Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:51
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 08:51:18
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 12223.43 | 1077.40 | 1077.40 |
Net Site Energy | 12223.43 | 1077.40 | 1077.40 |
Total Source Energy | 22611.29 | 1993.01 | 1993.01 |
Net Source Energy | 22611.29 | 1993.01 | 1993.01 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2457.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 557.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 544.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 640.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 561.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 89.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 124.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 3482.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 43.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4494.04 | 7729.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2457.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 557.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 544.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 561.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 89.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 124.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 3482.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 20.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2457.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 557.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 544.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 640.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 561.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 89.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 124.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 3482.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 43.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 114.49 | 523.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 216.59 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 396.12 | 681.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 114.49 | 523.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 216.59 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 396.12 | 681.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4494.043 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4494.043 | 100.00 |
Total On-Site and Utility Electric Sources | 4494.043 | 100.00 |
Total Electricity End Uses | 4494.043 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 78.48 | 2.97 |
Air to Air Heat Recovery for Heating | 2562.60 | 97.03 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2641.08 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 309.17 |
Time Setpoint Not Met During Occupied Cooling | 49.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8014.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:51 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.7179 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 9.6995 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.6995 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.2862 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 9.2569 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.0417 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4132 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8577 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8577 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.7179 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 4.2862 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.7049 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 9.2569 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.0417 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4132 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7327 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4132 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.8577 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.8577 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.7137 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-18:10 | 04-JAN-21:49 | - | - | - | - | - | - | - | - | - | - | 03-MAY-20:40 |
Heating | 0.00 | 622862.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 180947.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 36642.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 77265.07 | 75123.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31327.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 29162.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5857.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4738.52 | 306515.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1690.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 375896.10 | 1004501.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 622862.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 180947.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 36642.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 47590.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1023.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 29162.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 5857.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4738.52 | 306515.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 791.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 669.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2664.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1766.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1724.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 612.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5220.66 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2028.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1777.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 282.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 393.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.38 | 3775.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 138.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 14232.63 | 8378.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 234.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 155.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 151.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 34.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 332.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1254.50 | 738.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 234.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 155.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 151.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 34.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 332.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1254.50 | 738.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.28 | 0.661432 | 0.562000 | 1.28 | 1.00 | 0.500000 | 0.000576 | 0.000068 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.416967 | 0.122572 | 0.285000 | 0.118836 | 0.339538 | 0.500000 | 0.003108 | 0.000043 | 0.179860 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.225530 | 0.262420 | 0.610000 | 0.137574 | 0.699787 | 0.500000 | 0.001452 | 0.000018 | 0.137574 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.179736 | 0.696318 | 0.010000 | 0.001797 | 1.00 | 0.500000 | 0.000547 | 0.000027 | 0.111645 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.098413 | 0.733711 | 0.880000 | 0.086603 | 1.00 | 0.500000 | 0.000519 | 0.000019 | 0.086603 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.40 | 0.017511 | 0.010000 | 0.033960 | 0.300000 | 0.500000 | 0.021758 | 0.000035 | 0.147988 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.72 | 0.083786 | 0.591000 | 1.02 | 0.591000 | 0.500000 | 0.004547 | 0.000133 | 1.02 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.04 | 0.197935 | 0.564000 | 2.84 | 0.564000 | 0.500000 | 0.001925 | 0.000332 | 2.84 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.32 | 0.896318 | 0.538000 | 0.712420 | 1.00 | 0.500000 | 0.000425 | 0.000150 | 0.712420 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.18 | 0.115711 | 0.816000 | 1.78 | 0.816000 | 0.500000 | 0.003293 | 0.000156 | 1.78 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.29 | 0.110167 | 0.777000 | 1.78 | 0.777000 | 0.500000 | 0.003458 | 0.000157 | 1.78 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.30 | 0.061683 | 0.240000 | 0.550888 | 0.300000 | 0.500000 | 0.011110 | 0.000064 | 0.550888 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.726799 | 0.432085 | 0.259000 | 0.188241 | 1.00 | 0.500000 | 0.000882 | 0.000099 | 0.411072 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 7807.44 | 0.000068 | 164.56 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4930.32 | 0.000043 | 134.55 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2020.37 | 0.000018 | 46.80 |
MECH_FLR_1 VAV BOX REHEAT COIL | 3060.20 | 0.000027 | 83.51 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 2132.81 | 0.000019 | 55.98 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 4056.34 | 0.000035 | 110.70 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 15213.64 | 0.000133 | 353.63 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 37999.26 | 0.000332 | 866.95 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 9095.19 | 0.000080 | 259.91 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 9102.05 | 0.000080 | 260.11 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 51404.31 | 0.000450 | 1468.95 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 51550.13 | 0.000451 | 1473.12 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 9109.87 | 0.000080 | 260.33 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 9116.73 | 0.000080 | 260.52 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 17200.22 | 0.000150 | 448.52 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2747.27 | 0.000024 | 78.50 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2747.44 | 0.000024 | 78.51 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 13126.77 | 0.000115 | 375.10 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 17827.00 | 0.000156 | 391.66 |
DINING_FLR_6 VAV BOX REHEAT COIL | 17999.17 | 0.000157 | 395.86 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7328.36 | 0.000064 | 167.05 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11269.08 | 0.000099 | 307.55 |
VAV WITH REHEAT HEATING COIL | 379009.20 | 0.003316 | 5274.96 |
FLR_3_DOAS HEATING COIL | 35250.36 | 0.000308 | 490.61 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.17 | 0.000080 | 0.000365 |
ROOM_2_FLR_3 FAN COIL | 1.11 | 0.000080 | 0.000348 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.20 | 0.000450 | 0.002199 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.40 | 0.000451 | 0.001780 |
ROOM_5_FLR_3 FAN COIL | 1.06 | 0.000080 | 0.000332 |
ROOM_6_FLR_3 FAN COIL | 1.00 | 0.000080 | 0.000315 |
ROOM_1_FLR_6 FAN COIL | 0.304886 | 0.000024 | 0.000095 |
ROOM_2_FLR_6 FAN COIL | 0.288665 | 0.000024 | 0.000090 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.50 | 0.000115 | 0.000473 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.17 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.11 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.20 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.40 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.06 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.304886 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.288665 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.50 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008642 | 12.80 | 0.008500 | 0.000365 | 1.17 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008648 | 12.80 | 0.008500 | 0.000348 | 1.11 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008566 | 12.80 | 0.008500 | 0.002199 | 7.20 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008855 | 12.80 | 0.008500 | 0.001780 | 5.40 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008657 | 12.80 | 0.008500 | 0.000332 | 1.06 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008666 | 12.80 | 0.008500 | 0.000315 | 1.00 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008636 | 12.80 | 0.008500 | 0.000095 | 0.304886 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008643 | 12.80 | 0.008500 | 0.000090 | 0.288665 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008683 | 12.80 | 0.008500 | 0.000473 | 1.50 | |
VAV WITH REHEAT COOLING COIL | 26.57 | 6.70 | 0.010985 | 10.91 | 0.008500 | 0.016253 | 22.06 | 568294.77 |
FLR_3_DOAS COOLING COIL | 30.10 | 6.70 | 0.012726 | 11.90 | 0.008500 | 0.001989 | 2.05 | 69550.09 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 13.15 | 10.53 | 22.17 | 10.53 | 22.06 | 22.06 | 0.300000 | 0.477506 | 22.06 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 22.06 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 9.33 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.06 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.016253 | 0.000029 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.003316 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001989 | 0.000239 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000308 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.024239 | 3918.28 | |
HEATSYS1 PUMP | 0.006309 | 1881.04 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.006309 | 0.757023 |
COOLSYS1 | 0.024239 | 2.91 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 721103.55 | 721103.55 | 0.006309 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.024239 | 2712.76 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.024239 | 847515.67 | 848127.23 | 96.69 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.718 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.098 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 4.286 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.976 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.257 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.637 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.042 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.112 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 13293.583 | 6.718 | 124.824 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13293.583 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 650.557 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 650.557 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 753.347 | 9.699 | 60.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 753.347 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 406.155 | 4.286 | 199.096 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 406.155 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1748.285 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1748.285 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11828.200 | 9.042 | 28.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11828.200 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1718.521 | 4.413 | 82.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.521 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.035 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.035 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1818.789 | 4.413 | 82.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.789 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.5913 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.7799 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.7924 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.7799 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.7924 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.524 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.095 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.095 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
21 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
22 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
23 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
24 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
25 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
26 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
27 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
28 | 9 | 0.57998040E-15 | -0.30968906E-15 | -0.16543531E-09 | -0.94394381E-17 |
29 | 8 | 0.24079056E-07 | 0.80583727E-13 | 0.40057412E-03 | -0.27378716E-09 |
30 | 7 | -0.12920082E-01 | 0.41010748E-08 | -0.24062383E-01 | 0.14690605E-03 |
31 | 6 | 0.42378547 | 0.14160748E-05 | 0.48776087 | -0.49650686E-02 |
32 | 5 | -5.3704470 | 0.52534619E-04 | -4.5614765 | 0.65414341E-01 |
33 | 4 | 33.798395 | 0.42724899E-03 | 21.909926 | -0.43268566 |
34 | 3 | -112.91846 | 0.92631763E-03 | -56.552255 | 1.5396438 |
35 | 2 | 198.80798 | 0.51863526E-03 | 78.726696 | -2.9273457 |
36 | 1 | -171.78376 | 0.55128408E-04 | -55.503401 | 2.7564403 |
37 | 0 | 57.057407 | 0.31226006E-06 | 15.518392 | |
38 | 9 | -0.46044427E-14 | 0.27900089E-16 | -0.15673021E-09 | 0.84433218E-16 |
39 | 8 | 0.22857479E-07 | 0.10577188E-12 | 0.38804207E-03 | -0.25989740E-09 |
40 | 7 | -0.12547140E-01 | 0.54349272E-08 | -0.23525725E-01 | 0.14266556E-03 |
41 | 6 | 0.41365335 | 0.18858798E-05 | 0.47915629 | -0.48456347E-02 |
42 | 5 | -5.2715868 | 0.70260405E-04 | -4.4954992 | 0.64188504E-01 |
43 | 4 | 33.361217 | 0.57360532E-03 | 21.652286 | -0.42688098 |
44 | 3 | -111.98862 | 0.12479141E-02 | -56.043016 | 1.5262094 |
45 | 2 | 197.88677 | 0.70084509E-03 | 78.259217 | -2.9127162 |
46 | 1 | -171.44362 | 0.74708721E-04 | -55.366651 | 2.7504789 |
47 | 0 | 57.057407 | 0.42455547E-06 | 15.540314 | |
48 | 9 | -0.14490010E-14 | 0.30537737E-16 | -0.15613140E-09 | 0.37153042E-16 |
49 | 8 | 0.22775399E-07 | 0.10742354E-12 | 0.38719206E-03 | -0.25896410E-09 |
50 | 7 | -0.12521818E-01 | 0.55241817E-08 | -0.23489278E-01 | 0.14237764E-03 |
51 | 6 | 0.41296535 | 0.19175017E-05 | 0.47857136 | -0.48375248E-02 |
52 | 5 | -5.2648734 | 0.71459421E-04 | -4.4910111 | 0.64105260E-01 |
53 | 4 | 33.331527 | 0.58354868E-03 | 21.634754 | -0.42648676 |
54 | 3 | -111.92546 | 0.12698472E-02 | -56.008360 | 1.5252969 |
55 | 2 | 197.82418 | 0.71331385E-03 | 78.227414 | -2.9117223 |
56 | 1 | -171.42051 | 0.76052751E-04 | -55.357370 | 2.7500739 |
57 | 0 | 57.057407 | 0.43228786E-06 | 15.541820 | |
58 | 9 | -0.46044427E-14 | 0.27900089E-16 | -0.15673021E-09 | 0.84433218E-16 |
59 | 8 | 0.22857479E-07 | 0.10577188E-12 | 0.38804207E-03 | -0.25989740E-09 |
60 | 7 | -0.12547140E-01 | 0.54349272E-08 | -0.23525725E-01 | 0.14266556E-03 |
61 | 6 | 0.41365335 | 0.18858798E-05 | 0.47915629 | -0.48456347E-02 |
62 | 5 | -5.2715868 | 0.70260405E-04 | -4.4954992 | 0.64188504E-01 |
63 | 4 | 33.361217 | 0.57360532E-03 | 21.652286 | -0.42688098 |
64 | 3 | -111.98862 | 0.12479141E-02 | -56.043016 | 1.5262094 |
65 | 2 | 197.88677 | 0.70084509E-03 | 78.259217 | -2.9127162 |
66 | 1 | -171.44362 | 0.74708721E-04 | -55.366651 | 2.7504789 |
67 | 0 | 57.057407 | 0.42455547E-06 | 15.540314 | |
68 | 9 | -0.14490010E-14 | 0.30537737E-16 | -0.15613140E-09 | 0.37153042E-16 |
69 | 8 | 0.22775399E-07 | 0.10742354E-12 | 0.38719206E-03 | -0.25896410E-09 |
70 | 7 | -0.12521818E-01 | 0.55241817E-08 | -0.23489278E-01 | 0.14237764E-03 |
71 | 6 | 0.41296535 | 0.19175017E-05 | 0.47857136 | -0.48375248E-02 |
72 | 5 | -5.2648734 | 0.71459421E-04 | -4.4910111 | 0.64105260E-01 |
73 | 4 | 33.331527 | 0.58354868E-03 | 21.634754 | -0.42648676 |
74 | 3 | -111.92546 | 0.12698472E-02 | -56.008360 | 1.5252969 |
75 | 2 | 197.82418 | 0.71331385E-03 | 78.227414 | -2.9117223 |
76 | 1 | -171.42051 | 0.76052751E-04 | -55.357370 | 2.7500739 |
77 | 0 | 57.057407 | 0.43228786E-06 | 15.541820 | |
78 | 7 | -0.16359629E-14 | -0.14530353E-16 | -0.22331004E-13 | 0.54056000E-15 |
79 | 6 | 0.18262352E-10 | 0.22801053E-11 | 0.52333849E-09 | -0.18642118E-10 |
80 | 5 | -0.59540244E-07 | 0.11129510E-07 | -0.21928235E-05 | 0.17164558E-06 |
81 | 4 | 0.60861605E-04 | 0.41961443E-05 | 0.17683552E-02 | -0.28248824E-03 |
82 | 3 | -0.87523238E-02 | 0.14809838E-03 | -0.21562890 | 0.43346081E-01 |
83 | 2 | 0.12409989 | 0.64146884E-03 | 2.9009744 | -0.61915653 |
84 | 1 | -0.31397648 | 0.40472017E-03 | -7.1381115 | 1.5697592 |
85 | 0 | 0.19977219 | 0.56546383E-05 | 4.4522022 | |
86 | 7 | -0.22331004E-13 | -0.14530353E-16 | -0.16359629E-14 | 0.54056000E-15 |
87 | 6 | 0.52333849E-09 | 0.22801053E-11 | 0.18262352E-10 | -0.18642118E-10 |
88 | 5 | -0.21928235E-05 | 0.11129510E-07 | -0.59540244E-07 | 0.17164558E-06 |
89 | 4 | 0.17683552E-02 | 0.41961443E-05 | 0.60861605E-04 | -0.28248824E-03 |
90 | 3 | -0.21562890 | 0.14809838E-03 | -0.87523238E-02 | 0.43346081E-01 |
91 | 2 | 2.9009744 | 0.64146884E-03 | 0.12409989 | -0.61915653 |
92 | 1 | -7.1381115 | 0.40472017E-03 | -0.31397648 | 1.5697592 |
93 | 0 | 4.4522022 | 0.56546383E-05 | 0.19977219 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
103 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
104 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
105 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
106 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
107 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
108 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
109 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
110 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
111 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
112 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
113 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
114 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
115 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
116 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
117 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
118 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
119 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
120 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
121 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
122 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
123 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
124 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
125 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
126 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
127 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
128 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
129 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
130 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
131 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
132 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
133 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.296_SHGC_0.397 | 37 | 1 | VerySmooth | 1.681 | 1.681 | 1.000 | 0.398 | ||
2 | RESWINDOW_U_0.296_SHGC_0.397 | 38 | 1 | VerySmooth | 1.681 | 1.681 | 1.000 | 0.398 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 4.21643E-002 | 0.31125 | 0.49106 | 0.49106 | 0.43670 | 0.13422 | 0.17096 | 0.00000 | 0.84000 | 0.84000 | 0.10025 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 4.21643E-002 | 0.31125 | 0.49106 | 0.49106 | 0.43670 | 0.13422 | 0.17096 | 0.00000 | 0.84000 | 0.84000 | 0.10025 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1675 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.6548E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1914 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 0.1126 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1110 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.5145E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.5919E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.5255E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1907 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1153 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2188 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1339 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1228 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.6231E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 5.1557E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.0854E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.2217E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.4395E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.2534E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.8481E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.0919E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.2334E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.5200E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.6027E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.2217E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.4395E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.2534E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.8481E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.0919E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.2334E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.5200E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.6027E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 30066.79623 | 30066.79623 | 2.27970 | 2.27970 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1325.91101 | 1325.91101 | 5.93070E-002 | 0.85446 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 5498.63744 | 5498.63744 | 0.41697 | 0.41697 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 4021.52728 | 4021.52728 | 0.17986 | 0.17986 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2974.12226 | 2974.12226 | 0.22553 | 0.22553 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 29.85200 | 1.27254E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1325.13290 | 1325.13290 | 5.92697E-002 | 9.17347E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2370.73052 | 2370.73052 | 0.17974 | 0.17974 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 29.85200 | 1.27254E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 2496.14867 | 2496.14867 | 0.11165 | 0.11165 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1298.06229 | 1298.06229 | 9.84128E-002 | 9.84128E-002 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10000 | 1.27259E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1695.19407 | 1695.19407 | 7.58212E-002 | 7.58212E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44788.03576 | 44788.03576 | 3.39597 | 3.39597 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.10000 | 1.27259E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 3308.92430 | 3308.92430 | 0.14799 | 0.14799 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 22632.31670 | 22632.31670 | 1.71762 | 1.71762 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 10083.57939 | 10083.57939 | 0.45099 | 0.67639 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 66395.02017 | 66395.02017 | 5.03618 | 5.03618 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 23644.05924 | 23644.05924 | 1.05754 | 1.89399 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11452.77357 | 11452.77357 | 1.17017 | 1.17017 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.15733 | 1.27224E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 9095.19428 | 9095.19428 | 0.40916 | 0.40916 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10890.61042 | 10890.61042 | 1.11273 | 1.11273 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 9102.05136 | 9102.05136 | 0.40947 | 0.40947 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 70447.66845 | 70447.66845 | 7.19737 | 7.19737 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 51404.30925 | 51404.30925 | 2.31265 | 2.31265 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 52821.22889 | 52821.22889 | 5.39698 | 5.39698 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 51550.12675 | 51550.12675 | 2.31921 | 2.31921 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10365.28869 | 10365.28869 | 1.05906 | 1.05906 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27176E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 9109.87393 | 9109.87393 | 0.40982 | 0.40982 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9812.10518 | 9812.10518 | 1.00254 | 1.00254 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 23.63133 | 1.27146E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 9116.72960 | 9116.72960 | 0.41013 | 0.41013 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 17465.08561 | 17465.08561 | 1.32420 | 1.32420 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.10000 | 1.27259E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 13598.59741 | 13598.59741 | 0.60824 | 0.60824 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2984.00585 | 2984.00585 | 0.30489 | 0.30489 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.36400 | 1.27228E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2747.26698 | 2747.26698 | 0.12359 | 0.12359 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2825.24077 | 2825.24077 | 0.28866 | 0.28866 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2747.44370 | 2747.44370 | 0.12360 | 0.12360 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 14680.66731 | 14680.66731 | 1.50000 | 1.50000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 13126.77373 | 13126.77373 | 0.59054 | 0.59054 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28769.79378 | 28769.79378 | 2.18408 | 2.18408 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 8816.58979 | 8816.58979 | 0.39434 | 1.18780 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30218.19255 | 30218.19255 | 2.29400 | 2.29400 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 8987.51302 | 8987.51302 | 0.40199 | 1.18780 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30195.03447 | 30195.03447 | 2.29537 | 2.29537 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 25.03667 | 1.27170E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 4546.98539 | 4546.98539 | 0.20335 | 0.36735 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -32.70000 | 1.83376E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9585.90835 | 9585.90835 | 0.72680 | 0.72680 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.10000 | 1.27259E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 9190.49855 | 9190.49855 | 0.41107 | 0.41107 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 352218.77 | 22.05561 | 22.05561 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 446455.39 | 7.79415 | 7.79415 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 41147.75 | 17.66500 | 2.05125 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 117497.06 | 7.10817 | 2.05125 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.27970 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.66143 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28119 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.76023E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.83028E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28119 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7807.43536 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.83028E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 164.55535 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.41697 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12257 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28500 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11884 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33954 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.10838E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.31326E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17986 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4930.31801 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.31326E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 134.55297 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22553 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26242 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.61000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13757 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69979 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45187E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.76751E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13757 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2020.36805 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.76751E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 46.79652 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.17974 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.69632 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.79736E-003 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.47164E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.67720E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11165 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3060.20457 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.67720E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 83.51353 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.84128E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.73371 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.88000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.66032E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.19278E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.86588E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.66032E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2132.81028 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.86588E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 55.98337 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.39597 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.75108E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.39597E-002 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.17580E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.54866E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.14799 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4056.33645 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.54866E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 110.69787 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.71762 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.37863E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59100 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01511 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59100 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.54728E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.33096E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01511 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15213.64495 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.33096E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 353.62837 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.03618 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19794 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56400 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.84041 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56400 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.92487E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.32434E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.84041 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37999.25867 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.32434E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 866.95347 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.17017 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.17017 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.95687E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.64978E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70749 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64158E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.64978E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.17017 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9095.19428 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.95687E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 259.90949 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.11273 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.11273 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.96287E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.47691E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70748 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64831E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.47691E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.11273 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9102.05136 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.96287E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 260.10538 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.19737 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.19737 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.49707E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.19947E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70817 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56609E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.19947E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.19737 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 51404.30925 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.49707E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1468.95400 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.39698 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.39698 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.50983E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.77996E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70718 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.85520E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.77996E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.39698 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 51550.12675 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.50983E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1473.11998 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.05906 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.05906 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.96972E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.31686E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70746 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.65694E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.31686E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.05906 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9109.87393 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.96972E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 260.32887 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.00254 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.00254 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.97571E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.14737E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70744 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.66590E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.14737E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.00254 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9116.72960 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.97571E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 260.52472 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.32420 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.89632 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.53800 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71242 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.25072E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.50475E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71242 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17200.22391 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.50475E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 448.52360 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.30489 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.30489 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.40343E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.49475E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70750 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63582E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.49475E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.30489 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2747.26698 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.40343E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 78.50379 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.28866 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.28866 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.40358E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.00722E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70749 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64311E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.00722E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.28866 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2747.44370 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.40358E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 78.50884 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.50000 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.50000 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.14839E-004 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.73014E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70732 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68268E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.73014E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.50000 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 13126.77373 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14839E-004 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 375.09927 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.18408 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11571 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.81600 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78221 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81600 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.29268E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.55958E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78221 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17827.00004 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55958E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 391.66432 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.29400 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11017 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.77700 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78244 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77700 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.45839E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.57465E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78244 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17999.17235 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.57465E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 395.85900 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.29537 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.16826E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24000 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55089 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11097E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.41117E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55089 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7328.36161 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.41117E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 167.05270 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72680 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.43209 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25900 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18824 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.81770E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.85869E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41107 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11269.08472 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.85869E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 307.55254 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 13.14538 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 10.53168 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.17457 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 10.53168 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.05561 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.05561 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.47751 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.05561 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.05561 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 9.32920 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.57386 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90609 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.09852E-002 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 568294.77441 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.62532E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.05561 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 379009.20244 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.31574E-003 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5274.95827 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.05561 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.62532E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.92983E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.31574E-003 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 30.10000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.89838 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.27259E-002 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 69550.08568 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.98912E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 35250.35631 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.08385E-004 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 490.60592 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.98912E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.39397E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.08385E-004 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.42388E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 3918.27926 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 6.30853E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.75702 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 6.30853E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1881.04130 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 721103.54731 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 721103.55000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 6.30853E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.42388E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.90866 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.42388E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2712.75689 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.42388E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 847515.66996 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 848127.23000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 96.68650 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 7847.52 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4949.37 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2029.76 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 3072.03 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 2141.36 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 4072.01 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 15284.13 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 38178.32 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 9796.84 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 9804.23 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 55370.46 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 55527.51 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 9812.65 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 9820.03 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 17269.66 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2959.12 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2959.32 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 14139.09 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 17914.10 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 18087.02 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7362.92 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11312.62 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 217416.80 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 20221.20 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 19358.62 | 16336.83 | 3021.79 | 0.84 | 4466.08 | 45.30 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 18431.04 | 15542.32 | 2888.72 | 0.84 | 4240.77 | 43.01 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 117390.60 | 99931.01 | 17459.60 | 0.85 | 27890.71 | 282.88 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 92729.34 | 76501.47 | 16227.86 | 0.82 | 19913.02 | 201.97 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 17569.57 | 14801.62 | 2767.95 | 0.84 | 4028.92 | 40.86 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 16658.96 | 14020.53 | 2638.43 | 0.84 | 3806.89 | 38.61 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5038.55 | 4254.81 | 783.74 | 0.84 | 1165.08 | 11.82 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4776.84 | 4030.51 | 746.34 | 0.84 | 1101.36 | 11.17 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 25003.65 | 21004.22 | 3999.43 | 0.84 | 5683.23 | 57.64 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 603004.36 | 401178.33 | 201826.03 | 0.67 | 97070.83 | 984.55 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 60070.69 | 38934.02 | 21136.67 | 0.65 | 8372.83 | 84.92 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.270 | 0.259 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.270 | 0.259 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.270 | 0.259 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.270 | 0.259 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.780 | 0.698 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.780 | 0.698 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.780 | 0.698 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.780 | 0.698 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.296_SHGC_0.397 | N/A | 1.681 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.3765756061E-002 | 3.2006156989E-002 | Pass | Pass | 9.7223826213E-003 | 3.6790021764E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.6323653143E-002 | 8.0276059749E-002 | Pass | Pass | 0.1423613633 | 0.7622704300 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.8411104648E-004 | 6.3386116197E-004 | Pass | Pass | 5.0597102354E-002 | 8.6240567662E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.5115177750E-003 | 6.0050860552E-003 | Pass | Pass | 1.6022086143E-002 | 3.9576167105E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.1755933997E-002 | 2.1151862395E-002 | Pass | Pass | 1.0617002170E-002 | 2.2709481687E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.4952598684E-004 | 4.0057568719E-004 | Pass | Pass | 2.3040945314E-002 | 6.6380722177E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.8868551536E-002 | 6.8571897708E-002 | Pass | Pass | 6.4359085732E-002 | 0.1677967358 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.6228293478E-002 | 3.1023710364E-002 | Pass | Pass | 2.9457344074E-002 | 5.8369293712E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.9105653176E-002 | 0.3296283249 | Pass | Pass | 0.1111449061 | 0.3716894777 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2703937635E-002 | 0.3299756925 | Pass | Pass | 6.4206259574E-002 | 0.2096013805 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.4328936975E-002 | 6.6842801794E-002 | Pass | Pass | 3.0814483238E-002 | 0.1020508398 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.9903380666E-002 | 0.1994286001 | Pass | Pass | 8.6031743990E-002 | 0.4022362310 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2647932358E-002 | 0.3227499080 | Pass | Pass | 7.6933974081E-002 | 0.2014759506 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.4221753282E-002 | 0.3206874611 | Pass | Pass | 7.0814692378E-002 | 0.2537389476 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.9707830142E-004 | 2.9374638923E-003 | Pass | Pass | 6.8594240031E-002 | 0.1272550123 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2667624006E-002 | 0.3445996908 | Pass | Pass | 9.6985436530E-002 | 0.3052032073 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.3870963368E-002 | 0.3248562609 | Pass | Pass | 5.2028116138E-002 | 0.1724991487 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.1259726495E-002 | 0.2909261637 | Pass | Pass | 0.1885238756 | 0.4846461452 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.5916219864E-002 | 6.6735238441E-002 | Pass | Pass | 1.9656948810E-002 | 5.9912419209E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.1019672042E-002 | 7.1236711413E-002 | Pass | Pass | 1.8201874500E-002 | 5.1040804674E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.1884933375E-002 | 9.4010639799E-002 | Pass | Pass | 2.5292201138E-002 | 5.3248289174E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.0719045881E-003 | 1.3335705598E-002 | Pass | Pass | 2.8798902482E-002 | 3.9579166361E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3820.41 | 206.75 | 2543.66 | 7311.23 | 3156.84 | 17038.89 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.261 | 0.270 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.261 | 0.270 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.261 | 0.270 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.261 | 0.270 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.296_SHGC_0.397 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 1.681 | 0.398 | 0.438 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.296_SHGC_0.397 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 1.681 | 0.398 | 0.438 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.296_SHGC_0.397 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 1.681 | 0.398 | 0.438 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.296_SHGC_0.397 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.681 | 0.398 | 0.438 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.296_SHGC_0.397 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.681 | 0.398 | 0.438 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.296_SHGC_0.397 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.681 | 0.398 | 0.438 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.296_SHGC_0.397 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.681 | 0.398 | 0.438 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.296_SHGC_0.397 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 1.681 | 0.398 | 0.438 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.296_SHGC_0.397 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 1.681 | 0.398 | 0.438 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.296_SHGC_0.397 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.681 | 0.398 | 0.438 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.296_SHGC_0.397 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.681 | 0.398 | 0.438 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.296_SHGC_0.397 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.681 | 0.398 | 0.438 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.296_SHGC_0.397 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.681 | 0.398 | 0.438 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.296_SHGC_0.397 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.681 | 0.398 | 0.438 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.296_SHGC_0.397 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 1.681 | 0.398 | 0.438 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.296_SHGC_0.397 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 1.681 | 0.398 | 0.438 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.296_SHGC_0.397 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.681 | 0.398 | 0.438 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.296_SHGC_0.397 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.681 | 0.398 | 0.438 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.296_SHGC_0.397 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.681 | 0.398 | 0.438 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.296_SHGC_0.397 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.681 | 0.398 | 0.438 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.296_SHGC_0.397 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.681 | 0.398 | 0.438 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.296_SHGC_0.397 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 1.681 | 0.398 | 0.438 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.296_SHGC_0.397 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.681 | 0.398 | 0.438 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.296_SHGC_0.397 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.681 | 0.398 | 0.438 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.296_SHGC_0.397 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.681 | 0.398 | 0.438 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.296_SHGC_0.397 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.681 | 0.398 | 0.438 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.296_SHGC_0.397 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.681 | 0.398 | 0.438 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.296_SHGC_0.397 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 1.681 | 0.398 | 0.438 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.296_SHGC_0.397 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 1.681 | 0.398 | 0.438 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.296_SHGC_0.397 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.681 | 0.398 | 0.438 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 1.681 | 0.398 | 0.438 | |||||||||||||||||
North Total or Average | 432.95 | 1.681 | 0.398 | 0.438 | |||||||||||||||||
Non-North Total or Average | 780.84 | 1.681 | 0.398 | 0.438 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.7179 | 1978.83 | 13293.58 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 122.93 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 9.6995 | 67.07 | 650.56 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.26 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 9.6995 | 77.67 | 753.35 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.25 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 4.2862 | 94.76 | 406.16 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 2.31 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.7049 | 78.04 | 445.21 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 9.2569 | 188.86 | 1748.29 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 38.57 | 0.0000 | Y | 12.66 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.0417 | 1308.19 | 11828.20 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.40 | 0.0000 | Y | 91.93 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.78 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.79 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4132 | 1557.62 | 6874.08 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 56.74 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 6.96 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.62 | 0.0000 | Y | 28.02 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.62 | 0.0000 | Y | 28.02 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7327 | 103.30 | 1212.04 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4132 | 412.12 | 1818.79 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 15.01 |
Interior Lighting Total | 5.8577 | 11345.29 | 66457.67 | 364.89 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.52 | 83.52 | 193.43 | |
Exterior Lighting Total | 12338.45 | 193.43 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 721103.55 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 848127.23 | 2.96 | 848276.31 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12761.77 | 19358.62 | 16336.83 | 3021.79 | 0.84 | - | 4466.08 | 45.30 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12157.31 | 18431.04 | 15542.32 | 2888.72 | 0.84 | - | 4240.77 | 43.01 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 76906.37 | 117390.60 | 99931.01 | 17459.60 | 0.85 | - | 27890.71 | 282.88 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 62237.82 | 92729.34 | 76501.47 | 16227.86 | 0.82 | - | 19913.02 | 201.97 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11597.68 | 17569.57 | 14801.62 | 2767.95 | 0.84 | - | 4028.92 | 40.86 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11005.06 | 16658.96 | 14020.53 | 2638.43 | 0.84 | - | 3806.89 | 38.61 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3319.92 | 5038.55 | 4254.81 | 783.74 | 0.84 | - | 1165.08 | 11.82 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3149.45 | 4776.84 | 4030.51 | 746.34 | 0.84 | - | 1101.36 | 11.17 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 16539.34 | 25003.65 | 21004.22 | 3999.43 | 0.84 | - | 5683.23 | 57.64 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 568294.77 | 603004.36 | 401178.33 | 201826.03 | 0.67 | - | 97070.83 | 984.55 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 69550.09 | 60070.69 | 38934.02 | 21136.67 | 0.65 | - | 8372.83 | 84.92 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 7807.44 | 7847.52 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4930.32 | 4949.37 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2020.37 | 2029.76 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3060.20 | 3072.03 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2132.81 | 2141.36 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4056.34 | 4072.01 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15213.64 | 15284.13 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 37999.26 | 38178.32 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9095.19 | 9796.84 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9102.05 | 9804.23 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 51404.31 | 55370.46 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 51550.13 | 55527.51 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9109.87 | 9812.65 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9116.73 | 9820.03 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17200.22 | 17269.66 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2747.27 | 2959.12 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2747.44 | 2959.32 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 13126.77 | 14139.09 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 17827.00 | 17914.10 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 17999.17 | 18087.02 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7328.36 | 7362.92 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11269.08 | 11312.62 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 379009.20 | 217416.80 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 35250.36 | 20221.20 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.17 | 823.37 | 703.64 | 1.00 | 1.16 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.11 | 782.96 | 703.64 | 1.00 | 1.17 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.20 | 5064.33 | 703.64 | 1.00 | 0.95 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.40 | 3797.51 | 703.64 | 1.00 | 0.97 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.06 | 745.19 | 703.64 | 1.00 | 1.18 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.00 | 705.42 | 703.64 | 1.00 | 1.20 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.30 | 214.53 | 703.64 | 1.00 | 1.70 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.29 | 203.12 | 703.64 | 1.00 | 1.74 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.50 | 1055.45 | 703.64 | 1.00 | 1.11 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 22.06 | 49418.65 | 2240.64 | 1.00 | 1.11 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.024239 | 3918.28 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.006309 | 1881.04 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.024239 | 2712.76 | 111917.77 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 30066.80 | 30066.80 | 15.19 | 2.280 | 2.280 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.00 | 24.00 | 0.00930 | 24.81 | 0.01272 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 5498.64 | 5498.64 | 81.98 | 0.417 | 0.417 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00903 | 29.79 | 0.01273 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2974.12 | 2974.12 | 38.29 | 0.226 | 0.226 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00951 | 29.85 | 0.01273 | 0.092 | 0.00 |
MECH_FLR_1 | 2370.73 | 2370.73 | 14.43 | 0.180 | 0.180 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00893 | 29.85 | 0.01273 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1298.06 | 1298.06 | 13.70 | 0.098 | 0.098 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00904 | 30.10 | 0.01273 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44788.04 | 44788.04 | 573.92 | 3.396 | 3.396 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00856 | 30.10 | 0.01273 | 0.000 | 0.00 |
CAFE_FLR_1 | 22632.32 | 22632.32 | 119.84 | 1.718 | 1.718 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.00995 | 29.79 | 0.01273 | 0.676 | 0.00 |
LOBBY_FLR_1 | 66395.02 | 66395.02 | 50.75 | 5.036 | 5.036 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.00997 | 29.89 | 0.01273 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11452.77 | 11452.77 | 293.50 | 1.170 | 1.170 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00864 | 28.16 | 0.01272 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10890.61 | 10890.61 | 279.12 | 1.113 | 1.113 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00865 | 27.95 | 0.01272 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 70447.67 | 70447.67 | 2872.62 | 7.197 | 7.197 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00857 | 29.89 | 0.01273 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 52821.23 | 52821.23 | 2153.28 | 5.397 | 5.397 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 21.11 | 21.11 | 0.00886 | 24.81 | 0.01272 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10365.29 | 10365.29 | 265.63 | 1.059 | 1.059 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 21.11 | 21.11 | 0.00866 | 25.39 | 0.01272 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9812.11 | 9812.11 | 251.48 | 1.003 | 1.003 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 21.11 | 21.11 | 0.00867 | 23.63 | 0.01271 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 17465.09 | 17465.09 | 44.85 | 1.324 | 1.324 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00966 | 30.10 | 0.01273 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2984.01 | 2984.01 | 76.47 | 0.305 | 0.305 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00864 | 28.36 | 0.01272 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2825.24 | 2825.24 | 72.41 | 0.289 | 0.289 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00864 | 27.95 | 0.01272 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 14680.67 | 14680.67 | 598.46 | 1.500 | 1.500 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00868 | 29.89 | 0.01273 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28769.79 | 28769.79 | 86.75 | 2.184 | 2.184 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01048 | 30.10 | 0.01273 | 1.188 | 0.00 |
DINING_FLR_6 | 30218.19 | 30218.19 | 91.11 | 2.294 | 2.294 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01038 | 30.10 | 0.01273 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30195.03 | 30195.03 | 292.29 | 2.295 | 2.295 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 23.97 | 0.01004 | 25.04 | 0.01272 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9585.91 | 9585.91 | 23.26 | 0.727 | 0.727 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00908 | 30.10 | 0.01273 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1325.91 | 1325.91 | 0.67 | 0.059 | 0.854 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00792 | -32.70 | 0.00018 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4021.53 | 4021.53 | 59.96 | 0.180 | 0.180 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00751 | -32.70 | 0.00018 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1325.13 | 1325.13 | 17.06 | 0.059 | 0.092 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00744 | -32.70 | 0.00018 | 0.092 | 0.00 |
MECH_FLR_1 | 2496.15 | 2496.15 | 15.20 | 0.112 | 0.112 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00730 | -32.70 | 0.00018 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1695.19 | 1695.19 | 17.89 | 0.076 | 0.076 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00740 | -32.70 | 0.00018 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 3308.92 | 3308.92 | 42.40 | 0.148 | 0.148 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00729 | -32.70 | 0.00018 | 0.000 | 0.00 |
CAFE_FLR_1 | 10083.58 | 10083.58 | 53.39 | 0.451 | 0.676 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00757 | -32.70 | 0.00018 | 0.676 | 0.00 |
LOBBY_FLR_1 | 23644.06 | 23644.06 | 18.07 | 1.058 | 1.894 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00748 | -32.70 | 0.00018 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9095.19 | 9095.19 | 233.08 | 0.409 | 0.409 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00750 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9102.05 | 9102.05 | 233.28 | 0.409 | 0.409 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00750 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 51404.31 | 51404.31 | 2096.10 | 2.313 | 2.313 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00753 | -32.70 | 0.00018 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 51550.13 | 51550.13 | 2101.47 | 2.319 | 2.319 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00753 | -32.70 | 0.00018 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9109.87 | 9109.87 | 233.45 | 0.410 | 0.410 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00750 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9116.73 | 9116.73 | 233.66 | 0.410 | 0.410 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00750 | -32.70 | 0.00018 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 13598.60 | 13598.60 | 34.92 | 0.608 | 0.608 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00759 | -32.70 | 0.00018 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2747.27 | 2747.27 | 70.40 | 0.124 | 0.124 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00758 | -32.70 | 0.00018 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2747.44 | 2747.44 | 70.42 | 0.124 | 0.124 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00758 | -32.70 | 0.00018 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13126.77 | 13126.77 | 535.12 | 0.591 | 0.591 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00760 | -32.70 | 0.00018 | 0.099 | 0.00 |
BANQUET_FLR_6 | 8816.59 | 8816.59 | 26.58 | 0.394 | 1.188 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00768 | -32.70 | 0.00018 | 1.188 | 0.00 |
DINING_FLR_6 | 8987.51 | 8987.51 | 27.10 | 0.402 | 1.188 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00768 | -32.70 | 0.00018 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 4546.99 | 4546.99 | 44.02 | 0.203 | 0.367 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00723 | -32.70 | 0.00018 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9190.50 | 9190.50 | 22.30 | 0.411 | 0.411 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00773 | -32.70 | 0.00018 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 22.06 | 22.06 | 7.79 | 7.79 | 22.0556 | 10.5317 | 22.0556 | 0.4775 | 0.3000 |
FLR_3_DOAS | 17.66 | 2.05 | 7.11 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 7807.435 | 7807.435 | 1.281193 | 0.00006830 | 164.555 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7807.44 | 7807.44 | 1.281193 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00792442 | 49.0972 | 1325.91 | 0.00 | 7851.15 | 7851.15 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4930.318 | 4930.318 | 0.179860 | 0.00004313 | 134.553 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4930.32 | 4930.32 | 0.179860 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00751312 | 46.5852 | 4021.53 | 0.00 | 4954.77 | 4954.77 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 2020.368 | 2020.368 | 0.137574 | 0.00001768 | 46.797 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2020.37 | 2020.37 | 0.137574 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00743570 | 46.1073 | 1325.13 | 0.00 | 2031.18 | 2031.18 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 3060.205 | 3060.205 | 0.111645 | 0.00002677 | 83.514 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3060.20 | 3060.20 | 0.111645 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00730478 | 45.3052 | 2496.15 | 0.00 | 3075.38 | 3075.38 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 2132.810 | 2132.810 | 0.086603 | 0.00001866 | 55.983 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2132.81 | 2132.81 | 0.086603 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00740137 | 45.8972 | 1695.19 | 0.00 | 2143.51 | 2143.51 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 4056.336 | 4056.336 | 0.147988 | 0.00003549 | 110.698 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4056.34 | 4056.34 | 0.147988 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00728575 | 45.1922 | 3308.92 | 0.00 | 4076.45 | 4076.45 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 15213.645 | 15213.645 | 1.015112 | 0.00013310 | 353.628 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 15213.64 | 15213.64 | 1.015112 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00756758 | 46.9178 | 10083.58 | 0.00 | 15294.97 | 15294.97 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 37999.259 | 37999.259 | 2.840408 | 0.00033243 | 866.953 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 37999.26 | 37999.26 | 2.840408 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00747939 | 46.3751 | 23644.06 | 0.00 | 38203.63 | 38203.63 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12761.769 | -999.000 | 1.170169 | 0.00036498 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 12761.77 | 12356.63 | 1.170169 | 21.71 | 15.26 | 0.00864158 | 12.80 | 11.72 | 0.00850000 | 28.16 | 0.01272245 | 20.56 | 0.0000 | 21.11 | 0.00864158 | 53.1187 | 11452.77 | 0.00 | 13314.57 | 13314.57 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 9095.194 | 9095.194 | 0.409161 | 0.00007957 | 259.909 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9095.19 | 9095.19 | 0.409161 | 21.11 | 14.03 | 0.00750371 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00750371 | 46.2122 | 9095.19 | 0.00 | 9804.56 | 9804.56 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12157.313 | -999.000 | 1.112733 | 0.00034769 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 12157.31 | 11753.62 | 1.112733 | 21.71 | 15.27 | 0.00864831 | 12.80 | 11.72 | 0.00850000 | 27.95 | 0.01272209 | 20.50 | 0.0000 | 21.11 | 0.00864831 | 53.1596 | 10890.61 | 0.00 | 12683.27 | 12683.27 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 9102.051 | 9102.051 | 0.409469 | 0.00007963 | 260.105 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9102.05 | 9102.05 | 0.409469 | 21.11 | 14.03 | 0.00750410 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00750410 | 46.2146 | 9102.05 | 0.00 | 9811.96 | 9811.96 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 76906.374 | -999.000 | 7.197366 | 0.00219947 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 76906.37 | 75747.05 | 7.197366 | 21.71 | 15.20 | 0.00856609 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01272550 | 21.07 | 0.0000 | 21.11 | 0.00856609 | 52.6591 | 70447.67 | 0.00 | 80264.51 | 80264.51 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 51404.309 | 51404.309 | 2.312649 | 0.00044971 | 1468.954 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 51404.31 | 51404.31 | 2.312649 | 21.11 | 14.05 | 0.00753269 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00753269 | 46.3850 | 51404.31 | 0.00 | 55414.66 | 55414.66 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 62237.823 | -999.000 | 5.396982 | 0.00177996 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | unknown | 7/21 19:20:00 | 62237.82 | 57507.29 | 5.396982 | 21.71 | 15.45 | 0.00885520 | 12.80 | 11.72 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | 0.0000 | 21.11 | 0.00885520 | 54.4136 | 52821.23 | 0.00 | 64859.57 | 61565.98 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 51550.127 | 51550.127 | 2.319209 | 0.00045098 | 1473.120 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 51550.13 | 51550.13 | 2.319209 | 21.11 | 14.05 | 0.00753381 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00753381 | 46.3919 | 51550.13 | 0.00 | 55571.86 | 55571.86 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11597.678 | -999.000 | 1.059059 | 0.00033169 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | 7/21 10:00:00 | 11597.68 | 11190.95 | 1.059059 | 21.71 | 15.28 | 0.00865694 | 12.80 | 11.72 | 0.00850000 | 25.39 | 0.01271761 | 19.73 | 0.0000 | 21.11 | 0.00865694 | 53.2119 | 10365.29 | 0.00 | 12098.62 | 12098.62 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9109.874 | 9109.874 | 0.409821 | 0.00007970 | 260.329 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9109.87 | 9109.87 | 0.409821 | 21.11 | 14.03 | 0.00750446 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00750446 | 46.2168 | 9109.87 | 0.00 | 9820.39 | 9820.39 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 11005.056 | -999.000 | 1.002540 | 0.00031474 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | 7/21 09:10:00 | 11005.06 | 10597.89 | 1.002540 | 21.71 | 15.28 | 0.00866590 | 12.80 | 11.72 | 0.00850000 | 23.63 | 0.01271456 | 19.19 | 0.0000 | 21.11 | 0.00866590 | 53.2663 | 9812.11 | 0.00 | 11479.61 | 11479.61 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9116.730 | 9116.730 | 0.410129 | 0.00007976 | 260.525 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9116.73 | 9116.73 | 0.410129 | 21.11 | 14.03 | 0.00750485 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00750485 | 46.2191 | 9116.73 | 0.00 | 9827.78 | 9827.78 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 17200.224 | 17200.224 | 0.712420 | 0.00015048 | 448.524 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 17200.22 | 17200.22 | 0.712420 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00759147 | 47.0603 | 13598.60 | 0.00 | 17286.68 | 17286.68 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3319.919 | -999.000 | 0.304886 | 0.00009495 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3319.92 | 3218.68 | 0.304886 | 21.71 | 15.26 | 0.00863582 | 12.80 | 11.72 | 0.00850000 | 28.36 | 0.01272282 | 20.62 | 0.0000 | 21.11 | 0.00863582 | 53.0838 | 2984.01 | 0.00 | 3463.88 | 3463.88 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2747.267 | 2747.267 | 0.123590 | 0.00002403 | 78.504 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2747.27 | 2747.27 | 0.123590 | 21.11 | 14.10 | 0.00758461 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00758461 | 46.7042 | 2747.27 | 0.00 | 2961.54 | 2961.54 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3149.450 | -999.000 | 0.288665 | 0.00009007 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3149.45 | 3048.42 | 0.288665 | 21.71 | 15.26 | 0.00864311 | 12.80 | 11.72 | 0.00850000 | 27.95 | 0.01272209 | 20.50 | 0.0000 | 21.11 | 0.00864311 | 53.1280 | 2825.24 | 0.00 | 3285.84 | 3285.84 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2747.444 | 2747.444 | 0.123598 | 0.00002404 | 78.509 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2747.44 | 2747.44 | 0.123598 | 21.11 | 14.10 | 0.00758466 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00758466 | 46.7046 | 2747.44 | 0.00 | 2961.73 | 2961.73 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 16539.344 | -999.000 | 1.499998 | 0.00047301 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 16539.34 | 15868.02 | 1.499998 | 21.71 | 15.30 | 0.00868268 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01272550 | 21.07 | 0.0000 | 21.11 | 0.00868268 | 53.3683 | 14680.67 | 0.00 | 17252.76 | 17252.76 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13126.774 | 13126.774 | 0.590543 | 0.00011484 | 375.099 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 13126.77 | 13126.77 | 0.590543 | 21.11 | 14.11 | 0.00759892 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00759892 | 46.7900 | 13126.77 | 0.00 | 14150.70 | 14150.70 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 17827.000 | 17827.000 | 1.782213 | 0.00015596 | 391.664 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 17827.00 | 17827.00 | 1.782213 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00767810 | 47.5921 | 8816.59 | 0.00 | 17924.28 | 17924.28 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 17999.172 | 17999.172 | 1.782440 | 0.00015746 | 395.859 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 17999.17 | 17999.17 | 1.782440 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00768397 | 47.6281 | 8987.51 | 0.00 | 18097.35 | 18097.35 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7328.362 | 7328.362 | 0.550888 | 0.00006411 | 167.053 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 7328.36 | 7328.36 | 0.550888 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00723357 | 44.8749 | 4546.99 | 0.00 | 7367.79 | 7367.79 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 11269.085 | 11269.085 | 0.411072 | 0.00009859 | 307.553 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11269.08 | 11269.08 | 0.411072 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00772764 | 47.8946 | 9190.50 | 0.00 | 11324.97 | 11324.97 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 568294.774 | -999.000 | 22.055610 | 0.01625316 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 568294.77 | 406615.90 | 22.055610 | 26.57 | 18.81 | 0.01098525 | 10.91 | 10.91 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 42.2985 | 23.99 | 0.00970254 | 49.9790 | 290661.84 | 0.00 | 584307.32 | 403627.38 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 379009.202 | 379009.202 | 6.616683 | 0.00331574 | 5274.958 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 379009.20 | 379009.20 | 6.616683 | -32.70 | -32.70 | 0.00018338 | 16.70 | 12.79 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 140.9951 | 21.00 | 0.00755900 | 46.8626 | 92088.28 | 0.00 | 262581.98 | 262581.98 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 69550.086 | -999.000 | 2.051317 | 0.00198912 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 69550.09 | 44784.57 | 2.051317 | 30.10 | 21.13 | 0.01272586 | 11.90 | 11.35 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 99.9965 | 21.11 | 0.00869255 | 53.4267 | 172896.24 | 0.00 | 71135.90 | 45208.06 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 35250.356 | 35250.356 | 0.615395 | 0.00030839 | 490.606 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 35250.36 | 35250.36 | 0.615395 | -32.70 | -32.70 | 0.00018338 | 16.70 | 12.79 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 333.3216 | 21.11 | 0.00753372 | 46.3914 | 157999.77 | 0.00 | 24421.86 | 24421.86 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 7807.435 | 7807.435 | 1.281193 | 0.00006830 | 164.555 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 1.0613 | 1.082707 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7807.44 | 7807.44 | 1.0000 | 1.47839999 | 1.281193 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.06829588 | 60.00 | 32.22 | 27.78 | 0.000 | 7807.44 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00792442 | 21.00 | 0.00792442 | 49.0972 | 1325.91 | 0.00 | 7851.15 | 7851.15 | 1.47839999 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.81 | 15.15 | 0.00800000 | 42245.3 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4930.318 | 4930.318 | 0.179860 | 0.00004313 | 134.553 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 0.6702 | 0.683718 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 4930.32 | 4930.32 | 1.0000 | 0.20754523 | 0.179860 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.04312817 | 60.00 | 32.22 | 27.78 | 0.000 | 4930.32 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00751312 | 21.00 | 0.00751312 | 46.5852 | 4021.53 | 0.00 | 4954.77 | 4954.77 | 0.20754523 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60807.9 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2020.368 | 2020.368 | 0.137574 | 0.00001768 | 46.797 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 0.2746 | 0.280177 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2020.37 | 2020.37 | 1.0000 | 0.15874956 | 0.137574 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.01767326 | 60.00 | 32.22 | 27.78 | 0.000 | 2020.37 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00743570 | 21.00 | 0.00743570 | 46.1073 | 1325.13 | 0.00 | 2031.18 | 2031.18 | 0.15874956 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.15 | 17.75 | 0.00800000 | 49729.6 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3060.205 | 3060.205 | 0.111645 | 0.00002677 | 83.514 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 0.4160 | 0.424378 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3060.20 | 3060.20 | 1.0000 | 0.12883052 | 0.111645 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02676927 | 60.00 | 32.22 | 27.78 | 0.000 | 3060.20 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00730478 | 21.00 | 0.00730478 | 45.3052 | 2496.15 | 0.00 | 3075.38 | 3075.38 | 0.12883052 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60806.3 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2132.810 | 2132.810 | 0.086603 | 0.00001866 | 55.983 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 0.2899 | 0.295770 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2132.81 | 2132.81 | 1.0000 | 0.09993362 | 0.086603 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.01865685 | 60.00 | 32.22 | 27.78 | 0.000 | 2132.81 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00740137 | 21.00 | 0.00740137 | 45.8972 | 1695.19 | 0.00 | 2143.51 | 2143.51 | 0.09993362 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 37.63 | 20.47 | 0.00800000 | 58384.0 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4056.336 | 4056.336 | 0.147988 | 0.00003549 | 110.698 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 0.5514 | 0.562518 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 4056.34 | 4056.34 | 1.0000 | 0.17076742 | 0.147988 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.03548298 | 60.00 | 32.22 | 27.78 | 0.000 | 4056.34 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00728575 | 21.00 | 0.00728575 | 45.1922 | 3308.92 | 0.00 | 4076.45 | 4076.45 | 0.17076742 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60806.1 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15213.645 | 15213.645 | 1.015112 | 0.00013310 | 353.628 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 2.0682 | 2.109773 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 15213.64 | 15213.64 | 1.0000 | 1.17136253 | 1.015112 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.13308203 | 60.00 | 32.22 | 27.78 | 0.000 | 15213.64 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00756758 | 21.00 | 0.00756758 | 46.9178 | 10083.58 | 0.00 | 15294.97 | 15294.97 | 1.17136253 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.41 | 17.84 | 0.00800000 | 49992.1 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37999.259 | 37999.259 | 2.840408 | 0.00033243 | 866.953 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 5.1656 | 5.269598 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 37999.26 | 37999.26 | 1.0000 | 3.27761699 | 2.840408 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.33240018 | 60.00 | 32.22 | 27.78 | 0.000 | 37999.26 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00747939 | 21.00 | 0.00747939 | 46.3751 | 23644.06 | 0.00 | 38203.63 | 38203.63 | 3.27761699 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.03 | 17.37 | 0.00800000 | 48590.6 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12761.769 | -999.000 | 1.170169 | 0.00036498 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9043 | 1004.8586 | 1.1539 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.170169 | 1.35028756 | 4197.9300 | 999.8980 | 24.23636826 | 15.03 | 6.70 | 8.33 | 847515.67 | 1.5058 | 1.505757 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 12761.77 | 12356.63 | 1.0000 | 1.35028756 | 1.170169 | 21.71 | 15.26 | 0.00864158 | 43773.3 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.36494092 | 6.70 | 15.03 | 8.33 | 0.000 | 12761.77 | 28.16 | 0.01272245 | 20.56 | 0.00000000 | 0.0000 | 21.11 | 0.00864158 | 21.11 | 0.00864158 | 53.1187 | 11452.77 | 0.00 | 13314.57 | 13314.57 | 1.35028756 | 21.71 | 15.69 | 0.00864158 | 43773.3 | 12.05 | 11.93 | 0.00864158 | 33912.8 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9095.194 | 9095.194 | 0.409161 | 0.00007957 | 259.909 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.170169 | 1.35028756 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 1.2364 | 1.261288 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9095.19 | 9095.19 | 1.0000 | 0.47214053 | 0.409161 | 21.11 | 14.03 | 0.00750371 | 40271.6 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.07956061 | 60.00 | 32.22 | 27.78 | 0.000 | 9095.19 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00750371 | 21.11 | 0.00750371 | 46.2122 | 9095.19 | 0.00 | 9804.56 | 9804.56 | 0.47214053 | 16.60 | 12.67 | 0.00750371 | 35678.2 | 36.98 | 19.90 | 0.00750371 | 56444.4 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12157.313 | -999.000 | 1.112733 | 0.00034769 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9168 | 1004.8586 | 1.1539 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.112733 | 1.28400998 | 4197.9300 | 999.8980 | 24.23636826 | 15.03 | 6.70 | 8.33 | 847515.67 | 1.4345 | 1.434438 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 12157.31 | 11753.62 | 1.0000 | 1.28400998 | 1.112733 | 21.71 | 15.27 | 0.00864831 | 43790.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.34765564 | 6.70 | 15.03 | 8.33 | 0.000 | 12157.31 | 27.95 | 0.01272209 | 20.50 | 0.00000000 | 0.0000 | 21.11 | 0.00864831 | 21.11 | 0.00864831 | 53.1596 | 10890.61 | 0.00 | 12683.27 | 12683.27 | 1.28400998 | 21.71 | 15.69 | 0.00864831 | 43790.4 | 12.03 | 11.93 | 0.00864831 | 33912.6 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9102.051 | 9102.051 | 0.409469 | 0.00007963 | 260.105 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.112733 | 1.28400998 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 1.2373 | 1.262239 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9102.05 | 9102.05 | 1.0000 | 0.47249649 | 0.409469 | 21.11 | 14.03 | 0.00750410 | 40272.6 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.07962059 | 60.00 | 32.22 | 27.78 | 0.000 | 9102.05 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00750410 | 21.11 | 0.00750410 | 46.2146 | 9102.05 | 0.00 | 9811.96 | 9811.96 | 0.47249649 | 16.60 | 12.67 | 0.00750410 | 35679.2 | 36.98 | 19.90 | 0.00750410 | 56445.4 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 76906.374 | -999.000 | 7.197366 | 0.00219947 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7639 | 1004.8586 | 1.1539 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.197366 | 8.30521995 | 4197.9300 | 999.8980 | 24.23636826 | 15.03 | 6.70 | 8.33 | 847515.67 | 9.0743 | 9.074161 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 76906.37 | 75747.05 | 1.0000 | 8.30521995 | 7.197366 | 21.71 | 15.20 | 0.00856609 | 43582.2 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 2.19924713 | 6.70 | 15.03 | 8.33 | 0.000 | 76906.37 | 29.89 | 0.01272550 | 21.07 | 0.00000000 | 0.0000 | 21.11 | 0.00856609 | 21.11 | 0.00856609 | 52.6591 | 70447.67 | 0.00 | 80264.51 | 80264.51 | 8.30521995 | 21.71 | 15.62 | 0.00856609 | 43582.2 | 12.24 | 11.93 | 0.00856609 | 33917.9 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 51404.309 | 51404.309 | 2.312649 | 0.00044971 | 1468.954 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.197366 | 8.30521995 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 6.9879 | 7.128561 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 51404.31 | 51404.31 | 1.0000 | 2.66862341 | 2.312649 | 21.11 | 14.05 | 0.00753269 | 40346.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.44966145 | 60.00 | 32.22 | 27.78 | 0.000 | 51404.31 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00753269 | 21.11 | 0.00753269 | 46.3850 | 51404.31 | 0.00 | 55414.66 | 55414.66 | 2.66862341 | 16.60 | 12.69 | 0.00753269 | 35751.6 | 36.98 | 19.92 | 0.00753269 | 56516.9 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 62237.823 | -999.000 | 5.396982 | 0.00177996 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3014 | 1004.8586 | 1.1539 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.396982 | 6.22771162 | 4197.9300 | 999.8980 | 24.23636826 | 15.03 | 6.70 | 8.33 | 847515.67 | 7.3436 | 7.343423 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | unknown | unknown | unknown | 7/21 19:20:00 | Sensible | 62237.82 | 57507.29 | 1.0000 | 6.22771162 | 5.396982 | 21.71 | 15.45 | 0.00885520 | 44315.9 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 1.77977904 | 6.70 | 15.03 | 8.33 | 0.000 | 62237.82 | 24.81 | 0.01271660 | 19.55 | 0.00000000 | 0.0000 | 21.11 | 0.00885520 | 21.11 | 0.00885520 | 54.4136 | 52821.23 | 0.00 | 64859.57 | 61565.98 | 6.22771162 | 21.71 | 15.88 | 0.00885520 | 44315.9 | 12.03 | 11.93 | 0.00864560 | 33901.2 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 51550.127 | 51550.127 | 2.319209 | 0.00045098 | 1473.120 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.396982 | 6.22771162 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 7.0077 | 7.148783 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 51550.13 | 51550.13 | 1.0000 | 2.67619346 | 2.319209 | 21.11 | 14.05 | 0.00753381 | 40349.3 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.45093699 | 60.00 | 32.22 | 27.78 | 0.000 | 51550.13 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00753381 | 21.11 | 0.00753381 | 46.3919 | 51550.13 | 0.00 | 55571.86 | 55571.86 | 2.67619346 | 16.60 | 12.70 | 0.00753381 | 35754.4 | 36.98 | 19.92 | 0.00753381 | 56519.7 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11597.678 | -999.000 | 1.059059 | 0.00033169 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9328 | 1004.8586 | 1.1539 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.059059 | 1.22207505 | 4197.9300 | 999.8980 | 24.23636826 | 15.03 | 6.70 | 8.33 | 847515.67 | 1.3684 | 1.368407 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | unknown | unknown | 7/21 10:00:00 | Sensible | 11597.68 | 11190.95 | 1.0000 | 1.22207505 | 1.059059 | 21.71 | 15.28 | 0.00865694 | 43812.3 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.33165209 | 6.70 | 15.03 | 8.33 | 0.000 | 11597.68 | 25.39 | 0.01271761 | 19.73 | 0.00000000 | 0.0000 | 21.11 | 0.00865694 | 21.11 | 0.00865694 | 53.2119 | 10365.29 | 0.00 | 12098.62 | 12098.62 | 1.22207505 | 21.71 | 15.70 | 0.00865694 | 43812.3 | 12.01 | 11.93 | 0.00865694 | 33912.3 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9109.874 | 9109.874 | 0.409821 | 0.00007970 | 260.329 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.059059 | 1.22207505 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 1.2384 | 1.263324 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9109.87 | 9109.87 | 1.0000 | 0.47290257 | 0.409821 | 21.11 | 14.03 | 0.00750446 | 40273.5 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.07968902 | 60.00 | 32.22 | 27.78 | 0.000 | 9109.87 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00750446 | 21.11 | 0.00750446 | 46.2168 | 9109.87 | 0.00 | 9820.39 | 9820.39 | 0.47290257 | 16.60 | 12.67 | 0.00750446 | 35680.1 | 36.98 | 19.90 | 0.00750446 | 56446.3 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11005.056 | -999.000 | 1.002540 | 0.00031474 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9495 | 1004.8586 | 1.1539 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.002540 | 1.15685572 | 4197.9300 | 999.8980 | 24.23636826 | 15.03 | 6.70 | 8.33 | 847515.67 | 1.2985 | 1.298483 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | unknown | unknown | 7/21 09:10:00 | Sensible | 11005.06 | 10597.89 | 1.0000 | 1.15685572 | 1.002540 | 21.71 | 15.28 | 0.00866590 | 43835.1 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.31470523 | 6.70 | 15.03 | 8.33 | 0.000 | 11005.06 | 23.63 | 0.01271456 | 19.19 | 0.00000000 | 0.0000 | 21.11 | 0.00866590 | 21.11 | 0.00866590 | 53.2663 | 9812.11 | 0.00 | 11479.61 | 11479.61 | 1.15685572 | 21.71 | 15.71 | 0.00866590 | 43835.1 | 11.99 | 11.93 | 0.00866590 | 33912.0 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9116.730 | 9116.730 | 0.410129 | 0.00007976 | 260.525 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.002540 | 1.15685572 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 1.2393 | 1.264275 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9116.73 | 9116.73 | 1.0000 | 0.47325846 | 0.410129 | 21.11 | 14.03 | 0.00750485 | 40274.5 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.07974899 | 60.00 | 32.22 | 27.78 | 0.000 | 9116.73 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00750485 | 21.11 | 0.00750485 | 46.2191 | 9116.73 | 0.00 | 9827.78 | 9827.78 | 0.47325846 | 16.60 | 12.67 | 0.00750485 | 35681.1 | 36.98 | 19.90 | 0.00750485 | 56447.3 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17200.224 | 17200.224 | 0.712420 | 0.00015048 | 448.524 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 2.3382 | 2.385264 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 17200.22 | 17200.22 | 1.0000 | 0.82207969 | 0.712420 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.15045971 | 60.00 | 32.22 | 27.78 | 0.000 | 17200.22 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00759147 | 21.00 | 0.00759147 | 47.0603 | 13598.60 | 0.00 | 17286.68 | 17286.68 | 0.82207969 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 37.22 | 20.35 | 0.00800000 | 57962.7 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3319.919 | -999.000 | 0.304886 | 0.00009495 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8936 | 1004.8586 | 1.1539 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.304886 | 0.35181560 | 4197.9300 | 999.8980 | 24.23636826 | 15.03 | 6.70 | 8.33 | 847515.67 | 0.3917 | 0.391716 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3319.92 | 3218.68 | 1.0000 | 0.35181560 | 0.304886 | 21.71 | 15.26 | 0.00863582 | 43758.7 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.09493780 | 6.70 | 15.03 | 8.33 | 0.000 | 3319.92 | 28.36 | 0.01272282 | 20.62 | 0.00000000 | 0.0000 | 21.11 | 0.00863582 | 21.11 | 0.00863582 | 53.0838 | 2984.01 | 0.00 | 3463.88 | 3463.88 | 0.35181560 | 21.71 | 15.68 | 0.00863582 | 43758.7 | 12.06 | 11.93 | 0.00863582 | 33913.0 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2747.267 | 2747.267 | 0.123590 | 0.00002403 | 78.504 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.304886 | 0.35181560 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 0.3735 | 0.380981 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2747.27 | 2747.27 | 1.0000 | 0.14261382 | 0.123590 | 21.11 | 14.10 | 0.00758461 | 40477.1 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02403184 | 60.00 | 32.22 | 27.78 | 0.000 | 2747.27 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00758461 | 21.11 | 0.00758461 | 46.7042 | 2747.27 | 0.00 | 2961.54 | 2961.54 | 0.14261382 | 16.60 | 12.75 | 0.00758461 | 35883.0 | 36.98 | 19.96 | 0.00758461 | 56649.2 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3149.450 | -999.000 | 0.288665 | 0.00009007 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9071 | 1004.8586 | 1.1539 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.288665 | 0.33309750 | 4197.9300 | 999.8980 | 24.23636826 | 15.03 | 6.70 | 8.33 | 847515.67 | 0.3716 | 0.371603 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 3149.45 | 3048.42 | 1.0000 | 0.33309750 | 0.288665 | 21.71 | 15.26 | 0.00864311 | 43777.2 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.09006299 | 6.70 | 15.03 | 8.33 | 0.000 | 3149.45 | 27.95 | 0.01272209 | 20.50 | 0.00000000 | 0.0000 | 21.11 | 0.00864311 | 21.11 | 0.00864311 | 53.1280 | 2825.24 | 0.00 | 3285.84 | 3285.84 | 0.33309750 | 21.71 | 15.69 | 0.00864311 | 43777.2 | 12.05 | 11.93 | 0.00864311 | 33912.7 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2747.444 | 2747.444 | 0.123598 | 0.00002404 | 78.509 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.288665 | 0.33309750 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 0.3735 | 0.381005 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2747.44 | 2747.44 | 1.0000 | 0.14262300 | 0.123598 | 21.11 | 14.10 | 0.00758466 | 40477.3 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02403338 | 60.00 | 32.22 | 27.78 | 0.000 | 2747.44 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00758466 | 21.11 | 0.00758466 | 46.7046 | 2747.44 | 0.00 | 2961.73 | 2961.73 | 0.14262300 | 16.60 | 12.75 | 0.00758466 | 35883.2 | 36.98 | 19.96 | 0.00758466 | 56649.3 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16539.344 | -999.000 | 1.499998 | 0.00047301 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9807 | 1004.8586 | 1.1539 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.499998 | 1.73088475 | 4197.9300 | 999.8980 | 24.23636826 | 15.03 | 6.70 | 8.33 | 847515.67 | 1.9515 | 1.951473 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 16539.34 | 15868.02 | 1.0000 | 1.73088475 | 1.499998 | 21.71 | 15.30 | 0.00868268 | 43877.6 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.47296607 | 6.70 | 15.03 | 8.33 | 0.000 | 16539.34 | 29.89 | 0.01272550 | 21.07 | 0.00000000 | 0.0000 | 21.11 | 0.00868268 | 21.11 | 0.00868268 | 53.3683 | 14680.67 | 0.00 | 17252.76 | 17252.76 | 1.73088475 | 21.71 | 15.72 | 0.00868268 | 43877.6 | 11.94 | 11.93 | 0.00868268 | 33910.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13126.774 | 13126.774 | 0.590543 | 0.00011484 | 375.099 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.499998 | 1.73088475 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 1.7845 | 1.820373 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 13126.77 | 13126.77 | 1.0000 | 0.68144216 | 0.590543 | 21.11 | 14.11 | 0.00759892 | 40513.9 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.11482703 | 60.00 | 32.22 | 27.78 | 0.000 | 13126.77 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00759892 | 21.11 | 0.00759892 | 46.7900 | 13126.77 | 0.00 | 14150.70 | 14150.70 | 0.68144216 | 16.60 | 12.76 | 0.00759892 | 35919.3 | 36.98 | 19.97 | 0.00759892 | 56685.1 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17827.000 | 17827.000 | 1.782213 | 0.00015596 | 391.664 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 2.4234 | 2.472183 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 17827.00 | 17827.00 | 1.0000 | 2.05653990 | 1.782213 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.15594246 | 60.00 | 32.22 | 27.78 | 0.000 | 17827.00 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00767810 | 21.00 | 0.00767810 | 47.5921 | 8816.59 | 0.00 | 17924.28 | 17924.28 | 2.05653990 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.15 | 16.37 | 0.00800000 | 45650.5 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17999.172 | 17999.172 | 1.782440 | 0.00015746 | 395.859 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 2.4468 | 2.496059 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 17999.17 | 17999.17 | 1.0000 | 2.05680206 | 1.782440 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.15744855 | 60.00 | 32.22 | 27.78 | 0.000 | 17999.17 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00768397 | 21.00 | 0.00768397 | 47.6281 | 8987.51 | 0.00 | 18097.35 | 18097.35 | 2.05680206 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.23 | 16.39 | 0.00800000 | 45733.5 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7328.362 | 7328.362 | 0.550888 | 0.00006411 | 167.053 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 0.9962 | 1.016270 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 7328.36 | 7328.36 | 1.0000 | 0.63568355 | 0.550888 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.06410516 | 60.00 | 32.22 | 27.78 | 0.000 | 7328.36 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.78 | 0.00723357 | 21.00 | 0.00723357 | 44.8749 | 4546.99 | 0.00 | 7367.79 | 7367.79 | 0.63568355 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.97 | 17.35 | 0.00800000 | 48525.1 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11269.085 | 11269.085 | 0.411072 | 0.00009859 | 307.553 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 1.5319 | 1.562755 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11269.08 | 11269.08 | 1.0000 | 0.47434590 | 0.411072 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.09857681 | 60.00 | 32.22 | 27.78 | 0.000 | 11269.08 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00772764 | 21.00 | 0.00772764 | 47.8946 | 9190.50 | 0.00 | 11324.97 | 11324.97 | 0.47434590 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60809.6 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 568294.774 | -999.000 | 22.055610 | 0.01625316 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.2610 | 1004.8586 | 1.1539 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.055610 | 25.45051659 | 4197.9300 | 999.8980 | 24.23636826 | 15.03 | 6.70 | 8.33 | 847515.67 | 67.0542 | 67.054191 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 568294.77 | 406615.90 | 1.0000 | 25.45051659 | 22.055610 | 26.57 | 18.81 | 0.01098525 | 54718.6 | 10.91 | 10.91 | 0.00850000 | 32389.2 | 16.25150062 | 6.70 | 15.03 | 8.33 | 49418.651 | 518876.12 | 30.10 | 0.01272586 | 21.13 | 9.32920000 | 42.2985 | 23.99 | 0.00970905 | 23.99 | 0.00970254 | 49.9790 | 290661.84 | 0.00 | 584307.32 | 403627.38 | 25.45051659 | 26.57 | 19.28 | 0.01098525 | 54718.6 | 11.11 | 11.05 | 0.00816985 | 31760.0 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 379009.202 | 379009.202 | 6.616683 | 0.00331574 | 5274.958 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.055610 | 25.45051659 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 51.5227 | 52.559609 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 379009.20 | 379009.20 | 1.0000 | 7.63515498 | 6.616683 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 3.31539960 | 60.00 | 32.22 | 27.78 | 0.000 | 379009.20 | -32.70 | 0.00018338 | -32.70 | 9.32920000 | 140.9951 | 20.98 | 0.00758966 | 21.00 | 0.00755900 | 46.8626 | 92088.28 | 0.00 | 262581.98 | 262581.98 | 7.63515498 | 2.80 | -4.17 | 0.00018338 | 3273.1 | 37.01 | 13.61 | 0.00018338 | 37664.3 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 69550.086 | -999.000 | 2.051317 | 0.00198912 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.4967 | 1004.8586 | 1.1539 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.36698273 | 4197.9300 | 999.8980 | 24.23636826 | 15.03 | 6.70 | 8.33 | 847515.67 | 8.2063 | 8.206348 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 69550.09 | 44784.57 | 1.0000 | 2.36706595 | 2.051317 | 30.10 | 21.13 | 0.01272586 | 62784.4 | 11.90 | 11.35 | 0.00850000 | 33402.0 | 1.98892074 | 6.70 | 15.03 | 8.33 | 2195.006 | 67355.08 | 30.10 | 0.01272586 | 21.13 | 2.05124512 | 99.9965 | 21.11 | 0.00869221 | 21.11 | 0.00869255 | 53.4267 | 172896.24 | 0.00 | 71135.90 | 45208.06 | 2.36706595 | 30.10 | 21.63 | 0.01272586 | 62784.4 | 11.53 | 11.45 | 0.00838330 | 32732.0 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 35250.356 | 35250.356 | 0.615395 | 0.00030839 | 490.606 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.36698273 | 4197.9300 | 999.8980 | 6.30788487 | 54.44 | 82.22 | 27.78 | 735616.04 | 4.7920 | 4.888390 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 35250.36 | 35250.36 | 1.0000 | 0.71011979 | 0.615395 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 0.30835404 | 60.00 | 32.22 | 27.78 | 0.000 | 35250.36 | -32.70 | 0.00018338 | -32.70 | 2.05124512 | 333.3216 | 21.11 | 0.00753382 | 21.11 | 0.00753372 | 46.3914 | 157999.77 | 0.00 | 24421.86 | 24421.86 | 0.71011979 | 2.80 | -4.17 | 0.00018338 | 3273.1 | 37.01 | 13.61 | 0.00018338 | 37664.3 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 22.06 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 334.67 | 7941.33 | 197.00 |
RETAIL_1_FLR_1 | 4363.17 | 6659.17 | 2897.33 |
RETAIL_2_FLR_1 | 1563.33 | 7978.33 | 1246.00 |
MECH_FLR_1 | 3196.33 | 6344.50 | 2137.83 |
STORAGE_FLR_1 | 2849.00 | 8760.00 | 2849.00 |
LAUNDRY_FLR_1 | 8660.83 | 3277.50 | 3277.50 |
CAFE_FLR_1 | 2439.17 | 7417.67 | 1660.17 |
LOBBY_FLR_1 | 1580.50 | 7422.67 | 995.17 |
ROOM_1_FLR_3 | 3763.17 | 8320.00 | 3671.00 |
ROOM_2_FLR_3 | 4581.17 | 8097.67 | 4272.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 3407.83 | 8704.83 | 3401.83 |
ROOM_5_FLR_3 | 3648.33 | 8244.83 | 3618.83 |
ROOM_6_FLR_3 | 4371.33 | 8034.83 | 4133.00 |
CORRIDOR_FLR_3 | 2506.17 | 8532.50 | 2478.00 |
ROOM_1_FLR_6 | 4223.50 | 8244.67 | 4071.33 |
ROOM_2_FLR_6 | 4989.83 | 8081.17 | 4652.67 |
ROOM_3_MULT9_FLR_6 | 3125.67 | 8226.00 | 3040.83 |
BANQUET_FLR_6 | 1832.83 | 7128.83 | 982.33 |
DINING_FLR_6 | 2145.00 | 6295.00 | 682.83 |
KITCHEN_FLR_6 | 8550.00 | 6015.17 | 5902.50 |
CORRIDOR_FLR_6 | 3908.17 | 6704.67 | 2678.17 |
Facility | 8760.00 | 8760.00 | 8014.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 105.67 | 0.00 | 105.67 | 0.00 |
RETAIL_2_FLR_1 | 25.00 | 0.00 | 25.00 | 0.00 |
MECH_FLR_1 | 44.17 | 0.00 | 44.17 | 0.00 |
STORAGE_FLR_1 | 198.17 | 0.00 | 198.17 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 37.17 | 0.00 | 37.17 | 0.00 |
LOBBY_FLR_1 | 9.00 | 0.00 | 9.00 | 0.00 |
ROOM_1_FLR_3 | 20.33 | 7.00 | 20.33 | 7.00 |
ROOM_2_FLR_3 | 63.50 | 7.50 | 63.50 | 7.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 245.50 | 21.33 | 245.50 | 21.33 |
ROOM_5_FLR_3 | 34.33 | 1.00 | 34.33 | 1.00 |
ROOM_6_FLR_3 | 80.17 | 16.33 | 80.17 | 16.33 |
CORRIDOR_FLR_3 | 11.17 | 0.00 | 11.17 | 0.00 |
ROOM_1_FLR_6 | 45.17 | 9.33 | 45.17 | 9.33 |
ROOM_2_FLR_6 | 115.00 | 13.83 | 115.00 | 13.83 |
ROOM_3_MULT9_FLR_6 | 5.33 | 2.67 | 5.33 | 2.67 |
BANQUET_FLR_6 | 24.33 | 0.00 | 24.33 | 0.00 |
DINING_FLR_6 | 11.83 | 0.00 | 11.83 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 81.17 | 0.00 | 81.17 | 0.00 |
Facility | 309.17 | 49.00 | 309.17 | 49.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.73 | 106.50 | 4826.41 | 0.706 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.346 | 0.142 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.181 | 0.047 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.108 | 0.053 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.606 | 0.053 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 15.100 | 0.153 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.48 | 142.30 | 748.35 | 3.587 | 0.112 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.84 | 422.44 | 5183.56 | 1.453 | 0.046 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.341 | 0.184 | 0.000 | 0.041 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.342 | 0.184 | 0.000 | 0.033 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.388 | 0.082 | 0.000 | 0.067 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.341 | 0.184 | 0.000 | 0.041 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.342 | 0.184 | 0.000 | 0.043 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.396 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.341 | 0.184 | 0.000 | 0.048 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.342 | 0.184 | 0.000 | 0.035 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.388 | 0.150 | 0.000 | 0.077 |
BANQUET_FLR_6 | 144.84 | 249.90 | 1010.89 | 4.668 | 0.053 | 0.000 | 0.000 |
DINING_FLR_6 | 144.84 | 249.90 | 1010.89 | 4.689 | 0.053 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 15.226 | 0.154 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 0.459 | 0.037 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.73 | 106.50 | 4826.41 | 0.518 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 0.929 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.926 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.006 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.450 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 2.606 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.48 | 142.30 | 748.35 | 2.752 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.84 | 422.44 | 5183.56 | 1.144 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.294 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.84 | 249.90 | 1010.89 | 3.629 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.84 | 249.90 | 1010.89 | 3.693 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 4.129 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 0.312 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.73 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.48 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.84 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.84 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.84 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.89 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.41 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 29326650.58 | 0.00 | 29326650.58 | 0.00 | 29326650.58 | 26946214.98 | 5599.04 | 220.70 | 2940.27 | 0.00 |
RETAIL_1_FLR_1 | 3082013.34 | 0.00 | 3082013.34 | 326761.06 | 3408774.40 | 2498216.28 | 5104.61 | 112.55 | 3542.84 | 0.00 |
RETAIL_2_FLR_1 | 3133629.78 | 0.00 | 3133629.78 | 126130.18 | 3259759.96 | 2892943.94 | 5776.04 | 201.23 | 2782.73 | 0.00 |
MECH_FLR_1 | 605184.42 | 0.00 | 605184.42 | 298096.82 | 903281.24 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1969890.78 | 0.00 | 1969890.78 | 171985.45 | 2141876.22 | 1821682.01 | 5782.58 | 200.45 | 2776.98 | 0.00 |
LAUNDRY_FLR_1 | 40034945.04 | 0.00 | 40034945.04 | 407035.98 | 40441981.03 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 23145361.67 | 0.00 | 23145361.67 | 722323.83 | 23867685.50 | 21330615.53 | 5751.79 | 204.31 | 2803.90 | 0.00 |
LOBBY_FLR_1 | 64825041.24 | 0.00 | 64825041.24 | 2063844.16 | 66888885.40 | 59728886.00 | 5767.88 | 202.48 | 2789.64 | 0.00 |
ROOM_1_FLR_3 | 1406076.84 | 41986.41 | 1448063.24 | 189663.05 | 1637726.29 | 1946875.62 | 2433.33 | 5845.83 | 480.83 | 0.00 |
ROOM_2_FLR_3 | 1405912.09 | 33546.09 | 1439458.19 | 189648.58 | 1629106.76 | 1946647.51 | 2433.33 | 5960.83 | 365.84 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 144.27 | 1100056.24 | 52918.12 | 1152974.36 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 367.17 |
ROOM_4_MULT19_FLR_3 | 19070354.14 | 43233.45 | 19113587.58 | 52932.59 | 19166520.17 | 26405105.73 | 2433.33 | 5858.41 | 468.25 | 0.00 |
ROOM_5_FLR_3 | 1406076.84 | 42077.70 | 1448154.53 | 189663.05 | 1637817.58 | 1946875.62 | 2433.33 | 5845.83 | 480.83 | 0.00 |
ROOM_6_FLR_3 | 1405912.09 | 43317.59 | 1449229.69 | 189648.58 | 1638878.26 | 1946647.51 | 2433.33 | 5849.00 | 477.66 | 0.00 |
CORRIDOR_FLR_3 | 16205535.18 | 0.00 | 16205535.18 | 229340.78 | 16434875.96 | 14972100.18 | 5773.18 | 199.89 | 2786.93 | 0.00 |
ROOM_1_FLR_6 | 351519.21 | 49367.83 | 400887.04 | 189704.08 | 590591.11 | 486718.90 | 2271.04 | 5846.36 | 642.60 | 0.00 |
ROOM_2_FLR_6 | 351478.02 | 35185.88 | 386663.91 | 189689.61 | 576353.51 | 486661.88 | 2317.17 | 5994.44 | 448.39 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2258331.41 | 49337.69 | 2307669.10 | 97059.25 | 2404728.35 | 3126920.42 | 2433.33 | 5845.36 | 481.31 | 0.00 |
BANQUET_FLR_6 | 40637919.85 | 0.00 | 40637919.85 | 463209.69 | 41101129.53 | 37458366.31 | 5769.58 | 200.57 | 2789.85 | 0.00 |
DINING_FLR_6 | 40777228.36 | 0.00 | 40777228.36 | 463209.69 | 41240438.05 | 37458366.31 | 5752.05 | 200.93 | 2807.02 | 0.00 |
KITCHEN_FLR_6 | 41018200.18 | 0.00 | 41018200.18 | 414680.06 | 41432880.24 | 11584760.86 | 8.62 | 103.83 | 8647.54 | 0.00 |
CORRIDOR_FLR_6 | 4965940.36 | 0.00 | 4965940.36 | 405865.71 | 5371806.06 | 3961413.96 | 5089.52 | 82.26 | 3588.22 | 0.00 |
Total Facility | 0.19E+10 | 4469011.00 | 0.19E+10 | 19112579.17 | 0.20E+10 | 0.43E+10 | 8760.00 | 6400.26 | 8760.00 | 367.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9299 | 0.0000 | 0.9299 | 0.0000 | 0.9299 | 0.8545 | 5599.04 | 220.70 | 2940.27 |
RETAIL_1_FLR_1 | 0.0977 | 0.0000 | 0.0977 | 0.0104 | 0.1081 | 0.0792 | 5104.61 | 112.55 | 3542.84 |
RETAIL_2_FLR_1 | 0.0994 | 0.0000 | 0.0994 | 0.0040 | 0.1034 | 0.0917 | 5776.04 | 201.23 | 2782.73 |
MECH_FLR_1 | 0.0192 | 0.0000 | 0.0192 | 0.0095 | 0.0286 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0625 | 0.0000 | 0.0625 | 0.0055 | 0.0679 | 0.0578 | 5782.58 | 200.45 | 2776.98 |
LAUNDRY_FLR_1 | 1.2695 | 0.0000 | 1.2695 | 0.0129 | 1.2824 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7339 | 0.0000 | 0.7339 | 0.0229 | 0.7568 | 0.6764 | 5751.79 | 204.31 | 2803.90 |
LOBBY_FLR_1 | 2.0556 | 0.0000 | 2.0556 | 0.0654 | 2.1210 | 1.8940 | 5767.88 | 202.48 | 2789.64 |
ROOM_1_FLR_3 | 0.0446 | 0.0013 | 0.0459 | 0.0060 | 0.0519 | 0.0617 | 2433.33 | 5845.83 | 480.83 |
ROOM_2_FLR_3 | 0.0446 | 0.0011 | 0.0456 | 0.0060 | 0.0517 | 0.0617 | 2433.33 | 5960.83 | 365.84 |
ROOM_4_MULT19_FLR_3 | 0.6047 | 0.0014 | 0.6061 | 0.0017 | 0.6078 | 0.8373 | 2433.33 | 5858.41 | 468.25 |
ROOM_5_FLR_3 | 0.0446 | 0.0013 | 0.0459 | 0.0060 | 0.0519 | 0.0617 | 2433.33 | 5845.83 | 480.83 |
ROOM_6_FLR_3 | 0.0446 | 0.0014 | 0.0460 | 0.0060 | 0.0520 | 0.0617 | 2433.33 | 5849.00 | 477.66 |
CORRIDOR_FLR_3 | 0.5139 | 0.0000 | 0.5139 | 0.0073 | 0.5211 | 0.4748 | 5773.18 | 199.89 | 2786.93 |
ROOM_1_FLR_6 | 0.0111 | 0.0016 | 0.0127 | 0.0060 | 0.0187 | 0.0154 | 2271.04 | 5846.36 | 642.60 |
ROOM_2_FLR_6 | 0.0111 | 0.0011 | 0.0123 | 0.0060 | 0.0183 | 0.0154 | 2317.17 | 5994.44 | 448.39 |
ROOM_3_MULT9_FLR_6 | 0.0716 | 0.0016 | 0.0732 | 0.0031 | 0.0763 | 0.0992 | 2433.33 | 5845.36 | 481.31 |
BANQUET_FLR_6 | 1.2886 | 0.0000 | 1.2886 | 0.0147 | 1.3033 | 1.1878 | 5769.58 | 200.57 | 2789.85 |
DINING_FLR_6 | 1.2930 | 0.0000 | 1.2930 | 0.0147 | 1.3077 | 1.1878 | 5752.05 | 200.93 | 2807.02 |
KITCHEN_FLR_6 | 1.3007 | 0.0000 | 1.3007 | 0.0131 | 1.3138 | 0.3674 | 8.62 | 103.83 | 8647.54 |
CORRIDOR_FLR_6 | 0.1575 | 0.0000 | 0.1575 | 0.0129 | 0.1703 | 0.1256 | 5089.52 | 82.26 | 3588.22 |
Total Facility | 58.7016 | 0.1414 | 58.8430 | 0.4785 | 59.3215 | 73.9670 | 8760.00 | 6400.26 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.41E+09 | 0.00 | 0.41E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 38289269.18 | 338196.92 | 38627466.10 | 64690340.46 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 13.0776 | 0.0000 | 13.0776 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.2141 | 0.0107 | 1.2249 | 2.0513 | 8760.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 23.08 | 4545.46 | 0.00 | 0.00 | 0.00 | 4191.46 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6691.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 12.3909 | 15.0242 | 0.0000 | 0.0000 | 0.0000 | 10.9735 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.5896 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1340 |
Defaulted Fields | 1181 |
Fields with Defaults | 4002 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4494.04 | 66678.99 | 13-MAY-05:00 | 375896.10 | 29-JUN-18:10 |
Electricity:Building | 2199.98 | 28658.02 | 03-JUN-05:00 | 132137.22 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 266.04 | 3144.96 | 02-JAN-02:10 | 19685.67 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2192.89 | 28516.88 | 03-JUN-05:00 | 131895.89 | 02-JAN-20:10 |
InteriorLights:Electricity | 544.43 | 4623.20 | 03-JUN-05:00 | 45764.37 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 122.93 | 1117.06 | 02-JAN-02:10 | 10053.14 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 544.43 | 4623.20 | 03-JUN-05:00 | 45764.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 544.43 | 4623.20 | 03-JUN-05:00 | 45764.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 122.93 | 1117.06 | 02-JAN-02:10 | 10053.14 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 544.43 | 4623.20 | 03-JUN-05:00 | 45764.37 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.45 | 201.26 | 02-JAN-02:10 | 1197.92 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.05 | 233.06 | 02-JAN-02:10 | 1387.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.91 | 71.95 | 02-JAN-02:10 | 430.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.31 | 20.97 | 02-JAN-02:10 | 188.71 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.31 | 20.97 | 02-JAN-02:10 | 188.71 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 27.00 | 263.19 | 03-JUN-05:00 | 2538.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.66 | 59.98 | 03-JUN-05:00 | 1573.46 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.66 | 59.98 | 03-JUN-05:00 | 1573.46 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 240.93 | 2909.76 | 03-JUN-05:00 | 18013.24 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 91.93 | 798.35 | 03-JUN-05:00 | 7984.04 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 91.93 | 798.35 | 03-JUN-05:00 | 7984.04 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 253.77 | 3619.58 | 02-JAN-10:10 | 20179.99 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 253.84 | 3620.57 | 02-JAN-10:10 | 20185.51 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 3.85 | 55.20 | 01-JAN-02:10 | 290.10 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 3.85 | 55.19 | 01-JAN-02:10 | 290.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 30.06 | 428.75 | 02-JAN-10:10 | 2390.39 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 203.88 | 2433.51 | 27-MAY-05:00 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.02 | 184.21 | 27-MAY-05:00 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.02 | 184.21 | 27-MAY-05:00 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 203.88 | 2433.51 | 27-MAY-05:00 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.02 | 184.21 | 27-MAY-05:00 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.02 | 184.21 | 27-MAY-05:00 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 43.88 | 732.79 | 04-JAN-23:30 | 2790.68 | 04-JUL-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 774.41 | 2327.24 | 22-APR-00:10 | 193004.84 | 29-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 15.81 | 0.00 | 01-JAN-11:10 | 1307.93 | 23-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 20.98 | 598.27 | 09-JAN-04:40 | 716.64 | 03-AUG-13:30 |
Fans:Electricity | 561.29 | 11913.95 | 25-FEB-08:00 | 33453.50 | 29-JUN-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 707.19 | 13008.61 | 01-JUN-04:00 | 42546.09 | 29-JUN-21:10 |
ExteriorEquipment:Electricity | 640.54 | 9443.87 | 02-JAN-02:20 | 39153.73 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.51 | 379.00 | 03-JUN-05:00 | 1274.03 | 03-JAN-08:00 |
ElectricityPurchased:Facility | 4494.04 | 66678.99 | 13-MAY-05:00 | 375896.10 | 29-JUN-18:10 |
ElectricityPurchased:Plant | 4494.04 | 66678.99 | 13-MAY-05:00 | 375896.10 | 29-JUN-18:10 |
Cogeneration:ElectricityPurchased | 4494.04 | 66678.99 | 13-MAY-05:00 | 375896.10 | 29-JUN-18:10 |
General:Cogeneration:ElectricityPurchased | 4494.04 | 66678.99 | 13-MAY-05:00 | 375896.10 | 29-JUN-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4494.04 | 66678.99 | 13-MAY-05:00 | 375896.10 | 29-JUN-18:10 |
ElectricityNet:Plant | 4494.04 | 66678.99 | 13-MAY-05:00 | 375896.10 | 29-JUN-18:10 |
Cogeneration:ElectricityNet | 4494.04 | 66678.99 | 13-MAY-05:00 | 375896.10 | 29-JUN-18:10 |
General:Cogeneration:ElectricityNet | 4494.04 | 66678.99 | 13-MAY-05:00 | 375896.10 | 29-JUN-18:10 |
General:Fans:Electricity | 561.29 | 11913.95 | 25-FEB-08:00 | 33453.50 | 29-JUN-21:10 |
ExteriorLights:Electricity | 193.43 | 0.00 | 01-JAN-08:20 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.43 | 0.00 | 01-JAN-08:20 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 124.39 | 0.00 | 16-JAN-11:00 | 8265.52 | 27-JUN-09:00 |
General:HeatRecovery:Electricity | 124.39 | 0.00 | 16-JAN-11:00 | 8265.52 | 27-JUN-09:00 |
WaterSystems:Electricity | 90.74 | 1086.56 | 20-MAR-03:00 | 4738.75 | 09-MAR-19:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 20-MAR-03:00 | 4738.75 | 09-MAR-19:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 557.69 | 0.00 | 01-JAN-00:10 | 182398.39 | 29-JUN-15:30 |
General:Cooling:Electricity | 557.69 | 0.00 | 01-JAN-00:10 | 182398.39 | 29-JUN-15:30 |
Pumps:Electricity | 89.19 | 47.91 | 12-MAY-14:10 | 5857.64 | 29-JUN-18:10 |
General:Pumps:Electricity | 89.19 | 47.91 | 12-MAY-14:10 | 5857.64 | 29-JUN-18:10 |
WIRED_LTG_ELECTRICITY | 19.16 | 0.00 | 01-JAN-00:10 | 1610.91 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 7729.39 | 29270.80 | 24-APR-01:20 | 1004501.26 | 04-JAN-21:50 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 5940.55 | 15908.90 | 26-MAY-15:20 | 929377.50 | 04-JAN-21:50 |
WaterSystems:NaturalGas | 3482.62 | 15908.90 | 12-FEB-16:20 | 311632.67 | 22-FEB-22:00 |
Water Heater:WaterSystems:NaturalGas | 3482.62 | 15908.90 | 12-FEB-16:20 | 311632.67 | 22-FEB-22:00 |
Heating:NaturalGas | 2457.93 | 0.00 | 11-APR-18:40 | 695821.73 | 06-JAN-05:10 |
Boiler:Heating:NaturalGas | 2457.93 | 0.00 | 11-APR-18:40 | 695821.73 | 06-JAN-05:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 1727.53 | 0.00 | 01-JAN-00:10 | 571451.87 | 29-JUN-18:10 |
PlantLoopCoolingDemand:HVAC | 1727.53 | 0.00 | 01-JAN-00:10 | 571451.87 | 29-JUN-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 1727.53 | 0.00 | 01-JAN-00:10 | 571451.87 | 29-JUN-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAY-20:40 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAY-20:40 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAY-20:40 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAY-20:40 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAY-20:40 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAY-20:40 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 17912.01 | 129468.62 | 28-SEP-14:00 | 2434835.33 | 29-JUN-18:10 |
EnergyTransfer:Building | 4776.80 | 73345.12 | 15-FEB-11:00 | 341610.41 | 29-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 671.19 | 7619.09 | 08-JAN-04:00 | 35594.81 | 23-JUL-10:40 |
Refrigeration:EnergyTransfer | 181.95 | 3939.34 | 05-JAN-02:50 | 10367.68 | 19-SEP-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.98 | 1969.67 | 05-JAN-02:50 | 5183.84 | 19-SEP-06:30 |
General:Refrigeration:EnergyTransfer | 90.98 | 1969.67 | 05-JAN-02:50 | 5183.84 | 19-SEP-06:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.98 | 1969.67 | 05-JAN-02:50 | 5183.84 | 19-SEP-06:30 |
EnergyTransfer:Plant | 6945.74 | 19699.59 | 17-AUG-15:10 | 1370649.30 | 29-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.57 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.41 | 1732.93 | 09-JAN-04:40 | 2559.14 | 03-AUG-13:30 |
EnergyTransfer:Zone:BASEMENT | 362.96 | 8014.10 | 06-JAN-13:30 | 20334.62 | 26-JAN-07:00 |
Heating:EnergyTransfer | 498.36 | 0.00 | 08-FEB-13:30 | 120509.11 | 25-DEC-16:30 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 498.36 | 0.00 | 08-FEB-13:30 | 120509.11 | 25-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4187.46 | 48225.87 | 25-DEC-15:00 | 337988.82 | 29-JUN-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 362.96 | 8014.10 | 06-JAN-13:30 | 20334.62 | 26-JAN-07:00 |
General:Cooling:EnergyTransfer | 4187.46 | 48225.87 | 25-DEC-15:00 | 337988.82 | 29-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 362.96 | 8014.10 | 06-JAN-13:30 | 20334.62 | 26-JAN-07:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 32.41 | 0.00 | 30-OCT-16:30 | 4649.74 | 22-OCT-12:00 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 6.45 | 0.00 | 01-JAN-09:30 | 1910.00 | 08-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 6.45 | 0.00 | 01-JAN-09:30 | 1910.00 | 08-JAN-08:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 25.96 | 0.00 | 01-JAN-00:10 | 4649.74 | 22-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 25.96 | 0.00 | 01-JAN-00:10 | 4649.74 | 22-OCT-12:00 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.83 | 1.54 | 19-DEC-10:10 | 1923.15 | 30-JUN-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 191.75 | 21-DEC-11:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 191.75 | 21-DEC-11:00 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.82 | 0.00 | 06-JAN-12:30 | 1923.15 | 30-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.82 | 0.00 | 06-JAN-12:30 | 1923.15 | 30-JUN-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 9.64 | 0.01 | 03-FEB-19:50 | 1579.50 | 30-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 4.04 | 0.00 | 15-JAN-20:20 | 1310.05 | 06-JAN-13:30 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 4.04 | 0.00 | 15-JAN-20:20 | 1310.05 | 06-JAN-13:30 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 5.59 | 0.00 | 01-JAN-00:10 | 1579.50 | 30-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 5.59 | 0.00 | 01-JAN-00:10 | 1579.50 | 30-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 15.48 | 0.01 | 04-NOV-23:50 | 992.32 | 30-JUN-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 4.36 | 0.00 | 19-JAN-21:10 | 981.50 | 06-JAN-13:30 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 4.36 | 0.00 | 19-JAN-21:10 | 981.50 | 06-JAN-13:30 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.11 | 0.00 | 01-JAN-00:10 | 992.32 | 30-JUN-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.11 | 0.00 | 01-JAN-00:10 | 992.32 | 30-JUN-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 570.88 | 6549.07 | 06-JAN-05:00 | 39193.07 | 28-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 570.88 | 6549.07 | 06-JAN-05:00 | 39193.07 | 28-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 570.88 | 6549.07 | 06-JAN-05:00 | 39193.07 | 28-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 216.08 | 1.34 | 03-DEC-15:30 | 15778.38 | 22-OCT-12:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.17 | 0.00 | 01-JAN-00:10 | 1929.64 | 23-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.17 | 0.00 | 01-JAN-00:10 | 1929.64 | 23-JAN-09:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 215.91 | 0.00 | 07-JAN-09:10 | 15778.38 | 22-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 215.91 | 0.00 | 07-JAN-09:10 | 15778.38 | 22-OCT-12:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 715.55 | 989.40 | 21-DEC-10:50 | 38226.85 | 29-JUN-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.86 | 21-DEC-11:00 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.86 | 21-DEC-11:00 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 715.55 | 989.40 | 21-DEC-10:50 | 38226.85 | 29-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 715.55 | 989.40 | 21-DEC-10:50 | 38226.85 | 29-JUN-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 75.36 | 0.00 | 01-JAN-11:00 | 12785.29 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 39.96 | 0.00 | 01-JAN-11:00 | 7783.03 | 25-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 39.96 | 0.00 | 01-JAN-11:00 | 7783.03 | 25-DEC-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 35.40 | 0.00 | 01-JAN-00:10 | 12785.29 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 35.40 | 0.00 | 01-JAN-00:10 | 12785.29 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 71.20 | 0.00 | 03-JAN-08:00 | 12620.09 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 47.06 | 0.00 | 03-JAN-08:00 | 8228.00 | 06-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 47.06 | 0.00 | 03-JAN-08:00 | 8228.00 | 06-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 24.14 | 0.00 | 01-JAN-00:10 | 12620.09 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 24.14 | 0.00 | 01-JAN-00:10 | 12620.09 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 229.91 | 0.00 | 01-JAN-00:10 | 58521.66 | 22-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 43.67 | 0.00 | 01-JAN-00:10 | 31037.33 | 09-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 43.67 | 0.00 | 01-JAN-00:10 | 31037.33 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 186.24 | 0.00 | 01-JAN-00:10 | 58521.66 | 22-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 186.24 | 0.00 | 01-JAN-00:10 | 58521.66 | 22-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 379.46 | 0.00 | 01-JAN-08:00 | 67326.03 | 28-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 162.76 | 0.00 | 01-JAN-08:00 | 44469.19 | 06-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 162.76 | 0.00 | 01-JAN-08:00 | 44469.19 | 06-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 216.70 | 0.00 | 01-JAN-00:10 | 67326.03 | 28-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 216.70 | 0.00 | 01-JAN-00:10 | 67326.03 | 28-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 74.68 | 0.00 | 01-JAN-11:00 | 11371.84 | 29-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 39.81 | 0.00 | 01-JAN-11:00 | 7796.01 | 25-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 39.81 | 0.00 | 01-JAN-11:00 | 7796.01 | 25-DEC-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 34.87 | 0.00 | 01-JAN-00:10 | 11371.84 | 29-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 34.87 | 0.00 | 01-JAN-00:10 | 11371.84 | 29-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 71.41 | 0.00 | 02-JAN-11:00 | 12001.21 | 19-JUL-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 46.96 | 0.00 | 02-JAN-11:00 | 8114.89 | 06-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 46.96 | 0.00 | 02-JAN-11:00 | 8114.89 | 06-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 24.44 | 0.00 | 01-JAN-00:10 | 12001.21 | 19-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 24.44 | 0.00 | 01-JAN-00:10 | 12001.21 | 19-JUL-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 132.61 | 0.08 | 20-JAN-07:00 | 9511.82 | 30-JUN-18:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 15.27 | 0.00 | 02-JAN-21:10 | 6851.94 | 21-DEC-11:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 15.27 | 0.00 | 02-JAN-21:10 | 6851.94 | 21-DEC-11:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 117.33 | 0.00 | 01-JAN-00:10 | 9511.82 | 30-JUN-18:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 117.33 | 0.00 | 01-JAN-00:10 | 9511.82 | 30-JUN-18:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 22.58 | 0.00 | 02-JAN-11:00 | 3384.37 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.81 | 0.00 | 02-JAN-11:00 | 2417.28 | 18-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.81 | 0.00 | 02-JAN-11:00 | 2417.28 | 18-DEC-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.78 | 0.00 | 01-JAN-00:10 | 3384.37 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.78 | 0.00 | 01-JAN-00:10 | 3384.37 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 22.00 | 0.00 | 16-JAN-08:00 | 3494.09 | 06-MAY-19:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 15.92 | 0.00 | 16-JAN-08:00 | 2423.80 | 06-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 15.92 | 0.00 | 16-JAN-08:00 | 2423.80 | 06-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.08 | 0.00 | 01-JAN-00:10 | 3494.09 | 06-MAY-19:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.08 | 0.00 | 01-JAN-00:10 | 3494.09 | 06-MAY-19:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 96.68 | 0.00 | 01-JAN-11:00 | 16293.65 | 25-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 41.87 | 0.00 | 01-JAN-10:30 | 10941.09 | 11-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 41.87 | 0.00 | 01-JAN-10:30 | 10941.09 | 11-DEC-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 54.81 | 0.00 | 01-JAN-00:10 | 16293.65 | 25-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 54.81 | 0.00 | 01-JAN-00:10 | 16293.65 | 25-AUG-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 445.01 | 3266.77 | 06-JAN-13:30 | 21634.31 | 29-JUN-22:00 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 445.01 | 3266.77 | 06-JAN-13:30 | 21634.31 | 29-JUN-22:00 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 445.01 | 3266.77 | 06-JAN-13:30 | 21634.31 | 29-JUN-22:00 |
EnergyTransfer:Zone:DINING_FLR_6 | 471.79 | 4688.24 | 06-JAN-13:20 | 23040.30 | 29-JUN-22:00 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 471.79 | 4688.24 | 06-JAN-13:20 | 23040.30 | 29-JUN-22:00 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 471.79 | 4688.24 | 06-JAN-13:20 | 23040.30 | 29-JUN-22:00 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 580.22 | 5159.73 | 07-JAN-04:10 | 30522.50 | 23-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 580.22 | 5159.73 | 07-JAN-04:10 | 30522.50 | 23-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 59.10 | 0.35 | 19-JAN-19:40 | 6252.31 | 29-JUL-13:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 16.24 | 0.00 | 17-JAN-12:30 | 4720.06 | 07-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 16.24 | 0.00 | 17-JAN-12:30 | 4720.06 | 07-JAN-04:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 42.86 | 0.00 | 01-JAN-00:10 | 6252.31 | 29-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 42.86 | 0.00 | 01-JAN-00:10 | 6252.31 | 29-JUL-13:30 |
PlantLoopHeatingDemand:Facility | 2721.44 | 10714.25 | 26-AUG-01:10 | 625559.99 | 06-JAN-07:40 |
PlantLoopHeatingDemand:Plant | 900.58 | 10714.25 | 26-AUG-01:10 | 66771.64 | 23-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 900.58 | 10714.25 | 26-AUG-01:10 | 66771.64 | 23-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 900.58 | 10714.25 | 26-AUG-01:10 | 66771.64 | 23-FEB-07:10 |
EnergyTransfer:HVAC | 6189.48 | 0.00 | 31-MAY-15:10 | 722575.62 | 29-JUN-18:10 |
HeatingCoils:EnergyTransfer | 1820.86 | 0.00 | 11-APR-18:40 | 567170.80 | 06-JAN-05:10 |
PlantLoopHeatingDemand:HVAC | 1820.86 | 0.00 | 11-APR-18:40 | 567170.80 | 06-JAN-05:10 |
HeatingCoils:PlantLoopHeatingDemand | 1820.86 | 0.00 | 11-APR-18:40 | 567170.80 | 06-JAN-05:10 |
CoolingCoils:EnergyTransfer | 1727.53 | 0.00 | 01-JAN-00:10 | 571451.87 | 29-JUN-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 2562.60 | 0.00 | 01-JAN-00:40 | 419199.47 | 24-FEB-06:20 |
HeatRecoveryForCooling:EnergyTransfer | 78.48 | 0.00 | 01-JAN-00:10 | 154366.72 | 29-JUN-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 900.58 | 10714.25 | 26-AUG-01:10 | 66771.64 | 23-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 900.58 | 10714.25 | 26-AUG-01:10 | 66771.64 | 23-FEB-07:10 |
Boilers:EnergyTransfer | 1807.36 | 0.00 | 11-APR-18:40 | 564694.64 | 06-JAN-05:10 |
Chillers:EnergyTransfer | 1794.57 | 0.00 | 01-JAN-00:10 | 574750.99 | 29-JUN-18:10 |
HeatRejection:EnergyTransfer | 2352.25 | 0.00 | 01-JAN-00:10 | 755698.08 | 29-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 2352.25 | 0.00 | 01-JAN-00:10 | 755698.08 | 29-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -362.959 | 0.000 | 0.000 | 143.702 | 122.932 | 143.105 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -46.781 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 6.452 | -25.959 | 0.000 | 0.000 | 15.293 | 6.265 | 10.186 | 24.881 | 0.000 | 0.044 | 0.000 | 0.000 | -13.733 | 0.000 | -7.507 | -15.922 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.005 | -30.823 | 0.000 | 0.000 | 17.643 | 7.255 | 11.795 | 0.000 | 0.000 | 0.025 | 0.000 | 0.000 | 0.000 | 0.000 | -2.887 | -3.012 |
MECH_FLR_1 | 0.000 | 0.000 | 4.045 | -5.594 | 0.000 | 0.000 | 3.607 | 8.366 | 12.471 | 0.000 | 0.000 | 0.040 | 0.000 | 0.000 | 0.000 | 0.000 | -7.030 | -15.905 |
STORAGE_FLR_1 | 0.000 | 0.000 | 4.364 | -11.112 | 0.000 | 0.000 | 2.993 | 2.308 | 3.598 | 0.000 | 0.000 | 0.044 | 1.619 | 0.000 | 0.000 | 0.000 | -3.814 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -570.879 | 0.000 | 0.000 | 10.551 | 4.900 | 658.131 | 0.000 | 0.000 | 0.054 | 0.000 | 0.000 | 0.000 | 0.000 | -10.262 | -92.495 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.165 | -215.914 | 0.000 | 0.000 | 202.501 | 12.659 | 14.341 | 70.422 | 0.000 | 0.144 | 0.000 | 0.000 | -38.281 | 0.000 | -16.408 | -29.628 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -715.550 | 0.000 | 0.000 | 581.134 | 91.929 | 148.998 | 92.434 | 0.000 | 0.394 | 0.000 | 0.000 | -52.180 | 0.000 | -48.008 | -99.150 |
ROOM_1_FLR_3 | 46.389 | -30.452 | 0.000 | -11.373 | 0.000 | 0.000 | 9.768 | 4.922 | 10.478 | 45.506 | 0.000 | 0.232 | 0.000 | 0.000 | -31.442 | 0.000 | -17.224 | -26.803 |
ROOM_2_FLR_3 | 53.699 | -18.928 | 0.000 | -11.853 | 0.000 | 0.000 | 9.637 | 4.922 | 10.477 | 31.085 | 0.000 | 0.168 | 0.000 | 0.000 | -33.561 | 0.000 | -17.541 | -28.104 |
ROOM_3_MULT19_FLR_3 | 43.653 | -175.309 | 0.020 | -10.939 | 0.000 | 0.000 | 0.000 | 58.777 | 194.997 | 291.106 | 0.000 | 0.159 | 0.003 | 0.000 | -175.548 | 0.000 | -94.761 | -132.155 |
ROOM_4_MULT19_FLR_3 | 238.797 | -135.926 | 0.000 | -156.796 | 0.000 | 0.000 | 184.497 | 58.793 | 195.050 | 76.375 | 0.000 | 1.060 | 0.000 | 0.000 | -189.580 | 0.000 | -102.654 | -169.615 |
ROOM_5_FLR_3 | 46.233 | -29.914 | 0.000 | -11.377 | 0.000 | 0.000 | 9.764 | 4.922 | 10.478 | 45.009 | 0.000 | 0.233 | 0.000 | 0.000 | -30.895 | 0.000 | -17.257 | -27.196 |
ROOM_6_FLR_3 | 53.636 | -19.359 | 0.000 | -11.756 | 0.000 | 0.000 | 9.678 | 4.922 | 10.477 | 30.411 | 0.000 | 0.168 | 0.000 | 0.000 | -32.725 | 0.000 | -17.680 | -27.772 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 15.271 | -117.335 | 0.000 | 0.000 | 120.030 | 56.739 | 0.000 | 40.954 | 0.000 | 0.160 | 0.000 | 0.000 | -40.074 | 0.000 | -20.785 | -54.959 |
ROOM_1_FLR_6 | 15.502 | -7.634 | 0.000 | -2.838 | 0.000 | 0.000 | 2.446 | 1.231 | 2.620 | 11.335 | 0.000 | 0.059 | 0.000 | 0.000 | -7.833 | 0.000 | -4.326 | -10.561 |
ROOM_2_FLR_6 | 17.640 | -4.834 | 0.000 | -2.969 | 0.000 | 0.000 | 2.408 | 1.230 | 2.619 | 7.734 | 0.000 | 0.042 | 0.000 | 0.000 | -8.374 | 0.000 | -4.396 | -11.099 |
ROOM_3_MULT9_FLR_6 | 51.445 | -45.990 | 0.000 | -18.396 | 0.000 | 0.000 | 21.893 | 6.962 | 23.098 | 64.924 | 0.000 | 0.339 | 0.000 | 0.000 | -36.144 | 0.000 | -20.793 | -47.339 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -445.014 | 0.000 | 0.000 | 344.682 | 28.023 | 175.857 | 8.654 | 0.000 | 0.103 | 0.000 | 0.000 | -22.676 | 0.000 | -10.784 | -78.845 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -471.795 | 0.000 | 0.000 | 339.100 | 28.023 | 175.857 | 8.439 | 0.000 | 0.094 | 0.000 | 0.000 | -23.228 | 0.000 | -10.925 | -45.565 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -580.204 | 0.000 | 0.000 | 28.013 | 13.339 | 540.650 | 22.315 | 0.000 | 0.053 | 1.158 | 0.000 | -14.838 | 0.000 | -10.484 | -0.004 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 16.240 | -42.861 | 0.000 | 0.000 | 30.917 | 15.012 | 0.000 | 20.167 | 0.000 | 0.052 | 0.000 | 0.000 | -18.082 | 0.000 | -9.432 | -12.013 |
Total Facility | 566.994 | -468.346 | 46.563 | -3834.295 | 0.000 | 0.000 | 2090.256 | 544.430 | 2355.282 | 891.748 | 0.000 | 3.665 | 2.781 | 0.000 | -769.195 | 0.000 | -454.960 | -974.923 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 26-JAN-07:00 | 0.00 | 0.00 | 0.00 | -20333.49 | 0.00 | 0.00 | 5954.63 | 4468.11 | 5069.75 | 0.00 | 0.00 | 0.00 | 4841.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 22-OCT-12:00 | 0.00 | 0.00 | 0.00 | -4649.82 | 0.00 | 0.00 | 225.90 | 170.77 | 288.68 | 7494.48 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -84.12 | -3445.88 |
RETAIL_2_FLR_1 | 30-JUN-20:10 | 0.00 | 0.00 | 0.00 | -1923.31 | 0.00 | 0.00 | 697.61 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1.02 | -52.76 |
MECH_FLR_1 | 30-JUN-20:00 | 0.00 | 0.00 | 0.00 | -1579.45 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 4.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -77.31 |
STORAGE_FLR_1 | 30-JUN-10:35 | 0.00 | 0.00 | 0.00 | -995.18 | 0.00 | 0.00 | 30.94 | 52.42 | 89.22 | 0.00 | 0.00 | 47.05 | 775.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 28-JUN-20:00 | 0.00 | 0.00 | 0.00 | -39194.07 | 0.00 | 0.00 | 408.87 | 400.68 | 44299.38 | 0.00 | 0.00 | 13.91 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5928.77 |
CAFE_FLR_1 | 22-OCT-12:00 | 0.00 | 0.00 | 0.00 | -15778.66 | 0.00 | 0.00 | 2968.69 | 115.39 | 406.43 | 21070.58 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -185.92 | -8596.51 |
LOBBY_FLR_1 | 29-JUN-21:10 | 0.00 | 0.00 | 0.00 | -38234.81 | 0.00 | 0.00 | 26440.19 | 5322.69 | 7389.94 | 153.52 | 0.00 | 253.23 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1324.76 |
ROOM_1_FLR_3 | 04-MAY-15:11 | 0.00 | -15237.52 | 0.00 | -699.28 | 0.00 | 0.00 | 235.29 | 106.08 | 200.18 | 10701.20 | 0.00 | 0.00 | 4888.60 | 0.00 | -0.00 | 0.00 | -194.55 | 0.00 |
ROOM_2_FLR_3 | 06-MAY-19:01 | 0.00 | -16642.51 | 0.00 | -670.22 | 0.00 | 0.00 | 240.71 | 378.82 | 653.15 | 2744.65 | 0.00 | 0.00 | 13586.37 | 0.00 | -0.00 | 0.00 | -290.97 | 0.00 |
ROOM_3_MULT19_FLR_3 | 22-OCT-12:30 | 0.00 | -58523.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1492.91 | 2548.95 | 88570.38 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1302.49 | -32786.71 |
ROOM_4_MULT19_FLR_3 | 07-JUN-08:51 | 0.00 | -72861.73 | 0.00 | -9753.30 | 0.00 | 0.00 | 1673.35 | 1991.09 | 8433.45 | 13319.76 | 0.00 | 0.00 | 57431.43 | 0.00 | -0.00 | 0.00 | -234.04 | 0.00 |
ROOM_5_FLR_3 | 03-MAY-15:11 | 0.00 | -13663.83 | 0.00 | -695.87 | 0.00 | 0.00 | 235.28 | 106.08 | 200.18 | 3422.21 | 0.00 | 0.00 | 10599.63 | 0.00 | -0.00 | 0.00 | -203.68 | 0.00 |
ROOM_6_FLR_3 | 31-JUL-08:32 | 0.00 | -14053.51 | 0.00 | -926.64 | 0.00 | 0.00 | 59.49 | 166.68 | 452.99 | 9839.75 | 0.00 | 0.00 | 4671.92 | 0.00 | -0.00 | 0.00 | -210.69 | 0.00 |
CORRIDOR_FLR_3 | 30-JUN-18:40 | 0.00 | 0.00 | 0.00 | -9512.15 | 0.00 | 0.00 | 4080.40 | 4124.45 | 0.00 | 3020.59 | 0.00 | 139.11 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1852.41 |
ROOM_1_FLR_6 | 04-MAY-15:11 | 0.00 | -3974.38 | 0.00 | -175.11 | 0.00 | 0.00 | 58.82 | 26.52 | 50.05 | 2661.65 | 0.00 | 0.00 | 1411.07 | 0.00 | -0.00 | 0.00 | -58.63 | 0.00 |
ROOM_2_FLR_6 | 06-MAY-18:42 | 0.00 | -4658.97 | 0.00 | -196.33 | 0.00 | 0.00 | 47.86 | 94.71 | 121.15 | 1243.42 | 0.00 | 0.00 | 3428.26 | 0.00 | -0.00 | 0.00 | -80.10 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13-APR-15:11 | 0.00 | -19642.41 | 0.00 | -1076.08 | 0.00 | 0.00 | 529.40 | 150.05 | 441.28 | 7934.19 | 0.00 | 0.00 | 12497.21 | 0.00 | -0.00 | 0.00 | -833.63 | 0.00 |
BANQUET_FLR_6 | 29-JUN-22:00 | 0.00 | 0.00 | 0.00 | -21634.23 | 0.00 | 0.00 | 15644.65 | 1842.08 | 6747.90 | 76.48 | 0.00 | 40.97 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2717.86 |
DINING_FLR_6 | 29-JUN-22:00 | 0.00 | 0.00 | 0.00 | -23040.26 | 0.00 | 0.00 | 15644.53 | 1842.08 | 6747.90 | 63.86 | 0.00 | 40.97 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1299.08 |
KITCHEN_FLR_6 | 23-JUL-10:40 | 0.00 | 0.00 | 0.00 | -30525.51 | 0.00 | 0.00 | 464.21 | 363.61 | 23951.61 | 4287.79 | 0.00 | 50.99 | 1407.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 29-JUL-13:30 | 0.00 | 0.00 | 0.00 | -6253.10 | 0.00 | 0.00 | 462.68 | 341.02 | 0.00 | 3784.50 | 0.00 | 68.79 | 1596.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-JUN-18:02 | 0.00 | -165675.59 | 0.00 | -199176.47 | 0.00 | 0.00 | 77741.63 | 36642.55 | 120174.13 | 67901.48 | 0.00 | 5493.13 | 56899.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 07-JAN-04:03 | 0.00 | 0.00 | 2077.75 | 0.00 | 0.00 | 0.00 | 808.55 | 56.92 | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1483.33 | 0.00 | -602.90 | -1001.33 |
RETAIL_2_FLR_1 | 21-DEC-10:51 | 0.00 | 0.00 | 465.90 | 0.00 | 0.00 | 0.00 | 208.31 | 164.79 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -233.09 | -898.42 |
MECH_FLR_1 | 06-JAN-13:30 | 0.00 | 0.00 | 1310.06 | 0.00 | 0.00 | 0.00 | 45.63 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -544.52 | -1310.50 |
STORAGE_FLR_1 | 06-JAN-13:30 | 0.00 | 0.00 | 981.52 | 0.00 | 0.00 | 0.00 | 35.93 | 52.42 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -310.76 | -848.33 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 21-DEC-10:51 | 0.00 | 0.00 | 3762.50 | 0.00 | 0.00 | 0.00 | 2383.54 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -773.52 | 0.00 | -1331.71 | -4492.60 |
LOBBY_FLR_1 | 21-DEC-10:51 | 0.00 | 0.00 | 6.87 | 0.00 | 0.00 | 0.00 | 6985.83 | 1907.30 | 3694.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1078.95 | 0.00 | -3819.48 | -7696.54 |
ROOM_1_FLR_3 | 18-DEC-16:23 | 8467.44 | 363.91 | 0.00 | -363.91 | 0.00 | 0.00 | 266.42 | 106.08 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3567.17 | 0.00 | -1367.85 | -4105.11 |
ROOM_2_FLR_3 | 05-JAN-07:54 | 8822.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.62 | 212.14 | 948.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4019.13 | 0.00 | -1670.80 | -4514.14 |
ROOM_3_MULT19_FLR_3 | 09-JAN-05:00 | 31037.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.64 | 3333.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20268.16 | 0.00 | -8440.40 | -6159.49 |
ROOM_4_MULT19_FLR_3 | 06-JAN-10:51 | 49039.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2103.94 | 1267.05 | 2353.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12564.08 | 0.00 | -7924.31 | -34275.82 |
ROOM_5_FLR_3 | 21-DEC-16:12 | 8263.43 | 272.85 | 0.00 | -272.85 | 0.00 | 0.00 | 293.98 | 106.08 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2702.22 | 0.00 | -1073.80 | -5087.66 |
ROOM_6_FLR_3 | 06-JAN-07:53 | 8937.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.81 | 212.14 | 948.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3955.78 | 0.00 | -1786.68 | -4584.21 |
CORRIDOR_FLR_3 | 21-DEC-10:51 | 0.00 | 0.00 | 6902.56 | 0.00 | 0.00 | 0.00 | 1395.75 | 1288.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1600.15 | 0.00 | -1694.17 | -6292.89 |
ROOM_1_FLR_6 | 06-JAN-07:53 | 2709.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.63 | 53.04 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -985.80 | 0.00 | -447.78 | -1622.66 |
ROOM_2_FLR_6 | 05-JAN-07:53 | 2659.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.26 | 53.04 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -997.44 | 0.00 | -417.70 | -1592.04 |
ROOM_3_MULT9_FLR_6 | 11-DEC-16:23 | 11746.21 | 585.83 | 0.00 | -585.83 | 0.00 | 0.00 | 599.40 | 150.05 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3294.10 | 0.00 | -1323.84 | -8319.00 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 07-JAN-04:03 | 0.00 | 0.00 | 4747.78 | 0.00 | 0.00 | 0.00 | 1674.56 | 136.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1936.75 | 0.00 | -746.08 | -3875.92 |
Total Facility | 25-DEC-16:23 | 52364.01 | 62410.99 | 15395.43 | -62410.99 | 0.00 | 0.00 | 36858.03 | 11386.61 | 70977.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -59518.93 | 0.00 | -26348.84 | -101114.28 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.1746 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.0556 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 13.1454 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.5317 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2797 | 2.2797 | 1.2812 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4170 | 0.4170 | 0.1188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2255 | 0.2255 | 0.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1797 | 0.1797 | 0.0018 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0984 | 0.0984 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3960 | 3.3960 | 0.0340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7176 | 1.7176 | 1.0151 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0362 | 5.0362 | 2.8404 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3242 | 1.3242 | 0.7124 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1841 | 2.1841 | 1.7822 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2940 | 2.2940 | 1.7824 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2954 | 2.2954 | 0.5509 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7268 | 0.7268 | 0.1882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.1746 | 22.0556 | 22.1746 | 10.5317 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2812 | 1.2812 | 1.2812 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2085 | 0.2085 | 0.1188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1376 | 0.1376 | 0.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0899 | 0.0899 | 0.0018 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0866 | 0.0866 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6980 | 1.6980 | 0.0340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0151 | 1.0151 | 1.0151 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8404 | 2.8404 | 2.8404 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7124 | 0.7124 | 0.7124 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7822 | 1.7822 | 1.7822 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7824 | 1.7824 | 1.7824 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1477 | 1.1477 | 0.5509 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3634 | 0.3634 | 0.1882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 13.1454 | 10.5317 | 10.5317 | 10.5317 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 309.17 |
Number of hours cooling loads not met | 49.00 |
Number of hours not met | 358.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 2457.93 | 695821.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 557.69 | 182398.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 544.43 | 45764.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.43 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.51 | 1274.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 561.29 | 33453.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 89.19 | 5857.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 124.39 | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.75 | 3482.62 | 311632.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.81 | 1307.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 20.98 | 716.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1692.33 | 4494.04 |
Natural Gas | 1788.84 | 7729.39 |
Additional | 0.00 | 0.00 |
Total | 3481.17 | 12223.43 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 47.99 |
Space Heating | 0.00 |
Space Cooling | 49.16 |
Fans (All) | 49.47 |
Service Water Heating | 8.00 |
Receptacle Equipment | 145.30 |
Miscellaneous (All) | 396.12 |
Subtotal | 396.12 |
Natural Gas [MJ/m2] | |
Space Heating | 216.65 |
Service Water Heating | 306.97 |
Miscellaneous (All) | 681.29 |
Subtotal | 681.29 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 4.45 |
Space Heating | 20.11 |
Space Cooling | 4.56 |
Fans (All) | 4.59 |
Service Water Heating | 29.23 |
Receptacle Equipment | 28.12 |
Miscellaneous | 8.93 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8671.50 | 88.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8228.17 | 531.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8731.00 | 29.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8624.17 | 135.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8228.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 531.83 | 0.00 | 0.00 | 0.00 |
Average | 8724.31 | 35.69 | 0.00 | 0.00 | 0.00 |
Sum | 191934.83 | 785.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4125.83 | 28.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4101.50 | 52.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 52.50 | 0.00 | 0.00 | 0.00 |
Average | 288883.38 | 3.67 | 0.00 | 0.00 | 0.00 |
Sum | 6355434.33 | 80.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8750.00 | 10.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8669.50 | 90.50 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8442.17 | 317.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8584.33 | 175.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7944.50 | 815.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8733.67 | 26.33 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8666.33 | 93.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8524.17 | 235.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8490.50 | 269.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8458.00 | 302.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8719.33 | 40.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8656.83 | 103.17 | 0.00 | 0.00 | 0.00 |
Min | 7944.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 815.50 | 0.00 | 0.00 | 0.00 |
Average | 8646.85 | 113.15 | 0.00 | 0.00 | 0.00 |
Sum | 190230.67 | 2489.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50092.33 | 86.67 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59141.33 | 14.67 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 698837.83 | 11579.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1998930.00 | 116499.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4080.67 | 73.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4143.83 | 10.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4139.50 | 14.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100261.00 | 97.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4036.50 | 117.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1186430.33 | 59284.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1180121.17 | 65593.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107971.50 | 297.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 104117.67 | 1828.33 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1998930.00 | 116499.00 | 0.00 | 0.00 | 0.00 |
Average | 277273.58 | 11613.47 | 0.00 | 0.00 | 0.00 |
Sum | 6100018.67 | 255496.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:18
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307690E+11 | 20334.62 | 26-JAN-07:00 | -33.3 | -33.4 | 0.702835E+10 | 4646.28 | 24-JAN-22:10 | -33.3 | -33.4 |
February | 0.261336E+11 | 20038.48 | 14-FEB-07:00 | -33.3 | -33.4 | 0.643799E+10 | 4517.57 | 10-FEB-22:10 | -33.3 | -33.4 |
March | 0.260317E+11 | 16211.17 | 05-MAR-07:00 | -28.9 | -29.1 | 0.680813E+10 | 4403.40 | 01-MAR-22:10 | -28.9 | -29.1 |
April | 0.249831E+11 | 12274.00 | 22-APR-10:35 | 14.43 | 5.29 | 0.649410E+10 | 4164.13 | 21-APR-22:10 | 14.43 | 5.29 |
May | 0.275886E+11 | 13069.36 | 25-MAY-18:10 | 29.03 | 19.14 | 0.688051E+10 | 4282.98 | 12-MAY-22:10 | 29.03 | 19.14 |
June | 0.282875E+11 | 13909.44 | 25-JUN-10:35 | 27.43 | 22.06 | 0.685970E+10 | 4406.76 | 23-JUN-22:10 | 27.43 | 22.06 |
July | 0.317317E+11 | 14812.37 | 23-JUL-10:35 | 27.77 | 23.32 | 0.746073E+10 | 4656.49 | 27-JUL-22:10 | 15.32 | 15.25 |
August | 0.338801E+11 | 15447.98 | 31-AUG-21:00 | 22.80 | 20.41 | 0.793062E+10 | 4837.09 | 25-AUG-22:10 | 22.80 | 20.41 |
September | 0.337569E+11 | 17464.80 | 15-SEP-21:00 | 13.30 | 12.05 | 0.782094E+10 | 4837.07 | 01-SEP-21:40 | 13.30 | 12.05 |
October | 0.347544E+11 | 18123.32 | 27-OCT-21:00 | 4.40 | 4.12 | 0.811259E+10 | 4837.06 | 13-OCT-21:19 | 4.40 | 4.12 |
November | 0.324884E+11 | 16951.11 | 17-NOV-22:00 | 2.80 | -0.9 | 0.779380E+10 | 4837.05 | 16-NOV-22:19 | 2.80 | -0.9 |
December | 0.325525E+11 | 19389.06 | 24-DEC-07:51 | -31.1 | -31.3 | 0.753170E+10 | 4836.92 | 08-DEC-22:49 | -31.1 | -31.3 |
Annual Sum or Average | 0.362958E+12 | 0.871592E+11 | ||||||||
Minimum of Months | 0.249831E+11 | 12274.00 | -33.3 | -33.4 | 0.643799E+10 | 4164.13 | -33.3 | -33.4 | ||
Maximum of Months | 0.347544E+11 | 20334.62 | 29.03 | 23.32 | 0.811259E+10 | 4837.09 | 29.03 | 22.06 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291353E+09 | 1791.00 | 27-JAN-13:30 | -15.0 | -16.1 | 0.613056E+09 | 364.17 | 25-JAN-04:00 | -15.0 | -16.1 |
February | 0.792932E+09 | 2995.00 | 28-FEB-13:30 | 3.05 | -0.7 | 0.570838E+09 | 402.57 | 28-FEB-22:19 | -0.2 | -3.1 |
March | 0.118660E+10 | 2943.87 | 20-MAR-12:30 | 1.70 | -1.1 | 0.643744E+09 | 426.51 | 31-MAR-21:19 | 4.83 | 0.87 |
April | 0.216855E+10 | 3427.31 | 13-APR-13:10 | 17.98 | 6.86 | 0.655492E+09 | 491.30 | 13-APR-21:19 | 12.77 | 6.63 |
May | 0.334145E+10 | 3657.60 | 18-MAY-13:00 | 28.20 | 16.75 | 0.750904E+09 | 491.84 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.357033E+10 | 3743.40 | 30-JUN-13:00 | 31.70 | 24.46 | 0.751935E+09 | 491.84 | 15-JUN-21:40 | 31.70 | 24.46 |
July | 0.419132E+10 | 3868.87 | 23-JUL-13:10 | 30.00 | 22.77 | 0.803899E+09 | 491.84 | 07-JUL-21:30 | 30.00 | 22.77 |
August | 0.402420E+10 | 4207.41 | 26-AUG-12:40 | 25.40 | 19.23 | 0.793427E+09 | 491.84 | 04-AUG-21:40 | 25.40 | 19.23 |
September | 0.325336E+10 | 4247.46 | 01-SEP-13:15 | 24.80 | 18.00 | 0.709549E+09 | 491.84 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.212528E+10 | 4649.74 | 22-OCT-12:00 | 16.70 | 12.57 | 0.664690E+09 | 491.82 | 19-OCT-21:19 | 16.70 | 12.57 |
November | 0.810826E+09 | 2865.04 | 17-NOV-12:40 | 9.63 | 3.12 | 0.607354E+09 | 409.62 | 17-NOV-22:19 | 2.43 | -1.1 |
December | 0.202524E+09 | 1410.68 | 24-DEC-11:50 | -27.4 | -27.8 | 0.616375E+09 | 364.30 | 13-DEC-04:30 | -27.4 | -27.8 |
Annual Sum or Average | 0.259587E+11 | 0.818126E+10 | ||||||||
Minimum of Months | 0.202524E+09 | 1410.68 | -27.4 | -27.8 | 0.570838E+09 | 364.17 | -27.4 | -27.8 | ||
Maximum of Months | 0.419132E+10 | 4649.74 | 31.70 | 24.46 | 0.803899E+09 | 491.84 | 31.70 | 24.46 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134166E+10 | 1328.99 | 27-JAN-21:55 | -23.9 | -24.1 | 0.718158E+09 | 458.12 | 19-JAN-23:10 | -23.9 | -24.1 |
February | 0.165136E+10 | 1334.60 | 24-FEB-22:53 | -23.9 | -24.3 | 0.662179E+09 | 488.85 | 22-FEB-23:10 | -23.9 | -24.3 |
March | 0.220072E+10 | 1289.59 | 31-MAR-20:00 | 5.60 | 1.28 | 0.754355E+09 | 510.70 | 31-MAR-22:10 | 4.43 | 0.70 |
April | 0.267489E+10 | 1438.68 | 13-APR-20:00 | 14.40 | 6.82 | 0.775765E+09 | 550.54 | 13-APR-22:10 | 11.52 | 6.37 |
May | 0.323856E+10 | 1715.71 | 25-MAY-20:55 | 22.80 | 16.44 | 0.869096E+09 | 569.55 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.328865E+10 | 1923.15 | 30-JUN-20:10 | 23.77 | 17.76 | 0.859825E+09 | 569.55 | 30-JUN-22:10 | 18.85 | 15.86 |
July | 0.356387E+10 | 1807.98 | 24-JUL-21:00 | 19.40 | 17.92 | 0.911402E+09 | 569.55 | 07-JUL-21:30 | 19.40 | 17.92 |
August | 0.346079E+10 | 1721.25 | 25-AUG-21:00 | 17.80 | 16.38 | 0.905109E+09 | 569.55 | 04-AUG-21:40 | 17.80 | 16.38 |
September | 0.307962E+10 | 1650.33 | 01-SEP-21:00 | 15.00 | 14.30 | 0.835378E+09 | 569.55 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.275508E+10 | 1476.90 | 22-OCT-10:35 | 15.20 | 11.90 | 0.802858E+09 | 556.48 | 20-OCT-22:10 | 15.20 | 11.90 |
November | 0.216062E+10 | 1269.08 | 17-NOV-21:00 | 3.30 | -0.9 | 0.725429E+09 | 505.63 | 17-NOV-23:10 | 1.78 | -1.3 |
December | 0.140681E+10 | 1087.60 | 05-DEC-21:00 | 0.00 | -0.0 | 0.721297E+09 | 460.65 | 05-DEC-23:10 | 0.00 | -0.0 |
Annual Sum or Average | 0.308226E+11 | 0.954085E+10 | ||||||||
Minimum of Months | 0.134166E+10 | 1087.60 | -23.9 | -24.3 | 0.662179E+09 | 458.12 | -23.9 | -24.3 | ||
Maximum of Months | 0.356387E+10 | 1923.15 | 23.77 | 17.92 | 0.911402E+09 | 569.55 | 21.73 | 17.92 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2274894.42 | 14.62 | 19-JAN-21:00 | -3.3 | -3.9 | 0.150887E+09 | 97.53 | 19-JAN-22:10 | -3.9 | -4.6 |
February | 8725810.67 | 16.08 | 21-FEB-21:00 | -1.1 | -2.5 | 0.139243E+09 | 103.06 | 21-FEB-22:10 | -3.0 | -4.4 |
March | 20376816.25 | 18.28 | 31-MAR-20:00 | 5.60 | 1.28 | 0.160377E+09 | 113.11 | 29-MAR-21:10 | 5.60 | 1.28 |
April | 67751575.13 | 551.37 | 23-APR-20:00 | 21.70 | 14.26 | 0.177850E+09 | 120.45 | 13-APR-22:10 | 21.70 | 14.26 |
May | 0.671191E+09 | 1275.06 | 25-MAY-20:00 | 25.00 | 17.45 | 0.202857E+09 | 120.45 | 14-MAY-23:00 | 25.00 | 17.45 |
June | 0.114354E+10 | 1579.50 | 30-JUN-20:00 | 24.40 | 17.93 | 0.199112E+09 | 120.45 | 08-JUN-21:30 | 24.40 | 17.93 |
July | 0.161333E+10 | 1415.96 | 21-JUL-19:55 | 22.20 | 20.61 | 0.205008E+09 | 120.45 | 31-JUL-23:10 | 16.75 | 14.65 |
August | 0.133017E+10 | 1331.79 | 09-AUG-19:55 | 23.30 | 19.93 | 0.205843E+09 | 120.45 | 01-AUG-00:40 | 23.30 | 19.93 |
September | 0.590950E+09 | 1211.25 | 01-SEP-20:00 | 16.70 | 15.32 | 0.197480E+09 | 120.45 | 11-SEP-21:40 | 15.97 | 15.21 |
October | 0.112172E+09 | 602.64 | 22-OCT-20:00 | 8.30 | 6.66 | 0.190432E+09 | 120.45 | 04-OCT-21:10 | 8.30 | 6.66 |
November | 29524969.51 | 19.12 | 01-NOV-20:00 | 13.30 | 11.34 | 0.161044E+09 | 117.67 | 01-NOV-21:10 | 12.62 | 11.43 |
December | 3835179.45 | 14.83 | 05-DEC-21:00 | 0.00 | -0.0 | 0.152055E+09 | 98.48 | 05-DEC-22:10 | 0.00 | -0.0 |
Annual Sum or Average | 0.559384E+10 | 0.214219E+10 | ||||||||
Minimum of Months | 2274894.42 | 14.62 | -3.3 | -3.9 | 0.139243E+09 | 97.53 | -3.9 | -4.6 | ||
Maximum of Months | 0.161333E+10 | 1579.50 | 25.00 | 20.61 | 0.205843E+09 | 120.45 | 25.00 | 19.93 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37949.82 | 18.62 | 19-JAN-22:00 | -3.9 | -4.6 | 0.113741E+09 | 68.58 | 25-JAN-04:00 | -23.9 | -24.1 |
February | 13759267.93 | 213.72 | 21-FEB-21:50 | -2.5 | -4.0 | 0.105045E+09 | 68.58 | 24-FEB-23:40 | -23.9 | -24.2 |
March | 0.120154E+09 | 499.52 | 31-MAR-21:00 | 5.00 | 0.95 | 0.117205E+09 | 68.59 | 16-MAR-01:00 | 5.00 | 0.95 |
April | 0.781603E+09 | 750.90 | 23-APR-18:10 | 25.22 | 16.18 | 0.113610E+09 | 73.27 | 23-APR-23:10 | 14.63 | 10.70 |
May | 0.167662E+10 | 901.25 | 25-MAY-18:10 | 29.03 | 19.14 | 0.124197E+09 | 81.43 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.180059E+10 | 995.10 | 30-JUN-10:35 | 30.73 | 23.70 | 0.125098E+09 | 85.10 | 30-JUN-21:40 | 19.60 | 16.44 |
July | 0.196384E+10 | 981.82 | 23-JUL-10:35 | 27.77 | 23.32 | 0.132991E+09 | 83.22 | 21-JUL-22:10 | 27.77 | 23.32 |
August | 0.188395E+10 | 926.19 | 26-AUG-10:35 | 22.43 | 17.42 | 0.131008E+09 | 82.09 | 09-AUG-22:10 | 22.43 | 17.42 |
September | 0.162987E+10 | 914.07 | 01-SEP-10:35 | 22.77 | 18.04 | 0.119787E+09 | 80.57 | 01-SEP-22:10 | 13.90 | 13.22 |
October | 0.102162E+10 | 809.87 | 22-OCT-10:35 | 15.20 | 11.90 | 0.117872E+09 | 73.72 | 20-OCT-22:10 | 15.20 | 11.90 |
November | 0.219247E+09 | 621.01 | 01-NOV-21:00 | 12.80 | 11.56 | 0.112882E+09 | 69.48 | 01-NOV-22:10 | 11.52 | 10.61 |
December | 616708.07 | 82.57 | 05-DEC-22:00 | 0.00 | -0.0 | 0.115361E+09 | 68.58 | 13-DEC-04:30 | -23.9 | -24.2 |
Annual Sum or Average | 0.111119E+11 | 0.142880E+10 | ||||||||
Minimum of Months | 37949.82 | 18.62 | -3.9 | -4.6 | 0.105045E+09 | 68.58 | -23.9 | -24.2 | ||
Maximum of Months | 0.196384E+10 | 995.10 | 30.73 | 23.70 | 0.132991E+09 | 85.10 | 27.77 | 23.32 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.442435E+11 | 36431.57 | 19-JAN-21:00 | -3.3 | -3.9 | 0.649334E+09 | 381.56 | 14-JAN-05:19 | -3.3 | -3.9 |
February | 0.410475E+11 | 36902.45 | 21-FEB-21:00 | -1.1 | -2.5 | 0.587075E+09 | 381.58 | 28-FEB-23:19 | -0.8 | -3.5 |
March | 0.467720E+11 | 37380.48 | 31-MAR-20:00 | 5.60 | 1.28 | 0.652393E+09 | 381.58 | 28-MAR-21:00 | 5.60 | 1.28 |
April | 0.470896E+11 | 38137.90 | 13-APR-20:00 | 14.40 | 6.82 | 0.629502E+09 | 381.60 | 27-APR-21:10 | -1.9 | -2.9 |
May | 0.507825E+11 | 38948.87 | 18-MAY-20:00 | 21.10 | 14.14 | 0.650710E+09 | 381.62 | 26-MAY-21:10 | 17.13 | 14.19 |
June | 0.499507E+11 | 39193.07 | 28-JUN-20:00 | 25.00 | 19.70 | 0.630871E+09 | 381.64 | 26-JUN-21:10 | 25.00 | 19.70 |
July | 0.518897E+11 | 39049.85 | 21-JUL-20:00 | 22.20 | 20.61 | 0.649343E+09 | 381.67 | 03-JUL-21:10 | 22.20 | 20.61 |
August | 0.516354E+11 | 38967.74 | 08-AUG-20:00 | 25.00 | 20.33 | 0.652092E+09 | 381.69 | 30-AUG-21:10 | 19.32 | 17.13 |
September | 0.487242E+11 | 38753.37 | 01-SEP-20:00 | 16.70 | 15.32 | 0.629196E+09 | 381.63 | 07-SEP-21:10 | 18.80 | 13.65 |
October | 0.487312E+11 | 38148.18 | 19-OCT-20:00 | 13.30 | 10.24 | 0.649647E+09 | 381.58 | 05-OCT-21:10 | 13.30 | 10.24 |
November | 0.455307E+11 | 37509.83 | 01-NOV-20:00 | 13.30 | 11.34 | 0.628135E+09 | 381.59 | 01-NOV-01:10 | 13.30 | 11.34 |
December | 0.444802E+11 | 36519.52 | 05-DEC-21:00 | 0.00 | -0.0 | 0.649336E+09 | 381.57 | 06-DEC-00:30 | 0.00 | -0.0 |
Annual Sum or Average | 0.570877E+12 | 0.765763E+10 | ||||||||
Minimum of Months | 0.410475E+11 | 36431.57 | -3.3 | -3.9 | 0.587075E+09 | 381.56 | -3.3 | -3.9 | ||
Maximum of Months | 0.518897E+11 | 39193.07 | 25.00 | 20.61 | 0.652393E+09 | 381.69 | 25.00 | 20.61 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101003E+11 | 9065.01 | 27-JAN-13:40 | -14.8 | -15.9 | 0.814355E+10 | 5060.92 | 19-JAN-22:40 | -14.8 | -15.9 |
February | 0.126997E+11 | 11307.07 | 28-FEB-13:30 | 3.05 | -0.7 | 0.755699E+10 | 5692.45 | 28-FEB-22:40 | -0.4 | -3.3 |
March | 0.159445E+11 | 10824.44 | 18-MAR-13:20 | -2.0 | -5.8 | 0.858775E+10 | 5803.45 | 31-MAR-21:40 | 4.67 | 0.78 |
April | 0.188820E+11 | 12382.66 | 22-APR-13:20 | 16.67 | 6.95 | 0.868268E+10 | 6239.11 | 13-APR-21:40 | 16.67 | 6.95 |
May | 0.224891E+11 | 11673.03 | 18-MAY-15:23 | 28.70 | 16.46 | 0.946511E+10 | 6449.21 | 25-MAY-21:40 | 22.20 | 16.43 |
June | 0.226642E+11 | 12010.41 | 25-JUN-10:35 | 27.43 | 22.06 | 0.934054E+10 | 6462.76 | 30-JUN-22:10 | 18.85 | 15.86 |
July | 0.246099E+11 | 12509.20 | 29-JUL-13:10 | 28.98 | 20.74 | 0.985173E+10 | 6462.71 | 24-JUL-22:10 | 28.98 | 20.74 |
August | 0.241871E+11 | 13767.45 | 26-AUG-12:40 | 25.40 | 19.23 | 0.987357E+10 | 6462.66 | 08-AUG-22:10 | 25.40 | 19.23 |
September | 0.216252E+11 | 13345.04 | 01-SEP-15:10 | 26.10 | 17.79 | 0.917168E+10 | 6405.07 | 07-SEP-21:40 | 18.50 | 13.52 |
October | 0.188966E+11 | 15778.38 | 22-OCT-12:00 | 16.70 | 12.57 | 0.895890E+10 | 6357.19 | 19-OCT-21:40 | 16.70 | 12.57 |
November | 0.142777E+11 | 11020.57 | 17-NOV-11:40 | 8.17 | 2.57 | 0.817771E+10 | 5724.25 | 17-NOV-22:40 | 2.07 | -1.2 |
December | 0.953553E+10 | 10159.96 | 10-DEC-11:00 | -24.8 | -25.2 | 0.815717E+10 | 5120.90 | 05-DEC-22:40 | -24.8 | -25.2 |
Annual Sum or Average | 0.215912E+12 | 0.105967E+12 | ||||||||
Minimum of Months | 0.953553E+10 | 9065.01 | -24.8 | -25.2 | 0.755699E+10 | 5060.92 | -24.8 | -25.2 | ||
Maximum of Months | 0.246099E+11 | 15778.38 | 28.98 | 22.06 | 0.987357E+10 | 6462.76 | 28.98 | 20.74 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.428823E+11 | 30014.39 | 27-JAN-23:00 | -25.6 | -25.7 | 0.249522E+11 | 16695.89 | 19-JAN-23:10 | -25.6 | -25.7 |
February | 0.452455E+11 | 29891.29 | 24-FEB-22:53 | -23.9 | -24.3 | 0.233689E+11 | 17662.86 | 22-FEB-22:49 | -23.9 | -24.3 |
March | 0.541856E+11 | 28863.73 | 07-MAR-00:53 | -24.4 | -24.6 | 0.269226E+11 | 18256.53 | 31-MAR-22:10 | 4.43 | 0.70 |
April | 0.600371E+11 | 30366.77 | 13-APR-20:00 | 14.40 | 6.82 | 0.275944E+11 | 19183.60 | 13-APR-21:49 | 11.97 | 6.44 |
May | 0.694502E+11 | 35354.79 | 25-MAY-21:10 | 22.65 | 16.44 | 0.302194E+11 | 19186.19 | 15-MAY-22:10 | 22.65 | 16.44 |
June | 0.701131E+11 | 38226.85 | 29-JUN-21:10 | 27.62 | 23.70 | 0.297611E+11 | 19186.26 | 15-JUN-21:40 | 27.62 | 23.70 |
July | 0.751875E+11 | 36815.75 | 24-JUL-21:10 | 19.32 | 17.84 | 0.312245E+11 | 19186.29 | 07-JUL-21:30 | 19.32 | 17.84 |
August | 0.737705E+11 | 36023.71 | 25-AUG-21:10 | 17.62 | 16.26 | 0.312574E+11 | 19186.24 | 04-AUG-21:40 | 17.62 | 16.26 |
September | 0.669444E+11 | 35350.11 | 01-SEP-21:10 | 14.82 | 14.12 | 0.293251E+11 | 19186.04 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.622641E+11 | 32978.72 | 22-OCT-10:35 | 15.20 | 11.90 | 0.287295E+11 | 19184.39 | 19-OCT-21:19 | 15.20 | 11.90 |
November | 0.524295E+11 | 27696.15 | 17-NOV-21:00 | 3.30 | -0.9 | 0.260618E+11 | 18240.06 | 17-NOV-22:49 | 1.88 | -1.3 |
December | 0.430353E+11 | 27875.99 | 02-DEC-00:33 | -23.9 | -24.2 | 0.251751E+11 | 16805.41 | 05-DEC-23:10 | 0.00 | -0.0 |
Annual Sum or Average | 0.715545E+12 | 0.334592E+12 | ||||||||
Minimum of Months | 0.428823E+11 | 27696.15 | -25.6 | -25.7 | 0.233689E+11 | 16695.89 | -25.6 | -25.7 | ||
Maximum of Months | 0.751875E+11 | 38226.85 | 27.62 | 23.70 | 0.312574E+11 | 19186.29 | 27.62 | 23.70 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1674295.19 | 608.90 | 25-JAN-16:13 | -18.2 | -19.0 | 91803512.82 | 56.69 | 14-JAN-05:10 | -18.2 | -19.0 |
February | 33021038.24 | 3825.62 | 28-FEB-16:11 | 5.93 | 1.38 | 84208884.40 | 56.69 | 18-FEB-00:20 | 5.93 | 1.38 |
March | 0.128189E+09 | 3874.24 | 26-MAR-15:11 | 10.77 | 5.35 | 94410012.64 | 56.69 | 31-MAR-21:19 | 4.83 | 0.87 |
April | 0.497894E+09 | 3954.64 | 13-APR-15:11 | 20.00 | 8.11 | 93444338.88 | 56.69 | 13-APR-22:19 | 11.33 | 6.36 |
May | 0.139397E+10 | 3984.32 | 04-MAY-15:11 | 20.87 | 10.63 | 98951990.23 | 56.70 | 25-MAY-23:49 | 20.15 | 16.15 |
June | 0.170700E+10 | 3959.49 | 16-JUN-18:01 | 20.50 | 11.25 | 96015199.45 | 56.70 | 30-JUN-02:49 | 25.78 | 23.29 |
July | 0.218818E+10 | 3431.02 | 04-JUL-18:01 | 22.62 | 19.34 | 99362672.30 | 56.70 | 22-JUL-23:10 | 22.20 | 21.15 |
August | 0.174569E+10 | 3450.49 | 22-AUG-18:01 | 21.32 | 17.34 | 99181834.60 | 56.70 | 23-AUG-21:49 | 18.35 | 16.70 |
September | 0.887141E+09 | 3910.91 | 09-SEP-18:01 | 15.37 | 9.79 | 95076971.35 | 56.69 | 01-SEP-21:30 | 15.37 | 9.79 |
October | 0.255158E+09 | 3795.55 | 09-OCT-15:11 | 6.70 | 1.60 | 95617096.74 | 56.69 | 19-OCT-21:19 | 12.60 | 9.81 |
November | 11556836.44 | 3758.15 | 17-NOV-16:11 | 8.90 | 2.59 | 90255690.19 | 56.69 | 01-NOV-02:39 | 8.90 | 2.59 |
December | 744073.30 | 73.42 | 02-DEC-14:00 | -18.1 | -18.9 | 91848245.89 | 56.69 | 12-DEC-05:19 | -12.0 | -12.4 |
Annual Sum or Average | 0.885022E+10 | 0.113018E+10 | ||||||||
Minimum of Months | 744073.30 | 73.42 | -18.2 | -19.0 | 84208884.40 | 56.69 | -18.2 | -19.0 | ||
Maximum of Months | 0.218818E+10 | 3984.32 | 22.62 | 19.34 | 99362672.30 | 56.70 | 25.78 | 23.29 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67486.04 | 419.84 | 17-JAN-16:15 | -4.5 | -5.5 | 91186113.42 | 56.69 | 07-JAN-05:00 | -4.5 | -5.5 |
February | 5614458.50 | 2929.45 | 20-FEB-16:11 | 8.33 | 2.67 | 83327955.66 | 56.69 | 03-FEB-05:10 | 8.33 | 2.67 |
March | 50190614.18 | 3646.61 | 28-MAR-18:01 | 6.93 | 2.56 | 93235493.80 | 56.69 | 06-MAR-03:30 | 6.93 | 2.56 |
April | 0.266384E+09 | 4231.55 | 11-APR-18:11 | 13.90 | 5.53 | 93488362.55 | 68.17 | 11-APR-18:10 | 13.90 | 5.53 |
May | 0.100005E+10 | 4328.18 | 06-MAY-19:01 | 14.13 | 6.69 | 0.104677E+09 | 86.19 | 04-MAY-18:10 | 14.13 | 6.69 |
June | 0.130159E+10 | 3635.66 | 08-JUN-21:51 | 16.70 | 13.06 | 0.104885E+09 | 89.14 | 15-JUN-18:10 | 21.23 | 13.09 |
July | 0.165576E+10 | 3734.64 | 07-JUL-21:11 | 11.13 | 10.27 | 0.109925E+09 | 96.53 | 06-JUL-18:10 | 11.13 | 10.27 |
August | 0.118517E+10 | 3885.58 | 07-AUG-16:21 | 24.15 | 19.94 | 0.108136E+09 | 91.38 | 02-AUG-18:10 | 24.15 | 19.94 |
September | 0.483926E+09 | 4197.92 | 04-SEP-18:01 | 14.03 | 8.92 | 97969613.17 | 80.88 | 05-SEP-18:10 | 14.77 | 9.16 |
October | 82288230.23 | 2784.66 | 22-OCT-18:01 | 12.75 | 9.22 | 95105859.32 | 56.69 | 19-OCT-21:19 | 12.75 | 9.22 |
November | 4662166.44 | 1135.37 | 17-NOV-16:11 | 8.90 | 2.59 | 89495042.95 | 56.69 | 01-NOV-03:20 | 8.90 | 2.59 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -8.8 | -9.9 | 91603785.24 | 56.69 | 27-DEC-05:00 | -9.4 | -10.1 |
Annual Sum or Average | 0.603570E+10 | 0.116303E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -8.8 | -9.9 | 83327955.66 | 56.69 | -9.4 | -10.1 | ||
Maximum of Months | 0.165576E+10 | 4328.18 | 24.15 | 19.94 | 0.109925E+09 | 96.53 | 24.15 | 19.94 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2931564.55 | 185.10 | 05-JAN-15:05 | -26.2 | -26.6 | 0.00 | 0.00 | 01-JAN-00:10 | -26.2 | -26.6 |
February | 4883018.94 | 110.05 | 22-FEB-15:20 | -0.6 | -3.8 | 0.00 | 0.00 | 01-FEB-00:10 | -0.6 | -3.8 |
March | 12552159.48 | 219.34 | 31-MAR-14:20 | 8.30 | 2.95 | 0.00 | 0.00 | 01-MAR-00:10 | 8.30 | 2.95 |
April | 0.152451E+09 | 522.89 | 22-APR-13:25 | 16.95 | 7.09 | 0.00 | 0.00 | 01-APR-00:10 | 16.95 | 7.09 |
May | 0.341150E+09 | 547.58 | 18-MAY-13:05 | 28.25 | 16.75 | 0.00 | 0.00 | 01-MAY-00:10 | 28.25 | 16.75 |
June | 0.407658E+09 | 541.91 | 30-JUN-13:00 | 31.70 | 24.46 | 0.00 | 0.00 | 01-JUN-00:10 | 31.70 | 24.46 |
July | 0.535418E+09 | 575.12 | 23-JUL-13:20 | 30.00 | 22.71 | 0.00 | 0.00 | 01-JUL-00:10 | 30.00 | 22.71 |
August | 0.498477E+09 | 638.32 | 25-AUG-13:05 | 27.38 | 18.58 | 0.00 | 0.00 | 01-AUG-00:10 | 27.38 | 18.58 |
September | 0.337600E+09 | 646.36 | 01-SEP-13:20 | 24.80 | 18.00 | 0.00 | 0.00 | 01-SEP-00:10 | 24.80 | 18.00 |
October | 0.148890E+09 | 770.02 | 22-OCT-12:30 | 17.50 | 12.84 | 0.00 | 0.00 | 01-OCT-00:10 | 17.50 | 12.84 |
November | 7464036.58 | 139.17 | 17-NOV-15:15 | 10.40 | 3.35 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 3.35 |
December | 1093129.30 | 58.89 | 02-DEC-15:20 | -17.6 | -18.4 | 0.00 | 0.00 | 01-DEC-00:10 | -17.6 | -18.4 |
Annual Sum or Average | 0.245057E+10 | 0.00 | ||||||||
Minimum of Months | 1093129.30 | 58.89 | -26.2 | -26.6 | 0.00 | 0.00 | -26.2 | -26.6 | ||
Maximum of Months | 0.535418E+09 | 770.02 | 31.70 | 24.46 | 0.00 | 0.00 | 31.70 | 24.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1648350.01 | 225.69 | 19-JAN-19:05 | -3.3 | -3.9 | 89747681.46 | 56.69 | 29-JAN-00:20 | -7.8 | -8.5 |
February | 3657086.56 | 241.97 | 04-FEB-19:04 | 4.22 | 0.37 | 83735600.85 | 56.69 | 01-FEB-00:20 | 4.22 | 0.37 |
March | 18232567.30 | 947.80 | 28-MAR-18:01 | 6.93 | 2.56 | 94127730.20 | 56.69 | 29-MAR-21:10 | 1.60 | 0.74 |
April | 0.131058E+09 | 1016.67 | 18-APR-18:01 | 9.82 | 3.25 | 93115299.12 | 56.69 | 13-APR-21:49 | 9.82 | 3.25 |
May | 0.459624E+09 | 1081.75 | 21-MAY-21:01 | 13.12 | 7.18 | 0.101008E+09 | 74.99 | 26-MAY-21:49 | 16.87 | 14.10 |
June | 0.584756E+09 | 1087.04 | 07-JUN-08:51 | 21.10 | 11.94 | 0.100567E+09 | 77.33 | 15-JUN-21:10 | 14.22 | 10.92 |
July | 0.647198E+09 | 1028.44 | 01-JUL-21:01 | 12.93 | 11.86 | 0.104724E+09 | 78.04 | 06-JUL-21:40 | 17.23 | 14.08 |
August | 0.523692E+09 | 1011.02 | 01-AUG-21:11 | 15.37 | 12.90 | 0.103730E+09 | 76.21 | 01-AUG-21:10 | 15.37 | 12.90 |
September | 0.333368E+09 | 1077.26 | 04-SEP-18:01 | 14.03 | 8.92 | 95766351.57 | 73.45 | 01-SEP-21:10 | 14.03 | 8.92 |
October | 0.124262E+09 | 973.13 | 20-OCT-18:12 | 12.23 | 7.41 | 95959129.77 | 56.69 | 04-OCT-21:19 | 12.23 | 7.41 |
November | 22213546.71 | 729.23 | 01-NOV-18:03 | 12.02 | 10.48 | 91198608.18 | 56.69 | 01-NOV-21:19 | 12.43 | 11.31 |
December | 1585253.84 | 163.48 | 05-DEC-19:05 | 0.00 | -0.0 | 90969876.82 | 56.69 | 12-DEC-00:20 | -14.8 | -15.5 |
Annual Sum or Average | 0.285130E+10 | 0.114465E+10 | ||||||||
Minimum of Months | 1585253.84 | 163.48 | -3.3 | -3.9 | 83735600.85 | 56.69 | -14.8 | -15.5 | ||
Maximum of Months | 0.647198E+09 | 1087.04 | 21.10 | 12.90 | 0.104724E+09 | 78.04 | 17.23 | 14.10 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1387631.93 | 76.30 | 20-JAN-16:16 | -6.1 | -7.6 | 91521534.74 | 56.69 | 29-JAN-00:20 | -7.8 | -8.5 |
February | 16359412.41 | 3245.62 | 28-FEB-16:11 | 5.93 | 1.38 | 84129425.65 | 56.69 | 03-FEB-04:30 | 5.93 | 1.38 |
March | 86487805.61 | 3481.99 | 31-MAR-15:11 | 8.50 | 3.01 | 94621759.50 | 56.69 | 06-MAR-04:40 | 8.50 | 3.01 |
April | 0.507389E+09 | 3564.47 | 13-APR-15:11 | 20.00 | 8.11 | 93995879.49 | 56.69 | 14-APR-21:10 | 8.72 | 5.04 |
May | 0.130933E+10 | 3590.06 | 03-MAY-15:11 | 21.03 | 10.41 | 99236517.69 | 56.69 | 25-MAY-21:00 | 21.90 | 16.42 |
June | 0.181335E+10 | 3570.30 | 16-JUN-18:01 | 20.50 | 11.25 | 96243556.99 | 56.69 | 30-JUN-01:49 | 26.70 | 23.80 |
July | 0.218445E+10 | 3285.22 | 29-JUL-08:61 | 24.18 | 20.45 | 99482784.28 | 56.69 | 03-JUL-21:40 | 24.18 | 20.45 |
August | 0.167863E+10 | 3173.04 | 26-AUG-08:61 | 19.68 | 15.96 | 99353406.83 | 56.69 | 23-AUG-21:00 | 19.68 | 15.96 |
September | 0.864958E+09 | 3496.47 | 05-SEP-18:01 | 14.77 | 9.16 | 95159785.39 | 56.69 | 01-SEP-21:10 | 14.77 | 9.16 |
October | 0.231616E+09 | 3409.99 | 21-OCT-18:01 | 14.35 | 8.39 | 95612786.88 | 56.69 | 19-OCT-21:19 | 14.35 | 8.39 |
November | 22946202.65 | 2527.66 | 17-NOV-16:11 | 8.90 | 2.59 | 90187466.95 | 56.69 | 01-NOV-03:09 | 8.90 | 2.59 |
December | 580560.69 | 581.94 | 28-DEC-09:05 | -3.8 | -4.7 | 91759143.69 | 56.69 | 27-DEC-03:20 | -3.8 | -4.7 |
Annual Sum or Average | 0.871749E+10 | 0.113130E+10 | ||||||||
Minimum of Months | 580560.69 | 76.30 | -6.1 | -7.6 | 84129425.65 | 56.69 | -7.8 | -8.5 | ||
Maximum of Months | 0.218445E+10 | 3590.06 | 24.18 | 20.45 | 99482784.28 | 56.69 | 26.70 | 23.80 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -21.9 | -22.1 | 90744257.53 | 56.69 | 08-JAN-03:30 | -22.5 | -22.7 |
February | 1540719.08 | 659.75 | 27-FEB-09:03 | -15.7 | -16.5 | 83171676.93 | 56.69 | 20-FEB-04:40 | -15.7 | -16.5 |
March | 25215315.30 | 3102.37 | 26-MAR-08:61 | -0.9 | -2.8 | 93264190.99 | 56.69 | 07-MAR-05:30 | -0.9 | -2.8 |
April | 0.273229E+09 | 3377.28 | 21-APR-08:61 | 3.77 | -1.2 | 93611742.65 | 56.69 | 13-APR-21:40 | 3.77 | -1.2 |
May | 0.966205E+09 | 3451.42 | 27-MAY-08:51 | 20.60 | 13.60 | 0.102740E+09 | 75.01 | 18-MAY-21:40 | 20.60 | 13.60 |
June | 0.143102E+10 | 3591.11 | 28-JUN-08:61 | 25.37 | 20.52 | 0.102979E+09 | 78.05 | 27-JUN-21:10 | 25.37 | 20.52 |
July | 0.165934E+10 | 3745.19 | 31-JUL-08:32 | 18.70 | 13.63 | 0.108039E+09 | 78.57 | 26-JUL-21:10 | 18.70 | 13.63 |
August | 0.116716E+10 | 3552.98 | 20-AUG-08:51 | 20.60 | 15.45 | 0.105775E+09 | 75.58 | 04-AUG-21:10 | 20.60 | 15.45 |
September | 0.508750E+09 | 3490.56 | 04-SEP-18:01 | 14.03 | 8.92 | 96616394.00 | 73.45 | 01-SEP-21:10 | 14.03 | 8.92 |
October | 74369900.94 | 3109.79 | 09-OCT-08:62 | -1.1 | -2.3 | 94849397.74 | 56.69 | 19-OCT-21:19 | 12.60 | 9.81 |
November | 4413307.00 | 764.83 | 17-NOV-09:03 | 0.05 | -2.1 | 89486955.85 | 56.69 | 01-NOV-03:39 | 0.05 | -2.1 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -8.8 | -9.9 | 91394250.60 | 56.69 | 30-DEC-04:49 | -5.5 | -6.2 |
Annual Sum or Average | 0.611124E+10 | 0.115267E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -21.9 | -22.1 | 83171676.93 | 56.69 | -22.5 | -22.7 | ||
Maximum of Months | 0.165934E+10 | 3745.19 | 25.37 | 20.52 | 0.108039E+09 | 78.57 | 25.37 | 20.52 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 68404305.54 | 563.85 | 19-JAN-22:10 | -3.9 | -4.6 | 0.119499E+10 | 704.57 | 25-JAN-05:00 | -24.4 | -24.6 |
February | 0.500835E+09 | 1191.91 | 28-FEB-17:20 | 5.03 | 0.71 | 0.108376E+10 | 707.03 | 28-FEB-22:40 | -0.4 | -3.3 |
March | 0.128872E+10 | 1463.00 | 29-MAR-10:35 | 1.13 | -1.2 | 0.120783E+10 | 734.91 | 31-MAR-21:49 | 4.58 | 0.73 |
April | 0.279178E+10 | 1790.70 | 22-APR-10:35 | 14.43 | 5.29 | 0.121361E+10 | 817.94 | 23-APR-23:30 | 13.90 | 10.20 |
May | 0.403185E+10 | 2066.99 | 25-MAY-18:10 | 29.03 | 19.14 | 0.139379E+10 | 903.85 | 25-MAY-21:49 | 22.05 | 16.43 |
June | 0.423350E+10 | 2377.95 | 30-JUN-18:40 | 28.53 | 19.44 | 0.141499E+10 | 951.85 | 30-JUN-22:10 | 18.85 | 15.86 |
July | 0.467594E+10 | 2259.28 | 23-JUL-10:35 | 27.77 | 23.32 | 0.152425E+10 | 948.26 | 24-JUL-21:49 | 18.98 | 17.52 |
August | 0.440288E+10 | 2141.04 | 26-AUG-10:35 | 22.43 | 17.42 | 0.147621E+10 | 915.00 | 01-AUG-21:00 | 22.43 | 17.42 |
September | 0.374888E+10 | 2077.56 | 01-SEP-10:35 | 22.77 | 18.04 | 0.131964E+10 | 899.74 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.255125E+10 | 1822.99 | 22-OCT-10:35 | 15.20 | 11.90 | 0.123516E+10 | 801.50 | 22-OCT-23:40 | 6.30 | 5.02 |
November | 0.970787E+09 | 1382.25 | 17-NOV-11:40 | 8.17 | 2.57 | 0.115995E+10 | 718.45 | 01-NOV-22:10 | 8.17 | 2.57 |
December | 68860037.50 | 643.10 | 05-DEC-22:10 | 0.00 | -0.0 | 0.119751E+10 | 704.55 | 14-DEC-05:49 | -23.8 | -24.1 |
Annual Sum or Average | 0.293337E+11 | 0.154217E+11 | ||||||||
Minimum of Months | 68404305.54 | 563.85 | -3.9 | -4.6 | 0.108376E+10 | 704.55 | -24.4 | -24.6 | ||
Maximum of Months | 0.467594E+10 | 2377.95 | 29.03 | 23.32 | 0.152425E+10 | 951.85 | 22.43 | 17.52 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 462164.99 | 680.34 | 27-JAN-16:13 | -15.2 | -16.2 | 91304401.37 | 56.69 | 07-JAN-05:30 | -15.2 | -16.2 |
February | 30699949.66 | 3970.00 | 28-FEB-16:11 | 5.93 | 1.38 | 83852129.07 | 56.69 | 01-FEB-00:20 | 5.93 | 1.38 |
March | 0.130442E+09 | 4022.34 | 26-MAR-15:11 | 10.77 | 5.35 | 94012028.31 | 56.69 | 03-MAR-00:20 | 10.77 | 5.35 |
April | 0.504642E+09 | 4114.50 | 13-APR-15:11 | 20.00 | 8.11 | 93035705.21 | 56.69 | 23-APR-03:39 | 10.20 | 3.86 |
May | 0.140872E+10 | 4149.62 | 04-MAY-15:11 | 20.87 | 10.63 | 98806698.91 | 56.70 | 22-MAY-03:20 | 7.00 | 4.08 |
June | 0.172255E+10 | 4118.12 | 16-JUN-18:01 | 20.50 | 11.25 | 95918402.86 | 56.70 | 30-JUN-01:19 | 26.70 | 23.80 |
July | 0.219137E+10 | 3599.68 | 20-JUL-18:02 | 27.62 | 20.32 | 99268405.55 | 56.70 | 19-JUL-21:00 | 27.62 | 20.32 |
August | 0.172140E+10 | 3601.46 | 14-AUG-18:01 | 21.42 | 17.78 | 99032198.27 | 56.70 | 09-AUG-21:30 | 21.42 | 17.78 |
September | 0.820336E+09 | 4097.74 | 04-SEP-18:01 | 14.03 | 8.92 | 94811147.92 | 56.69 | 01-SEP-21:10 | 14.03 | 8.92 |
October | 0.237335E+09 | 3938.74 | 09-OCT-15:11 | 6.70 | 1.60 | 95113880.62 | 56.69 | 18-OCT-22:19 | 8.90 | 6.97 |
November | 9021746.91 | 3918.90 | 17-NOV-16:11 | 8.90 | 2.59 | 89812221.88 | 56.69 | 01-NOV-04:49 | 8.90 | 2.59 |
December | 197602.73 | 61.59 | 02-DEC-14:00 | -18.1 | -18.9 | 91631595.29 | 56.69 | 27-DEC-05:00 | -9.4 | -10.1 |
Annual Sum or Average | 0.877718E+10 | 0.112660E+10 | ||||||||
Minimum of Months | 197602.73 | 61.59 | -18.1 | -18.9 | 83852129.07 | 56.69 | -15.2 | -16.2 | ||
Maximum of Months | 0.219137E+10 | 4149.62 | 27.62 | 20.32 | 99268405.55 | 56.70 | 27.62 | 23.80 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5959.96 | 59.60 | 17-JAN-16:15 | -4.5 | -5.5 | 90362601.96 | 56.69 | 29-JAN-00:20 | -7.8 | -8.5 |
February | 3201357.34 | 1639.94 | 08-FEB-16:11 | 4.03 | -1.1 | 83117195.82 | 56.69 | 03-FEB-00:20 | 4.03 | -1.1 |
March | 47979318.11 | 3779.68 | 28-MAR-18:01 | 6.93 | 2.56 | 92968774.87 | 56.69 | 14-MAR-03:20 | 6.93 | 2.56 |
April | 0.262574E+09 | 4503.38 | 11-APR-18:11 | 13.90 | 5.53 | 93239072.38 | 74.27 | 17-APR-18:10 | 15.63 | 7.70 |
May | 0.102067E+10 | 4855.31 | 06-MAY-18:42 | 14.68 | 6.91 | 0.105561E+09 | 93.98 | 04-MAY-18:10 | 14.68 | 6.91 |
June | 0.135159E+10 | 3921.70 | 20-JUN-21:51 | 13.90 | 11.62 | 0.106097E+09 | 96.99 | 20-JUN-21:10 | 13.90 | 11.62 |
July | 0.171035E+10 | 3930.13 | 26-JUL-21:11 | 12.77 | 11.83 | 0.110896E+09 | 104.85 | 06-JUL-20:10 | 12.77 | 11.83 |
August | 0.119327E+10 | 4048.36 | 07-AUG-16:21 | 24.15 | 19.94 | 0.109049E+09 | 96.95 | 02-AUG-18:10 | 24.15 | 19.94 |
September | 0.420117E+09 | 4394.96 | 04-SEP-18:01 | 14.03 | 8.92 | 98060068.31 | 86.57 | 05-SEP-18:10 | 14.77 | 9.16 |
October | 67443173.50 | 2894.14 | 22-OCT-18:01 | 12.75 | 9.22 | 94579940.63 | 56.69 | 22-OCT-04:10 | 12.75 | 9.22 |
November | 2474059.25 | 851.58 | 09-NOV-16:13 | 0.53 | -4.0 | 89206822.57 | 56.69 | 24-NOV-04:19 | -10.9 | -11.5 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -8.8 | -9.9 | 91166622.33 | 56.69 | 04-DEC-04:40 | -9.2 | -9.6 |
Annual Sum or Average | 0.607968E+10 | 0.116430E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -8.8 | -9.9 | 83117195.82 | 56.69 | -10.9 | -11.5 | ||
Maximum of Months | 0.171035E+10 | 4855.31 | 24.15 | 19.94 | 0.110896E+09 | 104.85 | 24.15 | 19.94 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43950835.53 | 2220.41 | 27-JAN-16:11 | -15.2 | -16.2 | 93495914.68 | 56.69 | 01-JAN-00:30 | -15.2 | -16.2 |
February | 0.138586E+09 | 2254.04 | 28-FEB-16:11 | 5.93 | 1.38 | 86085104.58 | 56.69 | 28-FEB-22:19 | -0.2 | -3.1 |
March | 0.205428E+09 | 2265.92 | 23-MAR-15:11 | 0.77 | -4.0 | 95955054.74 | 56.69 | 29-MAR-21:19 | 1.50 | 0.53 |
April | 0.421720E+09 | 2302.20 | 13-APR-15:11 | 20.00 | 8.11 | 94220056.81 | 56.69 | 13-APR-21:30 | 12.50 | 6.57 |
May | 0.815531E+09 | 2278.19 | 14-MAY-15:11 | 20.00 | 8.29 | 98995975.04 | 56.69 | 24-MAY-21:00 | 18.20 | 13.12 |
June | 0.949752E+09 | 2261.19 | 16-JUN-18:01 | 20.50 | 11.25 | 95944348.67 | 56.69 | 28-JUN-22:00 | 22.20 | 18.51 |
July | 0.119654E+10 | 1998.04 | 01-JUL-18:01 | 20.82 | 15.66 | 99240688.24 | 56.69 | 12-JUL-21:49 | 20.68 | 17.35 |
August | 0.109327E+10 | 2004.49 | 07-AUG-15:12 | 23.13 | 19.60 | 99125403.40 | 56.69 | 29-AUG-21:30 | 18.05 | 17.29 |
September | 0.726999E+09 | 2230.06 | 05-SEP-18:01 | 14.77 | 9.16 | 95317165.59 | 56.69 | 01-SEP-22:10 | 14.77 | 9.16 |
October | 0.376408E+09 | 2244.48 | 09-OCT-15:11 | 6.70 | 1.60 | 96505856.89 | 56.69 | 19-OCT-21:30 | 12.50 | 9.82 |
November | 99675145.76 | 2230.58 | 17-NOV-16:11 | 8.90 | 2.59 | 91720352.98 | 56.69 | 17-NOV-22:19 | 2.43 | -1.1 |
December | 22174646.43 | 2107.18 | 02-DEC-16:12 | -18.9 | -19.5 | 93062207.82 | 56.69 | 22-DEC-00:20 | -14.6 | -15.3 |
Annual Sum or Average | 0.609003E+10 | 0.113967E+10 | ||||||||
Minimum of Months | 22174646.43 | 1998.04 | -18.9 | -19.5 | 86085104.58 | 56.69 | -15.2 | -16.2 | ||
Maximum of Months | 0.119654E+10 | 2302.20 | 23.13 | 19.60 | 99240688.24 | 56.69 | 22.20 | 18.51 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296381E+11 | 17992.52 | 27-JAN-22:40 | -25.0 | -25.2 | 0.150370E+11 | 10474.08 | 19-JAN-23:10 | -25.0 | -25.2 |
February | 0.286469E+11 | 19292.95 | 24-FEB-22:53 | -23.9 | -24.3 | 0.139926E+11 | 10592.51 | 21-FEB-22:40 | -23.9 | -24.3 |
March | 0.340320E+11 | 17868.63 | 07-MAR-00:53 | -24.4 | -24.6 | 0.160719E+11 | 10900.18 | 31-MAR-22:10 | 4.43 | 0.70 |
April | 0.367534E+11 | 18019.94 | 13-APR-21:00 | 13.30 | 6.73 | 0.162202E+11 | 11342.40 | 13-APR-22:10 | 11.52 | 6.37 |
May | 0.425786E+11 | 20783.11 | 25-MAY-21:52 | 21.90 | 16.42 | 0.176886E+11 | 11349.16 | 15-MAY-22:10 | 21.90 | 16.42 |
June | 0.430810E+11 | 21634.31 | 29-JUN-22:00 | 26.70 | 23.36 | 0.174482E+11 | 11349.22 | 01-JUN-21:19 | 26.70 | 23.36 |
July | 0.451827E+11 | 21021.36 | 21-JUL-21:52 | 21.70 | 20.13 | 0.180349E+11 | 11349.21 | 26-JUL-21:30 | 12.50 | 11.71 |
August | 0.439708E+11 | 20678.41 | 08-AUG-21:10 | 22.62 | 18.95 | 0.179746E+11 | 11349.20 | 04-AUG-21:40 | 22.62 | 18.95 |
September | 0.399890E+11 | 20267.60 | 01-SEP-21:10 | 14.82 | 14.12 | 0.169143E+11 | 11348.91 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.377662E+11 | 17824.33 | 19-OCT-21:00 | 12.80 | 9.78 | 0.167655E+11 | 11258.31 | 19-OCT-22:10 | 12.20 | 9.87 |
November | 0.332248E+11 | 17291.57 | 01-NOV-22:10 | 11.52 | 10.61 | 0.156082E+11 | 11057.79 | 01-NOV-22:10 | 11.52 | 10.61 |
December | 0.301475E+11 | 17601.00 | 23-DEC-21:43 | -23.9 | -24.3 | 0.152700E+11 | 10550.39 | 05-DEC-23:10 | -23.9 | -24.3 |
Annual Sum or Average | 0.445011E+12 | 0.197026E+12 | ||||||||
Minimum of Months | 0.286469E+11 | 17291.57 | -25.0 | -25.2 | 0.139926E+11 | 10474.08 | -25.0 | -25.2 | ||
Maximum of Months | 0.451827E+11 | 21634.31 | 26.70 | 23.36 | 0.180349E+11 | 11349.22 | 26.70 | 23.36 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324612E+11 | 19325.94 | 27-JAN-23:20 | -26.3 | -26.5 | 0.153942E+11 | 10873.33 | 19-JAN-23:10 | -26.3 | -26.5 |
February | 0.311159E+11 | 20050.17 | 24-FEB-22:53 | -23.9 | -24.3 | 0.144084E+11 | 11004.07 | 21-FEB-23:10 | -23.9 | -24.3 |
March | 0.366779E+11 | 18591.86 | 07-MAR-00:53 | -24.4 | -24.6 | 0.166370E+11 | 11308.39 | 31-MAR-22:10 | 4.43 | 0.70 |
April | 0.389646E+11 | 20059.87 | 13-APR-21:10 | 13.03 | 6.68 | 0.168028E+11 | 11344.62 | 13-APR-22:30 | 11.15 | 6.35 |
May | 0.444428E+11 | 22188.12 | 25-MAY-21:52 | 21.90 | 16.42 | 0.181336E+11 | 11349.16 | 15-MAY-22:10 | 21.90 | 16.42 |
June | 0.448289E+11 | 23040.30 | 29-JUN-22:00 | 26.70 | 23.36 | 0.178290E+11 | 11349.19 | 07-JUN-21:00 | 26.70 | 23.36 |
July | 0.469313E+11 | 22435.70 | 21-JUL-21:52 | 21.70 | 20.13 | 0.184168E+11 | 11349.19 | 26-JUL-21:30 | 12.50 | 11.71 |
August | 0.456837E+11 | 21886.29 | 08-AUG-21:52 | 21.70 | 18.33 | 0.183677E+11 | 11349.20 | 04-AUG-21:40 | 21.70 | 18.33 |
September | 0.417723E+11 | 20787.35 | 01-SEP-21:22 | 14.45 | 13.76 | 0.173627E+11 | 11348.90 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.400734E+11 | 19477.92 | 19-OCT-21:10 | 12.70 | 9.80 | 0.173931E+11 | 11344.53 | 20-OCT-23:10 | 7.20 | 5.59 |
November | 0.358417E+11 | 18576.77 | 01-NOV-21:10 | 12.62 | 11.43 | 0.162010E+11 | 11343.83 | 01-NOV-22:19 | 11.33 | 10.43 |
December | 0.329984E+11 | 18388.95 | 23-DEC-21:43 | -23.9 | -24.3 | 0.156620E+11 | 10952.10 | 05-DEC-23:10 | -23.9 | -24.3 |
Annual Sum or Average | 0.471792E+12 | 0.202608E+12 | ||||||||
Minimum of Months | 0.311159E+11 | 18388.95 | -26.3 | -26.5 | 0.144084E+11 | 10873.33 | -26.3 | -26.5 | ||
Maximum of Months | 0.469313E+11 | 23040.30 | 26.70 | 23.36 | 0.184168E+11 | 11349.20 | 26.70 | 23.36 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.417310E+11 | 24147.37 | 29-JAN-11:50 | -2.0 | -2.9 | 0.188360E+11 | 11319.71 | 07-JAN-18:10 | -2.0 | -2.9 |
February | 0.396738E+11 | 25679.83 | 22-FEB-11:40 | -2.2 | -4.8 | 0.170326E+11 | 11319.69 | 25-FEB-18:10 | -12.2 | -13.9 |
March | 0.462233E+11 | 27382.25 | 26-MAR-10:50 | 4.13 | 1.31 | 0.188736E+11 | 11319.65 | 04-MAR-18:10 | 4.13 | 1.31 |
April | 0.482781E+11 | 28860.01 | 22-APR-10:40 | 14.43 | 5.29 | 0.182622E+11 | 11319.65 | 22-APR-17:10 | 18.12 | 7.76 |
May | 0.536185E+11 | 29800.61 | 18-MAY-10:50 | 26.28 | 16.46 | 0.188716E+11 | 11319.69 | 20-MAY-17:10 | 13.47 | 7.89 |
June | 0.536672E+11 | 30483.73 | 25-JUN-10:40 | 27.43 | 22.06 | 0.182660E+11 | 11319.68 | 24-JUN-17:10 | 27.43 | 22.06 |
July | 0.560873E+11 | 30544.14 | 23-JUL-10:40 | 27.77 | 23.32 | 0.188681E+11 | 11319.67 | 29-JUL-17:10 | 29.72 | 21.17 |
August | 0.548107E+11 | 29882.84 | 20-AUG-10:35 | 23.53 | 15.84 | 0.188753E+11 | 11319.69 | 12-AUG-17:10 | 23.53 | 15.84 |
September | 0.506862E+11 | 29604.70 | 01-SEP-10:40 | 22.77 | 18.04 | 0.182615E+11 | 11319.68 | 09-SEP-17:10 | 17.02 | 10.38 |
October | 0.490296E+11 | 28407.06 | 22-OCT-10:40 | 15.20 | 11.90 | 0.188688E+11 | 11319.57 | 21-OCT-17:10 | 15.20 | 11.90 |
November | 0.443672E+11 | 25747.61 | 01-NOV-18:07 | 12.02 | 10.48 | 0.182586E+11 | 11319.68 | 25-NOV-18:10 | -15.0 | -15.5 |
December | 0.420429E+11 | 24480.93 | 28-DEC-11:40 | -1.9 | -3.4 | 0.188486E+11 | 11319.71 | 02-DEC-18:10 | -1.9 | -3.4 |
Annual Sum or Average | 0.580216E+12 | 0.222123E+12 | ||||||||
Minimum of Months | 0.396738E+11 | 24147.37 | -2.2 | -4.8 | 0.170326E+11 | 11319.57 | -15.0 | -15.5 | ||
Maximum of Months | 0.560873E+11 | 30544.14 | 27.77 | 23.32 | 0.188753E+11 | 11319.71 | 29.72 | 22.06 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22833035.63 | 747.68 | 27-JAN-13:50 | -14.6 | -15.8 | 0.125389E+10 | 745.68 | 04-JAN-00:00 | -14.6 | -15.8 |
February | 0.511158E+09 | 1541.04 | 22-FEB-11:50 | -2.0 | -4.7 | 0.114706E+10 | 758.17 | 28-FEB-22:40 | -0.4 | -3.3 |
March | 0.138282E+10 | 1686.47 | 29-MAR-10:50 | 1.42 | -1.1 | 0.129275E+10 | 824.00 | 31-MAR-21:40 | 4.67 | 0.78 |
April | 0.342207E+10 | 2203.18 | 23-APR-15:10 | 25.78 | 16.56 | 0.135967E+10 | 984.20 | 23-APR-23:10 | 14.63 | 10.70 |
May | 0.580231E+10 | 5531.45 | 18-MAY-14:10 | 28.57 | 16.73 | 0.163423E+10 | 1007.40 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.696625E+10 | 6063.47 | 30-JUN-14:10 | 31.28 | 23.89 | 0.163901E+10 | 1007.41 | 08-JUN-21:10 | 31.28 | 23.89 |
July | 0.812216E+10 | 6252.31 | 29-JUL-13:30 | 29.15 | 21.00 | 0.170487E+10 | 1007.40 | 01-JUL-01:10 | 29.15 | 21.00 |
August | 0.696098E+10 | 5610.95 | 24-AUG-14:10 | 25.18 | 17.78 | 0.170041E+10 | 1007.40 | 01-AUG-00:30 | 25.18 | 17.78 |
September | 0.495030E+10 | 5504.84 | 01-SEP-13:30 | 25.00 | 18.03 | 0.154861E+10 | 1007.40 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.348652E+10 | 2852.63 | 22-OCT-13:30 | 18.85 | 12.94 | 0.138625E+10 | 947.11 | 22-OCT-23:10 | 6.60 | 5.30 |
November | 0.121157E+10 | 1600.80 | 17-NOV-11:50 | 8.53 | 2.74 | 0.123349E+10 | 818.74 | 01-NOV-22:10 | 8.53 | 2.74 |
December | 22284528.95 | 739.94 | 28-DEC-12:30 | -1.7 | -3.3 | 0.126275E+10 | 745.76 | 13-DEC-04:30 | -1.7 | -3.3 |
Annual Sum or Average | 0.428613E+11 | 0.171630E+11 | ||||||||
Minimum of Months | 22284528.95 | 739.94 | -14.6 | -15.8 | 0.114706E+10 | 745.68 | -14.6 | -15.8 | ||
Maximum of Months | 0.812216E+10 | 6252.31 | 31.28 | 23.89 | 0.170487E+10 | 1007.41 | 31.28 | 23.89 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -8.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.00 | 0.00 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208531E+10 | 2077.69 | 07-JAN-04:03 | -23.7 |
February | 0.104460E+10 | 1666.37 | 13-FEB-07:30 | -24.4 |
March | 0.574134E+09 | 1633.53 | 05-MAR-02:30 | -25.2 |
April | 53927692.92 | 656.20 | 05-APR-06:10 | -13.5 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 36527739.73 | 786.68 | 30-OCT-06:54 | -9.4 |
November | 0.509975E+09 | 1616.37 | 25-NOV-07:20 | -19.0 |
December | 0.214806E+10 | 1868.54 | 26-DEC-02:50 | -23.7 |
Annual Sum or Average | 0.645253E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.2 | |
Maximum of Months | 0.214806E+10 | 2077.69 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1343065.91 | 263.49 | 09-JAN-10:45 | -23.4 |
February | 198705.34 | 44.51 | 02-FEB-10:53 | -22.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 3500979.87 | 465.90 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 5042751.11 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 3500979.87 | 465.90 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156164E+10 | 1310.05 | 06-JAN-13:30 | -23.6 |
February | 0.757818E+09 | 1027.22 | 14-FEB-10:20 | -24.3 |
March | 0.341213E+09 | 771.94 | 16-MAR-04:00 | -26.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.102408E+09 | 499.10 | 25-NOV-17:00 | -15.6 |
December | 0.128165E+10 | 1252.32 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 0.404473E+10 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.156164E+10 | 1310.05 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143416E+10 | 981.50 | 06-JAN-13:30 | -23.6 |
February | 0.862496E+09 | 897.80 | 14-FEB-10:40 | -23.5 |
March | 0.504350E+09 | 721.34 | 07-MAR-05:05 | -23.6 |
April | 25356966.19 | 228.06 | 05-APR-08:08 | -8.5 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 3101001.83 | 100.01 | 30-OCT-08:08 | -6.1 |
November | 0.243428E+09 | 552.38 | 25-NOV-17:00 | -15.6 |
December | 0.129130E+10 | 930.68 | 25-DEC-10:10 | -23.6 |
Annual Sum or Average | 0.436418E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.6 | |
Maximum of Months | 0.143416E+10 | 981.50 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -8.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.00 | 0.00 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58783778.36 | 1999.44 | 23-JAN-09:04 | -22.1 |
February | 15013609.12 | 1660.03 | 02-FEB-10:10 | -23.6 |
March | 2705382.37 | 400.39 | 16-MAR-09:20 | -15.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 848488.00 | 243.21 | 24-NOV-09:20 | -10.0 |
December | 87748834.26 | 3762.42 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 0.165100E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.6 | |
Maximum of Months | 87748834.26 | 3762.42 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 515.54 | 6.87 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 515.54 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 515.54 | 6.87 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259165E+10 | 2111.36 | 07-JAN-09:02 | -20.4 |
February | 0.162320E+10 | 2098.64 | 02-FEB-16:12 | -15.2 |
March | 0.115114E+10 | 2071.76 | 15-MAR-08:62 | -22.3 |
April | 0.365328E+09 | 2029.75 | 27-APR-08:61 | -1.7 |
May | 21520419.51 | 1956.02 | 01-MAY-08:61 | 1.73 |
June | 4071488.21 | 1089.27 | 22-JUN-18:04 | 19.32 |
July | 1522006.61 | 988.54 | 03-JUL-08:04 | 19.50 |
August | 4334136.63 | 1076.42 | 28-AUG-18:04 | 20.40 |
September | 35719012.86 | 1119.86 | 05-SEP-08:03 | 11.28 |
October | 0.423740E+09 | 2042.96 | 31-OCT-18:01 | -0.7 |
November | 0.120936E+10 | 2082.75 | 25-NOV-19:02 | -15.0 |
December | 0.255925E+10 | 2116.88 | 18-DEC-16:23 | -23.4 |
Annual Sum or Average | 0.999083E+10 | |||
Minimum of Months | 1522006.61 | 988.54 | -23.4 | |
Maximum of Months | 0.259165E+10 | 2116.88 | 20.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300906E+10 | 2205.47 | 05-JAN-07:54 | -32.2 |
February | 0.199136E+10 | 2086.99 | 02-FEB-16:12 | -15.2 |
March | 0.143065E+10 | 2073.80 | 15-MAR-08:62 | -22.3 |
April | 0.453485E+09 | 2016.79 | 05-APR-08:62 | -8.5 |
May | 25872055.95 | 1949.38 | 01-MAY-08:61 | 1.73 |
June | 2979485.60 | 1015.52 | 05-JUN-08:53 | 17.80 |
July | 754951.05 | 870.84 | 08-JUL-08:04 | 13.90 |
August | 4331562.38 | 1141.18 | 04-AUG-08:53 | 18.30 |
September | 41487307.84 | 1201.42 | 10-SEP-18:04 | 14.22 |
October | 0.511809E+09 | 2024.30 | 31-OCT-18:01 | -0.7 |
November | 0.141022E+10 | 2065.44 | 25-NOV-16:12 | -14.5 |
December | 0.288302E+10 | 2104.89 | 20-DEC-19:02 | -23.4 |
Annual Sum or Average | 0.117650E+11 | |||
Minimum of Months | 754951.05 | 870.84 | -32.2 | |
Maximum of Months | 0.300906E+10 | 2205.47 | 18.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224056E+09 | 408.39 | 09-JAN-05:00 | -33.3 |
February | 55180665.07 | 338.58 | 17-FEB-06:00 | -31.7 |
March | 7542720.08 | 162.84 | 05-MAR-06:00 | -27.2 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 21623168.16 | 202.94 | 29-NOV-06:00 | -20.6 |
December | 0.266169E+09 | 399.41 | 24-DEC-06:00 | -31.1 |
Annual Sum or Average | 0.574572E+09 | |||
Minimum of Months | 0.00 | 0.00 | -33.3 | |
Maximum of Months | 0.266169E+09 | 408.39 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.650890E+09 | 645.26 | 06-JAN-10:51 | -27.8 |
February | 0.409743E+09 | 585.40 | 01-FEB-16:11 | -20.4 |
March | 0.258884E+09 | 580.18 | 06-MAR-16:11 | -10.2 |
April | 30578504.33 | 548.88 | 04-APR-15:11 | -3.5 |
May | 275484.44 | 356.84 | 04-MAY-08:05 | 9.27 |
June | 42395.66 | 221.37 | 03-JUN-15:16 | 14.23 |
July | 25686.30 | 122.76 | 28-JUL-21:56 | 21.10 |
August | 152018.04 | 245.13 | 17-AUG-15:16 | 11.47 |
September | 506086.27 | 345.42 | 05-SEP-18:44 | 11.43 |
October | 14055142.87 | 541.40 | 30-OCT-15:12 | 5.00 |
November | 0.187261E+09 | 579.24 | 25-NOV-16:12 | -14.5 |
December | 0.589196E+09 | 590.01 | 20-DEC-16:12 | -20.6 |
Annual Sum or Average | 0.214161E+10 | |||
Minimum of Months | 25686.30 | 122.76 | -27.8 | |
Maximum of Months | 0.650890E+09 | 645.26 | 21.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258177E+10 | 2063.82 | 07-JAN-19:02 | -20.7 |
February | 0.161369E+10 | 2052.43 | 02-FEB-16:12 | -15.2 |
March | 0.113834E+10 | 2022.49 | 07-MAR-16:11 | -8.3 |
April | 0.350409E+09 | 1984.56 | 03-APR-15:11 | 2.97 |
May | 24067637.48 | 1106.92 | 29-MAY-18:04 | 12.13 |
June | 1794889.07 | 1021.00 | 11-JUN-08:04 | 10.78 |
July | 795351.08 | 987.66 | 03-JUL-08:04 | 19.50 |
August | 3620290.67 | 1081.88 | 18-AUG-15:14 | 15.20 |
September | 39478627.43 | 1165.00 | 22-SEP-18:03 | 12.93 |
October | 0.439877E+09 | 1994.54 | 31-OCT-18:01 | -0.7 |
November | 0.121342E+10 | 2044.54 | 25-NOV-16:12 | -14.5 |
December | 0.254544E+10 | 2065.87 | 21-DEC-16:12 | -15.8 |
Annual Sum or Average | 0.995271E+10 | |||
Minimum of Months | 795351.08 | 987.66 | -20.7 | |
Maximum of Months | 0.258177E+10 | 2065.87 | 19.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300007E+10 | 2234.33 | 06-JAN-07:53 | -35.0 |
February | 0.199289E+10 | 2051.70 | 01-FEB-16:11 | -20.4 |
March | 0.142070E+10 | 2015.01 | 07-MAR-16:11 | -8.3 |
April | 0.428874E+09 | 1970.46 | 03-APR-15:11 | 2.97 |
May | 29098540.02 | 1354.50 | 14-MAY-20:43 | 13.67 |
June | 1423370.22 | 1024.33 | 11-JUN-08:04 | 10.78 |
July | 615380.96 | 984.73 | 09-JUL-08:04 | 13.40 |
August | 3381845.37 | 1055.31 | 07-AUG-08:04 | 14.50 |
September | 48389501.44 | 1224.71 | 08-SEP-19:43 | 13.68 |
October | 0.537951E+09 | 1972.85 | 31-OCT-18:01 | -0.7 |
November | 0.140972E+10 | 2027.81 | 25-NOV-16:12 | -14.5 |
December | 0.286801E+10 | 2060.79 | 20-DEC-16:12 | -20.6 |
Annual Sum or Average | 0.117411E+11 | |||
Minimum of Months | 615380.96 | 984.73 | -35.0 | |
Maximum of Months | 0.300007E+10 | 2234.33 | 14.50 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145039E+10 | 1663.97 | 07-JAN-09:10 | -20.4 |
February | 0.511773E+09 | 1402.88 | 02-FEB-10:10 | -23.6 |
March | 0.195249E+09 | 896.55 | 07-MAR-09:08 | -16.7 |
April | 1546744.66 | 169.84 | 05-APR-06:10 | -13.5 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 2876685.35 | 234.88 | 30-OCT-08:03 | -6.1 |
November | 0.225517E+09 | 1050.35 | 25-NOV-17:00 | -15.6 |
December | 0.143044E+10 | 1725.64 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 0.381780E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.6 | |
Maximum of Months | 0.145039E+10 | 1725.64 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.344077E+10 | 2709.39 | 06-JAN-07:53 | -35.0 |
February | 0.221951E+10 | 2448.02 | 02-FEB-16:12 | -15.2 |
March | 0.162241E+10 | 2418.33 | 15-MAR-08:62 | -22.3 |
April | 0.582960E+09 | 2363.54 | 27-APR-08:61 | -1.7 |
May | 54665651.13 | 2284.51 | 01-MAY-08:61 | 1.73 |
June | 10201729.66 | 1088.71 | 04-JUN-08:03 | 13.27 |
July | 1519829.85 | 883.02 | 15-JUL-08:04 | 22.07 |
August | 10566871.34 | 1166.76 | 18-AUG-18:03 | 13.22 |
September | 89546400.35 | 1846.41 | 28-SEP-08:62 | 7.30 |
October | 0.682417E+09 | 2368.85 | 31-OCT-18:01 | -0.7 |
November | 0.170274E+10 | 2431.24 | 25-NOV-19:02 | -15.0 |
December | 0.338954E+10 | 2482.69 | 18-DEC-16:23 | -23.4 |
Annual Sum or Average | 0.138069E+11 | |||
Minimum of Months | 1519829.85 | 883.02 | -35.0 | |
Maximum of Months | 0.344077E+10 | 2709.39 | 22.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.390292E+10 | 2659.75 | 05-JAN-07:53 | -32.2 |
February | 0.265553E+10 | 2427.21 | 02-FEB-16:12 | -15.2 |
March | 0.196605E+10 | 2412.03 | 15-MAR-08:62 | -22.3 |
April | 0.701169E+09 | 2335.80 | 27-APR-08:61 | -1.7 |
May | 58298834.59 | 2271.20 | 01-MAY-08:61 | 1.73 |
June | 7480516.77 | 1196.81 | 05-JUN-08:53 | 17.80 |
July | 727862.80 | 983.24 | 31-JUL-08:53 | 18.90 |
August | 10114096.39 | 1114.03 | 18-AUG-18:03 | 13.22 |
September | 0.105440E+09 | 1921.80 | 28-SEP-08:62 | 7.30 |
October | 0.812427E+09 | 2346.04 | 30-OCT-08:62 | -6.1 |
November | 0.195198E+10 | 2402.95 | 25-NOV-19:02 | -15.0 |
December | 0.374435E+10 | 2645.75 | 20-DEC-07:54 | -29.2 |
Annual Sum or Average | 0.159165E+11 | |||
Minimum of Months | 727862.80 | 983.24 | -32.2 | |
Maximum of Months | 0.390292E+10 | 2659.75 | 18.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123523E+10 | 1300.84 | 12-JAN-19:13 | -22.4 |
February | 0.720600E+09 | 1286.27 | 02-FEB-16:12 | -15.2 |
March | 0.512978E+09 | 1270.67 | 16-MAR-08:62 | -19.0 |
April | 0.159786E+09 | 1247.47 | 26-APR-15:12 | -0.6 |
May | 11236096.00 | 740.28 | 05-MAY-08:03 | 8.17 |
June | 2781780.49 | 630.00 | 13-JUN-18:04 | 13.80 |
July | 1007787.50 | 514.06 | 17-JUL-08:04 | 15.00 |
August | 1972321.37 | 619.03 | 15-AUG-15:14 | 18.30 |
September | 10046451.63 | 602.55 | 26-SEP-15:14 | 13.90 |
October | 0.170971E+09 | 1241.29 | 30-OCT-08:62 | -6.1 |
November | 0.548659E+09 | 1282.36 | 25-NOV-19:02 | -15.0 |
December | 0.127675E+10 | 1305.13 | 11-DEC-16:23 | -17.2 |
Annual Sum or Average | 0.465202E+10 | |||
Minimum of Months | 1007787.50 | 514.06 | -22.4 | |
Maximum of Months | 0.127675E+10 | 1305.13 | 18.30 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -8.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.00 | 0.00 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -8.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.00 | 0.00 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -8.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.00 | 0.00 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.573998E+10 | 4747.73 | 07-JAN-04:03 | -23.7 |
February | 0.288228E+10 | 4597.06 | 17-FEB-09:45 | -23.4 |
March | 0.130486E+10 | 3620.56 | 05-MAR-08:63 | -25.9 |
April | 40802796.01 | 1529.13 | 05-APR-06:10 | -13.5 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 21795924.47 | 1215.44 | 30-OCT-06:58 | -9.4 |
November | 0.955979E+09 | 2979.36 | 25-NOV-07:20 | -19.0 |
December | 0.529475E+10 | 4740.98 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 0.162404E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.9 | |
Maximum of Months | 0.573998E+10 | 4747.73 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104372E+11 | 10053.14 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.942384E+10 | 10053.14 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.104694E+11 | 10053.14 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.100833E+11 | 10053.14 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.104553E+11 | 10053.14 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.101296E+11 | 10053.14 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.104091E+11 | 10053.14 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.104734E+11 | 10053.14 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.100874E+11 | 10053.14 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.104332E+11 | 10053.14 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.101215E+11 | 10053.14 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.104091E+11 | 10053.14 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.122932E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.942384E+10 | 10053.14 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.104734E+11 | 10053.14 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531884E+09 | 512.31 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.480243E+09 | 512.31 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.533523E+09 | 512.31 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.513850E+09 | 512.31 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.532806E+09 | 512.31 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.516207E+09 | 512.31 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.530449E+09 | 512.31 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.533728E+09 | 512.31 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.514055E+09 | 512.31 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.531679E+09 | 512.31 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.515797E+09 | 512.31 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.530449E+09 | 512.31 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.626467E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.480243E+09 | 512.31 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.533728E+09 | 512.31 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.615923E+09 | 593.26 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.556123E+09 | 593.26 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.617822E+09 | 593.26 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.595041E+09 | 593.26 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.616991E+09 | 593.26 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.597770E+09 | 593.26 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.614262E+09 | 593.26 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.618059E+09 | 593.26 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.595278E+09 | 593.26 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.615686E+09 | 593.26 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.597295E+09 | 593.26 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.614262E+09 | 593.26 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.725451E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.556123E+09 | 593.26 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.618059E+09 | 593.26 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.195918E+09 | 188.71 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.176896E+09 | 188.71 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.196522E+09 | 188.71 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.189275E+09 | 188.71 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.196257E+09 | 188.71 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.190143E+09 | 188.71 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.195389E+09 | 188.71 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.196597E+09 | 188.71 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.189351E+09 | 188.71 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.195842E+09 | 188.71 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.189992E+09 | 188.71 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.195389E+09 | 188.71 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.230757E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.176896E+09 | 188.71 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.196597E+09 | 188.71 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417273E+09 | 400.68 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.402047E+09 | 400.68 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415830E+09 | 400.68 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489965E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.128361E+10 | 1573.46 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.109408E+10 | 1573.46 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.112955E+10 | 1573.46 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.960046E+09 | 1573.46 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.868516E+09 | 1573.46 | 01-MAY-19:30 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.781163E+09 | 1573.46 | 01-JUN-19:00 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.829869E+09 | 1573.46 | 24-JUL-19:00 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.961812E+09 | 1573.46 | 01-AUG-19:49 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.103968E+10 | 1573.46 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.119504E+10 | 1573.46 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.121945E+10 | 1573.46 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.129632E+10 | 1573.46 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.126591E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.781163E+09 | 1573.46 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.129632E+10 | 1573.46 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.797862E+10 | 7984.04 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.714571E+10 | 7984.04 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.787363E+10 | 7984.04 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.747763E+10 | 7984.04 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.764463E+10 | 7984.04 | 01-MAY-19:30 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.735449E+10 | 7984.04 | 01-JUN-19:00 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.757872E+10 | 7984.04 | 24-JUL-19:00 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.773520E+10 | 7984.04 | 01-AUG-19:49 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.754567E+10 | 7984.04 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.790276E+10 | 7984.04 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.771764E+10 | 7984.04 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.797385E+10 | 7984.04 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.919286E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.714571E+10 | 7984.04 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.797862E+10 | 7984.04 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65789991.58 | 59.53 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 59414784.75 | 59.53 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 65267117.48 | 59.53 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 63743496.62 | 59.53 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 65528554.53 | 59.53 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 63237765.93 | 59.53 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 66042856.93 | 59.53 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 65267117.48 | 59.53 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 63760640.03 | 59.53 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 65781419.88 | 59.53 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 63490631.27 | 59.53 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 66051428.64 | 59.53 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.773376E+09 | 0.256575E+10 | ||||
Minimum of Months | 59414784.75 | 59.53 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 66051428.64 | 59.53 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.120431E+10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.108739E+10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.120803E+10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.116348E+10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.120640E+10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.116882E+10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.120107E+10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.120849E+10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.116395E+10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.120385E+10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.116789E+10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.120107E+10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141847E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.108739E+10 | 1160.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120849E+10 | 1160.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.259259E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.227270E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.244305E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.222050E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.216558E+10 | 2763.12 | 01-MAY-19:30 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.203636E+10 | 2763.12 | 01-JUN-19:00 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.212273E+10 | 2763.12 | 24-JUL-19:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.226888E+10 | 2763.12 | 01-AUG-19:49 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.230401E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.250289E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.249257E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.260137E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.280232E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.203636E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.260137E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.259259E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.227270E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.244305E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.222050E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.216558E+10 | 2763.12 | 01-MAY-19:30 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.203636E+10 | 2763.12 | 01-JUN-19:00 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.212273E+10 | 2763.12 | 24-JUL-19:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.226888E+10 | 2763.12 | 01-AUG-19:49 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.230401E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.250289E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.249257E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.260137E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.280232E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.203636E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.260137E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113599E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109410E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113446E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109454E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113207E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133389E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.127458E+10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.115083E+10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.127851E+10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.123137E+10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.127679E+10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.123701E+10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.127114E+10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.127900E+10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.123186E+10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.127409E+10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.123603E+10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.127114E+10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150123E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.115083E+10 | 1227.68 | 0.00 | 0.00 | |
Maximum of Months | 0.127900E+10 | 1227.68 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.104372E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.942384E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.104694E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.100833E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.104553E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.101296E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.104091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.104734E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.100874E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.104332E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.101215E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.104091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.122932E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.942384E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.104734E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.531884E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133633E+10 |
February | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102938E+10 |
March | 0.199990E+10 | 0.533523E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935681E+09 |
April | 0.192973E+10 | 0.513850E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 315508.77 | 0.567759E+09 |
May | 0.199475E+10 | 0.532806E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4960818.69 | 0.305909E+09 |
June | 0.193394E+10 | 0.516207E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14320060.37 | 0.172264E+09 |
July | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17505771.82 | 0.140975E+09 |
August | 0.199896E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6338987.04 | 0.176936E+09 |
September | 0.192879E+10 | 0.514055E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 261348.82 | 0.317739E+09 |
October | 0.199148E+10 | 0.531679E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527806E+09 |
November | 0.192552E+10 | 0.515797E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745197E+09 |
December | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125131E+10 |
Annual Sum or Average | 0.234744E+11 | 0.626467E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43702495.50 | 0.750728E+10 |
Minimum of Months | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140975E+09 |
Maximum of Months | 0.199990E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17505771.82 | 0.133633E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.615923E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515845E+09 |
February | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394908E+09 |
March | 0.231589E+10 | 0.617822E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359203E+09 |
April | 0.223463E+10 | 0.595041E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 253200.59 | 0.218272E+09 |
May | 0.230993E+10 | 0.616991E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3093797.37 | 0.116055E+09 |
June | 0.223950E+10 | 0.597770E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7515587.37 | 64337846.11 |
July | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9791170.03 | 52297067.31 |
August | 0.231480E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4019324.72 | 65649451.23 |
September | 0.223354E+10 | 0.595278E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 271477.62 | 0.122109E+09 |
October | 0.230614E+10 | 0.615686E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206172E+09 |
November | 0.222975E+10 | 0.597295E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288573E+09 |
December | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483403E+09 |
Annual Sum or Average | 0.271834E+11 | 0.725451E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24944557.69 | 0.288683E+10 |
Minimum of Months | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52297067.31 |
Maximum of Months | 0.231589E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9791170.03 | 0.515845E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121757E+10 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932549E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851588E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 303283.26 | 0.540686E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4504305.70 | 0.305506E+09 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13021990.25 | 0.178234E+09 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15950229.58 | 0.139418E+09 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5780380.85 | 0.177959E+09 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 238371.18 | 0.324660E+09 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523939E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696109E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114181E+10 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39798560.82 | 0.703003E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139418E+09 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15950229.58 | 0.121757E+10 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.195918E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699140E+09 |
February | 0.339028E+09 | 0.176896E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535612E+09 |
March | 0.376747E+09 | 0.196522E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484161E+09 |
April | 0.363528E+09 | 0.189275E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 525602.73 | 0.284108E+09 |
May | 0.375778E+09 | 0.196257E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5722266.67 | 0.141134E+09 |
June | 0.364321E+09 | 0.190143E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12782810.57 | 74950093.80 |
July | 0.374985E+09 | 0.195389E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16680967.88 | 58984245.92 |
August | 0.376571E+09 | 0.196597E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7646265.67 | 74734013.35 |
September | 0.363352E+09 | 0.189351E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 627807.58 | 0.149103E+09 |
October | 0.375161E+09 | 0.195842E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27926.72 | 0.267277E+09 |
November | 0.362735E+09 | 0.189992E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388291E+09 |
December | 0.374985E+09 | 0.195389E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656585E+09 |
Annual Sum or Average | 0.442217E+10 | 0.230757E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44013647.82 | 0.381408E+10 |
Minimum of Months | 0.339028E+09 | 0.176896E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58984245.92 |
Maximum of Months | 0.376747E+09 | 0.196597E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16680967.88 | 0.699140E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179595E+10 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138470E+10 |
March | 0.155131E+10 | 0.417273E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127132E+10 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 392974.21 | 0.787110E+09 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 6122254.14 | 0.423168E+09 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 17781458.09 | 0.243498E+09 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 21779331.53 | 0.190366E+09 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 7893260.78 | 0.243059E+09 |
September | 0.149615E+10 | 0.402047E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 325549.95 | 0.446142E+09 |
October | 0.154478E+10 | 0.415830E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749791E+09 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103790E+10 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168870E+10 |
Annual Sum or Average | 0.182090E+11 | 0.489965E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 54294828.69 | 0.102617E+11 |
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190366E+09 |
Maximum of Months | 0.155131E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 21779331.53 | 0.179595E+10 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.128361E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295668E+10 |
February | 0.236489E+11 | 0.109408E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227284E+10 |
March | 0.262800E+11 | 0.112955E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206737E+10 |
April | 0.253579E+11 | 0.960046E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1179812.51 | 0.124756E+10 |
May | 0.262123E+11 | 0.868516E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17033351.50 | 0.636802E+09 |
June | 0.254132E+11 | 0.781163E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45332217.86 | 0.340281E+09 |
July | 0.261570E+11 | 0.829869E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58978047.14 | 0.268849E+09 |
August | 0.262677E+11 | 0.961812E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20241670.15 | 0.345709E+09 |
September | 0.253456E+11 | 0.103968E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 745005.13 | 0.678540E+09 |
October | 0.261693E+11 | 0.119504E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117273E+10 |
November | 0.253025E+11 | 0.121945E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165321E+10 |
December | 0.261570E+11 | 0.129632E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276788E+10 |
Annual Sum or Average | 0.308468E+12 | 0.126591E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143510E+09 | 0.164085E+11 |
Minimum of Months | 0.236489E+11 | 0.781163E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268849E+09 |
Maximum of Months | 0.262800E+11 | 0.129632E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58978047.14 | 0.295668E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.797862E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.848667E+10 |
February | 0.702046E+11 | 0.714571E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653027E+10 |
March | 0.780153E+11 | 0.787363E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597230E+10 |
April | 0.752779E+11 | 0.747763E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3803745.80 | 0.366474E+10 |
May | 0.778146E+11 | 0.764463E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48329342.55 | 0.194979E+10 |
June | 0.754422E+11 | 0.735449E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120606E+09 | 0.109163E+10 |
July | 0.776503E+11 | 0.757872E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157323E+09 | 0.877554E+09 |
August | 0.779788E+11 | 0.773520E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60271504.73 | 0.110878E+10 |
September | 0.752414E+11 | 0.754567E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3314062.83 | 0.206720E+10 |
October | 0.776868E+11 | 0.790276E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347812E+10 |
November | 0.751137E+11 | 0.771764E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482133E+10 |
December | 0.776503E+11 | 0.797385E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795999E+10 |
Annual Sum or Average | 0.915726E+12 | 0.919286E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393647E+09 | 0.480084E+11 |
Minimum of Months | 0.702046E+11 | 0.714571E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877554E+09 |
Maximum of Months | 0.780153E+11 | 0.797862E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157323E+09 | 0.848667E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765252E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586601E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531938E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 419026.87 | 0.318371E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5193863.99 | 0.158435E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13931164.64 | 80703640.26 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17840848.04 | 57624469.38 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7419729.84 | 77015277.00 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 455568.61 | 0.166212E+09 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13246.07 | 0.296010E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423489E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715544E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45273448.06 | 0.417719E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57624469.38 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17840848.04 | 0.765252E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763473E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582777E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527064E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 385575.01 | 0.316075E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4789535.80 | 0.165857E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12435574.44 | 91957579.89 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16049957.47 | 71327636.54 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6413822.17 | 89048211.00 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 364877.76 | 0.169998E+09 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293428E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420172E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714716E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40439342.66 | 0.420589E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71327636.54 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16049957.47 | 0.763473E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 65789991.58 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188761E+09 |
February | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150165E+09 |
March | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145749E+09 |
April | 0.00 | 63743496.62 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108692E+09 |
May | 0.00 | 65528554.53 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 160313.38 | 67302814.66 |
June | 0.00 | 63237765.93 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 973649.19 | 43140910.99 |
July | 0.00 | 66042856.93 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 788441.65 | 36074918.46 |
August | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 174658.12 | 44177246.14 |
September | 0.00 | 63760640.03 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70389997.14 |
October | 0.00 | 65781419.88 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102222E+09 |
November | 0.00 | 63490631.27 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115486E+09 |
December | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173869E+09 |
Annual Sum or Average | 0.00 | 0.773376E+09 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2097062.34 | 0.124603E+10 |
Minimum of Months | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36074918.46 |
Maximum of Months | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 973649.19 | 0.188761E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212660E+09 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163210E+09 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148094E+09 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 124501.45 | 88394944.09 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1404367.32 | 44695331.35 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3545656.62 | 24017273.81 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4602585.23 | 17921688.51 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1887065.49 | 23037182.38 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 128493.02 | 46430876.68 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2251.83 | 82867817.36 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118842E+09 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199473E+09 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11694920.95 | 0.116964E+10 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17921688.51 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4602585.23 | 0.212660E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764764E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586578E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533681E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 426233.00 | 0.320667E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5220314.17 | 0.159336E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13943324.41 | 81381138.50 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17856741.32 | 57975933.70 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7455105.73 | 77461213.07 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 462659.69 | 0.166611E+09 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13862.38 | 0.296272E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423246E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715411E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45378240.70 | 0.418339E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57975933.70 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17856741.32 | 0.764764E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762942E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582496E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528227E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 401168.90 | 0.318586E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4808033.29 | 0.164350E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12376681.37 | 90915407.52 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15936105.61 | 70645623.87 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6434457.63 | 86921240.06 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 367377.41 | 0.168643E+09 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293427E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420159E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714482E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40323824.23 | 0.420179E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70645623.87 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15936105.61 | 0.762942E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.120431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938548E+09 |
February | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715970E+09 |
March | 0.387034E+10 | 0.120803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647211E+09 |
April | 0.373454E+10 | 0.116348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485344.53 | 0.387051E+09 |
May | 0.386038E+10 | 0.120640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5365190.70 | 0.205639E+09 |
June | 0.374269E+10 | 0.116882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12145315.91 | 0.115928E+09 |
July | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15131803.76 | 96433050.90 |
August | 0.386853E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6499351.39 | 0.116923E+09 |
September | 0.373273E+10 | 0.116395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393418.14 | 0.213486E+09 |
October | 0.385404E+10 | 0.120385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1640.55 | 0.361267E+09 |
November | 0.372639E+10 | 0.116789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518787E+09 |
December | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879006E+09 |
Annual Sum or Average | 0.454292E+11 | 0.141847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40022064.98 | 0.519625E+10 |
Minimum of Months | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96433050.90 |
Maximum of Months | 0.387034E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15131803.76 | 0.938548E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765375E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586264E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531559E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 408283.63 | 0.318061E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5063048.62 | 0.158999E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13668244.08 | 81231570.32 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17489627.60 | 58108755.99 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7219875.29 | 77464207.47 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 433389.78 | 0.166430E+09 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11633.31 | 0.295332E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422963E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716259E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44294102.31 | 0.417805E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58108755.99 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17489627.60 | 0.765375E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763291E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583270E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527308E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 376641.98 | 0.315980E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4681017.58 | 0.167775E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12233131.93 | 94034163.04 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15756521.50 | 73024499.23 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6265357.18 | 90837291.71 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 349531.39 | 0.170621E+09 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292596E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420258E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715194E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39662201.56 | 0.421419E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73024499.23 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15756521.50 | 0.763291E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396215E+09 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304672E+09 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276062E+09 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 211132.79 | 0.164995E+09 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2610199.27 | 81673751.13 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7026379.06 | 41608659.30 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8977961.32 | 29691973.87 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3707158.58 | 39773849.89 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 224478.40 | 86014804.95 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4541.84 | 0.153596E+09 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220058E+09 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369741E+09 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22761851.25 | 0.216410E+10 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29691973.87 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8977961.32 | 0.396215E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.259259E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191397E+10 |
February | 0.415303E+11 | 0.227270E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147185E+10 |
March | 0.461508E+11 | 0.244305E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134571E+10 |
April | 0.445315E+11 | 0.222050E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1081113.89 | 0.820757E+09 |
May | 0.460320E+11 | 0.216558E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12439445.38 | 0.435954E+09 |
June | 0.446286E+11 | 0.203636E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29582755.95 | 0.245437E+09 |
July | 0.459349E+11 | 0.212273E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40254696.65 | 0.192512E+09 |
August | 0.461292E+11 | 0.226888E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17933770.98 | 0.241059E+09 |
September | 0.445099E+11 | 0.230401E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1511228.71 | 0.453867E+09 |
October | 0.459565E+11 | 0.250289E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5800.62 | 0.775360E+09 |
November | 0.444343E+11 | 0.249257E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108845E+10 |
December | 0.459349E+11 | 0.260137E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179941E+10 |
Annual Sum or Average | 0.541708E+12 | 0.280232E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102809E+09 | 0.107843E+11 |
Minimum of Months | 0.415303E+11 | 0.203636E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192512E+09 |
Maximum of Months | 0.461508E+11 | 0.260137E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40254696.65 | 0.191397E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.259259E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192329E+10 |
February | 0.415303E+11 | 0.227270E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148231E+10 |
March | 0.461508E+11 | 0.244305E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136043E+10 |
April | 0.445315E+11 | 0.222050E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 958471.16 | 0.836777E+09 |
May | 0.460320E+11 | 0.216558E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11206279.79 | 0.447231E+09 |
June | 0.446286E+11 | 0.203636E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27309747.10 | 0.253848E+09 |
July | 0.459349E+11 | 0.212273E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36806243.34 | 0.199686E+09 |
August | 0.461292E+11 | 0.226888E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15960781.85 | 0.250010E+09 |
September | 0.445099E+11 | 0.230401E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1293457.05 | 0.466168E+09 |
October | 0.459565E+11 | 0.250289E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792727E+09 |
November | 0.444343E+11 | 0.249257E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110372E+10 |
December | 0.459349E+11 | 0.260137E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180906E+10 |
Annual Sum or Average | 0.541708E+12 | 0.280232E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 93534980.27 | 0.109253E+11 |
Minimum of Months | 0.415303E+11 | 0.203636E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199686E+09 |
Maximum of Months | 0.461508E+11 | 0.260137E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36806243.34 | 0.192329E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182731E+10 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141223E+10 |
March | 0.410691E+10 | 0.113599E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129865E+10 |
April | 0.396281E+10 | 0.109410E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 377772.69 | 0.805556E+09 |
May | 0.409635E+10 | 0.113446E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 5989470.63 | 0.434558E+09 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 17634853.46 | 0.251128E+09 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21440066.49 | 0.196836E+09 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 7680522.61 | 0.250929E+09 |
September | 0.396089E+10 | 0.109454E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 306415.54 | 0.458088E+09 |
October | 0.408962E+10 | 0.113207E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767681E+09 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106116E+10 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172029E+10 |
Annual Sum or Average | 0.482060E+11 | 0.133389E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 53429101.41 | 0.104844E+11 |
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196836E+09 |
Maximum of Months | 0.410691E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21440066.49 | 0.182731E+10 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.127458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166039E+10 |
February | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126980E+10 |
March | 0.409620E+10 | 0.127851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115286E+10 |
April | 0.395248E+10 | 0.123137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385195.40 | 0.708931E+09 |
May | 0.408566E+10 | 0.127679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5932326.37 | 0.405229E+09 |
June | 0.396110E+10 | 0.123701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17209879.38 | 0.239888E+09 |
July | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20900116.75 | 0.190713E+09 |
August | 0.409429E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7475293.71 | 0.240494E+09 |
September | 0.395056E+10 | 0.123186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297159.62 | 0.420547E+09 |
October | 0.407896E+10 | 0.127409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664063E+09 |
November | 0.394385E+10 | 0.123603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.922300E+09 |
December | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155676E+10 |
Annual Sum or Average | 0.480803E+11 | 0.150123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52199971.23 | 0.943198E+10 |
Minimum of Months | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190713E+09 |
Maximum of Months | 0.409620E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20900116.75 | 0.166039E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 10053.14 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 10053.14 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 10053.14 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 10053.14 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 10053.14 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 10053.14 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 10053.14 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 10053.14 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 10053.14 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 10053.14 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 10053.14 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 10053.14 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 512.31 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 778.27 | 06-JAN-09:00 |
February | 1169.53 | 01-FEB-00:10 | 512.31 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 743.51 | 14-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 512.31 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 674.88 | 05-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 512.31 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.48 | 23-APR-16:00 | 451.54 | 05-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 512.31 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.42 | 25-MAY-18:00 | 312.17 | 01-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 512.31 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.90 | 29-JUN-16:00 | 242.33 | 04-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 512.31 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.62 | 15-JUL-14:00 | 190.61 | 02-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 512.31 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.10 | 08-AUG-15:10 | 199.83 | 19-AUG-04:00 |
September | 1169.53 | 01-SEP-00:10 | 512.31 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 01-SEP-15:10 | 252.48 | 06-SEP-04:20 |
October | 1169.53 | 01-OCT-23:10 | 512.31 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 398.45 | 30-OCT-04:00 |
November | 1169.53 | 01-NOV-00:10 | 512.31 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 553.00 | 29-NOV-06:00 |
December | 1169.53 | 01-DEC-00:10 | 512.31 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 723.33 | 24-DEC-09:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.61 | |||||
Maximum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 118.90 | 778.27 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 593.26 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 303.78 | 06-JAN-09:00 |
February | 1354.32 | 01-FEB-00:10 | 593.26 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 293.87 | 14-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 593.26 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 265.27 | 05-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 593.26 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.41 | 23-APR-16:00 | 175.46 | 05-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 593.26 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 | 25-MAY-17:00 | 123.92 | 01-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 593.26 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.07 | 29-JUN-16:00 | 98.10 | 04-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 593.26 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.41 | 15-JUL-14:20 | 77.41 | 02-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 593.26 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.49 | 08-AUG-15:00 | 83.15 | 19-AUG-04:00 |
September | 1354.32 | 01-SEP-00:10 | 593.26 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 01-SEP-15:00 | 102.59 | 06-SEP-04:30 |
October | 1354.32 | 01-OCT-23:10 | 593.26 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 154.64 | 30-OCT-04:30 |
November | 1354.32 | 01-NOV-00:10 | 593.26 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 213.46 | 29-NOV-06:00 |
December | 1354.32 | 01-DEC-00:10 | 593.26 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 281.70 | 24-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.41 | |||||
Maximum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 49.07 | 303.78 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 720.44 | 06-JAN-09:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 694.54 | 14-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 626.92 | 05-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.81 | 23-APR-16:00 | 415.30 | 05-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.20 | 25-MAY-18:00 | 302.38 | 01-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.46 | 29-JUN-16:00 | 250.65 | 04-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.80 | 15-JUL-14:00 | 193.78 | 02-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.68 | 08-AUG-15:00 | 213.19 | 19-AUG-04:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.31 | 01-SEP-15:10 | 253.93 | 06-SEP-04:50 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 374.88 | 30-OCT-04:30 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 504.48 | 29-NOV-06:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 666.37 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.78 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 108.46 | 720.44 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 188.71 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 407.69 | 06-JAN-09:00 |
February | 220.32 | 01-FEB-00:10 | 188.71 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 394.26 | 14-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 188.71 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 359.12 | 05-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 188.71 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.31 | 23-APR-16:00 | 237.66 | 05-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 188.71 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.72 | 25-MAY-18:00 | 164.29 | 01-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 188.71 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.49 | 29-JUN-16:00 | 127.91 | 04-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 188.71 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.34 | 15-JUL-14:00 | 99.79 | 02-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 188.71 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.13 | 08-AUG-16:00 | 106.79 | 19-AUG-04:00 |
September | 220.32 | 01-SEP-00:10 | 188.71 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 01-SEP-16:00 | 130.27 | 06-SEP-04:30 |
October | 220.32 | 01-OCT-23:10 | 188.71 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 | 19-OCT-15:00 | 209.70 | 30-OCT-04:00 |
November | 220.32 | 01-NOV-00:10 | 188.71 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 291.06 | 29-NOV-06:00 |
December | 220.32 | 01-DEC-00:10 | 188.71 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 378.04 | 24-DEC-07:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.79 | |||||
Maximum of Months | 220.32 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 70.49 | 407.69 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1063.02 | 06-JAN-09:00 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1006.06 | 14-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 907.47 | 05-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 36.72 | 23-APR-16:00 | 610.78 | 05-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 74.01 | 25-MAY-18:00 | 435.65 | 01-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 148.11 | 29-JUN-16:00 | 347.34 | 04-JUN-05:00 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 96.68 | 15-JUL-14:00 | 264.59 | 02-JUL-05:00 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 91.07 | 08-AUG-15:10 | 293.86 | 19-AUG-04:00 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 29.12 | 01-SEP-15:10 | 347.73 | 06-SEP-05:00 |
October | 907.20 | 01-OCT-23:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 544.29 | 30-OCT-04:00 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 738.51 | 29-NOV-06:00 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 967.42 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 264.59 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 148.11 | 1063.02 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1573.46 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1735.46 | 06-JAN-05:00 |
February | 15368.40 | 01-FEB-00:10 | 1573.46 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1665.14 | 14-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1573.46 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1519.04 | 05-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1573.46 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.81 | 23-APR-17:30 | 998.19 | 05-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1573.46 | 01-MAY-19:30 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.37 | 25-MAY-18:00 | 692.71 | 01-MAY-06:00 |
June | 15368.40 | 01-JUN-00:10 | 1573.46 | 01-JUN-19:00 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.27 | 29-JUN-16:30 | 541.60 | 04-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1573.46 | 24-JUL-19:00 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.35 | 15-JUL-15:20 | 415.97 | 02-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1573.46 | 01-AUG-19:49 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.77 | 08-AUG-16:00 | 471.26 | 19-AUG-04:00 |
September | 15368.40 | 01-SEP-00:10 | 1573.46 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.32 | 01-SEP-16:00 | 577.16 | 06-SEP-04:20 |
October | 15368.40 | 01-OCT-23:10 | 1573.46 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 880.81 | 30-OCT-04:00 |
November | 15368.40 | 01-NOV-00:10 | 1573.46 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1222.61 | 29-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1573.46 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1613.16 | 24-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.97 | |||||
Maximum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 276.27 | 1735.46 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 7984.04 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5027.06 | 06-JAN-05:00 |
February | 45622.98 | 01-FEB-00:10 | 7984.04 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4834.25 | 14-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 7984.04 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 4340.51 | 05-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 7984.04 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.65 | 23-APR-16:00 | 2922.89 | 05-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 7984.04 | 01-MAY-19:30 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 438.65 | 25-MAY-18:00 | 2079.58 | 01-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 7984.04 | 01-JUN-19:00 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 796.99 | 29-JUN-16:00 | 1648.26 | 04-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 7984.04 | 24-JUL-19:00 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 552.80 | 15-JUL-15:00 | 1281.49 | 02-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 7984.04 | 01-AUG-19:49 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 512.38 | 08-AUG-16:00 | 1422.68 | 19-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 7984.04 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.92 | 01-SEP-16:00 | 1721.77 | 06-SEP-04:40 |
October | 45622.98 | 01-OCT-23:10 | 7984.04 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2608.28 | 30-OCT-04:30 |
November | 45622.98 | 01-NOV-00:10 | 7984.04 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3547.51 | 29-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 7984.04 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4638.26 | 24-DEC-07:54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1281.49 | |||||
Maximum of Months | 45622.98 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 796.99 | 5027.06 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 459.88 | 06-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 445.50 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 400.08 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 23-APR-16:00 | 263.23 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.33 | 25-MAY-16:50 | 182.29 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 29-JUN-16:00 | 141.73 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.64 | 15-JUL-15:20 | 103.69 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 08-AUG-16:00 | 117.05 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.93 | 01-SEP-16:00 | 141.89 | 06-SEP-04:30 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.79 | 19-OCT-15:20 | 232.39 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 322.16 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 426.16 | 24-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.69 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 459.88 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 454.95 | 06-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 444.72 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 400.06 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 23-APR-16:00 | 263.21 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.33 | 25-MAY-16:50 | 182.28 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.84 | 29-JUN-16:00 | 141.72 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.63 | 15-JUL-15:20 | 103.68 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 08-AUG-15:20 | 117.04 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-15:20 | 141.88 | 06-SEP-04:30 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 232.37 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 322.13 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 424.53 | 24-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.68 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.84 | 454.95 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 59.53 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 118.72 | 06-JAN-09:00 |
February | 0.00 | 01-FEB-00:10 | 59.53 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 111.62 | 14-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 59.53 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 99.25 | 05-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 59.53 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 75.95 | 05-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 59.53 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 | 25-MAY-18:00 | 56.81 | 01-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 59.53 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 | 29-JUN-16:00 | 48.01 | 04-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 59.53 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.77 | 15-JUL-14:00 | 39.18 | 02-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 59.53 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 | 08-AUG-15:10 | 41.46 | 19-AUG-04:00 |
September | 0.00 | 01-SEP-00:10 | 59.53 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 49.71 | 06-SEP-04:00 |
October | 0.00 | 01-OCT-00:10 | 59.53 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 66.51 | 30-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 59.53 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 77.93 | 29-NOV-06:00 |
December | 0.00 | 01-DEC-00:10 | 59.53 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 106.60 | 24-DEC-07:54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 | |||||
Maximum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 | 118.72 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 126.49 | 06-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 122.31 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 111.44 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.81 | 23-APR-16:00 | 73.46 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 25-MAY-16:50 | 50.88 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.24 | 29-JUN-16:00 | 39.56 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.92 | 15-JUL-15:20 | 28.94 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 | 08-AUG-15:20 | 32.67 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.92 | 01-SEP-15:18 | 39.60 | 06-SEP-04:40 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 19-OCT-15:20 | 64.86 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 89.91 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 117.03 | 24-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 24.24 | 126.49 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 461.40 | 06-JAN-09:10 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 445.13 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 400.08 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 23-APR-16:00 | 263.23 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.33 | 25-MAY-16:50 | 182.29 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.87 | 29-JUN-16:00 | 141.74 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.64 | 15-JUL-15:18 | 103.69 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.73 | 08-AUG-15:20 | 117.05 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-15:20 | 141.89 | 06-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.80 | 19-OCT-15:18 | 232.39 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 322.16 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 425.33 | 24-DEC-09:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.69 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.87 | 461.40 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 455.14 | 06-JAN-09:10 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 441.70 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 400.05 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.16 | 23-APR-16:00 | 263.21 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.33 | 25-MAY-16:50 | 182.28 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 29-JUN-16:00 | 141.73 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.63 | 15-JUL-15:18 | 103.68 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 08-AUG-15:20 | 117.04 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-15:20 | 141.88 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 232.37 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 322.14 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 423.93 | 24-DEC-09:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.68 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 455.14 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 559.06 | 06-JAN-09:00 |
February | 2263.36 | 01-FEB-00:10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 535.56 | 14-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 482.75 | 05-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.38 | 23-APR-16:00 | 317.31 | 05-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.82 | 25-MAY-18:00 | 219.46 | 01-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.75 | 29-JUN-16:00 | 178.41 | 04-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.53 | 15-JUL-14:00 | 143.49 | 02-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.03 | 08-AUG-16:00 | 148.74 | 19-AUG-04:00 |
September | 2263.36 | 01-SEP-00:10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.18 | 01-SEP-16:00 | 183.94 | 06-SEP-04:00 |
October | 2263.36 | 01-OCT-23:10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 | 19-OCT-15:00 | 280.01 | 30-OCT-04:00 |
November | 2263.36 | 01-NOV-00:10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 388.53 | 29-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 512.19 | 24-DEC-07:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.49 | ||||
Maximum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.75 | 559.06 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 454.33 | 06-JAN-07:40 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 445.43 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 400.66 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.79 | 23-APR-16:00 | 263.74 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.96 | 25-MAY-16:50 | 182.76 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.48 | 29-JUN-16:00 | 142.18 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.27 | 15-JUL-15:20 | 104.12 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.35 | 08-AUG-16:00 | 117.49 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.37 | 01-SEP-16:00 | 142.34 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 | 19-OCT-15:20 | 232.89 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 322.69 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 423.65 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.12 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.48 | 454.33 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 453.79 | 06-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 441.66 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 400.63 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.80 | 23-APR-16:00 | 263.72 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.96 | 25-MAY-16:50 | 182.75 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.48 | 29-JUN-16:00 | 142.17 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.27 | 15-JUL-15:20 | 104.12 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.35 | 08-AUG-16:00 | 117.48 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.58 | 01-SEP-15:20 | 142.33 | 06-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 232.87 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 322.67 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 421.48 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.12 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.48 | 453.79 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 238.08 | 06-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 228.23 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 204.99 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 | 23-APR-16:00 | 134.94 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.07 | 25-MAY-16:50 | 93.51 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 29-JUN-16:00 | 72.75 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.84 | 15-JUL-15:20 | 53.27 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.88 | 08-AUG-15:20 | 60.11 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.16 | 01-SEP-16:00 | 72.83 | 06-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 19-OCT-15:20 | 119.15 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 165.10 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 218.25 | 24-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.27 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 238.08 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1115.54 | 06-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1080.14 | 14-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 976.22 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.12 | 23-APR-16:00 | 661.62 | 05-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:30 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.44 | 25-MAY-18:00 | 473.35 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:00 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.82 | 29-JUN-16:00 | 369.52 | 04-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 24-JUL-19:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.18 | 15-JUL-15:00 | 282.54 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:49 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.29 | 08-AUG-15:00 | 321.11 | 19-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.61 | 01-SEP-15:00 | 381.29 | 06-SEP-04:20 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 | 19-OCT-15:00 | 590.02 | 30-OCT-04:20 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 803.38 | 29-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1043.12 | 24-DEC-07:59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.54 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 183.82 | 1115.54 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1121.61 | 06-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1085.98 | 14-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 976.22 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.94 | 23-APR-16:00 | 668.41 | 05-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:30 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.50 | 25-MAY-18:00 | 480.36 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:00 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.33 | 29-JUN-16:00 | 373.90 | 04-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 24-JUL-19:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.57 | 15-JUL-15:00 | 286.13 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:49 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.03 | 08-AUG-15:00 | 325.22 | 19-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.51 | 01-SEP-15:00 | 384.95 | 06-SEP-04:20 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 596.24 | 30-OCT-04:20 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 809.18 | 29-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1043.11 | 24-DEC-07:56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.13 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 179.33 | 1121.61 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1084.45 | 06-JAN-09:00 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1026.52 | 14-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 926.08 | 05-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 36.20 | 23-APR-16:00 | 623.80 | 05-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 74.19 | 25-MAY-18:00 | 445.33 | 01-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 149.69 | 29-JUN-16:00 | 355.36 | 04-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 97.20 | 15-JUL-14:00 | 271.02 | 02-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 91.55 | 08-AUG-15:50 | 300.88 | 19-AUG-04:00 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 28.41 | 01-SEP-16:00 | 355.77 | 06-SEP-04:00 |
October | 2401.70 | 01-OCT-23:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 556.12 | 30-OCT-04:00 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 754.03 | 29-NOV-06:00 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 987.38 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 271.02 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 149.69 | 1084.45 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 971.55 | 06-JAN-09:00 |
February | 2395.44 | 01-FEB-00:10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 937.86 | 14-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 850.29 | 05-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.47 | 23-APR-16:00 | 562.51 | 05-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.40 | 25-MAY-18:00 | 391.83 | 01-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.30 | 29-JUN-16:00 | 324.67 | 04-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.01 | 15-JUL-14:00 | 256.87 | 02-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.38 | 08-AUG-15:10 | 275.19 | 19-AUG-04:00 |
September | 2395.44 | 01-SEP-00:10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.61 | 01-SEP-15:50 | 331.84 | 06-SEP-04:00 |
October | 2395.44 | 01-OCT-23:10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 496.49 | 30-OCT-04:00 |
November | 2395.44 | 01-NOV-00:10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 688.59 | 29-NOV-06:00 |
December | 2395.44 | 01-DEC-00:10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 899.43 | 24-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.87 | ||||
Maximum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.30 | 971.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 20334.62 | 26-JAN-07:00 | 8945.92 | 4468.11 | 5069.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20038.48 | 14-FEB-07:00 | 8945.92 | 4468.11 | 5069.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16211.17 | 05-MAR-07:00 | 8945.92 | 3351.05 | 4055.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12274.00 | 22-APR-10:35 | 7667.93 | 5585.17 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13069.36 | 25-MAY-18:10 | 53675.50 | 53616.48 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13909.44 | 25-JUN-10:35 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14812.37 | 23-JUL-10:35 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15447.98 | 31-AUG-21:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17464.80 | 15-SEP-21:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18123.32 | 27-OCT-21:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16951.11 | 17-NOV-22:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19389.06 | 24-DEC-07:51 | 62621.41 | 31276.74 | 35488.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12274.00 | 7667.93 | 3351.05 | 4055.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20334.62 | 62621.41 | 53616.48 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1791.00 | 27-JAN-13:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.26 |
February | 2995.00 | 28-FEB-13:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.20 |
March | 2943.87 | 20-MAR-12:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.88 |
April | 3427.31 | 13-APR-13:10 | 519.79 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.72 |
May | 3657.60 | 18-MAY-13:00 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 46.74 | 0.00 |
June | 3743.40 | 30-JUN-13:00 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 | 0.00 |
July | 3868.87 | 23-JUL-13:10 | 259.90 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 66.03 | 0.00 |
August | 4207.41 | 26-AUG-12:40 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 | 0.00 |
September | 4247.46 | 01-SEP-13:15 | 519.79 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 8.92 | 0.00 |
October | 4649.74 | 22-OCT-12:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.12 |
November | 2865.04 | 17-NOV-12:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.07 |
December | 1410.68 | 24-DEC-11:50 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 673.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1410.68 | 259.90 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4649.74 | 519.79 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 | 673.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1328.99 | 27-JAN-21:55 | 2407.68 | 1054.69 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.55 |
February | 1334.60 | 24-FEB-22:53 | 4062.96 | 1186.52 | 1755.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.00 |
March | 1289.59 | 31-MAR-20:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.61 |
April | 1438.68 | 13-APR-20:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.19 |
May | 1715.71 | 25-MAY-20:55 | 2407.68 | 1054.69 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 |
June | 1923.15 | 30-JUN-20:10 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 |
July | 1807.98 | 24-JUL-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 |
August | 1721.25 | 25-AUG-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.58 |
September | 1650.33 | 01-SEP-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.24 |
October | 1476.90 | 22-OCT-10:35 | 902.88 | 395.51 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.10 |
November | 1269.08 | 17-NOV-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.21 |
December | 1087.60 | 05-DEC-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1087.60 | 902.88 | 395.51 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | |
Maximum of Months | 1923.15 | 4062.96 | 1186.52 | 1755.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14.62 | 19-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.60 |
February | 16.08 | 21-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.28 |
March | 18.28 | 31-MAR-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.13 |
April | 551.37 | 23-APR-20:00 | 190.94 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 |
May | 1275.06 | 25-MAY-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 0.00 |
June | 1579.50 | 30-JUN-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 0.00 |
July | 1415.96 | 21-JUL-19:55 | 445.54 | 1368.35 | 1678.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.64 |
August | 1331.79 | 09-AUG-19:55 | 891.07 | 2736.71 | 3357.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.25 |
September | 1211.25 | 01-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.72 |
October | 602.64 | 22-OCT-20:00 | 190.94 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.72 |
November | 19.12 | 01-NOV-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.62 |
December | 14.83 | 05-DEC-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14.62 | 190.94 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1579.50 | 891.07 | 2736.71 | 3357.79 | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 283.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18.62 | 19-JAN-22:00 | 195.84 | 167.74 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.82 |
February | 213.72 | 21-FEB-21:50 | 195.84 | 167.74 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.18 |
March | 499.52 | 31-MAR-21:00 | 195.84 | 167.74 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.18 |
April | 750.90 | 23-APR-18:10 | 1028.16 | 1027.41 | 1427.45 | 0.00 | 0.00 | 0.00 | 0.00 | 22.46 | 0.00 |
May | 901.25 | 25-MAY-18:10 | 1028.16 | 1006.45 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 39.30 | 0.00 |
June | 995.10 | 30-JUN-10:35 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 47.05 | 0.00 |
July | 981.82 | 23-JUL-10:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 31.44 | 0.00 |
August | 926.19 | 26-AUG-10:35 | 146.88 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2.12 | 0.00 |
September | 914.07 | 01-SEP-10:35 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 | 0.00 |
October | 809.87 | 22-OCT-10:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 |
November | 621.01 | 01-NOV-21:00 | 195.84 | 167.74 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.05 |
December | 82.57 | 05-DEC-22:00 | 195.84 | 167.74 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18.62 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 995.10 | 1028.16 | 1027.41 | 1427.45 | 0.00 | 0.00 | 0.00 | 0.00 | 47.05 | 162.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36431.57 | 19-JAN-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 421.56 |
February | 36902.45 | 21-FEB-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 382.08 |
March | 37380.48 | 31-MAR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 274.78 |
April | 38137.90 | 13-APR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 136.03 |
May | 38948.87 | 18-MAY-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 41.15 |
June | 39193.07 | 28-JUN-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 13.91 | 0.00 |
July | 39049.85 | 21-JUL-20:00 | 1411.20 | 801.37 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 25.45 |
August | 38967.74 | 08-AUG-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.02 | 0.00 |
September | 38753.37 | 01-SEP-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 104.75 |
October | 38148.18 | 19-OCT-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 156.47 |
November | 37509.83 | 01-NOV-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 153.34 |
December | 36519.52 | 05-DEC-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 365.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36431.57 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39193.07 | 1411.20 | 801.37 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 14.02 | 421.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9065.01 | 27-JAN-13:40 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1098.09 |
February | 11307.07 | 28-FEB-13:30 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 566.33 |
March | 10824.44 | 18-MAR-13:20 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.18 |
April | 12382.66 | 22-APR-13:20 | 10245.60 | 192.31 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.85 |
May | 11673.03 | 18-MAY-15:23 | 25614.00 | 288.47 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 118.66 | 0.00 |
June | 12010.41 | 25-JUN-10:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 113.46 | 0.00 |
July | 12509.20 | 29-JUL-13:10 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 120.95 | 0.00 |
August | 13767.45 | 26-AUG-12:40 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 34.85 | 0.00 |
September | 13345.04 | 01-SEP-15:10 | 8538.00 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 51.69 | 0.00 |
October | 15778.38 | 22-OCT-12:00 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.92 |
November | 11020.57 | 17-NOV-11:40 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.66 |
December | 10159.96 | 10-DEC-11:00 | 68304.00 | 923.09 | 3251.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9065.01 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15778.38 | 68304.00 | 923.09 | 3251.45 | 0.00 | 0.00 | 0.00 | 0.00 | 120.95 | 1375.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 30014.39 | 27-JAN-23:00 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4028.27 |
February | 29891.29 | 24-FEB-22:53 | 136868.94 | 15968.07 | 22169.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3954.03 |
March | 28863.73 | 07-MAR-00:53 | 136868.94 | 5322.69 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3941.82 |
April | 30366.77 | 13-APR-20:00 | 35484.54 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.79 |
May | 35354.79 | 25-MAY-21:10 | 91245.96 | 10645.38 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.21 |
June | 38226.85 | 29-JUN-21:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 253.23 | 0.00 |
July | 36815.75 | 24-JUL-21:10 | 91245.96 | 10645.38 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.28 |
August | 36023.71 | 25-AUG-21:10 | 91245.96 | 10645.38 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.93 |
September | 35350.11 | 01-SEP-21:10 | 91245.96 | 10645.38 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.30 |
October | 32978.72 | 22-OCT-10:35 | 30415.32 | 4577.51 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 595.56 |
November | 27696.15 | 17-NOV-21:00 | 35484.54 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1493.17 |
December | 27875.99 | 02-DEC-00:33 | 136868.94 | 5322.69 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3905.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 27696.15 | 30415.32 | 4577.51 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38226.85 | 136868.94 | 15968.07 | 22169.83 | 0.00 | 0.00 | 0.00 | 0.00 | 253.23 | 4028.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 608.90 | 25-JAN-16:13 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.09 |
February | 3825.62 | 28-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.59 |
March | 3874.24 | 26-MAR-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.26 |
April | 3954.64 | 13-APR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.35 |
May | 3984.32 | 04-MAY-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.19 |
June | 3959.49 | 16-JUN-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.23 |
July | 3431.02 | 04-JUL-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 | 0.00 |
August | 3450.49 | 22-AUG-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.10 |
September | 3910.91 | 09-SEP-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.79 |
October | 3795.55 | 09-OCT-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.66 |
November | 3758.15 | 17-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.45 |
December | 73.42 | 02-DEC-14:00 | 54.00 | 31.26 | 34.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 73.42 | 54.00 | 31.26 | 34.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3984.32 | 970.20 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 | 301.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 419.84 | 17-JAN-16:15 | 583.20 | 159.11 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.34 |
February | 2929.45 | 20-FEB-16:11 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.32 |
March | 3646.61 | 28-MAR-18:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.00 |
April | 4231.55 | 11-APR-18:11 | 1386.00 | 842.88 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.21 |
May | 4328.18 | 06-MAY-19:01 | 1170.00 | 947.05 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.74 |
June | 3635.66 | 08-JUN-21:51 | 1800.00 | 634.53 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.45 |
July | 3734.64 | 07-JUL-21:11 | 1800.00 | 634.53 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.03 |
August | 3885.58 | 07-AUG-16:21 | 972.00 | 265.18 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 |
September | 4197.92 | 04-SEP-18:01 | 1170.00 | 947.05 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.91 |
October | 2784.66 | 22-OCT-18:01 | 936.00 | 757.64 | 969.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.73 |
November | 1135.37 | 17-NOV-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.23 |
December | 0.00 | 01-DEC-00:05 | 360.00 | 41.67 | 89.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 360.00 | 41.67 | 89.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 | |
Maximum of Months | 4328.18 | 1800.00 | 947.05 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 185.10 | 05-JAN-15:05 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 |
February | 110.05 | 22-FEB-15:20 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.90 |
March | 219.34 | 31-MAR-14:20 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.40 |
April | 522.89 | 22-APR-13:25 | 0.00 | 39.29 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.29 |
May | 547.58 | 18-MAY-13:05 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 0.00 |
June | 541.91 | 30-JUN-13:00 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 8.82 | 0.00 |
July | 575.12 | 23-JUL-13:20 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 | 0.00 |
August | 638.32 | 25-AUG-13:05 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 0.00 |
September | 646.36 | 01-SEP-13:20 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 |
October | 770.02 | 22-OCT-12:30 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.14 |
November | 139.17 | 17-NOV-15:15 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.46 |
December | 58.89 | 02-DEC-15:20 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 58.89 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 770.02 | 0.00 | 39.29 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 8.82 | 98.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 225.69 | 19-JAN-19:05 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.16 |
February | 241.97 | 04-FEB-19:04 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.72 |
March | 947.80 | 28-MAR-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.66 |
April | 1016.67 | 18-APR-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.81 |
May | 1081.75 | 21-MAY-21:01 | 1386.00 | 506.11 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 |
June | 1087.04 | 07-JUN-08:51 | 288.00 | 209.59 | 887.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 |
July | 1028.44 | 01-JUL-21:01 | 1386.00 | 506.11 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.03 |
August | 1011.02 | 01-AUG-21:11 | 1800.00 | 398.93 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 |
September | 1077.26 | 04-SEP-18:01 | 1170.00 | 595.42 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.16 |
October | 973.13 | 20-OCT-18:12 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.14 |
November | 729.23 | 01-NOV-18:03 | 415.80 | 158.98 | 356.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.21 |
December | 163.48 | 05-DEC-19:05 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 163.48 | 288.00 | 158.98 | 356.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 | |
Maximum of Months | 1087.04 | 1800.00 | 595.42 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 76.30 | 20-JAN-16:16 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.83 |
February | 3245.62 | 28-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.85 |
March | 3481.99 | 31-MAR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.90 |
April | 3564.47 | 13-APR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 |
May | 3590.06 | 03-MAY-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.37 |
June | 3570.30 | 16-JUN-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 |
July | 3285.22 | 29-JUL-08:61 | 378.00 | 371.29 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.49 | 0.00 |
August | 3173.04 | 26-AUG-08:61 | 378.00 | 371.29 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.37 |
September | 3496.47 | 05-SEP-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 |
October | 3409.99 | 21-OCT-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.46 |
November | 2527.66 | 17-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.56 |
December | 581.94 | 28-DEC-09:05 | 216.00 | 250.05 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 76.30 | 216.00 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3590.06 | 970.20 | 663.02 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.49 | 197.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 360.00 | 49.25 | 89.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.79 |
February | 659.75 | 27-FEB-09:03 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.64 |
March | 3102.37 | 26-MAR-08:61 | 378.00 | 371.25 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.75 |
April | 3377.28 | 21-APR-08:61 | 252.00 | 291.69 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.80 |
May | 3451.42 | 27-MAY-08:51 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.43 |
June | 3591.11 | 28-JUN-08:61 | 252.00 | 291.69 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 |
July | 3745.19 | 31-JUL-08:32 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.67 |
August | 3552.98 | 20-AUG-08:51 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.46 |
September | 3490.56 | 04-SEP-18:01 | 1170.00 | 947.05 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.58 |
October | 3109.79 | 09-OCT-08:62 | 324.00 | 318.21 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.01 |
November | 764.83 | 17-NOV-09:03 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.56 |
December | 0.00 | 01-DEC-00:05 | 360.00 | 41.67 | 89.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 216.00 | 41.67 | 89.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 | |
Maximum of Months | 3745.19 | 1170.00 | 947.05 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 563.85 | 19-JAN-22:10 | 2263.36 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.46 |
February | 1191.91 | 28-FEB-17:20 | 1257.42 | 322.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.21 |
March | 1463.00 | 29-MAR-10:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.82 |
April | 1790.70 | 22-APR-10:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.08 |
May | 2066.99 | 25-MAY-18:10 | 10562.33 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.34 | 0.00 |
June | 2377.95 | 30-JUN-18:40 | 1760.39 | 1031.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.78 | 0.00 |
July | 2259.28 | 23-JUL-10:35 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.81 | 0.00 |
August | 2141.04 | 26-AUG-10:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 |
September | 2077.56 | 01-SEP-10:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 |
October | 1822.99 | 22-OCT-10:35 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.05 |
November | 1382.25 | 17-NOV-11:40 | 502.97 | 322.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.18 |
December | 643.10 | 05-DEC-22:10 | 2263.36 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 563.85 | 502.97 | 322.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2377.95 | 10562.33 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.34 | 217.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 680.34 | 27-JAN-16:13 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.25 |
February | 3970.00 | 28-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.83 |
March | 4022.34 | 26-MAR-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.52 |
April | 4114.50 | 13-APR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 |
May | 4149.62 | 04-MAY-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.68 |
June | 4118.12 | 16-JUN-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 |
July | 3599.68 | 20-JUL-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 30.66 | 0.00 |
August | 3601.46 | 14-AUG-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.41 |
September | 4097.74 | 04-SEP-18:01 | 1170.00 | 947.17 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.30 |
October | 3938.74 | 09-OCT-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.90 |
November | 3918.90 | 17-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.14 |
December | 61.59 | 02-DEC-14:00 | 54.00 | 31.26 | 34.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 61.59 | 54.00 | 31.26 | 34.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4149.62 | 1170.00 | 947.17 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 30.66 | 286.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 59.60 | 17-JAN-16:15 | 583.20 | 159.11 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.80 |
February | 1639.94 | 08-FEB-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.55 |
March | 3779.68 | 28-MAR-18:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.46 |
April | 4503.38 | 11-APR-18:11 | 1386.00 | 842.88 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.78 |
May | 4855.31 | 06-MAY-18:42 | 702.00 | 568.23 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.10 |
June | 3921.70 | 20-JUN-21:51 | 1800.00 | 634.53 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.78 |
July | 3930.13 | 26-JUL-21:11 | 1800.00 | 634.53 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.04 |
August | 4048.36 | 07-AUG-16:21 | 972.00 | 265.18 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 |
September | 4394.96 | 04-SEP-18:01 | 1170.00 | 947.05 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.58 |
October | 2894.14 | 22-OCT-18:01 | 936.00 | 757.64 | 969.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.41 |
November | 851.58 | 09-NOV-16:13 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.32 |
December | 0.00 | 01-DEC-00:05 | 360.00 | 41.67 | 89.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 360.00 | 41.67 | 89.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 | |
Maximum of Months | 4855.31 | 1800.00 | 947.05 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2220.41 | 27-JAN-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.04 |
February | 2254.04 | 28-FEB-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.71 |
March | 2265.92 | 23-MAR-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.68 |
April | 2302.20 | 13-APR-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 |
May | 2278.19 | 14-MAY-15:11 | 378.00 | 137.54 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 |
June | 2261.19 | 16-JUN-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.58 |
July | 1998.04 | 01-JUL-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 |
August | 2004.49 | 07-AUG-15:12 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 | 0.00 |
September | 2230.06 | 05-SEP-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.51 |
October | 2244.48 | 09-OCT-15:11 | 378.00 | 137.54 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.81 |
November | 2230.58 | 17-NOV-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.65 |
December | 2107.18 | 02-DEC-16:12 | 324.00 | 117.89 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1998.04 | 324.00 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2302.20 | 970.20 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 | 161.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17992.52 | 27-JAN-22:40 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 891.72 |
February | 19292.95 | 24-FEB-22:53 | 80966.30 | 5526.25 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.48 |
March | 17868.63 | 07-MAR-00:53 | 80966.30 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 884.51 |
April | 18019.94 | 13-APR-21:00 | 23990.02 | 2456.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.62 |
May | 20783.11 | 25-MAY-21:52 | 242898.91 | 16578.74 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.30 |
June | 21634.31 | 29-JUN-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 40.97 | 0.00 |
July | 21021.36 | 21-JUL-21:52 | 242898.91 | 16578.74 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.69 |
August | 20678.41 | 08-AUG-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.86 |
September | 20267.60 | 01-SEP-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.35 |
October | 17824.33 | 19-OCT-21:00 | 23990.02 | 2456.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.28 |
November | 17291.57 | 01-NOV-22:10 | 26988.77 | 921.04 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.13 |
December | 17601.00 | 23-DEC-21:43 | 62973.79 | 6447.29 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 874.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17291.57 | 23990.02 | 921.04 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21634.31 | 242898.91 | 16578.74 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 40.97 | 894.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19325.94 | 27-JAN-23:20 | 26988.77 | 921.04 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 921.83 |
February | 20050.17 | 24-FEB-22:53 | 80966.30 | 5526.25 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.48 |
March | 18591.86 | 07-MAR-00:53 | 80966.30 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 891.13 |
April | 20059.87 | 13-APR-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.16 |
May | 22188.12 | 25-MAY-21:52 | 242898.91 | 16578.74 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.30 |
June | 23040.30 | 29-JUN-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 40.97 | 0.00 |
July | 22435.70 | 21-JUL-21:52 | 242898.91 | 16578.74 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.69 |
August | 21886.29 | 08-AUG-21:52 | 215910.14 | 14736.65 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.87 |
September | 20787.35 | 01-SEP-21:22 | 215910.14 | 14736.65 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.78 |
October | 19477.92 | 19-OCT-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.71 |
November | 18576.77 | 01-NOV-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.15 |
December | 18388.95 | 23-DEC-21:43 | 62973.79 | 6447.29 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 881.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18388.95 | 26988.77 | 921.04 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23040.30 | 242898.91 | 16578.74 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 40.97 | 921.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24147.37 | 29-JAN-11:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 402.87 |
February | 25679.83 | 22-FEB-11:40 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 411.50 |
March | 27382.25 | 26-MAR-10:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 300.87 |
April | 28860.01 | 22-APR-10:40 | 1601.14 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 143.49 |
May | 29800.61 | 18-MAY-10:50 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 31.17 | 0.00 |
June | 30483.73 | 25-JUN-10:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 46.59 | 0.00 |
July | 30544.14 | 23-JUL-10:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 50.99 | 0.00 |
August | 29882.84 | 20-AUG-10:35 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 |
September | 29604.70 | 01-SEP-10:40 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 18.99 |
October | 28407.06 | 22-OCT-10:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 130.69 |
November | 25747.61 | 01-NOV-18:07 | 5603.98 | 2908.88 | 43813.67 | 44985.66 | 0.00 | 0.00 | 0.00 | 0.00 | 176.91 |
December | 24480.93 | 28-DEC-11:40 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 408.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 24147.37 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30544.14 | 5603.98 | 2908.88 | 43813.67 | 44985.66 | 0.00 | 0.00 | 0.00 | 50.99 | 411.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 747.68 | 27-JAN-13:50 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.18 |
February | 1541.04 | 22-FEB-11:50 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.15 |
March | 1686.47 | 29-MAR-10:50 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.48 |
April | 2203.18 | 23-APR-15:10 | 798.48 | 272.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.85 | 0.00 |
May | 5531.45 | 18-MAY-14:10 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.57 | 0.00 |
June | 6063.47 | 30-JUN-14:10 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.49 | 0.00 |
July | 6252.31 | 29-JUL-13:30 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.79 | 0.00 |
August | 5610.95 | 24-AUG-14:10 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.07 | 0.00 |
September | 5504.84 | 01-SEP-13:30 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 | 0.00 |
October | 2852.63 | 22-OCT-13:30 | 1064.64 | 545.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.66 |
November | 1600.80 | 17-NOV-11:50 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.03 |
December | 739.94 | 28-DEC-12:30 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 739.94 | 532.32 | 272.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6252.31 | 1064.64 | 545.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.49 | 578.18 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.350083E+12 | 219703.56 | 12-JAN-20:49 | 0.111312E+13 | 1004501.26 | 04-JAN-21:49 |
February | 0.310179E+12 | 216833.09 | 22-FEB-20:10 | 0.790047E+12 | 915142.10 | 01-FEB-21:00 |
March | 0.339989E+12 | 217061.18 | 13-MAR-19:49 | 0.705502E+12 | 750999.42 | 05-MAR-07:49 |
April | 0.330904E+12 | 279827.65 | 23-APR-18:10 | 0.584640E+12 | 555158.55 | 26-APR-17:49 |
May | 0.392030E+12 | 322396.55 | 25-MAY-19:00 | 0.494214E+12 | 429489.51 | 01-MAY-22:00 |
June | 0.444087E+12 | 375896.10 | 29-JUN-18:10 | 0.436792E+12 | 391453.13 | 02-JUN-17:00 |
July | 0.496621E+12 | 343646.35 | 03-JUL-20:19 | 0.434152E+12 | 379868.63 | 10-JUL-17:49 |
August | 0.453701E+12 | 338818.48 | 08-AUG-19:40 | 0.429999E+12 | 374533.88 | 04-AUG-17:40 |
September | 0.360367E+12 | 275686.20 | 01-SEP-19:10 | 0.448397E+12 | 378941.44 | 23-SEP-21:49 |
October | 0.337232E+12 | 235268.69 | 19-OCT-19:19 | 0.610903E+12 | 536296.83 | 31-OCT-17:00 |
November | 0.328813E+12 | 217871.58 | 27-NOV-20:30 | 0.646090E+12 | 550169.91 | 25-NOV-17:40 |
December | 0.350038E+12 | 218170.72 | 21-DEC-20:10 | 0.103553E+13 | 956358.65 | 19-DEC-21:30 |
Annual Sum or Average | 0.449404E+13 | 0.772939E+13 | ||||
Minimum of Months | 0.310179E+12 | 216833.09 | 0.429999E+12 | 374533.88 | ||
Maximum of Months | 0.496621E+12 | 375896.10 | 0.111312E+13 | 1004501.26 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.470569E+11 | 0.212246E+11 | 0.140003E+12 | 0.544023E+11 | 0.500956E+11 | 0.425329E+10 | 0.00 | 0.524884E+09 | 0.00 | 0.00 | 0.211264E+11 | 0.770466E+10 | 0.00 |
February | 0.422309E+11 | 0.174342E+11 | 0.126445E+12 | 0.491375E+11 | 0.427109E+11 | 0.393053E+10 | 0.00 | 0.100989E+10 | 0.00 | 0.00 | 0.169781E+11 | 0.696197E+10 | 0.00 |
March | 0.464617E+11 | 0.169456E+11 | 0.140056E+12 | 0.544045E+11 | 0.455747E+11 | 0.529809E+10 | 0.00 | 0.219838E+10 | 0.00 | 0.00 | 0.176396E+11 | 0.770289E+10 | 0.00 |
April | 0.444175E+11 | 0.140288E+11 | 0.135446E+12 | 0.526465E+11 | 0.435829E+11 | 0.666240E+10 | 0.00 | 0.149490E+11 | 0.00 | 0.00 | 0.812200E+10 | 0.746489E+10 | 0.00 |
May | 0.454391E+11 | 0.123631E+11 | 0.140035E+12 | 0.544026E+11 | 0.474777E+11 | 0.102571E+11 | 0.00 | 0.666184E+11 | 0.00 | 0.00 | 0.399978E+10 | 0.770426E+10 | 0.00 |
June | 0.437404E+11 | 0.108085E+11 | 0.135537E+12 | 0.526484E+11 | 0.478233E+11 | 0.114115E+11 | 0.00 | 0.126163E+12 | 0.00 | 0.00 | 0.485297E+10 | 0.745688E+10 | 0.00 |
July | 0.452572E+11 | 0.117117E+11 | 0.139944E+12 | 0.544000E+11 | 0.506193E+11 | 0.126046E+11 | 0.00 | 0.164462E+12 | 0.00 | 0.00 | 0.614776E+10 | 0.771239E+10 | 0.00 |
August | 0.458149E+11 | 0.135402E+11 | 0.140067E+12 | 0.544041E+11 | 0.491646E+11 | 0.117354E+11 | 0.00 | 0.124069E+12 | 0.00 | 0.00 | 0.342565E+10 | 0.770437E+10 | 0.00 |
September | 0.447432E+11 | 0.153614E+11 | 0.135457E+12 | 0.526468E+11 | 0.451341E+11 | 0.883254E+10 | 0.00 | 0.445579E+11 | 0.00 | 0.00 | 0.253630E+10 | 0.746620E+10 | 0.00 |
October | 0.467037E+11 | 0.183300E+11 | 0.139992E+12 | 0.544021E+11 | 0.452073E+11 | 0.543607E+10 | 0.00 | 0.108565E+11 | 0.00 | 0.00 | 0.487656E+10 | 0.770294E+10 | 0.00 |
November | 0.454867E+11 | 0.198920E+11 | 0.135531E+12 | 0.526481E+11 | 0.440340E+11 | 0.459083E+10 | 0.00 | 0.178942E+10 | 0.00 | 0.00 | 0.138043E+11 | 0.744870E+10 | 0.00 |
December | 0.470777E+11 | 0.217946E+11 | 0.139944E+12 | 0.544012E+11 | 0.498631E+11 | 0.418115E+10 | 0.00 | 0.486343E+09 | 0.00 | 0.00 | 0.208806E+11 | 0.771266E+10 | 0.00 |
Annual Sum or Average | 0.544430E+12 | 0.193435E+12 | 0.164846E+13 | 0.640544E+12 | 0.561288E+12 | 0.891935E+11 | 0.00 | 0.557685E+12 | 0.00 | 0.00 | 0.124390E+12 | 0.907428E+11 | 0.00 |
Minimum of Months | 0.422309E+11 | 0.108085E+11 | 0.126445E+12 | 0.491375E+11 | 0.427109E+11 | 0.393053E+10 | 0.00 | 0.486343E+09 | 0.00 | 0.00 | 0.253630E+10 | 0.696197E+10 | 0.00 |
Maximum of Months | 0.470777E+11 | 0.217946E+11 | 0.140067E+12 | 0.544045E+11 | 0.506193E+11 | 0.126046E+11 | 0.00 | 0.164462E+12 | 0.00 | 0.00 | 0.211264E+11 | 0.771266E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.651949E+12 | 0.00 | 0.309256E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.371091E+12 | 0.00 | 0.281753E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.241864E+12 | 0.00 | 0.311615E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.139604E+12 | 0.00 | 0.298080E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.399532E+11 | 0.00 | 0.302282E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.729380E+10 | 0.00 | 0.282385E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.127956E+10 | 0.00 | 0.281052E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.245720E+10 | 0.00 | 0.275504E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.339061E+11 | 0.00 | 0.267520E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.175454E+12 | 0.00 | 0.283546E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.213271E+12 | 0.00 | 0.285727E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.579809E+12 | 0.00 | 0.303899E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.245793E+13 | 0.00 | 0.348262E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.127956E+10 | 0.00 | 0.267520E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.651949E+12 | 0.00 | 0.311615E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 45764.37 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 39153.73 | 02-JAN-07:19 | 29931.64 | 12-JAN-19:19 | 4384.86 | 05-JAN-12:00 | 0.00 | 01-JAN-00:10 |
February | 45764.37 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 39153.73 | 01-FEB-07:19 | 29047.14 | 02-FEB-19:19 | 3922.91 | 01-FEB-16:19 | 0.00 | 01-FEB-00:10 |
March | 45764.37 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 39153.73 | 13-MAR-06:19 | 26011.58 | 07-MAR-19:10 | 4058.25 | 23-MAR-15:20 | 0.00 | 01-MAR-00:10 |
April | 45764.37 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 39153.17 | 03-APR-06:19 | 25454.25 | 23-APR-18:10 | 5463.51 | 23-APR-18:10 | 0.00 | 01-APR-00:10 |
May | 45764.37 | 01-MAY-19:30 | 12338.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 39151.72 | 22-MAY-06:19 | 30394.04 | 25-MAY-21:00 | 5680.01 | 25-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 45764.37 | 01-JUN-19:00 | 12338.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 39152.33 | 30-JUN-06:19 | 33453.50 | 29-JUN-21:10 | 5857.64 | 29-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 45764.37 | 24-JUL-19:00 | 12338.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 39152.01 | 03-JUL-06:19 | 32475.23 | 21-JUL-21:00 | 5811.14 | 21-JUL-19:19 | 0.00 | 01-JUL-00:10 |
August | 45764.37 | 01-AUG-19:49 | 12338.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 39153.23 | 31-AUG-06:19 | 30870.91 | 08-AUG-21:00 | 5762.24 | 08-AUG-15:30 | 0.00 | 01-AUG-00:10 |
September | 45764.37 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 39153.73 | 27-SEP-06:19 | 30092.99 | 01-SEP-21:40 | 5617.62 | 01-SEP-15:30 | 0.00 | 01-SEP-00:10 |
October | 45764.37 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 39153.73 | 02-OCT-06:19 | 25456.96 | 19-OCT-19:19 | 5361.02 | 19-OCT-15:20 | 0.00 | 01-OCT-00:10 |
November | 45764.37 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 39153.73 | 01-NOV-06:19 | 26710.17 | 25-NOV-19:10 | 3890.52 | 29-NOV-16:19 | 0.00 | 01-NOV-00:10 |
December | 45764.37 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 39153.73 | 01-DEC-07:19 | 29501.71 | 11-DEC-19:19 | 4334.04 | 24-DEC-12:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45764.37 | 12338.45 | 88863.15 | 39151.72 | 25454.25 | 3890.52 | 0.00 | |||||||
Maximum of Months | 45764.37 | 12338.45 | 88863.15 | 39153.73 | 33453.50 | 5857.64 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 2802.06 | 27-JAN-16:19 | 0.00 | 0.00 | 8265.52 | 01-JAN-00:10 | 4738.66 | 06-JAN-07:00 | 0.00 |
February | 6899.66 | 28-FEB-16:19 | 0.00 | 0.00 | 8265.52 | 01-FEB-00:10 | 4738.67 | 09-FEB-19:10 | 0.00 |
March | 15210.93 | 31-MAR-15:20 | 0.00 | 0.00 | 8265.52 | 01-MAR-00:10 | 4738.75 | 09-MAR-19:10 | 0.00 |
April | 94839.81 | 23-APR-18:10 | 0.00 | 0.00 | 8265.52 | 01-APR-18:40 | 4738.18 | 19-APR-06:19 | 0.00 |
May | 128246.37 | 25-MAY-18:10 | 0.00 | 0.00 | 8265.52 | 01-MAY-00:10 | 4738.47 | 18-MAY-18:10 | 0.00 |
June | 182398.39 | 29-JUN-15:30 | 0.00 | 0.00 | 8265.52 | 27-JUN-08:00 | 4738.53 | 08-JUN-18:10 | 0.00 |
July | 152959.98 | 15-JUL-15:20 | 0.00 | 0.00 | 8265.52 | 05-JUL-16:19 | 4738.72 | 13-JUL-18:10 | 0.00 |
August | 156148.26 | 08-AUG-15:30 | 0.00 | 0.00 | 8265.52 | 07-AUG-15:30 | 4738.55 | 24-AUG-18:10 | 0.00 |
September | 112706.59 | 01-SEP-15:30 | 0.00 | 0.00 | 8265.52 | 01-SEP-12:09 | 4738.05 | 27-SEP-06:19 | 0.00 |
October | 70069.11 | 19-OCT-15:20 | 0.00 | 0.00 | 8265.52 | 01-OCT-05:40 | 4738.08 | 05-OCT-18:10 | 0.00 |
November | 24225.86 | 01-NOV-15:20 | 0.00 | 0.00 | 8265.52 | 03-NOV-04:19 | 4738.36 | 08-NOV-19:10 | 0.00 |
December | 2192.41 | 02-DEC-14:09 | 0.00 | 0.00 | 8265.52 | 01-DEC-00:10 | 4738.74 | 07-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2192.41 | 0.00 | 0.00 | 8265.52 | 4738.05 | 0.00 | |||
Maximum of Months | 182398.39 | 0.00 | 0.00 | 8265.52 | 4738.75 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 219703.56 | 12-JAN-20:49 | 45764.37 | 86131.51 | 12338.45 | 31530.53 | 28435.04 | 1604.50 | 0.00 | 0.00 | 0.00 |
February | 216833.09 | 22-FEB-20:10 | 45764.37 | 86131.51 | 12338.45 | 31526.42 | 22749.64 | 3219.47 | 0.00 | 1186.13 | 0.00 |
March | 217061.18 | 13-MAR-19:49 | 45764.37 | 86131.51 | 12338.45 | 31530.53 | 23188.43 | 3453.17 | 0.00 | 819.35 | 0.00 |
April | 279827.65 | 23-APR-18:10 | 34717.52 | 74342.86 | 0.00 | 31270.21 | 25454.25 | 5463.51 | 0.00 | 94839.81 | 0.00 |
May | 322396.55 | 25-MAY-19:00 | 45764.37 | 86131.51 | 12338.45 | 31530.24 | 27029.25 | 5559.55 | 0.00 | 100563.89 | 0.00 |
June | 375896.10 | 29-JUN-18:10 | 36642.55 | 77265.07 | 0.00 | 31327.27 | 29162.04 | 5857.64 | 0.00 | 180947.10 | 0.00 |
July | 343646.35 | 03-JUL-20:19 | 40691.94 | 87910.25 | 12338.45 | 23990.91 | 28509.45 | 5733.22 | 0.00 | 130491.13 | 0.00 |
August | 338818.48 | 08-AUG-19:40 | 45764.37 | 86131.51 | 12338.45 | 31530.46 | 26931.90 | 5679.07 | 0.00 | 117093.62 | 0.00 |
September | 275686.20 | 01-SEP-19:10 | 45764.37 | 86131.51 | 12338.45 | 31526.42 | 24455.16 | 5045.94 | 0.00 | 65492.49 | 0.00 |
October | 235268.69 | 19-OCT-19:19 | 45764.37 | 86131.51 | 12338.45 | 31530.53 | 25456.96 | 4234.66 | 0.00 | 22903.03 | 0.00 |
November | 217871.58 | 27-NOV-20:30 | 45764.37 | 86131.51 | 12338.45 | 31530.53 | 23863.60 | 3450.05 | 0.00 | 810.83 | 0.00 |
December | 218170.72 | 21-DEC-20:10 | 45764.37 | 86131.51 | 12338.45 | 31526.42 | 27861.37 | 1039.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 216833.09 | 34717.52 | 74342.86 | 0.00 | 23990.91 | 22749.64 | 1039.97 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 375896.10 | 45764.37 | 87910.25 | 12338.45 | 31530.53 | 29162.04 | 5857.64 | 0.00 | 180947.10 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 695821.73 | 06-JAN-05:10 | 0.00 | 310448.22 | 31-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 659066.68 | 17-FEB-07:10 | 0.00 | 311632.67 | 22-FEB-21:00 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 608793.69 | 05-MAR-06:00 | 0.00 | 311590.36 | 01-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 189465.33 | 26-APR-08:09 | 0.00 | 309031.65 | 03-APR-20:30 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 154156.35 | 01-MAY-23:30 | 0.00 | 303537.29 | 02-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 139137.66 | 04-JUN-04:00 | 0.00 | 295179.56 | 02-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 42949.63 | 02-JUL-04:00 | 0.00 | 283797.95 | 13-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 91484.46 | 19-AUG-04:00 | 0.00 | 278473.45 | 14-AUG-20:00 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 134517.74 | 06-SEP-03:00 | 0.00 | 280581.19 | 25-SEP-20:49 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 203922.83 | 31-OCT-15:20 | 0.00 | 289268.42 | 31-OCT-20:49 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 228621.36 | 25-NOV-16:40 | 0.00 | 297379.70 | 28-NOV-21:49 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 673981.41 | 24-DEC-05:00 | 0.00 | 305176.74 | 29-DEC-21:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 42949.63 | 0.00 | 278473.45 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 695821.73 | 0.00 | 311632.67 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.00 | 19.38 | 51.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
February | 14.83 | 19.86 | 14.83 | 19.86 | 0.00 | 19.86 | 0.00 | 19.86 |
March | 3.67 | 20.27 | 3.67 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36.17 | 19.85 | 36.17 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 |
Annual Sum or Average | 105.67 | 19.64 | 105.67 | 19.64 | 0.00 | 19.64 | 0.00 | 19.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.00 | 20.27 | 51.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.33 | 20.09 | 24.33 | 20.09 | 0.00 | 20.09 | 0.00 | 20.09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.41 | 0.67 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Annual Sum or Average | 25.00 | 20.10 | 25.00 | 20.10 | 0.00 | 20.10 | 0.00 | 20.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.33 | 20.41 | 24.33 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.33 | 20.11 | 41.33 | 20.11 | 0.00 | 20.11 | 0.00 | 20.11 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.83 | 20.42 | 2.83 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Annual Sum or Average | 44.17 | 20.13 | 44.17 | 20.13 | 0.00 | 20.13 | 0.00 | 20.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.33 | 20.42 | 41.33 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 129.33 | 19.85 | 129.33 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 |
February | 17.50 | 20.17 | 17.50 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 51.33 | 20.06 | 51.33 | 20.06 | 0.00 | 20.06 | 0.00 | 20.06 |
Annual Sum or Average | 198.17 | 19.93 | 198.17 | 19.93 | 0.00 | 19.93 | 0.00 | 19.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.33 | 20.17 | 129.33 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.00 | 19.51 | 22.00 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
February | 4.67 | 19.89 | 4.67 | 19.89 | 0.00 | 19.89 | 0.00 | 19.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10.50 | 20.09 | 10.50 | 20.09 | 0.00 | 20.09 | 0.00 | 20.09 |
Annual Sum or Average | 37.17 | 19.72 | 37.17 | 19.72 | 0.00 | 19.72 | 0.00 | 19.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.00 | 20.09 | 22.00 | 20.09 | 0.00 | 20.09 | 0.00 | 20.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.00 | 20.10 | 9.00 | 20.10 | 0.00 | 20.10 | 0.00 | 20.10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 9.00 | 20.10 | 9.00 | 20.10 | 0.00 | 20.10 | 0.00 | 20.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.00 | 20.10 | 9.00 | 20.10 | 0.00 | 20.10 | 0.00 | 20.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.67 | 20.38 | 14.67 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
February | 1.17 | 20.42 | 1.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.77 | 1.00 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.74 | 2.17 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.76 | 2.00 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.77 | 1.17 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.50 | 20.37 | 4.50 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Annual Sum or Average | 20.33 | 20.38 | 20.33 | 20.38 | 7.00 | 20.58 | 7.00 | 20.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.67 | 20.42 | 14.67 | 20.42 | 2.17 | 21.77 | 2.17 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 45.00 | 20.16 | 45.00 | 20.16 | 0.00 | 20.16 | 0.00 | 20.16 |
February | 2.50 | 20.33 | 2.50 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
March | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.75 | 1.00 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.77 | 2.83 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.81 | 2.33 | 21.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.89 | 0.83 | 21.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.08 | 0.33 | 22.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15.83 | 20.35 | 15.83 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Annual Sum or Average | 63.50 | 20.21 | 63.50 | 20.21 | 7.50 | 20.30 | 7.50 | 20.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.00 | 20.55 | 45.00 | 20.55 | 2.83 | 22.08 | 2.83 | 22.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 125.67 | 19.75 | 125.67 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
February | 25.17 | 20.29 | 25.17 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
March | 1.67 | 20.33 | 1.67 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.77 | 1.50 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 21.85 | 7.50 | 21.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 21.80 | 8.17 | 21.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.76 | 4.00 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.50 | 20.35 | 1.50 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
December | 91.50 | 20.05 | 91.50 | 20.05 | 0.00 | 20.05 | 0.00 | 20.05 |
Annual Sum or Average | 245.50 | 19.93 | 245.50 | 19.93 | 21.33 | 20.01 | 21.33 | 20.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 125.67 | 20.35 | 125.67 | 20.35 | 8.17 | 21.85 | 8.17 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.17 | 20.28 | 28.17 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
February | 1.00 | 20.47 | 1.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.67 | 0.33 | 21.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
December | 5.00 | 20.40 | 5.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Annual Sum or Average | 34.33 | 20.31 | 34.33 | 20.31 | 1.00 | 20.33 | 1.00 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 28.17 | 20.55 | 28.17 | 20.55 | 0.50 | 21.78 | 0.50 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 50.33 | 20.00 | 50.33 | 20.00 | 0.00 | 20.00 | 0.00 | 20.00 |
February | 3.17 | 20.43 | 3.17 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.06 | 1.50 | 22.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 22.38 | 4.67 | 22.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 22.29 | 7.17 | 22.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 22.23 | 2.67 | 22.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.07 | 0.33 | 22.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.50 | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
December | 26.33 | 20.34 | 26.33 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Annual Sum or Average | 80.17 | 20.13 | 80.17 | 20.13 | 16.33 | 20.33 | 16.33 | 20.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.33 | 20.50 | 50.33 | 20.50 | 7.17 | 22.38 | 7.17 | 22.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.17 | 20.23 | 11.17 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11.17 | 20.23 | 11.17 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.17 | 20.23 | 11.17 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.17 | 20.11 | 33.17 | 20.11 | 0.00 | 20.11 | 0.00 | 20.11 |
February | 1.67 | 20.40 | 1.67 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.84 | 1.67 | 21.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.83 | 2.33 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.81 | 2.17 | 21.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.79 | 2.17 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.77 | 0.83 | 21.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10.33 | 20.38 | 10.33 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Annual Sum or Average | 45.17 | 20.19 | 45.17 | 20.19 | 9.33 | 20.34 | 9.33 | 20.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.17 | 20.40 | 33.17 | 20.40 | 2.33 | 21.84 | 2.33 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 71.33 | 19.90 | 71.33 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
February | 5.17 | 20.36 | 5.17 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
March | 0.17 | 20.51 | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.75 | 0.33 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.84 | 2.67 | 21.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.88 | 3.33 | 21.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.82 | 4.67 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.83 | 2.17 | 21.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 22.03 | 0.67 | 22.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
December | 38.17 | 20.21 | 38.17 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
Annual Sum or Average | 115.00 | 20.02 | 115.00 | 20.02 | 13.83 | 20.13 | 13.83 | 20.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.33 | 20.55 | 71.33 | 20.55 | 4.67 | 22.03 | 4.67 | 22.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 20.42 | 2.83 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
February | 0.50 | 20.50 | 0.50 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.81 | 0.83 | 21.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 20.44 | 2.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Annual Sum or Average | 5.33 | 20.44 | 5.33 | 20.44 | 2.67 | 20.70 | 2.67 | 20.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 20.50 | 2.83 | 20.50 | 0.83 | 21.81 | 0.83 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.50 | 19.46 | 21.50 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
February | 1.00 | 20.05 | 1.00 | 20.05 | 0.00 | 20.05 | 0.00 | 20.05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.83 | 20.03 | 1.83 | 20.03 | 0.00 | 20.03 | 0.00 | 20.03 |
Annual Sum or Average | 24.33 | 19.53 | 24.33 | 19.53 | 0.00 | 19.53 | 0.00 | 19.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.50 | 20.05 | 21.50 | 20.05 | 0.00 | 20.05 | 0.00 | 20.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.83 | 19.57 | 10.83 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
February | 0.17 | 20.24 | 0.17 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.27 | 0.83 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
Annual Sum or Average | 11.83 | 19.63 | 11.83 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.83 | 20.27 | 10.83 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.00 | 19.93 | 51.00 | 19.93 | 0.00 | 19.93 | 0.00 | 19.93 |
February | 7.17 | 20.25 | 7.17 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23.00 | 20.18 | 23.00 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
Annual Sum or Average | 81.17 | 20.03 | 81.17 | 20.03 | 0.00 | 20.03 | 0.00 | 20.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.00 | 20.25 | 51.00 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.28 | 32.83 | 22.22 | 32.83 | 22.17 |
February | 672.00 | 22.40 | 0.00 | 22.40 | 0.00 | 22.40 |
March | 744.00 | 21.90 | 0.00 | 21.90 | 0.00 | 21.90 |
April | 720.00 | 21.79 | 0.00 | 21.79 | 0.00 | 21.79 |
May | 744.00 | 22.03 | 0.00 | 22.03 | 0.00 | 22.03 |
June | 720.00 | 22.30 | 37.33 | 22.31 | 37.33 | 22.31 |
July | 738.83 | 22.85 | 58.83 | 22.86 | 58.83 | 22.87 |
August | 443.17 | 23.27 | 145.17 | 23.39 | 52.67 | 23.41 |
September | 373.33 | 23.58 | 60.50 | 23.62 | 15.33 | 23.62 |
October | 605.17 | 23.73 | 0.00 | 23.73 | 0.00 | 23.73 |
November | 692.83 | 23.68 | 0.00 | 23.68 | 0.00 | 23.68 |
December | 744.00 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
Annual Sum or Average | 7941.33 | 22.65 | 334.67 | 22.68 | 197.00 | 22.68 |
Minimum of Months | 373.33 | 21.79 | 0.00 | 21.79 | 0.00 | 21.79 |
Maximum of Months | 744.00 | 23.73 | 145.17 | 23.73 | 58.83 | 23.73 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 736.83 | 20.96 | 649.50 | 20.91 | 649.50 | 20.89 |
February | 634.50 | 21.20 | 425.17 | 21.11 | 423.17 | 21.06 |
March | 692.50 | 21.29 | 348.17 | 21.21 | 342.67 | 21.15 |
April | 628.17 | 21.67 | 109.67 | 21.69 | 80.67 | 21.62 |
May | 466.50 | 22.35 | 151.50 | 22.75 | 0.17 | 22.75 |
June | 378.17 | 22.64 | 331.67 | 23.21 | 67.83 | 23.23 |
July | 251.83 | 23.11 | 550.33 | 23.64 | 109.67 | 23.64 |
August | 294.50 | 22.77 | 441.33 | 23.42 | 64.67 | 23.43 |
September | 489.83 | 22.11 | 160.00 | 22.54 | 16.17 | 22.55 |
October | 652.67 | 21.40 | 138.50 | 21.52 | 86.33 | 21.47 |
November | 691.67 | 21.12 | 382.33 | 21.08 | 381.50 | 21.06 |
December | 742.00 | 21.00 | 675.00 | 20.96 | 675.00 | 20.95 |
Annual Sum or Average | 6659.17 | 21.59 | 4363.17 | 21.79 | 2897.33 | 21.66 |
Minimum of Months | 251.83 | 20.96 | 109.67 | 20.91 | 0.17 | 20.89 |
Maximum of Months | 742.00 | 23.11 | 675.00 | 23.64 | 675.00 | 23.64 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.99 | 386.00 | 20.96 | 386.00 | 20.95 |
February | 672.00 | 21.14 | 161.17 | 21.11 | 161.17 | 21.09 |
March | 744.00 | 21.32 | 69.00 | 21.30 | 69.00 | 21.27 |
April | 718.33 | 21.87 | 0.00 | 21.87 | 0.00 | 21.87 |
May | 670.50 | 22.54 | 26.67 | 22.59 | 0.00 | 22.59 |
June | 580.00 | 22.68 | 127.00 | 22.85 | 67.50 | 22.90 |
July | 469.33 | 22.95 | 235.33 | 23.20 | 111.33 | 23.24 |
August | 508.50 | 22.82 | 165.17 | 23.03 | 69.83 | 23.07 |
September | 665.00 | 22.53 | 28.50 | 22.56 | 16.67 | 22.58 |
October | 742.67 | 21.90 | 0.00 | 21.90 | 0.00 | 21.90 |
November | 720.00 | 21.31 | 31.00 | 21.30 | 31.00 | 21.29 |
December | 744.00 | 21.03 | 333.50 | 21.02 | 333.50 | 21.01 |
Annual Sum or Average | 7978.33 | 21.84 | 1563.33 | 21.86 | 1246.00 | 21.82 |
Minimum of Months | 469.33 | 20.99 | 0.00 | 20.96 | 0.00 | 20.95 |
Maximum of Months | 744.00 | 22.95 | 386.00 | 23.20 | 386.00 | 23.24 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.94 | 639.17 | 20.93 | 639.17 | 20.92 |
February | 672.00 | 21.12 | 480.83 | 21.07 | 480.83 | 21.05 |
March | 744.00 | 21.41 | 301.67 | 21.30 | 301.67 | 21.23 |
April | 720.00 | 22.76 | 0.00 | 22.76 | 0.00 | 22.76 |
May | 552.33 | 23.80 | 27.00 | 23.80 | 0.00 | 23.80 |
June | 205.83 | 23.99 | 243.17 | 24.00 | 3.83 | 24.00 |
July | 8.17 | 24.00 | 406.83 | 24.00 | 8.17 | 24.00 |
August | 17.83 | 23.95 | 338.67 | 24.00 | 0.00 | 24.00 |
September | 473.33 | 23.89 | 58.00 | 23.90 | 3.17 | 23.90 |
October | 743.00 | 23.15 | 0.00 | 23.15 | 0.00 | 23.15 |
November | 720.00 | 21.81 | 105.00 | 21.70 | 105.00 | 21.62 |
December | 744.00 | 21.01 | 596.00 | 21.00 | 596.00 | 20.99 |
Annual Sum or Average | 6344.50 | 22.17 | 3196.33 | 22.11 | 2137.83 | 21.90 |
Minimum of Months | 8.17 | 20.94 | 0.00 | 20.93 | 0.00 | 20.92 |
Maximum of Months | 744.00 | 24.00 | 639.17 | 24.00 | 639.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.77 | 701.33 | 20.76 | 701.33 | 20.76 |
February | 672.00 | 20.97 | 581.17 | 20.96 | 581.17 | 20.96 |
March | 744.00 | 21.00 | 443.67 | 21.00 | 443.67 | 21.00 |
April | 720.00 | 21.03 | 123.83 | 21.03 | 123.83 | 21.02 |
May | 744.00 | 21.52 | 10.50 | 21.51 | 10.50 | 21.51 |
June | 720.00 | 21.88 | 0.00 | 21.88 | 0.00 | 21.88 |
July | 744.00 | 22.20 | 0.00 | 22.20 | 0.00 | 22.20 |
August | 744.00 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
September | 720.00 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
October | 744.00 | 21.08 | 14.33 | 21.08 | 14.33 | 21.08 |
November | 720.00 | 21.00 | 311.33 | 21.00 | 311.33 | 21.00 |
December | 744.00 | 20.90 | 662.83 | 20.89 | 662.83 | 20.89 |
Annual Sum or Average | 8760.00 | 21.32 | 2849.00 | 21.22 | 2849.00 | 21.16 |
Minimum of Months | 672.00 | 20.77 | 0.00 | 20.76 | 0.00 | 20.76 |
Maximum of Months | 744.00 | 22.20 | 701.33 | 22.20 | 701.33 | 22.20 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 124.33 | 24.00 | 702.67 | 24.00 | 124.33 | 24.00 |
February | 120.50 | 24.00 | 652.67 | 24.00 | 120.50 | 24.00 |
March | 151.17 | 24.00 | 739.00 | 24.00 | 151.17 | 24.00 |
April | 175.50 | 24.00 | 720.00 | 24.00 | 175.50 | 24.00 |
May | 325.83 | 24.00 | 744.00 | 24.00 | 325.83 | 24.00 |
June | 448.83 | 24.00 | 720.00 | 24.00 | 448.83 | 24.00 |
July | 567.33 | 24.00 | 744.00 | 24.00 | 567.33 | 24.00 |
August | 533.17 | 24.00 | 744.00 | 24.00 | 533.17 | 24.00 |
September | 331.50 | 24.00 | 720.00 | 24.00 | 331.50 | 24.00 |
October | 217.00 | 24.00 | 744.00 | 24.00 | 217.00 | 24.00 |
November | 155.83 | 24.00 | 720.00 | 24.00 | 155.83 | 24.00 |
December | 126.50 | 24.00 | 710.50 | 24.00 | 126.50 | 24.00 |
Annual Sum or Average | 3277.50 | 24.00 | 8660.83 | 24.00 | 3277.50 | 24.00 |
Minimum of Months | 120.50 | 24.00 | 652.67 | 24.00 | 120.50 | 24.00 |
Maximum of Months | 567.33 | 24.00 | 744.00 | 24.00 | 567.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.00 | 21.02 | 420.00 | 20.98 | 420.00 | 20.96 |
February | 640.67 | 21.21 | 204.67 | 21.19 | 193.17 | 21.15 |
March | 706.67 | 21.36 | 102.83 | 21.36 | 87.67 | 21.33 |
April | 649.83 | 21.67 | 28.50 | 21.75 | 0.50 | 21.75 |
May | 597.67 | 22.03 | 81.50 | 22.19 | 7.17 | 22.21 |
June | 537.50 | 22.19 | 196.83 | 22.46 | 95.17 | 22.54 |
July | 432.83 | 22.45 | 359.50 | 22.78 | 162.00 | 22.86 |
August | 444.50 | 22.33 | 329.00 | 22.74 | 134.50 | 22.82 |
September | 561.17 | 22.01 | 121.00 | 22.28 | 20.33 | 22.30 |
October | 661.00 | 21.57 | 53.50 | 21.74 | 0.83 | 21.73 |
November | 701.33 | 21.27 | 92.50 | 21.25 | 89.50 | 21.22 |
December | 742.50 | 21.02 | 449.33 | 21.00 | 449.33 | 20.99 |
Annual Sum or Average | 7417.67 | 21.60 | 2439.17 | 21.73 | 1660.17 | 21.70 |
Minimum of Months | 432.83 | 21.02 | 28.50 | 20.98 | 0.50 | 20.96 |
Maximum of Months | 742.50 | 22.45 | 449.33 | 22.78 | 449.33 | 22.86 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.20 | 235.67 | 21.14 | 235.67 | 21.10 |
February | 672.00 | 21.50 | 70.50 | 21.45 | 70.50 | 21.41 |
March | 744.00 | 21.77 | 13.67 | 21.76 | 13.67 | 21.74 |
April | 710.67 | 22.32 | 0.00 | 22.32 | 0.00 | 22.32 |
May | 593.83 | 22.74 | 58.00 | 22.84 | 6.83 | 22.85 |
June | 485.00 | 22.87 | 208.33 | 23.13 | 103.00 | 23.21 |
July | 396.00 | 23.20 | 382.67 | 23.47 | 189.33 | 23.53 |
August | 393.50 | 23.10 | 342.50 | 23.40 | 159.83 | 23.48 |
September | 524.33 | 22.75 | 75.50 | 22.87 | 26.33 | 22.90 |
October | 695.33 | 22.33 | 3.67 | 22.33 | 0.00 | 22.33 |
November | 720.00 | 21.81 | 2.00 | 21.81 | 2.00 | 21.80 |
December | 744.00 | 21.26 | 188.00 | 21.21 | 188.00 | 21.17 |
Annual Sum or Average | 7422.67 | 22.11 | 1580.50 | 22.24 | 995.17 | 22.25 |
Minimum of Months | 393.50 | 21.20 | 0.00 | 21.14 | 0.00 | 21.10 |
Maximum of Months | 744.00 | 23.20 | 382.67 | 23.47 | 235.67 | 23.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.43 | 742.83 | 20.43 | 742.83 | 20.43 |
February | 672.00 | 20.70 | 596.67 | 20.65 | 596.67 | 20.63 |
March | 744.00 | 20.86 | 544.33 | 20.76 | 544.33 | 20.72 |
April | 711.67 | 21.26 | 206.67 | 21.15 | 205.00 | 21.08 |
May | 691.00 | 21.57 | 15.17 | 21.59 | 6.33 | 21.59 |
June | 636.00 | 21.53 | 22.33 | 21.59 | 6.83 | 21.60 |
July | 607.83 | 21.44 | 40.00 | 21.55 | 2.00 | 21.56 |
August | 636.33 | 21.46 | 26.33 | 21.53 | 1.00 | 21.54 |
September | 680.33 | 21.48 | 7.50 | 21.49 | 4.67 | 21.50 |
October | 732.83 | 21.08 | 224.33 | 20.96 | 224.33 | 20.89 |
November | 720.00 | 20.70 | 593.00 | 20.65 | 593.00 | 20.63 |
December | 744.00 | 20.42 | 744.00 | 20.42 | 744.00 | 20.42 |
Annual Sum or Average | 8320.00 | 21.06 | 3763.17 | 20.92 | 3671.00 | 20.83 |
Minimum of Months | 607.83 | 20.42 | 7.50 | 20.42 | 1.00 | 20.42 |
Maximum of Months | 744.00 | 21.57 | 744.00 | 21.59 | 744.00 | 21.60 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.34 | 744.00 | 20.34 | 744.00 | 20.34 |
February | 672.00 | 20.48 | 655.67 | 20.47 | 655.67 | 20.47 |
March | 744.00 | 20.61 | 647.67 | 20.56 | 647.67 | 20.54 |
April | 703.50 | 21.08 | 299.00 | 20.98 | 295.33 | 20.91 |
May | 644.83 | 21.78 | 69.50 | 22.09 | 22.00 | 22.15 |
June | 575.67 | 22.04 | 131.50 | 22.61 | 59.50 | 22.80 |
July | 551.83 | 22.20 | 157.33 | 22.85 | 75.00 | 23.12 |
August | 592.50 | 22.05 | 126.33 | 22.57 | 56.17 | 22.75 |
September | 664.83 | 21.57 | 49.33 | 21.78 | 16.67 | 21.82 |
October | 740.50 | 20.96 | 296.33 | 20.83 | 296.33 | 20.76 |
November | 720.00 | 20.52 | 660.50 | 20.51 | 660.50 | 20.50 |
December | 744.00 | 20.39 | 744.00 | 20.39 | 744.00 | 20.39 |
Annual Sum or Average | 8097.67 | 21.11 | 4581.17 | 21.06 | 4272.83 | 20.97 |
Minimum of Months | 551.83 | 20.34 | 49.33 | 20.34 | 16.67 | 20.34 |
Maximum of Months | 744.00 | 22.20 | 744.00 | 22.85 | 744.00 | 23.12 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.28 | 741.33 | 20.28 | 741.33 | 20.28 |
February | 672.00 | 20.59 | 645.00 | 20.58 | 645.00 | 20.58 |
March | 744.00 | 20.79 | 550.50 | 20.74 | 550.50 | 20.72 |
April | 720.00 | 21.19 | 128.67 | 21.14 | 128.67 | 21.10 |
May | 740.67 | 21.79 | 0.17 | 21.79 | 0.00 | 21.79 |
June | 697.50 | 22.06 | 28.17 | 22.11 | 27.67 | 22.16 |
July | 716.67 | 22.16 | 43.50 | 22.24 | 38.17 | 22.29 |
August | 742.00 | 22.07 | 22.33 | 22.11 | 22.33 | 22.14 |
September | 720.00 | 21.59 | 3.00 | 21.59 | 3.00 | 21.60 |
October | 744.00 | 21.15 | 43.17 | 21.13 | 43.17 | 21.10 |
November | 720.00 | 20.83 | 482.00 | 20.77 | 482.00 | 20.75 |
December | 744.00 | 20.39 | 720.00 | 20.38 | 720.00 | 20.38 |
Annual Sum or Average | 8704.83 | 21.24 | 3407.83 | 21.06 | 3401.83 | 20.95 |
Minimum of Months | 672.00 | 20.28 | 0.17 | 20.28 | 0.00 | 20.28 |
Maximum of Months | 744.00 | 22.16 | 741.33 | 22.24 | 741.33 | 22.29 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.40 | 742.67 | 20.40 | 742.67 | 20.40 |
February | 672.00 | 20.69 | 595.00 | 20.65 | 595.00 | 20.63 |
March | 744.00 | 20.95 | 520.50 | 20.83 | 520.50 | 20.78 |
April | 715.17 | 21.40 | 184.33 | 21.28 | 184.33 | 21.20 |
May | 697.17 | 21.64 | 2.83 | 21.64 | 2.83 | 21.63 |
June | 596.50 | 21.46 | 14.00 | 21.49 | 5.83 | 21.50 |
July | 578.67 | 21.36 | 18.67 | 21.42 | 1.00 | 21.43 |
August | 621.67 | 21.44 | 4.67 | 21.46 | 1.67 | 21.46 |
September | 672.50 | 21.48 | 6.00 | 21.49 | 5.33 | 21.50 |
October | 739.17 | 21.11 | 225.83 | 20.99 | 225.83 | 20.92 |
November | 720.00 | 20.69 | 593.67 | 20.65 | 593.67 | 20.63 |
December | 744.00 | 20.42 | 740.17 | 20.41 | 740.17 | 20.41 |
Annual Sum or Average | 8244.83 | 21.07 | 3648.33 | 20.91 | 3618.83 | 20.83 |
Minimum of Months | 578.67 | 20.40 | 2.83 | 20.40 | 1.00 | 20.40 |
Maximum of Months | 744.00 | 21.64 | 742.67 | 21.64 | 742.67 | 21.63 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.32 | 744.00 | 20.32 | 744.00 | 20.32 |
February | 672.00 | 20.46 | 662.00 | 20.46 | 662.00 | 20.46 |
March | 744.00 | 20.66 | 623.00 | 20.62 | 623.00 | 20.60 |
April | 720.00 | 21.30 | 253.33 | 21.17 | 253.33 | 21.09 |
May | 676.33 | 21.87 | 25.50 | 21.94 | 7.67 | 21.94 |
June | 519.83 | 21.85 | 111.67 | 22.31 | 41.67 | 22.43 |
July | 471.50 | 21.93 | 159.33 | 22.66 | 57.50 | 22.88 |
August | 572.17 | 21.89 | 85.50 | 22.19 | 37.00 | 22.27 |
September | 707.00 | 21.69 | 15.33 | 21.71 | 15.17 | 21.73 |
October | 744.00 | 20.97 | 298.17 | 20.85 | 298.17 | 20.79 |
November | 720.00 | 20.52 | 649.50 | 20.50 | 649.50 | 20.49 |
December | 744.00 | 20.37 | 744.00 | 20.37 | 744.00 | 20.37 |
Annual Sum or Average | 8034.83 | 21.09 | 4371.33 | 21.00 | 4133.00 | 20.90 |
Minimum of Months | 471.50 | 20.32 | 15.33 | 20.32 | 7.67 | 20.32 |
Maximum of Months | 744.00 | 21.93 | 744.00 | 22.66 | 744.00 | 22.88 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.97 | 611.33 | 20.97 | 611.33 | 20.96 |
February | 672.00 | 21.00 | 426.17 | 21.00 | 426.17 | 21.00 |
March | 744.00 | 21.02 | 251.83 | 21.02 | 251.83 | 21.01 |
April | 720.00 | 21.38 | 40.83 | 21.36 | 40.83 | 21.34 |
May | 744.00 | 22.38 | 0.00 | 22.38 | 0.00 | 22.38 |
June | 665.50 | 22.77 | 101.17 | 22.85 | 83.17 | 22.89 |
July | 581.17 | 23.24 | 148.50 | 23.27 | 138.33 | 23.29 |
August | 733.83 | 22.93 | 85.33 | 22.95 | 85.33 | 22.96 |
September | 720.00 | 22.17 | 18.50 | 22.18 | 18.50 | 22.19 |
October | 744.00 | 21.25 | 21.00 | 21.25 | 21.00 | 21.24 |
November | 720.00 | 21.00 | 236.50 | 21.00 | 236.50 | 21.00 |
December | 744.00 | 20.99 | 565.00 | 20.99 | 565.00 | 20.99 |
Annual Sum or Average | 8532.50 | 21.73 | 2506.17 | 21.63 | 2478.00 | 21.57 |
Minimum of Months | 581.17 | 20.97 | 0.00 | 20.97 | 0.00 | 20.96 |
Maximum of Months | 744.00 | 23.24 | 611.33 | 23.27 | 611.33 | 23.29 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.37 | 744.00 | 20.37 | 744.00 | 20.37 |
February | 672.00 | 20.61 | 627.67 | 20.57 | 627.67 | 20.56 |
March | 744.00 | 20.77 | 598.17 | 20.69 | 598.17 | 20.65 |
April | 706.00 | 21.16 | 328.17 | 21.04 | 326.00 | 20.97 |
May | 679.17 | 21.52 | 28.50 | 21.55 | 12.17 | 21.55 |
June | 614.17 | 21.46 | 41.83 | 21.56 | 12.17 | 21.57 |
July | 594.83 | 21.39 | 63.67 | 21.57 | 7.17 | 21.59 |
August | 624.83 | 21.40 | 52.83 | 21.53 | 13.00 | 21.54 |
September | 671.17 | 21.40 | 26.83 | 21.43 | 19.17 | 21.43 |
October | 730.50 | 20.97 | 332.83 | 20.84 | 332.83 | 20.77 |
November | 720.00 | 20.61 | 635.00 | 20.57 | 635.00 | 20.56 |
December | 744.00 | 20.39 | 744.00 | 20.39 | 744.00 | 20.39 |
Annual Sum or Average | 8244.67 | 20.98 | 4223.50 | 20.86 | 4071.33 | 20.78 |
Minimum of Months | 594.83 | 20.37 | 26.83 | 20.37 | 7.17 | 20.37 |
Maximum of Months | 744.00 | 21.52 | 744.00 | 21.57 | 744.00 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.27 | 744.00 | 20.27 | 744.00 | 20.27 |
February | 672.00 | 20.44 | 663.33 | 20.43 | 663.33 | 20.43 |
March | 744.00 | 20.55 | 679.17 | 20.51 | 679.17 | 20.50 |
April | 700.33 | 20.99 | 416.67 | 20.90 | 408.17 | 20.83 |
May | 635.33 | 21.83 | 97.00 | 22.24 | 40.33 | 22.37 |
June | 574.00 | 22.16 | 155.33 | 22.80 | 82.67 | 23.06 |
July | 552.83 | 22.32 | 188.83 | 23.03 | 97.00 | 23.35 |
August | 590.17 | 22.12 | 153.50 | 22.72 | 82.67 | 22.97 |
September | 664.67 | 21.54 | 72.67 | 21.80 | 37.00 | 21.86 |
October | 739.83 | 20.85 | 398.50 | 20.72 | 397.50 | 20.66 |
November | 720.00 | 20.46 | 676.83 | 20.45 | 676.83 | 20.44 |
December | 744.00 | 20.34 | 744.00 | 20.34 | 744.00 | 20.34 |
Annual Sum or Average | 8081.17 | 21.09 | 4989.83 | 21.07 | 4652.67 | 20.99 |
Minimum of Months | 552.83 | 20.27 | 72.67 | 20.27 | 37.00 | 20.27 |
Maximum of Months | 744.00 | 22.32 | 744.00 | 23.03 | 744.00 | 23.35 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.81 | 659.00 | 20.72 | 659.00 | 20.68 |
February | 661.50 | 21.09 | 474.17 | 20.96 | 474.17 | 20.90 |
March | 730.50 | 21.15 | 431.50 | 21.00 | 431.50 | 20.94 |
April | 689.00 | 21.36 | 150.33 | 21.27 | 150.33 | 21.20 |
May | 691.33 | 21.58 | 8.67 | 21.59 | 5.00 | 21.59 |
June | 632.67 | 21.51 | 15.83 | 21.54 | 9.50 | 21.55 |
July | 626.67 | 21.46 | 26.00 | 21.53 | 7.83 | 21.55 |
August | 640.17 | 21.46 | 29.50 | 21.54 | 2.33 | 21.54 |
September | 647.83 | 21.44 | 12.00 | 21.47 | 2.67 | 21.48 |
October | 703.17 | 21.15 | 173.50 | 21.12 | 153.33 | 21.05 |
November | 715.17 | 20.98 | 460.17 | 20.88 | 460.17 | 20.83 |
December | 744.00 | 20.70 | 685.00 | 20.63 | 685.00 | 20.61 |
Annual Sum or Average | 8226.00 | 21.21 | 3125.67 | 21.09 | 3040.83 | 21.00 |
Minimum of Months | 626.67 | 20.70 | 8.67 | 20.63 | 2.33 | 20.61 |
Maximum of Months | 744.00 | 21.58 | 685.00 | 21.59 | 685.00 | 21.59 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.29 | 253.33 | 21.17 | 253.33 | 21.09 |
February | 672.00 | 21.53 | 80.50 | 21.47 | 80.50 | 21.42 |
March | 744.00 | 21.78 | 5.00 | 21.77 | 5.00 | 21.77 |
April | 698.67 | 22.14 | 3.00 | 22.15 | 0.00 | 22.15 |
May | 490.83 | 22.39 | 103.67 | 22.61 | 6.33 | 22.63 |
June | 360.00 | 22.61 | 305.83 | 23.03 | 98.83 | 23.12 |
July | 337.50 | 22.89 | 432.17 | 23.21 | 173.83 | 23.29 |
August | 399.17 | 22.67 | 341.67 | 23.07 | 146.67 | 23.17 |
September | 510.33 | 22.31 | 109.33 | 22.54 | 24.67 | 22.58 |
October | 712.83 | 22.13 | 3.33 | 22.14 | 0.00 | 22.14 |
November | 715.50 | 21.83 | 1.83 | 21.84 | 0.00 | 21.84 |
December | 744.00 | 21.43 | 193.17 | 21.33 | 193.17 | 21.26 |
Annual Sum or Average | 7128.83 | 21.97 | 1832.83 | 22.13 | 982.33 | 22.13 |
Minimum of Months | 337.50 | 21.29 | 1.83 | 21.17 | 0.00 | 21.09 |
Maximum of Months | 744.00 | 22.89 | 432.17 | 23.21 | 253.33 | 23.29 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.48 | 117.83 | 21.38 | 117.83 | 21.30 |
February | 672.00 | 21.77 | 13.00 | 21.76 | 13.00 | 21.74 |
March | 730.00 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
April | 644.33 | 22.42 | 8.50 | 22.44 | 0.00 | 22.44 |
May | 357.17 | 22.54 | 197.00 | 22.93 | 6.33 | 22.94 |
June | 241.00 | 22.97 | 421.83 | 23.35 | 99.33 | 23.42 |
July | 235.17 | 23.42 | 573.83 | 23.45 | 179.00 | 23.52 |
August | 265.67 | 23.09 | 478.50 | 23.37 | 146.83 | 23.44 |
September | 347.83 | 22.40 | 210.33 | 22.86 | 26.00 | 22.90 |
October | 622.67 | 22.37 | 24.17 | 22.43 | 0.00 | 22.43 |
November | 691.17 | 22.13 | 5.50 | 22.14 | 0.00 | 22.14 |
December | 744.00 | 21.62 | 94.50 | 21.55 | 94.50 | 21.49 |
Annual Sum or Average | 6295.00 | 22.16 | 2145.00 | 22.44 | 682.83 | 22.47 |
Minimum of Months | 235.17 | 21.48 | 0.00 | 21.38 | 0.00 | 21.30 |
Maximum of Months | 744.00 | 23.42 | 573.83 | 23.45 | 179.00 | 23.52 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 428.00 | 23.76 | 656.83 | 23.90 | 380.17 | 23.92 |
February | 409.33 | 23.91 | 631.17 | 23.96 | 388.33 | 23.97 |
March | 473.67 | 23.97 | 728.00 | 23.98 | 467.50 | 23.99 |
April | 492.33 | 23.99 | 720.00 | 23.99 | 492.33 | 23.99 |
May | 542.50 | 23.99 | 744.00 | 23.99 | 542.50 | 23.99 |
June | 560.50 | 23.99 | 720.00 | 23.99 | 560.50 | 23.99 |
July | 598.00 | 23.99 | 744.00 | 23.99 | 598.00 | 23.99 |
August | 581.00 | 23.99 | 744.00 | 23.99 | 581.00 | 23.99 |
September | 530.33 | 23.99 | 720.00 | 23.99 | 530.33 | 23.99 |
October | 514.67 | 23.99 | 744.00 | 23.99 | 514.67 | 23.99 |
November | 458.50 | 23.99 | 718.50 | 23.99 | 458.50 | 23.99 |
December | 426.33 | 23.84 | 679.50 | 23.93 | 388.67 | 23.95 |
Annual Sum or Average | 6015.17 | 23.96 | 8550.00 | 23.98 | 5902.50 | 23.98 |
Minimum of Months | 409.33 | 23.76 | 631.17 | 23.90 | 380.17 | 23.92 |
Maximum of Months | 598.00 | 23.99 | 744.00 | 23.99 | 598.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.90 | 669.50 | 20.90 | 669.50 | 20.89 |
February | 672.00 | 21.01 | 484.33 | 21.00 | 484.33 | 20.99 |
March | 744.00 | 21.15 | 306.67 | 21.10 | 306.67 | 21.08 |
April | 709.67 | 21.93 | 22.67 | 21.90 | 22.67 | 21.88 |
May | 494.17 | 23.23 | 99.17 | 23.36 | 0.00 | 23.36 |
June | 259.00 | 23.62 | 302.17 | 23.82 | 65.83 | 23.84 |
July | 151.00 | 23.82 | 578.50 | 23.96 | 103.17 | 23.96 |
August | 173.50 | 23.61 | 450.83 | 23.88 | 80.00 | 23.88 |
September | 555.33 | 23.07 | 69.17 | 23.17 | 20.83 | 23.18 |
October | 738.00 | 21.80 | 10.33 | 21.79 | 10.33 | 21.78 |
November | 720.00 | 21.05 | 274.00 | 21.04 | 274.00 | 21.03 |
December | 744.00 | 20.96 | 640.83 | 20.96 | 640.83 | 20.96 |
Annual Sum or Average | 6704.67 | 21.76 | 3908.17 | 21.89 | 2678.17 | 21.76 |
Minimum of Months | 151.00 | 20.90 | 10.33 | 20.90 | 0.00 | 20.89 |
Maximum of Months | 744.00 | 23.82 | 669.50 | 23.96 | 669.50 | 23.96 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.27741 | 18.69417 | -0.2303 | 6.70144 |
February | 672.00000 | 22.40106 | 20.79981 | -0.1943 | 6.01214 |
March | 744.00000 | 21.90262 | 24.75080 | -0.2978 | 7.04184 |
April | 720.00000 | 21.78998 | 26.69485 | -0.3148 | 7.24445 |
May | 744.00000 | 22.02626 | 38.19939 | -1.2922 | 40.04191 |
June | 720.00000 | 22.29874 | 52.75029 | -1.1018 | 30.85512 |
July | 744.00000 | 22.85683 | 57.98507 | -0.8629 | 20.95590 |
August | 744.00000 | 23.45594 | 55.10405 | -0.6626 | 14.46433 |
September | 720.00000 | 23.70815 | 42.89252 | -0.6515 | 14.14638 |
October | 744.00000 | 23.76655 | 31.28413 | 0.22275 | 6.13270 |
November | 720.00000 | 23.69081 | 25.40210 | 0.16055 | 5.66178 |
December | 744.00000 | 22.96966 | 19.68567 | -0.0536 | 5.55336 |
Annual Sum or Average | 8760.00000 | 22.76376 | 34.60654 | -0.4415 | 13.78961 |
Minimum of Months | 672.00000 | 21.78998 | 18.69417 | -1.2922 | 5.55336 |
Maximum of Months | 744.00000 | 23.76655 | 57.98507 | 0.22275 | 40.04191 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99213 | 18.68545 | -0.6719 | 15.65111 |
February | 672.00000 | 21.35456 | 20.80841 | -0.5064 | 12.31293 |
March | 744.00000 | 21.47982 | 24.43153 | -0.4199 | 10.53025 |
April | 720.00000 | 21.96863 | 26.11206 | -0.2276 | 8.39689 |
May | 744.00000 | 22.93337 | 35.99466 | -0.8601 | 23.99016 |
June | 720.00000 | 23.22959 | 50.17987 | -0.6499 | 16.47553 |
July | 744.00000 | 23.61826 | 55.69226 | -0.4478 | 10.60085 |
August | 744.00000 | 23.41600 | 55.12413 | -0.5334 | 13.05507 |
September | 720.00000 | 22.68071 | 45.09160 | -0.8909 | 25.35410 |
October | 744.00000 | 21.71156 | 34.21540 | -0.2479 | 8.70375 |
November | 720.00000 | 21.23692 | 27.88389 | -0.4847 | 11.01548 |
December | 744.00000 | 21.00408 | 20.37955 | -0.6742 | 15.24415 |
Annual Sum or Average | 8760.00000 | 22.14032 | 34.63252 | -0.5515 | 14.28235 |
Minimum of Months | 672.00000 | 20.99213 | 18.68545 | -0.8909 | 8.39689 |
Maximum of Months | 744.00000 | 23.61826 | 55.69226 | -0.2276 | 25.35410 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.98947 | 19.73917 | -0.5504 | 11.51968 |
February | 672.00000 | 21.14240 | 21.87144 | -0.4800 | 10.01770 |
March | 744.00000 | 21.32264 | 25.33764 | -0.4017 | 8.67520 |
April | 720.00000 | 21.86998 | 26.68208 | -0.2417 | 6.82626 |
May | 744.00000 | 22.65219 | 37.08744 | -0.9895 | 26.79635 |
June | 720.00000 | 22.85792 | 51.51161 | -0.8196 | 20.23875 |
July | 744.00000 | 23.17312 | 57.44590 | -0.6615 | 14.76813 |
August | 744.00000 | 23.05391 | 56.67265 | -0.7140 | 16.41631 |
September | 720.00000 | 22.60787 | 45.70872 | -0.9524 | 25.05995 |
October | 744.00000 | 21.89983 | 34.43972 | -0.1867 | 6.43994 |
November | 720.00000 | 21.31265 | 28.41530 | -0.3877 | 8.39951 |
December | 744.00000 | 21.03226 | 21.35954 | -0.5296 | 11.00728 |
Annual Sum or Average | 8760.00000 | 21.99799 | 35.60678 | -0.5768 | 13.86449 |
Minimum of Months | 672.00000 | 20.98947 | 19.73917 | -0.9895 | 6.43994 |
Maximum of Months | 744.00000 | 23.17312 | 57.44590 | -0.1867 | 26.79635 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99973 | 13.62849 | 0.67967 | 15.57570 |
February | 672.00000 | 23.99978 | 15.47898 | 0.71841 | 16.68924 |
March | 744.00000 | 23.99980 | 18.51157 | 0.76607 | 18.17703 |
April | 720.00000 | 23.99981 | 20.12443 | 0.81642 | 19.81780 |
May | 744.00000 | 23.99980 | 30.70481 | 0.29872 | 8.69856 |
June | 720.00000 | 23.99977 | 44.35512 | 0.41550 | 10.38237 |
July | 744.00000 | 23.99984 | 50.67184 | 0.47109 | 11.23748 |
August | 744.00000 | 23.99988 | 49.66030 | 0.45283 | 10.96735 |
September | 720.00000 | 23.99982 | 38.41159 | 0.34139 | 9.15556 |
October | 744.00000 | 23.99983 | 27.04896 | 0.86497 | 21.56371 |
November | 720.00000 | 23.99988 | 21.10926 | 0.78683 | 18.84248 |
December | 744.00000 | 23.99976 | 14.97085 | 0.69416 | 15.99186 |
Annual Sum or Average | 8760.00000 | 23.99981 | 28.80692 | 0.60814 | 14.74468 |
Minimum of Months | 672.00000 | 23.99973 | 13.62849 | 0.29872 | 8.69856 |
Maximum of Months | 744.00000 | 23.99988 | 50.67184 | 0.86497 | 21.56371 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.02199 | 21.95722 | -0.5531 | 12.09775 |
February | 672.00000 | 21.31379 | 23.99458 | -0.4025 | 9.77890 |
March | 744.00000 | 21.46467 | 27.49544 | -0.3150 | 8.33972 |
April | 720.00000 | 21.84336 | 29.06500 | -0.1568 | 6.93877 |
May | 744.00000 | 22.26157 | 40.22049 | -0.9483 | 26.02670 |
June | 720.00000 | 22.39730 | 55.11630 | -0.7891 | 20.00206 |
July | 744.00000 | 22.67955 | 61.26067 | -0.6232 | 14.62063 |
August | 744.00000 | 22.65435 | 60.24901 | -0.6494 | 15.95951 |
September | 720.00000 | 22.31497 | 48.81029 | -0.8817 | 23.98511 |
October | 744.00000 | 21.79236 | 36.86580 | -0.1326 | 7.27187 |
November | 720.00000 | 21.32207 | 30.66629 | -0.3582 | 8.50940 |
December | 744.00000 | 21.02570 | 23.61443 | -0.5580 | 11.96047 |
Annual Sum or Average | 8760.00000 | 21.84390 | 38.36477 | -0.5315 | 13.81218 |
Minimum of Months | 672.00000 | 21.02199 | 21.95722 | -0.9483 | 6.93877 |
Maximum of Months | 744.00000 | 22.67955 | 61.26067 | -0.1326 | 26.02670 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.20017 | 22.18019 | -0.4655 | 9.85057 |
February | 672.00000 | 21.49695 | 24.19700 | -0.3604 | 8.15705 |
March | 744.00000 | 21.77144 | 27.54472 | -0.2633 | 6.98759 |
April | 720.00000 | 22.34154 | 28.88161 | -0.0957 | 5.82289 |
May | 744.00000 | 22.91861 | 39.44228 | -0.8515 | 21.36824 |
June | 720.00000 | 23.07501 | 53.67270 | -0.6939 | 16.15812 |
July | 744.00000 | 23.29967 | 59.74170 | -0.5626 | 12.25072 |
August | 744.00000 | 23.25875 | 58.80122 | -0.5894 | 13.01251 |
September | 720.00000 | 22.97351 | 47.63641 | -0.7794 | 18.76053 |
October | 744.00000 | 22.41318 | 36.35091 | -0.0294 | 5.91715 |
November | 720.00000 | 21.80748 | 30.46385 | -0.2403 | 6.75618 |
December | 744.00000 | 21.26409 | 23.76552 | -0.4425 | 9.43612 |
Annual Sum or Average | 8760.00000 | 22.32259 | 37.80761 | -0.4485 | 11.22422 |
Minimum of Months | 672.00000 | 21.20017 | 22.18019 | -0.8515 | 5.82289 |
Maximum of Months | 744.00000 | 23.29967 | 59.74170 | -0.0294 | 21.36824 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.42612 | 21.67995 | -0.8639 | 21.26442 |
February | 672.00000 | 20.69666 | 23.83225 | -0.7332 | 17.19205 |
March | 744.00000 | 20.85759 | 28.27733 | -0.6208 | 14.16647 |
April | 720.00000 | 21.28504 | 32.75024 | -0.4105 | 9.74993 |
May | 744.00000 | 21.69776 | 41.48682 | -1.2650 | 40.01908 |
June | 720.00000 | 21.74007 | 51.68778 | -1.1526 | 34.63795 |
July | 744.00000 | 21.77871 | 53.49385 | -1.0821 | 31.54553 |
August | 744.00000 | 21.72973 | 54.80527 | -1.1374 | 33.97713 |
September | 720.00000 | 21.58086 | 50.81265 | -1.3051 | 41.87120 |
October | 744.00000 | 21.10948 | 42.36454 | -0.4281 | 9.92615 |
November | 720.00000 | 20.70320 | 33.12301 | -0.6632 | 14.92509 |
December | 744.00000 | 20.42274 | 23.41371 | -0.8591 | 21.10031 |
Annual Sum or Average | 8760.00000 | 21.17114 | 38.21830 | -0.8779 | 24.24349 |
Minimum of Months | 672.00000 | 20.42274 | 21.67995 | -1.3051 | 9.74993 |
Maximum of Months | 744.00000 | 21.77871 | 54.80527 | -0.4105 | 41.87120 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.34373 | 21.79421 | -0.9159 | 23.35699 |
February | 672.00000 | 20.47876 | 24.16973 | -0.8200 | 19.80890 |
March | 744.00000 | 20.60523 | 28.66275 | -0.7108 | 16.44827 |
April | 720.00000 | 21.16458 | 32.99318 | -0.4672 | 10.91049 |
May | 744.00000 | 22.13976 | 41.19294 | -1.1612 | 37.30634 |
June | 720.00000 | 22.48429 | 51.07771 | -0.9463 | 29.14684 |
July | 744.00000 | 22.65396 | 53.47394 | -0.8379 | 25.48172 |
August | 744.00000 | 22.46253 | 55.07511 | -0.9443 | 28.63314 |
September | 720.00000 | 21.80752 | 51.04971 | -1.2762 | 41.55899 |
October | 744.00000 | 20.97264 | 42.77063 | -0.4846 | 10.74554 |
November | 720.00000 | 20.52336 | 33.45538 | -0.7236 | 16.60842 |
December | 744.00000 | 20.38555 | 23.49778 | -0.8933 | 22.47683 |
Annual Sum or Average | 8760.00000 | 21.34045 | 38.34115 | -0.8486 | 23.55974 |
Minimum of Months | 672.00000 | 20.34373 | 21.79421 | -1.2762 | 10.74554 |
Maximum of Months | 744.00000 | 22.65396 | 55.07511 | -0.4672 | 41.55899 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.28012 | 20.37002 | -0.8342 | 20.59620 |
February | 672.00000 | 20.59438 | 23.04367 | -0.7258 | 16.61736 |
March | 744.00000 | 20.78715 | 27.65330 | -0.6327 | 13.79490 |
April | 720.00000 | 21.18826 | 32.02474 | -0.4682 | 9.84375 |
May | 744.00000 | 21.80394 | 40.52940 | -1.3448 | 43.41589 |
June | 720.00000 | 22.12338 | 50.97672 | -1.1452 | 34.02321 |
July | 744.00000 | 22.22688 | 55.37089 | -1.0741 | 30.91366 |
August | 744.00000 | 22.07639 | 55.54439 | -1.1485 | 33.96694 |
September | 720.00000 | 21.58836 | 49.43114 | -1.3860 | 45.15734 |
October | 744.00000 | 21.15417 | 41.38200 | -0.4225 | 8.88147 |
November | 720.00000 | 20.82976 | 32.21985 | -0.5925 | 12.74115 |
December | 744.00000 | 20.39325 | 22.17707 | -0.7923 | 19.01821 |
Annual Sum or Average | 8760.00000 | 21.25730 | 37.64010 | -0.8817 | 24.12727 |
Minimum of Months | 672.00000 | 20.28012 | 20.37002 | -1.3860 | 8.88147 |
Maximum of Months | 744.00000 | 22.22688 | 55.54439 | -0.4225 | 45.15734 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.40275 | 21.65074 | -0.8682 | 21.45555 |
February | 672.00000 | 20.69351 | 23.82461 | -0.7338 | 17.10410 |
March | 744.00000 | 20.94645 | 28.13373 | -0.6016 | 13.73981 |
April | 720.00000 | 21.40989 | 32.64001 | -0.3762 | 9.32646 |
May | 744.00000 | 21.74501 | 41.28520 | -1.2555 | 39.57145 |
June | 720.00000 | 21.77821 | 50.95125 | -1.1283 | 33.62439 |
July | 744.00000 | 21.79742 | 52.90010 | -1.0769 | 31.39548 |
August | 744.00000 | 21.75236 | 54.51647 | -1.1359 | 33.90719 |
September | 720.00000 | 21.60273 | 50.73647 | -1.3005 | 41.67312 |
October | 744.00000 | 21.12291 | 42.21761 | -0.4294 | 9.92359 |
November | 720.00000 | 20.68984 | 33.12400 | -0.6651 | 14.97058 |
December | 744.00000 | 20.41656 | 23.39074 | -0.8593 | 21.14579 |
Annual Sum or Average | 8760.00000 | 21.19870 | 38.02075 | -0.8703 | 24.03303 |
Minimum of Months | 672.00000 | 20.40275 | 21.65074 | -1.3005 | 9.32646 |
Maximum of Months | 744.00000 | 21.79742 | 54.51647 | -0.3762 | 41.67312 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.31903 | 21.73983 | -0.9218 | 23.63849 |
February | 672.00000 | 20.46128 | 24.16353 | -0.8245 | 19.91641 |
March | 744.00000 | 20.66467 | 28.51454 | -0.6982 | 15.97736 |
April | 720.00000 | 21.29987 | 32.78141 | -0.4315 | 10.01161 |
May | 744.00000 | 22.05173 | 40.98084 | -1.1925 | 37.12041 |
June | 720.00000 | 22.42634 | 50.54812 | -0.9500 | 27.90963 |
July | 744.00000 | 22.62190 | 53.15598 | -0.8469 | 24.87490 |
August | 744.00000 | 22.34068 | 55.14050 | -0.9848 | 28.41149 |
September | 720.00000 | 21.72777 | 51.01814 | -1.3019 | 41.66744 |
October | 744.00000 | 20.97137 | 42.64782 | -0.4899 | 10.71166 |
November | 720.00000 | 20.52228 | 33.43538 | -0.7236 | 16.65353 |
December | 744.00000 | 20.37474 | 23.44927 | -0.8954 | 22.59483 |
Annual Sum or Average | 8760.00000 | 21.32019 | 38.20428 | -0.8554 | 23.30994 |
Minimum of Months | 672.00000 | 20.31903 | 21.73983 | -1.3019 | 10.01161 |
Maximum of Months | 744.00000 | 22.62190 | 55.14050 | -0.4315 | 41.66744 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.36562 | 22.00573 | -0.9355 | 24.04506 |
February | 672.00000 | 20.60899 | 24.26340 | -0.8011 | 19.44331 |
March | 744.00000 | 20.77181 | 28.78144 | -0.6770 | 15.86926 |
April | 720.00000 | 21.20552 | 33.33603 | -0.4491 | 10.73627 |
May | 744.00000 | 21.67517 | 41.99356 | -1.2782 | 40.91107 |
June | 720.00000 | 21.72579 | 52.60598 | -1.1550 | 34.99913 |
July | 744.00000 | 21.76609 | 54.68077 | -1.0820 | 31.78567 |
August | 744.00000 | 21.70588 | 56.34475 | -1.1443 | 34.50519 |
September | 720.00000 | 21.53340 | 52.14703 | -1.3363 | 43.60457 |
October | 744.00000 | 21.01046 | 43.30168 | -0.4747 | 11.04196 |
November | 720.00000 | 20.60903 | 33.81998 | -0.7234 | 16.73706 |
December | 744.00000 | 20.39113 | 23.78077 | -0.9226 | 23.52765 |
Annual Sum or Average | 8760.00000 | 21.11653 | 38.99780 | -0.9159 | 25.64105 |
Minimum of Months | 672.00000 | 20.36562 | 22.00573 | -1.3363 | 10.73627 |
Maximum of Months | 744.00000 | 21.76609 | 56.34475 | -0.4491 | 43.60457 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.27047 | 22.09227 | -0.9908 | 26.46269 |
February | 672.00000 | 20.43834 | 24.55140 | -0.8811 | 22.02453 |
March | 744.00000 | 20.55104 | 29.15569 | -0.7638 | 18.17782 |
April | 720.00000 | 21.09724 | 33.59396 | -0.5053 | 12.06560 |
May | 744.00000 | 22.19178 | 41.56284 | -1.1478 | 38.05429 |
June | 720.00000 | 22.55642 | 51.53602 | -0.9163 | 29.69468 |
July | 744.00000 | 22.70602 | 53.91663 | -0.8129 | 26.06176 |
August | 744.00000 | 22.51083 | 55.86792 | -0.9252 | 29.24593 |
September | 720.00000 | 21.78312 | 52.28653 | -1.3005 | 43.36769 |
October | 744.00000 | 20.86496 | 43.76317 | -0.5353 | 12.02496 |
November | 720.00000 | 20.46220 | 34.12081 | -0.7792 | 18.43351 |
December | 744.00000 | 20.34362 | 23.85574 | -0.9590 | 25.09639 |
Annual Sum or Average | 8760.00000 | 21.32012 | 38.93206 | -0.8764 | 25.07499 |
Minimum of Months | 672.00000 | 20.27047 | 22.09227 | -1.3005 | 12.02496 |
Maximum of Months | 744.00000 | 22.70602 | 55.86792 | -0.5053 | 43.36769 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.80640 | 23.54871 | -0.7258 | 17.41901 |
February | 672.00000 | 21.12846 | 25.65562 | -0.5775 | 13.87171 |
March | 744.00000 | 21.18505 | 29.92089 | -0.5073 | 12.09367 |
April | 720.00000 | 21.44814 | 34.07907 | -0.3596 | 9.22415 |
May | 744.00000 | 21.70733 | 42.27290 | -1.2982 | 41.75468 |
June | 720.00000 | 21.72720 | 52.38104 | -1.2038 | 37.07651 |
July | 744.00000 | 21.75850 | 54.83139 | -1.1415 | 34.27776 |
August | 744.00000 | 21.71957 | 55.25385 | -1.1703 | 35.63254 |
September | 720.00000 | 21.62838 | 50.43211 | -1.2900 | 41.40345 |
October | 744.00000 | 21.27159 | 42.82625 | -0.3653 | 9.17286 |
November | 720.00000 | 20.99950 | 34.39173 | -0.5578 | 12.81939 |
December | 744.00000 | 20.70242 | 25.25395 | -0.7541 | 18.08042 |
Annual Sum or Average | 8760.00000 | 21.34074 | 39.30965 | -0.8311 | 23.63143 |
Minimum of Months | 672.00000 | 20.70242 | 23.54871 | -1.2982 | 9.17286 |
Maximum of Months | 744.00000 | 21.75850 | 55.25385 | -0.3596 | 41.75468 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.29003 | 21.88083 | -0.4393 | 9.88056 |
February | 672.00000 | 21.53221 | 23.99655 | -0.3422 | 8.06796 |
March | 744.00000 | 21.77664 | 27.34342 | -0.2342 | 6.84070 |
April | 720.00000 | 22.18931 | 28.75843 | -0.0781 | 5.85865 |
May | 744.00000 | 22.74059 | 39.52113 | -0.7879 | 19.38636 |
June | 720.00000 | 22.92085 | 53.73775 | -0.6039 | 13.78778 |
July | 744.00000 | 22.97848 | 60.30615 | -0.5303 | 11.73910 |
August | 744.00000 | 22.87528 | 59.61135 | -0.5912 | 13.30064 |
September | 720.00000 | 22.61542 | 48.12346 | -0.7961 | 19.57240 |
October | 744.00000 | 22.19059 | 36.49097 | -0.0315 | 5.76234 |
November | 720.00000 | 21.84460 | 30.20101 | -0.1975 | 6.55236 |
December | 744.00000 | 21.42623 | 23.42482 | -0.3908 | 8.94868 |
Annual Sum or Average | 8760.00000 | 22.20170 | 37.86976 | -0.4192 | 10.82369 |
Minimum of Months | 672.00000 | 21.29003 | 21.88083 | -0.7961 | 5.76234 |
Maximum of Months | 744.00000 | 22.97848 | 60.30615 | -0.0315 | 19.57240 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.47996 | 21.72372 | -0.3567 | 8.66341 |
February | 672.00000 | 21.77294 | 23.77983 | -0.2496 | 7.10922 |
March | 744.00000 | 22.08787 | 27.01954 | -0.1267 | 6.18236 |
April | 720.00000 | 22.55368 | 28.35580 | 0.03635 | 5.72482 |
May | 744.00000 | 23.02341 | 38.98829 | -0.6636 | 15.40739 |
June | 720.00000 | 23.17456 | 53.01324 | -0.4912 | 11.02522 |
July | 744.00000 | 23.22422 | 59.50071 | -0.4213 | 9.43340 |
August | 744.00000 | 23.12560 | 58.81243 | -0.4807 | 10.67721 |
September | 720.00000 | 22.90666 | 47.42475 | -0.6688 | 15.51916 |
October | 744.00000 | 22.57083 | 35.90208 | 0.08734 | 5.86364 |
November | 720.00000 | 22.18375 | 29.78812 | -0.0824 | 6.02349 |
December | 744.00000 | 21.62455 | 23.23448 | -0.3058 | 7.92818 |
Annual Sum or Average | 8760.00000 | 22.48063 | 37.38058 | -0.3109 | 9.14154 |
Minimum of Months | 672.00000 | 21.47996 | 21.72372 | -0.6688 | 5.72482 |
Maximum of Months | 744.00000 | 23.22422 | 59.50071 | 0.08734 | 15.51916 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.85208 | 23.75153 | 0.80610 | 21.06322 |
February | 672.00000 | 23.94003 | 24.35922 | 0.87590 | 23.05581 |
March | 744.00000 | 23.97939 | 26.64578 | 0.94776 | 25.55478 |
April | 720.00000 | 23.99075 | 27.58937 | 1.02857 | 28.82679 |
May | 744.00000 | 23.99104 | 37.64794 | 0.61723 | 17.01042 |
June | 720.00000 | 23.99156 | 50.86351 | 0.75344 | 20.64239 |
July | 744.00000 | 23.99182 | 57.00694 | 0.81247 | 22.51661 |
August | 744.00000 | 23.99164 | 56.06457 | 0.76838 | 20.99789 |
September | 720.00000 | 23.99125 | 45.16471 | 0.63041 | 16.84477 |
October | 744.00000 | 23.99100 | 34.39319 | 1.05630 | 29.93165 |
November | 720.00000 | 23.99084 | 29.02104 | 0.95672 | 25.66517 |
December | 744.00000 | 23.89976 | 24.61913 | 0.82889 | 21.49840 |
Annual Sum or Average | 8760.00000 | 23.96672 | 36.50745 | 0.83986 | 22.79643 |
Minimum of Months | 672.00000 | 23.85208 | 23.75153 | 0.61723 | 16.84477 |
Maximum of Months | 744.00000 | 23.99182 | 57.00694 | 1.05630 | 29.93165 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.76832 | 16.52717 | -0.6915 | 15.46570 |
February | 672.00000 | 20.96509 | 18.69063 | -0.6154 | 13.05450 |
March | 744.00000 | 20.99801 | 22.38730 | -0.5637 | 11.72269 |
April | 720.00000 | 21.03099 | 24.50797 | -0.4948 | 10.24398 |
May | 744.00000 | 21.52065 | 36.01453 | -1.4146 | 46.62242 |
June | 720.00000 | 21.88267 | 51.22087 | -1.1932 | 35.43428 |
July | 744.00000 | 22.20237 | 57.61817 | -1.0397 | 28.02241 |
August | 744.00000 | 22.01140 | 56.89404 | -1.1136 | 31.35135 |
September | 720.00000 | 21.50347 | 45.26217 | -1.3639 | 43.84470 |
October | 744.00000 | 21.07851 | 32.79969 | -0.4239 | 8.88456 |
November | 720.00000 | 21.00032 | 25.58305 | -0.5287 | 10.93203 |
December | 744.00000 | 20.89689 | 18.09982 | -0.6490 | 14.06479 |
Annual Sum or Average | 8760.00000 | 21.32413 | 33.89348 | -0.8423 | 22.51871 |
Minimum of Months | 672.00000 | 20.76832 | 16.52717 | -1.4146 | 8.88456 |
Maximum of Months | 744.00000 | 22.20237 | 57.61817 | -0.4239 | 46.62242 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.96870 | 20.82370 | -0.6038 | 12.73854 |
February | 672.00000 | 20.99958 | 23.04941 | -0.5650 | 11.73661 |
March | 744.00000 | 21.02349 | 26.74470 | -0.5236 | 10.78488 |
April | 720.00000 | 21.37860 | 28.38211 | -0.4081 | 8.79495 |
May | 744.00000 | 22.37999 | 38.60447 | -1.1661 | 34.42004 |
June | 720.00000 | 22.84170 | 52.75849 | -0.9144 | 23.44274 |
July | 744.00000 | 23.32092 | 58.31756 | -0.7071 | 15.72366 |
August | 744.00000 | 22.93833 | 58.24943 | -0.8455 | 20.45264 |
September | 720.00000 | 22.17265 | 47.90847 | -1.1813 | 35.06950 |
October | 744.00000 | 21.25467 | 36.71458 | -0.3926 | 8.50918 |
November | 720.00000 | 21.00268 | 29.88114 | -0.5184 | 10.68527 |
December | 744.00000 | 20.98995 | 22.44634 | -0.5910 | 12.39867 |
Annual Sum or Average | 8760.00000 | 21.77812 | 37.07456 | -0.7019 | 17.08015 |
Minimum of Months | 672.00000 | 20.96870 | 20.82370 | -1.1813 | 8.50918 |
Maximum of Months | 744.00000 | 23.32092 | 58.31756 | -0.3926 | 35.06950 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.90035 | 19.82010 | -0.6584 | 14.38571 |
February | 672.00000 | 21.01381 | 22.40477 | -0.5859 | 12.34078 |
March | 744.00000 | 21.14803 | 26.18429 | -0.5046 | 10.54665 |
April | 720.00000 | 21.96012 | 27.45127 | -0.2689 | 7.48594 |
May | 744.00000 | 23.48161 | 36.14892 | -0.7831 | 19.25579 |
June | 720.00000 | 23.83637 | 49.27937 | -0.5543 | 11.87347 |
July | 744.00000 | 23.94440 | 55.10783 | -0.4639 | 9.64653 |
August | 744.00000 | 23.86141 | 54.66344 | -0.5122 | 10.77879 |
September | 720.00000 | 23.26097 | 45.02490 | -0.8103 | 19.89100 |
October | 744.00000 | 21.82011 | 35.45105 | -0.2534 | 7.35404 |
November | 720.00000 | 21.05093 | 29.44863 | -0.5109 | 10.59653 |
December | 744.00000 | 20.95933 | 21.58816 | -0.6322 | 13.56661 |
Annual Sum or Average | 8760.00000 | 22.27729 | 35.29133 | -0.5446 | 12.30824 |
Minimum of Months | 672.00000 | 20.90035 | 19.82010 | -0.8103 | 7.35404 |
Maximum of Months | 744.00000 | 23.94440 | 55.10783 | -0.2534 | 19.89100 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.94165 | 16.28224 | -0.6382 | 13.75113 |
February | 672.00000 | 21.11534 | 18.88724 | -0.5646 | 11.85837 |
March | 744.00000 | 21.41460 | 23.18705 | -0.4580 | 9.87977 |
April | 720.00000 | 22.75756 | 28.06152 | -0.1101 | 6.01336 |
May | 744.00000 | 23.84791 | 35.26830 | -0.7360 | 16.89670 |
June | 720.00000 | 23.99646 | 48.04904 | -0.5760 | 12.10616 |
July | 744.00000 | 23.99990 | 53.57242 | -0.5148 | 10.58408 |
August | 744.00000 | 23.99826 | 52.60317 | -0.5347 | 11.03067 |
September | 720.00000 | 23.92580 | 43.59682 | -0.6516 | 14.10668 |
October | 744.00000 | 23.14885 | 35.97557 | 0.03788 | 5.55880 |
November | 720.00000 | 21.80570 | 27.80473 | -0.3332 | 7.97415 |
December | 744.00000 | 21.01188 | 17.97498 | -0.6055 | 12.82555 |
Annual Sum or Average | 8760.00000 | 22.67137 | 33.52050 | -0.4736 | 11.05308 |
Minimum of Months | 672.00000 | 20.94165 | 16.28224 | -0.7360 | 5.55880 |
Maximum of Months | 744.00000 | 23.99990 | 53.57242 | 0.03788 | 16.89670 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.524884E+09 | 8542.29 | 19-JAN-19:05 | 134.69 | 0.163550E+10 | 0.00 | 0.216038E+10 | 0.56 | 3.12 | 01-JAN-16:12 | 0.00 | 0.00 |
February | 0.100989E+10 | 11824.83 | 28-FEB-16:11 | 191.61 | 0.314676E+10 | 0.00 | 0.415666E+10 | 0.89 | 3.12 | 01-FEB-13:10 | 0.00 | 0.00 |
March | 0.219838E+10 | 24258.41 | 31-MAR-18:01 | 362.88 | 0.685000E+10 | 0.00 | 0.904838E+10 | 1.52 | 3.12 | 01-MAR-03:40 | 0.00 | 0.00 |
April | 0.149490E+11 | 103442.78 | 23-APR-18:03 | 507.77 | 0.451085E+11 | 0.00 | 0.600575E+11 | 2.18 | 3.56 | 23-APR-18:03 | 0.00 | 0.00 |
May | 0.666184E+11 | 136810.95 | 25-MAY-18:03 | 723.70 | 0.200751E+12 | 0.00 | 0.267369E+12 | 2.96 | 3.73 | 26-MAY-08:53 | 0.00 | 0.00 |
June | 0.126163E+12 | 187840.03 | 29-JUN-18:03 | 718.64 | 0.408035E+12 | 0.00 | 0.534198E+12 | 3.13 | 4.18 | 19-JUN-18:03 | 0.00 | 0.00 |
July | 0.164462E+12 | 161854.24 | 15-JUL-15:13 | 744.00 | 0.551846E+12 | 0.00 | 0.716308E+12 | 3.23 | 4.20 | 15-JUL-21:53 | 0.00 | 0.00 |
August | 0.124069E+12 | 161725.52 | 08-AUG-15:13 | 740.96 | 0.403477E+12 | 0.00 | 0.527547E+12 | 3.12 | 4.15 | 09-AUG-21:52 | 0.00 | 0.00 |
September | 0.445579E+11 | 119140.08 | 01-SEP-15:13 | 656.99 | 0.134116E+12 | 0.00 | 0.178674E+12 | 2.79 | 3.98 | 01-SEP-08:52 | 0.00 | 0.00 |
October | 0.108565E+11 | 71358.79 | 19-OCT-15:13 | 386.55 | 0.326191E+11 | 0.00 | 0.434756E+11 | 1.61 | 3.28 | 19-OCT-15:13 | 0.00 | 0.00 |
November | 0.178942E+10 | 24285.16 | 01-NOV-15:15 | 309.81 | 0.546780E+10 | 0.00 | 0.725722E+10 | 1.34 | 3.12 | 02-NOV-06:00 | 0.00 | 0.00 |
December | 0.486343E+09 | 5757.26 | 05-DEC-19:05 | 138.58 | 0.151541E+10 | 0.00 | 0.200176E+10 | 0.58 | 3.12 | 01-DEC-10:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.557685E+12 | 5616.18 | 0.179457E+13 | 0.00 | 0.235225E+13 | 2.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.486343E+09 | 5757.26 | 134.69 | 0.151541E+10 | 0.00 | 0.200176E+10 | 0.56 | 3.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.164462E+12 | 187840.03 | 744.00 | 0.551846E+12 | 0.00 | 0.716308E+12 | 3.23 | 4.20 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.512912E+12 | 0.00 | 744.00 | 564694.64 | 06-JAN-05:10 | 0.00 | 39.63 | 60.00 | 2.16 | 0.00 | 0.27 | 0.78 | 06-JAN-05:10 |
February | 0.278454E+12 | 0.00 | 672.00 | 535904.87 | 17-FEB-07:05 | 0.00 | 39.61 | 60.00 | 1.32 | 0.00 | 0.16 | 0.74 | 17-FEB-07:05 |
March | 0.168947E+12 | 0.00 | 744.00 | 497078.78 | 05-MAR-07:00 | 0.00 | 41.56 | 60.00 | 0.79 | 0.00 | 0.09 | 0.69 | 05-MAR-07:00 |
April | 0.877057E+11 | 0.00 | 653.67 | 187377.81 | 03-APR-15:11 | 0.00 | 38.81 | 58.17 | 0.37 | 0.00 | 0.05 | 0.26 | 03-APR-15:11 |
May | 0.256769E+11 | 0.00 | 278.91 | 134835.07 | 01-MAY-08:03 | 0.00 | 32.32 | 42.71 | 0.08 | 0.00 | 0.01 | 0.19 | 01-MAY-08:03 |
June | 0.485676E+10 | 0.00 | 115.94 | 86620.20 | 04-JUN-05:00 | 0.00 | 35.01 | 38.81 | 0.02 | 0.00 | 0.00 | 0.12 | 04-JUN-05:00 |
July | 0.919582E+09 | 0.00 | 34.63 | 52200.82 | 08-JUL-08:04 | 0.00 | 32.52 | 33.96 | 0.00 | 0.00 | 0.00 | 0.07 | 08-JUL-08:04 |
August | 0.156789E+10 | 0.00 | 74.48 | 56953.68 | 19-AUG-05:00 | 0.00 | 36.98 | 39.05 | 0.01 | 0.00 | 0.00 | 0.08 | 19-AUG-05:00 |
September | 0.215487E+11 | 0.00 | 342.63 | 83744.06 | 06-SEP-04:00 | 0.00 | 38.65 | 49.10 | 0.08 | 0.00 | 0.01 | 0.12 | 06-SEP-04:00 |
October | 0.110329E+12 | 0.00 | 678.83 | 202880.09 | 31-OCT-15:12 | 0.00 | 38.17 | 58.68 | 0.43 | 0.00 | 0.06 | 0.28 | 31-OCT-15:12 |
November | 0.141041E+12 | 0.00 | 720.00 | 201933.96 | 03-NOV-15:11 | 0.00 | 40.59 | 60.00 | 0.66 | 0.00 | 0.08 | 0.28 | 03-NOV-15:11 |
December | 0.453406E+12 | 0.00 | 744.00 | 547614.09 | 24-DEC-06:00 | 0.00 | 40.38 | 60.00 | 1.96 | 0.00 | 0.23 | 0.76 | 24-DEC-06:00 |
Annual Sum or Average | 0.180736E+13 | 0.00 | 5803.08 | 0.00 | 37.83 | 51.64 | 0.66 | 0.00 | 0.08 | ||||
Minimum of Months | 0.919582E+09 | 0.00 | 34.63 | 52200.82 | 0.00 | 32.32 | 33.96 | 0.00 | 0.00 | 0.00 | 0.07 | ||
Maximum of Months | 0.512912E+12 | 0.00 | 744.00 | 564694.64 | 0.00 | 41.56 | 60.00 | 2.16 | 0.00 | 0.27 | 0.78 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.105698E+09 | 0.00 | 98.72 | 0.105698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3942.09 | 20-JAN-06:10 | 3942.09 | 20-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.108495E+09 | 0.00 | 97.04 | 0.108495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3977.83 | 07-FEB-06:10 | 3977.83 | 07-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.232678E+09 | 0.00 | 228.03 | 0.232678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4084.58 | 21-MAR-05:10 | 4084.58 | 21-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.144203E+11 | 0.00 | 215.93 | 0.144161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 189040.31 | 23-APR-18:10 | 185640.82 | 23-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.107254E+12 | 0.00 | 338.75 | 0.104452E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 272129.39 | 25-MAY-18:10 | 225810.13 | 25-MAY-18:10 | 0.00 | 0.00 | 0.00 |
June | 0.270368E+12 | 0.00 | 508.67 | 0.193695E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 439955.23 | 27-JUN-20:06 | 249692.90 | 29-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.374330E+12 | 0.00 | 614.67 | 0.249030E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 458860.11 | 21-JUL-19:34 | 225527.29 | 24-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.261078E+12 | 0.00 | 574.92 | 0.185393E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 423481.20 | 31-AUG-19:40 | 218132.47 | 08-AUG-18:10 | 0.00 | 0.00 | 0.00 |
September | 0.620193E+11 | 0.00 | 243.33 | 0.533830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 267661.56 | 01-SEP-10:40 | 191143.87 | 01-SEP-17:15 | 0.00 | 0.00 | 0.00 |
October | 0.886005E+10 | 0.00 | 107.43 | 0.886005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 133772.46 | 19-OCT-15:13 | 133772.46 | 19-OCT-15:13 | 0.00 | 0.00 | 0.00 |
November | 0.141186E+10 | 0.00 | 235.21 | 0.141186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58562.84 | 01-NOV-15:30 | 58562.84 | 01-NOV-15:30 | 0.00 | 0.00 | 0.00 |
December | 0.128478E+09 | 0.00 | 118.51 | 0.128478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3966.47 | 05-DEC-06:10 | 3966.47 | 05-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110032E+13 | 0.00 | 3381.22 | 0.811217E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.105698E+09 | 0.00 | 97.04 | 0.105698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3942.09 | 3942.09 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.374330E+12 | 0.00 | 614.67 | 0.249030E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 458860.11 | 249692.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 |
April | 0.763587E+09 | 0.00 | 38.50 | 0.763587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17053.28 | 23-APR-15:11 | 17053.28 | 23-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.659458E+10 | 0.00 | 216.33 | 0.634057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23288.14 | 26-MAY-12:20 | 18450.51 | 25-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.186341E+11 | 0.00 | 350.17 | 0.123181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37981.96 | 25-JUN-08:03 | 20654.95 | 29-JUN-15:12 | 0.00 | 0.00 | 0.00 |
July | 0.270719E+11 | 0.00 | 444.83 | 0.162218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40076.05 | 22-JUL-21:50 | 19265.14 | 15-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.183407E+11 | 0.00 | 418.17 | 0.117833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36048.40 | 31-AUG-20:50 | 19164.84 | 08-AUG-15:12 | 0.00 | 0.00 | 0.00 |
September | 0.363760E+10 | 0.00 | 140.33 | 0.291203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24121.93 | 01-SEP-01:00 | 17391.20 | 01-SEP-15:12 | 0.00 | 0.00 | 0.00 |
October | 0.479896E+09 | 0.00 | 22.67 | 0.479896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14460.52 | 19-OCT-15:15 | 14460.52 | 19-OCT-15:15 | 0.00 | 0.00 | 0.00 |
November | 71139999.81 | 0.00 | 4.33 | 71139999.81 | 0.00 | 0.00 | 0.00 | 0.00 | 6910.52 | 01-NOV-15:15 | 6910.52 | 01-NOV-15:15 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.755935E+11 | 0.00 | 1635.33 | 0.508904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.270719E+11 | 0.00 | 444.83 | 0.162218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40076.05 | 20654.95 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 576587.25 | 0.00 | 0.15 | 576587.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2127.90 | 25-JAN-16:13 | 2127.90 | 25-JAN-16:13 | 0.00 | 0.00 | 0.00 |
February | 0.100233E+09 | 0.00 | 16.73 | 0.100205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17150.35 | 20-FEB-16:11 | 17150.35 | 20-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.441316E+09 | 0.00 | 55.68 | 0.441091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17170.59 | 28-MAR-18:01 | 17170.59 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.179877E+10 | 0.00 | 210.84 | 0.166337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17166.29 | 16-APR-15:11 | 17166.29 | 16-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.531758E+10 | 0.00 | 553.67 | 0.368461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17169.05 | 04-MAY-15:11 | 17169.05 | 04-MAY-15:11 | 0.00 | 0.00 | 0.00 |
June | 0.713460E+10 | 0.00 | 615.03 | 0.398970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18438.24 | 10-JUN-15:12 | 17172.15 | 16-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.967590E+10 | 0.00 | 688.78 | 0.525845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18772.70 | 05-JUL-08:61 | 15302.23 | 08-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.758180E+10 | 0.00 | 641.82 | 0.384697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18518.86 | 30-AUG-08:62 | 15296.20 | 22-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.335929E+10 | 0.00 | 444.98 | 0.177421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18005.20 | 19-SEP-15:12 | 17170.05 | 09-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.867826E+09 | 0.00 | 129.17 | 0.498135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17155.65 | 09-OCT-15:11 | 17155.65 | 09-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 13855068.35 | 0.00 | 3.87 | 12404617.13 | 0.00 | 0.00 | 0.00 | 0.00 | 17088.53 | 17-NOV-16:11 | 17088.53 | 17-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362918E+11 | 0.00 | 3360.71 | 0.212697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.967590E+10 | 0.00 | 688.78 | 0.525845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18772.70 | 17172.15 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 203760.26 | 0.00 | 0.05 | 203760.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1333.53 | 17-JAN-16:15 | 1333.53 | 17-JAN-16:15 | 0.00 | 0.00 | 0.00 |
February | 11755755.52 | 0.00 | 3.46 | 11709929.21 | 0.00 | 0.00 | 0.00 | 0.00 | 13054.66 | 20-FEB-16:11 | 13054.66 | 20-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.163525E+09 | 0.00 | 24.41 | 0.163517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16333.60 | 28-MAR-18:01 | 16333.60 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.865157E+09 | 0.00 | 130.66 | 0.776315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18300.45 | 11-APR-18:11 | 18300.45 | 11-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.352509E+10 | 0.00 | 430.91 | 0.228153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18870.44 | 06-MAY-18:42 | 18870.44 | 06-MAY-18:42 | 0.00 | 0.00 | 0.00 |
June | 0.514921E+10 | 0.00 | 463.55 | 0.275147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19395.25 | 25-JUN-08:51 | 16269.52 | 03-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.701261E+10 | 0.00 | 508.49 | 0.368741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19664.69 | 23-JUL-08:51 | 16585.47 | 04-JUL-16:51 | 0.00 | 0.00 | 0.00 |
August | 0.478518E+10 | 0.00 | 463.09 | 0.218859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17816.54 | 30-AUG-08:51 | 16521.07 | 07-AUG-16:21 | 0.00 | 0.00 | 0.00 |
September | 0.154628E+10 | 0.00 | 296.22 | 0.613921E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18203.09 | 04-SEP-18:01 | 18203.09 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.201909E+09 | 0.00 | 49.43 | 90515347.77 | 0.00 | 0.00 | 0.00 | 0.00 | 12444.76 | 22-OCT-18:01 | 12444.76 | 22-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 2307953.19 | 0.00 | 0.47 | 1393522.33 | 0.00 | 0.00 | 0.00 | 0.00 | 4444.69 | 17-NOV-16:11 | 4444.69 | 17-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232632E+11 | 0.00 | 2370.74 | 0.125666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.701261E+10 | 0.00 | 508.49 | 0.368741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19664.69 | 18870.44 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 |
March | 0.338553E+09 | 0.00 | 14.89 | 0.338553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16999.94 | 31-MAR-14:00 | 16999.94 | 31-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.109050E+11 | 0.00 | 196.86 | 0.105041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41034.30 | 22-APR-13:25 | 41034.30 | 22-APR-13:25 | 0.00 | 0.00 | 0.00 |
May | 0.258428E+11 | 0.00 | 562.12 | 0.166617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43927.37 | 18-MAY-13:00 | 37979.21 | 06-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.325771E+11 | 0.00 | 621.72 | 0.140531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46491.08 | 30-JUN-13:00 | 35254.66 | 30-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.441483E+11 | 0.00 | 715.30 | 0.183475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48818.79 | 23-JUL-13:00 | 39453.29 | 23-JUL-13:20 | 0.00 | 0.00 | 0.00 |
August | 0.403474E+11 | 0.00 | 698.35 | 0.178582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52418.07 | 26-AUG-12:40 | 48024.08 | 25-AUG-13:10 | 0.00 | 0.00 | 0.00 |
September | 0.257927E+11 | 0.00 | 486.63 | 0.156021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53315.96 | 01-SEP-12:50 | 49238.59 | 01-SEP-13:15 | 0.00 | 0.00 | 0.00 |
October | 0.106619E+11 | 0.00 | 181.97 | 0.893898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61255.13 | 22-OCT-12:30 | 53741.66 | 21-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 33569458.44 | 0.00 | 2.50 | 33569458.44 | 0.00 | 0.00 | 0.00 | 0.00 | 5537.80 | 17-NOV-13:50 | 5537.80 | 17-NOV-13:50 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190647E+12 | 0.00 | 3480.34 | 0.102338E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.441483E+11 | 0.00 | 715.30 | 0.183475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61255.13 | 53741.66 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 5419342.82 | 0.00 | 0.22 | 5419342.82 | 0.00 | 0.00 | 0.00 | 0.00 | 12212.33 | 19-JAN-19:05 | 12212.33 | 19-JAN-19:05 | 0.00 | 0.00 | 0.00 |
February | 8881578.90 | 0.00 | 0.40 | 8881578.90 | 0.00 | 0.00 | 0.00 | 0.00 | 13506.43 | 04-FEB-19:04 | 13506.43 | 04-FEB-19:04 | 0.00 | 0.00 | 0.00 |
March | 0.228060E+09 | 0.00 | 19.50 | 0.227569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73033.05 | 28-MAR-18:01 | 73033.05 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.439332E+10 | 0.00 | 181.39 | 0.385817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77528.39 | 18-APR-18:01 | 77528.39 | 18-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.257823E+11 | 0.00 | 431.93 | 0.186459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80896.07 | 26-MAY-21:51 | 80889.33 | 21-MAY-21:01 | 0.00 | 0.00 | 0.00 |
June | 0.390232E+11 | 0.00 | 432.53 | 0.250568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92271.33 | 25-JUN-08:51 | 80169.24 | 02-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.460042E+11 | 0.00 | 449.95 | 0.281483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93144.29 | 23-JUL-08:51 | 75732.77 | 01-JUL-21:01 | 0.00 | 0.00 | 0.00 |
August | 0.354048E+11 | 0.00 | 411.95 | 0.197949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88766.57 | 28-AUG-21:52 | 74727.85 | 01-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.176811E+11 | 0.00 | 405.32 | 0.869101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84201.58 | 18-SEP-21:52 | 80669.44 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.328661E+10 | 0.00 | 184.90 | 0.156909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74952.97 | 20-OCT-18:12 | 74952.97 | 20-OCT-18:12 | 0.00 | 0.00 | 0.00 |
November | 0.302753E+09 | 0.00 | 22.65 | 0.128320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57440.85 | 01-NOV-18:03 | 51654.21 | 01-NOV-18:03 | 0.00 | 0.00 | 0.00 |
December | 2449030.34 | 0.00 | 0.14 | 2257700.47 | 0.00 | 0.00 | 0.00 | 0.00 | 7294.80 | 05-DEC-19:05 | 7294.80 | 05-DEC-19:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172123E+12 | 0.00 | 2540.87 | 0.106137E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2449030.34 | 0.00 | 0.14 | 2257700.47 | 0.00 | 0.00 | 0.00 | 0.00 | 7294.80 | 7294.80 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.460042E+11 | 0.00 | 449.95 | 0.281483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93144.29 | 80889.33 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 31834544.95 | 0.00 | 8.27 | 31756787.44 | 0.00 | 0.00 | 0.00 | 0.00 | 14592.14 | 28-FEB-16:11 | 14592.14 | 28-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.254572E+09 | 0.00 | 53.45 | 0.252438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15550.03 | 26-MAR-15:11 | 15550.03 | 26-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.181072E+10 | 0.00 | 249.36 | 0.165511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15551.68 | 23-APR-08:61 | 15551.68 | 23-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.497958E+10 | 0.00 | 573.47 | 0.333952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15552.85 | 05-MAY-08:62 | 15552.85 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.761738E+10 | 0.00 | 646.12 | 0.435415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16713.91 | 10-JUN-15:12 | 15554.16 | 03-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.970825E+10 | 0.00 | 707.12 | 0.532950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16588.75 | 05-JUL-08:61 | 13917.22 | 25-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.731243E+10 | 0.00 | 660.47 | 0.365109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16416.19 | 28-AUG-15:11 | 13871.92 | 21-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.327934E+10 | 0.00 | 436.26 | 0.170317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16291.69 | 19-SEP-15:12 | 15553.96 | 05-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.789884E+09 | 0.00 | 125.13 | 0.435123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15325.48 | 09-OCT-08:62 | 15325.48 | 09-OCT-08:62 | 0.00 | 0.00 | 0.00 |
November | 50862081.70 | 0.00 | 11.18 | 46405957.03 | 0.00 | 0.00 | 0.00 | 0.00 | 10861.22 | 17-NOV-16:11 | 10861.22 | 17-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 339408.52 | 0.00 | 0.06 | 339408.52 | 0.00 | 0.00 | 0.00 | 0.00 | 2001.80 | 28-DEC-09:05 | 2001.80 | 28-DEC-09:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.358352E+11 | 0.00 | 3470.88 | 0.207986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.970825E+10 | 0.00 | 707.12 | 0.532950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16713.91 | 15554.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 867006.87 | 0.00 | 0.25 | 867006.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2338.34 | 27-FEB-09:03 | 2338.34 | 27-FEB-09:03 | 0.00 | 0.00 | 0.00 |
March | 61306422.80 | 0.00 | 15.48 | 60884784.93 | 0.00 | 0.00 | 0.00 | 0.00 | 13892.22 | 26-MAR-08:61 | 13892.22 | 26-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.870020E+09 | 0.00 | 149.56 | 0.776947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14728.59 | 19-APR-08:62 | 14728.59 | 19-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.343298E+10 | 0.00 | 451.81 | 0.219562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15545.57 | 26-MAY-08:51 | 14813.42 | 06-MAY-19:01 | 0.00 | 0.00 | 0.00 |
June | 0.573225E+10 | 0.00 | 500.84 | 0.325150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19192.48 | 25-JUN-08:32 | 15249.31 | 27-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.705803E+10 | 0.00 | 518.58 | 0.380916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18977.00 | 29-JUL-08:32 | 16282.97 | 31-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.472233E+10 | 0.00 | 482.72 | 0.219574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17127.91 | 30-AUG-08:51 | 14839.32 | 20-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.169552E+10 | 0.00 | 305.31 | 0.800863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16754.14 | 01-SEP-08:51 | 15077.03 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.192685E+09 | 0.00 | 38.52 | 0.101713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14015.59 | 09-OCT-08:62 | 14015.59 | 09-OCT-08:62 | 0.00 | 0.00 | 0.00 |
November | 2230084.32 | 0.00 | 0.56 | 1404267.61 | 0.00 | 0.00 | 0.00 | 0.00 | 3016.58 | 20-NOV-19:04 | 2771.84 | 17-NOV-09:03 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237682E+11 | 0.00 | 2463.65 | 0.131947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.705803E+10 | 0.00 | 518.58 | 0.380916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19192.48 | 16282.97 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 135789.03 | 0.00 | 0.13 | 135789.03 | 0.00 | 0.00 | 0.00 | 0.00 | 606.86 | 27-JAN-16:13 | 606.86 | 27-JAN-16:13 | 0.00 | 0.00 | 0.00 |
February | 24958704.74 | 0.00 | 14.30 | 24930690.12 | 0.00 | 0.00 | 0.00 | 0.00 | 4467.21 | 20-FEB-16:11 | 4467.21 | 20-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.116408E+09 | 0.00 | 50.31 | 0.116368E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4472.45 | 28-MAR-18:01 | 4472.45 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.467533E+09 | 0.00 | 184.45 | 0.436326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4471.48 | 16-APR-15:11 | 4471.48 | 16-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.136565E+10 | 0.00 | 501.96 | 0.979146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4472.08 | 04-MAY-15:11 | 4472.08 | 04-MAY-15:11 | 0.00 | 0.00 | 0.00 |
June | 0.181015E+10 | 0.00 | 580.95 | 0.105313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4952.01 | 24-JUN-08:62 | 4472.69 | 01-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.241749E+10 | 0.00 | 677.14 | 0.134552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5083.24 | 05-JUL-08:61 | 3978.65 | 27-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.186408E+10 | 0.00 | 626.34 | 0.988520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4943.20 | 30-AUG-08:62 | 3993.63 | 22-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.788824E+09 | 0.00 | 373.69 | 0.445245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4735.70 | 19-SEP-15:12 | 4472.86 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.213878E+09 | 0.00 | 104.16 | 0.130451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4471.86 | 21-OCT-18:01 | 4471.86 | 21-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 3120197.47 | 0.00 | 2.89 | 2887157.89 | 0.00 | 0.00 | 0.00 | 0.00 | 4466.96 | 17-NOV-16:11 | 4466.96 | 17-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.907223E+10 | 0.00 | 3116.32 | 0.552266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.241749E+10 | 0.00 | 677.14 | 0.134552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5083.24 | 4472.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 1395516.65 | 0.00 | 2.44 | 1395516.65 | 0.00 | 0.00 | 0.00 | 0.00 | 1694.23 | 08-FEB-16:11 | 1694.23 | 08-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 40629923.79 | 0.00 | 23.96 | 40603906.21 | 0.00 | 0.00 | 0.00 | 0.00 | 4236.04 | 28-MAR-18:01 | 4236.04 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.221170E+09 | 0.00 | 107.54 | 0.202037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4872.98 | 11-APR-18:11 | 4872.98 | 11-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.918867E+09 | 0.00 | 391.85 | 0.615740E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5356.98 | 06-MAY-18:42 | 5356.98 | 06-MAY-18:42 | 0.00 | 0.00 | 0.00 |
June | 0.134982E+10 | 0.00 | 442.79 | 0.750134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5123.07 | 25-JUN-08:51 | 4237.35 | 20-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.181110E+10 | 0.00 | 505.91 | 0.982041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5187.71 | 23-JUL-08:51 | 4295.99 | 04-JUL-16:51 | 0.00 | 0.00 | 0.00 |
August | 0.120464E+10 | 0.00 | 453.27 | 0.571477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4697.04 | 30-AUG-08:51 | 4312.19 | 02-AUG-20:21 | 0.00 | 0.00 | 0.00 |
September | 0.338271E+09 | 0.00 | 241.94 | 0.144910E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4803.41 | 23-SEP-17:41 | 4803.41 | 23-SEP-17:41 | 0.00 | 0.00 | 0.00 |
October | 43666045.90 | 0.00 | 39.64 | 19667213.29 | 0.00 | 0.00 | 0.00 | 0.00 | 3241.29 | 22-OCT-18:01 | 3241.29 | 22-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 362477.91 | 0.00 | 0.29 | 265454.80 | 0.00 | 0.00 | 0.00 | 0.00 | 781.11 | 09-NOV-16:13 | 781.11 | 09-NOV-16:13 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.592993E+10 | 0.00 | 2209.64 | 0.332827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.181110E+10 | 0.00 | 505.91 | 0.982041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5356.98 | 5356.98 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.323399E+09 | 0.00 | 35.78 | 0.323290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22024.39 | 27-JAN-16:11 | 22024.39 | 27-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.111138E+10 | 0.00 | 104.23 | 0.110570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22055.58 | 04-FEB-16:11 | 22055.58 | 04-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.165535E+10 | 0.00 | 140.43 | 0.162998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22064.76 | 27-MAR-15:11 | 22064.76 | 27-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.339383E+10 | 0.00 | 286.71 | 0.313936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22064.25 | 29-APR-15:11 | 22064.25 | 29-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.681295E+10 | 0.00 | 554.24 | 0.452709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22061.90 | 13-MAY-18:01 | 22061.90 | 13-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.875297E+10 | 0.00 | 603.66 | 0.459928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24983.73 | 19-JUN-18:01 | 22057.94 | 16-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.117806E+11 | 0.00 | 677.70 | 0.609328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25384.88 | 25-JUL-18:02 | 19522.43 | 03-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.106068E+11 | 0.00 | 643.85 | 0.552291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24359.82 | 30-AUG-08:62 | 19688.22 | 27-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.626533E+10 | 0.00 | 491.31 | 0.371754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23296.15 | 19-SEP-15:12 | 22062.57 | 05-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.306306E+10 | 0.00 | 217.74 | 0.216190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22058.34 | 21-OCT-18:01 | 22058.34 | 21-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.773152E+09 | 0.00 | 70.11 | 0.761880E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22055.07 | 16-NOV-16:11 | 22055.07 | 16-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.152216E+09 | 0.00 | 21.37 | 0.152076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21483.11 | 02-DEC-16:12 | 21483.11 | 02-DEC-16:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.546911E+11 | 0.00 | 3847.13 | 0.337343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.152216E+09 | 0.00 | 21.37 | 0.152076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21483.11 | 19522.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.117806E+11 | 0.00 | 677.70 | 0.609328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25384.88 | 22064.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 811.78 | 565.87 | 245.91 | 693.60 | 864.46 | 0.00 | 0.00 | 0.00 |
February | 1013.41 | 681.99 | 331.42 | 977.07 | 728.03 | 0.00 | 0.00 | 0.00 |
March | 890.53 | 560.55 | 329.97 | 882.24 | 599.29 | 0.00 | 0.00 | 0.00 |
April | 812.99 | 440.64 | 372.35 | 881.16 | 393.86 | 0.00 | 0.00 | 0.00 |
May | 695.72 | 245.17 | 450.55 | 829.78 | 215.41 | 0.00 | 0.00 | 0.00 |
June | 611.25 | 160.71 | 450.54 | 779.60 | 141.72 | 0.00 | 0.00 | 0.00 |
July | 672.54 | 213.67 | 458.88 | 893.40 | 131.05 | 0.00 | 0.00 | 0.00 |
August | 713.81 | 296.54 | 417.27 | 919.78 | 153.42 | 0.00 | 0.00 | 0.00 |
September | 753.16 | 394.00 | 359.16 | 896.04 | 246.32 | 0.00 | 0.00 | 0.00 |
October | 669.97 | 399.48 | 270.49 | 705.01 | 375.39 | 0.00 | 0.00 | 0.00 |
November | 585.27 | 367.08 | 218.19 | 535.88 | 553.05 | 0.00 | 0.00 | 0.00 |
December | 623.49 | 409.18 | 214.31 | 490.42 | 838.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 736.08 | 392.80 | 343.28 | 788.98 | 435.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 585.27 | 160.71 | 214.31 | 490.42 | 131.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1013.41 | 681.99 | 458.88 | 977.07 | 864.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2285.91 | 1593.44 | 692.47 | 1943.78 | 2433.49 | 0.00 | 0.00 | 0.00 |
February | 2853.71 | 1920.44 | 933.26 | 2744.09 | 2046.65 | 0.00 | 0.00 | 0.00 |
March | 2507.67 | 1578.48 | 929.18 | 2480.60 | 1687.98 | 0.00 | 0.00 | 0.00 |
April | 2289.34 | 1240.82 | 1048.51 | 2484.54 | 1103.43 | 0.00 | 0.00 | 0.00 |
May | 1959.10 | 690.38 | 1268.72 | 2369.94 | 579.51 | 0.00 | 0.00 | 0.00 |
June | 1721.24 | 452.54 | 1268.70 | 2239.69 | 370.13 | 0.00 | 0.00 | 0.00 |
July | 1893.84 | 601.67 | 1292.17 | 2563.78 | 333.27 | 0.00 | 0.00 | 0.00 |
August | 2010.04 | 835.05 | 1174.99 | 2623.36 | 398.22 | 0.00 | 0.00 | 0.00 |
September | 2120.84 | 1109.47 | 1011.36 | 2536.31 | 673.45 | 0.00 | 0.00 | 0.00 |
October | 1886.59 | 1124.92 | 761.67 | 1979.37 | 1058.77 | 0.00 | 0.00 | 0.00 |
November | 1648.08 | 1033.68 | 614.40 | 1501.93 | 1563.56 | 0.00 | 0.00 | 0.00 |
December | 1755.72 | 1152.23 | 603.49 | 1373.25 | 2361.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2072.75 | 1106.11 | 966.64 | 2233.06 | 1213.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1648.08 | 452.54 | 603.49 | 1373.25 | 333.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2853.71 | 1920.44 | 1292.17 | 2744.09 | 2433.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2969.53 | 2069.97 | 899.55 | 2550.12 | 3265.22 | 0.00 | 0.00 | 0.00 |
February | 3707.13 | 2494.77 | 1212.36 | 3615.23 | 2748.03 | 0.00 | 0.00 | 0.00 |
March | 3257.60 | 2050.54 | 1207.06 | 3269.60 | 2279.84 | 0.00 | 0.00 | 0.00 |
April | 2973.98 | 1611.90 | 1362.08 | 3272.05 | 1512.86 | 0.00 | 0.00 | 0.00 |
May | 2544.98 | 896.84 | 1648.14 | 3106.10 | 810.60 | 0.00 | 0.00 | 0.00 |
June | 2235.99 | 587.87 | 1648.12 | 2927.88 | 528.08 | 0.00 | 0.00 | 0.00 |
July | 2460.21 | 781.61 | 1678.60 | 3358.87 | 473.05 | 0.00 | 0.00 | 0.00 |
August | 2611.16 | 1084.78 | 1526.38 | 3440.39 | 563.21 | 0.00 | 0.00 | 0.00 |
September | 2755.09 | 1441.27 | 1313.82 | 3326.81 | 943.03 | 0.00 | 0.00 | 0.00 |
October | 2450.78 | 1461.33 | 989.45 | 2596.11 | 1466.31 | 0.00 | 0.00 | 0.00 |
November | 2140.94 | 1342.81 | 798.13 | 1970.62 | 2139.86 | 0.00 | 0.00 | 0.00 |
December | 2280.78 | 1496.82 | 783.96 | 1797.77 | 3183.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2692.62 | 1436.90 | 1255.72 | 2931.05 | 1654.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2140.94 | 587.87 | 783.96 | 1797.77 | 473.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3707.13 | 2494.77 | 1678.60 | 3615.23 | 3265.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.50 | 111.88 | 48.62 | 138.71 | 175.45 | 0.00 | 0.00 | 0.00 |
February | 200.37 | 134.84 | 65.53 | 194.82 | 146.77 | 0.00 | 0.00 | 0.00 |
March | 176.07 | 110.83 | 65.24 | 176.35 | 120.31 | 0.00 | 0.00 | 0.00 |
April | 160.74 | 87.12 | 73.62 | 175.75 | 77.96 | 0.00 | 0.00 | 0.00 |
May | 137.56 | 48.47 | 89.08 | 166.22 | 39.70 | 0.00 | 0.00 | 0.00 |
June | 120.86 | 31.77 | 89.08 | 157.78 | 24.23 | 0.00 | 0.00 | 0.00 |
July | 132.97 | 42.25 | 90.73 | 181.07 | 21.01 | 0.00 | 0.00 | 0.00 |
August | 141.13 | 58.63 | 82.50 | 185.21 | 25.01 | 0.00 | 0.00 | 0.00 |
September | 148.91 | 77.90 | 71.01 | 179.29 | 45.45 | 0.00 | 0.00 | 0.00 |
October | 132.46 | 78.98 | 53.48 | 141.13 | 73.25 | 0.00 | 0.00 | 0.00 |
November | 115.72 | 72.58 | 43.14 | 107.31 | 110.59 | 0.00 | 0.00 | 0.00 |
December | 123.28 | 80.90 | 42.37 | 97.98 | 170.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 145.54 | 77.66 | 67.87 | 158.21 | 85.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.72 | 31.77 | 42.37 | 97.98 | 21.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.37 | 134.84 | 90.73 | 194.82 | 175.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.01 | 41.05 | 55.96 | 40.94 | 378.77 | 0.00 | 0.00 | 0.00 |
February | 156.96 | 72.03 | 84.93 | 102.70 | 304.90 | 0.00 | 0.00 | 0.00 |
March | 205.96 | 105.66 | 100.30 | 166.27 | 236.52 | 0.00 | 0.00 | 0.00 |
April | 262.85 | 133.36 | 129.49 | 257.85 | 142.93 | 0.00 | 0.00 | 0.00 |
May | 323.25 | 154.70 | 168.56 | 380.14 | 71.83 | 0.00 | 0.00 | 0.00 |
June | 310.57 | 134.16 | 176.41 | 391.97 | 44.32 | 0.00 | 0.00 | 0.00 |
July | 332.01 | 154.43 | 177.58 | 432.61 | 38.72 | 0.00 | 0.00 | 0.00 |
August | 272.54 | 123.52 | 149.02 | 343.19 | 46.28 | 0.00 | 0.00 | 0.00 |
September | 213.96 | 96.07 | 117.89 | 237.71 | 84.31 | 0.00 | 0.00 | 0.00 |
October | 135.30 | 54.44 | 80.85 | 115.86 | 141.62 | 0.00 | 0.00 | 0.00 |
November | 82.31 | 27.98 | 54.34 | 42.76 | 226.22 | 0.00 | 0.00 | 0.00 |
December | 72.55 | 25.13 | 47.42 | 22.21 | 366.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.71 | 93.67 | 112.03 | 211.84 | 173.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.55 | 25.13 | 47.42 | 22.21 | 38.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.01 | 154.70 | 177.58 | 432.61 | 378.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.13 | 0.00 | 23.13 | 0.15 | 218.95 | 0.00 | 0.00 | 0.00 |
February | 35.53 | 0.00 | 35.53 | 2.66 | 174.01 | 0.00 | 0.00 | 0.00 |
March | 43.72 | 0.00 | 43.72 | 7.80 | 132.99 | 0.00 | 0.00 | 0.00 |
April | 57.49 | 0.59 | 56.90 | 28.84 | 77.66 | 0.00 | 0.00 | 0.00 |
May | 80.61 | 4.26 | 76.35 | 75.90 | 36.82 | 0.00 | 0.00 | 0.00 |
June | 90.08 | 10.00 | 80.09 | 104.77 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 86.13 | 7.54 | 78.59 | 104.62 | 21.31 | 0.00 | 0.00 | 0.00 |
August | 65.41 | 1.24 | 64.17 | 71.86 | 25.93 | 0.00 | 0.00 | 0.00 |
September | 50.93 | 0.05 | 50.88 | 41.97 | 46.50 | 0.00 | 0.00 | 0.00 |
October | 35.31 | 0.00 | 35.31 | 14.98 | 77.60 | 0.00 | 0.00 | 0.00 |
November | 23.38 | 0.00 | 23.38 | 2.27 | 126.72 | 0.00 | 0.00 | 0.00 |
December | 19.60 | 0.00 | 19.60 | 0.00 | 209.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 1.98 | 49.04 | 38.20 | 97.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.60 | 0.00 | 19.60 | 0.00 | 21.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.08 | 10.00 | 80.09 | 104.77 | 218.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.01 | 41.05 | 55.96 | 42.15 | 376.74 | 0.00 | 0.00 | 0.00 |
February | 156.96 | 72.03 | 84.93 | 106.05 | 302.25 | 0.00 | 0.00 | 0.00 |
March | 205.96 | 105.66 | 100.30 | 170.09 | 234.03 | 0.00 | 0.00 | 0.00 |
April | 262.85 | 133.36 | 129.49 | 261.35 | 141.90 | 0.00 | 0.00 | 0.00 |
May | 323.25 | 154.70 | 168.56 | 378.92 | 73.35 | 0.00 | 0.00 | 0.00 |
June | 310.57 | 134.16 | 176.41 | 387.88 | 46.83 | 0.00 | 0.00 | 0.00 |
July | 332.01 | 154.43 | 177.58 | 428.27 | 41.76 | 0.00 | 0.00 | 0.00 |
August | 272.54 | 123.52 | 149.02 | 341.01 | 49.45 | 0.00 | 0.00 | 0.00 |
September | 213.96 | 96.07 | 117.89 | 238.62 | 84.79 | 0.00 | 0.00 | 0.00 |
October | 135.30 | 54.44 | 80.85 | 118.51 | 140.27 | 0.00 | 0.00 | 0.00 |
November | 82.31 | 27.98 | 54.34 | 44.80 | 224.39 | 0.00 | 0.00 | 0.00 |
December | 72.55 | 25.13 | 47.42 | 22.95 | 364.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.71 | 93.67 | 112.03 | 212.35 | 172.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.55 | 25.13 | 47.42 | 22.95 | 41.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.01 | 154.70 | 177.58 | 428.27 | 376.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.38 | 89.49 | 38.89 | 114.68 | 124.93 | 0.00 | 0.00 | 0.00 |
February | 160.26 | 107.85 | 52.41 | 158.02 | 109.01 | 0.00 | 0.00 | 0.00 |
March | 140.83 | 88.65 | 52.18 | 140.23 | 95.97 | 0.00 | 0.00 | 0.00 |
April | 128.57 | 69.68 | 58.88 | 132.69 | 77.35 | 0.00 | 0.00 | 0.00 |
May | 110.02 | 38.77 | 71.25 | 122.64 | 45.42 | 0.00 | 0.00 | 0.00 |
June | 96.67 | 25.41 | 71.25 | 114.51 | 31.55 | 0.00 | 0.00 | 0.00 |
July | 106.36 | 33.79 | 72.57 | 133.75 | 28.44 | 0.00 | 0.00 | 0.00 |
August | 112.88 | 46.90 | 65.99 | 137.97 | 33.98 | 0.00 | 0.00 | 0.00 |
September | 119.11 | 62.31 | 56.80 | 133.73 | 52.87 | 0.00 | 0.00 | 0.00 |
October | 105.95 | 63.18 | 42.78 | 105.59 | 73.95 | 0.00 | 0.00 | 0.00 |
November | 92.56 | 58.05 | 34.50 | 84.70 | 88.58 | 0.00 | 0.00 | 0.00 |
December | 98.60 | 64.71 | 33.89 | 81.88 | 118.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.41 | 62.12 | 54.29 | 121.46 | 73.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 92.56 | 25.41 | 33.89 | 81.88 | 28.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.26 | 107.85 | 72.57 | 158.02 | 124.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.51 | 0.00 | 18.51 | 0.07 | 179.21 | 0.00 | 0.00 | 0.00 |
February | 28.43 | 0.00 | 28.43 | 1.84 | 142.74 | 0.00 | 0.00 | 0.00 |
March | 34.98 | 0.00 | 34.98 | 5.90 | 108.55 | 0.00 | 0.00 | 0.00 |
April | 46.00 | 0.47 | 45.53 | 23.83 | 62.55 | 0.00 | 0.00 | 0.00 |
May | 64.50 | 3.41 | 61.09 | 64.06 | 28.57 | 0.00 | 0.00 | 0.00 |
June | 72.08 | 8.00 | 64.08 | 87.46 | 18.01 | 0.00 | 0.00 | 0.00 |
July | 68.91 | 6.03 | 62.88 | 87.97 | 15.62 | 0.00 | 0.00 | 0.00 |
August | 52.34 | 0.99 | 51.35 | 60.82 | 19.37 | 0.00 | 0.00 | 0.00 |
September | 40.75 | 0.04 | 40.71 | 35.13 | 36.45 | 0.00 | 0.00 | 0.00 |
October | 28.25 | 0.00 | 28.25 | 11.54 | 63.73 | 0.00 | 0.00 | 0.00 |
November | 18.71 | 0.00 | 18.71 | 1.51 | 105.52 | 0.00 | 0.00 | 0.00 |
December | 15.68 | 0.00 | 15.68 | 0.00 | 172.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.82 | 1.59 | 39.24 | 31.87 | 79.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.68 | 0.00 | 15.68 | 0.00 | 15.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 72.08 | 8.00 | 64.08 | 87.97 | 179.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.39 | 39.13 | 55.27 | 34.30 | 373.59 | 0.00 | 0.00 | 0.00 |
February | 150.02 | 64.51 | 85.51 | 86.25 | 294.84 | 0.00 | 0.00 | 0.00 |
March | 203.96 | 102.55 | 101.41 | 155.61 | 228.71 | 0.00 | 0.00 | 0.00 |
April | 280.91 | 151.46 | 129.45 | 276.09 | 137.09 | 0.00 | 0.00 | 0.00 |
May | 305.09 | 134.58 | 170.51 | 351.76 | 67.08 | 0.00 | 0.00 | 0.00 |
June | 344.27 | 164.69 | 179.58 | 435.29 | 42.28 | 0.00 | 0.00 | 0.00 |
July | 337.96 | 159.02 | 178.94 | 438.22 | 36.54 | 0.00 | 0.00 | 0.00 |
August | 260.13 | 113.70 | 146.43 | 324.02 | 44.57 | 0.00 | 0.00 | 0.00 |
September | 208.87 | 93.73 | 115.14 | 228.51 | 81.50 | 0.00 | 0.00 | 0.00 |
October | 125.75 | 47.28 | 78.46 | 99.82 | 137.95 | 0.00 | 0.00 | 0.00 |
November | 80.54 | 26.81 | 53.72 | 37.72 | 222.29 | 0.00 | 0.00 | 0.00 |
December | 74.04 | 27.78 | 46.26 | 21.48 | 362.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.70 | 93.84 | 111.86 | 208.01 | 168.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.04 | 26.81 | 46.26 | 21.48 | 36.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 344.27 | 164.69 | 179.58 | 438.22 | 373.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.50 | 111.88 | 48.62 | 138.57 | 175.22 | 0.00 | 0.00 | 0.00 |
February | 200.37 | 134.84 | 65.53 | 194.51 | 146.46 | 0.00 | 0.00 | 0.00 |
March | 176.07 | 110.83 | 65.24 | 175.36 | 119.89 | 0.00 | 0.00 | 0.00 |
April | 160.74 | 87.12 | 73.62 | 174.32 | 77.66 | 0.00 | 0.00 | 0.00 |
May | 137.56 | 48.47 | 89.08 | 165.68 | 39.26 | 0.00 | 0.00 | 0.00 |
June | 120.86 | 31.77 | 89.08 | 156.67 | 23.94 | 0.00 | 0.00 | 0.00 |
July | 132.97 | 42.25 | 90.73 | 180.45 | 20.56 | 0.00 | 0.00 | 0.00 |
August | 141.13 | 58.63 | 82.50 | 184.88 | 24.66 | 0.00 | 0.00 | 0.00 |
September | 148.91 | 77.90 | 71.01 | 178.84 | 45.03 | 0.00 | 0.00 | 0.00 |
October | 132.46 | 78.98 | 53.48 | 140.90 | 72.91 | 0.00 | 0.00 | 0.00 |
November | 115.72 | 72.58 | 43.14 | 107.19 | 110.44 | 0.00 | 0.00 | 0.00 |
December | 123.28 | 80.90 | 42.37 | 97.83 | 170.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 145.54 | 77.66 | 67.87 | 157.67 | 85.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.72 | 31.77 | 42.37 | 97.83 | 20.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.37 | 134.84 | 90.73 | 194.51 | 175.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.13 | 0.00 | 23.13 | 0.15 | 218.80 | 0.00 | 0.00 | 0.00 |
February | 35.53 | 0.00 | 35.53 | 2.54 | 173.88 | 0.00 | 0.00 | 0.00 |
March | 43.72 | 0.00 | 43.72 | 7.25 | 132.83 | 0.00 | 0.00 | 0.00 |
April | 57.49 | 0.59 | 56.90 | 27.58 | 77.62 | 0.00 | 0.00 | 0.00 |
May | 80.61 | 4.26 | 76.35 | 75.92 | 36.20 | 0.00 | 0.00 | 0.00 |
June | 90.08 | 10.00 | 80.09 | 103.88 | 23.13 | 0.00 | 0.00 | 0.00 |
July | 86.13 | 7.54 | 78.59 | 104.01 | 20.57 | 0.00 | 0.00 | 0.00 |
August | 65.41 | 1.24 | 64.17 | 71.82 | 25.07 | 0.00 | 0.00 | 0.00 |
September | 50.93 | 0.05 | 50.88 | 41.59 | 45.66 | 0.00 | 0.00 | 0.00 |
October | 35.31 | 0.00 | 35.31 | 14.64 | 77.06 | 0.00 | 0.00 | 0.00 |
November | 23.38 | 0.00 | 23.38 | 2.21 | 126.72 | 0.00 | 0.00 | 0.00 |
December | 19.60 | 0.00 | 19.60 | 0.00 | 209.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 1.98 | 49.04 | 37.85 | 96.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.60 | 0.00 | 19.60 | 0.00 | 20.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.08 | 10.00 | 80.09 | 104.01 | 218.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.39 | 39.13 | 55.27 | 35.03 | 370.96 | 0.00 | 0.00 | 0.00 |
February | 150.02 | 64.51 | 85.51 | 88.57 | 291.04 | 0.00 | 0.00 | 0.00 |
March | 203.96 | 102.55 | 101.41 | 158.83 | 225.21 | 0.00 | 0.00 | 0.00 |
April | 280.91 | 151.46 | 129.45 | 279.25 | 135.70 | 0.00 | 0.00 | 0.00 |
May | 305.09 | 134.58 | 170.51 | 351.72 | 68.11 | 0.00 | 0.00 | 0.00 |
June | 344.27 | 164.69 | 179.58 | 432.09 | 44.49 | 0.00 | 0.00 | 0.00 |
July | 337.96 | 159.02 | 178.94 | 434.17 | 39.21 | 0.00 | 0.00 | 0.00 |
August | 260.13 | 113.70 | 146.43 | 322.77 | 46.99 | 0.00 | 0.00 | 0.00 |
September | 208.87 | 93.73 | 115.14 | 230.12 | 81.45 | 0.00 | 0.00 | 0.00 |
October | 125.75 | 47.28 | 78.46 | 102.35 | 136.18 | 0.00 | 0.00 | 0.00 |
November | 80.54 | 26.81 | 53.72 | 38.79 | 219.60 | 0.00 | 0.00 | 0.00 |
December | 74.04 | 27.78 | 46.26 | 21.89 | 360.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.70 | 93.84 | 111.86 | 208.54 | 167.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.04 | 26.81 | 46.26 | 21.89 | 39.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 344.27 | 164.69 | 179.58 | 434.17 | 370.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.29 | 0.00 | 29.29 | 0.07 | 293.78 | 0.00 | 0.00 | 0.00 |
February | 45.00 | 0.00 | 45.00 | 2.36 | 233.06 | 0.00 | 0.00 | 0.00 |
March | 55.37 | 0.00 | 55.37 | 8.38 | 176.65 | 0.00 | 0.00 | 0.00 |
April | 72.81 | 0.74 | 72.06 | 36.37 | 101.98 | 0.00 | 0.00 | 0.00 |
May | 102.09 | 5.39 | 96.70 | 99.53 | 48.75 | 0.00 | 0.00 | 0.00 |
June | 114.08 | 12.66 | 101.42 | 135.97 | 31.79 | 0.00 | 0.00 | 0.00 |
July | 109.07 | 9.55 | 99.53 | 135.04 | 29.42 | 0.00 | 0.00 | 0.00 |
August | 82.84 | 1.57 | 81.27 | 93.37 | 35.49 | 0.00 | 0.00 | 0.00 |
September | 64.50 | 0.07 | 64.44 | 53.83 | 62.34 | 0.00 | 0.00 | 0.00 |
October | 44.72 | 0.00 | 44.72 | 17.54 | 103.46 | 0.00 | 0.00 | 0.00 |
November | 29.61 | 0.00 | 29.61 | 2.24 | 171.51 | 0.00 | 0.00 | 0.00 |
December | 24.82 | 0.00 | 24.82 | 0.00 | 281.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.61 | 2.51 | 62.11 | 49.01 | 130.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.82 | 0.00 | 24.82 | 0.00 | 29.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 114.08 | 12.66 | 101.42 | 135.97 | 293.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.80 | 0.00 | 10.80 | 0.03 | 108.30 | 0.00 | 0.00 | 0.00 |
February | 16.59 | 0.00 | 16.59 | 0.87 | 85.91 | 0.00 | 0.00 | 0.00 |
March | 20.41 | 0.00 | 20.41 | 3.09 | 65.12 | 0.00 | 0.00 | 0.00 |
April | 26.84 | 0.27 | 26.57 | 13.41 | 37.59 | 0.00 | 0.00 | 0.00 |
May | 37.64 | 1.99 | 35.65 | 36.69 | 17.97 | 0.00 | 0.00 | 0.00 |
June | 42.06 | 4.67 | 37.39 | 50.12 | 11.72 | 0.00 | 0.00 | 0.00 |
July | 40.21 | 3.52 | 36.69 | 49.78 | 10.84 | 0.00 | 0.00 | 0.00 |
August | 30.54 | 0.58 | 29.96 | 34.42 | 13.08 | 0.00 | 0.00 | 0.00 |
September | 23.78 | 0.02 | 23.75 | 19.84 | 22.98 | 0.00 | 0.00 | 0.00 |
October | 16.48 | 0.00 | 16.48 | 6.47 | 38.14 | 0.00 | 0.00 | 0.00 |
November | 10.91 | 0.00 | 10.91 | 0.82 | 63.22 | 0.00 | 0.00 | 0.00 |
December | 9.15 | 0.00 | 9.15 | 0.00 | 103.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.82 | 0.93 | 22.89 | 18.07 | 48.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.15 | 0.00 | 9.15 | 0.00 | 10.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.06 | 4.67 | 37.39 | 50.12 | 108.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.89 | 52.20 | 22.69 | 63.53 | 85.24 | 0.00 | 0.00 | 0.00 |
February | 93.49 | 62.92 | 30.58 | 90.29 | 70.89 | 0.00 | 0.00 | 0.00 |
March | 82.15 | 51.71 | 30.44 | 82.19 | 57.88 | 0.00 | 0.00 | 0.00 |
April | 75.00 | 40.65 | 34.35 | 82.68 | 37.35 | 0.00 | 0.00 | 0.00 |
May | 64.18 | 22.62 | 41.57 | 78.50 | 19.76 | 0.00 | 0.00 | 0.00 |
June | 56.39 | 14.83 | 41.56 | 73.87 | 12.80 | 0.00 | 0.00 | 0.00 |
July | 62.05 | 19.71 | 42.33 | 84.45 | 11.70 | 0.00 | 0.00 | 0.00 |
August | 65.85 | 27.36 | 38.49 | 86.81 | 13.55 | 0.00 | 0.00 | 0.00 |
September | 69.48 | 36.35 | 33.13 | 84.24 | 22.69 | 0.00 | 0.00 | 0.00 |
October | 61.81 | 36.85 | 24.95 | 65.99 | 35.50 | 0.00 | 0.00 | 0.00 |
November | 53.99 | 33.86 | 20.13 | 49.54 | 54.04 | 0.00 | 0.00 | 0.00 |
December | 57.52 | 37.75 | 19.77 | 44.69 | 83.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.91 | 36.24 | 31.67 | 73.78 | 41.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.99 | 14.83 | 19.77 | 44.69 | 11.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 93.49 | 62.92 | 42.33 | 90.29 | 85.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.27 | 141.69 | 61.58 | 172.43 | 231.37 | 0.00 | 0.00 | 0.00 |
February | 253.76 | 170.77 | 82.99 | 245.07 | 192.42 | 0.00 | 0.00 | 0.00 |
March | 222.99 | 140.36 | 82.62 | 223.09 | 157.11 | 0.00 | 0.00 | 0.00 |
April | 203.57 | 110.34 | 93.24 | 224.40 | 101.38 | 0.00 | 0.00 | 0.00 |
May | 174.21 | 61.39 | 112.82 | 213.07 | 53.63 | 0.00 | 0.00 | 0.00 |
June | 153.06 | 40.24 | 112.82 | 200.51 | 34.75 | 0.00 | 0.00 | 0.00 |
July | 168.40 | 53.50 | 114.90 | 229.21 | 31.74 | 0.00 | 0.00 | 0.00 |
August | 178.74 | 74.25 | 104.48 | 235.62 | 36.77 | 0.00 | 0.00 | 0.00 |
September | 188.59 | 98.66 | 89.93 | 228.64 | 61.60 | 0.00 | 0.00 | 0.00 |
October | 167.76 | 100.03 | 67.73 | 179.10 | 96.35 | 0.00 | 0.00 | 0.00 |
November | 146.55 | 91.92 | 54.63 | 134.46 | 146.68 | 0.00 | 0.00 | 0.00 |
December | 156.12 | 102.46 | 53.66 | 121.30 | 225.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 184.31 | 98.36 | 85.96 | 200.25 | 113.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 146.55 | 40.24 | 53.66 | 121.30 | 31.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 253.76 | 170.77 | 114.90 | 245.07 | 231.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.50 | 111.88 | 48.62 | 138.43 | 175.30 | 0.00 | 0.00 | 0.00 |
February | 200.37 | 134.84 | 65.53 | 194.28 | 146.57 | 0.00 | 0.00 | 0.00 |
March | 176.07 | 110.83 | 65.24 | 176.02 | 120.02 | 0.00 | 0.00 | 0.00 |
April | 160.74 | 87.12 | 73.62 | 175.20 | 77.61 | 0.00 | 0.00 | 0.00 |
May | 137.56 | 48.47 | 89.08 | 165.29 | 39.46 | 0.00 | 0.00 | 0.00 |
June | 120.86 | 31.77 | 89.08 | 156.98 | 23.93 | 0.00 | 0.00 | 0.00 |
July | 132.97 | 42.25 | 90.73 | 180.27 | 20.66 | 0.00 | 0.00 | 0.00 |
August | 141.13 | 58.63 | 82.50 | 184.38 | 24.66 | 0.00 | 0.00 | 0.00 |
September | 148.91 | 77.90 | 71.01 | 178.64 | 45.06 | 0.00 | 0.00 | 0.00 |
October | 132.46 | 78.98 | 53.48 | 140.99 | 72.66 | 0.00 | 0.00 | 0.00 |
November | 115.72 | 72.58 | 43.14 | 107.22 | 110.08 | 0.00 | 0.00 | 0.00 |
December | 123.28 | 80.90 | 42.37 | 97.72 | 170.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 145.54 | 77.66 | 67.87 | 157.69 | 85.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.72 | 31.77 | 42.37 | 97.72 | 20.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.37 | 134.84 | 90.73 | 194.28 | 175.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.01 | 41.05 | 55.96 | 40.80 | 378.59 | 0.00 | 0.00 | 0.00 |
February | 156.96 | 72.03 | 84.93 | 102.39 | 304.66 | 0.00 | 0.00 | 0.00 |
March | 205.96 | 105.66 | 100.30 | 165.78 | 235.91 | 0.00 | 0.00 | 0.00 |
April | 262.85 | 133.36 | 129.49 | 256.74 | 142.16 | 0.00 | 0.00 | 0.00 |
May | 323.25 | 154.70 | 168.56 | 378.27 | 71.29 | 0.00 | 0.00 | 0.00 |
June | 310.57 | 134.16 | 176.41 | 390.26 | 43.73 | 0.00 | 0.00 | 0.00 |
July | 332.01 | 154.43 | 177.58 | 430.85 | 38.04 | 0.00 | 0.00 | 0.00 |
August | 272.54 | 123.52 | 149.02 | 341.76 | 45.59 | 0.00 | 0.00 | 0.00 |
September | 213.96 | 96.07 | 117.89 | 236.75 | 83.46 | 0.00 | 0.00 | 0.00 |
October | 135.30 | 54.44 | 80.85 | 115.81 | 140.38 | 0.00 | 0.00 | 0.00 |
November | 82.31 | 27.98 | 54.34 | 42.94 | 225.20 | 0.00 | 0.00 | 0.00 |
December | 72.55 | 25.13 | 47.42 | 22.10 | 366.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.71 | 93.67 | 112.03 | 211.03 | 172.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.55 | 25.13 | 47.42 | 22.10 | 38.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.01 | 154.70 | 177.58 | 430.85 | 378.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.13 | 0.00 | 23.13 | 0.15 | 218.48 | 0.00 | 0.00 | 0.00 |
February | 35.53 | 0.00 | 35.53 | 2.73 | 173.80 | 0.00 | 0.00 | 0.00 |
March | 43.72 | 0.00 | 43.72 | 7.86 | 132.75 | 0.00 | 0.00 | 0.00 |
April | 57.49 | 0.59 | 56.90 | 28.86 | 77.39 | 0.00 | 0.00 | 0.00 |
May | 80.61 | 4.26 | 76.35 | 74.98 | 36.95 | 0.00 | 0.00 | 0.00 |
June | 90.08 | 10.00 | 80.09 | 103.79 | 23.87 | 0.00 | 0.00 | 0.00 |
July | 86.13 | 7.54 | 78.59 | 103.84 | 21.43 | 0.00 | 0.00 | 0.00 |
August | 65.41 | 1.24 | 64.17 | 71.29 | 26.08 | 0.00 | 0.00 | 0.00 |
September | 50.93 | 0.05 | 50.88 | 41.93 | 46.29 | 0.00 | 0.00 | 0.00 |
October | 35.31 | 0.00 | 35.31 | 15.29 | 76.85 | 0.00 | 0.00 | 0.00 |
November | 23.38 | 0.00 | 23.38 | 2.38 | 126.03 | 0.00 | 0.00 | 0.00 |
December | 19.60 | 0.00 | 19.60 | 0.00 | 209.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 1.98 | 49.04 | 37.98 | 97.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.60 | 0.00 | 19.60 | 0.00 | 21.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.08 | 10.00 | 80.09 | 103.84 | 218.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.01 | 41.05 | 55.96 | 41.99 | 376.20 | 0.00 | 0.00 | 0.00 |
February | 156.96 | 72.03 | 84.93 | 105.68 | 302.07 | 0.00 | 0.00 | 0.00 |
March | 205.96 | 105.66 | 100.30 | 169.68 | 233.47 | 0.00 | 0.00 | 0.00 |
April | 262.85 | 133.36 | 129.49 | 260.40 | 141.19 | 0.00 | 0.00 | 0.00 |
May | 323.25 | 154.70 | 168.56 | 376.50 | 73.44 | 0.00 | 0.00 | 0.00 |
June | 310.57 | 134.16 | 176.41 | 385.37 | 47.07 | 0.00 | 0.00 | 0.00 |
July | 332.01 | 154.43 | 177.58 | 425.89 | 41.87 | 0.00 | 0.00 | 0.00 |
August | 272.54 | 123.52 | 149.02 | 339.06 | 49.66 | 0.00 | 0.00 | 0.00 |
September | 213.96 | 96.07 | 117.89 | 237.67 | 84.22 | 0.00 | 0.00 | 0.00 |
October | 135.30 | 54.44 | 80.85 | 118.75 | 138.94 | 0.00 | 0.00 | 0.00 |
November | 82.31 | 27.98 | 54.34 | 45.00 | 223.49 | 0.00 | 0.00 | 0.00 |
December | 72.55 | 25.13 | 47.42 | 22.83 | 364.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.71 | 93.67 | 112.03 | 211.37 | 172.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.55 | 25.13 | 47.42 | 22.83 | 41.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.01 | 154.70 | 177.58 | 425.89 | 376.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.39 | 164.09 | 71.31 | 196.77 | 263.27 | 0.00 | 0.00 | 0.00 |
February | 293.86 | 197.76 | 96.10 | 277.68 | 220.63 | 0.00 | 0.00 | 0.00 |
March | 258.23 | 162.54 | 95.68 | 252.86 | 180.15 | 0.00 | 0.00 | 0.00 |
April | 235.75 | 127.77 | 107.97 | 253.83 | 115.30 | 0.00 | 0.00 | 0.00 |
May | 201.74 | 71.09 | 130.65 | 243.12 | 57.06 | 0.00 | 0.00 | 0.00 |
June | 177.25 | 46.60 | 130.65 | 231.95 | 34.28 | 0.00 | 0.00 | 0.00 |
July | 195.02 | 61.96 | 133.06 | 266.51 | 29.13 | 0.00 | 0.00 | 0.00 |
August | 206.99 | 85.99 | 121.00 | 271.18 | 35.46 | 0.00 | 0.00 | 0.00 |
September | 218.39 | 114.25 | 104.15 | 260.46 | 66.60 | 0.00 | 0.00 | 0.00 |
October | 194.27 | 115.84 | 78.43 | 203.39 | 109.51 | 0.00 | 0.00 | 0.00 |
November | 169.71 | 106.44 | 63.27 | 152.70 | 166.44 | 0.00 | 0.00 | 0.00 |
December | 180.80 | 118.65 | 62.14 | 138.73 | 255.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 213.44 | 113.90 | 99.54 | 228.75 | 127.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 169.71 | 46.60 | 62.14 | 138.73 | 29.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 293.86 | 197.76 | 133.06 | 277.68 | 263.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 161.90 | 0.00 | 161.90 | 0.40 | 1601.16 | 0.00 | 0.00 | 0.00 |
February | 248.70 | 0.00 | 248.70 | 13.30 | 1278.09 | 0.00 | 0.00 | 0.00 |
March | 306.05 | 0.01 | 306.04 | 45.78 | 978.47 | 0.00 | 0.00 | 0.00 |
April | 402.41 | 4.10 | 398.31 | 198.49 | 574.67 | 0.00 | 0.00 | 0.00 |
May | 564.28 | 29.82 | 534.46 | 551.27 | 272.07 | 0.00 | 0.00 | 0.00 |
June | 630.56 | 69.98 | 560.58 | 759.77 | 175.43 | 0.00 | 0.00 | 0.00 |
July | 602.86 | 52.76 | 550.10 | 768.08 | 153.70 | 0.00 | 0.00 | 0.00 |
August | 457.86 | 8.66 | 449.20 | 529.81 | 190.93 | 0.00 | 0.00 | 0.00 |
September | 356.52 | 0.36 | 356.15 | 299.88 | 347.63 | 0.00 | 0.00 | 0.00 |
October | 247.15 | 0.00 | 247.15 | 94.72 | 585.53 | 0.00 | 0.00 | 0.00 |
November | 163.64 | 0.00 | 163.64 | 11.74 | 957.02 | 0.00 | 0.00 | 0.00 |
December | 137.18 | 0.00 | 137.18 | 0.00 | 1541.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 357.13 | 13.87 | 343.26 | 274.41 | 719.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.18 | 0.00 | 137.18 | 0.00 | 153.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 630.56 | 69.98 | 560.58 | 768.08 | 1601.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 161.90 | 0.00 | 161.90 | 0.33 | 1623.76 | 0.00 | 0.00 | 0.00 |
February | 248.70 | 0.00 | 248.70 | 12.04 | 1301.79 | 0.00 | 0.00 | 0.00 |
March | 306.05 | 0.01 | 306.04 | 42.25 | 1002.98 | 0.00 | 0.00 | 0.00 |
April | 402.41 | 4.10 | 398.31 | 189.06 | 594.59 | 0.00 | 0.00 | 0.00 |
May | 564.28 | 29.82 | 534.46 | 538.51 | 281.37 | 0.00 | 0.00 | 0.00 |
June | 630.56 | 69.98 | 560.58 | 746.44 | 182.28 | 0.00 | 0.00 | 0.00 |
July | 602.86 | 52.76 | 550.10 | 755.44 | 160.30 | 0.00 | 0.00 | 0.00 |
August | 457.86 | 8.66 | 449.20 | 518.89 | 199.65 | 0.00 | 0.00 | 0.00 |
September | 356.52 | 0.36 | 356.15 | 290.56 | 360.98 | 0.00 | 0.00 | 0.00 |
October | 247.15 | 0.00 | 247.15 | 87.92 | 608.67 | 0.00 | 0.00 | 0.00 |
November | 163.64 | 0.00 | 163.64 | 10.32 | 985.75 | 0.00 | 0.00 | 0.00 |
December | 137.18 | 0.00 | 137.18 | 0.00 | 1564.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 357.13 | 13.87 | 343.26 | 267.59 | 736.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.18 | 0.00 | 137.18 | 0.00 | 160.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 630.56 | 69.98 | 560.58 | 755.44 | 1623.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.13 | 0.00 | 23.13 | 0.68 | 205.06 | 0.00 | 0.00 | 0.00 |
February | 35.53 | 0.00 | 35.53 | 5.20 | 162.57 | 0.00 | 0.00 | 0.00 |
March | 43.72 | 0.00 | 43.72 | 13.80 | 122.88 | 0.00 | 0.00 | 0.00 |
April | 57.49 | 0.59 | 56.90 | 45.44 | 73.22 | 0.00 | 0.00 | 0.00 |
May | 80.61 | 4.26 | 76.35 | 108.84 | 36.01 | 0.00 | 0.00 | 0.00 |
June | 90.08 | 10.00 | 80.09 | 141.35 | 23.67 | 0.00 | 0.00 | 0.00 |
July | 86.13 | 7.54 | 78.59 | 143.58 | 20.33 | 0.00 | 0.00 | 0.00 |
August | 65.41 | 1.24 | 64.17 | 106.12 | 23.43 | 0.00 | 0.00 | 0.00 |
September | 50.93 | 0.05 | 50.88 | 65.85 | 41.18 | 0.00 | 0.00 | 0.00 |
October | 35.31 | 0.00 | 35.31 | 27.04 | 69.07 | 0.00 | 0.00 | 0.00 |
November | 23.38 | 0.00 | 23.38 | 5.49 | 115.50 | 0.00 | 0.00 | 0.00 |
December | 19.60 | 0.00 | 19.60 | 0.16 | 195.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 1.98 | 49.04 | 55.61 | 90.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.60 | 0.00 | 19.60 | 0.16 | 20.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.08 | 10.00 | 80.09 | 143.58 | 205.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 188.78 | 78.25 | 110.53 | 83.25 | 700.47 | 0.00 | 0.00 | 0.00 |
February | 300.03 | 129.02 | 171.01 | 201.09 | 551.20 | 0.00 | 0.00 | 0.00 |
March | 407.89 | 205.08 | 202.81 | 356.00 | 424.71 | 0.00 | 0.00 | 0.00 |
April | 561.79 | 302.91 | 258.88 | 636.12 | 262.18 | 0.00 | 0.00 | 0.00 |
May | 610.14 | 269.14 | 341.00 | 825.48 | 134.21 | 0.00 | 0.00 | 0.00 |
June | 688.48 | 329.35 | 359.13 | 1001.42 | 88.62 | 0.00 | 0.00 | 0.00 |
July | 675.88 | 318.02 | 357.86 | 1015.41 | 76.08 | 0.00 | 0.00 | 0.00 |
August | 520.23 | 227.38 | 292.85 | 773.75 | 87.67 | 0.00 | 0.00 | 0.00 |
September | 417.72 | 187.45 | 230.27 | 557.34 | 151.09 | 0.00 | 0.00 | 0.00 |
October | 251.47 | 94.56 | 156.92 | 260.19 | 249.48 | 0.00 | 0.00 | 0.00 |
November | 161.06 | 53.63 | 107.44 | 99.87 | 405.47 | 0.00 | 0.00 | 0.00 |
December | 148.07 | 55.56 | 92.51 | 52.40 | 676.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 411.37 | 187.67 | 223.69 | 489.95 | 316.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 148.07 | 53.63 | 92.51 | 52.40 | 76.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 688.48 | 329.35 | 359.13 | 1015.41 | 700.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.50 | 111.88 | 48.62 | 147.36 | 166.90 | 0.00 | 0.00 | 0.00 |
February | 200.37 | 134.84 | 65.53 | 206.87 | 139.95 | 0.00 | 0.00 | 0.00 |
March | 176.07 | 110.83 | 65.24 | 190.70 | 113.28 | 0.00 | 0.00 | 0.00 |
April | 160.74 | 87.12 | 73.62 | 196.33 | 73.21 | 0.00 | 0.00 | 0.00 |
May | 137.56 | 48.47 | 89.08 | 197.62 | 38.12 | 0.00 | 0.00 | 0.00 |
June | 120.86 | 31.77 | 89.08 | 191.45 | 24.88 | 0.00 | 0.00 | 0.00 |
July | 132.97 | 42.25 | 90.73 | 217.30 | 21.15 | 0.00 | 0.00 | 0.00 |
August | 141.13 | 58.63 | 82.50 | 218.01 | 23.78 | 0.00 | 0.00 | 0.00 |
September | 148.91 | 77.90 | 71.01 | 205.30 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 132.46 | 78.98 | 53.48 | 158.68 | 66.68 | 0.00 | 0.00 | 0.00 |
November | 115.72 | 72.58 | 43.14 | 117.39 | 103.16 | 0.00 | 0.00 | 0.00 |
December | 123.28 | 80.90 | 42.37 | 105.01 | 161.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 145.54 | 77.66 | 67.87 | 179.13 | 80.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.72 | 31.77 | 42.37 | 105.01 | 21.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.37 | 134.84 | 90.73 | 218.01 | 166.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.29 | 0.00 | 29.29 | 0.06 | 295.08 | 0.00 | 0.00 | 0.00 |
February | 45.00 | 0.00 | 45.00 | 2.07 | 235.22 | 0.00 | 0.00 | 0.00 |
March | 55.37 | 0.00 | 55.37 | 7.37 | 179.24 | 0.00 | 0.00 | 0.00 |
April | 72.81 | 0.74 | 72.06 | 32.80 | 106.07 | 0.00 | 0.00 | 0.00 |
May | 102.09 | 5.39 | 96.70 | 92.05 | 53.35 | 0.00 | 0.00 | 0.00 |
June | 114.08 | 12.66 | 101.42 | 128.27 | 35.48 | 0.00 | 0.00 | 0.00 |
July | 109.07 | 9.55 | 99.53 | 129.38 | 31.90 | 0.00 | 0.00 | 0.00 |
August | 82.84 | 1.57 | 81.27 | 87.32 | 39.89 | 0.00 | 0.00 | 0.00 |
September | 64.50 | 0.07 | 64.44 | 48.53 | 68.68 | 0.00 | 0.00 | 0.00 |
October | 44.72 | 0.00 | 44.72 | 15.18 | 108.36 | 0.00 | 0.00 | 0.00 |
November | 29.61 | 0.00 | 29.61 | 2.02 | 174.07 | 0.00 | 0.00 | 0.00 |
December | 24.82 | 0.00 | 24.82 | 0.00 | 283.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.61 | 2.51 | 62.11 | 45.69 | 133.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.82 | 0.00 | 24.82 | 0.00 | 31.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 114.08 | 12.66 | 101.42 | 129.38 | 295.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.21 | 0.00 | 26.21 | 0.05 | 263.97 | 0.00 | 0.00 | 0.00 |
February | 40.26 | 0.00 | 40.26 | 1.85 | 210.45 | 0.00 | 0.00 | 0.00 |
March | 49.54 | 0.00 | 49.54 | 6.60 | 160.37 | 0.00 | 0.00 | 0.00 |
April | 65.14 | 0.66 | 64.48 | 29.35 | 94.90 | 0.00 | 0.00 | 0.00 |
May | 91.34 | 4.83 | 86.52 | 82.36 | 47.73 | 0.00 | 0.00 | 0.00 |
June | 102.07 | 11.33 | 90.74 | 114.77 | 31.74 | 0.00 | 0.00 | 0.00 |
July | 97.59 | 8.54 | 89.05 | 115.75 | 28.54 | 0.00 | 0.00 | 0.00 |
August | 74.12 | 1.40 | 72.71 | 78.12 | 35.69 | 0.00 | 0.00 | 0.00 |
September | 57.71 | 0.06 | 57.65 | 43.42 | 61.45 | 0.00 | 0.00 | 0.00 |
October | 40.01 | 0.00 | 40.01 | 13.58 | 96.95 | 0.00 | 0.00 | 0.00 |
November | 26.49 | 0.00 | 26.49 | 1.81 | 155.73 | 0.00 | 0.00 | 0.00 |
December | 22.21 | 0.00 | 22.21 | 0.00 | 253.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.81 | 2.25 | 55.57 | 40.88 | 119.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.21 | 0.00 | 22.21 | 0.00 | 28.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.07 | 11.33 | 90.74 | 115.75 | 263.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 599.20 | 417.69 | 181.52 | 504.45 | 684.60 | 0.00 | 0.00 | 0.00 |
February | 748.04 | 503.40 | 244.64 | 715.20 | 570.63 | 0.00 | 0.00 | 0.00 |
March | 657.33 | 413.77 | 243.57 | 650.33 | 468.31 | 0.00 | 0.00 | 0.00 |
April | 600.10 | 325.26 | 274.85 | 648.34 | 310.22 | 0.00 | 0.00 | 0.00 |
May | 513.54 | 180.97 | 332.57 | 606.46 | 173.37 | 0.00 | 0.00 | 0.00 |
June | 451.19 | 118.62 | 332.57 | 569.30 | 115.29 | 0.00 | 0.00 | 0.00 |
July | 496.43 | 157.72 | 338.72 | 658.80 | 101.95 | 0.00 | 0.00 | 0.00 |
August | 526.89 | 218.89 | 308.00 | 675.48 | 122.23 | 0.00 | 0.00 | 0.00 |
September | 555.93 | 290.82 | 265.11 | 655.48 | 199.76 | 0.00 | 0.00 | 0.00 |
October | 494.53 | 294.87 | 199.66 | 517.15 | 296.65 | 0.00 | 0.00 | 0.00 |
November | 432.01 | 270.96 | 161.05 | 391.36 | 438.01 | 0.00 | 0.00 | 0.00 |
December | 460.23 | 302.03 | 158.19 | 354.32 | 669.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 543.33 | 289.94 | 253.39 | 577.91 | 344.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.01 | 118.62 | 158.19 | 354.32 | 101.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 748.04 | 503.40 | 338.72 | 715.20 | 684.60 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217426E+10 | 0.151562E+10 | 0.658646E+09 | 0.185774E+10 | 0.231538E+10 |
February | 0.245165E+10 | 0.164987E+10 | 0.801775E+09 | 0.236373E+10 | 0.176126E+10 |
March | 0.238519E+10 | 0.150139E+10 | 0.883802E+09 | 0.236300E+10 | 0.160515E+10 |
April | 0.210728E+10 | 0.114215E+10 | 0.965132E+09 | 0.228396E+10 | 0.102088E+10 |
May | 0.186342E+10 | 0.656662E+09 | 0.120675E+10 | 0.222249E+10 | 0.576953E+09 |
June | 0.158436E+10 | 0.416550E+09 | 0.116781E+10 | 0.202071E+10 | 0.367348E+09 |
July | 0.180134E+10 | 0.572286E+09 | 0.122906E+10 | 0.239289E+10 | 0.350997E+09 |
August | 0.191187E+10 | 0.794265E+09 | 0.111760E+10 | 0.246353E+10 | 0.410921E+09 |
September | 0.195218E+10 | 0.102124E+10 | 0.930935E+09 | 0.232254E+10 | 0.638471E+09 |
October | 0.179444E+10 | 0.106998E+10 | 0.724468E+09 | 0.188829E+10 | 0.100544E+10 |
November | 0.151701E+10 | 0.951477E+09 | 0.565536E+09 | 0.138900E+10 | 0.143351E+10 |
December | 0.166997E+10 | 0.109596E+10 | 0.574011E+09 | 0.131353E+10 | 0.224686E+10 |
Annual Sum or Average | 0.232130E+11 | 0.123874E+11 | 0.108255E+11 | 0.248814E+11 | 0.137332E+11 |
Minimum of Months | 0.151701E+10 | 0.416550E+09 | 0.565536E+09 | 0.131353E+10 | 0.350997E+09 |
Maximum of Months | 0.245165E+10 | 0.164987E+10 | 0.122906E+10 | 0.246353E+10 | 0.231538E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.612258E+10 | 0.426788E+10 | 0.185470E+10 | 0.520621E+10 | 0.651786E+10 |
February | 0.690368E+10 | 0.464594E+10 | 0.225775E+10 | 0.663851E+10 | 0.495125E+10 |
March | 0.671653E+10 | 0.422781E+10 | 0.248873E+10 | 0.664404E+10 | 0.452109E+10 |
April | 0.593396E+10 | 0.321622E+10 | 0.271775E+10 | 0.643992E+10 | 0.286009E+10 |
May | 0.524726E+10 | 0.184912E+10 | 0.339814E+10 | 0.634765E+10 | 0.155216E+10 |
June | 0.446146E+10 | 0.117298E+10 | 0.328848E+10 | 0.580529E+10 | 0.959382E+09 |
July | 0.507246E+10 | 0.161152E+10 | 0.346095E+10 | 0.686683E+10 | 0.892620E+09 |
August | 0.538370E+10 | 0.223660E+10 | 0.314710E+10 | 0.702640E+10 | 0.106660E+10 |
September | 0.549721E+10 | 0.287576E+10 | 0.262145E+10 | 0.657411E+10 | 0.174558E+10 |
October | 0.505303E+10 | 0.301298E+10 | 0.204005E+10 | 0.530154E+10 | 0.283582E+10 |
November | 0.427181E+10 | 0.267930E+10 | 0.159251E+10 | 0.389301E+10 | 0.405275E+10 |
December | 0.470252E+10 | 0.308614E+10 | 0.161638E+10 | 0.367812E+10 | 0.632561E+10 |
Annual Sum or Average | 0.653662E+11 | 0.348822E+11 | 0.304840E+11 | 0.704216E+11 | 0.382808E+11 |
Minimum of Months | 0.427181E+10 | 0.117298E+10 | 0.159251E+10 | 0.367812E+10 | 0.892620E+09 |
Maximum of Months | 0.690368E+10 | 0.464594E+10 | 0.346095E+10 | 0.702640E+10 | 0.651786E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.795359E+10 | 0.554422E+10 | 0.240937E+10 | 0.683025E+10 | 0.874558E+10 |
February | 0.896828E+10 | 0.603534E+10 | 0.293294E+10 | 0.874597E+10 | 0.664803E+10 |
March | 0.872516E+10 | 0.549216E+10 | 0.323300E+10 | 0.875730E+10 | 0.610633E+10 |
April | 0.770856E+10 | 0.417805E+10 | 0.353051E+10 | 0.848115E+10 | 0.392133E+10 |
May | 0.681648E+10 | 0.240211E+10 | 0.441437E+10 | 0.831937E+10 | 0.217110E+10 |
June | 0.579569E+10 | 0.152376E+10 | 0.427192E+10 | 0.758908E+10 | 0.136878E+10 |
July | 0.658942E+10 | 0.209346E+10 | 0.449596E+10 | 0.899641E+10 | 0.126700E+10 |
August | 0.699373E+10 | 0.290547E+10 | 0.408826E+10 | 0.921473E+10 | 0.150851E+10 |
September | 0.714118E+10 | 0.373577E+10 | 0.340541E+10 | 0.862309E+10 | 0.244433E+10 |
October | 0.656418E+10 | 0.391403E+10 | 0.265015E+10 | 0.695341E+10 | 0.392736E+10 |
November | 0.554932E+10 | 0.348056E+10 | 0.206877E+10 | 0.510784E+10 | 0.554652E+10 |
December | 0.610884E+10 | 0.400907E+10 | 0.209977E+10 | 0.481515E+10 | 0.852557E+10 |
Annual Sum or Average | 0.849144E+11 | 0.453140E+11 | 0.396004E+11 | 0.924337E+11 | 0.521804E+11 |
Minimum of Months | 0.554932E+10 | 0.152376E+10 | 0.206877E+10 | 0.481515E+10 | 0.126700E+10 |
Maximum of Months | 0.896828E+10 | 0.603534E+10 | 0.449596E+10 | 0.921473E+10 | 0.874558E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.429890E+09 | 0.299664E+09 | 0.130226E+09 | 0.371530E+09 | 0.469934E+09 |
February | 0.484734E+09 | 0.326209E+09 | 0.158526E+09 | 0.471311E+09 | 0.355073E+09 |
March | 0.471594E+09 | 0.296850E+09 | 0.174744E+09 | 0.472341E+09 | 0.322227E+09 |
April | 0.416647E+09 | 0.225822E+09 | 0.190825E+09 | 0.455552E+09 | 0.202080E+09 |
May | 0.368431E+09 | 0.129833E+09 | 0.238598E+09 | 0.445211E+09 | 0.106330E+09 |
June | 0.313258E+09 | 82359121.90 | 0.230899E+09 | 0.408970E+09 | 62796125.70 |
July | 0.356159E+09 | 0.113151E+09 | 0.243008E+09 | 0.484980E+09 | 56278886.16 |
August | 0.378011E+09 | 0.157040E+09 | 0.220971E+09 | 0.496059E+09 | 66997956.98 |
September | 0.385981E+09 | 0.201917E+09 | 0.184063E+09 | 0.464719E+09 | 0.117798E+09 |
October | 0.354793E+09 | 0.211553E+09 | 0.143241E+09 | 0.378008E+09 | 0.196195E+09 |
November | 0.299940E+09 | 0.188123E+09 | 0.111817E+09 | 0.278154E+09 | 0.286651E+09 |
December | 0.330182E+09 | 0.216689E+09 | 0.113492E+09 | 0.262441E+09 | 0.455741E+09 |
Annual Sum or Average | 0.458962E+10 | 0.244921E+10 | 0.214041E+10 | 0.498928E+10 | 0.269810E+10 |
Minimum of Months | 0.299940E+09 | 82359121.90 | 0.111817E+09 | 0.262441E+09 | 56278886.16 |
Maximum of Months | 0.484734E+09 | 0.326209E+09 | 0.243008E+09 | 0.496059E+09 | 0.469934E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259838E+09 | 0.109959E+09 | 0.149878E+09 | 0.109666E+09 | 0.101451E+10 |
February | 0.379715E+09 | 0.174259E+09 | 0.205456E+09 | 0.248461E+09 | 0.737615E+09 |
March | 0.551641E+09 | 0.282992E+09 | 0.268649E+09 | 0.445330E+09 | 0.633506E+09 |
April | 0.681314E+09 | 0.345677E+09 | 0.335637E+09 | 0.668347E+09 | 0.370470E+09 |
May | 0.865799E+09 | 0.414337E+09 | 0.451462E+09 | 0.101816E+10 | 0.192376E+09 |
June | 0.804993E+09 | 0.347745E+09 | 0.457248E+09 | 0.101598E+10 | 0.114868E+09 |
July | 0.889269E+09 | 0.413638E+09 | 0.475630E+09 | 0.115871E+10 | 0.103718E+09 |
August | 0.729971E+09 | 0.330843E+09 | 0.399127E+09 | 0.919194E+09 | 0.123950E+09 |
September | 0.554579E+09 | 0.249016E+09 | 0.305564E+09 | 0.616142E+09 | 0.218535E+09 |
October | 0.362375E+09 | 0.145824E+09 | 0.216550E+09 | 0.310326E+09 | 0.379303E+09 |
November | 0.213360E+09 | 72511900.95 | 0.140848E+09 | 0.110821E+09 | 0.586375E+09 |
December | 0.194315E+09 | 67296880.31 | 0.127018E+09 | 59477665.37 | 0.980632E+09 |
Annual Sum or Average | 0.648717E+10 | 0.295410E+10 | 0.353307E+10 | 0.668061E+10 | 0.545586E+10 |
Minimum of Months | 0.194315E+09 | 67296880.31 | 0.127018E+09 | 59477665.37 | 0.103718E+09 |
Maximum of Months | 0.889269E+09 | 0.414337E+09 | 0.475630E+09 | 0.115871E+10 | 0.101451E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61951685.06 | 0.00 | 61951685.06 | 402920.51 | 0.586446E+09 |
February | 85953363.34 | 0.00 | 85953363.34 | 6432468.11 | 0.420961E+09 |
March | 0.117108E+09 | 4405.27 | 0.117104E+09 | 20889618.82 | 0.356212E+09 |
April | 0.149013E+09 | 1519386.08 | 0.147493E+09 | 74759836.51 | 0.201298E+09 |
May | 0.215918E+09 | 11409698.03 | 0.204509E+09 | 0.203279E+09 | 98630828.97 |
June | 0.233495E+09 | 25912133.64 | 0.207583E+09 | 0.271565E+09 | 61421325.26 |
July | 0.230682E+09 | 20190138.86 | 0.210492E+09 | 0.280211E+09 | 57076371.00 |
August | 0.175196E+09 | 3314268.08 | 0.171882E+09 | 0.192459E+09 | 69443700.73 |
September | 0.132019E+09 | 134863.33 | 0.131884E+09 | 0.108789E+09 | 0.120531E+09 |
October | 94570072.78 | 0.00 | 94570072.78 | 40115462.84 | 0.207832E+09 |
November | 60597452.09 | 0.00 | 60597452.09 | 5878335.12 | 0.328453E+09 |
December | 52490384.51 | 0.00 | 52490384.51 | 0.00 | 0.561210E+09 |
Annual Sum or Average | 0.160899E+10 | 62484893.28 | 0.154651E+10 | 0.120478E+10 | 0.306952E+10 |
Minimum of Months | 52490384.51 | 0.00 | 52490384.51 | 0.00 | 57076371.00 |
Maximum of Months | 0.233495E+09 | 25912133.64 | 0.210492E+09 | 0.280211E+09 | 0.586446E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259838E+09 | 0.109959E+09 | 0.149878E+09 | 0.112907E+09 | 0.100905E+10 |
February | 0.379715E+09 | 0.174259E+09 | 0.205456E+09 | 0.256559E+09 | 0.731196E+09 |
March | 0.551641E+09 | 0.282992E+09 | 0.268649E+09 | 0.455572E+09 | 0.626821E+09 |
April | 0.681314E+09 | 0.345677E+09 | 0.335637E+09 | 0.677409E+09 | 0.367808E+09 |
May | 0.865799E+09 | 0.414337E+09 | 0.451462E+09 | 0.101489E+10 | 0.196448E+09 |
June | 0.804993E+09 | 0.347745E+09 | 0.457248E+09 | 0.100538E+10 | 0.121388E+09 |
July | 0.889269E+09 | 0.413638E+09 | 0.475630E+09 | 0.114709E+10 | 0.111856E+09 |
August | 0.729971E+09 | 0.330843E+09 | 0.399127E+09 | 0.913360E+09 | 0.132447E+09 |
September | 0.554579E+09 | 0.249016E+09 | 0.305564E+09 | 0.618513E+09 | 0.219765E+09 |
October | 0.362375E+09 | 0.145824E+09 | 0.216550E+09 | 0.317424E+09 | 0.375709E+09 |
November | 0.213360E+09 | 72511900.95 | 0.140848E+09 | 0.116123E+09 | 0.581628E+09 |
December | 0.194315E+09 | 67296880.31 | 0.127018E+09 | 61457616.42 | 0.976989E+09 |
Annual Sum or Average | 0.648717E+10 | 0.295410E+10 | 0.353307E+10 | 0.669668E+10 | 0.545110E+10 |
Minimum of Months | 0.194315E+09 | 67296880.31 | 0.127018E+09 | 61457616.42 | 0.111856E+09 |
Maximum of Months | 0.889269E+09 | 0.414337E+09 | 0.475630E+09 | 0.114709E+10 | 0.100905E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.343844E+09 | 0.239683E+09 | 0.104160E+09 | 0.307165E+09 | 0.334603E+09 |
February | 0.387710E+09 | 0.260915E+09 | 0.126795E+09 | 0.382290E+09 | 0.263723E+09 |
March | 0.377200E+09 | 0.237433E+09 | 0.139767E+09 | 0.375583E+09 | 0.257036E+09 |
April | 0.333252E+09 | 0.180622E+09 | 0.152630E+09 | 0.343940E+09 | 0.200498E+09 |
May | 0.294687E+09 | 0.103846E+09 | 0.190841E+09 | 0.328483E+09 | 0.121657E+09 |
June | 0.250556E+09 | 65874196.92 | 0.184682E+09 | 0.296801E+09 | 81785685.03 |
July | 0.284871E+09 | 90502604.60 | 0.194368E+09 | 0.358233E+09 | 76177653.64 |
August | 0.302349E+09 | 0.125607E+09 | 0.176742E+09 | 0.369548E+09 | 91018089.70 |
September | 0.308723E+09 | 0.161502E+09 | 0.147221E+09 | 0.346637E+09 | 0.137049E+09 |
October | 0.283778E+09 | 0.169208E+09 | 0.114570E+09 | 0.282819E+09 | 0.198078E+09 |
November | 0.239904E+09 | 0.150469E+09 | 89435632.70 | 0.219537E+09 | 0.229594E+09 |
December | 0.264093E+09 | 0.173317E+09 | 90775828.88 | 0.219305E+09 | 0.318629E+09 |
Annual Sum or Average | 0.367097E+10 | 0.195898E+10 | 0.171199E+10 | 0.383034E+10 | 0.230985E+10 |
Minimum of Months | 0.239904E+09 | 65874196.92 | 89435632.70 | 0.219305E+09 | 76177653.64 |
Maximum of Months | 0.387710E+09 | 0.260915E+09 | 0.194368E+09 | 0.382290E+09 | 0.334603E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 49567917.68 | 0.00 | 49567917.68 | 197631.61 | 0.480001E+09 |
February | 68771805.56 | 0.00 | 68771805.56 | 4448879.80 | 0.345327E+09 |
March | 93698777.38 | 3524.69 | 93695252.70 | 15812788.43 | 0.290736E+09 |
April | 0.119226E+09 | 1215669.98 | 0.118010E+09 | 61763012.74 | 0.162133E+09 |
May | 0.172757E+09 | 9128968.36 | 0.163629E+09 | 0.171583E+09 | 76525946.10 |
June | 0.186821E+09 | 20732454.75 | 0.166088E+09 | 0.226708E+09 | 46673770.52 |
July | 0.184570E+09 | 16154252.14 | 0.168416E+09 | 0.235628E+09 | 41836979.20 |
August | 0.140176E+09 | 2651765.93 | 0.137524E+09 | 0.162910E+09 | 51892075.52 |
September | 0.105629E+09 | 107904.96 | 0.105521E+09 | 91054071.03 | 94467669.80 |
October | 75666086.86 | 0.00 | 75666086.86 | 30905710.39 | 0.170686E+09 |
November | 48484387.70 | 0.00 | 48484387.70 | 3923193.02 | 0.273510E+09 |
December | 41997873.92 | 0.00 | 41997873.92 | 0.00 | 0.460690E+09 |
Annual Sum or Average | 0.128737E+10 | 49994540.81 | 0.123737E+10 | 0.100493E+10 | 0.249448E+10 |
Minimum of Months | 41997873.92 | 0.00 | 41997873.92 | 0.00 | 41836979.20 |
Maximum of Months | 0.186821E+09 | 20732454.75 | 0.168416E+09 | 0.235628E+09 | 0.480001E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.252827E+09 | 0.104795E+09 | 0.148032E+09 | 91858406.82 | 0.100062E+10 |
February | 0.362937E+09 | 0.156071E+09 | 0.206866E+09 | 0.208662E+09 | 0.713277E+09 |
March | 0.546284E+09 | 0.274658E+09 | 0.271626E+09 | 0.416797E+09 | 0.612579E+09 |
April | 0.728128E+09 | 0.392595E+09 | 0.335533E+09 | 0.715621E+09 | 0.355325E+09 |
May | 0.817152E+09 | 0.360455E+09 | 0.456697E+09 | 0.942146E+09 | 0.179662E+09 |
June | 0.892340E+09 | 0.426871E+09 | 0.465468E+09 | 0.112828E+10 | 0.109586E+09 |
July | 0.905201E+09 | 0.425923E+09 | 0.479278E+09 | 0.117374E+10 | 97873834.45 |
August | 0.696741E+09 | 0.304535E+09 | 0.392207E+09 | 0.867855E+09 | 0.119380E+09 |
September | 0.541399E+09 | 0.242952E+09 | 0.298447E+09 | 0.592306E+09 | 0.211258E+09 |
October | 0.336797E+09 | 0.126641E+09 | 0.210156E+09 | 0.267349E+09 | 0.369473E+09 |
November | 0.208753E+09 | 69502968.90 | 0.139250E+09 | 97759686.42 | 0.576166E+09 |
December | 0.198313E+09 | 74413933.70 | 0.123899E+09 | 57524502.49 | 0.970659E+09 |
Annual Sum or Average | 0.648687E+10 | 0.295941E+10 | 0.352746E+10 | 0.655990E+10 | 0.531586E+10 |
Minimum of Months | 0.198313E+09 | 69502968.90 | 0.123899E+09 | 57524502.49 | 97873834.45 |
Maximum of Months | 0.905201E+09 | 0.426871E+09 | 0.479278E+09 | 0.117374E+10 | 0.100062E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.429890E+09 | 0.299664E+09 | 0.130226E+09 | 0.371138E+09 | 0.469299E+09 |
February | 0.484734E+09 | 0.326209E+09 | 0.158526E+09 | 0.470569E+09 | 0.354315E+09 |
March | 0.471594E+09 | 0.296850E+09 | 0.174744E+09 | 0.469675E+09 | 0.321115E+09 |
April | 0.416647E+09 | 0.225822E+09 | 0.190825E+09 | 0.451838E+09 | 0.201288E+09 |
May | 0.368431E+09 | 0.129833E+09 | 0.238598E+09 | 0.443769E+09 | 0.105158E+09 |
June | 0.313258E+09 | 82359121.90 | 0.230899E+09 | 0.406083E+09 | 62045635.57 |
July | 0.356159E+09 | 0.113151E+09 | 0.243008E+09 | 0.483314E+09 | 55056041.99 |
August | 0.378011E+09 | 0.157040E+09 | 0.220971E+09 | 0.495183E+09 | 66055866.14 |
September | 0.385981E+09 | 0.201917E+09 | 0.184063E+09 | 0.463543E+09 | 0.116715E+09 |
October | 0.354793E+09 | 0.211553E+09 | 0.143241E+09 | 0.377383E+09 | 0.195284E+09 |
November | 0.299940E+09 | 0.188123E+09 | 0.111817E+09 | 0.277839E+09 | 0.286256E+09 |
December | 0.330182E+09 | 0.216689E+09 | 0.113492E+09 | 0.262033E+09 | 0.455414E+09 |
Annual Sum or Average | 0.458962E+10 | 0.244921E+10 | 0.214041E+10 | 0.497237E+10 | 0.268800E+10 |
Minimum of Months | 0.299940E+09 | 82359121.90 | 0.111817E+09 | 0.262033E+09 | 55056041.99 |
Maximum of Months | 0.484734E+09 | 0.326209E+09 | 0.243008E+09 | 0.495183E+09 | 0.469299E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61951685.06 | 0.00 | 61951685.06 | 397624.70 | 0.586035E+09 |
February | 85953363.34 | 0.00 | 85953363.34 | 6150654.57 | 0.420647E+09 |
March | 0.117108E+09 | 4405.27 | 0.117104E+09 | 19416930.77 | 0.355785E+09 |
April | 0.149013E+09 | 1519386.08 | 0.147493E+09 | 71492948.26 | 0.201193E+09 |
May | 0.215918E+09 | 11409698.03 | 0.204509E+09 | 0.203345E+09 | 96970582.55 |
June | 0.233495E+09 | 25912133.64 | 0.207583E+09 | 0.269269E+09 | 59941646.28 |
July | 0.230682E+09 | 20190138.86 | 0.210492E+09 | 0.278570E+09 | 55091934.89 |
August | 0.175196E+09 | 3314268.08 | 0.171882E+09 | 0.192356E+09 | 67155039.66 |
September | 0.132019E+09 | 134863.33 | 0.131884E+09 | 0.107805E+09 | 0.118340E+09 |
October | 94570072.78 | 0.00 | 94570072.78 | 39218685.15 | 0.206403E+09 |
November | 60597452.09 | 0.00 | 60597452.09 | 5725933.19 | 0.328456E+09 |
December | 52490384.51 | 0.00 | 52490384.51 | 0.00 | 0.560851E+09 |
Annual Sum or Average | 0.160899E+10 | 62484893.28 | 0.154651E+10 | 0.119375E+10 | 0.305687E+10 |
Minimum of Months | 52490384.51 | 0.00 | 52490384.51 | 0.00 | 55091934.89 |
Maximum of Months | 0.233495E+09 | 25912133.64 | 0.210492E+09 | 0.278570E+09 | 0.586035E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.252827E+09 | 0.104795E+09 | 0.148032E+09 | 93821209.57 | 0.993582E+09 |
February | 0.362937E+09 | 0.156071E+09 | 0.206866E+09 | 0.214278E+09 | 0.704093E+09 |
March | 0.546284E+09 | 0.274658E+09 | 0.271626E+09 | 0.425423E+09 | 0.603214E+09 |
April | 0.728128E+09 | 0.392595E+09 | 0.335533E+09 | 0.723816E+09 | 0.351728E+09 |
May | 0.817152E+09 | 0.360455E+09 | 0.456697E+09 | 0.942047E+09 | 0.182417E+09 |
June | 0.892340E+09 | 0.426871E+09 | 0.465468E+09 | 0.111997E+10 | 0.115311E+09 |
July | 0.905201E+09 | 0.425923E+09 | 0.479278E+09 | 0.116288E+10 | 0.105013E+09 |
August | 0.696741E+09 | 0.304535E+09 | 0.392207E+09 | 0.864515E+09 | 0.125865E+09 |
September | 0.541399E+09 | 0.242952E+09 | 0.298447E+09 | 0.596470E+09 | 0.211116E+09 |
October | 0.336797E+09 | 0.126641E+09 | 0.210156E+09 | 0.274124E+09 | 0.364742E+09 |
November | 0.208753E+09 | 69502968.90 | 0.139250E+09 | 0.100548E+09 | 0.569213E+09 |
December | 0.198313E+09 | 74413933.70 | 0.123899E+09 | 58624447.34 | 0.965616E+09 |
Annual Sum or Average | 0.648687E+10 | 0.295941E+10 | 0.352746E+10 | 0.657652E+10 | 0.529191E+10 |
Minimum of Months | 0.198313E+09 | 69502968.90 | 0.123899E+09 | 58624447.34 | 0.105013E+09 |
Maximum of Months | 0.905201E+09 | 0.426871E+09 | 0.479278E+09 | 0.116288E+10 | 0.993582E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78457900.19 | 0.00 | 78457900.19 | 188033.44 | 0.786869E+09 |
February | 0.108855E+09 | 0.00 | 0.108855E+09 | 5710381.26 | 0.563813E+09 |
March | 0.148310E+09 | 5579.00 | 0.148304E+09 | 22433684.46 | 0.473146E+09 |
April | 0.188715E+09 | 1924206.60 | 0.186791E+09 | 94271472.31 | 0.264322E+09 |
May | 0.273447E+09 | 14449662.64 | 0.258997E+09 | 0.266574E+09 | 0.130577E+09 |
June | 0.295707E+09 | 32816082.29 | 0.262891E+09 | 0.352430E+09 | 82395276.04 |
July | 0.292144E+09 | 25569536.94 | 0.266575E+09 | 0.361689E+09 | 78785796.48 |
August | 0.221875E+09 | 4197311.41 | 0.217678E+09 | 0.250094E+09 | 95065592.87 |
September | 0.167193E+09 | 170795.89 | 0.167022E+09 | 0.139533E+09 | 0.161584E+09 |
October | 0.119767E+09 | 0.00 | 0.119767E+09 | 46986424.44 | 0.277115E+09 |
November | 76742849.59 | 0.00 | 76742849.59 | 5796991.93 | 0.444542E+09 |
December | 66475760.02 | 0.00 | 66475760.02 | 0.00 | 0.753182E+09 |
Annual Sum or Average | 0.203769E+10 | 79133174.77 | 0.195856E+10 | 0.154571E+10 | 0.411140E+10 |
Minimum of Months | 66475760.02 | 0.00 | 66475760.02 | 0.00 | 78785796.48 |
Maximum of Months | 0.295707E+09 | 32816082.29 | 0.266575E+09 | 0.361689E+09 | 0.786869E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 28922830.70 | 0.00 | 28922830.70 | 69316.91 | 0.290073E+09 |
February | 40128280.18 | 0.00 | 40128280.18 | 2105082.98 | 0.207845E+09 |
March | 54673143.46 | 2056.65 | 54671086.81 | 8269985.00 | 0.174421E+09 |
April | 69568148.80 | 709342.23 | 68858806.57 | 34752368.17 | 97440124.51 |
May | 0.100804E+09 | 5326743.96 | 95477070.28 | 98270214.67 | 48136045.29 |
June | 0.109010E+09 | 12097366.74 | 96912365.50 | 0.129920E+09 | 30374310.47 |
July | 0.107696E+09 | 9425990.07 | 98270426.58 | 0.133333E+09 | 29043706.84 |
August | 81792354.10 | 1547302.78 | 80245051.31 | 92194849.83 | 35045113.89 |
September | 61634371.65 | 62962.44 | 61571409.21 | 51437816.71 | 59566403.59 |
October | 44151086.47 | 0.00 | 44151086.47 | 17321141.60 | 0.102156E+09 |
November | 28290592.03 | 0.00 | 28290592.03 | 2137011.26 | 0.163877E+09 |
December | 24505717.69 | 0.00 | 24505717.69 | 0.00 | 0.277654E+09 |
Annual Sum or Average | 0.751176E+09 | 29171764.87 | 0.722005E+09 | 0.569812E+09 | 0.151563E+10 |
Minimum of Months | 24505717.69 | 0.00 | 24505717.69 | 0.00 | 29043706.84 |
Maximum of Months | 0.109010E+09 | 12097366.74 | 98270426.58 | 0.133333E+09 | 0.290073E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200585E+09 | 0.139822E+09 | 60763020.33 | 0.170153E+09 | 0.228315E+09 |
February | 0.226175E+09 | 0.152208E+09 | 73967383.70 | 0.218432E+09 | 0.171506E+09 |
March | 0.220044E+09 | 0.138509E+09 | 81534875.98 | 0.220146E+09 | 0.155035E+09 |
April | 0.194406E+09 | 0.105368E+09 | 89038181.29 | 0.214297E+09 | 96818462.74 |
May | 0.171909E+09 | 60579726.86 | 0.111329E+09 | 0.210258E+09 | 52918241.62 |
June | 0.146165E+09 | 38428434.40 | 0.107736E+09 | 0.191484E+09 | 33188284.56 |
July | 0.166182E+09 | 52795685.81 | 0.113387E+09 | 0.226183E+09 | 31325464.26 |
August | 0.176378E+09 | 73274118.98 | 0.103104E+09 | 0.232508E+09 | 36281116.19 |
September | 0.180097E+09 | 94213875.16 | 85883143.83 | 0.218342E+09 | 58823707.33 |
October | 0.165545E+09 | 98709572.15 | 66835481.23 | 0.176738E+09 | 95081127.48 |
November | 0.139951E+09 | 87777624.73 | 52173256.06 | 0.128404E+09 | 0.140077E+09 |
December | 0.154061E+09 | 0.101106E+09 | 52955074.19 | 0.119703E+09 | 0.222635E+09 |
Annual Sum or Average | 0.214150E+10 | 0.114279E+10 | 0.998707E+09 | 0.232665E+10 | 0.132201E+10 |
Minimum of Months | 0.139951E+09 | 38428434.40 | 52173256.06 | 0.119703E+09 | 31325464.26 |
Maximum of Months | 0.226175E+09 | 0.152208E+09 | 0.113387E+09 | 0.232508E+09 | 0.228315E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.544428E+09 | 0.379505E+09 | 0.164923E+09 | 0.461829E+09 | 0.619695E+09 |
February | 0.613885E+09 | 0.413123E+09 | 0.200763E+09 | 0.592869E+09 | 0.465502E+09 |
March | 0.597244E+09 | 0.375942E+09 | 0.221302E+09 | 0.597522E+09 | 0.420797E+09 |
April | 0.527658E+09 | 0.285990E+09 | 0.241668E+09 | 0.581646E+09 | 0.262785E+09 |
May | 0.466595E+09 | 0.164426E+09 | 0.302169E+09 | 0.570682E+09 | 0.143631E+09 |
June | 0.396721E+09 | 0.104303E+09 | 0.292419E+09 | 0.519726E+09 | 90079792.81 |
July | 0.451053E+09 | 0.143298E+09 | 0.307755E+09 | 0.613907E+09 | 85023717.49 |
August | 0.478727E+09 | 0.198881E+09 | 0.279846E+09 | 0.631075E+09 | 98474370.47 |
September | 0.488820E+09 | 0.255716E+09 | 0.233104E+09 | 0.592624E+09 | 0.159660E+09 |
October | 0.449323E+09 | 0.267918E+09 | 0.181405E+09 | 0.479704E+09 | 0.258070E+09 |
November | 0.379855E+09 | 0.238246E+09 | 0.141609E+09 | 0.348516E+09 | 0.380198E+09 |
December | 0.418154E+09 | 0.274424E+09 | 0.143731E+09 | 0.324898E+09 | 0.604278E+09 |
Annual Sum or Average | 0.581247E+10 | 0.310177E+10 | 0.271069E+10 | 0.631500E+10 | 0.358819E+10 |
Minimum of Months | 0.379855E+09 | 0.104303E+09 | 0.141609E+09 | 0.324898E+09 | 85023717.49 |
Maximum of Months | 0.613885E+09 | 0.413123E+09 | 0.307755E+09 | 0.631075E+09 | 0.619695E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.429890E+09 | 0.299664E+09 | 0.130226E+09 | 0.370776E+09 | 0.469514E+09 |
February | 0.484734E+09 | 0.326209E+09 | 0.158526E+09 | 0.469991E+09 | 0.354585E+09 |
March | 0.471594E+09 | 0.296850E+09 | 0.174744E+09 | 0.471441E+09 | 0.321458E+09 |
April | 0.416647E+09 | 0.225822E+09 | 0.190825E+09 | 0.454108E+09 | 0.201158E+09 |
May | 0.368431E+09 | 0.129833E+09 | 0.238598E+09 | 0.442726E+09 | 0.105691E+09 |
June | 0.313258E+09 | 82359121.90 | 0.230899E+09 | 0.406889E+09 | 62030585.70 |
July | 0.356159E+09 | 0.113151E+09 | 0.243008E+09 | 0.482842E+09 | 55338876.06 |
August | 0.378011E+09 | 0.157040E+09 | 0.220971E+09 | 0.493841E+09 | 66057153.36 |
September | 0.385981E+09 | 0.201917E+09 | 0.184063E+09 | 0.463031E+09 | 0.116797E+09 |
October | 0.354793E+09 | 0.211553E+09 | 0.143241E+09 | 0.377634E+09 | 0.194609E+09 |
November | 0.299940E+09 | 0.188123E+09 | 0.111817E+09 | 0.277925E+09 | 0.285328E+09 |
December | 0.330182E+09 | 0.216689E+09 | 0.113492E+09 | 0.261724E+09 | 0.455791E+09 |
Annual Sum or Average | 0.458962E+10 | 0.244921E+10 | 0.214041E+10 | 0.497293E+10 | 0.268836E+10 |
Minimum of Months | 0.299940E+09 | 82359121.90 | 0.111817E+09 | 0.261724E+09 | 55338876.06 |
Maximum of Months | 0.484734E+09 | 0.326209E+09 | 0.243008E+09 | 0.493841E+09 | 0.469514E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259838E+09 | 0.109959E+09 | 0.149878E+09 | 0.109281E+09 | 0.101401E+10 |
February | 0.379715E+09 | 0.174259E+09 | 0.205456E+09 | 0.247709E+09 | 0.737025E+09 |
March | 0.551641E+09 | 0.282992E+09 | 0.268649E+09 | 0.444028E+09 | 0.631864E+09 |
April | 0.681314E+09 | 0.345677E+09 | 0.335637E+09 | 0.665480E+09 | 0.368484E+09 |
May | 0.865799E+09 | 0.414337E+09 | 0.451462E+09 | 0.101316E+10 | 0.190939E+09 |
June | 0.804993E+09 | 0.347745E+09 | 0.457248E+09 | 0.101156E+10 | 0.113338E+09 |
July | 0.889269E+09 | 0.413638E+09 | 0.475630E+09 | 0.115400E+10 | 0.101875E+09 |
August | 0.729971E+09 | 0.330843E+09 | 0.399127E+09 | 0.915365E+09 | 0.122108E+09 |
September | 0.554579E+09 | 0.249016E+09 | 0.305564E+09 | 0.613649E+09 | 0.216322E+09 |
October | 0.362375E+09 | 0.145824E+09 | 0.216550E+09 | 0.310197E+09 | 0.375986E+09 |
November | 0.213360E+09 | 72511900.95 | 0.140848E+09 | 0.111293E+09 | 0.583712E+09 |
December | 0.194315E+09 | 67296880.31 | 0.127018E+09 | 59181670.74 | 0.981491E+09 |
Annual Sum or Average | 0.648717E+10 | 0.295410E+10 | 0.353307E+10 | 0.665490E+10 | 0.543715E+10 |
Minimum of Months | 0.194315E+09 | 67296880.31 | 0.127018E+09 | 59181670.74 | 0.101875E+09 |
Maximum of Months | 0.889269E+09 | 0.414337E+09 | 0.475630E+09 | 0.115400E+10 | 0.101401E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61951685.06 | 0.00 | 61951685.06 | 401272.21 | 0.585174E+09 |
February | 85953363.34 | 0.00 | 85953363.34 | 6608646.36 | 0.420456E+09 |
March | 0.117108E+09 | 4405.27 | 0.117104E+09 | 21064448.48 | 0.355563E+09 |
April | 0.149013E+09 | 1519386.08 | 0.147493E+09 | 74813848.82 | 0.200600E+09 |
May | 0.215918E+09 | 11409698.03 | 0.204509E+09 | 0.200838E+09 | 98961035.19 |
June | 0.233495E+09 | 25912133.64 | 0.207583E+09 | 0.269036E+09 | 61873297.20 |
July | 0.230682E+09 | 20190138.86 | 0.210492E+09 | 0.278121E+09 | 57406365.34 |
August | 0.175196E+09 | 3314268.08 | 0.171882E+09 | 0.190948E+09 | 69852486.16 |
September | 0.132019E+09 | 134863.33 | 0.131884E+09 | 0.108673E+09 | 0.119989E+09 |
October | 94570072.78 | 0.00 | 94570072.78 | 40963427.36 | 0.205839E+09 |
November | 60597452.09 | 0.00 | 60597452.09 | 6166317.09 | 0.326657E+09 |
December | 52490384.51 | 0.00 | 52490384.51 | 142.45 | 0.560856E+09 |
Annual Sum or Average | 0.160899E+10 | 62484893.28 | 0.154651E+10 | 0.119763E+10 | 0.306323E+10 |
Minimum of Months | 52490384.51 | 0.00 | 52490384.51 | 142.45 | 57406365.34 |
Maximum of Months | 0.233495E+09 | 25912133.64 | 0.210492E+09 | 0.278121E+09 | 0.585174E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259838E+09 | 0.109959E+09 | 0.149878E+09 | 0.112457E+09 | 0.100761E+10 |
February | 0.379715E+09 | 0.174259E+09 | 0.205456E+09 | 0.255659E+09 | 0.730768E+09 |
March | 0.551641E+09 | 0.282992E+09 | 0.268649E+09 | 0.454484E+09 | 0.625334E+09 |
April | 0.681314E+09 | 0.345677E+09 | 0.335637E+09 | 0.674965E+09 | 0.365956E+09 |
May | 0.865799E+09 | 0.414337E+09 | 0.451462E+09 | 0.100843E+10 | 0.196703E+09 |
June | 0.804993E+09 | 0.347745E+09 | 0.457248E+09 | 0.998887E+09 | 0.122001E+09 |
July | 0.889269E+09 | 0.413638E+09 | 0.475630E+09 | 0.114070E+10 | 0.112152E+09 |
August | 0.729971E+09 | 0.330843E+09 | 0.399127E+09 | 0.908139E+09 | 0.133010E+09 |
September | 0.554579E+09 | 0.249016E+09 | 0.305564E+09 | 0.616047E+09 | 0.218301E+09 |
October | 0.362375E+09 | 0.145824E+09 | 0.216550E+09 | 0.318064E+09 | 0.372139E+09 |
November | 0.213360E+09 | 72511900.95 | 0.140848E+09 | 0.116646E+09 | 0.579292E+09 |
December | 0.194315E+09 | 67296880.31 | 0.127018E+09 | 61151927.33 | 0.977271E+09 |
Annual Sum or Average | 0.648717E+10 | 0.295410E+10 | 0.353307E+10 | 0.666562E+10 | 0.544054E+10 |
Minimum of Months | 0.194315E+09 | 67296880.31 | 0.127018E+09 | 61151927.33 | 0.112152E+09 |
Maximum of Months | 0.889269E+09 | 0.414337E+09 | 0.475630E+09 | 0.114070E+10 | 0.100761E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.630475E+09 | 0.439486E+09 | 0.190989E+09 | 0.527035E+09 | 0.705141E+09 |
February | 0.710909E+09 | 0.478416E+09 | 0.232493E+09 | 0.671772E+09 | 0.533739E+09 |
March | 0.691638E+09 | 0.435359E+09 | 0.256279E+09 | 0.677249E+09 | 0.482507E+09 |
April | 0.611053E+09 | 0.331190E+09 | 0.279863E+09 | 0.657929E+09 | 0.298857E+09 |
May | 0.540340E+09 | 0.190413E+09 | 0.349927E+09 | 0.651174E+09 | 0.152838E+09 |
June | 0.459423E+09 | 0.120788E+09 | 0.338635E+09 | 0.601210E+09 | 88860795.61 |
July | 0.522341E+09 | 0.165946E+09 | 0.356395E+09 | 0.713816E+09 | 78023230.24 |
August | 0.554390E+09 | 0.230314E+09 | 0.324076E+09 | 0.726328E+09 | 94985189.75 |
September | 0.566078E+09 | 0.296131E+09 | 0.269946E+09 | 0.675123E+09 | 0.172635E+09 |
October | 0.520338E+09 | 0.310262E+09 | 0.210076E+09 | 0.544768E+09 | 0.293313E+09 |
November | 0.439891E+09 | 0.275901E+09 | 0.163990E+09 | 0.395806E+09 | 0.431408E+09 |
December | 0.484243E+09 | 0.317796E+09 | 0.166447E+09 | 0.371576E+09 | 0.683678E+09 |
Annual Sum or Average | 0.673112E+10 | 0.359200E+10 | 0.313912E+10 | 0.721379E+10 | 0.401598E+10 |
Minimum of Months | 0.439891E+09 | 0.120788E+09 | 0.163990E+09 | 0.371576E+09 | 78023230.24 |
Maximum of Months | 0.710909E+09 | 0.478416E+09 | 0.356395E+09 | 0.726328E+09 | 0.705141E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.433645E+09 | 0.00 | 0.433645E+09 | 1078873.98 | 0.428855E+10 |
February | 0.601651E+09 | 0.00 | 0.601651E+09 | 32175245.26 | 0.309196E+10 |
March | 0.819725E+09 | 30835.75 | 0.819694E+09 | 0.122615E+09 | 0.262074E+10 |
April | 0.104305E+10 | 10635299.72 | 0.103241E+10 | 0.514496E+09 | 0.148955E+10 |
May | 0.151137E+10 | 79864861.37 | 0.143151E+10 | 0.147651E+10 | 0.728708E+09 |
June | 0.163440E+10 | 0.181378E+09 | 0.145303E+10 | 0.196932E+10 | 0.454716E+09 |
July | 0.161471E+10 | 0.141326E+09 | 0.147339E+10 | 0.205722E+10 | 0.411659E+09 |
August | 0.122633E+10 | 23198997.94 | 0.120313E+10 | 0.141905E+10 | 0.511375E+09 |
September | 0.924096E+09 | 944007.52 | 0.923152E+09 | 0.777278E+09 | 0.901058E+09 |
October | 0.661965E+09 | 0.00 | 0.661965E+09 | 0.253697E+09 | 0.156829E+10 |
November | 0.424166E+09 | 0.00 | 0.424166E+09 | 30427044.26 | 0.248061E+10 |
December | 0.367419E+09 | 0.00 | 0.367419E+09 | 0.00 | 0.412831E+10 |
Annual Sum or Average | 0.112625E+11 | 0.437378E+09 | 0.108252E+11 | 0.865387E+10 | 0.226755E+11 |
Minimum of Months | 0.367419E+09 | 0.00 | 0.367419E+09 | 0.00 | 0.411659E+09 |
Maximum of Months | 0.163440E+10 | 0.181378E+09 | 0.147339E+10 | 0.205722E+10 | 0.428855E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.433645E+09 | 0.00 | 0.433645E+09 | 888581.76 | 0.434908E+10 |
February | 0.601651E+09 | 0.00 | 0.601651E+09 | 29133524.16 | 0.314929E+10 |
March | 0.819725E+09 | 30835.75 | 0.819694E+09 | 0.113158E+09 | 0.268638E+10 |
April | 0.104305E+10 | 10635299.72 | 0.103241E+10 | 0.490037E+09 | 0.154117E+10 |
May | 0.151137E+10 | 79864861.37 | 0.143151E+10 | 0.144233E+10 | 0.753632E+09 |
June | 0.163440E+10 | 0.181378E+09 | 0.145303E+10 | 0.193476E+10 | 0.472476E+09 |
July | 0.161471E+10 | 0.141326E+09 | 0.147339E+10 | 0.202338E+10 | 0.429359E+09 |
August | 0.122633E+10 | 23198997.94 | 0.120313E+10 | 0.138978E+10 | 0.534738E+09 |
September | 0.924096E+09 | 944007.52 | 0.923152E+09 | 0.753124E+09 | 0.935665E+09 |
October | 0.661965E+09 | 0.00 | 0.661965E+09 | 0.235482E+09 | 0.163026E+10 |
November | 0.424166E+09 | 0.00 | 0.424166E+09 | 26742514.26 | 0.255505E+10 |
December | 0.367419E+09 | 0.00 | 0.367419E+09 | 0.00 | 0.419072E+10 |
Annual Sum or Average | 0.112625E+11 | 0.437378E+09 | 0.108252E+11 | 0.843882E+10 | 0.232278E+11 |
Minimum of Months | 0.367419E+09 | 0.00 | 0.367419E+09 | 0.00 | 0.429359E+09 |
Maximum of Months | 0.163440E+10 | 0.181378E+09 | 0.147339E+10 | 0.202338E+10 | 0.434908E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61951685.06 | 0.00 | 61951685.06 | 1823060.66 | 0.549230E+09 |
February | 85953363.34 | 0.00 | 85953363.34 | 12569518.45 | 0.393294E+09 |
March | 0.117108E+09 | 4405.27 | 0.117104E+09 | 36952813.03 | 0.329113E+09 |
April | 0.149013E+09 | 1519386.08 | 0.147493E+09 | 0.117779E+09 | 0.189779E+09 |
May | 0.215918E+09 | 11409698.03 | 0.204509E+09 | 0.291512E+09 | 96439827.82 |
June | 0.233495E+09 | 25912133.64 | 0.207583E+09 | 0.366389E+09 | 61354496.86 |
July | 0.230682E+09 | 20190138.86 | 0.210492E+09 | 0.384552E+09 | 54451147.67 |
August | 0.175196E+09 | 3314268.08 | 0.171882E+09 | 0.284236E+09 | 62767090.87 |
September | 0.132019E+09 | 134863.33 | 0.131884E+09 | 0.170675E+09 | 0.106733E+09 |
October | 94570072.78 | 0.00 | 94570072.78 | 72424684.02 | 0.184996E+09 |
November | 60597452.09 | 0.00 | 60597452.09 | 14227684.54 | 0.299372E+09 |
December | 52490384.51 | 0.00 | 52490384.51 | 432420.38 | 0.523865E+09 |
Annual Sum or Average | 0.160899E+10 | 62484893.28 | 0.154651E+10 | 0.175357E+10 | 0.285139E+10 |
Minimum of Months | 52490384.51 | 0.00 | 52490384.51 | 432420.38 | 54451147.67 |
Maximum of Months | 0.233495E+09 | 25912133.64 | 0.210492E+09 | 0.384552E+09 | 0.549230E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.505619E+09 | 0.209575E+09 | 0.296044E+09 | 0.222973E+09 | 0.187614E+10 |
February | 0.725822E+09 | 0.312120E+09 | 0.413702E+09 | 0.486478E+09 | 0.133346E+10 |
March | 0.109249E+10 | 0.549277E+09 | 0.543213E+09 | 0.953523E+09 | 0.113754E+10 |
April | 0.145615E+10 | 0.785133E+09 | 0.671018E+09 | 0.164882E+10 | 0.679577E+09 |
May | 0.163419E+10 | 0.720859E+09 | 0.913329E+09 | 0.221096E+10 | 0.359463E+09 |
June | 0.178455E+10 | 0.853682E+09 | 0.930871E+09 | 0.259567E+10 | 0.229711E+09 |
July | 0.181027E+10 | 0.851785E+09 | 0.958489E+09 | 0.271967E+10 | 0.203770E+09 |
August | 0.139338E+10 | 0.609026E+09 | 0.784357E+09 | 0.207242E+10 | 0.234826E+09 |
September | 0.108272E+10 | 0.485870E+09 | 0.596851E+09 | 0.144462E+10 | 0.391633E+09 |
October | 0.673546E+09 | 0.253263E+09 | 0.420283E+09 | 0.696898E+09 | 0.668218E+09 |
November | 0.417477E+09 | 0.138996E+09 | 0.278481E+09 | 0.258851E+09 | 0.105099E+10 |
December | 0.396598E+09 | 0.148817E+09 | 0.247781E+09 | 0.140336E+09 | 0.181080E+10 |
Annual Sum or Average | 0.129728E+11 | 0.591840E+10 | 0.705442E+10 | 0.154512E+11 | 0.997614E+10 |
Minimum of Months | 0.396598E+09 | 0.138996E+09 | 0.247781E+09 | 0.140336E+09 | 0.203770E+09 |
Maximum of Months | 0.181027E+10 | 0.853682E+09 | 0.958489E+09 | 0.271967E+10 | 0.187614E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.429890E+09 | 0.299664E+09 | 0.130226E+09 | 0.394699E+09 | 0.447027E+09 |
February | 0.484734E+09 | 0.326209E+09 | 0.158526E+09 | 0.500464E+09 | 0.338573E+09 |
March | 0.471594E+09 | 0.296850E+09 | 0.174744E+09 | 0.510769E+09 | 0.303411E+09 |
April | 0.416647E+09 | 0.225822E+09 | 0.190825E+09 | 0.508882E+09 | 0.189772E+09 |
May | 0.368431E+09 | 0.129833E+09 | 0.238598E+09 | 0.529307E+09 | 0.102108E+09 |
June | 0.313258E+09 | 82359121.90 | 0.230899E+09 | 0.496247E+09 | 64494312.32 |
July | 0.356159E+09 | 0.113151E+09 | 0.243008E+09 | 0.582026E+09 | 56656154.22 |
August | 0.378011E+09 | 0.157040E+09 | 0.220971E+09 | 0.583927E+09 | 63691128.39 |
September | 0.385981E+09 | 0.201917E+09 | 0.184063E+09 | 0.532147E+09 | 0.106464E+09 |
October | 0.354793E+09 | 0.211553E+09 | 0.143241E+09 | 0.425009E+09 | 0.178594E+09 |
November | 0.299940E+09 | 0.188123E+09 | 0.111817E+09 | 0.304280E+09 | 0.267391E+09 |
December | 0.330182E+09 | 0.216689E+09 | 0.113492E+09 | 0.281269E+09 | 0.431943E+09 |
Annual Sum or Average | 0.458962E+10 | 0.244921E+10 | 0.214041E+10 | 0.564903E+10 | 0.255012E+10 |
Minimum of Months | 0.299940E+09 | 82359121.90 | 0.111817E+09 | 0.281269E+09 | 56656154.22 |
Maximum of Months | 0.484734E+09 | 0.326209E+09 | 0.243008E+09 | 0.583927E+09 | 0.447027E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78457900.19 | 0.00 | 78457900.19 | 157301.25 | 0.790350E+09 |
February | 0.108855E+09 | 0.00 | 0.108855E+09 | 5007899.99 | 0.569044E+09 |
March | 0.148310E+09 | 5579.00 | 0.148304E+09 | 19747729.27 | 0.480077E+09 |
April | 0.188715E+09 | 1924206.60 | 0.186791E+09 | 85021796.13 | 0.274938E+09 |
May | 0.273447E+09 | 14449662.64 | 0.258997E+09 | 0.246548E+09 | 0.142899E+09 |
June | 0.295707E+09 | 32816082.29 | 0.262891E+09 | 0.332487E+09 | 91962883.41 |
July | 0.292144E+09 | 25569536.94 | 0.266575E+09 | 0.346526E+09 | 85448584.21 |
August | 0.221875E+09 | 4197311.41 | 0.217678E+09 | 0.233873E+09 | 0.106840E+09 |
September | 0.167193E+09 | 170795.89 | 0.167022E+09 | 0.125782E+09 | 0.178024E+09 |
October | 0.119767E+09 | 0.00 | 0.119767E+09 | 40646243.44 | 0.290233E+09 |
November | 76742849.59 | 0.00 | 76742849.59 | 5234116.34 | 0.451189E+09 |
December | 66475760.02 | 0.00 | 66475760.02 | 0.00 | 0.758222E+09 |
Annual Sum or Average | 0.203769E+10 | 79133174.77 | 0.195856E+10 | 0.144103E+10 | 0.421923E+10 |
Minimum of Months | 66475760.02 | 0.00 | 66475760.02 | 0.00 | 85448584.21 |
Maximum of Months | 0.295707E+09 | 32816082.29 | 0.266575E+09 | 0.346526E+09 | 0.790350E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70196580.58 | 0.00 | 70196580.58 | 140738.02 | 0.707025E+09 |
February | 97392543.72 | 0.00 | 97392543.72 | 4480587.09 | 0.509119E+09 |
March | 0.132693E+09 | 4991.55 | 0.132688E+09 | 17668368.20 | 0.429527E+09 |
April | 0.168844E+09 | 1721594.93 | 0.167122E+09 | 76069323.14 | 0.245988E+09 |
May | 0.244654E+09 | 12928167.92 | 0.231726E+09 | 0.220587E+09 | 0.127852E+09 |
June | 0.264570E+09 | 29360673.16 | 0.235209E+09 | 0.297477E+09 | 82279540.23 |
July | 0.261382E+09 | 22877161.58 | 0.238505E+09 | 0.310038E+09 | 76451172.06 |
August | 0.198513E+09 | 3755350.42 | 0.194757E+09 | 0.209247E+09 | 95590134.60 |
September | 0.149588E+09 | 152811.73 | 0.149436E+09 | 0.112538E+09 | 0.159279E+09 |
October | 0.107156E+09 | 0.00 | 0.107156E+09 | 36366348.01 | 0.259672E+09 |
November | 68662118.30 | 0.00 | 68662118.30 | 4682983.72 | 0.403660E+09 |
December | 59476114.36 | 0.00 | 59476114.36 | 0.00 | 0.678314E+09 |
Annual Sum or Average | 0.182313E+10 | 70800751.30 | 0.175233E+10 | 0.128930E+10 | 0.377476E+10 |
Minimum of Months | 59476114.36 | 0.00 | 59476114.36 | 0.00 | 76451172.06 |
Maximum of Months | 0.264570E+09 | 29360673.16 | 0.238505E+09 | 0.310038E+09 | 0.707025E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160491E+10 | 0.111873E+10 | 0.486173E+09 | 0.135112E+10 | 0.183362E+10 |
February | 0.180966E+10 | 0.121783E+10 | 0.591823E+09 | 0.173022E+10 | 0.138047E+10 |
March | 0.176060E+10 | 0.110823E+10 | 0.652372E+09 | 0.174184E+10 | 0.125431E+10 |
April | 0.155547E+10 | 0.843062E+09 | 0.712407E+09 | 0.168049E+10 | 0.804086E+09 |
May | 0.137546E+10 | 0.484707E+09 | 0.890758E+09 | 0.162434E+10 | 0.464350E+09 |
June | 0.116948E+10 | 0.307471E+09 | 0.862014E+09 | 0.147562E+10 | 0.298823E+09 |
July | 0.132965E+10 | 0.422425E+09 | 0.907222E+09 | 0.176453E+10 | 0.273074E+09 |
August | 0.141123E+10 | 0.586276E+09 | 0.824952E+09 | 0.180920E+10 | 0.327394E+09 |
September | 0.144098E+10 | 0.753818E+09 | 0.687163E+09 | 0.169899E+10 | 0.517781E+09 |
October | 0.132455E+10 | 0.789789E+09 | 0.534760E+09 | 0.138514E+10 | 0.794536E+09 |
November | 0.111977E+10 | 0.702321E+09 | 0.417445E+09 | 0.101440E+10 | 0.113532E+10 |
December | 0.123267E+10 | 0.808966E+09 | 0.423701E+09 | 0.949023E+09 | 0.179303E+10 |
Annual Sum or Average | 0.171344E+11 | 0.914363E+10 | 0.799079E+10 | 0.182249E+11 | 0.108768E+11 |
Minimum of Months | 0.111977E+10 | 0.307471E+09 | 0.417445E+09 | 0.949023E+09 | 0.273074E+09 |
Maximum of Months | 0.180966E+10 | 0.121783E+10 | 0.907222E+09 | 0.180920E+10 | 0.183362E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 693.60 | 864.46 | 811.78 | 565.87 | 245.91 | 0.00 | 0.00 |
February | 977.07 | 728.03 | 1013.41 | 681.99 | 331.42 | 0.00 | 0.00 |
March | 882.24 | 599.29 | 890.53 | 560.55 | 329.97 | 0.00 | 0.00 |
April | 881.16 | 393.86 | 812.99 | 440.64 | 372.35 | 0.00 | 0.00 |
May | 829.78 | 215.41 | 695.72 | 245.17 | 450.55 | 0.00 | 0.00 |
June | 779.60 | 141.72 | 611.25 | 160.71 | 450.54 | 0.00 | 0.00 |
July | 893.40 | 131.05 | 672.54 | 213.67 | 458.88 | 0.00 | 0.00 |
August | 919.78 | 153.42 | 713.81 | 296.54 | 417.27 | 0.00 | 0.00 |
September | 896.04 | 246.32 | 753.16 | 394.00 | 359.16 | 0.00 | 0.00 |
October | 705.01 | 375.39 | 669.97 | 399.48 | 270.49 | 0.00 | 0.00 |
November | 535.88 | 553.05 | 585.27 | 367.08 | 218.19 | 0.00 | 0.00 |
December | 490.42 | 838.88 | 623.49 | 409.18 | 214.31 | 0.00 | 0.00 |
Annual Sum or Average | 788.98 | 435.48 | 736.08 | 392.80 | 343.28 | 0.00 | 0.00 |
Minimum of Months | 490.42 | 131.05 | 585.27 | 160.71 | 214.31 | 0.00 | 0.00 |
Maximum of Months | 977.07 | 864.46 | 1013.41 | 681.99 | 458.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1943.78 | 2433.49 | 2285.91 | 1593.44 | 692.47 | 0.00 | 0.00 |
February | 2744.09 | 2046.65 | 2853.71 | 1920.44 | 933.26 | 0.00 | 0.00 |
March | 2480.60 | 1687.98 | 2507.67 | 1578.48 | 929.18 | 0.00 | 0.00 |
April | 2484.54 | 1103.43 | 2289.34 | 1240.82 | 1048.51 | 0.00 | 0.00 |
May | 2369.94 | 579.51 | 1959.10 | 690.38 | 1268.72 | 0.00 | 0.00 |
June | 2239.69 | 370.13 | 1721.24 | 452.54 | 1268.70 | 0.00 | 0.00 |
July | 2563.78 | 333.27 | 1893.84 | 601.67 | 1292.17 | 0.00 | 0.00 |
August | 2623.36 | 398.22 | 2010.04 | 835.05 | 1174.99 | 0.00 | 0.00 |
September | 2536.31 | 673.45 | 2120.84 | 1109.47 | 1011.36 | 0.00 | 0.00 |
October | 1979.37 | 1058.77 | 1886.59 | 1124.92 | 761.67 | 0.00 | 0.00 |
November | 1501.93 | 1563.56 | 1648.08 | 1033.68 | 614.40 | 0.00 | 0.00 |
December | 1373.25 | 2361.71 | 1755.72 | 1152.23 | 603.49 | 0.00 | 0.00 |
Annual Sum or Average | 2233.06 | 1213.88 | 2072.75 | 1106.11 | 966.64 | 0.00 | 0.00 |
Minimum of Months | 1373.25 | 333.27 | 1648.08 | 452.54 | 603.49 | 0.00 | 0.00 |
Maximum of Months | 2744.09 | 2433.49 | 2853.71 | 1920.44 | 1292.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2550.12 | 3265.22 | 2969.53 | 2069.97 | 899.55 | 0.00 | 0.00 |
February | 3615.23 | 2748.03 | 3707.13 | 2494.77 | 1212.36 | 0.00 | 0.00 |
March | 3269.60 | 2279.84 | 3257.60 | 2050.54 | 1207.06 | 0.00 | 0.00 |
April | 3272.05 | 1512.86 | 2973.98 | 1611.90 | 1362.08 | 0.00 | 0.00 |
May | 3106.10 | 810.60 | 2544.98 | 896.84 | 1648.14 | 0.00 | 0.00 |
June | 2927.88 | 528.08 | 2235.99 | 587.87 | 1648.12 | 0.00 | 0.00 |
July | 3358.87 | 473.05 | 2460.21 | 781.61 | 1678.60 | 0.00 | 0.00 |
August | 3440.39 | 563.21 | 2611.16 | 1084.78 | 1526.38 | 0.00 | 0.00 |
September | 3326.81 | 943.03 | 2755.09 | 1441.27 | 1313.82 | 0.00 | 0.00 |
October | 2596.11 | 1466.31 | 2450.78 | 1461.33 | 989.45 | 0.00 | 0.00 |
November | 1970.62 | 2139.86 | 2140.94 | 1342.81 | 798.13 | 0.00 | 0.00 |
December | 1797.77 | 3183.08 | 2280.78 | 1496.82 | 783.96 | 0.00 | 0.00 |
Annual Sum or Average | 2931.05 | 1654.63 | 2692.62 | 1436.90 | 1255.72 | 0.00 | 0.00 |
Minimum of Months | 1797.77 | 473.05 | 2140.94 | 587.87 | 783.96 | 0.00 | 0.00 |
Maximum of Months | 3615.23 | 3265.22 | 3707.13 | 2494.77 | 1678.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 146.48 | 521.05 | 257.51 | 152.94 | 104.58 | 0.00 | 0.00 |
February | 276.67 | 430.82 | 357.33 | 206.87 | 150.46 | 0.00 | 0.00 |
March | 331.59 | 345.80 | 382.03 | 216.49 | 165.54 | 0.00 | 0.00 |
April | 429.64 | 216.93 | 423.60 | 220.49 | 203.11 | 0.00 | 0.00 |
May | 545.29 | 110.46 | 460.81 | 203.17 | 257.64 | 0.00 | 0.00 |
June | 549.23 | 68.02 | 431.42 | 165.94 | 265.49 | 0.00 | 0.00 |
July | 613.39 | 59.45 | 464.99 | 196.68 | 268.31 | 0.00 | 0.00 |
August | 528.14 | 71.04 | 413.67 | 182.15 | 231.52 | 0.00 | 0.00 |
September | 415.96 | 128.72 | 362.87 | 173.97 | 188.90 | 0.00 | 0.00 |
October | 253.99 | 211.86 | 267.76 | 133.43 | 134.33 | 0.00 | 0.00 |
November | 140.07 | 326.82 | 198.03 | 100.55 | 97.48 | 0.00 | 0.00 |
December | 93.31 | 509.40 | 195.82 | 106.03 | 89.80 | 0.00 | 0.00 |
Annual Sum or Average | 360.75 | 249.26 | 351.24 | 171.34 | 179.90 | 0.00 | 0.00 |
Minimum of Months | 93.31 | 59.45 | 195.82 | 100.55 | 89.80 | 0.00 | 0.00 |
Maximum of Months | 613.39 | 521.05 | 464.99 | 220.49 | 268.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 30.88 | 584.27 | 120.14 | 41.05 | 79.09 | 0.00 | 0.00 |
February | 99.30 | 466.85 | 192.49 | 72.03 | 120.46 | 0.00 | 0.00 |
March | 171.04 | 360.17 | 249.68 | 105.66 | 144.02 | 0.00 | 0.00 |
April | 287.78 | 217.15 | 320.34 | 133.95 | 186.39 | 0.00 | 0.00 |
May | 453.54 | 108.90 | 403.87 | 158.96 | 244.91 | 0.00 | 0.00 |
June | 491.04 | 68.92 | 400.65 | 144.16 | 256.49 | 0.00 | 0.00 |
July | 531.63 | 61.81 | 418.14 | 161.97 | 256.17 | 0.00 | 0.00 |
August | 412.48 | 74.99 | 337.95 | 124.76 | 213.19 | 0.00 | 0.00 |
September | 279.58 | 130.27 | 264.89 | 96.12 | 168.77 | 0.00 | 0.00 |
October | 131.81 | 216.19 | 170.60 | 54.44 | 116.16 | 0.00 | 0.00 |
November | 42.61 | 346.65 | 105.69 | 27.98 | 77.72 | 0.00 | 0.00 |
December | 14.86 | 566.21 | 92.15 | 25.13 | 67.02 | 0.00 | 0.00 |
Annual Sum or Average | 246.42 | 266.06 | 256.73 | 95.66 | 161.07 | 0.00 | 0.00 |
Minimum of Months | 14.86 | 61.81 | 92.15 | 25.13 | 67.02 | 0.00 | 0.00 |
Maximum of Months | 531.63 | 584.27 | 418.14 | 161.97 | 256.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 114.68 | 124.93 | 128.38 | 89.49 | 38.89 | 0.00 | 0.00 |
February | 158.02 | 109.01 | 160.26 | 107.85 | 52.41 | 0.00 | 0.00 |
March | 140.23 | 95.97 | 140.83 | 88.65 | 52.18 | 0.00 | 0.00 |
April | 132.69 | 77.35 | 128.57 | 69.68 | 58.88 | 0.00 | 0.00 |
May | 122.64 | 45.42 | 110.02 | 38.77 | 71.25 | 0.00 | 0.00 |
June | 114.51 | 31.55 | 96.67 | 25.41 | 71.25 | 0.00 | 0.00 |
July | 133.75 | 28.44 | 106.36 | 33.79 | 72.57 | 0.00 | 0.00 |
August | 137.97 | 33.98 | 112.88 | 46.90 | 65.99 | 0.00 | 0.00 |
September | 133.73 | 52.87 | 119.11 | 62.31 | 56.80 | 0.00 | 0.00 |
October | 105.59 | 73.95 | 105.95 | 63.18 | 42.78 | 0.00 | 0.00 |
November | 84.70 | 88.58 | 92.56 | 58.05 | 34.50 | 0.00 | 0.00 |
December | 81.88 | 118.96 | 98.60 | 64.71 | 33.89 | 0.00 | 0.00 |
Annual Sum or Average | 121.46 | 73.24 | 116.41 | 62.12 | 54.29 | 0.00 | 0.00 |
Minimum of Months | 81.88 | 28.44 | 92.56 | 25.41 | 33.89 | 0.00 | 0.00 |
Maximum of Months | 158.02 | 124.93 | 160.26 | 107.85 | 72.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.07 | 179.21 | 18.51 | 0.00 | 18.51 | 0.00 | 0.00 |
February | 1.84 | 142.74 | 28.43 | 0.00 | 28.43 | 0.00 | 0.00 |
March | 5.90 | 108.55 | 34.98 | 0.00 | 34.98 | 0.00 | 0.00 |
April | 23.83 | 62.55 | 46.00 | 0.47 | 45.53 | 0.00 | 0.00 |
May | 64.06 | 28.57 | 64.50 | 3.41 | 61.09 | 0.00 | 0.00 |
June | 87.46 | 18.01 | 72.08 | 8.00 | 64.08 | 0.00 | 0.00 |
July | 87.97 | 15.62 | 68.91 | 6.03 | 62.88 | 0.00 | 0.00 |
August | 60.82 | 19.37 | 52.34 | 0.99 | 51.35 | 0.00 | 0.00 |
September | 35.13 | 36.45 | 40.75 | 0.04 | 40.71 | 0.00 | 0.00 |
October | 11.54 | 63.73 | 28.25 | 0.00 | 28.25 | 0.00 | 0.00 |
November | 1.51 | 105.52 | 18.71 | 0.00 | 18.71 | 0.00 | 0.00 |
December | 0.00 | 172.00 | 15.68 | 0.00 | 15.68 | 0.00 | 0.00 |
Annual Sum or Average | 31.87 | 79.10 | 40.82 | 1.59 | 39.24 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 15.62 | 15.68 | 0.00 | 15.68 | 0.00 | 0.00 |
Maximum of Months | 87.97 | 179.21 | 72.08 | 8.00 | 64.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 141.80 | 517.75 | 254.90 | 151.01 | 103.89 | 0.00 | 0.00 |
February | 263.41 | 423.94 | 350.39 | 199.36 | 151.04 | 0.00 | 0.00 |
March | 320.65 | 338.28 | 380.03 | 213.38 | 166.66 | 0.00 | 0.00 |
April | 445.42 | 209.76 | 441.66 | 238.59 | 203.07 | 0.00 | 0.00 |
May | 514.47 | 103.37 | 442.65 | 183.05 | 259.59 | 0.00 | 0.00 |
June | 590.74 | 64.99 | 465.12 | 196.46 | 268.66 | 0.00 | 0.00 |
July | 617.76 | 56.19 | 470.94 | 201.27 | 269.67 | 0.00 | 0.00 |
August | 508.12 | 68.45 | 401.27 | 172.33 | 228.93 | 0.00 | 0.00 |
September | 405.91 | 125.10 | 357.79 | 171.63 | 186.15 | 0.00 | 0.00 |
October | 239.02 | 209.16 | 258.21 | 126.27 | 131.94 | 0.00 | 0.00 |
November | 135.70 | 323.52 | 196.26 | 99.39 | 96.86 | 0.00 | 0.00 |
December | 94.45 | 507.57 | 197.32 | 108.69 | 88.63 | 0.00 | 0.00 |
Annual Sum or Average | 356.80 | 244.92 | 351.23 | 171.51 | 179.73 | 0.00 | 0.00 |
Minimum of Months | 94.45 | 56.19 | 196.26 | 99.39 | 88.63 | 0.00 | 0.00 |
Maximum of Months | 617.76 | 517.75 | 470.94 | 238.59 | 269.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.12 | 576.70 | 117.53 | 39.13 | 78.40 | 0.00 | 0.00 |
February | 77.98 | 451.79 | 185.55 | 64.51 | 121.04 | 0.00 | 0.00 |
March | 155.41 | 347.38 | 247.68 | 102.55 | 145.13 | 0.00 | 0.00 |
April | 301.55 | 208.03 | 338.40 | 152.05 | 186.35 | 0.00 | 0.00 |
May | 426.19 | 102.86 | 385.70 | 138.84 | 246.87 | 0.00 | 0.00 |
June | 534.95 | 66.60 | 434.35 | 174.68 | 259.66 | 0.00 | 0.00 |
July | 537.54 | 59.13 | 424.09 | 166.56 | 257.53 | 0.00 | 0.00 |
August | 394.14 | 71.61 | 325.54 | 114.94 | 210.61 | 0.00 | 0.00 |
September | 269.87 | 125.27 | 259.81 | 93.78 | 166.02 | 0.00 | 0.00 |
October | 114.31 | 210.56 | 161.05 | 47.28 | 113.77 | 0.00 | 0.00 |
November | 36.06 | 341.39 | 103.92 | 26.81 | 77.10 | 0.00 | 0.00 |
December | 12.78 | 560.81 | 93.64 | 27.78 | 65.86 | 0.00 | 0.00 |
Annual Sum or Average | 241.08 | 259.42 | 256.72 | 95.82 | 160.89 | 0.00 | 0.00 |
Minimum of Months | 12.78 | 59.13 | 93.64 | 26.81 | 65.86 | 0.00 | 0.00 |
Maximum of Months | 537.54 | 576.70 | 434.35 | 174.68 | 259.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 175.69 | 658.34 | 318.25 | 193.89 | 124.35 | 0.00 | 0.00 |
February | 301.18 | 544.87 | 408.83 | 233.68 | 175.15 | 0.00 | 0.00 |
March | 299.90 | 439.92 | 380.93 | 192.08 | 188.85 | 0.00 | 0.00 |
April | 354.79 | 276.24 | 378.22 | 152.00 | 226.22 | 0.00 | 0.00 |
May | 425.14 | 137.46 | 378.12 | 91.39 | 286.73 | 0.00 | 0.00 |
June | 457.45 | 88.04 | 365.59 | 72.39 | 293.19 | 0.00 | 0.00 |
July | 496.13 | 81.35 | 379.73 | 86.28 | 293.45 | 0.00 | 0.00 |
August | 449.51 | 98.18 | 357.96 | 103.76 | 254.21 | 0.00 | 0.00 |
September | 386.03 | 169.10 | 346.35 | 135.09 | 211.26 | 0.00 | 0.00 |
October | 264.44 | 268.79 | 290.77 | 136.88 | 153.88 | 0.00 | 0.00 |
November | 167.56 | 415.96 | 241.06 | 125.78 | 115.28 | 0.00 | 0.00 |
December | 117.95 | 645.56 | 247.61 | 140.21 | 107.40 | 0.00 | 0.00 |
Annual Sum or Average | 324.66 | 317.68 | 340.65 | 138.03 | 202.62 | 0.00 | 0.00 |
Minimum of Months | 117.95 | 81.35 | 241.06 | 72.39 | 107.40 | 0.00 | 0.00 |
Maximum of Months | 496.13 | 658.34 | 408.83 | 233.68 | 293.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 146.07 | 520.73 | 257.51 | 152.94 | 104.58 | 0.00 | 0.00 |
February | 275.79 | 430.35 | 357.33 | 206.87 | 150.46 | 0.00 | 0.00 |
March | 330.84 | 344.97 | 382.03 | 216.49 | 165.54 | 0.00 | 0.00 |
April | 427.95 | 215.78 | 423.60 | 220.49 | 203.11 | 0.00 | 0.00 |
May | 542.45 | 109.63 | 460.81 | 203.17 | 257.64 | 0.00 | 0.00 |
June | 546.70 | 67.12 | 431.42 | 165.94 | 265.49 | 0.00 | 0.00 |
July | 610.82 | 58.39 | 464.99 | 196.68 | 268.31 | 0.00 | 0.00 |
August | 525.87 | 69.98 | 413.67 | 182.15 | 231.52 | 0.00 | 0.00 |
September | 414.35 | 127.48 | 362.87 | 173.97 | 188.90 | 0.00 | 0.00 |
October | 253.88 | 210.11 | 267.76 | 133.43 | 134.33 | 0.00 | 0.00 |
November | 140.31 | 325.43 | 198.03 | 100.55 | 97.48 | 0.00 | 0.00 |
December | 92.93 | 509.74 | 195.82 | 106.03 | 89.80 | 0.00 | 0.00 |
Annual Sum or Average | 359.43 | 248.37 | 351.24 | 171.34 | 179.90 | 0.00 | 0.00 |
Minimum of Months | 92.93 | 58.39 | 195.82 | 100.55 | 89.80 | 0.00 | 0.00 |
Maximum of Months | 610.82 | 520.73 | 464.99 | 220.49 | 268.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 30.80 | 583.35 | 120.14 | 41.05 | 79.09 | 0.00 | 0.00 |
February | 99.08 | 466.54 | 192.49 | 72.03 | 120.46 | 0.00 | 0.00 |
March | 170.71 | 359.38 | 249.68 | 105.66 | 144.02 | 0.00 | 0.00 |
April | 286.79 | 216.10 | 320.34 | 133.95 | 186.39 | 0.00 | 0.00 |
May | 450.21 | 109.11 | 403.87 | 158.96 | 244.91 | 0.00 | 0.00 |
June | 487.60 | 69.37 | 400.65 | 144.16 | 256.49 | 0.00 | 0.00 |
July | 528.49 | 62.07 | 418.14 | 161.97 | 256.17 | 0.00 | 0.00 |
August | 409.94 | 75.33 | 337.95 | 124.76 | 213.19 | 0.00 | 0.00 |
September | 278.50 | 129.41 | 264.89 | 96.12 | 168.77 | 0.00 | 0.00 |
October | 132.39 | 214.13 | 170.60 | 54.44 | 116.16 | 0.00 | 0.00 |
November | 43.04 | 345.18 | 105.69 | 27.98 | 77.72 | 0.00 | 0.00 |
December | 14.80 | 566.24 | 92.15 | 25.13 | 67.02 | 0.00 | 0.00 |
Annual Sum or Average | 245.23 | 265.54 | 256.73 | 95.66 | 161.07 | 0.00 | 0.00 |
Minimum of Months | 14.80 | 62.07 | 92.15 | 25.13 | 67.02 | 0.00 | 0.00 |
Maximum of Months | 528.49 | 583.35 | 418.14 | 161.97 | 256.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 196.77 | 263.27 | 235.39 | 164.09 | 71.31 | 0.00 | 0.00 |
February | 277.68 | 220.63 | 293.86 | 197.76 | 96.10 | 0.00 | 0.00 |
March | 252.86 | 180.15 | 258.23 | 162.54 | 95.68 | 0.00 | 0.00 |
April | 253.83 | 115.30 | 235.75 | 127.77 | 107.97 | 0.00 | 0.00 |
May | 243.12 | 57.06 | 201.74 | 71.09 | 130.65 | 0.00 | 0.00 |
June | 231.95 | 34.28 | 177.25 | 46.60 | 130.65 | 0.00 | 0.00 |
July | 266.51 | 29.13 | 195.02 | 61.96 | 133.06 | 0.00 | 0.00 |
August | 271.18 | 35.46 | 206.99 | 85.99 | 121.00 | 0.00 | 0.00 |
September | 260.46 | 66.60 | 218.39 | 114.25 | 104.15 | 0.00 | 0.00 |
October | 203.39 | 109.51 | 194.27 | 115.84 | 78.43 | 0.00 | 0.00 |
November | 152.70 | 166.44 | 169.71 | 106.44 | 63.27 | 0.00 | 0.00 |
December | 138.73 | 255.26 | 180.80 | 118.65 | 62.14 | 0.00 | 0.00 |
Annual Sum or Average | 228.75 | 127.35 | 213.44 | 113.90 | 99.54 | 0.00 | 0.00 |
Minimum of Months | 138.73 | 29.13 | 169.71 | 46.60 | 62.14 | 0.00 | 0.00 |
Maximum of Months | 277.68 | 263.27 | 293.86 | 197.76 | 133.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.40 | 1601.16 | 161.90 | 0.00 | 161.90 | 0.00 | 0.00 |
February | 13.30 | 1278.09 | 248.70 | 0.00 | 248.70 | 0.00 | 0.00 |
March | 45.78 | 978.47 | 306.05 | 0.01 | 306.04 | 0.00 | 0.00 |
April | 198.49 | 574.67 | 402.41 | 4.10 | 398.31 | 0.00 | 0.00 |
May | 551.27 | 272.07 | 564.28 | 29.82 | 534.46 | 0.00 | 0.00 |
June | 759.77 | 175.43 | 630.56 | 69.98 | 560.58 | 0.00 | 0.00 |
July | 768.08 | 153.70 | 602.86 | 52.76 | 550.10 | 0.00 | 0.00 |
August | 529.81 | 190.93 | 457.86 | 8.66 | 449.20 | 0.00 | 0.00 |
September | 299.88 | 347.63 | 356.52 | 0.36 | 356.15 | 0.00 | 0.00 |
October | 94.72 | 585.53 | 247.15 | 0.00 | 247.15 | 0.00 | 0.00 |
November | 11.74 | 957.02 | 163.64 | 0.00 | 163.64 | 0.00 | 0.00 |
December | 0.00 | 1541.34 | 137.18 | 0.00 | 137.18 | 0.00 | 0.00 |
Annual Sum or Average | 274.41 | 719.04 | 357.13 | 13.87 | 343.26 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 153.70 | 137.18 | 0.00 | 137.18 | 0.00 | 0.00 |
Maximum of Months | 768.08 | 1601.16 | 630.56 | 69.98 | 560.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.33 | 1623.76 | 161.90 | 0.00 | 161.90 | 0.00 | 0.00 |
February | 12.04 | 1301.79 | 248.70 | 0.00 | 248.70 | 0.00 | 0.00 |
March | 42.25 | 1002.98 | 306.05 | 0.01 | 306.04 | 0.00 | 0.00 |
April | 189.06 | 594.59 | 402.41 | 4.10 | 398.31 | 0.00 | 0.00 |
May | 538.51 | 281.37 | 564.28 | 29.82 | 534.46 | 0.00 | 0.00 |
June | 746.44 | 182.28 | 630.56 | 69.98 | 560.58 | 0.00 | 0.00 |
July | 755.44 | 160.30 | 602.86 | 52.76 | 550.10 | 0.00 | 0.00 |
August | 518.89 | 199.65 | 457.86 | 8.66 | 449.20 | 0.00 | 0.00 |
September | 290.56 | 360.98 | 356.52 | 0.36 | 356.15 | 0.00 | 0.00 |
October | 87.92 | 608.67 | 247.15 | 0.00 | 247.15 | 0.00 | 0.00 |
November | 10.32 | 985.75 | 163.64 | 0.00 | 163.64 | 0.00 | 0.00 |
December | 0.00 | 1564.64 | 137.18 | 0.00 | 137.18 | 0.00 | 0.00 |
Annual Sum or Average | 267.59 | 736.55 | 357.13 | 13.87 | 343.26 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 160.30 | 137.18 | 0.00 | 137.18 | 0.00 | 0.00 |
Maximum of Months | 755.44 | 1623.76 | 630.56 | 69.98 | 560.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 164.88 | 1006.02 | 372.41 | 190.13 | 182.28 | 0.00 | 0.00 |
February | 376.39 | 816.96 | 535.92 | 263.86 | 272.07 | 0.00 | 0.00 |
March | 542.86 | 643.23 | 627.69 | 315.91 | 311.78 | 0.00 | 0.00 |
April | 871.20 | 401.92 | 780.02 | 390.62 | 389.40 | 0.00 | 0.00 |
May | 1129.26 | 205.66 | 828.31 | 321.87 | 506.44 | 0.00 | 0.00 |
June | 1332.95 | 135.90 | 899.42 | 371.12 | 528.30 | 0.00 | 0.00 |
July | 1375.46 | 116.74 | 894.98 | 367.80 | 527.18 | 0.00 | 0.00 |
August | 1097.44 | 134.44 | 726.77 | 287.25 | 439.52 | 0.00 | 0.00 |
September | 827.04 | 231.90 | 617.56 | 265.40 | 352.16 | 0.00 | 0.00 |
October | 443.51 | 382.83 | 419.25 | 173.54 | 245.70 | 0.00 | 0.00 |
November | 207.01 | 608.40 | 300.16 | 126.20 | 173.96 | 0.00 | 0.00 |
December | 104.20 | 979.57 | 290.95 | 136.46 | 154.48 | 0.00 | 0.00 |
Annual Sum or Average | 707.59 | 470.53 | 607.92 | 267.32 | 340.61 | 0.00 | 0.00 |
Minimum of Months | 104.20 | 116.74 | 290.95 | 126.20 | 154.48 | 0.00 | 0.00 |
Maximum of Months | 1375.46 | 1006.02 | 899.42 | 390.62 | 528.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 416.23 | 1155.32 | 654.70 | 417.69 | 237.02 | 0.00 | 0.00 |
February | 663.17 | 960.35 | 833.29 | 503.40 | 329.89 | 0.00 | 0.00 |
March | 638.61 | 782.22 | 762.25 | 413.77 | 348.48 | 0.00 | 0.00 |
April | 707.19 | 507.90 | 738.05 | 326.66 | 411.39 | 0.00 | 0.00 |
May | 776.01 | 269.60 | 706.98 | 191.19 | 515.79 | 0.00 | 0.00 |
June | 805.52 | 175.69 | 667.35 | 142.61 | 524.74 | 0.00 | 0.00 |
July | 898.75 | 157.22 | 703.10 | 175.80 | 527.29 | 0.00 | 0.00 |
August | 839.48 | 196.38 | 683.85 | 221.86 | 461.99 | 0.00 | 0.00 |
September | 746.38 | 328.85 | 678.15 | 290.95 | 387.20 | 0.00 | 0.00 |
October | 538.15 | 494.20 | 579.25 | 294.87 | 284.38 | 0.00 | 0.00 |
November | 365.43 | 738.06 | 488.11 | 270.96 | 217.15 | 0.00 | 0.00 |
December | 283.39 | 1134.85 | 507.25 | 302.03 | 205.22 | 0.00 | 0.00 |
Annual Sum or Average | 639.49 | 573.39 | 665.75 | 294.70 | 371.06 | 0.00 | 0.00 |
Minimum of Months | 283.39 | 157.22 | 488.11 | 142.61 | 205.22 | 0.00 | 0.00 |
Maximum of Months | 898.75 | 1155.32 | 833.29 | 503.40 | 527.29 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.185774E+10 | 0.231538E+10 | 0.217426E+10 | 0.151562E+10 | 0.658646E+09 | 0.00 | 0.00 |
February | 0.236373E+10 | 0.176126E+10 | 0.245165E+10 | 0.164987E+10 | 0.801775E+09 | 0.00 | 0.00 |
March | 0.236300E+10 | 0.160515E+10 | 0.238519E+10 | 0.150139E+10 | 0.883802E+09 | 0.00 | 0.00 |
April | 0.228396E+10 | 0.102088E+10 | 0.210728E+10 | 0.114215E+10 | 0.965132E+09 | 0.00 | 0.00 |
May | 0.222249E+10 | 0.576953E+09 | 0.186342E+10 | 0.656662E+09 | 0.120675E+10 | 0.00 | 0.00 |
June | 0.202071E+10 | 0.367348E+09 | 0.158436E+10 | 0.416550E+09 | 0.116781E+10 | 0.00 | 0.00 |
July | 0.239289E+10 | 0.350997E+09 | 0.180134E+10 | 0.572286E+09 | 0.122906E+10 | 0.00 | 0.00 |
August | 0.246353E+10 | 0.410921E+09 | 0.191187E+10 | 0.794265E+09 | 0.111760E+10 | 0.00 | 0.00 |
September | 0.232254E+10 | 0.638471E+09 | 0.195218E+10 | 0.102124E+10 | 0.930935E+09 | 0.00 | 0.00 |
October | 0.188829E+10 | 0.100544E+10 | 0.179444E+10 | 0.106998E+10 | 0.724468E+09 | 0.00 | 0.00 |
November | 0.138900E+10 | 0.143351E+10 | 0.151701E+10 | 0.951477E+09 | 0.565536E+09 | 0.00 | 0.00 |
December | 0.131353E+10 | 0.224686E+10 | 0.166997E+10 | 0.109596E+10 | 0.574011E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.248814E+11 | 0.137332E+11 | 0.232130E+11 | 0.123874E+11 | 0.108255E+11 | 0.00 | 0.00 |
Minimum of Months | 0.131353E+10 | 0.350997E+09 | 0.151701E+10 | 0.416550E+09 | 0.565536E+09 | 0.00 | 0.00 |
Maximum of Months | 0.246353E+10 | 0.231538E+10 | 0.245165E+10 | 0.164987E+10 | 0.122906E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.520621E+10 | 0.651786E+10 | 0.612258E+10 | 0.426788E+10 | 0.185470E+10 | 0.00 | 0.00 |
February | 0.663851E+10 | 0.495125E+10 | 0.690368E+10 | 0.464594E+10 | 0.225775E+10 | 0.00 | 0.00 |
March | 0.664404E+10 | 0.452109E+10 | 0.671653E+10 | 0.422781E+10 | 0.248873E+10 | 0.00 | 0.00 |
April | 0.643992E+10 | 0.286009E+10 | 0.593396E+10 | 0.321622E+10 | 0.271775E+10 | 0.00 | 0.00 |
May | 0.634765E+10 | 0.155216E+10 | 0.524726E+10 | 0.184912E+10 | 0.339814E+10 | 0.00 | 0.00 |
June | 0.580529E+10 | 0.959382E+09 | 0.446146E+10 | 0.117298E+10 | 0.328848E+10 | 0.00 | 0.00 |
July | 0.686683E+10 | 0.892620E+09 | 0.507246E+10 | 0.161152E+10 | 0.346095E+10 | 0.00 | 0.00 |
August | 0.702640E+10 | 0.106660E+10 | 0.538370E+10 | 0.223660E+10 | 0.314710E+10 | 0.00 | 0.00 |
September | 0.657411E+10 | 0.174558E+10 | 0.549721E+10 | 0.287576E+10 | 0.262145E+10 | 0.00 | 0.00 |
October | 0.530154E+10 | 0.283582E+10 | 0.505303E+10 | 0.301298E+10 | 0.204005E+10 | 0.00 | 0.00 |
November | 0.389301E+10 | 0.405275E+10 | 0.427181E+10 | 0.267930E+10 | 0.159251E+10 | 0.00 | 0.00 |
December | 0.367812E+10 | 0.632561E+10 | 0.470252E+10 | 0.308614E+10 | 0.161638E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.704216E+11 | 0.382808E+11 | 0.653662E+11 | 0.348822E+11 | 0.304840E+11 | 0.00 | 0.00 |
Minimum of Months | 0.367812E+10 | 0.892620E+09 | 0.427181E+10 | 0.117298E+10 | 0.159251E+10 | 0.00 | 0.00 |
Maximum of Months | 0.702640E+10 | 0.651786E+10 | 0.690368E+10 | 0.464594E+10 | 0.346095E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.683025E+10 | 0.874558E+10 | 0.795359E+10 | 0.554422E+10 | 0.240937E+10 | 0.00 | 0.00 |
February | 0.874597E+10 | 0.664803E+10 | 0.896828E+10 | 0.603534E+10 | 0.293294E+10 | 0.00 | 0.00 |
March | 0.875730E+10 | 0.610633E+10 | 0.872516E+10 | 0.549216E+10 | 0.323300E+10 | 0.00 | 0.00 |
April | 0.848115E+10 | 0.392133E+10 | 0.770856E+10 | 0.417805E+10 | 0.353051E+10 | 0.00 | 0.00 |
May | 0.831937E+10 | 0.217110E+10 | 0.681648E+10 | 0.240211E+10 | 0.441437E+10 | 0.00 | 0.00 |
June | 0.758908E+10 | 0.136878E+10 | 0.579569E+10 | 0.152376E+10 | 0.427192E+10 | 0.00 | 0.00 |
July | 0.899641E+10 | 0.126700E+10 | 0.658942E+10 | 0.209346E+10 | 0.449596E+10 | 0.00 | 0.00 |
August | 0.921473E+10 | 0.150851E+10 | 0.699373E+10 | 0.290547E+10 | 0.408826E+10 | 0.00 | 0.00 |
September | 0.862309E+10 | 0.244433E+10 | 0.714118E+10 | 0.373577E+10 | 0.340541E+10 | 0.00 | 0.00 |
October | 0.695341E+10 | 0.392736E+10 | 0.656418E+10 | 0.391403E+10 | 0.265015E+10 | 0.00 | 0.00 |
November | 0.510784E+10 | 0.554652E+10 | 0.554932E+10 | 0.348056E+10 | 0.206877E+10 | 0.00 | 0.00 |
December | 0.481515E+10 | 0.852557E+10 | 0.610884E+10 | 0.400907E+10 | 0.209977E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.924337E+11 | 0.521804E+11 | 0.849144E+11 | 0.453140E+11 | 0.396004E+11 | 0.00 | 0.00 |
Minimum of Months | 0.481515E+10 | 0.126700E+10 | 0.554932E+10 | 0.152376E+10 | 0.206877E+10 | 0.00 | 0.00 |
Maximum of Months | 0.921473E+10 | 0.874558E+10 | 0.896828E+10 | 0.603534E+10 | 0.449596E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.392336E+09 | 0.139558E+10 | 0.689727E+09 | 0.409623E+09 | 0.280104E+09 | 0.00 | 0.00 |
February | 0.669318E+09 | 0.104223E+10 | 0.864449E+09 | 0.500467E+09 | 0.363982E+09 | 0.00 | 0.00 |
March | 0.888136E+09 | 0.926198E+09 | 0.102324E+10 | 0.579842E+09 | 0.443393E+09 | 0.00 | 0.00 |
April | 0.111363E+10 | 0.562277E+09 | 0.109796E+10 | 0.571500E+09 | 0.526462E+09 | 0.00 | 0.00 |
May | 0.146051E+10 | 0.295847E+09 | 0.123423E+10 | 0.544170E+09 | 0.690061E+09 | 0.00 | 0.00 |
June | 0.142359E+10 | 0.176308E+09 | 0.111825E+10 | 0.430104E+09 | 0.688147E+09 | 0.00 | 0.00 |
July | 0.164291E+10 | 0.159222E+09 | 0.124543E+10 | 0.526789E+09 | 0.718639E+09 | 0.00 | 0.00 |
August | 0.141458E+10 | 0.190277E+09 | 0.110798E+10 | 0.487883E+09 | 0.620099E+09 | 0.00 | 0.00 |
September | 0.107818E+10 | 0.333648E+09 | 0.940560E+09 | 0.450933E+09 | 0.489627E+09 | 0.00 | 0.00 |
October | 0.680280E+09 | 0.567443E+09 | 0.717168E+09 | 0.357377E+09 | 0.359791E+09 | 0.00 | 0.00 |
November | 0.363070E+09 | 0.847120E+09 | 0.513300E+09 | 0.260635E+09 | 0.252665E+09 | 0.00 | 0.00 |
December | 0.249934E+09 | 0.136439E+10 | 0.524497E+09 | 0.283986E+09 | 0.240511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.113765E+11 | 0.786054E+10 | 0.110768E+11 | 0.540331E+10 | 0.567348E+10 | 0.00 | 0.00 |
Minimum of Months | 0.249934E+09 | 0.159222E+09 | 0.513300E+09 | 0.260635E+09 | 0.240511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164291E+10 | 0.139558E+10 | 0.124543E+10 | 0.579842E+09 | 0.718639E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 82710426.49 | 0.156490E+10 | 0.321789E+09 | 0.109959E+09 | 0.211830E+09 | 0.00 | 0.00 |
February | 0.240236E+09 | 0.112940E+10 | 0.465668E+09 | 0.174259E+09 | 0.291409E+09 | 0.00 | 0.00 |
March | 0.458116E+09 | 0.964687E+09 | 0.668749E+09 | 0.282997E+09 | 0.385753E+09 | 0.00 | 0.00 |
April | 0.745916E+09 | 0.562853E+09 | 0.830327E+09 | 0.347197E+09 | 0.483130E+09 | 0.00 | 0.00 |
May | 0.121476E+10 | 0.291673E+09 | 0.108172E+10 | 0.425746E+09 | 0.655971E+09 | 0.00 | 0.00 |
June | 0.127278E+10 | 0.178650E+09 | 0.103849E+10 | 0.373657E+09 | 0.664831E+09 | 0.00 | 0.00 |
July | 0.142392E+10 | 0.165549E+09 | 0.111995E+10 | 0.433829E+09 | 0.686122E+09 | 0.00 | 0.00 |
August | 0.110478E+10 | 0.200856E+09 | 0.905167E+09 | 0.334158E+09 | 0.571009E+09 | 0.00 | 0.00 |
September | 0.724672E+09 | 0.337666E+09 | 0.686598E+09 | 0.249150E+09 | 0.437448E+09 | 0.00 | 0.00 |
October | 0.353048E+09 | 0.579049E+09 | 0.456945E+09 | 0.145824E+09 | 0.311120E+09 | 0.00 | 0.00 |
November | 0.110446E+09 | 0.898525E+09 | 0.273958E+09 | 72511900.95 | 0.201446E+09 | 0.00 | 0.00 |
December | 39808568.18 | 0.151655E+10 | 0.246806E+09 | 67296880.31 | 0.179509E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.777120E+10 | 0.839035E+10 | 0.809616E+10 | 0.301658E+10 | 0.507958E+10 | 0.00 | 0.00 |
Minimum of Months | 39808568.18 | 0.165549E+09 | 0.246806E+09 | 67296880.31 | 0.179509E+09 | 0.00 | 0.00 |
Maximum of Months | 0.142392E+10 | 0.156490E+10 | 0.111995E+10 | 0.433829E+09 | 0.686122E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.307165E+09 | 0.334603E+09 | 0.343844E+09 | 0.239683E+09 | 0.104160E+09 | 0.00 | 0.00 |
February | 0.382290E+09 | 0.263723E+09 | 0.387710E+09 | 0.260915E+09 | 0.126795E+09 | 0.00 | 0.00 |
March | 0.375583E+09 | 0.257036E+09 | 0.377200E+09 | 0.237433E+09 | 0.139767E+09 | 0.00 | 0.00 |
April | 0.343940E+09 | 0.200498E+09 | 0.333252E+09 | 0.180622E+09 | 0.152630E+09 | 0.00 | 0.00 |
May | 0.328483E+09 | 0.121657E+09 | 0.294687E+09 | 0.103846E+09 | 0.190841E+09 | 0.00 | 0.00 |
June | 0.296801E+09 | 81785685.03 | 0.250556E+09 | 65874196.92 | 0.184682E+09 | 0.00 | 0.00 |
July | 0.358233E+09 | 76177653.64 | 0.284871E+09 | 90502604.60 | 0.194368E+09 | 0.00 | 0.00 |
August | 0.369548E+09 | 91018089.70 | 0.302349E+09 | 0.125607E+09 | 0.176742E+09 | 0.00 | 0.00 |
September | 0.346637E+09 | 0.137049E+09 | 0.308723E+09 | 0.161502E+09 | 0.147221E+09 | 0.00 | 0.00 |
October | 0.282819E+09 | 0.198078E+09 | 0.283778E+09 | 0.169208E+09 | 0.114570E+09 | 0.00 | 0.00 |
November | 0.219537E+09 | 0.229594E+09 | 0.239904E+09 | 0.150469E+09 | 89435632.70 | 0.00 | 0.00 |
December | 0.219305E+09 | 0.318629E+09 | 0.264093E+09 | 0.173317E+09 | 90775828.88 | 0.00 | 0.00 |
Annual Sum or Average | 0.383034E+10 | 0.230985E+10 | 0.367097E+10 | 0.195898E+10 | 0.171199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.219305E+09 | 76177653.64 | 0.239904E+09 | 65874196.92 | 89435632.70 | 0.00 | 0.00 |
Maximum of Months | 0.382290E+09 | 0.334603E+09 | 0.387710E+09 | 0.260915E+09 | 0.194368E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 197631.61 | 0.480001E+09 | 49567917.68 | 0.00 | 49567917.68 | 0.00 | 0.00 |
February | 4448879.80 | 0.345327E+09 | 68771805.56 | 0.00 | 68771805.56 | 0.00 | 0.00 |
March | 15812788.43 | 0.290736E+09 | 93698777.38 | 3524.69 | 93695252.70 | 0.00 | 0.00 |
April | 61763012.74 | 0.162133E+09 | 0.119226E+09 | 1215669.98 | 0.118010E+09 | 0.00 | 0.00 |
May | 0.171583E+09 | 76525946.10 | 0.172757E+09 | 9128968.36 | 0.163629E+09 | 0.00 | 0.00 |
June | 0.226708E+09 | 46673770.52 | 0.186821E+09 | 20732454.75 | 0.166088E+09 | 0.00 | 0.00 |
July | 0.235628E+09 | 41836979.20 | 0.184570E+09 | 16154252.14 | 0.168416E+09 | 0.00 | 0.00 |
August | 0.162910E+09 | 51892075.52 | 0.140176E+09 | 2651765.93 | 0.137524E+09 | 0.00 | 0.00 |
September | 91054071.03 | 94467669.80 | 0.105629E+09 | 107904.96 | 0.105521E+09 | 0.00 | 0.00 |
October | 30905710.39 | 0.170686E+09 | 75666086.86 | 0.00 | 75666086.86 | 0.00 | 0.00 |
November | 3923193.02 | 0.273510E+09 | 48484387.70 | 0.00 | 48484387.70 | 0.00 | 0.00 |
December | 0.00 | 0.460690E+09 | 41997873.92 | 0.00 | 41997873.92 | 0.00 | 0.00 |
Annual Sum or Average | 0.100493E+10 | 0.249448E+10 | 0.128737E+10 | 49994540.81 | 0.123737E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 41836979.20 | 41997873.92 | 0.00 | 41997873.92 | 0.00 | 0.00 |
Maximum of Months | 0.235628E+09 | 0.480001E+09 | 0.186821E+09 | 20732454.75 | 0.168416E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.379804E+09 | 0.138673E+10 | 0.682717E+09 | 0.404459E+09 | 0.278259E+09 | 0.00 | 0.00 |
February | 0.637243E+09 | 0.102560E+10 | 0.847671E+09 | 0.482280E+09 | 0.365391E+09 | 0.00 | 0.00 |
March | 0.858834E+09 | 0.906057E+09 | 0.101788E+10 | 0.571508E+09 | 0.446370E+09 | 0.00 | 0.00 |
April | 0.115454E+10 | 0.543692E+09 | 0.114478E+10 | 0.618417E+09 | 0.526358E+09 | 0.00 | 0.00 |
May | 0.137796E+10 | 0.276870E+09 | 0.118558E+10 | 0.490288E+09 | 0.695295E+09 | 0.00 | 0.00 |
June | 0.153119E+10 | 0.168457E+09 | 0.120560E+10 | 0.509230E+09 | 0.696367E+09 | 0.00 | 0.00 |
July | 0.165462E+10 | 0.150499E+09 | 0.126136E+10 | 0.539074E+09 | 0.722287E+09 | 0.00 | 0.00 |
August | 0.136094E+10 | 0.183336E+09 | 0.107475E+10 | 0.461574E+09 | 0.613178E+09 | 0.00 | 0.00 |
September | 0.105213E+10 | 0.324254E+09 | 0.927380E+09 | 0.444870E+09 | 0.482510E+09 | 0.00 | 0.00 |
October | 0.640196E+09 | 0.560221E+09 | 0.691590E+09 | 0.338193E+09 | 0.353397E+09 | 0.00 | 0.00 |
November | 0.351737E+09 | 0.838560E+09 | 0.508693E+09 | 0.257626E+09 | 0.251067E+09 | 0.00 | 0.00 |
December | 0.252972E+09 | 0.135949E+10 | 0.528495E+09 | 0.291103E+09 | 0.237392E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112522E+11 | 0.772377E+10 | 0.110765E+11 | 0.540862E+10 | 0.566787E+10 | 0.00 | 0.00 |
Minimum of Months | 0.252972E+09 | 0.150499E+09 | 0.508693E+09 | 0.257626E+09 | 0.237392E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165462E+10 | 0.138673E+10 | 0.126136E+10 | 0.618417E+09 | 0.722287E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 59247033.81 | 0.154465E+10 | 0.314779E+09 | 0.104795E+09 | 0.209984E+09 | 0.00 | 0.00 |
February | 0.188657E+09 | 0.109297E+10 | 0.448890E+09 | 0.156071E+09 | 0.292819E+09 | 0.00 | 0.00 |
March | 0.416259E+09 | 0.930418E+09 | 0.663392E+09 | 0.274662E+09 | 0.388729E+09 | 0.00 | 0.00 |
April | 0.781610E+09 | 0.539223E+09 | 0.877140E+09 | 0.394114E+09 | 0.483026E+09 | 0.00 | 0.00 |
May | 0.114151E+10 | 0.275502E+09 | 0.103307E+10 | 0.371865E+09 | 0.661205E+09 | 0.00 | 0.00 |
June | 0.138660E+10 | 0.172621E+09 | 0.112583E+10 | 0.452783E+09 | 0.673051E+09 | 0.00 | 0.00 |
July | 0.143974E+10 | 0.158387E+09 | 0.113588E+10 | 0.446113E+09 | 0.689770E+09 | 0.00 | 0.00 |
August | 0.105566E+10 | 0.191811E+09 | 0.871938E+09 | 0.307849E+09 | 0.564089E+09 | 0.00 | 0.00 |
September | 0.699513E+09 | 0.324693E+09 | 0.673418E+09 | 0.243087E+09 | 0.430330E+09 | 0.00 | 0.00 |
October | 0.306155E+09 | 0.563957E+09 | 0.431367E+09 | 0.126641E+09 | 0.304726E+09 | 0.00 | 0.00 |
November | 93478209.54 | 0.884874E+09 | 0.269351E+09 | 69502968.90 | 0.199848E+09 | 0.00 | 0.00 |
December | 34225194.70 | 0.150207E+10 | 0.250804E+09 | 74413933.70 | 0.176390E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.760265E+10 | 0.818117E+10 | 0.809587E+10 | 0.302190E+10 | 0.507397E+10 | 0.00 | 0.00 |
Minimum of Months | 34225194.70 | 0.158387E+09 | 0.250804E+09 | 69502968.90 | 0.176390E+09 | 0.00 | 0.00 |
Maximum of Months | 0.143974E+10 | 0.154465E+10 | 0.113588E+10 | 0.452783E+09 | 0.689770E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.470571E+09 | 0.176328E+10 | 0.852394E+09 | 0.519327E+09 | 0.333067E+09 | 0.00 | 0.00 |
February | 0.728604E+09 | 0.131815E+10 | 0.989043E+09 | 0.565330E+09 | 0.423713E+09 | 0.00 | 0.00 |
March | 0.803252E+09 | 0.117828E+10 | 0.102027E+10 | 0.514458E+09 | 0.505813E+09 | 0.00 | 0.00 |
April | 0.919625E+09 | 0.716024E+09 | 0.980347E+09 | 0.393991E+09 | 0.586356E+09 | 0.00 | 0.00 |
May | 0.113870E+10 | 0.368175E+09 | 0.101275E+10 | 0.244782E+09 | 0.767973E+09 | 0.00 | 0.00 |
June | 0.118572E+10 | 0.228195E+09 | 0.947602E+09 | 0.187645E+09 | 0.759958E+09 | 0.00 | 0.00 |
July | 0.132882E+10 | 0.217888E+09 | 0.101708E+10 | 0.231090E+09 | 0.785986E+09 | 0.00 | 0.00 |
August | 0.120397E+10 | 0.262963E+09 | 0.958773E+09 | 0.277900E+09 | 0.680874E+09 | 0.00 | 0.00 |
September | 0.100060E+10 | 0.438298E+09 | 0.897745E+09 | 0.350163E+09 | 0.547581E+09 | 0.00 | 0.00 |
October | 0.708269E+09 | 0.719940E+09 | 0.778786E+09 | 0.366628E+09 | 0.412159E+09 | 0.00 | 0.00 |
November | 0.434322E+09 | 0.107816E+10 | 0.624840E+09 | 0.326024E+09 | 0.298816E+09 | 0.00 | 0.00 |
December | 0.315927E+09 | 0.172908E+10 | 0.663197E+09 | 0.375530E+09 | 0.287667E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102384E+11 | 0.100184E+11 | 0.107428E+11 | 0.435287E+10 | 0.638996E+10 | 0.00 | 0.00 |
Minimum of Months | 0.315927E+09 | 0.217888E+09 | 0.624840E+09 | 0.187645E+09 | 0.287667E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132882E+10 | 0.176328E+10 | 0.102027E+10 | 0.565330E+09 | 0.785986E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.391247E+09 | 0.139471E+10 | 0.689727E+09 | 0.409623E+09 | 0.280104E+09 | 0.00 | 0.00 |
February | 0.667203E+09 | 0.104111E+10 | 0.864449E+09 | 0.500467E+09 | 0.363982E+09 | 0.00 | 0.00 |
March | 0.886126E+09 | 0.923979E+09 | 0.102324E+10 | 0.579842E+09 | 0.443393E+09 | 0.00 | 0.00 |
April | 0.110926E+10 | 0.559313E+09 | 0.109796E+10 | 0.571500E+09 | 0.526462E+09 | 0.00 | 0.00 |
May | 0.145290E+10 | 0.293644E+09 | 0.123423E+10 | 0.544170E+09 | 0.690061E+09 | 0.00 | 0.00 |
June | 0.141705E+10 | 0.173971E+09 | 0.111825E+10 | 0.430104E+09 | 0.688147E+09 | 0.00 | 0.00 |
July | 0.163603E+10 | 0.156404E+09 | 0.124543E+10 | 0.526789E+09 | 0.718639E+09 | 0.00 | 0.00 |
August | 0.140849E+10 | 0.187448E+09 | 0.110798E+10 | 0.487883E+09 | 0.620099E+09 | 0.00 | 0.00 |
September | 0.107400E+10 | 0.330440E+09 | 0.940560E+09 | 0.450933E+09 | 0.489627E+09 | 0.00 | 0.00 |
October | 0.679996E+09 | 0.562761E+09 | 0.717168E+09 | 0.357377E+09 | 0.359791E+09 | 0.00 | 0.00 |
November | 0.363688E+09 | 0.843511E+09 | 0.513300E+09 | 0.260635E+09 | 0.252665E+09 | 0.00 | 0.00 |
December | 0.248910E+09 | 0.136529E+10 | 0.524497E+09 | 0.283986E+09 | 0.240511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.113349E+11 | 0.783258E+10 | 0.110768E+11 | 0.540331E+10 | 0.567348E+10 | 0.00 | 0.00 |
Minimum of Months | 0.248910E+09 | 0.156404E+09 | 0.513300E+09 | 0.260635E+09 | 0.240511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.163603E+10 | 0.139471E+10 | 0.124543E+10 | 0.579842E+09 | 0.718639E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 82501399.47 | 0.156243E+10 | 0.321789E+09 | 0.109959E+09 | 0.211830E+09 | 0.00 | 0.00 |
February | 0.239700E+09 | 0.112866E+10 | 0.465668E+09 | 0.174259E+09 | 0.291409E+09 | 0.00 | 0.00 |
March | 0.457217E+09 | 0.962565E+09 | 0.668749E+09 | 0.282997E+09 | 0.385753E+09 | 0.00 | 0.00 |
April | 0.743347E+09 | 0.560124E+09 | 0.830327E+09 | 0.347197E+09 | 0.483130E+09 | 0.00 | 0.00 |
May | 0.120585E+10 | 0.292246E+09 | 0.108172E+10 | 0.425746E+09 | 0.655971E+09 | 0.00 | 0.00 |
June | 0.126385E+10 | 0.179806E+09 | 0.103849E+10 | 0.373657E+09 | 0.664831E+09 | 0.00 | 0.00 |
July | 0.141550E+10 | 0.166246E+09 | 0.111995E+10 | 0.433829E+09 | 0.686122E+09 | 0.00 | 0.00 |
August | 0.109800E+10 | 0.201773E+09 | 0.905167E+09 | 0.334158E+09 | 0.571009E+09 | 0.00 | 0.00 |
September | 0.721868E+09 | 0.335438E+09 | 0.686598E+09 | 0.249150E+09 | 0.437448E+09 | 0.00 | 0.00 |
October | 0.354588E+09 | 0.573539E+09 | 0.456945E+09 | 0.145824E+09 | 0.311120E+09 | 0.00 | 0.00 |
November | 0.111564E+09 | 0.894701E+09 | 0.273958E+09 | 72511900.95 | 0.201446E+09 | 0.00 | 0.00 |
December | 39647379.17 | 0.151662E+10 | 0.246806E+09 | 67296880.31 | 0.179509E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.773364E+10 | 0.837415E+10 | 0.809616E+10 | 0.301658E+10 | 0.507958E+10 | 0.00 | 0.00 |
Minimum of Months | 39647379.17 | 0.166246E+09 | 0.246806E+09 | 67296880.31 | 0.179509E+09 | 0.00 | 0.00 |
Maximum of Months | 0.141550E+10 | 0.156243E+10 | 0.111995E+10 | 0.433829E+09 | 0.686122E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.527035E+09 | 0.705141E+09 | 0.630475E+09 | 0.439486E+09 | 0.190989E+09 | 0.00 | 0.00 |
February | 0.671772E+09 | 0.533739E+09 | 0.710909E+09 | 0.478416E+09 | 0.232493E+09 | 0.00 | 0.00 |
March | 0.677249E+09 | 0.482507E+09 | 0.691638E+09 | 0.435359E+09 | 0.256279E+09 | 0.00 | 0.00 |
April | 0.657929E+09 | 0.298857E+09 | 0.611053E+09 | 0.331190E+09 | 0.279863E+09 | 0.00 | 0.00 |
May | 0.651174E+09 | 0.152838E+09 | 0.540340E+09 | 0.190413E+09 | 0.349927E+09 | 0.00 | 0.00 |
June | 0.601210E+09 | 88860795.61 | 0.459423E+09 | 0.120788E+09 | 0.338635E+09 | 0.00 | 0.00 |
July | 0.713816E+09 | 78023230.24 | 0.522341E+09 | 0.165946E+09 | 0.356395E+09 | 0.00 | 0.00 |
August | 0.726328E+09 | 94985189.75 | 0.554390E+09 | 0.230314E+09 | 0.324076E+09 | 0.00 | 0.00 |
September | 0.675123E+09 | 0.172635E+09 | 0.566078E+09 | 0.296131E+09 | 0.269946E+09 | 0.00 | 0.00 |
October | 0.544768E+09 | 0.293313E+09 | 0.520338E+09 | 0.310262E+09 | 0.210076E+09 | 0.00 | 0.00 |
November | 0.395806E+09 | 0.431408E+09 | 0.439891E+09 | 0.275901E+09 | 0.163990E+09 | 0.00 | 0.00 |
December | 0.371576E+09 | 0.683678E+09 | 0.484243E+09 | 0.317796E+09 | 0.166447E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.721379E+10 | 0.401598E+10 | 0.673112E+10 | 0.359200E+10 | 0.313912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.371576E+09 | 78023230.24 | 0.439891E+09 | 0.120788E+09 | 0.163990E+09 | 0.00 | 0.00 |
Maximum of Months | 0.726328E+09 | 0.705141E+09 | 0.710909E+09 | 0.478416E+09 | 0.356395E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1078873.98 | 0.428855E+10 | 0.433645E+09 | 0.00 | 0.433645E+09 | 0.00 | 0.00 |
February | 32175245.26 | 0.309196E+10 | 0.601651E+09 | 0.00 | 0.601651E+09 | 0.00 | 0.00 |
March | 0.122615E+09 | 0.262074E+10 | 0.819725E+09 | 30835.75 | 0.819694E+09 | 0.00 | 0.00 |
April | 0.514496E+09 | 0.148955E+10 | 0.104305E+10 | 10635299.72 | 0.103241E+10 | 0.00 | 0.00 |
May | 0.147651E+10 | 0.728708E+09 | 0.151137E+10 | 79864861.37 | 0.143151E+10 | 0.00 | 0.00 |
June | 0.196932E+10 | 0.454716E+09 | 0.163440E+10 | 0.181378E+09 | 0.145303E+10 | 0.00 | 0.00 |
July | 0.205722E+10 | 0.411659E+09 | 0.161471E+10 | 0.141326E+09 | 0.147339E+10 | 0.00 | 0.00 |
August | 0.141905E+10 | 0.511375E+09 | 0.122633E+10 | 23198997.94 | 0.120313E+10 | 0.00 | 0.00 |
September | 0.777278E+09 | 0.901058E+09 | 0.924096E+09 | 944007.52 | 0.923152E+09 | 0.00 | 0.00 |
October | 0.253697E+09 | 0.156829E+10 | 0.661965E+09 | 0.00 | 0.661965E+09 | 0.00 | 0.00 |
November | 30427044.26 | 0.248061E+10 | 0.424166E+09 | 0.00 | 0.424166E+09 | 0.00 | 0.00 |
December | 0.00 | 0.412831E+10 | 0.367419E+09 | 0.00 | 0.367419E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.865387E+10 | 0.226755E+11 | 0.112625E+11 | 0.437378E+09 | 0.108252E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.411659E+09 | 0.367419E+09 | 0.00 | 0.367419E+09 | 0.00 | 0.00 |
Maximum of Months | 0.205722E+10 | 0.428855E+10 | 0.163440E+10 | 0.181378E+09 | 0.147339E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 888581.76 | 0.434908E+10 | 0.433645E+09 | 0.00 | 0.433645E+09 | 0.00 | 0.00 |
February | 29133524.16 | 0.314929E+10 | 0.601651E+09 | 0.00 | 0.601651E+09 | 0.00 | 0.00 |
March | 0.113158E+09 | 0.268638E+10 | 0.819725E+09 | 30835.75 | 0.819694E+09 | 0.00 | 0.00 |
April | 0.490037E+09 | 0.154117E+10 | 0.104305E+10 | 10635299.72 | 0.103241E+10 | 0.00 | 0.00 |
May | 0.144233E+10 | 0.753632E+09 | 0.151137E+10 | 79864861.37 | 0.143151E+10 | 0.00 | 0.00 |
June | 0.193476E+10 | 0.472476E+09 | 0.163440E+10 | 0.181378E+09 | 0.145303E+10 | 0.00 | 0.00 |
July | 0.202338E+10 | 0.429359E+09 | 0.161471E+10 | 0.141326E+09 | 0.147339E+10 | 0.00 | 0.00 |
August | 0.138978E+10 | 0.534738E+09 | 0.122633E+10 | 23198997.94 | 0.120313E+10 | 0.00 | 0.00 |
September | 0.753124E+09 | 0.935665E+09 | 0.924096E+09 | 944007.52 | 0.923152E+09 | 0.00 | 0.00 |
October | 0.235482E+09 | 0.163026E+10 | 0.661965E+09 | 0.00 | 0.661965E+09 | 0.00 | 0.00 |
November | 26742514.26 | 0.255505E+10 | 0.424166E+09 | 0.00 | 0.424166E+09 | 0.00 | 0.00 |
December | 0.00 | 0.419072E+10 | 0.367419E+09 | 0.00 | 0.367419E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.843882E+10 | 0.232278E+11 | 0.112625E+11 | 0.437378E+09 | 0.108252E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.429359E+09 | 0.367419E+09 | 0.00 | 0.367419E+09 | 0.00 | 0.00 |
Maximum of Months | 0.202338E+10 | 0.434908E+10 | 0.163440E+10 | 0.181378E+09 | 0.147339E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.441619E+09 | 0.269452E+10 | 0.997460E+09 | 0.509239E+09 | 0.488222E+09 | 0.00 | 0.00 |
February | 0.910571E+09 | 0.197639E+10 | 0.129651E+10 | 0.638329E+09 | 0.658181E+09 | 0.00 | 0.00 |
March | 0.145400E+10 | 0.172282E+10 | 0.168119E+10 | 0.846131E+09 | 0.835061E+09 | 0.00 | 0.00 |
April | 0.225814E+10 | 0.104179E+10 | 0.202181E+10 | 0.101248E+10 | 0.100934E+10 | 0.00 | 0.00 |
May | 0.302461E+10 | 0.550849E+09 | 0.221854E+10 | 0.862102E+09 | 0.135644E+10 | 0.00 | 0.00 |
June | 0.345501E+10 | 0.352263E+09 | 0.233131E+10 | 0.961953E+09 | 0.136935E+10 | 0.00 | 0.00 |
July | 0.368404E+10 | 0.312669E+09 | 0.239711E+10 | 0.985126E+09 | 0.141199E+10 | 0.00 | 0.00 |
August | 0.293939E+10 | 0.360095E+09 | 0.194659E+10 | 0.769380E+09 | 0.117721E+10 | 0.00 | 0.00 |
September | 0.214370E+10 | 0.601089E+09 | 0.160072E+10 | 0.687923E+09 | 0.912798E+09 | 0.00 | 0.00 |
October | 0.118789E+10 | 0.102537E+10 | 0.112291E+10 | 0.464816E+09 | 0.658093E+09 | 0.00 | 0.00 |
November | 0.536571E+09 | 0.157696E+10 | 0.778014E+09 | 0.327119E+09 | 0.450895E+09 | 0.00 | 0.00 |
December | 0.279101E+09 | 0.262367E+10 | 0.779271E+09 | 0.365507E+09 | 0.413764E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.223147E+11 | 0.148385E+11 | 0.191714E+11 | 0.843010E+10 | 0.107413E+11 | 0.00 | 0.00 |
Minimum of Months | 0.279101E+09 | 0.312669E+09 | 0.778014E+09 | 0.327119E+09 | 0.413764E+09 | 0.00 | 0.00 |
Maximum of Months | 0.368404E+10 | 0.269452E+10 | 0.239711E+10 | 0.101248E+10 | 0.141199E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111484E+10 | 0.309441E+10 | 0.175356E+10 | 0.111873E+10 | 0.634828E+09 | 0.00 | 0.00 |
February | 0.160435E+10 | 0.232327E+10 | 0.201590E+10 | 0.121783E+10 | 0.798070E+09 | 0.00 | 0.00 |
March | 0.171044E+10 | 0.209510E+10 | 0.204160E+10 | 0.110824E+10 | 0.933364E+09 | 0.00 | 0.00 |
April | 0.183303E+10 | 0.131647E+10 | 0.191303E+10 | 0.846708E+09 | 0.106632E+10 | 0.00 | 0.00 |
May | 0.207847E+10 | 0.722091E+09 | 0.189357E+10 | 0.512084E+09 | 0.138148E+10 | 0.00 | 0.00 |
June | 0.208790E+10 | 0.455382E+09 | 0.172976E+10 | 0.369648E+09 | 0.136011E+10 | 0.00 | 0.00 |
July | 0.240721E+10 | 0.421097E+09 | 0.188317E+10 | 0.470872E+09 | 0.141230E+10 | 0.00 | 0.00 |
August | 0.224847E+10 | 0.525974E+09 | 0.183162E+10 | 0.594229E+09 | 0.123739E+10 | 0.00 | 0.00 |
September | 0.193462E+10 | 0.852392E+09 | 0.175776E+10 | 0.754142E+09 | 0.100362E+10 | 0.00 | 0.00 |
October | 0.144138E+10 | 0.132367E+10 | 0.155147E+10 | 0.789789E+09 | 0.761683E+09 | 0.00 | 0.00 |
November | 0.947207E+09 | 0.191306E+10 | 0.126517E+10 | 0.702321E+09 | 0.562850E+09 | 0.00 | 0.00 |
December | 0.759037E+09 | 0.303958E+10 | 0.135862E+10 | 0.808966E+09 | 0.549653E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.201670E+11 | 0.180825E+11 | 0.209952E+11 | 0.929357E+10 | 0.117017E+11 | 0.00 | 0.00 |
Minimum of Months | 0.759037E+09 | 0.421097E+09 | 0.126517E+10 | 0.369648E+09 | 0.549653E+09 | 0.00 | 0.00 |
Maximum of Months | 0.240721E+10 | 0.309441E+10 | 0.204160E+10 | 0.121783E+10 | 0.141230E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770457E+10 | -0.754277E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161798967.2 | 81.21 | 0.00 | 0.00 |
February | 0.696188E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145919744.6 | 81.21 | 0.00 | 0.00 |
March | 0.770291E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161445817.7 | 81.21 | 0.00 | 0.00 |
April | 0.746480E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156207667.7 | 81.21 | 0.00 | 0.00 |
May | 0.770420E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413823.9 | 81.21 | 0.00 | 0.00 |
June | 0.745674E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156205578.9 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161411617.7 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161412220.6 | 81.21 | 0.00 | 0.00 |
September | 0.746614E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156206327.8 | 81.21 | 0.00 | 0.00 |
October | 0.770285E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413891.6 | 81.21 | 0.00 | 0.00 |
November | 0.744863E+10 | -0.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156207438.6 | 81.21 | 0.00 | 0.00 |
December | 0.771252E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161665807.5 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907417E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190131E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696188E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161798967.2 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771252E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145919744.6 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.129314E+12 | -0.127571E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174303E+10 | 80.10 | 0.00 | 0.00 |
February | 0.116967E+12 | -0.115405E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.156156E+10 | 79.76 | 0.00 | 0.00 |
March | 0.129476E+12 | -0.127730E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174577E+10 | 79.82 | 0.00 | 0.00 |
April | 0.125057E+12 | -0.123350E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170629E+10 | 80.28 | 0.00 | 0.00 |
May | 0.128810E+12 | -0.127032E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177871E+10 | 81.04 | 0.00 | 0.00 |
June | 0.120991E+12 | -0.119269E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.172116E+10 | 81.30 | 0.00 | 0.00 |
July | 0.120325E+12 | -0.118564E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176067E+10 | 81.27 | 0.00 | 0.00 |
August | 0.117900E+12 | -0.116158E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174239E+10 | 81.26 | 0.00 | 0.00 |
September | 0.114501E+12 | -0.112822E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167881E+10 | 81.26 | 0.00 | 0.00 |
October | 0.121426E+12 | -0.119692E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173313E+10 | 81.26 | 0.00 | 0.00 |
November | 0.122520E+12 | -0.120840E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168096E+10 | 81.32 | 0.00 | 0.00 |
December | 0.128918E+12 | -0.127175E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174316E+10 | 80.80 | 0.00 | 0.00 |
Annual Sum or Average | 0.147620E+13 | -0.145561E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205956E+11 | 80.79 | 0.00 | 0.00 |
Minimum of Months | 0.114501E+12 | -0.127730E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.177871E+10 | 79.76 | 0.00 | 0.00 |
Maximum of Months | 0.129476E+12 | -0.112822E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156156E+10 | 81.32 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.849645E+11 | -0.834307E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153384E+10 | 58.99 | 0.00 | 0.00 |
February | 0.784877E+11 | -0.771070E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.138075E+10 | 58.99 | 0.00 | 0.00 |
March | 0.866344E+11 | -0.850849E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154952E+10 | 58.99 | 0.00 | 0.00 |
April | 0.813033E+11 | -0.797992E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.150408E+10 | 58.99 | 0.00 | 0.00 |
May | 0.798347E+11 | -0.782904E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154434E+10 | 58.99 | 0.00 | 0.00 |
June | 0.727772E+11 | -0.712937E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.148349E+10 | 58.98 | 0.00 | 0.00 |
July | 0.712491E+11 | -0.697395E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150961E+10 | 58.98 | 0.00 | 0.00 |
August | 0.692379E+11 | -0.677534E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148451E+10 | 58.98 | 0.00 | 0.00 |
September | 0.673102E+11 | -0.658838E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142640E+10 | 58.98 | 0.00 | 0.00 |
October | 0.721694E+11 | -0.706979E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147151E+10 | 58.98 | 0.00 | 0.00 |
November | 0.739164E+11 | -0.724892E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142714E+10 | 58.98 | 0.00 | 0.00 |
December | 0.810490E+11 | -0.795441E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150486E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.918934E+12 | -0.901114E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.178201E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.673102E+11 | -0.850849E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.154952E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.866344E+11 | -0.658838E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.138075E+10 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.86 | 0.86 | 01-JAN-08:39 | 4251.13 | 35.65 | 234.50 | 240.00 | 3525.70 | 36.63 | 239.50 | 221.67 |
February | 265.33 | 0.86 | 0.86 | 01-FEB-08:39 | 6752.40 | 35.79 | 258.17 | 257.17 | 2831.09 | 31.86 | 258.00 | 238.00 |
March | 254.17 | 0.87 | 0.86 | 02-MAR-10:39 | 8791.73 | 33.54 | 207.67 | 321.17 | 791.87 | 22.76 | 218.17 | 268.17 |
April | 296.33 | 0.87 | 0.86 | 01-APR-07:00 | 1504.26 | 20.53 | 83.33 | 352.00 | 612.36 | 22.15 | 231.50 | 290.67 |
May | 437.50 | 0.87 | 0.86 | 01-MAY-06:40 | 1412.98 | 20.17 | 93.33 | 410.83 | 551.91 | 21.89 | 306.50 | 338.83 |
June | 401.83 | 0.87 | 0.86 | 01-JUN-05:30 | 1343.36 | 20.21 | 131.00 | 412.67 | 535.66 | 21.94 | 276.33 | 340.00 |
July | 409.17 | 0.87 | 0.86 | 01-JUL-05:40 | 1444.08 | 20.57 | 151.67 | 417.83 | 579.33 | 22.30 | 305.50 | 348.67 |
August | 352.83 | 0.87 | 0.86 | 01-AUG-07:40 | 1697.46 | 20.74 | 144.83 | 378.17 | 669.64 | 22.46 | 264.67 | 313.83 |
September | 344.17 | 0.87 | 0.86 | 01-SEP-06:49 | 2966.41 | 23.83 | 173.67 | 330.67 | 674.07 | 22.01 | 232.50 | 278.67 |
October | 299.00 | 0.87 | 0.86 | 01-OCT-06:49 | 4862.38 | 31.84 | 269.00 | 296.67 | 957.28 | 24.52 | 208.50 | 258.33 |
November | 255.50 | 0.87 | 0.86 | 01-NOV-08:09 | 3382.85 | 34.26 | 245.00 | 242.33 | 2668.51 | 34.87 | 245.17 | 212.17 |
December | 226.33 | 0.87 | 0.86 | 01-DEC-08:20 | 3112.08 | 33.70 | 209.83 | 225.83 | 2470.11 | 34.74 | 215.67 | 198.50 |
Annual Sum or Average | 3785.50 | 0.87 | 3142.96 | 26.30 | 2202.00 | 3885.33 | 1236.55 | 25.58 | 3002.00 | 3307.50 | ||
Minimum of Months | 226.33 | 0.86 | 0.86 | 1343.36 | 20.17 | 83.33 | 225.83 | 535.66 | 21.89 | 208.50 | 198.50 | |
Maximum of Months | 437.50 | 0.87 | 0.86 | 8791.73 | 35.79 | 269.00 | 417.83 | 3525.70 | 36.63 | 306.50 | 348.67 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.23 | 0.22 | 01-JAN-08:30 | 4669.21 | 35.75 | 235.17 | 247.33 | 3941.80 | 36.71 | 241.17 | 233.50 |
February | 265.33 | 0.24 | 0.22 | 01-FEB-08:39 | 7239.59 | 35.88 | 258.50 | 264.67 | 3313.61 | 31.74 | 234.83 | 249.50 |
March | 254.17 | 0.25 | 0.22 | 02-MAR-10:39 | 9284.73 | 33.72 | 211.33 | 332.50 | 1282.98 | 22.56 | 211.00 | 300.33 |
April | 296.33 | 0.25 | 0.22 | 01-APR-07:40 | 1889.36 | 20.61 | 78.00 | 367.00 | 996.39 | 22.11 | 235.17 | 332.33 |
May | 437.50 | 0.25 | 0.22 | 01-MAY-05:00 | 1678.50 | 20.62 | 135.67 | 426.67 | 816.48 | 22.17 | 319.50 | 387.83 |
June | 401.83 | 0.25 | 0.22 | 01-JUN-05:10 | 1586.93 | 20.73 | 164.00 | 430.67 | 778.38 | 22.28 | 303.83 | 386.17 |
July | 409.17 | 0.25 | 0.22 | 01-JUL-05:10 | 1716.92 | 21.00 | 194.00 | 434.17 | 851.26 | 22.56 | 325.00 | 395.17 |
August | 352.83 | 0.24 | 0.22 | 01-AUG-07:40 | 2022.85 | 21.07 | 161.33 | 390.67 | 993.84 | 22.64 | 283.17 | 353.33 |
September | 344.17 | 0.24 | 0.22 | 01-SEP-06:30 | 3304.93 | 24.06 | 178.67 | 341.67 | 1011.56 | 22.18 | 238.83 | 312.83 |
October | 299.00 | 0.24 | 0.22 | 01-OCT-06:49 | 5194.58 | 32.01 | 271.33 | 306.83 | 1290.23 | 24.65 | 211.50 | 280.50 |
November | 255.50 | 0.24 | 0.22 | 01-NOV-07:00 | 3681.88 | 34.35 | 245.67 | 250.50 | 2966.87 | 34.96 | 248.17 | 229.67 |
December | 226.33 | 0.23 | 0.22 | 01-DEC-08:09 | 3437.32 | 33.84 | 211.00 | 235.00 | 2793.44 | 34.85 | 216.67 | 213.17 |
Annual Sum or Average | 3785.50 | 0.24 | 3480.23 | 26.57 | 2344.67 | 4027.67 | 1572.55 | 25.71 | 3068.83 | 3674.33 | ||
Minimum of Months | 226.33 | 0.23 | 0.22 | 1586.93 | 20.61 | 78.00 | 235.00 | 778.38 | 22.11 | 211.00 | 213.17 | |
Maximum of Months | 437.50 | 0.25 | 0.22 | 9284.73 | 35.88 | 271.33 | 434.17 | 3941.80 | 36.71 | 325.00 | 395.17 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.65 | 0.60 | 01-JAN-10:30 | 422.54 | 14.97 | 0.00 | 215.33 | 193.36 | 18.44 | 0.00 | 111.67 |
February | 265.33 | 0.63 | 0.60 | 01-FEB-09:20 | 517.80 | 16.05 | 0.00 | 243.50 | 243.71 | 19.44 | 0.17 | 175.83 |
March | 254.17 | 0.63 | 0.60 | 02-MAR-10:39 | 530.36 | 16.77 | 0.00 | 318.33 | 264.72 | 20.12 | 10.00 | 229.00 |
April | 296.33 | 0.62 | 0.60 | 01-APR-07:00 | 606.38 | 17.50 | 0.00 | 366.17 | 295.32 | 20.83 | 58.83 | 306.17 |
May | 437.50 | 0.61 | 0.60 | 01-MAY-05:40 | 882.58 | 19.10 | 22.50 | 435.17 | 399.36 | 22.91 | 210.83 | 407.17 |
June | 401.83 | 0.61 | 0.60 | 01-JUN-04:49 | 1057.20 | 20.91 | 62.33 | 443.17 | 493.55 | 24.57 | 284.33 | 411.33 |
July | 409.17 | 0.61 | 0.60 | 01-JUL-04:49 | 1002.25 | 20.60 | 51.50 | 444.83 | 471.36 | 24.06 | 289.67 | 416.00 |
August | 352.83 | 0.61 | 0.60 | 01-AUG-07:40 | 827.37 | 18.63 | 7.17 | 393.33 | 382.56 | 21.80 | 180.17 | 345.33 |
September | 344.17 | 0.62 | 0.60 | 01-SEP-06:40 | 625.80 | 17.05 | 0.00 | 334.83 | 283.87 | 20.24 | 14.17 | 262.83 |
October | 299.00 | 0.63 | 0.60 | 01-OCT-07:19 | 531.85 | 15.99 | 0.00 | 285.50 | 231.04 | 19.23 | 0.00 | 186.33 |
November | 255.50 | 0.65 | 0.60 | 01-NOV-08:50 | 416.83 | 14.72 | 0.00 | 222.17 | 181.61 | 18.02 | 0.00 | 98.50 |
December | 226.33 | 0.65 | 0.60 | 01-DEC-09:30 | 398.84 | 14.66 | 0.00 | 200.17 | 175.52 | 18.05 | 0.00 | 67.83 |
Annual Sum or Average | 3785.50 | 0.62 | 697.09 | 17.66 | 143.50 | 3902.50 | 322.36 | 21.07 | 1048.17 | 3018.00 | ||
Minimum of Months | 226.33 | 0.61 | 0.60 | 398.84 | 14.66 | 0.00 | 200.17 | 175.52 | 18.02 | 0.00 | 67.83 | |
Maximum of Months | 437.50 | 0.65 | 0.60 | 1057.20 | 20.91 | 62.33 | 444.83 | 493.55 | 24.57 | 289.67 | 416.00 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.65 | 0.60 | 01-JAN-10:30 | 422.54 | 14.97 | 0.00 | 215.33 | 193.36 | 18.44 | 0.00 | 111.67 |
February | 265.33 | 0.63 | 0.60 | 01-FEB-09:20 | 517.80 | 16.05 | 0.00 | 243.50 | 243.71 | 19.44 | 0.17 | 175.83 |
March | 254.17 | 0.63 | 0.60 | 02-MAR-10:39 | 530.36 | 16.77 | 0.00 | 318.33 | 264.72 | 20.12 | 10.00 | 229.00 |
April | 296.33 | 0.62 | 0.60 | 01-APR-07:00 | 606.38 | 17.50 | 0.00 | 366.17 | 295.32 | 20.83 | 58.83 | 306.17 |
May | 437.50 | 0.61 | 0.60 | 01-MAY-05:40 | 882.58 | 19.10 | 22.50 | 435.17 | 399.36 | 22.91 | 210.83 | 407.17 |
June | 401.83 | 0.61 | 0.60 | 01-JUN-04:49 | 1057.20 | 20.91 | 62.33 | 443.17 | 493.55 | 24.57 | 284.33 | 411.33 |
July | 409.17 | 0.61 | 0.60 | 01-JUL-04:49 | 1002.25 | 20.60 | 51.50 | 444.83 | 471.36 | 24.06 | 289.67 | 416.00 |
August | 352.83 | 0.61 | 0.60 | 01-AUG-07:40 | 827.37 | 18.63 | 7.17 | 393.33 | 382.56 | 21.80 | 180.17 | 345.33 |
September | 344.17 | 0.62 | 0.60 | 01-SEP-06:40 | 625.80 | 17.05 | 0.00 | 334.83 | 283.87 | 20.24 | 14.17 | 262.83 |
October | 299.00 | 0.63 | 0.60 | 01-OCT-07:19 | 531.85 | 15.99 | 0.00 | 285.50 | 231.04 | 19.23 | 0.00 | 186.33 |
November | 255.50 | 0.65 | 0.60 | 01-NOV-08:50 | 416.83 | 14.72 | 0.00 | 222.17 | 181.61 | 18.02 | 0.00 | 98.50 |
December | 226.33 | 0.65 | 0.60 | 01-DEC-09:30 | 398.84 | 14.66 | 0.00 | 200.17 | 175.52 | 18.05 | 0.00 | 67.83 |
Annual Sum or Average | 3785.50 | 0.62 | 697.09 | 17.66 | 143.50 | 3902.50 | 322.36 | 21.07 | 1048.17 | 3018.00 | ||
Minimum of Months | 226.33 | 0.61 | 0.60 | 398.84 | 14.66 | 0.00 | 200.17 | 175.52 | 18.02 | 0.00 | 67.83 | |
Maximum of Months | 437.50 | 0.65 | 0.60 | 1057.20 | 20.91 | 62.33 | 444.83 | 493.55 | 24.57 | 289.67 | 416.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.257608E+12 | 312575.76 | 06-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138521E+12 | 308107.51 | 14-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.789649E+11 | 295442.93 | 05-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.650734E+11 | 102598.34 | 10-APR-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.242565E+11 | 91025.36 | 01-MAY-23:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.461424E+10 | 84007.25 | 04-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.870830E+09 | 33928.57 | 02-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124724E+10 | 51637.69 | 19-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.193012E+11 | 80773.68 | 06-SEP-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.864871E+11 | 103376.62 | 14-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.622163E+11 | 106001.57 | 11-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.217322E+12 | 304091.39 | 24-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.956482E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.870830E+09 | 33928.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.257608E+12 | 312575.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.479762E+09 | 6001.84 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.479762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.479762E+09 | 6001.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.457053E+10 | 4123.53 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.251266E+10 | 4028.91 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178810E+10 | 3852.90 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.566006E+09 | 1404.57 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27298605.18 | 706.04 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3676951.78 | 328.85 | 04-JUN-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1345643.89 | 185.09 | 19-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 28192274.24 | 361.68 | 23-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.641507E+09 | 1534.71 | 30-OCT-06:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181882E+10 | 2361.60 | 25-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.447335E+10 | 3964.14 | 24-DEC-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.457053E+10 | 4123.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.145907E+10 | 1558.53 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.664736E+09 | 1523.48 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.344201E+09 | 1317.73 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41279976.01 | 498.80 | 04-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 394896.25 | 229.14 | 01-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 43003534.72 | 387.24 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.254606E+09 | 715.60 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125330E+10 | 1499.52 | 24-DEC-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.406059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145907E+10 | 1558.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.241670E+10 | 2117.95 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106452E+10 | 2069.94 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.446132E+09 | 1195.22 | 16-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131800E+09 | 640.14 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187062E+10 | 2037.08 | 24-DEC-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.592977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.241670E+10 | 2117.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.313553E+10 | 1652.48 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.226196E+10 | 1614.91 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189654E+10 | 1544.97 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.731588E+09 | 876.53 | 05-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 49239354.72 | 536.62 | 01-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14319353.23 | 228.39 | 29-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.517684E+09 | 657.24 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146097E+10 | 1096.70 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292527E+10 | 1589.18 | 24-DEC-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.313553E+10 | 1652.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107238E+11 | 11737.44 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.491365E+10 | 11473.44 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330245E+10 | 10982.07 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113372E+10 | 5098.07 | 26-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152341E+09 | 2597.56 | 09-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84811861.12 | 2724.87 | 09-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14283041.55 | 1856.88 | 03-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110754E+09 | 2826.89 | 15-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.354587E+09 | 3204.36 | 28-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168951E+10 | 4914.12 | 06-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.358510E+10 | 6636.43 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101397E+11 | 11292.89 | 24-DEC-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 14283041.55 | 1856.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107238E+11 | 11737.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168430E+11 | 29296.52 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.546867E+10 | 28591.06 | 14-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.240950E+10 | 19158.25 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166505E+09 | 5243.78 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170089E+09 | 4709.93 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175576E+10 | 11453.83 | 26-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139318E+11 | 28188.92 | 24-DEC-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.407453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168430E+11 | 29296.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.199613E+11 | 13323.54 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117381E+11 | 13020.79 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.812949E+10 | 12107.47 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184353E+10 | 5169.96 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16007023.02 | 1567.72 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3459158.41 | 914.71 | 29-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.285139E+10 | 5427.79 | 30-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.884764E+10 | 8676.60 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190924E+11 | 12813.47 | 24-DEC-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.724834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.199613E+11 | 13323.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105292E+11 | 8176.66 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.571466E+10 | 7991.01 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.333213E+10 | 7645.11 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.388363E+09 | 2712.18 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.326931E+09 | 2398.64 | 30-OCT-06:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.289661E+10 | 4156.21 | 25-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.949676E+10 | 7863.71 | 24-DEC-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105292E+11 | 8176.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.834545E+10 | 13724.96 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.335348E+10 | 13417.85 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150881E+10 | 10186.28 | 05-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196099E+09 | 4489.72 | 05-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8107123.54 | 2843.86 | 01-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7129639.73 | 1907.44 | 13-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143962E+09 | 3103.03 | 30-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.975991E+09 | 4276.30 | 29-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.650777E+10 | 13207.98 | 24-DEC-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.834545E+10 | 13724.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.659142E+10 | 13858.05 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.210605E+10 | 13547.94 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.609920E+09 | 8895.37 | 05-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13784332.15 | 2757.86 | 05-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 170070.64 | 283.45 | 01-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3196410.63 | 1129.30 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.206855E+09 | 2625.99 | 29-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.477346E+10 | 13336.01 | 24-DEC-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.659142E+10 | 13858.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 27957523.17 | 2448.97 | 06-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 157499.48 | 211.05 | 14-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3214149.36 | 785.07 | 25-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31329172.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27957523.17 | 2448.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.265991E+11 | 36176.29 | 06-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143803E+11 | 35661.29 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.754033E+10 | 34299.09 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.818946E+09 | 5624.44 | 05-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17011489.57 | 1382.48 | 01-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18809.37 | 0.34 | 26-JUN-21:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20286.21 | 0.34 | 28-JUL-21:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20094.79 | 0.33 | 02-AUG-19:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5642.02 | 0.34 | 01-SEP-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.253962E+09 | 3973.53 | 30-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.312063E+10 | 9002.78 | 25-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227155E+11 | 34985.37 | 24-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.754458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5642.02 | 0.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.265991E+11 | 36176.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109779E+11 | 8504.14 | 16-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.694918E+10 | 8502.83 | 08-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.504121E+10 | 8503.62 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179662E+10 | 8501.66 | 04-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165464E+09 | 8217.54 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30493403.85 | 4621.65 | 22-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7515868.51 | 4243.85 | 03-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34396498.46 | 4610.37 | 28-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.285237E+09 | 4582.10 | 05-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.210895E+10 | 8502.94 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.523324E+10 | 8503.51 | 06-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107528E+11 | 8504.51 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.433830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7515868.51 | 4243.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109779E+11 | 8504.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125376E+11 | 8402.14 | 16-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.834193E+10 | 8400.96 | 09-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.614409E+10 | 8401.60 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217834E+10 | 8400.78 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183279E+09 | 8163.69 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23357546.71 | 4281.88 | 05-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3914667.74 | 3662.01 | 08-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33701423.01 | 4804.56 | 04-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.337217E+09 | 4990.52 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.251341E+10 | 8401.23 | 31-OCT-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.601551E+10 | 8402.53 | 09-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119506E+11 | 8402.50 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.502629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3914667.74 | 3662.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125376E+11 | 8402.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.159202E+11 | 29569.43 | 09-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.390154E+10 | 24437.35 | 17-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.529416E+09 | 11572.98 | 05-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151292E+10 | 14498.26 | 29-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188806E+11 | 28909.13 | 24-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.407447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.188806E+11 | 29569.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.637498E+11 | 46195.96 | 06-JAN-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.409305E+11 | 45606.18 | 18-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.282749E+11 | 45598.51 | 06-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.637392E+10 | 44364.13 | 04-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208520E+09 | 30313.56 | 04-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11461854.16 | 21226.22 | 03-JUN-15:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7753623.98 | 16629.73 | 28-JUL-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26601834.23 | 22974.09 | 17-AUG-15:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133667E+09 | 29572.45 | 05-SEP-18:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.491167E+10 | 44260.08 | 30-OCT-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.216815E+11 | 45606.20 | 28-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.576825E+11 | 45607.52 | 27-DEC-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223993E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7753623.98 | 16629.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.637498E+11 | 46195.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109724E+11 | 8299.94 | 16-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.692307E+10 | 8298.27 | 12-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.500217E+10 | 8299.38 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172797E+10 | 8299.17 | 26-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185012E+09 | 4580.29 | 29-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18713287.71 | 4246.64 | 11-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4795519.55 | 4245.88 | 03-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29119868.76 | 4626.01 | 28-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.318261E+09 | 4800.91 | 22-SEP-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.219281E+10 | 8297.99 | 29-OCT-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.525366E+10 | 8299.25 | 06-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107176E+11 | 8300.29 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.433456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4795519.55 | 4245.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109724E+11 | 8300.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125561E+11 | 8182.15 | 16-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.836606E+10 | 8180.90 | 09-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.612900E+10 | 8181.59 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.207406E+10 | 8181.38 | 26-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211057E+09 | 5384.08 | 14-MAY-20:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14621620.04 | 4260.32 | 11-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3208836.36 | 4111.91 | 09-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27556679.53 | 4378.25 | 07-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.387509E+09 | 4854.61 | 08-SEP-19:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.263764E+10 | 8181.18 | 31-OCT-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.602668E+10 | 8181.45 | 06-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119363E+11 | 8182.54 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.503698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3208836.36 | 4111.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125561E+11 | 8182.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.355165E+10 | 2471.89 | 16-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229964E+10 | 2471.67 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171398E+10 | 2472.24 | 21-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.667040E+09 | 2471.78 | 26-APR-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89189433.85 | 2413.56 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22916284.44 | 1124.38 | 04-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2953889.91 | 973.60 | 15-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18066296.62 | 1194.96 | 18-AUG-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143610E+09 | 2025.29 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.788712E+09 | 2471.98 | 13-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178249E+10 | 2472.99 | 21-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.346989E+10 | 2472.10 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2953889.91 | 973.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.355165E+10 | 2472.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.398600E+10 | 2438.06 | 06-JAN-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.271145E+10 | 2434.66 | 21-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204936E+10 | 2434.86 | 21-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.790719E+09 | 2434.39 | 26-APR-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89496333.66 | 2390.44 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16688367.34 | 1251.45 | 05-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1029019.99 | 1054.61 | 31-JUL-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16550417.47 | 1182.13 | 25-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165454E+09 | 2141.20 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.924954E+09 | 2435.01 | 11-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202505E+10 | 2436.19 | 21-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380757E+10 | 2434.73 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1029019.99 | 1054.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.398600E+10 | 2438.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125263E+11 | 11903.81 | 16-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.737937E+10 | 11901.21 | 05-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.538920E+10 | 11902.20 | 03-MAR-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.195015E+10 | 11887.70 | 26-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.237390E+09 | 6908.71 | 05-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 52501092.47 | 5980.65 | 13-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13245913.97 | 5118.90 | 09-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36867581.40 | 6126.41 | 03-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.261678E+09 | 5756.51 | 17-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211727E+10 | 11833.32 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.565271E+10 | 11902.38 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126905E+11 | 11905.04 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.483072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 13245913.97 | 5118.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126905E+11 | 11905.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.105698E+09 | 0.105698E+09 | 3942.09 | 20-JAN-06:10 | 3942.09 | 0.00 |
February | 0.00 | 0.00 | 0.108495E+09 | 0.108495E+09 | 3977.83 | 07-FEB-06:10 | 3977.83 | 0.00 |
March | 0.00 | 0.00 | 0.232678E+09 | 0.232678E+09 | 4084.58 | 21-MAR-05:10 | 4084.58 | 0.00 |
April | 0.00 | 0.00 | 0.144203E+11 | 0.144161E+11 | 189040.31 | 23-APR-18:10 | 185640.82 | 0.02 |
May | 0.00 | 0.00 | 0.107254E+12 | 0.104452E+12 | 272129.39 | 25-MAY-18:10 | 225810.13 | 0.30 |
June | 0.00 | 0.00 | 0.270368E+12 | 0.193695E+12 | 439955.23 | 27-JUN-20:06 | 192339.40 | 0.61 |
July | 0.00 | 0.00 | 0.374330E+12 | 0.249030E+12 | 458860.11 | 21-JUL-19:34 | 186740.74 | 0.83 |
August | 0.00 | 0.00 | 0.261078E+12 | 0.185393E+12 | 423481.20 | 31-AUG-19:40 | 191393.99 | 0.77 |
September | 0.00 | 0.00 | 0.620193E+11 | 0.533830E+11 | 267661.56 | 01-SEP-10:40 | 172517.96 | 0.24 |
October | 0.00 | 0.00 | 0.886005E+10 | 0.886005E+10 | 133772.46 | 19-OCT-15:13 | 133772.46 | 0.03 |
November | 0.00 | 0.00 | 0.141186E+10 | 0.141186E+10 | 58562.84 | 01-NOV-15:30 | 58562.84 | 0.01 |
December | 0.00 | 0.00 | 0.128478E+09 | 0.128478E+09 | 3966.47 | 05-DEC-06:10 | 3966.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.110032E+13 | 0.811217E+12 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 0.105698E+09 | 0.105698E+09 | 3942.09 | 3942.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.374330E+12 | 0.249030E+12 | 458860.11 | 225810.13 | 0.83 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.763587E+09 | 0.763587E+09 | 17053.28 | 23-APR-15:11 | 17053.28 | 0.01 |
May | 0.00 | 0.00 | 0.659458E+10 | 0.634057E+10 | 23288.14 | 26-MAY-12:20 | 16895.38 | 0.21 |
June | 0.00 | 0.00 | 0.186341E+11 | 0.123181E+11 | 37981.96 | 25-JUN-08:03 | 17634.05 | 0.43 |
July | 0.00 | 0.00 | 0.270719E+11 | 0.162218E+11 | 40076.05 | 22-JUL-21:50 | 15929.06 | 0.60 |
August | 0.00 | 0.00 | 0.183407E+11 | 0.117833E+11 | 36048.40 | 31-AUG-20:50 | 15895.92 | 0.56 |
September | 0.00 | 0.00 | 0.363760E+10 | 0.291203E+10 | 24121.93 | 01-SEP-01:00 | 8846.91 | 0.15 |
October | 0.00 | 0.00 | 0.479896E+09 | 0.479896E+09 | 14460.52 | 19-OCT-15:15 | 14460.52 | 0.01 |
November | 0.00 | 0.00 | 71139999.81 | 71139999.81 | 6910.52 | 01-NOV-15:15 | 6910.52 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.755935E+11 | 0.508904E+11 | 0.17 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.270719E+11 | 0.162218E+11 | 40076.05 | 17634.05 | 0.60 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 576587.25 | 576587.25 | 2127.90 | 25-JAN-16:13 | 2127.90 | 0.00 |
February | 0.00 | 0.00 | 0.100233E+09 | 0.100205E+09 | 17150.35 | 20-FEB-16:11 | 17150.35 | 0.00 |
March | 0.00 | 0.00 | 0.441316E+09 | 0.441091E+09 | 17170.59 | 28-MAR-18:01 | 17170.59 | 0.00 |
April | 0.00 | 0.00 | 0.179877E+10 | 0.166337E+10 | 17166.29 | 16-APR-15:11 | 17166.29 | 0.06 |
May | 0.00 | 0.00 | 0.531758E+10 | 0.368461E+10 | 17169.05 | 04-MAY-15:11 | 17169.05 | 0.52 |
June | 0.00 | 0.00 | 0.713460E+10 | 0.398970E+10 | 18438.24 | 10-JUN-15:12 | 11662.43 | 0.84 |
July | 0.00 | 0.00 | 0.967590E+10 | 0.525845E+10 | 18772.70 | 05-JUL-08:61 | 12493.05 | 0.93 |
August | 0.00 | 0.00 | 0.758180E+10 | 0.384697E+10 | 18518.86 | 30-AUG-08:62 | 12604.25 | 0.86 |
September | 0.00 | 0.00 | 0.335929E+10 | 0.177421E+10 | 18005.20 | 19-SEP-15:12 | 12028.03 | 0.59 |
October | 0.00 | 0.00 | 0.867826E+09 | 0.498135E+09 | 17155.65 | 09-OCT-15:11 | 17155.65 | 0.16 |
November | 0.00 | 0.00 | 13855068.35 | 12404617.13 | 17088.53 | 17-NOV-16:11 | 17088.53 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.362918E+11 | 0.212697E+11 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.967590E+10 | 0.525845E+10 | 18772.70 | 17170.59 | 0.93 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 203760.26 | 203760.26 | 1333.53 | 17-JAN-16:15 | 1333.53 | 0.00 |
February | 0.00 | 0.00 | 11755755.52 | 11709929.21 | 13054.66 | 20-FEB-16:11 | 13054.66 | 0.00 |
March | 0.00 | 0.00 | 0.163525E+09 | 0.163517E+09 | 16333.60 | 28-MAR-18:01 | 16333.60 | 0.00 |
April | 0.00 | 0.00 | 0.865157E+09 | 0.776315E+09 | 18300.45 | 11-APR-18:11 | 18300.45 | 0.04 |
May | 0.00 | 0.00 | 0.352509E+10 | 0.228153E+10 | 18870.44 | 06-MAY-18:42 | 18870.44 | 0.42 |
June | 0.00 | 0.00 | 0.514921E+10 | 0.275147E+10 | 19395.25 | 25-JUN-08:51 | 12527.85 | 0.64 |
July | 0.00 | 0.00 | 0.701261E+10 | 0.368741E+10 | 19664.69 | 23-JUL-08:51 | 12272.02 | 0.68 |
August | 0.00 | 0.00 | 0.478518E+10 | 0.218859E+10 | 17816.54 | 30-AUG-08:51 | 12025.04 | 0.62 |
September | 0.00 | 0.00 | 0.154628E+10 | 0.613921E+09 | 18203.09 | 04-SEP-18:01 | 18203.09 | 0.40 |
October | 0.00 | 0.00 | 0.201909E+09 | 90515347.77 | 12444.76 | 22-OCT-18:01 | 12444.76 | 0.06 |
November | 0.00 | 0.00 | 2307953.19 | 1393522.33 | 4444.69 | 17-NOV-16:11 | 4444.69 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.232632E+11 | 0.125666E+11 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.701261E+10 | 0.368741E+10 | 19664.69 | 18870.44 | 0.68 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.338553E+09 | 0.338553E+09 | 16999.94 | 31-MAR-14:00 | 16999.94 | 0.00 |
April | 0.00 | 0.00 | 0.109050E+11 | 0.105041E+11 | 41034.30 | 22-APR-13:25 | 41034.30 | 0.02 |
May | 0.00 | 0.00 | 0.258428E+11 | 0.166617E+11 | 43927.37 | 18-MAY-13:00 | 35544.01 | 0.43 |
June | 0.00 | 0.00 | 0.325771E+11 | 0.140531E+11 | 46491.08 | 30-JUN-13:00 | 35254.66 | 0.80 |
July | 0.00 | 0.00 | 0.441483E+11 | 0.183475E+11 | 48818.79 | 23-JUL-13:00 | 39176.98 | 0.96 |
August | 0.00 | 0.00 | 0.403474E+11 | 0.178582E+11 | 52418.07 | 26-AUG-12:40 | 47003.38 | 0.94 |
September | 0.00 | 0.00 | 0.257927E+11 | 0.156021E+11 | 53315.96 | 01-SEP-12:50 | 48742.97 | 0.55 |
October | 0.00 | 0.00 | 0.106619E+11 | 0.893898E+10 | 61255.13 | 22-OCT-12:30 | 50094.44 | 0.10 |
November | 0.00 | 0.00 | 33569458.44 | 33569458.44 | 5537.80 | 17-NOV-13:50 | 5537.80 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.190647E+12 | 0.102338E+12 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.441483E+11 | 0.183475E+11 | 61255.13 | 50094.44 | 0.96 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 5419342.82 | 5419342.82 | 12212.33 | 19-JAN-19:05 | 12212.33 | 0.00 |
February | 0.00 | 0.00 | 8881578.90 | 8881578.90 | 13506.43 | 04-FEB-19:04 | 13506.43 | 0.00 |
March | 0.00 | 0.00 | 0.228060E+09 | 0.227569E+09 | 73033.05 | 28-MAR-18:01 | 73033.05 | 0.00 |
April | 0.00 | 0.00 | 0.439332E+10 | 0.385817E+10 | 77528.39 | 18-APR-18:01 | 77528.39 | 0.06 |
May | 0.00 | 0.00 | 0.257823E+11 | 0.186459E+11 | 80896.07 | 26-MAY-21:51 | 69473.13 | 0.40 |
June | 0.00 | 0.00 | 0.390232E+11 | 0.250568E+11 | 92271.33 | 25-JUN-08:51 | 61309.18 | 0.58 |
July | 0.00 | 0.00 | 0.460042E+11 | 0.281483E+11 | 93144.29 | 23-JUL-08:51 | 59706.06 | 0.60 |
August | 0.00 | 0.00 | 0.354048E+11 | 0.197949E+11 | 88766.57 | 28-AUG-21:52 | 60456.80 | 0.55 |
September | 0.00 | 0.00 | 0.176811E+11 | 0.869101E+10 | 84201.58 | 18-SEP-21:52 | 60089.82 | 0.55 |
October | 0.00 | 0.00 | 0.328661E+10 | 0.156909E+10 | 74952.97 | 20-OCT-18:12 | 74952.97 | 0.21 |
November | 0.00 | 0.00 | 0.302753E+09 | 0.128320E+09 | 57440.85 | 01-NOV-18:03 | 51654.21 | 0.02 |
December | 0.00 | 0.00 | 2449030.34 | 2257700.47 | 7294.80 | 05-DEC-19:05 | 7294.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.172123E+12 | 0.106137E+12 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 2449030.34 | 2257700.47 | 7294.80 | 7294.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.460042E+11 | 0.281483E+11 | 93144.29 | 77528.39 | 0.60 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 31834544.95 | 31756787.44 | 14592.14 | 28-FEB-16:11 | 14592.14 | 0.00 |
March | 0.00 | 0.00 | 0.254572E+09 | 0.252438E+09 | 15550.03 | 26-MAR-15:11 | 15550.03 | 0.00 |
April | 0.00 | 0.00 | 0.181072E+10 | 0.165511E+10 | 15551.68 | 23-APR-08:61 | 15551.68 | 0.07 |
May | 0.00 | 0.00 | 0.497958E+10 | 0.333952E+10 | 15552.85 | 05-MAY-08:62 | 15552.85 | 0.53 |
June | 0.00 | 0.00 | 0.761738E+10 | 0.435415E+10 | 16713.91 | 10-JUN-15:12 | 10522.96 | 0.88 |
July | 0.00 | 0.00 | 0.970825E+10 | 0.532950E+10 | 16588.75 | 05-JUL-08:61 | 11682.89 | 0.95 |
August | 0.00 | 0.00 | 0.731243E+10 | 0.365109E+10 | 16416.19 | 28-AUG-15:11 | 11850.63 | 0.89 |
September | 0.00 | 0.00 | 0.327934E+10 | 0.170317E+10 | 16291.69 | 19-SEP-15:12 | 10776.53 | 0.59 |
October | 0.00 | 0.00 | 0.789884E+09 | 0.435123E+09 | 15325.48 | 09-OCT-08:62 | 15325.48 | 0.15 |
November | 0.00 | 0.00 | 50862081.70 | 46405957.03 | 10861.22 | 17-NOV-16:11 | 10861.22 | 0.00 |
December | 0.00 | 0.00 | 339408.52 | 339408.52 | 2001.80 | 28-DEC-09:05 | 2001.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.358352E+11 | 0.207986E+11 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.970825E+10 | 0.532950E+10 | 16713.91 | 15552.85 | 0.95 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 867006.87 | 867006.87 | 2338.34 | 27-FEB-09:03 | 2338.34 | 0.00 |
March | 0.00 | 0.00 | 61306422.80 | 60884784.93 | 13892.22 | 26-MAR-08:61 | 13892.22 | 0.00 |
April | 0.00 | 0.00 | 0.870020E+09 | 0.776947E+09 | 14728.59 | 19-APR-08:62 | 14728.59 | 0.05 |
May | 0.00 | 0.00 | 0.343298E+10 | 0.219562E+10 | 15545.57 | 26-MAY-08:51 | 13172.07 | 0.43 |
June | 0.00 | 0.00 | 0.573225E+10 | 0.325150E+10 | 19192.48 | 25-JUN-08:32 | 14461.13 | 0.68 |
July | 0.00 | 0.00 | 0.705803E+10 | 0.380916E+10 | 18977.00 | 29-JUL-08:32 | 14533.40 | 0.70 |
August | 0.00 | 0.00 | 0.472233E+10 | 0.219574E+10 | 17127.91 | 30-AUG-08:51 | 12517.82 | 0.65 |
September | 0.00 | 0.00 | 0.169552E+10 | 0.800863E+09 | 16754.14 | 01-SEP-08:51 | 13798.59 | 0.41 |
October | 0.00 | 0.00 | 0.192685E+09 | 0.101713E+09 | 14015.59 | 09-OCT-08:62 | 14015.59 | 0.05 |
November | 0.00 | 0.00 | 2230084.32 | 1404267.61 | 3016.58 | 20-NOV-19:04 | 1504.08 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.237682E+11 | 0.131947E+11 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.705803E+10 | 0.380916E+10 | 19192.48 | 14728.59 | 0.70 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 135789.03 | 135789.03 | 606.86 | 27-JAN-16:13 | 606.86 | 0.00 |
February | 0.00 | 0.00 | 24958704.74 | 24930690.12 | 4467.21 | 20-FEB-16:11 | 4467.21 | 0.00 |
March | 0.00 | 0.00 | 0.116408E+09 | 0.116368E+09 | 4472.45 | 28-MAR-18:01 | 4472.45 | 0.00 |
April | 0.00 | 0.00 | 0.467533E+09 | 0.436326E+09 | 4471.48 | 16-APR-15:11 | 4471.48 | 0.05 |
May | 0.00 | 0.00 | 0.136565E+10 | 0.979146E+09 | 4472.08 | 04-MAY-15:11 | 4472.08 | 0.48 |
June | 0.00 | 0.00 | 0.181015E+10 | 0.105313E+10 | 4952.01 | 24-JUN-08:62 | 2974.89 | 0.79 |
July | 0.00 | 0.00 | 0.241749E+10 | 0.134552E+10 | 5083.24 | 05-JUL-08:61 | 3091.95 | 0.91 |
August | 0.00 | 0.00 | 0.186408E+10 | 0.988520E+09 | 4943.20 | 30-AUG-08:62 | 3067.33 | 0.84 |
September | 0.00 | 0.00 | 0.788824E+09 | 0.445245E+09 | 4735.70 | 19-SEP-15:12 | 3069.95 | 0.50 |
October | 0.00 | 0.00 | 0.213878E+09 | 0.130451E+09 | 4471.86 | 21-OCT-18:01 | 4471.86 | 0.13 |
November | 0.00 | 0.00 | 3120197.47 | 2887157.89 | 4466.96 | 17-NOV-16:11 | 4466.96 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.907223E+10 | 0.552266E+10 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.241749E+10 | 0.134552E+10 | 5083.24 | 4472.45 | 0.91 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1395516.65 | 1395516.65 | 1694.23 | 08-FEB-16:11 | 1694.23 | 0.00 |
March | 0.00 | 0.00 | 40629923.79 | 40603906.21 | 4236.04 | 28-MAR-18:01 | 4236.04 | 0.00 |
April | 0.00 | 0.00 | 0.221170E+09 | 0.202037E+09 | 4872.98 | 11-APR-18:11 | 4872.98 | 0.03 |
May | 0.00 | 0.00 | 0.918867E+09 | 0.615740E+09 | 5356.98 | 06-MAY-18:42 | 5356.98 | 0.39 |
June | 0.00 | 0.00 | 0.134982E+10 | 0.750134E+09 | 5123.07 | 25-JUN-08:51 | 3231.96 | 0.61 |
July | 0.00 | 0.00 | 0.181110E+10 | 0.982041E+09 | 5187.71 | 23-JUL-08:51 | 3132.33 | 0.68 |
August | 0.00 | 0.00 | 0.120464E+10 | 0.571477E+09 | 4697.04 | 30-AUG-08:51 | 3018.35 | 0.61 |
September | 0.00 | 0.00 | 0.338271E+09 | 0.144910E+09 | 4803.41 | 23-SEP-17:41 | 4803.41 | 0.33 |
October | 0.00 | 0.00 | 43666045.90 | 19667213.29 | 3241.29 | 22-OCT-18:01 | 3241.29 | 0.05 |
November | 0.00 | 0.00 | 362477.91 | 265454.80 | 781.11 | 09-NOV-16:13 | 781.11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.592993E+10 | 0.332827E+10 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.181110E+10 | 0.982041E+09 | 5356.98 | 5356.98 | 0.68 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.323399E+09 | 0.323290E+09 | 22024.39 | 27-JAN-16:11 | 22024.39 | 0.00 |
February | 0.00 | 0.00 | 0.111138E+10 | 0.110570E+10 | 22055.58 | 04-FEB-16:11 | 22055.58 | 0.00 |
March | 0.00 | 0.00 | 0.165535E+10 | 0.162998E+10 | 22064.76 | 27-MAR-15:11 | 22064.76 | 0.01 |
April | 0.00 | 0.00 | 0.339383E+10 | 0.313936E+10 | 22064.25 | 29-APR-15:11 | 22064.25 | 0.08 |
May | 0.00 | 0.00 | 0.681295E+10 | 0.452709E+10 | 22061.90 | 13-MAY-18:01 | 22061.90 | 0.54 |
June | 0.00 | 0.00 | 0.875297E+10 | 0.459928E+10 | 24983.73 | 19-JUN-18:01 | 15485.40 | 0.82 |
July | 0.00 | 0.00 | 0.117806E+11 | 0.609328E+10 | 25384.88 | 25-JUL-18:02 | 15166.79 | 0.91 |
August | 0.00 | 0.00 | 0.106068E+11 | 0.552291E+10 | 24359.82 | 30-AUG-08:62 | 15450.93 | 0.87 |
September | 0.00 | 0.00 | 0.626533E+10 | 0.371754E+10 | 23296.15 | 19-SEP-15:12 | 16026.93 | 0.66 |
October | 0.00 | 0.00 | 0.306306E+10 | 0.216190E+10 | 22058.34 | 21-OCT-18:01 | 22058.34 | 0.26 |
November | 0.00 | 0.00 | 0.773152E+09 | 0.761880E+09 | 22055.07 | 16-NOV-16:11 | 22055.07 | 0.01 |
December | 0.00 | 0.00 | 0.152216E+09 | 0.152076E+09 | 21483.11 | 02-DEC-16:12 | 21483.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.546911E+11 | 0.337343E+11 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.152216E+09 | 0.152076E+09 | 21483.11 | 15166.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.117806E+11 | 0.609328E+10 | 25384.88 | 22064.76 | 0.91 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 191499.42 | 564694.64 | 06-JAN-05:10 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 115101.82 | 535904.87 | 17-FEB-07:05 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 63077.52 | 497078.78 | 05-MAR-07:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 33837.06 | 187377.81 | 03-APR-15:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 9586.67 | 134835.07 | 01-MAY-08:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1873.75 | 86620.20 | 04-JUN-05:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 343.34 | 52200.82 | 08-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 585.39 | 56953.68 | 19-AUG-05:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8313.54 | 83744.06 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 41192.00 | 202880.09 | 31-OCT-15:12 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 54413.77 | 201933.96 | 03-NOV-15:11 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 169282.59 | 547614.09 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 57311.15 | ||||
Minimum of Months | 0.00 | 0.00 | 343.34 | 52200.82 | ||
Maximum of Months | 0.00 | 0.00 | 191499.42 | 564694.64 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 610.63 | 26617.20 | 19-JAN-19:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 1300.74 | 36845.37 | 28-FEB-16:11 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 2557.50 | 75587.53 | 31-MAR-18:01 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 17402.96 | 368735.88 | 23-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 74951.67 | 465623.49 | 25-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 157420.79 | 598509.15 | 29-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 206035.75 | 589225.03 | 22-JUL-21:51 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 150641.21 | 538467.56 | 08-AUG-15:13 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 51742.38 | 430881.51 | 01-SEP-15:13 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 12178.56 | 233882.80 | 19-OCT-15:13 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2109.49 | 69014.46 | 01-NOV-15:15 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 565.79 | 17939.24 | 05-DEC-19:05 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 56905.38 | 0.00 | ||||
Minimum of Months | 565.79 | 17939.24 | 0.00 | 0.00 | ||
Maximum of Months | 206035.75 | 598509.15 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 32706.03 | 67723.70 | 31-JAN-07:57 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 33428.53 | 68376.25 | 24-FEB-07:59 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 33322.55 | 68327.47 | 01-MAR-07:55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 32343.83 | 66924.21 | 03-APR-06:57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30790.11 | 64317.86 | 01-MAY-06:55 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 29068.41 | 60692.79 | 01-JUN-06:57 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27603.50 | 57025.05 | 03-JUL-06:57 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 26864.03 | 54812.25 | 02-AUG-06:54 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26985.61 | 55239.42 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27961.72 | 58131.99 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 29529.22 | 61730.72 | 30-NOV-07:55 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 31258.11 | 65097.05 | 29-DEC-07:53 |
Annual Sum or Average | 0.00 | 30135.61 | ||||
Minimum of Months | 0.00 | 0.00 | 26864.03 | 54812.25 | ||
Maximum of Months | 0.00 | 0.00 | 33428.53 | 68376.25 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261333E+10 | 0.70 | 1299.30 | 01-JAN-21:30 | 0.92 |
February | 0.236042E+10 | 0.70 | 1299.30 | 01-FEB-03:30 | 0.92 |
March | 0.261333E+10 | 0.70 | 1299.30 | 03-MAR-19:05 | 0.92 |
April | 0.252903E+10 | 0.70 | 1299.30 | 12-APR-08:06 | 0.92 |
May | 0.261333E+10 | 0.70 | 1299.30 | 01-MAY-08:06 | 0.92 |
June | 0.252903E+10 | 0.69 | 1299.30 | 01-JUN-09:00 | 0.91 |
July | 0.261333E+10 | 0.69 | 1299.30 | 01-JUL-06:30 | 0.91 |
August | 0.261333E+10 | 0.69 | 1299.30 | 04-AUG-08:58 | 0.91 |
September | 0.252903E+10 | 0.70 | 1299.30 | 01-SEP-08:58 | 0.91 |
October | 0.261333E+10 | 0.70 | 1299.30 | 31-OCT-18:04 | 0.92 |
November | 0.252903E+10 | 0.70 | 1299.30 | 04-NOV-15:25 | 0.92 |
December | 0.261333E+10 | 0.70 | 1299.30 | 01-DEC-20:30 | 0.92 |
Annual Sum or Average | 0.307698E+11 | 0.70 | |||
Minimum of Months | 0.236042E+10 | 0.69 | 1299.30 | 0.91 | |
Maximum of Months | 0.261333E+10 | 0.70 | 1299.30 | 0.92 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.353609E+11 | 0.86 | 19884.67 | 18-JAN-19:50 | 1.09 |
February | 0.331947E+11 | 0.88 | 19904.87 | 27-FEB-19:40 | 1.09 |
March | 0.376565E+11 | 0.89 | 19903.97 | 16-MAR-18:50 | 1.09 |
April | 0.373693E+11 | 0.90 | 19988.63 | 14-APR-19:00 | 1.09 |
May | 0.399477E+11 | 0.92 | 25496.83 | 25-MAY-21:10 | 1.25 |
June | 0.394885E+11 | 0.92 | 28079.42 | 30-JUN-21:10 | 1.33 |
July | 0.412540E+11 | 0.93 | 26122.82 | 21-JUL-21:20 | 1.27 |
August | 0.408424E+11 | 0.92 | 25741.30 | 09-AUG-21:10 | 1.26 |
September | 0.385605E+11 | 0.91 | 25312.07 | 01-SEP-21:10 | 1.25 |
October | 0.389878E+11 | 0.90 | 22103.65 | 19-OCT-21:10 | 1.15 |
November | 0.367011E+11 | 0.89 | 20773.33 | 10-NOV-19:20 | 1.12 |
December | 0.357651E+11 | 0.87 | 19899.80 | 28-DEC-19:50 | 1.09 |
Annual Sum or Average | 0.455129E+12 | 0.90 | |||
Minimum of Months | 0.331947E+11 | 0.86 | 19884.67 | 1.09 | |
Maximum of Months | 0.412540E+11 | 0.93 | 28079.42 | 1.33 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:05 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:05 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:05 | 0.28 |
April | 0.198586E+09 | 0.28 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.28 | 76.61 | 01-MAY-00:10 | 0.28 |
June | 0.198586E+09 | 0.28 | 76.61 | 01-JUN-00:10 | 0.28 |
July | 0.205205E+09 | 0.28 | 76.61 | 01-JUL-00:10 | 0.28 |
August | 0.205205E+09 | 0.28 | 76.61 | 01-AUG-00:10 | 0.27 |
September | 0.198586E+09 | 0.28 | 76.61 | 01-SEP-00:10 | 0.27 |
October | 0.205205E+09 | 0.28 | 76.61 | 01-OCT-00:10 | 0.28 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:10 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:05 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.28 | |||
Minimum of Months | 0.185347E+09 | 0.28 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | -0.0 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | -0.0 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.20 | 612.92 | 01-JAN-07:10 | 0.28 |
February | 0.105030E+10 | 0.20 | 612.92 | 01-FEB-07:05 | 0.28 |
March | 0.116283E+10 | 0.20 | 612.92 | 01-MAR-07:05 | 0.28 |
April | 0.112532E+10 | 0.20 | 612.92 | 01-APR-06:05 | 0.28 |
May | 0.116283E+10 | 0.20 | 612.92 | 01-MAY-06:05 | 0.28 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.28 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.20 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.20 | 612.92 | 01-OCT-06:10 | 0.28 |
November | 0.112532E+10 | 0.20 | 612.92 | 01-NOV-06:05 | 0.28 |
December | 0.116283E+10 | 0.20 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.20 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.20 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.854025E+09 | 0.55 | 823.37 | 01-JAN-09:02 | 0.60 |
February | 0.474814E+09 | 0.49 | 823.37 | 01-FEB-09:02 | 0.60 |
March | 0.353362E+09 | 0.46 | 823.37 | 01-MAR-09:02 | 0.60 |
April | 0.226810E+09 | 0.46 | 823.37 | 01-APR-18:02 | 0.60 |
May | 0.271348E+09 | 0.52 | 823.37 | 01-MAY-08:61 | 0.60 |
June | 0.323214E+09 | 0.53 | 823.37 | 01-JUN-15:12 | 0.60 |
July | 0.406729E+09 | 0.55 | 823.37 | 01-JUL-08:61 | 0.60 |
August | 0.322147E+09 | 0.53 | 823.37 | 01-AUG-08:62 | 0.59 |
September | 0.192617E+09 | 0.49 | 823.37 | 01-SEP-08:62 | 0.59 |
October | 0.210773E+09 | 0.44 | 823.37 | 01-OCT-15:11 | 0.60 |
November | 0.340120E+09 | 0.46 | 823.37 | 01-NOV-08:62 | 0.60 |
December | 0.794323E+09 | 0.57 | 823.37 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.477028E+10 | 0.51 | |||
Minimum of Months | 0.192617E+09 | 0.44 | 823.37 | 0.59 | |
Maximum of Months | 0.854025E+09 | 0.57 | 823.37 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.964879E+09 | 0.59 | 782.96 | 01-JAN-09:02 | 0.60 |
February | 0.574831E+09 | 0.54 | 782.96 | 01-FEB-09:02 | 0.60 |
March | 0.399647E+09 | 0.50 | 782.96 | 01-MAR-09:02 | 0.60 |
April | 0.200970E+09 | 0.42 | 782.96 | 01-APR-15:12 | 0.60 |
May | 0.187721E+09 | 0.42 | 782.96 | 01-MAY-08:61 | 0.60 |
June | 0.226616E+09 | 0.40 | 782.96 | 01-JUN-08:51 | 0.60 |
July | 0.290157E+09 | 0.41 | 782.96 | 01-JUL-08:51 | 0.60 |
August | 0.198574E+09 | 0.39 | 782.96 | 01-AUG-08:51 | 0.59 |
September | 0.109475E+09 | 0.39 | 782.96 | 01-SEP-08:51 | 0.59 |
October | 0.199189E+09 | 0.41 | 782.96 | 01-OCT-15:11 | 0.60 |
November | 0.374416E+09 | 0.50 | 782.96 | 01-NOV-08:62 | 0.60 |
December | 0.894072E+09 | 0.59 | 782.96 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.462055E+10 | 0.46 | |||
Minimum of Months | 0.109475E+09 | 0.39 | 782.96 | 0.59 | |
Maximum of Months | 0.964879E+09 | 0.59 | 782.96 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.110274E+10 | 0.36 | 1467.91 | 09-JAN-05:00 | 0.61 |
February | 0.290749E+09 | 0.11 | 1294.73 | 17-FEB-06:00 | 0.61 |
March | 58287707.25 | 0.03 | 802.97 | 05-MAR-06:00 | 0.61 |
April | 0.393665E+09 | 0.16 | 1296.07 | 22-APR-13:25 | 0.60 |
May | 0.963555E+09 | 0.45 | 1385.86 | 18-MAY-13:05 | 0.60 |
June | 0.113932E+10 | 0.52 | 1384.07 | 30-JUN-13:00 | 0.60 |
July | 0.145887E+10 | 0.57 | 1459.75 | 23-JUL-13:20 | 0.60 |
August | 0.135810E+10 | 0.56 | 1601.53 | 25-AUG-13:10 | 0.60 |
September | 0.936924E+09 | 0.40 | 1621.64 | 01-SEP-13:15 | 0.60 |
October | 0.393452E+09 | 0.15 | 2733.46 | 22-OCT-12:30 | 0.60 |
November | 0.131345E+09 | 0.06 | 925.31 | 29-NOV-06:00 | 0.61 |
December | 0.134140E+10 | 0.45 | 1446.06 | 24-DEC-06:00 | 0.61 |
Annual Sum or Average | 0.956841E+10 | 0.32 | |||
Minimum of Months | 58287707.25 | 0.03 | 802.97 | 0.60 | |
Maximum of Months | 0.145887E+10 | 0.57 | 2733.46 | 0.61 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.469029E+10 | 0.51 | 3797.51 | 01-JAN-00:40 | 0.60 |
February | 0.269906E+10 | 0.46 | 3797.51 | 01-FEB-09:02 | 0.60 |
March | 0.176656E+10 | 0.42 | 3797.51 | 01-MAR-09:02 | 0.60 |
April | 0.711756E+09 | 0.40 | 3797.51 | 01-APR-08:62 | 0.60 |
May | 0.123509E+10 | 0.37 | 3797.51 | 01-MAY-08:61 | 0.60 |
June | 0.169733E+10 | 0.36 | 3797.51 | 01-JUN-08:51 | 0.60 |
July | 0.189800E+10 | 0.36 | 3797.51 | 01-JUL-08:51 | 0.60 |
August | 0.140147E+10 | 0.33 | 3797.51 | 01-AUG-08:51 | 0.59 |
September | 0.786401E+09 | 0.35 | 3797.51 | 01-SEP-08:51 | 0.59 |
October | 0.603763E+09 | 0.40 | 3797.51 | 01-OCT-08:61 | 0.60 |
November | 0.133375E+10 | 0.41 | 3797.51 | 03-NOV-15:11 | 0.60 |
December | 0.410484E+10 | 0.50 | 3797.51 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.229283E+11 | 0.41 | |||
Minimum of Months | 0.603763E+09 | 0.33 | 3797.51 | 0.59 | |
Maximum of Months | 0.469029E+10 | 0.51 | 3797.51 | 0.60 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.815585E+09 | 0.56 | 745.19 | 01-JAN-09:02 | 0.60 |
February | 0.460548E+09 | 0.48 | 745.19 | 01-FEB-09:02 | 0.60 |
March | 0.324521E+09 | 0.45 | 745.19 | 01-MAR-09:02 | 0.60 |
April | 0.211829E+09 | 0.48 | 745.19 | 01-APR-18:02 | 0.60 |
May | 0.249175E+09 | 0.54 | 745.19 | 01-MAY-08:61 | 0.60 |
June | 0.329895E+09 | 0.56 | 745.19 | 01-JUN-08:62 | 0.60 |
July | 0.394051E+09 | 0.57 | 745.19 | 01-JUL-08:61 | 0.60 |
August | 0.300959E+09 | 0.54 | 745.19 | 01-AUG-08:62 | 0.59 |
September | 0.185510E+09 | 0.50 | 745.19 | 01-SEP-08:62 | 0.60 |
October | 0.199247E+09 | 0.44 | 745.19 | 01-OCT-08:61 | 0.60 |
November | 0.325054E+09 | 0.46 | 745.19 | 01-NOV-08:62 | 0.60 |
December | 0.770374E+09 | 0.57 | 745.19 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.456675E+10 | 0.51 | |||
Minimum of Months | 0.185510E+09 | 0.44 | 745.19 | 0.59 | |
Maximum of Months | 0.815585E+09 | 0.57 | 745.19 | 0.60 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.902250E+09 | 0.59 | 705.42 | 01-JAN-01:20 | 0.60 |
February | 0.560582E+09 | 0.54 | 705.42 | 01-FEB-09:02 | 0.60 |
March | 0.375772E+09 | 0.49 | 705.42 | 01-MAR-09:02 | 0.60 |
April | 0.183740E+09 | 0.43 | 705.42 | 01-APR-15:12 | 0.60 |
May | 0.181529E+09 | 0.44 | 705.42 | 01-MAY-08:61 | 0.60 |
June | 0.248843E+09 | 0.43 | 705.42 | 01-JUN-08:51 | 0.60 |
July | 0.288047E+09 | 0.42 | 705.42 | 01-JUL-08:51 | 0.60 |
August | 0.195237E+09 | 0.40 | 705.42 | 01-AUG-08:51 | 0.59 |
September | 0.119161E+09 | 0.41 | 705.42 | 01-SEP-08:51 | 0.59 |
October | 0.191445E+09 | 0.41 | 705.42 | 01-OCT-08:61 | 0.60 |
November | 0.359718E+09 | 0.50 | 705.42 | 01-NOV-08:62 | 0.60 |
December | 0.841479E+09 | 0.58 | 705.42 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.444780E+10 | 0.47 | |||
Minimum of Months | 0.119161E+09 | 0.40 | 705.42 | 0.59 | |
Maximum of Months | 0.902250E+09 | 0.59 | 705.42 | 0.60 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.256148E+09 | 0.58 | 214.53 | 01-JAN-09:02 | 0.60 |
February | 0.155144E+09 | 0.52 | 214.53 | 01-FEB-09:02 | 0.60 |
March | 0.109954E+09 | 0.49 | 214.53 | 01-MAR-09:02 | 0.60 |
April | 67629405.61 | 0.47 | 214.53 | 01-APR-08:62 | 0.60 |
May | 74232538.72 | 0.52 | 214.53 | 01-MAY-08:61 | 0.60 |
June | 85231483.78 | 0.53 | 214.53 | 01-JUN-15:12 | 0.60 |
July | 0.104287E+09 | 0.55 | 214.53 | 01-JUL-08:61 | 0.60 |
August | 81905873.42 | 0.53 | 214.53 | 01-AUG-15:12 | 0.60 |
September | 51666483.97 | 0.49 | 214.53 | 01-SEP-08:62 | 0.59 |
October | 65009285.72 | 0.46 | 214.53 | 01-OCT-15:11 | 0.60 |
November | 0.106821E+09 | 0.50 | 214.53 | 01-NOV-08:62 | 0.60 |
December | 0.248112E+09 | 0.58 | 214.53 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.140614E+10 | 0.52 | |||
Minimum of Months | 51666483.97 | 0.46 | 214.53 | 0.59 | |
Maximum of Months | 0.256148E+09 | 0.58 | 214.53 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.280712E+09 | 0.59 | 203.12 | 01-JAN-01:10 | 0.60 |
February | 0.183287E+09 | 0.56 | 203.12 | 01-FEB-09:02 | 0.60 |
March | 0.124428E+09 | 0.53 | 203.12 | 01-MAR-09:02 | 0.60 |
April | 60962423.53 | 0.44 | 203.12 | 01-APR-08:62 | 0.60 |
May | 52676711.02 | 0.42 | 203.12 | 01-MAY-08:61 | 0.60 |
June | 61207393.66 | 0.40 | 203.12 | 01-JUN-08:51 | 0.60 |
July | 76268222.97 | 0.41 | 203.12 | 01-JUL-08:51 | 0.60 |
August | 51397190.99 | 0.38 | 203.12 | 01-AUG-08:51 | 0.59 |
September | 30808605.61 | 0.39 | 203.12 | 01-SEP-08:51 | 0.59 |
October | 62310643.50 | 0.43 | 203.12 | 01-OCT-15:11 | 0.60 |
November | 0.116557E+09 | 0.54 | 203.12 | 01-NOV-08:62 | 0.60 |
December | 0.264243E+09 | 0.59 | 203.12 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.136486E+10 | 0.47 | |||
Minimum of Months | 30808605.61 | 0.38 | 203.12 | 0.59 | |
Maximum of Months | 0.280712E+09 | 0.59 | 203.12 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.886720E+09 | 0.51 | 1055.45 | 01-JAN-09:02 | 0.60 |
February | 0.521083E+09 | 0.49 | 1055.45 | 01-FEB-09:02 | 0.60 |
March | 0.424257E+09 | 0.48 | 1055.45 | 01-MAR-09:02 | 0.60 |
April | 0.303280E+09 | 0.49 | 1055.45 | 02-APR-08:62 | 0.60 |
May | 0.333350E+09 | 0.52 | 1055.45 | 01-MAY-15:11 | 0.60 |
June | 0.370240E+09 | 0.53 | 1055.45 | 01-JUN-08:62 | 0.60 |
July | 0.467504E+09 | 0.55 | 1055.45 | 01-JUL-08:61 | 0.60 |
August | 0.430995E+09 | 0.53 | 1055.45 | 01-AUG-15:12 | 0.60 |
September | 0.308156E+09 | 0.50 | 1055.45 | 01-SEP-08:62 | 0.59 |
October | 0.312950E+09 | 0.45 | 1055.45 | 01-OCT-08:61 | 0.60 |
November | 0.392194E+09 | 0.47 | 1055.45 | 02-NOV-15:11 | 0.60 |
December | 0.857854E+09 | 0.52 | 1055.45 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.560858E+10 | 0.50 | |||
Minimum of Months | 0.303280E+09 | 0.45 | 1055.45 | 0.59 | |
Maximum of Months | 0.886720E+09 | 0.55 | 1055.45 | 0.60 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.279786E+10 | 0.254326E+10 | 1874.65 | 06-JAN-05:00 | 1704.06 | 1704.06 | 37.82 | 6.08 |
February | 0.190286E+10 | 0.172970E+10 | 1815.26 | 17-FEB-07:05 | 1650.07 | 1650.07 | 38.28 | 5.90 |
March | 0.152206E+10 | 0.138355E+10 | 1705.88 | 05-MAR-05:00 | 1550.64 | 1550.64 | 38.51 | 5.50 |
April | 0.804682E+09 | 0.731456E+09 | 1043.30 | 26-APR-08:03 | 948.36 | 948.36 | 31.47 | 1.57 |
May | 0.196576E+09 | 0.178688E+09 | 823.14 | 01-MAY-08:03 | 748.24 | 748.24 | 30.72 | 1.10 |
June | 36130204.82 | 32842356.18 | 623.94 | 04-JUN-05:00 | 567.16 | 567.16 | 33.07 | 0.77 |
July | 6612655.40 | 6010903.76 | 317.47 | 08-JUL-08:04 | 288.58 | 288.58 | 24.83 | 0.36 |
August | 14931137.04 | 13572403.57 | 463.15 | 19-AUG-05:00 | 421.00 | 421.00 | 34.77 | 0.54 |
September | 0.185429E+09 | 0.168555E+09 | 610.55 | 06-SEP-04:10 | 554.99 | 554.99 | 33.46 | 0.75 |
October | 0.943129E+09 | 0.857304E+09 | 1077.16 | 31-OCT-15:12 | 979.14 | 979.14 | 30.65 | 1.65 |
November | 0.137742E+10 | 0.125208E+10 | 1120.42 | 25-NOV-09:03 | 1018.46 | 1018.46 | 34.11 | 1.77 |
December | 0.269249E+10 | 0.244747E+10 | 1866.74 | 24-DEC-06:00 | 1696.87 | 1696.87 | 38.37 | 6.06 |
Annual Sum or Average | 0.124802E+11 | 0.113445E+11 | ||||||
Minimum of Months | 6612655.40 | 6010903.76 | 317.47 | 288.58 | 288.58 | 24.83 | 0.36 | |
Maximum of Months | 0.279786E+10 | 0.254326E+10 | 1874.65 | 1704.06 | 1704.06 | 38.51 | 6.08 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11777812.54 | 10706031.59 | 418.80 | 19-JAN-19:05 | 380.69 | 380.69 | 6.72 | 0.84 |
February | 40528549.58 | 36840451.57 | 785.34 | 28-FEB-16:11 | 713.87 | 713.87 | 6.72 | 1.65 |
March | 0.103864E+09 | 94412335.02 | 1528.21 | 31-MAR-18:01 | 1389.14 | 1389.14 | 6.72 | 3.65 |
April | 0.774658E+09 | 0.704164E+09 | 2779.68 | 23-APR-18:03 | 2526.73 | 2526.73 | 6.72 | 9.96 |
May | 0.286459E+10 | 0.260391E+10 | 2960.12 | 25-MAY-18:03 | 2690.74 | 2690.74 | 6.72 | 12.18 |
June | 0.423297E+10 | 0.384777E+10 | 3113.50 | 29-JUN-18:03 | 2830.17 | 2830.17 | 6.72 | 15.15 |
July | 0.520378E+10 | 0.473024E+10 | 3065.73 | 03-JUL-18:02 | 2786.75 | 2786.75 | 6.72 | 14.12 |
August | 0.435603E+10 | 0.395963E+10 | 3018.23 | 08-AUG-18:03 | 2743.58 | 2743.58 | 6.72 | 13.18 |
September | 0.210686E+10 | 0.191514E+10 | 2880.28 | 01-SEP-15:12 | 2618.18 | 2618.18 | 6.72 | 11.07 |
October | 0.589591E+09 | 0.535938E+09 | 2621.40 | 19-OCT-15:13 | 2382.85 | 2382.85 | 6.72 | 8.62 |
November | 63644498.10 | 57852848.77 | 1046.61 | 01-NOV-15:40 | 951.37 | 951.37 | 6.72 | 2.29 |
December | 7033388.86 | 6393350.47 | 286.14 | 05-DEC-19:05 | 260.10 | 260.10 | 6.72 | 0.56 |
Annual Sum or Average | 0.203553E+11 | 0.185030E+11 | ||||||
Minimum of Months | 7033388.86 | 6393350.47 | 286.14 | 260.10 | 260.10 | 6.72 | 0.56 | |
Maximum of Months | 0.520378E+10 | 0.473024E+10 | 3113.50 | 2830.17 | 2830.17 | 6.72 | 15.15 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.131533E+10 | 0.119564E+10 | 2712.76 | 01-JAN-10:35 | 2465.90 | 2465.90 | 6.72 | 24.24 |
February | 0.187124E+10 | 0.170096E+10 | 2712.76 | 01-FEB-12:20 | 2465.90 | 2465.90 | 6.74 | 24.24 |
March | 0.354385E+10 | 0.322136E+10 | 2712.76 | 01-MAR-00:05 | 2465.90 | 2465.90 | 6.73 | 24.24 |
April | 0.495889E+10 | 0.450763E+10 | 2712.76 | 01-APR-08:62 | 2465.90 | 2465.90 | 7.01 | 24.24 |
May | 0.706763E+10 | 0.642447E+10 | 2712.76 | 01-MAY-00:40 | 2465.90 | 2465.90 | 6.72 | 24.24 |
June | 0.701823E+10 | 0.637957E+10 | 2712.76 | 01-JUN-00:10 | 2465.90 | 2465.90 | 6.81 | 24.24 |
July | 0.726585E+10 | 0.660466E+10 | 2712.76 | 01-JUL-00:10 | 2465.90 | 2465.90 | 7.52 | 24.24 |
August | 0.723614E+10 | 0.657765E+10 | 2712.76 | 01-AUG-00:10 | 2465.90 | 2465.90 | 7.66 | 24.24 |
September | 0.641608E+10 | 0.583221E+10 | 2712.76 | 01-SEP-00:10 | 2465.90 | 2465.90 | 8.88 | 24.24 |
October | 0.377503E+10 | 0.343151E+10 | 2712.76 | 01-OCT-00:10 | 2465.90 | 2465.90 | 6.79 | 24.24 |
November | 0.302559E+10 | 0.275026E+10 | 2712.76 | 01-NOV-05:20 | 2465.90 | 2465.90 | 6.73 | 24.24 |
December | 0.135331E+10 | 0.123016E+10 | 2712.76 | 01-DEC-00:05 | 2465.90 | 2465.90 | 6.73 | 24.24 |
Annual Sum or Average | 0.548472E+11 | 0.498561E+11 | ||||||
Minimum of Months | 0.131533E+10 | 0.119564E+10 | 2712.76 | 2465.90 | 2465.90 | 6.72 | 24.24 | |
Maximum of Months | 0.726585E+10 | 0.660466E+10 | 2712.76 | 2465.90 | 2465.90 | 8.88 | 24.24 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 46.22 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 46.70 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 46.98 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 50.40 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 50.48 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 50.84 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 51.41 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 51.75 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 52.00 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 50.45 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 51.28 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 48.02 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 46.22 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.00 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 36.68 | 60.00 | 191499.42 | 564694.64 | 06-JAN-05:10 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 37.82 | 60.00 | 115101.82 | 535904.87 | 17-FEB-07:05 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 47.21 | 60.00 | 63077.52 | 497078.78 | 05-MAR-07:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 37.63 | 60.00 | 33837.06 | 187377.81 | 03-APR-15:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 45.77 | 60.00 | 9586.67 | 134835.07 | 01-MAY-08:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 39.30 | 60.00 | 1873.75 | 86620.20 | 04-JUN-05:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 40.29 | 40.29 | 343.34 | 52200.82 | 08-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 38.56 | 38.56 | 585.39 | 56953.68 | 19-AUG-05:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 39.27 | 39.27 | 8313.54 | 83744.06 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 39.36 | 60.00 | 41192.00 | 202880.09 | 31-OCT-15:12 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 38.56 | 60.00 | 54413.77 | 201933.96 | 03-NOV-15:11 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 43.73 | 60.00 | 169282.59 | 547614.09 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 57311.15 | ||||||
Minimum of Months | 0.00 | 0.00 | 36.68 | 38.56 | 343.34 | 52200.82 | ||
Maximum of Months | 0.00 | 0.00 | 47.21 | 60.00 | 191499.42 | 564694.64 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 610.63 | 26617.20 | 19-JAN-19:05 | 6.96 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 1300.74 | 36845.37 | 28-FEB-16:11 | 7.06 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 2557.50 | 75587.53 | 31-MAR-18:01 | 7.44 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 17402.96 | 368735.88 | 23-APR-18:03 | 10.33 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 74951.67 | 465623.49 | 25-MAY-18:03 | 11.29 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 157420.79 | 598509.15 | 29-JUN-18:03 | 12.60 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 206035.75 | 589225.03 | 22-JUL-21:51 | 12.51 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 150641.21 | 538467.56 | 08-AUG-15:13 | 12.00 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 51742.38 | 430881.51 | 01-SEP-15:13 | 10.94 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 12178.56 | 233882.80 | 19-OCT-15:13 | 9.00 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2109.49 | 69014.46 | 01-NOV-15:15 | 7.38 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 565.79 | 17939.24 | 05-DEC-19:05 | 6.88 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 56905.38 | 0.00 | ||||||
Minimum of Months | 565.79 | 17939.24 | 6.88 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 206035.75 | 598509.15 | 12.60 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 46.22 | 59.65 | 32706.03 | 67723.70 | 31-JAN-07:57 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 46.70 | 58.67 | 33428.53 | 68376.25 | 24-FEB-07:59 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 46.98 | 59.70 | 33322.55 | 68327.47 | 01-MAR-07:55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.40 | 59.55 | 32343.83 | 66924.21 | 03-APR-06:57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 50.48 | 59.02 | 30790.11 | 64317.86 | 01-MAY-06:55 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 50.84 | 58.74 | 29068.41 | 60692.79 | 01-JUN-06:57 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 51.41 | 59.03 | 27603.50 | 57025.05 | 03-JUL-06:57 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 51.75 | 58.93 | 26864.03 | 54812.25 | 02-AUG-06:54 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 52.00 | 59.30 | 26985.61 | 55239.42 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 50.45 | 58.40 | 27961.72 | 58131.99 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 51.28 | 59.03 | 29529.22 | 61730.72 | 30-NOV-07:55 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 48.02 | 59.27 | 31258.11 | 65097.05 | 29-DEC-07:53 |
Annual Sum or Average | 0.00 | 30135.61 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.22 | 58.40 | 26864.03 | 54812.25 | ||
Maximum of Months | 0.00 | 0.00 | 52.00 | 59.70 | 33428.53 | 68376.25 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.342692E+12 | 0.00 | 0.105698E+09 | 0.353609E+11 | 0.00 | 0.00 |
February | 0.178320E+12 | 0.00 | 0.108495E+09 | 0.331947E+11 | 0.00 | 0.00 |
March | 0.102732E+12 | 0.00 | 0.232678E+09 | 0.376565E+11 | 0.00 | 0.00 |
April | 0.701542E+11 | 0.00 | 0.144203E+11 | 0.373693E+11 | 0.00 | 0.00 |
May | 0.245101E+11 | 0.00 | 0.107254E+12 | 0.399477E+11 | 0.00 | 0.00 |
June | 0.470273E+10 | 0.00 | 0.270368E+12 | 0.394885E+11 | 0.00 | 0.00 |
July | 0.885113E+09 | 0.00 | 0.374330E+12 | 0.412540E+11 | 0.00 | 0.00 |
August | 0.135934E+10 | 0.00 | 0.261078E+12 | 0.408424E+11 | 0.00 | 0.00 |
September | 0.197089E+11 | 0.00 | 0.620193E+11 | 0.385605E+11 | 0.00 | 0.00 |
October | 0.928743E+11 | 0.00 | 0.886005E+10 | 0.389878E+11 | 0.00 | 0.00 |
November | 0.841505E+11 | 0.00 | 0.141186E+10 | 0.367011E+11 | 0.00 | 0.00 |
December | 0.291789E+12 | 0.00 | 0.128478E+09 | 0.357651E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.121388E+13 | 0.00 | 0.110032E+13 | 0.455129E+12 | 0.00 | 0.00 |
Minimum of Months | 0.885113E+09 | 0.00 | 0.105698E+09 | 0.331947E+11 | 0.00 | 0.00 |
Maximum of Months | 0.342692E+12 | 0.00 | 0.374330E+12 | 0.412540E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.265991E+11 | 0.00 | 0.00 | 0.261333E+10 | 0.00 | 0.00 |
February | 0.143803E+11 | 0.00 | 0.00 | 0.236042E+10 | 0.00 | 0.00 |
March | 0.754033E+10 | 0.00 | 0.00 | 0.261333E+10 | 0.00 | 0.00 |
April | 0.818946E+09 | 0.00 | 0.763587E+09 | 0.252903E+10 | 0.00 | 0.00 |
May | 17011489.57 | 0.00 | 0.659458E+10 | 0.261333E+10 | 0.00 | 0.00 |
June | 18809.37 | 0.00 | 0.186341E+11 | 0.252903E+10 | 0.00 | 0.00 |
July | 20286.21 | 0.00 | 0.270719E+11 | 0.261333E+10 | 0.00 | 0.00 |
August | 20094.79 | 0.00 | 0.183407E+11 | 0.261333E+10 | 0.00 | 0.00 |
September | 5642.02 | 0.00 | 0.363760E+10 | 0.252903E+10 | 0.00 | 0.00 |
October | 0.253962E+09 | 0.00 | 0.479896E+09 | 0.261333E+10 | 0.00 | 0.00 |
November | 0.312063E+10 | 0.00 | 71139999.81 | 0.252903E+10 | 0.00 | 0.00 |
December | 0.227155E+11 | 0.00 | 0.00 | 0.261333E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.754458E+11 | 0.00 | 0.755935E+11 | 0.307698E+11 | 0.00 | 0.00 |
Minimum of Months | 5642.02 | 0.00 | 0.00 | 0.236042E+10 | 0.00 | 0.00 |
Maximum of Months | 0.265991E+11 | 0.00 | 0.270719E+11 | 0.261333E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.353609E+11 | 0.105698E+09 | 0.342692E+12 | 0.451472E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.331947E+11 | 0.108495E+09 | 0.178320E+12 | 0.406880E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.376565E+11 | 0.232678E+09 | 0.102732E+12 | 0.391458E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373693E+11 | 0.144203E+11 | 0.701542E+11 | 0.120015E+12 | 37010745.63 | 0.00 | 0.00 | 0.00 |
May | 0.399477E+11 | 0.107254E+12 | 0.245101E+11 | 0.804326E+10 | 0.144646E+10 | 0.00 | 0.00 | 0.00 |
June | 0.394885E+11 | 0.270368E+12 | 0.470273E+10 | 0.123661E+10 | 0.226977E+11 | 0.00 | 0.00 | 0.00 |
July | 0.412540E+11 | 0.374330E+12 | 0.885113E+09 | 0.618747E+09 | 0.306509E+11 | 0.00 | 0.00 | 0.00 |
August | 0.408424E+11 | 0.261078E+12 | 0.135934E+10 | 0.427527E+09 | 0.113134E+11 | 0.00 | 0.00 | 0.00 |
September | 0.385605E+11 | 0.620193E+11 | 0.197089E+11 | 0.106247E+09 | 0.150340E+09 | 0.00 | 0.00 | 0.00 |
October | 0.389878E+11 | 0.886005E+10 | 0.928743E+11 | 0.419493E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367011E+11 | 0.141186E+10 | 0.841505E+11 | 0.279563E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357651E+11 | 0.128478E+09 | 0.291789E+12 | 0.453609E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.455129E+12 | 0.110032E+13 | 0.121388E+13 | 0.215538E+13 | 0.662958E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.331947E+11 | 0.105698E+09 | 0.885113E+09 | 0.106247E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.412540E+11 | 0.374330E+12 | 0.342692E+12 | 0.453609E+12 | 0.306509E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261333E+10 | 0.00 | 0.265991E+11 | 0.583443E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.00 | 0.143803E+11 | 0.585328E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.00 | 0.754033E+10 | 0.624085E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.763587E+09 | 0.818946E+09 | 0.401079E+11 | 45097326.53 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 0.659458E+10 | 17011489.57 | 0.148061E+11 | 0.538775E+09 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 0.186341E+11 | 18809.37 | 0.446914E+10 | 0.412878E+10 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 0.270719E+11 | 20286.21 | 0.201618E+10 | 0.537543E+10 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 0.183407E+11 | 20094.79 | 0.236758E+10 | 0.204203E+10 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 0.363760E+10 | 5642.02 | 0.140088E+11 | 57501585.92 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 0.479896E+09 | 0.253962E+09 | 0.363391E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 71139999.81 | 0.312063E+10 | 0.543444E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.00 | 0.227155E+11 | 0.594728E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.755935E+11 | 0.754458E+11 | 0.407218E+12 | 0.121876E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 0.00 | 5642.02 | 0.201618E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.270719E+11 | 0.265991E+11 | 0.624085E+11 | 0.537543E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.353609E+11 | 0.342692E+12 | 0.105698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.331947E+11 | 0.178320E+12 | 0.108495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.376565E+11 | 0.102732E+12 | 0.232678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373693E+11 | 0.701542E+11 | 0.144203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.399477E+11 | 0.245101E+11 | 0.107254E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.394885E+11 | 0.470273E+10 | 0.270368E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.412540E+11 | 0.885113E+09 | 0.374330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.408424E+11 | 0.135934E+10 | 0.261078E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.385605E+11 | 0.197089E+11 | 0.620193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.389878E+11 | 0.928743E+11 | 0.886005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367011E+11 | 0.841505E+11 | 0.141186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357651E+11 | 0.291789E+12 | 0.128478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.455129E+12 | 0.121388E+13 | 0.110032E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.331947E+11 | 0.885113E+09 | 0.105698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.412540E+11 | 0.342692E+12 | 0.374330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.261333E+10 | 0.265991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.143803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.754033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.818946E+09 | 0.763587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 17011489.57 | 0.659458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 18809.37 | 0.186341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 20286.21 | 0.270719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 20094.79 | 0.183407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 5642.02 | 0.363760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 0.253962E+09 | 0.479896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 0.312063E+10 | 71139999.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.227155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.754458E+11 | 0.755935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 5642.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.265991E+11 | 0.270719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.691866E+11 | 0.00 | 0.00 | 14163.77 | 0.00 | 80562534.16 | 0.190475E+09 | 0.00 | 0.60 |
February | 0.511607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
March | 0.488066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.462921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
May | 0.385802E+11 | 0.00 | 0.00 | 0.00 | 91012433.52 | 0.00 | 0.00 | 0.00 | 0.78 |
June | 0.249479E+11 | 0.00 | 0.00 | 0.00 | 0.308141E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
July | 0.196526E+11 | 95035190.51 | 0.00 | 39827.79 | 0.504422E+10 | 0.00 | 0.343974E+09 | 0.00 | 0.84 |
August | 0.105579E+11 | 0.400349E+09 | 0.00 | 12503099.71 | 0.169453E+10 | 0.00 | 0.162538E+11 | 0.00 | 0.89 |
September | 0.100762E+11 | 694418.67 | 0.00 | 30285045.19 | 17509225.36 | 0.00 | 0.318659E+11 | 0.00 | 0.80 |
October | 0.115504E+11 | 0.00 | 0.00 | 34629681.93 | 0.00 | 0.00 | 0.413845E+11 | 0.00 | 0.66 |
November | 0.157597E+11 | 0.00 | 0.00 | 24774272.53 | 0.00 | 0.00 | 0.312740E+11 | 0.00 | 0.62 |
December | 0.570657E+11 | 0.00 | 0.00 | 3518553.08 | 0.00 | 0.00 | 0.736050E+10 | 0.00 | 0.60 |
Annual Sum or Average | 0.403637E+12 | 0.496079E+09 | 0.00 | 0.105765E+09 | 0.992868E+10 | 80562534.16 | 0.128673E+12 | 0.00 | 0.71 |
Minimum of Months | 0.100762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.691866E+11 | 0.400349E+09 | 0.00 | 34629681.93 | 0.504422E+10 | 80562534.16 | 0.413845E+11 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.772860E+09 | 0.00 | 0.00 | 81641.37 | 0.00 | 0.686819E+10 | 0.103396E+09 | 0.00 | 1.12 |
February | 0.138466E+10 | 0.00 | 0.00 | 569541.50 | 0.00 | 0.338759E+10 | 0.444726E+09 | 0.00 | 1.07 |
March | 0.223860E+10 | 0.00 | 0.00 | 795231.04 | 0.00 | 0.198241E+10 | 0.551757E+09 | 0.00 | 1.05 |
April | 0.319580E+10 | 0.00 | 0.00 | 1906270.99 | 0.00 | 0.424925E+09 | 0.937517E+09 | 0.00 | 1.22 |
May | 0.255657E+10 | 14572109.16 | 0.00 | 3902054.26 | 0.00 | 0.00 | 0.120003E+10 | 0.00 | 1.50 |
June | 0.168575E+10 | 0.412769E+09 | 0.00 | 3033520.15 | 20040921.30 | 0.00 | 0.706813E+09 | 0.00 | 1.63 |
July | 0.950879E+09 | 0.685227E+09 | 0.00 | 3483229.47 | 22080314.18 | 0.00 | 0.101198E+10 | 0.00 | 1.74 |
August | 0.141605E+10 | 0.295310E+09 | 0.00 | 4186366.15 | 12157043.21 | 0.00 | 0.122250E+10 | 0.00 | 1.84 |
September | 0.277374E+10 | 3946095.45 | 0.00 | 3636921.04 | 24786.61 | 0.00 | 0.142554E+10 | 0.00 | 1.60 |
October | 0.385029E+10 | 0.00 | 0.00 | 1929204.32 | 0.00 | 0.366646E+09 | 0.887066E+09 | 0.00 | 1.24 |
November | 0.228951E+10 | 0.00 | 0.00 | 415772.82 | 0.00 | 0.177121E+10 | 0.287727E+09 | 0.00 | 1.04 |
December | 0.617625E+09 | 0.00 | 0.00 | 19906.70 | 0.00 | 0.627738E+10 | 25615634.35 | 0.00 | 1.09 |
Annual Sum or Average | 0.237323E+11 | 0.141182E+10 | 0.00 | 23959659.80 | 54303065.31 | 0.210783E+11 | 0.880467E+10 | 0.00 | 1.35 |
Minimum of Months | 0.617625E+09 | 0.00 | 0.00 | 19906.70 | 0.00 | 0.00 | 25615634.35 | 0.00 | 1.04 |
Maximum of Months | 0.385029E+10 | 0.685227E+09 | 0.00 | 4186366.15 | 22080314.18 | 0.686819E+10 | 0.142554E+10 | 0.00 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.627849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117983E+10 | 0.00 | 0.00 | 1.01 |
February | 0.536085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132759E+09 | 0.00 | 0.00 | 1.01 |
March | 0.524082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
April | 0.482098E+10 | 0.00 | 0.00 | 30276.83 | 0.00 | 0.00 | 0.149797E+09 | 0.00 | 1.08 |
May | 0.343369E+10 | 1077315.45 | 0.00 | 583903.59 | 8695536.07 | 0.00 | 0.712381E+09 | 0.00 | 1.31 |
June | 0.200692E+10 | 0.121943E+09 | 0.00 | 660875.62 | 0.212722E+09 | 0.00 | 0.675322E+09 | 0.00 | 1.42 |
July | 0.101572E+10 | 0.213453E+09 | 0.00 | 1225673.02 | 0.343784E+09 | 0.00 | 0.113594E+10 | 0.00 | 1.42 |
August | 0.162712E+10 | 48951581.48 | 0.00 | 1145409.99 | 0.175956E+09 | 0.00 | 0.124667E+10 | 0.00 | 1.50 |
September | 0.376485E+10 | 110816.08 | 0.00 | 351529.59 | 1843878.50 | 0.00 | 0.632021E+09 | 0.00 | 1.32 |
October | 0.534296E+10 | 0.00 | 0.00 | 52779.71 | 0.00 | 0.00 | 0.154173E+09 | 0.00 | 1.07 |
November | 0.493703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 |
December | 0.640264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509726E+09 | 0.00 | 0.00 | 1.01 |
Annual Sum or Average | 0.502321E+11 | 0.385536E+09 | 0.00 | 4050448.36 | 0.743001E+09 | 0.182231E+10 | 0.470630E+10 | 0.00 | 1.18 |
Minimum of Months | 0.101572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
Maximum of Months | 0.640264E+10 | 0.213453E+09 | 0.00 | 1225673.02 | 0.343784E+09 | 0.117983E+10 | 0.124667E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4439398.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263330E+10 | 0.00 | 0.00 | 0.13 |
February | 17801130.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875101E+09 | 0.00 | 0.00 | 0.06 |
March | 38745337.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257997E+09 | 0.00 | 0.00 | 0.02 |
April | 61178385.44 | 0.00 | 0.00 | 70991.53 | 0.00 | 0.00 | 35144174.34 | 0.00 | 0.01 |
May | 23790721.39 | 3678681.91 | 0.00 | 1658397.44 | 0.00 | 0.00 | 0.580511E+09 | 0.00 | 0.12 |
June | 2609328.57 | 0.163050E+09 | 0.00 | 1992613.82 | 0.00 | 0.00 | 0.624033E+09 | 0.00 | 0.20 |
July | 0.00 | 0.273531E+09 | 0.00 | 2530238.79 | 0.00 | 0.00 | 0.786932E+09 | 0.00 | 0.28 |
August | 1519920.37 | 92649567.19 | 0.00 | 2567131.67 | 0.00 | 0.00 | 0.902280E+09 | 0.00 | 0.24 |
September | 18010449.95 | 664059.48 | 0.00 | 1365682.30 | 0.00 | 0.00 | 0.643061E+09 | 0.00 | 0.11 |
October | 63197451.94 | 0.00 | 0.00 | 161953.66 | 0.00 | 0.00 | 98429644.14 | 0.00 | 0.02 |
November | 54739726.12 | 0.00 | 0.00 | 0.00 | 0.00 | 60921985.24 | 0.00 | 0.00 | 0.01 |
December | 7794172.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180177E+10 | 0.00 | 0.00 | 0.09 |
Annual Sum or Average | 0.293826E+09 | 0.533573E+09 | 0.00 | 10347009.21 | 0.00 | 0.562909E+10 | 0.367039E+10 | 0.00 | 0.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Maximum of Months | 63197451.94 | 0.273531E+09 | 0.00 | 2567131.67 | 0.00 | 0.263330E+10 | 0.902280E+09 | 0.00 | 0.28 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5439482.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468960E+10 | 0.00 | 0.00 | 0.52 |
February | 0.250878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320737E+10 | 0.00 | 0.00 | 0.52 |
March | 0.951634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234749E+10 | 0.00 | 0.00 | 0.52 |
April | 0.277430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354851E+09 | 0.00 | 0.00 | 0.56 |
May | 0.260786E+10 | 0.00 | 0.00 | 0.00 | 6152057.44 | 0.00 | 0.00 | 0.00 | 0.67 |
June | 0.168638E+10 | 0.00 | 0.00 | 0.00 | 0.208290E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
July | 0.135169E+10 | 0.00 | 0.00 | 0.00 | 0.347392E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
August | 0.180608E+10 | 0.00 | 0.00 | 0.00 | 0.141048E+09 | 0.00 | 0.00 | 0.00 | 0.77 |
September | 0.276697E+10 | 0.00 | 0.00 | 0.00 | 1230489.72 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 0.339151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68997311.43 | 0.00 | 0.00 | 0.55 |
November | 0.167450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143338E+10 | 0.00 | 0.00 | 0.52 |
December | 22702526.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432867E+10 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.192899E+11 | 0.00 | 0.00 | 0.00 | 0.704113E+09 | 0.164304E+11 | 0.00 | 0.00 | 0.61 |
Minimum of Months | 5439482.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.339151E+10 | 0.00 | 0.00 | 0.00 | 0.347392E+09 | 0.468960E+10 | 0.00 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.104879E+09 | 0.00 | 0.00 | 0.760488E+11 | 0.00 | 11.27 |
February | 0.00 | 0.00 | 0.00 | 95389572.06 | 0.00 | 0.00 | 0.637334E+11 | 0.00 | 12.11 |
March | 0.00 | 0.00 | 0.00 | 0.106700E+09 | 0.00 | 0.00 | 0.651838E+11 | 0.00 | 12.57 |
April | 0.00 | 0.00 | 0.00 | 0.105459E+09 | 0.00 | 0.00 | 0.650867E+11 | 0.00 | 14.01 |
May | 0.00 | 0.115171E+09 | 0.00 | 0.126200E+09 | 0.00 | 0.00 | 0.542170E+11 | 0.00 | 17.53 |
June | 0.00 | 0.464371E+10 | 0.00 | 0.101847E+09 | 0.00 | 0.00 | 0.344584E+11 | 0.00 | 18.89 |
July | 0.00 | 0.785696E+10 | 0.00 | 89180951.07 | 0.00 | 0.00 | 0.269419E+11 | 0.00 | 18.83 |
August | 0.00 | 0.316975E+10 | 0.00 | 0.105134E+09 | 0.00 | 0.00 | 0.368961E+11 | 0.00 | 19.99 |
September | 0.00 | 21554779.38 | 0.00 | 0.111570E+09 | 0.00 | 0.00 | 0.582079E+11 | 0.00 | 17.45 |
October | 0.00 | 0.00 | 0.00 | 0.104222E+09 | 0.00 | 0.00 | 0.715842E+11 | 0.00 | 13.82 |
November | 0.00 | 0.00 | 0.00 | 0.101578E+09 | 0.00 | 0.00 | 0.636715E+11 | 0.00 | 12.95 |
December | 0.00 | 0.00 | 0.00 | 0.103832E+09 | 0.00 | 0.00 | 0.740869E+11 | 0.00 | 11.58 |
Annual Sum or Average | 0.00 | 0.158072E+11 | 0.00 | 0.125599E+10 | 0.00 | 0.00 | 0.690117E+12 | 0.00 | 15.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 89180951.07 | 0.00 | 0.00 | 0.269419E+11 | 0.00 | 11.27 |
Maximum of Months | 0.00 | 0.785696E+10 | 0.00 | 0.126200E+09 | 0.00 | 0.00 | 0.760488E+11 | 0.00 | 19.99 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.482239E+11 | 0.00 | 0.00 | 200543.75 | 0.00 | 0.602404E+10 | 0.784373E+09 | 0.00 | 3.08 |
February | 0.358102E+11 | 0.00 | 0.00 | 1768720.22 | 0.00 | 0.166184E+10 | 0.307813E+10 | 0.00 | 3.06 |
March | 0.331080E+11 | 0.00 | 0.00 | 2497883.70 | 0.00 | 0.203441E+09 | 0.536294E+10 | 0.00 | 3.04 |
April | 0.250445E+11 | 0.00 | 0.00 | 6041477.23 | 0.00 | 0.00 | 0.116623E+11 | 0.00 | 3.30 |
May | 0.141033E+11 | 42831519.23 | 0.00 | 9555720.13 | 29289722.94 | 0.00 | 0.164608E+11 | 0.00 | 3.98 |
June | 0.756672E+10 | 0.156340E+10 | 0.00 | 8212018.59 | 0.882649E+09 | 0.00 | 0.121924E+11 | 0.00 | 4.27 |
July | 0.450625E+10 | 0.276183E+10 | 0.00 | 10044488.43 | 0.132151E+10 | 0.00 | 0.113275E+11 | 0.00 | 4.28 |
August | 0.585610E+10 | 0.108437E+10 | 0.00 | 13801313.05 | 0.579775E+09 | 0.00 | 0.153058E+11 | 0.00 | 4.53 |
September | 0.131703E+11 | 13098508.21 | 0.00 | 12087819.06 | 1758021.69 | 0.00 | 0.193413E+11 | 0.00 | 4.02 |
October | 0.287968E+11 | 0.00 | 0.00 | 7592869.20 | 0.00 | 0.00 | 0.119739E+11 | 0.00 | 3.28 |
November | 0.334945E+11 | 0.00 | 0.00 | 1018895.78 | 0.00 | 91054784.85 | 0.284629E+10 | 0.00 | 3.09 |
December | 0.450101E+11 | 0.00 | 0.00 | 78130.43 | 0.00 | 0.571952E+10 | 0.274464E+09 | 0.00 | 3.06 |
Annual Sum or Average | 0.294691E+12 | 0.546553E+10 | 0.00 | 72899879.58 | 0.281498E+10 | 0.136999E+11 | 0.110610E+12 | 0.00 | 3.59 |
Minimum of Months | 0.450625E+10 | 0.00 | 0.00 | 78130.43 | 0.00 | 0.00 | 0.274464E+09 | 0.00 | 3.04 |
Maximum of Months | 0.482239E+11 | 0.276183E+10 | 0.00 | 13801313.05 | 0.132151E+10 | 0.602404E+10 | 0.193413E+11 | 0.00 | 4.53 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147077E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691081E+10 | 0.00 | 0.00 | 1.24 |
February | 0.112473E+12 | 0.00 | 0.00 | 34673.92 | 0.00 | 0.522875E+09 | 0.427314E+09 | 0.00 | 1.23 |
March | 0.105629E+12 | 0.00 | 0.00 | 431301.31 | 0.00 | 0.00 | 0.257546E+10 | 0.00 | 1.23 |
April | 0.829608E+11 | 0.00 | 0.00 | 7139177.42 | 0.00 | 0.00 | 0.196653E+11 | 0.00 | 1.33 |
May | 0.412285E+11 | 74367818.57 | 0.00 | 31352994.01 | 0.127407E+09 | 0.00 | 0.445030E+11 | 0.00 | 1.62 |
June | 0.203892E+11 | 0.354376E+10 | 0.00 | 36213449.67 | 0.340601E+10 | 0.00 | 0.351162E+11 | 0.00 | 1.74 |
July | 0.108970E+11 | 0.661205E+10 | 0.00 | 48103190.31 | 0.491152E+10 | 0.00 | 0.337823E+11 | 0.00 | 1.75 |
August | 0.159473E+11 | 0.192782E+10 | 0.00 | 52966158.29 | 0.273184E+10 | 0.00 | 0.436382E+11 | 0.00 | 1.85 |
September | 0.396566E+11 | 14084609.97 | 0.00 | 29855345.77 | 26272920.76 | 0.00 | 0.512669E+11 | 0.00 | 1.62 |
October | 0.877096E+11 | 0.00 | 0.00 | 11073143.94 | 0.00 | 0.00 | 0.258073E+11 | 0.00 | 1.31 |
November | 0.998835E+11 | 0.00 | 0.00 | 299318.41 | 0.00 | 0.00 | 0.204833E+10 | 0.00 | 1.25 |
December | 0.141881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834496E+09 | 0.00 | 0.00 | 1.24 |
Annual Sum or Average | 0.905733E+12 | 0.121721E+11 | 0.00 | 0.217469E+09 | 0.112031E+11 | 0.826818E+10 | 0.258830E+12 | 0.00 | 1.45 |
Minimum of Months | 0.108970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 |
Maximum of Months | 0.147077E+12 | 0.661205E+10 | 0.00 | 52966158.29 | 0.491152E+10 | 0.691081E+10 | 0.512669E+11 | 0.00 | 1.85 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 20163729.14 | 0.00 | 0.00 | 8451.70 | 0.00 | 0.323815E+10 | 459084.94 | 0.00 | 0.34 |
February | 50173996.55 | 0.00 | 0.00 | 487998.60 | 0.00 | 0.205435E+10 | 27042937.61 | 0.00 | 0.34 |
March | 58263361.76 | 0.00 | 0.00 | 1729708.00 | 0.00 | 0.156373E+10 | 0.127548E+09 | 0.00 | 0.34 |
April | 51673672.40 | 922412.37 | 0.00 | 4975814.79 | 0.00 | 0.788172E+09 | 0.455614E+09 | 0.00 | 0.34 |
May | 20077789.66 | 13436745.01 | 1726.85 | 12252232.16 | 0.00 | 0.114200E+09 | 0.962027E+09 | 1494.79 | 0.34 |
June | 11991769.20 | 0.186440E+09 | 137748.83 | 10862583.09 | 324388.10 | 17428676.54 | 0.601628E+09 | 12662.75 | 0.34 |
July | 3512606.92 | 0.338175E+09 | 227357.02 | 9776471.11 | 0.00 | 540959.70 | 0.380761E+09 | 19971.47 | 0.34 |
August | 6884657.50 | 0.134667E+09 | 122671.16 | 10644995.58 | 1052372.78 | 18095628.40 | 0.517887E+09 | 12324.38 | 0.34 |
September | 25603171.35 | 8176426.57 | 0.00 | 8778538.20 | 0.00 | 0.227242E+09 | 0.835779E+09 | 0.00 | 0.34 |
October | 51605445.94 | 0.00 | 0.00 | 2715569.40 | 0.00 | 0.926968E+09 | 0.345430E+09 | 0.00 | 0.34 |
November | 49162981.27 | 0.00 | 0.00 | 159432.16 | 0.00 | 0.133737E+10 | 14221623.20 | 0.00 | 0.34 |
December | 11775819.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290247E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.360889E+09 | 0.681818E+09 | 489503.86 | 62391794.80 | 1376760.88 | 0.131887E+11 | 0.426840E+10 | 46453.39 | 0.34 |
Minimum of Months | 3512606.92 | 0.00 | 0.00 | 0.00 | 0.00 | 540959.70 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 58263361.76 | 0.338175E+09 | 227357.02 | 12252232.16 | 1052372.78 | 0.323815E+10 | 0.962027E+09 | 19971.47 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2820.25 | 0.00 | 0.325827E+10 | 131072.79 | 0.00 | 0.34 |
February | 12314803.79 | 0.00 | 0.00 | 110782.08 | 0.00 | 0.210572E+10 | 13654983.59 | 0.00 | 0.34 |
March | 22694146.30 | 0.00 | 0.00 | 777881.16 | 0.00 | 0.165463E+10 | 72961228.45 | 0.00 | 0.34 |
April | 95606870.87 | 775711.66 | 0.00 | 2919742.30 | 146592.64 | 0.877815E+09 | 0.323942E+09 | 0.00 | 0.34 |
May | 0.168192E+09 | 12944922.18 | 2179.92 | 8084400.42 | 486982.26 | 0.123838E+09 | 0.808313E+09 | 4307.61 | 0.34 |
June | 0.141863E+09 | 0.159226E+09 | 179309.49 | 7148957.09 | 27476450.71 | 15119443.50 | 0.477704E+09 | 10855.90 | 0.34 |
July | 0.105190E+09 | 0.265731E+09 | 252340.18 | 6354628.44 | 72388099.83 | 483416.75 | 0.282517E+09 | 10631.80 | 0.35 |
August | 0.136897E+09 | 0.103924E+09 | 121127.66 | 6755754.73 | 31775019.27 | 19957339.92 | 0.389837E+09 | 18099.81 | 0.34 |
September | 0.153495E+09 | 7492566.87 | 4515.62 | 4563684.80 | 676023.13 | 0.264611E+09 | 0.674605E+09 | 2362.96 | 0.34 |
October | 81604726.03 | 0.00 | 0.00 | 929186.35 | 0.00 | 0.105897E+10 | 0.185056E+09 | 0.00 | 0.34 |
November | 33100990.64 | 0.00 | 0.00 | 29463.93 | 0.00 | 0.136587E+10 | 1749855.51 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291390E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.950958E+09 | 0.550095E+09 | 559472.87 | 37677301.56 | 0.132949E+09 | 0.136592E+11 | 0.323047E+10 | 46258.09 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483416.75 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.168192E+09 | 0.265731E+09 | 252340.18 | 8084400.42 | 72388099.83 | 0.325827E+10 | 0.808313E+09 | 18099.81 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.912861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348458E+09 | 0.00 | 0.00 | 0.02 |
February | 0.753682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85220062.99 | 0.00 | 0.00 | 0.02 |
March | 0.915632E+09 | 0.00 | 0.00 | 165770.95 | 0.00 | 0.00 | 63024116.45 | 0.00 | 0.02 |
April | 0.705285E+09 | 19232417.77 | 0.00 | 1863813.43 | 0.00 | 0.00 | 0.513315E+09 | 0.00 | 0.02 |
May | 0.150069E+09 | 28406330.76 | 0.00 | 2494424.05 | 0.00 | 0.00 | 0.710456E+09 | 0.00 | 0.02 |
June | 96751917.72 | 0.253303E+09 | 0.00 | 1679266.95 | 0.00 | 0.00 | 0.427291E+09 | 0.00 | 0.02 |
July | 31293645.83 | 0.468661E+09 | 0.00 | 1386203.66 | 0.00 | 0.00 | 0.155376E+09 | 0.00 | 0.02 |
August | 81735854.69 | 0.339495E+09 | 0.00 | 1939797.88 | 0.00 | 0.00 | 0.185167E+09 | 0.00 | 0.02 |
September | 0.349159E+09 | 19476889.05 | 0.00 | 3355346.85 | 0.00 | 0.00 | 0.640249E+09 | 0.00 | 0.02 |
October | 0.737967E+09 | 0.00 | 0.00 | 2053724.57 | 0.00 | 0.00 | 0.420435E+09 | 0.00 | 0.02 |
November | 0.785392E+09 | 0.00 | 0.00 | 1984.89 | 0.00 | 44249924.87 | 7820242.21 | 0.00 | 0.02 |
December | 0.463368E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520899E+09 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.598320E+10 | 0.112857E+10 | 0.00 | 14940333.24 | 0.00 | 0.998827E+09 | 0.312313E+10 | 0.00 | 0.02 |
Minimum of Months | 31293645.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.915632E+09 | 0.468661E+09 | 0.00 | 3355346.85 | 0.00 | 0.520899E+09 | 0.710456E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.302258E+09 | 0.00 | 0.00 | 108556.38 | 0.00 | 0.438814E+11 | 14516724.14 | 0.00 | 0.39 |
February | 0.532614E+09 | 0.00 | 0.00 | 271896.21 | 0.00 | 0.281393E+11 | 0.244423E+09 | 0.00 | 0.39 |
March | 0.939266E+09 | 0.00 | 0.00 | 2906282.46 | 0.00 | 0.205151E+11 | 0.229492E+10 | 0.00 | 0.39 |
April | 0.133134E+10 | 10133917.18 | 0.00 | 26621761.85 | 2376587.28 | 0.555815E+10 | 0.107215E+11 | 0.00 | 0.39 |
May | 0.243138E+10 | 0.153171E+09 | 69215.76 | 98493683.15 | 29040840.18 | 37238340.11 | 0.124680E+11 | 2437.65 | 0.39 |
June | 0.204264E+10 | 0.210572E+10 | 540260.72 | 96429719.70 | 0.428819E+09 | 3316605.56 | 0.656373E+10 | 5894.54 | 0.39 |
July | 0.154591E+10 | 0.350681E+10 | 1192978.01 | 76198876.81 | 0.108195E+10 | 786337.64 | 0.372887E+10 | 10001.87 | 0.39 |
August | 0.195230E+10 | 0.125890E+10 | 1361806.66 | 86087615.25 | 0.582259E+09 | 6622427.26 | 0.546216E+10 | 43815.14 | 0.39 |
September | 0.214091E+10 | 97624393.89 | 0.00 | 66988497.70 | 13270932.96 | 60185620.01 | 0.126158E+11 | 0.00 | 0.39 |
October | 0.115043E+10 | 0.00 | 0.00 | 22193428.59 | 0.00 | 0.385422E+10 | 0.129672E+11 | 0.00 | 0.39 |
November | 0.917382E+09 | 0.00 | 0.00 | 3067166.97 | 0.00 | 0.151352E+11 | 0.294478E+10 | 0.00 | 0.39 |
December | 0.315008E+09 | 0.00 | 0.00 | 78983.72 | 0.00 | 0.391848E+11 | 25388976.85 | 0.00 | 0.38 |
Annual Sum or Average | 0.156014E+11 | 0.713237E+10 | 3164261.15 | 0.479446E+09 | 0.213771E+10 | 0.156376E+12 | 0.700513E+11 | 62149.21 | 0.39 |
Minimum of Months | 0.302258E+09 | 0.00 | 0.00 | 78983.72 | 0.00 | 786337.64 | 14516724.14 | 0.00 | 0.38 |
Maximum of Months | 0.243138E+10 | 0.350681E+10 | 1361806.66 | 98493683.15 | 0.108195E+10 | 0.438814E+11 | 0.129672E+11 | 43815.14 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17848377.43 | 0.00 | 0.00 | 299.15 | 0.00 | 0.324087E+10 | 63947.11 | 0.00 | 0.34 |
February | 45553413.68 | 0.00 | 0.00 | 186417.52 | 0.00 | 0.204870E+10 | 37614349.92 | 0.00 | 0.34 |
March | 55585407.52 | 0.00 | 0.00 | 999932.47 | 0.00 | 0.154432E+10 | 0.150370E+09 | 0.00 | 0.34 |
April | 40461590.24 | 919921.84 | 833.65 | 5066344.16 | 0.00 | 0.747444E+09 | 0.507463E+09 | 1656.88 | 0.34 |
May | 14799199.25 | 13436745.01 | 2515.49 | 11590910.57 | 0.00 | 0.138574E+09 | 0.943592E+09 | 706.15 | 0.34 |
June | 4200856.25 | 0.186575E+09 | 73578.20 | 12323022.17 | 265828.08 | 8795454.03 | 0.616591E+09 | 815.91 | 0.34 |
July | 3512606.92 | 0.338356E+09 | 61695.17 | 10316961.29 | 0.00 | 531069.47 | 0.380231E+09 | 4345.31 | 0.34 |
August | 7043107.73 | 0.134520E+09 | 271995.26 | 10641966.86 | 1052372.78 | 15305891.63 | 0.520521E+09 | 9718.14 | 0.34 |
September | 25053608.89 | 8176426.57 | 0.00 | 8266101.12 | 0.00 | 0.255141E+09 | 0.808942E+09 | 0.00 | 0.34 |
October | 52119775.54 | 0.00 | 0.00 | 2456424.29 | 0.00 | 0.950938E+09 | 0.321205E+09 | 0.00 | 0.34 |
November | 48030695.05 | 0.00 | 0.00 | 231565.31 | 0.00 | 0.132000E+10 | 32657416.09 | 0.00 | 0.34 |
December | 5746856.10 | 0.00 | 0.00 | 4137.62 | 0.00 | 0.290806E+10 | 431978.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.319955E+09 | 0.681984E+09 | 410617.78 | 62084082.54 | 1318200.85 | 0.131787E+11 | 0.431968E+10 | 17242.38 | 0.34 |
Minimum of Months | 3512606.92 | 0.00 | 0.00 | 299.15 | 0.00 | 531069.47 | 63947.11 | 0.00 | 0.34 |
Maximum of Months | 55585407.52 | 0.338356E+09 | 271995.26 | 12323022.17 | 1052372.78 | 0.324087E+10 | 0.943592E+09 | 9718.14 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325840E+10 | 0.00 | 0.00 | 0.34 |
February | 10880453.47 | 0.00 | 0.00 | 14172.80 | 0.00 | 0.211935E+10 | 1555817.24 | 0.00 | 0.34 |
March | 33155553.78 | 0.00 | 0.00 | 250528.88 | 0.00 | 0.165649E+10 | 61171859.04 | 0.00 | 0.34 |
April | 87320935.02 | 736745.41 | 5066.22 | 3060242.60 | 175207.70 | 0.816543E+09 | 0.393359E+09 | 5284.97 | 0.34 |
May | 0.152981E+09 | 13041963.13 | 0.00 | 7858897.08 | 396428.83 | 0.152381E+09 | 0.795206E+09 | 0.00 | 0.34 |
June | 0.128362E+09 | 0.160038E+09 | 58598.91 | 9063289.72 | 26791571.44 | 8440671.79 | 0.495970E+09 | 4222.26 | 0.34 |
July | 0.103723E+09 | 0.267564E+09 | 247360.16 | 6851569.60 | 70564361.37 | 554046.22 | 0.283416E+09 | 6308.62 | 0.35 |
August | 0.134442E+09 | 0.103638E+09 | 186864.05 | 6988898.90 | 32006980.34 | 16259001.35 | 0.395757E+09 | 6877.88 | 0.34 |
September | 0.136630E+09 | 7499445.45 | 0.00 | 4612113.77 | 676023.13 | 0.309054E+09 | 0.646978E+09 | 0.00 | 0.34 |
October | 82382409.90 | 0.00 | 0.00 | 834393.33 | 0.00 | 0.109314E+10 | 0.150210E+09 | 0.00 | 0.34 |
November | 24894271.09 | 0.00 | 0.00 | 33908.88 | 0.00 | 0.136859E+10 | 7235393.03 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291390E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.894772E+09 | 0.552519E+09 | 497889.33 | 39568015.58 | 0.130611E+09 | 0.137131E+11 | 0.323086E+10 | 22693.73 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554046.22 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.152981E+09 | 0.267564E+09 | 247360.16 | 9063289.72 | 70564361.37 | 0.325840E+10 | 0.795206E+09 | 6877.88 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.341925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352034E+11 | 0.00 | 0.00 | 0.34 |
February | 0.109187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175297E+11 | 0.00 | 0.00 | 0.34 |
March | 0.197561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738332E+10 | 0.00 | 0.00 | 0.34 |
April | 0.254461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295089E+09 | 0.00 | 0.00 | 0.36 |
May | 0.214529E+11 | 0.00 | 0.00 | 0.00 | 50608410.19 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.137759E+11 | 0.365426E+09 | 0.00 | 349281.92 | 0.134851E+10 | 0.00 | 98553107.99 | 0.00 | 0.47 |
July | 0.107067E+11 | 0.220087E+09 | 0.00 | 250182.34 | 0.263765E+10 | 0.00 | 0.412393E+09 | 0.00 | 0.47 |
August | 0.148573E+11 | 0.00 | 0.00 | 0.00 | 0.116030E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.227618E+11 | 0.00 | 0.00 | 0.00 | 10122325.58 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.281029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364121E+09 | 0.00 | 0.00 | 0.36 |
November | 0.193531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621319E+10 | 0.00 | 0.00 | 0.34 |
December | 0.352082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322747E+11 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.194072E+12 | 0.585513E+09 | 0.00 | 599464.27 | 0.520719E+10 | 0.992635E+11 | 0.510946E+09 | 0.00 | 0.40 |
Minimum of Months | 0.341925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.281029E+11 | 0.365426E+09 | 0.00 | 349281.92 | 0.263765E+10 | 0.352034E+11 | 0.412393E+09 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1606660.08 | 0.00 | 0.00 | 1985.77 | 0.00 | 0.812973E+09 | 115137.81 | 0.00 | 0.34 |
February | 7617370.65 | 0.00 | 0.00 | 114070.47 | 0.00 | 0.519192E+09 | 6089388.80 | 0.00 | 0.34 |
March | 11075969.75 | 0.00 | 0.00 | 428392.72 | 0.00 | 0.399915E+09 | 26398990.05 | 0.00 | 0.34 |
April | 11623025.93 | 230603.09 | 0.00 | 1249295.59 | 0.00 | 0.216420E+09 | 95816695.29 | 0.00 | 0.34 |
May | 5691611.88 | 3359186.25 | 557.99 | 3021729.77 | 0.00 | 61656929.01 | 0.206769E+09 | 247.42 | 0.34 |
June | 2960629.78 | 46609987.04 | 34567.54 | 2682585.62 | 81097.03 | 14179113.69 | 0.140655E+09 | 3035.35 | 0.34 |
July | 1046108.28 | 84543710.96 | 56412.89 | 2324352.51 | 0.00 | 193339.88 | 95084023.30 | 5419.24 | 0.34 |
August | 1809603.30 | 33541941.52 | 16169.62 | 2524883.78 | 402887.00 | 10931707.74 | 0.123112E+09 | 2638.67 | 0.34 |
September | 6817583.44 | 2044106.64 | 0.00 | 2046338.19 | 0.00 | 95391962.94 | 0.170095E+09 | 0.00 | 0.34 |
October | 10819116.31 | 0.00 | 0.00 | 639485.17 | 0.00 | 0.261867E+09 | 58353997.16 | 0.00 | 0.34 |
November | 9761923.82 | 0.00 | 0.00 | 34701.00 | 0.00 | 0.338819E+09 | 1613885.77 | 0.00 | 0.34 |
December | 1009437.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727551E+09 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 71839041.13 | 0.170330E+09 | 107708.04 | 15067820.58 | 483984.03 | 0.345909E+10 | 0.924103E+09 | 11340.68 | 0.34 |
Minimum of Months | 1009437.92 | 0.00 | 0.00 | 0.00 | 0.00 | 193339.88 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 11623025.93 | 84543710.96 | 56412.89 | 3021729.77 | 402887.00 | 0.812973E+09 | 0.206769E+09 | 5419.24 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 50.42 | 0.00 | 0.814583E+09 | 17531.73 | 0.00 | 0.34 |
February | 1515650.25 | 0.00 | 0.00 | 16309.84 | 0.00 | 0.528840E+09 | 2579002.07 | 0.00 | 0.34 |
March | 4216183.13 | 0.00 | 0.00 | 180352.94 | 0.00 | 0.418731E+09 | 14639181.29 | 0.00 | 0.34 |
April | 21099504.70 | 193927.91 | 0.00 | 738210.61 | 36648.16 | 0.233338E+09 | 69894914.30 | 0.00 | 0.34 |
May | 39616438.19 | 3236230.54 | 298.85 | 2071694.92 | 121745.56 | 55074957.91 | 0.180344E+09 | 1323.03 | 0.34 |
June | 34452464.74 | 39811007.07 | 40366.28 | 1880633.86 | 6869112.68 | 9942017.54 | 0.114184E+09 | 2725.98 | 0.34 |
July | 26160657.19 | 66468718.26 | 57776.99 | 1622710.87 | 18067330.82 | 136722.67 | 70716175.20 | 1804.24 | 0.35 |
August | 34063062.93 | 26061507.65 | 31998.86 | 1680035.43 | 7861391.24 | 10565678.40 | 92052994.23 | 4759.72 | 0.34 |
September | 38118781.75 | 1873141.72 | 881.46 | 1057034.74 | 169005.78 | 0.109382E+09 | 0.125760E+09 | 838.19 | 0.34 |
October | 18178858.77 | 0.00 | 0.00 | 201394.69 | 0.00 | 0.286312E+09 | 26948478.24 | 0.00 | 0.34 |
November | 4250013.09 | 0.00 | 0.00 | 4286.86 | 0.00 | 0.345742E+09 | 192309.29 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728475E+09 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.221672E+09 | 0.137645E+09 | 131322.44 | 9452715.19 | 33125234.24 | 0.354112E+10 | 0.697328E+09 | 11451.17 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136722.67 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 39616438.19 | 66468718.26 | 57776.99 | 2071694.92 | 18067330.82 | 0.814583E+09 | 0.180344E+09 | 4759.72 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 96941847.04 | 0.00 | 0.00 | 723342.32 | 0.00 | 0.503253E+10 | 0.103816E+09 | 0.00 | 0.39 |
February | 54818828.40 | 0.00 | 0.00 | 2643979.24 | 0.00 | 0.306877E+10 | 0.298099E+09 | 0.00 | 0.39 |
March | 56234373.58 | 0.00 | 0.00 | 4292416.48 | 0.00 | 0.230412E+10 | 0.448115E+09 | 0.00 | 0.39 |
April | 34351245.77 | 1481507.11 | 0.00 | 8145413.64 | 0.00 | 0.106726E+10 | 0.978898E+09 | 0.00 | 0.39 |
May | 22688958.28 | 21586230.63 | 0.00 | 15630702.13 | 0.00 | 0.182518E+09 | 0.155964E+10 | 0.00 | 0.39 |
June | 16633154.15 | 0.299381E+09 | 224720.12 | 13280194.89 | 582277.48 | 29022559.10 | 0.972051E+09 | 20346.21 | 0.39 |
July | 5641676.43 | 0.541906E+09 | 329968.95 | 11180929.99 | 1291680.68 | 1435944.94 | 0.615503E+09 | 19629.79 | 0.39 |
August | 10672710.59 | 0.216303E+09 | 133086.12 | 13974154.75 | 1751982.36 | 22939492.00 | 0.841422E+09 | 11015.84 | 0.39 |
September | 37958223.00 | 13132341.34 | 0.00 | 14339554.74 | 0.00 | 0.235358E+09 | 0.147491E+10 | 0.00 | 0.39 |
October | 77943656.53 | 0.00 | 0.00 | 7063178.57 | 0.00 | 0.114050E+10 | 0.905370E+09 | 0.00 | 0.39 |
November | 60867874.76 | 0.00 | 0.00 | 1662958.79 | 0.00 | 0.195817E+10 | 0.229342E+09 | 0.00 | 0.39 |
December | 60770046.96 | 0.00 | 0.00 | 263281.52 | 0.00 | 0.454173E+10 | 77865940.96 | 0.00 | 0.38 |
Annual Sum or Average | 0.535523E+09 | 0.109379E+10 | 687775.20 | 93200107.06 | 3625940.52 | 0.195844E+11 | 0.850503E+10 | 50991.83 | 0.39 |
Minimum of Months | 5641676.43 | 0.00 | 0.00 | 263281.52 | 0.00 | 1435944.94 | 77865940.96 | 0.00 | 0.38 |
Maximum of Months | 96941847.04 | 0.541906E+09 | 329968.95 | 15630702.13 | 1751982.36 | 0.503253E+10 | 0.155964E+10 | 20346.21 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.729167E+11 | 0.00 | 0.00 | 4117009.82 | 0.00 | 0.583599E+10 | 0.178628E+11 | 0.00 | 4.00 |
February | 0.476805E+11 | 0.00 | 0.00 | 6212012.73 | 0.00 | 0.319266E+09 | 0.231616E+11 | 0.00 | 3.97 |
March | 0.361657E+11 | 0.00 | 0.00 | 11808475.63 | 0.00 | 0.00 | 0.317153E+11 | 0.00 | 3.96 |
April | 0.230311E+11 | 0.00 | 0.00 | 19897842.83 | 0.00 | 0.00 | 0.413441E+11 | 0.00 | 4.28 |
May | 0.919265E+10 | 0.105951E+09 | 0.00 | 37712722.31 | 20652794.90 | 0.00 | 0.446231E+11 | 0.00 | 5.20 |
June | 0.347704E+10 | 0.375079E+10 | 0.00 | 37224168.14 | 0.561464E+09 | 0.00 | 0.314201E+11 | 0.00 | 5.60 |
July | 0.203175E+10 | 0.621238E+10 | 0.00 | 36681423.15 | 0.969461E+09 | 0.00 | 0.259633E+11 | 0.00 | 5.60 |
August | 0.427665E+10 | 0.222189E+10 | 0.00 | 39206511.14 | 0.688809E+09 | 0.00 | 0.330451E+11 | 0.00 | 5.91 |
September | 0.121764E+11 | 11752636.67 | 0.00 | 31011534.25 | 13569685.19 | 0.00 | 0.447847E+11 | 0.00 | 5.21 |
October | 0.244405E+11 | 0.00 | 0.00 | 20754378.12 | 0.00 | 0.00 | 0.467527E+11 | 0.00 | 4.21 |
November | 0.320237E+11 | 0.00 | 0.00 | 12649964.76 | 0.00 | 0.00 | 0.319209E+11 | 0.00 | 4.03 |
December | 0.671495E+11 | 0.00 | 0.00 | 5548075.51 | 0.00 | 0.575019E+09 | 0.218170E+11 | 0.00 | 3.99 |
Annual Sum or Average | 0.334562E+12 | 0.123028E+11 | 0.00 | 0.262824E+09 | 0.225396E+10 | 0.673028E+10 | 0.394411E+12 | 0.00 | 4.67 |
Minimum of Months | 0.203175E+10 | 0.00 | 0.00 | 4117009.82 | 0.00 | 0.00 | 0.178628E+11 | 0.00 | 3.96 |
Maximum of Months | 0.729167E+11 | 0.621238E+10 | 0.00 | 39206511.14 | 0.969461E+09 | 0.583599E+10 | 0.467527E+11 | 0.00 | 5.91 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.696099E+11 | 0.00 | 0.00 | 7189330.03 | 0.00 | 0.284481E+10 | 0.241700E+11 | 0.00 | 4.00 |
February | 0.426816E+11 | 0.00 | 0.00 | 10293100.71 | 0.00 | 73941920.56 | 0.284108E+11 | 0.00 | 3.98 |
March | 0.314972E+11 | 0.00 | 0.00 | 18112859.70 | 0.00 | 0.00 | 0.363861E+11 | 0.00 | 3.97 |
April | 0.161984E+11 | 0.00 | 0.00 | 28438899.68 | 0.00 | 0.00 | 0.482531E+11 | 0.00 | 4.29 |
May | 0.425758E+10 | 0.115102E+09 | 0.00 | 49220941.64 | 11517825.70 | 0.00 | 0.498902E+11 | 0.00 | 5.24 |
June | 0.204468E+10 | 0.403367E+10 | 0.00 | 46625740.65 | 0.318622E+09 | 0.00 | 0.331194E+11 | 0.00 | 5.65 |
July | 0.135087E+10 | 0.661340E+10 | 0.00 | 44683901.45 | 0.620119E+09 | 0.00 | 0.268758E+11 | 0.00 | 5.65 |
August | 0.216263E+10 | 0.239581E+10 | 0.00 | 48450469.17 | 0.524037E+09 | 0.00 | 0.354301E+11 | 0.00 | 5.96 |
September | 0.672425E+10 | 16252124.14 | 0.00 | 40382597.88 | 9073425.65 | 0.00 | 0.504961E+11 | 0.00 | 5.23 |
October | 0.188668E+11 | 0.00 | 0.00 | 29676604.46 | 0.00 | 0.00 | 0.523701E+11 | 0.00 | 4.22 |
November | 0.253560E+11 | 0.00 | 0.00 | 19495442.54 | 0.00 | 0.00 | 0.385963E+11 | 0.00 | 4.03 |
December | 0.630106E+11 | 0.00 | 0.00 | 9236580.43 | 0.00 | 0.201601E+09 | 0.263371E+11 | 0.00 | 3.99 |
Annual Sum or Average | 0.283761E+12 | 0.131742E+11 | 0.00 | 0.351806E+09 | 0.148337E+10 | 0.312035E+10 | 0.450335E+12 | 0.00 | 4.69 |
Minimum of Months | 0.135087E+10 | 0.00 | 0.00 | 7189330.03 | 0.00 | 0.00 | 0.241700E+11 | 0.00 | 3.97 |
Maximum of Months | 0.696099E+11 | 0.661340E+10 | 0.00 | 49220941.64 | 0.620119E+09 | 0.284481E+10 | 0.523701E+11 | 0.00 | 5.96 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.236950E+09 | 0.00 | 0.00 | 0.100527E+09 | 0.00 | 0.00 | 0.703067E+11 | 0.00 | 10.66 |
February | 18444838.01 | 0.00 | 0.00 | 94887020.88 | 0.00 | 0.00 | 0.605776E+11 | 0.00 | 11.62 |
March | 0.00 | 0.00 | 0.00 | 0.109017E+09 | 0.00 | 0.00 | 0.634048E+11 | 0.00 | 12.30 |
April | 0.00 | 0.00 | 0.00 | 0.110954E+09 | 0.00 | 0.00 | 0.649216E+11 | 0.00 | 14.34 |
May | 0.00 | 0.162832E+09 | 0.00 | 0.133636E+09 | 0.00 | 0.00 | 0.532625E+11 | 0.00 | 18.24 |
June | 0.00 | 0.535370E+10 | 0.00 | 0.108568E+09 | 0.00 | 0.00 | 0.335369E+11 | 0.00 | 19.68 |
July | 0.00 | 0.876337E+10 | 0.00 | 93309166.60 | 0.00 | 0.00 | 0.260298E+11 | 0.00 | 19.49 |
August | 0.00 | 0.371456E+10 | 0.00 | 0.110142E+09 | 0.00 | 0.00 | 0.354287E+11 | 0.00 | 20.56 |
September | 0.00 | 32569994.72 | 0.00 | 0.117224E+09 | 0.00 | 0.00 | 0.570173E+11 | 0.00 | 18.19 |
October | 0.00 | 0.00 | 0.00 | 0.107108E+09 | 0.00 | 0.00 | 0.700681E+11 | 0.00 | 13.94 |
November | 0.00 | 0.00 | 0.00 | 0.101593E+09 | 0.00 | 0.00 | 0.614753E+11 | 0.00 | 12.53 |
December | 53294947.66 | 0.00 | 0.00 | 0.100485E+09 | 0.00 | 0.00 | 0.687876E+11 | 0.00 | 10.93 |
Annual Sum or Average | 0.308690E+09 | 0.180270E+11 | 0.00 | 0.128745E+10 | 0.00 | 0.00 | 0.664817E+12 | 0.00 | 15.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 93309166.60 | 0.00 | 0.00 | 0.260298E+11 | 0.00 | 10.66 |
Maximum of Months | 0.236950E+09 | 0.876337E+10 | 0.00 | 0.133636E+09 | 0.00 | 0.00 | 0.703067E+11 | 0.00 | 20.56 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.224212E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136231E+11 | 0.00 | 0.00 | 0.40 |
February | 0.170805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670720E+10 | 0.00 | 0.00 | 0.35 |
March | 0.385094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344566E+10 | 0.00 | 0.00 | 0.34 |
April | 0.649639E+10 | 0.00 | 0.00 | 120233.41 | 0.00 | 0.247278E+09 | 57745231.58 | 0.00 | 0.36 |
May | 0.380030E+10 | 26965541.43 | 0.00 | 7247007.59 | 0.00 | 0.00 | 0.220058E+10 | 0.00 | 0.51 |
June | 0.170145E+10 | 0.869572E+09 | 0.00 | 8874764.51 | 1250194.16 | 0.00 | 0.237169E+10 | 0.00 | 0.63 |
July | 0.618388E+09 | 0.138095E+10 | 0.00 | 10274462.18 | 437885.23 | 0.00 | 0.289344E+10 | 0.00 | 0.69 |
August | 0.136158E+10 | 0.523262E+09 | 0.00 | 9190362.55 | 1483044.75 | 0.00 | 0.302452E+10 | 0.00 | 0.65 |
September | 0.474866E+10 | 5268042.12 | 0.00 | 3361545.40 | 39263.09 | 0.00 | 0.146767E+10 | 0.00 | 0.48 |
October | 0.734464E+10 | 0.00 | 0.00 | 181767.98 | 0.00 | 99323639.41 | 84340754.03 | 0.00 | 0.36 |
November | 0.417922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257608E+10 | 0.00 | 0.00 | 0.34 |
December | 0.210509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116073E+11 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.362443E+11 | 0.280602E+10 | 0.00 | 39250143.62 | 3210387.23 | 0.383059E+11 | 0.121000E+11 | 0.00 | 0.46 |
Minimum of Months | 0.210509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.734464E+10 | 0.138095E+10 | 0.00 | 10274462.18 | 1483044.75 | 0.136231E+11 | 0.302452E+10 | 0.00 | 0.69 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:51:18
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.141275E+12 | 0.354245E+11 | 0.435280E+12 | 0.111490E+13 | 0.153851E+12 |
February | 0.227964E+12 | 0.280192E+11 | 0.341311E+12 | 0.910922E+12 | 0.108036E+12 |
March | 0.326522E+12 | 0.263903E+11 | 0.327188E+12 | 0.883247E+12 | 0.942347E+11 |
April | 0.442464E+12 | 0.169095E+11 | 0.208056E+12 | 0.607432E+12 | 0.123513E+12 |
May | 0.498724E+12 | 0.965002E+10 | 0.114395E+12 | 0.413961E+12 | 0.295064E+12 |
June | 0.521354E+12 | 0.384015E+10 | 0.392911E+11 | 0.202948E+12 | 0.551018E+12 |
July | 0.531286E+12 | 0.143229E+10 | 0.867539E+10 | 0.112924E+12 | 0.732504E+12 |
August | 0.440007E+12 | 0.406508E+10 | 0.465082E+11 | 0.236871E+12 | 0.543092E+12 |
September | 0.330486E+12 | 0.991795E+10 | 0.123646E+12 | 0.429948E+12 | 0.203276E+12 |
October | 0.175026E+12 | 0.158450E+11 | 0.203972E+12 | 0.578254E+12 | 0.120245E+12 |
November | 0.880435E+11 | 0.216722E+11 | 0.279498E+12 | 0.747706E+12 | 0.910806E+11 |
December | 0.972587E+11 | 0.335862E+11 | 0.415844E+12 | 0.107195E+13 | 0.140911E+12 |
Annual Sum or Average | 0.382041E+13 | 0.206752E+12 | 0.254366E+13 | 0.731107E+13 | 0.315682E+13 |
Minimum of Months | 0.880435E+11 | 0.143229E+10 | 0.867539E+10 | 0.112924E+12 | 0.910806E+11 |
Maximum of Months | 0.531286E+12 | 0.354245E+11 | 0.435280E+12 | 0.111490E+13 | 0.732504E+12 |