | 0.417780E+09 | 0.871543E+09 | 0.448966E+09 | 0.422578E+09 | 0.00 | 0.00 |
October | 0.444221E+09 | 0.818707E+09 | 0.565118E+09 | 0.294972E+09 | 0.270147E+09 | 0.00 | 0.00 |
November | 51571616.30 | 0.143871E+10 | 0.206711E+09 | 0.126698E+09 | 80012760.80 | 0.00 | 0.00 |
December | 0.00 | 0.175210E+10 | 35794820.82 | 21403487.79 | 14391333.03 | 0.00 | 0.00 |
Annual Sum or Average | 0.112024E+11 | 0.930441E+10 | 0.108187E+11 | 0.568168E+10 | 0.513699E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.101492E+09 | 35794820.82 | 21403487.79 | 14391333.03 | 0.00 | 0.00 |
Maximum of Months | 0.193514E+10 | 0.175210E+10 | 0.170155E+10 | 0.936232E+09 | 0.829404E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1898272.60 | 0.167059E+10 | 48877384.73 | 15330505.74 | 33546878.99 | 0.00 | 0.00 |
February | 70332384.55 | 0.125138E+10 | 0.223807E+09 | 92969590.80 | 0.130837E+09 | 0.00 | 0.00 |
March | 0.486448E+09 | 0.100693E+10 | 0.690825E+09 | 0.304937E+09 | 0.385888E+09 | 0.00 | 0.00 |
April | 0.781895E+09 | 0.518675E+09 | 0.931919E+09 | 0.397201E+09 | 0.534718E+09 | 0.00 | 0.00 |
May | 0.152400E+10 | 0.239493E+09 | 0.141418E+10 | 0.698290E+09 | 0.715890E+09 | 0.00 | 0.00 |
June | 0.154461E+10 | 97201310.87 | 0.134402E+10 | 0.551697E+09 | 0.792319E+09 | 0.00 | 0.00 |
July | 0.152437E+10 | 0.118368E+09 | 0.128853E+10 | 0.540140E+09 | 0.748389E+09 | 0.00 | 0.00 |
August | 0.110310E+10 | 0.205100E+09 | 0.992277E+09 | 0.411199E+09 | 0.581078E+09 | 0.00 | 0.00 |
September | 0.512616E+09 | 0.421614E+09 | 0.588435E+09 | 0.224349E+09 | 0.364086E+09 | 0.00 | 0.00 |
October | 0.184978E+09 | 0.868862E+09 | 0.323766E+09 | 0.112303E+09 | 0.211463E+09 | 0.00 | 0.00 |
November | 1270184.85 | 0.156894E+10 | 69585760.46 | 20188305.78 | 49397454.68 | 0.00 | 0.00 |
December | 0.00 | 0.178406E+10 | 10449388.38 | 1936245.93 | 8513142.45 | 0.00 | 0.00 |
Annual Sum or Average | 0.773552E+10 | 0.975121E+10 | 0.792667E+10 | 0.337054E+10 | 0.455612E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 97201310.87 | 10449388.38 | 1936245.93 | 8513142.45 | 0.00 | 0.00 |
Maximum of Months | 0.154461E+10 | 0.178406E+10 | 0.141418E+10 | 0.698290E+09 | 0.792319E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 41644246.73 | 0.200327E+10 | 0.174973E+09 | 0.107858E+09 | 67115358.30 | 0.00 | 0.00 |
February | 0.289748E+09 | 0.144853E+10 | 0.540648E+09 | 0.339447E+09 | 0.201201E+09 | 0.00 | 0.00 |
March | 0.837294E+09 | 0.121449E+10 | 0.106986E+10 | 0.619919E+09 | 0.449939E+09 | 0.00 | 0.00 |
April | 0.132789E+10 | 0.705725E+09 | 0.135790E+10 | 0.683873E+09 | 0.674030E+09 | 0.00 | 0.00 |
May | 0.141444E+10 | 0.312154E+09 | 0.135576E+10 | 0.549843E+09 | 0.805918E+09 | 0.00 | 0.00 |
June | 0.152865E+10 | 0.132889E+09 | 0.135234E+10 | 0.451805E+09 | 0.900535E+09 | 0.00 | 0.00 |
July | 0.150305E+10 | 0.162391E+09 | 0.127963E+10 | 0.429191E+09 | 0.850437E+09 | 0.00 | 0.00 |
August | 0.128885E+10 | 0.276036E+09 | 0.114665E+10 | 0.483847E+09 | 0.662805E+09 | 0.00 | 0.00 |
September | 0.775056E+09 | 0.547777E+09 | 0.813528E+09 | 0.390316E+09 | 0.423212E+09 | 0.00 | 0.00 |
October | 0.391908E+09 | 0.103640E+10 | 0.579740E+09 | 0.316570E+09 | 0.263170E+09 | 0.00 | 0.00 |
November | 85992146.61 | 0.180696E+10 | 0.286135E+09 | 0.184585E+09 | 0.101550E+09 | 0.00 | 0.00 |
December | 283828.78 | 0.220358E+10 | 51795383.19 | 33737370.12 | 18058013.07 | 0.00 | 0.00 |
Annual Sum or Average | 0.948480E+10 | 0.118502E+11 | 0.100090E+11 | 0.459099E+10 | 0.541797E+10 | 0.00 | 0.00 |
Minimum of Months | 283828.78 | 0.132889E+09 | 51795383.19 | 33737370.12 | 18058013.07 | 0.00 | 0.00 |
Maximum of Months | 0.152865E+10 | 0.220358E+10 | 0.135790E+10 | 0.683873E+09 | 0.900535E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 15012448.75 | 0.159161E+10 | 0.112710E+09 | 65506021.51 | 47203819.41 | 0.00 | 0.00 |
February | 0.180925E+09 | 0.114588E+10 | 0.385608E+09 | 0.231929E+09 | 0.153680E+09 | 0.00 | 0.00 |
March | 0.678192E+09 | 0.951305E+09 | 0.873575E+09 | 0.506643E+09 | 0.366933E+09 | 0.00 | 0.00 |
April | 0.145583E+10 | 0.549945E+09 | 0.141782E+10 | 0.800800E+09 | 0.617020E+09 | 0.00 | 0.00 |
May | 0.145426E+10 | 0.266271E+09 | 0.132768E+10 | 0.639378E+09 | 0.688299E+09 | 0.00 | 0.00 |
June | 0.154394E+10 | 0.115771E+09 | 0.131066E+10 | 0.550743E+09 | 0.759918E+09 | 0.00 | 0.00 |
July | 0.143773E+10 | 0.127524E+09 | 0.119286E+10 | 0.476491E+09 | 0.716372E+09 | 0.00 | 0.00 |
August | 0.125396E+10 | 0.210772E+09 | 0.108557E+10 | 0.523234E+09 | 0.562332E+09 | 0.00 | 0.00 |
September | 0.705212E+09 | 0.423239E+09 | 0.724764E+09 | 0.370217E+09 | 0.354547E+09 | 0.00 | 0.00 |
October | 0.273805E+09 | 0.816612E+09 | 0.429109E+09 | 0.224934E+09 | 0.204174E+09 | 0.00 | 0.00 |
November | 56123651.49 | 0.142953E+10 | 0.206334E+09 | 0.126750E+09 | 79584391.43 | 0.00 | 0.00 |
December | 0.00 | 0.174643E+10 | 32673305.95 | 19979472.27 | 12693833.69 | 0.00 | 0.00 |
Annual Sum or Average | 0.905498E+10 | 0.937488E+10 | 0.909936E+10 | 0.453660E+10 | 0.456276E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.115771E+09 | 32673305.95 | 19979472.27 | 12693833.69 | 0.00 | 0.00 |
Maximum of Months | 0.154394E+10 | 0.174643E+10 | 0.141782E+10 | 0.800800E+09 | 0.759918E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.169030E+10 | 26718359.59 | 3269712.17 | 23448647.42 | 0.00 | 0.00 |
February | 10459592.78 | 0.130941E+10 | 0.133420E+09 | 36059635.70 | 97360660.42 | 0.00 | 0.00 |
March | 0.192390E+09 | 0.104424E+10 | 0.433527E+09 | 0.148966E+09 | 0.284562E+09 | 0.00 | 0.00 |
April | 0.840821E+09 | 0.550102E+09 | 0.947555E+09 | 0.415128E+09 | 0.532427E+09 | 0.00 | 0.00 |
May | 0.101826E+10 | 0.231213E+09 | 0.104031E+10 | 0.401436E+09 | 0.638875E+09 | 0.00 | 0.00 |
June | 0.126495E+10 | 97215469.41 | 0.115046E+10 | 0.427626E+09 | 0.722833E+09 | 0.00 | 0.00 |
July | 0.112630E+10 | 0.117789E+09 | 0.996291E+09 | 0.319384E+09 | 0.676907E+09 | 0.00 | 0.00 |
August | 0.805307E+09 | 0.204455E+09 | 0.773125E+09 | 0.264974E+09 | 0.508151E+09 | 0.00 | 0.00 |
September | 0.342993E+09 | 0.429028E+09 | 0.441656E+09 | 0.145601E+09 | 0.296055E+09 | 0.00 | 0.00 |
October | 52962647.49 | 0.909163E+09 | 0.187756E+09 | 42266213.40 | 0.145490E+09 | 0.00 | 0.00 |
November | 2230903.84 | 0.155626E+10 | 69209075.72 | 20239990.41 | 48969085.31 | 0.00 | 0.00 |
December | 0.00 | 0.177841E+10 | 7327873.51 | 512230.40 | 6815643.11 | 0.00 | 0.00 |
Annual Sum or Average | 0.565668E+10 | 0.991760E+10 | 0.620735E+10 | 0.222546E+10 | 0.398189E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 97215469.41 | 7327873.51 | 512230.40 | 6815643.11 | 0.00 | 0.00 |
Maximum of Months | 0.126495E+10 | 0.177841E+10 | 0.115046E+10 | 0.427626E+09 | 0.722833E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 79520464.71 | 0.794045E+09 | 0.137093E+09 | 91275520.48 | 45817293.31 | 0.00 | 0.00 |
February | 0.349949E+09 | 0.577766E+09 | 0.413690E+09 | 0.287260E+09 | 0.126429E+09 | 0.00 | 0.00 |
March | 0.767553E+09 | 0.495324E+09 | 0.775365E+09 | 0.524590E+09 | 0.250775E+09 | 0.00 | 0.00 |
April | 0.102402E+10 | 0.301408E+09 | 0.919396E+09 | 0.572179E+09 | 0.347217E+09 | 0.00 | 0.00 |
May | 0.911283E+09 | 0.147050E+09 | 0.784361E+09 | 0.407133E+09 | 0.377228E+09 | 0.00 | 0.00 |
June | 0.837290E+09 | 62327972.47 | 0.689656E+09 | 0.281446E+09 | 0.408211E+09 | 0.00 | 0.00 |
July | 0.855320E+09 | 67617451.01 | 0.685565E+09 | 0.296805E+09 | 0.388760E+09 | 0.00 | 0.00 |
August | 0.867204E+09 | 0.112285E+09 | 0.714275E+09 | 0.394111E+09 | 0.320165E+09 | 0.00 | 0.00 |
September | 0.600606E+09 | 0.224023E+09 | 0.551821E+09 | 0.329865E+09 | 0.221956E+09 | 0.00 | 0.00 |
October | 0.386396E+09 | 0.417358E+09 | 0.422283E+09 | 0.267901E+09 | 0.154383E+09 | 0.00 | 0.00 |
November | 0.146134E+09 | 0.709999E+09 | 0.221624E+09 | 0.156207E+09 | 65417484.74 | 0.00 | 0.00 |
December | 7227570.70 | 0.879928E+09 | 40501673.90 | 28550578.47 | 11951095.42 | 0.00 | 0.00 |
Annual Sum or Average | 0.683251E+10 | 0.478913E+10 | 0.635563E+10 | 0.363732E+10 | 0.271831E+10 | 0.00 | 0.00 |
Minimum of Months | 7227570.70 | 62327972.47 | 40501673.90 | 28550578.47 | 11951095.42 | 0.00 | 0.00 |
Maximum of Months | 0.102402E+10 | 0.879928E+09 | 0.919396E+09 | 0.572179E+09 | 0.408211E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.426393E+10 | 52395798.00 | 0.00 | 52395798.00 | 0.00 | 0.00 |
February | 0.00 | 0.344426E+10 | 0.209201E+09 | 0.00 | 0.209201E+09 | 0.00 | 0.00 |
March | 45419103.36 | 0.285317E+10 | 0.620424E+09 | 105278.48 | 0.620319E+09 | 0.00 | 0.00 |
April | 0.463676E+09 | 0.144606E+10 | 0.109634E+10 | 31279225.42 | 0.106506E+10 | 0.00 | 0.00 |
May | 0.147142E+10 | 0.589404E+09 | 0.173209E+10 | 0.277624E+09 | 0.145446E+10 | 0.00 | 0.00 |
June | 0.235094E+10 | 0.235799E+09 | 0.217020E+10 | 0.481494E+09 | 0.168871E+10 | 0.00 | 0.00 |
July | 0.212932E+10 | 0.289274E+09 | 0.189609E+10 | 0.316873E+09 | 0.157922E+10 | 0.00 | 0.00 |
August | 0.113750E+10 | 0.517812E+09 | 0.122207E+10 | 73251116.88 | 0.114882E+10 | 0.00 | 0.00 |
September | 0.276741E+09 | 0.115993E+10 | 0.652031E+09 | 2117014.40 | 0.649914E+09 | 0.00 | 0.00 |
October | 21586760.77 | 0.244263E+10 | 0.326061E+09 | 0.00 | 0.326061E+09 | 0.00 | 0.00 |
November | 0.00 | 0.400274E+10 | 97924012.29 | 0.00 | 97924012.29 | 0.00 | 0.00 |
December | 0.00 | 0.444745E+10 | 15894132.59 | 0.00 | 15894132.59 | 0.00 | 0.00 |
Annual Sum or Average | 0.789661E+10 | 0.256925E+11 | 0.100907E+11 | 0.118274E+10 | 0.890798E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.235799E+09 | 15894132.59 | 0.00 | 15894132.59 | 0.00 | 0.00 |
Maximum of Months | 0.235094E+10 | 0.444745E+10 | 0.217020E+10 | 0.481494E+09 | 0.168871E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.432257E+10 | 52395798.00 | 0.00 | 52395798.00 | 0.00 | 0.00 |
February | 0.00 | 0.349573E+10 | 0.209201E+09 | 0.00 | 0.209201E+09 | 0.00 | 0.00 |
March | 41401029.33 | 0.291251E+10 | 0.620424E+09 | 105278.48 | 0.620319E+09 | 0.00 | 0.00 |
April | 0.443006E+09 | 0.148821E+10 | 0.109634E+10 | 31279225.42 | 0.106506E+10 | 0.00 | 0.00 |
May | 0.143610E+10 | 0.606724E+09 | 0.173209E+10 | 0.277624E+09 | 0.145446E+10 | 0.00 | 0.00 |
June | 0.231510E+10 | 0.245483E+09 | 0.217020E+10 | 0.481494E+09 | 0.168871E+10 | 0.00 | 0.00 |
July | 0.209470E+10 | 0.301303E+09 | 0.189609E+10 | 0.316873E+09 | 0.157922E+10 | 0.00 | 0.00 |
August | 0.110883E+10 | 0.537154E+09 | 0.122207E+10 | 73251116.88 | 0.114882E+10 | 0.00 | 0.00 |
September | 0.260650E+09 | 0.120656E+10 | 0.652031E+09 | 2117014.40 | 0.649914E+09 | 0.00 | 0.00 |
October | 18107006.94 | 0.250905E+10 | 0.326061E+09 | 0.00 | 0.326061E+09 | 0.00 | 0.00 |
November | 0.00 | 0.405661E+10 | 97924012.29 | 0.00 | 97924012.29 | 0.00 | 0.00 |
December | 0.00 | 0.450179E+10 | 15894132.59 | 0.00 | 15894132.59 | 0.00 | 0.00 |
Annual Sum or Average | 0.771790E+10 | 0.261837E+11 | 0.100907E+11 | 0.118274E+10 | 0.890798E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.245483E+09 | 15894132.59 | 0.00 | 15894132.59 | 0.00 | 0.00 |
Maximum of Months | 0.231510E+10 | 0.450179E+10 | 0.217020E+10 | 0.481494E+09 | 0.168871E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 37737953.02 | 0.284546E+10 | 0.183740E+09 | 92895143.50 | 90845228.58 | 0.00 | 0.00 |
February | 0.416094E+09 | 0.205915E+10 | 0.699774E+09 | 0.381795E+09 | 0.317979E+09 | 0.00 | 0.00 |
March | 0.172143E+10 | 0.172995E+10 | 0.182161E+10 | 0.967508E+09 | 0.854105E+09 | 0.00 | 0.00 |
April | 0.264463E+10 | 0.979178E+09 | 0.233399E+10 | 0.118002E+10 | 0.115397E+10 | 0.00 | 0.00 |
May | 0.406232E+10 | 0.466531E+09 | 0.311556E+10 | 0.163443E+10 | 0.148113E+10 | 0.00 | 0.00 |
June | 0.400452E+10 | 0.201323E+09 | 0.284809E+10 | 0.122644E+10 | 0.162164E+10 | 0.00 | 0.00 |
July | 0.403956E+10 | 0.235170E+09 | 0.277348E+10 | 0.123732E+10 | 0.153617E+10 | 0.00 | 0.00 |
August | 0.326636E+10 | 0.377224E+09 | 0.229688E+10 | 0.108060E+10 | 0.121628E+10 | 0.00 | 0.00 |
September | 0.180915E+10 | 0.715402E+09 | 0.145991E+10 | 0.673283E+09 | 0.786625E+09 | 0.00 | 0.00 |
October | 0.799832E+09 | 0.142521E+10 | 0.888845E+09 | 0.407259E+09 | 0.481586E+09 | 0.00 | 0.00 |
November | 47257584.40 | 0.256782E+10 | 0.276289E+09 | 0.146883E+09 | 0.129405E+09 | 0.00 | 0.00 |
December | 0.00 | 0.310736E+10 | 46243047.61 | 23339458.72 | 22903588.89 | 0.00 | 0.00 |
Annual Sum or Average | 0.228489E+11 | 0.167098E+11 | 0.187444E+11 | 0.905177E+10 | 0.969265E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.201323E+09 | 46243047.61 | 23339458.72 | 22903588.89 | 0.00 | 0.00 |
Maximum of Months | 0.406232E+10 | 0.310736E+10 | 0.311556E+10 | 0.163443E+10 | 0.162164E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118083E+09 | 0.350341E+10 | 0.366938E+09 | 0.232347E+09 | 0.134592E+09 | 0.00 | 0.00 |
February | 0.710013E+09 | 0.253481E+10 | 0.112478E+10 | 0.731237E+09 | 0.393547E+09 | 0.00 | 0.00 |
March | 0.184707E+10 | 0.214101E+10 | 0.218642E+10 | 0.133541E+10 | 0.851008E+09 | 0.00 | 0.00 |
April | 0.273656E+10 | 0.128936E+10 | 0.271620E+10 | 0.146724E+10 | 0.124896E+10 | 0.00 | 0.00 |
May | 0.268812E+10 | 0.603784E+09 | 0.259040E+10 | 0.113155E+10 | 0.145885E+10 | 0.00 | 0.00 |
June | 0.277875E+10 | 0.261262E+09 | 0.249951E+10 | 0.881492E+09 | 0.161802E+10 | 0.00 | 0.00 |
July | 0.276764E+10 | 0.318505E+09 | 0.239513E+10 | 0.864158E+09 | 0.153097E+10 | 0.00 | 0.00 |
August | 0.249651E+10 | 0.540425E+09 | 0.223716E+10 | 0.102834E+10 | 0.120882E+10 | 0.00 | 0.00 |
September | 0.158421E+10 | 0.101915E+10 | 0.162821E+10 | 0.840415E+09 | 0.787792E+09 | 0.00 | 0.00 |
October | 0.880445E+09 | 0.183805E+10 | 0.118672E+10 | 0.681955E+09 | 0.504763E+09 | 0.00 | 0.00 |
November | 0.235156E+09 | 0.314272E+10 | 0.597725E+09 | 0.397632E+09 | 0.200092E+09 | 0.00 | 0.00 |
December | 3832976.99 | 0.387189E+10 | 0.108548E+09 | 72677014.83 | 35870688.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.188464E+11 | 0.210644E+11 | 0.196377E+11 | 0.966444E+10 | 0.997327E+10 | 0.00 | 0.00 |
Minimum of Months | 3832976.99 | 0.261262E+09 | 0.108548E+09 | 72677014.83 | 35870688.26 | 0.00 | 0.00 |
Maximum of Months | 0.277875E+10 | 0.387189E+10 | 0.271620E+10 | 0.146724E+10 | 0.161802E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770429E+10 | -0.754277E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161519206.9 | 81.21 | 0.00 | 0.00 |
February | 0.696181E+10 | -0.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145841884.6 | 81.21 | 0.00 | 0.00 |
March | 0.770288E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161422803.2 | 81.21 | 0.00 | 0.00 |
April | 0.746480E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156207525.4 | 81.21 | 0.00 | 0.00 |
May | 0.770421E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161414473.7 | 81.21 | 0.00 | 0.00 |
June | 0.745674E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156206303.3 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161411933.5 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161412947.0 | 81.21 | 0.00 | 0.00 |
September | 0.746614E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156206838.2 | 81.21 | 0.00 | 0.00 |
October | 0.770285E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161414149.2 | 81.21 | 0.00 | 0.00 |
November | 0.744866E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156232325.3 | 81.21 | 0.00 | 0.00 |
December | 0.771231E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161461200.4 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907412E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190075E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696181E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161519206.9 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771231E+10 | -0.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145841884.6 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.129588E+12 | -0.127854E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173372E+10 | 79.61 | 0.00 | 0.00 |
February | 0.117057E+12 | -0.115477E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158068E+10 | 79.61 | 0.00 | 0.00 |
March | 0.129601E+12 | -0.127849E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175285E+10 | 79.61 | 0.00 | 0.00 |
April | 0.125416E+12 | -0.123726E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169049E+10 | 79.61 | 0.00 | 0.00 |
May | 0.129531E+12 | -0.127784E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174767E+10 | 79.72 | 0.00 | 0.00 |
June | 0.125046E+12 | -0.123346E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170038E+10 | 80.30 | 0.00 | 0.00 |
July | 0.128899E+12 | -0.127142E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175655E+10 | 80.85 | 0.00 | 0.00 |
August | 0.128691E+12 | -0.126944E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174758E+10 | 81.20 | 0.00 | 0.00 |
September | 0.124510E+12 | -0.122827E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168286E+10 | 81.25 | 0.00 | 0.00 |
October | 0.128809E+12 | -0.127079E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173023E+10 | 80.97 | 0.00 | 0.00 |
November | 0.124931E+12 | -0.123262E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.166823E+10 | 80.46 | 0.00 | 0.00 |
December | 0.129442E+12 | -0.127718E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172458E+10 | 79.85 | 0.00 | 0.00 |
Annual Sum or Average | 0.152152E+13 | -0.150101E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205158E+11 | 80.26 | 0.00 | 0.00 |
Minimum of Months | 0.117057E+12 | -0.127854E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.175655E+10 | 79.61 | 0.00 | 0.00 |
Maximum of Months | 0.129601E+12 | -0.115477E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158068E+10 | 81.25 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.877390E+11 | -0.861972E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154177E+10 | 58.99 | 0.00 | 0.00 |
February | 0.792838E+11 | -0.778708E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.141301E+10 | 58.99 | 0.00 | 0.00 |
March | 0.878429E+11 | -0.862747E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156827E+10 | 58.99 | 0.00 | 0.00 |
April | 0.849544E+11 | -0.834448E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.150964E+10 | 58.99 | 0.00 | 0.00 |
May | 0.871491E+11 | -0.855929E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155624E+10 | 58.99 | 0.00 | 0.00 |
June | 0.812773E+11 | -0.797819E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.149545E+10 | 58.99 | 0.00 | 0.00 |
July | 0.807876E+11 | -0.792663E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152132E+10 | 58.99 | 0.00 | 0.00 |
August | 0.788778E+11 | -0.773836E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149420E+10 | 58.98 | 0.00 | 0.00 |
September | 0.760422E+11 | -0.746095E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.143268E+10 | 58.98 | 0.00 | 0.00 |
October | 0.800508E+11 | -0.785710E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147972E+10 | 58.99 | 0.00 | 0.00 |
November | 0.802340E+11 | -0.787899E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.144409E+10 | 58.99 | 0.00 | 0.00 |
December | 0.863375E+11 | -0.848187E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151880E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.990576E+12 | -0.972601E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.179752E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.760422E+11 | -0.862747E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.156827E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.878429E+11 | -0.746095E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.141301E+10 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.90 | 0.86 | 10-JAN-10:00 | 574.83 | 26.35 | 72.17 | 74.33 | 408.93 | 27.92 | 72.67 | 43.00 |
February | 205.83 | 0.87 | 0.86 | 01-FEB-11:50 | 2146.87 | 35.17 | 190.33 | 182.00 | 1724.43 | 36.18 | 191.33 | 154.83 |
March | 329.50 | 0.87 | 0.86 | 01-MAR-08:39 | 5075.51 | 33.29 | 283.33 | 307.33 | 2725.07 | 31.18 | 283.33 | 272.33 |
April | 421.83 | 0.87 | 0.86 | 01-APR-07:49 | 7136.28 | 30.35 | 272.83 | 386.17 | 787.27 | 21.92 | 305.67 | 321.00 |
May | 545.00 | 0.88 | 0.86 | 01-MAY-05:49 | 3204.18 | 21.47 | 177.00 | 457.50 | 581.02 | 20.58 | 325.17 | 361.67 |
June | 583.50 | 0.88 | 0.86 | 01-JUN-05:40 | 1417.82 | 18.34 | 156.50 | 481.33 | 555.06 | 20.17 | 311.33 | 371.50 |
July | 562.83 | 0.88 | 0.86 | 01-JUL-05:10 | 1759.90 | 19.00 | 151.67 | 478.50 | 565.76 | 20.28 | 314.83 | 366.50 |
August | 467.17 | 0.88 | 0.86 | 01-AUG-06:10 | 4901.94 | 25.99 | 236.00 | 409.33 | 627.27 | 20.86 | 271.67 | 330.00 |
September | 356.33 | 0.87 | 0.86 | 01-SEP-06:40 | 4159.93 | 30.91 | 277.50 | 323.83 | 1125.69 | 23.34 | 221.17 | 266.67 |
October | 265.50 | 0.87 | 0.86 | 01-OCT-07:49 | 2258.87 | 32.89 | 241.17 | 238.83 | 1774.34 | 33.88 | 244.50 | 209.00 |
November | 135.83 | 0.88 | 0.86 | 01-NOV-09:50 | 845.09 | 32.53 | 117.50 | 126.50 | 617.82 | 33.80 | 117.67 | 91.00 |
December | 71.17 | 0.94 | 0.86 | 05-DEC-11:20 | 136.87 | 5.67 | 0.00 | 11.33 | 81.03 | 8.76 | 0.00 | 0.83 |
Annual Sum or Average | 4053.17 | 0.88 | 3268.50 | 25.58 | 2176.00 | 3477.00 | 948.22 | 23.85 | 2659.33 | 2788.33 | ||
Minimum of Months | 71.17 | 0.87 | 0.86 | 136.87 | 5.67 | 0.00 | 11.33 | 81.03 | 8.76 | 0.00 | 0.83 | |
Maximum of Months | 583.50 | 0.94 | 0.86 | 7136.28 | 35.17 | 283.33 | 481.33 | 2725.07 | 36.18 | 325.17 | 371.50 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.37 | 0.22 | 03-JAN-11:50 | 675.72 | 26.83 | 72.50 | 86.00 | 508.21 | 28.37 | 72.67 | 61.17 |
February | 205.83 | 0.28 | 0.22 | 01-FEB-11:20 | 2418.17 | 35.29 | 190.33 | 190.17 | 1994.94 | 36.29 | 192.33 | 174.67 |
March | 329.50 | 0.26 | 0.22 | 01-MAR-08:30 | 5482.07 | 33.48 | 286.50 | 313.67 | 3132.52 | 31.22 | 276.50 | 295.50 |
April | 421.83 | 0.27 | 0.22 | 01-APR-07:19 | 7562.54 | 30.76 | 288.67 | 401.83 | 1211.96 | 21.95 | 300.83 | 362.00 |
May | 545.00 | 0.29 | 0.22 | 01-MAY-04:00 | 3502.88 | 22.00 | 205.83 | 479.33 | 878.57 | 20.84 | 336.50 | 427.83 |
June | 583.50 | 0.30 | 0.22 | 01-JUN-04:49 | 1670.72 | 18.92 | 158.00 | 512.33 | 806.92 | 20.58 | 342.67 | 443.83 |
July | 562.83 | 0.29 | 0.22 | 01-JUL-04:30 | 2019.32 | 19.58 | 175.17 | 505.50 | 824.49 | 20.66 | 326.33 | 433.67 |
August | 467.17 | 0.28 | 0.22 | 01-AUG-04:00 | 5213.60 | 26.54 | 261.50 | 429.50 | 938.32 | 21.13 | 283.33 | 383.33 |
September | 356.33 | 0.28 | 0.22 | 01-SEP-06:10 | 4454.49 | 31.18 | 281.83 | 336.17 | 1417.69 | 23.63 | 234.83 | 300.17 |
October | 265.50 | 0.27 | 0.22 | 01-OCT-07:40 | 2498.81 | 33.02 | 242.17 | 248.33 | 2012.33 | 33.99 | 246.00 | 227.67 |
November | 135.83 | 0.29 | 0.22 | 01-NOV-09:30 | 994.65 | 32.77 | 117.50 | 137.50 | 766.86 | 34.01 | 117.67 | 112.17 |
December | 71.17 | 0.60 | 0.22 | 04-DEC-11:09 | 154.59 | 7.11 | 0.00 | 23.83 | 97.57 | 10.14 | 0.00 | 7.83 |
Annual Sum or Average | 4053.17 | 0.29 | 3557.85 | 26.02 | 2280.00 | 3664.17 | 1236.53 | 24.12 | 2729.67 | 3229.83 | ||
Minimum of Months | 71.17 | 0.26 | 0.22 | 154.59 | 7.11 | 0.00 | 23.83 | 97.57 | 10.14 | 0.00 | 7.83 | |
Maximum of Months | 583.50 | 0.60 | 0.22 | 7562.54 | 35.29 | 288.67 | 512.33 | 3132.52 | 36.29 | 342.67 | 443.83 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.84 | 0.66 | 31-JAN-11:30 | 119.83 | 7.97 | 0.00 | 12.17 | 57.96 | 11.51 | 0.00 | 0.00 |
February | 205.83 | 0.71 | 0.60 | 05-FEB-12:20 | 264.91 | 12.35 | 0.00 | 139.67 | 126.49 | 15.90 | 0.00 | 17.33 |
March | 329.50 | 0.64 | 0.60 | 01-MAR-09:30 | 471.58 | 15.38 | 0.00 | 289.17 | 221.65 | 18.78 | 3.00 | 186.83 |
April | 421.83 | 0.62 | 0.60 | 01-APR-07:40 | 596.33 | 17.55 | 10.17 | 407.33 | 296.58 | 20.89 | 72.83 | 346.17 |
May | 545.00 | 0.62 | 0.60 | 01-MAY-04:49 | 751.80 | 19.62 | 89.00 | 505.00 | 362.25 | 23.20 | 213.67 | 463.17 |
June | 583.50 | 0.62 | 0.60 | 01-JUN-03:30 | 937.57 | 21.18 | 149.00 | 546.33 | 441.02 | 23.50 | 287.67 | 502.83 |
July | 562.83 | 0.62 | 0.60 | 01-JUL-03:30 | 846.81 | 20.42 | 125.33 | 536.00 | 381.38 | 22.73 | 225.17 | 473.17 |
August | 467.17 | 0.63 | 0.60 | 01-AUG-04:40 | 635.34 | 17.84 | 35.00 | 435.33 | 302.90 | 21.44 | 103.00 | 356.50 |
September | 356.33 | 0.65 | 0.60 | 01-SEP-05:00 | 462.55 | 15.27 | 0.00 | 316.67 | 210.54 | 18.54 | 5.33 | 189.00 |
October | 265.50 | 0.68 | 0.60 | 01-OCT-07:00 | 330.00 | 13.35 | 0.00 | 211.50 | 144.48 | 16.69 | 0.00 | 22.17 |
November | 135.83 | 0.79 | 0.60 | 06-NOV-12:30 | 162.37 | 9.90 | 0.00 | 46.00 | 76.57 | 13.70 | 0.00 | 0.00 |
December | 71.17 | 0.94 | 0.82 | 04-DEC-11:30 | 44.09 | 3.23 | 0.00 | 0.00 | 22.01 | 6.32 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.65 | 612.45 | 17.10 | 408.50 | 3445.17 | 287.86 | 20.24 | 910.67 | 2557.17 | ||
Minimum of Months | 71.17 | 0.62 | 0.60 | 44.09 | 3.23 | 0.00 | 0.00 | 22.01 | 6.32 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.94 | 0.82 | 937.57 | 21.18 | 149.00 | 546.33 | 441.02 | 23.50 | 287.67 | 502.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.84 | 0.66 | 31-JAN-11:30 | 119.83 | 7.97 | 0.00 | 12.17 | 57.96 | 11.51 | 0.00 | 0.00 |
February | 205.83 | 0.71 | 0.60 | 05-FEB-12:20 | 264.91 | 12.35 | 0.00 | 139.67 | 126.49 | 15.90 | 0.00 | 17.33 |
March | 329.50 | 0.64 | 0.60 | 01-MAR-09:30 | 471.58 | 15.38 | 0.00 | 289.17 | 221.65 | 18.78 | 3.00 | 186.83 |
April | 421.83 | 0.62 | 0.60 | 01-APR-07:40 | 596.33 | 17.55 | 10.17 | 407.33 | 296.58 | 20.89 | 73.00 | 346.17 |
May | 545.00 | 0.62 | 0.60 | 01-MAY-04:49 | 751.80 | 19.62 | 89.00 | 505.00 | 362.25 | 23.20 | 213.67 | 463.17 |
June | 583.50 | 0.62 | 0.60 | 01-JUN-03:30 | 937.57 | 21.18 | 149.00 | 546.33 | 441.02 | 23.50 | 287.67 | 502.83 |
July | 562.83 | 0.62 | 0.60 | 01-JUL-03:30 | 846.81 | 20.42 | 125.33 | 536.00 | 381.38 | 22.73 | 225.17 | 473.17 |
August | 467.17 | 0.63 | 0.60 | 01-AUG-04:40 | 635.34 | 17.84 | 35.00 | 435.33 | 302.90 | 21.44 | 103.00 | 356.50 |
September | 356.33 | 0.65 | 0.60 | 01-SEP-05:00 | 462.55 | 15.27 | 0.00 | 316.67 | 210.54 | 18.54 | 5.33 | 189.00 |
October | 265.50 | 0.68 | 0.60 | 01-OCT-07:00 | 330.00 | 13.35 | 0.00 | 211.50 | 144.48 | 16.69 | 0.00 | 22.17 |
November | 135.83 | 0.79 | 0.60 | 06-NOV-12:30 | 162.37 | 9.90 | 0.00 | 46.00 | 76.57 | 13.70 | 0.00 | 0.00 |
December | 71.17 | 0.94 | 0.82 | 04-DEC-11:30 | 44.09 | 3.23 | 0.00 | 0.00 | 22.01 | 6.32 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.65 | 612.45 | 17.10 | 408.50 | 3445.17 | 287.86 | 20.24 | 910.83 | 2557.17 | ||
Minimum of Months | 71.17 | 0.62 | 0.60 | 44.09 | 3.23 | 0.00 | 0.00 | 22.01 | 6.32 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.94 | 0.82 | 937.57 | 21.18 | 149.00 | 546.33 | 441.02 | 23.50 | 287.67 | 502.83 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.276081E+12 | 373210.10 | 12-JAN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242711E+12 | 356814.75 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127665E+12 | 345790.96 | 01-MAR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.632566E+11 | 109446.71 | 10-APR-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.406960E+11 | 95656.33 | 27-MAY-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.287538E+10 | 64215.61 | 02-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130801E+10 | 28101.20 | 31-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110795E+11 | 103116.66 | 31-AUG-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.733214E+11 | 104685.95 | 29-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.711826E+11 | 109118.75 | 14-OCT-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.260753E+12 | 352420.76 | 30-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.342364E+12 | 359739.73 | 15-DEC-07:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151329E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.130801E+10 | 28101.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.342364E+12 | 373210.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.530355E+09 | 6792.49 | 12-JAN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.384526E+09 | 6471.68 | 27-FEB-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122939E+09 | 2514.03 | 01-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.530355E+09 | 6792.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.581441E+10 | 4560.49 | 12-JAN-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.357954E+10 | 4429.27 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197105E+10 | 4183.05 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.359434E+09 | 1559.51 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15526340.28 | 458.73 | 28-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1002054.07 | 166.49 | 30-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.241917E+09 | 1016.10 | 30-SEP-06:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176255E+10 | 2176.05 | 30-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.504439E+10 | 4214.13 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.657227E+10 | 4390.20 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.253621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.657227E+10 | 4560.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138529E+10 | 1546.88 | 12-JAN-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.858508E+09 | 1503.51 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.394894E+09 | 1079.22 | 01-MAR-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29317657.62 | 529.41 | 03-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10219450.03 | 274.49 | 25-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.239576E+09 | 671.70 | 29-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110728E+10 | 1432.28 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152808E+10 | 1490.62 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.555316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152808E+10 | 1546.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173018E+10 | 2067.60 | 12-JAN-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111966E+10 | 2009.11 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.436866E+09 | 1507.48 | 01-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11852877.53 | 301.70 | 03-APR-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95018495.31 | 504.19 | 31-OCT-09:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131358E+10 | 1720.25 | 30-NOV-10:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195592E+10 | 1991.69 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.666307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.195592E+10 | 2067.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.299126E+10 | 1662.92 | 12-JAN-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.245883E+10 | 1615.74 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209444E+10 | 1527.07 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.732290E+09 | 961.28 | 03-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23991729.75 | 320.06 | 27-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 910174.10 | 202.57 | 31-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231109E+09 | 583.96 | 30-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134752E+10 | 1049.82 | 27-OCT-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.277347E+10 | 1538.25 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.318442E+10 | 1601.67 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.318442E+10 | 1662.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.132778E+11 | 12035.94 | 12-JAN-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.784396E+10 | 11698.17 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.353267E+10 | 10343.61 | 01-MAR-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.748477E+09 | 5620.89 | 03-APR-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76710763.91 | 3185.62 | 27-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 44896117.20 | 1921.73 | 27-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30185571.01 | 2995.09 | 05-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78834890.33 | 2674.43 | 07-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.949468E+09 | 4681.58 | 27-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.375947E+10 | 7719.18 | 30-OCT-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113941E+11 | 11143.45 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149128E+11 | 11597.77 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.566494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 30185571.01 | 1921.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149128E+11 | 12035.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173344E+11 | 29386.87 | 12-JAN-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.847825E+10 | 27945.09 | 27-FEB-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225701E+10 | 18472.17 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148626E+09 | 6455.25 | 04-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20475331.01 | 2912.25 | 27-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179811E+10 | 11212.96 | 29-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126249E+11 | 27212.48 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185143E+11 | 28319.53 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.611761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.185143E+11 | 29386.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.213043E+11 | 13221.94 | 12-JAN-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148666E+11 | 12847.15 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.895259E+10 | 11818.23 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143036E+10 | 6263.28 | 03-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101788E+10 | 4598.25 | 27-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.828138E+10 | 8846.03 | 30-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190750E+11 | 12231.62 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231428E+11 | 12735.39 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.980710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.231428E+11 | 13221.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115680E+11 | 8667.71 | 12-JAN-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.780043E+10 | 8422.13 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.434270E+10 | 7960.60 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.628384E+09 | 3582.33 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113185E+09 | 1480.85 | 30-SEP-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304574E+10 | 4258.46 | 27-OCT-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106005E+11 | 8018.97 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129478E+11 | 8349.01 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.510468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129478E+11 | 8667.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.623401E+10 | 14119.65 | 12-JAN-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.397823E+10 | 13550.90 | 27-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.216717E+10 | 9408.07 | 01-MAR-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.424603E+09 | 5115.49 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19653608.25 | 2685.72 | 02-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 318558.12 | 530.93 | 02-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1304222.49 | 811.33 | 31-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19125783.75 | 3364.40 | 31-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148582E+09 | 4343.79 | 28-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133177E+10 | 5657.80 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.479534E+10 | 13078.44 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.582636E+10 | 13608.68 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.249465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 318558.12 | 530.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.623401E+10 | 14119.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.454455E+10 | 14243.02 | 12-JAN-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246566E+10 | 13546.63 | 27-FEB-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.958061E+09 | 8022.29 | 01-MAR-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88176139.38 | 3430.51 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 323537.72 | 476.58 | 02-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3096685.33 | 2514.32 | 31-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7351548.96 | 2394.41 | 28-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.420131E+09 | 3841.75 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.309800E+10 | 12100.71 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.397340E+10 | 13652.60 | 15-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.454455E+10 | 14243.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 7134034.86 | 1285.92 | 12-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7134034.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7134034.86 | 1285.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.275460E+11 | 42369.95 | 12-JAN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.243633E+11 | 41625.35 | 27-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141195E+11 | 39115.13 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.211243E+10 | 9202.18 | 03-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9958.87 | 0.62 | 14-MAY-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25530.76 | 0.63 | 28-JUN-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30044.83 | 0.64 | 13-JUL-23:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2765664.03 | 497.09 | 31-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118221E+09 | 2133.03 | 29-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.417806E+10 | 9436.78 | 27-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.266023E+11 | 39496.77 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.329465E+11 | 40833.59 | 15-DEC-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9958.87 | 0.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.329465E+11 | 42369.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123620E+11 | 8805.26 | 22-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.903707E+10 | 8806.33 | 09-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.606276E+10 | 8804.25 | 10-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150197E+10 | 8803.48 | 05-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123359E+09 | 5131.86 | 01-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10819188.38 | 4764.30 | 08-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13403439.01 | 4877.46 | 06-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 61912437.55 | 5429.39 | 19-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113468E+10 | 8738.30 | 28-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.510992E+10 | 8806.47 | 20-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112556E+11 | 8803.93 | 02-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134376E+11 | 8805.58 | 24-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.601110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10819188.38 | 4764.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.134376E+11 | 8806.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126773E+11 | 8562.87 | 22-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100999E+11 | 8564.02 | 09-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.761930E+10 | 8562.38 | 20-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215148E+10 | 8560.98 | 05-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159385E+09 | 4700.51 | 01-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6943824.78 | 4392.28 | 06-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9658459.22 | 4871.98 | 05-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 83377725.73 | 4977.87 | 14-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151811E+10 | 8558.99 | 29-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.598699E+10 | 8564.16 | 20-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118096E+11 | 8561.45 | 02-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135499E+11 | 8563.21 | 24-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.656719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6943824.78 | 4392.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135499E+11 | 8564.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.387947E+11 | 42780.72 | 12-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137650E+11 | 25045.30 | 27-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122738E+10 | 22341.83 | 01-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.979265E+09 | 12661.95 | 30-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.302639E+11 | 28404.57 | 30-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.484757E+11 | 39578.74 | 15-DEC-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133506E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.484757E+11 | 42780.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.581511E+11 | 47353.45 | 12-JAN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.468199E+11 | 47020.00 | 03-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340691E+11 | 47010.29 | 04-MAR-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.870046E+10 | 46346.05 | 02-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89930104.63 | 39030.38 | 26-MAY-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10833959.68 | 22655.38 | 01-JUN-18:46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12607704.01 | 19597.30 | 31-JUL-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 97832494.84 | 22539.83 | 31-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.237003E+10 | 45470.92 | 30-SEP-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200204E+11 | 47021.51 | 29-OCT-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.541283E+11 | 47022.57 | 18-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.638348E+11 | 47030.68 | 23-DEC-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288305E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10833959.68 | 19597.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.638348E+11 | 47353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122430E+11 | 8666.43 | 22-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.860333E+10 | 8667.53 | 09-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.515749E+10 | 8665.04 | 09-MAR-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147574E+10 | 8664.05 | 04-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 83081806.44 | 4944.25 | 27-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5145527.16 | 4627.74 | 24-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8406528.47 | 4867.67 | 04-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 47741083.31 | 4775.48 | 14-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.938244E+09 | 8508.52 | 27-SEP-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.461289E+10 | 8667.67 | 20-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112293E+11 | 8665.05 | 02-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134172E+11 | 8666.75 | 24-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.578215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5145527.16 | 4627.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.134172E+11 | 8667.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125499E+11 | 8431.11 | 22-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.961334E+10 | 8432.29 | 09-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.651030E+10 | 8429.65 | 09-MAR-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214612E+10 | 8428.60 | 04-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117271E+09 | 5146.57 | 28-MAY-20:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4316124.73 | 4667.66 | 24-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5641907.39 | 4588.90 | 26-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 62050829.30 | 4901.69 | 14-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124851E+10 | 8352.77 | 27-SEP-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.539894E+10 | 8432.42 | 20-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117945E+11 | 8429.65 | 02-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135326E+11 | 8431.46 | 24-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.629834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4316124.73 | 4588.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135326E+11 | 8432.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.399833E+10 | 2593.56 | 22-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299501E+10 | 2594.02 | 09-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208538E+10 | 2593.71 | 22-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.586231E+09 | 2593.45 | 07-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84459318.80 | 1828.79 | 27-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5469407.09 | 1224.88 | 25-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6894374.18 | 1076.25 | 12-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41061117.23 | 2517.72 | 30-AUG-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.477699E+09 | 2593.70 | 28-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179569E+10 | 2594.06 | 20-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.368421E+10 | 2593.10 | 02-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.432767E+10 | 2593.72 | 24-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5469407.09 | 1076.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.432767E+10 | 2594.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.409387E+10 | 2505.46 | 22-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329370E+10 | 2505.94 | 09-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.256018E+10 | 2505.62 | 22-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.810101E+09 | 2505.48 | 06-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 98520552.26 | 2044.85 | 27-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3452832.71 | 1153.11 | 28-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4999706.70 | 1143.94 | 04-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 47704242.26 | 2444.35 | 31-AUG-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.618892E+09 | 2506.03 | 27-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205885E+10 | 2506.14 | 03-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384940E+10 | 2504.97 | 02-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.436445E+10 | 2505.63 | 24-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3452832.71 | 1143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.436445E+10 | 2506.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167088E+11 | 13179.78 | 07-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104084E+11 | 13179.29 | 07-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.596717E+10 | 13178.96 | 09-MAR-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132860E+10 | 13176.27 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130525E+09 | 8380.65 | 01-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13700106.18 | 6326.89 | 25-JUN-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15481483.66 | 5883.92 | 06-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 58482608.76 | 6689.15 | 20-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.860328E+09 | 12853.93 | 28-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.523497E+10 | 13180.21 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147051E+11 | 13178.40 | 02-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189992E+11 | 13180.39 | 24-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.744308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 13700106.18 | 5883.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.189992E+11 | 13180.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 75168325.83 | 75168325.83 | 3903.82 | 20-JAN-06:10 | 3903.82 | 0.00 |
February | 0.00 | 0.00 | 85185202.38 | 85185202.38 | 3956.80 | 07-FEB-06:10 | 3956.80 | 0.00 |
March | 0.00 | 0.00 | 0.156560E+09 | 0.156560E+09 | 4012.86 | 21-MAR-05:10 | 4012.86 | 0.00 |
April | 0.00 | 0.00 | 0.736317E+09 | 0.736317E+09 | 22928.05 | 22-APR-16:10 | 22928.05 | 0.00 |
May | 0.00 | 0.00 | 0.354295E+11 | 0.354295E+11 | 157352.54 | 31-MAY-17:50 | 157352.54 | 0.00 |
June | 0.00 | 0.00 | 0.131458E+12 | 0.130430E+12 | 226960.36 | 29-JUN-20:00 | 209096.86 | 0.25 |
July | 0.00 | 0.00 | 0.166461E+12 | 0.164044E+12 | 251880.33 | 29-JUL-17:15 | 219473.22 | 0.60 |
August | 0.00 | 0.00 | 0.980209E+11 | 0.979070E+11 | 205466.83 | 11-AUG-19:20 | 205466.83 | 0.39 |
September | 0.00 | 0.00 | 0.479464E+10 | 0.479464E+10 | 61221.95 | 02-SEP-17:50 | 61221.95 | 0.00 |
October | 0.00 | 0.00 | 0.209132E+09 | 0.209132E+09 | 4092.39 | 17-OCT-05:10 | 4092.39 | 0.00 |
November | 0.00 | 0.00 | 51529095.41 | 51529095.41 | 3846.30 | 02-NOV-05:10 | 3846.30 | 0.00 |
December | 0.00 | 0.00 | 54200966.70 | 54200966.70 | 3890.95 | 26-DEC-06:10 | 3890.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.437532E+12 | 0.433972E+12 | 0.11 | |||
Minimum of Months | 0.00 | 0.00 | 51529095.41 | 51529095.41 | 3846.30 | 3846.30 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.166461E+12 | 0.164044E+12 | 251880.33 | 219473.22 | 0.60 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 2616969.90 | 2616969.90 | 594.90 | 22-APR-14:20 | 594.90 | 0.00 |
May | 0.00 | 0.00 | 0.174643E+10 | 0.174643E+10 | 14983.87 | 31-MAY-15:55 | 14983.87 | 0.00 |
June | 0.00 | 0.00 | 0.831331E+10 | 0.823859E+10 | 19533.33 | 30-JUN-12:20 | 17636.60 | 0.18 |
July | 0.00 | 0.00 | 0.101207E+11 | 0.994242E+10 | 19236.07 | 29-JUL-18:02 | 18188.68 | 0.42 |
August | 0.00 | 0.00 | 0.609004E+10 | 0.605039E+10 | 17533.36 | 11-AUG-18:02 | 17533.36 | 0.27 |
September | 0.00 | 0.00 | 0.172724E+09 | 0.172724E+09 | 4990.84 | 07-SEP-16:00 | 4990.84 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.264459E+11 | 0.261532E+11 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101207E+11 | 0.994242E+10 | 19533.33 | 18188.68 | 0.42 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 239058.60 | 239058.60 | 1241.63 | 15-FEB-16:14 | 1241.63 | 0.00 |
March | 0.00 | 0.00 | 0.121475E+09 | 0.121475E+09 | 16500.21 | 22-MAR-15:11 | 16500.21 | 0.00 |
April | 0.00 | 0.00 | 0.234628E+10 | 0.233699E+10 | 16741.34 | 30-APR-15:11 | 16741.34 | 0.01 |
May | 0.00 | 0.00 | 0.455038E+10 | 0.419884E+10 | 16743.06 | 20-MAY-18:01 | 16743.06 | 0.15 |
June | 0.00 | 0.00 | 0.738088E+10 | 0.482457E+10 | 16743.29 | 12-JUN-18:02 | 16743.29 | 0.80 |
July | 0.00 | 0.00 | 0.744636E+10 | 0.407821E+10 | 16410.33 | 17-JUL-18:01 | 14161.22 | 0.90 |
August | 0.00 | 0.00 | 0.527977E+10 | 0.290887E+10 | 16728.75 | 30-AUG-18:01 | 16728.75 | 0.78 |
September | 0.00 | 0.00 | 0.103972E+10 | 0.653860E+09 | 16741.06 | 07-SEP-15:11 | 16741.06 | 0.21 |
October | 0.00 | 0.00 | 35399910.38 | 31397051.30 | 14597.76 | 13-OCT-15:12 | 14597.76 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.282005E+11 | 0.191544E+11 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.744636E+10 | 0.482457E+10 | 16743.29 | 16743.29 | 0.90 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 35837.71 | 35837.71 | 249.08 | 08-FEB-19:06 | 249.08 | 0.00 |
March | 0.00 | 0.00 | 2391357.31 | 2391357.31 | 2609.18 | 26-MAR-15:14 | 2609.18 | 0.00 |
April | 0.00 | 0.00 | 0.116807E+10 | 0.116693E+10 | 15059.55 | 30-APR-18:01 | 15059.55 | 0.00 |
May | 0.00 | 0.00 | 0.249851E+10 | 0.222751E+10 | 17098.74 | 14-MAY-20:41 | 17098.74 | 0.13 |
June | 0.00 | 0.00 | 0.485174E+10 | 0.282049E+10 | 16101.25 | 30-JUN-21:51 | 13376.38 | 0.68 |
July | 0.00 | 0.00 | 0.492373E+10 | 0.255313E+10 | 16670.32 | 08-JUL-21:51 | 14485.14 | 0.68 |
August | 0.00 | 0.00 | 0.271824E+10 | 0.122702E+10 | 15489.33 | 12-AUG-21:52 | 12011.76 | 0.55 |
September | 0.00 | 0.00 | 0.354650E+09 | 0.195425E+09 | 15051.55 | 07-SEP-18:01 | 15051.55 | 0.11 |
October | 0.00 | 0.00 | 5109649.15 | 4276050.31 | 6395.47 | 03-OCT-15:11 | 6395.47 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.165225E+11 | 0.101972E+11 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.492373E+10 | 0.282049E+10 | 17098.74 | 17098.74 | 0.68 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.212467E+09 | 0.212467E+09 | 14969.98 | 31-MAR-15:10 | 14969.98 | 0.00 |
April | 0.00 | 0.00 | 0.247679E+11 | 0.247679E+11 | 58278.29 | 22-APR-13:20 | 58278.29 | 0.00 |
May | 0.00 | 0.00 | 0.372354E+11 | 0.372354E+11 | 56484.24 | 12-MAY-13:20 | 56484.24 | 0.00 |
June | 0.00 | 0.00 | 0.444233E+11 | 0.272788E+11 | 53162.71 | 30-JUN-12:30 | 40132.61 | 0.69 |
July | 0.00 | 0.00 | 0.469766E+11 | 0.210376E+11 | 60514.68 | 23-JUL-13:30 | 55543.62 | 0.97 |
August | 0.00 | 0.00 | 0.422681E+11 | 0.223085E+11 | 64029.71 | 25-AUG-13:15 | 62093.69 | 0.84 |
September | 0.00 | 0.00 | 0.167611E+11 | 0.142584E+11 | 54028.67 | 09-SEP-13:10 | 54028.67 | 0.15 |
October | 0.00 | 0.00 | 0.157266E+10 | 0.157266E+10 | 36234.56 | 03-OCT-13:00 | 36234.56 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.214218E+12 | 0.148672E+12 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.469766E+11 | 0.372354E+11 | 64029.71 | 62093.69 | 0.97 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4818929.20 | 4818929.20 | 9429.63 | 20-JAN-19:07 | 9429.63 | 0.00 |
February | 0.00 | 0.00 | 9858592.53 | 9477873.12 | 14637.49 | 07-FEB-19:04 | 14637.49 | 0.00 |
March | 0.00 | 0.00 | 74322653.10 | 74322653.10 | 49075.48 | 22-MAR-18:02 | 49075.48 | 0.00 |
April | 0.00 | 0.00 | 0.474493E+10 | 0.473413E+10 | 77065.74 | 30-APR-18:01 | 77065.74 | 0.00 |
May | 0.00 | 0.00 | 0.229546E+11 | 0.217586E+11 | 80617.29 | 31-MAY-21:51 | 80617.29 | 0.10 |
June | 0.00 | 0.00 | 0.387976E+11 | 0.295245E+11 | 82902.55 | 07-JUN-21:51 | 82902.55 | 0.57 |
July | 0.00 | 0.00 | 0.416771E+11 | 0.283365E+11 | 84577.35 | 15-JUL-20:41 | 68414.14 | 0.60 |
August | 0.00 | 0.00 | 0.268728E+11 | 0.165825E+11 | 81733.36 | 12-AUG-21:52 | 64436.87 | 0.50 |
September | 0.00 | 0.00 | 0.700923E+10 | 0.398892E+10 | 75809.53 | 10-SEP-18:01 | 75809.53 | 0.33 |
October | 0.00 | 0.00 | 0.697399E+09 | 0.589480E+09 | 72355.50 | 06-OCT-18:02 | 72355.50 | 0.02 |
November | 0.00 | 0.00 | 4137477.13 | 4137477.13 | 11765.86 | 01-NOV-18:06 | 11765.86 | 0.00 |
December | 0.00 | 0.00 | 2148308.83 | 2148308.83 | 13359.93 | 24-DEC-19:05 | 13359.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142849E+12 | 0.105610E+12 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 2148308.83 | 2148308.83 | 9429.63 | 9429.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.416771E+11 | 0.295245E+11 | 84577.35 | 82902.55 | 0.60 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 172056.54 | 172056.54 | 1405.44 | 09-FEB-16:15 | 1405.44 | 0.00 |
March | 0.00 | 0.00 | 0.181465E+09 | 0.181465E+09 | 15785.00 | 22-MAR-15:11 | 15785.00 | 0.00 |
April | 0.00 | 0.00 | 0.215278E+10 | 0.211546E+10 | 15793.05 | 21-APR-08:61 | 15793.05 | 0.01 |
May | 0.00 | 0.00 | 0.639102E+10 | 0.593863E+10 | 15794.49 | 01-MAY-08:61 | 15794.49 | 0.19 |
June | 0.00 | 0.00 | 0.838478E+10 | 0.571507E+10 | 15793.60 | 12-JUN-18:02 | 15793.60 | 0.84 |
July | 0.00 | 0.00 | 0.915083E+10 | 0.559681E+10 | 15326.17 | 17-JUL-18:01 | 13018.03 | 0.94 |
August | 0.00 | 0.00 | 0.639467E+10 | 0.376906E+10 | 15792.73 | 10-AUG-18:02 | 15792.73 | 0.82 |
September | 0.00 | 0.00 | 0.146635E+10 | 0.869586E+09 | 15794.30 | 10-SEP-15:11 | 15794.30 | 0.31 |
October | 0.00 | 0.00 | 90488886.65 | 69210499.31 | 14865.37 | 04-OCT-08:62 | 14865.37 | 0.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.342126E+11 | 0.242554E+11 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.915083E+10 | 0.593863E+10 | 15794.49 | 15794.49 | 0.94 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 56694.67 | 56694.67 | 396.82 | 08-FEB-19:06 | 396.82 | 0.00 |
March | 0.00 | 0.00 | 38074067.69 | 38074067.69 | 4053.41 | 11-MAR-09:01 | 4053.41 | 0.00 |
April | 0.00 | 0.00 | 0.866029E+09 | 0.843367E+09 | 14286.57 | 21-APR-08:61 | 14286.57 | 0.01 |
May | 0.00 | 0.00 | 0.444477E+10 | 0.409156E+10 | 14918.07 | 14-MAY-20:41 | 14918.07 | 0.17 |
June | 0.00 | 0.00 | 0.620928E+10 | 0.412035E+10 | 15281.45 | 10-JUN-21:51 | 15281.45 | 0.71 |
July | 0.00 | 0.00 | 0.660214E+10 | 0.401721E+10 | 15884.02 | 22-JUL-08:32 | 15884.02 | 0.73 |
August | 0.00 | 0.00 | 0.397859E+10 | 0.219822E+10 | 14698.62 | 12-AUG-21:52 | 11401.24 | 0.62 |
September | 0.00 | 0.00 | 0.629718E+09 | 0.351970E+09 | 14287.47 | 10-SEP-15:11 | 14287.47 | 0.19 |
October | 0.00 | 0.00 | 17137540.84 | 9636001.69 | 9034.91 | 04-OCT-08:62 | 9034.91 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.227858E+11 | 0.156704E+11 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.660214E+10 | 0.412035E+10 | 15884.02 | 15884.02 | 0.73 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 28110.05 | 28110.05 | 281.10 | 09-FEB-16:15 | 281.10 | 0.00 |
March | 0.00 | 0.00 | 23407078.62 | 23407078.62 | 4272.96 | 22-MAR-15:11 | 4272.96 | 0.00 |
April | 0.00 | 0.00 | 0.592936E+09 | 0.591891E+09 | 4365.35 | 30-APR-15:11 | 4365.35 | 0.00 |
May | 0.00 | 0.00 | 0.107858E+10 | 0.995272E+09 | 4365.44 | 25-MAY-18:01 | 4365.44 | 0.14 |
June | 0.00 | 0.00 | 0.179621E+10 | 0.120425E+10 | 4365.56 | 07-JUN-15:12 | 4365.56 | 0.77 |
July | 0.00 | 0.00 | 0.180304E+10 | 0.101463E+10 | 4327.39 | 27-JUL-08:62 | 3338.43 | 0.87 |
August | 0.00 | 0.00 | 0.123910E+10 | 0.715334E+09 | 4455.86 | 13-AUG-08:61 | 3427.41 | 0.71 |
September | 0.00 | 0.00 | 0.237541E+09 | 0.159291E+09 | 4365.26 | 07-SEP-15:11 | 4365.26 | 0.16 |
October | 0.00 | 0.00 | 6009999.33 | 5061386.68 | 2923.30 | 03-OCT-15:11 | 2923.30 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.677685E+10 | 0.470916E+10 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.180304E+10 | 0.120425E+10 | 4455.86 | 4365.56 | 0.87 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 574359.98 | 574359.98 | 803.37 | 22-MAR-15:13 | 803.37 | 0.00 |
April | 0.00 | 0.00 | 0.283154E+09 | 0.283046E+09 | 3885.22 | 30-APR-18:01 | 3885.22 | 0.00 |
May | 0.00 | 0.00 | 0.553345E+09 | 0.491217E+09 | 4951.68 | 09-MAY-19:42 | 4951.68 | 0.12 |
June | 0.00 | 0.00 | 0.120055E+10 | 0.698772E+09 | 4500.20 | 28-JUN-21:32 | 4391.61 | 0.66 |
July | 0.00 | 0.00 | 0.120564E+10 | 0.632238E+09 | 4343.00 | 24-JUL-21:51 | 3550.69 | 0.67 |
August | 0.00 | 0.00 | 0.607548E+09 | 0.280564E+09 | 4056.72 | 12-AUG-21:52 | 3013.19 | 0.50 |
September | 0.00 | 0.00 | 67063246.82 | 38725715.22 | 3882.93 | 07-SEP-18:01 | 3882.93 | 0.07 |
October | 0.00 | 0.00 | 734556.32 | 588538.99 | 980.10 | 01-OCT-15:13 | 734.35 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.391861E+10 | 0.242573E+10 | 0.17 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.120564E+10 | 0.698772E+09 | 4951.68 | 4951.68 | 0.67 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.128249E+09 | 0.128249E+09 | 26299.81 | 15-FEB-16:11 | 26299.81 | 0.00 |
March | 0.00 | 0.00 | 0.184839E+10 | 0.184668E+10 | 26329.21 | 22-MAR-15:11 | 26329.21 | 0.00 |
April | 0.00 | 0.00 | 0.588844E+10 | 0.581264E+10 | 26331.24 | 18-APR-18:01 | 26331.24 | 0.02 |
May | 0.00 | 0.00 | 0.802667E+10 | 0.714754E+10 | 26333.09 | 03-MAY-15:11 | 26333.09 | 0.23 |
June | 0.00 | 0.00 | 0.102020E+11 | 0.642163E+10 | 26333.28 | 15-JUN-18:01 | 26333.28 | 0.78 |
July | 0.00 | 0.00 | 0.114212E+11 | 0.625876E+10 | 26333.35 | 13-JUL-18:02 | 26333.35 | 0.90 |
August | 0.00 | 0.00 | 0.967647E+10 | 0.573077E+10 | 26329.06 | 21-AUG-18:01 | 26329.06 | 0.80 |
September | 0.00 | 0.00 | 0.374639E+10 | 0.241095E+10 | 26328.69 | 30-SEP-15:11 | 26328.69 | 0.42 |
October | 0.00 | 0.00 | 0.858165E+09 | 0.771096E+09 | 26316.20 | 14-OCT-15:11 | 26316.20 | 0.03 |
November | 0.00 | 0.00 | 2758308.64 | 2758308.64 | 9089.92 | 08-NOV-16:12 | 9089.92 | 0.00 |
December | 0.00 | 0.00 | 120642.89 | 120642.89 | 1206.43 | 24-DEC-09:05 | 1206.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.517989E+11 | 0.365312E+11 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.114212E+11 | 0.714754E+10 | 26333.35 | 26333.35 | 0.90 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 209225.35 | 643026.81 | 12-JAN-10:20 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 179554.27 | 605297.09 | 27-FEB-07:05 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 89518.50 | 555678.12 | 01-MAR-07:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 34149.88 | 202976.61 | 03-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15554.42 | 118633.03 | 27-MAY-15:14 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1157.92 | 64359.88 | 02-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 517.66 | 58041.58 | 05-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 4359.52 | 127020.71 | 31-AUG-08:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 32886.16 | 188083.46 | 27-SEP-15:11 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55421.32 | 213028.04 | 30-OCT-08:05 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 196968.51 | 595088.79 | 29-NOV-10:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 246398.29 | 617417.82 | 15-DEC-10:50 |
Annual Sum or Average | 0.00 | 88310.25 | ||||
Minimum of Months | 0.00 | 0.00 | 517.66 | 58041.58 | ||
Maximum of Months | 0.00 | 0.00 | 246398.29 | 643026.81 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 196.60 | 22835.25 | 23-JAN-19:07 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 392.67 | 31266.61 | 07-FEB-19:04 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 1756.80 | 47000.40 | 22-MAR-18:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18695.18 | 211563.01 | 22-APR-15:13 | 0.00 | 0.00 | 01-APR-00:10 |
May | 49324.29 | 248598.70 | 31-MAY-18:02 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 104577.89 | 399350.55 | 29-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 118072.74 | 450467.32 | 29-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 78755.03 | 394305.12 | 23-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 15760.66 | 182546.90 | 09-SEP-15:13 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 2143.96 | 72906.33 | 03-OCT-18:01 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 154.72 | 21178.42 | 05-NOV-18:07 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 144.58 | 30736.02 | 24-DEC-19:05 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 32736.61 | 0.00 | ||||
Minimum of Months | 144.58 | 21178.42 | 0.00 | 0.00 | ||
Maximum of Months | 118072.74 | 450467.32 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 33737.59 | 68885.44 | 30-JAN-07:56 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 33743.90 | 68880.69 | 28-FEB-07:54 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 33766.52 | 68884.17 | 01-MAR-07:54 |
April | 0.00 | 0.00 | 01-APR-00:10 | 33748.43 | 68848.30 | 03-APR-06:58 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 33512.34 | 68873.68 | 12-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32336.82 | 67157.39 | 01-JUN-06:59 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31153.87 | 64354.24 | 03-JUL-06:58 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 30452.18 | 62404.47 | 01-AUG-06:55 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 30345.67 | 61949.66 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 30894.82 | 63842.68 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 31955.31 | 66397.06 | 30-NOV-07:59 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 33223.08 | 68859.25 | 28-DEC-07:57 |
Annual Sum or Average | 0.00 | 32398.27 | ||||
Minimum of Months | 0.00 | 0.00 | 30345.67 | 61949.66 | ||
Maximum of Months | 0.00 | 0.00 | 33766.52 | 68885.44 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261333E+10 | 0.68 | 1299.30 | 01-JAN-00:20 | 0.89 |
February | 0.236042E+10 | 0.68 | 1299.30 | 01-FEB-00:05 | 0.89 |
March | 0.261333E+10 | 0.68 | 1299.30 | 01-MAR-00:10 | 0.90 |
April | 0.252903E+10 | 0.68 | 1299.30 | 01-APR-00:10 | 0.89 |
May | 0.261333E+10 | 0.68 | 1299.30 | 01-MAY-00:20 | 0.89 |
June | 0.252903E+10 | 0.68 | 1299.30 | 01-JUN-00:40 | 0.89 |
July | 0.261333E+10 | 0.68 | 1299.30 | 01-JUL-01:20 | 0.88 |
August | 0.261333E+10 | 0.68 | 1299.30 | 01-AUG-00:50 | 0.88 |
September | 0.252903E+10 | 0.68 | 1299.30 | 01-SEP-08:61 | 0.89 |
October | 0.261333E+10 | 0.68 | 1299.30 | 01-OCT-00:30 | 0.89 |
November | 0.252903E+10 | 0.68 | 1299.30 | 01-NOV-00:10 | 0.89 |
December | 0.261333E+10 | 0.68 | 1299.30 | 01-DEC-00:10 | 0.90 |
Annual Sum or Average | 0.307698E+11 | 0.68 | |||
Minimum of Months | 0.236042E+10 | 0.68 | 1299.30 | 0.88 | |
Maximum of Months | 0.261333E+10 | 0.68 | 1299.30 | 0.90 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.348854E+11 | 0.82 | 19036.49 | 19-JAN-19:40 | 1.02 |
February | 0.318998E+11 | 0.83 | 19136.82 | 02-FEB-19:40 | 1.03 |
March | 0.364471E+11 | 0.84 | 19143.91 | 19-MAR-19:10 | 1.03 |
April | 0.363504E+11 | 0.86 | 19844.83 | 21-APR-21:10 | 1.05 |
May | 0.386459E+11 | 0.87 | 22348.34 | 31-MAY-21:10 | 1.12 |
June | 0.386350E+11 | 0.88 | 25012.64 | 22-JUN-21:10 | 1.20 |
July | 0.398222E+11 | 0.88 | 24975.33 | 12-JUL-21:10 | 1.20 |
August | 0.392660E+11 | 0.87 | 24549.47 | 11-AUG-21:10 | 1.19 |
September | 0.365455E+11 | 0.86 | 19265.50 | 09-SEP-21:00 | 1.03 |
October | 0.367588E+11 | 0.85 | 19233.49 | 18-OCT-19:00 | 1.03 |
November | 0.338869E+11 | 0.83 | 19082.26 | 02-NOV-18:40 | 1.03 |
December | 0.347454E+11 | 0.82 | 18929.17 | 24-DEC-20:10 | 1.02 |
Annual Sum or Average | 0.437889E+12 | 0.85 | |||
Minimum of Months | 0.318998E+11 | 0.82 | 18929.17 | 1.02 | |
Maximum of Months | 0.398222E+11 | 0.88 | 25012.64 | 1.20 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:05 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:05 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:10 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:10 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:10 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:10 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:10 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:10 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:10 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | -0.0 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | -0.0 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:10 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:10 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:10 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.825012E+09 | 0.57 | 824.33 | 01-JAN-09:02 | 0.59 |
February | 0.594607E+09 | 0.54 | 824.33 | 01-FEB-09:02 | 0.59 |
March | 0.393278E+09 | 0.45 | 824.33 | 01-MAR-09:02 | 0.59 |
April | 0.231194E+09 | 0.46 | 824.33 | 01-APR-08:62 | 0.59 |
May | 0.246499E+09 | 0.51 | 824.33 | 01-MAY-15:11 | 0.58 |
June | 0.364506E+09 | 0.53 | 824.33 | 01-JUN-08:61 | 0.58 |
July | 0.342306E+09 | 0.53 | 824.33 | 01-JUL-08:61 | 0.58 |
August | 0.262372E+09 | 0.51 | 824.33 | 01-AUG-08:61 | 0.58 |
September | 0.158279E+09 | 0.43 | 824.33 | 01-SEP-15:11 | 0.58 |
October | 0.330937E+09 | 0.47 | 824.33 | 01-OCT-15:11 | 0.58 |
November | 0.729952E+09 | 0.57 | 824.33 | 01-NOV-08:62 | 0.59 |
December | 0.960061E+09 | 0.57 | 824.33 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.543900E+10 | 0.51 | |||
Minimum of Months | 0.158279E+09 | 0.43 | 824.33 | 0.58 | |
Maximum of Months | 0.960061E+09 | 0.57 | 824.33 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.849937E+09 | 0.57 | 741.40 | 01-JAN-09:02 | 0.59 |
February | 0.668302E+09 | 0.57 | 741.40 | 01-FEB-09:02 | 0.59 |
March | 0.459478E+09 | 0.52 | 741.40 | 01-MAR-09:02 | 0.59 |
April | 0.204717E+09 | 0.43 | 741.40 | 01-APR-08:62 | 0.59 |
May | 0.150040E+09 | 0.40 | 741.40 | 01-MAY-15:11 | 0.58 |
June | 0.230032E+09 | 0.40 | 741.40 | 01-JUN-08:61 | 0.58 |
July | 0.221672E+09 | 0.40 | 741.40 | 01-JUL-08:61 | 0.58 |
August | 0.136908E+09 | 0.36 | 741.40 | 01-AUG-08:61 | 0.58 |
September | 0.139865E+09 | 0.39 | 741.40 | 01-SEP-15:11 | 0.58 |
October | 0.354188E+09 | 0.50 | 741.40 | 02-OCT-08:62 | 0.58 |
November | 0.784925E+09 | 0.57 | 741.40 | 01-NOV-08:62 | 0.59 |
December | 0.954708E+09 | 0.57 | 741.40 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.515477E+10 | 0.47 | |||
Minimum of Months | 0.136908E+09 | 0.36 | 741.40 | 0.58 | |
Maximum of Months | 0.954708E+09 | 0.57 | 741.40 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271249E+10 | 0.58 | 3573.14 | 12-JAN-16:00 | 0.59 |
February | 0.111635E+10 | 0.37 | 1478.30 | 27-FEB-16:00 | 0.59 |
March | 0.111027E+09 | 0.04 | 1372.58 | 01-MAR-05:00 | 0.59 |
April | 0.908658E+09 | 0.29 | 1812.44 | 22-APR-13:20 | 0.59 |
May | 0.139977E+10 | 0.48 | 1762.02 | 12-MAY-13:20 | 0.59 |
June | 0.171517E+10 | 0.57 | 1656.59 | 10-JUN-14:00 | 0.58 |
July | 0.172784E+10 | 0.56 | 1894.45 | 23-JUL-13:30 | 0.58 |
August | 0.158891E+10 | 0.53 | 2002.22 | 25-AUG-13:15 | 0.58 |
September | 0.678681E+09 | 0.29 | 1692.05 | 09-SEP-13:10 | 0.58 |
October | 0.172700E+09 | 0.09 | 1202.56 | 03-OCT-13:00 | 0.59 |
November | 0.225202E+10 | 0.56 | 1605.29 | 30-NOV-16:00 | 0.59 |
December | 0.317435E+10 | 0.59 | 3389.07 | 15-DEC-15:10 | 0.59 |
Annual Sum or Average | 0.175580E+11 | 0.41 | |||
Minimum of Months | 0.111027E+09 | 0.04 | 1202.56 | 0.58 | |
Maximum of Months | 0.317435E+10 | 0.59 | 3573.14 | 0.59 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.390950E+10 | 0.50 | 3844.18 | 01-JAN-09:02 | 0.59 |
February | 0.324552E+10 | 0.47 | 3844.18 | 01-FEB-09:02 | 0.59 |
March | 0.215643E+10 | 0.42 | 3844.18 | 01-MAR-00:10 | 0.59 |
April | 0.841152E+09 | 0.40 | 3844.18 | 01-APR-08:62 | 0.59 |
May | 0.113246E+10 | 0.36 | 3844.18 | 01-MAY-08:61 | 0.58 |
June | 0.192269E+10 | 0.35 | 3844.18 | 01-JUN-08:61 | 0.58 |
July | 0.187989E+10 | 0.35 | 3844.18 | 01-JUL-08:61 | 0.58 |
August | 0.119734E+10 | 0.32 | 3844.18 | 01-AUG-08:61 | 0.58 |
September | 0.596508E+09 | 0.39 | 3844.18 | 01-SEP-08:61 | 0.58 |
October | 0.127781E+10 | 0.41 | 3844.18 | 01-OCT-08:62 | 0.58 |
November | 0.356481E+10 | 0.50 | 3844.18 | 01-NOV-08:62 | 0.59 |
December | 0.448793E+10 | 0.51 | 3844.18 | 01-DEC-00:10 | 0.59 |
Annual Sum or Average | 0.262120E+11 | 0.41 | |||
Minimum of Months | 0.596508E+09 | 0.32 | 3844.18 | 0.58 | |
Maximum of Months | 0.448793E+10 | 0.51 | 3844.18 | 0.59 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.808108E+09 | 0.57 | 777.46 | 01-JAN-09:02 | 0.59 |
February | 0.551305E+09 | 0.53 | 777.46 | 01-FEB-09:02 | 0.59 |
March | 0.332684E+09 | 0.43 | 777.46 | 01-MAR-09:02 | 0.59 |
April | 0.213952E+09 | 0.49 | 777.46 | 01-APR-08:62 | 0.59 |
May | 0.326899E+09 | 0.55 | 777.46 | 01-MAY-08:61 | 0.58 |
June | 0.398819E+09 | 0.55 | 777.46 | 01-JUN-08:61 | 0.58 |
July | 0.413637E+09 | 0.55 | 777.46 | 01-JUL-08:61 | 0.58 |
August | 0.301906E+09 | 0.53 | 777.46 | 01-AUG-08:61 | 0.58 |
September | 0.159864E+09 | 0.45 | 777.46 | 01-SEP-08:61 | 0.58 |
October | 0.294634E+09 | 0.45 | 777.46 | 01-OCT-08:62 | 0.58 |
November | 0.730469E+09 | 0.57 | 777.46 | 01-NOV-08:62 | 0.59 |
December | 0.953016E+09 | 0.57 | 777.46 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.548529E+10 | 0.52 | |||
Minimum of Months | 0.159864E+09 | 0.43 | 777.46 | 0.58 | |
Maximum of Months | 0.953016E+09 | 0.57 | 777.46 | 0.59 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.831654E+09 | 0.57 | 703.10 | 01-JAN-09:02 | 0.59 |
February | 0.622058E+09 | 0.56 | 703.10 | 01-FEB-09:02 | 0.59 |
March | 0.386485E+09 | 0.46 | 703.10 | 01-MAR-09:02 | 0.59 |
April | 0.183989E+09 | 0.43 | 703.10 | 01-APR-08:62 | 0.59 |
May | 0.243541E+09 | 0.48 | 703.10 | 01-MAY-08:61 | 0.58 |
June | 0.301872E+09 | 0.42 | 703.10 | 01-JUN-08:61 | 0.58 |
July | 0.297050E+09 | 0.42 | 703.10 | 01-JUL-08:61 | 0.58 |
August | 0.192699E+09 | 0.41 | 703.10 | 01-AUG-08:61 | 0.58 |
September | 0.132327E+09 | 0.40 | 703.10 | 01-SEP-08:61 | 0.58 |
October | 0.312856E+09 | 0.47 | 703.10 | 02-OCT-15:12 | 0.58 |
November | 0.773189E+09 | 0.57 | 703.10 | 01-NOV-08:62 | 0.59 |
December | 0.939302E+09 | 0.57 | 703.10 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.521702E+10 | 0.48 | |||
Minimum of Months | 0.132327E+09 | 0.40 | 703.10 | 0.58 | |
Maximum of Months | 0.939302E+09 | 0.57 | 703.10 | 0.59 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.264264E+09 | 0.58 | 214.96 | 01-JAN-09:02 | 0.59 |
February | 0.190202E+09 | 0.56 | 214.96 | 01-FEB-09:02 | 0.59 |
March | 0.122231E+09 | 0.49 | 214.96 | 01-MAR-09:02 | 0.59 |
April | 67782293.07 | 0.46 | 214.96 | 01-APR-08:62 | 0.59 |
May | 62891568.22 | 0.51 | 214.96 | 01-MAY-15:11 | 0.58 |
June | 90231958.94 | 0.53 | 214.96 | 01-JUN-08:61 | 0.58 |
July | 84941539.61 | 0.52 | 214.96 | 01-JUL-08:61 | 0.58 |
August | 64679666.25 | 0.50 | 214.96 | 01-AUG-08:61 | 0.58 |
September | 48713934.41 | 0.43 | 214.96 | 01-SEP-15:11 | 0.58 |
October | 0.102393E+09 | 0.50 | 214.96 | 02-OCT-08:62 | 0.58 |
November | 0.241242E+09 | 0.58 | 214.96 | 01-NOV-08:62 | 0.59 |
December | 0.296111E+09 | 0.58 | 214.96 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.163568E+10 | 0.52 | |||
Minimum of Months | 48713934.41 | 0.43 | 214.96 | 0.58 | |
Maximum of Months | 0.296111E+09 | 0.58 | 214.96 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.262206E+09 | 0.58 | 191.29 | 01-JAN-09:02 | 0.59 |
February | 0.209659E+09 | 0.57 | 191.29 | 01-FEB-09:02 | 0.59 |
March | 0.147028E+09 | 0.55 | 191.29 | 01-MAR-09:02 | 0.59 |
April | 61825664.90 | 0.45 | 191.29 | 01-APR-08:62 | 0.59 |
May | 38132197.80 | 0.40 | 191.29 | 01-MAY-15:11 | 0.58 |
June | 58222604.59 | 0.40 | 191.29 | 01-JUN-08:61 | 0.58 |
July | 55442252.27 | 0.40 | 191.29 | 01-JUL-08:61 | 0.58 |
August | 32980040.70 | 0.36 | 191.29 | 01-AUG-08:61 | 0.58 |
September | 44977925.49 | 0.41 | 191.29 | 01-SEP-15:11 | 0.58 |
October | 0.112662E+09 | 0.52 | 191.29 | 01-OCT-08:62 | 0.58 |
November | 0.244999E+09 | 0.58 | 191.29 | 01-NOV-08:62 | 0.59 |
December | 0.285892E+09 | 0.58 | 191.29 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.155403E+10 | 0.48 | |||
Minimum of Months | 32980040.70 | 0.36 | 191.29 | 0.58 | |
Maximum of Months | 0.285892E+09 | 0.58 | 191.29 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.115635E+10 | 0.55 | 1292.62 | 01-JAN-09:02 | 0.59 |
February | 0.722376E+09 | 0.49 | 1292.62 | 01-FEB-09:02 | 0.59 |
March | 0.494752E+09 | 0.47 | 1292.62 | 01-MAR-09:02 | 0.59 |
April | 0.393187E+09 | 0.51 | 1292.62 | 01-APR-08:62 | 0.59 |
May | 0.407994E+09 | 0.53 | 1292.62 | 01-MAY-15:11 | 0.58 |
June | 0.481477E+09 | 0.53 | 1292.62 | 01-JUN-08:61 | 0.58 |
July | 0.508521E+09 | 0.53 | 1292.62 | 01-JUL-08:61 | 0.58 |
August | 0.458263E+09 | 0.52 | 1292.62 | 01-AUG-08:61 | 0.58 |
September | 0.278774E+09 | 0.47 | 1292.62 | 01-SEP-08:61 | 0.58 |
October | 0.413326E+09 | 0.45 | 1292.62 | 01-OCT-15:11 | 0.58 |
November | 0.973881E+09 | 0.54 | 1292.62 | 01-NOV-08:62 | 0.59 |
December | 0.136186E+10 | 0.57 | 1292.62 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.765076E+10 | 0.51 | |||
Minimum of Months | 0.278774E+09 | 0.45 | 1292.62 | 0.58 | |
Maximum of Months | 0.136186E+10 | 0.57 | 1292.62 | 0.59 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.950081E+09 | 0.863624E+09 | 2083.42 | 12-JAN-10:50 | 1893.83 | 1893.83 | 38.37 | 7.10 |
February | 0.717941E+09 | 0.652609E+09 | 1928.74 | 27-FEB-09:13 | 1753.22 | 1753.22 | 39.11 | 6.88 |
March | 0.261141E+09 | 0.237378E+09 | 1601.33 | 01-MAR-07:10 | 1455.61 | 1455.61 | 39.21 | 6.39 |
April | 18818331.96 | 17105863.75 | 79.71 | 03-APR-08:03 | 72.46 | 72.46 | 32.16 | 1.74 |
May | 4957563.76 | 4506425.45 | 28.95 | 28-MAY-02:30 | 26.32 | 26.32 | 42.93 | 1.05 |
June | 221345.89 | 201203.41 | 7.50 | 02-JUN-04:00 | 6.82 | 6.82 | 28.69 | 0.49 |
July | 90743.97 | 82486.27 | 5.69 | 04-JUL-18:04 | 5.17 | 5.17 | 42.16 | 0.41 |
August | 1620827.50 | 1473332.20 | 31.81 | 31-AUG-04:10 | 28.91 | 28.91 | 35.89 | 1.10 |
September | 15337732.66 | 13941998.99 | 54.30 | 27-SEP-15:11 | 49.36 | 49.36 | 28.92 | 1.45 |
October | 41427040.05 | 37657179.40 | 112.25 | 30-OCT-08:05 | 102.03 | 102.03 | 35.12 | 2.05 |
November | 0.811998E+09 | 0.738106E+09 | 1956.34 | 29-NOV-10:10 | 1778.31 | 1778.31 | 39.43 | 6.92 |
December | 0.117065E+10 | 0.106412E+10 | 2011.77 | 15-DEC-10:50 | 1828.70 | 1828.70 | 38.90 | 7.00 |
Annual Sum or Average | 0.399429E+10 | 0.363081E+10 | ||||||
Minimum of Months | 90743.97 | 82486.27 | 5.69 | 5.17 | 5.17 | 28.69 | 0.41 | |
Maximum of Months | 0.117065E+10 | 0.106412E+10 | 2083.42 | 1893.83 | 1893.83 | 42.93 | 7.10 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1357982.75 | 1234406.32 | 340.40 | 20-JAN-19:07 | 309.42 | 309.42 | 6.72 | 0.68 |
February | 6298852.83 | 5725657.22 | 477.80 | 07-FEB-19:04 | 434.32 | 434.32 | 6.72 | 0.98 |
March | 79050122.19 | 71856561.07 | 1091.09 | 22-MAR-18:02 | 991.80 | 991.80 | 6.72 | 2.54 |
April | 0.101890E+10 | 0.926178E+09 | 2009.75 | 22-APR-15:11 | 1826.86 | 1826.86 | 6.72 | 6.46 |
May | 0.238809E+10 | 0.217077E+10 | 1974.27 | 31-MAY-15:10 | 1794.61 | 1794.61 | 6.72 | 6.22 |
June | 0.355992E+10 | 0.323597E+10 | 2465.77 | 21-JUN-18:03 | 2241.38 | 2241.38 | 6.72 | 12.56 |
July | 0.388296E+10 | 0.352961E+10 | 2502.20 | 20-JUL-18:03 | 2274.50 | 2274.50 | 6.72 | 13.29 |
August | 0.306703E+10 | 0.278793E+10 | 2465.30 | 11-AUG-15:12 | 2240.95 | 2240.95 | 6.72 | 12.55 |
September | 0.914495E+09 | 0.831276E+09 | 2010.28 | 09-SEP-15:11 | 1827.34 | 1827.34 | 6.72 | 6.46 |
October | 0.108564E+09 | 98684319.81 | 1407.71 | 03-OCT-18:01 | 1279.61 | 1279.61 | 6.72 | 3.56 |
November | 1082003.22 | 983540.93 | 400.29 | 01-NOV-18:06 | 363.86 | 363.86 | 6.72 | 0.81 |
December | 926033.48 | 841764.43 | 445.18 | 24-DEC-19:05 | 404.67 | 404.67 | 6.72 | 0.91 |
Annual Sum or Average | 0.150287E+11 | 0.136611E+11 | ||||||
Minimum of Months | 926033.48 | 841764.43 | 340.40 | 309.42 | 309.42 | 6.72 | 0.68 | |
Maximum of Months | 0.388296E+10 | 0.352961E+10 | 2502.20 | 2274.50 | 2274.50 | 6.72 | 13.29 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.499597E+09 | 0.454133E+09 | 2119.18 | 01-JAN-00:05 | 1926.33 | 1926.33 | 6.73 | 18.93 |
February | 0.782795E+09 | 0.711560E+09 | 2119.18 | 02-FEB-00:05 | 1926.33 | 1926.33 | 6.73 | 18.93 |
March | 0.217044E+10 | 0.197293E+10 | 2119.18 | 01-MAR-12:30 | 1926.33 | 1926.33 | 6.74 | 18.93 |
April | 0.438905E+10 | 0.398964E+10 | 2119.18 | 01-APR-00:40 | 1926.33 | 1926.33 | 6.72 | 18.93 |
May | 0.558573E+10 | 0.507743E+10 | 2119.18 | 01-MAY-00:10 | 1926.33 | 1926.33 | 6.78 | 18.93 |
June | 0.548401E+10 | 0.498497E+10 | 2119.18 | 01-JUN-00:10 | 1926.33 | 1926.33 | 7.27 | 18.93 |
July | 0.567474E+10 | 0.515834E+10 | 2119.18 | 01-JUL-00:10 | 1926.33 | 1926.33 | 7.50 | 18.93 |
August | 0.563108E+10 | 0.511866E+10 | 2119.18 | 01-AUG-00:10 | 1926.33 | 1926.33 | 7.69 | 18.93 |
September | 0.412218E+10 | 0.374706E+10 | 2119.18 | 01-SEP-00:10 | 1926.33 | 1926.33 | 6.83 | 18.93 |
October | 0.237144E+10 | 0.215564E+10 | 2119.18 | 01-OCT-08:00 | 1926.33 | 1926.33 | 6.75 | 18.93 |
November | 0.383117E+09 | 0.348254E+09 | 2119.18 | 01-NOV-00:20 | 1926.33 | 1926.33 | 6.73 | 18.93 |
December | 0.364983E+09 | 0.331770E+09 | 2119.18 | 19-DEC-18:20 | 1926.33 | 1926.33 | 6.74 | 18.93 |
Annual Sum or Average | 0.374592E+11 | 0.340504E+11 | ||||||
Minimum of Months | 0.364983E+09 | 0.331770E+09 | 2119.18 | 1926.33 | 1926.33 | 6.72 | 18.93 | |
Maximum of Months | 0.567474E+10 | 0.515834E+10 | 2119.18 | 1926.33 | 1926.33 | 7.69 | 18.93 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 45.59 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 46.58 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 47.14 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 49.92 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 49.97 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 50.36 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 50.31 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 51.05 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 50.80 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 50.04 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 50.31 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 47.50 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 45.59 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 51.05 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 41.16 | 60.00 | 209225.35 | 643026.81 | 12-JAN-10:20 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 38.92 | 60.00 | 179554.27 | 605297.09 | 27-FEB-07:05 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 39.59 | 60.00 | 89518.50 | 555678.12 | 01-MAR-07:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 47.29 | 60.00 | 34149.88 | 202976.61 | 03-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 29.71 | 60.00 | 15554.42 | 118633.03 | 27-MAY-15:14 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 29.13 | 29.13 | 1157.92 | 64359.88 | 02-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 42.41 | 42.41 | 517.66 | 58041.58 | 05-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 26.96 | 26.96 | 4359.52 | 127020.71 | 31-AUG-08:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 30.76 | 60.00 | 32886.16 | 188083.46 | 27-SEP-15:11 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 37.27 | 60.00 | 55421.32 | 213028.04 | 30-OCT-08:05 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 45.46 | 60.00 | 196968.51 | 595088.79 | 29-NOV-10:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 40.09 | 60.00 | 246398.29 | 617417.82 | 15-DEC-10:50 |
Annual Sum or Average | 0.00 | 88310.25 | ||||||
Minimum of Months | 0.00 | 0.00 | 26.96 | 26.96 | 517.66 | 58041.58 | ||
Maximum of Months | 0.00 | 0.00 | 47.29 | 60.00 | 246398.29 | 643026.81 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 196.60 | 22835.25 | 23-JAN-19:07 | 6.99 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 392.67 | 31266.61 | 07-FEB-19:04 | 7.09 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 1756.80 | 47000.40 | 22-MAR-18:02 | 7.29 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18695.18 | 211563.01 | 22-APR-15:13 | 9.37 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 49324.29 | 248598.70 | 31-MAY-18:02 | 9.83 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 104577.89 | 399350.55 | 29-JUN-18:03 | 11.74 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 118072.74 | 450467.32 | 29-JUL-18:03 | 12.38 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 78755.03 | 394305.12 | 23-AUG-18:03 | 11.67 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 15760.66 | 182546.90 | 09-SEP-15:13 | 9.00 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 2143.96 | 72906.33 | 03-OCT-18:01 | 7.62 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 154.72 | 21178.42 | 05-NOV-18:07 | 6.97 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 144.58 | 30736.02 | 24-DEC-19:05 | 7.09 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 32736.61 | 0.00 | ||||||
Minimum of Months | 144.58 | 21178.42 | 6.97 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 118072.74 | 450467.32 | 12.38 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 45.59 | 59.63 | 33737.59 | 68885.44 | 30-JAN-07:56 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 46.58 | 58.88 | 33743.90 | 68880.69 | 28-FEB-07:54 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 47.14 | 59.43 | 33766.52 | 68884.17 | 01-MAR-07:54 |
April | 0.00 | 0.00 | 01-APR-00:10 | 49.92 | 59.12 | 33748.43 | 68848.30 | 03-APR-06:58 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 49.97 | 59.20 | 33512.34 | 68873.68 | 12-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 50.36 | 59.46 | 32336.82 | 67157.39 | 01-JUN-06:59 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 50.31 | 58.74 | 31153.87 | 64354.24 | 03-JUL-06:58 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 51.05 | 59.57 | 30452.18 | 62404.47 | 01-AUG-06:55 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 50.80 | 58.89 | 30345.67 | 61949.66 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 50.04 | 59.45 | 30894.82 | 63842.68 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 50.31 | 58.59 | 31955.31 | 66397.06 | 30-NOV-07:59 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 47.50 | 59.27 | 33223.08 | 68859.25 | 28-DEC-07:57 |
Annual Sum or Average | 0.00 | 32398.27 | ||||||
Minimum of Months | 0.00 | 0.00 | 45.59 | 58.59 | 30345.67 | 61949.66 | ||
Maximum of Months | 0.00 | 0.00 | 51.05 | 59.63 | 33766.52 | 68885.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.362802E+12 | 0.00 | 75168325.83 | 0.348854E+11 | 0.00 | 0.00 |
February | 0.296546E+12 | 0.00 | 85185202.38 | 0.318998E+11 | 0.00 | 0.00 |
March | 0.154895E+12 | 0.00 | 0.156560E+09 | 0.364471E+11 | 0.00 | 0.00 |
April | 0.678582E+11 | 0.00 | 0.736317E+09 | 0.363504E+11 | 0.00 | 0.00 |
May | 0.408322E+11 | 0.00 | 0.354295E+11 | 0.386459E+11 | 0.00 | 0.00 |
June | 0.292059E+10 | 0.00 | 0.131458E+12 | 0.386350E+11 | 0.00 | 0.00 |
July | 0.133950E+10 | 0.00 | 0.166461E+12 | 0.398222E+11 | 0.00 | 0.00 |
August | 0.111824E+11 | 0.00 | 0.980209E+11 | 0.392660E+11 | 0.00 | 0.00 |
September | 0.760616E+11 | 0.00 | 0.479464E+10 | 0.365455E+11 | 0.00 | 0.00 |
October | 0.932639E+11 | 0.00 | 0.209132E+09 | 0.367588E+11 | 0.00 | 0.00 |
November | 0.332580E+12 | 0.00 | 51529095.41 | 0.338869E+11 | 0.00 | 0.00 |
December | 0.434922E+12 | 0.00 | 54200966.70 | 0.347454E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.187520E+13 | 0.00 | 0.437532E+12 | 0.437889E+12 | 0.00 | 0.00 |
Minimum of Months | 0.133950E+10 | 0.00 | 51529095.41 | 0.318998E+11 | 0.00 | 0.00 |
Maximum of Months | 0.434922E+12 | 0.00 | 0.166461E+12 | 0.398222E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.275460E+11 | 0.00 | 0.00 | 0.261333E+10 | 0.00 | 0.00 |
February | 0.243633E+11 | 0.00 | 0.00 | 0.236042E+10 | 0.00 | 0.00 |
March | 0.141195E+11 | 0.00 | 0.00 | 0.261333E+10 | 0.00 | 0.00 |
April | 0.211243E+10 | 0.00 | 2616969.90 | 0.252903E+10 | 0.00 | 0.00 |
May | 9958.87 | 0.00 | 0.174643E+10 | 0.261333E+10 | 0.00 | 0.00 |
June | 25530.76 | 0.00 | 0.831331E+10 | 0.252903E+10 | 0.00 | 0.00 |
July | 30044.83 | 0.00 | 0.101207E+11 | 0.261333E+10 | 0.00 | 0.00 |
August | 2765664.03 | 0.00 | 0.609004E+10 | 0.261333E+10 | 0.00 | 0.00 |
September | 0.118221E+09 | 0.00 | 0.172724E+09 | 0.252903E+10 | 0.00 | 0.00 |
October | 0.417806E+10 | 0.00 | 0.00 | 0.261333E+10 | 0.00 | 0.00 |
November | 0.266023E+11 | 0.00 | 0.00 | 0.252903E+10 | 0.00 | 0.00 |
December | 0.329465E+11 | 0.00 | 0.00 | 0.261333E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.131989E+12 | 0.00 | 0.264459E+11 | 0.307698E+11 | 0.00 | 0.00 |
Minimum of Months | 9958.87 | 0.00 | 0.00 | 0.236042E+10 | 0.00 | 0.00 |
Maximum of Months | 0.329465E+11 | 0.00 | 0.101207E+11 | 0.261333E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.348854E+11 | 75168325.83 | 0.362802E+12 | 0.491262E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318998E+11 | 85185202.38 | 0.296546E+12 | 0.407406E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.364471E+11 | 0.156560E+09 | 0.154895E+12 | 0.471966E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363504E+11 | 0.736317E+09 | 0.678582E+11 | 0.200715E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.386459E+11 | 0.354295E+11 | 0.408322E+11 | 0.346330E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.386350E+11 | 0.131458E+12 | 0.292059E+10 | 0.180840E+10 | 79790083.12 | 0.00 | 0.00 | 0.00 |
July | 0.398222E+11 | 0.166461E+12 | 0.133950E+10 | 0.399419E+10 | 0.383766E+09 | 0.00 | 0.00 | 0.00 |
August | 0.392660E+11 | 0.980209E+11 | 0.111824E+11 | 0.286841E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.365455E+11 | 0.479464E+10 | 0.760616E+11 | 0.243175E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.367588E+11 | 0.209132E+09 | 0.932639E+11 | 0.317974E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.338869E+11 | 51529095.41 | 0.332580E+12 | 0.495558E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347454E+11 | 54200966.70 | 0.434922E+12 | 0.466905E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.437889E+12 | 0.437532E+12 | 0.187520E+13 | 0.288512E+13 | 0.463556E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.318998E+11 | 51529095.41 | 0.133950E+10 | 0.346330E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.398222E+11 | 0.166461E+12 | 0.434922E+12 | 0.495558E+12 | 0.383766E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261333E+10 | 0.00 | 0.275460E+11 | 0.651611E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.00 | 0.243633E+11 | 0.544731E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.00 | 0.141195E+11 | 0.672616E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 2616969.90 | 0.211243E+10 | 0.490923E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 0.174643E+10 | 9958.87 | 0.207932E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 0.831331E+10 | 25530.76 | 0.514383E+10 | 0.112554E+09 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 0.101207E+11 | 30044.83 | 0.421613E+10 | 0.294708E+09 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 0.609004E+10 | 2765664.03 | 0.932308E+10 | 40011200.84 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 0.172724E+09 | 0.118221E+09 | 0.309535E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 0.00 | 0.417806E+10 | 0.589529E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 0.00 | 0.266023E+11 | 0.649096E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.00 | 0.329465E+11 | 0.623056E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.264459E+11 | 0.131989E+12 | 0.492586E+12 | 0.447273E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 0.00 | 9958.87 | 0.421613E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.101207E+11 | 0.329465E+11 | 0.672616E+11 | 0.294708E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.348854E+11 | 0.362802E+12 | 75168325.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318998E+11 | 0.296546E+12 | 85185202.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.364471E+11 | 0.154895E+12 | 0.156560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363504E+11 | 0.678582E+11 | 0.736317E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.386459E+11 | 0.408322E+11 | 0.354295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.386350E+11 | 0.292059E+10 | 0.131458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.398222E+11 | 0.133950E+10 | 0.166461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.392660E+11 | 0.111824E+11 | 0.980209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.365455E+11 | 0.760616E+11 | 0.479464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.367588E+11 | 0.932639E+11 | 0.209132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.338869E+11 | 0.332580E+12 | 51529095.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347454E+11 | 0.434922E+12 | 54200966.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.437889E+12 | 0.187520E+13 | 0.437532E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.318998E+11 | 0.133950E+10 | 51529095.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.398222E+11 | 0.434922E+12 | 0.166461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.261333E+10 | 0.275460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.243633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.141195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.211243E+10 | 2616969.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 9958.87 | 0.174643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 25530.76 | 0.831331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 30044.83 | 0.101207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 2765664.03 | 0.609004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 0.118221E+09 | 0.172724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 0.417806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 0.266023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.329465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.131989E+12 | 0.264459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 9958.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.329465E+11 | 0.101207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.687475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35315824.65 | 0.00 | 0.00 | 0.60 |
February | 0.607504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65955757.37 | 0.00 | 0.00 | 0.60 |
March | 0.535778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.482911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
May | 0.473171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 |
June | 0.351338E+11 | 0.00 | 0.00 | 0.00 | 4183801.43 | 0.00 | 0.00 | 0.00 | 0.87 |
July | 0.336822E+11 | 0.00 | 0.00 | 0.00 | 17056338.06 | 0.00 | 0.00 | 0.00 | 0.86 |
August | 0.333702E+11 | 0.00 | 0.00 | 3909204.79 | 0.00 | 0.00 | 0.677915E+10 | 0.00 | 0.83 |
September | 0.201162E+11 | 0.00 | 0.00 | 15608995.69 | 0.00 | 0.00 | 0.303884E+11 | 0.00 | 0.67 |
October | 0.200616E+11 | 0.00 | 0.00 | 16450341.91 | 0.00 | 0.00 | 0.293428E+11 | 0.00 | 0.61 |
November | 0.543252E+11 | 0.00 | 0.00 | 5644099.48 | 0.00 | 0.00 | 0.113503E+11 | 0.00 | 0.61 |
December | 0.748166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
Annual Sum or Average | 0.550190E+12 | 0.00 | 0.00 | 41612641.86 | 21240139.49 | 0.101272E+09 | 0.778607E+11 | 0.00 | 0.69 |
Minimum of Months | 0.200616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.748166E+11 | 0.00 | 0.00 | 16450341.91 | 17056338.06 | 65955757.37 | 0.303884E+11 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 67334539.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772762E+10 | 0.00 | 0.00 | 1.12 |
February | 0.692430E+09 | 0.00 | 0.00 | 7992.96 | 0.00 | 0.518105E+10 | 16142772.35 | 0.00 | 1.03 |
March | 0.191186E+10 | 0.00 | 0.00 | 829715.58 | 0.00 | 0.267956E+10 | 0.587668E+09 | 0.00 | 1.05 |
April | 0.283001E+10 | 0.00 | 0.00 | 3455158.79 | 0.00 | 0.304166E+09 | 0.214797E+10 | 0.00 | 1.30 |
May | 0.266711E+10 | 0.00 | 0.00 | 5297441.81 | 0.00 | 0.00 | 0.242435E+10 | 0.00 | 1.66 |
June | 0.139720E+10 | 1027577.58 | 0.00 | 7976440.73 | 0.00 | 0.00 | 0.242414E+10 | 0.00 | 1.95 |
July | 0.147199E+10 | 3332902.34 | 0.00 | 7888083.76 | 0.00 | 0.00 | 0.200279E+10 | 0.00 | 1.88 |
August | 0.205940E+10 | 0.00 | 0.00 | 6256734.72 | 0.00 | 0.00 | 0.223857E+10 | 0.00 | 1.84 |
September | 0.387423E+10 | 0.00 | 0.00 | 1689748.24 | 0.00 | 54398988.85 | 0.106703E+10 | 0.00 | 1.24 |
October | 0.260294E+10 | 0.00 | 0.00 | 304979.37 | 0.00 | 0.179010E+10 | 0.236564E+09 | 0.00 | 1.03 |
November | 0.143359E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657850E+10 | 0.00 | 0.00 | 1.06 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850905E+10 | 0.00 | 0.00 | 1.14 |
Annual Sum or Average | 0.197179E+11 | 4360479.92 | 0.00 | 33706295.95 | 0.00 | 0.328244E+11 | 0.131452E+11 | 0.00 | 1.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
Maximum of Months | 0.387423E+10 | 3332902.34 | 0.00 | 7976440.73 | 0.00 | 0.850905E+10 | 0.242435E+10 | 0.00 | 1.95 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.599882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138057E+10 | 0.00 | 0.00 | 1.01 |
February | 0.633275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191959E+09 | 0.00 | 0.00 | 1.01 |
March | 0.574811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
April | 0.496315E+10 | 0.00 | 0.00 | 57346.59 | 0.00 | 0.00 | 0.217722E+09 | 0.00 | 1.05 |
May | 0.445826E+10 | 0.00 | 0.00 | 281857.25 | 0.00 | 0.00 | 0.617895E+09 | 0.00 | 1.28 |
June | 0.259235E+10 | 0.00 | 0.00 | 1254470.05 | 448860.93 | 0.00 | 0.118004E+10 | 0.00 | 1.46 |
July | 0.237496E+10 | 413982.95 | 0.00 | 1224567.71 | 1415913.58 | 0.00 | 0.124263E+10 | 0.00 | 1.44 |
August | 0.323986E+10 | 0.00 | 0.00 | 827409.97 | 0.00 | 0.00 | 0.107026E+10 | 0.00 | 1.40 |
September | 0.526748E+10 | 0.00 | 0.00 | 20888.19 | 0.00 | 0.00 | 0.118491E+09 | 0.00 | 1.12 |
October | 0.526260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 |
November | 0.675765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287305E+09 | 0.00 | 0.00 | 1.01 |
December | 0.659297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143376E+10 | 0.00 | 0.00 | 1.01 |
Annual Sum or Average | 0.595890E+11 | 413982.95 | 0.00 | 3666539.76 | 1864774.51 | 0.329360E+10 | 0.444704E+10 | 0.00 | 1.15 |
Minimum of Months | 0.237496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
Maximum of Months | 0.675765E+10 | 413982.95 | 0.00 | 1254470.05 | 1415913.58 | 0.143376E+10 | 0.124263E+10 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5792171.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171478E+10 | 0.00 | 0.00 | 0.08 |
February | 13777471.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104636E+10 | 0.00 | 0.00 | 0.06 |
March | 36643397.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345837E+09 | 0.00 | 0.00 | 0.02 |
April | 58675992.91 | 0.00 | 0.00 | 99377.95 | 0.00 | 5693165.30 | 67909481.94 | 0.00 | 0.01 |
May | 21900786.52 | 0.00 | 0.00 | 1328609.92 | 0.00 | 0.00 | 0.623717E+09 | 0.00 | 0.09 |
June | 373886.40 | 149037.46 | 0.00 | 3409522.16 | 0.00 | 0.00 | 0.117755E+10 | 0.00 | 0.24 |
July | 703608.87 | 720995.99 | 0.00 | 3843681.44 | 0.00 | 0.00 | 0.121365E+10 | 0.00 | 0.25 |
August | 4697724.30 | 0.00 | 0.00 | 2619441.81 | 0.00 | 0.00 | 0.108407E+10 | 0.00 | 0.19 |
September | 51067094.27 | 0.00 | 0.00 | 360139.53 | 0.00 | 0.00 | 0.222208E+09 | 0.00 | 0.03 |
October | 56374067.85 | 0.00 | 0.00 | 7817.33 | 0.00 | 45415608.75 | 6250896.79 | 0.00 | 0.01 |
November | 8148371.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110476E+10 | 0.00 | 0.00 | 0.06 |
December | 3598663.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174054E+10 | 0.00 | 0.00 | 0.09 |
Annual Sum or Average | 0.261753E+09 | 870033.45 | 0.00 | 11668590.14 | 0.00 | 0.600339E+10 | 0.439536E+10 | 0.00 | 0.10 |
Minimum of Months | 373886.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Maximum of Months | 58675992.91 | 720995.99 | 0.00 | 3843681.44 | 0.00 | 0.174054E+10 | 0.121365E+10 | 0.00 | 0.25 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464725E+10 | 0.00 | 0.00 | 0.52 |
February | 75067699.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403393E+10 | 0.00 | 0.00 | 0.52 |
March | 0.561023E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305891E+10 | 0.00 | 0.00 | 0.52 |
April | 0.282384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438905E+09 | 0.00 | 0.00 | 0.54 |
May | 0.319694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
June | 0.237378E+10 | 0.00 | 0.00 | 0.00 | 282674.80 | 0.00 | 0.00 | 0.00 | 0.75 |
July | 0.227571E+10 | 0.00 | 0.00 | 0.00 | 1152396.21 | 0.00 | 0.00 | 0.00 | 0.74 |
August | 0.271292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 |
September | 0.339188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.207477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123940E+10 | 0.00 | 0.00 | 0.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443663E+10 | 0.00 | 0.00 | 0.52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505492E+10 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.194859E+11 | 0.00 | 0.00 | 0.00 | 1435071.00 | 0.229099E+11 | 0.00 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.339188E+10 | 0.00 | 0.00 | 0.00 | 1152396.21 | 0.505492E+10 | 0.00 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.101490E+09 | 0.00 | 0.00 | 0.815901E+11 | 0.00 | 11.69 |
February | 0.00 | 0.00 | 0.00 | 95071065.46 | 0.00 | 0.00 | 0.755997E+11 | 0.00 | 11.92 |
March | 0.00 | 0.00 | 0.00 | 0.107692E+09 | 0.00 | 0.00 | 0.697572E+11 | 0.00 | 12.37 |
April | 0.00 | 0.00 | 0.00 | 0.106040E+09 | 0.00 | 0.00 | 0.666234E+11 | 0.00 | 13.30 |
May | 0.00 | 0.00 | 0.00 | 0.123619E+09 | 0.00 | 0.00 | 0.647279E+11 | 0.00 | 16.77 |
June | 0.00 | 4412399.63 | 0.00 | 0.133189E+09 | 0.00 | 0.00 | 0.475222E+11 | 0.00 | 19.31 |
July | 0.00 | 23219977.02 | 0.00 | 0.139851E+09 | 0.00 | 0.00 | 0.455562E+11 | 0.00 | 18.90 |
August | 0.00 | 0.00 | 0.00 | 0.124978E+09 | 0.00 | 0.00 | 0.550538E+11 | 0.00 | 18.48 |
September | 0.00 | 0.00 | 0.00 | 0.103530E+09 | 0.00 | 0.00 | 0.689942E+11 | 0.00 | 14.50 |
October | 0.00 | 0.00 | 0.00 | 0.105660E+09 | 0.00 | 0.00 | 0.671203E+11 | 0.00 | 12.70 |
November | 0.00 | 0.00 | 0.00 | 99564903.98 | 0.00 | 0.00 | 0.811940E+11 | 0.00 | 11.85 |
December | 0.00 | 0.00 | 0.00 | 0.101026E+09 | 0.00 | 0.00 | 0.901050E+11 | 0.00 | 11.62 |
Annual Sum or Average | 0.00 | 27632376.65 | 0.00 | 0.134171E+10 | 0.00 | 0.00 | 0.813844E+12 | 0.00 | 14.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 95071065.46 | 0.00 | 0.00 | 0.455562E+11 | 0.00 | 11.62 |
Maximum of Months | 0.00 | 23219977.02 | 0.00 | 0.139851E+09 | 0.00 | 0.00 | 0.901050E+11 | 0.00 | 19.31 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.366024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178141E+11 | 0.00 | 0.00 | 3.07 |
February | 0.444710E+11 | 0.00 | 0.00 | 28.11 | 0.00 | 0.363531E+10 | 7556385.94 | 0.00 | 3.06 |
March | 0.382899E+11 | 0.00 | 0.00 | 2529443.50 | 0.00 | 0.312169E+09 | 0.378933E+10 | 0.00 | 3.05 |
April | 0.190388E+11 | 0.00 | 0.00 | 11644923.28 | 0.00 | 0.00 | 0.195080E+11 | 0.00 | 3.22 |
May | 0.132933E+11 | 0.00 | 0.00 | 14273104.39 | 0.00 | 0.00 | 0.242856E+11 | 0.00 | 3.92 |
June | 0.795945E+10 | 3331964.42 | 0.00 | 20373736.09 | 0.00 | 0.00 | 0.198483E+11 | 0.00 | 4.45 |
July | 0.811775E+10 | 13199906.48 | 0.00 | 20813575.89 | 624036.68 | 0.00 | 0.185391E+11 | 0.00 | 4.40 |
August | 0.109364E+11 | 0.00 | 0.00 | 19900988.83 | 0.00 | 0.00 | 0.210054E+11 | 0.00 | 4.30 |
September | 0.244397E+11 | 0.00 | 0.00 | 6383356.10 | 0.00 | 0.00 | 0.153578E+11 | 0.00 | 3.40 |
October | 0.350557E+11 | 0.00 | 0.00 | 1059312.52 | 0.00 | 0.140146E+09 | 0.361289E+10 | 0.00 | 3.07 |
November | 0.395291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124212E+11 | 0.00 | 0.00 | 3.07 |
December | 0.361026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230875E+11 | 0.00 | 0.00 | 3.07 |
Annual Sum or Average | 0.313836E+12 | 16531870.90 | 0.00 | 96978468.71 | 624036.68 | 0.574104E+11 | 0.125954E+12 | 0.00 | 3.51 |
Minimum of Months | 0.795945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 |
Maximum of Months | 0.444710E+11 | 13199906.48 | 0.00 | 20813575.89 | 624036.68 | 0.230875E+11 | 0.242856E+11 | 0.00 | 4.45 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139284E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130161E+11 | 0.00 | 0.00 | 1.24 |
February | 0.134460E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200415E+09 | 0.00 | 0.00 | 1.24 |
March | 0.118209E+12 | 0.00 | 0.00 | 49832.84 | 0.00 | 0.00 | 0.424217E+09 | 0.00 | 1.23 |
April | 0.762760E+11 | 0.00 | 0.00 | 10619724.68 | 0.00 | 0.00 | 0.306549E+11 | 0.00 | 1.29 |
May | 0.498958E+11 | 0.00 | 0.00 | 30559562.06 | 0.00 | 0.00 | 0.549692E+11 | 0.00 | 1.57 |
June | 0.285768E+11 | 1000657.29 | 0.00 | 59636273.13 | 8263199.55 | 0.00 | 0.496699E+11 | 0.00 | 1.81 |
July | 0.242483E+11 | 19713487.55 | 0.00 | 60337393.32 | 18052997.42 | 0.00 | 0.508563E+11 | 0.00 | 1.79 |
August | 0.342614E+11 | 0.00 | 0.00 | 52521935.21 | 0.00 | 0.00 | 0.550957E+11 | 0.00 | 1.73 |
September | 0.767792E+11 | 0.00 | 0.00 | 11108756.37 | 0.00 | 0.00 | 0.343690E+11 | 0.00 | 1.37 |
October | 0.104166E+12 | 0.00 | 0.00 | 840943.08 | 0.00 | 0.00 | 0.444606E+10 | 0.00 | 1.24 |
November | 0.144918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479969E+09 | 0.00 | 0.00 | 1.24 |
December | 0.157904E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.775600E+10 | 0.00 | 0.00 | 1.24 |
Annual Sum or Average | 0.108898E+13 | 20714144.84 | 0.00 | 0.225674E+09 | 26316196.97 | 0.214524E+11 | 0.280485E+12 | 0.00 | 1.42 |
Minimum of Months | 0.242483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 |
Maximum of Months | 0.157904E+12 | 19713487.55 | 0.00 | 60337393.32 | 18052997.42 | 0.130161E+11 | 0.550957E+11 | 0.00 | 1.81 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313387E+10 | 0.00 | 0.00 | 0.34 |
February | 12640658.57 | 0.00 | 0.00 | 4541.26 | 0.00 | 0.284209E+10 | 354934.37 | 0.00 | 0.34 |
March | 63369411.89 | 0.00 | 0.00 | 562297.55 | 0.00 | 0.208861E+10 | 50963930.53 | 0.00 | 0.34 |
April | 47139578.48 | 0.00 | 0.00 | 6774063.91 | 0.00 | 0.744521E+09 | 0.615220E+09 | 0.00 | 0.34 |
May | 12904981.40 | 0.00 | 0.00 | 12934212.44 | 0.00 | 83612760.21 | 0.124994E+10 | 0.00 | 0.34 |
June | 5618808.80 | 1456554.35 | 0.00 | 18843644.67 | 0.00 | 2704411.04 | 0.978328E+09 | 0.00 | 0.34 |
July | 9694162.79 | 5149425.80 | 0.00 | 17137761.31 | 0.00 | 2356254.88 | 0.812175E+09 | 0.00 | 0.34 |
August | 16650340.72 | 27665.92 | 0.00 | 13242422.38 | 0.00 | 43790182.52 | 0.985567E+09 | 0.00 | 0.34 |
September | 58982010.66 | 0.00 | 0.00 | 3922157.21 | 0.00 | 0.648064E+09 | 0.609088E+09 | 0.00 | 0.34 |
October | 46005693.63 | 0.00 | 0.00 | 259024.23 | 0.00 | 0.143549E+10 | 41795600.62 | 0.00 | 0.34 |
November | 494681.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298986E+10 | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348444E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.273500E+09 | 6633646.08 | 0.00 | 73680124.95 | 0.00 | 0.174994E+11 | 0.534344E+10 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2356254.88 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 63369411.89 | 5149425.80 | 0.00 | 18843644.67 | 0.00 | 0.348444E+10 | 0.124994E+10 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313350E+10 | 0.00 | 0.00 | 0.34 |
February | 0.00 | 0.00 | 0.00 | 1708.11 | 0.00 | 0.285453E+10 | 227902.04 | 0.00 | 0.34 |
March | 13127976.94 | 0.00 | 0.00 | 40138.42 | 0.00 | 0.217113E+10 | 18948573.25 | 0.00 | 0.34 |
April | 66123620.37 | 0.00 | 0.00 | 4075094.30 | 0.00 | 0.919780E+09 | 0.423511E+09 | 0.00 | 0.34 |
May | 0.187995E+09 | 0.00 | 0.00 | 9154944.97 | 0.00 | 0.130093E+09 | 0.103199E+10 | 0.00 | 0.34 |
June | 0.212795E+09 | 1296630.43 | 0.00 | 14202825.29 | 159753.26 | 2042959.14 | 0.776336E+09 | 0.00 | 0.34 |
July | 0.186239E+09 | 4502080.36 | 1407.51 | 12620072.38 | 643308.23 | 1779979.24 | 0.640626E+09 | 2026.38 | 0.35 |
August | 0.211206E+09 | 27094.47 | 0.00 | 7825900.45 | 568.21 | 60415445.80 | 0.779679E+09 | 0.00 | 0.34 |
September | 0.100747E+09 | 0.00 | 0.00 | 1871578.20 | 0.00 | 0.827389E+09 | 0.389894E+09 | 0.00 | 0.34 |
October | 22435678.90 | 0.00 | 0.00 | 66350.54 | 0.00 | 0.148782E+10 | 13047715.95 | 0.00 | 0.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299001E+10 | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348403E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.100067E+10 | 5825805.26 | 1407.51 | 49858612.66 | 803629.70 | 0.180625E+11 | 0.407426E+10 | 2026.38 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1779979.24 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.212795E+09 | 4502080.36 | 1407.51 | 14202825.29 | 643308.23 | 0.348403E+10 | 0.103199E+10 | 2026.38 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 28764303.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158675E+10 | 0.00 | 0.00 | 0.02 |
February | 0.567568E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475325E+09 | 0.00 | 0.00 | 0.02 |
March | 0.961912E+09 | 0.00 | 0.00 | 86222.31 | 0.00 | 0.00 | 53291289.49 | 0.00 | 0.02 |
April | 0.194916E+09 | 0.00 | 0.00 | 5136256.78 | 0.00 | 0.00 | 0.121437E+10 | 0.00 | 0.02 |
May | 46112482.36 | 0.00 | 0.00 | 5377539.20 | 0.00 | 0.00 | 0.132243E+10 | 0.00 | 0.02 |
June | 42805097.32 | 2236465.14 | 0.00 | 5353004.40 | 0.00 | 0.00 | 0.982247E+09 | 0.00 | 0.02 |
July | 0.00 | 9384865.07 | 0.00 | 5409255.29 | 0.00 | 0.00 | 0.690395E+09 | 0.00 | 0.02 |
August | 37188853.91 | 0.00 | 0.00 | 5818697.36 | 0.00 | 0.00 | 0.923439E+09 | 0.00 | 0.02 |
September | 0.487607E+09 | 0.00 | 0.00 | 2644482.81 | 0.00 | 0.00 | 0.867000E+09 | 0.00 | 0.02 |
October | 0.932175E+09 | 0.00 | 0.00 | 354613.80 | 0.00 | 29297128.40 | 0.166652E+09 | 0.00 | 0.02 |
November | 0.189592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129851E+10 | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195678E+10 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.348864E+10 | 11621330.21 | 0.00 | 30180071.94 | 0.00 | 0.534666E+10 | 0.621982E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.961912E+09 | 9384865.07 | 0.00 | 5818697.36 | 0.00 | 0.195678E+10 | 0.132243E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.232636E+09 | 0.00 | 0.00 | 125750.46 | 0.00 | 0.422508E+11 | 20467435.01 | 0.00 | 0.39 |
February | 0.368893E+09 | 0.00 | 0.00 | 218223.68 | 0.00 | 0.382320E+11 | 0.121913E+09 | 0.00 | 0.39 |
March | 0.912534E+09 | 0.00 | 0.00 | 1572366.72 | 0.00 | 0.275520E+11 | 0.141962E+10 | 0.00 | 0.39 |
April | 0.106766E+10 | 0.00 | 0.00 | 29370184.84 | 0.00 | 0.711856E+10 | 0.109575E+11 | 0.00 | 0.39 |
May | 0.278238E+10 | 0.00 | 0.00 | 0.108592E+09 | 0.00 | 32751995.42 | 0.155135E+11 | 0.00 | 0.39 |
June | 0.356138E+10 | 14968626.21 | 0.00 | 0.169453E+09 | 4786344.92 | 6628031.60 | 0.989987E+10 | 0.00 | 0.39 |
July | 0.283483E+10 | 59766092.83 | 74931.06 | 0.162926E+09 | 9994579.82 | 4464216.87 | 0.840903E+10 | 5084.35 | 0.39 |
August | 0.305329E+10 | 367520.27 | 0.00 | 0.105566E+09 | 7707.42 | 28436865.92 | 0.111791E+11 | 0.00 | 0.39 |
September | 0.138744E+10 | 0.00 | 0.00 | 40139616.19 | 0.00 | 0.165144E+10 | 0.148247E+11 | 0.00 | 0.39 |
October | 0.922142E+09 | 0.00 | 0.00 | 6909414.21 | 0.00 | 0.142571E+11 | 0.547749E+10 | 0.00 | 0.39 |
November | 0.220110E+09 | 0.00 | 0.00 | 98825.12 | 0.00 | 0.403217E+11 | 15719662.05 | 0.00 | 0.39 |
December | 0.115059E+09 | 0.00 | 0.00 | 58577.20 | 0.00 | 0.471294E+11 | 14301530.25 | 0.00 | 0.39 |
Annual Sum or Average | 0.174584E+11 | 75102239.31 | 74931.06 | 0.625030E+09 | 14788632.16 | 0.218585E+12 | 0.778532E+11 | 5084.35 | 0.39 |
Minimum of Months | 0.115059E+09 | 0.00 | 0.00 | 58577.20 | 0.00 | 4464216.87 | 14301530.25 | 0.00 | 0.39 |
Maximum of Months | 0.356138E+10 | 59766092.83 | 74931.06 | 0.169453E+09 | 9994579.82 | 0.471294E+11 | 0.155135E+11 | 5084.35 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313387E+10 | 0.00 | 0.00 | 0.34 |
February | 22308634.69 | 0.00 | 0.00 | 3306.06 | 0.00 | 0.283256E+10 | 223448.12 | 0.00 | 0.34 |
March | 72762362.28 | 0.00 | 0.00 | 702812.56 | 0.00 | 0.200986E+10 | 0.120186E+09 | 0.00 | 0.34 |
April | 28132213.48 | 0.00 | 0.00 | 5917291.54 | 0.00 | 0.732093E+09 | 0.647512E+09 | 0.00 | 0.34 |
May | 7432446.57 | 0.00 | 0.00 | 15748256.27 | 0.00 | 53652835.55 | 0.128256E+10 | 0.00 | 0.34 |
June | 6647829.48 | 1456554.35 | 0.00 | 20184114.72 | 0.00 | 1165167.77 | 0.977498E+09 | 0.00 | 0.34 |
July | 6935351.99 | 5149425.80 | 0.00 | 21163730.34 | 0.00 | 1500060.01 | 0.811764E+09 | 0.00 | 0.34 |
August | 10158602.98 | 27665.92 | 0.00 | 14826089.45 | 0.00 | 36139200.31 | 0.998126E+09 | 0.00 | 0.34 |
September | 44652208.57 | 0.00 | 0.00 | 4680380.60 | 0.00 | 0.573798E+09 | 0.696926E+09 | 0.00 | 0.34 |
October | 51298893.15 | 0.00 | 0.00 | 442456.30 | 0.00 | 0.136964E+10 | 0.102174E+09 | 0.00 | 0.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299036E+10 | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348444E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.250329E+09 | 6633646.08 | 0.00 | 83668437.83 | 0.00 | 0.172191E+11 | 0.563697E+10 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1165167.77 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 72762362.28 | 5149425.80 | 0.00 | 21163730.34 | 0.00 | 0.348444E+10 | 0.128256E+10 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313350E+10 | 0.00 | 0.00 | 0.34 |
February | 387220.50 | 0.00 | 0.00 | 1528.83 | 0.00 | 0.285420E+10 | 163155.25 | 0.00 | 0.34 |
March | 50651267.24 | 0.00 | 0.00 | 154738.45 | 0.00 | 0.210464E+10 | 47804235.81 | 0.00 | 0.34 |
April | 66981693.11 | 0.00 | 0.00 | 3271633.25 | 0.00 | 0.885082E+09 | 0.458154E+09 | 0.00 | 0.34 |
May | 0.134517E+09 | 0.00 | 0.00 | 12372248.94 | 0.00 | 91191782.88 | 0.112115E+10 | 0.00 | 0.34 |
June | 0.214467E+09 | 1296630.43 | 0.00 | 16561262.50 | 159753.26 | 1199552.14 | 0.773149E+09 | 0.00 | 0.34 |
July | 0.175165E+09 | 4505514.25 | 0.00 | 16027053.88 | 643308.23 | 1147814.54 | 0.648925E+09 | 0.00 | 0.35 |
August | 0.192106E+09 | 27094.47 | 0.00 | 9988794.38 | 568.21 | 47077371.87 | 0.809954E+09 | 0.00 | 0.34 |
September | 98442966.53 | 0.00 | 0.00 | 2633481.51 | 0.00 | 0.698711E+09 | 0.520115E+09 | 0.00 | 0.34 |
October | 33857838.16 | 0.00 | 0.00 | 121830.70 | 0.00 | 0.145315E+10 | 36246534.54 | 0.00 | 0.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299001E+10 | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348403E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.966577E+09 | 5829239.15 | 0.00 | 61132572.44 | 803629.70 | 0.177439E+11 | 0.441566E+10 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1147814.54 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.214467E+09 | 4505514.25 | 0.00 | 16561262.50 | 643308.23 | 0.348403E+10 | 0.112115E+10 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365050E+11 | 0.00 | 0.00 | 0.34 |
February | 0.633459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274211E+11 | 0.00 | 0.00 | 0.34 |
March | 0.199994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973677E+10 | 0.00 | 0.00 | 0.34 |
April | 0.263226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479409E+09 | 0.00 | 0.00 | 0.35 |
May | 0.262615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.186425E+11 | 0.00 | 0.00 | 822544.34 | 2322051.30 | 0.00 | 0.857846E+09 | 0.00 | 0.49 |
July | 0.177581E+11 | 0.00 | 0.00 | 1316674.56 | 9466436.83 | 0.00 | 0.936327E+09 | 0.00 | 0.48 |
August | 0.222225E+11 | 0.00 | 0.00 | 12170.59 | 0.00 | 0.00 | 62989477.14 | 0.00 | 0.47 |
September | 0.278629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
October | 0.207886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643589E+10 | 0.00 | 0.00 | 0.34 |
November | 0.186790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345823E+11 | 0.00 | 0.00 | 0.34 |
December | 0.574796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409644E+11 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.190321E+12 | 0.00 | 0.00 | 2151389.49 | 11788488.14 | 0.156125E+12 | 0.185716E+10 | 0.00 | 0.39 |
Minimum of Months | 0.574796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.278629E+11 | 0.00 | 0.00 | 1316674.56 | 9466436.83 | 0.409644E+11 | 0.936327E+09 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783467E+09 | 0.00 | 0.00 | 0.34 |
February | 567183.29 | 0.00 | 0.00 | 365.04 | 0.00 | 0.713190E+09 | 15147.66 | 0.00 | 0.34 |
March | 12213429.75 | 0.00 | 0.00 | 106464.41 | 0.00 | 0.526844E+09 | 11713716.55 | 0.00 | 0.34 |
April | 12091816.86 | 0.00 | 0.00 | 1648569.64 | 0.00 | 0.217364E+09 | 0.122310E+09 | 0.00 | 0.34 |
May | 3588818.51 | 0.00 | 0.00 | 3049945.30 | 0.00 | 59946852.13 | 0.273263E+09 | 0.00 | 0.34 |
June | 1693031.96 | 364138.59 | 0.00 | 4565174.39 | 0.00 | 1039878.61 | 0.244076E+09 | 0.00 | 0.34 |
July | 2518502.87 | 1287356.45 | 0.00 | 4096127.75 | 0.00 | 4621512.04 | 0.199105E+09 | 0.00 | 0.34 |
August | 3895421.61 | 6916.48 | 0.00 | 3096436.32 | 0.00 | 25729868.44 | 0.232091E+09 | 0.00 | 0.34 |
September | 15452391.91 | 0.00 | 0.00 | 871141.95 | 0.00 | 0.219110E+09 | 94580506.68 | 0.00 | 0.34 |
October | 6501049.03 | 0.00 | 0.00 | 42969.00 | 0.00 | 0.369379E+09 | 4965262.71 | 0.00 | 0.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747590E+09 | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871110E+09 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 58521645.78 | 1658411.52 | 0.00 | 17477193.80 | 0.00 | 0.453939E+10 | 0.118212E+10 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1039878.61 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 15452391.91 | 1287356.45 | 0.00 | 4565174.39 | 0.00 | 0.871110E+09 | 0.273263E+09 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783375E+09 | 0.00 | 0.00 | 0.34 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713689E+09 | 0.00 | 0.00 | 0.34 |
March | 1474486.05 | 0.00 | 0.00 | 7078.41 | 0.00 | 0.548735E+09 | 596380.18 | 0.00 | 0.34 |
April | 14593872.47 | 0.00 | 0.00 | 948546.98 | 0.00 | 0.256786E+09 | 81044020.90 | 0.00 | 0.34 |
May | 46374692.67 | 0.00 | 0.00 | 2150043.97 | 0.00 | 67161534.57 | 0.224123E+09 | 0.00 | 0.34 |
June | 52832584.27 | 324157.61 | 0.00 | 3664651.11 | 39938.32 | 572881.84 | 0.194274E+09 | 0.00 | 0.34 |
July | 46112567.74 | 1125520.09 | 170.43 | 3136227.94 | 160827.06 | 1928364.75 | 0.159139E+09 | 688.05 | 0.35 |
August | 52338142.89 | 6773.62 | 0.00 | 1803952.02 | 142.05 | 27814640.95 | 0.182825E+09 | 0.00 | 0.34 |
September | 22400833.85 | 0.00 | 0.00 | 370720.03 | 0.00 | 0.251363E+09 | 55840526.44 | 0.00 | 0.34 |
October | 4128134.65 | 0.00 | 0.00 | 8354.00 | 0.00 | 0.375999E+09 | 707796.59 | 0.00 | 0.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747502E+09 | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871008E+09 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.240255E+09 | 1456451.32 | 170.43 | 12089574.46 | 200907.43 | 0.464593E+10 | 0.898549E+09 | 688.05 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572881.84 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 52832584.27 | 1125520.09 | 170.43 | 3664651.11 | 160827.06 | 0.871008E+09 | 0.224123E+09 | 688.05 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 36792372.58 | 0.00 | 0.00 | 121.05 | 0.00 | 0.499644E+10 | 136415.75 | 0.00 | 0.39 |
February | 80621724.30 | 0.00 | 0.00 | 386581.95 | 0.00 | 0.445207E+10 | 52550668.54 | 0.00 | 0.39 |
March | 51047271.12 | 0.00 | 0.00 | 4099478.72 | 0.00 | 0.308348E+10 | 0.400474E+09 | 0.00 | 0.39 |
April | 15759379.45 | 0.00 | 0.00 | 12847706.07 | 0.00 | 0.893397E+09 | 0.134850E+10 | 0.00 | 0.39 |
May | 8077007.15 | 0.00 | 0.00 | 19526452.04 | 0.00 | 83589621.97 | 0.207216E+10 | 0.00 | 0.39 |
June | 9626638.52 | 2339404.48 | 0.00 | 24434574.58 | 0.00 | 4289031.67 | 0.157660E+10 | 0.00 | 0.39 |
July | 12075863.43 | 8270607.80 | 0.00 | 24306018.30 | 0.00 | 3779994.84 | 0.131117E+10 | 0.00 | 0.39 |
August | 16065049.89 | 44434.86 | 0.00 | 21072409.35 | 0.00 | 38726296.94 | 0.162542E+10 | 0.00 | 0.39 |
September | 45421094.03 | 0.00 | 0.00 | 9760404.75 | 0.00 | 0.574933E+09 | 0.149006E+10 | 0.00 | 0.39 |
October | 79072066.50 | 0.00 | 0.00 | 2286774.19 | 0.00 | 0.195408E+10 | 0.411576E+09 | 0.00 | 0.39 |
November | 32293890.49 | 0.00 | 0.00 | 13637.23 | 0.00 | 0.476514E+10 | 5432276.23 | 0.00 | 0.39 |
December | 0.00 | 0.00 | 0.00 | 1786.04 | 0.00 | 0.559633E+10 | 107329.63 | 0.00 | 0.39 |
Annual Sum or Average | 0.386852E+09 | 10654447.13 | 0.00 | 0.118736E+09 | 0.00 | 0.264463E+11 | 0.102942E+11 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 121.05 | 0.00 | 3779994.84 | 107329.63 | 0.00 | 0.39 |
Maximum of Months | 80621724.30 | 8270607.80 | 0.00 | 24434574.58 | 0.00 | 0.559633E+10 | 0.207216E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.683196E+11 | 0.00 | 0.00 | 4570356.48 | 0.00 | 0.370547E+10 | 0.235200E+11 | 0.00 | 4.00 |
February | 0.618846E+11 | 0.00 | 0.00 | 4931365.21 | 0.00 | 0.150583E+09 | 0.224428E+11 | 0.00 | 3.98 |
March | 0.443573E+11 | 0.00 | 0.00 | 8838017.26 | 0.00 | 0.00 | 0.300614E+11 | 0.00 | 3.97 |
April | 0.262573E+11 | 0.00 | 0.00 | 17619803.53 | 0.00 | 0.00 | 0.408087E+11 | 0.00 | 4.13 |
May | 0.157394E+11 | 0.00 | 0.00 | 32708130.36 | 0.00 | 0.00 | 0.500025E+11 | 0.00 | 5.05 |
June | 0.611795E+10 | 5570698.88 | 0.00 | 47625921.49 | 241225.77 | 0.00 | 0.428998E+11 | 0.00 | 5.80 |
July | 0.553344E+10 | 20699123.26 | 0.00 | 46880084.19 | 2994676.08 | 0.00 | 0.414249E+11 | 0.00 | 5.71 |
August | 0.115354E+11 | 0.00 | 0.00 | 37928731.18 | 0.00 | 0.00 | 0.443210E+11 | 0.00 | 5.52 |
September | 0.234017E+11 | 0.00 | 0.00 | 21789200.89 | 0.00 | 0.00 | 0.463153E+11 | 0.00 | 4.41 |
October | 0.322478E+11 | 0.00 | 0.00 | 12780647.29 | 0.00 | 0.00 | 0.358803E+11 | 0.00 | 4.00 |
November | 0.681014E+11 | 0.00 | 0.00 | 4225023.88 | 0.00 | 0.00 | 0.231135E+11 | 0.00 | 3.99 |
December | 0.818921E+11 | 0.00 | 0.00 | 2888962.24 | 0.00 | 0.129748E+10 | 0.207390E+11 | 0.00 | 4.00 |
Annual Sum or Average | 0.445388E+12 | 26269822.15 | 0.00 | 0.242786E+09 | 3235901.84 | 0.515354E+10 | 0.421529E+12 | 0.00 | 4.55 |
Minimum of Months | 0.553344E+10 | 0.00 | 0.00 | 2888962.24 | 0.00 | 0.00 | 0.207390E+11 | 0.00 | 3.97 |
Maximum of Months | 0.818921E+11 | 20699123.26 | 0.00 | 47625921.49 | 2994676.08 | 0.370547E+10 | 0.500025E+11 | 0.00 | 5.80 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.603580E+11 | 0.00 | 0.00 | 8371684.78 | 0.00 | 0.222041E+10 | 0.329301E+11 | 0.00 | 4.00 |
February | 0.528331E+11 | 0.00 | 0.00 | 8634520.97 | 0.00 | 5730074.97 | 0.316066E+11 | 0.00 | 3.98 |
March | 0.362062E+11 | 0.00 | 0.00 | 14370663.25 | 0.00 | 0.00 | 0.381814E+11 | 0.00 | 3.97 |
April | 0.209573E+11 | 0.00 | 0.00 | 24846990.10 | 0.00 | 0.00 | 0.460969E+11 | 0.00 | 4.14 |
May | 0.755733E+10 | 0.00 | 0.00 | 42596454.56 | 0.00 | 0.00 | 0.584029E+11 | 0.00 | 5.08 |
June | 0.363338E+10 | 5809936.93 | 0.00 | 59037815.65 | 0.00 | 0.00 | 0.457097E+11 | 0.00 | 5.84 |
July | 0.303711E+10 | 21463092.83 | 0.00 | 59298059.72 | 2222603.02 | 0.00 | 0.442144E+11 | 0.00 | 5.75 |
August | 0.606467E+10 | 0.00 | 0.00 | 47803809.68 | 0.00 | 0.00 | 0.500364E+11 | 0.00 | 5.55 |
September | 0.176909E+11 | 0.00 | 0.00 | 30025059.00 | 0.00 | 0.00 | 0.520449E+11 | 0.00 | 4.41 |
October | 0.267653E+11 | 0.00 | 0.00 | 19863237.32 | 0.00 | 0.00 | 0.413325E+11 | 0.00 | 4.00 |
November | 0.603846E+11 | 0.00 | 0.00 | 7857906.73 | 0.00 | 0.00 | 0.307955E+11 | 0.00 | 3.99 |
December | 0.689999E+11 | 0.00 | 0.00 | 6054475.14 | 0.00 | 46520973.92 | 0.348434E+11 | 0.00 | 4.00 |
Annual Sum or Average | 0.364488E+12 | 27273029.76 | 0.00 | 0.328761E+09 | 2222603.02 | 0.227266E+10 | 0.506195E+12 | 0.00 | 4.56 |
Minimum of Months | 0.303711E+10 | 0.00 | 0.00 | 6054475.14 | 0.00 | 0.00 | 0.307955E+11 | 0.00 | 3.97 |
Maximum of Months | 0.689999E+11 | 21463092.83 | 0.00 | 59298059.72 | 2222603.02 | 0.222041E+10 | 0.584029E+11 | 0.00 | 5.84 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 92272228.10 | 0.00 | 0.00 | 96895471.23 | 0.00 | 0.00 | 0.743857E+11 | 0.00 | 10.74 |
February | 11899587.72 | 0.00 | 0.00 | 93130648.72 | 0.00 | 0.00 | 0.693276E+11 | 0.00 | 11.20 |
March | 0.00 | 0.00 | 0.00 | 0.109519E+09 | 0.00 | 0.00 | 0.668453E+11 | 0.00 | 12.03 |
April | 0.00 | 0.00 | 0.00 | 0.112715E+09 | 0.00 | 0.00 | 0.668572E+11 | 0.00 | 13.53 |
May | 0.00 | 0.00 | 0.00 | 0.134423E+09 | 0.00 | 0.00 | 0.663469E+11 | 0.00 | 17.90 |
June | 0.00 | 7409603.40 | 0.00 | 0.144879E+09 | 0.00 | 0.00 | 0.496202E+11 | 0.00 | 20.48 |
July | 0.00 | 30187877.60 | 0.00 | 0.153078E+09 | 0.00 | 0.00 | 0.461950E+11 | 0.00 | 20.03 |
August | 0.00 | 0.00 | 0.00 | 0.134162E+09 | 0.00 | 0.00 | 0.559166E+11 | 0.00 | 19.31 |
September | 0.00 | 0.00 | 0.00 | 0.108578E+09 | 0.00 | 0.00 | 0.688321E+11 | 0.00 | 14.78 |
October | 0.00 | 0.00 | 0.00 | 0.106228E+09 | 0.00 | 0.00 | 0.648923E+11 | 0.00 | 12.34 |
November | 0.00 | 0.00 | 0.00 | 95440412.85 | 0.00 | 0.00 | 0.739820E+11 | 0.00 | 10.87 |
December | 3851347.53 | 0.00 | 0.00 | 96001866.70 | 0.00 | 0.00 | 0.816969E+11 | 0.00 | 10.58 |
Annual Sum or Average | 0.108023E+09 | 37597481.00 | 0.00 | 0.138505E+10 | 0.00 | 0.00 | 0.784898E+12 | 0.00 | 14.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 93130648.72 | 0.00 | 0.00 | 0.461950E+11 | 0.00 | 10.58 |
Maximum of Months | 92272228.10 | 30187877.60 | 0.00 | 0.153078E+09 | 0.00 | 0.00 | 0.816969E+11 | 0.00 | 20.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125984E+11 | 0.00 | 0.00 | 0.38 |
February | 0.408901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913686E+10 | 0.00 | 0.00 | 0.35 |
March | 0.285876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516057E+10 | 0.00 | 0.00 | 0.34 |
April | 0.622892E+10 | 0.00 | 0.00 | 424563.21 | 0.00 | 0.559441E+09 | 0.324207E+09 | 0.00 | 0.35 |
May | 0.442568E+10 | 0.00 | 0.00 | 6092260.42 | 0.00 | 0.00 | 0.300400E+10 | 0.00 | 0.49 |
June | 0.533391E+09 | 1489331.48 | 0.00 | 18379798.09 | 0.00 | 0.00 | 0.623831E+10 | 0.00 | 0.73 |
July | 0.755628E+09 | 5492376.63 | 0.00 | 18860544.51 | 0.00 | 0.00 | 0.543919E+10 | 0.00 | 0.70 |
August | 0.274952E+10 | 0.00 | 0.00 | 9834497.72 | 0.00 | 0.00 | 0.379377E+10 | 0.00 | 0.58 |
September | 0.726908E+10 | 0.00 | 0.00 | 96456.87 | 0.00 | 25366450.36 | 75275534.35 | 0.00 | 0.37 |
October | 0.439043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280920E+10 | 0.00 | 0.00 | 0.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113880E+11 | 0.00 | 0.00 | 0.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138187E+11 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.296203E+11 | 6981708.11 | 0.00 | 53688120.83 | 0.00 | 0.554966E+11 | 0.188747E+11 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.726908E+10 | 5492376.63 | 0.00 | 18860544.51 | 0.00 | 0.138187E+11 | 0.623831E+10 | 0.00 | 0.73 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:50:54
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.402264E+11 | 0.365448E+11 | 0.460464E+12 | 0.115280E+13 | 0.153320E+12 |
February | 0.175456E+11 | 0.314498E+11 | 0.387962E+12 | 0.100022E+13 | 0.127717E+12 |
March | 0.183981E+12 | 0.305779E+11 | 0.376632E+12 | 0.100343E+13 | 0.105048E+12 |
April | 0.364412E+12 | 0.200873E+11 | 0.246242E+12 | 0.705375E+12 | 0.124908E+12 |
May | 0.490351E+12 | 0.122555E+11 | 0.144263E+12 | 0.504706E+12 | 0.209174E+12 |
June | 0.510199E+12 | 0.788036E+10 | 0.911228E+11 | 0.374074E+12 | 0.369855E+12 |
July | 0.454258E+12 | 0.707193E+10 | 0.852626E+11 | 0.352413E+12 | 0.427920E+12 |
August | 0.332988E+12 | 0.929579E+10 | 0.111685E+12 | 0.423167E+12 | 0.296046E+12 |
September | 0.141376E+12 | 0.145408E+11 | 0.186278E+12 | 0.549386E+12 | 0.114095E+12 |
October | 0.460282E+11 | 0.238644E+11 | 0.308681E+12 | 0.812811E+12 | 0.937236E+11 |
November | -0.161029E+11 | 0.356349E+11 | 0.443467E+12 | 0.113102E+13 | 0.143308E+12 |
December | -0.528910E+11 | 0.379835E+11 | 0.471476E+12 | 0.119130E+13 | 0.168424E+12 |
Annual Sum or Average | 0.243192E+13 | 0.267187E+12 | 0.331354E+13 | 0.920070E+13 | 0.233354E+13 |
Minimum of Months | -0.528910E+11 | 0.707193E+10 | 0.852626E+11 | 0.352413E+12 | 0.937236E+11 |